= Strategic locations in Process, utlty
‘areas where specific safety
operations are to be carried out such
as
* Areas near heat exchangers,
condensers
Barring gears of steam turbine
* Some — portions of roads
interconnecting substations and
process plants.
vil) As_a good engineering practice the AC.
‘emergency load is generally considered as
20-25% of Normal Lighting load. However
for small plants, where A.C. emergency
load is not substantialwhere there is no
separate standby 0.G. set, D.C. critical
lighting system may take care of entire
emergency lighting.
vi)The following operational philosophy is
recommended. Under normal operation,
both emergency and normal lighting shall
be fed by Normal power source. On failure
of normal supply, emergency lighting load
will be transfered to emergency source
after the start of D.G. set within 15 seconds.
rica lighting (0.C. supply based) will be
nomally kept ‘ON’ and during
Normalemergency power failure, battery
will provide power.
vil) Besides, adequate number of self
‘contained portable hand lamps and Battery
‘emergency lighting units shall be provided
for immediate use in emergency at remote
stations and at other strategic places (safe
areas), wherever required, for personnel
safety
ix) HPMVIMLL lamps shall generally be used
{or outdoor plant lighting. Keeping in view
the restrike time lag and to avoid complete
darkness in case of a voltage dip/brown out
Conditions, necessary incandescent lamps
may be judiciously distributed throughout
the plant area. Incandescent lamps may be
considered for emergency lighting to
achieve this objective, Fluorescent lamps
may be used for indoor lighting in non-
pracess bulidings and control rooms. Safe
‘area street lighting and yard lighting may
employ sodium vapour lamps. Low
Pressure sodiun: vapour lamps shall not be
installed in hazardous areas,
x) The ilumination levels in different areas
shall be as per good engineering practice,
Depending on the nature of job activities to
be camed out the suggested minimum
ilumination levels for various areas are as
under
‘Areas Miumination
in Lux
= Main roads (along process 7 - 10
units, power houses,
‘workshops, ete.)
= Secondary roads (along 3 - 5
storage tanks setting
basins etc.)
= Tank farm 10
~ Pump houses, sheds 100
= Main operation platforms 60
& access stairs
~ Ordinary platforms 20
+ Process areas, pipe 60
racks, heat exchanger,
heater, separators, cooling
tower, columns, pig
launching/receiving loading
area, flare etc
= Switchgear blag 150-200
= Transformer bay 100
= Battery oom 150
= Control room bldg Jlaboratory 400
placate
= Boller house 150
= Charger/UPS rooms 160-200
= Cooling tower 60
+ Switehyard () operating area 100
(i other areas 50
~ Warehouse 100
= Office 309
= Compressor area 200
+ Watehroom 100
= Stairs 50
+ Conidorsite 70