T8411R Electronic Heat Pump Thermostat: Caution
T8411R Electronic Heat Pump Thermostat: Caution
INSTALLATION INSTRUCTIONS
The T8411R Heat Pump Thermostat provides 24V
control of two-stage heating and one-stage cooling heat
pump system with manual changeover from heat to cool.
CAUTION
First stage heating and cooling cycle rates are fixed at Electrical Shock or Equipment Damage
3 cph. Second stage heating cycle rate is selectable at Hazard.
3, 4, 5, 6, 9 or 12 cph. Temperature indication can be set Can shock individuals or short equipment
for °F or °C. circuitry.
Disconnect power supply before installation.
The T8411R Heat Pump Thermostat is powered directly
from the system transformer. Batteries are not required
because setpoints are held permanently by non-volatile
Location
memory. Install the thermostat about 5 ft (1.5m) above the floor in
an area with good air circulation at average temperature.
The T8411R includes a thermostat, wallplate (for wiring See Fig. 1. Do not install the thermostat where it can be
and mounting thermostat), and owner’s guide. A 7 3/8 in. affected by:
x 5 3/4 in. (188mm x146 mm) decorator cover plate (for — drafts or dead spots behind doors and in corners.
covering wall marks) is available separately. Order — hot or cold air from ducts.
Honeywell part no. 209649A (taupe color). — radiant heat from the sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall
behind the thermostat.
MERCURY NOTICE This thermostat is a precision instrument and was
If this control is replacing a control that contains
mercury in a sealed tube, do not place your old carefully adjusted at the factory. Handle it carefully.
control in the trash.
YES
NO
NO
5 FEET
[1.5 METERS]
NO
M11338
G
L
MOUNTING WALLPLATE W2
SCREWS (2)
R
1 WHEN USING WALL ANCHORS, DRILL 3/16 INCH E
HOLES FOR DRYWALL, 7/32 INCH HOLES FOR
PLASTER OR WOOD.
M12202A
W1
Fig. 2. Mounting wallplate to wall. B
1
Y
Wiring O
IMPORTANT
Use an 18-gauge maximum wire for wiring the 1 NOT ALL MODELS HAVE BOTH O AND B TERMINALS. M11334A
T8411R Thermostat.
All wiring must comply with local electrical codes and Fig. 3. Wiring connections.
ordinances.
NOTE: To ensure proper mounting of thermostat,
restrict all wiring to the shaded area. See Fig. 4.
CAUTION
Electrical Shock or Equipment Damage
Hazard.
Can shock individuals or short equipment
circuitry.
Disconnect power supply before installation.
69-1486-1 2
T8411R ELECTRONIC HEAT PUMP THERMOSTAT
R
W2 Mounting Thermostat to Wallplate
1. Engage the tabs at the top of the thermostat and
E
wallplate.
W1 2. Swing down the thermostat and press the lower
B edge of the thermostat onto the wallplate to latch.
1
See Fig. 6.
Y
O
L1
R (HOT)
THERMISTOR STAGE 2 RELAY
SENSOR L2
AUXILARY
THERMOSTAT HEAT RELAY 1
LOGIC SYSTEM
SWITCH W2
RELAY
EM. HT.
L
HEAT CHANGEOVER
VALVE HEAT
OFF
B
COOL CHANGEOVER
3 VALVE COOL
O
STAGE 1 RELAY COMPRESSOR
CONTACTOR
2 COMPRESSOR
CONTACTOR
HEAT
W1
EMERGENCY
HEAT RELAY
FAN SWITCH E
FAN RELAY
ON
G
POWER AUTO
SUPPLY C
2 REMOVE JUMPER, WHEN SUPPLIED, FOR SYSTEMS WITH SEPARATE HEATING COMPRESSOR CONTACTOR (W1 SEPARATE FROM Y).
Fig. 5. T8411R two-stage heat and one-stage cool wiring diagram with manual changeover.
3 69-1486-1
T8411R ELECTRONIC HEAT PUMP THERMOSTAT
FAN Switch
DASHED LINES INDICATE TABS
ON BACK OF THERMOSTAT Fan switch settings are:
On: The fan runs continuously. Use for improved air
circulation and air quality.
Auto: Normal setting for most homes. The fan starts
and stops with the equipment.
Em Ht
Aux Ht
SYSTEM Switch
System switch settings control thermostat operation as
AuFA
to NO
follows:
n
Cool: The thermostat controls the cooling system.
Off: Both heating and cooling are off.
Cool SYSTE
Off M
Heat
E
Heat: The thermostat controls the heating system.
Em Ht: Thermostat cycles auxiliary heat (W2) and
mH
t
A ENGAGE TABS AT TOP OF THERMOSTAT emergency heat relay (E) as needed to maintain
WITH SLOTS ON MOUNTING PLATE. setpoint. Terminal L is energized continuously.
Fault heat relay is on continuously. Cooling system
is off. Compressor is de-energized.
TEMPERATURE DISPLAY
Set
Room
INCREASE SETTING
DECREASE SETTING
FA
AutoN
On Em Ht
Aux Ht
Coo
l OffSYST
HeaEM
t Em
H t
Set
Room
FAN
Au to O
B PRESS LOWER EDGE OF n
Set Room
M18425
69-1486-1 4
T8411R ELECTRONIC HEAT PUMP THERMOSTAT
Set Temperature Setpoint 2. Press the ▲▼ keys simultaneously for more than
one second to light all segments on display and to
NOTE: Temperature setpoint range is 40° to 99°F (4° to enter installer setup mode. When the keys are
39°C). released, a two-digit software revision code is dis-
played.
The temperature setpoint and the room temperature are
shown separately on the digital display. The ▼ indicator
points to Set when the temperature setpoint is displayed
and to Room when the room temperature is displayed M18426
.
OPTIONAL SYSTEM CHECKOUT
INDICATOR
When the heat or cool outputs are turned on, the five-
Set Room ROOM TEMPERATURE minute off-timer safety feature is bypassed.
SETPOINT TEMPERATURE When in steps 2 and 3 only, the ▼ key can be used to
M14679
turn heat or cool outputs on and off. Change the
SYSTEM switch setting to test heat or cool outputs. No
To set temperature setpoint:
action takes place If the system switch is in the Off
1. Select Heat or Cool by sliding the SYSTEM switch
position.
in the lower right corner of the thermostat to the
desired mode. See Fig. 7.
The following examples of system settings show a two
2. To display the temperature setpoint on the digital
digit software code on the display. The code shown is
display, press either the ▲ or ▼ key once. The
only an example; codes may vary.
temperature setpoint is displayed for approxi-
mately five seconds as the indicator points to Set
System setting at Heat:
and flashes.
To turn heat on, press the ▼ key.
M14680
M18431
degrees.
M18432
M14682 M18434
M14688
M14683
5 69-1486-1
T8411R ELECTRONIC HEAT PUMP THERMOSTAT
5. Press the ▼ key to change the °C or °F indication. 10. Press the ▲ key to save all changes, exit installer
setup mode and return to normal operation.
M18420