NMH-AUF-016-Flow Duct Air Velocity Sensor Analog Input 0-10 V Not Tested
Fan Airflow Status From
NMH-AUF-016-FlowSts Binary Input NoFlow;Flow Not Tested
DPS
NMH-AUF-016-Rh Duct Humidity Analog Input 0-10V Not Tested
NMH-AUF-016-RunSts Fan Run Status From MCC Binary Input Off;On Not Tested
NMH-AUF-016-Trip Fan Trip Status From MCC Binary Input Normal;Trip Not Tested
Not Ready for T&C
Fan In Auto Position At
NMH-AUF-018-AutoSts Binary Input NotInAuto;Auto Not Tested
MCC
NMH-AUF-018-Cmd Fan Command Binary Ouput Stop;Start Not Tested
NMH-AUF-018-Flow Duct Air Velocity Sensor Analog Input 0-10 V Not Tested
Fan Airflow Status From
NMH-AUF-018-FlowSts Binary Input NoFlow;Flow Not Tested
DPS
DDCP-SF-04-04A Page 1 of 6
NMH-AUF-018-Rh Duct Humidity Analog Input 0-10V Not Tested
NMH-AUF-018-RunSts Fan Run Status From MCC Binary Input Off;On Not Tested
NMH-AUF-018-Trip Fan Trip Status From MCC Binary Input Normal;Trip Not Tested
NMH-DEH-161-RmTemp Room Temperature Analog Input NTC 20K Tested 23.6 ºC No Access to Reach DEH
NMH-DEH-164-Cmd Heater On Off Command Binary Ouput Off;On Not Tested Off;On
NMH-DEH-164-RmTemp Room Temperature Analog Input NTC 20K Tested 17.9 ºC No Power from DP
NMH-DEH-164-Sts Heater On Off Status Binary Input Off;On Not Tested Off;On
DDCP-SF-04-04A Page 2 of 6
NMH-DEH-167-Sts Heater On Off Status Binary Input Off;On Not Tested Off;On No Relay for Status
NMH-DEH-169-Cmd Heater On Off Command Binary Ouput Off;On Not Tested Off;On
NMH-DEH-169-RmTemp Room Temperature Analog Input NTC 20K Tested 17.6 ºC No Access to Reach DEH
NMH-DEH-169-Sts Heater On Off Status Binary Input Off;On Not Tested Off;On
NMH-DEH-182-Cmd Heater On Off Command Binary Ouput Off;On Not Tested Off;On
NMH-DEH-182-RmTemp Room Temperature Analog Input NTC 20K Tested 21.6 ºC No Termination for Power & BMS
NMH-DEH-182-Sts Heater On Off Status Binary Input Off;On Not Tested Off;On
NMH-DEH-185-RmTemp Room Temperature Analog Input NTC 20K Tested 22.6 ºC No DEH At Location
DDCP-SF-04-04A Page 3 of 6
NMH-DEH-188-RmTemp Room Temperature Analog Input NTC 20K Tested 23.6 ºC
NMH-DEH-191-RmTemp Room Temperature Analog Input NTC 20K Tested 21.2 ºC No Access to Reach DEH
NMH-DP-L2-CCU-MECH1-Flt Panel Fault Status Binary Input Normal;Alarm Not Tested Normal;Alarm No Continuity in Cable
NMH-DP-L2-CCU-MECH1-Sts Panel On Off Status Binary Input Off;On Not Tested Off;On No Continuity in Cable
DDCP-SF-04-04A Page 4 of 6
NMH-DP-L2-CCU-MECH-Flt Panel Fault Status Binary Input Normal;Alarm Tested Normal;Alarm
NMH-DP-L2-ICU-MECH1-Flt Panel Fault Status Binary Input Normal;Alarm Tested Normal;Alarm Broker Always Showing NC
DDCP-SF-04-04A Page 5 of 6
Field Side No termination
DDCP-SF-04-04A Page 6 of 6