Air System Sizing Summary for PISO DE VENTA

Project Name: SUPERCITO CHEDRAUI TECNOLÓGICO 09/02/2022 


Prepared by: Ivan Hernandez 11:23a.m. 

Air System Information


    Air System Name ............................... PISO DE VENTA Number of zones ............................................................. 1
    Equipment Class ............................................... UNDEF Floor Area ............................................................... 3171.0 ft²
    Air System Type ................................................ SZCAV Location ........................................... Xalapa, Ver, Mexico

Sizing Calculation Information

    Calculation Months ..................................... Mar to Nov Zone CFM Sizing ................. Sum of space airflow rates


    Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Central Cooling Coil Sizing Data

    Total coil load .......................................................... 18.6 Tons Load occurs at ................................................... Jun 1700


    Total coil load ....................................................... 222.7 MBH OA DB / WB ...................................................... 87.1 / 69.4 °F
    Sensible coil load ................................................. 192.9 MBH Entering DB / WB ............................................. 76.6 / 61.7 °F
    Coil CFM at Jun 1700 ........................................... 9444 CFM Leaving DB / WB .............................................. 54.2 / 52.8 °F
    Max block CFM ..................................................... 9444 CFM Coil ADP ..................................................................... 51.7 °F
    Sum of peak zone CFM ........................................ 9444 CFM Bypass Factor .......................................................... 0.100
    Sensible heat ratio ............................................... 0.866 Resulting RH ................................................................. 46 %
    ft²/Ton ................................................................... 170.9 Design supply temp. ................................................... 54.0 °F
    BTU/(hr-ft²) ............................................................. 70.2 Zone T-stat Check .................................................... 1 of 1 OK
    Water flow @ 10.0 °F rise .................................... 44.56 gpm Max zone temperature deviation .................................. 0.0 °F

Supply Fan Sizing Data

    Actual max CFM .................................................... 9444 CFM Fan motor BHP ........................................................... 5.17 BHP


    Standard CFM ....................................................... 7980 CFM Fan motor kW ............................................................. 4.10 kW
    Actual max CFM/ft² ................................................ 2.98 CFM/ft² Fan static .................................................................... 2.00 in wg

Outdoor Ventilation Air Data


    Design airflow CFM ................................................. 945 CFM CFM/person .............................................................. 15.00 CFM/person
    CFM/ft² ................................................................... 0.30 CFM/ft²

Hourly Analysis Program v4.90 Page  1  of  6 


Zone Sizing Summary for PISO DE VENTA
Project Name: SUPERCITO CHEDRAUI TECNOLÓGICO 09/02/2022 
Prepared by: Ivan Hernandez 11:23a.m. 

Air System Information


    Air System Name ............................... PISO DE VENTA Number of zones ............................................................. 1
    Equipment Class ............................................... UNDEF Floor Area ............................................................... 3171.0 ft²
    Air System Type ................................................ SZCAV Location ........................................... Xalapa, Ver, Mexico

Sizing Calculation Information

    Calculation Months ..................................... Mar to Nov Zone CFM Sizing ................. Sum of space airflow rates


    Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²
PISO DE VENTA 174.9 9444 9444 Jul 2000 53.8 3171.0 2.98

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
          Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
PISO DE VENTA
          PISO DE VENTA                      1 174.9 Jul 2000 9444 53.8 3171.0 2.98

Hourly Analysis Program v4.90 Page  2  of  6 


Air System Design Load Summary for PISO DE VENTA
Project Name: SUPERCITO CHEDRAUI TECNOLÓGICO 09/02/2022 
Prepared by: Ivan Hernandez 11:23a.m. 

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB      87.1 °F / 69.4 °F HEATING OA DB / WB      42.8 °F / 40.0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 144 ft² 8838 - 144 ft² - -
Wall Transmission 1755 ft² 13109 - 1755 ft² 21477 -
Roof Transmission 3171 ft² 21235 - 3171 ft² 27910 -
Window Transmission 144 ft² 1770 - 144 ft² 4436 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 3171 ft² 0 - 3171 ft² 0 -
Partitions 1780 ft² 4895 - 1780 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 4757 W 16227 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1W 2 - 0 0 -
People 63 15434 12915 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 74480 0 - 0 0
Safety Factor 10% / 10% 15599 1292 0% 0 0
>> Total Zone Loads - 171589 14207 - 53823 0
Zone Conditioning - 168803 14207 - 4350 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 9444 CFM 0 - 9444 CFM 0 -
Ventilation Load 945 CFM 10087 15530 945 CFM 9425 0
Supply Fan Load 9444 CFM 14002 - 9444 CFM -14002 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 192892 29737 - -228 0
Central Cooling Coil - 192892 29768 - 0 0
>> Total Conditioning - 192892 29768 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page  3  of  6 


System Psychrometrics for PISO DE VENTA
Project Name: SUPERCITO CHEDRAUI TECNOLÓGICO 09/02/2022 
Prepared by: Ivan Hernandez 11:23a.m. 

June DESIGN COOLING DAY, 1700

TABLE 1:        SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 87.1 0.01421 945 400 10087 15530
Vent - Return Mixing Outlet 76.6 0.01052 9444 1039 - -
Central Cooling Coil Outlet 54.2 0.00974 9444 1039 192892 29768
Supply Fan Outlet 55.8 0.00974 9444 1039 14002 -
Cold Supply Duct Outlet 55.8 0.00974 9444 1039 - -
Zone Air - 75.4 0.01011 9444 1110 168803 14207
Return Plenum Outlet 75.4 0.01011 9444 1110 0 -

    Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 0.913 BTU/(hr-CFM-F)
    Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4010.5 BTU/(hr-CFM)
    Site Altitude = 4589.0 ft

TABLE 2:        ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
PISO DE VENTA 171589 Cooling 168803 75.4 9444 1110 0 0

Hourly Analysis Program v4.90 Page  4  of  6 


System Psychrometrics for PISO DE VENTA
Project Name: SUPERCITO CHEDRAUI TECNOLÓGICO 09/02/2022 
Prepared by: Ivan Hernandez 11:23a.m. 

WINTER DESIGN HEATING

TABLE 1:        SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 42.8 0.00552 945 400 -9425 0
Vent - Return Mixing Outlet 52.6 0.00552 9444 482 - -
Central Cooling Coil Outlet 52.6 0.00552 9444 482 0 0
Supply Fan Outlet 54.2 0.00552 9444 482 14002 -
Cold Supply Duct Outlet 54.2 0.00552 9444 482 - -
Zone Air - 53.7 0.00552 9444 491 -4350 0
Return Plenum Outlet 53.7 0.00552 9444 491 0 -

    Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 0.913 BTU/(hr-CFM-F)
    Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4010.5 BTU/(hr-CFM)
    Site Altitude = 4589.0 ft

TABLE 2:        ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
PISO DE VENTA -53823 Deadband -4350 53.7 9444 491 0 0

Hourly Analysis Program v4.90 Page  5  of  6 


Psychrometric Analysis for PISO DE VENTA
Project Name: SUPERCITO CHEDRAUI TECNOLÓGICO 09/02/2022 
Prepared by: Ivan Hernandez 11:23a.m. 

Location: Xalapa, Ver, Mexico


Altitude: 4589.0 ft.
Data for: June DESIGN COOLING DAY, 1700
0.020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 0.018
5. Room Air

0.016
1

Specific Humidity ( lb/lb )


0.014

0.012
2
5
3 4
0.010

0.008

0.006

0.004

0.002

0.000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program v4.90 Page  6  of  6 