1 Manufacturer Draeger

2 Model Dräger Flame 3000


3 Type Multi Channel IR Flame Detector
4 Application Flame / Fire Detection of Hydrocarbon Fires only
5 SIL N/A
GENERAL 6 Weight Aluminium 2.5 kg / 5.5 lbs.
7 Weight Stainless Steel 6 kg / 13.2 lbs.
8 Dimension 100 X 200 mm / 3.9" x 8.7"
9
10
11
12 Sensitivity 0.1 m² n-heptane fire at 60 meters (1 sq. foot fire at 200 feet)
13 Field of View Horizontal 120°, Vertical 80° (for full detection range, without reduced cone effect)
14 Electrical connection M20, M25, 1/2" NPT, 3/4” NPT, single or double entries available.
15 Hazardous area protection ATEX, IECEx & FM
16 Response time 10 - 30 seconds, configurable
17 Output Signals
18 Analog Catastrophic Failure 0 mA
19 Analog Optical Fault 2 mA
20 Analog Healthy condition 4 mA
21 Analog Alarm 18 mA
22 Analog Over range 21 mA (factory configurable for latching/non-latching alarm)
23 Relay 2 Relays for Fault & Alarm Ratings 125 VAC, 0.5 A; 30 VDC, 2A
DETECTOR 24 Ambient Conditions: Temperature -60°C to +85°C / -76°F to +185°F
25 Ambient Conditions: Pressure 915 to 1055 hPa / 27.9 to 31.2 inch of Hg
26 Ambient Conditions: Humidity 0 to 90 %RH, non condensing
27 Power Supply 18 to 32 VDC
28 Power consumption 6W (250mA at 24 VDC)
29 Housing environmental protection IP 66 / NEMA 4X
30 Housing material Aluminium Alloy Grade HE30 or Stainless Steel grade 316. Epoxy coated.
31 Automatic fault diagnostic feature Yes
32 Cabling 3 wire 0-20 mA
33 Cabling 4 wire Relays for NFPA fire panel (Fire and Fault alarm)
34
35
36
37 Detector Part No. Dräger Flame 3000 1 x M20 Cable Entry Aluminium 42 09 462
38 Detector Part No. Dräger Flame 3000 2 x M20 Cable Entry Aluminium 42 09 463
39 Detector Part No. Dräger Flame 3000 1 x M25 Cable Entry Aluminium 42 09 460
40 Detector Part No. Dräger Flame 3000 2 x M25 Cable Entry Aluminium 42 09 461
41 Detector Part No. Dräger Flame 3000 1 x 3/4NPT Cable Entry Aluminium 42 09 464
42 Detector Part No. Dräger Flame 3000 2 x 3/4NPT Cable Entry Aluminium 42 09 465
43 Detector Part No. Dräger Flame 3000 2 x 1/2NPT Cable Entry Aluminium 42 09 467
44 Detector Part No. Dräger Flame 3000 1 x 1/2NPT Cable Entry Aluminium 42 09 476
45 Detector Part No. Dräger Flame 3000 1 x M20 Cable Entry Stainless Steel 42 09 470
ORDERING INFO 46 Detector Part No. Dräger Flame 3000 2 x M20 Cable Entry Stainless Steel 42 09 471
47 Detector Part No. Dräger Flame 3000 1 x M25 Cable Entry Stainless Steel 42 09 468
48 Detector Part No. Dräger Flame 3000 2 x M25 Cable Entry Stainless Steel 42 09 469
49 Detector Part No. Dräger Flame 3000 1 x 3/4NPT Cable Entry Stainless Steel 42 09 477
50 Detector Part No. Dräger Flame 3000 2 x 3/4NPT Cable Entry Stainless Steel 42 09 478
51 Detector Part No. Dräger Flame 3000 1 x 1/2NPT Cable Entry Stainless Steel 42 09 474
52 Detector Part No. Dräger Flame 3000 2 x 1/2NPT Cable Entry Stainless Steel 42 09 475
53
54
55
56 Test tool Part No. Dräger Flame Simulator Test Torch 42 09 307
57
ACCESSORIES
58
59
60 Approvals - FM performance FM 3260
61 Approvals ATEX: II 2G EEx d IIC T4
62 Approvals IECEx: Ex d IIC T4
63 Approvals - FM area Class I, Zone 1, Aex/Exd d IIC, T4 ambient: -60 °C to +85 °C
APPROVALS
64 Approvals - FM area Class I Zone 1 AEx/Ex d IIC T4, ambient: -60 °C to +85 °C