85000-0378 - ReadySET Application Profile, Art Galleries

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Architecturally Sensitive Sites

Application profile:

Art
galleries
ReadySET air aspirating smoke detectors

Concealed Detection: Hidden in plain sight. Retain your unique


There are applications where “out of sight, out of mind” is an essential element of suc- design characteristics
cessful smoke detection. Architectural considerations frequently call for walls and ceilings
unblemished by spot detectors and wiring conduits. In other instances, the risk of tamper- ReadySET is particularly well-suited to
ing can be greatly reduced by reducing the visibility of smoke detection equipment within refined architectural settings, such as
the protected space.
art galleries and even high-end com-
ReadySET air aspirating smoke detectors draw a continuous air sample through a single
mercial and residential properties, or
or branched sampling pipe network. This network can run discreetly behind or within ar-
chitectural elements and terminate with flexible capillary tubes a mere 10 mm in diameter. any location where there is a need to
Capillary sampling provides an effective and affordable means of strategically locating the preserve unique design characteristics.
actual sample ports away from the main pipe trunk. Ports may be either finished flush or
otherwise concealed in ceiling or wall features. ReadySET provides a practical solution
because the sampling pipe network can
Sampling pipe may be up to 164 ft (50 m) in length with as many as ten individual sam-
pling points per detector. According to NFPA 72, for purpose and placement and spacing, run discreetly behind walls and above
each ReadySET sampling point is the equivalent of a spot-type smoke detector. Transport architectural features such as lighting
time from the furthest sampling point on a pipe branch cannot exceed 120 seconds.
valences and crown moldings. The use
Unlike traditional spot detection, ReadySET sampling points do not require electrical
of flush-terminated capillary sampling
devices, power, wiring, or junction boxes. In fact, annual testing need only be carried out
at the detector base unit and at the sampling point furthest from it. further conceals sampling points, re-
In addition, the ReadySET detector remains within reach, regardless of how inaccessible ducing them to openings no bigger than
the sampling points are. This permits maintenance to be carried out and electrical con- a pencil.
nections to be made in a convenient location away from the protected space.

Where to use ReadySET


• Art Galleries
• High-End Residential
• Heritage Buildings
• Hotel Lobbies
• Museums

A P P L I C AT I O N P R O F I L E 85000-0378
See ReadySET installation guide for configuration details. Issue 1
Sample Layout

E:10
P:5
H:9

P:3

H:4 H:5

P:4

H:3

P:2
H:6

H:2

H:7

E:8
H:1

P:1

Legend

Capillary tube
Sampling hole
End cap hole
Detector

Page 2 of 4 D ATA S H E E T 85000-0378


See ReadySET installation guide for configuration details. Issue 1
Sample Layout Specifications

Hole Hole size Flow Flow Transit time Hole sensitivity


number (inches) (liter/min) percentage (seconds) (% obs/ft)
1 9/64 6.08 10.6% 1.7 3.75
2 9/64 5.74 10.1% 3.2 3.97
3 9/64 5.41 9.5% 5.1 4.21
4 9/64 5.19 9.1% 6.7 4.39
5 9/64 4.71 8.2% 14.4 4.84
6 9/64 4.58 8.0% 17.4 4.98
7 9/64 4.49 7.9% 20.7 5.07
8 5/32 7.37 12.9% 23.1 3.09
9 9/64 5.1 8.9% 8.9 4.47
10 5/32 8.4 14.7% 9.9 2.71

The balance between sampling holes is 83.3%. The balance between sampling pipes is 100.0%.
Flow rate for this pipe is 57.10 liters per minute with the aspirator set to 1.
The total flow rate is 57.10 liters per minute.
Detector sensitivity is set to 0.40% obs/ft in the hole calculation options.
The detector type is ReadySET.
There are 0 holes on this pipe run excluding the endcap hole.
There are 8 capillaries on this pipe run.
This pipe run length is 122.00 feet.
The total pipe length is 122.00 feet.

Technical Specifications
ReadySET Air Sampling Smoke Detector
Supply Voltage 22.25V - 26.4V
Current consumption 350 mA
7.5" W x 9.0" H x 4.3" D
Size
(190 mm W x 230 mm H x 110 mm D)
Weight 2.65 lbs. (1.2 kg)
Operating temperature range 32 ° to 100 °F (0 ° to 38 °C), UL 268 compliant
Operating humidity range 0 - 90% Non Condensing
Coverage area 2,500 sq. ft. (232 sq. m)
Sensitivity range (Obs/ft) 0.12% to 7.62% obs/ft. (0.4% to 25% obs/m)
Maximum sensitivity resolution 0.12% obs/ft. (0.4% obs/m)
Detection principle Laser light scattering mass detection
Particle sensitivity range 0.0003 μm to 10 μm
Relay contact rating 1 A @ 24 Vdc resistive load
Sampling pipe inlets 1
Sampling pipe internal diameter 3/4" (20 mm)
Alarm Fault Relays Alarm, Pre-Alarm, and Fault
Chamber service intervals Greater than eight years (depending on environment)
Dust separator (filter) replacement intervals Greater than five years (depending on environment)
Laser lifetime (MTTF) Greater than 1,000 years
Programming Internal DIP Switches
Enclosure NEMA-1
See Data Sheet 85001-0627 for product details and ordering information.

Page 3 of 4 D ATA S H E E T 85000-0378


See ReadySET installation guide for configuration details. Issue 1
ReadySET technology extends the range
of applications far beyond that normally
Contact us...
associated with aspirated smoke detection...
Email: edwards.fire@fs.utc.com
Web: www.est-fire.com ReadySET is ideal for
Laser Dust Discrimination
EST is an EDWARDS brand.
small, localized and
1016 Corporate Park Drive
discrete applications
Mebane, NC 27302 where air aspirating Laser signal
Average 1
shows steady
In Canada, contact Chubb Edwards... smoke detection is output due to
smoke and Sensor signal
Email: inquiries@chubbedwards.com desired. It fits nicely spikes due to smoke & dust
Web: www.chubbedwards.com
where spot detection dust particles.
This application profile is for and beam detection
information only and is not intended
as a substitute for authorized are problematic.
installation guides or verbatim
legislated requirements. For detailed Because aspirated
Spikes are Average 2
configuration and setup instructions, air sampling actively electronically
consult the ReadySET Installation eliminated Sensor signal
Guide. For authoritative specifications draws air into the from detector
dust eliminated

regarding the application of life safety detector instead of signal


systems, consult current editions
of applicable codes and standards.
relying on convec-
The remaining steady output represents underlying smoke density
For interpretation of those codes tion currents, it tends
and standards, consult your local to provide a quicker Laser Dust Discrimination employs a sophisticated algorithm that identifies
authority having jurisdiction. and eliminates spikes in the obscuration reading caused by particulate mat-
reaction to incipient ter in the airstream. This makes it possible for ReadySET detectors to reach
Contents © 2013 UTC Fire &
Security Americas Corporation, Inc.
(developing) indicators higher levels of sensitivity without sacrificing reliability – a perennial trade-off
All rights reserved. Specifications of combustion. among competing products.
subject to change without notice.
Edwards is part of UTC Climate, Waste Gate Technology is a powerful ReadySET advantage that
Controls & Security, a unit of United dramatically extends the life of its particulate filters. This exclusive aspiration
Technologies Corporation. technique diverts most of the particulate matter that would normally load the
detector filters, giving ReadySET longer life and more capacity per maintenance
cycle than any such detector on the market today.

Environmental Compensation
The Initial 15-minute learning
process provides a starting
point for environmental Sensitivity is maintained
compensation. During the first 24-hours, regardless of changes in
ReadySET operates at a de- ambient conditions.
creased sensitivity and adjusts
% obscuration / ft

to the most stable level using


Smoke Density

the ClassiFire algorithm.

15 Minutes 1st 24 Hours


1 Month1 Year

Time

Environmental compensation – a first among such devices – opens the door


to projects that prove impractical for competing detectors. Self-calibration
and sliding alarm thresholds liberate ReadySET from areas where air
handling is strictly controlled, making them ideal for public commercial areas
– as well as dust and contaminant-laden industrial settings. All this while
remaining highly sensitive to incipient indicators of fire yet reliable enough to
all but eliminate nuisance alarms.
07-01-13

Page 4 of 4 D ATA S H E E T 85000-0378


See ReadySET installation guide for configuration details. Issue 1