Professional Documents
Culture Documents
CTSaturation
CTSaturation
net/publication/352297229
CITATIONS READS
0 21
1 author:
Khaled Ghambirlou
University of Tripoli
4 PUBLICATIONS 1 CITATION
SEE PROFILE
All content following this page was uploaded by Khaled Ghambirlou on 10 June 2021.
CITATIONS READS
0 106
7 authors, including:
Omar Mrehel
University of Tripoli
19 PUBLICATIONS 31 CITATIONS
SEE PROFILE
All content following this page was uploaded by Omar Mrehel on 26 March 2020.
Abstract – This paper focuses on a phenomenon known as VB : is the CT terminal voltage across external burden.
“CT Saturation” which occurs when currents of too much IP : is the primary current .
amplitude passes through the CT. CT Saturation has a ZE : is the exciting impedance .
negative effect on the CT since it decreases its reliability. IST : is the total secondary current .
In addition, the paper will discuss factors that control the
RS : is the secondary resistance.
time at which saturation occurs including “Burden
Impedance”, “Transformer Ratio” and “Primary IS : is the secondary load current .
Impedance” as well as opening secondary winding of CT. XL : is the leakage reactance.
These factors will be examined using MATLAB software. IE : is the exciting current .
The results shows that the saturation of CT is affecting by NP: NS is the CT turn ratio.
Asymmetry Current ,Burden resistor ,turn ratio and (X/R)
ZB : is the burden impedance.
ratio on the CT saturation
Index Terms— Transformer; Saturation; Power system
Current Transformers; protection element ; Protective CT saturation describes the state in a CT when it is no
relay. longer able to reproduce an output current in proportion
to its primary current or its ratio. The main cause of CT
I. INTRODUCTION saturation is the property of the core that goes into
magnetic saturation due to a number of reasons including
Current transformer is important equipment for the large primary currents, high burden or an open circuit in
power system protection component. Current the secondary [3] .
transformers are commonly used for current metering and voltage Saturation: The saturation voltage (VX) is the
providing protection in high voltage systems.. Their main symmetrical voltage across the secondary winding of the
function is transforming the high current into a low CT for which the peak induction just exceeds the
current (1 or 5 A) adequate to be processed in measuring saturation flux density where Vx is used to find the
and protection equipment (such as relays and recorders) Saturation factor Ks which can be defined as the ratio of
.They also isolate the measuring equipment from the high the saturation voltage to the excitation voltage and is an
voltage of the monitored circuit. Figure 1 shows the index of how close a CT is to saturation. It is used to
equivalent circuit of CT including load impedance.[1,2] calculate the time-to-saturate under transient
conditions[3].
(1)
(4)
where (3)
The voltage developed across CT secondary will be given
by
2
1st Conference of Industrial Technology ( CIT2017)
The peak value of ac flux is given by the following G. Minimizing the Effects of Current Transformer
relationship: Saturation
A general rule frequently used in relaying to minimize
(10) the CT saturation effects is to select a CT with AC voltage
rating at least twice that required for the maximum steady-
state symmetrical fault current.
To find the instantaneous flux in the core Adding
Equation (9),(10) Ways to avoid saturation :
To avoid AC saturation, a CT should be capable
(11)
of a secondary saturation voltage .
C. CT over sizing Factor Where is the primary current divided by the
turns ratio, and is the total secondary
Typically, an efficient design of transformer would burden ( [7].
correspond to choosing the core cross section area such To avoid saturation with a dc component in the
that should be near the knee point of B - H curve. primary wave and with pure resistive burden, the
One obvious way of avoiding CT saturation on dc flux is required (But ignoring effect of remanence
by the summation of + ) to oversize saturation voltage is:
the core, such that the corresponding B for the flux is
).
below the knee-point[5].
Where X and R are the primary system
Hence, the factor is called Core- reactance and resistance up to the point of fault.
oversizing factor Which equal To avoid saturation under the worst case or
scenario of pre magnetization (in the worst
direction) which is the worst possible case, the
required saturation voltage is :
) (12)
Where:
Figure 6 The Circuit Used In MATLAB Simulink of CT
: is the time-to-saturation
:is the primary system time constant
A. Effect of Burden
: is the saturation In this test, the CT ratio is setting at 2500 : 5, the
:is the secondary winding resistance. primary impedance is also setting at R =100 ohm and L =
:is the burden resistance[3,6]. 1 H, while R load is setting to 4 and 14 ohm respectively.
3
1st Conference of Industrial Technology ( CIT2017)
Figure (7,8) Show the output of secondary current with C. Effect of Hysteresis With Different Burden
different Burden resistances. In this case the burden are is changed from 1 ohm to be
10
Secondary Current Vs time
9 ohm , and the parameters of this test are (Turn ration
8
2500:5), frequency 50Hz,Breaker Time (1/50), R primary
100 Ω &L primary 1H.Figure 10 Shows the Simulink
6
Scope output For the flux and secondary current with the
effect of the hysteresis.
IS
-2 2
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1
time (s)
Figure 7 Secondary Current with burden of 4 Ohm, 1
IS
Secondary Current Vs time
7
0
6
-1
5
4 -2
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1
3
time (s)
IS
2 FLUX Vs time
1 2
0
1.5
-1
FLUX
1
-2
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1
time (s) 0.5
Figure 8 Secondary Current with burden of 14 Ohm
0
5 10
IS
2
IS
0 0
0
-5 -2
-10
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1 0.11 0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1 0 0.02 0.04 0.06 0.08 0.1
time (s) time (s)
time (s) Primary Current Vs time
FLUX Vs time FLUX Vs time 5000
2
10
Ip
1.5 0
5
FLUX
1 -5000
FLUX
-5 -0.5 0
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.11
time (s)
time (s) -5
0 0.02 0.04 0.06 0.08 0.1
(a) (b) time (s)
Figure (9 ) Simulink Output a) Without Hysteresis. b) with Hysteresis Figure 11 Simulink Output At No Asymmetry Current For Primary
For Secondary Current and Flux. Current, Secondary Current and Flux .
4
1st Conference of Industrial Technology ( CIT2017)
-1
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1 0.11
time (s)
Secondary Current Vs time
10
IS
-10
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1 0.11 Fig 14 The Secondary Current when the X\R ratio = 0.628
time (s)
FLUX Vs time
10
FLUX
-10
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1 0.11
time (s)
F. Effect of Asymmetry Current with Hystersis and It was Found From Figure 13(a,b) The Secondary
burden Current when the X\R ratio = 0.628 and the time-to-
In this case The breaker closing time is changed in saturation is approximately 0.138S . However The
order to close at a voltage zero crossing. t = 1/50 s is Secondary Current when the X\R ratio = 8.79 and the
used. This switching instant will produce full current time-to-saturation is approximately 0.0379 S .
asymmetry in the shunt reactor . The parameters of this
test are (Turn ration 2500:5),R burden 9 Ω , frequency H. Effect of Turn Ratio
50Hz, R primary 100 Ω &L primary 1H. Figure 13
Shows the Simulink Scope output For the flux , primary In this test, the load impedance is to 2 ohm and the
and secondary currents. primary impedance is set constant at R =100 ohm and L =
1 H, while the CT ratio is variable between 200:1 and
x 10
4
Primary Current Vs time 2500:5. Figure (16,17) Shows the output of secondary
1
current with different turns ratio .
Ip
0
Secondary Current Vs time
25
-1
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1 0.11
time (s)
Secondary Current Vs time 20
5
IS
0 15
-5
IS
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1 0.11 10
time (s)
FLUX Vs time
2 5
FLUX
0
0
-2
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1 0.11
-5
time (s) 0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1 0.11
0.11
Figure13 Simulink Output At Asymmetry Current and Hysteresis t ime (s)
with High Burden For Primary Current, Secondary Current and Flux .
Fig 16 The Secondary Current When the .CT ratio 200:1
5
1st Conference of Industrial Technology ( CIT2017)
IV. CONCLUSION
Secondary Current Vs time
10
By investigate the effect of flux on the CT, where
it was found that the increase of flux above a
8
certain limit leads to saturation.
The impact of X\R ratio was analyzed, and found
6
that as the X\R ratio increase the time to saturation
will be sorted.
IS
4
When the remnant flux is extremely high, the core
2
will reach the saturation almost immediately,
especial when the burden is high.
0
CTs that have lowest ratio, they are the fastest to
saturation.
-2
Simulation results show that the maximum dc
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1 0.11
component of a fault occurs when the
t ime (s)
instantaneous voltage is zero, which is make the
Fig 17 The Secondary Current When the CT ratio 2500:5 primary current unsymmetrical, and then results
shorter CTs saturation.
From the simulation outputs illustrated in Figure
The maximum dc component of a fault occurs
(16,17), It is clear that at 2500:5 turns ratio time to
when the instantaneous voltage is zero. Then the
saturation is approximately 0.044S while at 200:1 turns
dc component starts decaying according to the
ratio time to saturation decreases to approximately
time constant of the primary power system. The
0.029mS.
larger time constant will result in the longer
I. Effect of Over voltage decaying process, and then longer CT saturation
period.
In the effect of over voltage , The primary breaker time The CTs have the lowest burden and Rct show
sets at t=(1.25/50 S) and change the secondary switch the best performance and they have large time to
opening time to t=0.2S. The overvoltage at this case saturation.
produced when the secondary switch is open. Figure 18
The overvoltage on the secondary of the CT
Shows the output of primary , secondary current and the
should be avoided by which (open circuit). in
flux at this case .
this case, the flux, which is corresponding to
voltage, will increase and shorten the time to
saturation
Primary Current Vs time .
5000
REFERENCES
Ip
-5000
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1 0.11 [1] Sachin Tiwari, Aditya Pandey “ Current Transfromer Sizing &
time (s) Saturation Calculation with Transient Performance Analysis of
-4 CT Using ATP Software”, IJAREEIE Vol 4, Issue 5, May 2015.
x 10 Secondary Current Vs time
5 [2] Roy E. Cosse, Donald G.Dunn, Robert M. Spiewak, “CT
SATURATION CALCULATION “ , IEEE Paper No. PCIC -
+ 2005-32.
IS
0 [3] IEEE Guide for the Application of Current Transformers Used for
Protective Relaying Purposes, IEEE Std C37.110-1996.
-5 [4] Norman T Stringer, “ The Effect of Dc offset on Current-
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1 0.11
Operated Relays,” IEEE Transactions on Industry Application,
time (s)
Vol 34, no.1, pp.154-159, Jan/Feb.1998.
FLUX Vs time [5] Riyas Ahamed M , Vimaraj M , Arjuna Rao S, “ Saturation
10 Analysis of Current Transformer “ ,Int J Res Rev Volume 2, Issue
FL UX
6 , June 2015 .
0 [6] IEEE Guide for the Application of Current Transformers Used for
Protective Relaying Purposes, IEEE Std C37.110-2007.April
-10 2008.
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1 0.11 [7] Zhihan Xut, Matt Proctor, Ilia Voloh, “CT saturation tolerance for
time (s) 87L applications” the 68th Annual Conference for Protective
Relay Engineers. March 30 2015-April 2 2015 College Station,
TX, USA.