Professional Documents
Culture Documents
Drawing 2
Drawing 2
Drawing 2
800
52
550 125
DIMENSIONS 2200 (INCLUDES 75mm BASE FRAME & 10mm AVP) X 800 X 800 mm (H X W X D)
EXTERIOR - RAL7038 (LIGHT ARCRAFT GREY)
FINISH POWDER COAT
INTERIOR - RAL9003 (SIGNALWEIB)
BASE FRAME - BLACK
MULTICORE CABLE
MAIN & SUBSIDIARY - BLACK LETTERS
146
LABELS
GLAND AREA 567 ON A WHITE BACKGROUND
PANEL MOUNTING
160
PANEL MAIN SUPPORT -3mm (EG SHEET STEEL)
(HOLES IN BASE CHANNEL) OTHERS - 2mm (EG SHEET STEEL)
ENCLOSURE DEGREE OF IP 41
200
PROTECTION
WEIGHT 450kg (APPROXIMATE)
800
BOTTOM VIEW DOOR ACCESS FRONT
CABLE ENTRY BOTTOM
3 UNDRILLED GLAND PLATES WILL BE PROVIDED
200
GLAND PLATES
MADE OF 3mm EG SHEET STEEL MOUNTED ON
TOP OF THE BASE FRAME
ALL WIRE USED WITH IN THE PANEL SHALL BE RATED 600/1000V WITH
WIRE
PVC INSULATED STRANDED ANNEALED COPPER CONDUCTOR
158
SEPARATE SPIRALING FOR AC , DC WIRING ETC IN THE CABLE TRUNK FOR SEGREGATION.
105 590 105 WIRE SIZES FOR CT CIRCUIT- 2.5 Sq.mm
FOR VT CIRCUIT- 1.5 Sq.mm
FOR DC CIRCUIT- 1.5 Sq.mm
FOR AC CIRCUIT- 1.5 Sq.mm
FOR CONTROL CIRCUIT- 1.5 Sq.mm
REAR FOR TRIPPING CIRCUIT- 2.5 Sq.mm
FOR ANNUNCIATION CIRCUIT- 1.5 Sq.mm
FOR EARTHING CONNECTION- 2.5 Sq.mm
DOOR HANDLE PANEL DOOR LOCK HANDLE SHOULD BE WITH KEY AND PAD LOCK FACILITY.
FOLLOWING 31-TMMS-01
LABEL ALL LABELS SHALL BE FIXED WITH SMALL SCREWS FOR ALL DEVICES AND EQUIPMENT.
'F' CIRCUIT NAME & PANEL NUMBER LABELS SHOULD BE UNIFORM IN SIZE IS TEXT.
LUGS CT TERMINAL LUGS SHALL BE RING TYPE HOOK TYPE TERMINALS SHALL NOT BE ACCEPTED.
GROUNDING A COPPER GROUND BUS 150mm Sq.(30x5 Sq.mm) SHALL BE PROVIDED FOR ENTIRE LENGTH
OF THE PANEL
SPECIFICATION REFERENCE PANEL CONSTRUCTION:31TMSS-01 R1 , WIRING SPECIFICATION:CLAUSE7 OF 01TMSS-01,R2
OPTIMIZED PANEL DESIGN SCHEMATIC
OPDS-ALSTOM-007A-1
PROTECTION ENGINEERING DEPARTMENT
CLIENT NATIONAL GRID SA
CONTRACTOR NCC
PROJECT CONSTRUCTION OF NEW DHAHRAN CENTRAL 230/69kV BSP(EOA)
TITLE 230/69/13.8kV POWER TRAFO T703 HV PROTN.PANEL MAIN-1(LOD)
PANEL =7T3.A716/A717+R1
GRID
DRAWING NUMBER REV.
6306PHP047-EOA-ED-501063 0
SHEET DESCRIPTION REV SHEET DESCRIPTION REV
000 COVER SHEET 0 031B BINARY INPUT SBEF-HV 0
001 INDEX SHEET 0 032 BINARY INPUT 64-HV 0
002 ELECTRICAL SYMBOLS 0 033 LOCKOUT TRIP RELAY CIRCUIT 0
003 ELECTRICAL SYMBOLS 0 033A LOCKOUT TRIP RELAY CIRCUIT 0
004 ELECTRICAL SYMBOLS 0 034 LOCKOUT TRIP RELAY CIRCUIT & SUPERVISION 0
005 DRAWING PRINCIPLE 0 035 87T-1 PROTECTION IN/OUT SELECTION 0
006 EXTERNAL VIEW 0 036 64-HV PROTECTION IN/OUT SELECTION 0
007 CONSTRUCTIONAL DETAILS 0 037 CB A716 & CB A717 CLOSE BLOCK CKT 0
008 TECHNICAL & LABEL DETAILS 0 038 CB A716 TC-1 CIRCUIT 0
009 FRONT VIEW 0 039 CB A717 TC-1 CIRCUIT 0
010 INTERNAL VIEW 0 040 CB A716 & A717 CBF-1 INITIATION. 0
011 LIST OF APPARATUS 0 041 CB A716 & A717 CBF-2 INITIATION. 0
012 LIST OF APPARATUS 0 042 69kV SIDE CB TC-1 & CLOSE BLOCK CKT 0
013 LIST OF APPARATUS 0 043 69kV SIDE CBF-1 & 2 CIRCUIT 0
014 LIST OF APPARATUS 0 044 13.8kV CLOSE BLOCK ,CBF-1 INITI.& TC-1 CIRCUIT 0
015 LIST OF APPARATUS 0 045 SIGNALS TO AR & SET-2 PANEL 0
016 PROTECTION LOGIC DIAGRAM 0 046 SIGNALS TO FR CIRCUIT 0
017 PROTECTION LOGIC DIAGRAM 0 047 SIGNALS TO IO MODULE 0
018 PROTECTION LOGIC DIAGRAM 0 048 SPARE CONTACTS 0
019 PROTECTION LOGIC DIAGRAM 0 049 FO COMMUNICATION CIRCUIT 0
021 DC DISTRIBUTION 0 050 SAS POINT LIST 0
022 CUBICLE LIGHTING, HEATER & SOCKET 0 051 FR SIGNAL LIST 0
023 CT CIRCUIT 87T-1 (HV SIDE) 0 052 87T-1 RELAY BLOCK REFERENCE 0
024 CT CIRCUIT 87T-1 (MV SIDE) 0 053 51G-HV RELAY BLOCK REFERENCE 0
025 CT CIRCUIT 87T-1 (LV SIDE) & VT CIRCUIT 0 053A 51G-MV RELAY BLOCK REFERENCE 0
027 CT CIRCUIT 51G-HV 0 053B SBEF-HV RELAY BLOCK REFERENCE 0
027A CT CIRCUIT 51G-MV 0 054 64-HV RELAY BLOCK REFERENCE 0
028 CT CIRCUIT 64-HV 0 055 TEST BLOCK REFERENCE 0
029 BINARY INPUTS 87T-1 0 056 TERMINAL BLOCK REFERENCE 0
030 BINARY INPUTS 87T-1 0 057 TERMINAL BLOCK REFERENCE 0
031 BINARY INPUTS 51G-HV 0 058 TERMINAL BLOCK REFERENCE 0
031A BINARY INPUTS 51G-MV 0
SYMBOL CODE DESCRIPTION SYMBOL CODE DESCRIPTION SYMBOL CODE DESCRIPTION
MAKE CONTACT
F FUSE LINK H SIGNAL LAMP
MAKE CONTACT DELAYED WHEN RELEASING CONTROL OPERATED BY MOTOR T CURRENT TRANSFORMER - SINGLE LINE DIAGRAM
BREAK CONTACT DELAYED WHEN RELEASING CONTROL BY PRESSURE T CURRENT TRANSFORMER - TRIPOLAR DRAWING
* P
MAKE CONTACT WHICH OPERATES EARLIER P INDICATING INSTRUMENT - GENERAL SYMBOL VT VOLTAGE TRANSFORMER - SINGLE LINE DIAGRAM
RELATIVE TO THE ASSEMBLY OF CONTACTS
Q DISCONNECTOR (ISOLATOR)
IL ILLUMINATION LAMP HS HUMIDITY SENSOR SWITCH
SYMBOL CODE DESCRIPTION SYMBOL CODE DESCRIPTION SYMBOL CODE DESCRIPTION
2 POSITION COMBINED
DISCREPANCY SWITCH FOR DISCONNECTOR
DISCONNECTOR & EARTH SWITCH
3 POSITION COMBINED
CURRENT TRANSDUCER
DISCONNECTOR & EARTH SWITCH
+R2 +R2
006-A1 020-D1
-R2 -R2
006-A1 020-D1
476
TERMINAL BLOCK LABEL FR
13 14
WITH TERMINAL NUMBER
52CBF DWG: NO. 8602/AES/P/DWG/...
201-4A
TS1 MCTI 40 SHEET NO. 051
CT21Y 17 18 25 6 6
050-5A
CT21B 21 22 27 7 7
050-5A
CT21N 25 26 28 8 8
050-5A
E
EXTERNAL INTERCUBICLE WIRING
USING MULTICORE CABLES
NOTE:
200
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS
200
OTHERWISE SPECIFIED.
2. HAVE COUPLING LINKS TO CONNECT ADJACENT
PANELS TO FORM A CONTINUOUS EARTH BAR.
3. EARTH BAR TO BE FITTED TO REAR OF PANEL.
4. PANEL DOORS TO BE BONDED TO EARTH WITH
WIRING ACCESS 6Sq.mm BRAIDED COPPER.
AT BOTH SIDES OF CUBICLE 5. ALL EXTERNAL LABELS TO BE FIXED WITH SCREWS.
2200
2115
EARTH BAR
(SEE NOTE-3)
800
140
40
ANTI-VIBRATION PAD 50
(10mm THICKNESS)
BASE FRAME 85 BASE FRAME BASE FRAME