WIND LOADING ANALYSIS - Main Wind-Force Resisting System

Indian code - IS 875 -PART 3 (2015)


Job Name : Transmission Tower at Deulipali-I Subject : Wind Load Calculation
Job Number : Originator: Checker:

Wind load 1st level Ht - @ -6.00m to -0.003m


Input Date :

Basic Wind Speed m/s Code Page.no


Design Wind Pressure 50 IS 875 : Class 5.2 51
K1 (Risk factor) 1.08 IS 875 : Table :1 7
K2 1.05 IS 875 : Table :2 8
k3 1 IS 875 : Class 5.3.3.1 8
k4 1.3 IS 875 8
Wind Load Calculation :
Design wind Speed (Vz) Design Wind Speed
Vz = Vb x K1 x K2 x K3 (IS 875 - Pg : 5)
Basic Wind speed (Vz) 73.71 m/s
Wind Pressure (Pz) 3259.89846 N/m^2
3.25989846 kN/m^2
Wind force = force x wind pressure x area of structure
F = Cf x pz x A
Force Coefficients
solidity ratio 0.132
Shape coefficient 1.868

Lengthof section 8.721


Height of section 6

total wind force 42.0603045 kN.m Force Coefficients

n. of nodes 8

force per node 5.258

5.29
Wind load of 5.29 on 8 nodes