Professional Documents
Culture Documents
Lecture 1
Lecture 1
3. Reactive power compensation for voltage control in the transmission and distribution
systems
5. Voltage Stability.
References
• Haadi Saadat, Power System Analysis (2002)
power system.
• Q is required for loads that need magnetic field excitation like induction motors and
transformers.
• At balance, I/V = (B/X)1/2 → Natural (surge) impedance loading (SIL) of the system.
Simple Power System Model
• The receiving end voltage is greater than the sending end voltage.
• The impedance of the load is less than the surge impedance of the line.
Load = 360 MW
• The receiving end voltage is greater than the sending end voltage.
• The impedance of the load is less than the surge impedance of the line.
Voltage and Reactive Power Control
• Why the Inductance absorb Q and the Capacitance produce Q in AC power system?
• If an alternator is loaded by a capacitor, the capacitor supplies a current with the change
in voltage every ½ cycle. Due to the 180 deg. phase shift between the capacitor current
and inductor current, the capacitor current is added to the magnetic field of the
alternator.
Voltage and Reactive Power Control
• Well designed power system → Good quality of reliable supply.
• Equipment operates satisfactorily if the voltage is within ±3% or ±5% of their ratings.
• If the voltage varies beyond its limits, the equipment performance suffers and hence, the
equipment life is also sacrificed.
• For example, the induction motor torque (which forms about 70% of the total load) varies
as square of the terminal voltage.
• When power is supplied to a load through a transmission line keeping the sending end
variations depending upon the magnitude and the power factor of the load.
• The higher the load with smaller power factor is → the greater the voltage
variation becomes.
Voltage and Reactive Power Control
• Voltage variations at a node (bus) indicate unbalance between the reactive power
• If the generated (Q) is greater than consumed, the voltage goes up and vice versa.
• Whenever the voltage level of a particular bus undergoes variation this is due to the
• In Figure, the generator node with reference voltage 𝑽𝟏 and the load node with voltage 𝑽𝟐 .
• Assume a lossless line (𝑅 = 0) and constant 𝑽𝟏 (by adjusting the generator excitation), then
𝑽𝟐 = 𝑽𝟏 − 𝑰 ∙ 𝒁 = 𝑽𝟏 − 𝑰 ∙ 𝑗𝑋 (1)
Voltage and Reactive Power Control
𝑽∗𝟏 ∙ 𝑰 = 𝑃 − 𝑗𝑄 or 𝑽𝟏 ∙ 𝑰∗ = 𝑃 + 𝑗𝑄 (2)
• Eq. (2) represents the supplied power by the generator assuming inductive load, hence the current
supplied by the generator is:
𝑃 − 𝑗𝑄
𝑰=
𝑽∗𝟏
𝑃 − 𝑗𝑄
𝑽𝟐 = 𝑽𝟏 − ∙ 𝑗𝑋
𝑽∗𝟏
𝑄∙𝑋 𝑃∙𝑋
𝑽𝟐 = 𝑉1 − −𝑗 (3)
𝑉1 𝑉1
Voltage and Reactive Power Control
• It is shown that the load voltage 𝑽𝟐 is not significantly affected due to the load real
component 𝑃 as it is perpendicular to the phasor 𝑽𝟏 whereas the voltage drop due to
reactive component 𝑄 is directly subtracted from 𝑽𝟏 .
• Assuming the voltage drop due to 𝑃 is negligible, the voltage drop is directly proportional to
𝑄 as follows,
𝑄∙𝑋
𝑉1 − 𝑉2 ≅ (4)
𝑉1
Voltage and Reactive Power Control
𝑄∙𝑋
• In order to keep 𝑽𝟐 fixed for a particular 𝑽𝟏 , the voltage drop must remain
𝑉1
constant.
𝑄∙𝑋
• 𝑄 could be locally adjusted to keep 𝑉1
constant at the value which fixes 𝑽𝟐 at
• Since the voltage variation is more for larger loads (larger reactive power), the variation
could be controlled by switching in suitable series capacitors 𝑋𝑐 .
• Series compensation → modify the total reactance between the sending and
receiving ends to control the voltage drop.