E-071882-Approved dt.

23/06/2022
DUBAI MUNICIPALITY STAMP

Refer CL/MD sheet for corrections /comments


AB
for the  cables and breakers rating.

NORTH DIR

NOTES:

MAIN CONSULTANT :

B+G+3+ROOF COMMERCIAL AND


PROJECT RESIDENTIAL BUILDING
(MERAAS PLOT AT AL SATWA)

· M M ABDULLA AHMAD MOHAMMAD


OWNER
BIN FAHAD ALMHEIRI
· MDB-1
FORM 4b, TYPE 6, TTA,
ELS

FAULT LEVEL 50kA FOR 1Sec


FUSES MASTER
· RYB1 RYB2 RYB3 RYB5 RYB6 RYB7 RYB8
DEVELOPER MERAAS ESTATES (L.L.C)
BUSBARS: RYB4
RATED NOMINAL A A A V OC ACH
CURRENT: 2500Amps 230/400V,
400 kVAR CAPACITOR
· 50Hz 3-PHASE R Y B VSS
BMS
SC
EF
HST
PF
BANK PANEL-1 BLOCK PLOT LOCATION
· PMU
SURGE PROTECTION
ACTUAL CONNECTED LOAD = 1301.46 kW
DEMAND FACTOR= 0.85 MODULE. 3342846 AL SATWA (334)
MAXIMUM DEMAND LOAD= 1106.24 kW

· 0.85
0.85 EARTHING BAR

MDB-1
2x1C 150 sq.mm Cu.
CABLE Y/G AS ECC DRAWING TITLE
MIN. 6M APART
By DEWA
EARTH EARTH

· PIT PIT

TRF. NO.1
PROVISION FOR MOBILE
GENERATOR
1500 KVA

ELECTRICAL SCHEMATIC-1
· BY DEWA

· ARCHITECT ENG WISSAM DRAWING NO.

·
REGISTRATION NO.
STRUCTURAL
7095

ENG FADI
EP - 10-008
· ENGINEER
ELECTRICAL
REGISTRATION NO. 46609

SCALE DATE DRAWN JOB NO.


N.T.S
1:100 SEPTEMBER-2021 AMIR 19-DXB-221
DUBAI MUNICIPALITY STAMP

NORTH DIR

NOTES:

ELS ELS ELS ELS ELS ELS ELS

MAIN CONSULTANT :

250 KVA
PRIME RATED
GEN. SET

G B+G+3+ROOF COMMERCIAL AND


PROJECT RESIDENTIAL BUILDING
(MERAAS PLOT AT AL SATWA)

· ABDULLA AHMAD MOHAMMAD


OWNER
BIN FAHAD ALMHEIRI
·
MASTER
· MDB-2 DEVELOPER MERAAS ESTATES (L.L.C)
FORM 4b, TYPE 6, TTA,
FAULT LEVEL 50kA FOR 1Sec
FUSES

· BUSBARS: RYB1 RYB2 RYB3 RYB4 RYB5 RYB6 RYB7 RYB8 RYB9 BLOCK PLOT LOCATION
· RATED NOMINAL A A A V OC ACH
CURRENT: 2500Amps 230/400V,
50Hz 3-PHASE R Y B VSS SC HST 400 kVAR CAPACITOR 3342846 AL SATWA (334)
BMS EF PF
BANK PANEL-1
· ACTUAL CONNECTED LOAD = 1322.54 kW
PMU
SURGE PROTECTION
DEMAND FACTOR= 0.85
MAXIMUM DEMAND LOAD= 1124.16 kW
MODULE.
DRAWING TITLE
0.85 EARTHING BAR
0.85
· MDB-2
2x1C 150 sq.mm Cu.
CABLE Y/G AS ECC
MIN. 6M APART
By DEWA
EARTH
PIT
EARTH
PIT
ELECTRICAL SCHEMATIC-2
· PROVISION FOR MOBILE
TRF. NO.2
1500 KVA
GENERATOR

BY DEWA

· ARCHITECT ENG WISSAM DRAWING NO.

Refer CL/MD sheet for corrections /comments


·
· AB
for the  cables and breakers rating.
REGISTRATION NO.
STRUCTURAL
ENGINEER
7095

ENG FADI
EP - 10-009
ELECTRICAL
REGISTRATION NO. 46609

SCALE DATE DRAWN JOB NO.


N.T.S
1:100 SEPTEMBER-2021 AMIR 19-DXB-221
Refer Guarantee letter and sectional details
submitted for the proposed Attic Slab for LV Room.
No wet area is permitted above or in the wall of LV room/MDB/SMDB/DB locations.
Comply strictly with checklist submitted by the consultant, during project execution.
Also refer DEWA regulations for the electrical installations and comply.
No wet area is permitted above or in the wall of LV room/MDB/SMDB/DB locations.
Comply strictly with checklist submitted by the consultant, during project execution.
Also refer DEWA regulations for the electrical installations and comply.
DUBAI MUNICIPALITY STAMP

NORTH DIR

NOTES:

AC Room
Em Lights
150 min.

MAIN CONSULTANT :

Non combustible doors

B+G+3+ROOF COMMERCIAL AND


PROJECT RESIDENTIAL BUILDING
(MERAAS PLOT AT AL SATWA)

ABDULLA AHMAD MOHAMMAD


OWNER
BIN FAHAD ALMHEIRI

MASTER
DEVELOPER MERAAS ESTATES (L.L.C)

BLOCK PLOT LOCATION


3342846 AL SATWA (334)

DRAWING TITLE

ELECTRICAL ROOM DETAILS-1

ARCHITECT ENG WISSAM DRAWING NO.

REGISTRATION NO.
STRUCTURAL
7095
EP-10-010
ENG FADI
ENGINEER
ELECTRICAL
REGISTRATION NO. 46609

SCALE DATE DRAWN JOB NO.


N.T.S
1:100 SEPTEMBER-2021 AMIR 19-DXB-221
All doors should be
non combustible
DUBAI MUNICIPALITY STAMP

NORTH DIR

NOTES:

MAIN CONSULTANT :

B+G+3+ROOF COMMERCIAL AND


PROJECT RESIDENTIAL BUILDING
(MERAAS PLOT AT AL SATWA)

ABDULLA AHMAD MOHAMMAD


OWNER
BIN FAHAD ALMHEIRI

MASTER
DEVELOPER MERAAS ESTATES (L.L.C)

BLOCK PLOT LOCATION


3342846 AL SATWA (334)

DRAWING TITLE

ELECTRICAL ROOM DETAILS-2

ARCHITECT ENG WISSAM DRAWING NO.

REGISTRATION NO.
STRUCTURAL
7095
EP-10-011
ENG FADI
ENGINEER
ELECTRICAL
REGISTRATION NO. 46609

SCALE DATE DRAWN JOB NO.


N.T.S
1:100 SEPTEMBER-2021 AMIR 19-DXB-221