HORIZONTAL SPLIT CASE FIRE PUMP SYSTEM
DIESEL ENGINE DRIVEN
1. Fuel Tank, Diesel Engine 7. Discharge Pressure Gauge 13. Jockey Pump Controller
2. Isolation Gate Valve (suction) 8. Enclosed Waste Cone with Sight Glasses 14. Jockey Pump
3. Compound Suction Gauge 9. Main Relief Valve 15. Isolation Valves
4. Automatic Air Release Valve 10. Low Suction Pressure Shutoff Valve 16. Ball Drip Valve
5. Diesel Engine Drive 11. Fire Pump Controller 17. Test Valve Manifold with Hose Valves,
6. Horizontal Split Case Fire Pump 12. System Check Valve Caps & Chains
Pump: Horizontal split case, double-suction, UL Listed, FM Approved, mounted on a common base with and flexibly
coupled to a diesel engine. Pump sized for rated capacity and head. Also must be capable of producing 150% rated flow
at not less than 65% rated head and not to exceed 140% rated head at a shutoff or no-flow condition.
Diesel Engine: UL Listed or FM Approved diesel engine adequately sized so as to not overload at any point on the pump
hydraulic curve. Consideration must be given and de-rates applied based on job site elevation and ambient temperature.
Engines must be specifically designed for fire protection service.
Coupling: Flexible type, sized to transmit the horsepower requirements of the pump. Coupling shall be furnished with an
OSHA-design coupling guard.
Base: Fabricated steel design base capable of adequately supporting the weight of the pump and driver. After pump has
been fully piped and accurately aligned with the engine, the base should be fully grouted into place.
Controller: Diesel engine controller starts the engine automatically on a loss of system pressure. System pressure is
monitored via a sensing line from the system side of the check valve. Controller can also be manually started. Controllers
are UL Listed and FM Approved specifically for fire pump service.
Standard Pump Accessories: Accessories furnished with the fire pump system include: suction and discharge gauges
and automatic air release valve. Other accessories commonly furnished as part of the fire pump package include: hose
valve manifold with hose valves, caps and chains, flowmeter, main relief valve and enclosed waste cone, ball drip valve,
eccentric suction reducer, concentric discharge increaser.
Standard Engine Accessories: Accessories furnished with the diesel engine include: engine starting batteries, battery
rack, battery cables, engine exhaust flexible connector and silencer.
Jockey Pump: Jockey pump keeps pressure in the system to prevent the main fire pump from operating to maintain
system pressure. Jockey pumps are generally a few gallons per minute sized to overcome small system leaks and
typically sized for 10 PSI greater than the rated pressure of the main fire pump. Jockey pumps are not required to be
UL Listed or FM Approved.
Jockey Pump Controller: Starts the jockey pump across the line by sensing the system pressure via a sensing line from
the system side of the check valve. This sensing line must be independent from the main fire pump controller sensing line.
Controller is sized per the jockey pump motor horsepower and voltage. Jockey pump controllers are UL Listed specifically
for this service.
HORIZONTAL SPLIT CASE FIRE PUMP SYSTEM
ELECTRIC MOTOR DRIVEN
Pump: Horizontal split case, double-suction, UL Listed, FM the application. Common types of controllers include:
Approved, mounted on a common base with and flexibly across-the-line, primary resistor, part-winding, wye-delta,
coupled to an electric motor. Pump sized for rated capacity auto-transformer, and soft start. Controllers are UL Listed
and head. Also must be capable of producing 150% rated and FM Approved specifically for fire pump service.
flow at not less than 65% rated head and not to exceed
140% rated head at a shutoff or no-flow condition. Standard Accessories: Accessories furnished with the
fire pump system include: suction and discharge gauges,
Electric Motor: UL Listed or FM Approved motor sized so casing relief valve and automatic air release valve. Other
as to not overload at any point on the pump hydraulic curve accessories commonly furnished as part of the fire pump
as per NFPA #20. Motors are open-drip proof type with a package include: hose valve manifold with hose valves,
1.15 service factor wound for the correct voltage. Motor caps and chains, flowmeter, main relief valve and enclosed
to be compatible with the type of controller (i.e., starting waste cone, ball drip valve, eccentric suction reducer,
characteristics). concentric discharge increaser.
Coupling: Flexible type, sized to transmit the horsepower Jockey Pump: Jockey pump keeps pressure in the system
requirements of the pump. Coupling shall be furnished with to prevent the main fire pump from operating to maintain
an OSHA-design coupling guard. system pressure. Jockey pumps are generally a few gallons
per minute sized to overcome small system leaks and
Base: Fabricated steel design base capable of adequately typically sized for 10 PSI greater than the rated pressure
supporting the weight of the pump and driver. After pump of the main fire pump. Jockey pumps are not required to be
has been fully piped and accurately aligned with the motor, UL Listed or FM Approved.
the base should be fully grouted into place.
Jockey Pump Controller: Starts the jockey pump across
Controller: Electric motor controller starts the motor the line by sensing the system pressure via a sensing line
automatically on a loss of system pressure. System from the system side of the check valve. This sensing line
pressure is monitored via a sensing line from the system must be independent from the main fire pump controller
side of the check valve. Controller can also be manually sensing line. Controller is sized per the jockey pump motor
started. The type of motor starting, and therefore the type horsepower and voltage. Jockey pump controllers are UL
of controller, varies depending upon the specifics of Listed specifically for this service.
APPROVED CONTROLLER STARTING METHODS
STARTING
STARTING
CURRENT
TORQUE
(% MOTOR TYPE
TYPE STARTING CHARACTERISTICS ADVANTAGES RESTRAINTS (% LOCKED
FULL LOAD TRANSITION
ROTOR
STARTING
TORQUE)
CURRENT)
Across-the-line Connects motor directly to power * Least expensive * High inrush current 600% 100% Not applicable
source. Full voltage applied to motor * Highest starting torque
when controller is actuated.
* Low maintenance
* Standard motor used
Primary When controller is actuated, a * Smooth starting * High power loss through resistors 300% 25% Closed
Resistance resistance is connected to each * Low shock to motor * Must dissipate heat
Reduced Voltage phase. Resistors are by-passed after
* Standard motor used * Low torque per ampere input
a time delay and motor then runs at
full voltage. * Medium relative cost
* Not recommended for transfer
switch applications
Part Winding Motor starts on one winding. After * Low relative cost * Not recommended for frequent 390% 42% Closed
a time delay, second winding is * Low starting torque starting
connected in parallel to the line. * Low starting torque
* Low maintenance
* Special motor required
Wye-Delta On controller activation, motor windings * Moderate to low relative cost * Medium starting torque 200% 33% Open
Open-Transition wye-connected for starting. After a time * Low motor stress * Special motor required for 200V
delay, automatically converts to delta
* Low starting current * Power line transients
connection for running, applying full
voltage to motor windings. Most often * Can affect other equipment
used with transfer switch/emergency sharing same power source.
generator applications.
Wye-Delta Same sequence as Open Transition. * Moderate to high relative cost * Medium starting torque 200% 33% Closed
Closed-Transition Connected to resistors in each phase * Low motor stress * Special motor may be required
during transition from wye to delta. for 200V
* Low starting current
* No line transients
Auto Starters supply reduced voltage * Good for heavy starting loads * High relative cost Closed
Transformer starting at motor terminals through use * Highest starting torque
Reduced Voltage of tapped, 3-phase autotransformer.
* Standard motor used
A timing relay causes transfer of motor
w/50% tap from reduced voltage start to line voltage * Low starting current 150% 25%
w/65% tap operation without disconnecting motor * Starting torque adjustable 252% 42%
w/80% tap from power source. 384% 64%
Soft Start/Stop Reduces inrush current to motor with * Low inrush current * High relative cost Adjustable Varies Closed
adjustable ramp time. Stop sequence * Adjustable ramp time 50% - 500%
reduces possibility of surges occurring
* Reduces system surges
in the system.
* Standard motor used
Long established as a leading fire pump manufacturer, Fairbanks Morse Pump offers a broad range of
horizontal split case, vertical in-line and vertical turbine designs over a wide range of rated capacities
and pressures…pumps for every fire pump application. Split case and vertical turbine pumps have
the option of being driven via either an electric motor or diesel engine, and are furnished as a
complete package with controller, jockey pump and its controller, as well as standard fire pump system
accessories.
Units are Underwriters Laboratories Listed and Factory Mutual Approved specifically for fire pump
service continually meeting their stringent inspection, testing and record-keeping standards. Split case
rated capacities range from 250 GPM through 5000 GPM, vertical in-line rated capacities range from
50 GPM through 750 GPM, and vertical turbine fire pumps cover 250 GPM through 4500 GPM, all with
a wide range of rated pressures.
The Fairbanks Morse Pump sales family includes highly qualified distributors and representatives well
versed in fire pump systems, who provide prompt and accurate quotations, submittals and acceptance
testing as required. These sales professionals stand ready to address and meet your fire pump needs,
and are backed by many years of factory knowledge and experience.
RATED RATED
CAPACITY HEAD
250 GPM 40 – 167 PSI
500 GPM 40 – 278 PSI
750 GPM 40 – 266 PSI
1000 GPM 40 – 244 PSI
1250 GPM 43 – 236 PSI
1500 GPM 40 – 228 PSI
2000 GPM 53 – 210 PSI
2500 GPM 50 – 213 PSI
3000 GPM 60 – 165 PSI
3500 GPM 94 – 151 PSI
4000 GPM 94 – 223 PSI
4500 GPM 90 – 223 PSI
5000 GPM 88 – 221 PSI
Pump Features:
Pump Features:
VERTICAL TURBINE
RATED RATED
CAPACITY HEAD
250 GPM PSI
500 GPM 100 – 370 PSI
750 GPM 99 – 361 PSI
1000 GPM 96 – 316 PSI
1500 GPM 98 – 320 PSI
2000 GPM 98 – 198 PSI
2500 GPM 100 – 187 PSI
3000 GPM 100 – 189 PSI
3500 GPM 101 – 180 PSI
4000 GPM 120 – 189 PSI
4500 GPM 120 – 181 PSI
Pump Features:
• Bronze impellers
• Cast iron bowl (multi-stage)
• Stainless steel bowl shaft
• Carbon steel open lineshaft
• Steel column pipe
• Cast iron or fabricated steel discharge heads
• Brass suction strainer
• Packed stuffing box
PACKAGED FIRE PUMP SYSTEMS
When the application calls for a completely packaged fire pump system, Fairbanks Morse Pump has the
capability to meet these requirements. Systems include the pump, driver, controller, jockey pump and
jockey pump controller all mounted on a common base. Controller is pre-wired to the driver,
sensing lines are pre-piped from the controllers to the system side of the check valve, and suction and
discharge piping is piped to the edge of the common base. Isolation valves, check valve, and test
header piping (and/or flowmeter piping) can be supplied as required. For diesel engine driven units, the
package would also include the mounting of the fuel tank, piping of fuel lines to the engine and
connection of batteries to the engine.
Should your requirements include the packaged fire pump system to include an enclosure, Fairbanks
Morse Pump can provide the protective structure to house the system. Packaged systems can be
designed for use with horizontal split case, vertical turbine or vertical in-line pump designs.
SUCTION DISCHARGE
AD R R A E E G
AX AW
B A
4 – H DIA
HOLES VIEW A–A
DISCHARGE E E SUCTION
AD R R A
AW G AX
B A
4 – H DIA
HOLES VIEW A–A
SUCTION
PUMP SIZE
POWER
SERIES
CASE
DISCH MODEL BORE A B D E G H O R S U V W X Z AA AB AC AD AW AX CP YY ZZ
2-1/2 2.5”1823BF 10B 3 2 8 10 8 3-1/2 3/4 5/8 16 4 4 1-1/8 2-7/8 13-1/2 9-3/4 4 2-1/8 1/4 1/8 9-1/2 – – 24 10
(203) (254) (203) (89) (19) (16) (406) (102) (102) (29) (73) (343) (248) (102) (54) (6) (3) (241) – – (610) (254)
3 3”1824F 10 4 2 8 10 9 3-1/2 3/4 5/8 16-1/4 4 4-1/2 1-1/8 2-7/8 13-1/2 10 4-1/2 2-1/8 1/4 1/8 9-1/2 – 1/2 24 11
(203) (254) (229) (89) (19) (16) (413) (102) (114) (29) (73) (343) (254) (114) (54) (6) (3) (241) – (13) (610) (279)
4 4”1823AF 11 5 3 10 12 10 4-1/4 7/8 3/4 18-3/8 5 5 1-3/8 3 14-1/2 11-1/4 5 2-3/8 3/8 3/16 9-1/2 – 1/2 26 12-3/4
-CF (254) (305) (254) (108) (22) (19) (467) (127) (127) (35) (76) (368) (286) (127) (60) (10) (5) (241) (13) (660) (324) `
4 4” 1823DF 11 5 3 10 12 10 4-1/4 7/8 3/4 18-3/8 5 5 1-3/8 3 14-1/2 12 5 2-3/8 3/8 3/16 9-1/2 --- 1/2 26 12-3/4
(254) (305) (254) (108) (22) (19) (467) (127) (127) (35) (76) (368) (305) (127) (60) (10) (5) (241) -- (13) (660) (324)
4 4” 1824F 15 5 3 10 12 11 4-1/4 7/8 3/4 21-1/8 5 5-1/2 1-3/8 3 14-1/2 13 5-1/2 2-3/8 3/8 3/16 9-1/2 – – 26 14
(254) (305) (279) (108) (22) (19) (537) (127) (140) (35) (76) (368) (330) (140) (60) (10) (5) (241) – – (660) (356)
5 5” 1822BF 11 6 4 10 12 11 4-1/4 7/8 3/4 19-3/4 5 5-1/2 1-1/2 3-1/2 16 11-1/4 5-1/2 2-7/8 3/8 3/16 11 – 3/4 28-1/2 13-1/4
-CF/-DF (254) (305) (279) (108) (22) (19) (502) (127) (140) (38) (89) (406) (286) (140) (73) (10) (5) (279) – (19) (724) (337)
5 5” 1823F 15 6 4 10 12 12-1/2 4-1/4 7/8 3/4 22-1/2 5 6-1/4 1-1/2 3-1/2 16 13-1/4 6-1/4 2-7/8 3/8 3/16 11 – – 28-1/2 15 1-1/4
(254) (305) (318) (108) (22) (19) (572) (127) (159) (38) (89) (406) (337) (159) (73) (10) (5) (279) – – (724) (381) (32)
5 5” 1824F 17 6 4 10 12 12-1/2 4-1/4 7/8 3/4 22-1/2 5 6-1/4 1-1/2 3-1/2 16 14 6-1/4 2-7/8 3/8 3/16 11 – – 28-1/2 15
(254) (305) (318) (108) (22) (19) (572) (127) (159) (38) (89) (406) (356) (159) (73) (10) (5) (279) – – (724) (381)
6 6” 1822F 11 8 4 10 12 12-1/2 4-1/4 7/8 3/4 21-7/8 5 6-1/4 1-1/2 3-1/2 16 11-3/4 6-1/4 2-7/8 3/8 3/16 11 – 1-1/4 28-1/2 14-1/2
(254) (305) (318) (108) (22) (19) (556) (127) (159) (38) (89) (406) (298) (159) (73) (10) (5) (279) – (32) (724) (368)
6 6” 1822HHF 11HH 8 4A 12 14-1/2 16-1/2 5 1-1/4 7/8 25-3/4 6 8-5/8 1-1/2 3-3/8 18-1/8 10 8-5/8 2-7/8 3/8 3/16 12-1/8 – – 32-7/8 15
(305) (368) (419) (127) (32) (22) (654) (152) (219) (38) (86) (460) (254) (219) (73) (10) (5) (308) (835) (381)
6 6” 1823HHF 14HH 8 5A 12 14-1/2 16-1/2 5 1-1/4 7/8 27 6 7-1/2 1-3/4 4-1/8 20-1/2 15 7-1/2 2-7/8 3/8 3/16 14-1/2 – – 36-3/4 17
(305) (368) (419) (127) (32) (22) (686) (152) (191) (44) (105) (519) (381) (191) (73) (10) (5) (368) (933) (432)
6 6” 1823F 15 8 5 12 14 13-1/2 5 1 7/8 24--7/8 6 6-3/4 1-3/4 4 18 14-1/4 6-3/4 2-7/8 3/8 3/16 12 – 3/4 32 16-3/4
-BF (305) (356) (343) (127) (25) (22) (632) (152) (171) (44) (102) (457) (362) (171) (73) (10) (5) (305) – (19) (813) 425
6 6” 1824BF 18 8 5 12 14 14-3/4 5 3/4 7/8 27-1/4 6 8 1-3/4 4 18 16 8 2-7/8 3/8 3/16 12 – 3/4 32 18
-CF (305) (356) (375) (127) (19) (22) (692) (152) (203) (44) (102) (457) (406) (203) (73) (10) (5) (305) – (19) (813) (457)
6 6” 1825F 20 8 5 12 14 14-3/4 5 1 7/8 27-3/4 6 8 1-3/4 4 18 15-3/4 8 2-7/8 3/8 3/16 12 – 3/4 32 18
(305) (356) (375) (127) (25) (22) (705) (152) (203) (44) (102) (457) (400) (203) (73) (10) (5) (305) – (19) (813) (457)
8 8” 1822F 12 10 5 12 14 14-3/4 5 1-1/4 7/8 26-3/8 6 8 1-3/4 4 18 17 9 2-7/8 3/8 3/16 12 1-3/4 2 32 17-3/4
(305) (356) (375 (127) (32) (22) (670) (152) (203) (44) (102) (457) (432) (229) (73) (10) (5) (305) (44) (51) (813) (451)
8 8” 1824BF 17 10 5 12 14 14-3/4 5 1-1/4 7/8 27-1/8 6 8 1-3/4 4 18 17 8 2-7/8 3/8 3/16 12 3/4 2 32 17-3/4
(305) (356) (375) (127) (32) (22) (689) (152) (203) (44) (102) (457) (432) (203) (73) (10) (5) (305) (19) (51) (813) (451)
2
8 8” 1825F 21 10 6B 20 17 18-1/2 9 1 15/16 32-1/2 7-1/2 9-1/2 2-1/8 5-7/16 21-7/8 18 9-1/2 4-3/4 1/2 1/4 14-3/8 – – 38 21
(51)
-AF (508) (432) (470) (229) (25) (24) (826) (191) (241) (54) (138) (556) (457) (241) (121) (13) (6) (365) – – (965) (533)
10 10” 1823CF 15 12 6B 15 22 25 6-1/2 1 7/8 38-1/2 10 13-1/2 2-1/8 5-7/16 21-7/8 17 13-1/2 4-3/4 1/2 1/4 11-7/8 – – 38 20 1-1/4
(381) (559) (635) (165) (25) (22) (978) (254) (343) (54) (138) (556) (432) (343) (121) (13) (6) (301) – – (965) (508) (32)
10 10” 1824F 18 12 6B 15 22 25 6-1/2 1 7/8 39-1/2 10 13-1/2 2-1/8 5-7/16 21-7/8 18 13-1/2 4-3/4 1/2 1/4 11-7/8 – – 38 22
(381) (559) (635) (165) (25) (22) (1003) (254) (343) (54) (138) (556) (457) (343) (121) (13) (6) (301) – – (965) (559)
10 10” 1824DF 18D 12 7A 15 22 25 6-1/2 1-1/4 7/8 40-1/2 10 12-1/4 2-1/8 5 24-1/4 20 12-1/4 6-5/8 1/2 1/4 14-1/4 – – 43 24 2
(381) (559) (635) (165) (32) (22) (1029) (254) (311) (54) (127) (616) (508) (311) (168) (13) (6) (362) – – (1092) (610) (51)
12 12” 1824AF 18 14 7 15 22 24 6-1/2 1 7/8 40-1/8 10 15 2-1/2 6-5/8 25-1/4 18 15 5 5/8 5/16 15-1/4 – – 43-7/8 23
(381) (559) (610) (165) (25) (22) (1019) (254) (381) (64) (168) (641) (457) (381) (127) (16) (8) (387) – – (1114) (584)
NOTES
STD. 125# SUCTION OPT. 125# SUCTION OPT. 250# SUCTION
1. All dimensions are in inches (mm). AND DISCHARGE FLANGE , 250# DIS- AND DISCHARGE
2. Dimensions may vary ± 3/8" (10). FLANGES CHARGE FLANGE FLANGES
3. Not for construction purposes unless certified. * Pump sizes 6” 1822HHF & 6” 1823HHF are furnished as standard
4. Suction & discharge flanges ANSI Standard flat face. with 125# suction flange and 250# discharge flange.
FAIRBANKS MODEL 1800 PUMPS Section 912 Page 231
ON STANDARD STEEL BASE Date April 1, 2008
A
COUPLING GUARD
CP ZZ PIPE TAP FAR SIDE ZZ PIPE TAP NEAR SIDE Supersedes Section 912 Page 231
C
APPROX.
W YY X
DISCHARGE
X YY
SUCTION
Dated June 1, 2007
DISCHARGE
S Z Z S
D D
HG HG
SUCTION
1-1/2 1-1/2
1-1/2 HE 1-1/2 HE (38)
[4] HH FOUNDATION BOLTS (38) (38) (38)
HY HA HA
HF HP
HB VIEW A-A VIEW A-A
A RIGHT HAND ROTATION LEFT HAND ROTATION
18 21 23 22 24 24 25 25 26 26 28 29 29 28 30 30 33 32 35 34 38 36 40 40 44
PUMP SIZE
C;
D S W X Z CP HY YY ZZ
APPROC
CASE
DISCH MODEL
BORE
1-1/2 2.5" 1823BF 10B 3 8 4 13-1/2 9-3/4 4 20 5 10
(203) (102) (343) (247) (102) (609) (127) (254) BASE 5 7 7 9 9 9 9 10 11 10 11 11 11 11 12 - - - - - - - -
2
3 3" 1824F 10 4 9* 1-1/2 13-1/2 10 4-1/2 24 5 11
(228) (114) (343) (254) (114) (609) (127) (279) BASE 5 7 7 9 9 9 9 10 11 10 11 11 11 11 12 - - - - - - - -
4 4" 1823AFCF 11A 10+ 5 14-1/2 11-1/4 5 26 6 12-3/4
5
11C (254) (127) (368) (286) (124) (660) (152) (324) BASE 7 7 9 11 11 11 11 11 11 11 11 11 12 12 12 15 15 15 15 15 15 15 -
4 4" 1823DF 11D 5 10+ 5-1/2 14-1/2 12 5 26 6 12-3/4
3
(254) (140) -368 (305) (124) (660) (152) (324) BASE 7 7 9 11 11 11 11 11 11 11 11 11 12 12 12 15 15 15 15 - - - -
4 4" 1824F 15 5 11 5-1/2 14-1/2 13 5-1/2 26 6 14
(279) (140) (368) (330) (140) (660) (152) (355) BASE - 7 9 11 11 11 11 11 11 11 11 11 12 12 12 15 15 15 15 - - - -
5 5" 1822BFCF 11B 11** 6-1/4 16 11-1/4 5-1/2 28-1/2 6 13-1/4
6
11C (279) (159) (406) (286) (140) (723) (152) (336) BASE 7 9 10 11 11 11 11 12 12 12 12 12 12 12 12 15 15 15 15 15 15 15 15
5 5" 1823F 15 6 12-1/2 6-1/4 16 13-1/4 6-1/4 26-1/2 6 15
1-1/4
(217) (159) (406) (336) (159) (673) (152) (381) BASE 7 9 10 11 11 11 11 12 12 12 12 12 12 12 12 15 15 15 15 15 15 15 15
4
5 5" 1824F 17 6 12-1/2 6-1/4 16 14 6-1/4 28-1/2 6 15
(217) (159) (406) (355) (159) (723) (152) (381) BASE 7 9 10 11 11 11 11 12 12 12 12 12 12 12 12 15 15 15 15 15 15 15 15
6 6" 1822F 11 8 12-1/2 8-5/8 16 11-3/4 6-1/4 28-1/2 6 14-1/2
(217) (219) (406) (298) (159) (723) (152) (368) BASE 7 9 10 11 11 11 11 12 12 12 12 12 12 12 12 15 15 15 15 15 15 15 15
6 6" 1822HHF 11HH 8 16-1/2 8/5/08 18-1/2 10 8-5/8 32-7/8 8 15
4A
(419) (219) (460) (254) (219) (835) (203) (381) BASE 13 15 - 15 - 16 - 16 - 16
6 6" 1823HHF 14HH 8 16-1/2 7-1/2 20-1/2 15 7-1/2 36-3/4 8 17
5A
(419) (191) (519) (381) (191) (933) (203) (431) BASE 15 - 16 - 16 - 16 - 16
6 6" 1823BF 15B 13-1/2 6-3/4 18 14-1/4 6-3/4 32 7 16-3/4
8
15C (343) (171) (457) (368) (171) (812) (178) (425) BASE - 11 12 12 12 12 12 12 12 12 12 12 13 13 15 15 15 16 16 16 16 16
6 6"1824BFCF 18B 14-3/4 8 18 16 8 32 7 18
8
18C (374) (203 (457) (406) (203) (812) (178) (457) BASE 10 11 12 12 12 12 12 12 12 12 12 12 13 13 15 15 15 16 16 16 16 16
6 6" 1825F 20 8 14-3/4 8 18 15-3/4 8 32 7 18
5
(374) (203) (457) (400) (203) (812) (178) (457) BASE 10 11 12 12 12 12 12 12 12 12 12 12 13 13 15 15 15 16 16 16 16 16
8 8" 1822F 12 10 14-3/4 8 18 17 9 32 7 17-3/4
(374) (203) (457) (431) (228) (812) (178) (450) BASE 10 11 12 12 12 12 12 12 12 12 12 12 13 13 15 15 15 16 16 16 16 16
8 8" 1824BF 17B 10 14-3/4 8 18 17 8 32 7 17-3/4
(374) (203) (457) (431) (203) (812) (178) (450) BASE 10 11 12 12 12 12 12 12 12 12 12 12 13 13 15 15 15 16 16 16 16 16
2
8 8" 1825FAF 21 18-1/2 9-1/2 21-7/8 18 9-1/2 38 11 21
10
21A (470) (241) (555) (457) (241) (964) (279) (533) BASE 14 14 16 16 16 16 16 16 16 17
10 10" 1823CF 15C 12 25 13-1/2 21-7/8 17 13-1/2 38 11 20
6B 1-1/4
(635) (343) (555) (431) (343) (964) (279) (508) BASE 14 14 14 14 16 16 16 16 16 16 16 17
10 10" 1824F 18 12 25 13-1/2 21-7/8 18 13-1/2 38 11 22
(635) (343) (555) (457) (343) (964) (279) (558) BASE 14 14 16 16 16 16 16 16 16 17
2
10 10" 1824DF 18D 12 25 12-1/4 24-1/4 20 12-1/4 43 11-1/2 24
7A
(635) (311) (616) (508) (311) (1092) (292) (610) BASE 16 16 17
12 12" 1824AF 18A 14 24 15 25-1/4 18 15 44 11 23
7
(609) (381 (615) (457) (381) (1117) (279) (584) BASE 16 16 16 16 17 17 17
BASE HA HB HE HG HH HF HP
NOTES - D is 9.0” when using frames 364TS and 365TS. 5 12 38 9 3 1/2 17 20
1. All dimensions are in inches. * D is 10-1/2” when using frames 324TS - 365TS. (305) (964) (228) (76) (13) (431) (508)
2. Dimensions may vary ± 3/8". ** D is 12 when using frames 404TS - 445TS. 7 13 42 10 4 5/8 17 24
(330) (1066) (254) (101) (15) (431) (609)
3. Not for construction purposes unless certified. *** Pump sizes 6”1822HHF & 6”1823HHF are 9 15 44 12 3-3/8 5/8 19 24
4. Coupling gap may vary 1/8" thru 2-1/16". furnished as standard with 125# suction flange (381) (1117) (305) (86) (15) (482) (609)
5. Conduit box is shown in approximate location. & 250# discharge flange. 10 18 44 15 4 5/8 42 1
(457) (1117) (381) (101) (15) (1066) (25)
Dimensions are not specifed as they vary with + D is 10-1/2” when using frames 404TS - 405T 11 18 48 15 4 5/8 46 1
each motor manufacturer. and D is 11 when using frames 444TS - 445TS. (457) (1219) (381) (101) (15) (1168) (25)
12 18 54 15 4 5/8 52 1
6. Suction and discharge flanges are ANSI standard (457) (1371) (381) (101) (15) (1320) (25)
flat face. 13 18 60 15 4 5/8 35 24
(457) (1524) (381) (101) (15) (888) (609)
14 18 65 15 4 5/8 40 24
(457) (1651) (381) (101) (15) (1015) (609)
15 22 60 19 4 5/8 58 1
(558) (1524) (482) (101) (15) (1473) (25)
16 22 72 19 4 5/8 70 1
(558) (1828) (482) (101) (15) (1778) (25)
17 22 84 19 4 5/8 82 1
(558) (2133) (482) (101) (15) (2082) (25)
1000 G.P.M. 913 SERIES Section 913 Page 433
Date December 2009
DIESEL ENGINE DRIVE
Supersedes All Previous Editions
130 PSI
120 87%
80
115 PSI
84%
(METERS of H 2O)
100 80%
97
P.S.I.
97 PSI
60
80 to
1000
146
40
60 P.S.I.
1500
BHP
40 200
100
BHP FOR 97 PSI CURVE
0
U.S. GPM 200 400 600 800 1000 1200 1400 1600 1800 2000
L/S 25 50 75 100 125
M 3/HR 75 150 225 300 375 450
PC-147573
60 90 PSI 82%
80 82%
75 PSI 80%
(METERS of H 2O)
50
60 70%
40 60 PSI
P.S.I.
to
50 PSI 60%
40
20 1000
BHP
90
20 1500 120 P.S.I.
BHP FOR 90 PSI CURVE
80
0
U.S. GPM 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400
L/S 25 50 75 100 125 150
M 3/HR 100 200 300 400 500
PC-123155
LMR PLUS Electric Fire Pump Controllers 1-1
Features
FD70 Reduced Voltage - Wye Delta (Star-Delta) Open Transition July 2011
LMR
Power I/O Board Membrane Keypad
Transformers Door Mount
S Incoming line voltage is run directly to the I/O The membrane keypad is accessible from the
PLU board from the incoming lines. The I/O board front door of the controller.
will accept voltage inputs between 100 and
600V.
Product Description
NEMA Rating
The FD70 LMR Plus Controllers use a method The standard membrane keypad is rated for
of connecting the pump motor windings into NEMA 2, 3R, 4, 4X and 12.
wye configuration to start, then switching to a
delta configuration to run. Alarm & Status LED’s
This reduces the starting current of the motor Output Relays A total of 20, ( 10 Status - 10 Alarm ) LED’s
significantly. Five, 8 Amp, 2 Form - C (DPDT) output relays provide indication on the membrane keypad.
Wye-Delta starting is the only method that has a are provided standard on each power I/O board.
starting torque efficiency of 100%. The FD70 They are designated for: Common Alarm,
can be programmed for either fully automatic or
Status LED’s Alarm LED’s
Phase Failure, Phase Reversal, Pump Run and Power On Phase Reversal
semi-automatic operations. Future #1. Each socket has an LED mounted on Pump Running Phase Failure
the I/O board which indicates each relay’s coil Local Start Fail To Start
The use of an embedded web page for status.
retrieving diagnostics and history reports, along Remote Start Undervoltage
Deluge Valve Overvoltage
with USB and Ethernet communication ports for Optional Output Relay Boards Emergency Start Low Room Temperature
downloading data, make the LMR Plus Series of There is provision to add up to eight additional Interlock On Locked Rotor Trip
controllers easy to troubleshoot and maintain. relay outputs, via optional relay output boards. Low Pressure Low Suction Pressure
As well, critical information can be easily Each board contains a maximum of 2 additional Auto Shutdown Enabled Source 2 Disconnected
accessed and used for report generation and relays. The Power I/O Board will accept a Programmable LED # 1 Programmable LED # 2
analysis, which aids in providing effective, maximum of 4 optional boards which mount in a
reliable fire protection. snap-on configuration. Silence Button
Each board provides an area for the user to A silence pushbutton on the membrane can be
Product Features label the terminal number and relay name. used to silence the buzzer. When an alarm
Logic Controller Board condition exists, the alarm buzzer will sound. If
Communication Drain Valve Solenoid the Silence Alarm button is pressed, the alarm
The controller can be ordered with the option to All LMR Plus electric controllers are equipped buzzer will turn off. If a subsequent alarm
display and output current values and status, on with a drain valve solenoid used for weekly test condition occurs after the silence button is
command, from various software protocols purposes. pressed, the buzzer will re-sound. Pressing the
through the appropriate port(s). Silence Alarm button again, will silence the
buzzer.
Embedded Web Page USB External Drive
The web page is a multifunction tool that allows General Motor Test Button
the user to view the controller’s current status, When using an external USB Drive, the drive The motor test button on the membrane can be
data values, programmed set points and history. should conform to the following specifications: used to simulate an automatic start.
It is accessed using the optional ethernet port.
Min: 128mb Automatic Shutdown Enabled
Ethernet Port Max: 2 Gig FAT16 protocol When the Automatic Shutdown function is
An optional Ethernet port can be used for direct USB 1.0 or 2.0 enabled, a Green LED will indicate on the
connection to a computer for data transfer. controller membrane.
INTERLOCK ON
LOW SUCTION
PUMP START
INPUT #1
INPUT #2
INPUT #3
INPUT #4
INPUT #5
INPUT #6
INPUT #7
INPUT #8
INPUT #9
CUSTOMER INPUTS
INTERNAL CONNECTIONS
COMMON ALARM
(NORMALLY ENERGIZED)
COMMON ALARM
(NORMALLY ENERGIZED)
PHASE FAILURE
(NORMALLY ENERGIZED)
ALARM CONTACTS
PHASE FAILURE
(NORMALLY ENERGIZED)
PHASE REVERSAL
PHASE REVERSAL
FUTURE #1
FUTURE #1
PUMP RUN
PUMP RUN
N. Y. C.
APPROVED
Field Connections
LMR
PLU
S
COMMON ALARM
(NORMALLY ENERGIZED)
COMMON ALARM
(NORMALLY ENERGIZED)
PHASE FAILURE
(NORMALLY ENERGIZED)
ALARM CONTACTS
PHASE FAILURE
(NORMALLY ENERGIZED)
PHASE REVERSAL
PHASE REVERSAL
FUTURE #1 NOTE:
1. MOTOR CONNECTIONS VARY, PLEASE
REFER TO SPECIFIC MOTOR CONNECTION
FUTURE #1 DIAGRAM.
2. PLEASE OBSERVE PROPER PHASE
ROTATION, A,B,C-L1,L2,L3 AS CONTROLLER
IS PHASE SENSITIVE.
PUMP RUN 3. CABLE SIZE TO BE 125% OF FULL LOAD
CURRENT. REFER TO WIRE SIZE TABLE IN
NFPA 70.
PUMP RUN
N. Y. C.
APPROVED
Dimensions
Standard Enclosure - Type NEMA 2, 3R, 4, 4X, 12
LMR
PLU
S
A
17.65 [448] B
3A13357H01
3A13357H01
START
STOP
62.00 [1575]
74.00 [1880]
5.00 [127]
16.00 [406]
1 - START PUSHBUTTON
2 - STOP PUSHBUTTON 14.00
3 - MAIN POWER SWITCH 11.26 [286]
[356]
4 - MSH (EMERGENCY START HANDLE) 1.11 [28]
5 - MAIN LMR PLUS DISPLAY
6 - RECOMMENDED CABLE ACCESS (BOTTOM ONLY)
1.37 [35]
C 1.13 [29]
3.35 [85]
50 - 100 200 - 208V 100,000 Consult Consult 315 41.83 30.25 21.30
60 - 125 220 - 240V Factory Factory (143) (1062) (768) (541)
100 - 200 * 380 - 415V
125 - 250 440 - 480V
125 - 300 550 - 600V 25,000 35,000
125 - 150 200 - 208V 100,000 Consult 420 54.83 43.25 34.30
Factory (190) (1393) (1099) (871)
150 - 200 220 - 240V
250 - 300 * 380 - 415V
300 - 400 440 - 480V
350 - 500 550 - 600V 25,000 35,000
* Coils Available: 380V-50Hz, 380V-60Hz, 415V-50Hz, 415V-60Hz
SEISMIC QUALIFIED
NOTES:
U.B.C and C.B.C 1. All enclosures finished in FirePump red.
N. Y. C. 2. Cable Entrance bottom only.
APPROVED 3. Standard Enclosure type NEMA 2.
Must Be Installed Per Applicable Code
and Manufacturers Recommendations
S Z
HD
6 (152)
130 PSI
120 87%
80
115 PSI
84%
(METERS of H 2O)
100 80%
97
P.S.I.
97 PSI
60
80 to
1000
146
40
60 P.S.I.
1500
BHP
40 200
100
BHP FOR 97 PSI CURVE
0
U.S. GPM 200 400 600 800 1000 1200 1400 1600 1800 2000
L/S 25 50 75 100 125
M 3/HR 75 150 225 300 375 450
PC-147573
60 90 PSI 82%
80 82%
75 PSI 80%
(METERS of H 2O)
50
60 70%
40 60 PSI
P.S.I.
to
50 PSI 60%
40
20 1000
BHP
90
20 1500 120 P.S.I.
BHP FOR 90 PSI CURVE
80
0
U.S. GPM 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400
L/S 25 50 75 100 125 150
M 3/HR 100 200 300 400 500
PC-123155
DIESEL Engine Fire Pump Controllers 1-1
Features
FD120 Diesel Engine Controllers March 2013
Programmable Features
• Languages
(English, French, Spanish Standard. Other
languages are available. Consult factory.)
Alarm LED’s • Date and Time
The controller is supplied with fourteen (14) red • Pressure Start and Stop Points
alarm LED’s for the following: • Low and High Pressure Alarms
BATTERY #1 FAILURE • Stop Mode
CHARGER # 1 FAILURE • Low Suction Shutdown
BATTERY #2 FAILURE • Pressure Recording Parameters
• Run Period Timer
CHARGER # 2 FAILURE
LOW PRESSURE • Weekly Test Timer Standards & Certification
SYSTEM OVER PRESSURE • Sequential Start Timer
• AC Failure Alarm The FD120 Diesel Engine Fire Pump Controllers
LOW SUCTION PRESSURE meet or exceed the requirements of Underwriters
LOW FUEL • AC Fail to Start
Laboratories, Underwriters Laboratories Canada,
FAIL TO START Factory Mutual, the Canadian Standards
HIGH ENGINE TEMP
LOW OIL PRESSURE Enclosures Association, New York City building code, CE
mark and U.B.C / C.B.C. Seismic requirements,
ENGINE OVER SPEED and are built to NFPA 20 standards.
ECM SELECTOR IN ALT POSITION Ratings
FUEL INJECTION MALFUNCTION All FD120 controllers come standard with NEMA
2 enclosures unless otherwise ordered.
Statistics Available options include: NEMA 3R, 4, 4X, 12.
Up to 27 of statistical points are recorded to
provide a quick review of how the system has Reduced Size
been operating. The statistics can be viewed on A streamlined internal design has allowed the
the main display, saved to a USB disk drive, or overall size of the DIESEL Plus controllers to be
N. Y. C.
viewed on the embedded webpage. reduced from previous models. See dimen- APPROVED
sional drawings on our website.
INTERLOCK ON
LOW SUCTION
PUMP START
NOTES:
LOW FUEL
INPUT #10
INPUT #1
INPUT #2
INPUT #3
INPUT #4
INPUT #5
INPUT #6
INPUT #7
INPUT #8
INPUT #9
1. DELUGE VALVE INPUT NORMALLY CLOSED.
REMOVE JUMPER IF USED.
2. ALL RELAY CONTACTS ARE SHOWN IN NO POWER
CONDITION.
3. ALARM CONTACTS RATED FOR 8A/250VAC. ENGINE
RUN CONTACTS RATED 10A/250VAC. CUSTOMER INPUTS
OPTION RELAY #1
(2 SETS FORM-C)
ENGINE RUN
OPTION RELAY #2
(2 SETS FORM-C)
ENGINE RUN
FUTURE #1
OPTION RELAY #4
(2 SETS FORM-C)
ALARM CONTACTS
FUTURE #2
LOW FUEL
OPTION RELAY #6
(2 SETS FORM-C)
LOW FUEL
OPTION RELAY #7
AUTO MODE (2 SETS FORM-C)
COMMON ALARM
(NORMALLY ENERGIZED)
COMMON ALARM
(NORMALLY ENERGIZED)
90-240VAC POWER
BATTERY #2 INPUT(+)
BATTERY #1 CRANK
BATTERY #2 CRANK
BATTERIES (-)
BATTERIES (-)
FUEL SOLENOID
ECM IN ALTERNATE
FUEL INJECTOR FAIL
SEISMIC QUALIFIED
U.B.C and C.B.C
N. Y. C.
APPROVED
Must Be Installed Per Applicable Code
and Manufacturers Recommendations
Dimensions
Standard Enclosure - Type NEMA 2, 3R, (*4, 4X), 12
19.19 [487]
26.72 [679] 15.00 [381]
7.00 [178]
2.00 [51]
13.11 [333]
34.98 [888]
32.98 [838]
52.98 [1346]
18.00 [457]
10.56 [268]
Flow
Models GPM
Series HP Range
PVM/PVMI/PVMX 2 1/2 – 3 1 – 15
PVM/PVMI/PVMX 4 1/2 – 7.5 3 – 36
PVM/PVMI/PVMX 8 3/4 – 10 5 – 56
PVM/PVMI/PVMX 16 5 – 20 8 – 95
PVM 32 3 – 30 15 – 180
PSI
270
80 PVM(I/X)4−80 − 2 HP
240
PVM(I/X)4−80/7 − 1.5
70
210
PVM(I/X)4−60− 2 HP
60
180
PVM(I/X)4−50 − 1 HP
50
Head − ft
Head − m
150
PVM(I/X)4−40 − 1 HP
40
120
PVM(I/X)4−30 − .75 H
30
90
PVM(I/X)4−20 − .5 HP
20
60
PVM(I/X)4−20/1 − .33 HP
10
30
0 0
0 5 10 15 20 25 30 35 40
Capacity − USgpm
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0 8.5 9.0
9
PVM (I/X) 4 SERIES
Performance Curves – PVM (I/X) 4 Series
Nominal RPM: 2875
Based on Fresh Water @ 68 F.
Maximum Working Pressure: 360 PSI
1,000
300
900
PVM(I/X)4−260 - 7.5 HP
250
800
PVM(I/X)4−240 - 5 HP
PVM(I/X)4−220 - 5 HP
700
200
PVM(I/X)4−190 - 5 HP
600
Head − ft
Head − m
PVM(I/X)4−160 − 3 HP
150 500
PVM(I/X)4−150 − 3 HP
PVM(I/X)4−140 − 3 HP
PVM(I/X)4−130 − 3 HP
400
PVM(I/X)4−120 − 3 HP
PVM(I/X)4−110 − 2 HP
100 PVM(I/X)4−100 − 2 HP
300
PVM(I/X)4−90 − 2 HP
200
50
100
0 0
0 5 10 15 20 25 30 35 40
Capacity − USgpm
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0 8.5 9.0
Capacity − m3/h
10
PVM (I/X) 4 SERIES
Single Stage Performance Data – PVM (I/X) 4 Series
40 100
12
90
10
80
30
70
8
60
Efficiency − %
Head − ft
Head − m
6 20 50
40
4
30
10
20
2
10
0 0 0
0.4
Power − hp
Power − kW
0.2
0.2
0.1
0.0 0.0
3 10
NPSHr − ft
NPSHr − m
2
5
1
0 0
0 10 20 30 40
Capacity − USgpm
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0 8.5 9.0
Capacity − m3/h
11
PVM4 SERIES
Cast Iron Construction
FLANGED
Allow Space
THREADED
Technical Information
to Remove
D Motor D MINIMUM PUMPING RATES: 3 GPM
C C
FLOW RANGE: 3 – 36 GPM
MINIMUM SUCTION PIPE SIZES:
1-1/4” Nominal Diameter, Schedule 40 Pipe
B F F B
3/4" NPT MAXIMUM INLET PRESSURE:
Vent Plug 20/1 - 20 – 90 PSI
30 - 80/7 – 145 PSI
1/4" NPT
Gauge Tap 80 - 160 – 220 PSI
E ANSI 250 lb A E MAXIMUM AMBIENT TEMPERATURE: 104° F
A 1-1/4" Flange 1/4" NPT
Gauge Tap LIQUID TEMPERATURE RANGE: +5° F to +250° F
1-1/4"
NPT MOTOR OPTIONS: TEFC or ODP
CONSTRUCTION MATERIALS: See Page 16.
3" 1-1/4" ANSI. 250 lb. 4-Bolt Flange
9-7/8" 10"
3-15/16" 3-15/16"
3-1/16"
3-7/8"
1/2" Dia. – 4 Places 5-1/2"
* Measurements represent the largest number possible for each model using standard efficiency motors.
12
PVM4 SERIES
Cast Iron Construction
FLANGED
Allow Space
THREADED
Technical Information
to Remove
D Motor D MINIMUM PUMPING RATES: 3 GPM
C C
FLOW RANGE: 3 – 36 GPM
MINIMUM SUCTION PIPE SIZES:
1-1/4” Nominal Diameter, Schedule 40 Pipe
B F F B
3/4" NPT MAXIMUM INLET PRESSURE:
Vent Plug 20/1 - 20 – 90 PSI
30 - 80/7 – 145 PSI
1/4" NPT
Gauge Tap 80 - 160 – 220 PSI
E ANSI 250 lb A E MAXIMUM AMBIENT TEMPERATURE: 104° F
A 1-1/4" Flange 1/4" NPT
Gauge Tap LIQUID TEMPERATURE RANGE: +5° F to +250° F
1-1/4"
NPT MOTOR OPTIONS: TEFC or ODP
CONSTRUCTION MATERIALS: See Page 16.
3" 1-1/4" ANSI. 250 lb. 4-Bolt Flange
9-7/8" 10"
3-15/16" 3-15/16"
3-1/16"
3-7/8"
1/2" Dia. – 4 Places 5-1/2"
The XT Series of Jockey Pump Controllers Eaton's XTJP and XTJY series of jockey pump
incorporate Eaton’s XT Power Controls which controllers are supplied standard with an 1/8 DIN,
are designed for the global marketplace. The NEMA 4X digital panel meter that displays current
XT controls carry global ratings, are small in pressure and hi and low setpoints on a 4-digit,
size and are available in a wide variety of superbright LED display. Pressure input is
operating voltages. They are easy to install provided by a 4-20mA pressure sensor.
and maintain, due to their modular, plug-in
design.
All jockey pump controllers are wired with a Enclosures have an oven baked powder paint
120V control power transformer as standard. finish and are supplied with NEMA 2 rating,
unless otherwise ordered. Available options
include: NEMA 3R, 4, 4X, 12.
Technical Data
Product Description
ACROSS-THE-LINE (Direct On Line) JOCKEY PUMP CONTROLLERS
ACROSS THE LINE
Line Voltage
JOCKEY PUMP CONTROLLERS
200 - 208V 220 - 240V 380 - 415V 440 - 480V 550 - 600V 120V 1 ph 240V 1 ph
The XTJP jockey pump controllers operate
across-the-line. Full voltage is applied to the
motor for starting by the use of a single motor Motor Horsepower
starter. Starting inrush current is approximately
600% of rated full load amperes. 1/3 - 15Hp 1/3 - 40Hp 1/3 - 50Hp 1/3 - 50Hp 1/3 - 50Hp 1/3 - 5Hp 1/3 - 10Hp
WYE-DELTA (Star-Delta)
JOCKEY PUMP CONTROLLERS
When six or twelve-lead delta connected WYE-DELTA (Star-Delta) JOCKEY PUMP CONTROLLERS
jockey pump motors are started wye (star)
connected, approximately 58% of line voltage Line Voltage
is applied to each winding. The motor
develops 33% of full-voltage starting torque 200 - 208V 220 - 240V 380 - 415V 440 - 480V 550 - 600V
and draws 33% of normal locked-rotor current
from the line. After an adjustable time delay
(during which the motor accelerates), it is Motor Horsepower
reconnected for normal operation. 1/3 - 15Hp 1/3 - 40Hp 1/3 - 50Hp 1/3 - 50Hp 1/3 - 50Hp
(0.74 - 11.03KW) (0.74 - 29.42KW) (0.74 - 36.78KW) (0.74 - 36.78KW) (0.74 - 36.78KW)
Product Features
Combination Motor Controllers
N. Y. C.
APPROVED
Sealed Rotary Handle Mechanism
N. Y. C.
APPROVED
Dimensions
Standard Enclosure - Type NEMA 2 - Jockey Pump Controller
10.75
[273]
16.13 8.00
[410] [203]
Ø 0.27 [Ø7] x4
WALL MTG. HOLES
1
2
3
13.00 16.35
4
[330] [415]
NOTES:
1 - ISOLATION SWITCH
2 - HAND/OFF/AUTO SWITCH PIPING ENTRANCE 8.59
3 - DOOR LATCH 8.08 1/4" NPT - FEMALE [218]
4 - DIGITAL DISPLAY [205]
2.13
[54]
Dimensions in inches and [millimeters] 4.03
[102]
200 - 208V 220 - 240V 380 - 415V 440 - 480V 550 - 600V
Motor Hp Withstand Motor Hp Withstand Motor Hp Withstand Motor Hp Withstand Motor Hp Withstand
Rating (kA) Rating (kA) Rating (kA) Rating (kA) Rating (kA)
0.33 - 3 65 0.33 - 3 65 0.33 - 5 65 0.33 - 7.5 65 0.33 - 10 18
4 50 4 50 7.5 - 10 18 10 50
5 - 10 18 5 - 10 18 15 - 20 18
N. Y. C.
Pending
APPROVED
FLOAT-OPERATED
AIR RELEASE VALVE
D
1/2" PIPING BY
OTHERS (SEE NOTE 5)
CASING RELIEF VALVE
3-1/2" (89) DIA. SUCTION AND 3/4" NPT OUTLET
DISCHARGE GAUGES WITH
1/4" SHUT-OFF COCKS
C
VALVE INLET SIZE "B"
(PIPING BY OTHERS)
NOTES:
1. Accuracy is approximately ± 1%.
2. Flow meter is Gerand Model K Venturi type rated for 500 PSI
with butt-weld or grooved connections and for 275 PSI with
Class 150 flanged connections.
3. Proper operation requires that minimum distances of straight
pipe runs be maintained both upstream and downstream from
flowmeter. Refer to manufacturer's instructions before
attempting installation.
4. Meter range is 50% to 200% of nominal rated flow. Dial is direct
reading in G.P.M. for the specified range.
GERAND VENTURI FLOW METERS
NOMINAL BUTT-WELD GROOVED CLASS 150 FLANGES
FLOW RATE PIPE OPTION "A" FAIRBANKS OPTION "A" FAIRBANKS OPTION "B" FAIRBANKS
G.P.M. SIZE NUMBER DIM. PART NUMBER NUMBER DIM. PART NUMBER NUMBER DIM. PART NUMBER
100 2.5 91MP 3 366-0377-649 91LN 4 366-0337-649 91PL 9.5 366-0244-649
150 3 91MR 3.5 366-0378-649 91LP 4.38 366-0338-649 91PM 9 366-0245-649
200 3 91MT 3.5 366-0379-649 91LR 4.38 366-0339-649 91PN 9 366-0246-649
4 91MW 3.5 366-0380-649 91LT 5 366-0340-649 91PP 9.5 366-0247-649
250 4 91NA 3.5 366-0381-649 91M 3.75 366-0154-649 91PR 9.5 366-0248-649
5 91ND 5 366-0384-649 91MB 5 366-0343-649 91RA 12 366-0251-649
300 4 91NB 3.5 366-0382-649 91LW 3.75 366-0341-649 91PT 9.5 366-0249-649
450 4 91NC 3.5 366-0383-649 91MA 3.75 366-0342-649 91PW 9.5 366-0250-649
5 91NE 5 366-0385-649 91MC 5 366-0344-649 91RB 12 366-0252-649
500 5 91NF 5 366-0386-649 91N 5 366-0155-649 91RC 12 366-0253-649
6 91NH 6 366-0388-649 91ME 6 366-0346-649 91RE 13 366-0255-649
750 5 91NG 5 366-0387-649 91MD 5 366-0345-649 91RD 12 366-0254-649
6 91NJ 6 366-0389-649 91P 6 366-0156-649 91RF 13 366-0256-649
1000 6 91NK 6 366-0390-649 91R 6 366-0157-649 91RG 13 366-0257-649
8 91NP 7 366-0392-649 91MF 7 366-0347-649 91RJ 15 366-0359-649
1250 6 91NL 6 366-0391-649 91T 6 366-0158-649 91RH 13 366-0258-649
8 91NR 7 366-0393-649 91MG 7 366-0348-649 91RK 15 366-0360-649
1500 8 91NT 7 366-0394-649 91W 7 366-0159-649 91RL 15 366-0361-649
10 91PC 8 366-0398-649 91MH 8 366-0349-649 91RR 16 366-0355-649
2000 8 91NW 7 366-0395-649 91AA 7 366-0160-649 91RM 15 366-0362-649
10 91PD 8 366-0399-649 91MJ 8 366-0350-649 91RT 16 366-0366-649
2500 8 91PA 7 366-0396-649 91AB 7 366-0161-649 91RN 15 366-0363-649
10 91PE 8 366-0400-649 91MK 8 366-0351-649 91RW 16 366-0367-649
3000 8 91PB 7 366-0397-649 91AC 7 366-0162-649 91RP 15 366-0364-649
10 91PF 8 366-0401-649 91ML 8 366-0352-649 91TA 16 366-0368-649
3500 10 91PG 8 366-0402-649 91AD 8 366-0163-649 91TB 16 366-0369-649
12 91PJ 12 366-0406-649 91MM 12 366-0355-649 91TD 21 366-0373-649
4000 10 91PH 8 366-0403-649 91AE 8 366-0164-649 91TC 16 366-0370-649
12 91PK 12 366-0407-649 91MN 12 366-0356-649 91TE 21 366-0374-649
FAIRBANKS FIRE PUMPS Section 916 Page 205
OPTION 79 - MAIN RELIEF VALVE Date June 1, 2007
Supersedes Section 916 Page 205
OPTION 80 - WASTE CONE Dated October 1, 2006
"A" MAIN RELIEF VALVE INLET SIZE "A" MAIN RELIEF VALVE INLET SIZE
C F
B E
Y Y
WASTE CONE WASTE CONE
4-3/4 (121)
1/2 NPT" OUTLET
5-1/4
(133)
HYDR8AC
(VAL-MATIC VM15A)
OR APPROVED EQUAL USED
WITH HORIZONTAL FIRE PUMPS
WORKING PRESSURE UP TO 300 PSI
(FM APPROVED)
1/2" NPT INLET
9-1/2 (241)
12
(305)
HYDR8AD
(VAL-MATIC #102)
USED WITH VERTICAL TURBINE FIRE PUMPS
WORKING PRESSURE UP TO 300 PSI
NOTES:
1. All dimensions are in inches (mm) and may vary ± 1/4 (6).
FAIRBANKS MODEL 1800 & 1900 PUMPS Section 916 Page 251
DIESEL BATTERIES, RACKS, & CABLES Date April 2006
POS NOTES:
16.25
(419)
BATTERY
5.5 (140) RACK
20.5 23.5
(521) (597)
60" or 80"
NOTES: POSITIVE CABLE (1524 or 2032)
1. All cables are SAE J55BA type SGT with
tensile attachment of 700-800 lbs.
2. Positive & negative cables 60" (1524) long 17/32 DIA. HOLE (TYPICAL)
are 2/0 gauge; positive & negative cables 80" 60" or 80"
(2032) long are 3/0 gauge.
3. Terminal clamps have steel reinforced (1524 or 2032)
inserts.
NEGATIVE CABLE
4. Not all cable types are required for every
engine. Refer to Section 916 page 252 for
cable applicability. 12"
INTERCONNECTING (305)
CABLE
Section 916 Page 252 FAIRBANKS MODEL 1800 & 1900 PUMPS
Date October 2006 DIESEL BATTERY CABLE DIAGRAMS
Supersedes Section 916 Page 252
Dated April 2006
12 VOLT SYSTEM
REQUIRED COMPONENTS ENGINE APPLICABILITY
POS
(1) BATTERY RACK CUMMINS: 6BTA 5.9-F1
(2) BATTERIES 6BTA 5.9-F2
12V (2) POSITIVE CABLES 6BTA 5.9-F4
(2) NEGATIVE CABLES 6CTA 8.3-F1
NEG 6CTA 8.3-F2
6CTA 8.3-F3
POS
CLARKE-DETROIT:
12V VMFP-04HN VMFP-04HT
NEG VMFP-06HT VMFP-T6HT
VMFP-L6HR VMFP-T6HR
JU4H-UF10 JU4H-UF20
JU4H-UF30 JU4H-UF40
JU4H-UF50 JU6H-UF30
JU6H-UF50 JU6H-UF60
JW6H-UF30 JW6H-UF40
JW6H-UF50 JW6H-UF60
NOTES:
1. Clarke “VMFP,” “JU4H” & “JU6H” Engines require cable sets of different lengths. On these engine
models, a 2/0 guage postive and negative cable set 60” (1524 mm) long, and a 3/0 guage positive
and negativecable set 80” (2032 mm) long are furnished.
2. Refer to Section 916, Page 251 for details of batteries, racks and cables.
POS
24 VOLT SYSTEM
NEG
REQUIRED COMPONENTS ENGINE APPLICABILITY
POS
24V
(2) BATTERY RACKS CLARKE-DETROIT:
(4) BATTERIES DDFP-08FH DDFP-08FA
(2) POSITIVE CABLES
NEG (2) NEGATIVE CABLES CATERPILLAR:
(2) INTERCONNECTING ALL MODELS
POS CABLES
NEG
POS
24V
NEG
Section 916 Page 256 FAIRBANKS FIRE PUMPS
Date April 2009 SINGLE WALL FUEL TANKS WITH FITTINGS
Supersedes Section 916 Page 256
Dated April 2006
19
11
2
17
C D E F 6"
12 "A" DIA.
22
14
L
13
2" NPT CPLGS. FOR
CUST. FURN. LEGS H
4 G
B FUEL SUPPLY
FUEL RETURN 14
NOMINAL USABLE
TANK SIZE VOLUME A B C D E F G H L Z
IN GALLONS IN GALLONS
119 105 24 (609) 61 (1548) 6 (152) 6 (152) 6 (152) 19 (482) 37 (939) 14 (355) 3 (76) 4
187 165 30 (761) 61 (1548) 6 (152) 6 (152) 6 (152) 19 (482) 37 (939) 16 (406) 3 (76) 4
300 270 38 (964) 61 (1548) 6 (152) 6 (152) 6 (152) 19 (482) 37 (939) 23 (584) 3-3/4 (95) 4
359 320 36 (914) 73 (1853) 6 (152) 6 (152) 6 (152) 31 (787) 44 (1117) 23 (584) 3-3/4 (95) 4
572 515 48 (1218) 73 (1853) 6 (152) 6 (152) 6 (152) 31 (787) 44 (1117) 30 (761) 4-3/4 (121) 4
849 766 64 (1626) 61 (1548) 6 (152) 6 (152) 6 (152) 19 (482) 44 (1117) 30 (761) 4-3/4 (121) 4
1100 993 64 (1626) 79 (2007) 6 (152) 6 (152) 6 (152) 37 (940) 44 (1117) 30 (761) 4-3/4 (121) 6
NOTES
1. All dimensions are in inches and may vary ± 1/4".
2. Components shown are shipped loose for field assembly.
3. Illustration is for component identification only. Actual installation must meet
local codes and all applicable standards.
4. Refer to Section 916 pages 255 through 258 for the location and applicability
of each component shown above
FAIRBANKS FIRE PUMPS Section 916 Page 261
DIESEL ENGINE MUFFLERS Date June 1, 2007
Supersedes Section 916 Page 261
B Dated October 1, 2006
A DIA.
BY-PASS VALVES
NORMALLY CLOSED GAUGE
TO
ENGINE
REGULATOR VALVES
STRAINERS SOLENOID
VALVE
FROM
PUMP
This instructional data explains the installation and shutdown to prevent the waste of cooling water. (One
operation of the cooling system for UL listed, FM red wire must be connected to terminal #1 of the engine
approved Fire Pump engines equipped with heat junction box, the other red wire to terminal #11 of the
exchangers. engine junction box, and the green wire grounded to the
engine block. Refer to applicable wiring diagrams.)
Engines equipped with heat exchangers use an engine
mounted water pump to circulate jacket water around 4. The valves in the BYPASS Iine of the loop are nor-
the tubes of the heat exchanger to maintain proper mally CLOSED. They should ONLY be opened to pro-
jacket water temperatures. Cooling water, supplied by vide cooling water to the engine if the regulator valve
the Fire Pump, is piped through the tubes and dis- or solenoid valve require repair.
charged to waste.
5. Valves "A" and "B" are normally OPEN. They should
REQUIREMENTS ONLY be closed if repair is required to the regulator
valve or solenoid valve.
The loop portion of the cooling water supply piping,
shown above, incorporates all components required 6. The gauge indicates back pressure on the cooling
by NFPA and is sized to provide the required volume water discharge. The recommended back pressure to
of water at the proper pressure for the heat exchang- assure adequate flow is 15-20 PSI and should not
ers of the engine models listed in Table A. exceed the allowable pressure shown in Table A.
Model 1800 & 1900 pumps are shipped from the plant 7. Since cooling loop components are subject to
with the loop piped between the pump and engine. bumps and movement during shipping. all compo-
The pipe and loop sizes are determined by the engine nents must be checked for pipe strain and leakage
model. prior to initial startup.
1. A flushing type strainer is used to protect the regu- The cooling water outlet piping from the engine heat
lator valve, solenoid valve and the tubes of the heat exchanger must be at least the size listed in Table A.
exchanger from foreign material. The piping must be short, have no valves and dis-
charge into an open waste cone. If deviations from the
2. The regulator valve is used to control the volume requirement of discharge to an open waste cone are
and pressure of the cooling water. permitted by the authority having jurisdiction, the
proposed plumbing must be reviewed to assure that
3. The solenoid valve opens automatically when the the back pressure created wiII not reduce the cooling
engine is started and closes automatically on engine water flow to below that required for the engine.
Section 916 Page 302 FAIRBANKS MODEL 1800 & 5900
Date April 2006 DIESEL ENGINE DRIVEN FIRE PUMP
COOLING WATER PIPING DATA
If the outlet piping from two or more engines is connected adjusting is necessary, see the following procedure:
to a common manifold, the manifold piping should be
sized such that the velocity resulting from the combined With the pump operating at the rated duty, the adjustment
flow is the same as that in the outlet piping between the is made after the engine block temperature has risen to the
manifold and heat exchanger. level required to open the engine thermostat. The thermo-
stat opens at approximately 170°F. The temperature will
Adequate pipe supports must be provided for the loop and stabilize and then decrease slightly. At this point, the regu-
outlet piping to minimize vibration and prevent excessive lator is adjusted between 15 and 20 PSI by turning the reg-
strain at the heat exchanger, pump and engine connec- ulator screw clockwise to increase the pressure and coun-
tions. terclockwise to reduce the pressure. The regulator screw is
then locked into place with the locknut provided.
Engine coolant should be added in accordance with the
engine manufacturer’s recommendations. MAINTENANCE
The regulator valve is adjusted during operational tests at the 2. If cooling water temperature changes, the regulator
plant and set between 15 and 20 PSI back pressure. If additional valve may require adjustment.