Download as pdf or txt
Download as pdf or txt
You are on page 1of 74

Aspen Flare System Analyzer V11 - aspenONE

Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design

Network
Name Location Upstream Downstream Ignored Tailpipe Length
Node Node (m)

Stack Con 1 Tip No No 100.000


Header 3 Tee 3 Con 1 No No 50.000
Header 2 Tee 2 Tee 3 No No 50.000
Header 1 Tee 1 Tee 2 No No 50.000
Tailpipe 4 Source 4 Tee 3 No Yes 25.000
Tailpipe 3 Source 3 Tee 2 No Yes 25.000
Tailpipe 2 Source 2 Tee 1 No Yes 25.000
Tailpipe 1 Source 1 Tee 1 No Yes 25.000

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 1 of 5


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design

Network
Name Elevation Material Roughness Thermal Nominal Schedule Internal Wall
Change (mm) Conductivity Diameter Diameter Thickness
(m) (W/m-K) (mm) (mm)
Stack 100.000 Carbon Steel 0.04572 51.91 32 inch 40 777.850 17.475
Header 3 0.000 Carbon Steel 0.04572 51.91 32 inch 40 777.850 17.475
Header 2 0.000 Carbon Steel 0.04572 51.91 32 inch 40 777.850 17.475
Header 1 0.000 Carbon Steel 0.04572 51.91 20 inch 30 482.600 12.700
Tailpipe 4 0.000 Carbon Steel 0.04572 51.91 18 inch 40 428.650 14.275
Tailpipe 3 0.000 Carbon Steel 0.04572 51.91 18 inch 40 428.650 14.275
Tailpipe 2 0.000 Carbon Steel 0.04572 51.91 18 inch 40 428.650 14.275
Tailpipe 1 0.000 Carbon Steel 0.04572 51.91 18 inch 40 428.650 14.275

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 2 of 5


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design

Network
Name Pipe Sizeable Length Fittings Fittings Ambient External Medium
Insulation Insulation
Class Multiplier Loss A Loss B Temperature Velocity Description Thickness
(C) (m/s) (mm)
Stack No Yes 0.000 0.000 Glass Fibre 0.00
Header 3 No Yes 0.000 0.000 Glass Fibre 0.00
Header 2 No Yes 0.000 0.000 Glass Fibre 0.00
Header 1 No Yes 0.000 0.000 Glass Fibre 0.00
Tailpipe 4 No Yes 0.000 0.000 Glass Fibre 0.00
Tailpipe 3 No Yes 0.000 0.000 Glass Fibre 0.00
Tailpipe 2 No Yes 0.000 0.000 Glass Fibre 0.00
Tailpipe 1 No Yes 0.000 0.000 Glass Fibre 0.00

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 3 of 5


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design

Network
Name Insulation Outlet Duty VLE Horizontal Inclined
Conductivity Temperature (kJ/hr) Method Pres. Drop Pres. Drop
(W/m-K) (C)
Stack 0.040 0.000e+000 Model Default Model Default Model Default
Header 3 0.040 0.000e+000 Model Default Model Default Model Default
Header 2 0.040 0.000e+000 Model Default Model Default Model Default
Header 1 0.040 0.000e+000 Model Default Model Default Model Default
Tailpipe 4 0.040 0.000e+000 Model Default Model Default Model Default
Tailpipe 3 0.040 0.000e+000 Model Default Model Default Model Default
Tailpipe 2 0.040 0.000e+000 Model Default Model Default Model Default
Tailpipe 1 0.040 0.000e+000 Model Default Model Default Model Default

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 4 of 5


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design

Network
Name Vertical Two Phase Friction Damping
Pres. Drop Elements Factor Factor

Stack Model Default Model Default


Header 3 Model Default Model Default
Header 2 Model Default Model Default
Header 1 Model Default Model Default
Tailpipe 4 Model Default Model Default
Tailpipe 3 Model Default Model Default
Tailpipe 2 Model Default Model Default
Tailpipe 1 Model Default Model Default

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 5 of 5


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design

Component Data
Name ID Mol. Wt. Critical Critical Critical Char. Accentric SRK Accentric
Temperature Pressure Volume Volume Factor Factor
(K) (bar) (m3/kgmole) (m3/kgmole)
Methane 1 16.043 190.70 46.407 0.09900 0.09939 0.01150 0.00740
Ethane 2 30.070 305.43 48.839 0.14800 0.14575 0.09860 0.09830
Propane 3 44.097 369.90 42.567 0.20000 0.20008 0.15240 0.15320

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 1 of 3


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design

Component Data
Name Norm. Boiling Standard Watson Enthalpy Enthalpy Enthalpy Enthalpy
Point Density Factor Term A Term B Term C Term D
(K) (kg/m3) (kJ/kgmole) (kJ/kgmole/K) (kJ/kgmole/K^2) (kJ/kgmole/K^3)
Methane 111.63 299.39 19.563 -2.08237e+002 3.79349e+001 -3.42110e-002 9.08317e-005
Ethane 184.55 355.68 19.471 -5.31485e+001 3.43669e+001 -9.73062e-003 1.27590e-004
Propane 231.05 506.68 14.732 1.74134e+003 1.74183e+001 9.32250e-002 1.74838e-005

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 2 of 3


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design

Component Data
Name Enthalpy Enthalpy Entropy Viscosity Viscosity Type Heat of Combustion
Term E Term F Term A Term B Term (kJ/kgmole)
(kJ/kgmole/K^4) (kJ/kgmole/K^5)
Methane -5.97559e-008 1.38113e-011 1.00000e+000 -0.00201 0.02547 HC -802703.0
Ethane -1.02032e-007 2.65245e-011 1.00000e+000 0.07231 0.04698 HC -1428510.0
Propane -2.94205e-008 7.40547e-012 1.00000e+000 0.07112 -0.06538 HC -2044970.0

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 3 of 3


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design

Scenario Data
Name System Ambient Header Header Header Header Header Tailpipe Tailpipe
Back Pres. Temperature Mach No. Vap. Vel. Liq. Vel. Rho V2 Noise Mach No. Vap. Vel.
(bar) (C) (m/s) (m/s) (kg/m/s2) (dB) (m/s)
Default Scenario 0.5000 0.5000
Source 1 Only 0.5000 0.5000
Source 2 Only 0.5000 0.5000
Source 3 Only 0.5000 0.5000
Source 4 Only 0.5000 0.5000

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 1 of 2


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design

Scenario Data
Name Tailpipe Tailpipe Tailpipe
Liq. Vel. Rho V2 Noise
(m/s) (kg/m/s2) (dB)
Default Scenario
Source 1 Only
Source 2 Only
Source 3 Only
Source 4 Only

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 2 of 2


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design

Fittings
Name Location Upstream Downstream Fitting List
Node Node

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 1 of 1


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design

Messages:Problem
No. Message

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 1 of 1


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design

Messages:Basis
No. Message

1 Ambient temperature = 15.00 C


2 Atmospheric pressure = 1.01325 bar
3 Check for choke flow = True
4 Enable heat transfer calculations = False
5 External radiation = False
6 Calculation mode = Design
7 Rated flow = False
8 Rated flow nodes = False
9 Rated flow tailpipe = False
10 External medium velocity = 10.00 m/s
11 Include kinetic energy = False
12 Ignore kinetic energy in separators = False
13 Code for kinetic energy basis = Inlet Pipe Velocity
14 Property_IgnoreKEforVelInit = No
15 Calculate ignored sources as zero flow = False
16 Check MABP for inactive sources = False
17 Ignore valve flange size change in design calculations = True
18 Maximum system velocity = 500.000 m/s
19 Code to indicate which scenarios are calculated = All Scenarios
20 VLE = Compressible Gas
21 Code for enthalpy method = Ideal Gas
22 Vle source outlet temperature = Peng Robinson
23 Enthalpy source outlet temperature = Peng Robinson
24 Code for horizontal pressure drop method = Isothermal Gas
25 Code for inclined pressure drop method = Isothermal Gas
26 Code for vertical pressure drop method = Isothermal Gas
27 Number of elements for pipe calculation = 10
28 Friction factor = Chen
29 Property_HoldUpCorrForBBPresDrop = Payne (1979)
30 Use pipe roughness for fitting or not? = Yes
31 Roughness for fitting = 0.04572 mm
32 Property_NonflashingLiquidMethod = API Liquid (Capacity Certified)
33 Property_FlashingLiquidMethod = HEM
34 Property_TwoPhaseMethod = HEM
35 Property_SteamMethod = API Steam
36 Property_SteamLimitTemperature = 650.00 C
37 Property_VaporMethod = API Vapor
38 Property_VaporZLowerLimit = 0.80
39 Property_VaporZUpperLimit = 1.10
40 Warn mach number for sizing = True
41 Warn velocity for sizing = True
42 Warn Rho V2 for sizing = True
43 Warn noise for sizing = True
44 Warn ice form for sizing = True
45 Warn BP for sizing = True
46 Warn choke for sizing = True
47 Warn slug for sizing = True
48 Warn temperature for sizing = True

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 1 of 2


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design

Messages:Basis
No. Message

49 Warn pressure basis = Static Pressure


50 Warn physical property failure = True
51 Warn heat balance failure = True
52 Warn choke pressure failure = True
53 Warn pressure drop failure = True
54 Warn liquid with vapour method failure = True
55 Warn Correlation range failure = False
56 Warn initial while sizing = True
57 Warn size change while sizing = True
58 Warn limit reached while sizing = True
59 Pressure tolerance in properties loop (%) = 1.0e-003
60 Pressure tolerance for unit operation calculations (%) = 1.0e-002
61 Pressure tolerance for loop calculations (%) = 1.0e-002
62 Mass balance tolerance in outer loop (%) = 1.0e-002
63 Number of iterations in inner (properties) loop = 25
64 Number of iterations for loop calculations = 500
65 Property_IterationsInitVel = 10
66 Damping factor for inner (properties) loop = 1.0e+000
67 Damping factor for loop calculations = 1.0e+000
68 Select loop convergence method = Newton Raphson
69 Select analyzer for looped systems = Convergent
70 Are loop calculations echoed = False
71 Keep bad = False
72 Update flow estimates from solution = Do Not Update
73 Property_IgnoreZeroLengthPipes = Include in Network Calculation
74 Initial pressure for property calculations = 1.01325 bar
75 Multiplier for pipe length = 1.00
76 Initial phase method for sizing = Multi Phase
77 Minimum temperature for carbon steel = -29.00 C
78 Maximum temperature for carbon steel = 400.00 C
79 Minimum temperature for stainless steel = -69.00 C
80 Maximum temperature for stainless steel = 500.00 C
81 Inlet flow check = 3
82 Gauge inlet check = False
83 Ignore inlet = 0
84 Design option = False
85 Design schedule = 40
86 Property_SolverEngine = Flarenet
87 Property_DoAIVScreening = False
88 Property_AIVScreeningSelection = Enum_FixedAPI
89 Property_AIVFixedLimit = 155 dB
90 Property_PublishedAIVCurve = Carucci and Mueller (1982)
91 Property_AIVMixedPhaseOption = Enum_VaporPhaseOnly
92 Property_AIVVaporFractionOption = Mass
93 Property_AIVVaporFractionLimit = 95.0%
94 Property_AIVFlowBasis = Rated Flow
95 Engine = Flarenet Solver Engine

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 2 of 2


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design

Messages:Solver
No. Message

1 Calculations Started At 6:10 pm


2 Calculation Time = 0:00:03

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 1 of 1


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design

Messages:Sizer
No. Message

1 'Tailpipe 4' Initialised To 4 inch / 40


2 'Tailpipe 3' Initialised To 4 inch / 40
3 'Tailpipe 2' Initialised To 4 inch / 40
4 'Tailpipe 1' Initialised To 5 inch / 40
5 'Header 1' Initialised To 8 inch / 30
6 'Header 2' Initialised To 8 inch / 40
7 'Header 3' Initialised To 8 inch / 40
8 'Stack' Initialised To 8 inch / 40
9 'Stack' Changed To 10 inch / 40 By Scenario Default Scenario
10 'Stack' Changed To 12 inch / 40 By Scenario Default Scenario
11 'Stack' Changed To 14 inch / 40 By Scenario Default Scenario
12 'Stack' Changed To 16 inch / 40 By Scenario Default Scenario
13 'Stack' Changed To 18 inch / 40 By Scenario Default Scenario
14 'Stack' Changed To 20 inch / 40 By Scenario Default Scenario
15 'Stack' Changed To 24 inch / 40 By Scenario Default Scenario
16 'Stack' Changed To 32 inch / 40 By Scenario Default Scenario
17 'Header 3' Changed To 10 inch / 40 By Scenario Default Scenario
18 'Header 3' Changed To 12 inch / 40 By Scenario Default Scenario
19 'Header 3' Changed To 14 inch / 40 By Scenario Default Scenario
20 'Header 3' Changed To 16 inch / 40 By Scenario Default Scenario
21 'Header 3' Changed To 18 inch / 40 By Scenario Default Scenario
22 'Header 3' Changed To 20 inch / 40 By Scenario Default Scenario
23 'Header 3' Changed To 24 inch / 40 By Scenario Default Scenario
24 'Header 3' Changed To 32 inch / 40 By Scenario Default Scenario
25 'Header 2' Changed To 10 inch / 40 By Scenario Default Scenario
26 'Header 2' Changed To 12 inch / 40 By Scenario Default Scenario
27 'Header 2' Changed To 14 inch / 40 By Scenario Default Scenario
28 'Header 2' Changed To 16 inch / 40 By Scenario Default Scenario
29 'Header 2' Changed To 18 inch / 40 By Scenario Default Scenario
30 'Header 2' Changed To 20 inch / 40 By Scenario Default Scenario
31 'Header 2' Changed To 24 inch / 40 By Scenario Default Scenario
32 'Header 2' Changed To 32 inch / 40 By Scenario Default Scenario
33 'Header 1' Changed To 10 inch / 30 By Scenario Default Scenario
34 'Header 1' Changed To 12 inch / 30 By Scenario Default Scenario
35 'Header 1' Changed To 14 inch / 30 By Scenario Default Scenario
36 'Header 1' Changed To 16 inch / 30 By Scenario Default Scenario
37 'Header 1' Changed To 18 inch / 30 By Scenario Default Scenario
38 'Header 1' Changed To 20 inch / 30 By Scenario Default Scenario
39 'Tailpipe 1' Changed To 6 inch / 40 By Scenario Default Scenario
40 'Tailpipe 1' Changed To 8 inch / 40 By Scenario Default Scenario
41 'Tailpipe 1' Changed To 10 inch / 40 By Scenario Default Scenario
42 'Tailpipe 1' Changed To 12 inch / 40 By Scenario Default Scenario
43 'Tailpipe 2' Changed To 5 inch / 40 By Scenario Default Scenario
44 'Tailpipe 2' Changed To 6 inch / 40 By Scenario Default Scenario
45 'Tailpipe 2' Changed To 8 inch / 40 By Scenario Default Scenario
46 'Tailpipe 2' Changed To 10 inch / 40 By Scenario Default Scenario
47 'Tailpipe 2' Changed To 12 inch / 40 By Scenario Default Scenario
48 'Tailpipe 3' Changed To 5 inch / 40 By Scenario Default Scenario

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 1 of 2


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design

Messages:Sizer
No. Message

49 'Tailpipe 3' Changed To 6 inch / 40 By Scenario Default Scenario


50 'Tailpipe 3' Changed To 8 inch / 40 By Scenario Default Scenario
51 'Tailpipe 3' Changed To 10 inch / 40 By Scenario Default Scenario
52 'Tailpipe 3' Changed To 12 inch / 40 By Scenario Default Scenario
53 'Tailpipe 3' Changed To 14 inch / 40 By Scenario Default Scenario
54 'Tailpipe 4' Changed To 5 inch / 40 By Scenario Default Scenario
55 'Tailpipe 4' Changed To 6 inch / 40 By Scenario Default Scenario
56 'Tailpipe 4' Changed To 8 inch / 40 By Scenario Default Scenario
57 'Tailpipe 4' Changed To 10 inch / 40 By Scenario Default Scenario
58 'Tailpipe 4' Changed To 12 inch / 40 By Scenario Default Scenario
59 'Tailpipe 4' Changed To 14 inch / 40 By Scenario Default Scenario
60 'Tailpipe 1' Changed To 14 inch / 40 By Scenario Source 1 Only
61 'Tailpipe 1' Changed To 16 inch / 40 By Scenario Source 1 Only
62 'Tailpipe 1' Changed To 18 inch / 40 By Scenario Source 1 Only
63 'Tailpipe 2' Changed To 14 inch / 40 By Scenario Source 2 Only
64 'Tailpipe 2' Changed To 16 inch / 40 By Scenario Source 2 Only
65 'Tailpipe 2' Changed To 18 inch / 40 By Scenario Source 2 Only
66 'Tailpipe 3' Changed To 16 inch / 40 By Scenario Source 3 Only
67 'Tailpipe 3' Changed To 18 inch / 40 By Scenario Source 3 Only
68 'Tailpipe 4' Changed To 16 inch / 40 By Scenario Source 4 Only
69 'Tailpipe 4' Changed To 18 inch / 40 By Scenario Source 4 Only

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 2 of 2


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design

Messages:Loop
No. Message

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 1 of 1


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Default Scenario

Source Data
Name Location Outlet Type Ignored Inlet Inlet Temp. Allowable
Pipe Pressure Spec. Backpressure
(bar) (C) (bar)
Source 1 Tailpipe 1 Control Valve No 10.000 15 5.000
Source 2 Tailpipe 2 Control Valve No 10.000 15 5.000
Source 3 Tailpipe 3 Control Valve No 10.000 15 5.000
Source 4 Tailpipe 4 Control Valve No 10.000 15 5.000

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 1 of 5


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Default Scenario

Source Data
Name Outlet Mass Rated Mass Volumetric FlowOutlet Flange Valves Relief Valve Orifice Orifice
Temperature Flow Flow (m3/hr) Diameter Type Area
(C) (kg/hr) (kg/hr) (mm) (mm2)
Source 1 15.000 100,000.000 11,619.996
Source 2 15.000 100,000.000 9,064.261
Source 3 15.000 100,000.000 7,290.923
Source 4 15.000 100,000.000 6,048.973

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 2 of 5


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Default Scenario

Source Data
Name Back Pres. Outlet Fittings Inlet Length Inlet Elev. Inlet Material Inlet Roughness Inlet Nom. Inlet
Limit Loss Method (m) Change (mm) Diameter Schedule
(bar) (m)
Source 1 Calculated 0.000 0.000 Carbon Steel 0.046 12 inch 40
Source 2 Calculated 0.000 0.000 Carbon Steel 0.046 12 inch 40
Source 3 Calculated 0.000 0.000 Carbon Steel 0.046 12 inch 40
Source 4 Calculated 0.000 0.000 Carbon Steel 0.046 12 inch 40

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 3 of 5


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Default Scenario

Source Data
Name Inlet Intern.Inlet PipeInlet FittingsInlet Fittings Static Inlet VLE Inlet Temp. Vapour Enthalpy
Diameter Class Loss A Loss B Pres. Drop Method Calc. Fraction (kJ/hr)
(mm) (bar) (C)
Source 1 303.225 No 0.000 0.000 0.000 Model Default 15.000 1.000 10,171.316
Source 2 303.225 No 0.000 0.000 0.000 Model Default 15.000 1.000 10,803.309
Source 3 303.225 No 0.000 0.000 0.000 Model Default 15.000 1.000 11,435.302
Source 4 303.225 No 0.000 0.000 0.000 Model Default 15.000 1.000 12,599.673

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 4 of 5


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Default Scenario

Source Data
Name Entropy Energy Composition Mol. Wt. SPL Methane Ethane Propane
(kJ/kgmole/K) (kJ/hr) Basis (dB)

Source 1 228.822 50,856,581.097 Molecular Weight 20.000 0.717894 0.282106 0.000000


Source 2 233.332 43,213,235.525 Molecular Weight 25.000 0.361439 0.638561 0.000000
Source 3 232.169 38,117,671.810 Molecular Weight 30.000 0.004983 0.995017 0.000000
Source 4 225.339 35,999,065.695 Molecular Weight 35.000 0.000000 0.648530 0.351470

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 5 of 5


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Default Scenario

Pressure/Flow Summary(Velocities Based Upon Nominal Flows)


Name Internal Equivalent Fittings Length Length Mass Molar Rated Mass
Diameter Length (K X D /Ft) (m) Flow Flow Flow
(mm) (m) (kg/hr) (kgmole/hr) (kg/hr)
Header 2 777.850 50.00 0.00 50.000 300000.0 12333.33 300000.0
Header 3 777.850 50.00 0.00 50.000 400000.0 15190.48 400000.0
Stack 777.850 100.00 0.00 100.000 400000.0 15190.48 400000.0
Header 1 482.600 50.00 0.00 50.000 200000.0 9000.00 200000.0
Tailpipe 1 428.650 25.00 0.00 25.000 100000.0 5000.00 100000.0
Tailpipe 2 428.650 25.00 0.00 25.000 100000.0 4000.00 100000.0
Tailpipe 3 428.650 25.00 0.00 25.000 100000.0 3333.33 100000.0
Tailpipe 4 428.650 25.00 0.00 25.000 100000.0 2857.14 100000.0

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 1 of 6


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Default Scenario

Pressure/Flow Summary(Velocities Based Upon Nominal Flows)


Name Static Pressure Noise Static Source Upstream Upstream Upstream
Drop (dB) Back Pressure Static Pressure Temperature Velocity
(bar) (bar) (bar) (C) (m/s)
Header 2 0.06163 74.0 1.92160 15.00 89.016
Header 3 0.12240 83.9 1.77290 15.00 118.714
Stack 0.29765 90.9 1.65051 15.00 127.613
Header 1 0.38842 86.7 2.25290 15.00 144.042
Tailpipe 1 0.06728 63.8 2.56688 2.56688 14.98 89.134
Tailpipe 2 0.05237 61.1 2.57125 2.57125 15.00 70.743
Tailpipe 3 0.05659 64.9 2.02218 2.02217 15.00 74.680
Tailpipe 4 0.05142 64.7 1.89306 1.89306 15.00 68.070

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 2 of 6


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Default Scenario

Pressure/Flow Summary(Velocities Based Upon Nominal Flows)


Name Upstream Upstream Upstream Upstream Upstream Downstream
Mach No. Rho V2 Enthalpy Flow Volume Flow SPL Static Pressure
(kg/m/s2) (kJ/hr) (m3/hr) (dB) (bar)
Header 2 0.257 15610 1.322e+008 1.523e+005 1.85996
Header 3 0.360 27757 1.682e+008 2.031e+005 1.65051
Stack 0.386 29838 1.682e+008 2.183e+005 1.35286
Header 1 0.395 43747 9.407e+007 9.485e+004 1.86448
Tailpipe 1 0.230 17157 5.086e+007 4.631e+004 2.49959
Tailpipe 2 0.208 13617 4.321e+007 3.675e+004 2.51888
Tailpipe 3 0.244 14375 3.812e+007 3.880e+004 1.96558
Tailpipe 4 0.244 13103 3.600e+007 3.536e+004 1.84164

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 3 of 6


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Default Scenario

Pressure/Flow Summary(Velocities Based Upon Nominal Flows)


Name Downstream Downstream Downstream Downstream Downstream Downstream
Temperature Velocity Mach No. Rho V2 Enthalpy Flow Volume Flow
(C) (m/s) (kg/m/s2) (kJ/hr) (m3/hr)
Header 2 15.00 91.994 0.266 16132 1.322e+008 1.574e+005
Header 3 15.00 127.613 0.386 29838 1.682e+008 2.183e+005
Stack 15.00 155.971 0.472 36469 1.682e+008 2.668e+005
Header 1 15.00 174.321 0.478 52943 9.407e+007 1.148e+005
Tailpipe 1 14.98 91.552 0.236 17622 5.086e+007 4.756e+004
Tailpipe 2 15.00 72.235 0.213 13904 4.321e+007 3.753e+004
Tailpipe 3 15.00 76.870 0.251 14796 3.812e+007 3.993e+004
Tailpipe 4 15.00 70.014 0.251 13477 3.600e+007 3.637e+004

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 4 of 6


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Default Scenario

Pressure/Flow Summary(Velocities Based Upon Nominal Flows)


Name Downstream Flow Static Pipe Static Pipe Static Pipe Pipe
SPL Regime Friction Loss Accel. Loss Elevation Loss Fittings Loss
(dB) (bar) (bar) (bar) (bar)
Header 2 Single Phase/Single Phase 0.00000
Header 3 Single Phase/Single Phase 0.00000
Stack Single Phase/Single Phase 0.00000
Header 1 Single Phase/Single Phase 0.00000
Tailpipe 1 Single Phase/Single Phase 0.00000
Tailpipe 2 Single Phase/Single Phase 0.00000
Tailpipe 3 Single Phase/Single Phase 0.00000
Tailpipe 4 Single Phase/Single Phase 0.00000

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 5 of 6


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Default Scenario

Pressure/Flow Summary(Velocities Based Upon Nominal Flows)


Name Friction Reynolds Duty Overall External External
Factor Number (kJ/hr) HTC Convective HTC Radiative HTC
(W/m2/C) (W/m2/C) (W/m2/C)
Header 2 0.01107 13742297 0.000e+000
Header 3 0.01102 18692854 0.000e+000
Stack 0.01101 18857029 0.000e+000
Header 1 0.01200 14530887 0.000e+000
Tailpipe 1 0.01236 7908419 0.000e+000
Tailpipe 2 0.01235 8379860 0.000e+000
Tailpipe 3 0.01233 8906422 0.000e+000
Tailpipe 4 0.01233 9238914 0.000e+000

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 6 of 7


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Default Scenario

Pressure/Flow Summary(Velocities Based Upon Nominal Flows)


Name Internal Wall External
HTC Temperature Temperature
(W/m2/C) (C) (C)
Header 2
Header 3
Stack
Header 1
Tailpipe 1
Tailpipe 2
Tailpipe 3
Tailpipe 4

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 7 of 7


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 1 Only

Source Data
Name Location Outlet Type Ignored Inlet Inlet Temp. Allowable
Pipe Pressure Spec. Backpressure
(bar) (C) (bar)
Source 1 Tailpipe 1 Control Valve No 10.000 15 5.000
Source 2 Tailpipe 2 Control Valve Yes 10.000 15 5.000
Source 3 Tailpipe 3 Control Valve Yes 10.000 15 5.000
Source 4 Tailpipe 4 Control Valve Yes 10.000 15 5.000

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 1 of 5


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 1 Only

Source Data
Name Outlet Mass Rated Mass Volumetric FlowOutlet Flange Valves Relief Valve Orifice Orifice
Temperature Flow Flow (m3/hr) Diameter Type Area
(C) (kg/hr) (kg/hr) (mm) (mm2)
Source 1 15.000 100,000.000 11,619.996
Source 2 15.000 0.000 0.000
Source 3 15.000 0.000 0.000
Source 4 15.000 0.000 0.000

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 2 of 5


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 1 Only

Source Data
Name Back Pres. Outlet Fittings Inlet Length Inlet Elev. Inlet Material Inlet Roughness Inlet Nom. Inlet
Limit Loss Method (m) Change (mm) Diameter Schedule
(bar) (m)
Source 1 Calculated 0.000 0.000 Carbon Steel 0.046 12 inch 40
Source 2 Calculated 0.000 0.000 Carbon Steel 0.046 12 inch 40
Source 3 Calculated 0.000 0.000 Carbon Steel 0.046 12 inch 40
Source 4 Calculated 0.000 0.000 Carbon Steel 0.046 12 inch 40

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 3 of 5


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 1 Only

Source Data
Name Inlet Intern.Inlet PipeInlet FittingsInlet Fittings Static Inlet VLE Inlet Temp. Vapour Enthalpy
Diameter Class Loss A Loss B Pres. Drop Method Calc. Fraction (kJ/hr)
(mm) (bar) (C)
Source 1 303.225 No 0.000 0.000 0.000 Model Default 15.000 1.000 10,171.316
Source 2 303.225 No 0.000 0.000 0.000 Model Default 15.000 1.000 10,803.309
Source 3 303.225 No 0.000 0.000 0.000 Model Default 15.000 1.000 11,435.302
Source 4 303.225 No 0.000 0.000 0.000 Model Default 15.000 1.000 12,599.673

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 4 of 5


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 1 Only

Source Data
Name Entropy Energy Composition Mol. Wt. SPL Methane Ethane Propane
(kJ/kgmole/K) (kJ/hr) Basis (dB)

Source 1 228.822 50,856,581.097 Molecular Weight 20.000 0.717894 0.282106 0.000000


Source 2 233.332 43,213,235.525 Molecular Weight 25.000 0.361439 0.638561 0.000000
Source 3 232.169 38,117,671.810 Molecular Weight 30.000 0.004983 0.995017 0.000000
Source 4 225.339 35,999,065.695 Molecular Weight 35.000 0.000000 0.648530 0.351470

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 5 of 5


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 1 Only

Pressure/Flow Summary(Velocities Based Upon Nominal Flows)


Name Internal Equivalent Fittings Length Length Mass Molar Rated Mass
Diameter Length (K X D /Ft) (m) Flow Flow Flow
(mm) (m) (kg/hr) (kgmole/hr) (kg/hr)
Header 2 777.850 50.00 0.00 50.000 100000.0 5000.00 100000.0
Header 3 777.850 50.00 0.00 50.000 100000.0 5000.00 100000.0
Stack 777.850 100.00 0.00 100.000 100000.0 5000.00 100000.0
Header 1 482.600 50.00 0.00 50.000 100000.0 5000.00 100000.0
Tailpipe 1 428.650 25.00 0.00 25.000 100000.0 5000.00 100000.0

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 1 of 6


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 1 Only

Pressure/Flow Summary(Velocities Based Upon Nominal Flows)


Name Static Pressure Noise Static Source Upstream Upstream Upstream
Drop (dB) Back Pressure Static Pressure Temperature Velocity
(bar) (bar) (bar) (C) (m/s)
Header 2 0.01412 58.3 1.10925 14.98 62.914
Header 3 0.01435 58.7 1.09314 14.98 63.843
Stack 0.02934 62.2 1.07879 14.98 64.696
Header 1 0.19137 82.2 1.24115 14.98 146.013
Tailpipe 1 0.14405 78.3 1.48971 1.48972 14.98 154.084

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 2 of 6


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 1 Only

Pressure/Flow Summary(Velocities Based Upon Nominal Flows)


Name Upstream Upstream Upstream Upstream Upstream Downstream
Mach No. Rho V2 Enthalpy Flow Volume Flow SPL Static Pressure
(kg/m/s2) (kJ/hr) (m3/hr) (dB) (bar)
Header 2 0.162 3678 5.086e+007 1.076e+005 1.09512
Header 3 0.165 3732 5.086e+007 1.092e+005 1.07879
Stack 0.167 3782 5.086e+007 1.107e+005 1.04945
Header 1 0.376 22173 5.086e+007 9.615e+004 1.04978
Tailpipe 1 0.397 29659 5.086e+007 8.005e+004 1.34567

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 3 of 6


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 1 Only

Pressure/Flow Summary(Velocities Based Upon Nominal Flows)


Name Downstream Downstream Downstream Downstream Downstream Downstream
Temperature Velocity Mach No. Rho V2 Enthalpy Flow Volume Flow
(C) (m/s) (kg/m/s2) (kJ/hr) (m3/hr)
Header 2 14.98 63.728 0.164 3725 5.086e+007 1.090e+005
Header 3 14.98 64.696 0.167 3782 5.086e+007 1.107e+005
Stack 14.98 66.510 0.171 3888 5.086e+007 1.138e+005
Header 1 14.98 172.731 0.445 26230 5.086e+007 1.137e+005
Tailpipe 1 14.98 170.651 0.440 32848 5.086e+007 8.866e+004

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 4 of 6


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 1 Only

Pressure/Flow Summary(Velocities Based Upon Nominal Flows)


Name Downstream Flow Static Pipe Static Pipe Static Pipe Pipe
SPL Regime Friction Loss Accel. Loss Elevation Loss Fittings Loss
(dB) (bar) (bar) (bar) (bar)
Header 2 Single Phase/Single Phase 0.00000
Header 3 Single Phase/Single Phase 0.00000
Stack Single Phase/Single Phase 0.00000
Header 1 Single Phase/Single Phase 0.00000
Tailpipe 1 Single Phase/Single Phase 0.00000

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 5 of 6


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 1 Only

Pressure/Flow Summary(Velocities Based Upon Nominal Flows)


Name Friction Reynolds Duty Overall External External
Factor Number (kJ/hr) HTC Convective HTC Radiative HTC
(W/m2/C) (W/m2/C) (W/m2/C)
Header 2 0.01147 4357500 0.000e+000
Header 3 0.01147 4357512 0.000e+000
Stack 0.01147 4358154 0.000e+000
Header 1 0.01214 7072777 0.000e+000
Tailpipe 1 0.01236 7927635 0.000e+000

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 6 of 6


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 2 Only

Source Data
Name Location Outlet Type Ignored Inlet Inlet Temp. Allowable
Pipe Pressure Spec. Backpressure
(bar) (C) (bar)
Source 1 Tailpipe 1 Control Valve Yes 10.000 15 5.000
Source 2 Tailpipe 2 Control Valve No 10.000 15 5.000
Source 3 Tailpipe 3 Control Valve Yes 10.000 15 5.000
Source 4 Tailpipe 4 Control Valve Yes 10.000 15 5.000

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 1 of 5


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 2 Only

Source Data
Name Outlet Mass Rated Mass Volumetric FlowOutlet Flange Valves Relief Valve Orifice Orifice
Temperature Flow Flow (m3/hr) Diameter Type Area
(C) (kg/hr) (kg/hr) (mm) (mm2)
Source 1 15.000 0.000 0.000
Source 2 15.000 100,000.000 9,064.261
Source 3 15.000 0.000 0.000
Source 4 15.000 0.000 0.000

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 2 of 5


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 2 Only

Source Data
Name Back Pres. Outlet Fittings Inlet Length Inlet Elev. Inlet Material Inlet Roughness Inlet Nom. Inlet
Limit Loss Method (m) Change (mm) Diameter Schedule
(bar) (m)
Source 1 Calculated 0.000 0.000 Carbon Steel 0.046 12 inch 40
Source 2 Calculated 0.000 0.000 Carbon Steel 0.046 12 inch 40
Source 3 Calculated 0.000 0.000 Carbon Steel 0.046 12 inch 40
Source 4 Calculated 0.000 0.000 Carbon Steel 0.046 12 inch 40

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 3 of 5


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 2 Only

Source Data
Name Inlet Intern.Inlet PipeInlet FittingsInlet Fittings Static Inlet VLE Inlet Temp. Vapour Enthalpy
Diameter Class Loss A Loss B Pres. Drop Method Calc. Fraction (kJ/hr)
(mm) (bar) (C)
Source 1 303.225 No 0.000 0.000 0.000 Model Default 15.000 1.000 10,171.316
Source 2 303.225 No 0.000 0.000 0.000 Model Default 15.000 1.000 10,803.309
Source 3 303.225 No 0.000 0.000 0.000 Model Default 15.000 1.000 11,435.302
Source 4 303.225 No 0.000 0.000 0.000 Model Default 15.000 1.000 12,599.673

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 4 of 5


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 2 Only

Source Data
Name Entropy Energy Composition Mol. Wt. SPL Methane Ethane Propane
(kJ/kgmole/K) (kJ/hr) Basis (dB)

Source 1 228.822 50,856,581.097 Molecular Weight 20.000 0.717894 0.282106 0.000000


Source 2 233.332 43,213,235.525 Molecular Weight 25.000 0.361439 0.638561 0.000000
Source 3 232.169 38,117,671.810 Molecular Weight 30.000 0.004983 0.995017 0.000000
Source 4 225.339 35,999,065.695 Molecular Weight 35.000 0.000000 0.648530 0.351470

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 5 of 5


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 2 Only

Pressure/Flow Summary(Velocities Based Upon Nominal Flows)


Name Internal Equivalent Fittings Length Length Mass Molar Rated Mass
Diameter Length (K X D /Ft) (m) Flow Flow Flow
(mm) (m) (kg/hr) (kgmole/hr) (kg/hr)
Header 2 777.850 50.00 0.00 50.000 100000.0 4000.00 100000.0
Header 3 777.850 50.00 0.00 50.000 100000.0 4000.00 100000.0
Stack 777.850 100.00 0.00 100.000 100000.0 4000.00 100000.0
Header 1 482.600 50.00 0.00 50.000 100000.0 4000.00 100000.0
Tailpipe 2 428.650 25.00 0.00 25.000 100000.0 4000.00 100000.0

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 1 of 6


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 2 Only

Pressure/Flow Summary(Velocities Based Upon Nominal Flows)


Name Static Pressure Noise Static Source Upstream Upstream Upstream
Drop (dB) Back Pressure Static Pressure Temperature Velocity
(bar) (bar) (bar) (C) (m/s)
Header 2 0.01135 56.3 1.09020 15.00 51.081
Header 3 0.01150 56.5 1.07725 15.00 51.699
Stack 0.02341 60.0 1.06575 15.00 52.260
Header 1 0.14986 80.0 1.19246 15.00 121.254
Tailpipe 2 0.13555 79.4 1.29284 1.29284 15.00 141.685

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 2 of 6


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 2 Only

Pressure/Flow Summary(Velocities Based Upon Nominal Flows)


Name Upstream Upstream Upstream Upstream Upstream Downstream
Mach No. Rho V2 Enthalpy Flow Volume Flow SPL Static Pressure
(kg/m/s2) (kJ/hr) (m3/hr) (dB) (bar)
Header 2 0.150 2986 4.321e+007 8.739e+004 1.07885
Header 3 0.152 3022 4.321e+007 8.844e+004 1.06575
Stack 0.153 3055 4.321e+007 8.940e+004 1.04234
Header 1 0.356 18413 4.321e+007 7.985e+004 1.04260
Tailpipe 2 0.416 27273 4.321e+007 7.361e+004 1.15729

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 3 of 6


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 2 Only

Pressure/Flow Summary(Velocities Based Upon Nominal Flows)


Name Downstream Downstream Downstream Downstream Downstream Downstream
Temperature Velocity Mach No. Rho V2 Enthalpy Flow Volume Flow
(C) (m/s) (kg/m/s2) (kJ/hr) (m3/hr)
Header 2 15.00 51.621 0.151 3017 4.321e+007 8.831e+004
Header 3 15.00 52.260 0.153 3055 4.321e+007 8.940e+004
Stack 15.00 53.440 0.157 3124 4.321e+007 9.142e+004
Header 1 15.00 138.795 0.407 21077 4.321e+007 9.140e+004
Tailpipe 2 15.00 158.398 0.464 30489 4.321e+007 8.229e+004

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 4 of 6


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 2 Only

Pressure/Flow Summary(Velocities Based Upon Nominal Flows)


Name Downstream Flow Static Pipe Static Pipe Static Pipe Pipe
SPL Regime Friction Loss Accel. Loss Elevation Loss Fittings Loss
(dB) (bar) (bar) (bar) (bar)
Header 2 Single Phase/Single Phase 0.00000
Header 3 Single Phase/Single Phase 0.00000
Stack Single Phase/Single Phase 0.00000
Header 1 Single Phase/Single Phase 0.00000
Tailpipe 2 Single Phase/Single Phase 0.00000

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 5 of 6


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 2 Only

Pressure/Flow Summary(Velocities Based Upon Nominal Flows)


Name Friction Reynolds Duty Overall External External
Factor Number (kJ/hr) HTC Convective HTC Radiative HTC
(W/m2/C) (W/m2/C) (W/m2/C)
Header 2 0.01144 4617524 0.000e+000
Header 3 0.01144 4617530 0.000e+000
Stack 0.01144 4617972 0.000e+000
Header 1 0.01213 7476288 0.000e+000
Tailpipe 2 0.01235 8405019 0.000e+000

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 6 of 6


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 3 Only

Source Data
Name Location Outlet Type Ignored Inlet Inlet Temp. Allowable
Pipe Pressure Spec. Backpressure
(bar) (C) (bar)
Source 1 Tailpipe 1 Control Valve Yes 10.000 15 5.000
Source 2 Tailpipe 2 Control Valve Yes 10.000 15 5.000
Source 3 Tailpipe 3 Control Valve No 10.000 15 5.000
Source 4 Tailpipe 4 Control Valve Yes 10.000 15 5.000

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 1 of 5


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 3 Only

Source Data
Name Outlet Mass Rated Mass Volumetric FlowOutlet Flange Valves Relief Valve Orifice Orifice
Temperature Flow Flow (m3/hr) Diameter Type Area
(C) (kg/hr) (kg/hr) (mm) (mm2)
Source 1 15.000 0.000 0.000
Source 2 15.000 0.000 0.000
Source 3 15.000 100,000.000 7,290.923
Source 4 15.000 0.000 0.000

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 2 of 5


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 3 Only

Source Data
Name Back Pres. Outlet Fittings Inlet Length Inlet Elev. Inlet Material Inlet Roughness Inlet Nom. Inlet
Limit Loss Method (m) Change (mm) Diameter Schedule
(bar) (m)
Source 1 Calculated 0.000 0.000 Carbon Steel 0.046 12 inch 40
Source 2 Calculated 0.000 0.000 Carbon Steel 0.046 12 inch 40
Source 3 Calculated 0.000 0.000 Carbon Steel 0.046 12 inch 40
Source 4 Calculated 0.000 0.000 Carbon Steel 0.046 12 inch 40

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 3 of 5


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 3 Only

Source Data
Name Inlet Intern.Inlet PipeInlet FittingsInlet Fittings Static Inlet VLE Inlet Temp. Vapour Enthalpy
Diameter Class Loss A Loss B Pres. Drop Method Calc. Fraction (kJ/hr)
(mm) (bar) (C)
Source 1 303.225 No 0.000 0.000 0.000 Model Default 15.000 1.000 10,171.316
Source 2 303.225 No 0.000 0.000 0.000 Model Default 15.000 1.000 10,803.309
Source 3 303.225 No 0.000 0.000 0.000 Model Default 15.000 1.000 11,435.302
Source 4 303.225 No 0.000 0.000 0.000 Model Default 15.000 1.000 12,599.673

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 4 of 5


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 3 Only

Source Data
Name Entropy Energy Composition Mol. Wt. SPL Methane Ethane Propane
(kJ/kgmole/K) (kJ/hr) Basis (dB)

Source 1 228.822 50,856,581.097 Molecular Weight 20.000 0.717894 0.282106 0.000000


Source 2 233.332 43,213,235.525 Molecular Weight 25.000 0.361439 0.638561 0.000000
Source 3 232.169 38,117,671.810 Molecular Weight 30.000 0.004983 0.995017 0.000000
Source 4 225.339 35,999,065.695 Molecular Weight 35.000 0.000000 0.648530 0.351470

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 5 of 5


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 3 Only

Pressure/Flow Summary(Velocities Based Upon Nominal Flows)


Name Internal Equivalent Fittings Length Length Mass Molar Rated Mass
Diameter Length (K X D /Ft) (m) Flow Flow Flow
(mm) (m) (kg/hr) (kgmole/hr) (kg/hr)
Header 2 777.850 50.00 0.00 50.000 100000.0 3333.33 100000.0
Header 3 777.850 50.00 0.00 50.000 100000.0 3333.33 100000.0
Stack 777.850 100.00 0.00 100.000 100000.0 3333.33 100000.0
Tailpipe 3 428.650 25.00 0.00 25.000 100000.0 3333.33 100000.0

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 1 of 6


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 3 Only

Pressure/Flow Summary(Velocities Based Upon Nominal Flows)


Name Static Pressure Noise Static Source Upstream Upstream Upstream
Drop (dB) Back Pressure Static Pressure Temperature Velocity
(bar) (bar) (bar) (C) (m/s)
Header 2 0.00947 54.5 1.07732 15.00 42.926
Header 3 0.00957 54.7 1.06651 15.00 43.365
Stack 0.01942 58.1 1.05694 15.00 43.761
Tailpipe 3 0.11983 79.0 1.19713 1.19712 15.00 127.072

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 2 of 6


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 3 Only

Pressure/Flow Summary(Velocities Based Upon Nominal Flows)


Name Upstream Upstream Upstream Upstream Upstream Downstream
Mach No. Rho V2 Enthalpy Flow Volume Flow SPL Static Pressure
(kg/m/s2) (kJ/hr) (m3/hr) (dB) (bar)
Header 2 0.140 2509 3.812e+007 7.343e+004 1.06785
Header 3 0.141 2535 3.812e+007 7.419e+004 1.05694
Stack 0.142 2558 3.812e+007 7.486e+004 1.03752
Tailpipe 3 0.414 24460 3.812e+007 6.602e+004 1.07730

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 3 of 6


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 3 Only

Pressure/Flow Summary(Velocities Based Upon Nominal Flows)


Name Downstream Downstream Downstream Downstream Downstream Downstream
Temperature Velocity Mach No. Rho V2 Enthalpy Flow Volume Flow
(C) (m/s) (kg/m/s2) (kJ/hr) (m3/hr)
Header 2 15.00 43.310 0.141 2532 3.812e+007 7.409e+004
Header 3 15.00 43.761 0.142 2558 3.812e+007 7.486e+004
Stack 15.00 44.588 0.145 2606 3.812e+007 7.628e+004
Tailpipe 3 15.00 141.356 0.460 27209 3.812e+007 7.344e+004

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 4 of 6


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 3 Only

Pressure/Flow Summary(Velocities Based Upon Nominal Flows)


Name Downstream Flow Static Pipe Static Pipe Static Pipe Pipe
SPL Regime Friction Loss Accel. Loss Elevation Loss Fittings Loss
(dB) (bar) (bar) (bar) (bar)
Header 2 Single Phase/Single Phase 0.00000
Header 3 Single Phase/Single Phase 0.00000
Stack Single Phase/Single Phase 0.00000
Tailpipe 3 Single Phase/Single Phase 0.00000

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 5 of 6


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 3 Only

Pressure/Flow Summary(Velocities Based Upon Nominal Flows)


Name Friction Reynolds Duty Overall External External
Factor Number (kJ/hr) HTC Convective HTC Radiative HTC
(W/m2/C) (W/m2/C) (W/m2/C)
Header 2 0.01141 4907145 0.000e+000
Header 3 0.01141 4907149 0.000e+000
Stack 0.01141 4907477 0.000e+000
Tailpipe 3 0.01233 8929849 0.000e+000

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 6 of 6


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 4 Only

Source Data
Name Location Outlet Type Ignored Inlet Inlet Temp. Allowable
Pipe Pressure Spec. Backpressure
(bar) (C) (bar)
Source 1 Tailpipe 1 Control Valve Yes 10.000 15 5.000
Source 2 Tailpipe 2 Control Valve Yes 10.000 15 5.000
Source 3 Tailpipe 3 Control Valve Yes 10.000 15 5.000
Source 4 Tailpipe 4 Control Valve No 10.000 15 5.000

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 1 of 5


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 4 Only

Source Data
Name Outlet Mass Rated Mass Volumetric FlowOutlet Flange Valves Relief Valve Orifice Orifice
Temperature Flow Flow (m3/hr) Diameter Type Area
(C) (kg/hr) (kg/hr) (mm) (mm2)
Source 1 15.000 0.000 0.000
Source 2 15.000 0.000 0.000
Source 3 15.000 0.000 0.000
Source 4 15.000 100,000.000 6,048.973

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 2 of 5


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 4 Only

Source Data
Name Back Pres. Outlet Fittings Inlet Length Inlet Elev. Inlet Material Inlet Roughness Inlet Nom. Inlet
Limit Loss Method (m) Change (mm) Diameter Schedule
(bar) (m)
Source 1 Calculated 0.000 0.000 Carbon Steel 0.046 12 inch 40
Source 2 Calculated 0.000 0.000 Carbon Steel 0.046 12 inch 40
Source 3 Calculated 0.000 0.000 Carbon Steel 0.046 12 inch 40
Source 4 Calculated 0.000 0.000 Carbon Steel 0.046 12 inch 40

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 3 of 5


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 4 Only

Source Data
Name Inlet Intern.Inlet PipeInlet FittingsInlet Fittings Static Inlet VLE Inlet Temp. Vapour Enthalpy
Diameter Class Loss A Loss B Pres. Drop Method Calc. Fraction (kJ/hr)
(mm) (bar) (C)
Source 1 303.225 No 0.000 0.000 0.000 Model Default 15.000 1.000 10,171.316
Source 2 303.225 No 0.000 0.000 0.000 Model Default 15.000 1.000 10,803.309
Source 3 303.225 No 0.000 0.000 0.000 Model Default 15.000 1.000 11,435.302
Source 4 303.225 No 0.000 0.000 0.000 Model Default 15.000 1.000 12,599.673

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 4 of 5


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 4 Only

Source Data
Name Entropy Energy Composition Mol. Wt. SPL Methane Ethane Propane
(kJ/kgmole/K) (kJ/hr) Basis (dB)

Source 1 228.822 50,856,581.097 Molecular Weight 20.000 0.717894 0.282106 0.000000


Source 2 233.332 43,213,235.525 Molecular Weight 25.000 0.361439 0.638561 0.000000
Source 3 232.169 38,117,671.810 Molecular Weight 30.000 0.004983 0.995017 0.000000
Source 4 225.339 35,999,065.695 Molecular Weight 35.000 0.000000 0.648530 0.351470

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 5 of 5


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 4 Only

Pressure/Flow Summary(Velocities Based Upon Nominal Flows)


Name Internal Equivalent Fittings Length Length Mass Molar Rated Mass
Diameter Length (K X D /Ft) (m) Flow Flow Flow
(mm) (m) (kg/hr) (kgmole/hr) (kg/hr)
Header 3 777.850 50.00 0.00 50.000 100000.0 2857.14 100000.0
Stack 777.850 100.00 0.00 100.000 100000.0 2857.14 100000.0
Tailpipe 4 428.650 25.00 0.00 25.000 100000.0 2857.14 100000.0

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 1 of 6


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 4 Only

Pressure/Flow Summary(Velocities Based Upon Nominal Flows)


Name Static Pressure Noise Static Source Upstream Upstream Upstream
Drop (dB) Back Pressure Static Pressure Temperature Velocity
(bar) (bar) (bar) (C) (m/s)
Header 3 0.00819 53.2 1.05884 15.00 37.324
Stack 0.01659 56.5 1.05065 15.00 37.619
Tailpipe 4 0.10204 77.8 1.15910 1.15910 15.00 112.144

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 2 of 6


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 4 Only

Pressure/Flow Summary(Velocities Based Upon Nominal Flows)


Name Upstream Upstream Upstream Upstream Upstream Downstream
Mach No. Rho V2 Enthalpy Flow Volume Flow SPL Static Pressure
(kg/m/s2) (kJ/hr) (m3/hr) (dB) (bar)
Header 3 0.133 2182 3.600e+007 6.385e+004 1.05065
Stack 0.134 2199 3.600e+007 6.436e+004 1.03406
Tailpipe 4 0.400 21586 3.600e+007 5.826e+004 1.05706

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 3 of 6


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 4 Only

Pressure/Flow Summary(Velocities Based Upon Nominal Flows)


Name Downstream Downstream Downstream Downstream Downstream Downstream
Temperature Velocity Mach No. Rho V2 Enthalpy Flow Volume Flow
(C) (m/s) (kg/m/s2) (kJ/hr) (m3/hr)
Header 3 15.00 37.619 0.134 2199 3.600e+007 6.436e+004
Stack 15.00 38.230 0.136 2235 3.600e+007 6.540e+004
Tailpipe 4 15.00 123.117 0.439 23698 3.600e+007 6.396e+004

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 4 of 6


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 4 Only

Pressure/Flow Summary(Velocities Based Upon Nominal Flows)


Name Downstream Flow Static Pipe Static Pipe Static Pipe Pipe
SPL Regime Friction Loss Accel. Loss Elevation Loss Fittings Loss
(dB) (bar) (bar) (bar) (bar)
Header 3 Single Phase/Single Phase 0.00000
Stack Single Phase/Single Phase 0.00000
Tailpipe 4 Single Phase/Single Phase 0.00000

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 5 of 6


Printed At 11/2/2023 6:21:16 pm
Aspen Flare System Analyzer V11 - aspenONE
Version 37.0.0.395
User Name : A. User
Job Code : Documentation
Project : Flarenet
Description : Simple Convergent System With 4 Scenarios Design
Scenario : Source 4 Only

Pressure/Flow Summary(Velocities Based Upon Nominal Flows)


Name Friction Reynolds Duty Overall External External
Factor Number (kJ/hr) HTC Convective HTC Radiative HTC
(W/m2/C) (W/m2/C) (W/m2/C)
Header 3 0.01140 5090368 0.000e+000
Stack 0.01140 5090620 0.000e+000
Tailpipe 4 0.01233 9257223 0.000e+000

C:\Program Files\AspenTech\Aspen Flare System Analyzer V11.0\Samples\Convergent\Sample-C1.fnwx Page 6 of 6


Printed At 11/2/2023 6:21:16 pm

You might also like