L-L 100-415V AC, L-N 58-240V AC
L1
L2 Setting Ranges Brief Overview
L3
Undervoltage : Off, 1% – 25% The Data LED showing value. Press “UP” or
N
L1 L2 L3 N
(OPTIONAL)
Time delay for undervoltage : 0.1s – 30s “DOWN” to scroll through the parameters as
Overvoltage : Off, 1% – 20% shown in Figure 2 and 3 (depends on L-L or L-N
R1 R2 Time delay for overvoltage : 0.1s – 30s setting).
AUX
Unbalance : Off, 3% – 20% a
h
NC NO COM NC NO COM Time delay for unbalance : 0.5s – 30s b
Phase loss : Fixed time <0.5s
Figure 5 Phase sequence : Fixed time <0.5s g
Start time delay : 0s – 999s c U 12
Neutral connection is optional when Phase
option is set to L-L. Neutral connection is d
required when Phase option is set to L-N. (refer Auxiliary Supply (AUX)
to Setting b - Phase) f
Model MU350-415V : 380V(-25%) - 415V(+20%) AC
Model MU350-220V : 220V(-25%) - 240V(+20%) AC e U 23
Model MU350-110V : 100V(-25%) - 120V(+20%) AC
Supply frequency : 45Hz to 65Hz
Maximum power consumption : 3VA Figure 1: Front panel overview
6. Case Dimensions
9 6 mm Measuring Input Symbols
a – Auxiliary power U 31
Line to line : 100 - 415(+20%) VAC
supply LED
Line to Neutral : 58 - 240(+20%) VAC
U<< - Undervoltage
b – Trip/Pickup LED
Contacts t<< - Undervoltage time
Contact arrangement : Change-over c – Up key delay Frequency
9 6 mm
2 3