Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

FR 1.

2
Electric thrust actuator
Electric thrust actuator FR 1.2
with safety reset

FR 1.2
Electric thrust actuator
with safety reset
on electrical power failure

Seite 2

Features
• Safety reset on electrical power failure
• Universal technology with 2-point,
3-point or continous 0-10V and 4-20mA
activation with only one actuator type
• Characteristic adjustable (equal percentage, linear,
quadratic)
• Operating time adjustable
• Operative ambient temperatures -10°C up to +55°C
• Enclosure IP 66
• Travel indicator
• Additional devices available
• Direction of closure: stem in outwards motion

Edition 06/08 - Data subject to alteration - Regularly updated data on www.ari-armaturen.com! Data sheet 000014 english
FR 1.2
Technical data

Type FR 1.2 Additional accessories


Closing force kN 2,0 kN (at travel 40 mm) Plug-in module for 230V 50/60Hz (+/- 15%) supply tension and 3-point input
signal, 0-10V and 4-20mA controlling, additional capacity 2VA (feedback
Travel mm max. 49 mm
signal only 0-10V, not 4-20mA)
Positioning speed mm/s 0,17 / 0,25 / 0,50 mm/s
2 auxiliary change over switches, continously adjustable, add. load 5(2) A,
On power cut-out: 12...250V~, min. load 250 mA, 12V
Closure time s 28 s (for travel 20 mm); 35 s (for travel 30 mm)
Direction of closure Extended stem on electrical power failure 230V Module
Manual adjustment with crank lever on the outside of the housing
Continous
Operative amb. temperature °C -10°C up to +55°C
Permitted ambient humitity < 95% rF without condensation
y = 0...10V y = 4...20mA yo = 0...10V Continous
Installation position vertically righted to horizontally
X XX
21 1 2a 2b 3u 3i 44 L
230V~
Enclosure (acc. to EN 60529) IP 66
N
C
Protection class (acc. to EN 60730) III
43 N 41 42
Response time at 3-point ms 200 ms
M Module
Mains 24V 50/60Hz 1~ +/- 20% S1 S2 S3 S4
3u 3i 44
230V~
On 0% 0V 4mA 0V
24VDC +/- 15% 41
100% 10V 20mA 10V
Spindle
100%
230V 50/60Hz 1~ +/- 15% (optional) Off
S1; S2 = Drivetime 42
0% 10V 20mA 10V
S3; S4 = Characteristic 100% 0V 4mA 0V
0%
Position controller
Control signal 1 0 ... 10 V, Ri = 100 kOhm (not at 230V) 2pt 3pt
L L
Control signal 2 4 ... 20 mA, Ri = 50 kOhm N
230V~
N
230V~

Position indicator 0 ... 10 V, burden > 2,5 kOhm (not at 230V)


Rated input in operation VA 20 VA 1) 43 N 41 42 43 N 41 42

Rated input in idleness VA 7 VA


Module Module
Electrical connection to internal terminal via (max. 2,5mm2) 230V~ 230V~
3 break through-type cable lead throughs for
M20x1,5 (2x) and M16x1,5 FR1.2 FR1.2

Limit switch-off load depending


Operating mode (acc. to VDE) 24V 50/60Hz 1~, 24VDC S6-80% duty cycle
Auxiliary change over switch
230V 50/60Hz 1~, S6-50% duty cycle
4 5 6 7 8 9
Weight kg 6 kg
1) Transformators has to be designed for this value, to avoid malfunction
6
4
X S1
5
9
7
X S2
8
0% 100%

Wiring diagram Dimensions

Continous
24 V~/=

y = 0...10V y = 4...20mA yo = 0...10V


3pt
21 1 2a 2b 3u 3i 44
24 V~/=

C
21 1 2a 2b 3u 3i 44

3u 3i 44
M 2pt
0% 0V 4mA 0V 24 V~/=
S1 S2 S3 S4 2a 100%
On 10V 20mA 10V Spindle
0% 10V 20mA 10V 100%
Off 2b 100% 0V 4mA 0V 21 1 2a 2b 3u 3i44
S1; S2 = Drivetime 0%
S3; S4 = Characteristic

Technology for the Future.


GERMAN QUALITY VALVES

ARI-Armaturen Albert Richter GmbH & Co. KG, D-33750 Schloß Holte-Stukenbrock,
Tel. +49 52 07 / 994-0, Telefax +49 52 07 / 994-158 or 159 Internet: http://www.ari-armaturen.com E-mail: info.vertrieb@ari-armaturen.com

2 Edition 06/08 - Data subject to alteration - Regularly updated data on www.ari-armaturen.com!