VTS TF Air System PVT.

LTD
Survey No. 13/1, Kanekallu Village, Near Devangonthi
railway station; Makanahalli Road, Hosakote, Bangalore –
560 067. Karnataka.; India
DivisionTel_710
vishnu.r@vtsgroup.com

Technical data for item 1 Offer number 492A/LIVE.EUR/VR/2022-22


Project name KNOWB4U,Kochi

Type SVSSupply Supply airflow 2 9520.00 m³/h


Unit Type: Indoor External pressure 203 Pa
Project Tag 5600 CFM
Size SVS100
Set SVS100-R-FCV

Insulation thickness 40 mm
Insulation Polyurethane Foam SFP Summer 0.83 kW/m³/s
Weight of the set (+/- 10%)* 245 Kg

Comment 1:

Page: 1/6

ClimaCAD On-Line 4.0.4.1, (Since 5/17/2021) 12/14/2022 9:35:29 AM


VTS TF Air System PVT. LTD
Survey No. 13/1, Kanekallu Village, Near Devangonthi
railway station; Makanahalli Road, Hosakote, Bangalore –
560 067. Karnataka.; India
DivisionTel_710
vishnu.r@vtsgroup.com

Technical data for item 1 Offer number 492A/LIVE.EUR/VR/2022-22

Sizes [mm]

Air intake Supply FF 2120x575 Lt 1119 Hid 575 Wi 2120


Air outlet Supply FS 1400x410 LtA 1169 Hiu 575 W 2200
Hi 575
H 655

Unit design
INR_SVS100_PUR_Casing1
INR_SVS100_PUR_Casing2
INR_SVS100_PUR_Casing3

Page: 2/6

ClimaCAD On-Line 4.0.4.1, (Since 5/17/2021) 12/14/2022 9:35:29 AM


VTS TF Air System PVT. LTD
Survey No. 13/1, Kanekallu Village, Near Devangonthi
railway station; Makanahalli Road, Hosakote, Bangalore –
560 067. Karnataka.; India
DivisionTel_710
vishnu.r@vtsgroup.com

Technical data for item 1 Offer number 492A/LIVE.EUR/VR/2022-22


INR_SVS100_PUR_Casing4
INR_SVS100_PUR_Casing5

Temperature Conditions
Reference atmospheric pressure 101325 Pa Winter outdoor reference temperature 6.2 °C
External air Return air
DBT RH DA DBT RH DA

Summer 43.8 °C 46 % 1.2000 kg/m³ 25.0 °C 50 % 1.2000 kg/m³

Supply

External Panel Filter

Type PG4/50.Flat.Ext.Sld

Coarse 80% (ISO 16890) - EFF CLASS Flat[4.0]/50


E

Filter Energy Performance Class E


50% Dirty Air Pressure Drop 72 Pa Initial Air Pressure Drop 44 Pa
100% Dirty Air Pressure Drop 100 Pa Air velocity 2.13 m/s

Chilled Water Coil

Type WCL SVS100 4R DT SH.St.St.Std Number of rows 4 Connection Supply/Return:


DN50/DN50

Standard Circuits 17,23 [dm^3]

Medium Water Maximum working pressure 16 bar


Intake air DBT / RH 25.0 °C / 50 % Discharge air DBT / RH 13.2 °C / 90 %
Air velocity 2.45 m/s Pressure drop Wet / Dry Wet / Dry 102 Pa / 79 Pa
Air Pressure 101325 Pa Air Density 1.2000 kg/m³
Air Volume Flow 9520.00 m³/h
Cooling capacity: Sensible / Total 38.2 kW/49.0 kW Medium temperature: Inlet / Outlet 7.0 °C/12.0 °C
Medium flow rate 8.40 m³/h Medium pressure drop 18.72 kPa

Plug-Fan Set

Fan Section PLUG_DD_400_1,50_2

Qty in section x2
Fan Set Designed for wet operating conditions
The fan system effects is taken into account in the fan performances.

Fan PLUG_VS_400_AF_Px 2

VS 400 x 2-1,5|2 x2

Page: 3/6

ClimaCAD On-Line 4.0.4.1, (Since 5/17/2021) 12/14/2022 9:35:29 AM


VTS TF Air System PVT. LTD
Survey No. 13/1, Kanekallu Village, Near Devangonthi
railway station; Makanahalli Road, Hosakote, Bangalore –
560 067. Karnataka.; India
DivisionTel_710
vishnu.r@vtsgroup.com

Technical data for item 1 Offer number 492A/LIVE.EUR/VR/2022-22


Total Static Pressure 400 Pa Impeller efficiency: Static / Total 66 %/75 %
Dynamic pressure 52 Pa Shaft power 0.80 kW x 2
External pressure 203 Pa Working revolutions 1869 1/min
Total Pressure 452 Pa
Air Volume Flow 9520.00 m³/h

Motor AC_IE2_F_90S_IMB3_4p_1.5_50x 2

400V 50Hz

Motor enclousure IMB3 Rated Currect 3.2 A x 2


IEC Size 90S Rated revolutions 1445 1/min
Operational Voltage 400 V/3 ph Rated Power 1.50 kW x 2
Name plate RPM 400 V/3 ph/50 Hz Motor Version Standard

VFD

_AC _AC

VFD Required Connecting Point CP Provided by others


VFD Qty in section 2 VFD Voltage Supply 400/3/50 V/ph/Hz
VFD Settings VFD Rated Power 1.50 kW x 2
VFD in selection Included VFD HMI No
VFD 1PH ModBus Comm Board No
EPC for mean contaminated filters 2.33 kW EPC for clean filters 2.20 kW
SFP for clean filters 0.83 kW/m³/s Air Pressure 101325 Pa
Air Density 1.2000 kg/m³

Acoustic data

Acoustic power level


Frequency 125 [Hz] 250 [Hz] 500 [Hz] 1000 [Hz] 2000 [Hz] 4000 [Hz] 8000 [Hz] Lw [dB(A)]
[dB(A)]
Inlet [dB(A)] 53.3 67.3 73.3 72.3 68.3 57.3 51.3 77.1
Outlet [dB(A)] 58.3 72.3 78.3 78.3 76.3 71.3 65.3 83.3
Environment [dB(A)] 48.3 58.9 58.6 56.5 56.7 42.3 33.3 64.0

Acoustic pressure Frequency 125 [Hz] 250 [Hz] 500 [Hz] 1000 [Hz] 2000 [Hz] 4000 [Hz] 8000 [Hz] Lp [dB(A)]
level at 1 meter
distance [dB(A)] [dB(A)] 41.3 51.9 51.6 49.5 49.7 35.3 26.3 57.0

AHU Discharge and Intake Opening Sizes &Unit


Supply
Accessories
Controls Selection Mode: No controls

AHU Discharge and Intake Opening Sizes Supply


Air Inlet Front 2120x575
Air Outlet Front (Small) 1400x410
Control application

Functional Code AS|0|1|0|0|0|0|0|6|0|0|0|0|0|0|1


Section splits

Page: 4/6

ClimaCAD On-Line 4.0.4.1, (Since 5/17/2021) 12/14/2022 9:35:29 AM


VTS TF Air System PVT. LTD
Survey No. 13/1, Kanekallu Village, Near Devangonthi
railway station; Makanahalli Road, Hosakote, Bangalore –
560 067. Karnataka.; India
DivisionTel_710
vishnu.r@vtsgroup.com

Technical data for item 1 Offer number 492A/LIVE.EUR/VR/2022-22


Transport Sections Mass [Kg] LENGTH [mm] WIDTH [mm] HEIGHT [mm]
1 245 1119 2200 655

Transport Sections Dims

Page: 5/6

ClimaCAD On-Line 4.0.4.1, (Since 5/17/2021) 12/14/2022 9:35:29 AM