SHORT CIRCUIT ANALYSIS AND CALCULATIONS

PROJECT NAME :AS BUILT PLAN OF TWO STOREY COMMERCIAL BUILDING


OWNER :TESSIE M. GALLETO
LOCATED AT SANGHAN, CABADBARAN CITY, AGUSAN DEL NORTE

PER-UNIT METHOD : LINE-TO-LINE FAULT @230V - FAULT X1


Line Data One Line Diagram Impedance Diagram Calculations
VOLTAGE DROP COMPUTATIONS
ANECO Data Fault at X1 10,000kVA Base
25,000kVA PUR PUX
3phase Source Step#1: Pux(3Ф) = 10,000/25000 Basic VD formula for 1Phase System
SLGF Amps= = 0.4 Voltage Drop (VD) = 200% x L x Rw x Itotal
S.C. kVA Step#2: Pux(1Ф) = 2 x 0.4 Where:
= 0.8 0.8000 L = Length of the Service Drop Aneco Feeder=20mtrs
Step#3 Pux = (1.22)(10000)/(100)(50)
Pux = (1.22)(10000)/(20)(50)2.44 2.4400
Rw =Resistance of the Conductor wire (from PEC-1 , 2017, Table 10.1.1.8 page941)
Step#4 Pur = (0.7625)(10000)/(100)(50) Rw#14.00mm2 Copper= 0.510Ώ/305m
Pur = (1.22)(10000)/(20)(50)1.525 1.525 Rw#14.00mm2 Aluminum= 0.808/305m
ANECO Step#5 PUX= 2(0.00008)(10000) I-total = Total Load Amps of the System From Schedule of Loads section
COMMONAL (1000) (0.230)2
Thus Itotal= 43.4 Amps
SERVICE PUX = 0.030245747 0.0302
TRANSFORMER Step#6 PUX = 2(25/1000)x 0.0475x (10000) To solve the VD of the Main Feeder Service Drop
1x50kVA (1000) (0.230)2 VD(copper)= 200% x (20m) x (0.510Ώ/305m) x 43.40
Single Phase PUX = 0.448960302 0.4490 2.9 volts
%X= 1.22 Step#7 PUR = 2(25/1000)x 0.6404x (10000) VOLTAGE REGULATION %= 2.9/230Volts x 100%
%R= 0.7625 (1000) (0.230)2 =
%Z= 0.02 PUR = 6.052930057 6.0529
1.26 %
X/R ratio: 1.6 TOTAL PUR and PUX= 7.57793 3.719206 VD(Aluminum)= 200% x (20m) x (0.808Ώ/305m) x 43.40
as per table 1.3 Step#8 PUZ= ((7.57793)2 + (3.719206)2 )1/2 4.6 volts
Service Drop/F PUZ= 8.4414 VOLTAGE REGULATION %= 4.6/230Volts x 100%
2w-#14.0mm2THW Cu = 2.0 %
I-sc LL @230V,1Ф = 10,000/ (0.230)x(8.4414)
Fault at X1 = 5150.6 Amps
MAIN ACB = 5.2 kA
60AT/60AF I-sc total = 5.2 kA
23OV/1Ø Therefore use:
10kAIC ICCR rating 10 kAIC

C-constant from Table#6 page #27


IEEE std 241-1990
IEEE Recommended Practice for Commercial Bldg
Power Systems - Copyright IEEE Inc.

FROM THE OFFICE OF: NO. SEAL PROJECT TITLE APPROVED PER PLAN AND SPECIFICATIONS CAD BY: SHEET CONTENT: SHEET NO
PRC REG.
VALIDITY
AS-BUILT PLAN OF TWO STOREY E
PTR
NO. TESSIE M. GALLETO
PROFESSIONAL ELECTRICAL ENGINEER DATE COMMERCIAL BUILDING 44
PLACE
OWNER
TN
NO. LOCATION: SANGHAN CABADBARAN CITY, AGUSAN DEL NORTE ADDRESS: SANGHAN CABADBARAN CITY, AGUSAN DEL NORTE

You might also like