REPUBLIC OF THE PHILIPPINES

DPWH
SCHEDULE OF EQUIPMENT ILOILO CITY

AIR COOLED CONDENSING UNIT


NOMINAL COMPRESSOR DATA CONDENSING UNIT
GENERAL NOTES : AREA COOLING
QTY. UNIT CAPACITY ELEC CHARACTERISTICS NO. OF ELEC CHARACTERISTICS
1. ALL MECHANICAL WORKS SHALL BE DONE IN ACCORDANCE WITH THE LATEST REQUIREMENTS OF THE DESIGNATION SERVE KW
PHILIPPINE BUILDING CODE REGULATIONS. WINDOW TYPE A/C NO. INPUT PROFELLER
TR HP BTU/HR VOLTS PHASE CYCLE OF FANS VOLTS PHASE CYCLE
2. AIR CONDITIONED SPACE IS DESIGNED AT 22°C ± 1° WITH 55% ± 5% RH.

AS SHOWN 5.0 60,000 1 6.09 220 1 60 1 220 1 60 BUILDING OFFICIAL


3. INSTALL ALL EQUIPMENT IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. IN CASE OF 6 ACCU - 1
SUBSTITUTION OF EQUIPMENT, SUBMIT BROCHURES, LITERATURES TO THE ARCHITECT FOR APPROVAL.
ELASTOMERIC PIPE INSTALLATION REFRIGERANT PIPE
ACCU - 2 AS SHOWN 3.0 36,000 1 4.02 220 1 60 1 220 1 60
4. ALL EQUIPMENT HANGERS SHALL BE PROVIDED WITH VIBRATION ISOLATOR. 18
5. ALL EXHAUST DUCTWORKS SHALL BE FABRICATED & INSTALLED AS PER THE LATEST EDITION OF 1 220 1 60
65 ACCU - 3 AS SHOWN 2.5 24,000 1 2.7 220 1 60
SMACNA STANDARD & ASHRAE GUIDE.
6. ALL EXHAUST DUCT AND FRESH AIR DUCT SHALL BE GALVANIZED IRON SHEETS.
18 ACCU - 4 AS SHOWN 2.0 18,000 1 1.78 220 1 60 1 220 1 60
7. FLEXIBLE DUCT SHALL BE PROVIDED TO CONNECT FRESH AIR DUCT TO FRESH AIR BLOWER AND
EXHAUST DUCT TO EXHAUST BLOWER.
21 ACCU - 5 AS SHOWN 1.5 12,986 1 1.3 220 1 60 1 220 1 60
8. PROVIDE SPLITTER DAMPER AND COLLAR FOR EVERY BRANCH DUCT.
DRAIN LINE
ANGLE BAR FOR SUPPORT
9. ALL EXHAUST AND FRESH AIR DUCT SHALL BE SLIP JOINT IN CONNECTION. 18 ACCU - 6 AS SHOWN 1.0 9,000 1 0.99 220 1 60 1 220 1 60
CONCRETE
10. USE 100MM PVC SERIES 1000 FOR ALL T&B EXHAUST.
11. DETAILED DRAWINGS ONLY INDICATED DIMENSION & METHODS AND ARE NOT DRAWN TO SCALE. PVC PIPE SLEEVE MECHANICAL
12. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE INDICATED.
FAN COIL UNIT
13. REFRIGERANT PIPES INSULATION SHALL BE 12MM THICK PRE FORMED THERMAL
COIL DATA MOTOR DATA
ELASTOMERIC CLOSED CELL INSULATION. NOMINAL
UNIT
14. ALL REFRIGERANT PIPES SHALL BE HARD DRAWN TYPE L. PIPE SLEEVE DETAIL QTY
DESIGNATION
TYPE CAPACITY
NO. OF NO. OF ROWS FINS/INCH
ELEC CHARACTERISTICS
15. ALL MATERIALS SHALL BE CLEAN AND NEW. CKT MIN. MIN. DRIVE
TR HP BTU/HR VOLTS PHASE CYCLE
16. ALL WORKS SHALL CONFORM WITH EXISTING MALL REGULATIONS AND GUIDELINES.

6 FCU - 1 FLOOR MOUNTED 5.0 60,000 1 4 12 DIRECT 220 1 60


TYPICAL WINDOW TYPE A/C INSTALLATION DETAIL
18 FCU - 2 FLOOR MOUNTED 3.0 36,000 1 4 12 DIRECT 220 1 60

65 FCU - 3 WALL MOUNTED 2.5 24,000 1 4 12 DIRECT 220 1 60

18 FCU - 4 WALL MOUNTED 2.0 18,000 1 4 12 DIRECT 220 1 60

21 FCU - 5 WALL MOUNTED 1.5 12,986 1 4 12 DIRECT 220 1 60


AIR COOLED CONDENSING UNIT

18 FCU - 6 WALL MOUNTED 1.0 9,000 1 4 12 DIRECT 220 1 60

SUCTION LINE
12 mm THICK PRE-FORMED
THERMAL ELASTOMERIC
WINDOW TYPE AIRCONDITIONING UNIT
CLOSED CELL INSULATION
KW COIL DATA MOTOR DATA
LIQUID LINE NOMINAL
UNIT CAPACITY INPUT
QTY TYPE ELEC CHARACTERISTICS
DESIGNATION NO. OF NO. OF ROWS FINS/INCH
AIR COOLED CONDENSING UNIT DRIVE
CKT MIN. MIN.
HP BTU/HR WATTS VOLTS PHASE CYCLE

60 ACU- 1 WINDOW TYPE 2.0 18,000 1,792 1 4 12 DIRECT 220 1 60


SUCTION LINE

LIQUID LINE 3 ACU- 2 WINDOW TYPE 1.0 9,000 900 1 4 12 DIRECT 220 1 60

REF. PIPE

PIPE INSULATION DETAIL


FAN COIL UNIT

VENTILATION EQUIPMENT
FAN COIL UNIT
MOTOR DATA
UNIT TOTAL STATIC
QTY TYPE CAPACITY, CFM ELEC CHARACTERISTICS
DESIGNATION PRESSURE, IN. OF WATER WATTS
STEEL SPRING RUBBER VOLTS PHASE CYCLE
& SHEAR TYPE VIBRATION
9mmØ ALL THREADED STEEL RODS 11 EAB-1 1.5 1,200 746
ISOLATOR (TYP. TO 2) TUBE-AXIAL BLOWER 220 1 60
SUPPORT FROM BLDG. STRUCTURE
LENGTH OF RODS TO SUIT SPACE
AVAILABLE (TYP. TO 2) 11 FAB-1 TUBE-AXIAL BLOWER 1.5 1,080 746 220 1 60

DRAIN LINE
ADJUSTABLE
MOTOR
MOTOR MOUNT
DRAIN LINE

BELT GUARD TO POWER SOURCE


OIL RESISTANT BELT
MOUNTING BRACKET
GREASE VENTILATION FAN
NIPPLE
FAN AIR FLOW NOMINAL TOTAL STATIC
UNIT PRESSURE MOTOR RATING MOTOR DATA
TYPICAL FLOOR MOUNTED A/C INSTALLATION DETAIL QTY
DESIGNATION
TYPE CAPACITY

DUCT WORK DUCT WORK


CFM IN. OF WATER WATTS VOLTS PHASE CYCLE

FLEXIBLE CONNECTOR
FAN DUCT WORK 5 EF-1 CEILING MOUNTED CASETTE TYPE 195 0.25 28 220 1 60
BOLTS
133 EF-2 CEILING MOUNTED CASETTE TYPE 50 0.25 11 220 1 60
CONNECT DUCTWORK
TO FAN WITH 3mm. THK.
NEOPRENE GASKET

TYPICAL WALL MOUNTED A/C INSTALLATION DETAIL


TUBE AXIAL BLOWER DETAIL

REPRESENTED BY:
DIEGO A. LOSANTA
PROJECT TITLE ILOILO MISSION HOSPITAL EXTENSION REPUBLIC ACT 545
THIS DRAWING AS AN INSTRUMENT OF SERVICE IS THE PROPERTY SHEET NO.
N.G. MORALIDAD & ASSOCIATES PROFESSIONAL MECHANICAL ENGINEER & MEDICAL CENTER DR. ELMER Q. PEDREGOSA OF THE ARCHITECT , WHETHER THE OBJECT FOR WHICH IT IS MADE IS
EXECUTED OR NOT. THIS DRAWING MAY NOT BE COPIED OR REPRODUCED
MD, MPH, MHA, FPCHA IN WHOLE OR IN PART , NOR USED IN ANOTHER PROJECT WITHOUT
PROJECT NO.
ARCHITECT (84-BED HOSPITAL) HOSPITAL ADMINISTRATOR THE WRITTEN CONSENT OF THE ARCHITECT.

M6
PRESIDENTIAL DECREE 49
PRC REG NO. 2178 PTR: 5680600 "PROTECTION OF INTELLECTUAL PROPERTY" ISSUED 14 NOV. 1972.
2F TIBIAO BUILDING JALANDONI ST. ILOILO CITY LOCATION ARCHITECTURAL DESIGNS, DRAWINGS & MODELS ARE CREATIVE WORKS
TEL/FAX. NO. (033) 338-0173 TIN: 1220010689 DATE: 01-05-17
JARO, ILOILO CITY OWNER OF THE ARCHITECT, AND ARE RECOGNIZED AS INTELLECTUAL PROPERTY
DULY PROTECTED UNDER P.D. 49.