Comat Releco Relays C2 C3 C4 C5

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 18

1.

3 Industrial Relays - pluggable


C2-A2x
2 pole | changeover contact

Main circuit
Available contact materials AgNi for C2-A20
AgNi + 5 µ Au for C2-A28
Recommended minimum contact load 10 mA / 10 V for C2-A20
5 mA / 5 V for C2-A28
Maximum contact load AC 10 A / 250 V AC-1
Maximum contact load DC 10 A / 30 V DC-1
Rated current 10 A
Inrush current 30 A, 20 ms
AC load 2500 VA
DC load fig. 3. fig. 1. Wiring diagram
Mechanical endurance (cycles) ≥ 20 000 000
Electrical endurance at rated load AC-1 (cycles) ≥ 500 000 4 3 5 6 2
12 14 22 24 A1 (+)

Control circuit
Nominal voltage see table product references 11 21 A2
Operating voltage range 0.8 UN … 1.1 UN 1 8 7
Pick-up voltage ≤ 0.8 UN
Release voltage ≥ 0.1 UN
fig. 2. AC voltage endurance
Power consumption AC / DC 2.2 VA / 1.3 W
10
Coil table
V AC Ω mA V DC Ω mA AC-1AC 1

switching cycles x10 6


Cos ϕAC15
0.4
12 16 185 12 115 104
24 67 96 24 480 50 1
48 296 45 48 1 850 26
60 405 36 110 9 216 12
115 1 753 19 220 38 720 5.7
230 7 078 10
0.1
kVA 0.5 1 1.5 2 2.5
Insulation
Test voltage open contact 1 kV / 1 min
fig. 3. DC load limit curve
Test voltage contact / contact 2.5 kV / 1 min
Test voltage contact / coil 2.5 kV / 1 min 10
Pollution degree 3
DC-1 DC1
Overvoltage category III L/R 40 ms
DC13
Insulation resistance at 500 V ≥ 1 GΩ
1
General data
Amps.

Ambient temperature storage (no ice) -40 … 80 °C


Ambient temperature operation -40 … 70 °C
Pick-up time / bounce time 16 ms / ≤ 3 ms 0.1
Release time / bounce time 8 ms / ≤ 1 ms Volt 50 100 150 200
Maximum switching frequency at rated load 1200 / h
Dimension fig. 4. fig. 4. Dimension (mm)
Weight 79 g
Housing material PA / PC
21 11

A2 8 1 A1
Product references 7 2
35

6 3
Type (x refers to 24 5 4 14
Description 12 24 48 110 115 220 230
contact material)
52

22 21 12

AC 50 Hz C2-A2x/AC…V ✓ ✓ ✓ ✓ ✓
35
LED C2-A2xX/AC…V ✓ ✓ ✓ ✓ ✓
RC Suppressor C2-A2xR/AC…V ✓ ✓ ✓ ✓ ✓

DC C2-A2x/DC…V ✓ ✓ ✓ ✓ ✓
LED C2-A2xX/DC…V ✓ ✓ ✓ ✓ ✓
LED & Free wheeling diode C2-A2xDX/DC…V ✓ ✓ ✓ ✓ ✓
Technical approvals, conformities
LED & Polarity & Free wheeling diode C2-A2xFX/DC…V ✓ ✓ ✓ ✓ ✓

Standards IEC/EN 61810; IEC/EN 60947


AC / DC bridge recifier & LED C2-A2xBX/UC…V ✓ ✓

AC relays also available as 60 Hz. Other voltages on request. Please contact support@comatreleco.com. Approvals
«…» List coil voltage to complete product references
C2-A20 only
Accessories
Socket S2-B, S2-PO
Blanking plug SO-NP (BAG 10 PCS)

1.3 Industrial Relays -
1.3 Industrial Relays - pluggable

pluggable
C3-A3x
3 pole | changeover contact

Main circuit

1
Available contact materials AgNi for C3-A30
AgNi + 5 µ Au for C3-A38
AgNi + 0.2 µ Au for C3-A39
Recommended minimum contact load 10 mA / 10 V for C3-A30, C3-A39
5 mA / 5 V for C3-A38
Maximum contact load AC 10 A / 250 V AC-1
Maximum contact load DC 10 A / 30 V DC-1
Rated current 10 A
Inrush current 30 A, 20 ms
AC load 2500 VA fig. 1. Wiring diagram
DC load fig. 3.
Mechanical endurance (cycles) ≥ 20 000 000 4 3 5 7 8 9 2
12 14 22 24 32 34 A1 (+)
Electrical endurance at rated load AC-1 (cycles) ≥ 500 000

Control circuit 11 21 31 A2
Nominal voltage see table product references 1 6 11 10
Operating voltage range 0.8 UN … 1.1 UN
Pick-up voltage ≤ 0.8 UN
fig. 2. AC voltage endurance
Release voltage ≥ 0.1 UN
Power consumption AC / DC 2.2 VA / 1.3 W
10

Coil table AC-1AC 1

switching cycles x10 6


Cos ϕAC15
0.4
V AC Ω mA V DC Ω mA
12 16 185 12 115 104
1
24 67 96 24 480 50
48 296 45 48 1 850 26
60 405 36 60 2 900 21
115 1 753 19 110 9 216 12
0.1
230 7 078 10 220 38 720 5.7 kVA 0.5 1 1.5 2 2.5
Insulation
Test voltage open contact 1 kV / 1 min
fig. 3. DC load limit curve
Test voltage contact / contact 2.5 kV / 1 min
Test voltage contact / coil 2.5 kV / 1 min 10
Pollution degree 3
DC-1 DC1
Overvoltage category III L/R 40 ms
DC13
Insulation resistance at 500 V ≥ 1 GΩ
1
General data
Amps.

Ambient temperature storage (no ice) -40 … 80 °C


Ambient temperature operation -40 … 70 °C
Pick-up time / bounce time 16 ms / ≤ 3 ms 0.1
Release time / bounce time 8 ms / ≤ 1 ms Volt 50 100 150 200
Maximum switching frequency at rated load 1200 / h
Dimension fig. 4. fig. 4. Dimension (mm)
Weight 81 g
Housing material PA / PC
31 11
A2 A1
11 1
Product references 34
10 2
14
35

9 3
4
Type (x refers to
8
32 7 6 5 12
Description 12 24 48 60 110 115 220 230
contact material)
52

24 22
21

AC 50 Hz C3-A3x/AC…V ✓ ✓ ✓ ✓ ✓ ✓
35
LED C3-A3xX/AC…V ✓ ✓ ✓ ✓ ✓ ✓
RC Suppressor C3-A3xR/AC…V ✓ ✓ ✓ ✓ ✓ ✓

DC C3-A3x/DC…V ✓ ✓ ✓ ✓ ✓ ✓
LED C3-A3xX/DC…V ✓ ✓ ✓ ✓ ✓ ✓
LED & Free wheeling diode C3-A3xDX/DC…V ✓ ✓ ✓ ✓ ✓ ✓
Technical approvals, conformities
LED & Polarity & Free wheeling diode C3-A3xFX/DC…V ✓ ✓ ✓ ✓ ✓ ✓

Standards IEC/EN 61810; IEC/EN 60947


AC / DC bridge recifier & LED C3-A3xBX/UC…V ✓ ✓ ✓ ✓

AC relays also available as 60 Hz. Other voltages on request. Please contact support@comatreleco.com. Approvals
«…» List coil voltage to complete product references
C3-A30 only
Accessories
Socket S3-B, S3-S, S3-PO, S3-M, S3-M0, S3-M1
Blanking plug SO-NP (BAG 10 PCS) WoR 2.1 | 41

1.3 Industrial Relays -
1.3 Industrial Relays - pluggable

pluggable
C3-G30
3 pole | normally open contact

Main circuit

1
Available contact materials AgNi
Recommended minimum contact load 10 A / 30 V
Maximum contact load AC 10 A / 250 V AC-1
Maximum contact load DC 10 A / 30 V DC-1
Rated current 10 A
Inrush current 30 A, 20 ms
AC load 2500 VA
DC load fig. 3.
Mechanical endurance (cycles) ≥ 20 000 000
Electrical endurance at rated load AC-1 (cycles) ≥ 500 000 fig. 1. Wiring diagram

Control circuit
Gap: 3 7 9 2
1 mm 14 24 34 A1 (+)
Nominal voltage see table product references
Operating voltage range 0.8 UN … 1.1 UN
Pick-up voltage ≤ 0.8 UN 11 21 31 A2
Release voltage ≥ 0.1 UN 1 6 11 10
Power consumption AC / DC 2.4 VA / 1.6 W
fig. 2. AC voltage endurance
Coil table
V AC Ω mA V DC Ω mA 10
12 16 214 12 90 104
AC-1AC 1

switching cycles x10 6


24 67 100 24 440 66
Cos ϕAC15
0.4
48 286 50 48 1 788 34
115 1 697 17 60 2 117 20.7 1
230 6 850 10.4 110 9 334 15
220 30 307 7.5

Insulation 0.1
Test voltage open contact 2 kV / 1 min kVA 0.5 1 1.5 2 2.5
Test voltage contact / contact 2.5 kV / 1 min
Test voltage contact / coil 2.5 kV / 1 min
fig. 3. DC load limit curve
Pollution degree 3
Overvoltage category III 10
Insulation resistance at 500 V ≥ 1 GΩ
DC-1
L/R 40 ms
General data
Ambient temperature storage (no ice) -40 … 80 °C 1
Ambient temperature operation -40 … 60 °C
Amps.

Pick-up time / bounce time 20 ms / ≤ 3 ms


Release time / bounce time 8 ms / ≤ 1 ms
Maximum switching frequency at rated load 1200 / h 0.1
Dimension fig. 4. Volt 50 100 150 200
Weight 81 g
Housing material PA / PC fig. 4. Dimension (mm)

Product references
31 11
A1
Description Type 12 24 48 60 110 115 220 230 A2
10
11 1
2
34 14
35

9 3

AC 50 Hz C3-G30/AC…V ✓ ✓ ✓ ✓ ✓ 32
8
7 6 5
4
12

LED C3-G30X/AC…V
52

✓ ✓ ✓ ✓ ✓ 24
21
22

RC Suppressor C3-G30R/AC…V ✓ ✓ ✓ ✓ ✓
35

DC C3-G30/DC…V ✓ ✓ ✓ ✓ ✓ ✓
LED C3-G30X/DC…V ✓ ✓ ✓ ✓ ✓ ✓
LED & Free wheeling diode C3-G30DX/DC…V ✓ ✓ ✓ ✓ ✓ ✓
LED & Polarity & Free wheeling diode C3-G30FX/DC…V ✓ ✓ ✓ ✓ ✓ ✓

AC relays also available as 60 Hz. Other voltages on request. Please contact support@comatreleco.com. Technical approvals, conformities
«…» List coil voltage to complete product references
Standards IEC/EN 61810; IEC/EN 60947
Accessories
Socket S3-B, S3-S, S3-PO, S3-M, S3-M0, S3-M1 Approvals
Blanking plug SO-NP (BAG 10 PCS)



WoR 2.1 | 43
1.3 Industrial Relays - pluggable
C3-M10
1 pole | normally open serial contact with blow magnet

Main circuit
Available contact materials AgNi
Recommended minimum contact load 10 mA / 10 V
Maximum contact load AC 10 A / 250 V AC-1
Maximum contact load DC 10 A / 220 V DC-1
Rated current 10 A
Inrush current 30 A, 20 ms
AC load 2500 VA
DC load fig. 3.
Mechanical endurance (cycles) ≥ 20 000 000
Electrical endurance at rated load AC-1 (cycles) ≥ 500 000 fig. 1. Wiring diagram

Gap: 3 9 2
Control circuit Magnet
> 3 mm 14 34 A1 (+)
Nominal voltage see table product references (1.7 + 1.7)
Operating voltage range 0.8 UN … 1.1 UN
Pick-up voltage ≤ 0.8 UN A2
Release voltage ≥ 0.1 UN 10
Power consumption AC / DC 2.4 VA / 1.3 W
fig. 2. AC voltage endurance
Coil table
V AC Ω mA V DC Ω mA 10
12 16 214 12 115 104
24 67 100 24 440 55 AC-1AC 1

switching cycles x10 6


Cos ϕAC15
0.4
48 286 50 48 1 750 27
115 1 697 17 60 2 900 21 1
230 6 850 10.4 110 9 216 12
220 38 720 5.7

Insulation 0.1
Test voltage open contact 2.5 kV / 1 min kVA 0.5 1 1.5 2 2.5
Test voltage contact / coil 2.5 kV / 1 min
Pollution degree 3
fig. 3. DC load limit curve
Overvoltage category III
Insulation resistance at 500 V ≥ 1 GΩ 10

General data DC-1 110V


DC-1 220V
Ambient temperature storage (no ice) -40 … 80 °C
Ambient temperature operation -40 … 60 °C 1
Ops. x10 6
Ops.

1
Pick-up time / bounce time 20 ms / ≤ 3 ms
Release time / bounce time 10 ms / ≤ 1 ms
Maximum switching frequency at rated load 1200 / h
Dimension fig. 4. 0.1
0.1
Weight 90 g 2 4 6 8 10 Amps.
Housing material PA / PC
fig. 4. Dimension (mm)
Product references

Description Type 12 24 48 110 115 220 230 31 11


A2 A1
11 1
AC 50 Hz C3-M10/AC…V ✓ ✓ ✓ ✓ ✓ 34
10 2
14
35

9 3

LED C3-M10X/AC…V ✓ ✓ ✓ ✓ ✓ 32
8
7 6 5
4
12

RC Suppressor C3-M10R/AC…V
52

✓ ✓ ✓ ✓ ✓ 24 22
21

35
DC C3-M10/DC…V ✓ ✓ ✓ ✓ ✓
LED C3-M10X/DC…V ✓ ✓ ✓ ✓ ✓
LED & Free wheeling diode C3-M10DX/DC…V ✓ ✓ ✓ ✓ ✓
LED & Polarity & Free wheeling diode C3-M10FX/DC…V ✓ ✓ ✓ ✓ ✓

AC relays also available as 60 Hz. Other voltages on request. Please contact support@comatreleco.com.
«…» List coil voltage to complete product references Technical approvals, conformities

Accessories Standards IEC/EN 61810; IEC/EN 60947


Socket S3-B, S3-S, S3-PO, S3-M, S3-M0, S3-M1
Blanking plug SO-NP (BAG 10 PCS) Approvals




44 | WoR 2.1
1.3 Industrial Relays -
1.3 Industrial Relays - pluggable

pluggable
C3-N34
3 pole | changeover contact | sensitive coil

Main circuit

1
Available contact materials AgNi + 0.2 µ Au
Recommended minimum contact load 10 mA / 10 V
Maximum contact load AC 6 A / 250 V AC-1
Maximum contact load DC 6 A / 30 V DC-1
Rated current 6A
Inrush current 30 A, 20 ms
AC load 1500 VA
DC load fig. 3.
Mechanical endurance (cycles) ≥ 20 000 000
Electrical endurance at rated load AC-1 (cycles) ≥ 150 000 fig. 1. Wiring diagram

Control circuit 4 3 5 7 8 9 2
12 14 22 24 32 34 A1(+)
Nominal voltage see table product references
Operating voltage range 0.8 UN … 1.1 UN
Pick-up voltage ≤ 0.8 UN 11 21 31 A2
Release voltage ≥ 0.1 UN 1 6 11 10
Power consumption AC / DC 800 mW
fig. 2. AC voltage endurance
Coil table
V DC Ω mA 10
12 186 65

switching cycles x10 6


24 693 35
48 2 844 17 AC1
AC-1

60 4 482 13 1
110 14 872 7.4

Insulation
Test voltage open contact 1 kV / 1 min
0.1
Test voltage contact / contact 2.5 kV / 1 min VA 0 250 500 750 1000 1250
Test voltage contact / coil 2.5 kV / 1 min
Pollution degree 3
fig. 3. DC load limit curve
Overvoltage category III
Insulation resistance at 500 V ≥ 1 GΩ 10

General data DC1


DC-1
Ambient temperature storage (no ice) -40 … 80 °C
Ambient temperature operation -40 … 60 °C 1
Pick-up time / bounce time 18 ms / ≤ 3 ms
Amps.

Release time / bounce time 10 ms / ≤ 1 ms


Maximum switching frequency at rated load 1200 / h
Dimension fig. 4.
0.1
Weight 90 g Volt 50 100 150 200
Housing material PA / PC
fig. 4. Dimension (mm)
Product references

Description Type 12 24 48 60 110 31 11


A2 A1
11 1
DC C3-N34/DC…V ✓ ✓ ✓ ✓ ✓ 34
10 2
14
35

9 3
8 4
AC relays also available as 60 Hz. Other voltages on request. Please contact support@comatreleco.com. 32 7 6 5 12
52

22
«…» List coil voltage to complete product references 24
21

35
Accessories
Socket S3-B, S3-S, S3-PO, S3-M, S3-M0, S3-M1
Blanking plug SO-NP (BAG 10 PCS)


Technical approvals, conformities

Standards IEC/EN 61810; IEC/EN 60947

Approvals

WoR 2.1 | 45
1.3 Industrial Relays - pluggable
C3-R2xN
2 pole | changeover contact | remanence

Main circuit
Available contact materials AgNi for C3-R20N
AgNi + 5 µ Au for C3-R28N
Recommended minimum contact load 10 mA / 10 V for C3-R20N
5 mA / 5 V for C3-R28N
Maximum contact load AC 10 A / 250 V AC-1
Maximum contact load DC 10 A / 30 V DC-1
Rated current 10 A
Inrush current 30 A, 20 ms
AC load 2500 VA
DC load fig. 3. fig. 1. Wiring diagram
Mechanical endurance (cycles) ≥ 20 000 000
Electrical endurance at rated load AC-1 (cycles) ≥ 500 000 4 3 8 9 2 6
12 14 32 34 A1 A3
ON (+) OFF (+ )
Control circuit
Nominal voltage see table product references 11 31 A2 (-)
Operating voltage range 0.8 UN … 1.1 UN 1 11 10
Pick-up voltage (latch) ≤ 0.8 UN
Release voltage (delatch) ≤ 0.8 UN
fig. 2. AC voltage endurance
ON pulse power AC 1.8 VA, DC 1.5 W
OFF pulse power AC 0.3 VA, DC 0.5 W
10

Coil table Internal diagram AC-1AC 1

switching cycles x10 6


Cos ϕAC15
0.4
V AC mA ON mA OFF V DC mA ON mA OFF A1 A3 A1
+ +
24 88 8 12 121 32 1
A3
48 31 5 24 60 18
115 13 2 36 45 15
230 8 0.7 48 32 7 A2 A2
60 25 9 DC AC
0.1
72 21 9 kVA 0.5 1 1.5 2 2.5
110 12.4 3.2
fig. 3. DC load limit curve
Insulation
Test voltage open contact 1 kV / 1 min 10
Test voltage contact / contact 2.5 kV / 1 min
DC-1 DC1
Test voltage contact / coil 2.5 kV / 1 min L/R 40 ms
DC13
Pollution degree 3
Overvoltage category III 1
Insulation resistance at 500 V ≥ 1 GΩ
Amps.

General data
Ambient temperature storage (no ice) -40 … 80 °C 0.1
Ambient temperature operation -40 … 60 °C Volt 50 100 150 200
Minimum pulse length ON / OFF 50 ms
Maximum switching frequency at rated load 1200 / h fig. 4. Dimension (mm)
Dimension fig. 4.
Weight 81 g
Housing material PA / PC A2
31 11
A1
11 1
10 2
34 14
35

9 3

Product references 32
8
7 6 5
4
12
52

Type (x refers to 24
21
22

Description 12 24 48 110 115 230


contact material)
35
AC 50 Hz C3-R2xN/AC…V ✓ ✓ ✓ ✓ ✓

DC C3-R2xN/DC…V ✓ ✓ ✓ ✓

AC relays also available as 60 Hz. Other voltages on request. Please contact support@comatreleco.com.
«…» List coil voltage to complete product references
Technical approvals, conformities
Accessories
Socket S3-B, S3-S, S3-PO, S3-M, S3-M0, S3-M1 Standards IEC/EN 61810; IEC/EN 60947
Blanking plug SO-NP (BAG 10 PCS)
Approvals


46 | WoR 2.1
1.3 Industrial Relays -
1.3 Industrial Relays - pluggable

pluggable
C3-T3x
3 pole | changeover twin contact

Main circuit

1
Available contact materials AgNi + 0.2 µ Au for C3-T31
AgNi + 5 µ Au for C3-T32
Recommended minimum contact load 5 mA / 5 V for C3-T31
1 mA / 5 V for C3-T32
Maximum contact load AC 6 A / 250 V AC-1
Maximum contact load DC 6 A / 30 V DC-1
Rated current 6A
Inrush current 15 A, 20 ms
AC load 1200 VA
DC load fig. 3. fig. 1. Wiring diagram
Mechanical endurance (cycles) ≥ 20 000 000
Electrical endurance at rated load AC-1 (cycles) ≥ 180 000 4 3 5 7 8 9 2
12 14 22 24 32 34 A1 (+)

Control circuit
Nominal voltage see table product references 11 21 31 A2
Operating voltage range 0.8 UN … 1.1 UN 1 6 11 10
Pick-up voltage ≤ 0.8 UN
Release voltage ≥ 0.1 UN
fig. 2. AC voltage endurance
Power consumption AC / DC 2.2 VA / 1.3 W
10
Coil table

switching cycles x10 6


V AC Ω mA V DC Ω mA
AC1
AC-1
12 16 185 12 115 104
24 67 96 24 480 50 1
48 296 45 48 1 850 26
60 405 36 60 2 900 21
115 1 753 19 110 9 216 12
230 7 078 10 220 38 720 5.7
0.1
VA 0 250 500 750 1000 1250
Insulation
Test voltage open contact 1 kV / 1 min
fig. 3. DC load limit curve
Test voltage contact / contact 2.5 kV / 1 min
Test voltage contact / coil 2.5 kV / 1 min 10
Pollution degree 3
Overvoltage category III DC1
DC-1
Insulation resistance at 500 V ≥ 1 GΩ
1
General data
Amps.

Ambient temperature storage (no ice) -40 … 80 °C


Ambient temperature operation -40 … 70 °C
Pick-up time / bounce time 8 ms / ≤ 3 ms
0.1
Release time / bounce time 18 ms / ≤ 1 ms Volt 50 100 150 200
Maximum switching frequency at rated load 1200 / h
Dimension fig. 4. fig. 4. Dimension (mm)
Weight 81 g
Housing material PA / PC
31 11
A2 A1
11 1
Product references 34
10 2
14
35

9 3
4
Type (x refers to
8
32 7 6 5 12
Description 12 24 48 60 110 115 220 230
contact material)
52

24 22
21

AC 50 Hz C3-T3x/AC…V ✓ ✓ ✓ ✓ ✓
35
LED C3-T3xX/AC…V ✓ ✓ ✓ ✓ ✓
RC Suppressor C3-T3xR/AC…V ✓ ✓ ✓ ✓ ✓

DC C3-T3x/DC…V ✓ ✓ ✓ ✓ ✓ ✓
LED C3-T3xX/DC…V ✓ ✓ ✓ ✓ ✓ ✓
LED & Free wheeling diode C3-T3xDX/DC…V ✓ ✓ ✓ ✓ ✓ ✓
Technical approvals, conformities
LED & Polarity & Free wheeling diode C3-T3xFX/DC…V ✓ ✓ ✓ ✓ ✓ ✓

AC relays also available as 60 Hz. Other voltages on request. Please contact support@comatreleco.com. Standards IEC/EN 61810; IEC/EN 60947
«…» List coil voltage to complete product references
Approvals
Accessories
Socket S3-B, S3-S, S3-PO, S3-M, S3-M0, S3-M1
Blanking plug SO-NP (BAG 10 PCS)

WoR 2.1 | 47

1.3 Industrial Relays - pluggable
C3-X10
1 pole | normally open serial contact

Main circuit
Available contact materials AgNi
Recommended minimum contact load 10 mA / 10 V
Maximum contact load AC 10 A / 250 V AC-1
Maximum contact load DC 10 A / 30 V DC-1
Rated current 10 A
Inrush current 30 A, 20 ms
AC load 2500 VA
DC load fig. 3.
Mechanical endurance (cycles) ≥ 20 000 000
Electrical endurance at rated load AC-1 (cycles) ≥ 500 000 fig. 1. Wiring diagram

Gap: 3 9 2
Control circuit
> 3 mm 14 34 A1 (+)
Nominal voltage see table product references (1.7 + 1.7)
Operating voltage range 0.8 UN … 1.1 UN
Pick-up voltage ≤ 0.8 UN A2
Release voltage ≥ 0.1 UN 10
Power consumption AC / DC 2.4 VA / 1.3 W
fig. 2. AC voltage endurance
Coil table
V AC Ω mA V DC Ω mA 10
12 16 214 12 115 104
24 67 100 24 440 55 AC-1AC 1

switching cycles x10 6


Cos ϕAC15
0.4
48 286 50 48 1 750 27
115 1 697 17 60 2 900 21 1
230 6 850 10.4 110 9 216 12
220 38 720 5.7

Insulation 0.1
Test voltage open contact 2.5 kV / 1 min kVA 0.5 1 1.5 2 2.5
Test voltage contact / coil 2.5 kV / 1 min
Pollution degree 3
fig. 3. DC load limit curve
Overvoltage category III
Insulation resistance at 500 V ≥ 1 GΩ
10 DC-1
L/R 40 ms
General data
Ambient temperature storage (no ice) -40 … 80 °C
Ambient temperature operation -40 … 60 °C
1
Pick-up time / bounce time 18 ms / ≤ 3 ms
Release time / bounce time 8 ms / ≤ 1 ms
Amps.

Maximum switching frequency at rated load 1200 / h


Dimension fig. 4. 0,1
Weight 83 g Volt 25 75 125 175 225
Housing material PA / PC
fig. 4. Dimension (mm)
Product references

Description Type 12 24 48 60 110 115 220 230 31 11


A2 A1
11 1
AC 50 Hz C3-X10/AC…V ✓ ✓ ✓ ✓ ✓ 34
10 2
14
35

9 3

LED C3-X10X/AC…V ✓ ✓ ✓ ✓ ✓ 32
8
7 6 5
4
12

RC Suppressor C3-X10R/AC…V
52

✓ ✓ ✓ ✓ ✓ 24 22
21

35
DC C3-X10/DC…V ✓ ✓ ✓ ✓ ✓ ✓
LED C3-X10X/DC…V ✓ ✓ ✓ ✓ ✓ ✓
LED & Free wheeling diode C3-X10DX/DC…V ✓ ✓ ✓ ✓ ✓ ✓
LED & Polarity & Free wheeling diode C3-X10FX/DC…V ✓ ✓ ✓ ✓ ✓ ✓

AC relays also available as 60 Hz. Other voltages on request. Please contact support@comatreleco.com.
«…» List coil voltage to complete product references Technical approvals, conformities

Accessories Standards IEC/EN 61810; IEC/EN 60947


Socket S3-B, S3-S, S3-PO, S3-M, S3-M0, S3-M1
Blanking plug SO-NP (BAG 10 PCS) Approvals




48 | WoR 2.1
1.3 Industrial Relays -
1.3 Industrial Relays - pluggable

pluggable
C4-A4x
4 pole | changeover contact | faston

Main circuit

1
Available contact materials AgNi for C4-A40
AgNi + 5 µ Au for C4-A48
Recommended minimum contact load 10 mA / 5 V for C4-A40
5 mA / 5 V for C4-A48
Maximum contact load AC 10 A / 250 V AC-1
Maximum contact load DC 10 A / 30 V DC-1
Rated current 10 A
Inrush current 30 A, 20 ms
AC load 2500 VA
DC load fig. 3. fig. 1. Wiring diagram
Mechanical endurance (cycles) ≥ 20 000 000
Electrical endurance at rated load AC-1 (cycles) ≥ 500 000 1 2 4 5 7 8 10 11 13
12 14 22 24 32 34 42 44 A1(+)

Control circuit
Nominal voltage see table product references 11 21 31 41 A2
Operating voltage range 0.8 UN … 1.1 UN 3 6 9 12 14
Pick-up voltage ≤ 0.8 UN
Release voltage ≥ 0.1 UN
fig. 2. AC voltage endurance
Power consumption AC / DC 2.4 VA / 1.4 W
10
Coil table
V AC Ω mA V DC Ω mA AC-1AC 1

switching cycles x10 6


12 16 214 12 105 114 Cos ϕAC15
0.4

24 65 103 24 414 58
1
48 286 51 48 1 664 29
115 1 697 22 60 2 581 23
230 6 850 10.4 110 8 117 13.6
400 18 802 6 220 30 307 6.2
0.1
Insulation kVA 0.5 1 1.5 2 2.5
Test voltage open contact 1 kV / 1 min
Test voltage contact / contact 2.5 kV / 1 min
fig. 3. DC load limit curve
Test voltage contact / coil 2.5 kV / 1 min
Pollution degree 3 10
Overvoltage category III
DC-1 DC1
Insulation resistance at 500 V ≥ 1 GΩ L/R 40 ms
DC13

General data 1
Ambient temperature storage (no ice) -40 … 80 °C
Amps.

Ambient temperature operation -40 … 60 °C


Pick-up time / bounce time 20 ms / ≤ 3 ms
Release time / bounce time 8 ms / ≤ 1 ms 0.1
Maximum switching frequency at rated load 1200 / h Volt 50 100 150 200
Dimension fig. 4.
Weight 90 g fig. 4. Dimension (mm)
Housing material PA / PC

Product references 1
2
4
5
7
8
10
11

Type (x refers to
Description 12 24 48 60 110 115 220 230 400
35

6 9

contact material)
52.5

3 12

AC 50 Hz C4-A4x/AC…V ✓ ✓ ✓ ✓ ✓ ✓ 13 14

LED C4-A4xX/AC…V ✓ ✓ ✓ ✓ ✓ ✓
35
RC Suppressor C4-A4xR/AC…V ✓ ✓ ✓ ✓ ✓ ✓

DC C4-A4x/DC…V ✓ ✓ ✓ ✓ ✓ ✓
3
LED C4-A4xX/DC…V ✓ ✓ ✓ ✓ ✓ ✓ FASTON .110
LED & Free wheeling diode C4-A4xDX/DC…V ✓ ✓ ✓ ✓ ✓ ✓
LED & Polarity & Free wheeling diode C4-A4xFX/DC…V ✓ ✓ ✓ ✓ ✓ ✓
Technical approvals, conformities
AC / DC bridge recifier & LED C4-A4xBX/UC…V ✓ ✓ ✓
Standards IEC/EN 61810; IEC/EN 60947
AC relays also available as 60 Hz. Other voltages on request. Please contact support@comatreleco.com.
«…» List coil voltage to complete product references Approvals

Accessories C4-A40 only


Socket S4-J, S4-L, S4-P
Blanking plug SO-NP (BAG 10 PCS)
Wall mounting adapter S5-R (BAG 5 PCS) WoR 2.1 | 49

1.3 Industrial Relays -
1.3 Industrial Relays - pluggable

pluggable
C4-R3x
3 pole | changeover contact | remanence | faston

Main circuit

1
Available contact materials AgNi for C4-R30
AgNi + 5 µ Au for C4-R38
Recommended minimum contact load 10 mA / 10 V for C4-R30
5 mA / 5 V for C4-R38
Maximum contact load AC 10 A / 250 V AC-1
Maximum contact load DC 10 A / 30 V DC-1
Rated current 10 A
Inrush current 30 A, 20 ms
AC load 2500 VA
DC load fig. 3. fig. 1. Wiring diagram
Mechanical endurance (cycles) ≥ 20 000 000
Electrical endurance at rated load AC-1 (cycles) ≥ 500 000 1 2 4 5 7 8 13 12
12 14 22 24 32 34 A1 A3
ON (+) OFF (+)
Control circuit
Nominal voltage see table product references 11 21 31 A2 (-)
Operating voltage range 0.8 UN … 1.1 UN 3 6 9 14
Pick-up voltage (latch) ≤ 0.8 UN
Release voltage (delatch) ≤ 0.8 UN
fig. 2. AC voltage endurance
ON pulse power AC 1.8 VA, DC 1.5 W
OFF pulse power AC 0.3 VA, DC 0.5 W
10

Coil table Internal diagram AC-1AC 1

switching cycles x10 6


Cos ϕAC15
0.4
V AC mA ON mA OFF V DC mA ON mA OFF A1 A3 A1
+ +
24 75 12 12 145 25 1
A3
48 54 6 24 71 12
115 22 2.5 48 33 6
230 8 1.3 60 26.1 8.5 A2 A2
400 on request on request 110 14 5 DC AC
0.1
kVA 0.5 1 1.5 2 2.5
Insulation
Test voltage open contact 1 kV / 1 min
fig. 3. DC load limit curve
Test voltage contact / contact 2.5 kV / 1 min
Test voltage contact / coil 2.5 kV / 1 min 10
Pollution degree 3
DC-1 DC1
Overvoltage category III L/R 40 ms
DC13
Insulation resistance at 500 V ≥ 1 GΩ
1
General data
Amps.

Ambient temperature storage (no ice) -40 … 80 °C


Ambient temperature operation -40 … 60 °C
Minimum pulse length ON / OFF 50 ms 0.1
Maximum switching frequency at rated load 1200 / h Volt 50 100 150 200
Dimension fig. 4.
Weight 95 g fig. 4. Dimension (mm)
Housing material PA / PC

Product references 1
2
4
5
7
8
10
11

Type (x refers to
Description 12 24 48 60 110 115 230 400
35

6 9

contact material)
52.5

3 12

AC 50 Hz C4-R3x/AC…V ✓ ✓ ✓ ✓ ✓ 13 14

35
DC C4-R3x/DC…V ✓ ✓ ✓ ✓ ✓

AC relays also available as 60 Hz. Other voltages on request. Please contact support@comatreleco.com.
«…» List coil voltage to complete product references 3
FASTON .110

Accessories
Socket S4-J, S4-L, S4-P Technical approvals, conformities
Blanking plug SO-NP (BAG 10 PCS)
Wall mounting adapter S5-R (BAG 5 PCS) Standards IEC/EN 61810; IEC/EN 60947

Approvals

WoR 2.1 | 51
1.3 Industrial Relays - pluggable
C4-X20
2 pole | normally open serial contact | faston

Main circuit
Available contact materials AgNi
Recommended minimum contact load 10 mA / 10 V
Maximum contact load AC 10 A / 250 V AC-1
Maximum contact load DC 10 A / 30 V DC-1
Rated current 10 A
Inrush current 30 A, 20 ms
AC load 2500 VA
DC load fig. 3.
Mechanical endurance (cycles) ≥ 20 000 000
Electrical endurance at rated load AC-1 (cycles) ≥ 500 000 fig. 1. Wiring diagram

Control circuit Gap:


> 3 mm 2 5 8 11 13
Nominal voltage see table product references (1.7 + 1.7) 14 24 34 44 A1 (+)
Operating voltage range 0.8 UN … 1.1 UN
Pick-up voltage ≤ 0.8 UN A2
Release voltage ≥ 0.1 UN 14
Power consumption AC / DC 2.4 VA / 1.3 W
fig. 2. AC voltage endurance
Coil table
V AC Ω mA V DC Ω mA
10
12 15.6 769 12 111 109
24 65 100 24 443 54 AC-1AC 1

switching cycles x10 6


Cos ϕAC15
0.4
48 286 50 48 1 796 27
115 1 700 21 60 2 829 21
1
230 6 800 10 110 9 216 12
400 31 600 12.7 220 36 155 6.5

Insulation 0.1
Test voltage open contact 2.5 kV / 1 min kVA 0.5 1 1.5 2 2.5
Test voltage contact / contact 2.5 kV / 1 min
Test voltage contact / coil 2.5 kV / 1 min
fig. 3. DC load limit curve
Pollution degree 3
Overvoltage category III 10
DC-1
Insulation resistance at 500 V ≥ 1 GΩ L/R 40 ms

General data
Ambient temperature storage (no ice) -40 … 80 °C 1
Ambient temperature operation -40 … 60 °C
Amps.

Pick-up time / bounce time 20 ms / ≤ 3 ms


Release time / bounce time 8 ms / ≤ 1 ms
Maximum switching frequency at rated load 1200 / h 0.1
Dimension fig. 4. Volt 50 100 150 200
Weight 90 g
Housing material PA / PC fig. 4. Dimension (mm)

Product references
1 4 7 10
2 5 8 11
Description Type 12 24 48 60 110 115 220 230 400
35

6 9

AC 50 Hz C4-X20/AC…V ✓ ✓ ✓ ✓ ✓ ✓
52.5

3 12

LED C4-X20X/AC…V ✓ ✓ ✓ ✓ ✓ ✓ 13 14

RC Suppressor C4-X20R/AC…V ✓ ✓ ✓ ✓ ✓ ✓
35

DC C4-X20/DC…V ✓ ✓ ✓ ✓ ✓ ✓
LED C4-X20X/DC…V ✓ ✓ ✓ ✓ ✓ ✓
3
LED & Free wheeling diode C4-X20DX/DC…V ✓ ✓ ✓ ✓ ✓ ✓ FASTON .110
LED & Polarity & Free wheeling diode C4-X20FX/DC…V ✓ ✓ ✓ ✓ ✓ ✓

AC relays also available as 60 Hz. Other voltages on request. Please contact support@comatreleco.com. Technical approvals, conformities
«…» List coil voltage to complete product references
Standards IEC/EN 61810; IEC/EN 60947
Accessories
Socket S4-J, S4-L, S4-P Approvals
Blanking plug SO-NP (BAG 10 PCS)
Wall mounting adapter S5-R (BAG 5 PCS)


52 | WoR 2.1
1.3 Industrial Relays -
1.3 Industrial Relays - pluggable

pluggable
C5-A20
2 pole | changeover contact | faston

Main circuit

1
Available contact materials AgNi
Recommended minimum contact load 10 mA / 10 V
Maximum contact load AC 16 A / 400 V AC-1
Maximum contact load DC 16 A / 30 V DC-1
Rated current 16 A
Inrush current 40 A, 20 ms
AC load 4000 VA
DC load fig. 3.
Mechanical endurance (cycles) ≥ 20 000 000
Electrical endurance at rated load AC-1 (cycles) ≥ 300 000 fig. 1. Wiring diagram

Control circuit 1 4 3 6 A
12 14 32 34 A1 (+)
Nominal voltage see table product references
Operating voltage range 0.8 UN … 1.1 UN
Pick-up voltage ≤ 0.8 UN 11 31 A2
Release voltage ≥ 0.1 UN 7 9 B
Power consumption AC / DC 2.4 VA / 1.4 W
fig. 2. AC voltage endurance
Coil table
V AC Ω mA V DC Ω mA 10
12 15.6 769 12 111 109
AC1 Ω

switching cycles x10 6


24 65 100 24 443 58 AC-1 AC1
CosϕϕAC15
Cos 0.4
0.4
48 286 50 48 1 796 30
1
115 1 700 21 60 2 829 21.2
230 6 800 10 110 9 216 13
400 31 600 12.7 220 36 155 6.2

Insulation 0.1
Test voltage open contact 1 kV / 1 min kVA 0.66 1.33 2 2.6 3.3 4
Test voltage contact / contact 4 kV / 1 min
Test voltage contact / coil 4 kV / 1 min
fig. 3. DC load limit curve
Pollution degree 3
Overvoltage category III
16
Insulation resistance at 500 V ≥ 3 GΩ 10
DC-1
General data L/R 40 ms
Ambient temperature storage (no ice) -40 … 80 °C 1
Ambient temperature operation -40 … 60 °C
Pick-up time / bounce time 20 ms / ≤ 3 ms
Amps.

Release time / bounce time 10 ms / ≤ 1 ms


Maximum switching frequency at rated load 1200 / h 0.1
Dimension fig. 4. Volt 50 100 150 200
Weight 90 g
Housing material PA / PC fig. 4. Dimension (mm)

Product references

Description Type 12 24 48 60 110 115 220 230 400


AC 50 Hz C5-A20/AC…V ✓ ✓ ✓ ✓ ✓ ✓
LED C5-A20X/AC…V ✓ ✓ ✓ ✓ ✓ ✓
RC Suppressor C5-A20R/AC…V ✓ ✓ ✓ ✓ ✓ ✓

DC C5-A20/DC…V ✓ ✓ ✓ ✓ ✓ ✓
LED C5-A20X/DC…V ✓ ✓ ✓ ✓ ✓ ✓
LED & Free wheeling diode C5-A20DX/DC…V ✓ ✓ ✓ ✓ ✓ ✓
LED & Polarity & Free wheeling diode C5-A20FX/DC…V ✓ ✓ ✓ ✓ ✓ ✓

Technical approvals, conformities


AC / DC bridge recifier & LED C5-A20BX/UC…V ✓ ✓

AC relays also available as 60 Hz. Other voltages on request. Please contact support@comatreleco.com. Standards IEC/EN 61810; IEC/EN 60947
«…» List coil voltage to complete product references
Approvals
Accessories
Socket S5-M, S5-P
Blanking plug SO-NP (BAG 10 PCS)
Wall mounting adapter S5-R (BAG 5 PCS)
WoR 2.1 | 53

1.3 Industrial Relays - pluggable
C5-A3x
3 pole | changeover contact | faston

Main circuit
Available contact materials AgNi for C5-A30
AgSnO2 for C5-A35
Recommended minimum contact load 10 mA / 10 V
Maximum contact load AC 16 A / 400 V AC-1
Maximum contact load DC 16 A / 30 V DC-1
Rated current 16 A
Inrush current 40 A, 20 ms
AC load 4000 VA
DC load fig. 3.
Mechanical endurance (cycles) ≥ 20 000 000 fig. 1. Wiring diagram
Electrical endurance at rated load AC-1 (cycles) ≥ 300 000
1 4 2 5 3 6 A
12 14 22 24 32 34 A1(+)
Control circuit
Nominal voltage see table product references
Operating voltage range 0.8 UN … 1.1 UN 11 21 31 A2
Pick-up voltage ≤ 0.8 UN 7 8 9 B
Release voltage ≥ 0.1 UN
Power consumption AC / DC 2.4 VA / 1.4 W
fig. 2. AC voltage endurance

Coil table
10
V AC Ω mA V DC Ω mA
AC1 Ω

switching cycles x10 6


12 15.6 769 12 111 109 AC-1 AC1
CosϕϕAC15
Cos 0.4
0.4
24 65 100 24 443 58
1
48 286 50 48 1 796 30
115 1 700 21 60 2 829 21.2
230 6 800 10 110 9 216 13
400 31 600 12.7 220 36 155 6.2
0.1
Insulation kVA 0.66 1.33 2 2.6 3.3 4
Test voltage open contact 1 kV / 1 min
Test voltage contact / contact 4 kV / 1 min
fig. 3. DC load limit curve
Test voltage contact / coil 4 kV / 1 min
Pollution degree 3
16
Overvoltage category III 10
Insulation resistance at 500 V ≥ 3 GΩ DC-1
L/R 40 ms
General data 1
Ambient temperature storage (no ice) -40 … 80 °C
Ambient temperature operation -40 … 60 °C
Amps.

Pick-up time / bounce time 20 ms / ≤ 3 ms


Release time / bounce time 10 ms / ≤ 1 ms 0.1
Maximum switching frequency at rated load 1200 / h Volt 50 100 150 200
Dimension fig. 4.
Weight 95 g fig. 4. Dimension (mm)
Housing material PA / PC

Product references
Type (x refers to
Description 12 24 48 60 110 115 220 230 400
contact material)
AC 50 Hz C5-A3x/AC…V ✓ ✓ ✓ ✓ ✓ ✓
LED C5-A3xX/AC…V ✓ ✓ ✓ ✓ ✓ ✓
RC Suppressor C5-A3xR/AC…V ✓ ✓ ✓ ✓ ✓ ✓

DC C5-A3x/DC…V ✓ ✓ ✓ ✓ ✓ ✓
LED C5-A3xX/DC…V ✓ ✓ ✓ ✓ ✓ ✓
LED & Free wheeling diode C5-A3xDX/DC…V ✓ ✓ ✓ ✓ ✓ ✓
LED & Polarity & Free wheeling diode C5-A3xFX/DC…V ✓ ✓ ✓ ✓ ✓ ✓
Technical approvals, conformities
AC / DC bridge recifier & LED C5-A3xBX/UC…V ✓ ✓
Standards IEC/EN 61810; IEC/EN 60947
AC relays also available as 60 Hz. Other voltages on request. Please contact support@comatreleco.com.
«…» List coil voltage to complete product references Approvals

Accessories C5-A30 only


Socket S5-M, S5-P
Blanking plug SO-NP (BAG 10 PCS)
Wall mounting adapter S5-R (BAG 5 PCS)

1.3 Industrial Relays -
1.3 Industrial Relays - pluggable

pluggable
C5-G3x
3 pole | normally open contact | faston

Main circuit

1
Available contact materials AgNi for C5-G30
AgSnO2 for C5-G35
Recommended minimum contact load 10 mA / 10 V
Maximum contact load AC 16 A / 400 V AC-1
Maximum contact load DC 16 A / 30 V DC-1
Rated current 16 A
Inrush current 40 A, 20 ms
AC load 4000 VA
DC load fig. 3.
Mechanical endurance (cycles) ≥ 20 000 000 fig. 1. Wiring diagram
Electrical endurance at rated load AC-1 (cycles) ≥ 300 000
Gap: 4 5 6 A
1.7 mm 14 24 34 A1 (+)
Control circuit
Nominal voltage see table product references
Operating voltage range 0.8 UN … 1.1 UN 11 21 31 A2
Pick-up voltage ≤ 0.8 UN 7 8 9 B
Release voltage ≥ 0.1 UN
Power consumption AC / DC 2.4 VA / 1.6 W
fig. 2. AC voltage endurance

Coil table
10
V AC Ω mA V DC Ω mA
AC1 Ω

switching cycles x10 6


12 15.6 769 12 111 109 AC-1 AC1
CosϕϕAC15
Cos 0.4
0.4
24 65 100 24 443 58 1
48 286 50 48 1 796 30
115 1 700 21 60 2 829 21.2
230 6 800 10 110 9 216 13
400 31 600 12.7 220 36 155 6.2
0.1
Insulation kVA 0.66 1.33 2 2.6 3.3 4
Test voltage open contact 2 kV / 1 min
Test voltage contact / contact 4 kV / 1 min
fig. 3. DC load limit curve
Test voltage contact / coil 4 kV / 1 min
Pollution degree 3
Overvoltage category III 16
10
Insulation resistance at 500 V ≥ 3 GΩ
DC-1 DC1
L/R 40 ms
DC13
General data
1
1
Ambient temperature storage (no ice) -40 … 80 °C
Ambient temperature operation -40 … 60 °C
Amps.

Pick-up time / bounce time 20 ms / ≤ 3 ms


Release time / bounce time 10 ms / ≤ 1 ms
0.1
Maximum switching frequency at rated load 1200 / h Volt 50 100 150 200
Dimension fig. 4.
Weight 95 g fig. 4. Dimension (mm)
Housing material PA / PC

Product references
Type (x refers to
Description 12 24 48 60 110 115 220 230 400
contact material)
AC 50 Hz C5-G3x/AC…V ✓ ✓ ✓ ✓ ✓ ✓
LED C5-G3xX/AC…V ✓ ✓ ✓ ✓ ✓ ✓
RC Suppressor C5-G3xR/AC…V ✓ ✓ ✓ ✓ ✓ ✓

DC C5-G3x/DC…V ✓ ✓ ✓ ✓ ✓ ✓
LED C5-G3xX/DC…V ✓ ✓ ✓ ✓ ✓ ✓
LED & Free wheeling diode C5-G3xDX/DC…V ✓ ✓ ✓ ✓ ✓ ✓
LED & Polarity & Free wheeling diode C5-G3xFX/DC…V ✓ ✓ ✓ ✓ ✓ ✓
Technical approvals, conformities
AC relays also available as 60 Hz. Other voltages on request. Please contact support@comatreleco.com.
«…» List coil voltage to complete product references Standards IEC/EN 61810; IEC/EN 60947

Accessories Approvals
Socket S5-M, S5-P
Blanking plug SO-NP (BAG 10 PCS)
Wall mounting adapter S5-R (BAG 5 PCS)

WoR 2.1 | 55

1.3 Industrial Relays - pluggable
C5-M10
1 pole | normally open serial contact with blow magnet | faston

Main circuit
Available contact materials AgNi
Recommended minimum contact load 10 mA / 10 V
Maximum contact load AC 16 A / 400 V AC-1
Maximum contact load DC 10 A / 220 V DC-1
Rated current 16 A
Inrush current 40 A, 20 ms
AC load 4000 VA
DC load 2200 W
Mechanical endurance (cycles) ≥ 20 000 000
Electrical endurance at rated load AC-1 (cycles) ≥ 300 000 fig. 1. Wiring diagram

Gap: 4 6 A
Control circuit Magnet
> 3 mm
Nominal voltage see table product references 14 34 A1 (+)
(1.7 + 1.7)
Operating voltage range 0.8 UN … 1.1 UN
Pick-up voltage ≤ 0.8 UN A2
Release voltage ≥ 0.1 UN B
Power consumption AC / DC 2.4 VA / 1.3 W
fig. 2. AC voltage endurance
Coil table
V AC Ω mA V DC Ω mA 10
12 15.6 769 12 111 109
AC1 Ω

switching cycles x10 6


24 65 100 24 443 58 AC-1 AC1
CosϕϕAC15
Cos 0.4
0.4
48 286 50 48 1 796 30 1
115 1 700 21 60 2 829 21.2
230 6 800 10 110 9 216 13
400 31 600 12.7 220 36 155 6.2

Insulation 0.1
Test voltage open contact 4 kV / 1 min kVA 0.66 1.33 2 2.6 3.3 4
Test voltage contact / coil 4 kV / 1 min
Pollution degree 3
fig. 3. DC voltage endurance
Overvoltage category III
Insulation resistance at 500 V ≥ 3 GΩ 10

General data DC-1 110V


DC-1 220V
Ambient temperature storage (no ice) -40 … 80 °C
Ambient temperature operation -40 … 60 °C 1
Ops. x10 6
Ops.

1
Pick-up time / bounce time 20 ms / ≤ 3 ms
Release time / bounce time 10 ms / ≤ 1 ms
Maximum switching frequency at rated load 1200 / h
Dimension fig. 4. 0.1
0.1
Weight 90 g 2 4 6 8 10 Amps.
Housing material PA / PC
fig. 4. Dimension (mm)
Product references

Description Type 12 24 48 60 110 115 220 230 400


AC 50 Hz C5-M10/AC…V ✓ ✓ ✓ ✓ ✓ ✓
LED C5-M10X/AC…V ✓ ✓ ✓ ✓ ✓ ✓
RC Suppressor C5-M10R/AC…V ✓ ✓ ✓ ✓ ✓ ✓

DC C5-M10/DC…V ✓ ✓ ✓ ✓ ✓ ✓
LED C5-M10X/DC…V ✓ ✓ ✓ ✓ ✓ ✓
LED & Free wheeling diode C5-M10DX/DC…V ✓ ✓ ✓ ✓ ✓ ✓
LED & Polarity & Free wheeling diode C5-M10FX/DC…V ✓ ✓ ✓ ✓ ✓ ✓

AC relays also available as 60 Hz. Other voltages on request. Please contact support@comatreleco.com.
«…» List coil voltage to complete product references Technical approvals, conformities

Accessories Standards IEC/EN 61810; IEC/EN 60947


Socket S5-M, S5-P
Blanking plug SO-NP (BAG 10 PCS) Approvals
Wall mounting adapter S5-R (BAG 5 PCS)



56 | WoR 2.1
1.3 Industrial Relays -
1.3 Industrial Relays - pluggable

pluggable
C5-M20
2 pole | normally open contact with blow magnet | faston

Main circuit

1
Available contact materials AgNi
Recommended minimum contact load 10 mA / 10 V
Maximum contact load AC 16 A / 250 V AC-1
Maximum contact load DC 7 A / 110 V DC-1
Rated current 16 A
Inrush current 40 A, 20 ms
AC load 4000 VA
DC load fig. 3.
Mechanical endurance (cycles) ≥ 20 000 000
Electrical endurance at rated load AC-1 (cycles) ≥ 300 000 fig. 1. Wiring diagram

Gap: 4 6 A
Control circuit Magnet
1.7 mm
Nominal voltage see table product references 14 34 A1 (+)

Operating voltage range 0.8 UN … 1.1 UN


Pick-up voltage ≤ 0.8 UN A2
11 31
Release voltage ≥ 0.1 UN 7 9 B
Power consumption AC / DC 2.4 VA / 1.6 W
fig. 2. AC voltage endurance
Coil table
V AC Ω mA V DC Ω mA 10

12 15.6 769 12 111 109


AC-1
24 65 100 24 443 58 Cos ϕ 0.4
48 286 50 48 1 796 30

switching cycles x10 6


115 1 700 21 60 2 829 21.2

Ops.
1

230 6 800 10 110 9 216 13


400 31 600 12.7 220 36 155 6.2

Insulation 0.1

kVA 0.66 1.33 2 2.6 3.3 4


Test voltage open contact 2 kV / 1 min KVA
Test voltage contact / contact 4 kV / 1 min
Test voltage contact / coil 3 kV / 1 min
fig. 3. DC load limit curve
Pollution degree 3
Overvoltage category III
10
Insulation resistance at 500 V ≥ 3 GΩ DC-1
L/R 40 ms

General data
Ambient temperature storage (no ice) -40 … 80 °C
1
Ambient temperature operation -40 … 60 °C
Amps.

Pick-up time / bounce time 20 ms / ≤ 3 ms


Release time / bounce time 10 ms / ≤ 1 ms
0.1
Maximum switching frequency at rated load 1200 / h
Volt 50 100 150 200
Dimension fig. 4.
Weight 90 g
Housing material PA / PC fig. 4. Dimension (mm)

Product references

Description Type 12 24 48 60 110 115 220 230 400


AC 50 Hz C5-M20/AC…V ✓ ✓ ✓ ✓ ✓ ✓
LED C5-M20X/AC…V ✓ ✓ ✓ ✓ ✓ ✓
RC Suppressor C5-M20R/AC…V ✓ ✓ ✓ ✓ ✓ ✓

DC C5-M20/DC…V ✓ ✓ ✓ ✓ ✓ ✓
LED C5-M20X/DC…V ✓ ✓ ✓ ✓ ✓ ✓
LED & Free wheeling diode C5-M20DX/DC…V ✓ ✓ ✓ ✓ ✓ ✓
LED & Polarity & Free wheeling diode C5-M20FX/DC…V ✓ ✓ ✓ ✓ ✓ ✓

AC relays also available as 60 Hz. Other voltages on request. Please contact support@comatreleco.com. Technical approvals, conformities
«…» List coil voltage to complete product references
Standards IEC/EN 61810; IEC/EN 60947
Accessories
Socket S5-M, S5-P Approvals
Blanking plug SO-NP (BAG 10 PCS)
Wall mounting adapter S5-R (BAG 5 PCS)


WoR 2.1 | 57
1.3 Industrial Relays - pluggable
C5-R20
2 pole | changeover contact | remanence | faston

Main circuit
Available contact materials AgNi
Recommended minimum contact load 10 mA / 10 V
Maximum contact load AC 10 A / 400 V AC-1
Maximum contact load DC 10 A / 30 V DC-1
Rated current 10 A
Inrush current 30 A, 20 ms
AC load 4000 VA
DC load fig. 3.
Mechanical endurance (cycles) ≥ 20 000 000
Electrical endurance at rated load AC-1 (cycles) ≥ 300 000 fig. 1. Wiring diagram

Control circuit 1 4 3 6 A 8
12 14 32 34 A1 A3
Nominal voltage see table product references ON (+) OFF (+)
Operating voltage range 0.8 UN … 1.1 UN
Pick-up voltage (latch) ≤ 0.8 UN 11 31 A2 (-)
Release voltage (delatch) ≤ 0.8 UN 7 9 B
ON pulse power AC 1.8 VA, DC 1.5 W
OFF pulse power AC 0.3 VA, DC 0.5 W
fig. 2. AC voltage endurance

Coil table Internal diagram


10
V AC mA ON mA OFF V DC mA ON mA OFF A1 A3 A1
+ + AC1 Ω

switching cycles x10 6


24 75 12 12 145 25 AC-1 AC1
A3 CosϕϕAC15
Cos 0.4
0.4
48 54 6 24 71 12 1
115 22 2.5 48 33 6
230 8 1.3 110 14 5 A2 A2
DC AC

Insulation 0.1
Test voltage open contact 1 kV / 1 min kVA 0.66 1.33 2 2.6 3.3 4
Test voltage contact / contact 4 kV / 1 min
Test voltage contact / coil 4 kV / 1 min
fig. 3. DC load limit curve
Pollution degree 3
Overvoltage category III 10
Insulation resistance at 500 V ≥ 3 GΩ
DC-1 DC1
L/R 40 ms
DC13
General data
Ambient temperature storage (no ice) -40 … 80 °C 1
Ambient temperature operation -40 … 60 °C
Amps.

Minimum pulse length ON / OFF 50 ms


Maximum switching frequency at rated load 1200 / h
Dimension fig. 4. 0.1
Weight 95 g Volt 50 100 150 200
Housing material PA / PC
fig. 4. Dimension (mm)
Product references

Description Type 12 24 48 110 115 230 400


AC 50 Hz C5-R20/AC…V ✓ ✓ ✓ ✓ ✓

DC C5-R20/DC…V ✓ ✓ ✓ ✓

AC relays also available as 60 Hz. Other voltages on request. Please contact support@comatreleco.com.
«…» List coil voltage to complete product references

Accessories
Socket S5-M, S5-P
Blanking plug SO-NP (BAG 10 PCS)
Wall mounting adapter S5-R (BAG 5 PCS) Technical approvals, conformities

Standards IEC/EN 61810; IEC/EN 60947

Approvals

58 | WoR 2.1
1.3 Industrial Relays -
1.3 Industrial Relays - pluggable

pluggable
C5-X10
1 pole | normally open serial contact | faston

Main circuit

1
Available contact materials AgNi
Recommended minimum contact load 10 mA / 10 V
Maximum contact load AC 16 A / 400 V AC-1
Maximum contact load DC 16 A / 30 V DC-1
Rated current 16 A
Inrush current 40 , 20 ms
AC load 4000 VA
DC load fig. 3.
Mechanical endurance (cycles) ≥ 20 000 000
Electrical endurance at rated load AC-1 (cycles) ≥ 300 000 fig. 1. Wiring diagram

Gap: 4 6 A
Control circuit
> 3 mm 14 34 A1 (+)
Nominal voltage see table product references
Operating voltage range 0.8 UN … 1.1 UN
Pick-up voltage ≤ 0.8 UN A2
Release voltage ≥ 0.1 UN B
Power consumption AC / DC 2.4 VA / 1.3 W
fig. 2. AC voltage endurance
Coil table
V AC Ω mA V DC Ω mA 10
12 15.6 769 12 111 109
AC1 Ω

switching cycles x10 6


24 65 100 24 443 58 AC-1 AC1
CosϕϕAC15
Cos 0.4
0.4
48 286 50 48 1 796 30
1
115 1 700 21 60 2 829 21.2
230 6 800 10 110 9 216 13
400 31 600 12.7 220 36 155 6.2

Insulation 0.1
Test voltage open contact 4 kV / 1 min kVA 0.66 1.33 2 2.6 3.3 4
Test voltage contact / coil 4 kV / 1 min
Pollution degree 3
fig. 3. DC load limit curve
Overvoltage category III
Insulation resistance at 500 V ≥ 3 GΩ
16 DC1
DC-1 DC13
10
L/R 40 ms
General data
Ambient temperature storage (no ice) -40 … 80 °C
Ambient temperature operation -40 … 60 °C 1
Pick-up time / bounce time 20 ms / ≤ 3 ms
Release time / bounce time 10 ms / ≤ 1 ms
Amps.

Maximum switching frequency at rated load 1200 / h


Dimension fig. 4. 0.1
Weight 90 g Volt 50 100 150 200
Housing material PA / PC
fig. 4. Dimension (mm)
Product references

Description Type 12 24 48 60 110 115 220 230 400


AC 50 Hz C5-X10/AC…V ✓ ✓ ✓ ✓ ✓ ✓
LED C5-X10X/AC…V ✓ ✓ ✓ ✓ ✓ ✓
RC Suppressor C5-X10R/AC…V ✓ ✓ ✓ ✓ ✓ ✓

DC C5-X10/DC…V ✓ ✓ ✓ ✓ ✓ ✓
LED C5-X10X/DC…V ✓ ✓ ✓ ✓ ✓ ✓
LED & Free wheeling diode C5-X10DX/DC…V ✓ ✓ ✓ ✓ ✓ ✓
LED & Polarity & Free wheeling diode C5-X10FX/DC…V ✓ ✓ ✓ ✓ ✓ ✓

AC relays also available as 60 Hz. Other voltages on request. Please contact support@comatreleco.com.
«…» List coil voltage to complete product references Technical approvals, conformities

Accessories Standards IEC/EN 61810; IEC/EN 60947


Socket S5-M, S5-P
Blanking plug SO-NP (BAG 10 PCS) Approvals
Wall mounting adapter S5-R (BAG 5 PCS)



WoR 2.1 | 59

You might also like