Application profile:
Art
galleries
ReadySET air aspirating smoke detectors
A P P L I C AT I O N P R O F I L E 85000-0378
See ReadySET installation guide for configuration details. Issue 1
Sample Layout
E:10
P:5
H:9
P:3
H:4 H:5
P:4
H:3
P:2
H:6
H:2
H:7
E:8
H:1
P:1
Legend
Capillary tube
Sampling hole
End cap hole
Detector
The balance between sampling holes is 83.3%. The balance between sampling pipes is 100.0%.
Flow rate for this pipe is 57.10 liters per minute with the aspirator set to 1.
The total flow rate is 57.10 liters per minute.
Detector sensitivity is set to 0.40% obs/ft in the hole calculation options.
The detector type is ReadySET.
There are 0 holes on this pipe run excluding the endcap hole.
There are 8 capillaries on this pipe run.
This pipe run length is 122.00 feet.
The total pipe length is 122.00 feet.
Technical Specifications
ReadySET Air Sampling Smoke Detector
Supply Voltage 22.25V - 26.4V
Current consumption 350 mA
7.5" W x 9.0" H x 4.3" D
Size
(190 mm W x 230 mm H x 110 mm D)
Weight 2.65 lbs. (1.2 kg)
Operating temperature range 32 ° to 100 °F (0 ° to 38 °C), UL 268 compliant
Operating humidity range 0 - 90% Non Condensing
Coverage area 2,500 sq. ft. (232 sq. m)
Sensitivity range (Obs/ft) 0.12% to 7.62% obs/ft. (0.4% to 25% obs/m)
Maximum sensitivity resolution 0.12% obs/ft. (0.4% obs/m)
Detection principle Laser light scattering mass detection
Particle sensitivity range 0.0003 μm to 10 μm
Relay contact rating 1 A @ 24 Vdc resistive load
Sampling pipe inlets 1
Sampling pipe internal diameter 3/4" (20 mm)
Alarm Fault Relays Alarm, Pre-Alarm, and Fault
Chamber service intervals Greater than eight years (depending on environment)
Dust separator (filter) replacement intervals Greater than five years (depending on environment)
Laser lifetime (MTTF) Greater than 1,000 years
Programming Internal DIP Switches
Enclosure NEMA-1
See Data Sheet 85001-0627 for product details and ordering information.
Environmental Compensation
The Initial 15-minute learning
process provides a starting
point for environmental Sensitivity is maintained
compensation. During the first 24-hours, regardless of changes in
ReadySET operates at a de- ambient conditions.
creased sensitivity and adjusts
% obscuration / ft
Time