Professional Documents
Culture Documents
User's Manual GB Mini-Marex-C - System - Bosch Rexroth
User's Manual GB Mini-Marex-C - System - Bosch Rexroth
User's Manual GB Mini-Marex-C - System - Bosch Rexroth
Mini-Marex-C -System
Imprint page 2
Explanation of symbols page 5
Safety advises page 5
SYSTEM
INSTALLATION
ELECTRICAL CONNECTION
6 Grounding page 16
TESTS
OPERATING INSTRUCTIONS
APPENDIX
Registration page 52
Explanation of Some passages within this user’s manual are marked with
symbols opposite. To these passages attention has to be paid in
Symbols and Signs: particular.
This sign is to be found where special advises and tips are given
to the system operator.
The admissible cable length between battery and supply unit must
not exceed 10m, if wire size 2,5mm² is used.
1 System Set-up
The Mini-Marex-C control system is designed for the remote control of marine propulsion plants with
reversing gears .
Mounting kit for connecting the push-pull cable ( ball joint, hex.
nut, cable clamp, and shim ). For each cable one (1) kit is
required.
The connection between control panel and actuator is completed by means of the connecting cable
screwed on to control panel and actuator.
For the mechanical connection between actuator and operating lever of throttle and reversing gear
short push-pull cables have to be used and connected by means of suitable mounting kits.
The operating voltage is supplied to the actuator from the power source passing the supply unit.
The block diagram below shows by way of example the configuration of a twin engine propulsion
system with two (2) control stations and mechanical operated throttle control and gear shifting. Clearly
shown are the individual system components as well as the connections of the electrical cables.
For further block diagrams showing single and twin engine systems see ’appendix’.
Pneumatik
REXROTH
MANNESMANN
Pneumatik
REXROTH
MANNESMANN
MANNESMANN MANNESMANN
REXROTH REXROTH
Pneumatik Pneumatik
2 Control Panel
When mounting the control panel, provide enough space below the console to be accessible for
plugging the electrical cable connections. Space is also needed to secure the cable externally using
tie wraps.
The control panel mounted on the console surface has to be secured with the enclosed hex nuts M5
and flat washers.
M5
max 40 mm
Panel
To prevent water getting between console surface and control panel, a circulating form seal is fixed
on the underside of the control panel.
212
max 40 mm
max 40 mm
Pultplatte
Pultplatte
50
50
4
4
46
46
M5 M5
175 175
Pneumatik
MANNESMANN
Pneumatik
REXROTH
MANNESMANN REXROTH
100
180
R5
R5
10 x 45°
10 x 45°
0,2
76
74
0,2
151
149
6. 149 0,2
6.
154 0,2
Actuator and supply unit should be installed close together. Watch the length of the supply cable to the
actuator - 1,5m.
The actuator and supply unit are fastened with 4 mounting screws each. Mounting holes and outline
dimensions of the components are shown overleaf. Bulkhead mounting with the cable connections and
push-pull cables directed downwards is preferred according to the drawing below.
The devices should be installed in the engine room to a location that will ensure poor vibration. Also
they should be located away from direct engine heat ( admissible temperature range 248K...333K /
corresponding to -25°C...+60°C ), but so that the push-pull cable have a moderate length and easy
bends.
connection for
optional start interlock
connection for 390 mm
supply voltage
REXROTH
MANNESMANN
Pneumatik
MANNESMANN
REXROTH
Pneumatik
adjustments on
electronic board
min. 300 mm
supply cable
1,5m long
Provide sufficient space to be accessible for electrical and push-
pull cable installations.
After mounting the actuator, the cover has to open completely.
For the control set up or adjustment modifications all devices for
adjustments placed on the electronic board have to be accessible
without restrictions.
The actuator and supply unit are designed for the control of
Diesel engines. If gas engine propulsion systems are used, locate
the components outside the explosive area. The regulations
regarding explosive areas have to be followed.
The outline dimensions of the different actuator types are identical. The various types differ from each
other in the number and arrangement of sockets on the front plate only. The actuators are to be
fastened by means of four (4) mounting screws M8.
284
50 59
1 5 6 2 7
81
10
33
273
330
310 DREHZAHL
323 699 402 0
DREHZAHL
U =10V ... 32V I =7A
GETRIEBE
I = 30 A
RPM GEAR
REXROTH
Pneumatik 323 699 412 0 1 2 3 4
6
Supply Unit:
The unit has to be fastened by means of four (4) mounting screws M8.
88
80
30
cable length
1,50 m
*
220
200
60
* for cable
**
MANNESMANN
REXROTH
Pneumatik
8-12
8,2
** for cable
6-10
160
200
4 Push-Pull Cables
For the mechanical connection between actuator and engine throttle lever and gear shift lever
type 33C push-pull cables have to be used.
**
10-32 UNF-2A
22,1
min 5
3,27
8,5
min 5
6,35
effectiveness depends on the total degrees of bends.
Put mounting plate ( 6 ) with the recess into the provided groove of the cable rod ( 2 ) and reinstall it to
actuator.
6 receiver groove
7
GETRIEBE
GEAR
6
2 7
recess
Turn one of both hex nuts ( 3 ) onto cable rod end until stop.
Retract actuator guide ( 2 ) by means of handwheel ( 1 ) until there is a distance "a" of approx. 1mm
between flange (5) and guide (2). At the same time put cable rod thread through the guide’s hole (2).
Press rubber seal ( 4 ) tight onto cable rod joint and adjust cable until there is a distance of approx.
2mm between thread end and seal. In this position tighten second hex nut (3) to the guide (2).
For connecting the push-pull cables to engine throttle - and reversing gear lever a mounting kit, Pc.No.
323 699 006 2 is available. The listed parts ( one each ) are shown below.
.
For each cable one ( 1 ) connection kit is needed.
The max. travel for throttle and gear shift movements is 70mm. Any position for ‘Idle speed, Full
speed, Ahead, Astern, Neutral’ can be adjusted electrically within this travel stroke independent of each
other.
Recommended is a travel of approx. 60 mm. Longer travel
reduces the adjustment possibilities, shorter travel decreases the
control accuracy.
For installation the push-pull cables use the mounting stencil enclosed to the actuator.
Connect ball head of the ball joint to the throttle and gear shift lever and watch the lever movement "s"
(approx. 60mm) between the end positions (Idle ↔ Full speed / Ahead ↔ Astern). It must be centrally
within the adjustable range ( hatched range of mounting stencil ).
= =
"s"
mounting stencil
ball joint
Locate the anchor device ( cable clamp, shim ) so that the push-pull cable forms a right angle ( 90° ) to
the central axis of the travel stroke. Mark the distance to the fastening of the anchor device according
to the mounting stencil, or measure the distance 188mm - see drawing below.
Take care that during the arched travel the joint tube is swerved
out of the cable’s axle direction as even as possible-
max. admissible swerve angle ± 8°
Greater swerve angles may cause function failures of the
DC motors.
"s"
188
°
90
Turn hex nut and ball joint onto the cable rod end and fasten the ball joint by means of the counter nut.
Connect ball joint to lever ball head. Check the wanted movement by turning the handwheel ( 1 ) inside
the actuator ( see drawing on page 13 )
Within the wanted travel the guide (2) should not reach the
actuator stops. Provide a safe distance "a" = 4mm (see drawing
on page 13). Also the cable movement must not be restricted by
any external mechanical stop. Misadjusted cables may cause
motors to lock and to destroy. System failure, danger of fire.
"s"
ball joint
hex. nut
anchor clamp
5 Power Supply
The control system operates from 10V up to 32Volt, DC and draws 30A (shortly), 10A (continuously).
6 Grounding
Actuator and supply unit have to be grounded according to the actualities on-the-spot.
The actuator and supply unit have to be grounded directly to one of the four mounting screws of each
device. If a direct grounding (connection to ship’s mass) is not possible, the grounding has to be
carried out by means of flexible earth leads or earth strips ( see tables below ).
The above said goes also for data cables, e.g. ‘start interlock’ or ‘RPM pick-up’ specially marked in the
operating manual and diagrams.
Not used sockets must be sealed by means of the included protective plugs. Otherwise the
actuators´s protection will be dimished.
1 Control Panel
323 699 400 0 1 5 6 2
Station 1
2 Control Panel
Station 2
3 Control Panel
DREHZAHL
323 699 402 0
Station 4
323 699 402 0 1 5 6 2 7
5 Supply Unit
+ + +
104
101
103
102
connection: connection:
start interlock power supply
max. 2,5mm²
MANNESMANN
REXROTH
Pneumatik
LED 2 fuse
green F2 = 10A T
to actuator connection No.5
LED 1 fuse
green F1 = 3,15A mT
*) Not delivered by
Rexroth Mecman GmbH
The admissible cable length must not exceed 10m, if wire size 2,5
mm² is used. Function failure
Protecting the subsequented electronics and DC motors, the supply unit is provided with the fuses
F1=3,15A (medium- slow-blow) for the electronics and F2=10A (slow-blow) for the DC motors. A green
LED is assigned to each fuse. The LEDs are lighted, if the fuses are in order and when supply voltage
has been turned on.
The supply unit provides a potential-free relay contact (terminals 103 and 104) to be used for a start
interlock that requires the control system to be in definite conditions. The engine can be started under
the following conditions only:
If the starting requirements are not fulfilled, the relay contact interrupts the connection between key
start ( key switch, start push button, or others ) and start solenoid relay.
The maximum load given to the relay contacts inside the actuator
amounts 32V DC / 2A.
Higher loads may destroy the relay.
For higher loads provide an external relay.
key start
104
103
+ shielded cable connection:
start interlock
battery source
-
starting relay
REXROTH
MANNESMANN
Pneumatik
+ supply unit
starter starting battery
-
to actuator
Strip PVC cover and shielding back ring-like and fasten a metallic
clamp around the open shield. Connect the clamp directly to
mass.
If the metallic clamp can’t be connected directly to the mass, an
ground strip (see fig. left ) between clamp and mass has to be
used.
On the cable’s type plate a 10-figure Pc. No. - 894 620 24 2 - is stated. At the place marked
a figure is indicating the different cable lengths being available.
26
26
type plate
For single engine propulsion systems one (1) female connector plug at the underside of the control
panel is provided for connecting the cable to the control panel.
MANNESMANN REXROTH Pneumatik MANNESMANN REXROTH Pneumatik MANNESMANN REXROTH Pneumatik MANNESMANN REXROTH Pneumatik
to actuator socket 4
to actuator socket 2
to actuator socket 3
1 2 3 4
Pneumatik
REXROTH
MANNESMANN
actuator
For twin engine propulsion systems two (2) female connector plugs at the underside of the control
panel are provided for connecting the cables to the control panels; one each for Port and Stbd.
Stbd actuator
Port actuator
Port actuator
to socket 1
to socket 1
to socket 2
to socket 2
3 4 3 4
1 2 1 2
Pneumatik Pneumatik
REXROTH REXROTH
MANNESMANN MANNESMANN
Port Stbd
actuator actuator
10 Intercommunication Cable
( For twin engine propulsion only )
The intercommunication cable serves the internal data transfer between Port and Stbd actuator within
twin engine systems.
On the cable’s type plate a 10-figure Pc. No. - 894 620 26 2 - is stated. At the place marked
a figure is indicating the different cable lengths being available.
26
26
type plate
6 6
Pneumatik Pneumatik
REXROTH REXROTH
MANNESMANN MANNESMANN
Port Stbd
actuator actuator
11 RPM Cable
( For twin engine propulsion including sychronization option only )
This RPM cable serves the connection between engine speed pick-up and actuators with
synchronization option.
On the cable’s type plate a 10-figure Pc. No. - 894 620 27 2 - is stated. At the place marked
a figure is indicating the different cable lengths being available.
26
type plate
At the free end of the RPM-cable there are four (4) colour coded wires - WH ( withe ), BN ( brown ),
GN ( green ) and YE ( yellow ). For connecting the RPM pick-up the BN ( brown ) and GN ( green ) are
needed only. The RPM pick-up has to be connected according to the manufacturers instructions.
For each engine one RPM pick-up is needed to give a speed signal to the actuator.
As RPM pick-ups may be used electric tachometers as well as pulse generators. In many cases the
speed signal taken from the dynamo terminal "W" meets the technical requirements and a separate
RPM pick-up is not necessary.
Technical requirements:
130 Hz for frequency range a)
Z) "Vss" ( Volt Spitze-Spitze ) stands for voltage of the AC signals amplitude from peak to peak.
1 Vss
up to
100 Vss
GN
G
BN
GN
BN
Terminal "W" GN
G
(-) BN
Strip PVC cover and shielding back ring-like and fasten a metallic
clamp around the open shield. Connect the clamp directly to
mass.
If the metallic clamp can’t be connected directly to mass, an
ground strip (see fig. left ) between clamp and mass has to be
used.
Depending on the actuator’s installation position it might be
possible that the circuit board is placed upside down contrary to
the shown illustration. In this case the location of the adjustment
devices is "mirror effected".
Operating +5V
THROTTLE DRIVE CLUTCH DRIVE Voltage
1 2 3 4 5 6 7 8
POTENTIOMETER Plug
Stroke Adjustments
P1 P2
P1 = Coarse adjustment
P2 = Fine adjustment open
OFF ON
FUNCTION SWITCHES
LED 5
Diagnostics of Faults
LED 3 2 2 2
3 3 3
LED 2
open
open
open
4 4 4
5 5 5
LED 1 6 6 6
7 7 7
8 8 8
The overleaf table shows the various adjustment devices and their related functions.
Function Switch-I
Function Switch-II
1
0/1s T1: Holding time of power boost before clutch engagement
2
0 / 0,5 s
3
0/2s T2: Holding time of power boost after clutch engagement
open
4
0/1s
5
0/6s
6
0/3s T3: Delay time before reversing
7
0 / 1,5 s
8
Power boost NO / YES
Function Switch-III
13 Basic Adjustments
Before basic adjustments are carried out, turn OFF the supply
voltage and shut OFF the engine. Also the push-pull cables to
gear shift lever and throttle lever must be disconnected.
Otherwise there is an accident risk.
5
6
7
8
Procedure of command transfer from one control station to the another station.
With this setting a station transfer to any other control station is possible only, if the operator
has moved the transmitter lever either in NEUTRAL position or into the same direction range
(AHEAD or ASTERN) as the transmitter in command.
With this setting a station transfer is possible at any time without any interlocking. The
command is transferred immediately to the requesting station and any possible lever position
from there now is transmitted to the control.
Similarity between the frequency ranges of the actuator’s speed sensoring and used RPM pick-up.
Generally the actuators described in this manual can be applied for cable gear shifting only.
The switch position „operation / transmitter alignment and release of remote stations“ is described
separately on page 36. The signal transmitter alignment and release of remote stations is carried out
after all the other adjustments have been completed.
open
5
6
7
8
¾
DIP-switch II-1 T1: Holding time of power boost before clutch engagement
DIP-switch II-2
„Holding time T1“ ( before clutch engagement ) is active only, if
the feature „power boost“ has been selected by means of the DIP
switch II-8.
st
After the transmitter lever is moved into the 1 detent AHEAD or ASTERN, before clutch engagement
the set „holding time T1“ passes by.
„Holding time T1“ is adjustable between 0 and 1.5 seconds by means of the DIP-switches II-1
and II-2.
¾
DIP-switch II-3 T2: Holding time of power boost after clutch engagement
„Holding time T2“ ( after clutch engagement ) is active only, if the
feature „power boost“ has been selected by means of the DIP
switch II-8.
After clutch engagement ( Ahead or Astern ) the „holding time T2“ passes by, before the control will
release a new order given by the signal transmitter.
„Holding time T2“ is adjustable between 0 and 3 seconds by means of the DIP-switches II-3
and II-4.
DIP-switch II-5
DIP-switch II-6
DIP-switch II-7 ¾ T3: Delay time before reversing
For a reversing maneuver AHEAD ↔ ASTERN or coming out of a drive position into NEUTRAL the
adjusted „delay time T3“ is activated automatically. The pause delays the clutch disengagement.
Example:
The transmitter lever is moved from AHEAD to ASTERN ( or reversed). Immediately the throttle setting
drops to idle speed, but the gear remains engaged AHEAD ( or ASTERN ) according to the adjusted
delay time. This allows to decrease the vessel speed before reversing takes place and speed is built
up again.
The maximum pause on a straight „Crash Reversing“ is achieved, if the control position was set for
more than five (5) times the adjusted „delay time“. With a command period less than five (5) times the
adjusted automatically„delay time“, as well as with a decreased engine speed the pause will be
shortened by the control. For reversing with idle speed the pause is zero. The delay time from
ASTERN to AHEAD in principle is half that for reversing from AHEAD to ASTERN.
The „maximum delay time T3“ is adjustable between 0 and 10.5 seconds by means
of the DIP-switches II-5, II-6 and II-7.
During a later sea trial the most favourable „reversing time T3“ according to the vessel and propulsion
system may be found out and adjusted as follows.
2. Move lever in FULL AHEAD position and take the time the engine attains
two thirds of its maximum speed.
3. Set the measured time by means of the DIP-switches II-5, II-6 and II-7.
4. Do some more reversals over the complete speed range and determine
the most favourable reversing time for propulsion and ship.
Begin the reversals always with low speed and increase the
speed easily. Reset and adapt the „delay time T3“ A „crash
maneuver“ with a reversing time too short may cause damages to
clutch, gear, and engine.
The setting „power boost YES" activates the following functions and are processed by the control. If
„power boost NO“ is set, these functions are not taken in account by the control, even if delay times
have been set..
→T1: Holding time of power boost before clutch engagement ( DIP-switch II-1 and II-2 )
→T2: Holding time of power boost after clutch engagement( DIP-switch II-3 and II-4 )
→Second idle speed ( will be set later together with the speed adjustments )
The combination of these three (3) functions shall be explained with the following example.
Example:
The transmitter lever is moved from NEUTRAL to the AHEAD detent position ( idle ). The control runs
the following steps:
1. Power boost
The engine speed increases up to the adjusted value of the „second idle speed“.
2. Holding time T1
The adjusted holding time T1 insures that the increased engine speed (second idle speed.) is built up
before clutch engagement.
3. Clutch engagement
At the end of holding time T1 the AHEAD clutch is engaged.
4. Holding time T2
The adjusted holding time T2 insures a safe clutch engagement absorbing the propeller’s back torque
by means of the increased speed (second idle speed ).
5. Idle speed
At the end of holding time T2 the engine speed is set back to idle. In case the transmitter lever was
moved to a position with a higher nominal speed value preset, the engine speed is released to that
value without dropping to idle before.
14 Stroke Adjustment
By means of the function switch-III and the potentiometer P1 and P2 the following
gear shift positions are adjusted
Ahead
Neutral
Astern
To do any adjustment, first turn ON the control and take over command at control station 1
( main station ) with the transmitter levers in NEUTRAL position. The procedure of activating the
control is described in section „operating instructions on page 48.
open
5
6
7
8
DIP-switch III-2: special adjustment (control station ) / standard adjustment ( engine room )
All adjustments must be carried out in standard adjustment mode.
DIP-switch III-2 always in ON position
open
4 4 4
5 3...8 5 5
6 6 6
7 7 7
8 8 8
After DIP-switch 1 is set in ON position, the control is in adjustment mode and the corresponding
actuator drive moves to the last stored position.
4.) 5.)
Adjust the wanted position approximately Adjust the wanted position exactly
by means of pot P1 ( coarse adjustment ) by means of pot P2 ( fine adjustment )
By means of the potentiometers all positions to be adjusted can be displaced over the total travel
range. The position „minimum speed“ ( Idle ) can be shifted from the retracted to the extracted actuator
drive position, and the position „maximum speed“ ( Full speed ) then is set to the retracted actuator
drive position (reversal of travel direction). In the same way the positions „Gear AHEAD“ and „ Gear
ASTERN“ may be interchanged.
In case the pot’ s adjustment range is not sufficient for getting the
wanted travel position, the adjustment procedure has to be
interrupted ( DIP-switch-1 on OFF ). After the potentiometer is set
back and alternated to adjustment mode ( DIP-switch-1 in ON
position ), the adjustment may be continued. Do not change the
other DIP switches.
After the wanted position has been adjusted, exit the adjustment mode as follows.
4 4 4
5 3...8
5 5
6 6 6
7 7 7
8 8 8
After DIP-switch-1 is set in OFF position, the chosen actuator travel position is stored in the control
memory. The corresponding actuator drive moves to NEUTRAL (gear shift adjustment) or to Idle
(throttle adjustment).
In the following the next position can be adjusted in the same way. Chose the switch combinations for
the position to be adjusted according to the table and follow the programming steps from 1.) to 8.) .
In practice for the following described push-pull cable adjustments
an assistant has proved worthwhile. While one person does the
adjustment according to „section 14 stroke adjustment“, the other
person may check the implementation at the gear shift lever.
Move gear shift lever into the position to be adjusted ( „Ahead“, „Astern“, „Neutral“ ) and adjust the
actuator drive ( as described in „section 14 stroke adjustment“ ) that way to connect the gear shift
cable in the different lever positions smoothly.
The max. travel for the gear shift movement between the
positions AHEAD and ASTERN is max. 70mm.
Recommended is a travel of approx. 50....60 mm. Longer travel
reduces the adjustment possibilities, shorter travel decreases the
control accuracy.
Position DIP-switch
3 4 5 6 7 8
Gear AHEAD ON OFF OFF OFF OFF ON
open
open
open
open
open
4 4 4 4 4 4
5 3...8 5 5 5 5 5 3...8
6 6 6 6 6 6
7 7 7 7 7 7
8 8 8 8 8 8
In practice for the following described push-pull cable adjustments
an assistant has proved worthwhile. While one person does the
adjustment according to „section 14 stroke adjustment“, the other
person may check the implementation at the throttle lever.
nd
Move throttle lever into the position to be adjusted ( „Idle“, „Full speed“, „2 Idle speed“ ) and adjust the
actuator drive ( as described in „section 14 stroke adjustment“ ) that way to connect the throttle cable in
the different lever positions smoothly.
stop stop
The max. travel for the throttle movement between the positions
Idle and Full speed is max. 70mm.
Recommended is a travel of approx. 50....60 mm. Longer travel
reduces the adjustment possibilities, shorter travel decreases the
control accuracy.
Position DIP-switch
3 4 5 6 7 8
minimum speed ( Idle ) OFF OFF OFF OFF OFF ON
open
open
open
open
open
4 4 4 4 4 4
5 3...8 5 5 5 5 5 3...8
6 6 6 6 6 6
7 7 7 7 7 7
8 8 8 8 8 8
15 Transmitter Alignment
and Release of Control Stations
NEUTRAL
Gear AHEAD (detent) Gear ASTERN
(detent) (detent)
2 1 2
Action: Turn ON the control. Align twin engine systems separately, i.e. turn ON one control
at a time.
Transmitter to be aligned.
Lighting of the transmitter to be aligned flashes with high repetition, the lighting of all
the other transmitters blinks with low repetition.
Action: Move transmitter lever in the position to be aligned ( “Idle / Ahead detent”, "Full speed
/ Ahead”, “Idle / Astern detent”, “Full speed / Astern”
Result: If the alignment was successful, after 3 seconds the buzzer will sound once.
If the alignment wasn't successful, after 3 seconds the buzzer will sound 3 times.
Repeat the alignment procedure.
Action: Align all the other lever positions in the same way.
Action Move to the next control station and depress „station transfer“ button for 3 seconds
until the lighting is flashing with high repetition.
(For the alignment the transmitters must be positioned in NEUTRAL again.)
In the following carry out the alignment procedure as described above.
After the cables are disconnected, turn ON the control and take over command at one remote station.
Then carry out the following control operations:
“Gear Neutral”
Detent “Gear Ahead”
Move from “Idle-Ahead” to “Full-Ahead”
“Gear Neutral ”
“Gear Neutral”
Check that the push-pull cable movements are done accordingly to the operation commands. Check
that cable positions and directions are identical with the adjusted values.
Do the checks in the same way at each existing control station.
If required, minimum speed ( Idle ) and second idle speed can be adjusted with the aid of a rev
counter. Within twin engine systems the adjustments for both engines must match. For the adjustment
procedure see „section 14 stroke adjustment”.
For the final adjustments during sea trial open water is necessary.
Operate carefully and start slowly to learn the features of the
control.
Connect the gear cables to the shift lever in “Neutral” position.
If required, during sea trial the rated speed ( full speed ) is brought into line and the “delay times” ( if
wanted ) are set. The optional feature “Synchronization” ( if available ) has to be adjusted and checked.
For the tests during sea trial at least one assisting person is
needed.
The rated speed of the engine can't be exceeded by the control,
but can only let move the throttle lever in its maximum position.
Further attempts to increase the speed would cause blocking of
the actuator drive. Realise that the rev counter at the control
station may show inaccuracies caused by manufacturing
tolerances.
If however the speed must be modified nevertheless, the engine has to be turned OFF before. For the
wanted correction follow the advises in " section 14 stroke adjustment.
After correction, the throttle lever must not move against the
mechanical stop. Function failures, danger of fire.
Example:
The rated (full) speed of the "Master" engine is 2500 RPMs and the rated speed of the "Slave" engine
is only 2450 RPMs. The control tries to synchronize both engines at "Full Speed", but because of the
lower rated speed of the "Slave" engine, it is not possible to attain the "Master" engine speed. An active
speed control (synchronization) is not possible any more.
If the “Slave” engine does not attain the speed value of the “Master” engine within 20 seconds, the
control will cancel the active speed control ( synchronization ) and both engines will follow the speed
setting by means of the "Master“ transmitter lever only, i.e. Full Speed of „Master“ engine is 2500
RPMs; Full Speed of „Slave“ engine is 2450 RPMs. Indication is given at the control station by means
of the quick blinking push button “special features” ( on 0,2sec / off 0,2sec ).
Remedial action:
There are three possibilities to take remedial action:
During sea trial now the most favourable „reversing time T3“ according to the vessel and propulsion
system may be determined and adjusted as follows.
2. Move lever in „Full Ahead“ position and take the time the vessel attains two thirds of its
maximum speed.
3. Set this time with the DIP-switches II-5, II-6, and II-7.
4. Do some more reversals over the complete speed range and determine the most
favourable „reversing time T3“ for propulsion and ship.
Begin the reversals always with low speed and increase the
speed easily. Reset and adapt the „delay time T3“, if necessary. A
crash maneuver with a reversing time too short may cause
damages to clutch, gear, or engine.
18 Signal Transmitter
Neutral
Gear ASTERN (detent) Gear AHEAD
(detent) (detent)
2 1
2
3 3
Operating Panel
Buzzer
1. Standard- operation
"Ahead" or "Aster" clutch is engaged, the engine is idling.
19 Control Panel
The push button „station transfer“ is located at each control panel only once, even for twin engine
systems. The push button is lighted permanently and indicates that the control is power supplied. The
push button is used for the control transfer to other stations. The procedure of take over command and
station transfer is described on page 48 up. Apart from this the push button has two additional
functions.
The engine is idling while the clutch is remaining disengaged. Now the transmitter lever can be moved
up to position “3 Full speed” for speed setting through the total range between the positions 2 and 3.
To exit „Warming up“, return the transmitter lever to position “1 Neutral. The normal „beep“ tone
indicates "Neutral-Position". The transmitter lighting changes to steady. The „Warming up“ feature is
cancelled.
1. Alarm lamp:
This indicating device is located at each control station, one for each control system, i.e. for twin
engine systems two ( one for Port / one for Stbd. ).
In case of a failure the alarm lamp will show a red steady light .
2. Lamp test:
After the control is turned ON, the alarm lamp also shows a
steady light, but it is turned off after taking over control.
for this function the push buttons has to be depressed permanently testing the transmitter lighting as
well as all lighted lamps and push buttons ( except „Dimmer“ button / lighted version available from
middle 1997 ) of the operating panel. As soon as the button is released, the normal condition will
appear.
By means of this push button it can be selected between a bright control panel lighting (day light) and a
darker lighting ( night light ).
In night light mode the brightness may be dimmed continuously and the push button is lighted as well.
Depress and hold down push button "Dimmer". The total range of brightness is run through. As soon
as the wanted brightness shows up release the push button. If the control was switched off ( supply
voltage was turned off ), the wanted brightness has to be adjusted again.
.
Alarm lamp and buzzer are not affected by the dimmer.
By means of this push button a special feature established before can be activated and deactivated.
Requirement is the installation of actuators comprising the corresponding software for the options
questioned. A later system extension by a special feature is not possible.
For corresponding applications the various actuators including the options "trolling", "modulation" or
"synchronization" are available. The special features "trolling" and "modulation" are described in
additional manuals and are not subject of this manual.
If actuators including the special feature "synchronization" are applied, within twin engine propulsion
systems the engine speed of both engines may be synchronized. For the synchronization a speed
signal ( RPM pick-up ) from each engine given to the actuator is required.
Pushing the button will alternately set the option „synchronization“ back and forth between
synchronization and normal. As long as the option is effective the push button shows a
blinking light.
„Synchronization“ can be activated only, when both transmitter
levers are in cruise position „Ahead“ or the option „Warming-Up“
is in operation. Switch off synchronization before leaving the
Ahead range or warming-up mode. As soon as one of both
transmitters is moved out of the range without having cancelled
synchronization before, the control will do it automatically. Push
button lighting „special feature“ blinks quickly ( on 0,2sec / off
0,2sec ) and an steady buzzer tone sounds at the operating
control station.
To clear the warning condition, move the other transmitter lever to
NEUTRAL position. So long the warning is effective, the
corresponding engine will stay at idle speed.
In synchronization mode the engine speed of both engines together can be controlled by the „Master“
transmitter only ( see „section 17.2 special feature synchronization“ / page 39 ). In case of a station
transfer the activated „synchronization“ function will be transferred also.
Two of these indicator lamps are included in control panels for twin engine propulsion systems, one for
the Port control and one for Stbd. The indicator lamp shows that the corresponding control is ON. The
lamp does not indicate which transmitter has the command at a time.
19.6 Buzzer
One buzzer for each control is located underneath the control panel ( one at single engine panels, at
twin engine panels one for Port and one for Starboard).
The buzzer supports the visual indicating of transmitter lighting and alarm lamp by acoustic tones. Also
each time the transmitter has taken up „Neutral“ position it indicates it with a short „beep“. If the
"Warming up" option has been called up, a short "double beep"-tone is produced.
The transmitter lighting is carried out as a green point on the transmitter scale at „Neutral“.
Steady light indicates which transmitter has the command at a time. The transmitter lighting at the
other station is OFF. The transmitter lighting blinks when station transfer is requested.
If the transmitter is in "Warming up" mode, this is indicated by means of a short-termed rhythmical
extinguishing transmitter lighting.
20 Turning ON Control
1. Turn ON control
Result: ¾Indicator lamp „Alarm“ (red) shows steady light at all stations.
¾Push button „station transfer“ (white) shows steady light at all stations.
¾Buzzer sounds with low repetition at all stations.
¾For twin engine systems only: indicator lamp „Remote Control ON“ (green)
shows steady light at all stations.
2. Requesting control:
Remote control may be requested at each remote station. The transmitter lever must be placed in
„Neutral“ before.
If there is still a low repetition lighting and buzzer tone, mostly the
transmitter lever is not placed in „Neutral“.
The lighted transmitter now has the command. The control is set into service.
21 Station Transfer
The control offers two options for station transfer ( interlocked or free ) to be selected by means of
DIP-switch I-2 ( see page 26 ) on the actuator circuit board. Within twin engine systems both controls
must have identical adjustments.
Action: ¾Move transmitter lever into the transfer position ( Neutral or same direction as lever
in command).
¾Depress push button „Station transfer“ (white) once.
The command now is requested at this new station and the control has released the take over of
command shown by light and tone with high repetition.
If there is a low repetition lighting and tone, the station transfer will
not be executed. In this case check that the transmitter levers are
placed in the right position. Or there is a control failure.
Action: ¾ Depress push button „station transfer“ (white) one more time.
The station transfer is completed. The lighted transmitter has the command.
With this option, on request the station transfer takes place disregarding the lever positions of the
transmitters involved. The transfer proceeds in one step only.
The station transfer is completed and the control carries out immediately the set lever position of the
transmitter just has taken over the command.
Mini-Marex-C
APPENDIX
Why?
Thus
-
send us a fax
write us "
give us a call
On the opposite page you will find a registration sheet ( front and reverse ) with some questions.
Question No. 4 refers to the actuator’s type No., serial No., and date of production. All asked details
( 1st. and 2nd. line ) you might take from the type plate located at the front of the actuator.
1st. line
323 699 410 0
2nd. line
SN:109 24.96
U N =10V ... 32V IN = 7 A
I MAX. = 30 A
MANNESMANN REXROTH
Pneumatik
1 5 6 2 7
Important !
Indicate absolutely the name of the vessel ( question 7 ).
Your details are filed with us according to the ship’s name. If there are two or more ships with the same
name, the next characteristics are ship yard and year of construction ( question 9 ).
If the ship’s name is going to be changed, e.g. because of sale, please inform us about this too.
-Germany-
Advertisements in others:..........................................................
magazines ..........................................................
7. Name of vessel....................................................................................................................
8. Type of vessel
Motor Yacht Sailing Yacht Work boat Passenger ship Authority ship
Length.............................................................................................................................
Width:..............................................................................................................................
Name ............................................................
Address ............................................................
............................................................
............................................................
............................................................
............................................................
Telephone ............................................................
Fax ............................................................
Pneumatik
MANNESMANN REXROTH
MANNESMANN
REXROTH
Pneumatik
MANNESMANN
Pneumatik
REXROTH
Pneumatik
MANNESMANN REXROTH
MANNESMANN REXROTH Pneumatik MANNESMANN REXROTH Pneumatik MANNESMANN REXROTH Pneumatik MANNESMANN REXROTH Pneumatik
REXROTH
Pneumatik
MANNESMANN
BLOCK DIAGRAMS
MANNESMANN
Pneumatik
REXROTH
MANNESMANN
REXROTH
Pneumatik
MANNESMANN
REXROTH
Pneumatik
MANNESMANN
Pneumatik
REXROTH
MANNESMANN
Pneumatik
REXROTH
MANNESMANN
REXROTH
Pneumatik
MANNESMANN
REXROTH
Pneumatik
MANNESMANN
Pneumatik
REXROTH
MANNESMANN
Pneumatik
MANNESMANN REXROTH
REXROTH
Pneumatik
MANNESMANN
REXROTH
Pneumatik
MANNESMANN
Pneumatik
REXROTH
MANNESMANN
Pneumatik
REXROTH
MANNESMANN
REXROTH
Pneumatik
MANNESMANN
REXROTH
Pneumatik
MANNESMANN
Pneumatik
REXROTH
Diagnostic of Faults
The Mini-Marex control comprises an extensive fault analysis program for identification, evaluation,
and indication of faults. A fault realised by the control is indicated via the alarm lamp at the station
in command. In some cases the visual alarm is supported by means of the buzzer.
The type of fault is indicated by five (5) LEDs arranged on the circuit board which is located inside
the actuator cover. They are visible through a cut-out in the circuit board’s protective plate, after the
actuator has been opened. The exact location of the LEDs is shown in the figure below.
Via the LEDs all faults realised by the control are indicated as fault No. in binary code. The table
below assists converting the binary code into decimal fault Nos.
LED 1 2 3 4 5
Valence 1 2 4 8 16
To each LED a definite valence is assigned, the valence sum of the lighted LED‘s results in the
fault No.
Examples:
The fault indication is active only as long as the fault condition lasts. As soon as the
fault is cleared the LED will be OFF. The possible cause of fault then can’t be recalled
any more.
All faults the Mini-Marex control is able to realise are described on the following pages in the order
of their fault Nos.
In case several faults arise at the same time, always the fault with the highest fault No. is indicated,
until all faults have been cleared.
The buzzer activated by some alarm reports may be stopped by pushing the „station transfer“
button at the corresponding control station. But because of this the alarm is not cancelled.
Fault-No. 1:
Actuator Indication Control Station Indication
Fault-No. 2:
Actuator Indication Control Station Indication
Cause of fault: when turning ON control, DIP-switch I-6 is set in ON position (terminal input)
Delay: none
Fault-No. 3:
Actuator Indication Control Station Indication
Delay: none
Fault-No. 4:
Actuator Indication Control Station Indication
Fault-No. 5:
Actuator Indication Control Station Indication
Cause of fault: station gaining command is defective or wire break at station gaining command:
possible causes: defective potentiometer or micro switch; pot value doesn’t match
with switch signal; contact fault at plugs; wire break or short circuit at control
station, connecting cable, or actuator.
Fault exit: after approx. 30sec requesting the command is cancelled and following fault
indication automatically is cleared;
correct cause of fault.
Fault-No. 6:
Actuator Indication Control Station Indication
Delay: none
Fault exit: set DIP-switch III-1 in OFF position (operation); repeat programming
Fault-No. 7:
Actuator Indication Control Station Indication
Delay: none
Fault-No. 8:
Actuator Indication Control Station Indication
Cause of fault: wire break or short circuit at intercommunication cable between the actuators:
possible cause: contact fault at plugs; wire break or short circuit at connection
cable or at one of the two actuators
Consequence: synchronization OFF; avoiding unforced speed variation fault No.7 is set, if
synchronization was activated before,
without synchronization, manoeuvring is still possible; both controls operate
separately
Fault-No. 9:
Actuator Indication Control Station Indication
Consequence: synchronization OFF; speed runs to idle or stays idling; gear can be shifted to
„Neutral“ one time only or can’t be moved out of „Neutral“; station transfer is
not possible
Delay: none
Fault-No. 10
Actuator Indication Control Station Indication
Consequence: synchronization OFF; speed runs to idle or stays idling; gear can be shifted to
„Neutral“ one time only
Delay: none
Fault-No. 11
Actuator Indication Control Station Indication
Fault-No. 12
Actuator Indication Control Station Indication
Cause of fault: wire break or short circuit at potentiometer for RPM feed back
Consequence: synchronization OFF; speed runs to the mechanical stop at idle position
(speed crash maneuver); gear can be shifted
Fault-No. 13
Actuator Indication Control Station Indication
Cause of fault: wire break or short circuit at potentiometer for clutch feed back
Consequence: synchronization OFF; speed runs to idle position; gear can’t be shifted any more
Fault-No. 14
Actuator Indication Control Station Indication
Cause of fault: false feed back from interface circuit board used for electrical gear shifting:
possible cause: gear doesn’t shift; pressure switch defective or not connected
(but activated from interface board); contact fault at connector plugs; wire break or
short circuit between actuator and gear switches; defective interface board or defective ICs on
main circuit board
Consequence: synchronization OFF; if synchronization was active before, for the slave control
fault No. 7 is set additionally, but the set speed remains.
Fault-No. 15
Actuator Indication Control Station Indication
Cause of fault: wire break or short circuit at interface circuit board used for electrcal gear shifting
possible cause: wire break or short circuit between gear interface board and
motherboard
Consequence: synchronization OFF; if synchronization was active before, for the slave control
fault No. 7 is set additionally, but the set speed remains.
Fault-No. 16
Actuator Indication Control Station Indication
Consequence: synchronization OFF; if synchronization was activated before, for the slave control
fault No.7 is set granting speed setting only, after the transmitter has been
brought to „Neutral“;
speed variation into the blocked direction is not possible;
gear can be shifted
Delay: none
Fault-No. 17
Actuator Indication Control Station Indication
Fault-No. 18
Actuator Indication Control Station Indication
Consequence: speed setting is not possible any more; gear can be shifted one time to „Neutral“
Delay: none
Fault-No. 19
Actuator Indication Control Station Indication
Consequence: speed runs to idle; gear shifting is not possible any more
Delay: none
Fault-No. 20
Actuator Indication Control Station Indication
Delay: none
Fault exit: set DIP-switch I-5 in ON position (electrical operated); initiate control again
Fault-No. 21
Actuator Indication Control Station Indication
Delay: none
Fault-No. 22
Actuator Indication Control Station Indication
Delay: none
Fault-No. 23
Actuator Indication Control Station Indication
Delay: none
Fault exit: set DIP-switch I-7 in ON position (transmitter alignment), afterwards in OFF
position (operation) again; sum check now is corrected; the control acts like after
a new initiation
Fault-No. 24
Actuator Indication Control Station Indication
Delay: none
Fault exit: apply matching EEPROM and EPROM and initiate control again
Fault-No. 25
Actuator Indication Control Station Indication
Delay: none
Fault exit: apply matching EEPROM and EPROM and initiate control again
Fault-No. 26
Actuator Indication Control Station Indication
Delay: none
Fault-No. 27
Actuator Indication Control Station Indication
Delay: none
Fault-No. 28
Actuator Indication Control Station Indication
Delay: none
Fault-No. 29
Actuator Indication Control Station Indication
Delay: none