Airflow Discrepancies

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Different Methods Needed to Resolve

Airflow Discrepancies
William F. Arnold, III, TBE
PHI Service Agency, Inc.

Our firm was asked to help evaluate a large fan system that was previously documented
as being low on airflow. The system in question consisted of a roof-mounted fan and
30 exhaust grilles serving primarily locker rooms, showers and restrooms. The grilles
varied in design flow rates from 30 cubic feet per minute (CFM) to 1500 CFM.

T
he system was previously balanced by another firm that the original test and retest. The mechanical contractor was
reported a large discrepancy between the duct traverse informed there must still be leakage in the distribution system.
at the fan and airflow measurements at the individual
The mechanical contractor reached out to our firm as a fresh
air devices. The air devices were measured using a flow set of eyes on the project to evaluate and help troubleshoot the
hood. The test & balance (TAB) firm concluded that there airflow discrepancy.
was substantial duct leakage causing the low airflow at the
Our firm evaluated the system, starting at the fan and
grilles. The difference between the fan traverse and grilles
going throughout the duct system for signs of any obvious
was 30 percent.
problems that might be causing the airflow difference. Visual
The original duct install was sealed and pressure tested. The inspections of the duct and air device connections found them
mechanical contractor spent numerous additional manhours to be properly sealed.
re-sealing ductwork where accessible. Inaccessible ductwork The fan was tested per AABC guidelines (rotation, rotations
was sealed from the inside through access panels. After per minute, volts amps, static pressure). Once this data was
sealing was completed, the original TAB firm revisited the tabulated and compared to the fan’s performance curve it was
site to retest the system and found no difference between determined the fan was exhausting the specified amount of air.

2 TAB Journal Spring 2020


A suitable location for a duct traverse was available below the At this point, we obtained the air device performance
roof deck; the traverse indicated that the fan was exhausting submittals and measured the pressure differential across each
the required airflow. The traversed airflow was within two air device. The devices were perforated style, so we were able
percent of the data plotted on the performance curve. to insert a static tip into each device. The pressure measures
ranged from 0.03 in. w.g. to 0.10 in. w.g. After all pressures
After the fan was tested and we were confident it was were obtained and airflows calculated for the subbranch tested,
performing as intended, we measured all associated air it was determined that the air devices were delivering more air
devices using a flow hood. The results we measured were the than the flow hood indicated. It appeared that the flow hood
same as reported by the previous TAB firm. was inducing additional static on the air devices, resulting in
We utilized several flow hoods to ensure they were not the false measurements.
cause of the low flows measured. All hoods used had the The air device performance cutsheets indicated corrected
same results: low on airflow. A large majority of the ductwork areas for each size device. We utilized this information along
was located above a sheetrock ceiling, so traversing each air with a rotating vane anemometer to measure the airflow
device was not an option. We were able to locate an exposed and found the terminals were within the traversed airflow.
duct roughly two-thirds down line from the fan serving 10 air We then balanced the system utilizing the rotating vane
devices. The traverse indicated the sub-branch was slightly anemometer measurements.
above design flow, but the associated air devices were low In conclusion, several means and methods should be used to
when using a hood. determine a system’s actual flow.

TAB Journal Spring 2020 3

You might also like