Phasor Modeling Approaches and Simulation Guidelines of Voltage-Source Converters in Grid-Integration Studies
Phasor Modeling Approaches and Simulation Guidelines of Voltage-Source Converters in Grid-Integration Studies
19, 2022.
Digital Object Identifier 10.1109/ACCESS.2022.3174958
ABSTRACT With the large integration of converter-interfaced generation (CIG) and widespread of power
electronic interfaced technologies, power system dynamic behaviour is becoming progressively faster. As a
consequence, is often unclear when to use EMT or Phasor models in grid integration studies. Therefore,
this paper presents useful simulation guidelines of Voltage-Source Converters (VSCs) used in AC grid
integration studies. It also presents several EMT and Phasor models suited to simulate CIG and renewable
energy resources connected to power systems. Several modelling approaches and suitability analyses were
provided based on a comprehensive comparative study among the models. Various studies were performed
in a small system, composed of two generators, and a CIGRE benchmark system, both modelled in Simulink.
We address a gap related to the suitability of CIGs phasor models in studies where the boundary between
electromagnetic and electromechanical transients overlap. An insightful analysis of the adequate simulation
time step for each model and study is also provided.
This work is licensed under a Creative Commons Attribution 4.0 License. For more information, see https://creativecommons.org/licenses/by/4.0/
51826 VOLUME 10, 2022
V. A. Lacerda et al.: Phasor Modeling Approaches and Simulation Guidelines of VSCs in Grid-Integration Studies
dq+ dq−
(Ic and Ic ) are the ones described by the Laplace trans- However, it neglects completely the dynamics of the current-
form of (2), as follows control. Thus, this model should be used in studies where
these dynamics are not especially relevant.
Icd+? = (vd+ d+?
g − vc + ωg LIcq+ )/(R + sL) (14) Moreover, neglecting the time constant of the inner loop
Icq+? = (vq+ q+?
g − vc − ωg LIcd+ )/(R + sL) (15) also affects the total (inner + outer) closed-loop response.
To maintain the new closed-loop time constant equal to the
Icd−? = (vd− d−?
g − vc − ωg LIcq− )/(R + sL) (16)
original closed-loop time constant we define:
Icq−? = (vq− q−?
g − vc + ωg LIcd− )/(R + sL) (17)
Gpq (s) 1
where superscript ? means the reference signal and ωg is the Cpq (s) = = (19)
1 + Gpq (s) 1 + τpq s
grid frequency. Using this approach, the complete control
structure used in EMT simulations is preserved (see Fig. 2), where τpq = 1/ωpq is the original closed-loop time constant
which facilitates comparison between PM and EMT. in (9), Cpq (s) is the new close-loop transfer function and
Gpq (s) is the new open-loop transfer function, defined as
B. PHASOR MODEL I1 3
In this model, the VSC inner control is substituted by a first Gpq (s) = Kpq (s) vqg (20)
2
order transfer function with time constant τc , defined to match
the original closed-loop bandwidth: where Kpq (s) is the new controller transfer function.
Solving (19) for Kpq (s) yields:
1
τc = (18) 2 1
ωc Kpq (s) = q (21)
3vg τpq s
With this approximation, the DSRF closed-control structure
is removed, including the cross-coupling term ωg L. As a Thus, to have the same time constant, the original PI con-
consequence, the inner-loop output becomes the low-pass fil- troller is substituted by an integrator with a gain equal
q q
tered (τc ) current reference defined by the outer-loop control, to 2/(3vg τpq ). As vg is variable, it is often useful to consider a
q
which is transformed to the abc frame and sent to the current static gain by using Vg,pk ≈ vg . Note that in this structure, the
source. signal sent to the integrator is the error between the reference
and the measured power output, hence a closed-loop.
C. PHASOR MODEL I0
In this model, the VSC inner control is completely removed. D. PHASOR MODEL PQ1
As the inner control is the fastest dynamics of the VSC (when Further simplification can be achieved if the outer-loop is
neglecting the switching), removing this loop allows bigger substituted by a first-order transfer function with the same
time steps to be used, which greatly speeds up simulations. time constant (τpq ) as the original loop, similar to PM I1 .
IV. METHODOLOGY
In order to assess the aforementioned models, various studies
were performed in a small system and a CIGRE bench-
mark HV system, modelled in Simulink. The small system
was composed of a synchronous generator, a transmission
line and a VSC. The CIGRE system was composed of four
synchronous generators, eight transmission lines and two
VSCs. The CIGRE system was based on the European HV
transmission system in [32], with a few adaptations. Both
systems were simulated using a fixed time step and the V. SIMULATION RESULTS
Euler method (algorithm ode1 in Matlab). The single-line This section presents the simulation results, followed by brief
diagrams of the both systems are depicted in Fig. 3 and discussions. Due to the extensive number of tests, only a
Fig. 4, and their parameters are summarized in Table 2, in the portion of the cases and variables are presented, which are
Appendix. representative of each test.
For all tests, the EMT AVG model running at 5 µs was
defined as the reference model, while the phasor models A. SMALL SYSTEM
and the AVG EMT model running at bigger time steps 1) SETPOINT TRACKING
were compared against the reference model. The EMT SW In this test, active and reactive power setpoints were set to
model was not used as the reference model because the high 50 MW and 30 Mvar at t = 0.6 s and t = 0.8 s, respectively.
frequency components present in the currents and voltages Negative-sequence control and LVRT were disabled during
would equally increase the RMSE in all models, thus pre- this test, as well as frequency and voltage droop. Fig. 5
cluding a precise comparison among them. presents the converter currents for all models with a time step
Three key aspects were analysed for each model: of 25 µs, 250 µs and 2500 µs, respectively.
i) Precision, ii) Minimum simulation time step and iii) Total As can be observed, for smaller time steps, both EMT and
execution time. PM models presented very similar results. However, as the
The precision was quantified using the Root-Mean-Square simulation time step increases, the models that represent
Error (RMSE) between the variables simulated using each faster dynamics starts to deviate from the reference until
model and the variables simulated using the reference they completely diverge. This can be better visualized by
model: varying the simulation time step between 5 µs and 12000 µs,
v
u N
as shown in Fig. 6.
u1 X 2 As can be observed in this test, the PM PQ1 model is worse
RMSE = t xref (k) − x̂(k) (23)
N than the other models for small time steps but its precision
k=1
gets similar to the others for bigger time steps. Although the
where k is the sample, N is the time window length, xref is PM I1 and I0 approximate or neglect the current loop, they
a variable in the reference model and x̂ is the same variable presented low error because their dynamics are smoothed by
in the model being assessed. In this study, the RMSE was the outer loop, which is slower.
divided by a proper base in each study, to present the results When the simulation time step gets closer to the model’s
in a meaningful scale. fastest dynamics, the error increases dramatically. In the
The minimum simulation time step was defined as the system of Fig. 3, the fastest dynamics are related to the
time step necessary to capture all the system dynamics and VSC current control loop, which have a time constant equal to
phenomena being analysed, which was assessed using the 1/ωc = 1.18 ms. This is evident in Fig. 7a that shows the PM
precision. full model error for several current control bandwidths. As the
The total execution time was defined as the time necessary bandwidth increases, the maximum simulation time step to
to run each study. achieve low errors reduces proportionally. However, much
Table 1 summarizes the tests performed in both systems. higher time steps can be used (Fig. 7b) when performing the
FIGURE 7. Test 1 – Pac RMSE for several time steps and power control
bandwidths. a) PM full and b) PM I0 model.
FIGURE 9. Test 2 – Te simulated by each model at 25 µs. FIGURE 11. Test 3 – Ib simulated by each model at 350 µs.
FIGURE 10. EMT and PM models simulation times for several time steps.
FIGURE 15. Test 4 – Te simulated by each model at 350 µs. FIGURE 18. Test 5 – Pac simulated by each model at 850 µs.
FIGURE 19. Test 5 – Pac setpoint tracking RMSE simulated by each model
intrinsic in the DSC in EMT [31] or in any other filtering- at several time steps.
based method.
FIGURE 20. Test 1 large system – i d + simulated by each model at 850 µs.
FIGURE 21. Test 1 CIGRE system – i d + RMSE simulated by each model at FIGURE 24. Test 3 CIGRE system – VSC 1 i d + simulated by each model
several time steps. at 850 µs.
FIGURE 22. Test 2 CIGRE system – VSC 1 Pac simulated by each model FIGURE 25. Test 3 CIGRE system – VSC 1 Pac simulated by each model
at 750 µs. at 700 µs.
3) LINE OUTAGE
In this test, a permanent 1 single-phase fault at phase C FIGURE 27. Test 3 CIGRE system – SG 2 Ic simulated by each model
was applied to the line connecting bus 1 to bus 3. The line at 650 µs.
was isolated by two circuit breakers, that opened 200 ms and
250 ms after the fault, respectively, producing a transient in C. ADDITIONAL TESTS
the system. In addition to the tests shown in the previous subsections,
After each transient (fault, first breaker opening and second further simulations regarding specific tests were performed
breaker opening) it is possible to observe in Fig. 24 and in more detail and are presented next.
Fig. 25 that the difference between EMT and most PM models
was high only for about 30 ms. The same is not true for the 1) PLL DYNAMICS
most approximated PM PQ1 , which took about 100 ms to A growing concern about the PLL dynamics has been
match the EMT model after each event. observed in recent years as they are often involved
FIGURE 31. Converter current iq+ during the connection of a new load.
To confirm the accuracy of (24), a phase jump test was per- Phasor models with and without equivalent PLL.
formed both in EMT and in Phasor, and is shown in Fig. 29.
VII. CONCLUSION
time step is chosen, the simulation speed can be increased
This paper reviewed EMT and phasor models currently used
in one or two orders of magnitude (as shown in Fig. 10),
to simulate VSC in grid integration studies. Several modelling
transforming hours of simulation in minutes. This allows
guidelines and suitability analyses were provided based on
larger models to be simulated or a higher number of tests
a comprehensive comparative study amongst the models.
to be performed in a feasible time. Another advantage of
We addressed a gap related to the suitability of phasor models
PMs is a more straightforward interpretation of the results.
in studies where the boundary between electromagnetic and
Analysing current and voltage phasors is more simple than
electromechanical domains were overlapped. An insightful
their waveforms. Thus, using PM models can also contribute
analysis of the adequate simulation time step for each model
to increase the level of understanding of the simulation and
and study was provided. The recommendations were based
consequently speed up the post-simulation time, where the
on a systematic comparison amongst the models in several
analysis and interpretation of the results are performed.
different scenarios.
However, one must carefully analyse if the chosen PM
From the tests performed, it could be observed that the
is able to represent well the set of studies to be performed.
major advantage of PMs is the possibility to increase the
The results presented in the previous sections show that tests
simulation time step and reduce the execution time. Another
involving electromechanical transients and non-solid sym-
advantage is a more straightforward interpretation of the
metrical faults are well represented by PM models. However,
results when compared to detailed waveforms in EMT. How-
asymmetrical faults and symmetrical faults that drops voltage
ever, the set of studies to be performed by PMs must be
near to zero dramatically influence converters’ PLLs. As all
carefully analysed. As the PMs consider some idealistic con-
PM models consider an ideal PLL, their results might be
ditions, e.g an ideal PLL, their results might be mistakenly
mistakenly optimistic in these cases. The equivalent PLL
optimistic in cases involving large transients.
shown in subsection V-C1 can also be considered, but as the
The recommendations provided aim to contribute to the
grid’s dynamics are not modelled in phasor, they will not
discussion about the most suitable models of modern power
be captured by the equivalent PLL, even if it is precisely
grids, where the widespread of power electronic interfaced
modelled. In all cases, the PMs took about 100 ms to closely
technologies and the reduced inertia are making the grid’s
track EMT models (this time vary depending on the system
dynamic behaviour to become progressively faster.
equivalent X/R ratio). Thus, in the simulated systems, tran-
sients faster than 100 ms might not be correctly represented
by PMs. APPENDIX
Another important aspect to be considered in both EMT TEST SYSTEMS PARAMETERS
and phasor simulation is the choice of the simulation time The SGs parameters of the CIGRE system are summarized
step. Choosing an arbitrary low time step will lead to an in Table 2. The SG parameters of the small system are equal
unnecessary slow simulation. Choosing an arbitrary high time to G1 in the CIGRE system, but with nominal power equal
step might lead to inaccurate results or numerical instability. to 400 MVA. The transmission lines parameters at 50 Hz
Based on the results of the previous section, we recommend are: R1 = 0.121 /km, R0 = 0.446 /km, L1 = 1.33mH/km,
that the simulation time step should be between five and ten L0 = 3.73mH/km, C1 = 8.762 nF/km and C0 = 6.373 nF/km.
TABLE 2. CIGRE system parameters - Synchronous generators. [8] M. S.-P. Hwang and A. R. Wood, ‘‘A new modelling framework for power
supply networks with converter based loads and generators—The harmonic
state-space,’’ in Proc. IEEE Int. Conf. Power Syst. Technol. (POWERCON),
Oct. 2012, pp. 1–6.
[9] M. S.-P. Hwang and A. R. Wood, ‘‘Harmonic state-space modelling of a
controlled HVdc converter,’’ Electr. Power Syst. Res., vol. 124, pp. 65–73,
Jul. 2015.
[10] J. Kwon, X. Wang, F. Blaabjerg, C. L. Bak, V.-S. Sularea, and C. Busca,
‘‘Harmonic interaction analysis in a grid-connected converter using har-
monic state-space (HSS) modeling,’’ IEEE Trans. Power Electron., vol. 32,
no. 9, pp. 6823–6835, Sep. 2017.
[11] D. Shu, H. Yang, and G. He, ‘‘A harmonic phasor domain cosimula-
tion method and new insight for harmonic analysis of large-scale VSC-
MMC based AC/DC grids,’’ IEEE Trans. Power Electron., vol. 36, no. 4,
pp. 3909–3924, Apr. 2021.
[12] F. Milan and Á. O. Manjavacas, ‘‘Frequency-dependent model for transient
stability analysis,’’ IEEE Trans. Power Syst., vol. 34, no. 1, pp. 806–809,
Jan. 2019.
[13] S. D’Arco, J. A. Suul, and J. Beerten, ‘‘Configuration and model order
selection of frequency-dependent π models for representing DC cables in
The parameters of the converters are summarized in small-signal eigenvalue analysis of HVDC transmission systems,’’ IEEE
J. Emerg. Sel. Topics Power Electron., vol. 9, no. 2, pp. 2410–2426,
Table 3. The converter used in the small system has the same Apr. 2021.
parameters as the VSC 1 shown in Table 3. [14] V. Jalili-Marandi, V. Dinavahi, K. Strunz, J. A. Martinez, and A. Ramirez,
‘‘Interfacing techniques for transient stability and electromagnetic tran-
sient programs IEEE task force on interfacing techniques for simulation
TABLE 3. Converters parameters. tools,’’ IEEE Trans. Power Del., vol. 24, no. 4, pp. 2385–2395, Oct. 2009.
[15] Y. Zhang, A. M. Gole, W. Wu, B. Zhang, and H. Sun, ‘‘Development
and analysis of applicability of a hybrid transient simulation platform
combining TSA and EMT elements,’’ IEEE Trans. Power Syst., vol. 28,
no. 1, pp. 357–366, Feb. 2013.
[16] A. A. V. D. Meer, M. Gibescu, M. A. M. M. V. D. Meijden, W. L. Kling,
and J. A. Ferreira, ‘‘Advanced hybrid transient stability and EMT simu-
lation for VSC-HVDC systems,’’ IEEE Trans. Power Del., vol. 30, no. 3,
pp. 1057–1066, Jun. 2015.
[17] P. Zadkhast, X. Lin, F. Howell, B. Ko, and K. Hur, ‘‘Practical chal-
lenges in hybrid simulation studies interfacing transient stability and
electro-magnetic transient simulations,’’ Electr. Power Syst. Res., vol. 190,
Jan. 2021, Art. no. 106596.
[18] S. Cole, J. Beerten, and R. Belmans, ‘‘Generalized dynamic VSC MTDC
model for power system stability studies,’’ IEEE Trans. Power Syst.,
vol. 25, no. 3, pp. 1655–1662, Aug. 2010.
[19] B. Berggren, R. Majumder, and N. Johansson, ‘‘A generic VSC HVDC
primary control structure suitable for stability studies,’’ in Proc. EPRI
HVDC FACTS Conf., 2013, pp. 1–8.
REFERENCES [20] N. Trinh, M. Zeller, K. Wuerflinger, and I. Erlich, ‘‘Generic model of
MMC-VSC-HVDC for interaction study with AC power system,’’ IEEE
[1] P. Kundur, J. Paserba, V. Ajjarapu, G. Andersson, A. Bose, C. Canizares,
Trans. Power Syst., vol. 31, no. 1, pp. 27–34, Jan. 2016.
N. Hatziargyriou, D. Hill, A. Stankovic, C. Taylor, T. Van Cutsem,
and V. Vittal, ‘‘Definition and classification of power system stability [21] G. De Carne, M. Liserre, M. Langwasser, M. Ndreko, R. Bachmann,
IEEE/CIGRE joint task force on stability terms and definitions,’’ IEEE R. W. De Doncker, R. Dimitrovski, B. J. Mortimer, A. Neufeld, and
Trans. Power Syst., vol. 19, no. 2, pp. 1387–1401, Aug. 2004. F. Rojas, ‘‘Which deepness class is suited for modeling power electronics?:
A guide for choosing the right model for grid-integration studies,’’ IEEE
[2] N. Hatziargyriou, J. Milanovic, C. Rahmann, V. Ajjarapu, C. Canizares,
Ind. Electron. Mag., vol. 13, no. 2, pp. 41–55, Jun. 2019.
I. Erlich, D. Hill, I. Hiskens, I. Kamwa, B. Pal, P. Pourbeik,
J. Sanchez-Gasca, A. Stankovic, T. V. Cutsem, V. Vittal, and C. Vournas, [22] M. Paolone, T. Gaunt, X. Guillaud, M. Liserre, S. Meliopoulos, A. Monti,
‘‘Definition and classification of power system stability revisited & T. Van Cutsem, V. Vittal, and C. Vournas, ‘‘Fundamentals of power sys-
extended,’’ IEEE Trans. Power Syst., vol. 36, no. 4, pp. 3271–3281, tems modelling in the presence of converter-interfaced generation,’’ Electr.
Jul. 2021. Power Syst. Res., vol. 189, Dec. 2020, Art. no. 106811.
[3] S. R. Sanders, J. M. Noworolski, X. Z. Liu, and G. C. Verghese, ‘‘General- [23] Technical Brochure 604: Guide for the Development of Models for HVDC
ized averaging method for power conversion circuits,’’ IEEE Trans. Power Converters in a HVDC Grid, CIGRE Working Group B4-57, Paris, France,
Electron., vol. 6, no. 2, pp. 251–259, Apr. 1991. 2014.
[4] T. Demiray and G. Andersson, ‘‘Simulation of power systems dynamics [24] S. S. Khan and E. Tedeschi, ‘‘Modeling of MMC for fast and accurate
using dynamic phasor models,’’ in Proc. 10th Symp. Spec. Electr. Oper. simulation of electromagnetic transients: A review,’’ Energies, vol. 10,
Expansion Planning (SEPOPE), May 2006, pp. 1–9. no. 8, p. 1161, 2017.
[5] M. Daryabak, S. Filizadeh, J. Jatskevich, A. Davoudi, M. Saeedifard, [25] W. Lu and B.-T. Ooi, ‘‘Optimal acquisition and aggregation of offshore
V. K. Sood, J. A. Martinez, D. Aliprantis, J. Cano, and A. Mehrizi-Sani, wind power by multiterminal voltage-source HVDC,’’ IEEE Trans. Power
‘‘Modeling of LCC-HVDC systems using dynamic phasors,’’ IEEE Trans. Del., vol. 18, no. 1, pp. 201–206, Jan. 2003.
Power Del., vol. 29, no. 4, pp. 1989–1998, Aug. 2014. [26] H.-S. Song and K. Nam, ‘‘Dual current control scheme for PWM converter
[6] G. N. Love and A. R. Wood, ‘‘Harmonic state space model of power under unbalanced input voltage conditions,’’ IEEE Trans. Ind. Electron.,
electronics,’’ in Proc. 13th Int. Conf. Harmon. Quality Power, Sep. 2008, vol. 46, no. 5, pp. 953–959, Oct. 1999.
pp. 1–6. [27] S. Golestan, J. M. Guerrero, and J. C. Vasquez, ‘‘Three-phase PLLs:
[7] J. Arrillaga and N. R. Watson, ‘‘The harmonic domain revisited,’’ in Proc. A review of recent advances,’’ IEEE Trans. Power Electron., vol. 32, no. 3,
13th Int. Conf. Harmon. Quality Power, Sep. 2008, pp. 1–9. pp. 1894–1907, Mar. 2017.
[28] S.-K. Chung, ‘‘A phase tracking system for three phase utility interface EDUARDO PRIETO ARAUJO (Senior Member,
inverters,’’ IEEE Trans. Power Electron., vol. 15, no. 3, pp. 431–438, IEEE) received the degree in industrial engineer-
May 2000. ing from the School of Industrial Engineering of
[29] L. Harnefors and H.-P. Nee, ‘‘Model-based current control of AC machines Barcelona (ETSEIB), Technical University of Cat-
using the internal model control method,’’ IEEE Trans. Ind. Appl., vol. 34, alonia (UPC), Barcelona, Spain, in 2011 and the
no. 1, pp. 133–141, Jan./Feb. 1998. Ph.D. degree in electrical engineering from the
[30] C. Bajracharya, M. Molinas, J. A. Suul, and T. M. Undeland, ‘‘Under- UPC, in 2016. He joined CITCEA-UPC Research
standing of tuning techniques of converter controllers for VSC-HVDC,’’ in
Group, in 2010, and he is currently a Serra Hunter
Proc. Nordic Workshop Power Ind. Electron. (NORPIE), Espoo, Finland,
Lecturer with the Electrical Engineering Depart-
Jun. 2008, pp. 1–8.
[31] J. Svensson, M. Bongiorno, and A. Sannino, ‘‘Practical implementation of ment, UPC. Since 2021, he has been a Visiting
delayed signal cancellation method for phase-sequence separation,’’ IEEE Professor at the Automatic Control Laboratory, ETH Zurich. His main
Trans. Power Del., vol. 22, no. 1, pp. 18–26, Jan. 2007. interests include renewable generation systems, control of power converters
[32] Technical Brochure 575: Benchmark Systems for Network Integration of for HVDC applications, interaction analysis between converters, and power
Renewable and Distributed Energy Resources, CIGRE Task Force C6-04, electronics dominated power systems.
Paris, France, 2014.
[33] H. N. V. Pico and B. B. Johnson, ‘‘Transient stability assessment of
multi-machine multi-converter power systems,’’ IEEE Trans. Power Syst.,
vol. 34, no. 5, pp. 3504–3514, Sep. 2019.
[34] E. Robles, S. Ceballos, J. Pou, J. L. Martín, J. Zaragoza, and P. Ibañez,
‘‘Variable-frequency grid-sequence detector based on a quasi-ideal low-
pass filter stage and a phase-locked loop,’’ IEEE Trans. Power Electron.,
vol. 25, no. 10, pp. 2552–2563, Oct. 2010.
[35] F. Gonzalez-Espin, E. Figueres, and G. Garcera, ‘‘An adaptive
synchronous-reference-frame phase-locked loop for power quality
improvement in a polluted utility grid,’’ IEEE Trans. Ind. Electron.,
vol. 59, no. 6, pp. 2718–2731, Jun. 2012.
[36] M. Karimi-Ghartemani, ‘‘Linear and pseudolinear enhanced phased-
locked loop (EPLL) structures,’’ IEEE Trans. Ind. Electron., vol. 61, no. 3,
pp. 1464–1474, Mar. 2014.
[37] I. Serban and C. Marinescu, ‘‘Control strategy of three-phase battery MARC CHEAH-MAÑE (Member, IEEE) received
energy storage systems for frequency support in microgrids and with the degree in industrial engineering from the
uninterrupted supply of local loads,’’ IEEE Trans. Power Electron., vol. 29, School of Industrial Engineering of Barcelona
no. 9, pp. 5010–5020, Sep. 2014. (ETSEIB), Universitat Politecnica de Catalunya
[38] M. G. Taul, X. Wang, P. Davari, and F. Blaabjerg, ‘‘Robust fault ride (UPC), Barcelona, Spain, in 2013, and the Ph.D.
through of converter-based generation during severe faults with phase degree in electrical engineering from Cardiff Uni-
jumps,’’ IEEE Trans. Ind. Appl., vol. 56, no. 1, pp. 570–583, Jan. 2020. versity, Cardiff, U.K., in 2017. From 2017 to 2020,
[39] H. Dommel, ‘‘Digital computer solution of electromagnetic transients he was a Research Associate with the CITCEA-
in single-and multiphase networks,’’ IEEE Trans. Power App. Syst., UPC, Barcelona. Since March 2020, he has been a
vol. PAS-88, no. 4, pp. 388–399, Apr. 1969. Serra Hunter Lecturer at the Electrical Engineering
[40] J. C. G. de Siqueira, B. D. Bonatto, J. R. Marti, J. A. Hollman, and Department, UPC. His research interests include power systems with power
H. W. Dommel, ‘‘Optimum time step size and maximum simulation time in
electronics, high-voltage direct current systems, and wind and photovoltaic
EMTP-based programs,’’ in Proc. Power Syst. Comput. Conf., Aug. 2014,
generation.
pp. 1–7.
[41] S. Henschel, ‘‘Analysis of electromagnetic and electromechanical power
system transients with dynamic phasors,’’ Ph.D. dissertation, Fac. Appl.
Sci., Dept. Elect. Comput. Eng., Univ. British Columbia, Vancouver, BC,
Canada, 1999.
[42] N. Watson and J. Arrillaga, Power Systems Electromagnetic Transients
Simulation, 2nd ed. London, U.K.: IET, 2018.