GENERAL NOTES
PARKING LEVEL FLOOR PLANS NOT FOR
1. REFER TO SHEET A0.01 FOR 'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK. CONSTRUCTION
2. PROVIDE STEEL ANGLE CORNER GUARDS FROM FINISH FLOOR TO 4’-0” ABOVE FINISH FLOOR AT ALL COLUMN LOCATIONS
EXPOSED TO DRIVE AISLES AND PARKING STALLS AND AS SHOWN.
3. PROVIDE GUARDS AT EXPOSED PIPING AND CONDUITS.
4. PROVIDE BOLLARDS TO PROTECT DUCTS, EQUIPMENT AND OTHER CONSTRUCTION FROM IMPACT BY VEHICLES, IN
ACCORDANCE WITH DETAIL 11/A1.21.
3
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
5. SEE SLAB PLANS FOR CONCRETE WALL LOCATIONS, UNO. COORDINATE WITH STRUCTURAL DRAWINGS
A4.02 A4.01 6. REFER TO STRUCTURAL DRAWINGS FOR COLUMNS, SHEAR WALL AND BEAM SIZES.
7. SEE SHEETS A0.21, A0.31 FOR WALL ASSEMBLIES.
8. SEE FIRE/LIFE SAFETY SHEETS BEGINNING ON SHEET G2.01 FOR LOCATIONS OF FIRE EXTINGUISHER CABINETS.
9. SEE ENLARGED PLANS FOR DETAILED DIMENSIONS, WALL TAGS AND DOOR TAGS
1 11 10. HM DOOR OPENINGS IN CONCRETE CURBS AND WALLS INCLUDE 1" CONSTRUCTION TOLERANCE. MASONRY OPENINGS
2 3 3.9 4 5 5.2 6 6.2 7 8 8.4 8.8 9 10
DO NOT INCLUDE ANY TOLERANCE.
13 14 15 16 17 18
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
11. MAINTAIN MINIMUM CLEAR HEIGHT OF 98 INCHES, MEASURED VERTICALLY FROM FLOOR LEVEL TO LOWEST OVERHEAD
A4.55 A4.55 A4.55 A4.56 A4.56 A4.56 OBSTRUCTION, COMMENCING AT POINT OF ENTRY OF PARKING GARAGE TO LOCATION OF ALL VAN ACCESSIBLE PARKING
STALLS REGARDLESS OF WHERE SUCH STALLS ARE LOCATED IN THE GARAGE. 38 NORTHWEST DAVIS, SUITE 300
PROVIDE EMBED PLATES WITH WELDED
HATCH DENOTING LOCATION 98 INCHES CLEAR IS REQUIRED. PORTLAND, OR 97209
KNIFE PLATES FOR LADDER ATTACHMENT
503.245.7100
12. GARAGE DRAINS 1'4" PER FOOT UNO.
I 1505 5TH AVE, SUITE 300
SEATTLE, WA 98101
5' - 0"

1
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
X3.0 1
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
206.576.1600
A4.02 0 14 A4.02
GALV MTL 1014 HOWARD STREET
LADDER SAN FRANCISCO, CA 94103
H 415.252.7063
GARAGE EXHAUST © ANKROM MOISAN ARCHITECTS, INC.
19' - 11"

FIRE

16' - 2"
X3.0
WATER Y3.0 0 12
0 12
2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
STORAGE 2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.02 A4.02
TANK
P398 3' - 0 1/2"

2' - 4 3/4"
G

BACK-UP CLEARANCE
TANK COATING 5 SIDES UP TO FLOOR CEILING ABOVE

22' - 0 1/2"
DRIVE AISLE
1
21' - 4"

20' - 3"
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.51
EL: 152'-9"

THE MARK AT SEATTLE


1200 45TH ST SEATTLE, WA 98105
PROVIDE MECHANICAL SEAL DEVICES EL: 157'-0"
AT FIRE PUMP PIPE PENETRATIONS 17.89% 11.67% 5.83%

F 12 26' - 1" 9' - 4" EL: 157'-10 1/2" EL: 157'-3 1/2"
SLOPE UP 1" BETWEEN CONCRETE WALLS (TYP)

P300
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.54 SF39
EL: 157'-0"
6"

LCD ACQUISITIONS, LLC


PARKING 2
SHAFT EL: 157'-1" __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

STAIR 1 P310
A4.51
RR MECH. STORAGE S01
105' - 0"

SHAFT
P301A P301A P300A
BUILDING P300B 3' - 11 1/4" 22' - 0" 16' - 2"
P300A P300B
17' - 0"

ENGINEER 9C.3 BACK-UP CLEARANCE


2 6

2 8 *
P301

4J.2

4.81%
1
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ SHAFT 1
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.01 3 A4.01
LOBBY UP
A6.01
3' - 0"

UP ELEV 2 P300
ELEV 1
STAIR 2 E02 E01
D P301 S01P3
S02
5' - 0"

4J.2
0 8 * S02P3 SHAFT
C
EL: 155'-11" 3
11 3' - 8 1/4"
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.51
A4.54 EXIT REVISION DATE REASON FOR ISSUE
10' - 7 1/2"

Y3.0 1 Date 2 Permit Corrections #2 (first


EL: 152'-9" PASSAGEWAY 3 2 18 1
A6.03 was 100% DD set)
S02A A6.21
20' - 1"
21' - 6"

10
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.54 8' - 10" STORM WATER EJECTOR SUMP


10' - 10 1/2"

BELOW (PER PLUMBING)

5.10% EL: 155'-11" 4


__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.52
EL: 152'-9"

B
X3.0
0 14
15' - 2"

12' - 7"
9x SDCI APPROVAL STAMP
14' - 9"

2 C2
5' - 5"
9x
2 C2

19' - 9" 23' - 7"

15' - 2" 21' - 0" 14' - 5" 2' - 7" 6' - 8" 2' - 10" 15' - 6" 2' - 2" 9' - 5 1/2" 4' - 4 1/2" 4' - 10" 8' - 5" 2' - 9" 17' - 3" 14' - 9"

9
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
8
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
7
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
6
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
5
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
LEVEL P3 FLOOR
A4.53 A4.53 A4.53 A4.52 A4.52
1' - 10" 142' - 2" PLAN
1' - 1 1/2"
BIM 360://Seattle II/210310-20-Seattle II.rvt

60% CD SET
3
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.02 A4.01

DATE PROJECT NUMBER


11/18/2022 210310

1 LEVEL P3 PLAN
1/8" = 1'-0"
SHEET NUMBER

A2.P03
NORTH
11/18/2022 12:07:41 PM
GENERAL NOTES - SLAB PLANS
1.
2.
REFER TO SHEET A0.01 FOR 'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK.
ELEVATION TAGS INDICATE TOP OF CONCRETE, UNLESS NOTED OTHERWISE.
NOT FOR
3. VERIFY AND COORDINATE SLAB PENETRATIONS INCLUDING SLEEVES & BLOCKOUTS AS REQUIRED FOR PLUMBING,
MECHANICAL, ELECTRICAL, ETC. NOTIFY ARCHITECT OF ANY CONFLICTS OR DISCREPENCIES. CONSTRUCTION
4. PROVIDE SLAB BLOCKOUTS FOR RECESSED DOOR HARDWARE.
5. SLAB PLANS INDICATE LAYOUT DIMENSIONS FOR CONCRETE SLABS, CURBS, CONCRETE WALLS, DEPRESSIONS, AND SLOPES,
ONLY. REFER TO STRUCTURAL FOR ADDITIONAL REQUIREMENTS.
6. ROOF, DECK AND BALCONY SLABS SLOPE TO DRAIN 1/4" PER FT, UNO.
7. VERIFY HOISTWAY CLEARANCES, ROUGH OPENING REQUIREMENTS (ELEVATOR DOORS, LOUVERS, ETC.) AND NOTIFY
3
__ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___
2
__ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___
ARCHITECT OF ANY DISCREPENCIES.
A4.02 A4.01 8. PROVIDE HOUSEKEEPING PADS REQUIRED FOR FLOOR-MOUNTED EQUIPMENT AS REQUIRED OR AS INDICATED ON MEP OR
FIRE PROTECTION DRAWINGS.
9. PROVIDE CAST OR SAWN CONTROL JOINTS IN SLABS ON GRADE AT LOCATIONS INDICATED ON STRUCTURAL OR
1 2 3 3.9 5 5.2 6.2 7 8.4 8.8 9 10 11 ARCHITECTURAL DRAWINGS. IN THE EVENT OF CONFLICT, NOTFIY THE ARCHITECT PRIOT TO PLACEMENT OF CONCRETE.
10. CONFORM TO VAPOR BARRIER OR WATERPROOF MEMBRANE MANUFACTURERS MINIMUM SPACING REQUIREMENTS
BETWEEN MULTIPLE ADJACENT PENETRATIONS.
11. ALIGN EDGE OF SLAB WITH FACE OR ADJACENT COLUMN OR CONCRETE WALL, UNLESS NOTED OTHERWISE.
38 NORTHWEST DAVIS, SUITE 300
PORTLAND, OR 97209
503.245.7100

I 1505 5TH AVE, SUITE 300


SEATTLE, WA 98101
5' - 0"

1
__ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___
1
__ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___
206.576.1600
A4.02 A4.02
H
1014 HOWARD STREET
SAN FRANCISCO, CA 94103
415.252.7063
© ANKROM MOISAN ARCHITECTS, INC.
19' - 11"

2
__ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___
2
__ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___

A4.02 A4.02
8"

SEE PLAN (ABOVE)


157'-0"
10"

2' - 4 3/4"
G
SLAB PLAN LEGEND
4"

4"
3"

3' - 0 1/2" SLAB STEP


EL: 152'-9"
21' - 4"

OVERFRAMING

THE MARK AT SEATTLE


17.89% 11.67% 5.83%

1200 45TH ST SEATTLE, WA 98105


SLAB BREAK LINE, UNO
EL: 157'-10 1/2" EL: 157'-0"
EL: 157'-3 1/2"
F SLAB ON GRADE
21' - 2 3/4" 6' - 0" 21' - 2 1/4"
157'-0"
6"

E RAMP ON GRADE

LCD ACQUISITIONS, LLC


4' - 7" 1'-2"

8' - 11 3/4"
CONCRETE CURB
105' - 0"

7' - 2 1/2" 157'-1" 7" 2' - 9"

1' - 2"
17' - 0"

FLOOR DRAIN FD

4.81%
1 1

8"
__ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___ __ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___

A4.01 A4.01 ROOF DRAIN WITH OVERFLOW

5' - 6"

5' - 6"
9" 10"
7' - 10 1/2"

1' - 1 3/4"
D
5' - 0"

4' - 7"

C
EL: 155'-11"
REVISION DATE REASON FOR ISSUE
EL: 152'-9"
4 FTØ MANHOLE LID

8'' CONC PRECAST VAULT LID


21' - 6"

5.10%
EL: 155'-11"
EL: 152'-9"

B
6' - 8" 2' - 2" 4' - 4 1/2" 3' - 0 1/2"

SDCI APPROVAL STAMP


14' - 9"

5' - 5"
3' - 8 1/2"
2' - 2"

2' - 2"
A

LEVEL P3 SLAB PLAN

15'-2" 21'-0" 14'-5" 9'-3" 2'-10" 17'-8" 9'-5 1/2" 9'-2 1/2" 8'-5" 2'-9" 17'-3" 14'-9"
142' - 2"
BIM 360://Seattle II/210310-20-Seattle II.rvt

60% CD SET
3
__ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___
2
__ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___

A4.02 A4.01

DATE PROJECT NUMBER


11/18/2022 210310

1 LEVEL P3 - SLAB PLAN


1/8" = 1'-0"
SHEET NUMBER

A2.P03S
PROJECT
11/18/2022 10:24:29 AM
GENERAL NOTES
PARKING LEVEL FLOOR PLANS NOT FOR
1. REFER TO SHEET A0.01 FOR 'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK. CONSTRUCTION
2. PROVIDE STEEL ANGLE CORNER GUARDS FROM FINISH FLOOR TO 4’-0” ABOVE FINISH FLOOR AT ALL COLUMN LOCATIONS
EXPOSED TO DRIVE AISLES AND PARKING STALLS AND AS SHOWN.
3. PROVIDE GUARDS AT EXPOSED PIPING AND CONDUITS.
4. PROVIDE BOLLARDS TO PROTECT DUCTS, EQUIPMENT AND OTHER CONSTRUCTION FROM IMPACT BY VEHICLES, IN
ACCORDANCE WITH DETAIL 11/A1.21.
3
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
5. SEE SLAB PLANS FOR CONCRETE WALL LOCATIONS, UNO. COORDINATE WITH STRUCTURAL DRAWINGS
A4.02 A4.01 6. REFER TO STRUCTURAL DRAWINGS FOR COLUMNS, SHEAR WALL AND BEAM SIZES.
7. SEE SHEETS A0.21, A0.31 FOR WALL ASSEMBLIES.
8. SEE FIRE/LIFE SAFETY SHEETS BEGINNING ON SHEET G2.01 FOR LOCATIONS OF FIRE EXTINGUISHER CABINETS.
9. SEE ENLARGED PLANS FOR DETAILED DIMENSIONS, WALL TAGS AND DOOR TAGS
1 11 10. HM DOOR OPENINGS IN CONCRETE CURBS AND WALLS INCLUDE 1" CONSTRUCTION TOLERANCE. MASONRY OPENINGS
2 3 3.9 4 5 5.2 6 6.2 7 8 8.4 8.8 9 10
DO NOT INCLUDE ANY TOLERANCE.
13 14 15 16 17 18
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
11. MAINTAIN MINIMUM CLEAR HEIGHT OF 98 INCHES, MEASURED VERTICALLY FROM FLOOR LEVEL TO LOWEST OVERHEAD
A4.55 A4.55 A4.55 A4.56 A4.56 A4.56
17' - 10 3/4" OBSTRUCTION, COMMENCING AT POINT OF ENTRY OF PARKING GARAGE TO LOCATION OF ALL VAN ACCESSIBLE PARKING
CHAIN LINK FENCE STALLS REGARDLESS OF WHERE SUCH STALLS ARE LOCATED IN THE GARAGE. 38 NORTHWEST DAVIS, SUITE 300
HATCH DENOTING LOCATION 98 INCHES CLEAR IS REQUIRED. PORTLAND, OR 97209
503.245.7100
12. GARAGE DRAINS 1'4" PER FOOT UNO.
I 1505 5TH AVE, SUITE 300
SEATTLE, WA 98101
5' - 0"

1
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
OPEN TO BELOW X3.0 1
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
206.576.1600
A4.02 0 14 A4.02
H
1014 HOWARD STREET
33 BIKES SAN FRANCISCO, CA 94103
42" ∅ FIRE 415.252.7063
4J.2 CISTERN
FIRE SERVICE 2 8 GARAGE EXHAUST © ANKROM MOISAN ARCHITECTS, INC.
VALVES 9C.3 MANHOLE LID
28' - 0 7/8"

4J.2 2 6
2 8 *
19' - 11"

BIKE

16' - 2"
PARKING
2 FIRE PUMP P205 2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ P202A __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.02 ROOM A4.02


P202
4J.2 9C.3
2 8 * 2 6 CHAIN LINK FENCE P205
G
EL: 160'-1"

Y3.0 X3.0

BACK-UP CEARANCE
0 12 0 12

22' - 0 1/2"
DRIVE AISLE
1
21' - 4"

20' - 3"
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.51

THE MARK AT SEATTLE


1200 45TH ST SEATTLE, WA 98105
EL: 166'-0" EL: 166'-0"
F 12
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
5.21% 11.67% 11.67% 11.67%
A4.54 SF38

LCD ACQUISITIONS, LLC


P200
6"

2
6' - 5 1/4"

22' - 1 1/2"
STAIR SHAFT STAIR 1 3' - 10 3/4" 22' - 0" 16' - 2 1/2" __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

MECH. A4.51
S02P2

ACCESS S01 BACK-UP CLEARANCE


105' - 0"

16' - 2 1/2" BACK-UP CLEARANCE P200A

SHAFT

4.81% DOWN (1/2"/12")


E04 STORAGE 4J.2
P200A P200B 2 8 *
17' - 0"

T.O. WALL EL: 161'-6 1/2" P200B


9C.3
2 6
5.93%

3' - 10"
1
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
6' - 1 3/4" 4' - 8" SHAFT ELEVATOR
1
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.01 A4.01
15' - 8 1/8"

EL: 161'-6 1/2" LOBBY 165'-3 1/4"


UP DN
9C.3 P200
2 6 UP DN ELEV 2 ELEV 1 PARKING
STAIR 2 E02 E01 S01P2 P210
D S02
RAILING EL: 166'-1"
5' - 0"

4' - 1 3/4" SHAFT


C
3
11 __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.51
2 5/8"

__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.54
9C.4 Y3.0 4 REVISION DATE REASON FOR ISSUE
PARKING 1 2 2 18
4 A6.01 1 Date 2 Permit Corrections #2 (first
P210 A6.21
A6.03 was 100% DD set)
EL: 161'-5"
19' - 9 7/8"
21' - 6"

EL: 164'-11"
10
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.54

1.88% DOWN (0"/12") 6.40% DOWN (1"/12")


4
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

CHAIN LINK FENCE EL: 161'-6 1/2" A4.52

B LOCATION FOR FUTURE


RETAIL TENANT
P210 CONDENSER UNITS.
P207 PROVIDE SLEEVES UP TO
15' - 0"
15' - 1 5/8"

RETAIL. SDCI APPROVAL STAMP


14' - 9"

X3.0
0 12

15' - 2" 21' - 0" 14' - 5" 2' - 7" 6' - 8" 2' - 10" 15' - 6" 2' - 2" 9' - 5 1/2" 4' - 4 1/2" 4' - 10" 8' - 5" 2' - 9" 17' - 3" 14' - 9"

9
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
8
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
7
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
6
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
5
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
LEVEL P2 FLOOR
A4.53 A4.53 A4.53 A4.52 A4.52

1' - 10" 142' - 2" 1' - 1 1/2"


PLAN
BIM 360://Seattle II/210310-20-Seattle II.rvt

60% CD SET
3
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.02 A4.01

DATE PROJECT NUMBER


11/18/2022 210310

1 LEVEL P2 - PLAN
1/8" = 1'-0"
SHEET NUMBER

A2.P02
NORTH
11/18/2022 10:24:33 AM
GENERAL NOTES - SLAB PLANS
1.
2.
REFER TO SHEET A0.01 FOR 'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK.
ELEVATION TAGS INDICATE TOP OF CONCRETE, UNLESS NOTED OTHERWISE.
NOT FOR
3. VERIFY AND COORDINATE SLAB PENETRATIONS INCLUDING SLEEVES & BLOCKOUTS AS REQUIRED FOR PLUMBING,
MECHANICAL, ELECTRICAL, ETC. NOTIFY ARCHITECT OF ANY CONFLICTS OR DISCREPENCIES. CONSTRUCTION
4. PROVIDE SLAB BLOCKOUTS FOR RECESSED DOOR HARDWARE.
5. SLAB PLANS INDICATE LAYOUT DIMENSIONS FOR CONCRETE SLABS, CURBS, CONCRETE WALLS, DEPRESSIONS, AND SLOPES,
ONLY. REFER TO STRUCTURAL FOR ADDITIONAL REQUIREMENTS.
6. ROOF, DECK AND BALCONY SLABS SLOPE TO DRAIN 1/4" PER FT, UNO.
7. VERIFY HOISTWAY CLEARANCES, ROUGH OPENING REQUIREMENTS (ELEVATOR DOORS, LOUVERS, ETC.) AND NOTIFY
3
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ ARCHITECT OF ANY DISCREPENCIES.
A4.02 A4.01 8. PROVIDE HOUSEKEEPING PADS REQUIRED FOR FLOOR-MOUNTED EQUIPMENT AS REQUIRED OR AS INDICATED ON MEP OR
FIRE PROTECTION DRAWINGS.
9. PROVIDE CAST OR SAWN CONTROL JOINTS IN SLABS ON GRADE AT LOCATIONS INDICATED ON STRUCTURAL OR
1 2 3 3.9 5 5.2 6.2 7 8.4 8.8 9 10 11 ARCHITECTURAL DRAWINGS. IN THE EVENT OF CONFLICT, NOTFIY THE ARCHITECT PRIOT TO PLACEMENT OF CONCRETE.
10. CONFORM TO VAPOR BARRIER OR WATERPROOF MEMBRANE MANUFACTURERS MINIMUM SPACING REQUIREMENTS
BETWEEN MULTIPLE ADJACENT PENETRATIONS.
11. ALIGN EDGE OF SLAB WITH FACE OR ADJACENT COLUMN OR CONCRETE WALL, UNLESS NOTED OTHERWISE.
38 NORTHWEST DAVIS, SUITE 300
PORTLAND, OR 97209
503.245.7100

I 1505 5TH AVE, SUITE 300


SEATTLE, WA 98101
5' - 0"

1' - 0" 1' - 5"


1
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
1
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
206.576.1600
A4.02 A4.02
H
1014 HOWARD STREET
SAN FRANCISCO, CA 94103
415.252.7063
© ANKROM MOISAN ARCHITECTS, INC.
19' - 11"

2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.02 A4.02
10"

2' - 4 3/4"
G
SLAB PLAN LEGEND

4"
8" EL: 166'-0"
3"
5.83%
3' - 0 1/2"
SLAB STEP
EL: 166'-3 1/2"
21' - 4"

OVERFRAMING
EL: 166'-10 1/2"
EL: 160'-1"

THE MARK AT SEATTLE


1200 45TH ST SEATTLE, WA 98105
SLAB BREAK LINE, UNO

F SLAB ON GRADE
21' - 2 3/4" 6' - 0" 21' - 2 1/4"
EL: 160'-1" EL: 166'-0"
6"

E RAMP ON GRADE

LCD ACQUISITIONS, LLC


4' - 7"

8' - 11 3/4"
1'-2"
CONCRETE CURB
105' - 0"

9 1/2"

7" 2' - 9"

1' - 2"
7' - 2 1/2"
17' - 0"

FLOOR DRAIN FD
8 3/4"

4.81%
5.93%

1 1

8"
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.01 A4.01 ROOF DRAIN WITH OVERFLOW


7' - 2 1/2" 1"

5' - 6"
D
5' - 0"

EL: 161'-5"
C
EL: 164'-11"
REVISION DATE REASON FOR ISSUE
21' - 6"

EL: 161'-5"
EL: 161'-6 1/2"
1.88% 6.40% EL: 164'-11"

B
3' - 0 1/2"

SDCI APPROVAL STAMP


14' - 9"

5' - 5"
3' - 8 1/2"

3' - 8 1/2"
2' - 7" 2' - 2" 4' - 4 1/2"
2' - 2"

2' - 2"
A

LEVEL P2 SLAB PLAN

15'-2" 21'-0" 14'-5" 9'-3" 2'-10" 17'-8" 9'-5 1/2" 9'-2 1/2" 8'-5" 2'-9" 17'-3" 14'-9"
142' - 2"
BIM 360://Seattle II/210310-20-Seattle II.rvt

60% CD SET
3
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.02 A4.01

DATE PROJECT NUMBER


11/18/2022 210310

1 LEVEL P2 - SLAB PLAN


1/8" = 1'-0"
SHEET NUMBER

A2.P02S
PROJECT
11/18/2022 12:07:40 PM
GENERAL NOTES
NOT FOR
PARKING LEVEL FLOOR PLANS
1. REFER TO SHEET A0.01 FOR 'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK.
CONSTRUCTION
2. PROVIDE STEEL ANGLE CORNER GUARDS FROM FINISH FLOOR TO 4’-0” ABOVE FINISH FLOOR AT ALL COLUMN LOCATIONS
EXPOSED TO DRIVE AISLES AND PARKING STALLS AND AS SHOWN.
3. PROVIDE GUARDS AT EXPOSED PIPING AND CONDUITS.
4. PROVIDE BOLLARDS TO PROTECT DUCTS, EQUIPMENT AND OTHER CONSTRUCTION FROM IMPACT BY VEHICLES, IN
3
__ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___
2 ACCORDANCE WITH DETAIL 11/A1.21.
__ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___

A4.02 A4.01 5. SEE SLAB PLANS FOR CONCRETE WALL LOCATIONS, UNO. COORDINATE WITH STRUCTURAL DRAWINGS
6. REFER TO STRUCTURAL DRAWINGS FOR COLUMNS, SHEAR WALL AND BEAM SIZES.
EMERGENCY GENERATOR PER 7. SEE SHEETS A0.21, A0.31 FOR WALL ASSEMBLIES.
1 2 3 3.9 4 5 5.2 6 6.2 7 8 8.4 8.8 9 10 11 8. SEE FIRE/LIFE SAFETY SHEETS BEGINNING ON SHEET G2.01 FOR LOCATIONS OF FIRE EXTINGUISHER CABINETS.
ELECTRICAL
TANK TYPE: UL 2085 9. SEE ENLARGED PLANS FOR DETAILED DIMENSIONS, WALL TAGS AND DOOR TAGS
FUEL TYPE: DIESEL 10. HM DOOR OPENINGS IN CONCRETE CURBS AND WALLS INCLUDE 1" CONSTRUCTION TOLERANCE. MASONRY OPENINGS
13 14 15 16 17 18 DO NOT INCLUDE ANY TOLERANCE.
FUEL STORAGE: 750 GAL __ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___ __ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___
__ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___ __ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___
__ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___
__ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___

A4.55 A4.55 A4.55 A4.56 A4.56 A4.56 11. MAINTAIN MINIMUM CLEAR HEIGHT OF 98 INCHES, MEASURED VERTICALLY FROM FLOOR LEVEL TO LOWEST OVERHEAD
USEABLE CAPACITY (APPROX 820 17' - 11" 16' - 0"
OBSTRUCTION, COMMENCING AT POINT OF ENTRY OF PARKING GARAGE TO LOCATION OF ALL VAN ACCESSIBLE PARKING 38 NORTHWEST DAVIS, SUITE 300
GAL TOTAL CAPACITY)
STALLS REGARDLESS OF WHERE SUCH STALLS ARE LOCATED IN THE GARAGE. PORTLAND, OR 97209
FLOOR MOUNTED SINGLE ACCESSIBLE CAR
HATCH DENOTING LOCATION 98 INCHES CLEAR IS REQUIRED. 503.245.7100
CHARGING STATION

I 12. GARAGE DRAINS 1'4" PER FOOT UNO. 1505 5TH AVE, SUITE 300
SEATTLE, WA 98101
5' - 0"

1 OPEN TO BELOW FLOOR MOUNTED DUAL CAR CHARGING STATION 1 206.576.1600


4' - 0 181/256"
__ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___ __ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___

11' - 5 1/2"
A4.02 A4.02
H 17' - 9" MDF
1014 HOWARD STREET
BACKUP GENERATOR MPOE SAN FRANCISCO, CA 94103
1 P107 415.252.7063

3' - 2"
4' - 8 3/32" A5.44 P106
4' - 3 1/32" © ANKROM MOISAN ARCHITECTS, INC.
28' - 7 5/8"

6' - 3" DHW


19' - 11"

OPEN
13' - 4"

PUMP RM 20 BIKES
TO
P108 9J.0 9J.1
0 6 BELOW
1 6.0
2 BIKE 2

16' - 0"
__ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___ __ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___

A4.02 ROOM A4.02


P102 P107 P105
8"
FENCING P105
ACCESSIBLE EV
6' - 5 75/256"

G CHARGING
VAN
SPACE
10"

X3.0
0 12

8' - 0" 8' - 0" 8' - 0"


MECHANICAL LOUVER RETAIL ELEVATOR PIT ABOVE
3'-0" 1
21' - 4"

__ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___

WALL MOUNTED DUAL CAR CHARGING STATION A4.51

THE MARK AT SEATTLE


1200 45TH ST SEATTLE, WA 98105
EL: 169'-1" Y3.0
F 2 24
12 5.83% 11.67% 18.03% 11.67% EL: 175'-0"
EL: 175'-0"

3'-0"
__ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___

A4.54 SF37

2"
E
6"

LCD ACQUISITIONS, LLC


P100
2
6' - 5 1/4"

9C.3 SHAFT
__ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___

2 6 9J.0 STAIR 1 CRASH BARS AT 6'-6" A4.51


ST02P1

MECH. 0 6
105' - 0"

PER DETAIL 10/A1.21

SHAFT
S01 3' - 10 3/4" 22' - 0" 16' - 0"
P100A MAINTENCE
P100A P100B RM. BACK-UP CLEARANCE
17' - 0"

EL: 170'-6 1/2" 9C.3

4.81% DOWN (1/2"/12")


16' - 2 1/2" 22' - 1 1/2" P100B 2 6
1 SHAFT 1
__ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___
BACK-UP CLEARANCE ELEV. 4J.2 __ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___

A4.01 2 8 * A4.01
15' - 2 1/8"

4' - 0" 5' - 11 3/4" 4' - 8" UP


LOBBY DN
DN
ELEV 1
UP ELEV 2 P100
E01
5.93%

D STAIR 2 E02 ST01P1


S02 EL: 175'-1"
X3.0 RAILING
5' - 0"

0 14 SHAFT
C
3
11 EL: 173'-11" __ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___

__ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___

9C.4 Y3.0 _ 3 A4.51


A4.54 REVISION DATE REASON FOR ISSUE
1 2 18 A3.13
1 3 5
BACK-UP CLEARANCE

A6.04 A6.21 A6.01


EL: 170'-5"
20' - 0 1/2"
21' - 6"

PARKING
10
__ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___ P110
A4.54

4J.2 1.88% DOWN (0"/12") 6.39% DOWN (1"/12")


0 8 * 4
EL: 173'-11"
__ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___

EL: 170'-6 1/2" EL: 173'-11" A4.52


P103A
B
P103

BOOSTER
PUMP DOMESTIC
SKID
WATER / BIKE
15' - 2 1/2"

SDCI APPROVAL STAMP


BOILER ROOM
15' - 0"
14' - 9"

CW P103 22 BIKES P104


BOOSTER WATER EQUIPMENT /
PUMP RPBP ASSEMBLIES
SKID
A 3
_
A3.14
2
_
A3.14
X3.0
36' - 5" 0 12

15' - 2" 21' - 0" 14' - 5" 9' - 3" 2' - 10" 17' - 8" 9' - 5 1/2" 9' - 2 1/2" 8' - 5" 2' - 9" 17' - 3" 14' - 9"

9
__ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___
8
__ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___
7
__ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___
6
__ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___
5
__ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___
LEVEL P1 FLOOR
A4.53 A4.53 A4.53 A4.52 A4.52
142' - 2" PLAN
1' - 1 1/2"
1' - 10"
BIM 360://Seattle II/210310-20-Seattle II.rvt

60% CD SET

3
__ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___
2
__ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___

A4.02 A4.01
DATE PROJECT NUMBER
11/18/2022 210310

1 LEVEL P1 - PLAN
1/8" = 1'-0"
SHEET NUMBER

A2.P01
NORTH
11/18/2022 10:24:24 AM
GENERAL NOTES - SLAB PLANS
1.
2.
REFER TO SHEET A0.01 FOR 'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK.
ELEVATION TAGS INDICATE TOP OF CONCRETE, UNLESS NOTED OTHERWISE.
NOT FOR
3. VERIFY AND COORDINATE SLAB PENETRATIONS INCLUDING SLEEVES & BLOCKOUTS AS REQUIRED FOR PLUMBING,
MECHANICAL, ELECTRICAL, ETC. NOTIFY ARCHITECT OF ANY CONFLICTS OR DISCREPENCIES. CONSTRUCTION
4. PROVIDE SLAB BLOCKOUTS FOR RECESSED DOOR HARDWARE.
5. SLAB PLANS INDICATE LAYOUT DIMENSIONS FOR CONCRETE SLABS, CURBS, CONCRETE WALLS, DEPRESSIONS, AND SLOPES,
ONLY. REFER TO STRUCTURAL FOR ADDITIONAL REQUIREMENTS.
6. ROOF, DECK AND BALCONY SLABS SLOPE TO DRAIN 1/4" PER FT, UNO.
7. VERIFY HOISTWAY CLEARANCES, ROUGH OPENING REQUIREMENTS (ELEVATOR DOORS, LOUVERS, ETC.) AND NOTIFY
3
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ ARCHITECT OF ANY DISCREPENCIES.
A4.02 A4.01 8. PROVIDE HOUSEKEEPING PADS REQUIRED FOR FLOOR-MOUNTED EQUIPMENT AS REQUIRED OR AS INDICATED ON MEP OR
FIRE PROTECTION DRAWINGS.
9. PROVIDE CAST OR SAWN CONTROL JOINTS IN SLABS ON GRADE AT LOCATIONS INDICATED ON STRUCTURAL OR
1 2 3 3.9 5 5.2 6.2 7 8.4 8.8 9 10 11 ARCHITECTURAL DRAWINGS. IN THE EVENT OF CONFLICT, NOTFIY THE ARCHITECT PRIOT TO PLACEMENT OF CONCRETE.
10. CONFORM TO VAPOR BARRIER OR WATERPROOF MEMBRANE MANUFACTURERS MINIMUM SPACING REQUIREMENTS
BETWEEN MULTIPLE ADJACENT PENETRATIONS.
11. ALIGN EDGE OF SLAB WITH FACE OR ADJACENT COLUMN OR CONCRETE WALL, UNLESS NOTED OTHERWISE.
38 NORTHWEST DAVIS, SUITE 300
PORTLAND, OR 97209
503.245.7100

I 1505 5TH AVE, SUITE 300


SEATTLE, WA 98101
5' - 0"

1
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
1
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
206.576.1600
A4.02 A4.02
H
1014 HOWARD STREET
SAN FRANCISCO, CA 94103
415.252.7063
© ANKROM MOISAN ARCHITECTS, INC.
19' - 11"

2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.02 A4.02
10"

2' - 4 3/4"
G
SLAB PLAN LEGEND

4"

4"
8"
3"

5.83% 3' - 0 1/2"


18.03% 11.67% SLAB STEP

EL: 175'-10 1/2"


21' - 4"

OVERFRAMING
EL: 175'-3 1/2"

THE MARK AT SEATTLE


1200 45TH ST SEATTLE, WA 98105
SLAB BREAK LINE, UNO

EL: 169'-1"

F SLAB ON GRADE
21' - 2 3/4" 6' - 0" 21' - 2 1/4" EL: 175'-0"
EL: 169'-1"
6"

E RAMP ON GRADE

LCD ACQUISITIONS, LLC


4' - 7"
1'-2"

8' - 11 3/4"
CONCRETE CURB
105' - 0"

2 1/4"

7" 2' - 9"

1' - 2"
7' - 2 1/2"
17' - 0"

FLOOR DRAIN FD
8 3/4"

4.81%
1 1
5.93%

8"
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.01 A4.01 ROOF DRAIN WITH OVERFLOW

5' - 6"
D
4' - 7"
5' - 0"

EL: 170'-5"
C
EL: 173'-11"
REVISION DATE REASON FOR ISSUE
21' - 6"

EL: 170'-6 1/2"


6.39% EL: 173'-11"

B
3' - 0 1/2"

SDCI APPROVAL STAMP


14' - 9"

5' - 5"
3' - 8 1/2"

3' - 8 1/2"
2' - 2"

2' - 2"
2' - 7"
1' - 0"

2' - 2" 4' - 4 1/2"


A

LEVEL P1 SLAB PLAN

15'-2" 21'-0" 14'-5" 9'-3" 2'-10" 17'-8" 9'-5 1/2" 9'-2 1/2" 8'-5" 2'-9" 17'-3" 14'-9"
142' - 2"
BIM 360://Seattle II/210310-20-Seattle II.rvt

60% CD SET
3
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.02 A4.01

DATE PROJECT NUMBER


11/18/2022 210310

1 LEVEL P1 - SLAB PLAN


1/8" = 1'-0"
SHEET NUMBER

A2.P01S
PROJECT
11/18/2022 10:22:37 AM
GENERAL NOTES - FLOOR PLANS
1.
2.
REFER TO SHEET A0.01 FOR 'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK.
PRIOR TO FRAMING VERIFY THAT FINAL APPLIANCE AND PLUMBING FIXTURE SIZES/CLEARANCES MATCH THOSE USED AS
NOT FOR
3.
BASIS OF DESIGN SHOWN ON DRAWING A5.01.
REFERENCE SLAB PLANS FOR CONCRETE WALL LOCATIONS, UNO. COORDINATE WITH STRUCTURAL DRAWINGS. CONSTRUCTION
4. SEE SHEETS A0.21 & A0.31 FOR WALL ASSEMBLIES.
5. SEE SHEET A0.41 FOR TYPICAL FRAMING AND ACOUSTICAL DETAILS.
6. SEE FIRE/LIFE SAFETY SHEETS BEGINNING ON G2.00 SERIES FOR LOCATIONS OF FIRE EXTINGUISHER CABINETS. (NONE
LOCATED YET)
7. SEE SHEETS BEGINNING ON A5.01 FOR TYPICAL ACCESSIBILITY CLEARANCES. SEE SHEETS BEGINNING ON G3.01 FOR
3 2 ACCESSIBLE ROUTE.
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

_ 1 _ 2 G
_
A4.02 A4.01 8. REFER TO ENLARGED UNIT PLANS (A5.2x - A5.3X SERIES) FOR DETAILED INFORMATION WITHIN EACH RESIDENTIAL UNIT
A3.12 A3.05 A4.56
9. REFER TO STRUCTURAL DRAWINGS FOR COLUMNS, SHEAR WALL AND BEAM SIZES.
10. UNIT DEMISING WALLS SHALL BE WALL TYPE 9A.2 TYPICAL UNO.
11. CORRIDOR WALLS SHALL BE WALL TYPE 9C.1 TYPICAL UNO.
1 2 3 3.9 4 5 5.2 6 6.2 7 8 8.4 8.8 9 10 11
12. PROVIDE CONTROL JOINTS PER DETAIL 9/A0.44 AS WALL ASSEMBLY RATING REQUIRES AT 30' MAXIMUM SPACING OR AS
13 14 OTHERWISE INDICATED PER PLAN. ALIGN JOINTS WITH CEILING CONTROL JOINTS.
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
15
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
16
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
17 18
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.55 A4.55 A4.55 A4.56 A4.56 A4.56


38 NORTHWEST DAVIS, SUITE 300
4' - 9" 10' - 5"

X3.0
21' - 0" 21' - 2 1/8" 61' - 9 7/8"

LEED
8' - 3"
GENERAL NOTES PORTLAND, OR 97209
503.245.7100
3 20
I
PACKAGE
HOLDING
SHOWER
ROOM
PARKING LEVEL FLOOR PLANS 1505 5TH AVE, SUITE 300
SEATTLE, WA 98101
5' - 0"

5' - 0"
X3.5
1 108 118 1 206.576.1600

5' - 4"
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
36' - 5" 0 10 __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
1. REFER TO SHEET A0.01 FOR 'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK.
A4.02 X3.5 A4.02
H 0 10 2. PROVIDE STEEL ANGLE CORNER GUARDS FROM FINISH FLOOR TO 4’-0” ABOVE FINISH FLOOR AT ALL COLUMN LOCATIONS
EXPOSED TO DRIVE AISLES AND PARKING STALLS AND AS SHOWN. 1014 HOWARD STREET
4J.2 191'-9 3/4" SAN FRANCISCO, CA 94103
SHAFT 9J.1 IDF 3. PROVIDE GUARDS AT EXPOSED PIPING AND CONDUITS.

4' - 4"
2 8 4J.2 HVAC 415.252.7063
CONC TRANSFORMER 418 1 6.0 FD 4. PROVIDE BOLLARDS TO PROTECT DUCTS, EQUIPMENT AND OTHER CONSTRUCTION FROM IMPACT BY VEHICLES, IN
2 8 109 DN
EXHAUST SHAFT PARCEL 124 ACCORDANCE WITH DETAIL 11/A1.21. © ANKROM MOISAN ARCHITECTS, INC.

18' - 0 5/8"
3HR TRANS RM UP

109

118
106 5. SEE SLAB PLANS FOR CONCRETE WALL LOCATIONS, UNO. COORDINATE WITH STRUCTURAL DRAWINGS
23' - 4"

3' - 8"
ABOVE TRANSFORMER Y3.0 104D
INTAKE LOUVRE 9J.1 E3.1

20' - 5 3/4"
7' - 2" 108 Y3.0 6. REFER TO STRUCTURAL DRAWINGS FOR COLUMNS, SHEAR WALL AND BEAM SIZES.
19' - 11"

104 3 10 9J.0 1 6.0 0 6 DN


W/ FIRE DAMPER 9J.1 0 10 3 7. SEE SHEETS A0.21, A0.31 FOR WALL ASSEMBLIES.
0 6 106
4J.0 4x4x1/4" ANGLE 18" A.F.F. MAILROOM 1 6.0 A6.08

4' - 4"
EL: 189'-6" 8. SEE FIRE/LIFE SAFETY SHEETS BEGINNING ON SHEET G2.01 FOR LOCATIONS OF FIRE EXTINGUISHER CABINETS.
0 8 BACK DAM 107 9J.1
2 125 1 6.0 2 9. SEE ENLARGED PLANS FOR DETAILED DIMENSIONS, WALL TAGS AND DOOR TAGS
PAINTED YELLOW
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.02 A4.02 10. HM DOOR OPENINGS IN CONCRETE CURBS AND WALLS INCLUDE 1" CONSTRUCTION TOLERANCE. MASONRY OPENINGS

6' - 5 3/8"

119
EL: 187'-0" 201 DO NOT INCLUDE ANY TOLERANCE.
2x2x2 SUMP 104B 8" DN 9 EL: 188'-0" DN
EL: 188'-0" 11. MAINTAIN MINIMUM CLEAR HEIGHT OF 98 INCHES, MEASURED VERTICALLY FROM FLOOR LEVEL TO LOWEST OVERHEAD
EL: 183'-0" A6.09 EL: 189'-5"
EL: 180'-9" 1 120 OBSTRUCTION, COMMENCING AT POINT OF ENTRY OF PARKING GARAGE TO LOCATION OF ALL VAN ACCESSIBLE PARKING
EL: 188'-0"
G A6.24 S4 1
_ STALLS REGARDLESS OF WHERE SUCH STALLS ARE LOCATED IN THE GARAGE.
MECH
104C

3' - 4"
A3.15

121A
104 9C.3 E5.1 HATCH DENOTING LOCATION 98 INCHES CLEAR IS REQUIRED.
1 2 6 CORR. 205 187'-6"
1 6
Y3.0 A6.05 Y3.0 FIRE 104A 9J.1 RETAIL 12. GARAGE DRAINS 1'4" PER FOOT UNO.
DN 3 12 1 12
COMMAND MAILBOXES 1 6.0 9J.1 ELEVATOR ELEVATOR 5' TO HYDR
ANTS AND
VAULTS

8' - 0"
OPEN TO PARKING SF17

M.O.
1 6.0
9C.3
CENTER MACHINE
3 RAMP BELOW 2 6 LOBBY
ROOM

DRIVE AISLE
103 RETAIL 120 EL: 188'-1 1/4" 1
21' - 4"

A6.05 180'-3" 5.83% 11.67% EL: 179'-4 1/2" 18.03% 121C

20' - 1"
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

22' - 3"
121A
K

2' - 0"
R SIDEWAL

121B A4.51
. CLEA

N.I.C.
6' MIN

7 EL: 188'-0" EL: 187'-11 1/2"

104AA

THE MARK AT SEATTLE


5 32 SF
EL: 179'-11 1/2" A6.09 121

1200 45TH ST SEATTLE, WA 98105


180'-2 1/2" A6.09 ELEVATOR
CONTROLLER SF16

5' - 4"
M.O.
A
_
F 56' - 3 3/4" 13' - 7 3/8" 6' - 1" 4' - 7" 188'-0" 49' - 5 7/8"
90' - 3"

PROTECTED PLASTIC CORRIDOR A4.51


12
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

WRAP AROUND COLUMN 9M.0 103A 105 9C.1


A4.54 EL: 180'-0" 1 6
E 0 2.5 DN

4' - 0"
EL: 180'-3" EL: 180'-3"
S0101
CL

LCD ACQUISITIONS, LLC


100C
6.67%

6.67%
6"

2
SHAFT STAIR 1 EGRESS 9J.1
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
9' - 3"

4' - 8"
A4.51

SHAFT

M.O.
EL: 180'-7"
EL: 180'-7" MECHANICAL 122D 1 6.0 186'-6"
1 EL: 180'-7" STAIR 2 S01 S01A
105' - 0"

54' - 0"
100A STORAGE 3 SF15
9J.0
13.33%
13.33%

A3.05
100BELEC.
R1 S02 100A
0' - 0 6 DN UP 122D A6.07
0"

1' - 4"
17' - 0"

100B
EL: 181'-3"
WORKROOM 122C
6" 116
117 RR
1 EL: 181'-3" DW SHAFT ELEV. 1

8' - 0"
M.O.
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
122C __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

E
_ A4.01 RR 115 LOBBY SF14 A4.01
A4.54 12' - 8" 3' - 0" 10' - 0" 9J.0
115 REF 100
ELEV 1 0 6
DN ELEV 2
E01 RR

2' - 8" 4' - 0"


D UP E02
4J.0 EGRESS EL: 187'-1" 186'-3 3/8"
117

0 8 122B 1
_
5' - 0"

9J.0 S02A
DN SHAFT 122B 2 A3.06

M.O.
0 6 _
SF13 A3.13
C
S0201

1 3
11 9M.2 114 __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

1' - 4"
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

0 * Y3.0 A6.07 SF12 _ 3 A4.51


A4.54 3 REVISION DATE REASON FOR ISSUE
1 2 18 1 BUSINESS A3.13

8' - 0"
NEIGHBORHOOD OPEN 1 Date 2 Permit Corrections #2 (first

M.O.
A6.22 A6.09 A6.02 DN
OFFICE 3 N.I.C. E5.1 185'-6 1/2" SPACE was 100% DD set)
X3.0 9J.0 2
CRASH BAR AT 8'-2" 0 6 114 122 1 6 SEE G1.12 AND
0 14 A6.04 LOBBY DESK
PER DETAIL 10/A1.21 9M.0 9J.1 LANDSCAPE DRAWINGS
21' - 6"

0 3.63 1 6.0
EL: 186'-6" RECEPTION
1
_
10 26' - 10 1/4" OFFICE 2 65' - 6 7/8" 30' - 3 3/4" EL: 184'-0"
113 101
A3.11 __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

113
A4.54 122A 1
_

32' - 6 3/8"
EL: 186'-7 5/8" A3.13
OVERHEAD GARAGE EL: 184'-0"
S2 4
20.09%

VAULTS
ANTS AND

DOOR 111 5' TO HYDR


__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

9J.0
101B

A4.52

23' - 0 1/4"
0 6

23' - 0 1/4"
EL: 186'-6" VESTIBULE
B
110
19.86%

EL: 184'-0"
K
R SIDEWAL

S1
. CLEA
6' MIN

101A B
4' - 9"

9J.1 _
188'-7 1/8" 3 LEASING LEASING EL: 186'-10 3/4" A4.52
112 1 6.0 EL: 183'-4"
A5.20 111 OFFICE CW1 DN
101A

SIGHT TRIANGLE EL: 188'-11 7/8"


EL: 188'-0 3/4" MANAGER 110
BUILDING INTERCOM 1
SDCI APPROVAL STAMP
PARKING
14' - 9"

E5.1 A6.08
3.15% 12.49%

PER EXHIBIT E 112 SF5


S5.2 9J.0 1 6
8' - 11 5/8"

23.54.030 GARAGE
10' - 0"

E5.1 1 6 0 6 EL: 182'-11"


1 6 1
130 9J.0 E5.1 __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

EL: 189'-3"

1' - 4"
9M.0 1 6 A4.57
10' - 0" 0 6 EL: 182'-10"
0 3.63

2' - 0"

2' - 6"
EL: 189'-8" EL: 183'-6"
EL: 189'-1 1/2" SF6 SF7 SF8 SF9 SF10 SF11
A _ 3
EL: 189'-0 1/2" EL: 188'-6" SF1 SF2 SF3 SF4 EL: 186'-6" A3.14 EL: 186'-2" EL: 182'-9"
1' - 4" 1' - 4" 1' - 4" 1' - 4" 1' - 4" 1' - 4"
_ 2
SIGHT TRIANGLE PER 4' - 6" 10' - 0" 3' - 0" 10' - 0" 2' - 8" 5' - 4" 2' - 8" 5' - 4" 7' - 4" 3' - 4" 8' - 0" 11' - 9 5/8" 3' - 4 5/8" 8' - 0" 4' - 0" 2' - 8" 8' - 0" 3' - 4" 3' - 4" 2' - 8" 8' - 0" 7' - 4"
A3.14
6' MIN. CLEAR SIDEWALK

6' MIN. CLEAR SIDEWALK

6' MIN. CLEAR SIDEWALK

CANOPY ABOVE
5' TO HYDRANTS AND VAULTS

5' TO HYDRANTS AND VAULTS

5' TO HYDRANTS AND VAULTS


EXHIBIT F 23.54.030 5 1/4" M.O. M.O. M.O. M.O. M.O. M.O. M.O. M.O. M.O.

EXISTING STRAIN POLE


CANOPY ABOVE CANOPY ABOVE RELOCATED PARKING METER EXISTING STRAIN POLE
(TO BE REMOVED)
PEDESTRAIN SAFETY
ALERT SIGN 9
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
8
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
7
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
6
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
5
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
LEVEL 1 FLOOR PLAN
A4.53 A4.53 A4.53 A4.52 A4.52

15' - 2" 21' - 0" 14' - 5" 9' - 3" 2' - 10" 17' - 8" 9' - 5 1/2" 4' - 4 1/2" 4' - 10" 8' - 5" 2' - 9" 17' - 3" 14' - 9"
27' - 11 1/4" 37' - 4" 60' - 6 1/4" 7' - 4"
BIM 360://Seattle II/210310-20-Seattle II.rvt

1' - 10" 142' - 2"


60% CD SET
1' - 1 1/2"

3 D 1
_ C 2 2
_
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ _ _ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.02 A4.53 A3.14 A4.52 A4.01 A3.06

DATE PROJECT NUMBER


11/18/2022 210310

1 LEVEL 1 - PLAN
1/8" = 1'-0"
SHEET NUMBER

A2.01
NORTH
11/18/2022 10:22:41 AM
GENERAL NOTES - SLAB PLANS
1.
2.
REFER TO SHEET A0.01 FOR 'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK.
ELEVATION TAGS INDICATE TOP OF CONCRETE, UNLESS NOTED OTHERWISE.
NOT FOR
3. VERIFY AND COORDINATE SLAB PENETRATIONS INCLUDING SLEEVES & BLOCKOUTS AS REQUIRED FOR PLUMBING,
MECHANICAL, ELECTRICAL, ETC. NOTIFY ARCHITECT OF ANY CONFLICTS OR DISCREPENCIES. CONSTRUCTION
4. PROVIDE SLAB BLOCKOUTS FOR RECESSED DOOR HARDWARE.
5. SLAB PLANS INDICATE LAYOUT DIMENSIONS FOR CONCRETE SLABS, CURBS, CONCRETE WALLS, DEPRESSIONS, AND SLOPES,
ONLY. REFER TO STRUCTURAL FOR ADDITIONAL REQUIREMENTS.
6. ROOF, DECK AND BALCONY SLABS SLOPE TO DRAIN 1/4" PER FT, UNO.
7. VERIFY HOISTWAY CLEARANCES, ROUGH OPENING REQUIREMENTS (ELEVATOR DOORS, LOUVERS, ETC.) AND NOTIFY
3
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ ARCHITECT OF ANY DISCREPENCIES.
A4.02 A4.01 8. PROVIDE HOUSEKEEPING PADS REQUIRED FOR FLOOR-MOUNTED EQUIPMENT AS REQUIRED OR AS INDICATED ON MEP OR
FIRE PROTECTION DRAWINGS.
9. PROVIDE CAST OR SAWN CONTROL JOINTS IN SLABS ON GRADE AT LOCATIONS INDICATED ON STRUCTURAL OR
1 2 3 3.9 5 5.2 6.2 7 8.4 8.8 9 10 11 ARCHITECTURAL DRAWINGS. IN THE EVENT OF CONFLICT, NOTFIY THE ARCHITECT PRIOT TO PLACEMENT OF CONCRETE.
10. CONFORM TO VAPOR BARRIER OR WATERPROOF MEMBRANE MANUFACTURERS MINIMUM SPACING REQUIREMENTS
BETWEEN MULTIPLE ADJACENT PENETRATIONS.
11. ALIGN EDGE OF SLAB WITH FACE OR ADJACENT COLUMN OR CONCRETE WALL, UNLESS NOTED OTHERWISE.
38 NORTHWEST DAVIS, SUITE 300
PORTLAND, OR 97209
503.245.7100
EL: 188'-0"
I 1505 5TH AVE, SUITE 300

0" / 12"
SEATTLE, WA 98101
5' - 0"

1
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
EL: 188'-1" 1
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
206.576.1600
A4.02 A4.02
H

9"
1014 HOWARD STREET
4' - 4 1/4" SAN FRANCISCO, CA 94103
415.252.7063
© ANKROM MOISAN ARCHITECTS, INC.
19' - 11"

B.O. SUMP EL: 180'-9"

EL: 188'-0"
2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.02 EL: 182'-9" A4.02


8"

6' - 6"

6' - 6"
10"

4"

2' - 4 3/4"
G

1' - 4"

3' - 2 1/2"
8" 3" SLAB PLAN LEGEND
EL: 183'-0"

8' - 3"

8' - 3"
3' - 0 1/2"
SLAB STEP
EL: 188'-0" 187'-7"
187'-9"
21' - 4"

EL: 180'-3" EL: 179'-4 1/2" OVERFRAMING

0" / 12"

THE MARK AT SEATTLE


EL: 179'-11 1/2"

1200 45TH ST SEATTLE, WA 98105


SLAB BREAK LINE, UNO

EL: 187'-0"
F SLAB ON GRADE
21' - 2 3/4" 6' - 0" 21' - 2 1/4"
EL: 180'-3" EL: 180'-3"
6"

9"
E RAMP ON GRADE

LCD ACQUISITIONS, LLC


6' - 2" 4' - 7"

8' - 11 3/4"
1' - 2" 5' - 4"
EL: 180'-7" EL: 180'-7"
CONCRETE CURB
105' - 0"

EL: 187'-1"

1' - 2"
T.O. WALL EL: 188'-0"
17' - 0"

EL: 181'-3" 7" 2' - 9" FLOOR DRAIN FD


EL: 181'-3"
1 EL: 184'-0" 1
9' - 9"

7' - 2 1/2"
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.01 A4.01 ROOF DRAIN WITH OVERFLOW

5' - 6" 8"


7"
T.O. WALL EL: 187'-6"

1' - 6"
6"

D
CL

CL

10"
5' - 0"

4' - 5" DN

C CL
T.O. WALL EL: 187'-0"

REVISION DATE REASON FOR ISSUE


1 Date 2 Permit Corrections #2 (first
was 100% DD set)
EL: 184'-0" T.O. WALL EL: 186'-6"
EL: 186'-6"
21' - 6"

EL: 186'-7 5/8"

EL: 187'-7 3/4"


B
T.O. WALL EL: 189'-6" T.O. WALL EL: 188'-0" 3' - 0 1/2"
10' - 8 1/2"

EL: 188'-6"
10' - 11"

12' - 7"
SUB SLAB EL: 188'-10 1/2" EL: 186'-6" SDCI APPROVAL STAMP
14' - 9"

EL: 189'-1 1/2"


183'-2"

EL: 188'-6" 2' - 2" 4' - 4 1/2"


A 5' - 5"
SUB SLAB EL: 189'-1 1/2" T.O. TRELLIS EL: 186'-0" T.O. WALL EL: 185'-0"
T.O. WALL EL: 188'-7" T.O. WALL EL: 188'-0"
T.O. WALL EL: 186'-6" T.O. WALL EL: 185'-6"
T.O. WALL EL: 189'-1" T.O. WALL EL: 188'-6"

LEVEL 1 SLAB PLAN

15'-2" 21'-0" 14'-5" 9'-3" 2'-10" 17'-8" 9'-5 1/2" 9'-2 1/2" 8'-5" 2'-9" 17'-3" 14'-9"
142' - 2"
BIM 360://Seattle II/210310-20-Seattle II.rvt

60% CD SET
3
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.02 A4.01

DATE PROJECT NUMBER


11/18/2022 210310

1 LEVEL 1 - SLAB PLAN


1/8" = 1'-0"
SHEET NUMBER

A2.01S
PROJECT
11/18/2022 10:22:49 AM
GENERAL NOTES - FLOOR PLANS
1.
2.
REFER TO SHEET A0.01 FOR 'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK.
PRIOR TO FRAMING VERIFY THAT FINAL APPLIANCE AND PLUMBING FIXTURE SIZES/CLEARANCES MATCH THOSE USED AS
NOT FOR
3.
BASIS OF DESIGN SHOWN ON DRAWING A5.01.
REFERENCE SLAB PLANS FOR CONCRETE WALL LOCATIONS, UNO. COORDINATE WITH STRUCTURAL DRAWINGS. CONSTRUCTION
4. SEE SHEETS A0.21 & A0.31 FOR WALL ASSEMBLIES.
5. SEE SHEET A0.41 FOR TYPICAL FRAMING AND ACOUSTICAL DETAILS.
6. SEE FIRE/LIFE SAFETY SHEETS BEGINNING ON G2.00 SERIES FOR LOCATIONS OF FIRE EXTINGUISHER CABINETS. (NONE
LOCATED YET)
7. SEE SHEETS BEGINNING ON A5.01 FOR TYPICAL ACCESSIBILITY CLEARANCES. SEE SHEETS BEGINNING ON G3.01 FOR
3 F
_ 1
_ 2 1 2 ACCESSIBLE ROUTE.
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

_ _ G
_
A4.02 A4.55 xA3.91 A4.01 A3.12 A3.05 SHARED CAFE/PEDESTRIAN CONNECTION 8. REFER TO ENLARGED UNIT PLANS (A5.2x - A5.3X SERIES) FOR DETAILED INFORMATION WITHIN EACH RESIDENTIAL UNIT
A4.56
AND TEMPORARY TRUCK LOADING AREA 9. REFER TO STRUCTURAL DRAWINGS FOR COLUMNS, SHEAR WALL AND BEAM SIZES.
INCLUDING TRASH PICKUP 10. UNIT DEMISING WALLS SHALL BE WALL TYPE 9A.2 TYPICAL UNO.
11. CORRIDOR WALLS SHALL BE WALL TYPE 9C.1 TYPICAL UNO.
1 11
2 3 3.9 4 5 5.2 6 6.2 7 8 8.4 8.8 9 10 12. PROVIDE CONTROL JOINTS PER DETAIL 9/A0.44 AS WALL ASSEMBLY RATING REQUIRES AT 30' MAXIMUM SPACING OR AS
13 14 OTHERWISE INDICATED PER PLAN. ALIGN JOINTS WITH CEILING CONTROL JOINTS.
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
SIM __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
15
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
16
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
17 18
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.55 A4.55 A4.55 A4.56 A4.56 A4.56


5 38 NORTHWEST DAVIS, SUITE 300
A5.41 PORTLAND, OR 97209
15' - 2" 44' - 3 3/4" 31' - 9 1/8" 50' - 11 1/8"
503.245.7100
BACK-UP GENERATOR
I X3.5 FUEL FILL STATION
1505 5TH AVE, SUITE 300
1' - 5 3/8"

0 8 SEATTLE, WA 98101
5'-0"

5'-0"
1 X3.5 1 206.576.1600
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
3 6 5' - 3" EL: 199'-0" EL: 196'-7 1/2"
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.02 EL: 190'-10" A4.02


H 250
X3.4 1014 HOWARD STREET
X3.0 GAS METER 0 10 SAN FRANCISCO, CA 94103
2 10 ALCOVE 3 EL: 190'-7"
_ 415.252.7063

2 9/128
MURAL/ART A3.15 5
© ANKROM MOISAN ARCHITECTS, INC.
X3.5 WALL

3%
A6.07
0 10 Y3.0 Y3.0 6'-11" E5.2

3.2
"
RAMP ABOVE Y3.0 2 10 2 10 EL: 198'-0" T.O. DRAIN EL: 197'-11" DN
205A 0 6

20'-5 3/4"
19'-11"

2 10 EL: 198'-0"
X3.0 [No Slope]

2 3/8"
2 10 UP
2 E5.1 E3.1 2
ELEC.

10' - 0 5/8"
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

9C.3 0 6 __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.02 1 6 A4.02
203 2 6 S5
8' - 0"
ELEC. 3' - 3 1/4"
1 11' - 4" 3' - 4"
9J.1
203A 1 6.0
G SF19 SF18 1
39' - 11"

221A
STUDY

3' - 4"
EL: 198'-0" E5.1 A3.15
1' - 4" 1 6
9C.3 TRASH AREA
2 6
4J.2 ROOM 9M.0 206 9J.1 9M.0
TRASH STAGING 27' - 0 1/2"
2 8 0 2.5 1 6.0 0 2.5
203B

AREA ABOVE 204 SF17

8' - 0"
221B
2 RETAIL
A6.24 221 1
21'-4"

34' - 9 3/4" 42' - 11 3/4" 6' - 6 7/8" 7' - 8 1/8" 5' - 0 1/4" 33' - 0 1/8"
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.51

THE MARK AT SEATTLE


2' - 0"
4J.2
2 8

1200 45TH ST SEATTLE, WA 98105


X3.0 STEEL POSTS

204

207
206

5' - 4"
0 12 OPEN TO A
RR AND CROSS BEAM SF16 _

5' - 0 1/4"
Y3.0 CORRIDOR 9C.1 BELOW A4.51
F 12 207 1 6 SUPPORT FOR
1 24
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

203 200.1 9J.1 STOREFRONT


6"

A4.54

ST0102
1 6.0

4' - 0"
E

LCD ACQUISITIONS, LLC


2
SHAFT EGRESS __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

4' - 8"
A4.51
1 MECH. ELEC. S01B SF15
_ STAIR 2

SHAFT
9x.x DN

54'-0"
A3.05 BIKE 1 6.0 S02 M107 200A UP
17' - 9 1/4"

9M.2 200B 200A


105'-0"

ROOM
17'-0"

0 * 54 BIKES (7 ARE 5' - 0" 5' - 5" 21' - 10 1/8"

1' - 4"
202 S6
ACCESSIBLE) 202
1 SHAFT 1

8' - 0"
ELEV.
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

E
_ A4.01 SF14 A4.01
A4.54 OPEN TO
9x.x 9M.0 LOBBY MTL CANOPY
1 6.0 0 6 ELEV 2 ELEV 1 STAIR 1 9J.0 BELOW
200 S01 0 6 BELOW
9J.0 UP E02 E01

2' - 8" 4' - 0"


D 0 6 DN
MAINT STEEL POSTS AND CROSS BEAM 1
_
ST0202
5'-0"

201B 201A SHAFT SUPPORT FOR STOREFRONT 2 A3.06


CORR SF13
_
A3.13
C 201A
TBD 3
11 9J.0
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

1' - 4"
CONC SLAB __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

9M.0 2 _ 3 A4.51
A4.54 0 6 3 REVISION DATE REASON FOR ISSUE
0 3.63 A6.02 SF12 A3.13

8' - 0 3/4"
OPEN TO A6.04 2 Y3.0 1 Date 2 Permit Corrections #2 (first
BELOW A6.22 2 18 5
OPEN TO was 100% DD set)
4J.0 OPEN TO BELOW A7.51
0 8 BELOW
30' - 10 3/8"
21'-6"

9J.0 OPEN TO
1

1' - 3"
_ 0 6
A3.11
10
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
CONDENSER OPEN TO STEEL POSTS AND CROSS BEAMS FOR BELOW
A4.54 BELOW 9M.0 STOREFRONT ENTRY & VESTIBULE 1
FARM 9J.1 _
STEEL BEAMS AND 0 3.63 1 6.0 OPEN TO A3.13
201B 9J.0
OPEN GRATING FOR 0 6 BELOW
4
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

CONDENSER FARM A4.52

21' - 8 1/2"

23'-0 1/4"
S2
B OPEN TO
S1 B
_
OPEN TO BELOW STEEL POST
9J.0 CW1 A4.52
BELOW 0 6
E5.1 9M.0 STEEL CROSS BEAMS SDCI APPROVAL STAMP
0 3.63 E5.1
14'-9"

1 6 STEEL POSTS AND CROSS BEAM SF5 SUPPORT FOR STOREFRONT


E5.1 1 6

1' - 4"
SUPPORT FOR STOREFRONT
10' - 0"

1 6
1
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

9M.0 A4.57
0 3.63

2'-6"
SF6 SF7 SF8 SF9 SF10 SF11
A 3
_
SF1 SF2 SF3 SF4 A3.14
2
_
A3.14 MTL & LAM / TEM GLASS
CANOPY BELOW
MTL CANOPY EXISTING STRAIN POLE
MTL CANOPY BELOW MTL CANOPY BELOW (TO BE REMOVED)
1 4'-0"
2 BELOW MTL & LAM / TEMP 4
3 EXISTING STRAIN POLE
A7.51 (TO BE REMOVED) A7.51 1'-4"
A7.51
1'-4" GLASS CANOPY BELOW A7.51 1'-4"
M.O.
1'-4" 1'-4" 1'-4"
NEW EYE BOLT TO BE INSTALLED
ON BUILDING STRUCTURE
LEVEL 2 FLOOR PLAN
27'-1 1/4" 2'-8" 5'-4" 2'-8" 5'-4" 7'-4" 3'-4" 8'-0" 15'-2 1/4" 8'-0" 2'-8" 8'-0" 3'-4" 3'-4" 2'-8" 8'-0" 7'-4"
M.O. M.O. M.O. M.O. M.O. M.O. M.O. M.O. M.O.
2'-7" 2'-2"
15'-2" 21'-0" 14'-5" 6'-8" 2'-10" 15'-6" 9'-5 1/2" 4'-10" 8'-5" 2'-9" 17'-3" 14'-9"

9 8 7 6 5 4'-4 1/2"
BIM 360://Seattle II/210310-20-Seattle II.rvt

60% CD SET
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.53 A4.53 A4.53 A4.52 A4.52


1'-10" 1'-1 1/2"
142'-2"

3 D 1
_ C 2 2
_
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ _ _ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.02 A4.53 A3.14 A4.52 A4.01 A3.06

DATE PROJECT NUMBER


11/18/2022 210310

1 LEVEL 2 - PLAN
1/8" = 1'-0"
SHEET NUMBER

A2.02
NORTH
11/18/2022 10:22:52 AM
GENERAL NOTES - SLAB PLANS
1.
2.
REFER TO SHEET A0.01 FOR 'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK.
ELEVATION TAGS INDICATE TOP OF CONCRETE, UNLESS NOTED OTHERWISE.
NOT FOR
3. VERIFY AND COORDINATE SLAB PENETRATIONS INCLUDING SLEEVES & BLOCKOUTS AS REQUIRED FOR PLUMBING,
MECHANICAL, ELECTRICAL, ETC. NOTIFY ARCHITECT OF ANY CONFLICTS OR DISCREPENCIES. CONSTRUCTION
4. PROVIDE SLAB BLOCKOUTS FOR RECESSED DOOR HARDWARE.
5. SLAB PLANS INDICATE LAYOUT DIMENSIONS FOR CONCRETE SLABS, CURBS, CONCRETE WALLS, DEPRESSIONS, AND SLOPES,
ONLY. REFER TO STRUCTURAL FOR ADDITIONAL REQUIREMENTS.
6. ROOF, DECK AND BALCONY SLABS SLOPE TO DRAIN 1/4" PER FT, UNO.
7. VERIFY HOISTWAY CLEARANCES, ROUGH OPENING REQUIREMENTS (ELEVATOR DOORS, LOUVERS, ETC.) AND NOTIFY
3
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ ARCHITECT OF ANY DISCREPENCIES.
A4.02 A4.01 8. PROVIDE HOUSEKEEPING PADS REQUIRED FOR FLOOR-MOUNTED EQUIPMENT AS REQUIRED OR AS INDICATED ON MEP OR
FIRE PROTECTION DRAWINGS.
9. PROVIDE CAST OR SAWN CONTROL JOINTS IN SLABS ON GRADE AT LOCATIONS INDICATED ON STRUCTURAL OR
1 2 3 3.9 5 5.2 6.2 7 8.4 8.8 9 10 11 ARCHITECTURAL DRAWINGS. IN THE EVENT OF CONFLICT, NOTFIY THE ARCHITECT PRIOT TO PLACEMENT OF CONCRETE.
10. CONFORM TO VAPOR BARRIER OR WATERPROOF MEMBRANE MANUFACTURERS MINIMUM SPACING REQUIREMENTS
BETWEEN MULTIPLE ADJACENT PENETRATIONS.
11. ALIGN EDGE OF SLAB WITH FACE OR ADJACENT COLUMN OR CONCRETE WALL, UNLESS NOTED OTHERWISE.
38 NORTHWEST DAVIS, SUITE 300
PORTLAND, OR 97209
T.O.PLANTER WALL EL: 199'-0" T.O.PLANTER WALL EL: 192'-9 3/4" 503.245.7100
EL: 198'-0" T.O. WALL EL: 200'-6"
I 1505 5TH AVE, SUITE 300
SEATTLE, WA 98101
5' - 0"

1 SUB SLAB EL: 196'-0" 1 206.576.1600


SUB SLAB EL: 196'-0"
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.02 A4.02
H
1014 HOWARD STREET

4' - 9"
EL: 198'-0" SAN FRANCISCO, CA 94103
415.252.7063
SUB SLAB EL: 197'-0" © ANKROM MOISAN ARCHITECTS, INC.
EL: 197'-0 1/2"
19' - 11"

4' - 4 3/8"
EL: 197'-4"

2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.02 A4.02
EL: 198'-0"

EL: 197'-0"

4.58%
10"

1' - 0 5/8"

2' - 4 3/4"
2' - 8 1/2"
G
SLAB PLAN LEGEND

9"

2' - 10"
8" EL: 198'-0"
3"

8' - 3"

8' - 3"
3' - 2 1/2"
1 3' - 0 1/2"
EL: 198'-0"
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A5.41 SLAB STEP


21' - 4"

OVERFRAMING
198'-0"

THE MARK AT SEATTLE


12 21' - 4 1/8"

14' - 0"

1200 45TH ST SEATTLE, WA 98105


__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A5.41 SLAB BREAK LINE, UNO

EL: 198'-0"
1' - 10"

SLAB ON GRADE
F

2 3/8"
21' - 2 3/4" 6' - 0" 21' - 2 1/4"
6"
6"

E RAMP ON GRADE

LCD ACQUISITIONS, LLC


9"
5' - 10 3/4"
5' - 6 1/4" 1' - 6" 4' - 3"

7' - 1 1/4"
1' - 2"

8' - 11 3/4"
CONCRETE CURB
105' - 0"

2' - 9"
2' - 3"
7" 8"

1' - 2"
17' - 0"

7' - 2 1/2" 3' - 7 1/4" FLOOR DRAIN FD


5' - 0 3/4" 6' - 2"

6"
1 1

8"
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.01 8 3/4" A4.01 ROOF DRAIN WITH OVERFLOW

8"
EL: 198'-1"

5' - 6"
7"
1' - 9 3/4"

9' - 0"

9' - 0"
10 3/4"

D
5' - 2 3/8"
5' - 0"

6 5/8"

C
12' - 0 5/8"
REVISION DATE REASON FOR ISSUE
21' - 6"

B
3' - 0 1/2"
10' - 8 1/2"
10' - 11"
12' - 7"

SDCI APPROVAL STAMP


14' - 9"

A 5' - 5"

LEVEL 2 SLAB PLAN

15'-2" 21'-0" 14'-5" 9'-3" 2'-10" 17'-8" 9'-5 1/2" 9'-2 1/2" 8'-5" 2'-9" 17'-3" 14'-9"
142' - 2"
BIM 360://Seattle II/210310-20-Seattle II.rvt

60% CD SET
3
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.02 A4.01

DATE PROJECT NUMBER


11/18/2022 210310

1 LEVEL 2 - SLAB PLAN


1/8" = 1'-0"
SHEET NUMBER

A2.02S
PROJECT
11/18/2022 10:23:01 AM
GENERAL NOTES - FLOOR PLANS
1.
2.
REFER TO SHEET A0.01 FOR 'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK.
PRIOR TO FRAMING VERIFY THAT FINAL APPLIANCE AND PLUMBING FIXTURE SIZES/CLEARANCES MATCH THOSE USED AS
NOT FOR
3.
BASIS OF DESIGN SHOWN ON DRAWING A5.01.
REFERENCE SLAB PLANS FOR CONCRETE WALL LOCATIONS, UNO. COORDINATE WITH STRUCTURAL DRAWINGS. CONSTRUCTION
4. SEE SHEETS A0.21 & A0.31 FOR WALL ASSEMBLIES.
5. SEE SHEET A0.41 FOR TYPICAL FRAMING AND ACOUSTICAL DETAILS.
6. SEE FIRE/LIFE SAFETY SHEETS BEGINNING ON G2.00 SERIES FOR LOCATIONS OF FIRE EXTINGUISHER CABINETS. (NONE
LOCATED YET)
7. SEE SHEETS BEGINNING ON A5.01 FOR TYPICAL ACCESSIBILITY CLEARANCES. SEE SHEETS BEGINNING ON G3.01 FOR
3 F
_ 1
_ 2 1 2 ACCESSIBLE ROUTE.
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

_ _ G
_
A4.02 A4.55 xA3.91 A4.01 A3.12 A3.05 8. REFER TO ENLARGED UNIT PLANS (A5.2x - A5.3X SERIES) FOR DETAILED INFORMATION WITHIN EACH RESIDENTIAL UNIT
A4.56
9. REFER TO STRUCTURAL DRAWINGS FOR COLUMNS, SHEAR WALL AND BEAM SIZES.
NEIGHBORHOOD OPEN SPACE
10. UNIT DEMISING WALLS SHALL BE WALL TYPE 9A.2 TYPICAL UNO.
SEE T1.12 AND LANDSCAPE
11. CORRIDOR WALLS SHALL BE WALL TYPE 9C.1 TYPICAL UNO.
1 2 DRAWINGS 3 3.9 4 5 5.2 6 6.2 7 8 8.4 8.8 9 10 11 12. PROVIDE CONTROL JOINTS PER DETAIL 9/A0.44 AS WALL ASSEMBLY RATING REQUIRES AT 30' MAXIMUM SPACING OR AS
13 14 OTHERWISE INDICATED PER PLAN. ALIGN JOINTS WITH CEILING CONTROL JOINTS.
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
15
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
16
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
17 18
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.55 A4.55 A4.55 A4.56 A4.56 A4.56


38 NORTHWEST DAVIS, SUITE 300
145' - 1 1/2" PORTLAND, OR 97209
503.245.7100
FUEL FILL ALLEY
I 1505 5TH AVE, SUITE 300
1.28% 5.00% 9.14% 9.13% 9.13% 9.13% 9.13% 9.14% 9.15% 9.14% 15.06% 15.05% 19.25% 19.25% 19.29% 17.62% SEATTLE, WA 98101
5' - 0"

X3.5
1
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
3 6 1
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
206.576.1600
A4.02 206'-6" 206'-5" 200'-0" 199'-0" 198'-0" 197'-0" 196'-0" 190'-10" A4.02
H
1014 HOWARD STREET
SAN FRANCISCO, CA 94103
_
3 415.252.7063
EL: 206'-6" A3.15

11' - 0"
5' - 0" © ANKROM MOISAN ARCHITECTS, INC.
350 7
A6.07
19' - 11"

E5.1
1 6
1
2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ A6.09 2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

X.4 A4.02 DN A4.02


NEIGHBORHOOD OPEN SPACE
46' - 3"


X3.4
0 6

1' - 1 3/4"
G 3 1

4' min to parking lane


3' MIN. TO FURNITURE 5' MIN. TO ADJACENT BI KE RACK

vehic. travel
3' min to
A6.24

3' - 4 1/8"
lane
A3.15

5' - 6 1/4"
LINE OF TOWER (ABOVE)
S5.2 3' - 9"
SF31 SF30 SF29 3' - 10" SF28 1 6 SF27 24
20' - 2" 13' - 6 1/2" 3' - 10" 12' - 2" 3' - 10" 8' - 2" 12' - 2" 5' - 5 3/4" 12' - 5 1/2" 18' - 3 1/8" 5' - 11 1/2"

5' TO HYDRANTS AND VAULTS

6' MIN. CLEAR SIDEWALK

S31A
DUMPSTER STORAGE BELOW 7' - 6 1/8"
311A S5.2 2 Q5.1 Q5.1 9J.1
2 6 2 6 1
21' - 4"

1 6 A5.41 1 6.0 __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

312A STUDY A4.51


LINE OF TOWER (ABOVE)
9C.3

THE MARK AT SEATTLE


SF32 T.O.PLANTER WALL EL: 212'-10"
OPEN 2 6 11 318

1200 45TH ST SEATTLE, WA 98105


__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

STUDY 6'-6" A0.43


T.O.PLANTER WALL EL: 214'-2" STUDY IDF

318
9J.1 311 A
312A 1 6.0 316
TRASH _
F

316
12 313 Q5.1 CORRIDOR 9C.3 3 A4.51

4'-7"
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

2 6 S01C 2 6 A6.02

28' - 8 1/8"
A4.54

313
9M.0
6"

LCD ACQUISITIONS, LLC


0 2.5
312 2
S.1 4 SHAFT DHW __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.51
STUDY STAIR 1 4' - 10 1/4"
1 A6.04 PUMP RM

53' - 4 3/4"
_ STAIR 2 ELEC.

SHAFT
312B S01
A3.05 2 SF33 RR S02 300A
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

9J.1 300A 300B 300B


105' - 0"

A4.57 9C.3
17' - 0"

1 6.0 315 9C.3


2 6 2 6
1 SHAFT 10 A10.07 11 1
314 6"
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

E
_ A4.01 12' - 1 5/8" 7' - 8" 9' - 4 3/4" 372 A4.01
4
_
ELEV.
A4.54 23

DWM
A3.15 311 LOBBY
ELEV 1

63' - 8 7/8"
ELEV 2

62' - 9 7/8"
300

ST0103
9J.1 E02 E01
D STUDY
8' - 4"

Y3.1 1 6.0 1
3 8 9C.1 ST0203 _
5' - 0"

S5.2 314
1 6
9J.1 1 6 EL: 209'-1" SHAFT 2 A3.06

SP
1 6.0 _
S8

9' - 4 1/4"
315

9G.2 A3.13
C EP
5' - 2 3/4"

3 3
11 CORRIDOR 209'-0" SLOPE FLOOR DOWN 1" UNIT D3 __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
Y3.0 1 _ 3 A4.51
A4.54 300.1 2 18 301 REVISION DATE REASON FOR ISSUE
9M.2 31' - 10 3/8" 5' - 4"
A6.21
15' - 6 3/4" 5' - 4" 14' - 11 1/2" A3.13
0 * 1
_
58' - 3"

Y3.1 9M.2 xA3.92


3 12
0 *
DW DW DW
9A.2
21' - 6"

DWM
1 8.0
1
_
UNIT C2
10 DW 302
A3.11 __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

DW
A4.54 1
_
EP SP A3.13
E3.1 DWM
EP
UNIT D2
4
SP

0 6 UNIT C1 303 9A.1 __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

1 8.0 A4.52
TYPE A DWM
29' - 9"

22' - 4 1/2"
29' - 0 3/8"

B 304
3' - 11"

SP EP
B
_
28' - 0 3/8" 45' - 10 7/8" 35' - 4" 13' - 11 5/8"
A4.52

SDCI APPROVAL STAMP


14' - 9"

6' - 6 1/8"
6' - 6 1/8"

9A.1 21 22
9' - 2 1/8"

1 8.0
1
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.57

A 3
_
4' - 11 1/2"
SF20A SF20 SF21A SF21 SF22 SF23 SF24 SF25 A3.14
MASONRY VENEER ON E5.1 2
_
NEW EYE BOLT TO BE INSTALLED LINE OF TOWER (ABOVE)
EXT OF CONC WALL 1 6 A3.14
ON BUILDING STRUCTRE
EXISTING STRAIN POLE
2' - 8" 1' - 4"
(TO BE REMOVED) EXISTING STRAIN POLE
M.O. 1' - 4" 1' - 4"
2' - 3 1/4" 7' - 4" 3' - 4" 2' - 8" 6' - 8" 2' - 8" 5' - 4" 2' - 8" 5' - 4" 7' - 4" 3' - 4" 8' - 0" 1' - 4" 12' - 4 5/8" 48' - 4 1/8" 2' - 3"
M.O. M.O. M.O. M.O. M.O. M.O. M.O.
LEVEL 3 FLOOR PLAN
6" 15' - 2" 21' - 0" 14' - 5" 2' - 7" 6' - 8" 2' - 10" 15' - 6" 2' - 2" 9' - 5 1/2" 4' - 4 1/2" 4' - 10" 8' - 5" 2' - 9" 17' - 3" 14' - 9"
125' - 5 1/2" 17' - 2 1/2"

9 8 7 6 5
BIM 360://Seattle II/210310-20-Seattle II.rvt

60% CD SET
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

1' - 10" A4.53 A4.53 A4.53 A4.52 A4.52


142' - 2" 1' - 1 1/2"

3 D 1
_ C 2 2
_
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ _ _ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.02 A4.53 A3.14 A4.52 A4.01 A3.06

DATE PROJECT NUMBER


11/18/2022 210310

1 LEVEL 3 - PLAN
1/8" = 1'-0"
SHEET NUMBER

A2.03
NORTH
11/18/2022 10:23:05 AM
GENERAL NOTES - SLAB PLANS
1.
2.
REFER TO SHEET A0.01 FOR 'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK.
ELEVATION TAGS INDICATE TOP OF CONCRETE, UNLESS NOTED OTHERWISE.
NOT FOR
3. VERIFY AND COORDINATE SLAB PENETRATIONS INCLUDING SLEEVES & BLOCKOUTS AS REQUIRED FOR PLUMBING,
MECHANICAL, ELECTRICAL, ETC. NOTIFY ARCHITECT OF ANY CONFLICTS OR DISCREPENCIES. CONSTRUCTION
4. PROVIDE SLAB BLOCKOUTS FOR RECESSED DOOR HARDWARE.
5. SLAB PLANS INDICATE LAYOUT DIMENSIONS FOR CONCRETE SLABS, CURBS, CONCRETE WALLS, DEPRESSIONS, AND SLOPES,
ONLY. REFER TO STRUCTURAL FOR ADDITIONAL REQUIREMENTS.
6. ROOF, DECK AND BALCONY SLABS SLOPE TO DRAIN 1/4" PER FT, UNO.
7. VERIFY HOISTWAY CLEARANCES, ROUGH OPENING REQUIREMENTS (ELEVATOR DOORS, LOUVERS, ETC.) AND NOTIFY
3
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ ARCHITECT OF ANY DISCREPENCIES.
A4.02 A4.01 8. PROVIDE HOUSEKEEPING PADS REQUIRED FOR FLOOR-MOUNTED EQUIPMENT AS REQUIRED OR AS INDICATED ON MEP OR
FIRE PROTECTION DRAWINGS.
9. PROVIDE CAST OR SAWN CONTROL JOINTS IN SLABS ON GRADE AT LOCATIONS INDICATED ON STRUCTURAL OR
1 2 3 3.9 5 5.2 6.2 7 8.4 8.8 9 10 11 ARCHITECTURAL DRAWINGS. IN THE EVENT OF CONFLICT, NOTFIY THE ARCHITECT PRIOT TO PLACEMENT OF CONCRETE.
10. CONFORM TO VAPOR BARRIER OR WATERPROOF MEMBRANE MANUFACTURERS MINIMUM SPACING REQUIREMENTS
BETWEEN MULTIPLE ADJACENT PENETRATIONS.
11. ALIGN EDGE OF SLAB WITH FACE OR ADJACENT COLUMN OR CONCRETE WALL, UNLESS NOTED OTHERWISE.
38 NORTHWEST DAVIS, SUITE 300
PORTLAND, OR 97209
503.245.7100
T.O. DRAIN EL: 206'-2"

I 1505 5TH AVE, SUITE 300


SEATTLE, WA 98101
5' - 0"

1
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
1
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
206.576.1600
A4.02 EL: 209'-4" A4.02
H EL: 206'-3" 1014 HOWARD STREET
EL: 206'-3" SAN FRANCISCO, CA 94103
T.O. WALL EL: 209'-0"
415.252.7063
EL: 206'-1"
EL: 208'-4"
T.O. DRAIN EL: 206'-1" © ANKROM MOISAN ARCHITECTS, INC.
EL: 206'-3"
19' - 11"

2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
EL: 208'-4" 2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

X.4 A4.02 A4.02

T.O. WALL EL: 210'-6"


10"

2' - 4 3/4"
G
SLAB PLAN LEGEND

9"
8"

3' - 7"

8' - 3 3/8"
8' - 3"
1
3' - 0 1/2"
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A5.41 SLAB STEP

T.O. WALL EL: 210'-6"


EL: 206'-6"
21' - 4"

OVERFRAMING

THE MARK AT SEATTLE


12

1200 45TH ST SEATTLE, WA 98105


__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

EL: 208'-4" A5.41 SLAB BREAK LINE, UNO


1' - 10"

EL: 208'-4"
F SLAB ON GRADE
6"
6"

E RAMP ON GRADE

LCD ACQUISITIONS, LLC


1' - 4"
5' - 6 1/4" 1' - 6" 4' - 3"

8' - 11 3/4"
1' - 2"
2' - 1 1/4" CONCRETE CURB
1 3/4"
105' - 0"

7" 2' - 9"8" 2' - 3"

1' - 2"
17' - 0"

FLOOR DRAIN FD

6"
1 EL: 209'-1" 1

8"
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.01 7' - 2 1/2" A4.01 ROOF DRAIN WITH OVERFLOW

8"
5' - 6"
1' - 9 3/4"

10 3/4"

D
5' - 0"

3' - 5"
6 5/8"

T.O. DRAIN EL: 208'-4"


11' - 10"

C
EL: 209'-0" EL: 209'-0" T.O. WALL EL: 210'-6"
REVISION DATE REASON FOR ISSUE
1' - 10"

T.O. RIDGE (TYP) EL: 208'-6"


21' - 6"

T.O. DRAIN EL: 208'-4"

B T.O. WALL EL: 209'-0"


4' - 10"

2' - 2" 4' - 4 1/2" 3' - 0 1/2"

SDCI APPROVAL STAMP


14' - 9"

1' - 1 1/4"
2' - 7" T.O. DRAIN EL: 208'-4"
3' - 10"

4' - 4"
2' - 2"

2' - 2"
A 5' - 5"
T.O. DRAIN EL: 208'-4" T.O. RIDGE EL: 208'-6"

T.O. WALL EL: 210'-6" T.O. WALL EL: 210'-6"


T.O. DRAIN EL: 208'-4"
T.O. DRAIN EL: 208'-4"

LEVEL 3 SLAB PLAN

15'-2" 21'-0" 14'-5" 9'-3" 2'-10" 17'-8" 9'-5 1/2" 9'-2 1/2" 8'-5" 2'-9" 17'-3" 14'-9"
142' - 2"
BIM 360://Seattle II/210310-20-Seattle II.rvt

60% CD SET
3
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.02 A4.01

DATE PROJECT NUMBER


11/18/2022 210310

1 LEVEL 3 - SLAB PLAN


1/8" = 1'-0"
SHEET NUMBER

A2.03S
PROJECT
11/18/2022 10:23:13 AM
GENERAL NOTES - FLOOR PLANS
1.
2.
REFER TO SHEET A0.01 FOR 'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK.
PRIOR TO FRAMING VERIFY THAT FINAL APPLIANCE AND PLUMBING FIXTURE SIZES/CLEARANCES MATCH THOSE USED AS
NOT FOR
3.
BASIS OF DESIGN SHOWN ON DRAWING A5.01.
REFERENCE SLAB PLANS FOR CONCRETE WALL LOCATIONS, UNO. COORDINATE WITH STRUCTURAL DRAWINGS. CONSTRUCTION
4. SEE SHEETS A0.21 & A0.31 FOR WALL ASSEMBLIES.
5. SEE SHEET A0.41 FOR TYPICAL FRAMING AND ACOUSTICAL DETAILS.
6. SEE FIRE/LIFE SAFETY SHEETS BEGINNING ON G2.00 SERIES FOR LOCATIONS OF FIRE EXTINGUISHER CABINETS. (NONE
LOCATED YET)
7. SEE SHEETS BEGINNING ON A5.01 FOR TYPICAL ACCESSIBILITY CLEARANCES. SEE SHEETS BEGINNING ON G3.01 FOR
3 F
_ 1
_ 2 ACCESSIBLE ROUTE.
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

_ 1 _ 2 G
_
A4.02 A4.55 xA3.91 A4.01 8. REFER TO ENLARGED UNIT PLANS (A5.2x - A5.3X SERIES) FOR DETAILED INFORMATION WITHIN EACH RESIDENTIAL UNIT
A3.12 A3.05 A4.56
9. REFER TO STRUCTURAL DRAWINGS FOR COLUMNS, SHEAR WALL AND BEAM SIZES.
10. UNIT DEMISING WALLS SHALL BE WALL TYPE 9A.2 TYPICAL UNO.
Y.2 11. CORRIDOR WALLS SHALL BE WALL TYPE 9C.1 TYPICAL UNO.
1 Y.1 2 3 3.9 4 5 5.2 6 6.2 7 8 8.4 8.8 9 10 10.5 11 12. PROVIDE CONTROL JOINTS PER DETAIL 9/A0.44 AS WALL ASSEMBLY RATING REQUIRES AT 30' MAXIMUM SPACING OR AS
13 14 OTHERWISE INDICATED PER PLAN. ALIGN JOINTS WITH CEILING CONTROL JOINTS.
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
15
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
16
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
17 18
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.55 A4.55 A4.55 A4.56 A4.56 A4.56


38 NORTHWEST DAVIS, SUITE 300
2' - 7 7/8" 15' - 2" 63' - 1" 2' - 9 5/8" 26' - 0 1/4" 2' - 9 1/8" 25' - 4" 7' - 3 5/8" PORTLAND, OR 97209
503.245.7100

I 1505 5TH AVE, SUITE 300


SEATTLE, WA 98101
5' - 0"

1
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
1
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
206.576.1600
A4.02 A4.02
H
1014 HOWARD STREET
SAN FRANCISCO, CA 94103
_
3 415.252.7063
CATENARY
A3.15 © ANKROM MOISAN ARCHITECTS, INC.
LIGHTING

24' - 11"
19' - 11"

2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
15 2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

X.4 A4.02 3' - 9 3/8" 8' - 0" 64' - 4 1/4" A4.02

3/8" / 1
16' - 0"

1' - 10 3/8"
13' - 0" 25' - 4"
4° 15' - 0" 14 4' - 7 7/8"
8' - 7" 11 12' - 0"

2
8' - 8 1/8"

"
G 1

4' min to parking lane


3' MIN. TO FURNITURE 5' MIN. TO ADJACENT BI KE RACK

5' -
A3.15

3/8" / 12"
7

4' - 9 3/8"
12

3/8
24

"
120

12
4° ° 13


UNIT E5 3
NO OPERABLE OPENINGS
24' - 0 1/2"

407 9M.0
WITHIN 10 FEET OF A5.41
0 2.5 1
21' - 4"

GENERATOR EXHAUST UNIT A1


__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

X.3 A4.51
401 9A.1

THE MARK AT SEATTLE


1 8.0

1200 45TH ST SEATTLE, WA 98105


BACK-UP GEN EXHAUST DW DW

DWM
10FT ABOVE GRADE 10
10

SP
SP
'-

TRASH EP DWM SP

A
0"

38' - 11"
_

EP

39' - 2 1/2"
F 413 A4.51
38' - 10"

12
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
46' - 1"

A4.54

413
VENTING FOR UNIT 406 IS
6"

E
DWM

LCD ACQUISITIONS, LLC


IN SOFFIT BELOW 2
9C.3 SHAFT DHW 9J.1
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

NO BUILDING OPENINGS AND 16 2 6 JAN. 1 6.0 STAIR 1 ST0104 A4.51


1
_ 408 STAIR 2 PUMP RM S01

SHAFT
FIRE RATED FIXED GLAZING
A3.05 2 400A ELEC.
WITHIN 10 FEET OF S02 UNIT D4
EP

__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.57 9A.1 400A 400B 400B


105' - 0"
17' - 0"

TRANSFORMER EXHAUST 1 8.0 402


22' - 1 3/8"

9C.1 DW
1 SHAFT 1 6 1
DW
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

E
_ A4.01 DWM
A4.01
ELEV.
SP

4 408
A4.54 _ UNIT A2
A3.15
TYPE A LOBBY 9C.3 9A.1
ELEV 2 ELEV 1 2 6 1 8.0
400
10

LOUVER FOR 406 E01


'-

D E02
3' - 10 1/4"

TRANSFORMER
0"

9A.2 409 1
ST0204 _
5' - 0"

EXHAUST 1 8.0 SHAFT 9


EP

2
_ A3.06
1/8" / 12" 5' - 0 7/8"
UNIT E2 A3.13

10' - 4"
C STORAGE CORRIDOR 8
7' - 1 3/4"

EP
403 3
5' - 9 1/2"

11 1/8" / 12" ROOF _ 2 9C.1 __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

409 400.2 9C.1 5 4 Y3.0 4 3 A4.51


3' - 3 3/8" _
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.54 POP-UP A3.11 SF34 1 6 1 3.63 REVISION DATE REASON FOR ISSUE
A6.04 A6.22 2 18 A6.02 A3.13
1/8" / 12" 7
1
_
DW
xA3.92
7' - 8 3/8"
11' - 4"
21' - 6"

20' - 7 1/2"

1
SP

_ DWM

10

41' - 2"
A3.11 __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
DW
A4.54 DW
EP

1
_
UNIT D6 A3.13
LINE OF TOWER (ABOVE) TYPE A

SP
25 4
UNIT B3 9A.1 404
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

30' - 7 3/4"
1 8.0 A4.52

30' - 6 1/2"
SP EP
405
29' - 2"

DWM
B
6 B
9A.1 _
17' - 7 3/8" 34' - 0" 1 8.0 50' - 4 7/8" 33' - 1 5/8" A4.52
DWM

PODIUM SDCI APPROVAL STAMP


14' - 9"

X.2 20
3' - 1 3/4" 6' - 6 3/8"

21 9A.1
9' - 0 5/8"

8' - 7 1/8"

DECK 1 8.0
220'-10" 4
410
3° 220'-0"
1' - 1"

1' - 1"

A 3
_
A3.14 5
2
_ 58' - 10 7/8"
A3.14


LEVEL 4 FLOOR PLAN
63' - 10 1/4" 12' - 5" 58' - 10 3/4" 6°

15' - 2" 21' - 0" 14' - 5" 2' - 7" 6' - 8" 2' - 10" 15' - 6" 2' - 2" 9' - 5 1/2" 4' - 4 1/2" 4' - 10" 8' - 5" 2' - 9" 17' - 3" 7' - 9" 7' - 0"

9 8 7 6 5
BIM 360://Seattle II/210310-20-Seattle II.rvt

60% CD SET
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.53 A4.53 A4.53 A4.52 A4.52


1' - 10" 142' - 2" 1' - 1 1/2"

3 D 1
_ C 2 2
_
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ _ _ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.02 A4.53 A3.14 A4.52 A4.01 A3.06

DATE PROJECT NUMBER


11/18/2022 210310

1 LEVEL 4 - PLAN
1/8" = 1'-0"
SHEET NUMBER

A2.04
NORTH
11/18/2022 10:23:16 AM
GENERAL NOTES - SLAB PLANS
1.
2.
REFER TO SHEET A0.01 FOR 'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK.
ELEVATION TAGS INDICATE TOP OF CONCRETE, UNLESS NOTED OTHERWISE.
NOT FOR
3. VERIFY AND COORDINATE SLAB PENETRATIONS INCLUDING SLEEVES & BLOCKOUTS AS REQUIRED FOR PLUMBING,
MECHANICAL, ELECTRICAL, ETC. NOTIFY ARCHITECT OF ANY CONFLICTS OR DISCREPENCIES. CONSTRUCTION
4. PROVIDE SLAB BLOCKOUTS FOR RECESSED DOOR HARDWARE.
5. SLAB PLANS INDICATE LAYOUT DIMENSIONS FOR CONCRETE SLABS, CURBS, CONCRETE WALLS, DEPRESSIONS, AND SLOPES,
ONLY. REFER TO STRUCTURAL FOR ADDITIONAL REQUIREMENTS.
6. ROOF, DECK AND BALCONY SLABS SLOPE TO DRAIN 1/4" PER FT, UNO.
7. VERIFY HOISTWAY CLEARANCES, ROUGH OPENING REQUIREMENTS (ELEVATOR DOORS, LOUVERS, ETC.) AND NOTIFY
3
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ ARCHITECT OF ANY DISCREPENCIES.
A4.02 A4.01 8. PROVIDE HOUSEKEEPING PADS REQUIRED FOR FLOOR-MOUNTED EQUIPMENT AS REQUIRED OR AS INDICATED ON MEP OR
FIRE PROTECTION DRAWINGS.
Y.2 9. PROVIDE CAST OR SAWN CONTROL JOINTS IN SLABS ON GRADE AT LOCATIONS INDICATED ON STRUCTURAL OR
Y.1 ARCHITECTURAL DRAWINGS. IN THE EVENT OF CONFLICT, NOTFIY THE ARCHITECT PRIOT TO PLACEMENT OF CONCRETE.
1 2 3 3.9 5 5.2 6.2 7 8.4 8.8 9 10 10.5 11
10. CONFORM TO VAPOR BARRIER OR WATERPROOF MEMBRANE MANUFACTURERS MINIMUM SPACING REQUIREMENTS
BETWEEN MULTIPLE ADJACENT PENETRATIONS.
11. ALIGN EDGE OF SLAB WITH FACE OR ADJACENT COLUMN OR CONCRETE WALL, UNLESS NOTED OTHERWISE.
38 NORTHWEST DAVIS, SUITE 300
PORTLAND, OR 97209
503.245.7100

I 1505 5TH AVE, SUITE 300


SEATTLE, WA 98101
5' - 0"

1
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
1
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
206.576.1600
A4.02 A4.02
H
1014 HOWARD STREET
SAN FRANCISCO, CA 94103
415.252.7063
© ANKROM MOISAN ARCHITECTS, INC.
19' - 11"

2 2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
10 1/2" __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

X.4 A4.02 3 1/2" A4.02

7' - 5 1/2"
2' - 4 1/2"

4° 2' - 6 5/8"
2' - 2 5/8" 6 1/2"
10"

3 1/2"
G
SLAB PLAN LEGEND

2' - 1"
4' - 9 3/8" 2' - 1"
9"

3 1/2"

4 1/8"
3' - 7"
8"

8' - 3 3/8"

8' - 3 3/8"

2' - 4 3/4"
2' - 11 3/4"

SLAB STEP

4' - 9 3/8"
21' - 4"

OVERFRAMING
X.3 2' - 9 3/8"

THE MARK AT SEATTLE


EL: 220'-0"
12

1200 45TH ST SEATTLE, WA 98105


__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A5.41 SLAB BREAK LINE, UNO


1' - 10"

6' - 11 7/8"
5' - 6 1/4" 1' - 6"
F SLAB ON GRADE
3' - 5" 4' - 3"
6"
6"

E RAMP ON GRADE

LCD ACQUISITIONS, LLC


1' - 4"

7' - 0 1/4"

8' - 0 1/4"
8' - 11 3/4"
1' - 2" 2' - 1 1/4" CONCRETE CURB
1 3/4"
105' - 0"

8 1/4"

7" 2' - 9"8" 2' - 3"

1' - 2"
17' - 0"

8 3/4" 7' - 2 1/2" FLOOR DRAIN FD


4' - 10 1/4"

6"
1 1

8"
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.01 EL: 220'-1" A4.01 ROOF DRAIN WITH OVERFLOW


1' - 0 1/4"

8"
5' - 6"
2' - 8 3/4"

4' - 6"

D 5' - 4 1/2"

4 1/2"
8 3/4"
5' - 0"

2' - 4 1/8"
EL: 219'-11 1/2" EL: 219'-10 1/2"
C
6' - 0"
REVISION DATE REASON FOR ISSUE
EL: 220'-0"

T.O. WALL EL: 223'-6" 3' - 6 1/8"

T.O. WALL EL: 222'-9"


21' - 6"

EL: 220'-0"

T.O. DRAIN EL: 219'-4"

T.O. DRAIN EL: 219'-6"

T.O. WALL EL: 221'-11"

B
5' - 0 7/8"

T.O. DRAIN EL: 219'-4" 2' - 2" 4' - 10"


2' - 7" 3' - 0 1/2"

SDCI APPROVAL STAMP


14' - 9"

X.2
1' - 11 1/4"
2' - 4"
3 1/2"

3 1/2"
3' - 10"

4' - 4"

4' - 4"
2' - 2"

A
T.O. WALL EL: 221'-6" T.O. RIDGE EL: 219'-6" 3 7/8"
T.O. WALL EL: 221'-11"
T.O. DRAIN EL: 219'-4" T.O. DRAIN EL: 219'-4"

LEVEL 4 SLAB PLAN


4° 6°

15'-2" 21'-0" 14'-5" 9'-3" 2'-10" 17'-8" 9'-5 1/2" 9'-2 1/2" 8'-5" 2'-9" 17'-3" 7'-9" 7'-0"
142' - 2"
BIM 360://Seattle II/210310-20-Seattle II.rvt

60% CD SET
2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.01

DATE PROJECT NUMBER


11/18/2022 210310

1 LEVEL 4 - SLAB PLAN


1/8" = 1'-0"
SHEET NUMBER

A2.04S
PROJECT
11/18/2022 10:23:23 AM
GENERAL NOTES - FLOOR PLANS
1.
2.
REFER TO SHEET A0.01 FOR 'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK.
PRIOR TO FRAMING VERIFY THAT FINAL APPLIANCE AND PLUMBING FIXTURE SIZES/CLEARANCES MATCH THOSE USED AS
NOT FOR
3.
BASIS OF DESIGN SHOWN ON DRAWING A5.01.
REFERENCE SLAB PLANS FOR CONCRETE WALL LOCATIONS, UNO. COORDINATE WITH STRUCTURAL DRAWINGS. CONSTRUCTION
4. SEE SHEETS A0.21 & A0.31 FOR WALL ASSEMBLIES.
5. SEE SHEET A0.41 FOR TYPICAL FRAMING AND ACOUSTICAL DETAILS.
6. SEE FIRE/LIFE SAFETY SHEETS BEGINNING ON G2.00 SERIES FOR LOCATIONS OF FIRE EXTINGUISHER CABINETS. (NONE
LOCATED YET)
7. SEE SHEETS BEGINNING ON A5.01 FOR TYPICAL ACCESSIBILITY CLEARANCES. SEE SHEETS BEGINNING ON G3.01 FOR
F
_ 1
_ 2 1 2 ACCESSIBLE ROUTE.
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

_ _
A4.55 xA3.91 A4.01 A3.12 A3.05 8. REFER TO ENLARGED UNIT PLANS (A5.2x - A5.3X SERIES) FOR DETAILED INFORMATION WITHIN EACH RESIDENTIAL UNIT
9. REFER TO STRUCTURAL DRAWINGS FOR COLUMNS, SHEAR WALL AND BEAM SIZES.
10. UNIT DEMISING WALLS SHALL BE WALL TYPE 9A.2 TYPICAL UNO.
11. CORRIDOR WALLS SHALL BE WALL TYPE 9C.1 TYPICAL UNO.
1 Y.1 1.8 2 3 3.9 4 5 5.2 6 6.2 7 8 8.4 8.8 9 Y.2 10 10.5 11 12. PROVIDE CONTROL JOINTS PER DETAIL 9/A0.44 AS WALL ASSEMBLY RATING REQUIRES AT 30' MAXIMUM SPACING OR AS
OTHERWISE INDICATED PER PLAN. ALIGN JOINTS WITH CEILING CONTROL JOINTS.

15' - 9 7/8" 65' - 1" 2' - 9 5/8" 26' - 0 1/4" 2' - 9 1/8" 25' - 4" 7' - 3 5/8"
38 NORTHWEST DAVIS, SUITE 300
PORTLAND, OR 97209
503.245.7100

I 1505 5TH AVE, SUITE 300


SEATTLE, WA 98101
206.576.1600

H
1014 HOWARD STREET
SAN FRANCISCO, CA 94103
415.252.7063
22' - 3 1/2"

25' - 0 1/8"
© ANKROM MOISAN ARCHITECTS, INC.

64' - 4 1/4"
X.4
25' - 4"

1' - 10 3/8"
1' - 10 3/8"
2' - 7 1/2"

4° 15
11
G

5' -

/8"
61
7
9A.1 14

4' - 9 1/4"

4' - 9 1/4"
3/8
UNIT B2 12

5' -
1 8.0

"
°
4° 507
UNIT B1 13 120
508 3 9M.0 150°
31' - 0 1/4" 34' - 3 3/8" A5.41 0 2.5 25' - 0 1/4" 30' - 9 5/8"
21' - 4"

9A.1
SP

DW JAN.
X.3 1 8.0

SP

THE MARK AT SEATTLE


25' - 0 3/4"

514
DW UNIT A1

1200 45TH ST SEATTLE, WA 98105


DWM
DWM

DWM
SP 501 EP DWM SP

TRASH

38' - 11"
EP
46' - 0 7/8"

39' - 1 3/8"
514 513
45' - 11 1/2"

12
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

10
A4.54 DW
EP

EP
6"

E 5' - 0 3/4"

LCD ACQUISITIONS, LLC


16 513
DW SHAFT
TYPE A UNIT ON 9A.1 UNIT B4 MECH. ELEC. S0105
_ 1
LEVEL 8 - SEE 1 8.0 506 STAIR 2 500A 500B UNIT D4

SHAFT
A3.05 9C.3 9J.1 9C.1
S02 1 6.0 500B DN 502
A2.22 FOR TYPE A 2 6 3' - 4" 1 6

1' - 3 1/2"
16' - 11 5/8"

DWM
500A UP
17' - 0"

UNIT PLAN DW
SHAFT
EP

1
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
1
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

E
_ A4.01 A4.01
27' - 5 1/8"

A4.54 4
_
A3.15 ELEV. STAIR 1
UP ELEV 2 ELEV 1
SP

DN
E02
LOBBY E01 S01
D
80' - 1"

500 1
_
5' - 0"

9C.1 S0205 9
1 6
SHAFT 9A.1
5' - 0 7/8" 2
_ A3.06
1 8.0 8
A3.13

10' - 4"
C EP
UNIT E2 3' - 3 3/8"
5' - 3 3/8"

11 2 17 CORRIDOR
6' - 3"

_
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
9A.1 6 5 Y3.0 9C.1 5 503 3
_
A4.54 A3.11 1 8.0 500.1 2 18 1 6 1' - 9 1/2" REVISION DATE REASON FOR ISSUE
18 A6.04 A6.22 A6.02 7 A3.13
1
_ 1 Date 2 Permit Corrections #2 (first
DW was 100% DD set)
16' - 8" xA3.92
DW

EP
7' - 8 3/8"
UNIT E3
21' - 6"

DWM
1
_ 504
10
A3.11 __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.54 1
_
A3.13
DWM

TYPE A UNIT ON

41' - 2"
SP
6
LEVELS 19 & 20 -

30' - 7 3/4"

30' - 6 1/2"
30' - 1 7/8"

19 SEE A2.21 FOR SP


30' - 6"

DWM
B SP

TYPE A UNIT
UNIT E1
40' - 2 1/4"
505
PLAN 48' - 8" 30' - 9"
2' - 4 5/8"
9A.1 9A.1 SDCI APPROVAL STAMP
X.2
6' - 5 1/4"

3 1 8.0
14' - 9"

1 8.0 4
6' - 10"

8' - 2"

2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

2 A7.35
EP

2' - 9"

A 3° 1 3
_ 5
A3.14
X.1 51' - 3 3/8" 2
_ 58' - 10 7/8"
A3.14


6° LEVEL 5 -20 FLOOR
51' - 3 1/4" 11' - 10" 58' - 10 3/4"
PLAN
13' - 2" 2' - 0" 21' - 0" 14' - 5" 9' - 3" 2' - 10" 17' - 8" 9' - 5 1/2" 9' - 2 1/2" 8' - 5" 2' - 9" 17' - 3" 7' - 9"

9 8 7
BIM 360://Seattle II/210310-20-Seattle II.rvt

60% CD SET
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.53 A4.53 A4.53


1' - 10" 135' - 2" 8' - 1 1/2"

D 1
_ 2 2
_
_ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.53 A3.14 A4.01 A3.06

DATE PROJECT NUMBER


11/18/2022 210310

1 LEVEL 5-20 - PLAN


1/8" = 1'-0"
SHEET NUMBER

A2.05
NORTH
11/18/2022 10:23:27 AM
GENERAL NOTES - SLAB PLANS
1.
2.
REFER TO SHEET A0.01 FOR 'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK.
ELEVATION TAGS INDICATE TOP OF CONCRETE, UNLESS NOTED OTHERWISE.
NOT FOR
3. VERIFY AND COORDINATE SLAB PENETRATIONS INCLUDING SLEEVES & BLOCKOUTS AS REQUIRED FOR PLUMBING,
MECHANICAL, ELECTRICAL, ETC. NOTIFY ARCHITECT OF ANY CONFLICTS OR DISCREPENCIES. CONSTRUCTION
4. PROVIDE SLAB BLOCKOUTS FOR RECESSED DOOR HARDWARE.
5. SLAB PLANS INDICATE LAYOUT DIMENSIONS FOR CONCRETE SLABS, CURBS, CONCRETE WALLS, DEPRESSIONS, AND SLOPES,
ONLY. REFER TO STRUCTURAL FOR ADDITIONAL REQUIREMENTS.
6. ROOF, DECK AND BALCONY SLABS SLOPE TO DRAIN 1/4" PER FT, UNO.
7. VERIFY HOISTWAY CLEARANCES, ROUGH OPENING REQUIREMENTS (ELEVATOR DOORS, LOUVERS, ETC.) AND NOTIFY
2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ ARCHITECT OF ANY DISCREPENCIES.
A4.01 8. PROVIDE HOUSEKEEPING PADS REQUIRED FOR FLOOR-MOUNTED EQUIPMENT AS REQUIRED OR AS INDICATED ON MEP OR
FIRE PROTECTION DRAWINGS.
Y.2 9. PROVIDE CAST OR SAWN CONTROL JOINTS IN SLABS ON GRADE AT LOCATIONS INDICATED ON STRUCTURAL OR
1 Y.1 1.8 2 3 3.9 5 5.2 6.2 7 8.4 8.8 9 10 10.5 11 ARCHITECTURAL DRAWINGS. IN THE EVENT OF CONFLICT, NOTFIY THE ARCHITECT PRIOT TO PLACEMENT OF CONCRETE.
10. CONFORM TO VAPOR BARRIER OR WATERPROOF MEMBRANE MANUFACTURERS MINIMUM SPACING REQUIREMENTS
BETWEEN MULTIPLE ADJACENT PENETRATIONS.
11. ALIGN EDGE OF SLAB WITH FACE OR ADJACENT COLUMN OR CONCRETE WALL, UNLESS NOTED OTHERWISE.
38 NORTHWEST DAVIS, SUITE 300
PORTLAND, OR 97209
503.245.7100

I 1505 5TH AVE, SUITE 300


SEATTLE, WA 98101
5' - 0"

206.576.1600

H
1014 HOWARD STREET
SAN FRANCISCO, CA 94103
415.252.7063
© ANKROM MOISAN ARCHITECTS, INC.
19' - 11"

1' - 1 1/2"
X.4

2' - 4 3/4"
3 1/2"
2' - 4 1/2"


2' - 2 5/8" 7"

4 1/8"
G
SLAB PLAN LEGEND

9"
3 1/8" 2' - 6 5/8"

3 1/2"
3 1/2"
8"

3' - 7"
10"

6' - 11 3/8"
8' - 3 3/8"

8' - 3 3/8"
4' - 11 3/8"
2' - 11 3/4" 3' - 0 1/2" 3 1/2"

SLAB STEP
21' - 4"

2' - 9 3/8" OVERFRAMING


X.3

THE MARK AT SEATTLE


12

1200 45TH ST SEATTLE, WA 98105


__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A5.41 SLAB BREAK LINE, UNO

EL: 229'-8"

6' - 11 7/8"
F SLAB ON GRADE
5' - 5" 4' - 3"
21' - 2 3/4"

E RAMP ON GRADE

LCD ACQUISITIONS, LLC


1' - 4"

7' - 0 1/4"

8' - 2 3/4"
8' - 11 3/4"
1' - 2" 2' - 1 1/4" CONCRETE CURB
1 3/4"
105' - 0"

8 1/4"

7' - 2 1/2" 7" 2' - 9"8" 2' - 3"


17' - 6"

1' - 2"
FLOOR DRAIN FD
5' - 0 3/4"

6"
1 1
4' - 5 5/8"

8"
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

EL: 229'-9" __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.01 A4.01 ROOF DRAIN WITH OVERFLOW

8"
5' - 6"
2' - 8 3/4"

1' - 9 3/4"

4 1/2"
D
8 3/4" 2' - 6"
5' - 0"

C
EL: 229'-8" EL: 229'-6 1/2"
6' - 0 1/2"

REVISION DATE REASON FOR ISSUE

2' - 3 7/8"
21' - 6"

EL: 229'-8"

4' - 10"
3' - 0 1/2"

B
2' - 7"
EL: 229'-7 1/2"
SDCI APPROVAL STAMP
14' - 9"

X.2
3 3/4"
3 1/2" 5' - 5"

2' - 2"
3' - 10"

4' - 4"

4' - 4"
EL: 229'-6 1/2"
3"

2' - 2"
2' - 2"

3 1/2"
A

X.1

LEVEL 5-19 SLAB


4° 6°
PLAN
13'-2" 2'-0" 21'-0" 14'-5" 9'-3" 2'-10" 17'-8" 9'-5 1/2" 9'-2 1/2" 8'-5" 2'-9" 17'-3" 7'-9" 7'-0"
142' - 2"
BIM 360://Seattle II/210310-20-Seattle II.rvt

60% CD SET
2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.01

DATE PROJECT NUMBER


11/18/2022 210310

1 LEVEL 5-19 - SLAB PLAN


1/8" = 1'-0"
SHEET NUMBER

A2.05S
PROJECT
11/18/2022 10:23:30 AM
GENERAL NOTES - SLAB PLANS
1.
2.
REFER TO SHEET A0.01 FOR 'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK.
ELEVATION TAGS INDICATE TOP OF CONCRETE, UNLESS NOTED OTHERWISE.
NOT FOR
3. VERIFY AND COORDINATE SLAB PENETRATIONS INCLUDING SLEEVES & BLOCKOUTS AS REQUIRED FOR PLUMBING,
MECHANICAL, ELECTRICAL, ETC. NOTIFY ARCHITECT OF ANY CONFLICTS OR DISCREPENCIES. CONSTRUCTION
4. PROVIDE SLAB BLOCKOUTS FOR RECESSED DOOR HARDWARE.
5. SLAB PLANS INDICATE LAYOUT DIMENSIONS FOR CONCRETE SLABS, CURBS, CONCRETE WALLS, DEPRESSIONS, AND SLOPES,
ONLY. REFER TO STRUCTURAL FOR ADDITIONAL REQUIREMENTS.
6. ROOF, DECK AND BALCONY SLABS SLOPE TO DRAIN 1/4" PER FT, UNO.
7. VERIFY HOISTWAY CLEARANCES, ROUGH OPENING REQUIREMENTS (ELEVATOR DOORS, LOUVERS, ETC.) AND NOTIFY
2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ ARCHITECT OF ANY DISCREPENCIES.
A4.01 8. PROVIDE HOUSEKEEPING PADS REQUIRED FOR FLOOR-MOUNTED EQUIPMENT AS REQUIRED OR AS INDICATED ON MEP OR
FIRE PROTECTION DRAWINGS.
Y.2 9. PROVIDE CAST OR SAWN CONTROL JOINTS IN SLABS ON GRADE AT LOCATIONS INDICATED ON STRUCTURAL OR
Y.1 1.8 2 3 3.9 5 5.2 6.2 7 8.4 8.8 9 10 10.5 ARCHITECTURAL DRAWINGS. IN THE EVENT OF CONFLICT, NOTFIY THE ARCHITECT PRIOT TO PLACEMENT OF CONCRETE.
10. CONFORM TO VAPOR BARRIER OR WATERPROOF MEMBRANE MANUFACTURERS MINIMUM SPACING REQUIREMENTS
BETWEEN MULTIPLE ADJACENT PENETRATIONS.
11. ALIGN EDGE OF SLAB WITH FACE OR ADJACENT COLUMN OR CONCRETE WALL, UNLESS NOTED OTHERWISE.
38 NORTHWEST DAVIS, SUITE 300
PORTLAND, OR 97209
503.245.7100

I 1505 5TH AVE, SUITE 300


SEATTLE, WA 98101
5' - 0"

206.576.1600

H
1014 HOWARD STREET
SAN FRANCISCO, CA 94103
415.252.7063
© ANKROM MOISAN ARCHITECTS, INC.
19' - 11"

1' - 1 1/2"
X.4 3 1/2"


10"

2' - 4 3/4"
2' - 2 5/8" 7"

3 1/2"
G 3 1/8" 2' - 6 5/8"
SLAB PLAN LEGEND

2' - 1"
8"

3' - 7"

6' - 11 3/8"

6' - 11 3/8"
9"

8' - 3 3/8"

8' - 3 3/8"
3 1/2"
3' - 0 1/2" 3 1/2"
4° 2' - 11 3/4"
SLAB STEP
21' - 4"

2' - 9 3/8" OVERFRAMING


X.3

THE MARK AT SEATTLE


12

1200 45TH ST SEATTLE, WA 98105


__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A5.41 SLAB BREAK LINE, UNO

6' - 11 7/8"
EL: 374'-8"
F SLAB ON GRADE
3' - 5" 4' - 3" 21' - 2 3/4" 8' - 6 1/4" 18' - 8"

E RAMP ON GRADE

LCD ACQUISITIONS, LLC


1' - 4"

7' - 0 1/4"

8' - 2 3/4"
2' - 1 1/4" CONCRETE CURB
1 3/4"
105' - 0"

8 1/4"

7" 2' - 9"8" 2' - 3"


17' - 6"

1' - 2"
FLOOR DRAIN FD

6"
1 EL: 374'-9" 1
1' - 9 3/4"

8"
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.01 A4.01 ROOF DRAIN WITH OVERFLOW

8"
5' - 6"
2' - 8 3/4"

4 1/2"
D
80' - 1"

3' - 6"
8 3/4" 2' - 6"
5' - 0"

5' - 0"
2' - 8 1/8"
10 1/2"

10 1/2"
C
1' - 1 1/4" EL: 374'-8" EL: 374'-6 1/2"

5' - 8 1/2"
1' - 1 1/2"
6' - 0 1/2"

2' - 3 7/8" REVISION DATE REASON FOR ISSUE

EL: 374'-8"
21' - 6"

3' - 0 1/2"

B
5' - 2"

4' - 10"
EL: 374'-8"
1' - 9 1/4" SDCI APPROVAL STAMP
14' - 9"

X.2
3 3/4"
3 1/2"
5' - 5"
3' - 10"

4' - 4"

4' - 4"
EL: 374'-6 1/2"
2' - 2"
2' - 2"

2' - 2"
2' - 7"

3 1/2"
3"

A 3°

X.1

LEVEL 20 SLAB PLAN


1 11
4° 6°

122' - 0"
142' - 2"
BIM 360://Seattle II/210310-20-Seattle II.rvt

2'-0" 21'-0" 14'-5" 9'-3" 2'-10" 17'-8" 9'-5 1/2" 9'-2 1/2" 8'-5" 2'-9" 17'-3" 7'-9"
60% CD SET
2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.01

DATE PROJECT NUMBER


11/18/2022 210310

1 LEVEL 20 - SLAB PLAN


1/8" = 1'-0"
SHEET NUMBER

A2.20S
PROJECT
11/18/2022 10:23:37 AM
GENERAL NOTES - FLOOR PLANS
1.
2.
REFER TO SHEET A0.01 FOR 'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK.
PRIOR TO FRAMING VERIFY THAT FINAL APPLIANCE AND PLUMBING FIXTURE SIZES/CLEARANCES MATCH THOSE USED AS
NOT FOR
3.
BASIS OF DESIGN SHOWN ON DRAWING A5.01.
REFERENCE SLAB PLANS FOR CONCRETE WALL LOCATIONS, UNO. COORDINATE WITH STRUCTURAL DRAWINGS. CONSTRUCTION
4. SEE SHEETS A0.21 & A0.31 FOR WALL ASSEMBLIES.
5. SEE SHEET A0.41 FOR TYPICAL FRAMING AND ACOUSTICAL DETAILS.
6. SEE FIRE/LIFE SAFETY SHEETS BEGINNING ON G2.00 SERIES FOR LOCATIONS OF FIRE EXTINGUISHER CABINETS. (NONE
LOCATED YET)
7. SEE SHEETS BEGINNING ON A5.01 FOR TYPICAL ACCESSIBILITY CLEARANCES. SEE SHEETS BEGINNING ON G3.01 FOR
2 1 2 ACCESSIBLE ROUTE.
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

_ _ 2
_
A4.01 A3.12 A3.05 8. REFER TO ENLARGED UNIT PLANS (A5.2x - A5.3X SERIES) FOR DETAILED INFORMATION WITHIN EACH RESIDENTIAL UNIT
A3.15
9. REFER TO STRUCTURAL DRAWINGS FOR COLUMNS, SHEAR WALL AND BEAM SIZES.
10. UNIT DEMISING WALLS SHALL BE WALL TYPE 9A.2 TYPICAL UNO.
11. CORRIDOR WALLS SHALL BE WALL TYPE 9C.1 TYPICAL UNO.
Y.1 1.8 2 3 3.9 4 5 5.2 6 6.2 7 8 8.4 8.8 9 Y.2 10 10.5 12. PROVIDE CONTROL JOINTS PER DETAIL 9/A0.44 AS WALL ASSEMBLY RATING REQUIRES AT 30' MAXIMUM SPACING OR AS
OTHERWISE INDICATED PER PLAN. ALIGN JOINTS WITH CEILING CONTROL JOINTS.

15' - 9 7/8" 65' - 1" 2' - 9 5/8" 26' - 0 1/4" 2' - 9 1/8" 25' - 4" 7' - 3 5/8"
38 NORTHWEST DAVIS, SUITE 300
PORTLAND, OR 97209
503.245.7100

I 1505 5TH AVE, SUITE 300


SEATTLE, WA 98101
206.576.1600

H
1014 HOWARD STREET
SAN FRANCISCO, CA 94103
415.252.7063
22' - 3 1/2"

25' - 0 1/8"
© ANKROM MOISAN ARCHITECTS, INC.

64' - 4 1/4"
X.4
25' - 4"

1' - 10 3/8"
1' - 10 3/8"
2' - 7 1/2"

4° 15
11
G

5' -

/8"
61
7
14

4' - 9 1/4"

4' - 9 1/4"
3/8
UNIT B2 12

5' -
9A.1

"
120 °
4° 1 8.0
2107 ° 13 120
3
2980 UNIT B1 9M.0
21' - 4"

31' - 0 1/4" 34' - 3 3/8" A5.41 25' - 0 1/4" 30' - 9 5/8"


0 2.5

2998
2108
SP

X.3 DW JAN.
3002

SP
9A.1

THE MARK AT SEATTLE


25' - 0 3/4"

2114 1 8.0
2999 DW

1200 45TH ST SEATTLE, WA 98105


DWM
DWM

UNIT A1

2225

2227
DWM
SP
DWM

2236
EP SP

2101

38' - 11"
9C.1

EP
5' - 11 1/8"
TRASH

2471
46' - 0 7/8"

2151
2114 1 3.63

39' - 1 3/8"
F 9C.1
45' - 11 1/2"

2413

2226
1 3.63 2113 10
EP

1' - 10 3/8"

2113
6"

LCD ACQUISITIONS, LLC


16

13' - 10 3/4"
DW SHAFT STAIR 1
DHW
EP

9A.1 S0121
1 1 8.0 9M.0 S01 UNIT D4
_ PUMP RM
16' - 11 5/8"

SHAFT
A3.05 UNIT B4 0 .88 2102
2100B 2100B ELEC. DN
2106 2100A S2100A UP
17' - 0"

9C.3
9C.3 2 6 DW
1
SP
2 6 SHAFT 4 1
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

ELEV. __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.57
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.01 A4.01
27' - 5 1/8"

25' - 8 3/4"

LOBBY
UP ELEV 2 2100 ELEV 1 2150
DWM

DN E01
E02
D
80' - 1"

16' - 9 1/4"
STAIR 2 1
_
5' - 0"

S0221 S02 2148 9


SHAFT 9A.1
5' - 0 7/8" 2
_ A3.06
1 8.0 8
A3.13

10' - 4"
C EP

9C.1 3' - 3 3/8"


2 9C.1 CORRIDOR Y3.0 UNIT E2
6' - 3"

_ 17 9A.1 1 1 3.63 3
_
A3.11 1 8.0 1 6 2100.2 2 12 2103 1' - 9 1/2" REVISION DATE REASON FOR ISSUE
18 5' - 7 3/8" 27' - 2 3/8" A6.23 5' - 1 7/8" 21' - 0 1/2" 7 A3.13

2153
DW
16' - 8" DW

DWM
EP
21' - 6"

2144

7' - 8 3/8"
UNIT E4
1
_
2729
A3.11
TYPE A 2737
2104 1
_

2015
2022

2008
1957

A3.13
DWM

41' - 2"
SP
6
UNIT E1 2033

30' - 7 3/4"
2010

2105 2012

30' - 6 1/2"
2727
30' - 1 7/8"

19
30' - 6"

SP

2026

DWM
B SP

2740
1959

40' - 2 1/4" 48' - 8" 30' - 10"


2732

2783

2735
2' - 3 5/8"
9A.1 SDCI APPROVAL STAMP
X.2
6' - 5 1/4"

1 8.0 3
14' - 9"

4 9A.1
6' - 10"

8' - 1 1/2"

1 8.0
1 2
EP

2' - 9"

A 3° 3
_ 5
A3.14
51' - 3 3/8" 2
_ 58' - 10 7/8"
X.1 A3.14


6° LEVEL 21 FLOOR
1 11
51' - 3 1/4" 11' - 10" 58' - 10 3/4"
PLAN
13' - 2" 2' - 0" 21' - 0" 14' - 5" 9' - 3" 2' - 10" 17' - 8" 9' - 5 1/2" 9' - 2 1/2" 8' - 5" 2' - 9" 17' - 3" 7' - 9"
BIM 360://Seattle II/210310-20-Seattle II.rvt

15' - 0" 122' - 0" 8' - 1 1/2"


60% CD SET
1 K
_ 2 2
_
_ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A3.14 A3.16 A4.01 A3.06

DATE PROJECT NUMBER


11/18/2022 210310

1 LEVEL 21 - PLAN
1/8" = 1'-0"
SHEET NUMBER

A2.21
NORTH
11/18/2022 10:23:40 AM
GENERAL NOTES - SLAB PLANS
1.
2.
REFER TO SHEET A0.01 FOR 'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK.
ELEVATION TAGS INDICATE TOP OF CONCRETE, UNLESS NOTED OTHERWISE.
NOT FOR
3. VERIFY AND COORDINATE SLAB PENETRATIONS INCLUDING SLEEVES & BLOCKOUTS AS REQUIRED FOR PLUMBING,
MECHANICAL, ELECTRICAL, ETC. NOTIFY ARCHITECT OF ANY CONFLICTS OR DISCREPENCIES. CONSTRUCTION
4. PROVIDE SLAB BLOCKOUTS FOR RECESSED DOOR HARDWARE.
5. SLAB PLANS INDICATE LAYOUT DIMENSIONS FOR CONCRETE SLABS, CURBS, CONCRETE WALLS, DEPRESSIONS, AND SLOPES,
ONLY. REFER TO STRUCTURAL FOR ADDITIONAL REQUIREMENTS.
6. ROOF, DECK AND BALCONY SLABS SLOPE TO DRAIN 1/4" PER FT, UNO.
7. VERIFY HOISTWAY CLEARANCES, ROUGH OPENING REQUIREMENTS (ELEVATOR DOORS, LOUVERS, ETC.) AND NOTIFY
2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ ARCHITECT OF ANY DISCREPENCIES.
A4.01 8. PROVIDE HOUSEKEEPING PADS REQUIRED FOR FLOOR-MOUNTED EQUIPMENT AS REQUIRED OR AS INDICATED ON MEP OR
FIRE PROTECTION DRAWINGS.
Y.2 9. PROVIDE CAST OR SAWN CONTROL JOINTS IN SLABS ON GRADE AT LOCATIONS INDICATED ON STRUCTURAL OR
Y.1 1.8 2 3 3.9 5 5.2 6.2 7 8.4 8.8 9 10 10.5 ARCHITECTURAL DRAWINGS. IN THE EVENT OF CONFLICT, NOTFIY THE ARCHITECT PRIOT TO PLACEMENT OF CONCRETE.
10. CONFORM TO VAPOR BARRIER OR WATERPROOF MEMBRANE MANUFACTURERS MINIMUM SPACING REQUIREMENTS
BETWEEN MULTIPLE ADJACENT PENETRATIONS.
11. ALIGN EDGE OF SLAB WITH FACE OR ADJACENT COLUMN OR CONCRETE WALL, UNLESS NOTED OTHERWISE.
38 NORTHWEST DAVIS, SUITE 300
PORTLAND, OR 97209
503.245.7100

I 1505 5TH AVE, SUITE 300


SEATTLE, WA 98101
5' - 0"

206.576.1600

H
1014 HOWARD STREET
SAN FRANCISCO, CA 94103
415.252.7063
© ANKROM MOISAN ARCHITECTS, INC.
19' - 11"

X.4 1' - 1 1/2" 10 1/2"


3 1/2"


2' - 2 5/8" 2' - 6 5/8"
10"

2' - 4 3/4"
G 7"

3 1/2"
3 1/8"
SLAB PLAN LEGEND

2' - 1"
9"

3 1/2"
3' - 7"
8"

6' - 11 3/8"

6' - 11 3/8"
8' - 3 3/8"

8' - 3 3/8"
3 1/2"
4° 2' - 11 3/4" 3' - 0 1/2"
SLAB STEP
21' - 4"

2' - 9 3/8" OVERFRAMING


X.3

THE MARK AT SEATTLE


12

1200 45TH ST SEATTLE, WA 98105


__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A5.41 SLAB BREAK LINE, UNO

6' - 11 7/8"
F EL: 384'-4"
SLAB ON GRADE
5' - 5" 4' - 3"

E RAMP ON GRADE

LCD ACQUISITIONS, LLC


1' - 4"

7' - 0 1/4"

8' - 2 3/4"
2' - 1 1/4" CONCRETE CURB
1 3/4" 8 1/4"

7" 2' - 9"8" 2' - 3"


17' - 6"

1' - 2"
FLOOR DRAIN FD

6"
1 EL: 384'-5" 1

8"
1' - 11"
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.01 A4.01 ROOF DRAIN WITH OVERFLOW

8"
5' - 6"
2' - 11 1/4"

4 1/2"
D 8 3/4"
80' - 1"

3' - 6"
2' - 8 1/8"
5' - 0"

5' - 0"

2' - 6"
10 1/2"

EL: 384'-4" EL: 384'-2 1/2"


C
1' - 1 1/2"

5' - 8 1/2"
6' - 0 1/2"

1' - 1 1/4" EL: 384'-4"


REVISION DATE REASON FOR ISSUE
4' - 3 7/8"

3 1/2"
21' - 6"

3' - 0 1/2"

B
5' - 2"

EL: 384'-3 1/2"


SDCI APPROVAL STAMP
14' - 9"

X.2 1' - 9 1/4"

5' - 5"
3 7/8"

3 1/2"
3' - 10"

4' - 4"

4' - 4"
EL: 384'-2 1/2"
3"

2' - 2" 4' - 4 1/2"


2' - 2"

2' - 2"
1' - 7"

2' - 7"
A 3°
1' - 8 1/2"
X.1

LEVEL 21 SLAB PLAN


1 11
4° 6°

122' - 0"
BIM 360://Seattle II/210310-20-Seattle II.rvt

2'-0" 21'-0" 14'-5" 9'-3" 2'-10" 17'-8" 9'-5 1/2" 9'-2 1/2" 8'-5" 2'-9" 17'-3" 7'-9"
60% CD SET
2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.01

DATE PROJECT NUMBER


11/18/2022 210310

1 LEVEL 21 - SLAB PLAN


1/8" = 1'-0"
SHEET NUMBER

A2.21S
PROJECT
11/18/2022 10:23:47 AM
GENERAL NOTES - FLOOR PLANS
1.
2.
REFER TO SHEET A0.01 FOR 'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK.
PRIOR TO FRAMING VERIFY THAT FINAL APPLIANCE AND PLUMBING FIXTURE SIZES/CLEARANCES MATCH THOSE USED AS
NOT FOR
3.
BASIS OF DESIGN SHOWN ON DRAWING A5.01.
REFERENCE SLAB PLANS FOR CONCRETE WALL LOCATIONS, UNO. COORDINATE WITH STRUCTURAL DRAWINGS. CONSTRUCTION
4. SEE SHEETS A0.21 & A0.31 FOR WALL ASSEMBLIES.
5. SEE SHEET A0.41 FOR TYPICAL FRAMING AND ACOUSTICAL DETAILS.
6. SEE FIRE/LIFE SAFETY SHEETS BEGINNING ON G2.00 SERIES FOR LOCATIONS OF FIRE EXTINGUISHER CABINETS. (NONE
LOCATED YET)
7. SEE SHEETS BEGINNING ON A5.01 FOR TYPICAL ACCESSIBILITY CLEARANCES. SEE SHEETS BEGINNING ON G3.01 FOR
2 1 2 ACCESSIBLE ROUTE.
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

_ _ 2
_
A4.01 A3.12 A3.05 8. REFER TO ENLARGED UNIT PLANS (A5.2x - A5.3X SERIES) FOR DETAILED INFORMATION WITHIN EACH RESIDENTIAL UNIT
A3.15
9. REFER TO STRUCTURAL DRAWINGS FOR COLUMNS, SHEAR WALL AND BEAM SIZES.
10. UNIT DEMISING WALLS SHALL BE WALL TYPE 9A.2 TYPICAL UNO.
11. CORRIDOR WALLS SHALL BE WALL TYPE 9C.1 TYPICAL UNO.
Y.1 1.8 2 3 3.9 4 5 5.2 6 6.2 7 8 8.4 8.8 9 Y.2 10 10.5 12. PROVIDE CONTROL JOINTS PER DETAIL 9/A0.44 AS WALL ASSEMBLY RATING REQUIRES AT 30' MAXIMUM SPACING OR AS
OTHERWISE INDICATED PER PLAN. ALIGN JOINTS WITH CEILING CONTROL JOINTS.

38 NORTHWEST DAVIS, SUITE 300


PORTLAND, OR 97209
503.245.7100

I 1505 5TH AVE, SUITE 300


SEATTLE, WA 98101
206.576.1600

H
1014 HOWARD STREET
SAN FRANCISCO, CA 94103
415.252.7063
22' - 3 1/2"

25' - 0 1/8"
© ANKROM MOISAN ARCHITECTS, INC.

64' - 4 1/4"
X.4
25' - 4"

1' - 10 3/8"
1' - 10 3/8"
2' - 7 1/2"

4° 15
11
G

5' -

/8"
61
7
14

4' - 9 1/4"

4' - 9 1/4"
3/8
12

5' -
UNIT B2 9A.1

"
120 °

2207 1 8.0 UNIT B1 ° 13 120
2208 3

21' - 4"
A5.41
31' - 0 1/4" 34' - 3 3/8" 55' - 9 7/8"
JAN.
21' - 4"

21' - 4"
9A.1
SP

DW
X.3 1 8.0

SP
2214

THE MARK AT SEATTLE


25' - 0 3/4"

UNIT C3

SP
DW

1200 45TH ST SEATTLE, WA 98105


DW DW
DWM

2201
DWM

DWM
45' - 11 1/2"

TRASH
46' - 0 7/8"

2214

39' - 1 3/8"
EP

F 9A.1 2200.1 10
1 8.0
EP

1' - 10 3/8"
6"

LCD ACQUISITIONS, LLC


16 2200.1
DW SHAFT
EP

S0122 9A.1
1 1 8.0
_ UNIT B5 STAIR 2

SHAFT
A3.05 ELEC. UP
S02 2200B DWH2200A DN
TYPE A 2200A
16' - 11 5/8"
17' - 0"

2206 PUMP RM
9C.3
2 6 2200B 5' - 0"
1
SP
SHAFT 1
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

POOL __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

28' - 0 3/8"
A4.01 A4.01

25' - 10 5/8"
27' - 5 1/8"

25' - 6 1/8"

ELEV. EQUIPMENT
ELEV 2 LOBBY ELEV 1 STAIR 1 2212
DWM

DN
UP E02 E01 S01
D 2200
80' - 1"

1
_
5' - 0"

S0222 9C.3 9
SHAFT 2 6 2
_ A3.06
POOL ABOVE 8
4"

5' - 0 7/8"
A3.13

10' - 4"
C
3' - 3 3/8"
2 Y3.0
6' - 3"

_ 17 8 CORRIDOR 2 7 9A.1 3
A3.11 9A.1 2 12 1 8.0 1' - 9 1/2" _
REVISION DATE REASON FOR ISSUE
18 1 8.0 8' - 0 3/4" A6.04 23' - 10 1/8" 2200.2 A6.23 22' - 0 1/8" A6.02 4' - 9 1/2"2212 148 7 A3.13

16' - 8"
DW
7' - 11 1/8"
21' - 6"

1
_ UNIT C4
A3.11
DO 1
_
2204 A3.13
DWM

EP

EP
6
UNIT D5

30' - 7 3/4"
30' - 6"

30' - 8 5/8"

30' - 6 1/2"
30' - 1 7/8"

19 DWM SP

2203
UNIT E1
B SP

2205
1' - 10 3/8" SP DWM

40' - 2 1/4" 40' - 0" 39' - 11 3/8"

9A.1 9A.1 SDCI APPROVAL STAMP


X.2 1 8.0 1 8.0 DW
6' - 5 1/4"

3
14' - 9"

4
6' - 10"

8' - 1 1/2"

2 DW
EP

2' - 9"

A 3° 1 3
_ 5
A3.14
51' - 3 3/8" 2
_ 58' - 10 7/8"
X.1 A3.14


6° LEVEL 22 FLOOR
1 11
51' - 3 1/4" 11' - 10" 58' - 10 3/4"
PLAN
13' - 2" 2' - 0" 21' - 0" 14' - 5" 9' - 3" 2' - 10" 17' - 8" 9' - 5 1/2" 9' - 2 1/2" 8' - 5" 2' - 9" 17' - 3" 7' - 9"
BIM 360://Seattle II/210310-20-Seattle II.rvt

15' - 0" 122' - 0" 8' - 1 1/2"


60% CD SET
1 K
_ 2 2
_
_ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A3.14 A3.16 A4.01 A3.06

DATE PROJECT NUMBER


11/18/2022 210310

1 LEVEL 22 - PLAN
1/8" = 1'-0"
SHEET NUMBER

A2.22
NORTH
11/18/2022 10:23:51 AM
GENERAL NOTES - SLAB PLANS
1.
2.
REFER TO SHEET A0.01 FOR 'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK.
ELEVATION TAGS INDICATE TOP OF CONCRETE, UNLESS NOTED OTHERWISE.
NOT FOR
3. VERIFY AND COORDINATE SLAB PENETRATIONS INCLUDING SLEEVES & BLOCKOUTS AS REQUIRED FOR PLUMBING,
MECHANICAL, ELECTRICAL, ETC. NOTIFY ARCHITECT OF ANY CONFLICTS OR DISCREPENCIES. CONSTRUCTION
4. PROVIDE SLAB BLOCKOUTS FOR RECESSED DOOR HARDWARE.
5. SLAB PLANS INDICATE LAYOUT DIMENSIONS FOR CONCRETE SLABS, CURBS, CONCRETE WALLS, DEPRESSIONS, AND SLOPES,
ONLY. REFER TO STRUCTURAL FOR ADDITIONAL REQUIREMENTS.
6. ROOF, DECK AND BALCONY SLABS SLOPE TO DRAIN 1/4" PER FT, UNO.
7. VERIFY HOISTWAY CLEARANCES, ROUGH OPENING REQUIREMENTS (ELEVATOR DOORS, LOUVERS, ETC.) AND NOTIFY
2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ ARCHITECT OF ANY DISCREPENCIES.
A4.01 8. PROVIDE HOUSEKEEPING PADS REQUIRED FOR FLOOR-MOUNTED EQUIPMENT AS REQUIRED OR AS INDICATED ON MEP OR
FIRE PROTECTION DRAWINGS.
9. PROVIDE CAST OR SAWN CONTROL JOINTS IN SLABS ON GRADE AT LOCATIONS INDICATED ON STRUCTURAL OR
Y.1 1.8 2 3 3.9 5 5.2 6.2 7 8.4 8.8 9 Y.2 10 10.5 ARCHITECTURAL DRAWINGS. IN THE EVENT OF CONFLICT, NOTFIY THE ARCHITECT PRIOT TO PLACEMENT OF CONCRETE.
10. CONFORM TO VAPOR BARRIER OR WATERPROOF MEMBRANE MANUFACTURERS MINIMUM SPACING REQUIREMENTS
BETWEEN MULTIPLE ADJACENT PENETRATIONS.
11. ALIGN EDGE OF SLAB WITH FACE OR ADJACENT COLUMN OR CONCRETE WALL, UNLESS NOTED OTHERWISE.
38 NORTHWEST DAVIS, SUITE 300
PORTLAND, OR 97209
503.245.7100

I 1505 5TH AVE, SUITE 300


SEATTLE, WA 98101
5' - 0"

206.576.1600

H
1014 HOWARD STREET
SAN FRANCISCO, CA 94103
415.252.7063
© ANKROM MOISAN ARCHITECTS, INC.
19' - 11"

1' - 1 1/2"
X.4

4 1/8"
3 1/2"
2' - 4 1/2"


2' - 2 5/8" 3 1/8" 2' - 6 5/8"
10"

2' - 4 3/4"
G 7"
SLAB PLAN LEGEND

3 1/2"
2' - 1"
9"

3 1/2"
3' - 7"
8"

6' - 11 3/8"

6' - 11 3/8"
8' - 3 3/8"

8' - 3 3/8"
2' - 11 3/4"
4° 3' - 0 1/2"
SLAB STEP
3 1/2"
21' - 4"

2' - 9 3/8" OVERFRAMING


X.3

THE MARK AT SEATTLE


12

1200 45TH ST SEATTLE, WA 98105


__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A5.41 SLAB BREAK LINE, UNO

6' - 11 7/8"
EL: 394'-0"
F SLAB ON GRADE
5' - 5" 4' - 3"
21' - 2 3/4"

E RAMP ON GRADE

LCD ACQUISITIONS, LLC


1' - 4"

6' - 1 1/8"
6' - 9 3/4"
8' - 11 3/4"
1' - 2" 2' - 1 1/4" CONCRETE CURB
1 3/4" 8 1/4"

7" 2' - 9"8" 2' - 3"


17' - 6"

1' - 2"
4' - 10 1/4" FLOOR DRAIN FD

6"
1 1
1' - 9 3/4"

8"
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

4' - 10 3/4" EL: 394'-1" __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.01 A4.01 ROOF DRAIN WITH OVERFLOW

8"
5' - 6"
2' - 6"
10 3/4"

4 1/2"
D
80' - 1"

7' - 2 1/2" 1' - 1 1/2"

3' - 6"
5' - 0"

5' - 0"

5' - 0"
2' - 8 1/8"
10 1/2"

10 1/2"
C
1' - 1 1/4" EL: 393'-11 1/2" EL: 393'-10 1/2"

5' - 8 1/2"
6' - 0 1/2"

2' - 3 7/8"
REVISION DATE REASON FOR ISSUE
EL: 394'-0"

3 1/2"
21' - 6"

2' - 2" 3' - 0 1/2"

B
5' - 2"

4' - 10"

EL: 394'-0"
SDCI APPROVAL STAMP
14' - 9"

X.2 1' - 9 1/4"

5' - 5" 3 7/8"


3' - 10"

4' - 4"

4' - 4"
EL: 393'-10 1/2"
2' - 2"

1' - 7"

3 1/2"
2' - 7"
3"

A 3°

X.1

LEVEL 22 SLAB PLAN


1 11
4° 6°

122' - 0"
BIM 360://Seattle II/210310-20-Seattle II.rvt

2'-0" 21'-0" 14'-5" 9'-3" 2'-10" 17'-8" 9'-5 1/2" 9'-2 1/2" 8'-5" 2'-9" 17'-3" 7'-9"
60% CD SET
2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.01

DATE PROJECT NUMBER


11/18/2022 210310

1 LEVEL 22 - SLAB PLAN


1/8" = 1'-0"
SHEET NUMBER

A2.22S
PROJECT
11/18/2022 1:05:12 PM
GENERAL NOTES - FLOOR PLANS
1.
2.
REFER TO SHEET A0.01 FOR 'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK.
PRIOR TO FRAMING VERIFY THAT FINAL APPLIANCE AND PLUMBING FIXTURE SIZES/CLEARANCES MATCH THOSE USED AS
NOT FOR
3.
BASIS OF DESIGN SHOWN ON DRAWING A5.01.
REFERENCE SLAB PLANS FOR CONCRETE WALL LOCATIONS, UNO. COORDINATE WITH STRUCTURAL DRAWINGS. CONSTRUCTION
4. SEE SHEETS A0.21 & A0.31 FOR WALL ASSEMBLIES.
5. SEE SHEET A0.41 FOR TYPICAL FRAMING AND ACOUSTICAL DETAILS.
6. SEE FIRE/LIFE SAFETY SHEETS BEGINNING ON G2.00 SERIES FOR LOCATIONS OF FIRE EXTINGUISHER CABINETS. (NONE
LOCATED YET)
7. SEE SHEETS BEGINNING ON A5.01 FOR TYPICAL ACCESSIBILITY CLEARANCES. SEE SHEETS BEGINNING ON G3.01 FOR
2 1 2 ACCESSIBLE ROUTE.
__ ____ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ___

_ _ 2
_
A4.01 A3.12 A3.05 8. REFER TO ENLARGED UNIT PLANS (A5.2x - A5.3X SERIES) FOR DETAILED INFORMATION WITHIN EACH RESIDENTIAL UNIT
A3.15
9. REFER TO STRUCTURAL DRAWINGS FOR COLUMNS, SHEAR WALL AND BEAM SIZES.
10. UNIT DEMISING WALLS SHALL BE WALL TYPE 9A.2 TYPICAL UNO.
11. CORRIDOR WALLS SHALL BE WALL TYPE 9C.1 TYPICAL UNO.
Y.1 1.8 2 3 3.9 4 5 5.2 6 6.2 7 8 8.4 8.8 9 Y.2 10 10.5 12. PROVIDE CONTROL JOINTS PER DETAIL 9/A0.44 AS WALL ASSEMBLY RATING REQUIRES AT 30' MAXIMUM SPACING OR AS
OTHERWISE INDICATED PER PLAN. ALIGN JOINTS WITH CEILING CONTROL JOINTS.

5' - 9 1/4" 30' - 5 5/8" 8' - 1 1/2" 10' - 8 1/2"


38 NORTHWEST DAVIS, SUITE 300
PORTLAND, OR 97209
503.245.7100

I 1505 5TH AVE, SUITE 300


SEATTLE, WA 98101
206.576.1600

H
1014 HOWARD STREET
SAN FRANCISCO, CA 94103
415.252.7063
22' - 3 1/2"

© ANKROM MOISAN ARCHITECTS, INC.

BUILDING SIGN

STEEL STRUCTURE FOR


MECHANICAL SCREEN TO BE HOT
DIPPED GALVANIZED
X.4 8
__ ____ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ___

A4.57
2' - 7 1/2"

4° 15
11
G
RR
14 2306
7' - 0"

12

4° 13

S5.4 SHOWER S5.4

20' - 6 3/8"
3
1 6 2305 1 6
21' - 4"

T.O. GRATING EL: 405'-6" A5.41


X.3 9J.1
MECHANICAL 1 6.0 9

THE MARK AT SEATTLE


2304 34 __ ____ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ___

A4.57

1200 45TH ST SEATTLE, WA 98105


2304
405'-3"
MTL GRATING W/ 9J.1 2315A
CONDENSER Y3.0 2304B
ALUM RAIL SPACERS 1 6.0 CORRIDOR
29' - 10 3/4"

F FARM 2 24 IDF 29

FD
2307 10
16 1598 SF 2304B 2305 2306
EMERGENCY POOL RING

1/2" / 12"
6"

LCD ACQUISITIONS, LLC


MECH EQUIP CURB RAILS 9C.3 3
SHAFT MECH S01R
__ ____ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ___

2 6 2307 A4.57
1
_ STAIR 2 2300B ELEC.

SHAFT
A3.05 EL: 405'-4 1/4" 2300A DN
S02 UP POOL POLES
2300B 2300A POOL
17' - 0"

23' - 2"
28.1 2300D
3' - 4"
SHAFT 4 1
ELEV.
__ ____ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ___
__ ____ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ___

A4.57 A4.01
9C.3
2301 LOBBY 2 6
UP ELEV 2 2300 ELEV 1 STAIR 1 (2) OUTDOOR TELEVISIONS
DN E02 E01 S01
6' - 11 1/4"

D 7
80' - 1"

__ ____ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ___

A4.57 1
_
5' - 0"

S02R 9M.0 9

5/8" / 12"
SHAFT 0 2.5 2
_ A3.06
A3.13
C EMERGENCY 8
ICE REF
2
_ 17 PHONE 27.1
Y3.0 ROOF 3
_
A3.11 9 LOCATION 3 REVISION DATE REASON FOR ISSUE
18 2303 S13 2 12 2301A 7 A3.13
4 A6.04 A6.23 8 DECK 1 Date 2 Permit Corrections #2 (first
A0.41 A6.02 5

EQ
6 __ ____ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ___ 2300E was 100% DD set)
__ ____ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ___

SKY A4.57
A4.57
FITNESS LOUNGE
21' - 6"

405'-3 3/8"
2303 2301
1

26' - 8 1/2"
_
A3.11
26' - 8"

32
1
_
9J.1 A3.13
33 1 6.0
33' - 4 3/4" 6
EQ
19 1' - 10 3/4"

B
S5.2
1 6
1' - 9"

2302A 2301B

SDCI APPROVAL STAMP


X.2 30 3 SF36 31
YOGA/STRETCHING
14' - 9"

9' - 6 1/4"
2 4
TERRACE SF35
9' - 7"

2300F

A 1 3
_ 5
A3.14
PROTECT ROOF STEEL COLUMNS 2
_
X.1 A3.14
AND BEAMS WITH INTUMESCENT
PAINT TO PROVIDE 1.5 HOUR PROTECT ROOF STEEL COLUMNS
RATING AND BEAMS WITH INTUMESCENT
PAINT TO PROVIDE 1.5 HOUR
RATING
LEVEL ROOF PLAN
1 11
1' - 3 5/8" 30' - 8 3/8" 14' - 4 3/4" 35' - 7 7/8" 3' - 1"

2' - 0" 21' - 0" 14' - 5" 2' - 7" 6' - 8" 2' - 10" 15' - 6" 2' - 2" 9' - 5 1/2" 4' - 4 1/2" 4' - 10" 8' - 5" 2' - 9" 17' - 3" 7' - 9"
BIM 360://Seattle II/210310-20-Seattle II.rvt

15' - 0" 122' - 0" 8' - 1 1/2"


60% CD SET
1 K
_ 2 2
_
_ __ ____ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ___

A3.14 A3.16 A4.01 A3.06

DATE PROJECT NUMBER


11/18/2022 210310

1 ROOF LEVEL - PLAN


1/8" = 1'-0"
SHEET NUMBER

A2.23
NORTH
11/18/2022 10:24:01 AM
GENERAL NOTES - SLAB PLANS
1.
2.
REFER TO SHEET A0.01 FOR 'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK.
ELEVATION TAGS INDICATE TOP OF CONCRETE, UNLESS NOTED OTHERWISE.
NOT FOR
3. VERIFY AND COORDINATE SLAB PENETRATIONS INCLUDING SLEEVES & BLOCKOUTS AS REQUIRED FOR PLUMBING,
MECHANICAL, ELECTRICAL, ETC. NOTIFY ARCHITECT OF ANY CONFLICTS OR DISCREPENCIES. CONSTRUCTION
4. PROVIDE SLAB BLOCKOUTS FOR RECESSED DOOR HARDWARE.
5. SLAB PLANS INDICATE LAYOUT DIMENSIONS FOR CONCRETE SLABS, CURBS, CONCRETE WALLS, DEPRESSIONS, AND SLOPES,
ONLY. REFER TO STRUCTURAL FOR ADDITIONAL REQUIREMENTS.
6. ROOF, DECK AND BALCONY SLABS SLOPE TO DRAIN 1/4" PER FT, UNO.
7. VERIFY HOISTWAY CLEARANCES, ROUGH OPENING REQUIREMENTS (ELEVATOR DOORS, LOUVERS, ETC.) AND NOTIFY
2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ ARCHITECT OF ANY DISCREPENCIES.
A4.01 8. PROVIDE HOUSEKEEPING PADS REQUIRED FOR FLOOR-MOUNTED EQUIPMENT AS REQUIRED OR AS INDICATED ON MEP OR
FIRE PROTECTION DRAWINGS.
9. PROVIDE CAST OR SAWN CONTROL JOINTS IN SLABS ON GRADE AT LOCATIONS INDICATED ON STRUCTURAL OR
ARCHITECTURAL DRAWINGS. IN THE EVENT OF CONFLICT, NOTFIY THE ARCHITECT PRIOT TO PLACEMENT OF CONCRETE.
1 11
Y.1 1.8 2 3 3.9 5 5.2 6.2 7 8.4 8.8 9 Y.2 10 10.5 10. CONFORM TO VAPOR BARRIER OR WATERPROOF MEMBRANE MANUFACTURERS MINIMUM SPACING REQUIREMENTS
BETWEEN MULTIPLE ADJACENT PENETRATIONS.
11. ALIGN EDGE OF SLAB WITH FACE OR ADJACENT COLUMN OR CONCRETE WALL, UNLESS NOTED OTHERWISE.
38 NORTHWEST DAVIS, SUITE 300
PORTLAND, OR 97209
503.245.7100

I 1505 5TH AVE, SUITE 300


SEATTLE, WA 98101
206.576.1600

H
1014 HOWARD STREET
SAN FRANCISCO, CA 94103
415.252.7063
© ANKROM MOISAN ARCHITECTS, INC.

T.O. RIDGE EL: 404'-6"

T.O. DRAIN EL: 404'-2"


1' - 1 1/2"
X.4
T.O. CURB EL: 404'-6"

3 1/2"
2' - 4 1/2"

2' - 2 5/8"

4 1/8"
3 1/2"
7" 2' - 6 5/8"
G 3 1/8"
SLAB PLAN LEGEND

2' - 1"
6' - 11 3/8"

6' - 11 3/8"

3 1/2"
2' - 11 3/4"

3 1/2" SLAB STEP

OVERFRAMING
X.3

THE MARK AT SEATTLE


12

1200 45TH ST SEATTLE, WA 98105


__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A5.41 SLAB BREAK LINE, UNO

9' - 5"
2' - 9 3/8"
T.O. RIDGE EL: 404'-6"
F SLAB ON GRADE
48' - 5"

E RAMP ON GRADE

LCD ACQUISITIONS, LLC


1' - 4"
1' - 2" 2' - 1 1/4" EL: 404'-2" CONCRETE CURB
1 3/4"
8 3/4"
EL: 404'-2"
T.O. DRAIN EL: 404'-2"
7" 2' - 9"8" 2' - 3"

1' - 2"
EL: 400'-9" FD
FLOOR DRAIN
4' - 8 1/8"

6"
1 1

8"
5' - 2 3/8"

8' - 0 1/4"
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.01 T.O. DRAIN EL: 404'-2" 7' - 2 1/2" 8 1/4" A4.01 ROOF DRAIN WITH OVERFLOW

8"
5' - 6"
2' - 8 3/4"

T.O. DRAIN EL: 404'-2"


D EL: 405'-3"
10 3/4"

EL: 404'-6"

10 1/2"
9"

C
2' - 3 7/8" 1' - 1 1/2"

6' - 0"
2' - 4 5/8" REVISION DATE REASON FOR ISSUE

EL: 404'-2"
T.O. DRAIN EL: 404'-2"

T.O. CURB EL: 404'-6" T.O. CURB EL: 404'-6"

B
4' - 10 1/2"

3' - 9 1/4"
T.O. RIDGE EL: 404'-6"

SDCI APPROVAL STAMP


X.2 1' - 5 3/4"

3 7/8"

3 1/2"
3"

T.O. CURB EL: 404'-6"


A T.O. CURB EL: 404'-6"
T.O. RIDGE EL: 404'-6" T.O. RIDGE EL: 404'-6"
T.O. DRAIN EL: 404'-4"
X.1
T.O. DRAIN EL: 404'-2"

LEVEL ROOF SLAB


PLAN
122'-0"
BIM 360://Seattle II/210310-20-Seattle II.rvt

2'-0" 21'-0" 14'-5" 9'-3" 2'-10" 17'-8" 9'-5 1/2" 9'-2 1/2" 8'-5" 2'-9" 17'-3" 7'-9"
60% CD SET
2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.01

DATE PROJECT NUMBER


11/18/2022 210310

1 ROOF LEVEL - SLAB PLAN


1/8" = 1'-0"
SHEET NUMBER

A2.23S
PROJECT
11/18/2022 1:07:56 PM
GENERAL NOTES - FLOOR PLANS
1.
2.
REFER TO SHEET A0.01 FOR 'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK.
PRIOR TO FRAMING VERIFY THAT FINAL APPLIANCE AND PLUMBING FIXTURE SIZES/CLEARANCES MATCH THOSE USED AS
NOT FOR
3.
BASIS OF DESIGN SHOWN ON DRAWING A5.01.
REFERENCE SLAB PLANS FOR CONCRETE WALL LOCATIONS, UNO. COORDINATE WITH STRUCTURAL DRAWINGS. CONSTRUCTION
4. SEE SHEETS A0.21 & A0.31 FOR WALL ASSEMBLIES.
5. SEE SHEET A0.41 FOR TYPICAL FRAMING AND ACOUSTICAL DETAILS.
6. SEE FIRE/LIFE SAFETY SHEETS BEGINNING ON G2.00 SERIES FOR LOCATIONS OF FIRE EXTINGUISHER CABINETS. (NONE
LOCATED YET)
1
_ 2
_ 2
_
7. SEE SHEETS BEGINNING ON A5.01 FOR TYPICAL ACCESSIBILITY CLEARANCES. SEE SHEETS BEGINNING ON G3.01 FOR
2
__ ____ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ___

A3.12 A3.05 A3.15 ACCESSIBLE ROUTE.


A4.01
8. REFER TO ENLARGED UNIT PLANS (A5.2x - A5.3X SERIES) FOR DETAILED INFORMATION WITHIN EACH RESIDENTIAL UNIT
9. REFER TO STRUCTURAL DRAWINGS FOR COLUMNS, SHEAR WALL AND BEAM SIZES.
10. UNIT DEMISING WALLS SHALL BE WALL TYPE 9A.2 TYPICAL UNO.
1 11
Y.1 1.8 2 3 3.9 4 5 5.2 6 6.2 7 8 8.4 8.8 9 Y.2 10 10.5 11. CORRIDOR WALLS SHALL BE WALL TYPE 9C.1 TYPICAL UNO.
12. PROVIDE CONTROL JOINTS PER DETAIL 9/A0.44 AS WALL ASSEMBLY RATING REQUIRES AT 30' MAXIMUM SPACING OR AS
OTHERWISE INDICATED PER PLAN. ALIGN JOINTS WITH CEILING CONTROL JOINTS.

38 NORTHWEST DAVIS, SUITE 300


PORTLAND, OR 97209
503.245.7100
I
1505 5TH AVE, SUITE 300
SEATTLE, WA 98101
206.576.1600
H
1014 HOWARD STREET
SAN FRANCISCO, CA 94103
415.252.7063
© ANKROM MOISAN ARCHITECTS, INC.

X.4 EXPOSED CONC SLAB W/ HR


8
__ ____ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ___

WATERPROOFING @
A4.57

EXPOSED PROJECTED SLAB


G
T.O. RIDGE EL: 414'-2"

418'-3"

T.O. DRAIN EL: 414'-10 1/8" 1.91% 1.91%

2.27%
21'-4"

X.3 1
_
T.O. RIDGE EL: 414'-11 5/8" 9
G2.06 2.27% 2.27% 2.27%
__ ____ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ___

THE MARK AT SEATTLE


A4.57

1200 45TH ST SEATTLE, WA 98105


9

2.27%

2.27%
1.91% 1.91% A6.02
F STEEL SUPPORT FRAME W/ STEEL 29
OUTRIGGERS (PER STRUCT)
6"

E
2400

LCD ACQUISITIONS, LLC


3
SHAFT
ELEV 2 ELEV. STAIR 1 __ ____ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ___

A4.57
2402
1 10 S01
_ STAIR 2 CTRL RM LOBBY S01EP
A3.05 A6.04 S02 75 76 DN
17'-0"

SHIP LADDER
1 SHAFT 4 1
__ ____ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ___

2401
__ ____ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ___ __ ____ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ___

A4.01 T.O. DRAIN EL: 414'-5 5/8" A4.57 A4.01


ELEV 1
DN ELEV 2 ELEV 1
CTRL RM
3.87%

E02 74 E01
D 7 2.10%
80'-1"

__ ____ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ___

A4.57 1
_
5'-0"

3.65%

SHAFT _ 2 A3.06
A3.13
C
2 2410
_ 27 5 3
_
A3.11
4 A3.13
J 6 A10.10 REVISION DATE REASON FOR ISSUE
_ A6.23
5
__ ____ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ___

A3.16 A4.57 __ ____ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ___

A4.57
21'-6"

1
_ 8.00%
16.00% A10.10 7 4 A10.10
A3.11 A10.10 6
1
_
FIREPLACE EXHAUST A3.13

X.2
14'-9"

SDCI APPROVAL STAMP

A 3

_
A3.14
2
_
X.1 A3.14

4° 6°

ELEVATOR
PENTHOUSE PLAN
2'-0" 21'-0" 14'-5" 2'-7" 6'-8" 2'-10" 15'-6" 2'-2" 9'-5 1/2" 4'-4 1/2" 4'-10" 8'-5" 2'-9" 17'-3" 7'-9"
15'-0" 122'-0" 8'-1 1/2"
BIM 360://Seattle II/210310-20-Seattle II.rvt

60% CD SET
1 K
_ 2 2
_
_ __ ____ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ___

A3.14 A3.16 A4.01 A3.06

DATE PROJECT NUMBER

1 ELEV PENTHOUSE FLOOR PLAN


1/8" = 1'-0"
11/18/2022
SHEET NUMBER
210310

A2.24
PROJECT
11/18/2022 10:24:09 AM
GENERAL NOTES - SLAB PLANS
1.
2.
REFER TO SHEET A0.01 FOR 'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK.
ELEVATION TAGS INDICATE TOP OF CONCRETE, UNLESS NOTED OTHERWISE.
NOT FOR
3. VERIFY AND COORDINATE SLAB PENETRATIONS INCLUDING SLEEVES & BLOCKOUTS AS REQUIRED FOR PLUMBING,
MECHANICAL, ELECTRICAL, ETC. NOTIFY ARCHITECT OF ANY CONFLICTS OR DISCREPENCIES. CONSTRUCTION
4. PROVIDE SLAB BLOCKOUTS FOR RECESSED DOOR HARDWARE.
5. SLAB PLANS INDICATE LAYOUT DIMENSIONS FOR CONCRETE SLABS, CURBS, CONCRETE WALLS, DEPRESSIONS, AND SLOPES,
ONLY. REFER TO STRUCTURAL FOR ADDITIONAL REQUIREMENTS.
2 6. ROOF, DECK AND BALCONY SLABS SLOPE TO DRAIN 1/4" PER FT, UNO.
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.01 7. VERIFY HOISTWAY CLEARANCES, ROUGH OPENING REQUIREMENTS (ELEVATOR DOORS, LOUVERS, ETC.) AND NOTIFY
ARCHITECT OF ANY DISCREPENCIES.
8. PROVIDE HOUSEKEEPING PADS REQUIRED FOR FLOOR-MOUNTED EQUIPMENT AS REQUIRED OR AS INDICATED ON MEP OR
1 11 FIRE PROTECTION DRAWINGS.
Y.1 1.8 2 3 3.9 5 5.2 6.2 7 8.4 8.8 9 Y.2 10 10.5 9. PROVIDE CAST OR SAWN CONTROL JOINTS IN SLABS ON GRADE AT LOCATIONS INDICATED ON STRUCTURAL OR
ARCHITECTURAL DRAWINGS. IN THE EVENT OF CONFLICT, NOTFIY THE ARCHITECT PRIOT TO PLACEMENT OF CONCRETE.
10. CONFORM TO VAPOR BARRIER OR WATERPROOF MEMBRANE MANUFACTURERS MINIMUM SPACING REQUIREMENTS
BETWEEN MULTIPLE ADJACENT PENETRATIONS.
11. ALIGN EDGE OF SLAB WITH FACE OR ADJACENT COLUMN OR CONCRETE WALL, UNLESS NOTED OTHERWISE.
38 NORTHWEST DAVIS, SUITE 300
PORTLAND, OR 97209
I 503.245.7100

1505 5TH AVE, SUITE 300


H SEATTLE, WA 98101
206.576.1600

1014 HOWARD STREET


SAN FRANCISCO, CA 94103
415.252.7063
© ANKROM MOISAN ARCHITECTS, INC.

X.4

T.O. DRAIN EL: 414'-2"


G

SLAB PLAN LEGEND


SLAB STEP
21' - 4"

2' - 9 3/8"
X.3
12
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
OVERFRAMING
A5.41

THE MARK AT SEATTLE


6' - 5 7/8"

1200 45TH ST SEATTLE, WA 98105


SLAB BREAK LINE, UNO
F
48' - 5"
SLAB ON GRADE
6"

RAMP ON GRADE

LCD ACQUISITIONS, LLC


1' - 7 1/4" EL: 414'-3"

CONCRETE CURB
17' - 0"

7"
1 1
FLOOR DRAIN FD

8' - 0 1/4"
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.01 A4.01

5' - 6"

5' - 6"
ROOF DRAIN WITH OVERFLOW
D
80' - 1"

3' - 6"
5' - 0"

7' - 2 1/2"

REVISION DATE REASON FOR ISSUE


21' - 6"

B
14' - 9"

X.2
SDCI APPROVAL STAMP

X.1

LEVEL PENTHOUSE
122' - 0"
2' - 0" 21' - 0" 14' - 5" 9' - 3" 2' - 10" 17' - 8" 9' - 5 1/2" 9' - 2 1/2" 8' - 5" 2' - 9" 17' - 3" 7' - 9"
SLAB PLAN
BIM 360://Seattle II/210310-20-Seattle II.rvt

60% CD SET

1
DATE PROJECT NUMBER
ELEV PENTHOUSE SLAB PLAN 11/18/2022 210310
1/8" = 1'-0" SHEET NUMBER

A2.24S
PROJECT
11/18/2022 1:09:31 PM
GENERAL NOTES - FLOOR PLANS
1.
2.
REFER TO SHEET A0.01 FOR 'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK.
PRIOR TO FRAMING VERIFY THAT FINAL APPLIANCE AND PLUMBING FIXTURE SIZES/CLEARANCES MATCH THOSE USED AS
NOT FOR
3.
BASIS OF DESIGN SHOWN ON DRAWING A5.01.
REFERENCE SLAB PLANS FOR CONCRETE WALL LOCATIONS, UNO. COORDINATE WITH STRUCTURAL DRAWINGS. CONSTRUCTION
4. SEE SHEETS A0.21 & A0.31 FOR WALL ASSEMBLIES.
5. SEE SHEET A0.41 FOR TYPICAL FRAMING AND ACOUSTICAL DETAILS.
6. SEE FIRE/LIFE SAFETY SHEETS BEGINNING ON G2.00 SERIES FOR LOCATIONS OF FIRE EXTINGUISHER CABINETS. (NONE
LOCATED YET)
2 1 2 7. SEE SHEETS BEGINNING ON A5.01 FOR TYPICAL ACCESSIBILITY CLEARANCES. SEE SHEETS BEGINNING ON G3.01 FOR
__ ____ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ___

_ _ 2
_
A4.01 A3.12 A3.05 ACCESSIBLE ROUTE.
A3.15
8. REFER TO ENLARGED UNIT PLANS (A5.2x - A5.3X SERIES) FOR DETAILED INFORMATION WITHIN EACH RESIDENTIAL UNIT
9. REFER TO STRUCTURAL DRAWINGS FOR COLUMNS, SHEAR WALL AND BEAM SIZES.
10. UNIT DEMISING WALLS SHALL BE WALL TYPE 9A.2 TYPICAL UNO.
Y.1 1.8 2 3 3.9 4 5 5.2 6 6.2 7 8 8.4 8.8 9 Y.2 10 10.5 11. CORRIDOR WALLS SHALL BE WALL TYPE 9C.1 TYPICAL UNO.
12. PROVIDE CONTROL JOINTS PER DETAIL 9/A0.44 AS WALL ASSEMBLY RATING REQUIRES AT 30' MAXIMUM SPACING OR AS
OTHERWISE INDICATED PER PLAN. ALIGN JOINTS WITH CEILING CONTROL JOINTS.

38 NORTHWEST DAVIS, SUITE 300


PORTLAND, OR 97209
503.245.7100
I
1505 5TH AVE, SUITE 300
SEATTLE, WA 98101
206.576.1600
H
1014 HOWARD STREET
SAN FRANCISCO, CA 94103
22' - 3 1/2"

415.252.7063
© ANKROM MOISAN ARCHITECTS, INC.

T.O. MECH SCREEN EL: 424'-0 1/4"


T.O. MECH SCREEN EL: 419'-6 1/2"

X.4 8
__ ____ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ___

A4.57
2' - 7 1/2"


G
T.O. ROOF EL: 414'-11 5/8"

1/4" / 12"
1/4" / 12"
T.O. PARAPET EL: 410'-4"
1/4" / 12" 1/4" / 12"
21' - 4"

X.3 1
_ 9
__ ____ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ___

G2.06 1/4" / 12" 1/4" / 12" 1/4" / 12" A4.57

THE MARK AT SEATTLE


T.O. TRELLIS EL: 422'-4 1/2"

1200 45TH ST SEATTLE, WA 98105


PLANTER

1/4" / 12"
T.O. MECH SCREEN EL: 432'-11 1/2"

1/4" / 12"
1/4" / 12" 1/4" / 12"
STEEL OUTRIGGERS

FD
(PER STRUCT)
F
6"

T.O. MECH SCREEN EL: 432'-11 1/2"

LCD ACQUISITIONS, LLC


425'-10" 3
__ ____ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ___

E A4.57 DN
1
_ EL: 429'-1"
A3.05 EQ EQ
2
17' - 0"

EL: 425'-10"
1 1 A10.10 3 4 1
__ ____ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ___
__ ____ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ___ __ ____ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ___

A4.01 A4.57 A4.01


1/2" / 12" 1/2" / 12"

3 x 12 POWERED ROOF HATCH W/


EL: 426'-6" EL: 425'-10" EL: 425'-10" REMOTE OPERATOR LOCATED ON
D 7
80' - 1"

__ ____ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ___

1/4" / 12" WALL AT BOTTOM OF SHIPS LADDER

3/8" / 12"
T.O. MECH SCREEN EL: 427'-2" A4.57 1
_
5' - 0"

_ 2 A3.06
1/4" / 12"
A3.13
C
2
_ 5 3
_
A3.11
MECH PLATFORM & SHIPS LADDER T.O. ROOF EL: 420'-9 1/4" A3.13
6 A10.10 REVISION DATE REASON FOR ISSUE
__ ____ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ___

OVER EXPOSED MECH DUCT 5


A4.57 __ ____ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ___

A4.57
30 x 30 SMOKE EXHAUST HATCH
21' - 6"

T.O. MECH SCREEN EL: 432'-11 1/2"


1
_ T.O. ROOF EL: 421'-3 1/2" A10.10 7 4 A10.10 A10.10 6
A3.11
1
_
A3.13
1 7/8" / 12" 1" / 12"

T.O. ROOF EL: 421'-2 1/8" FIREPLACE EXHAUST


B.O. ROOF EL: 416'-3 1/4" T.O. DRAIN EL: 415'-8"

B.O. ROOF EL: 416'-2 1/2"

X.2 SDCI APPROVAL STAMP


14' - 9"

ROOF DECK EL: 405'-3"

A 3° 3
_
T.O. PARAPET EL: 410'-3" A3.14 T.O. TRELLIS EL: 422'-11 5/8"
T.O. TRELLIS EL: 420'-4 3/4"
2
X.1 _
A3.14

1
4° 6°
11 ELEVATOR
PENTHOUSE ROOF
13' - 2" 2' - 0" 21' - 0" 14' - 5" 9' - 3" 2' - 10" 17' - 8" 9' - 5 1/2" 9' - 2 1/2" 8' - 5" 2' - 9" 17' - 3" 7' - 9"
PLAN
BIM 360://Seattle II/210310-20-Seattle II.rvt

15' - 0" 122' - 0" 8' - 1 1/2"


60% CD SET
1 K
_ 2 2
_
_ __ ____ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ___

A3.14 A3.16 A4.01 A3.06

DATE PROJECT NUMBER

1 PENT ROOF 11/18/2022 210310


SHEET NUMBER
1/8" = 1'-0"

A2.25
PROJECT
11/18/2022 12:07:44 PM
GENERAL NOTES - ENLARGED PLANS
4
__ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___

A5.40
NOT FOR
1. REFER TO SHEET A0.01 FOR 'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK.
145'-1 1/2" 2.
3.
SEE SLAB PLANS FOR CONCRETE WALL LOCATIONS, UNO. COORDINATE WITH STRUCTURAL DRAWINGS.
SEE SHEETS A0.21, A0.31 FOR WALL ASSEMBLIES.
CONSTRUCTION
4. SEE ENLARGED ELEVATIONS AND WALL SECTIONS FOR ADDITIONAL EXTERIOR DETAILS.
5. SEE FIRE/LIFE SAFETY SHEETS BEGINNING ON SHEET G2.01 FOR LOCATIONS OF RATED CONSTRUCTION AND EXITING
ALLEY INFORMATION.
6. SEE SHEETS BEGINNING ON A5.01 FOR TYPICAL ACCESSIBILITY CLEARANCES.

15'-0"
CONCRETE 9.14% SLOPE 7. PRIOR TO FRAMING VERIFY THAT FINAL APPLIANCE AND PLUMBING FIXTURE SIZES/CLEARANCES MATCH THOSE USED AS
350
SURFACE BASIS OF DESIGN SHOWN ON DRAWING A5.01.
EL: 206'-5" EL: 199'-9" 8. SEE SHEETS A5.04 AND A5.05 FOR 'TYPE A' DWELLING UNIT REQUIREMENTS. SEE G0.31 FOR QUANTITY AND DISTRIBUTION
EL: 206'-5 3/4" OF TYPE A DWELLING UNITS.
9. DWELLING UNITS ARE 'TYPE B' UNO. PROVIDE REINFORCEMENT IN WALLS FOR FUTURE INSTALLATION OF GRAB BARS AT
ALL WATER CLOSETS AND BATHTUBS IN ALL RESIDENTIAL UNITS. SEE SHEETS A5.06 AND A5.07 FOR 'TYPE B' DWELLING

MW
4' - 9"
UNIT REQUIREMENTS.

7'-11"
CONCRETE EL: 206'-6"
COMMERCIAL 10. CARBON MONOXIDE ALARMS TO BE INSTALLED OUTSIDE OF EACH SEPARATE BEDROOM IN THE IMMEDIATE VICINITY OF
SURFACE
4CY DUMPSTER THE BEDROOM PER 2015 SEATTLE FIRE CODE SECTION 915.

MW
5'-9"
2
__ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___
11. ALL COLUMNS IN UNITS NOT FURRED DUE TO SPACE CONSTRAINTS SHALL BE SKIM COATED AND PAINTED TO MATCH 38 NORTHWEST DAVIS, SUITE 300
A4.02 SURROUNDING GWB WALL. ROUND COLUMNS IN UNITS TO HAVE COLUMN COVER. PORTLAND, OR 97209
12. CLOSET DOORS TO BE CENTERED ON OPENING, UNO. ALL CLOSETS TO BE 24" MAXIMUM GWB TO GWB. 503.245.7100
TRASH
13. ALL INTERIOR UNIT PARTITIONS TO BE WALL TYPE 9J.0 - 3.63 UNO.
STAGING AREA DN
14. SEE KITCHEN ELEVATIONS ON SHEETS A10.20 - A10.22 FOR ACCESSIBLE OUTLETS AND SWITCH LOCATION AREAS. 1505 5TH AVE, SUITE 300
NEIGHBORHOOD OPEN SPACE
SEATTLE, WA 98101

MW
TYP 206.576.1600

4' min to parking lane


3' MI N. TO FU RNITU RE 5' MI N. TO ADJACENT BI K E RACK

vehic. travel
3' min to
lane
3

32'-10"
1014 HOWARD STREET
A5.40
SAN FRANCISCO, CA 94103

5' TO HYDRANTS AND VAULTS


415.252.7063

6' MIN. CLEAR SIDEWALK


5'-10"
1 © ANKROM MOISAN ARCHITECTS, INC.
__ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___

A5.41 EL: 206'-6"


TRASH
BIN
STAGING

BH
12
__ ____ ____ ____ _____ ____ ____ ____ ____ ____ ____ ____ ___

A4.54

THE MARK AT SEATTLE


1200 45TH ST SEATTLE, WA 98105
3 TRASH STAGE ENLARGED
2 LEVEL 3 - TRASH STAGE DIAGRAM

LCD ACQUISITIONS, LLC


3/16" = 1'-0" 1" = 10'-0"

ALLEY
5
REVISION DATE REASON FOR ISSUE
A5.41 9.15% SLOPE

10'-2"
H F E
UP
TRASH
ROOM
?

STUDY SDCI APPROVAL STAMP


AREA

ELEC.
LEVEL 3
209' - 0" CORRIDOR

BIKE
ROOM BUSINESS SOLID WASTE TRASH
N.I.C.
ELEV.
STAGE DIAGRAM
LOBBY
BIM 360://Seattle II/210310-20-Seattle II.rvt

60% CD SET

DATE PROJECT NUMBER


11/18/2022 210310
SHEET NUMBER

4 SECTION THRU TRASH STAGING


3/16" = 1'-0" 1 LEVEL 2 - TRASH STAGE DIAGRAM
3/32" = 1'-0"

PROJECT
A5.40
11/18/2022 10:33:23 AM
GENERAL NOTES - ENLARGED PLANS
NOT FOR
1. REFER TO SHEET A0.01 FOR 'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK.

4
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
6 6.2 6 6.2
2.
3.
SEE SLAB PLANS FOR CONCRETE WALL LOCATIONS, UNO. COORDINATE WITH STRUCTURAL DRAWINGS.
SEE SHEETS A0.21, A0.31 FOR WALL ASSEMBLIES.
CONSTRUCTION
A5.40 4. SEE ENLARGED ELEVATIONS AND WALL SECTIONS FOR ADDITIONAL EXTERIOR DETAILS.
6
9G.1 5. SEE FIRE/LIFE SAFETY SHEETS BEGINNING ON SHEET G2.01 FOR LOCATIONS OF RATED CONSTRUCTION AND EXITING
9G.1 9M.0 INFORMATION.
2 C4 2 C4 0 3.63
6. SEE SHEETS BEGINNING ON A5.01 FOR TYPICAL ACCESSIBILITY CLEARANCES.
7. PRIOR TO FRAMING VERIFY THAT FINAL APPLIANCE AND PLUMBING FIXTURE SIZES/CLEARANCES MATCH THOSE USED AS
LANDSCAPING ABOVE 9C.1 BASIS OF DESIGN SHOWN ON DRAWING A5.01.

3'-10 3/4"
4'-3"

4'-3"
12
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
1 6 12
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
12
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
8. SEE SHEETS A5.04 AND A5.05 FOR 'TYPE A' DWELLING UNIT REQUIREMENTS. SEE G0.31 FOR QUANTITY AND DISTRIBUTION
CONCRETE STRUCTURE A5.41 A5.41 A5.41 OF TYPE A DWELLING UNITS.
ENCLOSURE 9G.1 9. DWELLING UNITS ARE 'TYPE B' UNO. PROVIDE REINFORCEMENT IN WALLS FOR FUTURE INSTALLATION OF GRAB BARS AT
2 C4
ALL WATER CLOSETS AND BATHTUBS IN ALL RESIDENTIAL UNITS. SEE SHEETS A5.06 AND A5.07 FOR 'TYPE B' DWELLING

8 1/2"
10'-2 1/4"
9C.1

9'-7"
9C.3 9J.1 UNIT REQUIREMENTS.
METAL SCREEN 1 3.63 2 6
9C.1 9G.1
1 3.63 1 3.63 10. CARBON MONOXIDE ALARMS TO BE INSTALLED OUTSIDE OF EACH SEPARATE BEDROOM IN THE IMMEDIATE VICINITY OF
TRASH TRASH 2 C4
9M.0 THE BEDROOM PER 2015 SEATTLE FIRE CODE SECTION 915.

5'-11 1/4"

5'-11 1/4"

4'-11 3/4"
0 3.63 413
67 SF 11. ALL COLUMNS IN UNITS NOT FURRED DUE TO SPACE CONSTRAINTS SHALL BE SKIM COATED AND PAINTED TO MATCH 38 NORTHWEST DAVIS, SUITE 300
4CY SURROUNDING GWB WALL. ROUND COLUMNS IN UNITS TO HAVE COLUMN COVER. PORTLAND, OR 97209
6'-0"

F Y3.0
F 12. CLOSET DOORS TO BE CENTERED ON OPENING, UNO. ALL CLOSETS TO BE 24" MAXIMUM GWB TO GWB. 503.245.7100
Y3.0 1 24 F CORRIDOR
1 24 13. ALL INTERIOR UNIT PARTITIONS TO BE WALL TYPE 9J.0 - 3.63 UNO.
39 SF
14. SEE KITCHEN ELEVATIONS ON SHEETS A10.20 - A10.22 FOR ACCESSIBLE OUTLETS AND SWITCH LOCATION AREAS. 1505 5TH AVE, SUITE 300
E E E SEATTLE, WA 98101
9C.3 206.576.1600
2 6

7'-2" 1014 HOWARD STREET


10'-0 3/4" SAN FRANCISCO, CA 94103
8'-3"
415.252.7063
6 6.2 © ANKROM MOISAN ARCHITECTS, INC.

1 TRASH ENCLOSURE SECTION


1/4" = 1'-0" 2 LEVEL 3 TRASH ROOM PLAN
1/4" = 1'-0" 3 LEVEL 4 - 22 TRASH ROOM PLAN
1/4" = 1'-0" 4 ROOF LEVEL TRASH PLAN
1/4" = 1'-0"

ELEV PENT
414' - 3"

THE MARK AT SEATTLE


1200 45TH ST SEATTLE, WA 98105
GENERATOR FUEL FILL SATTION

9'-0"
GAS METER
METAL SCREEN THAT IS AT LEATS 50 % OPEN

23'-8 1/2" 18'-4 1/2"

LCD ACQUISITIONS, LLC


ROOF LEVEL
405' - 3"

H 5.2

Y3.0

11'-3"
6 2 10
TRASH ROOM
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A5.41
ACCESS
4" SLAB AND STEPS TO BE
2'-11 3/4"

POURED AFTER GAS LINE


1'-2" 4'-6" 11" 4'-6" IS INSTALLED
COMMERCIAL COMMERCIAL RESIDENCIAL
3'-5"
3'-0"

Y3.0 96GA FOOD 96GA FOOD 2CY FOOD

8'-0"
2 10 RESID. RESID. RESID. 198'-3 3/4" LEVEL 22
GAS LINE TRENCH
394' - 0" REVISION DATE REASON FOR ISSUE
2'-6" 6'-6"
1 Date 2 Permit Corrections #2 (first
COMMERCIAL COMMERCIAL

3' - 0 1/2"
7'-0"

LEVEL 2 was 100% DD set)


4CY TRASH 4CY TRASH 10" 10" 198' - 0"

4.20%
X3.5
0 8
EL: 198'-0"

2' - 0"

7' - 11"

7' - 4"
LEVEL 4
29'-7 1/2"

220' - 0"
9'-0"

G
4.58%

COMMERCIAL COMMERCIAL
4CY RECYCLE 4CY RECYCLE
CAFE
188' - 0" SDCI APPROVAL STAMP
LOBBY/LEASE
186' - 6"

11'-0"
4J.2
2'-0"

2 8 TRASH

6 GAS LINE TRENCH


ROOM
204

4'-0"
1/4" = 1'-0"
7'-0"

COMMERCIAL COMMERCIAL LEVEL 3


RESIDENCIAL
4CY RECYCLE 4CY TRASH 209' - 0"
4CY TRASH
RESIDENCIAL
4CY RECYCLE
4J.2
2 8 RECYCLE RECYCLE SOLID WASTE TRASH
CHUTE CHUTE
ROOM PLAN

11'-0"
BIM 360://Seattle II/210310-20-Seattle II.rvt

60% CD SET

LEVEL 2
3 3.9 4 5 5.2 6 6.2
198' - 0"
DATE PROJECT NUMBER
11/18/2022 210310
SHEET NUMBER

5 LEVEL 2 - TRASH ROOM PLAN


1/4" = 1'-0" 12 TRASH CHUTE SECTION
1/4" = 1'-0"
PROJECT
A5.41
11/18/2022 10:33:29 AM
1 2 3 1 2 3
4
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A5.42
NOT FOR
CONSTRUCTION
TRANSFORMER EXHAUST
SHAFT

I I

X3.0
3 20

5'-4"
H H
38 NORTHWEST DAVIS, SUITE 300
PORTLAND, OR 97209
503.245.7100

4'-5"
1505 5TH AVE, SUITE 300
SEATTLE, WA 98101
SL P. 206.576.1600
O TRANSFORMER TY
4J.0 TRANSFORMER VAULT PE T 0"
O 1 0'-

3'-7"
0 8 SU 104
EXHAUST LOUVER 0M" PER 1014 HOWARD STREET
P/, "
ABOVE 1/2 , 1/2 SAN FRANCISCO, CA 94103
2""
P ER U MP 415.252.7063
S
1 0'- TO
3HR RATED HORIZONTAL 0" O PE © ANKROM MOISAN ARCHITECTS, INC.
TY SL
EXHAUST SHAFT ABOVE P.

4'-5"
SUPPLY VENT W/ 3-HR RATED
FIRE DAMPER, 18" AFF SBC
REMOVABLE OIL 428.8.8.3 PROVIDE 3-HOUR
CONTAINMENT SILL FIRE RATED DAMPE WITH AN
ACTIVATION TEMPERATURE
18'-11" 3'-0" 7'-2" REMOVABLE OIL
OF 140 DEGREES
CONTAINMENT SILL
3
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ PULLING IRONS PER

2' - 0"
A5.42 Y3.0 1' - 5 1/2" 9' - 6" SCL REQUIREMENTS
3 12
IN THE EXPOSED
G G
SLAB STRUCTURE

18"L X 18"W X 12"D 3HR FIRE RATED


3HR FIRE RATED RECESSED DRY SUMP DOOR WITH
12' - 2" 12' - 2"
DOOR WITH PANIC PANIC

THE MARK AT SEATTLE


HARDWARE

1200 45TH ST SEATTLE, WA 98105


10' - 0"
GENERATOR EXHAUST,
3HR FIRE RATED
SEE A5.44 10' - 9 5/8"
DOOR WITH 180
DEGREE SWING

LCD ACQUISITIONS, LLC


__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A5.43

3 HOUR RATED SOFFIT FOR TRANSFORMER 2 HOUR RATED SOFFIT FOR


EXHAUST PER 7/A5.43 GENERATOR EXHAUST PER 2/A5.45

C C

3HR RATED VERTICAL


EXHAUST SHAFT ABOVE

REVISION DATE REASON FOR ISSUE

1 TRANSFORMER ROOM PLAN


1/4" = 1'-0"
3 2 1
2 TRANSFORMER ROOM RCP
1/4" = 1'-0"
G H I

LEVEL 2 LEVEL 2
198' - 0" 198' - 0"
SDCI APPROVAL STAMP
10'-0"

10'-0"
CAFE CAFE
188' - 0" 188' - 0"
1'-6"

1'-6"
LOBBY/LEASE
186' - 6"
LOBBY/LEASE
186' - 6"
ENLARGED
TRANSFORMER
2'-6"

2'-6"
LEVEL 1 LEVEL 1
184' - 0" 184' - 0"
ROOM
BIM 360://Seattle II/210310-20-Seattle II.rvt

60% CD SET

DATE PROJECT NUMBER


11/18/2022 210310

3 TRANSFORMER ROOM SECTION


1/4" = 1'-0" 4 TRANSFORMER ROOM SECTION
1/4" = 1'-0"
SHEET NUMBER

A5.42
PROJECT
11/18/2022 10:33:35 AM
1 1 1 2
NOT FOR
Y.1 CONSTRUCTION

D D D
Y3.1 4 4
3 8 __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

4
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
A5.43 A5.43
A5.43

C C C
9G.2
3 9M.2
0 * 11
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

38 NORTHWEST DAVIS, SUITE 300


Y3.1 A4.54
3 12 PORTLAND, OR 97209
503.245.7100

1505 5TH AVE, SUITE 300


SEATTLE, WA 98101
206.576.1600
9M.2
0 *
1014 HOWARD STREET
SAN FRANCISCO, CA 94103
415.252.7063
© ANKROM MOISAN ARCHITECTS, INC.
5
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
5
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A5.43 A5.43

1 TRANSFORMER EXHAUST ON LEVEL 2


1/4" = 1'-0" 2 TRANSFORMER EXHAUST ON LEVEL 3
1/4" = 1'-0" 3 TRANSFORMER EXHAUST ON LEVEL 4
1/4" = 1'-0"

THE MARK AT SEATTLE


1200 45TH ST SEATTLE, WA 98105
11
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A4.54

LCD ACQUISITIONS, LLC


X3.5
3 6
LEVEL 4 LEVEL 4
220' - 0" 220' - 0"

9G.2
3

Y3.1
3 8
11'-0"

11'-0"

REVISION DATE REASON FOR ISSUE


LEVEL 3 LEVEL 3 1 Date 2 Permit Corrections #2 (first
209' - 0" 209' - 0" was 100% DD set)

9G.2
3
11'-0"

11'-0"

9G.2
3

FIRE CAULK

CONCRETE SLAB

LEVEL 2 LEVEL 2
3HR MECHANICAL ENCLOSURE SDCI APPROVAL STAMP
198' - 0" 198' - 0"

MTL J-RUNNER
7
A5.43
THERMAL INSULATION - MINERAL BATT
SIM

3C
3
14'-0"
8'-10 1/2"

9G.2 X3.0
3 C2 3 14

FIRE CAULK
ENLARGED
TRANSFORMER
3C
LEVEL 1
184' - 0"
3 C2 EXHAUST DETAILS
DRYWALL SUSPENSION FRAMING
BIM 360://Seattle II/210310-20-Seattle II.rvt

60% CD SET
RC CHANNEL

FASTEN J-RUNNER TO J-RUNNER (PER


STRUCT)
DATE PROJECT NUMBER
11/18/2022 210310

4 TRANSFORMER EXHAUST SECTION


1/4" = 1'-0" 5 TRANSFORMER EXHAUST ON L4
1/4" = 1'-0" 7 3 HR HORIZONTAL SHAFT
1 1/2" = 1'-0"
SHEET NUMBER

A5.43
11/18/2022 10:33:44 AM
1 2 1 2

NOT FOR
CONSTRUCTION
I I 1 2

Y3.0
3 12

6'-7 3/4"
H H
148'-6" G
7'-4 1/2"
9G.1 9G.1
2 C4 2 C4
9J.0 38 NORTHWEST DAVIS, SUITE 300
0 6
PORTLAND, OR 97209
GENERATOR EXHAUST IN TWO 503.245.7100
HOUR RATED SHAFT UP TO
9G.1
2 C4 UNDERSIDE OF L2 SLAB 1505 5TH AVE, SUITE 300
SEATTLE, WA 98101
BACKUP 206.576.1600

GEN 1014 HOWARD STREET


13'-4"

ROOM SAN FRANCISCO, CA 94103


P102 415.252.7063
© ANKROM MOISAN ARCHITECTS, INC.
2
EMERGENCY __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A5.45
GENERATOR PER EXTENT OF 2 HOUR
ELECTRICAL RATED CHASE FOR
TANK TYPE: UL 2085 GENERATOR EXHAUST
FUEL TYPE: DIESEL
FUEL STORAGE: 750 GAL
USEABLE CAPACITY
(APPROX 820 GAL TOTAL SIM
CAPACITY)
9
6'-5 1/4"

__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A5.44
G G
F
9J.0
0 6

E 2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A5.45

THE MARK AT SEATTLE


1200 45TH ST SEATTLE, WA 98105
GENERATOR TAILPIPE AND ROOM
GENERATOR ROOM INTAKE
EXHAUST EXTENDS VERTICALLY
AIR LOUVER PER MECHANICAL
FROM THIS ROOM UP THROUGH
RATED SHAFT ON L1

1 LEVEL P1 - ENLARGED GENERATOR PLAN


2 LEVEL P1 - ENLARGED GENERATOR RCP
3 GENERATOR EXHAUST ON LEVEL 1

LCD ACQUISITIONS, LLC


1/4" = 1'-0" 1/4" = 1'-0" 1/4" = 1'-0"
GENERATOR TAILPIPE TERMINATION IN
2 WINDOW WALL SYSTEM. TAILPIPE TO EXTEND E F
MINIMUM 3' FROM SURROUNDING WALL.

LEVEL 5 LEVEL 5
229' - 8" 229' - 8"

1 2
2
2

9'-8"
9x TWO HOUR VERTICAL SHAFT FROM
2 C2 9x
UNDERSIDE OF L2 SLAB TO 2 C2 TWO HOUR VERTICAL SHAFT
UNDERSIDE OF L4 SLAB REVISION DATE REASON FOR ISSUE
FROM UNDERSIDE OF L2 SLAB
G TO UNDERSIDE OF L4 SLAB 1 Date 2 Permit Corrections #2 (first
9x 9x was 100% DD set)
2 C2 2 C2
F 9x
F 2 C2 LEVEL 4 LEVEL 4
220' - 0" 220' - 0"
12' - 2" E E
9x
2 C2

9C.3
2 6

11'-0"
GENERATOR EXHAUST AND

6 GENERATOR EXHAUST ON LEVEL 3


GENERATOR ROOM EXHAUST

5 GENERATOR EXHAUST ON LEVEL 2


TRANSFERS OVER AT UNDERSIDE OF
L2 SLAB IN TWO HOUR RATED SOFFIT 1/4" = 1'-0"
1/4" = 1'-0"
SDCI APPROVAL STAMP

3" DIAMETER ROOM EXHAUST


LEVEL 3 LEVEL 3
PIPE PER MECHANICAL
209' - 0" 209' - 0"
TWO HOUR SOFFIT UNDER L4 SLAB
FOR GENERATOR TO EXHAUST 1
FROM BUILDING A5.45
2 2

9x 9x TWO HOUR VERTICAL SHAFT FROM


2 C2 2 C2

11'-0"
UNDERSIDE OF L2 SLAB TO
UNDERSIDE OF L4 SLAB FOR
9x
F 2 C2 GENERATOR EXHAUST AND ALIGN
9M.1 GENERATOR ROOM EXHAUST
1 2.5

E F
9x
2 C2
2 C2
9x
F 7' - 0 91/128" ENLARGED
E E LEVEL 2 LEVEL 2
GENERATOR ROOM
198' - 0" 198' - 0"
9x
2 C2
BIM 360://Seattle II/210310-20-Seattle II.rvt

9M.1
60% CD SET
1 2.5

DATE PROJECT NUMBER

10 SHAFT SECTION 11/18/2022 210310

4 7 8 9
1/4" = 1'-0" SHEET NUMBER
GENERATOR EXHAUST RCP LEVEL 1 GENERATOR EXHAUST ON LEVEL 4 GENERATOR EXHAUST RCP LEVEL 4 GEN. EXHAUST SECTION
1/4" = 1'-0" 1/4" = 1'-0" 1/4" = 1'-0" 1/4" = 1'-0"
A5.44
PROJECT
11/18/2022 10:33:47 AM
SEE
ASSEMBLIES
SEE
ASSEMBLIES CONCRETE SLAB
NOT FOR
CONSTRUCTION
FIRE CAULK

Level 3 2HR MECHANICAL ENCLOSURE


EL. 209' - 0"
FIRE CAULK
THERMAL INSULATION -
MINERAL BATT

MTL J-RUNNER

RC CHANNEL
ACOUSTIC SEALANT

9G.3 9G.3
ACOUSTIC SEALANT 2 C2 2 C2
38 NORTHWEST DAVIS, SUITE 300
PORTLAND, OR 97209
503.245.7100

ACOUSTIC SEALANT
1505 5TH AVE, SUITE 300
SEATTLE, WA 98101
DEFLECTION TRACK 3C
2 C2 206.576.1600

TYPE S & G DRYWALL


1014 HOWARD STREET
ACOUSTIC SEALANT SCREWS (PER ASSEMBLY)
SAN FRANCISCO, CA 94103
SEE SEE 415.252.7063
ASSEMBLIES ASSEMBLIES © ANKROM MOISAN ARCHITECTS, INC.

1 WALL/FLOOR INTERSECTION @ 2 HR EXHAUST SHAFT


1 1/2" = 1'-0" 2 2 HR HORIZONTAL SHAFT
1 1/2" = 1'-0"

THE MARK AT SEATTLE


1200 45TH ST SEATTLE, WA 98105

LCD ACQUISITIONS, LLC


REVISION DATE REASON FOR ISSUE

SDCI APPROVAL STAMP

ENLARGED
GENERATOR
EXHAUST DETAILS
BIM 360://Seattle II/210310-20-Seattle II.rvt

60% CD SET

DATE PROJECT NUMBER


11/18/2022 210310
SHEET NUMBER

A5.45
11/18/2022 10:34:50 AM
1 4
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
2 3
A5.40

NOT FOR
H
6' - 9 3/8"
CONSTRUCTION
1 1/2" ø MTL HANDRAIL

RIGID XPS INSULATION


206'-6" DOOR BEYOND

1 1/2"
209'-0"
1" / 12
" LEVEL 3
209' - 0"

209'-0"
38 NORTHWEST DAVIS, SUITE 300

1 1/2"
2
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ PORTLAND, OR 97209
A6.09 503.245.7100

1505 5TH AVE, SUITE 300


SEATTLE, WA 98101
206.576.1600

1014 HOWARD STREET

1 RAMP 02 PLAN - LEVEL 3


1/4" = 1'-0" 2 RAMP 02 - SECTION
1/4" = 1'-0"
SAN FRANCISCO, CA 94103
415.252.7063
© ANKROM MOISAN ARCHITECTS, INC.

6
8 8.4
C
8 8.4

PARTIAL HEIGHT WALL PER PLAN


1' - 0 3/4"

PROVIDES EDGE RESTRAINT FOR RAMP


DN 6'-8"
1 1/2" ø MTL HANDRAIL
1 1/2" ø MTL HANDRAIL
C
6
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

6' - 7 7/8"
7'-0"

5'-0 3/4"
A6.09

3' - 6"

THE MARK AT SEATTLE


7' - 0"

1200 45TH ST SEATTLE, WA 98105


6"
F

7"
E
4'-10 3/4" LEVEL 1 LEVEL 1
1' - 0 3/4"

184' - 0" 184' - 0"

LCD ACQUISITIONS, LLC


4
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A6.09

6.2

3 RAMP 01 INTERIOR PLAN - LEVEL 1


1/4" = 1'-0" 4 RAMP 01 INTERIOR - SECTION
1/4" = 1'-0" 5 RAMP 02 INTERIOR PLAN - LEVEL 1
1/4" = 1'-0" 6 RAMP 02 INTERIOR - SECTION
1/4" = 1'-0"

REVISION DATE REASON FOR ISSUE


1 Date 2 Permit Corrections #2 (first
6 6.2 was 100% DD set)
6 6.2 7
8 8.4
8 8.4
6'-0"

1 1/2" ø MTL HANDRAIL


1 1/2" ø MTL HANDRAIL
6'-0"
8
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
5'-0 3/4"

A6.09

11 6' - 0"
F 6' - 0" __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A6.09

4'-0"

6"
E
6"

SDCI APPROVAL STAMP

LEVEL 1 LEVEL 1
184' - 0" 184' - 0"

7 RAMP 03 INTERIOR PLAN - LEVEL 1


1/4" = 1'-0" 8 RAMP 03 INTERIOR - SECTION
1/4" = 1'-0" 9 RAMP 04 INTERIOR PLAN - LEVEL 1
1/4" = 1'-0" 11 RAMP 04 INTERIOR- SECTION
1/4" = 1'-0"
RAMPS
BIM 360://Seattle II/210310-20-Seattle II.rvt

60% CD SET

DATE PROJECT NUMBER


11/18/2022 210310
SHEET NUMBER

A6.09
11/18/2022 10:34:59 AM
5 5.2 6 6.2 7 5 5.2 6 6.2 7
SEE GENERAL NOTES FOR ELEVATORS
SHEET A6.23 NOT FOR
CONSTRUCTION

MECH.
P300A STORAGE

SHAFT
LEVEL 4
P300B
REAR COUNTERWEIGHT REAR COUNTERWEIGHT 220' - 0"
SHAFT 1' - 7" 5" 5" 1' - 7"
ELEV PIT
LADDER

1' - 1 5/8"

1' - 1 5/8"
148'-7" 148'-7"
2x2x2 PIT SUP W SUMP PUMP 2x2x2 PIT SUP W
WITH FLUSH MOUNTED LOBBY SUMP PUMP WITH
FLUSH MOUNTED PENT ROOF
STEEL GRATE COVER P300 ELEV.

3' - 6"

3' - 6"

11'-0"
ELEV 2 ELEV 1 STEEL GRATE COVER 423' - 3" 38 NORTHWEST DAVIS, SUITE 300
9' - 0"
E02 E01 LOBBY PORTLAND, OR 97209

9' - 0"
4
300

7' - 0"

7' - 0"
503.245.7100
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A6.21

4' - 2"
CB CB 1505 5TH AVE, SUITE 300
150'-7" 4' - 2" EL: 157'-1"
D 150'-7" SEATTLE, WA 98101

9'-0"
206.576.1600
LEVEL 3

1"

1"
209' - 0" 1014 HOWARD STREET
ELEVATOR CALL SAN FRANCISCO, CA 94103
C 415.252.7063

17' - 10 3/4"
BUTTON, TYP

1' - 4 1/2"

1' - 4 1/2"
8' - 0 1/2" CLR 8 7/8" 8' - 4 3/4" 8 7/8" 8' - 0 1/2" CLR ELEV PENT © ANKROM MOISAN ARCHITECTS, INC.
2' - 1 1/8" 25' - 11 1/2" 2' - 0" 414' - 3"

11'-0"
ELEV.
5 5.2 6 6.2 7
LOBBY
ELEV.

7' - 0"

7' - 0"

9'-0"
200

6' - 11 3/4"
LOBBY

7' - 0"
2300

1 ELEVATOR 1&2 - LEVEL P3


LEVEL 2

1"

1"
1/4" = 1'-0"
198' - 0" ROOF LEVEL
405' - 3"

2' - 0 5/8"

2' - 0 5/8"
MECH.
P200A

THE MARK AT SEATTLE


STORAGE ELEV.
SHAFT

1200 45TH ST SEATTLE, WA 98105


P200B LOBBY

11'-3"
ELEV.

14'-0"
7' - 0"

7' - 0"
100
SHAFT ELEV 2 LOBBY ELEV 1
E02 2200 E01

7' - 0"

7' - 0"
ELEVATOR
LOBBY

LCD ACQUISITIONS, LLC


P200
LOBBY/LEASE
3' - 6"

3' - 6"

ELEV 2 ELEV 1 186' - 6" LEVEL 22

3' - 1"

3' - 1"

1"

1"
E02 E01 394' - 0"
9' - 0"

9' - 0"

4
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A6.21 LEVEL 1
184' - 0"

1' - 1 5/8"
CB EL: 166'-1" CB

1' - 1"
D
4' - 2"

4' - 2"

LOWEST LEVEL OF FDA ELEV.


183' - 6"

9'-8"
LOBBY
ELEV 2 ELEV. ELEV 1

6' - 11"

7' - 0"
2100
E02 E01

10'-0"
C LOBBY

7' - 0"

7' - 0"
P100
8' - 0 1/2" CLR 8 FT MIN 8' - 0 1/2" CLR
2' - 1 1/8" 25' - 11 1/2" 2' - 0"
LEVEL 21

1"

1"
384' - 4" REVISION DATE REASON FOR ISSUE
5 5.2 6 6.2 7

1' - 1 5/8"

1' - 1 5/8"
LEVEL P1
174' - 0"

2 ELEVATOR 1&2 - LEVEL P2


1/4" = 1'-0"
3
A6.42 7' - 0"
ELEVATOR

7' - 0"
LOBBY

9'-0"
P200 LEVEL 6
239' - 4"

6 5/8"
7 5/8"
1' - 1 5/8"

1' - 1 5/8"
LEVEL P2
165' - 0"
MECH. PIT LADDER TO
ELEV.

9'-8"
P100A PIT LADDER TO EXTEND AT LEAST 48" SDCI APPROVAL STAMP
MAINTENCE
EXTEND AT LEAST 48" ABOVE DOOR SILL LOBBY
SHAFT

6' - 11"

7' - 0"
RM. ABOVE DOOR SILL 500
P100B
LOBBY
7' - 0"

7' - 0"
SHAFT 7

9'-0"
A6.42 P300

ELEV. LEVEL 5

1"

1"
LOBBY 229' - 8"
P100
3' - 6"

3' - 6"

1' - 1"

1' - 1"

9@12"EA.= 9' - 0"

6 5/8"
7 5/8"
ELEV 2 ELEV 1 LEVEL P3
E01 156' - 0" ELEV.
9' - 0"

9' - 0"

4
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
E02
A6.21
PIT DEPTH
5" 5" LOBBY
6' - 6"
FLUSH 1' - 7" 1' - 7"

9'-8"
400
D
CB EL: 175'-1" CB MOUNTED STEEL FLUSH MOUNTED
ELEVATOR PLANS
4' - 2"

4' - 2"

6' - 11"

7' - 0"
GRATE COVER STEEL GRATE
A6.42
SUMP PUMP
COVER
AND SECTIONS
2' - 0"

2' - 0"

SUMP
C PUMP LEVEL 4

1"

1"
BIM 360://Seattle II/210310-20-Seattle II.rvt

8' - 0 1/2" CLR 8 FT MIN 8' - 0 1/2" CLR


220' - 0"
60% CD SET
2' - 1 1/8" 25' - 11 1/2" 2' - 0"
LEVEL P4
10
146' - 0"
5 5.2 6 6.2 7 A6.42

DATE PROJECT NUMBER


11/18/2022 210310
SHEET NUMBER

3 ELEVATOR 1&2 - LEVEL P1


1/4" = 1'-0" 4 ELEVATOR SECTION
1/4" = 1'-0" 5 ELEVATOR SECTION CONT.
1/4" = 1'-0" A6.21
11/18/2022 10:35:07 AM
NOT FOR
CONSTRUCTION

MECHANICAL MECH.
SEE GENERAL NOTES FOR ELEVATORS
100A M107
ELEC. SHEET A6.23

SHAFT

SHAFT
100B
ELEC.
5 A10.04 7 200A
SHAFT SHAFT 10 A10.07 11
8

ELEV. ELEV. 38 NORTHWEST DAVIS, SUITE 300


LOBBY

3' - 6"

3' - 6"

3' - 6"

3' - 6"
LOBBY PORTLAND, OR 97209
ELEV 2 100 ELEV 1 ELEV 2 200 ELEV 1 503.245.7100

8' - 8" CLR

8' - 8" CLR


8' - 8" CLR

8' - 8" CLR


4 E01 4 E01
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

E02 __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

E02
A6.21 A6.21 1505 5TH AVE, SUITE 300
D SEATTLE, WA 98101
EL: 187'-1" D EL: 198'-1"

4' - 2"

4' - 2"

4' - 2"

4' - 2"
206.576.1600
6' - 0"
1014 HOWARD STREET
DN SAN FRANCISCO, CA 94103
415.252.7063

C C © ANKROM MOISAN ARCHITECTS, INC.


8' - 0 1/2" CLR 8 FT MIN 8' - 0 1/2" CLR 8 FT MIN 8' - 0 1/2" CLR
8' - 0 1/2" CLR
2' - 1 1/8" 25' - 11 1/2" 2' - 0" 2' - 0" 25' - 11 1/2"

5 5.2 6 6.2
5 5.2 6 6.2 7
4
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A6.09

1 ELEVATOR 1&2 - LEVEL 1


1/4" = 1'-0" 2 ELEVATOR 1&2 - LEVEL 2
1/4" = 1'-0"

DHW DHW
PUMP RM PUMP RM

THE MARK AT SEATTLE


300A 400A

1200 45TH ST SEATTLE, WA 98105


ELEC. ELEC.
SHAFT

SHAFT
300B 400B

SHAFT 1 A10.09 2 SHAFT 2 A10.01 3

LCD ACQUISITIONS, LLC


ELEV. ELEV.
LOBBY
3' - 6"

3' - 6"

3' - 6"

3' - 6"
LOBBY
ELEV 2 300 ELEV 1 ELEV 2 400 ELEV 1
8' - 8" CLR

8' - 8" CLR


8' - 8" CLR

8' - 8" CLR


4 E01 E01
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

E02 E02
A6.21
D D
EL: 209'-1" EL: 220'-1"
4' - 2"

4' - 2"

4' - 2"

4' - 2"
5
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

6' - 0" A6.21 6' - 0"

C C
8' - 0 1/2" CLR 8 FT MIN 8' - 0 1/2" CLR 8' - 0 1/2" CLR 8 FT MIN 8' - 0 1/2" CLR
2' - 0" 25' - 11 1/2" 2' - 0" 2' - 0" 25' - 11 1/2" 2' - 0"
CORRIDOR REVISION DATE REASON FOR ISSUE
400.2
5 5.2 6 6.2 7
5 5.2 6 6.2 7

3 ELEVATOR 1&2 - LEVEL 3


1/4" = 1'-0" 4 ELEVATOR 1&2 - LEVEL 4
1/4" = 1'-0"

MECH. MECH.
500A 2000A SDCI APPROVAL STAMP
ELEC. ELEC.
SHAFT

SHAFT
500B 2000B

SHAFT SHAFT

ELEV.
ELEV.
LOBBY
3' - 6"

3' - 6"

3' - 6"

3' - 6"
LOBBY ELEV 1 ELEV 2 2000 ELEV 1
ELEV 2
500 E01 E01
8' - 8" CLR

8' - 8" CLR

E02
8' - 8" CLR

8' - 8" CLR


E02

D D
EL: 229'-9" EL: 374'-9" ELEVATOR PLANS
4' - 2"

4' - 2"

4' - 2"

4' - 2"
5 5
AND SECTIONS
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A6.21 6' - 0" A6.21

C C
BIM 360://Seattle II/210310-20-Seattle II.rvt

2' - 0"
8' - 0 1/2" CLR 8 FT MIN
25' - 11 1/2"
8' - 0 1/2" CLR
2' - 0"
8' - 0 1/2" CLR 8 FT MIN 8' - 0 1/2" CLR 60% CD SET
2' - 0" 25' - 11 1/2" 2' - 0"

5 5.2 6 6.2 7 5 5.2 6 6.2 7


DATE PROJECT NUMBER
11/18/2022 210310
SHEET NUMBER

5 ELEVATOR 1&2 - LEVEL 5-19


1/4" = 1'-0" 6 ELEVATOR 1&2 - LEVEL 20
1/4" = 1'-0"

PROJECT
A6.22
11/18/2022 10:35:13 AM
GENERAL NOTES - ELEVATOR PLANS
DHW
1.
2.
REFER TO SHEET A0.01 FOR 'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK.
VERIFY ELEVATOR SHAFT DIMENSIONS WITH MANUFACTURER PRIOR TO CONSTRUCTION.
NOT FOR
PUMP RM
2100B
3.
4.
COORDINATE SIZE AND LOCATION OF HOIST BEAM WITH ELEVATOR MANUFACTURER.
COORDINATE ENTRANCE ROUGH OPENING SIZE AND LOCATION WITH ELEVATOR MANUFACTURER. CONSTRUCTION
ELEC. Seattle Projects must include the following on their plans

SHAFT
S2100A 1. SBC SECTION 3022 AND ASME SECTIONS 2.7 AND 2.8. PIPES, DUCTS, CONDUITS, AND EQUIPMENT NOT USED FOR THE
SHAFT OPERATION OF THE ELEVATORS ARE PROHIBITED IN MACHINE ROOM AND HOISTWAYS.
2. SBC 3020. MAINTAIN ALL REQUIRED WORKING CLEARANCES IN MACHINE ROOM.
3. ASME RULE 2.2.2. WATERPROOF AS NECESSARY TO PREVENT ENTRY OF GROUND WATER. SUMP PUMPS MAY BE INSTALLED
FOR FLOOD CONTROL BUT NOT APPROVED TO MAINTAIN A DRY PIT.
4. SBC 3023, ASME RULE 2.2.4. PROVIDE PIT LADDER.
ELEV.
5. ASME RULE 2.7.5.2. MACHINE ROOM TEMPERATURE AND HUMIDITY CONTROL.
LOBBY

3' - 6"

3' - 6"
ELEV 2 ELEV 1 6. SBC 3016.5., ASME A17.1, 2.14 AND SECTION 713.14. CONTROL OF SMOKE AND HOT GASES IN ELEVATOR HOISTWAY.
2100

8' - 8" CLR


7. SBC 3016.3. COMPLY WITH SEISMIC REQUIREMENTS.

8' - 8" CLR


E02 E01
8. ASME RULE 2.7.4. PROVIDE 7’-0’ CLEAR HEADROOM IN MACHINE ROOM.
9. SBC 3016.4. AND CHAPTER 11; ACCOMMODATE PEOPLE WITH DISABILITIES.
D
384'-5" 10. ASME SECTION 2.4 AND 3.4. PROVIDE PROPER TOP CAR RUNBYS, CLEARANCES AND REFUGE SPACE.
38 NORTHWEST DAVIS, SUITE 300

4' - 2"

4' - 2"
11. ASME RULE 2.1.1.2 AND 2.11.14. GROUT ALL MASONRY JAMBS AND HEADERS TO RETAIN FIRE RATING OF HOISTWAY. IN
PORTLAND, OR 97209
5 OTHER THAN MASONRY, PROVIDE LABELED ENTRANCE ASSEMBLIES INSTALLED AS TESTED.
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

6' - 0" 503.245.7100


A6.21 12. SBC 3020. GROUT BEHIND ALL HOISTWAY PENETRATIONS FOR PIPES, FIXTURES, ETC.
13. SBC 3016.5 ELEVATOR HOISTWAYS SHALL NOT BE VENTED OR PRESSURIZED THROUGH ELEVATOR MACHINE ROOMS.
1505 5TH AVE, SUITE 300
14. SBC 3016.5.4 VENTILATION AND PRESSURIZATION EQUIPMENT, DUCTS, ETC. CANNOT BE LOCATED IN ELEVATOR MACHINE
SEATTLE, WA 98101
C ROOMS, HOISTWAYS, OR SPACES.
206.576.1600
15. ASME RULES 2.1.1.2 AND 2.14.1.8 GLASS USED IN OR ON ELEVATOR HOISTWAYS AND CARS MUST BE LAMINATED AND MEET
8' - 0 1/2" CLR 8 FT MIN 8' - 0 1/2" CLR
THE REQUIREMENTS OF ASME Z97.1.
1014 HOWARD STREET
2' - 0" 25' - 11 1/2" 2' - 0" 16. SBC 106 PROVIDE CALCULATIONS AND DRAWINGS TO SDCI FOR APPROVAL OF THE STRESSES AS NOTED IN THE APPLICABLE
SAN FRANCISCO, CA 94103
RULES OF ASME SECTION 2.9.
415.252.7063
17. ASME SECTION 2.6. PROVIDE CALCULATIONS TO DPD FOR APPROVAL OF THE ABILITY OF THE PIT FLOOR AND STRUCTURE TO
WITHSTAND THE ELEVATOR BUFFER ENGAGEMENT REACTIONS. © ANKROM MOISAN ARCHITECTS, INC.
5 5.2 6 6.2 7
18. ASME 2.27.1. PROVIDE MEANS OF TWO-WAY CONVERSATION BETWEEN EACH ELEVATOR AND A READILY ACCESSIBLE POINT
(MAIN ELEVATOR LOBBY) OUTSIDE THE HOISTWAY.
19. ASME 2.27.1.1.2 THIS STRUCTURE IS CONSIDERED AS UNATTENDED, AND AN ADDITIONAL EMERGENCY SIGNALING DEVICES
SHALL BE PROVIDED (PHONE TO ANSWERING SERVICE).

1 ELEVATOR 1&2 - LEVEL 21


1/4" = 1'-0"
20. ASME 2.27.1.1.5 PROVIDE AN EMERGENCY POWER SUPPLY FOR THE DEVICES REQUIRED BY 2.27.1 THE SUPPLY SHALL BE
CAPABLE OF OPERATING THE AUDIBLE DEVICE FOR AT LEAST ONE HOUR AND THE MEANS OF A TWO-WAY CONVERSATION
FOR AT LEAST FOUR HOURS.
21. SBC 3016.9. INSTALL APPROVED KEY RETAINER BOX, KEYED TO THE SECURE CITY KEY.
22. SBC 3016.10 KEYS REQUIRED FOR THE OPERATION OF ELEVATOR, FIRE EMERGENCY SERVICE, THE MACHINE ROOM AND THE
MECHANICAL HOISTWAY ACCESS KEY SHALL BE TAGGED AND KEPT IN THE KEY BOX.
DWH 23. IN ELEVATOR MACHINE ROOMS, DISCONNECT TO BE ON THE LOCK JAM SIDE OF THE MACHINE ROOM DOOR AND NOT MORE
THAN 24" FROM THE JAM TO OPERATING HANDLE. WAC 296-96-02460 (2007).
PUMP RM
24. COMPLY WITH APPLICABLE CODES. ELEVATOR NOTES
2200B
ELEC.
SHAFT

2200A

SHAFT

THE MARK AT SEATTLE


1200 45TH ST SEATTLE, WA 98105
ELEV.
LOBBY
3' - 6"

ELEV 2 2200 3' - 6" ELEV 1


8' - 8" CLR

8' - 8" CLR


E02 E01

LCD ACQUISITIONS, LLC


D
394'-1"
4' - 2"

4' - 2"

5
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

6' - 0"
A6.21

C
8' - 0 1/2" CLR 8 FT MIN 8' - 0 1/2" CLR
2' - 0" 25' - 11 1/2" 2' - 0"

5 5.2 6 6.2 7

F REVISION DATE REASON FOR ISSUE


E

2 ELEVATOR 1&2 - LEVEL 22


1/4" = 1'-0" 5' - 4"

ELEV 2
7 7/8"

74
19' - 11 5/8"

ELEV.
CTRL RM LOBBY

9' - 7 1/2"
75 76
MECH
2300B
ELEC.
SHAFT

2
2300A
1 A10.10 3
SHAFT SHAFT 74

7 7/8"
SDCI APPROVAL STAMP
8' - 3 1/2"
ELEV.
LOBBY 414'-3"
3' - 6"

3' - 6"

ELEV 2 2300 ELEV 1 ELEV 2 ELEV 1


8' - 8" CLR

8' - 8" CLR

8' - 8 5/8"
E02 E01 E02 E01
ELEV 1
D D
405'-4 1/4" CTRL RM
4' - 2"

4' - 2"

74
5 5
6' - 0"
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___ __ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A6.21 A6.21

C C ELEVATOR PLANS
8' - 0 1/2" CLR 8 FT MIN
2' - 1 1/8" 25' - 11 1/2"
8' - 0 1/2" CLR
2' - 0"
8' - 0 1/2" 9 1/2" 8' - 3 5/8"
9 3/8"
8' - 0 1/2" AND SECTIONS
25' - 11 1/2"

13 A12.26
BIM 360://Seattle II/210310-20-Seattle II.rvt

5 5.2 6 6.2 7 60% CD SET


5 5.2 6 6.2 7

3 ELEVATOR 1&2 - ROOF LEVEL


1/4" = 1'-0" 4 ELEVATOR PENTHOUSE FLOOR PLAN
1/4" = 1'-0"
DATE
11/18/2022
SHEET NUMBER
PROJECT NUMBER
210310

A6.23
PROJECT
11/18/2022 10:35:19 AM
8.4
8.4 8.8
NOT FOR
CONSTRUCTION

6"
LEVEL 4
220' - 0"

4' - 8 1/8"
6' - 4 1/4" CLR

3' - 4"

3' - 4"

8' - 5 7/8"
5' - 10 1/4" CLR
CAFE 38 NORTHWEST DAVIS, SUITE 300
G 188' - 0" PORTLAND, OR 97209
503.245.7100

3' - 3"

3' - 3"
4
2' - 8 1/2"

1505 5TH AVE, SUITE 300


__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A6.24
SEATTLE, WA 98101
206.576.1600

OVERUN
11' - 6"
3 5/8"

11' - 0"
1014 HOWARD STREET
SAN FRANCISCO, CA 94103
LEVEL 1
EXTERIOR 415.252.7063
184' - 0"
© ANKROM MOISAN ARCHITECTS, INC.
6' - 0 1/4" LOWEST LEVEL OF FDA
183' - 6"

8.4 183'-0"

ELEVATOR

1 RETAIL ELEV - LEVEL 1


1/2" = 1'-0"
CAB
181'-8"

LEVEL 3

8' - 10"
209' - 0"

8' - 0"
PARKING

6' - 8"
P110

THE MARK AT SEATTLE


1200 45TH ST SEATTLE, WA 98105
CB

6' - 4 1/4" CLR


4' - 8 1/8"

LCD ACQUISITIONS, LLC


1' - 0"
EL

11' - 0"
LEVEL P1
5' - 10 1/4" CLR

TEMP GLASS W/SS STANDOFFS 174' - 0"


ETCHED PUBLIC ELEV SIGN INTERIOR

G
EXTERIOR
4
2' - 8 1/2"

2' - 8 1/2"

__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___

A6.24

8.4
6' - 6 7/8"
LEVEL 2
198' - 0"
5 LOWER RETAIL ELEV
1/2" = 1'-0"
REVISION DATE REASON FOR ISSUE

2 RETAIL ELEV - LEVEL 2


1/2" = 1'-0"

20 MIN RATED ELEVATOR


DOOR W/SMOKE GASKET

10' - 0"
INTERIOR INTERIOR

SDCI APPROVAL STAMP


3"

CONC TRANSFER BEAM (PER STRUCT)


4' - 8 1/8"

6' - 4 1/4" CLR


3' - 0"

GRATE
5' - 10 1/4" CLR

18x18x18 SUMP
CAFE
188' - 0"

G
RETAIL ELEVATOR
1' - 2 3/4"

4
PLANS AND
4' - 2"
__ ____ ____ ____ ____ ____ ____ ____ ____ ____ _____ ____ ___
3' - 3 1/8"

A6.24

TEMP GLASS W/SS STANDOFFS


ETCHED PUBLIC ELEV SIGN SECTIONS
LEVEL 1
BIM 360://Seattle II/210310-20-Seattle II.rvt

X.4 183'-10"
184' - 0" 60% CD SET
LOWEST LEVEL OF FDA
183' - 6"
4 5/8" 5' - 11 5/8"
182'-4"
DATE PROJECT NUMBER
8.4
11/18/2022 210310
SHEET NUMBER

3 RETAIL ELEV - LEVEL 3


1/2" = 1'-0" 4 RETAIL ELEV
1/2" = 1'-0"

PROJECT
A6.24