Ex d Surface Mount Ex d Trunnion Mount Ex de Surface Mount

Model G-SND

Global Series® Hazardous Location Sounder


Federal Signal Global Series® Sounders are available in explosion-proof Ex versions, increased safety Ex de wiring box
versions and are certified for gas Group IIC environments.
The Global Series Sounder can be wired to perform two separate functions. A single tone can be selected via a rotary
switch; once power is supplied, it will sound the selected tone. Alternatively, multiple tones can be selected remotely by
choosing the appropriate combination of inputs.1 This allows a unique sound to match a specific alarm condition or to be
used to escalate an alarm condition.
The Global Series sounder can be combined with all other Global Series audible and visual products in several custom
configurations. Custom configurations can be ordered directly from the factory. Optional coupling kits, which allow limited
field fixturing, are available.

F E A T U R E S

• Supports 3 operational voltages: 24VDC, • Two M20 entries standard on Ex d models, three M20 entries
120VAC 50/60Hz, and 230VAC 50/60Hz standard on Ex de models
• Optional 316 stainless steel ratchet adjustable • Type 4X, IP66 enclosure
mounting U-bracket (field installation required) • Zone 1, 21 Rated, IECEx, ATEX, Ex d IIC, Ex de IIC and Ex tb IIIC
• Gain control • UL and cUL Listed for Class I, Division 2, Groups A, B, C and D;
• Non-metallic corrosion resistant design Class II, Division 2, Groups F and G; Class III
• 15 watt design • UL and cUL Listed for Class I, Zone 1 AEx db IIC T4: Zone 21,
AEx tb IIIC T4/135°C)
• Field customizable legend plates available2
• UL Fire Listed (24VDC operating voltage ONLY)
• Optional indicator rings are available in six colors:
Black, Blue, Green, Magenta, Red and Yellow

1 Refer to application guide for specific wiring details


OPERATING NOMINAL DECIBELS4 2
MODEL Recommended labels: BRADY #B-855 Toughwash labels or
V O LTA G E OPERATING CURRENT3 10' 1M ULINE #S-16643 weather resistant
3 Operating current varies with frequency content and input
G-SND 24VDC 0.460 amps 100 110 power
4 Measured using on-board tone 9 at nominal input voltage
120/230VAC 50/60Hz 0.140/0.080 amps 100 110

UL/cUL HAZARDOUS LOCATION RATING UL/cUL HAZARDOUS LOCATION CLASS/ZONE


TEMPERTURE CODE AT 70°C TEMPERTURE CODE AT 70°C
T4
Class I, Division 2, Groups A, B, C, D T4
ATEX/IECEx HAZARDOUS LOCATION RATING
Class II, Division 2, Groups F, G T6
TEMPERTURE CODE AT 49°C TEMPERTURE CODE AT 70°C
Class III T6 T5 (in IIB) T4 (in IIB)
T4 (in IIC) T4 (in IIC)

Patent No. 9,886,832 B2

Num-
ber
Global Series® Hazardous Location Sounder (G-SND)
Audible Ex d Surface Mount Audible w/ U-Bracket Mount Audible Ex de Surface Mount

3X M20

8.23"/ 209.0 mm

8.23"/ 209.0 mm
8.23"/ 209.0 mm

gland
2X M20 entries
gland

3.25"/ 82.6 mm
entries

1.38"/
35.1 mm
3.08"/ 78.2 mm
5.22"/ 132.6 mm 10.72"/ 272.3 mm
U-bracket

8.47"/ 215.1 mm
ø 5.27"/ 133.9 mm mounting detail 2X ø.34"/ 8.6 mm

4.17"/ 105.9 mm
5.63"/ 143.0 mm
4.17"/ 105.9 mm

4.83"/122.7 mm
2X M6 screw hole
4X C’bored

2.36"/ 59.9 mm
holes to fit
M8 socket
head cap
screws

4.17"/ 105.9 mm 7.50"/ 190.6 mm 4.06"/ 4.17"/


103.1 mm 105.9 mm
1.25"/ 31.8 mm 4X C’bored holes to fit
M8 socket head cap screws

S P E C I F I C A T I O N S

Operating Temperature: -67ºF to 158ºF -55ºC to 70ºC Class II, Division 2, Groups F,G T6 @ 70°C
ATEX/IECEx Certification Marking: Class III T6 @ 70°C
Ex db IIB T5 Gb or Ex db e IIB T5 Gb UL and cUL E12629
Ex tb  IIIC  T100ºC Db IP66
Net Product Weight:
Ex db IIC T4 Gb or Ex db e IIC T4 Gb
Ex tb IIIC T135ºC Db IP66 Ex d Surface Mount 9.61 lbs 4.36 kg
ATEX: Baseefa15ATEX0155X Ex d U-Bracket Mount 11.59 lbs 5.26 kg
IECEx: IECEx BAS 15.0104X Ex de Surface Mount 12.43 lbs 5.64 kg
External Fasteners: 316 stainless steel
Terminals: Ex d: 11 way block R E P L A C E M E N T P A R T S
(3 in, 3 out with 4-tone selection terminals & select line)
Ex de: 3-pole, 4 position quad pole terminal blocks
Description Part Number
Cable Entries: Ex d: 2 entries - M20 x 1.5
Ex de: 3 entries - M20 x 1.5 Multi-voltage G-SND Sounder Kit (Includes PCBAs,
UL and cUL Certification Marking: Bracket, Driver, & Mounting Screws) K859501404
Class I, Division 2, Groups A,B,C,D T4 @ 70°C Accessories
E-Box Endcap with M20 Opening K859500805-02
E-Box Endcap with M25 Opening K859500805-01
H O W T O O R D E R E-Box Cover Assembly (Includes two terminal blocks,
mounting plate, retention hardware) K859501414
G - SND - MV - D Adapter, M20 Male to 1/2” Female NPT K231246A
Adapter, M20 Male to 3/4” Female NPT K231247
MODEL TYPE Indicate MV for
SND Sounder D & T configurations
MV Multi-voltage
Select a voltage for
CONFIGURATION * Field Installation Required
E configurations
024 24VDC D Ex d Surface Mount
120 120VAC T Ex d U-Bracket Mount*
230 220-240VAC E Ex de Surface Mount
#850000769 Rev. A0

2645 Federal Signal Dr., University Park, IL 60484 Tel: +1 708.534.4756 Email: signalsupport@fedsig.com www.fedsig.com
S2000 | 1222