09 WATER SUPPLY FACILITIES

09.01 General

Iron and steel plant is as such a heat intensive


process wherein a considerable quantity of cooling
water is required for control of metallurgical
processes as well as for dissipation of unutilized
heat. In order to conserve precious fresh water,
water economy has been an underlying criterion for
selection of plant and equipment. In order to further
economize on fresh water demand, closed circuit
water re-circulation systems have been planned to
effect extensive recycling and reuse of return water
from plant processes. Clarified water from surface
water will be used in the secondary side of plate
heat exchangers for cooling of process water in the
primary side and also for direct cooling circuits.
Primary side water will be re-circulated in closed
circuits.
Evaporative cooling towers will be provided for
cooling clarified water re-circulating in the
secondary circuits and direct cooling circuits.
Process water losses will be compensated by adding
make-up water of respective qualities.

09.02 Requirement of water

Estimated requirement of water for various plant


units and process is indicated in table-09.01.

Table - 09.01
Estimated water requirement
2

Water requirement, m3/h

Sl. Consumer unit Circulation water Make-up water


No
Soft water Industrial Soft Industrial
in Primary water water make-up
ckt secondary make - up water
ckt/open
ckt cooling

1 Induction Furnaces 350 350 2.0 17

2 Ladle Furnace 110 110 1.0 6

3 FEU Unit for 360 18


EAF + LF

4 Continuous Billet
Caster
- Mould cooling 180 180 1.0 9
(closed circuit)
- Machine cooling 84 84 0.5 4
(closed circuit)
- Spray & machine 72 10 7
cooling (open
circuit)

5 Hot Rolling Mill 160 50 2 5

5 Soft water plant 10

6 Misc. Service water 7


(General purpose)

7 Plant Drinking 15
Water

Total make-up
water requirement 98
3

The total requirement of fresh water from surface


water source to meet process make-up and drinking
needs is estimated as 98 m³/hr.

09.03 Availability of water

Make up water will be available from Desalination


plant, provided by ministry of housing, electricity
and water. A water treatment plant shall be
installed for cooling, filtering and reuse of cooling
water.