This document provides the technical specifications for a 33 kV solid core post insulator for use in outdoor installations. Key specifications include a nominal system voltage of 33 kV, highest equipment voltage of 36 kV, porcelain construction suitable for heavily polluted areas, 70 kV dry and wet withstand voltage, 170 kV impulse withstand voltage, and a minimum creepage distance of 1065 mm. The insulator is to be mounted in an upright position outdoors under heavy pollution conditions.
This document provides the technical specifications for a 33 kV solid core post insulator for use in outdoor installations. Key specifications include a nominal system voltage of 33 kV, highest equipment voltage of 36 kV, porcelain construction suitable for heavily polluted areas, 70 kV dry and wet withstand voltage, 170 kV impulse withstand voltage, and a minimum creepage distance of 1065 mm. The insulator is to be mounted in an upright position outdoors under heavy pollution conditions.
This document provides the technical specifications for a 33 kV solid core post insulator for use in outdoor installations. Key specifications include a nominal system voltage of 33 kV, highest equipment voltage of 36 kV, porcelain construction suitable for heavily polluted areas, 70 kV dry and wet withstand voltage, 170 kV impulse withstand voltage, and a minimum creepage distance of 1065 mm. The insulator is to be mounted in an upright position outdoors under heavy pollution conditions.
Technical particulars for 33 kV solid core Post Insulator
Specification for 36 KV post insulator:
1.0 Nominal System Voltage : 33 KV
2.0 Highest equipment Voltage : 36 KV 3.0 Type : Porcelain solid core post insulator 4.0 One minute power frequency : 70 KV (rms) dry & wet withstand voltage 5.0 Impulse withstand voltage : 170 kVp (peak) 6.0 Frequency : 50Hz 7.0 Porcelain insulator : Porcelain insulator petticoats should be alternate shade design, suitable for heavily polluted area. 8.0 Colour of glaze Brown 9.0 Cantilever Strength : 4 KN 10.0 Torsional Strength : 2.54 kNm 11.0 Tension Strength : 30 kN 12.0 Compression Strength : 80 kN 13.0 PF Withstand Voltage : Dry 95 kV Wet 80kV 14.0 PF Flashover Voltage : Dry 125 kV Wet 100kV 15.0 Impulse Withstand Voltage : 170 kVp 16.0 Impulse Flashover Voltage : +ve 225 kVp, -ve 240kVp 17.0 Service condition : Outdoor electrically exposed installation. 17.1 Temperature : As per IS-3156 17.2 Altitude : Sea level 17.3 Atmospheric condition : Heavily saline polluted atmosphere with humidity varying between 50% to 98%. Average rain fall:1800 mm 17.4 Type of installation : Outdoor, electrically exposed installation. 18.0 Creepage distance Minimum creepage distance of porcelain insulator 1065 mm 19.0 Approx. height in mm 508 mm 20.0 Mounting dimensions Bottom metal fitting should have 15mm dia.(for M12 bolts) X 4nos.plain holes on 76 mm PCD. Top metal fitting should have tapped bolt holes M12 X 4nos. on 76 mm PCD. 21.0 Mounting face diameter 113 mm (approx.) 22.0 Mounting position Insulator will be used in upright (vertical) position 23.0 APPLICABLE STANDARDS : 23.1 For the insulator stack : IS-2544 and IEC-60273 IS- 5350(for dimensions) 23.2 For metallic parts : Black heart malleable to IS 2108. 23.3 Galvanising of metallic parts : All ferrous parts to be hot dip galvanized IS 2633 24.0 GENERAL 24.1 Vendor should submit the following documents in triplicate along with offer. 24.1.1 Dimensional drawing along with detailed material specification. 24.1.2 Type test certificate as per IS 2544 24.1.3 Guaranteed technical specifications. 24.2 Vendor should submit the following documents in triplicate along with supply of material. 24.2.1 Routine / acceptance test certificate as per IS 2544 and IEC-60273 24.2.2 Test report of galvanizing test as per IS 2633.