Question (5): (16 Marks)

For the shown fig. an existing concrete beam in upper roof slab at axis 2. its required
to hold an additional elevator load with 8 ton in the middle span. Check the safty of
this beam only and take the nessary engineering action for this beam ( the clear height
of floor under beam not less than 2.20 m).

Examiners Signature
Dr. Ghada Diaa , Prof. Dr. Ahmed Ali and Prof. Dr. Hany Abdalla Page 6 of 20
Question (6): (40 Marks)
A old factory consists of one story as shown in the next figure with 8.0 m spans.
The slab th. was 28 cm with 42 cm drop panel. The client wants to add 4 new
floors and also increase L.L of the exisiting floor from 500 kg/m2 to be 1000
kg/m2. It is required to check the marked elements on plan of the factory to
carry the added loads from this modification as follows:

n Check the status of the two columns mentioned in plan to carry the new
floors ( safe or not) (4Marks)

n Check the status of the footings mentioned in plan to carry the new loads
( safe or not) (4Marks)

n Advise the client about your recommendation to modify the factory for
the clouded columns and footings show all available alternatives to solve
this issue. ( we need only sketches)
‫ﻣﻄﻠﻮب ﻛﺎﻓﮫ اﻟﺤﻠﻮل اﻟﻤﻤﻜﻨﮫ – اذﻛﺮ ﻣﻊ اﻟﺮﺳﻢ ﻓﻘﻂ‬ (8Marks)

n Suggest the suitable enginerring solution to solve any structural problem


for the two mentioned locations of columns and footing only. ( need
calculation and sketch ) (16 Marks)

n For the existing roof and due to increase of L.L the marked locations show
in slab was subjected to an increase of 26.5% for positive moment location
from the original moments. Its required to take an actions for this issue
( need calculation and sketch ) (8 Marks)

Using Data:
- Fcu = 300 kg/cm2 and Fy= 4000 kg/cm2
- Soil bearing capacity = 1.75 kg/cm2.
- L.L= 1000 kg/m2, flooring 250 kg/m2 and no internal wall
- H floor = 3.25 m b wall = 25 cm wall density = 1.8 t/m3

- Column type C1 --- 30*60 cm has 10T16 vertical reinforcement with 6R8/m
stirrups
- Column type C5 --- 70*70 cm has 32T16 vertical reinforcement with 8R8/m
stirrups

Examiners Signature
Dr. Ghada Diaa , Prof. Dr. Ahmed Ali and Prof. Dr. Hany Abdalla Page 9 of 20
- Isolated type F1 -- 275*245*30 cm plain concrete and 215*185*50 cm
reinforced concrete with 6T16/m in two directions.
- Isolated type F5 -- 415*415*30 cm plain concrete and 355*355*60 cm
reinforced concrete with 8T18/m in two directions.

Roof plan

Examiners Signature
Dr. Ghada Diaa , Prof. Dr. Ahmed Ali and Prof. Dr. Hany Abdalla Page 10 of 20
Footing plan

Columns plan

Examiners Signature
Dr. Ghada Diaa , Prof. Dr. Ahmed Ali and Prof. Dr. Hany Abdalla Page 11 of 20
fcu & fy in N/mm2 for all Equations
d=c1Ö(Mu / fcu b) , As =Mu /fy j d ,

R=Mu/fcubd2 , As =w (fcu/fy) bd, As/ =a. As


B (for T-sec.) = smaller of (16ts + b) and (L/5 + b)
mmax (for Beams)= 5*10-4. fcu (for fy = 360 N/mm2)
Minimum Rft. Main Rft. in Beams Stirrups in Beams
(1.1/fy).bd or
As min (0.4/fy)b.s
1.3Asreq
Absolute Minimum 0.15/100 5f 8/m

qcu=0.24Ö( fcu/gc) N /mm2 qcu max=0.70Ö( fcu/gc) N /mm2

qst u = qu - qcu/2 = Ast.( fyst /gs) / b.s qu = Qu / b d

Examiners Signature
Dr. Ghada Diaa , Prof. Dr. Ahmed Ali and Prof. Dr. Hany Abdalla Page 20 of 20