Section 7, Design Records GE 16V228 Engine For Bharat Heavy Electricals LTD., Bhopal, GEK-114659
Section 7, Design Records GE 16V228 Engine For Bharat Heavy Electricals LTD., Bhopal, GEK-114659
, Bhopal, GEK-114659
Figure 7-28. HT and LT Coolant Flow Schematic, Part 1 of 2. (84E904863, Sheet 2) (AutoCAD)
Figure 7-28. HT and LT Coolant Flow Schematic, Part 2 of 2. (84E904863, Sheet 3) (AutoCAD)
Figure 7-31. Combustion Air and Exhaust System Schematic. (84E904863, Sheet 6) (AutoCAD)
TABLE 7-20. INSTRUMENT LIST FOR BHEL FAR 1542 16V228 ENGINE
SS810 (ex EPS) N/A Cam gear pin speed pick up N/A N/A MPU N/A Monitor, engine position No GE ECP
SS811 (ex DSS1) SH811 Cam gear speed sensor #1 N/A N/A MPU >1150 RPM Shutdown, SRLC overspeed GCP GE ECP
SS812 (ex DSS2) SH812 Cam gear speed sensor #2 N/A N/A MPU >1150 RPM Shutdown, SRLC overspeed GCP GE ECP
Warning during run, disallow
ZS800 (BOS) N/A Limit switch, barring over engaged OFF ON Digital switch 0V - Cranking is not allowed No GE ECP
an engine start
-68 mbar 68 mbar 4 mA = -68 mbar Shutdown, +2 in 10 sec,
PT800 (ex COP) PAH800 Crankcase overpressure >0 mbar, Warning GCP GE ECP
-1 psi 1 psi 20 mA = +68 mbar +10 in 0.5 sec
SS810 N/A Engine speed N/A N/A MPU 1000 RPM N/A GP Intergen GP
RH800 N/A Genset running hours N/A N/A -- N/A N/A GP Intergen GP
9xx - ALTERNATOR
TAHH900 >125°C Shutdown
TT900 Windings temp U -10°C 150°C Pt100 GCP AVK JB1
TAH901 >110°C Warning
TAHH901 >125°C Shutdown
TT901 Windings temp V -10°C 150°C Pt100 GCP AVK JB1
TAH901 >110°C Warning
TAHH902 >125°C Shutdown
TT902 Windings temp W -10°C 150°C Pt100 GCP AVK JB1
TAH902 >110°C Warning
TAHH910 >90°C Shutdown
TT910 Front bearing temp -10°C 150°C Pt100 GCP AVK JB1
TAH910 >85°C Warning
TAHH911 >90°C Shutdown
TT911 Rear bearing temp -10°C 150°C Pt100 GCP AVK JB1
TAH911 >85°C Warning