Professional Documents
Culture Documents
Transformers 22-02-2023
Transformers 22-02-2023
1. Introduction
A transformer is a device which uses the phenomenon of mutual induction to
change the values of alternating voltages and currents.
One of the main advantages of a.c. transmission and distribution is the
ease with which an alternating voltage can be increased or decreased by
transformers.
Losses in transformers are generally low and thus efficiency is high.
Being static they have a long life and are very stable.
A transformer is represented in Figure 1(a) as consisting of two electrical
circuits linked by a common ferromagnetic core. One coil is termed the primary
winding which is connected to the supply of electricity, and the other the
secondary winding, which may be connected to a load. A circuit diagram
symbol for a transformer is shown in Figure 1(b).
Figure 1: Transformer.
V1/V2 is called the voltage ratio and N1/N2 the turn’s ratio, or the transformation
ratio of the transformer. If N2 is less than N1 then V2 is less than V1 and the
device is termed a step-down transformer. If N2 is greater, then N1 then V2 is
greater than V1 and the device is termed a step-up transformer.
Hence,
Example 1
An ideal transformer with a turns ratio of 2:7 is fed from a 240 V supply.
Determine its output voltage.
Solution
Turns ratio is
Example 2
An ideal transformer has a turns ratio of 8:1 and the primary current is 3 A
when it is supplied at 240 V. Calculate the secondary voltage and current.
Example 3
A 5 kVA single-phase transformer has a turns ratio of 10:1 and is fed from a 2.5
kV supply. Neglecting losses, determine (a) the full-load secondary current, (b)
the minimum load resistance which can be connected across the secondary
winding to give full load kVA, (c) the primary current at full load kVA.
Solution
The primary induced e.m.f. E1 is in phase opposition to V1 (by Lenz’s law) and
is shown 180° out of phase with V1 and equal in magnitude. The secondary
induced e.m.f. is shown for a 2:1 turns ratio transformer.
Example 4
A 2400 V/400 V single-phase transformer takes a no-load current of 0.5 A and
the core loss is 400 W. Determine the values of the magnetizing and core loss
components of the no-load current. Draw to scale the no-load phasor diagram
for the transformer.
Solution
Since 1 Wb/s = 1 volt, the average e.m.f. induced in each turn = 4ƒΦ𝑚 volts.
As the flux Φ varies sinusoidally, then a sinusoidal e.m.f. will be induced in
each turn of both primary and secondary windings.
Hence,
Example 7
A single-phase, 50 Hz transformer has 25 primary turns and 300 secondary
turns. The cross-sectional area of the core is 300 cm2. When the primary
winding is connected to a 250 V supply, determine (a) the maximum value of
5. Transformer construction
i. There are broadly two types of single-phase double-wound transformer
constructions as shown in Figure 4.
The core type and
The shell type.
The low and high voltage windings are wound as shown to reduce
leakage flux.
7. Regulation of a transformer
When the secondary of a transformer is loaded, the secondary terminal voltage,
V2, falls. As the power factor decreases, this voltage drop increases. This is
called the regulation of the transformer and it is usually expressed as a
percentage of the secondary no-load voltage, E2.
For full-load conditions:
The fall in voltage, (E2 - V2), is caused by the resistance and reactance of the
windings.
Typical values of voltage regulation are about 3% in small transformers and
about 1% in large transformers.
Example 8
A 5 kVA, 200 V/400 V, single-phase transformer has a secondary terminal
voltage of 387.6 volts when loaded. Determine the regulation of the
transformer.
(b) (b) Iron losses are constant for a given value of frequency and flux density
and are of two types—hysteresis loss and eddy current loss.
i. Hysteresis loss is the heating of the core as a result of the internal
molecular structure reversals which occur as the magnetic flux alternates.
The loss is proportional to the area of the hysteresis loop and thus low
loss nickel iron alloys are used for the core since their hysteresis loops
have small areas.
ii. Eddy current loss is the heating of the core due to e.m.f.s being induced
not only in the transformer windings but also in the core. These induced
e.m.f.s set up circulating currents -the eddy currents. Owing to the low
resistance of the core, eddy currents can be quite considerable and can
cause a large power loss and excessive heating of the core.
Eddy current losses can be reduced by:
Increasing the resistivity of the core material or,
Example 9
A 200 kVA rated transformer has a full-load copper loss of 1.5 kW and an iron
loss of 1 kW. Determine the transformer efficiency at full load and 0.85 power
factor.
Solution
Example 10
Determine the efficiency of the transformer in Problem 16 at half full-load and
0.85 power factor.
Example 11
A 400 kVA transformer has a primary winding resistance of 0.5 Ω and a
secondary winding resistance of 0.001 Ω. The iron loss is 2.5 kW and the
primary and secondary voltages are 5 kV and 320 V respectively. If the power
factor of the load is 0.85, determine the efficiency of the transformer (a) on full
load, and (b) on half load.
Figure 7: Auto-transformer.
Example 12
A single-phase auto transformer has a voltage ratio 320 V:250 V and supplies a
load of 20 kVA at 250 V. Assuming an ideal transformer, determine the current
in each section of the winding.
Solution
from which
Current transformers isolate the ammeter from the main circuit and allow the
use of a standard range of ammeters giving full-scale deflections of 1 A, 2 A or
5 A.
For very large currents the transformer core can be mounted around the
conductor or bus-bar. Thus, the primary then has just one turn.