Construction Details
Table of contents
Evolution
Construction Details
02
Table of contents
Evolution
Construction Details
03
401-402
611 701
111
612
601-602
603/604 702
501-503
04
Phase II Phase I
Expected length: Corner length:
Phase 1 - Panel length: 4500 mm 110 cm 110 cm
joint dim. joint dim.
A6 A10 AB3
A7 A9 AB2
A3 A2 AB1
A3 A2 AB1
A6 AB3
A6 AB3
A3 A4 AB2
A3 A2 AB1
A1 A8 AB1
05
Reveal 0 mm Reveal 0 mm Reveal 0 mm
Backing tray
IPN core
D
80/100/120/150
Reveal 10/20/50 mm
M 600/900/1000
Factory
applied D
gasket 80/100/120/150 0 100mm
06
Cut end
D
22
Load Spreader
Usage depends on statical calculation.
M
M
Reveal 0
Reveal 10/20/50
M
0 100mm
Project: General Construction Details
Kingspan Facades Europe
System: Evolution
08
Kingspan Evolution
Horizontally laid panel
Thickness to meet U value
Load spreader
M
Substructure
by others
0 100mm
This construction detail merely represents a potential example of
execution. Kingspan can not be held liable or responsible for its Project: General Construction Details
proper application, transferability and adaptation to local and structural Kingspan Facades Europe
conditions on a specific building/project. This is solely the System: Evolution
responsibility of the user.
Drawing Title: Inline Black - horizontal joint
This is a generic construction detail. Supporting (secondary) steelwork
member section types and sizes are indicative only. Drawn By: MS Date: 2019.03.13
www.kingspanfacades.com
Secondary steelwork is typically provided by the structural steelwork
Drawing N.: KF-EVO-201-xxxx-04 Rev: 00 © Kingspan 2014
contractor.
09
a (min. 200 mm)
Air seal EPDM bubble gasket
b 28 b
60 x10mm VJ1
25 50 50 25
PIR canister applied insulation to fill any gaps
to maintain continuity of insulation
Air seal gun-garde sealant to male joint
19
51
Panel length (A) 28 Panel length (A)
AWP joint filler and
non setting gun grade sealant
SP 8 Aluminium top hat
SP10 EPDM push in gasket
4 mm dia sealing tape
0 100mm
This construction detail merely represents a potential example of
execution. Kingspan can not be held liable or responsible for its Project: General Construction Details
proper application, transferability and adaptation to local and structural Kingspan Facades Europe
conditions on a specific building/project. This is solely the System: Evolution
responsibility of the user.
Drawing Title: Inline Black- vertical joint
This is a generic construction detail. Supporting (secondary) steelwork Note Drawn By: BB Date: 25.09.2015
member section types and sizes are indicative only.
Secondary steelwork is typically provided by the structural steelwork
a & b - according to structural/static requirements www.kingspanfacades.com
b - min. support width, 40 mm Drawing N.: KF-EVO-202-xxxx-04 Rev: AH © Kingspan 2014
contractor.
10
Kingspan Evolution
horizontally laid panel
Thickness to meet U value
Load spreader
M
Substructure by others
0 100mm
This construction detail merely represents a potential example of
execution. Kingspan can not be held liable or responsible for its Project: General Construction Details
proper application, transferability and adaptation to local and structural Kingspan Facades Europe
conditions on a specific building/project. This is solely the System: Evolution
responsibility of the user.
Drawing Title: Inline Silver - horizontal joint
This is a generic construction detail. Supporting (secondary) steelwork
member section types and sizes are indicative only. Drawn By: BB Date: 25.09.2015
www.kingspanfacades.com
Secondary steelwork is typically provided by the structural steelwork
Drawing N.: KF-EVO-211-xxxx-04 Rev: AH © Kingspan 2014
contractor.
11
a (min. 200 mm)
Air seal EPDM bubble gasket
b 28 b
60 x10mm VJ1
25 50 50 25
PIR canister applied insulation to fill any gaps
to maintain continuity of insulation
Air seal gun-garde sealant to male joint
D
25
19
51
Panel length (A) 28 Panel length (A)
AWP joint filler and
non setting gun grade sealant
SP8 Aluminium top hat
SP9 Snap in aluminium
4 mm dia sealing tape
0 100mm
This construction detail merely represents a potential example of
execution. Kingspan can not be held liable or responsible for its Project: General Construction Details
proper application, transferability and adaptation to local and structural Kingspan Facades Europe
conditions on a specific building/project. This is solely the System: Evolution
responsibility of the user.
Note Drawing Title: Inline Silver - vertical jiont
This is a generic construction detail. Supporting (secondary) steelwork a & b - according to structural/static requirements Drawn By: BB Date: 25.09.2015
member section types and sizes are indicative only. a min = 2 x b + 28 www.kingspanfacades.com
Secondary steelwork is typically provided by the structural steelwork
contractor. b - min. support width, 40 mm Drawing N.: KF-EVO-222-xxxx-04 Rev: AH © Kingspan 2014
12
Line of the Q2 EPDM gasket
Kingspan Evolution
horizontally laid panel
Thickness to meet U value
Load spreader
M
Substructure by others
0 100mm
This construction detail merely represents a potential example of
execution. Kingspan can not be held liable or responsible for its Project: General Construction Details
proper application, transferability and adaptation to local and structural Kingspan Facades Europe
conditions on a specific building/project. This is solely the System: Evolution
responsibility of the user.
Drawing Title: Q2 Horizontal joint Reveal 0
This is a generic construction detail. Supporting (secondary) steelwork
member section types and sizes are indicative only. Drawn By: BB Date: 21.12.2017
www.kingspanfacades.com
Secondary steelwork is typically provided by the structural steelwork
Drawing N.: BEVOC-231-xxxx-04 Rev: AH © Kingspan 2014
contractor.
15
Line of the Q2 EPDM gasket
Kingspan Evolution
horizontally laid panel
Thickness to meet U value
Load spreader
M
Substructure by others
0 100mm
This construction detail merely represents a potential example of
execution. Kingspan can not be held liable or responsible for its Project: General Construction Details
proper application, transferability and adaptation to local and structural Kingspan Facades Europe
conditions on a specific building/project. This is solely the System: Evolution
responsibility of the user.
Drawing Title: Q2 Horizontal joint Reveal 10
This is a generic construction detail. Supporting (secondary) steelwork
member section types and sizes are indicative only. Drawn By: BB Date: 21.12.2017
www.kingspanfacades.com
Secondary steelwork is typically provided by the structural steelwork
Drawing N.: BEVOC-232-xxxx-04 Rev: AH © Kingspan 2014
contractor.
16
Line of the Q2 EPDM gasket
Kingspan Evolution
horizontally laid panel
Thickness to meet U value
Load spreader
M
Substructure by others
0 100mm
This construction detail merely represents a potential example of
execution. Kingspan can not be held liable or responsible for its Project: General Construction Details
proper application, transferability and adaptation to local and structural Kingspan Facades Europe
conditions on a specific building/project. This is solely the System: Evolution
responsibility of the user.
Drawing Title: Q2 Horizontal joint Reveal 20
This is a generic construction detail. Supporting (secondary) steelwork
member section types and sizes are indicative only. Drawn By: BB Date: 21.12.2017
www.kingspanfacades.com
Secondary steelwork is typically provided by the structural steelwork
Drawing N.: BEVOC-233-xxxx-04 Rev: AH © Kingspan 2014
contractor.
17
Line of the Q2 EPDM gasket
Kingspan Evolution
horizontally laid panel
Thickness to meet U value
Load spreader
M
Substructure by others
0 100mm
This construction detail merely represents a potential example of
execution. Kingspan can not be held liable or responsible for its Project: General Construction Details
proper application, transferability and adaptation to local and structural Kingspan Facades Europe
conditions on a specific building/project. This is solely the System: Evolution
responsibility of the user.
Drawing Title: Q2 Horizontal joint Reveal 50
This is a generic construction detail. Supporting (secondary) steelwork
member section types and sizes are indicative only. Drawn By: BB Date: 21.12.2017
www.kingspanfacades.com
Secondary steelwork is typically provided by the structural steelwork
Drawing N.: BEVOC-234-xxxx-04 Rev: AH © Kingspan 2014
contractor.
18
a (min. 190/200 mm) Air seal EPDM bubble gasket 95 x 10 mm VJ2
25 50 50 25
PIR board
site applied indulation
b 20 20 b
Air seal gun-grade sealant to male joint
D
Panel lenght A Panel lenght A
10/20
Q2 EPDM gasket
Push-in EPDM Gasket
for 10 mm joint
0 100mm
This construction detail merely represents a potential example of
execution. Kingspan can not be held liable or responsible for its Project: General Construction Details
proper application, transferability and adaptation to local and structural Kingspan Facades Europe
conditions on a specific building/project. This is solely the System: Evolution
responsibility of the user.
Note Drawing Title: Q2 Vertical joint
This is a generic construction detail. Supporting (secondary) steelwork a & b - according to structural/static requirements
member section types and sizes are indicative only. 50 Drawn By: BB Date: 21.12.2017
a min = 2 x b + 60 www.kingspanfacades.com
Secondary steelwork is typically provided by the structural steelwork
contractor. b - min. support width, 40 mm Drawing N.: BEVOC-235-xxxx-04 Rev: AH © Kingspan 2014
19
a (min. 190/200 mm) Air seal EPDM bubble gasket 95 x 10 mm VJ2
25 50 50 25
PIR board
site applied indulation
b 20 20 b
Air seal gun-grade sealant to male joint
Panel lenght A Panel lenght A
10/20
Q2 EPDM gasket
Factory applied reveal adapter
to maintain continuity
of air- and watertightness,
exept for reveal 0
Push-in EPDM Gasket
for 10 mm joint
0 100mm
This construction detail merely represents a potential example of
execution. Kingspan can not be held liable or responsible for its Project: General Construction Details
proper application, transferability and adaptation to local and structural Kingspan Facades Europe
conditions on a specific building/project. This is solely the System: Evolution
responsibility of the user.
Note Drawing Title: Q2 Vertical joint with reveal adapter
This is a generic construction detail. Supporting (secondary) steelwork a & b - according to structural/static requirements Drawn By: BB Date: 21.12.2017
member section types and sizes are indicative only. a min = 2 x b + 50/60 www.kingspanfacades.com
Secondary steelwork is typically provided by the structural steelwork
contractor. b - min. support width, 40 mm Drawing N.: BEVOC-236-xxxx-04 Rev: AH © Kingspan 2014
20
Line of the aluminium insert
Kingspan Evolution
horizontally laid panel
Thickness to meet U value
Load spreader
M
Substructure by others
0 100mm
This construction detail merely represents a potential example of
execution. Kingspan can not be held liable or responsible for its Project: General Construction Details
proper application, transferability and adaptation to local and structural Kingspan Facades Europe
conditions on a specific building/project. This is solely the System: Evolution
responsibility of the user.
Drawing Title: Q2 Horizontal joint Reveal 0
This is a generic construction detail. Supporting (secondary) steelwork
member section types and sizes are indicative only. Drawn By: BB Date: 21.12.2017
www.kingspanfacades.com
Secondary steelwork is typically provided by the structural steelwork
Drawing N.: BEVOC-241-xxxx-04 Rev: AH © Kingspan 2014
contractor.
21
Line of the aluminium insert
Kingspan Evolution
horizontally laid panel
Thickness to meet U value
Load spreader
M
Substructure by others
0 100mm
This construction detail merely represents a potential example of
execution. Kingspan can not be held liable or responsible for its Project: General Construction Details
proper application, transferability and adaptation to local and structural Kingspan Facades Europe
conditions on a specific building/project. This is solely the System: Evolution
responsibility of the user.
Drawing Title: Q2 Horizontal joint Reveal 10
This is a generic construction detail. Supporting (secondary) steelwork
member section types and sizes are indicative only. Drawn By: BB Date: 21.12.2017
www.kingspanfacades.com
Secondary steelwork is typically provided by the structural steelwork
Drawing N.: BEVOC-242-xxxx-04 Rev: AH © Kingspan 2014
contractor.
22
Line of the aluminium insert
Kingspan Evolution
horizontally laid panel
Thickness to meet U value
Load spreader
M
Substructure by others
0 100mm
This construction detail merely represents a potential example of
execution. Kingspan can not be held liable or responsible for its Project: General Construction Details
proper application, transferability and adaptation to local and structural Kingspan Facades Europe
conditions on a specific building/project. This is solely the System: Evolution
responsibility of the user.
Drawing Title: Q2 Horizontal joint Reveal 20
This is a generic construction detail. Supporting (secondary) steelwork
member section types and sizes are indicative only. Drawn By: BB Date: 2015-09-25
www.kingspanfacades.com
Secondary steelwork is typically provided by the structural steelwork
Drawing N.: BEVOC-243-xxxx-04 Rev: AH © Kingspan 2014
contractor.
23
Line of the aluminium insert
Kingspan Evolution
horizontally laid panel
Thickness to meet U value
Load spreader
M
Substructure by others
0 100mm
This construction detail merely represents a potential example of
execution. Kingspan can not be held liable or responsible for its Project: General Construction Details
proper application, transferability and adaptation to local and structural Kingspan Facades Europe
conditions on a specific building/project. This is solely the System: Evolution
responsibility of the user.
Drawing Title: Q2 Horizontal joint Reveal 50
This is a generic construction detail. Supporting (secondary) steelwork
member section types and sizes are indicative only. Drawn By: BB Date: 2015-09-25
www.kingspanfacades.com
Secondary steelwork is typically provided by the structural steelwork
Drawing N.: BEVOC-244-xxxx-04 Rev: AH © Kingspan 2014
contractor.
24
Air seal EPDM bubble gasket 95 x 10 mm VJ2
a (min. 200 mm) PIR board
site applied indulation
b 20 20 b
Air seal gun-grade sealant to male joint
25 50
Panel lenght A 20 Panel lenght A
Push in EPDM gasket receiver
Powder coated extruded aluminium insert
0 100mm
This construction detail merely represents a potential example of
execution. Kingspan can not be held liable or responsible for its Project: General Construction Details
proper application, transferability and adaptation to local and structural Kingspan Facades Europe
conditions on a specific building/project. This is solely the System: Evolution
responsibility of the user.
Note Drawing Title: Q2A Vertical joint
This is a generic construction detail. Supporting (secondary) steelwork a & b - according to structural/static requirements Drawn By: BB Date: 2015-09-25
member section types and sizes are indicative only. a min = 2 x b + 60 www.kingspanfacades.com
Secondary steelwork is typically provided by the structural steelwork
contractor. b - min. support width, 40 mm Drawing N.: BEVOC-245-xxxx-04 Rev: AH © Kingspan 2014
25
Air seal EPDM bubble gasket 95 x 10 mm VJ2
a (min. 200 mm) PIR board
site applied indulation
b 20 20 b
Air seal gun-grade sealant to male joint
D
25 50
Panel lenght A 20 Panel lenght A
Push in EPDM gasket receiver
Powder coated extruded aluminium insert
Factory applied reveal adapter
to maintain continuity
of air- and watertightness,
exept for reveal 0
0 100mm
This construction detail merely represents a potential example of
execution. Kingspan can not be held liable or responsible for its Project: General Construction Details
proper application, transferability and adaptation to local and structural Kingspan Facades Europe
conditions on a specific building/project. This is solely the System: Evolution
responsibility of the user.
Note Drawing Title: Q2A Vertical joint with reveal adapter
This is a generic construction detail. Supporting (secondary) steelwork a & b - according to structural/static requirements Drawn By: BB Date: 2015-09-25
member section types and sizes are indicative only. a min = 2 x b + 60 www.kingspanfacades.com
Secondary steelwork is typically provided by the structural steelwork
contractor. b - min. support width, 40 mm Drawing N.: BEVOC-246-xxxx-04 Rev: AH © Kingspan 2014
26
a (min. 60 mm)
D
Kingspan Evolution
horizontally laid panel
Thickness to meet U value
Self drilling fastener
Substructure by others
0 100mm
This construction detail merely represents a potential example of
execution. Kingspan can not be held liable or responsible for its Project: General Construction Details
proper application, transferability and adaptation to local and structural Kingspan Facades Europe
conditions on a specific building/project. This is solely the System: Evolution
responsibility of the user.
Drawing Title: Intermediate support
This is a generic construction detail. Supporting (secondary) steelwork
member section types and sizes are indicative only. Drawn By: BB Date: 21.12.2017
Note www.kingspanfacades.com
Secondary steelwork is typically provided by the structural steelwork
contractor. a - according to structural/static requirements Drawing N.: KF-EVO-251-xxxx-04 Rev: AH © Kingspan 2014
27
Primary steel structure
By others
Kingspan Evolution
Horizontally laid panel
Thickness to meet U value
Variant I
Steel structure
Kingspan Evolution
Horizontally laid panel
Thickness to meet U value
Variant II
Secondary steel structure
Kingspan Evolution
Horizontally laid panel
Thickness to meet U value
Variant III
Concrete wall
Comment
a - according to statical requirements
a min = 40 mm 0 100mm
This construction detail merely represents a potential example of
execution. Kingspan can not be held liable or responsible for its Project: General Construction Details
proper application, transferability and adaptation to local and structural Kingspan Facades Europe
conditions on a specific building/project. This is solely the System: Evolution
responsibility of the user.
Drawing Title: Primary constructions - variants
This is a generic construction detail. Supporting (secondary) steelwork
member section types and sizes are indicative only. Drawn By: BB Date: 2015-09-25
www.kingspanfacades.com
Secondary steelwork is typically provided by the structural steelwork
Drawing N.: KF-EVO-252-xxxx-04 Rev: AH © Kingspan 2014
contractor.
28
50
Substructure by others
25
Air seal
Kingspan Evolution
Lenght A
Factory applied
internal flashing
D
25 50
Lenght B
Corner Panel
Joint Option A min. A max. B min. B max. Lenght max. Angle
Inline Silver
Inline Black
250 1500 250 4500 6000 90-180
Aluframe
Light
Q2
D + 200 1500 D + 200 2500 4000 90-180
Q2A
0 100mm
29
Substructure by others
Air seal
Kingspan Evolution
Horizontally laid panel
Thickness to meet U value
Pa
ne
ll
en
gt
h
L
100
Note
R min - 4000 mm
L max - 6000 mm
a - 45 - 170°
0 100mm
30
50
Substructure by others
25
Air seal
Factory applied
internal flashing
Kingspan Evolution
Horizontally laid panel
Thickness to meet U value
B
25 50
Corner Panel C
Joint Option A B C Angle
Inline Silver
Inline Black
250 - 1500 mm 300 - 3000 mm 250 - 1500 mm 90-180
Aluframe
Light
Q2
Please contact Benchmark team
Q2A
0 100mm
31
Air seal EPDM bubble gasket 95 x 10 mm VJ2
Q2 or Q2A gasket
Panel lenght A
Substructure by others
Kingspan Evolution
20
20 b
50 25
20 Panel lenght A
0 100mm
32
Internal corner Internal corner
Reveal 0 Reveal 10, 20, 50
Panel lenght A
Cover flashing
Site applied insulation in the reveal
Compressible sealing tape P16 20x3 mm PE
Panel lenght A Air seal EPDM bubble gasket 95 x 10 mm VJ2
Q2 or Q2A vertical system
Kingspan Evolution
Horizontally laid panel
Thickness to meet U value
Substructure
by others
0 100mm
This construction detail merely represents a potential example of
execution. Kingspan can not be held liable or responsible for its Project: General Construction Details
proper application, transferability and adaptation to local and structural Kingspan Facades Europe
conditions on a specific building/project. This is solely the System: Evolution
responsibility of the user.
Drawing Title: Internal corner with gasket I
This is a generic construction detail. Supporting (secondary) steelwork
member section types and sizes are indicative only. Drawn By: BB Date: 21.12.2017
www.kingspanfacades.com
Secondary steelwork is typically provided by the structural steelwork
Drawing N.: KF-EVO-311-xxxx-04 Rev: AH © Kingspan 2014
contractor.
33
Internal corner
Reveal 0
Panel lenght A
Compressible sealing tape P16 20x3 mm PE
Internal corner flashing
Panel lenght A
Q2 or Q2A vertical system
Kingspan Evolution
Horizontally laid panel
Thickness to meet U value
Substructure
by others
0 100mm
This construction detail merely represents a potential example of
execution. Kingspan can not be held liable or responsible for its Project: General Construction Details
proper application, transferability and adaptation to local and structural Kingspan Facades Europe
conditions on a specific building/project. This is solely the System: Evolution
responsibility of the user.
Drawing Title: Internal corner with flashing
This is a generic construction detail. Supporting (secondary) steelwork
member section types and sizes are indicative only. Drawn By: BB Date: 21.12.2017
www.kingspanfacades.com
Secondary steelwork is typically provided by the structural steelwork
Drawing N.: KF-EVO-312-xxxx-04 Rev: AH © Kingspan 2014
contractor.
34
Parapet flashing
Site applied insulation
by others
Parapet support by others
Load spreader
Self drilling fastener with E16 pad
P17 20x5 mm PE compressible sealing tape
Substructure
by others
Kingspan Evolution
horizontally laid panel
Thickness to meet U value
0 100mm
This construction detail merely represents a potential example of
execution. Kingspan can not be held liable or responsible for its Project: General Construction Details
proper application, transferability and adaptation to local and structural Kingspan Facades Europe
conditions on a specific building/project. This is solely the System: Evolution
responsibility of the user.
Drawing Title: Modular parapet
This is a generic construction detail. Supporting (secondary) steelwork
member section types and sizes are indicative only. Drawn By: BB Date: 21.12.2017
www.kingspanfacades.com
Secondary steelwork is typically provided by the structural steelwork
Drawing N.: KF-EVO-401-xxxx-04 Rev: AH © Kingspan 2014
contractor.
35
Parapet flashing
Site applied insulation
by others
Parapet support by others
Self drilling fastener every 1000 mm
P17 20x5 mm PE compressible sealing tape
Substructure
by others
Kingspan Evolution
horizontally laid panel
Thickness to meet U value
0 100mm
This construction detail merely represents a potential example of
execution. Kingspan can not be held liable or responsible for its Project: General Construction Details
proper application, transferability and adaptation to local and structural Kingspan Facades Europe
conditions on a specific building/project. This is solely the System: Evolution
responsibility of the user.
Drawing Title: Nonmodular parapet
This is a generic construction detail. Supporting (secondary) steelwork
member section types and sizes are indicative only. Drawn By: BB Date: 21.12.2017
www.kingspanfacades.com
Secondary steelwork is typically provided by the structural steelwork
Drawing N.: KF-EVO-402-xxxx-04 Rev: AH © Kingspan 2014
contractor.
36
D
Substructure by others
Internal finish
to architect's design
Module M
Module M
horizontally laid panel
Thickness to meet U value
D
0 100mm
This construction detail merely represents a potential example of
execution. Kingspan can not be held liable or responsible for its Project: General Construction Details
proper application, transferability and adaptation to local and structural Kingspan Facades Europe
conditions on a specific building/project. This is solely the System: Evolution
responsibility of the user.
Drawing Title: Modular window - sill detail
This is a generic construction detail. Supporting (secondary) steelwork
member section types and sizes are indicative only. Drawn By: BB Date: 2015-09-25
www.kingspanfacades.com
Secondary steelwork is typically provided by the structural steelwork
Drawing N.: KF-EVO-603-xxxx-04 Rev: AH © Kingspan 2014
contractor.
42
Window by others
P21 10x3 mm
Butil compressible sealing tape
Jamb flashing Internal finish to architect's design
Site applied insulation Substructure by others
P17
Sill support 20x5 mm PE
compressible sealing tape
Sill flashing
Kingspan Evolution
horizontally laid panel
Thickness to meet U value
D
0 100mm
This construction detail merely represents a potential example of
execution. Kingspan can not be held liable or responsible for its Project: General Construction Details
proper application, transferability and adaptation to local and structural Kingspan Facades Europe
conditions on a specific building/project. This is solely the System: Evolution
responsibility of the user.
Drawing Title: Nonmodular window - sill detail
This is a generic construction detail. Supporting (secondary) steelwork
member section types and sizes are indicative only. Drawn By: BB Date: 2015-09-25
www.kingspanfacades.com
Secondary steelwork is typically provided by the structural steelwork
Drawing N.: KF-EVO-604-xxxx-04 Rev: AH © Kingspan 2014
contractor.
43
Internal finish to architect's design
Substructure by others
P17
20x5 mm PE
compressible sealing tape
Panel lenght
Kingspan Evolution
horizontally laid panel
Thickness to meet U value Window by others
P21 10x3 mm
AWP joint filler and Butil compressible sealing tape
non setting gun grade sealant
Site applied insulation
Jamb flashing
0 100mm
This construction detail merely represents a potential example of
execution. Kingspan can not be held liable or responsible for its Project: General Construction Details
proper application, transferability and adaptation to local and structural Kingspan Facades Europe
conditions on a specific building/project. This is solely the System: Evolution
responsibility of the user.
Drawing Title: Nonmodular window - jamb detail
This is a generic construction detail. Supporting (secondary) steelwork
member section types and sizes are indicative only. Drawn By: BB Date: 21.12.2017
www.kingspanfacades.com
Secondary steelwork is typically provided by the structural steelwork
Drawing N.: KF-EVO-605-xxxx-04 Rev: AH © Kingspan 2014
contractor.
44
D
Module M
Module M
horizontally laid panel
Thickness to meet U value
D
0 100mm
This construction detail merely represents a potential example of
execution. Kingspan can not be held liable or responsible for its Project: General Construction Details
proper application, transferability and adaptation to local and structural Kingspan Facades Europe
conditions on a specific building/project. This is solely the System: Evolution
responsibility of the user.
Drawing Title: Window sill with window adapter
This is a generic construction detail. Supporting (secondary) steelwork
member section types and sizes are indicative only. Drawn By: BB Date: 2015-09-25
www.kingspanfacades.com
Secondary steelwork is typically provided by the structural steelwork
Drawing N.: KF-EVO-612-xxxx-04 Rev: AH © Kingspan 2014
contractor.
46
Internal finish to architect's design
Substructure by others
Compressible sealing tape P17 20x5 mm PE
Site applied insulation
D
Panel lenght
Kingspan Evolution Schüco AWS 75
horizontally laid panel Window profile by others
Thickness to meet U value
Site applied insulation
AWP joint filler and
non setting gun grade sealant SP 8 Aluminium top hat
SP10 EPDM push in gasket
4 mm dia butyl sealant
0 100mm
This construction detail merely represents a potential example of
execution. Kingspan can not be held liable or responsible for its Project: General Construction Details
proper application, transferability and adaptation to local and structural Kingspan Facades Europe
conditions on a specific building/project. This is solely the System: Evolution
responsibility of the user.
Drawing Title: Window jamb with top hat profile
This is a generic construction detail. Supporting (secondary) steelwork
member section types and sizes are indicative only. Drawn By: BB Date: 21.12.2017
www.kingspanfacades.com
Secondary steelwork is typically provided by the structural steelwork
Drawing N.: KF-EVO-613-xxxx-04 Rev: AH © Kingspan 2014
contractor.
47
Internal finish to architect's design
Substructure by others
Compressible sealing tape P17 20x5 mm PE
D
Panel lenght
Kingspan Evolution Schüco AWS 75
horizontally laid panel Window profile by others
Thickness to meet U value
Site applied insulation
AWP joint filler and
non setting gun grade sealant L-profile by others
Butyl sealing tape
10x3 mm - P21
0 100mm
This construction detail merely represents a potential example of
execution. Kingspan can not be held liable or responsible for its Project: General Construction Details
proper application, transferability and adaptation to local and structural Kingspan Facades Europe
conditions on a specific building/project. This is solely the System: Evolution
responsibility of the user.
Drawing Title: Window jamb with recessed gasket
This is a generic construction detail. Supporting (secondary) steelwork
member section types and sizes are indicative only. Drawn By: BB Date: 21.12.2017
www.kingspanfacades.com
Secondary steelwork is typically provided by the structural steelwork
Drawing N.: KF-EVO-614-xxxx-04 Rev: AH © Kingspan 2014
contractor.
48
D
Substructure by others
Internal finish
to architect's design
Module M
Module M
Thickness to meet U value
D
0 100mm
This construction detail merely represents a potential example of
execution. Kingspan can not be held liable or responsible for its Project: General Construction Details
proper application, transferability and adaptation to local and structural Kingspan Facades Europe
conditions on a specific building/project. This is solely the System: Evolution
responsibility of the user.
Drawing Title: Curtain wall - sill detail
This is a generic construction detail. Supporting (secondary) steelwork
member section types and sizes are indicative only. Drawn By: BB Date: 2015-09-25
www.kingspanfacades.com
Secondary steelwork is typically provided by the structural steelwork
Drawing N.: KF-EVO-702-xxxx-04 Rev: AH © Kingspan 2014
contractor.
50
Internal finish to architect's design
Substructure by others
Compressible sealing tape P17 20x5 mm PE
Site applied insulation
PIR board
site applied indulation
Panel lenght
Kingspan Evolution Curtain wall by others
horizontally laid panel
Thickness to meet U value L-profile by others
AWP joint filler and
non setting gun grade sealant Push in EPDM gasket receiver
Powder coated extruded aluminium insert
0 100mm
This construction detail merely represents a potential example of
execution. Kingspan can not be held liable or responsible for its Project: General Construction Details
proper application, transferability and adaptation to local and structural Kingspan Facades Europe
conditions on a specific building/project. This is solely the System: Evolution
responsibility of the user.
Drawing Title: Curtain wall - jamb detail
This is a generic construction detail. Supporting (secondary) steelwork
member section types and sizes are indicative only. Drawn By: BB Date: 21.12.2017
www.kingspanfacades.com
Secondary steelwork is typically provided by the structural steelwork
Drawing N.: KF-EVO-703-xxxx-04 Rev: AH © Kingspan 2014
contractor.
51
Site applied insulation
Compressible sealing tape P17 20x5 mm PE
a (min. 60 mm)
Self adhesive sealing tape
P18 20x4 mm PU
Endwall flashing
D
Panel lenght
Benchmark Evolution
horizontally laid panel
Thickness to meet U value
AWP joint filler and
non setting gun grade sealant
0 100mm
This construction detail merely represents a potential example of
execution. Kingspan can not be held liable or responsible for its Project: General Construction Details
proper application, transferability and adaptation to local and structural Kingspan Facades Europe
conditions on a specific building/project. This is solely the System: Evolution
responsibility of the user.
Drawing Title: Endwall detail
This is a generic construction detail. Supporting (secondary) steelwork
member section types and sizes are indicative only. Drawn By: BB Date: 21.12.2017
www.kingspanfacades.com
Secondary steelwork is typically provided by the structural steelwork
Drawing N.: KF-EVO-801-xxxx-04 Rev: AH © Kingspan 2014
contractor.
52
Drip flashing K160
Substructure by others
Benchmark Evolution
Horizontally laid panel
Thickness to meet U value
P17
20x5 mm PE
Butyl sealing tape compressible sealing tape
10x3 mm - P21
0 100mm
53
Compressible sealing tape P17 20x5 mm PE
a (min. 100 mm) a (min. 100 mm)
D
25 50 50 25
Panel lenght Louvers lenght Panel lenght
Benchmark Evolution
horizontally laid panel Benchmark Design Louvre
Thickness to meet U value
Louvre frame
AWP joint filler and Butyl sealing tape
non setting gun grade sealant 10x3 mm - P21
0 100mm
This construction detail merely represents a potential example of
execution. Kingspan can not be held liable or responsible for its Project: General Construction Details
proper application, transferability and adaptation to local and structural Kingspan Facades Europe
conditions on a specific building/project. This is solely the System: Evolution
responsibility of the user.
Drawing Title: Louvre horizontal section
This is a generic construction detail. Supporting (secondary) steelwork
member section types and sizes are indicative only. Drawn By: BB Date: 21.12.2017
www.kingspanfacades.com
Secondary steelwork is typically provided by the structural steelwork
Drawing N.: KF-EVO-902-xxxx-04 Rev: AH © Kingspan 2014
contractor.
54
Closure flashing
(one or two part depending
on penetration shape) Penetration
Gun grade sealant pointing
Butyl sealing tape
10x3 mm - P21 Fire rated canister applied insulation
Benchmark Evolution
horizontally laid panel
Thickness to meet U value
Closure flashing
(one or two part depending
on penetration shape)
0 100mm
This construction detail merely represents a potential example of
execution. Kingspan can not be held liable or responsible for its Project: General Construction Details
proper application, transferability and adaptation to local and structural Kingspan Facades Europe
conditions on a specific building/project. This is solely the System: Evolution
responsibility of the user.
Drawing Title: Penetration detail
This is a generic construction detail. Supporting (secondary) steelwork Note Drawn By: BB Date: 21.12.2017
member section types and sizes are indicative only. Where the penetration size excesses 300 mm www.kingspanfacades.com
Secondary steelwork is typically provided by the structural steelwork
contractor. trimming supports must be provided. Drawing N.: KF-EVO-1001-xxxx-04 Rev: AH © Kingspan 2014
55
Structural support to bracket
Benchmark Evolution Ferrules to prevent crushing of panel
horizontally laid panel
Thickness to meet U value Support bracket
Weather seal pad to bracket
0 100mm
This construction detail merely represents a potential example of
execution. Kingspan can not be held liable or responsible for its Project: General Construction Details
proper application, transferability and adaptation to local and structural Kingspan Facades Europe
conditions on a specific building/project. This is solely the System: Evolution
responsibility of the user.
Drawing Title: Support bracket
This is a generic construction detail. Supporting (secondary) steelwork
member section types and sizes are indicative only. Drawn By: BB Date: 21.12.2017
www.kingspanfacades.com
Secondary steelwork is typically provided by the structural steelwork
Drawing N.: KF-EVO-1002-xxxx-04 Rev: AH © Kingspan 2014
contractor.
56