NATIONAL GRID

Title: Index Number:


CL-NG-6460-002-059
Check List of Auxiliary Relays Commissioning Page Number:
1 of 4

1.0 Equipment General Data and Information

Substation
Bay/Panel
Equipment Serial No
2.0 General Mechanical Checks and Visual Inspection

Item Description Done Remarks


General Visual Inspection
1. (marked check list as per CL-NG-6460-002-55 should be
attached )
On Units fitted with hand reset flag indicators, check that the
flag is free to fall before, or just, any contacts closes. Make
2. sure that the reset mechanism in the cover is correctly located
with respect to the relay element and the flag (or mechanism)
can be reset.
Check condition of any connectors, contacts alignment and
3.
travel.
4. Check armature gap.
Check Lockout mechanism. (For hand reset auxiliary relays,
5. Trip Lockout Relay (86) and Bi-stable relay
For electrical reset auxiliary relays)
Check Reset mechanism. (For hand reset auxiliary relays,
6. Trip Lockout Relay (86) and Bi-stable relay
For electrical reset auxiliary relays)

3.0 Electrical tests

Item Description Done Remarks


General Electrical Tests
1. (marked check list as per CL-NG-6460-002-56 should be
attached )
2. Check the continuity of the contacts.
3. Check the resistance of all output contacts.
Check the pick-up voltage and current of operating Coil. (The
4.
relay should switch cleanly with one movement.)
Check the AUTO-RESET function.( For auto reset auxiliary
5. relays, Trip Auto Reset Relay (94))
Archiving System Website: http://AMAS
NATIONAL GRID

Title: Index Number:


CL-NG-6460-002-059
Check List of Auxiliary Relays Commissioning Page Number:
2 of 4

6. Check the Reset mechanism. (For hand reset)


Check pick up voltage and current of Reset Coil. (For
7.
electrically reset & Bi-stable relay)
Check Drop off voltage and current of Reset Coil. (For
8.
electrically reset & Bi-stable relay)
Check the operating time of the Reset Coil at lowest nominal
9.
supply voltage. (For electrically reset )
Check the operating time of the operate Coil at lowest
10.
nominal supply voltage. (For electrically reset)
Check Operate Coil and Rest Coil power consumption during

operation at nominal rated voltage. (For auto reset, hand
11.
reset, Bi-stable, electrically reset, Trip Lockout Relay(86), Trip
Auto Reset Relay(94))
Check operate and Reset Coil resistance. (For electrically
12.
reset)
Check external Reset input if applicable. (For electrically
13.
reset)
Check Change-Over time for contacts which makes/breaks.
14.
(For Bi-stable relay)
Check power consumption of operate and Reset Coil. (For Bi-
15.
stable relay)
Verify trip test for circuit breaker and closing block. (Trip

16. Lockout Relay (86), Trip Auto Reset Relay (94))

Check Drop off voltage and current of operating Coil. (For


17. auto reset, hand reset, Bi-stable, electrically reset, Trip
Lockout Relay (86), Trip Auto Reset Relay (94))
Check the operating and Reset time at lower nominal supply
18. voltage. (For auto reset, hand reset, Bi-stable, electrically
reset, Trip Lockout Relay (86), Trip Auto Reset Relay (94))
Check Relay Burden during operation at nominal rated
19. voltage. (For auto reset, hand reset, Bi-stable, electrically
reset, Trip Lockout Relay (86), Trip Auto Reset Relay (94))
Check Operating coil resistance. (For auto reset, hand reset,
20. Bi-stable, electrically reset, Trip Lockout Relay (86), Trip Auto
Reset Relay (94))
Check the reset ratio (reset ratio = drop off / pick up). (For
21. auto reset, hand reset, Bi-stable, electrically reset, Trip
Lockout Relay (86), Trip Auto Reset Relay (94))
Check power consumption of the relay. (For auto reset, hand
22. reset, Bi-stable, electrically reset, Trip Lockout Relay (86),
Trip Auto Reset Relay (94))
Archiving System Website: http://AMAS
NATIONAL GRID

Title: Index Number:


CL-NG-6460-002-059
Check List of Auxiliary Relays Commissioning Page Number:
3 of 4

Perform the functional test of the relay for which it is being


23. used. (For auto reset, hand reset, Bi-stable, electrically reset,
Trip Lockout Relay (86), Trip Auto Reset Relay (94))
Check operation indicator /Flag/LED function. (For auto reset,
24. hand reset, Bi-stable, electrically reset, Trip Lockout Relay
(86), Trip Auto Reset Relay (94))

CSD Contractor T&C Contractor


Name
Sign.

Archiving System Website: http://AMAS


NATIONAL GRID

Title: Index Number:


CL-NG-6460-002-059
Check List of Auxiliary Relays Commissioning Page Number:
4 of 4

Archiving System Website: http://AMAS