NATIONAL GRID

Title: Index Number:


CL-NG-6460-002-030
Check Lest of Metal Enclosed Bus Duct Commissioning Page Number:
1 of 3

1.0 Equipment General Data and Information

Substation
Bay/Panel
Equipment Serial No
2.0 Mechanical Checks and Visual Inspections

Item Description Done Remarks

1. Inspect for physical damage or defects.


Check bus arrangement for conformance with approved
2.
drawings.
Check tightness of all bolted connections (torque wrench
3.
method).
4. Check that all enclosure grounding is securely connected.
Inspect internal compartments for cleanliness (free from dust
5.
and moisture).
Check for watertight seals at joints including expanding
6.
interface points.
Check bus conductor support insulators for cracked
7.
insulation, chipped porcelain, etc.
8. Check quality of paint work (inside and outside).
Check that ventilation opening are not blocked, and meet
9.
specified Degree of Protection.
10. Moisture drain holes available at bottom of enclosure.
Check anti-condensation heaters mounted at the correct
11.
locations (bottom)

Archiving System Website: http://AMAS


NATIONAL GRID

Title: Index Number:


CL-NG-6460-002-030
Check Lest of Metal Enclosed Bus Duct Commissioning Page Number:
2 of 3

3.0 Electrical Tests

Item Description Done Remarks


1. Perform phasing checks. Ensure correct phase identification.
2. Perform continuity check.
3. Bus joint resistance test by 100 ampere DC Test
4. Insulation resistance test
5. Heaters and thermostats functional test. Measure the heater
currents. Ensure that the heater circuit switched off
automatically, when bus is energized (thermostatically control).
6. HV test (to ground and between phases).

CSD Contractor T&C Contractor


Name
Sign.