PROJECT: REESIDENTIAL & COMMERCIAL BUILDING DUBAI -AL SATWA PLOT NO: 3342846
DETAILS OF CONNECTED LOAD & MAXIMUM DEMAND & Kwh METERING
ECC CONNECTED LOAD (KW) PROPOSED TYPE & No. OF kWh METERS
PROTECTION RATING PHASE CABLE CONDUCTOR REMARKS
NO.CORES & 1 - PH 3- PH
PANEL REFERENCE 4P/TP MCCB ACB SIZE R.PH Y.PH B.PH TOTAL LV / HV CT (3)
COMPOSITION SIZE (1) (2)
2500 1 NO.2400/5A CT
INCOMER TR-01/MDB-01 TP
SET@0.85
BY DEWA 2X1C:300 433.78 433.88 433.80 1301.46 40 1 INTEGRAL METER
2500 1 NO.2400/5A CT
INCOMER TR-02/MDB-02 TP
SET@0.85
BY DEWA 2X1C:300 440.85 440.70 440.99 1322.54 61 1 INTEGRAL METER
This approval supersedes our previous approval issued vide same Ref.
dated 13/08/20 for the same project due to modification in LV panels.
Total connected load changed to 2624.0 Kw.
CAP. BANK-1 TP 800 50 XLPE/SWA/PVC 2X4C-300 2X1C-150 400 KVAR CAPACITOR BANK
1000 3 240 3 120
STANDBY LOAD(FIRE PUMP) 433.78 433.88 433.80 1301.46
MAX. DEMAND (3PH) 1106.24 kW 0.85 TOTAL DIVERSIFIED LOAD (3 PH) 1106.24 kW
Type of Meter (Rating of Incomer): (1) Up to 60 A (2) Up to 125 A (3) LV CT.... /... A / HV CT ..../..A (* 400 / 5Amps CT Metering)
Ensure to switch off some loads that TCL on TR. not exceeding
950Kw during fire mode/ test.
REESIDENTIAL & COMMERCIAL BUILDING DUBAI -AL SATWA
PROJECT:
LOCATION OF MDB-1 - LV ROOM
COMPLETION DATE: LOAD DISTRIBUTION SCHEDULE (3-PHASE) GROUND FLOOR
MDB/SMDB: MDB-2
INCOMER 4P 2500 Set @0.85 50 ˂--------------------- BY DEWA --------------------> 2X1C-300 440.85 440.70 440.99 0 61 1 2400/5A CT Meter
MOB. GENERATOR 4P 2500 Set @0.85 PROVISION FOR MOBILE GENERATOR
OUTGOING: 300 150 PF Meter
SMDB-RETAI-1 TP 400A 300 50 XLPE/SWA/PVC 4C-185 1C-95 58.57 58.62 58.98 176.17 17
CAP. BANK-2 TP 800 50 XLPE/SWA/PVC 2X4C-300 2X1C-150 400 KVAR CAPACITOR BANK
1000 3 240 3 120
TOTAL CONNECTED LOAD PER PHASE 440.85 440.70 440.99 1322.54
MAX. DEMAND (3PH) 1124.16 kW 0.85 TOTAL DIVERSIFIED LOAD (3 PH) 1124.16 kW
Type of Meter (Rating of Incomer): (1) Up to 60 A (2) Up to 125 A (3) LV CT.... /... A / HV CT ..../..A (* 400 / 5Amps CT Metering)
XLPE/SWA/FIRE
MAF-B1-01 TP 63 35 4C-16 1C-10 6.67 6.67 6.67 20.00 100mA ELS+ALARM
RATED CABLE
XLPE/SWA/FIRE
MAF-B1-02 TP 63 35 4C-16 1C-10 6.67 6.67 6.67 20.00 100mA ELS+ALARM
RATED CABLE
XLPE/SWA/FIRE
SEF-B1-01 TP 63 35 4C-16 1C-10 6.67 6.67 6.67 20.00 100mA ELS+ALARM
RATED CABLE
XLPE/SWA/FIRE
SEF-B1-02 TP 63 35 4C-16 1C-10 6.67 6.67 6.67 20.00 100mA ELS+ALARM
RATED CABLE
XLPE/SWA/FIRE
JOCKY PUMP TP 20 35 4C-10 1C-10 2.00 2.00 2.00 6.00 30mA ELS+ALARM
RATED CABLE
LOAD
INCOMER TP 63 35 XLPE/SWA/PVC 4C-16 1C-10 6.45 7.00 6.60 0
OUTGOING:
DRAINAGE PUMP TP 20 35 XLPE/SWA/PVC 4C-10 1C-10 1.60 1.70 1.70 5.00 30mA ELCB
CIRCULATION PUMP TP 20 35 XLPE/SWA/PVC 4C-6 1C-6 1.00 1.00 1.00 3.00 30mA ELCB
TRANSFER PUMP TP 20 35 XLPE/SWA/PVC 4C-6 1C-6 1.60 1.70 1.70 5.00 30mA ELCB
LOAD
INCOMER TP 630 35 XLPE/SWA/PVC 2X4C-240 2C1C-120 95.81 94.64 95.15 0
OUTGOING:
MAX. CONNECTED (3PH) 257.04 kW 0.9 TOTAL CONNECTED LOAD (3 PH) 285.60 kW
Type of Meter
SP/TP
FEEDER DUTY CABLE TYPE REMARKS
F/S 2/4 X 2/3/4C X IC, mm2 R - PH Y - PH B - PH 1 - PH 3 - PH 3 - PH LV
DB No. ACB MCCB kA CONNECT CT
ISO IC mm2 mm2 kW kW kW (1) (2) (3) (4)
ED LOAD
INCOMER TP 400 35 XLPE/SWA/PVC 2x4C-150 2x1C-95 73.40 73.84 73.02 10
OUTGOING:
SP/TP
FEEDER DUTY CABLE TYPE REMARKS
F/S 2/4 X 2/3/4C X IC, mm2 R - PH Y - PH B - PH CONNEC 1 - PH 3 - PH 3 - PH LV
DB No. ACB MCCB kA CT
ISO IC mm2 mm2 kW kW kW TED (1) (2) (3) (4)
LOAD
INCOMER TP 400 35 XLPE/SWA/PVC 2x4C-150 2x1C-95 70.69 71.68 71.90 10
OUTGOING:
SP/TP
FEEDER DUTY CABLE TYPE REMARKS
F/S 2/4 X 2/3/4C X IC, mm2 R - PH Y - PH B - PH 1 - PH 3 - PH 3 - PH LV
DB No. ACB MCCB kA CONNECTED CT
ISO IC mm2 mm2 kW kW kW (1) (2) (3) (4)
LOAD
INCOMER TP 300 35 XLPE/SWA/PVC 4C-185 1C-95 58.57 58.62 58.98 17 0
OUTGOING:
400A 300 150
DB-SH1 TP 40 35 XLPE/SWA/PVC 4C-10 1C-10 4.02 1.84 2.58 8.44 1
SP/TP
FEEDER DUTY CABLE TYPE REMARKS
F/S 2/4 X 2/3/4C X IC, mm2 R - PH Y - PH B - PH 1 - PH 3 - PH 3 - PH LV
DB No. ACB MCCB kA CONNECTED CT
ISO IC mm2 mm2 kW kW kW (1) (2) (3) (4)
LOAD
INCOMER TP 350 35 XLPE/SWA/PVC 4C-240 1C-120 55.96 55.96 55.97 14 0
OUTGOING:
SP/TP
FEEDER DUTY CABLE TYPE REMARKS
F/S 2/4 X 2/3/4C X IC, mm2 R - PH Y - PH B - PH 1 - PH 3 - PH 3 - PH LV
DB No. ACB MCCB kA CONNECT CT
ISO IC mm2 mm2 kW kW kW (1) (2) (3) (4)
ED LOAD
INCOMER TP 400 35 XLPE/SWA/PVC 2x4C-150 2x1C-95 72.52 72.90 72.28 10
OUTGOING:
SUPPLY FAN FOR FAHU -1 TP 40 35 XLPE/SWA/PVC 4C-16 1C-16 5.00 5.00 5.00 15.00 100mA ELCB
VRF-01 TP 40 35 XLPE/SWA/PVC 4C-10 1C-10 4.37 4.37 4.37 13.10 100mA ELCB
WATER BOOSTER PUMP TP 20 35 XLPE/SWA/PVC 4C-6 1C-6 1.40 1.30 1.30 4.00 30mA ELCB
WATER FILTERATION
TP 20 35 XLPE/SWA/PVC 4C-4 1C-4 0.65 0.65 0.70 2.00 30mA ELCB
PUMP
SPARE TP 40 6.01 6.01 6.01 18.03 100mA ELCB
VRF-02 TP 40 35 XLPE/SWA/PVC 4C-10 1C-10 5.23 5.23 5.23 15.70 100mA ELCB
VRF-02 TP 40 35 XLPE/SWA/PVC 4C-10 1C-10 5.00 5.00 5.00 15.00 100mA ELCB
SMDB-RF2 Rev.0
REESIDENTIAL & COMMERCIAL BUILDING DUBAI -AL
PROJECT:
SATWA
REESIDENTIAL & COMMERCIAL BUILDING DUBAI -AL SATWA
PROJECT:
LOCATION OF ROOF FLOOR
COMPLETION DATE: LOAD DISTRIBUTION SCHEDULE (3-PHASE) ELECTRICAL ROOM
MDB/SMDB: ESMDB-RF
LOAD
INCOMER TP 100 35 FIRE RATED CABLE 4C-35 1C-16 14.63 13.88 14.43 0
OUTGOING:
XLPE/SWA/FIRE
GEAF-1 TP 20 35 4C-4 1C-4 0.67 0.67 0.67 2.00 100mA ELS+ALARM
RATED CABLE
XLPE/SWA/FIRE
GEF-1 TP 63 35 4C-16 1C-10 8.33 8.33 8.33 25.00 100mA ELS+ALARM
RATED CABLE
GSM TP 40 35 XLPE/SWA/PVC 4C-10 1C-10 1.67 1.67 1.67 5.00 100mA ELCB
GSM TP 40 35 XLPE/SWA/PVC 4C-10 1C-10 1.67 1.67 1.67 5.00 100mA ELCB
RATING OF
ECC WIRE
CCT WIRE
SIZE mm2
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
RESIDENTIAL BUILDING
13A SSO
EXTRACT
COOKER
SHAVER
OUTLET
OUTLET
OUTLET
W/UNIT
TP+N+E
POINT
REMARKS
CHAN
BELL
(MERAAS PLOT AT AL
1SOL
FLEX
CCU
W/M
FAN
LTG
W/H
15A
32A
H/D
IND
R Y B
AC
SATWA)
30mA 100m
SEC-2 40A,
ISOLATOR
40A, 4P 4P
SPACE
40A TPN
2 Y1
A
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-SS REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
PROJECT: COMMERCIAL & RESIDENTIAL BUILDING
DB No: EDB-BF1 LOAD DISTRIBUTION SCHEDULE (3-PHASE) LOCATION: BASEMENT ELECTRICAL ROOM
Fed From: ESMDB-BF
LOAD PER CIRCUIT
MCB RATING
RATING OF
ECC WIRE
CCT WIRE
WATT
SIZE mm2
COMMERCIAL AND
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
RESIDENTIAL BUILDING
13A DSO
13A SSO
EXTRACT
COOKER
OTHER
OUTLET
TP+N+E
W/UNIT
15A S/O
REMARKS
CHAN
(MERAAS PLOT AT AL
FLEX
1SOL
SH/O
CCU
W/M
FCU
FAN
W/H
LTG
32A
H/D
IND
R Y B
SATWA)
30mA
30mA
SEC-3 40A,
4P 100mA
100m
40A,
4P
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) EDB-BF1 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
WATT
SIZE mm2
COMMERCIAL AND
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
RESIDENTIAL BUILDING
13A SSO
EXTRACT
COOKER
OTHER
OUTLET
TP+N+E
W/UNIT
15A S/O
REMARKS
CHAN
(MERAAS PLOT AT AL
FLEX
1SOL
SH/O
CCU
W/M
FCU
FAN
W/H
LTG
32A
H/D
IND
R Y B
SATWA)
20 Y7 20 SPARE 300.00
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-BF1 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
WATT
SIZE mm2
SIZE mm2
INCOMER
IN AMPS
CIR. NO
SL.NO.
ELCB
13A DSO
13A SSO
EXTRACT
COOKER
OTHER
ROOM/AREA
OUTLET
W/UNIT
TP+N+E
15A S/O
REMARKS
CHAN
1SOL
FLEX
SH/O
CCU
W/M
FCU
FAN
LTG
W/H
32A
H/D
IND
R Y B
30mA
19 R7 SPACE
SEC-5 40A, 4P
21 B7 20 150.00 150.00
22 R8 SPACE
CABLE SIZE 4C 10mm2 XLPE/SWA/PVC + 1C 10mm2 Y/G ECC TOTAL CONNECTED: 9300.00
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-GF1 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
MCB RATING
CONNECTED LOAD / POINTS
RATING OF
RATING OF
CCT WIRE
ECC WIRE
WATT
SIZE mm2
SIZE mm2
INCOMER
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXTRACT
COOKER
OTHER
ROOM/AREA
OUTLET
15A S/O
W/UNIT
TP+N+E
REMARKS
CHAN
D.SO
1SOL
FLEX
SH/O
13A
CCU
W/M
FCU
LTG
FAN
W/H
32A
H/D
IND
R Y B
30mA
30mA
11 Y4 32 6.0 6.0 CORRIDOR 1 3000 3000.00 ISO. IN FLOOR BOX FOR KIOSK
12 B4 32 6.0 6.0 CORRIDOR 1 3000 3000.00 ISO. IN FLOOR BOX FOR KIOSK
13 R5 32 6.0 6.0 CORRIDOR 1 3000 3000.00 ISO. IN FLOOR BOX FOR KIOSK
SEC-5 SEC-4
30mA 30mA
40A, 40A,
4P
14 Y5 32 6.0 6.0 CORRIDOR 1 3000 3000.00 ISO. IN FLOOR BOX FOR KIOSK
15 B5 32 6.0 6.0 CORRIDOR 1 3000 3000.00 ISO. IN FLOOR BOX FOR KIOSK
16 R6 32 6.0 6.0 CORRIDOR 1 3000 3000.00 ISO. IN FLOOR BOX FOR KIOSK
100A TPN ISOLATOR
4P
39 B13 SPACE
40 R14 SPACE
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-GF1 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
WATT
SIZE mm2
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXTRACT
COOKER
OTHER
ROOM/AREA
OUTLET
TP+N+E
W/UNIT
15A S/O
REMARKS
CHAN
FLEX
1SOL
SH/O
CCU
W/M
FCU
FAN
W/H
LTG
32A
H/D
IND
R Y B
CU-GF.32 UVR+TIMER
40A, 4P
+CONTROL
2 Y1 20 4.0 4.0 FCU-GF.32 1 190.00 190.00
ISOLATOR
40A TPN
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-GF1 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
WATT
INCOMER
SIZE mm2
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXTRACT
OTHER
13A DSO
ROOM/AREA
OUTLET
W/UNIT
TP+N+E
15A S/O
REMARKS
CHAN
1SOL
FLEX
SH/O
W/M
FCU
FAN
LTG
W/H
32A
H/D
IND
R Y B
100m
40A,
100m
40A TPN ISOLATOR
40A,
5 Y2 1033.33 UVR+TIMER+CO
4P
NTROL
6 B2 1033.33
7 R3 32 4.0 4.0 SHOP 5 400.00 2000.00 RING
SEC-3
30mA
40A,
13 R5 20 SPARE 300.00
14 Y5 SPACE
15 B5 SPACE
Total connected Loads (W) 4023.33 1833.33 2583.33 8440.00
4.02 1.83 2.58
CABLE SIZE 4C 10mm2 XLPE/SWA/PVC + 1C 10mm2 Y/G ECC TOTAL CONNECTED: 8440.00
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-SH1 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
WATT
SIZE mm2
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXTRACT
OTHER
13A DSO
ROOM/AREA
OUTLET
TP+N+E
W/UNIT
15A S/O
REMARKS
CHAN
FLEX
1SOL
SH/O
W/M
FCU
FAN
W/H
LTG
32A
H/D
IND
R Y B
3 B1 10 SPARE 500.00
40A, 4P
100mA
SEC-2
6 B2 SPACE
7 R3 SPACE
SEC-3
30mA
40A,
SHOP
4P
15 B5 SPACE
Total connected Loads (W) 3440.00 2700.00 1900.00 8040.00
3.44 2.70 1.90
CABLE SIZE 4C 10mm2 XLPE/SWA/PVC + 1C 10mm2 Y/G ECC TOTAL CONNECTED: 8040.00
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-SH2 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
WATT
SIZE mm2
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXTRACT
OTHER
13A DSO
ROOM/AREA
OUTLET
TP+N+E
W/UNIT
15A S/O
REMARKS
CHAN
FLEX
1SOL
SH/O
W/M
FCU
FAN
W/H
LTG
32A
H/D
IND
R Y B
40A, SEC-1 40A,
4P 100mA
4 R2 1033.33
30mA 100mA
SEC-3 SEC-2
UVR+TIMER+C
4P
8 Y3 20 SPARE 250.00
9 B3 32 4.0 4.0 SHOP 5 400.00 2000.00 RING
10 R4 20 4.0 4.0 FCU-GF.03 1 390.00 390.00
SEC-4 40A, 4P
12 B4 SPACE
13 R5 20 SPARE 300.00 300.00
14 Y5 SPACE
15 B5 SPACE
Total connected Loads (W) 2373.33 2583.33 3333.33 8290.00
2.37 2.58 3.33
CABLE SIZE 4C 10mm2 XLPE/SWA/PVC + 1C 10mm2 Y/G ECC TOTAL CONNECTED: 8290.00
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-SH3 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
WATT
SIZE mm2
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXTRACT
OTHER
13A DSO
ROOM/AREA
OUTLET
TP+N+E
W/UNIT
15A S/O
REMARKS
CHAN
FLEX
1SOL
SH/O
W/M
FCU
FAN
W/H
LTG
32A
H/D
IND
R Y B
40A,
5 Y2 1033.33 UVR+TIMER+C
4P
15 B5 SPACE
Total connected Loads (W) 3633.33 2433.33 2123.33 8190.00
3.63 2.43 2.12
CABLE SIZE 4C 10mm2 XLPE/SWA/PVC + 1C 10mm2 Y/G ECC TOTAL CONNECTED: 8190.00
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-SH4 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
WATT
SIZE mm2
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXTRACT
OTHER
13A DSO
ROOM/AREA
OUTLET
TP+N+E
W/UNIT
15A S/O
REMARKS
CHAN
FLEX
1SOL
SH/O
W/M
FCU
FAN
W/H
LTG
32A
H/D
IND
R Y B
1 R1 SPACE
30mA 100mA 100mA
SEC-3 SEC-2 SEC-1
40A,
40A,
UVR+TIMER+C
4P
8 Y3 20 SPARE 200.00
9 B3 20 4.0 4.0 SHOP 1 400.00 400.00
10 R4 SPACE
SEC-4 40A, 4P
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-SH5 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
WATT
SIZE mm2
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXTRACT
OTHER
13A DSO
ROOM/AREA
OUTLET
TP+N+E
W/UNIT
15A S/O
REMARKS
CHAN
FLEX
1SOL
SH/O
W/M
FCU
FAN
W/H
LTG
32A
H/D
IND
R Y B
2 Y1 10 SPARE 250.00
3 B1 SPACE
UVR+TIMER+C
5 Y2 20 SPARE 250.00 250.00
ONTROL
6 B2 SPACE
30mA
12 B4 20 SPARE 1 250.00
13 R5 20 SPARE 300 300.00
14 Y5 SPACE
15 B5 SPACE
Total connected Loads (W) 4060.00 1090.00 2250.00 7400.00
4.06 1.09 2.25
CABLE SIZE 4C 10mm2 XLPE/SWA/PVC + 1C 10mm2 Y/G ECC TOTAL CONNECTED: 7400.00
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-SH6 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
WATT
SIZE mm2
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXTRACT
OTHER
13A DSO
ROOM/AREA
OUTLET
TP+N+E
W/UNIT
15A S/O
REMARKS
CHAN
FLEX
1SOL
SH/O
W/M
FCU
FAN
W/H
LTG
32A
H/D
IND
R Y B
2 Y1 SPACE
4P
100m
40A,
4P
30mA
40A,
4P
8 Y3 SPACE
9 B3 20 4.0 4.0 SHOP 1 400.00 400.00
10 R4 20 SPARE 250.00 250.00
SEC-4 40A,
4P 100mA
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-SH7 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
WATT
SIZE mm2
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXTRACT
OTHER
13A DSO
ROOM/AREA
OUTLET
TP+N+E
W/UNIT
15A S/O
REMARKS
CHAN
FLEX
1SOL
SH/O
W/M
FCU
FAN
W/H
LTG
32A
H/D
IND
R Y B
100mA 100mA
2 Y1 SPACE
3 B1 SPACE
40A TPN ISOLATOR
4 R2 20 SPARE 250.00
40A,
4P
30mA
8 Y3 SPACE
9 B3 32 4.0 4.0 SHOP 5 400.00 2000.00 RING
10 R4 20 SPARE 250.00 250.00
SEC-4 40A, 4P
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-SH8 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
WATT
SIZE mm2
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXTRACT
OTHER
13A DSO
ROOM/AREA
OUTLET
TP+N+E
W/UNIT
15A S/O
REMARKS
CHAN
FLEX
1SOL
SH/O
W/M
FCU
FAN
W/H
LTG
32A
H/D
IND
R Y B
100m
40A,
2 Y1 SPACE
4P
3 B1 SPACE
40A TPN ISOLATOR
8 Y3 SPACE
9 B3 32 4.0 4.0 SHOP 5 400.00 2000.00 RING
10 R4 20 SPARE 200.00 200.00
SEC-4 40A, 4P
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-SH9 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
WATT
SIZE mm2
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXTRACT
OTHER
13A DSO
ROOM/AREA
OUTLET
TP+N+E
W/UNIT
15A S/O
REMARKS
CHAN
FLEX
1SOL
SH/O
W/M
FCU
FAN
W/H
LTG
32A
H/D
IND
R Y B
UVR+TIMER+C
4P
5 Y2 SPACE
ONTROL
6 B2 32 6.0 6.0 CU-GF.10 1 2740.00 2740
7 R3 20 SPARE 200.00 200.00
40A,
4P
12 B4 SPACE
13 R5 20 SPARE 300.00 300.00
14 Y5 SPACE
15 B5 SPACE
Total connected Loads (W) 2000.00 2500.00 3140.00 7640.00
2.00 2.50 3.14
CABLE SIZE 4C 10mm2 XLPE/SWA/PVC + 1C 10mm2 Y/G ECC TOTAL CONNECTED: 7640.00
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-SH10 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
WATT
SIZE mm2
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXTRACT
OTHER
13A DSO
ROOM/AREA
OUTLET
TP+N+E
W/UNIT
15A S/O
REMARKS
CHAN
FLEX
1SOL
SH/O
W/M
FCU
FAN
W/H
LTG
32A
H/D
IND
R Y B
3 B1 SPACE
40A TPN ISOLATOR
100m
40A,
4P
5 Y2 SPACE
A
30mA
40A,
12 B4 SPACE
13 R5 20 SPARE 300.00 300.00
14 Y5 SPACE
15 B5 SPACE
Total connected Loads (W) 2100.00 2450.00 3140.00 7690.00
2.10 2.45 3.14
CABLE SIZE 4C 10mm2 XLPE/SWA/PVC + 1C 10mm2 Y/G ECC TOTAL CONNECTED: 7690.00
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-SH11 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
WATT
SIZE mm2
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXTRACT
OTHER
13A DSO
ROOM/AREA
OUTLET
TP+N+E
W/UNIT
15A S/O
REMARKS
CHAN
FLEX
1SOL
SH/O
W/M
FCU
FAN
W/H
LTG
32A
H/D
IND
R Y B
2 Y1 SPACE
3 B1 10 SPARE 250 250.00
40A TPN ISOLATOR
8 Y3 SPACE
9 B3 32 4.0 4.0 SHOP 5 400.00 2000.00 RING
SEC-4 40A, 4P
10 R4 20 SPARE 200.00
11 Y4 20 4.0 4.0 SIGN BOARD 1 1000.00 1000.00
100mA
12 B4 SPACE
13 R5 20 SPARE 300.00 300.00
14 Y5 SPACE
15 B5 SPACE
Total connected Loads (W) 1600.00 3740.00 2500.00 7840.00
1.60 3.74 2.50
CABLE SIZE 4C 10mm2 XLPE/SWA/PVC + 1C 10mm2 Y/G ECC TOTAL CONNECTED: 7840.00
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-SH12 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
WATT
SIZE mm2
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXTRACT
OTHER
13A DSO
ROOM/AREA
OUTLET
TP+N+E
W/UNIT
15A S/O
REMARKS
CHAN
FLEX
1SOL
SH/O
W/M
FCU
FAN
W/H
LTG
32A
H/D
IND
R Y B
1 R1 10 SPARE 200.00
100mA 100mA
SEC-2 SEC-1
40A,
4P
2 Y1 SPACE
40A TPN ISOLATOR
30mA
40A,
4P
8 Y3 SPACE
9 B3 20 4.0 4.0 SHOP 1 400.00 400.00
SPARE
100mA
10 R4 20 400.00 400.00
SEC-4
40A,
4P
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-SH13 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
WATT
SIZE mm2
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXTRACT
OTHER
13A DSO
ROOM/AREA
OUTLET
TP+N+E
W/UNIT
15A S/O
REMARKS
CHAN
FLEX
1SOL
SH/O
W/M
FCU
FAN
W/H
LTG
32A
H/D
IND
R Y B
40A, 4P
2 Y1 SPACE
40A TPN ISOLATOR
3 B1 SPACE
4 R2 20 SPARE 250.00 250.00
100mA
SEC-2
40A,
4P
30mA
40A,
4P
11 Y4 SPACE
12 B4 SPACE
Total connected Loads (W) 1550.00 2190.00 2510.00 6250.00
1.55 2.19 2.51
CABLE SIZE 4C 10mm2 XLPE/SWA/PVC + 1C 10mm2 Y/G ECC TOTAL CONNECTED: 6250.00
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-SH14 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
WATT
SIZE mm2
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXTRACT
13A DSO
OTHER
ROOM/AREA
OUTLET
TP+N+E
W/UNIT
15A S/O
REMARKS
CHAN
FLEX
1SOL
SH/O
W/M
FCU
FAN
W/H
LTG
32A
H/D
IND
R Y B
2 Y1 10 SPARE 250.00
40A TPN ISOLATOR
3 B1 10 SPARE 250.00
4 R2 1220.00
40A,
UVR+TIMER+
4P
100m 30mA
8 Y3 SPACE
9 B3 32 4.0 4.0 SHOP 5 400.00 2000.00 RING
10 R4 20 SPARE 250.00 250.00
SEC-4
40A,
4P
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-SH15 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
WATT
SIZE mm2
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXTRACT
OTHER
13A DSO
ROOM/AREA
OUTLET
TP+N+E
W/UNIT
15A S/O
REMARKS
CHAN
FLEX
1SOL
SH/O
W/M
FCU
FAN
W/H
LTG
32A
H/D
IND
R Y B
2 Y1 SPACE
40A TPN ISOLATOR
5 Y2 1033.33 UVR+TIMER+C
4P
30mA
8 Y3 SPACE
9 B3 20 4.0 4.0 SHOP 1 400.00 400.00
10 R4 SPACE
100mA
SEC-4
40A,
4P
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-SH16 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
SEC-1 RATIN
RATIN
SL.NO
ELCB
WIRE
WIRE
INCO
G OF
G OF ROOM/AR
MCB
SIZE
SIZE
ECC
G IN
CCT
CIR.
W/UNI
NO
REMARKS
DSO
13A
OUT
RAC
FCU
W/M
1SO
N+E
EXT
LTG
W/H
FLE
TP+
.
S/O
13A
15A
32A
CH
AN
H/D
OT
HE
SH/
SS
EA T R Y B
R
O
L
1 R1 10 2.5 2.5 SHOP 8 50.00 400.00
100mA 100mA 100mA 30mA 100mA 100mA
40A,
4P
2 Y1 SPACE
3 B1 10 2.5 2.5 SHOP 8 50.00 400.00
4 R2 1660.00
SEC-6 SEC-5 SEC-4 SEC-3 SEC-2
40A,
5 Y2 1660.00 UVR+TIMER+C
4P
ONTROL
6 B2 1660.00
7 R3 SPACE
40A,
11 Y4 SPACE
4P
14 Y5 63 6616.67
4P
17 Y6 63 6616.67
4P
SPARE 1 19850.00
18 B6 A 6616.67
Total connected Loads (kW) 15863.33 16893.33 16693.33 49450.00
15.86 16.89 16.69
CABLE SIZE 4C 35mm2 XLPE/SWA/PVC + 1C 16 mm2 Y/G ECC TOTAL CONNECTED: 49450.00
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-SH17 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
40A, RATIN
RATIN
SL.NO
100m 100m ELCB
WIRE
WIRE
INCO
G OF
G OF
ROOM/AR
SIZE
SIZE
MCB
G IN
ECC
CCT
CIR.
W/UNI
NO
REMARKS
13A
DSO
OUT
RAC
W/M
FCU
N+E
1SO
LTG
W/H
EXT
TP+
32A
FLE
.
13A
15A
CH
S/O
AN
SH/
H/D
HE
OT
SS
EA T R Y B
R
O
L
1 R1 10 2.5 2.5 SHOP 8 50.00 400.00
SEC-2 SEC-1
4P
125A TPN ISOLATOR
2 Y1 10 SPARE 250.00
A
UVR+TIMER+C
4P
ONTROL
6 B2 1660.00
7 R3 20 4.0 4.0 SHOP 1 400.00 400.00
SEC-3
30mA
40A,
100m
40A,
12 B4 20 SPARE 150.00
13 R5 TP 6616.67
100mA 100mA
SEC-6 SEC-5
40A,
14 Y5 63 6616.67
4P
SPARE 1 19850.00
15 B5 A 6616.67
Future load subject to DEWA's prior approval and
16 R6 TP AB
inspection as and when it is being connected. 6616.67
40A,
17 Y6 63 6616.67
4P
SPARE 1 19850.00
18 B6 A 6616.67
Total connected Loads (kW) 16693.33 15913.33 17443.33 50050.00
16.69 15.91 17.44
CABLE SIZE 4C 35mm2 XLPE/SWA/PVC + 1C 16 mm2 Y/G ECC TOTAL CONNECTED: 50050.00
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-SH18 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
WATT
SIZE mm2
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXTRACT
OTHER
13A DSO
ROOM/AREA
OUTLET
TP+N+E
W/UNIT
15A S/O
REMARKS
CHAN
FLEX
1SOL
SH/O
W/M
FCU
FAN
W/H
LTG
32A
H/D
IND
R Y B
4 R2 1220.00
40A,
UVR+TIMER+C
4P
30mA
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-SH19 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
WATT
SIZE mm2
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXTRACT
13A DSO
OTHER
ROOM/AREA
OUTLET
TP+N+E
W/UNIT
15A S/O
REMARKS
CHAN
FLEX
1SOL
SH/O
W/M
FCU
FAN
W/H
LTG
32A
H/D
IND
R Y B
100mA
4 R2 1456.67
SEC-2
100m
40A,
UVR+TIMER+C
4P
5 Y2 1456.67 ONTROL
6 B2 1456.67
7 R3 SPACE
SEC-3
30mA
40A,
4P
11 Y4 20 SPARE 250.00
100mA
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-SH20 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
WATT
SIZE mm2
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
13A TSSO
EXTRACT
OTHER
ROOM/AREA
OUTLET
TP+N+E
W/UNIT
15A S/O
REMARKS
CHAN
FLEX
1SOL
SH/O
W/M
FCU
FAN
W/H
LTG
32A
H/D
IND
R Y B
100m
40A,
4P
4 R2 1456.67
SEC-2
100m
40A,
UVR+TIMER+C
4P
ONTROL
6 B2 1456.67
7 R3 20 4.0 4.0 SHOP 1 400.00 400.00
SEC-3
30mA
40A,
4P
12 B4 20 SPARE 250.00
13 R5 SPACE
14 Y5 20 SPARE 250.00 250.00
15 B5 SPACE
Total connected Loads (W) 2836.67 3106.67 4156.67 10100.00
2.84 3.11 4.16
CABLE SIZE 4C 10mm2 XLPE/SWA/PVC + 1C 10mm2 Y/G ECC TOTAL CONNECTED: 10100.00
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-SH21 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
WATT
SIZE mm2
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXTRACT
OTHER
13A DSO
ROOM/AREA
OUTLET
TP+N+E
W/UNIT
15A S/O
REMARKS
CHAN
FLEX
1SOL
SH/O
W/M
FCU
FAN
W/H
LTG
32A
H/D
IND
R Y B
4 R2 1456.67
40A,
UVR+TIMER+
4P
30mA
40A,
4P
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-SH22 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
WATT
SIZE mm2
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXTRACT
OTHER
13A DSO
ROOM/AREA
OUTLET
TP+N+E
W/UNIT
15A S/O
REMARKS
CHAN
FLEX
1SOL
SH/O
W/M
FCU
FAN
W/H
LTG
32A
H/D
IND
R Y B
4 R2 1456.67
40A,
UVR+TIMER+C
4P
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-SH23 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
WATT
SIZE mm2
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXTRACT
OTHER
13A DSO
ROOM/AREA
OUTLET
TP+N+E
W/UNIT
15A S/O
REMARKS
CHAN
FLEX
1SOL
SH/O
W/M
FCU
FAN
W/H
LTG
32A
H/D
IND
R Y B
4 R2 1456.67
SEC-2
100m
40A,
UVR+TIMER+C
4P
5 Y2 1456.67 ONTROL
6 B2 1456.67
7 R3 20 4.0 4.0 SHOP 1 400.00 400.00
SEC-3
30mA
40A,
4P
12 B4 SPACE
13 R5 SPACE
14 Y5 20 SPARE 250.00 250.00
15 B5 SPACE
Total connected Loads (W) 2836.67 3156.67 3906.67 9900.00
2.84 3.16 3.91
CABLE SIZE 4C 10mm2 XLPE/SWA/PVC + 1C 10mm2 Y/G ECC TOTAL CONNECTED: 9900.00
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-SH24 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
WATT
SIZE mm2
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXTRACT
OTHER
13A DSO
ROOM/AREA
OUTLET
TP+N+E
W/UNIT
15A S/O
REMARKS
CHAN
FLEX
1SOL
SH/O
W/M
FCU
FAN
W/H
LTG
32A
H/D
IND
R Y B
4 R2 1456.67
100mA
SEC-2
40A,
UVR+TIMER+C
4P
30mA
40A,
4P
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-SH25 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
WATT
SIZE mm2
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXTRACT
OTHER
13A DSO
ROOM/AREA
OUTLET
TP+N+E
W/UNIT
15A S/O
REMARKS
CHAN
FLEX
1SOL
SH/O
W/M
FCU
FAN
W/H
LTG
32A
H/D
IND
R Y B
4 R2 1456.67
SEC-2
100m
40A,
UVR+TIMER+
4P
CONTROL
6 B2 1456.67
7 R3 SPACE
SEC-3
30mA
40A,
4P
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-SH26 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
WATT
SIZE mm2
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXTRACT
OTHER
13A DSO
ROOM/AREA
OUTLET
TP+N+E
W/UNIT
15A S/O
REMARKS
CHAN
FLEX
1SOL
SH/O
W/M
FCU
FAN
W/H
LTG
32A
H/D
IND
R Y B
UVR+TIMER+
5 Y2 20 6.0 6.0 CU-GF.27 1 4370 1456.67
CONTROL
6 B2 1456.67
7 R3 20 4.0 4.0 SHOP 1 400.00 400.00
SEC-3
30mA
40A,
4P
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-SH27 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
WATT
SIZE mm2
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXTRACT
OTHER
13A DSO
ROOM/AREA
OUTLET
TP+N+E
W/UNIT
15A S/O
REMARKS
CHAN
FLEX
1SOL
SH/O
W/M
FCU
FAN
W/H
LTG
32A
H/D
IND
R Y B
1 R1 SPACE
100mA
SEC-1
40A,
4P
100m
ONTROL
40A,
4P
FCU-GF.28
A
30mA
40A,
4P
10 R4
100mA
SEC-4
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-SH28 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
WATT
SIZE mm2
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXTRACT
13A D.SO
OTHER
ROOM/AREA
OUTLET
TP+N+E
W/UNIT
15A S/O
REMARKS
CHAN
FLEX
1SOL
SH/O
W/M
FCU
FAN
W/H
LTG
32A
H/D
IND
R Y B
3 B1 10 SPARE 200.00
4 R2 32 6.0 6.0 CU-GF.29 1 2110 2110.00
40A,
UVR+TIMER+C
4P
30mA
40A,
4P
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-SH29 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
WATT
SIZE mm2
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXTRACT
13A D.SO
OTHER
ROOM/AREA
OUTLET
TP+N+E
W/UNIT
15A S/O
REMARKS
CHAN
FLEX
1SOL
SH/O
W/M
FCU
FAN
W/H
LTG
32A
H/D
IND
R Y B
6 B2 SPACE
7 R3 20 4.0 4.0 SHOP 1 400.00 400.00
SEC-3
30mA
40A,
4P
10 R4
SEC-4
40A,
4P
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-SH30 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
WATT
SIZE mm2
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXTRACT
13A D.SO
OTHER
ROOM/AREA
OUTLET
TP+N+E
W/UNIT
15A S/O
REMARKS
CHAN
FLEX
1SOL
SH/O
W/M
FCU
FAN
W/H
LTG
32A
H/D
IND
R Y B
UVR+TIMER+C
4P
30mA
40A,
4P
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-SH31 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
WATT
SIZE mm2
SIZE mm2
INCOMER
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXHAUST
COOKER
ROOM/AREA
SHAVER
OUTLET
OUTLET
W/UNIT
TP+N+E
POINT
REMARKS
CHAN
HOOD
BELL
D.SO
W/M
FCU
D/W
W/H
ISOL
H/D
13A
LTG
15A
32A
IND
R Y B
AC
1 R1 20 4.0 4.0 CORRIDOR 1 400.00 400.00
SEC-1 40A,
BED ROOM
4P 30mA
30mA
4P
21 B7 10 2.5 2.5 BED ROOM, MASTER BED ROOM & BATH 5 3 1 50/100 650.00
22 R8 1220.00
40A, 4P
100mA
SEC-5
UVR+TIMER+CONTRO
23 Y8 20 6.0 6.0 CU-1F.01.1 1 3660 1220.00 L
24 B8 1220.00
25 R9 32 6.0 6.0 CU-1F.01.2 2740 2740.00
100mA 1
SEC-6 40A, 4P
CABLE SIZE 4C 16mm2 XLPE/SWA/PVC + 1C 16mm2 Y/G ECC TOTAL CONNECTED: 22520.00
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-FF1 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
WATT
INCOMER
SIZE mm2
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXHAUST
COOKER
ROOM/AREA
SHAVER
OUTLET
OUTLET
W/UNIT
TP+N+E
POINT
REMARKS
CHAN
HOOD
D.SO
BELL
D/W
ISOL
13A
W/M
FCU
LTG
W/H
15A
32A
H/D
IND
AC
R Y B
BED ROOM
4P 30mA
BATH
4P 30mA
30mA
4P
17 Y6 10 2.5 2.5 BED ROOM & MASTER BED ROOM 6 3 1 50/100 700.00
18 B6 10 2.5 2.5 KITCHEN 2 1 50/100 200.00
19 R7 10 2.5 2.5 CORRIDOR 10 1 1 50/100/100 700.00
20 Y7 SPACE
21 B7 10 SPARE 200.00
22 R8 1456.67
SEC-5
100m
40A,
4P
24 B8 1456.67
25 R9 32 6.0 6.0 CU-1F.02.2 1 2740 2740.00
SEC-6 40A,
4P 100mA
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-FF2 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
SIZE mm2
SIZE mm2
INCOMER
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXHAUST
COOKER
ROOM/AREA
SHAVER
OUTLET
OUTLET
W/UNIT
TP+N+E
POINT
REMARKS
CHAN
HOOD
BELL
D.SO
D/W
ISOL
13A
W/M
FCU
LTG
W/H
15A
32A
IND
H/D
R Y B
AC
1 R1 20 4.0 4.0 CORRIDOR 1 400 400.00
SEC-1 40A,
BED ROOM
4P 30mA
BATH
4P 30mA
30mA
40A,
4P
17 Y6 SPACE
18 B6 10 2.5 2.5 KITCHEN 2 1 50/100 200.00
19 R7 10 2.5 2.5 CORRIDOR 8 1 50/100 500.00
20 Y7 SPACE
21 B7 10 2.5 2.5 BED ROOM & MASTER BED ROOM 7 3 1 50/100 750.00
22 R8 1220.00
SEC-5
100m
40A,
UVR+TIMER+
4P
CONTROL
24 B8 1220.00
25 R9 20 4.0 4.0 FCU-1F.03.1 - WC 1 470 470.00
SEC-6 40A,
4P 100mA
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-FF3 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
*Armored cable to be used for all external services
PROJECT: COMMERCIAL & RESIDENTIAL BUILDING
DB No: DB-FF4 LOAD DISTRIBUTION SCHEDULE (3-PHASE) LOCATION:FIRST FLOOR FLAT
Fed From: SMDB-FF1
MCB RATING
RATING OF
ECC WIRE
CCT WIRE
SIZE mm2
SIZE mm2
INCOMER
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXHAUST
COOKER
ROOM/AREA
SHAVER
OUTLET
OUTLET
W/UNIT
TP+N+E
POINT
REMARKS
CHAN
HOOD
D.SO
BELL
D/W
ISOL
13A
W/M
FCU
LTG
W/H
15A
32A
H/D
IND
R Y B
AC
1 R1 20 4.0 4.0 CORRIDOR 1 400 400.00
SEC-1 40A,
2 1
3 B1 20 4.0 4.0 KITCHEN (D/W) 1 1500 1500.00
4 R2 32 4.0 4.0 SITTING AREA DINING 3 1 200 / 400 1000.00 RING
5 Y2 20 4.0 4.0 BED ROOM 2 1 200 / 400 800.00
6 B2 20 4.0 4.0 KITCHEN (W/M) 1 1500 1500.00
7 R3 20 4.0 4.0 STORE 2 1 200 / 400 800.00
40A, SEC-2 40A,
30mA
4P
17 Y6 10 2.5 2.5 BED ROOM & MASTER BED ROOM 7 3 1 50/100 750.00
18 B6 10 2.5 2.5 KITCHEN 2 1 50/100 200.00
19 R7 10 2.5 2.5 CORRIDOR 8 1 50/100 500.00
20 Y7 SPACE
21 B7 10 SPARE 200 200.00
22 R8 1220.00
SEC-5
100m
40A,
UVR+TIMER+CO
4P
NTROL
24 B8 1220.00
25 R9 20 6.0 6.0 FCU-1F.04.1 - WC 1 470 470.00
SEC-6 40A,
4P 100mA
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-FF4 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
*Armored cable to be used for all external services
PROJECT: COMMERCIAL & RESIDENTIAL BUILDING
DB No: DB-FF5 LOAD DISTRIBUTION SCHEDULE (3-PHASE) LOCATION: FIRST FLOOR FLAT
Fed From: SMDB-FF1
MCB RATING
RATING OF
ECC WIRE
CCT WIRE
SIZE mm2
SIZE mm2
INCOMER
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXHAUST
COOKER
ROOM/AREA
SHAVER
OUTLET
OUTLET
W/UNIT
TP+N+E
POINT
REMARKS
CHAN
HOOD
D.SO
BELL
D/W
ISOL
13A
W/M
FCU
LTG
W/H
15A
32A
H/D
IND
R Y B
AC
1 R1 20 4.0 4.0 KITCHEN 1 1500.00 1500.00
SEC-1 40A,
3 B1 32 4.0 4.0 DINING & SITTING AREA 4 1 200 / 400 1200.00 RING
4 R2 20 SPARE 200.00 200.00
5 Y2 20 4.0 4.0 KITCHEN 1 1500.00 1500.00
6 B2 20 4.0 4.0 CORRIDOR (ONU) 1 200 / 400 400.00
7 R3 32 4.0 4.0 KITCHEN 1 3 200 / 400 1400.00 RING
SEC-2 40A,
SPACE
4P 30mA
8 Y3
9 B3 20 4.0 4.0 BED ROOM-1 2 1 200 / 400 800.00
40A TPN ISOLATOR
100m
40A,
UVR+TIMER+
4P
CONTROL
15 B5 1033.33
16 R6 10 2.5 2.5 KITCHEN 2 1 50/100 200.00
SEC-4 40A,
4P 100mA
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-FF5 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
SIZE mm2
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A D.SO
13A SSO
EXHAUST
COOKER
ROOM/AREA
SHAVER
OUTLET
OUTLET
TP+N+E
W/UNIT
POINT
REMARKS
CHAN
HOOD
BELL
D/W
ISOL
W/M
W/H
LTG
15A
32A
H/D
IND
AC
R Y B
30mA
40A,
4P
17 Y6 10 2.5 2.5 BED ROOM & MASTER BED ROOM 7 3 1 50/100 750.00
18 B6 10 2.5 2.5 KITCHEN 2 1 50/100 200.00
19 R7 10 2.5 2.5 CORRIDOR 8 1 50/100 500.00
20 Y7 SPACE
21 B7 10 SPARE 200.00
22 R8 1220.00
SEC-5
100m
40A,
UVR+TIMER+
4P
CONTROL
24 B8 1220.00
25 R9 20 4.0 4.0 FCU-1F.06.1 - WC 1 470 470.00
SEC-6 40A,
UVR+TIMER+
4P 100mA
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-FF6 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
*Armored cable to be used for all external services
PROJECT: COMMERCIAL & RESIDENTIAL BUILDING
DB No: DB-FF7 LOAD DISTRIBUTION SCHEDULE (3-PHASE) LOCATION: FIRST FLOOR FLAT
Fed From: SMDB-FF1
MCB RATING
RATING OF
ECC WIRE
CCT WIRE
SIZE mm2
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A D.SO
13A SSO
EXHAUST
COOKER
ROOM/AREA
SHAVER
OUTLET
OUTLET
TP+N+E
W/UNIT
POINT
REMARKS
CHAN
HOOD
BELL
D/W
ISOL
W/M
W/H
LTG
15A
32A
H/D
IND
AC
R Y B
30mA
40A,
4P
17 Y6 10 2.5 2.5 BED ROOM & MASTER BED ROOM 7 3 1 50/100 750.00
18 B6 10 2.5 2.5 KITCHEN 2 1 50/100 200.00
19 R7 10 2.5 2.5 CORRIDOR 8 1 50/100 500.00
20 Y7 SPACE
21 B7 10 SPARE 200.00
22 R8 1033.33
SEC-5
100m
40A,
UVR+TIMER+C
4P
ONTROL
24 B8 1033.33
25 R9 20 4.0 4.0 FCU-1F.07.2 - BATH 250 250.00
SEC-6 40A,
4P 100mA
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-FF7 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
*Armored cable to be used for all external services
PROJECT: COMMERCIAL & RESIDENTIAL BUILDING
DB No: DB-FF8 LOAD DISTRIBUTION SCHEDULE (3-PHASE) LOCATION:FIRST FLOOR FLAT
Fed From: SMDB-FF1
MCB RATING
RATING OF
ECC WIRE
CCT WIRE
SIZE mm2
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A D.SO
13A SSO
EXHAUST
COOKER
ROOM/AREA
SHAVER
OUTLET
OUTLET
TP+N+E
W/UNIT
POINT
REMARKS
CHAN
HOOD
BELL
D/W
ISOL
W/M
W/H
LTG
15A
32A
H/D
IND
AC
R Y B
30mA
40A,
4P
17 Y6 10 2.5 2.5 BED ROOM & MASTER BED ROOM 9 2 2 50/100 850.00
18 B6 10 2.5 2.5 KITCHEN 3 1 50/100 250.00
19 R7 10 2.5 2.5 CORRIDOR 8 1 50/100 500.00
20 Y7 SPACE
21 B7 10 SPARE 200 200.00
22 R8 1220.00
SEC-5
100m
40A,
UVR+TIMER+
4P
CONTROL
24 B8 1220.00
25 R9 32 6.0 6.0 CU-1F.08.2 1 2740 2740.00
SEC-6 40A,
4P 100mA
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-FF8 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
*Armored cable to be used for all external services
PROJECT: COMMERCIAL & RESIDENTIAL BUILDING
DB No: DB-FF9 LOAD DISTRIBUTION SCHEDULE (3-PHASE) LOCATION: FIRST FLOOR FLAT
Fed From: SMDB-FF1
MCB RATING
RATING OF
ECC WIRE
CCT WIRE
INCOMER
SIZE mm2
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A DSO
13A SSO
EXHAUST
COOKER
ROOM/AREA
SHAVER
OUTLET
OUTLET
W/UNIT
TP+N+E
POINT
REMARKS
CHAN
BELL
HOOD
D/W
ISOL
W/M
LTG
W/H
15A
32A
H/D
IND
R Y B
AC
1 R1 20 4.0 4.0 CORRIDOR 1 400 400.00
SEC-1 40A,
30mA
40A,
4P
17 Y6 10 2.5 2.5 BED ROOM & MASTER BED ROOM 9 3 1 50/100 550.00
18 B6 10 2.5 2.5 KITCHEN 2 1 50/100 200.00
19 R7 10 2.5 2.5 CORRIDOR 6 1 1 50/100 500.00
20 Y7 SPACE
21 B7 10 SPARE 250 250.00
22 R8 1220.00
SEC-7 SEC-6 SEC-5
UVR+TIMER+CO
4P
NTROL
24 B8 1220.00
25 R9 1033.33
UVR+TIMER+CO
4P
NTROL
27 B9 1033.33
28 R10 20 SPARE 250 250.00
4P
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-FF9 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
*Armored cable to be used for all external services
PROJECT: COMMERCIAL & RESIDENTIAL BUILDING
DB No: DB-FF10 LOAD DISTRIBUTION SCHEDULE (3-PHASE) LOCATION: FIRST FLOOR FLAT
Fed From: SMDB-FF1
MCB RATING
RATING OF
ECC WIRE
CCT WIRE
SIZE mm2
SIZE mm2
INCOMER
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXHAUST
COOKER
ROOM/AREA
SHAVER
OUTLET
OUTLET
W/UNIT
TP+N+E
POINT
REMARKS
CHAN
HOOD
BELL
D.SO
D/W
ISOL
13A
W/M
FCU
LTG
W/H
15A
32A
IND
H/D
R Y B
AC
1 R1 20 4.0 4.0 KITCHEN 1 1500.00 1500.00
SEC-1 40A,
KITCHEN (W/M)
4P 30mA
LPG SENSOR
4P 30mA
14 Y5 SPACE
15 B5 10 2.5 2.5 DINING & SITTING AREA 7 2 1 50/100 650.00
16 R6 10 SPARE 200.00 200.00
17 Y6 10 2.5 2.5 WC 2 50/100 100.00
18 B6 10 2.5 2.5 BED ROOM-1 & BATH 7 1 1 50/100 550.00
19 R7 1220.00
SEC-4
100m
40A,
UVR+TIMER+
4P
CONTROL
21 B7 1220.00
22 R8 20 4.0 4.0 FCU-1F.10.1 - WC 1 470 470.00
SEC-5 40A,
4P 100mA
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-FF10 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
SIZE mm2
SIZE mm2
INCOMER
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXHAUST
COOKER
ROOM/AREA
SHAVER
OUTLET
OUTLET
W/UNIT
TP+N+E
POINT
REMARKS
CHAN
HOOD
D.SO
BELL
D/W
ISOL
13A
W/M
FCU
LTG
W/H
15A
32A
H/D
IND
R Y B
AC
1 R1 20 4.0 4.0 CORRIDOR 1 200 / 400 400.00
SEC-1 40A,
30mA
4P
17 Y6 10 2.5 2.5 BED ROOM & MASTER BED ROOM 5 3 1 50/100 650.00
18 B6 10 2.5 2.5 KITCHEN 2 1 50/100 200.00
19 R7 10 2.5 2.5 CORRIDOR 11 1 1 50/100 750.00
20 Y7 SPACE
21 B7 SPACE
22 R8 1456.67
SEC-5
100m
40A,
UVR+TIMER+
4P
CONTROL
24 B8 1456.67
25 R9 20 4.0 4.0 FCU-1F.11.1 -WC 1 530 530.00
SEC-6 40A,
4P 100mA
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-FF11 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
*Armored cable to be used for all external services
PROJECT: COMMERCIAL & RESIDENTIAL BUILDING
DB No: DB-FF12 LOAD DISTRIBUTION SCHEDULE (3-PHASE) LOCATION: FIRST FLOOR FLAT
Fed From: MCB RATING SMDB-FF2
CONNECTED LOAD / POINTS LOAD PER CIRCUIT WATT
RATING OF
RATING OF
ECC WIRE
CCT WIRE
SIZE mm2
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A D.SO
13A SSO
EXHAUST
COOKER
ROOM/AREA
SHAVER
OUTLET
OUTLET
TP+N+E
W/UNIT
POINT
REMARKS
CHAN
HOOD
BELL
D/W
ISOL
W/M
W/H
LTG
15A
32A
H/D
IND
AC
R Y B
30mA
40A,
4P
17 Y6 10 2.5 2.5 BED ROOM & MASTER BED ROOM 7 3 1 50/100 750.00
18 B6 10 2.5 2.5 KITCHEN 2 1 50/100 200.00
19 R7 10 2.5 2.5 CORRIDOR 8 1 50/100 500.00
20 Y7 SPACE
21 B7 SPACE
22 R8 1220.00
SEC-5
100m
40A,
UVR+TIMER+
4P
CONTROL
24 B8 1220.00
25 R9 32 6.0 6.0 CU-1F.12.2 1 2740 2740.00
SEC-6 40A,
4P 100mA
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-FF12 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
*Armored cable to be used for all external services
PROJECT: COMMERCIAL & RESIDENTIAL BUILDING
DB No: DB-FF13 LOAD DISTRIBUTION SCHEDULE (3-PHASE) LOCATION: FIRST FLOOR FLAT
Fed From: MCB RATING SMDB-FF2
CONNECTED LOAD / POINTS LOAD PER CIRCUIT WATT
RATING OF
RATING OF
ECC WIRE
CCT WIRE
SIZE mm2
SIZE mm2
INCOMER
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXHAUST
COOKER
ROOM/AREA
SHAVER
OUTLET
OUTLET
TP+N+E
W/UNIT
POINT
REMARKS
CHAN
HOOD
D.SO
BELL
D/W
ISOL
13A
W/M
FCU
LTG
W/H
15A
32A
H/D
IND
R Y B
AC
1 R1 20 4.0 4.0 CORRIDOR 1 200 / 400 400.00
SEC-1 40A,
30mA
4P
17 Y6 SPACE
18 B6 10 2.5 2.5 KITCHEN 2 1 50/100 200.00
19 R7 10 2.5 2.5 CORRIDOR 8 1 50/100 500.00
20 Y7 SPACE
21 B7 10 2.5 2.5 BED ROOM & MASTER BED ROOM 7 3 1 50/100 750.00
22 R8 1220.00
SEC-6 SEC-5
100m 100m
40A, 40A,
UVR+TIMER+C
4P
ONTROL
24 B8 1220.00
25 R9 1033.33
UVR+TIMER+C
4P
ONTROL
27 B9 1033.33
28 R10 20 SPARE 250 250.00
SEC-7 40A,
4P 100mA
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-FF13 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
*Armored cable to be used for all external services
PROJECT: COMMERCIAL & RESIDENTIAL BUILDING
DB No: DB-FF14 LOAD DISTRIBUTION SCHEDULE (3-PHASE) LOCATION: FIRST FLOOR FLAT
Fed From: SMDB-FF2
MCB RATING
RATING OF
ECC WIRE
CCT WIRE
SIZE mm2
SIZE mm2
INCOMER
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXTRACT
COOKER
ROOM/AREA
SHAVER
OUTLET
OUTLET
TP+N+E
W/UNIT
POINT
REMARKS
CHAN
D.SO
BELL
D/W
ISOL
13A
W/M
FCU
FAN
LTG
W/H
15A
32A
H/D
IND
R Y B
AC
1 R1 20 4.0 4.0 KITCHEN D/W 1 1500.00 1500.00
SEC-1 40A,
3 B1 32 4.0 4.0 DINING & SITTING AREA 3 1 200 / 400 1000.00 RING
4 R2 SPACE
5 Y2 20 4.0 4.0 KITCHEN 1 1500.00 1500.00
6 B2 20 4.0 4.0 CORRIDOR (ONU) 1 200 / 400 400.00
7 R3 32 4.0 4.0 KITCHEN 1 3 200 / 400 1400.00 RING
SEC-2 40A,
9 B3 SPACE
40A TPN ISOLATOR
100m
40A,
UVR+TIMER+
4P
CONTROL
15 B5 1033.33
16 R6 10 2.5 2.5 KITCHEN 2 1 50/100 200.00
SEC-4 40A,
4P 100mA
17 Y6 SPACE
18 B6 10 2.5 2.5 DINING & SITTING AREA 7 2 50/100 550.00
19 R7 10 SPARE 300.00 300.00
20 Y7 SPACE
21 B7 10 2.5 2.5 BED ROOM-1 7 1 1 1 50/100 650.00
22 R8 20 4.0 4.0 FCU-1F.14.1 -WC 1 390 390.00
SEC-5 40A,
4P 100mA
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-FF14 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
SIZE mm2
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A D.SO
13A SSO
EXHAUST
COOKER
ROOM/AREA
SHAVER
OUTLET
OUTLET
TP+N+E
W/UNIT
POINT
REMARKS
CHAN
HOOD
BELL
D/W
ISOL
W/M
W/H
LTG
15A
32A
H/D
IND
AC
R Y B
30mA
40A,
4P
17 Y6 SPACE
18 B6 10 2.5 2.5 KITCHEN 2 1 50/100 200.00
19 R7 10 2.5 2.5 CORRIDOR 8 1 50/100 500.00
20 Y7 SPACE
21 B7 10 2.5 2.5 BED ROOM & MASTER BED ROOM 7 3 1 50/100 750.00
22 R8 1220.00
SEC-6 SEC-5
100m 100m
40A, 40A,
UVR+TIMER+
4P
CONTROL
24 B8 1220.00
25 R9 1033.33
UVR+TIMER+
4P
CONTROL
27 B9 1033.33
28 R10 20 SPARE 300 300.00
SEC-7 40A,
4P 100mA
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-FF15 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
*Armored cable to be used for all external services
PROJECT: COMMERCIAL & RESIDENTIAL BUILDING
DB No: DB-FF16 LOAD DISTRIBUTION SCHEDULE (3-PHASE) LOCATION: FIRST FLOOR FLAT
Fed From: MCB RATING SMDB-FF2
CONNECTED LOAD / POINTS LOAD PER CIRCUIT WATT
RATING OF
RATING OF
ECC WIRE
CCT WIRE
SIZE mm2
SIZE mm2
INCOMER
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXHAUST
COOKER
ROOM/AREA
SHAVER
OUTLET
OUTLET
TP+N+E
W/UNIT
POINT
REMARKS
CHAN
HOOD
D.SO
BELL
D/W
ISOL
13A
W/M
FCU
LTG
W/H
15A
32A
H/D
IND
R Y B
AC
1 R1 20 4.0 4.0 CORRIDOR 1 200 / 400 400.00
SEC-1 40A,
30mA
4P
17 Y6 SPACE
18 B6 10 2.5 2.5 KITCHEN 2 1 50/100 200.00
19 R7 10 2.5 2.5 CORRIDOR 8 1 50/100 500.00
20 Y7 SPACE
21 B7 10 2.5 2.5 BED ROOM & MASTER BED ROOM 7 3 1 50/100 650.00
22 R8 1220.00
SEC-6 SEC-5
100m 100m
40A, 40A,
UVR+TIMER+CO
4P
NTROL
24 B8 1220.00
25 R9 1033.33
UVR+TIMER+CO
4P
NTROL
27 B9 1033.33
28 R10 20 SPARE 300 300.00
SEC-7 40A,
4P 100mA
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-FF16 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
*Armored cable to be used for all external services
PROJECT: COMMERCIAL & RESIDENTIAL BUILDING
DB No: DB-FF17 LOAD DISTRIBUTION SCHEDULE (3-PHASE) LOCATION:FIRST FLOOR FLAT
Fed From: MCB RATING SMDB-FF2
CONNECTED LOAD / POINTS LOAD PER CIRCUIT WATT
RATING OF
RATING OF
ECC WIRE
CCT WIRE
SIZE mm2
SIZE mm2
INCOMER
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXHAUST
COOKER
ROOM/AREA
SHAVER
OUTLET
OUTLET
TP+N+E
W/UNIT
POINT
REMARKS
CHAN
HOOD
D.SO
BELL
FCU
D/W
ISOL
13A
W/M
LTG
W/H
15A
32A
H/D
IND
R Y B
AC
1 R1 20 4.0 4.0 CORRIDOR 1 200 / 400 400.00
SEC-1 40A,
30mA
4P
17 Y6 10 2.5 2.5 BED ROOM & MASTER BED ROOM 8 3 1 50/100 800.00
18 B6 10 2.5 2.5 KITCHEN 2 1 50/100 200.00
19 R7 10 2.5 2.5 CORRIDOR 10 1 1 50/100 700.00
20 Y7 SPACE
21 B7 SPACE
22 R8 1220.00
SEC-6 SEC-5
100m 100m
40A, 40A,
UVR+TIMER+
4P
CONTROL
24 B8 1220.00
25 R9 1033.33
UVR+TIMER+
4P
CONTROL
27 B9 1033.33
28 R10 20 SPARE 300 300.00
SEC-7 40A,
4P 100mA
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-FF17 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
*Armored cable to be used for all external services
PROJECT: COMMERCIAL & RESIDENTIAL BUILDING
DB No: DB-FF18 LOAD DISTRIBUTION SCHEDULE (3-PHASE) LOCATION: FIRST FLOOR FLAT
Fed From: SMDB-FF2
MCB RATING
RATING OF
ECC WIRE
CCT WIRE
SIZE mm2
SIZE mm2
INCOMER
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXHAUST
COOKER
ROOM/AREA
SHAVER
OUTLET
OUTLET
TP+N+E
W/UNIT
POINT
REMARKS
CHAN
HOOD
D.SO
BELL
D/W
ISOL
13A
W/M
FCU
LTG
W/H
15A
32A
H/D
IND
R Y B
AC
1 R1 20 4.0 4.0 KITCHEN 1 1500.00 1500.00
SEC-1 40A,
3 B1 32 4.0 4.0 DINING & SITTING AREA 3 1 200 / 400 1000.00 RING
4 R2 20 4.0 4.0 KITCHEN 1 1500.00 1500.00
5 Y2 20 4.0 4.0 CORRIDOR 1 1 200 / 400 600.00
6 B2 20 4.0 4.0 CORRIDOR (ONU) 1 200 / 400 400.00
7 R3 20 SPARE 300 300.00
SEC-2 40A,
14 Y5 SPACE
15 B5 10 2.5 2.5 DINING & SITTING AREA 6 2 1 50/100 600.00
16 R6 10 SPARE 300.00 300.00
17 Y6 10 2.5 2.5 WC 2 50/100 200.00
18 B6 10 2.5 2.5 BED ROOM-1 & BATH 5 1 1 50/100 450.00
19 R7 20 4.0 4.0 FCU-1F.18.2 -BATH 1 190 190.00
SEC-4
100m
40A,
4P
UVR+TIMER+
4P 100mA
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-FF18 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
SIZE mm2
SIZE mm2
INCOMER
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXHAUST
COOKER
ROOM/AREA
SHAVER
OUTLET
OUTLET
TP+N+E
W/UNIT
POINT
REMARKS
CHAN
HOOD
D.SO
BELL
D/W
ISOL
13A
W/M
FCU
LTG
W/H
15A
32A
H/D
IND
R Y B
AC
1 R1 20 4.0 4.0 KITCHEN 1 1500.00 1500.00
SEC-1 40A,
3 B1 32 4.0 4.0 DINING & SITTING AREA 4 1 200 / 400 1200.00 RING
4 R2 20 4.0 4.0 KITCHEN 1 1500.00 1500.00
5 Y2 20 4.0 4.0 LPG SENSOR 100 100.00
6 B2 SPACE
7 R3 20 SPARE 250.00 250.00
SEC-2 40A,
100m
40A,
4P
20 Y7 SPACE
A
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-FF19 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
SIZE mm2
SIZE mm2
INCOMER
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
SHAVER
OUTLET
EXHAUST
COOKER
ROOM/AREA
OUTLET
TP+N+E
W/UNIT
POINT
REMARKS
CHAN
HOOD
D.SO
BELL
D/W
ISOL
13A
W/M
FCU
LTG
W/H
15A
32A
H/D
IND
R Y B
AC
1 R1 20 4.0 4.0 KITCHEN 1 1500.00 1500.00
SEC-1 40A,
3 B1 32 4.0 4.0 DINING & SITTING AREA 4 1 200 / 400 1200.00 RING
4 R2 20 4.0 4.0 KITCHEN 1 1500.00 1500.00
5 Y2 20 4.0 4.0 LPG SENSOR 100 100.00
6 B2 SPACE
7 R3 20 SPARE 200.00 200.00
SEC-2 40A,
100m
40A,
4P
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-FF20 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE WATT
SIZE mm2
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
13A TSSO
EXTRACT
OTHER
ROOM/AREA
OUTLET
TP+N+E
W/UNIT
15A S/O
REMARKS
CHAN
FLEX
1SOL
SH/O
W/M
FCU
FAN
W/H
LTG
32A
H/D
IND
R Y B
12 B4 SPACE 0.00
13 R5 SPACE 0.00
SEC-3 40A,
4P 100mA
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-TS1 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
WATT
SIZE mm2
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXTRACT
OTHER
13A DSO
ROOM/AREA
OUTLET
TP+N+E
W/UNIT
15A S/O
REMARKS
CHAN
FLEX
1SOL
SH/O
W/M
FCU
FAN
W/H
LTG
32A
H/D
IND
R Y B
20 Y7 32 4.0 4.0 2nd FLOR TELEPHONE & ELECTRICL ROOM 3 400.00 1200.00 RING
4P 30mA
21 B7 32 4.0 4.0 3rd FLOR TELEPHONE & ELECTRICL ROOM 3 400.00 1200.00 RING
22 R8 20 4.0 4.0 CDT RACK FIRST FLOOR TEL ROOM 1 1500.00 1500.00
23 Y8 20 SPARE 300.00 600.00
24 B8 SPARE 300.00 600.00
Total connected Loads (W) 4750.00 3850.00 3850.00 12450.00
CABLE SIZE 4C 10mm2 XLPE/SWA/PVC + 1C 10mm2 Y/G ECC TOTAL CONNECTED: 12450.00
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-TS1 REV.A
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
SIZE mm2
SIZE mm2
INCOMER
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXHAUST
COOKER
ROOM/AREA
SHAVER
OUTLET
OUTLET
W/UNIT
TP+N+E
POINT
REMARKS
CHAN
HOOD
BELL
D.SO
D/W
ISOL
13A
W/M
FCU
LTG
W/H
15A
32A
IND
H/D
R Y B
AC
1 R1 20 4.0 4.0 KITCHEN (D/W) 1 1500.00 1500.00
SEC-1 40A,
CORRIDOR (ONU)
4P 30mA
BATH
4P 30mA
14 Y5 SPACE
15 B5 10 2.5 2.5 BED ROOM-1 3 2 1 50/100 450.00
16 R6 SPACE
17 Y6 10 2.5 2.5 WC 2 50.00 100.00
18 B6 10 2.5 2.5 DINING & SITTING AREA 9 2 1 50/100 650.00
19 R7 1456.67
SEC-4
100m
40A,
UVR+TIMER+CO
4P
NTROL
21 B7 1456.67
22 R8 20 4.0 4.0 FCU-RF.01.1 530 530.00
SEC-5 40A,
4P 100mA
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-RF1 REV.0
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
WATT
SIZE mm2
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A D.SO
13A SSO
OOUTLET
EXHAUST
COOKER
ROOM/AREA
SHAVER
OUTLET
TP+N+E
W/UNIT
POINT
REMARKS
CHAN
HOOD
BELL
ISOL
D /W
W/M
W/H
LTG
15A
32A
H/D
IND
AC
R Y B
30mA
40A,
4P
14 Y5 SPACE
15 B5 SPACE
16 R6 10 2.5 2.5 SITTING AREA DINING 2 2 50/100 300.00
SEC-4 40A,
4P 100mA
17 Y6 10 2.5 2.5 BED ROOM & MASTER BED ROOM 6 2 1 50/100 600.00
18 B6 10 2.5 2.5 KITCHEN 2 1 50/100 200.00
19 R7 10 2.5 2.5 CORRIDOR 8 1 50/100 500.00
20 Y7 10 2.5 2.5 BATH 2 1 50/100 200.00
21 B7 SPACE
22 R8 1456.67
SEC-6 SEC-5
100m 100m
40A, 40A,
UVR+TIMER+
4P
CONTROL
24 B8 1456.67
25 R9 1220.00
UVR+TIMER+
4P
CONTROL
27 B9 1220.00
28 R10 SPACE
SEC-7 40A,
4P 100mA
RATING OF
ECC WIRE
CCT WIRE
SIZE mm2 WATT
INCOMER
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A D.SO
13A SSO
EXHAUST
COOKER
ROOM/AREA
SHAVER
OUTLET
OUTLET
TP+N+E
W/UNIT
POINT
REMARKS
CHAN
HOOD
BELL
D/W
ISOL
W/M
FCU
W/H
LTG
15A
32A
H/D
IND
AC
R Y B
30mA
40A,
4P
14 Y5 SPACE
15 B5 SPACE
16 R6 10 2.5 2.5 SITTING AREA DINING 4 2 1 50/100 500.00
SEC-4 40A,
4P 100mA
17 Y6 10 2.5 2.5 BED ROOM & MASTER BED ROOM 6 2 1 50/100 600.00
18 B6 10 2.5 2.5 KITCHEN 2 1 50/100 200.00
19 R7 10 2.5 2.5 CORRIDOR 8 1 50/100 600.00
20 Y7 SPACE
21 B7 SPACE
22 R8 1456.67
SEC-5
100m
40A,
UVR+TIMER+
4P
CONTROL
24 B8 1456.67
25 R9 1220.00
SEC-6 40A,
UVR+TIMER+
4P 100mA
RATING OF
ECC WIRE
CCT WIRE
SIZE mm2
SIZE mm2
INCOMER
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXHAUST
COOKER
ROOM/AREA
SHAVER
OUTLET
OUTLET
W/UNIT
TP+N+E
POINT
REMARKS
CHAN
HOOD
D.SO
BELL
D/W
ISOL
13A
W/M
FCU
LTG
W/H
15A
32A
H/D
IND
R Y B
AC
1 R1 20 4.0 4.0 KITCHEN 1 1500.00 1500.00
SEC-1 40A,
3 B1 32 4.0 4.0 DINING & SITTING AREA 3 1 200 / 400 1000.00 RING
4 R2 20 4.0 4.0 KITCHEN 1 1500.00 1500.00
5 Y2 SPACE
6 B2 20 4.0 4.0 CORRIDOR (ONU) 1 200 / 400 400.00
7 R3 32 4.0 4.0 KITCHEN 1 3 200 / 400 1400.00 RING
SEC-2 40A,
40A TPN ISOLATOR
8 Y3 SPACE
4P 30mA
100m 100m
40A, 40A,
UVR+TIMER+CO
4P
NTROL
21 B7 1456.67
22 R8 32 6.0 6.0 CU-RF.04.2 1 2740 2740.00
UVR+TIMER+CO
4P
NTROL
24 B8 20 4.0 4.0 FCU-RF.04.2 1 250 250.00
Total connected Loads (W) 6586.67 7396.67 5106.67 19090.00
6.59 7.40 5.11 19.09
CABLE SIZE 4C 10mm2 XLPE/SWA/PVC + 1C 10mm2 Y/G ECC TOTAL CONNECTED: 19090.00
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-RF4 REV.0
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE WATT
SIZE mm2
SIZE mm2
INCOMER
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXHAUST
COOKER
ROOM/AREA
SHAVER
OUTLET
OUTLET
W/UNIT
TP+N+E
POINT
REMARKS
CHAN
HOOD
D.SO
BELL
D/W
ISOL
13A
W/M
FCU
LTG
W/H
15A
32A
H/D
IND
R Y B
AC
1 R1 20 4.0 4.0 CORRIDOR(ONU) 1 200 / 400 400.00
SEC-1 40A,
30mA
4P
14 Y5 SPACE
15 B5 SPACE
16 R6 10 2.5 2.5 SITTING AREA DINING 6 2 1 50/100 500.00
SEC-4 40A,
4P 100mA
17 Y6 10 2.5 2.5 BED ROOM & MASTER BED ROOM 6 2 1 50/100 500.00
18 B6 10 2.5 2.5 KITCHEN 2 1 50/100 200.00
19 R7 10 2.5 2.5 CORRIDOR 8 1 50/100 500.00
20 Y7 SPACE
21 B7 SPACE
22 R8 1456.67
SEC-7 SEC-6 SEC-5
UVR+TIMER+CO
4P
NTROL
24 B8 1456.67
25 R9 1220.00
UVR+TIMER+CO
4P
NTROL
27 B9 1220.00
28 R10 20 4.0 4.0 FCU-RF.05.1 530 530.00
4P
29 Y10 SPACE
A
RATING OF
ECC WIRE
CCT WIRE
WATT
SIZE mm2
SIZE mm2
INCOMER
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXHAUST
COOKER
ROOM/AREA
SHAVER
OUTLET
OUTLET
TP+N+E
W/UNIT
POINT
REMARKS
CHAN
HOOD
D.SO
BELL
D/W
ISOL
13A
W/M
FCU
LTG
W/H
15A
32A
H/D
IND
R Y B
AC
1 R1 20 4.0 4.0 CORRIDOR(ONU) 1 200 / 400 400.00
SEC-1 40A,
30mA
4P
14 Y5 SPACE
15 B5 SPACE
16 R6 10 2.5 2.5 SITTING AREA DINING 4 2 1 50/100 500.00
SEC-4 40A,
4P 100mA
17 Y6 10 2.5 2.5 BED ROOM & MASTER BED ROOM 6 2 1 50/100 500.00
18 B6 10 2.5 2.5 KITCHEN 2 1 50/100 200.00
19 R7 10 2.5 2.5 CORRIDOR 8 1 50/100 500.00
20 Y7 SPACE
21 B7 SPACE
22 R8 1456.67
SEC-7 SEC-6 SEC-5
UVR+TIMER+C
4P
ONTROL
24 B8 1456.67
25 R9 1220.00
UVR+TIMER+C
4P
ONTROL
27 B9 1220.00
28 R10 SPACE
4P
RATING OF
ECC WIRE
CCT WIRE
SIZE mm2
SIZE mm2
INCOMER
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXHAUST
COOKER
ROOM/AREA
SHAVER
OUTLET
OUTLET
W/UNIT
TP+N+E
POINT
REMARKS
CHAN
HOOD
D.SO
BELL
D/W
ISOL
13A
W/M
FCU
LTG
W/H
15A
32A
H/D
IND
R Y B
AC
1 R1 20 4.0 4.0 KITCHEN 1 1500.00 1500.00
SEC-1 40A,
3 B1 32 4.0 4.0 DINING & SITTING AREA 3 1 200 / 400 1000.00 RING
4 R2 20 4.0 4.0 KITCHEN 1 1500.00 1500.00
5 Y2 20 4.0 4.0 STORE 1 1 200 / 400 600.00
6 B2 20 4.0 4.0 CORRIDOR (ONU) 1 200 / 400 400.00
7 R3 32 4.0 4.0 KITCHEN 1 3 200 / 400 1400.00 RING
SEC-2 40A,
40A TPN ISOLATOR
8 Y3 SPACE
4P 30mA
14 Y5 SPACE
15 B5 10 2.5 2.5 DINING & SITTING AREA 11 2 1 50/100 850.00
16 R6 SPACE
17 Y6 SPACE
18 B6 10 2.5 2.5 BED ROOM-1 4 1 1 50/100 400.00
19 R7 1456.67
SEC-5 SEC-4
100m 100m
40A, 40A,
UVR+TIMER+CO
4P
NTROL
21 B7 1456.67
22 R8 20 4.0 4.0 FCU-RF.07.1 1 530 530.00
4P
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-RF7 REV.0
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
SIZE mm2 WATT
SIZE mm2
INCOMER
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXHAUST
COOKER
ROOM/AREA
SHAVER
OUTLET
OUTLET
TP+N+E
W/UNIT
POINT
REMARKS
CHAN
HOOD
D.SO
BELL
D/W
ISOL
13A
W/M
FCU
LTG
W/H
15A
32A
H/D
IND
R Y B
AC
1 R1 20 4.0 4.0 CORRIDOR(ONU) 1 400.00 400.00
SEC-1 40A,
30mA
4P
14 Y5 SPACE
15 B5 SPACE
16 R6 10 2.5 2.5 SITTING AREA DINING 3 2 50/100 350.00
SEC-4 40A,
4P 100mA
17 Y6 10 2.5 2.5 BED ROOM & MASTER BED ROOM 9 3 2 50/100 950.00
18 B6 10 2.5 2.5 KITCHEN 2 1 50/100 200.00
19 R7 10 2.5 2.5 CORRIDOR 6 1 50/100 400.00
20 Y7 SPACE
21 B7 SPACE
22 R8 1456.67
SEC-7 SEC-6 SEC-5
UVR+TIMER+CO
4P
NTROL
24 B8 1456.67
25 R9 1220.00
UVR+TIMER+CO
4P
NTROL
27 B9 1220.00
28 R10 20 4.0 4.0 FCU-RF.08.1 1 530 530.00
4P
29 Y10 SPACE
A
RATING OF
ECC WIRE
CCT WIRE
SIZE mm2
SIZE mm2
INCOMER
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXHAUST
COOKER
ROOM/AREA
SHAVER
OUTLET
OUTLET
W/UNIT
TP+N+E
POINT
REMARKS
CHAN
HOOD
D.SO
BELL
D/W
ISOL
13A
W/M
FCU
LTG
W/H
15A
32A
H/D
IND
R Y B
AC
1 R1 20 4.0 4.0 KITCHEN 1 1500.00 1500.00
SEC-1 40A,
3 B1 32 4.0 4.0 DINING & SITTING AREA 3 1 200 / 400 1000.00 RING
4 R2 20 4.0 4.0 KITCHEN 1 1500.00 1500.00
5 Y2 20 4.0 4.0 STORE 1 1 200 / 400 600.00
6 B2 20 4.0 4.0 CORRIDOR (ONU) 1 200 / 400 400.00
7 R3 SPACE
SEC-2 40A,
40A TPN ISOLATOR
14 Y5 SPACE
15 B5 10 2.5 2.5 DINING & SITTING AREA 5 2 1 50/100 550.00
16 R6 SPACE
17 Y6 10 2.5 2.5 WC 2 50.00 100.00
18 B6 10 2.5 2.5 BED ROOM-1 6 1 1 50/100 500.00
19 R7 1456.67
SEC-5 SEC-4
100m 100m
40A, 40A,
UVR+TIMER+CO
4P
NTROL
21 B7 1456.67
22 R8 32 6.0 6.0 CU-RF.09.2 1 2740 2740.00
4P
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-RF9 REV.0
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
RATING OF
ECC WIRE
CCT WIRE
SIZE mm2
SIZE mm2
INCOMER
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXHAUST
COOKER
ROOM/AREA
SHAVER
OUTLET
OUTLET
W/UNIT
TP+N+E
POINT
REMARKS
CHAN
HOOD
D.SO
BELL
D/W
ISOL
13A
W/M
FCU
LTG
W/H
15A
32A
H/D
IND
R Y B
AC
1 R1 20 4.0 4.0 KITCHEN 1 1500.00 1500.00
SEC-1 40A,
3 B1 32 4.0 4.0 DINING & SITTING AREA 3 1 200 / 400 1000.00 RING
4 R2 20 4.0 4.0 KITCHEN 1 1500.00 1500.00
5 Y2 20 4.0 4.0 STORE 2 1 200 / 400 800.00
6 B2 20 4.0 4.0 CORRIDOR (ONU) 1 200 / 400 400.00
7 R3 32 4.0 4.0 KITCHEN 1 3 200 / 400 1400.00 RING
SEC-2 40A,
40A TPN ISOLATOR
8 Y3 SPACE
4P 30mA
14 Y5 SPACE
15 B5 10 2.5 2.5 DINING & SITTING AREA 5 2 50/100 450.00
16 R6 SPACE
17 Y6 SPACE
18 B6 10 2.5 2.5 BED ROOM-1 9 1 1 1 50/100 750.00
19 R7 1456.67
SEC-5 SEC-4
100m 100m
40A, 40A,
UVR+TIMER+CO
4P
NTROL
21 B7 1456.67
22 R8 20 4.0 4.0 FCU-RF.10.1 1 530.00 530.00
4P
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-RF10 REV.0
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
MCB RATING
CONNECTED LOAD / POINTS
RATING OF
RATING OF
ECC WIRE
CCT WIRE
WATT
INCOMER
SIZE mm2
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
13A TSSO
EXTRACT
OTHER
ROOM/AREA
OUTLET
W/UNIT
TP+N+E
15A S/O
REMARKS
CHAN
1SOL
FLEX
SH/O
W/M
FCU
FAN
LTG
W/H
32A
H/D
IND
R Y B
4P 30mA
30mA
40A,
4P
30mA
40A,
CLEANING CRADLE
33 B11 1000.00
34 R12 SPACE
35 Y12 SPACE
36 B12 20 SPARE 300.00 300.00
Total connected Loads (W) 5700.00 5900.00 5450.00 17050.00
CABLE SIZE 4C 10mm2 XLPE/SWA/PVC + 1C 10mm2 Y/G ECC TOTAL CONNECTED: 17.05
PROJECT: COMMERCIAL AND RESIDENTIAL BUILDING (MERAAS PLOT AT AL SATWA) DB-RF REV.0
Ex. FAN = Exhaust Fan, SH.SO = Shaver Socket - outlet, W/H = Water Heater, H/D = Hand Dryer, FCU = FAN COOLING UNIT,
*Armored cable to be used for all external services
PROJECT: COMMERCIAL & RESIDENTIAL BUILDING
DB No: EDB-RF LOAD DISTRIBUTION SCHEDULE (3-PHASE) LOCATION: ROOF FLOOR ELEC ROOM
Fed From: ESMDB-RF
LOAD PER CIRCUIT
MCB RATING
CONNECTED LOAD / POINTS
RATING OF
RATING OF
ECC WIRE
CCT WIRE
WATT
INCOMER
SIZE mm2
SIZE mm2
IN AMPS
CIR. NO
SL.NO.
ELCB
13A SSO
EXTRACT
13A D.SO
OTHER
ROOM/AREA
OUTLET
W/UNIT
TP+N+E
15A S/O
REMARKS
CHAN
1SOL
FLEX
SH/O
W/M
FCU
FAN
LTG
W/H
32A
H/D
IND
R Y B
8 Y3 20 SPARE 200.00
4P 30mA
LOAD
INCOMER TP 400 35 FIRE RATED CABLE 4C-300 1C-150 68.40 67.15 67.04 0
OUTGOING:
XLPE/SWA/FIRE
ESMDB-RF TP 100 35 4C-35 1C-16 14.63 13.88 14.43 42.95
RATED CABLE
XLPE/SWA/FIRE
LIFT-1 TP 40 35 4C-10 1C-10 3.67 3.67 3.67 11.00 300mA ELCB
RATED CABLE
XLPE/SWA/FIRE
LIFT-2 TP 40 35 4C-10 1C-10 3.67 3.67 3.67 11.00 300mA ELCB
RATED CABLE
XLPE/SWA/FIRE
LIFT-3 TP 40 35 4C-10 1C-10 3.67 3.67 3.67 11.00 300mA ELCB
RATED CABLE
XLPE/SWA/FIRE
ESMDB-BF TP 200 35 4C-95 1C-50 33.07 32.77 33.06 98.90
RATED CABLE
MAIN TEL ROOM TP 63 35 XLPE/SWA/PVC 4C-16 1C-16 1.00 1.00 1.00 3.00 100mA ELCB
MAIN TEL ROOM TP 63 35 XLPE/SWA/PVC 4C-16 1C-16 1.00 1.00 1.00 3.00 100mA ELCB