TENSILE ADHESION STRENGTH TEST REPORT

Substrate : Cement Sand Render


Adhesive : Davco Super TTB 998
Test on Day 8 : 15.04.2021
Installation Date : 07.04.2021

TEST DETAILS
Location : Chamber Residence
Temperature : Ambient temperature
Surface preparation : Damp and clean the substrate with water prior to tiling
Test specimen : Homogeneous Porcelain Tile (BIa)
Specimen geometry : 50 x 50 x 12mm
Adhesive application : 6 x 6 mm notched trowel
Final thickness : 3 mm
Test Equipment : ( ) Proceq DY-216 Pull-Off Tester model STS (S/N: DT02-007-0021)
: (√ ) Proceq DY-216 Pull-Off Tester model STS (S/N: DT02-004-0044)
Ramp rate : 250 N/s
Reference : EN 12004

TEST RESULTS

Results
Test : Day 8
Mixing
No.: Adhesive system
ratio
Tensile Adhesion Tensile Adhesion
Failure Pattern
Force (N) Pressure (MPa)

8275 3.31 CFS

7450 2.98 CFS

7350 2.94 CFS


Davco Super TTB 998
25%
+
8125 3.25 CFS
Water
7700 3.08 CFS

8200 3.28 AFT

Mean 7850 3.14


Specification: EN 12004 required the tensile adhesion strength to be ≥ 0.5 N/mm2 for C1 tile adhesive and ≥ 1.0 N/mm2
for C2 after 28 days conditioning under standard condition

Conclusion:
1. From the test results obtained from site, Davco Super TTB 998 when mixed with clean water is in compliance to EN12004.

CFS = Cohesion failure within substrate

The test report shall not be reproduced wholly or in parts and no reference shall be made by the Client to the report in any publicity material without the written
consent of SIKA KIMIA.