PROTOCOL OF SITE ACCEPTANCE TEST

AND HANDING OVER


PROJECT NUMBER: 201912-SERV
PROJECT NAME: COMMISSIONIG - FMZ5000 - GE BINTULU
CUSTOMER: GE POWER SOLUTIONS (MALAYSIA) SDN BHD
ORDER NO.: 4101891787
PLACE: BINTULU TANJUNG KIDURONG COMBINED CYCLE POWER PLANT
DATE OF INSTALLATION: 15/10/2019 – 31/10/2019

SCOPE: FIRE ALARM SYSTEM [x]


GAS WARNING SYSTEM [X]
FIRE DETECTORS [X]
GAS DETECTORS [X]
ALARM EQUIPMENT [X]
FIRE PROTECTION SYSTEM [X]
NOTIFIER ALARM SYSTEM [x]
It is hereby certified by the undersigned representatives that the above mentioned system has been
delivered, installed and started up in accordance with the purchase order: The cooperative test of the
system has been carried out according to the following test procedure. Optional complaints and/or
residual work has been noted.
The system is [ ] ready for operation
[ ] not ready for operation
[ ] the actuation control of the extinguishing system is mechanically blocked
[ ] the extinguishing system is sharp
[ ] the extinguishing system is not sharp Locking split pin not pulled [ ]
Valve handle retracted [X]
[ ] the mechanical prewarning time is adjusted with ...........sec
[ ] All keys have been handed over to......GE………………………........
Remarks: ...................................................................................................................................................

.................Alarm Counter : ……………...............Fault Counter : ................................................

Waiting hours:

Place: BINTULU TANJUNG KIDURONG Date: 31/10/2019

Representative: MX Fir e Solutions Customer


Minimax Branch Office GE Power Solutions ( Malaysia) Sdn Bhd

Signature:
------------------------------------------- ------------------------------------------

Page 1 von 23
PROTOCOL OF SITE ACCEPTANCE TEST
AND HANDING OVER
A) General

The upkeep work in accordance with the regulations serves to preserve or to restore the specified
condition of the fire alarm system, which also includes restoring the rated sensitivity of the detectors. This
optimisation of the response sensitivity of the detectors not only improves the operational readiness of the
system for the early detection of fire, but also enhances the sensitivity of the system to unpermissible
sources of deception, which are to be avoided.

As we have no influence on the operating and ambient conditions in which the system is installed, we draw
attention to the fact that corresponding deception variables deriving from the operating environment are to
be avoided in respect of the criteria for the detectors. Sources of deception are for example welding /
burning ; exhaust gases from internal-combustion engines ; process-related concentrations of aerosols or
dust ; emissions through ventilation ducts ; gases/vapours ; non-compliance with the ban on smoking.

B) RELATED DOCUMENTS

System must be checked according to the following documents with the latest release / revision

ITEM DOCUMENT TITLE GE DOCUMENT CODE MX DOCUMENT CODE


1 Block / Loop Diagram TJK/10/G/SG----GE01/BD/201 19.41150-02-02
Internal Wiring (Control
2 TJK/10/G/SG----GE01/WD/201 19.41150-02-02
Panel)
3 Logic Diagram TJK/10/G/SG----GE01/LO/201 19.41150-02-05
Equipment Manual / Data
4 TJK/10/G/SG----GE01/DS/201 19.41150-05-66
Sheets

Page 2 von 23
PROTOCOL OF SITE ACCEPTANCE TEST
AND HANDING OVER

C) Visual Inspection of the Installed Fire Alarm and Gas Warning


System

Check the proper, complete installation as well as the identification labelling


through inspection and comparison with the construction documents. [ _____]
The alarm signals must be recognisable on the Fire Panel in respect of the
location of the alarm, in other words check the labelling of the lines. [ _____]
Check the identification markings of fire alarm distributors and jointly laid
lines. [ _____]
Check the power feeder line; this must only be used to feed power to the
power supply unit and must be a separate line with its own separate fuse.
The fuse must be especially labelled and should be located in the main
distribution board. [ _____]
Check the identification markings of all equipment of the fire alarm and gas
warning system; all elements must be clearly identified without any risk of
confusion. [ _____]
Check whether fire detectors are correctly selected in respect of fire
development, room height, ambient temperature, air movements, vibrations,
humidity, smoke, dust and similar aerosols and optical radiation and are
correctly positioned. A change in the purpose for which rooms or buildings
are used necessitates a thorough revision check in these regards. [ _____]
Check whether the location of the Fire Panel is suitable. A change in the
purpose for which rooms or buildings are used necessitates a thorough
revision check in these regards. [ _____]

D) Inspection and Testing on the Fire Panel

 Type of the Fire Panel: FMZ 5000 Serial No.:

 Type of the Fire Panel: Serial No.:

 [ X ] ready for operation [ ] not ready for operation

 [ X ] All keys were present ....... Siemens......................

Page 3 von 23
PROTOCOL OF SITE ACCEPTANCE TEST
AND HANDING OVER
D1) Detectors:

Cleaning of all automatic detectors in each line with subsequent performance


test by release [ _____]
Cleaning and maintenance of all non-automatic detectors in each line with
subsequent performance test by release [ _____]
For each alarm line, simulate wire break and short-circuit. For this, release
at least one automatic or non-automatic detector per line. Interrupt or short-
circuit the line cable. Check the fire and fault signalling on the Fire Panel,from
the Line List. [ _____]

D2) Fire Panel:

Clean the Fire Panel, check all clamping joints to make sure they are tight [ _____]
Test the proper function of all buttons and switches by actuating them [ _____]
Check the setting values of all detector alarm, control and monitoring lines by
measuring (line voltage, line current, fault threshold) [ _____]
Then check all detector alarm, control and monitoring lines for indications of
fire, wire break and/or short-circuit by means of the test switches (only FMZ
/ 5000) [ _____]
In intrinsically safe circuits, check the Zener barriers for effectiveness by
measuring [ _____]
Measure the line input voltage [ _____]
Measure and adjust the output voltage on the power supply unit [ _____]
Check and adjust the charging voltage [ _____]
Check voltage L1 and N against ground [ _____]
Check uninterrupted operation in case of line and battery failure. [ _____]
Measure the system current that flows from the battery to the system when
the line voltage is switched off. measured value: ................mA [ _____]
If the battery is monitored, disconnect the battery cable on the battery.
The fault message must appear. [ _____]
Carry out a load test on the battery to check the battery capacity that is still
available; if necessary, replace the battery. [ _____]
Check the alarm relaying and the dependence, safety and logic circuits for
effectiveness. [ _____]

Page 4 von 23
PROTOCOL OF SITE ACCEPTANCE TEST
AND HANDING OVER
Input Groups Loop 1
MODULE Group FUNCTION ADDRESS OK REMARKS
10CYE10CU251-B01
A1 101/Det.1 1 Fire Group
Optical smoke detector OMX95
10CYE10CT251-B02
A1 102/Det.2 2 Fire Group
Heat detector WMX5000
10CYE10CH254-S52
A1 104/Det.2 3 Fire Group
Manual call point DMX3195-I yellow
10CYE10CH256-S62
A1 121/Det.2 4&5 Fire Group
Status indicator IP66 lamp controlled
10CYE10CH200-S03
A1 110/Det.3 6 Fire Group
Manual call point DMX3195-I red
10CYE10CH254-S53
A1 104/Det.3 7 Fire Group
Manual call point DMX3195-I yellow
10CYE10CH256-S63 Extinguishing
A1 121/Det.3 8&9
Status indicator IP66 lamp controlled Group
10CYE10CH256-S64 Extinguishing
A1 121/Det.4 25 & 26
Status indicator IP66 lamp controlled Group
10CYE10CH254-S54
A1 104/Detc.4 27 Fire Group
Manual call point DMX3195-I yellow
10CYE10CH216-S61 Extinguishing
A1 122/Detc.1 10 & 11
Status indicator IP66 lamp controlled Group
10CYE10CH214-S51
A1 109/Detc.1 12 Fire Group
Manual call point DMX3195-I yellow
10CYE10CR211-B01
A1 106/Detc.1 14 Fire Group
Flame detector FMX5000 IR 3GD
10CYE10CT211-B01
A1 106/Detc.2 15 Fire Group
Heat detector WMX5000 3GD
10CYE10CT211-B03
A1 107/Det.1 16 Fire Group
Heat detector WMX5000 3GD
10CYE10CR211-B04
A1 107/Detc.2 17 Fire Group
Flame detector FMX5000 IR 3GD
10CYE10CQ211-S01
A1
Isolator ISX 284 3GD
10CYE10CR211-B05
A1 107/Det.1 18 Fire Group
Flame detector FMX5000 IR 3GD
10CYE10CT231-B01
A1 111/Det.1 Heat detector WMX5000 FS Flex 3GD (HTC) 19 Fire Group
260°C
10CYE10CT231-B02
A1 122/Det.2 Heat detector WMX5000 FS Flex 3GD (HTC) 20 Fire Group
280°C
10CYE10CH214-S53
A1 251/Det.2 21 Fire Group
Manual call point DMX3195-I yellow
10CYE10CH200-S05
A1 110/Det.5 22 Fire Group
Manual call point DMX3195-I red
10CYE10CH216-S63 Extinguishing
A1 122/Det.3 23 & 24
Status indicator IP66 lamp controlled Group

Page 5 von 23
PROTOCOL OF SITE ACCEPTANCE TEST
AND HANDING OVER
Input Groups Loop 2
MODULE Group FUNCTION ADDRESS OK REMARKS
10CYE10CR221-B01
A1 201/Det.1 1 Fire Group
Flame detector FMX5000 IR
10CYE10CT221-B02
A1 202/Det.2 2 Fire Group
Heat detector WMX5000
10CYE10CT221-B04
A1 202/Det.4 3 Fire Group
Heat detector WMX5000
10CYE10CH224-S51
A1 204/Det.1 4 Fire Group
Manual call point DMX3195-I yellow
10CYE10CH200-S01
A1 110/Det.1 5 Fire Group
Manual call point DMX3195-I red
10CYE10CH314-S51
A1 314/Det.1 6 Fire Group
Manual call point DMX3195-I yellow
10CYE10CH200-S07
A1 110/Det.7 7 Fire Group
Manual call point DMX3195-I red
10CYE10CR311-B01
A1 312/Det.1 8 Fire Group
Flame detector FMX5000 IR
10CYE10CT311-B02
A1 311/Det.2 9 Fire Group
Heat detector WMX5000

Input Groups Loop 3


MODULE Group FUNCTION ADDRESS OK REMARKS
10CYE10CT251-B01
A2 102/Det.1 1 Fire Group
Heat detector WMX5000
10CYE10CU251-B02
A2 101/Det.2 2 Fire Group
Optical smoke detector OMX95
10CYE10CH256-S61
A2 121/Det.1 3&4 Fire Group
Status indicator IP66 lamp controlled
10CYE10CH200-S02
A2 110/Det.1 5 Fire Group
Manual call point DMX3195-I
10CYE10CH254-S51
A2 104/Det.1 6 Fire Group
Manual call point DMX3195-I yellow
10CYE10CH254-S55
A2 104/Det.5 28 Fire Group
Manual call point DMX3195-I yellow
10CYE10CH256-S65 Extinguishing
A2 121/Det.5 29 & 30
Status indicator IP66 lamp controlled Group
10CYE10CH216-S62 Extinguishing
A2 122/Det.2 7&8
Status indicator IP66 lamp controlled Group
10CYE10CH200-S06
A2 110/Det.6 9 Fire Group
Manual call point DMX3195-I red
10CYE10CH214-S52
A2 109/Det.2 10 Fire Group
Manual call point DMX3195-I yellow
10CYE10CR211-B02
A2 107/Det.2 11 Fire Group
Flame detector FMX5000 IR 3GD
10CYE10CR211-B03
A2 106/Det.3 12 Fire Group
Flame detector FMX5000 IR 3GD
10CYE10CT211-B02
A2 108/Det.2 13 Fire Group
Heat detector WMX5000 3GD
10CYE10CT211-B04
A2 108/Det.4 14 Fire Group
Heat detector WMX5000 3GD
Page 6 von 23
PROTOCOL OF SITE ACCEPTANCE TEST
AND HANDING OVER
10CYE10CQ211-S02
A2
Isolator ISX 284 3GD
10CYE10CR211-B06
A2 107/Det.3 15 Fire Group
Flame detector FMX5000 IR 3GD
10CYE10CR211-B07
A2 106/Det.4 16 Fire Group
Flame detector FMX5000 IR 3GD
10CYE10CR211-B08
A2 107/Det.4 17 Fire Group
Flame detector FMX5000 IR 3GD
10CYE10CH214-S54
A2 109/Det.4 18 Fire Group
Manual call point DMX3195-I yellow
10CYE10CH216-S64 Extinguishing
A2 122/Det.4 19 & 20
Status indicator IP66 lamp controlled Group
10CYE10CH200-S04
A2 110/Det.4 21 Fire Group
Manual call point DMX3195-I red
10SGJ25CG011-S01 Extinguishing
A2 130/Det.1 31
CO2 LP Selector Valve Group
10SGJ25CP011 Extinguishing
A2 127/Det.1 32
Pressure Switch Group
10SGJ25CG001-S01 Extinguishing
A2 131/Det.1 33
CO2 LP Selector Valve Group
10SGJ25CP001 Extinguishing
A2 125/Det.1 34
Pressure Switch Group
10SGJ25CP002 Extinguishing
A2 125/Det.2 35
Pressure Switch Group
10SGJ21CG001-S01 Extinguishing
A2 129/Det.1 36
CO2 LP Selector Valve Group
10SGJ21CP001 Extinguishing
A2 126/Det.1 37
Pressure Switch Group
10SGJ21CP002 Extinguishing
A2 126/Det.2 38
Pressure Switch Group
10SGJ21CG011-S01 Extinguishing
A2 128/Det.1 39
CO2 LP Selector Valve Group
10SGJ21CP011 Extinguishing
A2 136/Det.1 40
Pressure Switch Group
10SGJ23CG001-S01 Extinguishing
A2 132/Det.1 41
CO2 LP Selector Valve Group
10SGJ23CP001 Extinguishing
A2 119/Det.1 42
Pressure Switch Group
10SGJ23CP002 Extinguishing
A2 119/Det.2 43
Pressure Switch Group
10SGJ29CG001-S01 Extinguishing
A2 133/Det.1 44
CO2 LP Selector Valve Group
10SGJ29CP001 Extinguishing
A2 195/Det.1 45
Pressure Switch Group
10SGJ01CG001-S01 Extinguishing
A2 135/Det.1 46
CO2 LP Selector Valve Group
10SGJ01AH001-S01 Extinguishing
A2 134/Det.1 47
Common Fault Control Panel Co2 Tank Group

10CYE10CT231-B03
A2 111/Det.2 Heat detector WMX5000 FS Flex 3GD 22 Fire Group
(HTC) 260°C

10CYE10CT231-B04
A2 113/Det.1 Heat detector WMX5000 FS Flex 3GD 23 Fire Group
(HTC) 280°C

Page 7 von 23
PROTOCOL OF SITE ACCEPTANCE TEST
AND HANDING OVER
10CYE10CH214-S55
A2 109/Det.5 24 Fire Group
Manual call point DMX3195-I yellow
10CYE10CH216-S65 Extinguishing
A2 122/Det.5 25 &26
Status indicator IP66 lamp controlled Group

Input Groups Loop 4


MODULE Group FUNCTION ADDRESS OK REMARKS
10CYE10CT221-B01
A2 202/Det.1 1 Fire Group
Heat detector WMX5000
10CYE10CT291-B01
A2 141/Det.1 2 Fire Group
Heat detector WMX5000 3GD
10CYE10CH294-S51
A2 144/Det.1 3 Fire Group
Manual call point DMX3195-I yellow
10CYE10CT221-B03
A2 202/Det.2 4 Fire Group
Heat detector WMX5000
10CYE10CR221-B02
A2 201/Det.2 5 Fire Group
Flame detector FMX5000 IR
10SGC22CP001 Extinguishing
A2 223/Det.1 6
Pressure Switch Group
10SGC22CP002 Extinguishing
A2 223/Det.2 7
Pressure Switch Group
10SGK31CP001 Extinguishing
A2 315/Det.1 8
Pressure Switch Group
10SGK31CP002 Extinguishing
A2 315/Det.2 9
Pressure Switch Group
10SGK31CP010 Extinguishing
A2 316/Det.1 10
Pressure Switch Group
10CYE10CT311-B01 Heat detector WMX5000
A2 311/Det.1 11 Fire Group

Input Groups Loop 5


MODULE Group FUNCTION ADDRESS OK REMARKS
10CYE10CU112-B01 Optical smoke detector
A3 512/Det.1 1 Fire Group
OMX95
10CYE10CU111-B01 Optical smoke detector
A3 511/Det.1 2 Fire Group
OMX95
10CYE10CU151-B01 Optical smoke detector
A3 551/Det.1 3 Fire Group
OMX95
10CYE10CU152-B01 Optical smoke detector
A3 552/Det.1 4 Fire Group
OMX95
10CYE10CU151-B02 Optical smoke detector
A3 551/Det.2 5 Fire Group
OMX95
10CYE10CU152-B02 Optical smoke detector
A3 552/Det.2 6 Fire Group
OMX95
10CYE10CU151-B03 Optical smoke detector
A3 551/Det.3 7 Fire Group
OMX95
10CYE10CU152-B03 Optical smoke detector
A3 552/Det.3 8 Fire Group
OMX95
Page 8 von 23
PROTOCOL OF SITE ACCEPTANCE TEST
AND HANDING OVER
10CYE10CH134-S51 Manual call point
A3 534/Det.1 9 Fire Group
DMX3195-I yellow
10CYE10CU131-B01 OMX5005
A3 131/Det.1 10 Fire Group
Inside Aspirating Smoke Detector AMX5001
10CYE10CU131-B02 OMX5005
A3 132/Det.2 11 Fire Group
Inside Aspirating Smoke Detector AMX5001
A3 Fault Aspirating Smoke Detector AMX5001 12 Fire Group
10SGK16CP001 Extinguishing
A3 565/Det.1 13
Pressure Switch Group
10SGK15CP001 Extinguishing
A3 555/Det.1 14
Pressure Switch Group
10SGK13CP001 Extinguishing
A3 535/Det.1 15
Pressure Switch Group
10SGK11CP001 Extinguishing
A3 515/Det.1 16
Pressure Switch Group
10SGK16CP010 Extinguishing
A3 566/Det.1 17
Pressure Gauge Extinguishing Loss Monitoring Group
10SGK15CP010 Extinguishing
A3 556/Det.1 18
Pressure Gauge Extinguishing Loss Monitoring Group
10SGK13CP010 Extinguishing
A3 536/Det.1 19
Pressure Gauge Extinguishing Loss Monitoring Group
10SGK11CP010 Extinguishing
A3 516/Det.1 20
Pressure Gauge Extinguishing Loss Monitoring Group
10CYE10CH100-S01
A3 501/Det.1 21 Fire Group
Manual call point DMX3195-I red
10CYE10CH100-S02
A3 510/Det.1 22 Fire Group
Manual call point DMX3195-I red
10CYE10CH164-S51
A3 564/Det.1 23 Fire Group
Manual call point DMX3195-I yellow
10CYE10CH114-S51
A3 514/Det.1 24 Fire Group
Manual call point DMX3195-I yellow
10CYE10CH154-S51
A3 554/Det.1 25 Fire Group
Manual call point DMX3195-I yellow
10CYE10CU161-B01
A3 561/Det.1 26 Fire Group
Optical smoke detector OMX95
10CYE10CU162-B01
A3 562/Det.1 27 Fire Group
Optical smoke detector OMX95
10CYE10CU161-B02
A3 561/Det.2 28 Fire Group
Optical smoke detector OMX95
10CYE10CU162-B02
A3 562/Det.2 29 Fire Group
Optical smoke detector OMX95
10CYE10CU112-B02
A3 512/Det.2 30 Fire Group
Optical smoke detector OMX95
10CYE10CU111-B02
A3 511/Det.2 31 Fire Group
Optical smoke detector OMX95
10CYE10CT008-B01
A3 508/Det.1 32 Fire Group
Sensor cable Proline TH, violet

Page 9 von 23
PROTOCOL OF SITE ACCEPTANCE TEST
AND HANDING OVER
Monitoring Output
MODULE Group FUNCTION TERMINAL OK REMARKS
10CYE10EH021-E61
A10 51/Unit.1 X1:1 / 2
Flash light CWB ATEX MX 24V DC red
10CYE10EH021-E62
A10 51/Unit.2 X1:1 / 2
Flash light CWB ATEX MX 24V DC red
10CYE10EH021-E63
A10 51/Unit.3 X1:1 / 2
Flash light CWB ATEX MX 24V DC red
10CYE10EH021-E64
A11 52/Unit.1 X1:1 / 2
Flash light CWB ATEX MX 24V DC red
10CYE10EH021-E65
A11 52/Unit.2 X1:1 / 2
Flash light CWB ATEX MX 24V DC red
10CYE10EH021-H01
A12 53/Unit.1 X1:1 / 2
Sounder DS10 MX Ex
10CYE10EH021-H02
A12 53/Unit.2 X1:1 / 2
Sounder DS10 MX Ex
10CYE10EH021-E51
Unit.1 X103-3&4
Warning light panel LWA 90-KT red
10CYE10EH021-E52
Unit.2 X103-3&4
Warning light panel LWA 90-KT red
10CYE10EH021-E53
Unit.3 X103-3&4
Warning light panel LWA 90-KT red
10CYE10EH021-E54
Unit.4 X103-3&4
Warning light panel LWA 90-KT red
10CYE10EH021-E55
Unit.5 X103-3&4
Warning light panel LWA 90-KT red
10CYE10EH020-H01
A13 54/Unit.1 X1:1 / 2
Sounder PA 5, IP 66
10CYE10EH020-H02
A13 54/Unit.2 X1:1 / 2
Sounder PA 5, IP 66
10CYE10EH025-H01
A14 55/Unit.1 X1:1 / 2
Sounder PA 5, IP 66
10CYE10EH025-E61
A14 55/Unit.2 X1:1 / 2
Flash light PY X-S-05-SSM 24V DC, red
10CYE10EH025-E51
Unit.1 X103-1&2
Warning light panel LWA 90-KT red
10CYE10EH025-E52
Unit.2 X103-1&2
Warning light panel LWA 90-KT red
10CYE10EH025-E53
Unit.3 X103-1&2
Warning light panel LWA 90-KT red
10CYE10EH025-E54
Unit.4 X103-1&2
Warning light panel LWA 90-KT red
10CYE10EH025-E55
Unit.5 X103-1&2
Warning light panel LWA 90-KT red
10CYE10EH022-H01
A15 56/Unit.1 X1:1 / 2
Sounder PA 5, IP 66 1
10CYE10EH022-E61
A15 56/Unit.2 X1:1 / 2
Flash light PY X-S-05-SSM 24V DC, red
10SGC22AA101-Y01
A16 57/Unit1 X1:1 / 2
Impulse Solenoid
10CYE10EH031-H01
A17 58/Unit1 X1:1 / 2
Sounder PA 5, IP 66
10CYE10EH031-E61
A17 58/Unit.2 X1:1 / 2
Flash light PY X-S-05-SSM 24V DC, red

Page 10 von 23
PROTOCOL OF SITE ACCEPTANCE TEST
AND HANDING OVER
10SGK31AA001-Y01
A19 59/Unit.1 X1:1 / 2
Solenoid
10CYE10EH029-E61
A10 71/Unit.1 X3:1 / 2
Flash light PY X-S-05-SSM 24V DC, red
10SGJ01AA003-Y01
A18 69/Unit.1 X2:1 / 2
Redundant Solenoid (CO2 Master Valve)
10SGJ01AA003-Y01
A19 70/Unit.1 X2:1 / 2
Redundant Solenoid (CO2 Master Valve)
10SGJ25AA013-Y01
A11 72/Unit.1 X3:1 / 2
Solenoid (Generator Enclosure)
10SGJ25AA003-Y01
A12 73/Unit.1 X3:1 / 2
Solenoid (Generator Enclosure)
10SGJ25AA004-Y01
A13 74/Unit.1 X3:1 / 2
Solenoid (Generator Enclosure)
10SGJ21AA013-Y01
A14 75/Unit.1 X3:1 / 2
Solenoid (GT Thermal Block)
10SGJ21AA003-Y01
A15 76/Unit.1 X3:1 / 2
Solenoid (GT Thermal Block)
10SGJ21AA004-Y01
A16 77/Unit.1 X3:1 / 2
Solenoid (GT Thermal Block)
10SGJ23AA003-Y01
A17 78/Unit.1 X3:1 / 2
Solenoid (GT Exhaust End Bearing)
10SGJ29AA003-Y01
A18 79/Unit.1 X3:1 / 2
Solenoid (Control Valve Block)
10SGJ29AA004-Y01
A19 80/Unit.1 X3:1 / 2
Solenoid (Control Valve Block)
10CYE10EH016-H01
A19 60/Unit.1 X1:1 / 2
Sounder PA 5, IP 66
10CYE10EH016-E61
A19 60/Unit.2 X1:1 / 2
Flash light PY X-S-05-SSM 24V DC, red
10SGK16AA001-Y01
A10 61/Unit.1 X2:1 / 2
Solenoid (Battery Module B1)
10CYE10EH015-H01
A11 62/Unit.1 X2:1 / 2
Sounder PA 5, IP 66
10CYE10EH015-E61
A11 62/Unit.2 X2:1 / 2
Flash light PY X-S-05-SSM 24V DC, red
10SGK15AA001-Y01
A12 63/Unit.1 X2:1 / 2
Solenoid (Starting Module K1)
10CYE10EH013-H01
A13 64/Unit.1 X2:1 / 2
Sounder PA 5, IP 66
10CYE10EH013-E61
A13 64/Unit.2 X2:1 / 2
Flash light PY X-S-05-SSM 24V DC, red
10SGK13AA001-Y01
A14 65/Unit.1 X2:1 / 2
Solenoid (Exitation Module E1)
A15 66/Unit.1 10CYE10EH011-H01 Sounder PA 5, IP 66 X2:1 / 2
10CYE10EH011-E61
A15 66/Unit.2 X2:1 / 2
Flash light PY X-S-05-SSM 24V DC, red
10SGK11AA001-Y01
A16 67/Unit.1 X2:1 / 2
Solenoid (Control Module A1)
10CYE10EH010-H01
A17 68/Unit.1 X2:1 / 2
Sounder PA 5, IP 66
10CYE10EH008-H01
A10 81/Unit.1 X4:1 / 2
Sounder PA 5, IP 66
10CYE10EH008-E61
A10 81/Unit.2 X4:1 / 2
Flash light PY X-S-05-SSM 24V DC, red
Page 11 von 23
PROTOCOL OF SITE ACCEPTANCE TEST
AND HANDING OVER

Gas Detection Group


LOCATION FUNCTION TERMINAL OK REMARKS
Battery Module Area 10CYQ10CQ161-B01
XGAS 1/2/3
16 Fixed gas detector Sensepoint XRL (Hydrogen)
Propane Ignition Gas 10CYQ10CQ281-B01
XGAS 5/6/7
Cabinet Area 28 Fixed gas detector Sensepoint XRL (Methane)
Fuel Gas Control 10CYQ10CQ291-B01
XGAS 9/10/11
Valve Block Area 29 Infrared gas detector Searchpoint Optima Plus
GT Thermal Block 10CYQ10CQ212-B01 Ex-infrared open path gas
XGAS 13/14/15
Exhaust Vent. Duct detector Crossduct (Short Range Methane)
GT Thermal Block 10CYQ10CQ213-B01 Ex-infrared open path gas
XGAS 17/18/19
Exhaust Vent. Duct detector Crossduct (Short Range Methane)
GT Thermal Block 10CYQ10CQ214-B01 Ex-infrared open path gas
XGAS 21/22/23
Exhaust Vent. Duct detector Crossduct (Short Range Methane)
10CYQ10CH001
Gas Turbine Building XRESET 1/2/3/4
Reset box Bartec
10CYQ10CQ200-E61
XFL :1 / 2
Flash light PY X-S-05-SSM 24V DC, blue
10CYQ10CQ200-E62
XFL :1 / 2
Flash light PY X-S-05-SSM 24V DC, blue
10CYQ10CQ200-E63
XFL :1 / 2
Flash light PY X-S-05-SSM 24V DC, blue

Page 12 von 23
PROTOCOL OF SITE ACCEPTANCE TEST
AND HANDING OVER
Minimax Relay Contact
RELAIS FUNCTION TERMINAL OK REMARKS
A20 FIRE AT STEP UP
RM8.01:X1 TRANSFORMER
CYE10 EG001, CARD 1, BIT 0
A20 FIRE AT AUXILIARY
RM8.01:X2 TRANSFORMER
CYE10 EG002, CARD 1, BIT 1
A20 FIRE AT BRUSH GEAR
RM8.01:X3 COMPARTMENT
CYE10 EG004, CARD 1, BIT 2
A20 FIRE AT
RM8.01:X4 AIR INTAKE
CYE10 EG005, CARD 1, BIT 3
A20 FIRE AT
RM8.01:X5 PULSE AIR SKID
CYE10 EG006, CARD 1, BIT 4
A20 FIRE AT
RM8.01:X6 FOGGING/ EVAP.
CYE10 EG007, CARD 1, BIT 5
A20 FIRE AT SPARE
RM8.01:X7 HIGH FOGGING
CYE10 EG008, CARD 1, BIT 6
A20 FIRE AT SPARE
RM8.01:X8 GT FIRE FIGHTING MODULE
CYE10 EG009, CARD 1, BIT 7

RELAIS FUNCTION TERMINAL OK REMARKS


A21 FIRE AT CONTROL COMP.
RM8.02:X1 LV MODULE A1
CYE10 EG011, CARD 1, BIT 8
A21 FIRE AT NOX & FUEL OIL FC
RM8.02:X2 AND TRANSFORMER MODULE
CYE10 EG012, CARD 1, BIT 9
A21 FIRE AT EXCITATION
RM8.02:X3 TRANSFORMER MODULE E1
CYE10 EG013, CARD 1, BIT 10
A21 FIRE AT EXCITATION SYSTEM
RM8.02:X4 TRANSFORMER MODULE P1
CYE10 EG014, CARD 1, BIT 11
A21 FIRE AT SSD-SES
RM8.02:X5 COMBINED UNIT MODULE K1,
CYE10 EG015, CARD 1, BIT 12
A21 FIRE AT DC-UPS AND
RM8.02:X6 BATTERY MODULE B1
CYE10 EG016, CARD 1, BIT 13
A21 FIRE AT
RM8.02:X7 GENERATOR BREAKER
CYE10 EG017, CARD 1, BIT 14
A21 FIRE AT
RM8.02:X8 ACTIVE GENO MODULE
CYE10 EG018, CARD 1, BIT 15

Page 13 von 23
PROTOCOL OF SITE ACCEPTANCE TEST
AND HANDING OVER
Minimax Relay Contact
RELAIS FUNCTION TERMINAL OK REMARKS
A22 FIRE AT
RM8.03:X1 ELECTRICAL MODULE CABLE
CELLAR
CYE10 EG019, CARD 2, BIT 0
A22 FIRE AT
RM8.03:X2 GT THERMAL BLOCK ENCLOSURE
CYE10 EG021, CARD 2, BIT 1
A22 FIRE AT
RM8.03:X3 AUXILIARY MODULE
CYE10 EG022, CARD 2, BIT 2
A22 FIRE AT
RM8.03:X4 EXHAUST END BEARING
CYE10 EG023, CARD 2, BIT 3
A22 FIRE AT GENO PRESSURITATION
RM8.03:X5 SKID
CYE10 EG024, CARD 2, BIT 4
A22 FIRE AT
RM8.03:X6 GENERATOR COMPARTMENT
CYE10 EG025, CARD 2, BIT 5
A22 FIRE AT
RM8.03:X7 SEAL OIL UNIT
CYE10 EG027, CARD 2, BIT 6
A22 FIRE AT
RM8.03:X8 IGNITION PROPAN GAS CABINET
CYE10 EG028, CARD 2, BIT 7

RELAIS FUNCTION TERMINAL OK REMARKS


A23 FIRE AT
RM8.04:X1 FUEL GAS MODULE
CYE10 EG029, CARD 2, BIT 8
A23 FIRE AT
RM8.04:X2 FUEL OIL NOX MODULE
CYE10 EG031, CARD 2, BIT 9
A23 FIRE
RM8.04:X3 AT FUEL GAS BLOCK
CYE10 EG032, CARD 2, BIT 10
A23 FIRE AT
RM8.04:X4 CLOSED COOLING WATER MODULE
CYE10 EG033, CARD 2, BIT 11
A23 FIRE AT
RM8.04:X5 OIL DRAIN PIT
CYE10 EG034, CARD 2, BIT 12
A23 FIRE AT
RM8.04:X6 EXHAUST END DIFFUSOR
COMPARTMENT
CYE10 EG035, CARD 2, BIT 13
A23 FIRE AT
RM8.04:X7 EMERGENCY DIESEL GENERATOR
CYE10 EG036, CARD 2, BIT 14
A23 FIRE AT
RM8.04:X8 OTC AREA
CYE10 EG039, CARD 2, BIT 15

Page 14 von 23
PROTOCOL OF SITE ACCEPTANCE TEST
AND HANDING OVER
Minimax Relay Contact
RELAIS FUNCTION TERMINAL OK REMARKS
A24 FIRE AT ST COMPARTMENT
RM8.05:X1 ST OIL FOUNDATION TRENCHES
CYE10 EG041, CARD 3, BIT 0
A24 FIRE AT
RM8.05:X2 ST IP/LP BEARINGS
CYE10 EG043, CARD 3, BIT 1
A24 FIRE AT
RM8.05:X3 ST HP BEARING
CYE10 EG044, CARD 3, BIT 2
A24 FIRE AT AREA
RM8.05:X4 BELOW ST OPERATING FLOOR
CYE10 EG046, CARD 3, BIT 3
A24 FIRE AT
RM8.05:X5 ST HYDRAULIC OIL UNIT
CYE10 EG047, CARD 3, BIT 4
A24 FIRE AT
RM8.05:X6 ST CABLE TRAY
CYE10 EG048, CARD 3, BIT 5
A24 GT FIRE EXTINGUISHING SYSTEM
RM8.05:X7 RELEASED
CYE10 EG050, CARD 3, BIT 6
A24 ST FIRE EXTINGUISHING SYSTEM
RM8.05:X8 RELEASED
CYE10 EG051, CARD 3, BIT 7

RELAIS FUNCTION TERMINAL OK REMARKS


A25 COMMON FAULT
RM8.06:X1 GT FIRE DETECTION SYSTEM
CYE10 EG071, CARD 3, BIT 8
A25 Fire Control Unit -
RM8.06:X2 Disabled
CYE10 EG072, CARD 3, BIT 9
A25 COMMON FAULT
RM8.06:X3 GT EXTINGUISHING SYSTEM
DISABLED
CYE10 EG073, CARD 3, BIT 10
A25 COMMON FAULT
RM8.06:X4 ST FIRE EXTINGUISHING SYSTEM
DISABLED
CYE10 EG074, CARD 3, BIT 11
A25 COMMON FAULT
RM8.06:X5 ST FIRE DETECTION
CYE10 EG075, CARD 3, BIT 12
A25 PULSE AIR COMPRESSOR SKID
RM8.06:X6 VENTILATION COMMAND OFF
CYE10 EG306, CARD 3, BIT 13
A25 FOGGING SKID/ EVAP. COOLER
RM8.06:X7 VENTILATION COMMAND OFF
CYE10 EG307, CARD 3, BIT 14
A25 HIGH FOGGING SKID
RM8.06:X8 VENTILATION COMMAND OFF
CYE10 EG308, CARD 3, BIT 15

Page 15 von 23
PROTOCOL OF SITE ACCEPTANCE TEST
AND HANDING OVER
Minimax Relay Contact
RELAIS FUNCTION TERMINAL OK REMARKS
A26 GT FIRE FIGHTING MODULE
RM8.07:X1 VENTILATION COMMAND OFF
CYE10 EG309, CARD 4, BIT 0
A26 CONTROL & LV MODULE A1
RM8.07:X2 VENTILATION COMMAND OFF
CYE10 EG311, CARD 4, BIT 1
A26 NOX & FUEL OIL FC AND TRANSFORMER
RM8.07:X3 MODULE Z1
VENTILATION COMMAND OFF
CYE10 EG312, CARD 4, BIT 2
A26 EXITATION TRANSFORMER MODULE E1
RM8.07:X4 VENTILATION COMMAND OFF
CYE10 EG313, CARD 4, BIT 3
A26 EXITATION SYSTEM TRANSFORMER
RM8.07:X5 MODULE P1 VENTILATION COMMAND OFF
CYE10 EG314, CARD 4, BIT 4
A26 SSD SES COMBI UNIT MODULE K1
RM8.07:X6 VENTILATION COMMAND OFF
CYE10 EG315, CARD 4, BIT 5
A26 DC UPS AND BATTERY MODULE B1
RM8.07:X7 VENTILATION COMMAND OFF
CYE10 EG316, CARD 4, BIT 6
A26 ACTIVE GENO MODULE
RM8.07:X8 VENTILATION COMMAND OFF
CYE10 EG318, CARD 4, BIT 7

RELAIS FUNCTION TERMINAL OK REMARKS


A27 GT THERMAL HALL RECIRC. FANS
RM8.08:X1 VENTILATION COMMAND OFF
CYE10 EG320, CARD 4, BIT 8
A27 GT THERMAL BLOCK
RM8.08:X2 VENTILATION COMMAND OFF
CYE10 EG321, CARD 4, BIT 9
A27 GT AUXILIARY MODULE
RM8.08:X3 VENTILATION COMMAND OFF
CYE10 EG322, CARD 4, BIT 10
A27 EXHAUST END BEARING
RM8.08:X4 VENTILATION COMMAND OFF
CYE10 EG323, CARD 4, BIT 11
A27 GENERATOR PRESSURIZATION SKID
RM8.08:X5 VENTILATION COMMAND OFF
CYE10 EG324, CARD 4, BIT 12
A27 GENERATOR COMPARTMENT
RM8.08:X6 VENTILATION COMMAND OFF
CYE10 EG325, CARD 4, BIT 13
A27 FUEL GAS MODULE
RM8.08:X7 VENTILATION COMMAND OFF
CYE10 EG329, CARD 4, BIT 14
A27 FUEL OIL NOX WATER
RM8.08:X8 MODULE
VENTILATION COMMAND OFF
CYE10 EG331, CARD 4, BIT 15

Page 16 von 23
PROTOCOL OF SITE ACCEPTANCE TEST
AND HANDING OVER
Minimax Relay Contact
RELAIS FUNCTION TERMINAL OK REMARKS
A28 CLOSED COOLING WATER MODULE
RM8.09:X1 VENTILATION COMMAND OFF
CYE10 EG333, CARD 5, BIT 0
A28 EXHAUST END DIFFUSOR
RM8.09:X2 VENTILATION COMMAND OFF
CYE10 EG335, CARD 5, BIT 1
A28 FIRE - STAND BY DIESEL GENERATOR -
RM8.09:X3 VENTILATION COMMAND OFF
CYE10 EG336, CARD 5, BIT 2
A28 GT THERMAL BLOCK
RM8.09:X4 VENTILATION COMMAND ON
CYE10 EG421, CARD 5, BIT 3
A28 GENO COMPARTMENT
RM8.09:X5 VENTILATION COMMAND ON
CYE10 EG425, CARD 5, BIT 4
A28 H2 SEAL OIL UNIT
RM8.09:X6 VENTILATION COMMAND ON
CYE10 EG427, CARD 5, BIT 5
A28 FUEL GAS MODULE
RM8.09:X7 VENTILATION COMMAND ON
CYE10 EG429, CARD 5, BIT 6
A28 SPARE
RM8.09:X8 CARD 5, BIT 7

RELAIS FUNCTION TERMINAL OK REMARKS


A30 GT LOAD SHEDDING TRIP X10:3
RM8.11:X1 CYE10 EG061 X10:4
K02
A30 GT TRIP CHANNEL 1 X10:9
RM8.11:X2 CYE10 EG091 X10:10
K05
A30 SPARE
RM8.11:X3
K01
A30 COMMON GT FIREALARM X10:1
RM8.11:X4 CYE10 EG070 X10:2

A30 SPARE
RM8.11:X5

A30 SPARE
RM8.11:X6

A30 SPARE
RM8.11:X7

A30 SPARE
RM8.11:X8

Page 17 von 23
PROTOCOL OF SITE ACCEPTANCE TEST
AND HANDING OVER
Minimax Relay Contact
RELAIS FUNCTION TERMINAL OK REMARKS
A31 GT LOAD SHEDDING TRIP X10:5
RM8.12:X1 CYE10 EG062 X10:6
K03
A31 GT TRIP CHANNEL 2 X10:11
RM8.12:X2 CYE10 EG092 X10:12
K06
A31 SPARE
RM8.12:X3

A31 SPARE
RM8.12:X4

A31 SPARE
RM8.12:X5

A31 SPARE
RM8.12:X6

A31 SPARE
RM8.12:X7

A31 SPARE
RM8.12:X8

RELAIS FUNCTION TERMINAL OK REMARKS


A32 GT LOAD SHEDDING TRIP X10:7
RM8.13:X1 CYE10 EG063 X10:8
K04
A32 GT TRIP CHANNEL 3 X10:13
RM8.13:X2 CYE10 EG093 X10:14
K07
A32 SPARE
RM8.13:X3

A32 GAS DETECTION SYSTEM F101:2


RM8.13:X4 SWITCHING OFF X110:5
K100
A32 GT GENERATOR X103:1
RM8.13:X5 "DO NOT ENTER"PANEL CO2 ALARM X103:2
K33
A32 GT THERMAL BLOCK X103:3
RM8.13:X6 "DO NOT ENTER" PANEL CO2 ALARM X103:4
K34
A32 SPARE
RM8.13:X7

A32 SPARE
RM8.13:X8

Page 18 von 23
PROTOCOL OF SITE ACCEPTANCE TEST
AND HANDING OVER
Minimax Relay Contact
RELAIS FUNCTION TERMINAL OK REMARKS
A33 GT FIRE FIGHTING MODULE X35:1
RM8.14:X1 VENTILATION COMMAND OFF X35:1
CYE10 EG309, CARD 4, BIT 0
A33 CONTROL & LV MODULE A1 X35:3
RM8.14:X2 VENTILATION COMMAND OFF X35:4
K15 CYE10 EG311, CARD 4, BIT 1
A33 NOX & FUEL OIL FC AND TRANSFORMER X35:5
RM8.14:X3 MODULE Z1 VENTILATION COMMAND OFF X35:6
CYE10 EG312, CARD 4, BIT 2
A33 EXITATION TRANSFORMER MODULE E1 X35:7
RM8.14:X4 VENTILATION COMMAND OFF X35:8
K16 CYE10 EG313, CARD 4, BIT 3
A33 EXITATION SYSTEM TRANSFORMER X35:9
RM8.14:X5 MODULE P1 VENTILATION COMMAND OFF X35:10
CYE10 EG314, CARD 4, BIT 4
A33 SSD SES COMBI UNIT MODULE K1 X35:11
RM8.14:X6 VENTILATION COMMAND OFF X35:12
K17 CYE10 EG315, CARD 4, BIT 5
A33 DC UPS AND BATTERY MODULE B1 X35:13
RM8.14:X7 VENTILATION COMMAND OFF X35:14
K18 CYE10 EG316, CARD 4, BIT 6
A33 ACTIVE GENO MODULE X35:15
RM8.14:X8 VENTILATION COMMAND OFF X35:16
CYE10 EG318, CARD 4, BIT 7

RELAIS FUNCTION TERMINAL OK REMARKS


A34 GT THERMAL HALL RECIRC. FANS X35:19
RM8.15:X1 VENTILATION COMMAND OFF X35:20
CYE10 EG320, CARD 4, BIT 8
A34 GT THERMAL BLOCK X30:7
RM8.15:X2 VENTILATION COMMAND OFF X30:8
K08 CYE10 EG321, CARD 4, BIT 9
A34 GT AUXILIARY MODULE X30:9
RM8.15:X3 VENTILATION COMMAND OFF X30:10
K09 CYE10 EG322, CARD 4, BIT 10
A34 EXHAUST END BEARING X30:11
RM8.15:X4 VENTILATION COMMAND OFF X30:12
K10 CYE10 EG323, CARD 4, BIT 11
A34 GENERATOR PRESSURIZATION SKID X30:13
RM8.15:X5 VENTILATION COMMAND OFF X30:14
CYE10 EG324, CARD 4, BIT 12
A34 GENERATOR COMPARTMENT X30:15
RM8.15:X6 VENTILATION COMMAND OFF X30:16
K11 CYE10 EG325, CARD 4, BIT 13
A34 FUEL GAS MODULE X30:17
RM8.15:X7 VENTILATION COMMAND OFF X30:18
CYE10 EG329, CARD 4, BIT 14
A34 FUEL OIL NOX WATER MODULE X30:19
RM8.15:X8 VENTILATION COMMAND OFF X30:20
K12 CYE10 EG331, CARD 4, BIT 15

Page 19 von 23
PROTOCOL OF SITE ACCEPTANCE TEST
AND HANDING OVER
Minimax Relay Contact
RELAIS FUNCTION TERMINAL OK REMARKS
A35 CLOSED COOLING WATER MODULE X30:21
RM8.16:X1 VENTILATION COMMAND OFF X30:22
CYE10 EG333
A35 EXHAUST END DIFFUSOR X30:23
RM8.16:X2 VENTILATION COMMAND OFF X30:24
K13 CYE10 EG335
A35 FIRE - STAND BY DIESEL GENERATOR - X35:21
RM8.16:X3 VENTILATION COMMAND OFF X35:22
K19 CYE10 EG336
A35 GT THERMAL BLOCK X30:27
RM8.16:X4 VENTILATION COMMAND ON X30:28
K14 CYQ10 EG421
A35 SPARE
RM8.16:X5

A35 SPARE
RM8.16:X6

A35 SPARE
RM8.16:X7

A35 SPARE
RM8.16:X8

RELAIS FUNCTION TERMINAL OK REMARKS


A36 GT FIRE EXTINGUISHING SYSTEM X80:1
RM8.17:X1 RELEASED X80:2
K21 CYE10 EG150
A36 GT FIRE EXTINGUISHING SYSTEM X80:3
RM8.17:X2 SYSTEM DISABLED X80:4
K22 CYE10 EG160
A36 GT FIRE & GAS DETECTION SYSTEM X80:5
RM8.17:X3 GT COMMON FIRE ALARM X80:6
K23 CYE10 EG170
A36 GT FIRE DETECTION FIRE IN GAS TURBINE X80:7
RM8.17:X4 / GENERATOR ENCLOSURE X80:8
K24 CYE10 EG171
A36 GT FIRE DETECTION X80:9
RM8.17:X5 FIRE AT GT AUXILIARIES X80:10
K25 CYE10 EG172
A36 GT FIRE DETECTION X80:11
RM8.17:X6 FIRE - FUEL OIL NOX WATER MODULE X80:12
K26 CYE10 EG173
A36 GT FIRE DETECTION X80:13
RM8.17:X7 FIRE IN ELECTRICAL MODULES X80:14
K27 CYE10 EG174
A36 FIRE PROTECTION & GAS DETECTION X80:15
RM8.17:X8 SYSTEM COMMON FAULT X80:16
K28 CYE10 EG180
Minimax Relay Contact

Page 20 von 23
PROTOCOL OF SITE ACCEPTANCE TEST
AND HANDING OVER
RELAIS FUNCTION TERMINAL OK REMARKS
A37 GT FIRE & GAS DETECTION SYSTEM X80:17
RM8.16:X1 PANEL DISABLED X80:18
K29 CYE10 EG181
A37 COMMON SIGNAL X80:19
RM8.16:X2 SPARE X80:20
K30 CYE10 EG190
A37 COMMON SIGNAL X80:21
RM8.16:X3 SPARE X80:22
K31 CYE10 EG191
A37 COMMON SIGNAL X80:23
RM8.16:X4 SPARE X80:24
K32 CYE10 EG192
A37 SPARE
RM8.16:X5

A37 SPARE
RM8.16:X6

A37 SPARE
RM8.16:X7

A37 SPARE
RM8.16:X8

C3) External Alarms and Actuators:

Clean and carry out tests on all visual alarms (flashing lamps, rotating
beacons, notice-boards) [ _____]
In the case of monitored alarms, carry out wire break and short-circuit by
disconnecting or jumpering the line [ _____]
Clean and carry out tests on all audible alarms (hooters, sirens).
In the case of monitored alarms, carry out wire break and short-circuit by
disconnecting or jumpering the line [ _____]
Clean and carry out tests on all indicator devices outside the Fire Panel
(annunciators, parallel indicators) [ _____]
In the case of monitored alarms, carry out wire break and short-circuit by
disconnecting or jumpering the line [ _____]
Check the proper functioning of actuators outside the Fire Panel (e. .g key-
operated switches) [ _____]
Check the proper functioning of indicator devices outside the Fire Panel
(annunciators, parallel indicators) [ _____]
Check the proper functioning of all audible alarms [ _____]
Check the proper functioning of all visual alarms [ _____]

Page 21 von 23
PROTOCOL OF SITE ACCEPTANCE TEST
AND HANDING OVER

E) Commissioning Punchlist

Erection
ITEM KIND OF DEFECTS Company
Minimax GE

1   

2   

3   

4   

5   

6   

7   

8   

9   

10   

11   

12   

SIGNATURES DEFECT LIST


Name Company Position Date Signature
Client
Approval
Contractor
Approval
Subcontractor
Approval

Page 22 von 23
PROTOCOL OF SITE ACCEPTANCE TEST
AND HANDING OVER

Remarks:

Date: 31/10/2019
Name of the Service Technician:

Wan Mohd Zahiruddin


MX Fire Solutions GE Power Solutions ( Malaysia) Sdn Bhd
Minimax Branch Office

----------------------------------------------- ---------------------------------------------------
Signature Signature
Service Technician Execution of the work confirmed

Page 23 von 23