TESTING /COMMISSIONING REPORT

Saudi Arabia JOB NO: SAB000565

AL MOUAWASAT HOSPITAL - MADINA


CPO-PC-6A DATE: 12-10-2021 COMMISSIONING BY: MOHAMED ASHIQ
BMS - HVAC SYSTEM DDC No: DDCP-SF-04-04A Revision: 00

BMS - HVAC SYSTEM


State Text/Device
Point Name Point Description Point Type Status Present Value Remark
Type/ Polarity
Fan In Auto Position At
NMH-AUF-016-AutoSts Binary Input NotInAuto;Auto Not Tested
MCC
NMH-AUF-016-Cmd Fan Command Binary Ouput Stop;Start Not Tested

NMH-AUF-016-Filter Dirty Filter Binary Input Normal;Alarm Not Tested

NMH-AUF-016-Flow Duct Air Velocity Sensor Analog Input 0-10 V Not Tested
Fan Airflow Status From
NMH-AUF-016-FlowSts Binary Input NoFlow;Flow Not Tested
DPS
NMH-AUF-016-Rh Duct Humidity Analog Input 0-10V Not Tested

NMH-AUF-016-RunSts Fan Run Status From MCC Binary Input Off;On Not Tested

NMH-AUF-016-SpdCtrl VFD Speed Control Analog Output 0-10V Not Tested

NMH-AUF-016-SpdFb VFD Speed Feedback Analog Input 0-10V Not Tested

NMH-AUF-016-Temp Duct Temperature Analog Input NTC 20K Not Tested

NMH-AUF-016-Trip Fan Trip Status From MCC Binary Input Normal;Trip Not Tested
Not Ready for T&C
Fan In Auto Position At
NMH-AUF-018-AutoSts Binary Input NotInAuto;Auto Not Tested
MCC
NMH-AUF-018-Cmd Fan Command Binary Ouput Stop;Start Not Tested

NMH-AUF-018-Filter Dirty Filter Binary Input Normal;Alarm Not Tested

NMH-AUF-018-Flow Duct Air Velocity Sensor Analog Input 0-10 V Not Tested
Fan Airflow Status From
NMH-AUF-018-FlowSts Binary Input NoFlow;Flow Not Tested
DPS

DDCP-SF-04-04A Page 1 of 6
NMH-AUF-018-Rh Duct Humidity Analog Input 0-10V Not Tested

NMH-AUF-018-RunSts Fan Run Status From MCC Binary Input Off;On Not Tested

NMH-AUF-018-SpdCtrl VFD Speed Control Analog Output 0-10V Not Tested

NMH-AUF-018-SpdFb VFD Speed Feedback Analog Input 0-10V Not Tested

NMH-AUF-018-Temp Duct Temperature Analog Input NTC 20K Not Tested

NMH-AUF-018-Trip Fan Trip Status From MCC Binary Input Normal;Trip Not Tested

NMH-DEH-161-Cmd Heater On Off Command Binary Ouput Off;On Not Tested

NMH-DEH-161-RmTemp Room Temperature Analog Input NTC 20K Tested 23.6 ºC No Access to Reach DEH

NMH-DEH-161-Sts Heater On Off Status Binary Input Off;On Not Tested

NMH-DEH-162-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-162-RmTemp Room Temperature Analog Input NTC 20K Tested 19.6 ºC

NMH-DEH-162-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-163-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-163-RmTemp Room Temperature Analog Input NTC 20K Tested 18.2 ºC

NMH-DEH-163-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-164-Cmd Heater On Off Command Binary Ouput Off;On Not Tested Off;On

NMH-DEH-164-RmTemp Room Temperature Analog Input NTC 20K Tested 17.9 ºC No Power from DP

NMH-DEH-164-Sts Heater On Off Status Binary Input Off;On Not Tested Off;On

NMH-DEH-165-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-165-RmTemp Room Temperature Analog Input NTC 20K Tested 19.6 ºC

NMH-DEH-165-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-166-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-166-RmTemp Room Temperature Analog Input NTC 20K Tested 19.8 ºC

NMH-DEH-166-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-167-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-167-RmTemp Room Temperature Analog Input NTC 20K Tested 20.6 ºC

DDCP-SF-04-04A Page 2 of 6
NMH-DEH-167-Sts Heater On Off Status Binary Input Off;On Not Tested Off;On No Relay for Status

NMH-DEH-168-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-168-RmTemp Room Temperature Analog Input NTC 20K Tested 20.2 ºC

NMH-DEH-168-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-169-Cmd Heater On Off Command Binary Ouput Off;On Not Tested Off;On

NMH-DEH-169-RmTemp Room Temperature Analog Input NTC 20K Tested 17.6 ºC No Access to Reach DEH

NMH-DEH-169-Sts Heater On Off Status Binary Input Off;On Not Tested Off;On

NMH-DEH-170-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-170-RmTemp Room Temperature Analog Input NTC 20K Tested 21.6 ºC

NMH-DEH-170-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-182-Cmd Heater On Off Command Binary Ouput Off;On Not Tested Off;On

NMH-DEH-182-RmTemp Room Temperature Analog Input NTC 20K Tested 21.6 ºC No Termination for Power & BMS

NMH-DEH-182-Sts Heater On Off Status Binary Input Off;On Not Tested Off;On

NMH-DEH-184-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-184-RmTemp Room Temperature Analog Input NTC 20K Tested 23.6 ºC

NMH-DEH-184-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-185-Cmd Heater On Off Command Binary Ouput Off;On Not Tested

NMH-DEH-185-RmTemp Room Temperature Analog Input NTC 20K Tested 22.6 ºC No DEH At Location

NMH-DEH-185-Sts Heater On Off Status Binary Input Off;On Not Tested

NMH-DEH-186-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-186-RmTemp Room Temperature Analog Input NTC 20K Tested 23.6 ºC

NMH-DEH-186-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-187-Cmd Heater On Off Command Binary Ouput Off;On Not Tested


Transformer connection not yet
NMH-DEH-187-RmTemp Room Temperature Analog Input NTC 20K Tested 21.2 ºC
and No Proper Access
NMH-DEH-187-Sts Heater On Off Status Binary Input Off;On Not Tested

NMH-DEH-188-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

DDCP-SF-04-04A Page 3 of 6
NMH-DEH-188-RmTemp Room Temperature Analog Input NTC 20K Tested 23.6 ºC

NMH-DEH-188-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-189-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-189-RmTemp Room Temperature Analog Input NTC 20K Tested 23.6 ºC

NMH-DEH-189-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-190-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-190-RmTemp Room Temperature Analog Input NTC 20K Tested 23.6 ºC

NMH-DEH-190-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-191-Cmd Heater On Off Command Binary Ouput Off;On Not Tested

NMH-DEH-191-RmTemp Room Temperature Analog Input NTC 20K Tested 21.2 ºC No Access to Reach DEH

NMH-DEH-191-Sts Heater On Off Status Binary Input Off;On Not Tested

NMH-DEH-192-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-192-RmTemp Room Temperature Analog Input NTC 20K Tested 23.6 ºC

NMH-DEH-192-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-193-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-193-RmTemp Room Temperature Analog Input NTC 20K Tested 23.6 ºC

NMH-DEH-193-Sts Heater On Off Status Binary Input Off;On Tested Off;On


No Provision for CMD in the Panel,
NMH-DL-L2-CCU-Cmd Panel On Off Command Binary Ouput Off;On Not Tested Off;On
Please Confirm to remove
NMH-DL-L2-CCU-Flt Panel Fault Status Binary Input Normal;Alarm Tested Normal;Alarm

NMH-DL-L2-CCU-Sts Panel On Off Status Binary Input Off;On Tested Off;On

NMH-DP-L2-CCU-Flt Panel Fault Status Binary Input Normal;Alarm Tested Normal;Alarm

NMH-DP-L2-CCU-MECH1-Flt Panel Fault Status Binary Input Normal;Alarm Not Tested Normal;Alarm No Continuity in Cable

NMH-DP-L2-CCU-MECH1-Sts Panel On Off Status Binary Input Off;On Not Tested Off;On No Continuity in Cable

NMH-DP-L2-CCU-MECH2-Flt Panel Fault Status Binary Input Normal;Alarm Tested Normal;Alarm

NMH-DP-L2-CCU-MECH2-Sts Panel On Off Status Binary Input Off;On Tested Off;On

DDCP-SF-04-04A Page 4 of 6
NMH-DP-L2-CCU-MECH-Flt Panel Fault Status Binary Input Normal;Alarm Tested Normal;Alarm

NMH-DP-L2-CCU-MECH-Sts Panel On Off Status Binary Input Off;On Tested Off;On

NMH-DP-L2-CCU-Sts Panel On Off Status Binary Input Off;On Tested Off;On

NMH-DP-L2-ICU-MECH1-Flt Panel Fault Status Binary Input Normal;Alarm Tested Normal;Alarm Broker Always Showing NC

NMH-DP-L2-ICU-MECH1-Sts Panel On Off Status Binary Input Off;On Tested Off;On

NMH-DP-L2-ICU-MECH2-Flt Panel Fault Status Binary Input Normal;Alarm Tested Normal;Alarm

NMH-DP-L2-ICU-MECH2-Sts Panel On Off Status Binary Input Off;On Tested Off;On

NMH-EDL-L2-CCU-Flt Panel Fault Status Binary Input Normal;Alarm Tested Normal;Alarm

NMH-EDL-L2-CCU-Sts Panel On Off Status Binary Input Off;On Tested Off;On

NMH-EDP-L2-CCU-Flt Panel Fault Status Binary Input Normal;Alarm Tested Normal;Alarm

NMH-EDP-L2-CCU-UPS1-Flt Panel Fault Status Binary Input Normal;Alarm Tested Normal;Alarm

NMH-EDP-L2-CCU-UPS1-Sts Panel On Off Status Binary Input Off;On Tested Off;On

NMH-EDP-L2-CCU-UPS2-Flt Panel Fault Status Binary Input Normal;Alarm Tested Normal;Alarm

NMH-EDP-L2-CCU-UPS2-Sts Panel On Off Status Binary Input Off;On Tested Off;On

NMH-EDP-L2-CCU-Sts Panel On Off Status Binary Input Off;On Tested Off;On

NMH-EDP-L2-CCU-UPS-Flt Panel Fault Status Binary Input Normal;Alarm Tested Normal;Alarm

NMH-EDP-L2-CCU-UPS-Sts Panel On Off Status Binary Input Off;On Tested Off;On

NMH-ESMDB-L2-DS-N-Flt Panel Fault Status Binary Input Normal;Alarm Tested Normal;Alarm

NMH-ESMDB-L2-DS-N-Sts Panel On Off Status Binary Input Off;On Tested Off;On

NMH-UVL-029-Change UV Lamp Change Binary Input Normal;Change Not Tested

NMH-UVL-029-Fail UV Lamp Fail Alarm Binary Input Normal;Fail Not Tested

NMH-UVL-030-Change UV Lamp Change Binary Input Normal;Change Not Tested

NMH-UVL-030-Fail UV Lamp Fail Alarm Binary Input Normal;Fail Not Tested


Field Side No termination
NMH-UVL-033-Change UV Lamp Change Binary Input Normal;Change Not Tested

NMH-UVL-033-Fail UV Lamp Fail Alarm Binary Input Normal;Fail Not Tested

NMH-UVL-034-Change UV Lamp Change Binary Input Normal;Change Not Tested

DDCP-SF-04-04A Page 5 of 6
Field Side No termination

NMH-UVL-034-Fail UV Lamp Fail Alarm Binary Input Normal;Fail Not Tested


No. of Not
Total No. of Points: 120 No. of Tested: 72
Tested:
48 60%
General Note:

TESTED BY WITNESSED BY WITNESSED BY

HONEYWELL REPRESENTATIVE MEP CONTRACTOR REPRESENTATIVE CONSULTANT REPRESENTATIVE

Name : Mohamed Ashiq Name : Name :

Signature : Signature : Signature :