Outdoor Unit
Class 8HP 10HP 12HP 14HP 16HP

MF2 Model Name U-8MF2E8 U-10MF2E8 U-12MF2E8 U-14MF2E8 U-16MF2E8

Indoor Unit
Class 22 28 36 45 56 60 73 90 106 140 160
U1 4-Way Cassette S-22MU1E51 S-28MU1E51 S-36MU1E51 S-45MU1E51 S-56MU1E51 S-60MU1E51 S-73MU1E51 S-90MU1E51 S-106MU1E51 S-140MU1E51 S-160MU1E51
S-22MU1E5 S-28MU1E5 S-36MU1E5 S-45MU1E5 S-56MU1E5 S-73MU1E5 S-106MU1E5 S-140MU1E5 S-160MU1E5

Y1 4-Way Cassette 60×60 S-22MY1E5 S-28MY1E5 S-36MY1E5 S-45MY1E5 S-56MY1E5

L1 2-Way Cassette S-22ML1E5 S-28ML1E5 S-36ML1E5 S-45ML1E5 S-56ML1E5 S-73ML1E5

D1 1-Way Cassette S-28MD1E5 S-36MD1E5 S-45MD1E5 S-56MD1E5 S-73MD1E5

K1 Wall Mounted S-22MK1E5 S-28MK1E5 S-36MK1E5 S-45MK1E5 S-56MK1E5 S-73MK1E5 S-106MK1E5

T1 Ceiling S-36MT1E5 S-45MT1E5 S-56MT1E5 S-73MT1E5 S-106MT1E5 S-140MT1E5

F1 Low Silhouette Ducted S-22MF1E5 S-28MF1E5 S-36MF1E5 S-45MF1E5 S-56MF1E5 S-73MF1E5 S-90MF1E5 S-106MF1E5 S-140MF1E5 S-160MF1E5

F2 Low Silhouette Ducted S-22MF2E5 S-28MF2E5 S-36MF2E5 S-45MF2E5 S-56MF2E5 S-60MF2E5 S-73MF2E5 S-90MF2E5 S-106MF2E5 S-140MF2E5 S-160MF2E5

M1 Slim Low Static Ducted S-22MM1E5 S-28MM1E5 S-36MM1E5 S-45MM1E5 S-56MM1E5

P1 Floor Standing S-22MP1E5 S-28MP1E5 S-36MP1E5 S-45MP1E5 S-56MP1E5 S-71MP1E5

R1 Concealed Floor S-22MR1E5 S-28MR1E5 S-36MR1E5 S-45MR1E5 S-56MR1E5 S-71MR1E5


Standing

Class 73 106 140 224 280

E1 High Static Pressure


Ducted
S-73ME1E5 S-106ME1E5 S-140ME1E5 S-224ME1E5 S-280ME1E5

85464869270000 REFERENCE NO.TD831170-00

%QXGTKPFF 
IMPORTANT!
Please Read Before Starting
This air conditioning system meets strict safety and
operating standards. As the installer or service person, SPECIAL PRECAUTIONS
it is an important part of your job to install or service the
system so it operates safely and efficiently. WARNING When Wiring

For safe installation and trouble-free operation, you ELECTRICAL SHOCK CAN CAUSE
must: SEVERE PERSONAL INJURY OR DEATH.
Carefully read this instruction booklet before beginning. ONLY A QUALIFIED, EXPERIENCED
ELECTRICIAN SHOULD ATTEMPT TO
Follow each installation or repair step exactly as shown. WIRE THIS SYSTEM.
Observe all local, state, and national electrical codes. • Do not supply power to the unit until all wiring and tubing
This product is intended for professional use. are completed or reconnected and checked.
Permission from the power supplier is required when • Highly dangerous electrical voltages are used in this system.
installing the U-8MF2E8 outdoor unit that is connected Carefully refer to the wiring diagram and these instructions
to a 16 A distribution network. when wiring. Improper connections and inadequate
This equipment complies with EN/IEC 61000-3-12 grounding can cause accidental injury or death.
provided that the short-circuit power Ssc is greater than • Connect all wiring tightly. Loose wiring may cause
or equals to the values corresponding to each model as overheating at connection points and a possible fire hazard.
shown in the table below at the interface point between • Provide a power outlet to be used exclusively for each
the user’s supply and the public system. unit.
It is the responsibility of the installer or user of the • ELCB must be incorporated in the fixed wiring.
equipment to ensure; by consultation with the distribution
Circuit breaker must be incorporated in the fixed wiring
network operator if necessary that the equipment is
in accordance with the wiring regulations.
connected only to supply with a short-circuit power Ssc
greater than or equals to the values corresponding to U-8MF2E8 U-10MF2E8 U-12MF2E8
each model as shown in the table below. Circuit breaker 25 A 25 A 35 A
U-10MF2E8 U-12MF2E8 U-14MF2E8 U-16MF2E8 U-14MF2E8 U-16MF2E8
Ssc 1,150 kVA 3,800 kVA 5,200 kVA 5,900 kVA Circuit breaker 40 A 50 A
This equipment complies with EN/IEC 61000-3-11 • Provide a power outlet exclusively for each unit, and
provided that the system impedance Zmax is less than full disconnection means having a contact separation
or equal to the values corresponding to each model as in all poles must be incorporated in the fixed wiring in
shown in the table below at the interface point between accordance with the wiring rules.
the user’s supply and the public system. Consult with • To prevent possible hazards from insulation failure,
the supply authority for the system impedance Zmax. the unit must be grounded.
U-10MF2E8 U-12MF2E8 U-14MF2E8 U-16MF2E8
When Transporting
Zmax — 0.180  0.180  0.180 
Be careful when picking up and moving the indoor and
Pay close attention to all warning and caution notices
outdoor units. Get a partner to help, and bend your knees
given in this manual.
when lifting to reduce strain on your back. Sharp edges or
This symbol refers to a hazard or unsafe thin aluminum fins on the air conditioner can cut your fingers.
WARNING practice which can result in severe When Installing…
personal injury or death.
This symbol refers to a hazard or unsafe Select an installation location which is rigid and strong
CAUTION practice which can result in personal enough to support or hold the unit, and select a location
injury or product or property damage. for easy maintenance.
…In a Room
If Necessary, Get Help Properly insulate any tubing run inside a room to prevent
These instructions are all you need for most installation “sweating” that can cause dripping and water damage to
sites and maintenance conditions. If you require help for a walls and floors.
special problem, contact our sales/service outlet or your
certified dealer for additional instructions. Keep the fire alarm and the air outlet at
CAUTION least 1.5 m away from the unit.
In Case of Improper Installation …In Moist or Uneven Locations
The manufacturer shall in no way be responsible for Use a raised concrete pad or concrete blocks to provide
improper installation or maintenance service, including a solid, level foundation for the outdoor unit. This prevents
failure to follow the instructions in this document. water damage and abnormal vibration.

%QXGTKPFF 
…In an Area with High Winds • Do not touch the air inlet or the
Securely anchor the outdoor unit down with bolts and a sharp aluminum fins of the
metal frame. Provide a suitable air baffle. CAUTION outdoor unit. You may get injured.
…In a Snowy Area (for Heat Pump-type Systems) • Ventilate any enclosed areas when
Install the outdoor unit on a raised platform that is higher installing or testing the refrigeration
than drifting snow. Provide snow vents. system. Escaped refrigerant gas, on
contact with fire or heat, can produce
When Connecting Refrigerant Tubing
dangerously toxic gas.
• When performing piping work do not • Confirm after installation that no
mix air except for specified refrigerant refrigerant gas is leaking. If the gas
(R410A) in refrigeration cycle. It comes in contact with a burning stove,
causes capacity down, and risk of gas water heater, electric room heater
explosion and injury due to high or other heat source, it can cause the
tension inside the refrigerant cycle. generation of poisonous gas.
WARNING • Refrigerant gas leakage may cause
Others
fire.
• Do not add or replace refrigerant • Do not touch the air inlet or the
other than specified type. It may CAUTION sharp aluminum fins of the
cause product damage, burst and outdoor unit. You may get injured.
injury, etc. • Do not sit or step on the unit,
• Ventilate the room well, in the event that is refrigerant you may fall down accidentally.
gas leaks during the installation. Be careful not to allow • Do not stick any object into the
contact of the refrigerant gas with a flame as this will FAN CASE.
cause the generation of poisonous gas. You may be injured and the
• Keep all tubing runs as short as possible. unit may be damaged.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces
of the flare and union tubes before connecting them,
then tighten the nut with a torque wrench for a leak-free
connection.
• Check carefully for leaks before starting the test run.
• Do not leak refrigerant while piping work for an
installation or re-installation, and while repairing
refrigeration parts.
Handle liquid refrigerant carefully as it may cause
frostbite.

When Servicing
• Turn the power OFF at the main power box
(mains), wait at least 10 minutes until it is
discharged, then open the unit to check or repair
electrical parts and wiring.
• Keep your fingers and clothing away from any moving
parts.
• Clean up the site after you finish, remembering to
check that no metal scraps or bits of wiring have been
left inside the unit being serviced.
• This product must not be
modified or disassembled under
WARNING any circumstances. Modified or
disassembled unit may cause fire,
electric shock or injury.
• Do not clean inside the indoor and
outdoor units by users. Engage
authorized dealer or specialist for
cleaning.
• In case of malfunction of this
appliance, do not repair by yourself.
Contact to the sales dealer or service
dealer for a repair.

ii

%QXGTKPFF 
Check of Density Limit 2. The standards for minimum room volume are as follows.
The room in which the air conditioner is to be installed (1) No partition (shaded portion)
requires a design that in the event of refrigerant gas
leaking out, its density will not exceed a set limit.
The refrigerant (R410A), which is used in the air conditioner,
is safe, without the toxicity or combustibility of ammonia, and
is not restricted by laws imposed to protect the ozone layer.
However, since it contains more than air, it poses the risk of
(2) When there is an effective opening with the adjacent room
suffocation if its density should rise excessively. Suffocation
for ventilation of leaking refrigerant gas (opening without
from leakage of refrigerant is almost non-existent. With the
a door, or an opening 0.15% or larger than the respective
recent increase in the number of high density buildings,
floor spaces at the top or bottom of the door).
however, the installation of multi air conditioner systems is
on the increase because of the need for effective use of floor Outdoor unit
space, individual control, energy conservation by curtailing heat Refrigerant tubing
and carrying power, etc.
Most importantly, the multi air conditioner system is able Indoor unit
to replenish a large amount of refrigerant compared to
conventional individual air conditioners. If a single unit of the
multi air conditioner system is to be installed in a small room,
select a suitable model and installation procedure so that if the (3) If an indoor unit is installed in each partitioned room and
refrigerant accidentally leaks out, its density does not reach the the refrigerant tubing is interconnected, the smallest room
limit (and in the event of an emergency, measures can be made of course becomes the object. But when mechanical
before injury can occur). ventilation is installed interlocked with a gas leakage
In a room where the density may exceed the limit, create an detector in the smallest room where the density limit is
opening with adjacent rooms, or install mechanical ventilation exceeded, the volume of the next smallest room becomes
combined with a gas leak detection device. The density is as the object.
given below. Refrigerant tubing
Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m3)
< Density limit (kg/m3) Outdoor unit
The density limit of refrigerant which is used in multi air
Very
conditioners is 0.3 kg/m3 (ISO 5149). small Indoor unit
room
Small Medium Large room
NOTE room room
1. If there are 2 or more refrigerating systems in a single
refrigerating device, the amount of refrigerant should be as Mechanical ventilation device – Gas leak detector
charged in each independent device.
For the amount of charge in this example: 3. The minimum indoor floor space compared with the
amount of refrigerant is roughly as follows: (When the
Outdoor unit ceiling is 2.7 m high)
e.g., charged
amount (10 kg) e.g., charged m2 m3
amount (15 kg) 125 337.5
120 324.0
115 310.5
Indoor unit 110 297.0
105 283.5
100 270.0
(when the ceiling is 2.7 m high)

95 256.0
90 243.0
Room A Room B Room C Room D Room E Room F 85 229.5 Range below the
Min. indoor volume

80 216.0 density limit of


Min. indoor floor area

75 202.5 0.3 kg/m³


The possible amount of leaked refrigerant gas in rooms A, (Countermeasures
B and C is 10 kg. 70 189.0
not needed)
65 175.5
The possible amount of leaked refrigerant gas in rooms D, 60 162.0
E and F is 15 kg. 55 148.5
50 135.0 Range above the
45 121.5 density limit of
40 108.0 0.3 kg/m³
(Countermeasures
35 94.5 needed)
30 81.0
25 67.5
20 54.0
15 40.5
10 27.0
5 13.5
0 0.0
0 10 20 30 40 50 60 70 80 90 100 kg
Total amount of refrigerant

iii

%QXGTKPFF 
Precautions for Installation Using New Refrigerant
1. Care regarding tubing
1-1. Process tubing
Material: Use C1220 phosphorous deoxidized copper specified in JIS H3300 “Copper and Copper Alloy Seamless Pipes and Tubes.”
For tubes of ø22.22 or larger, use C1220 T-1/2H material or H material, and do not bend the tubes.
Tubing size: Be sure to use the sizes indicated in the table below.
Use a tube cutter when cutting the tubing, and be sure to remove any flash. This also applies to distribution joints (optional).
When bending tubing, use a bending radius that is 4 times the outer diameter of the tubing or larger.

Use sufficient care in handling the tubing. Seal the tubing ends with caps or tape to prevent dirt,
CAUTION moisture, or other foreign substances from entering. These substances can result in system
malfunction.
Unit: mm
Material O
Outer diameter 6.35 9.52 12.7 15.88 19.05 22.22
Copper tube
Wall thickness 0.8 0.8 0.8 1.0 1.0 1.15

Unit: mm
Material 1/2 H, H
Outer diameter 25.4 28.58 31.75 38.1 41.28
Copper tube
Wall thickness 1.0 1.0 1.1 over 1.35 over 1.45

1-2. Prevent impurities including water, dust and oxide from entering the tubing. Impurities can cause R410A refrigerant deterioration
and compressor defects. Due to the features of the refrigerant and refrigerating machine oil, the prevention of water and other
impurities becomes more important than ever.

2. Be sure to recharge the refrigerant only in liquid form.


2-1. Since R410A is a non-azeotrope, recharging the refrigerant in gas form can lower performance and cause defects in the unit.
2-2. Since refrigerant composition changes and performance decreases when gas leaks, collect the remaining refrigerant and recharge
the required total amount of new refrigerant after fixing the leak.

3. Different tools required


3-1. Tool specifications have been changed due to the characteristics of R410A.
Some tools for R22- and R407C-type refrigerant systems cannot be used.
R407C tools Manifold gauge
Item New tool? compatible Remarks
with R410A?
Manifold gauge Yes No Types of refrigerant, refrigerating machine oil,
and pressure gauge are different.
Charge hose Yes No To resist higher pressure, material must be changed.
Vacuum pump Yes Yes Use a conventional vacuum pump if it is equipped
with a check valve. If it has no check valve,
purchase and attach a vacuum pump adapter.
Leak detector Yes No Leak detectors for CFC and HCFC that react to Vacuum pump
chlorine do not function because R410A contains
no chlorine. Leak detectors for HFC134a can be Outlet
used for R410A. Inlet
Flaring oil Yes No For systems that use R22, apply mineral oil
(Suniso oil) to the flare nuts on the tubing to
prevent refrigerant leakage. For machines that
use R407C or R410A, apply synthetic oil (ether
oil) to the flare nuts.
* Using tools for R22 and R407C and new tools for R410A together can cause defects.

3-2. Use R410A exclusive cylinder only.


Single-outlet valve Valve
(with siphon tube)
Liquid refrigerant should be
recharged with the cylinder
standing on end as shown.

Liquid

iv

%QXGTKPFF 
IMPORTANT INFORMATION REGARDING THE REFRIGERANT USED
This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. Do not vent gases into the atmosphere.

Refrigerant type: R410A


GWP(1) value: 1975
(1)
GWP = global warming potential

Periodical inspections for refrigerant leaks may be required depending on European or local legislation.
Please contact your local dealer for more information.

Please fill in with indelible ink,


the factory refrigerant charge of the product
the additional refrigerant amount charged in the field and
+ the total refrigerant charge
on the refrigerant charge label supplied with the product.

The filled out label must be adhered in the proximity of the product charging port (e.g. onto the inside of the service cover).

* English text printed on this label is original. Each


5 6 language label will be sealed on this original text.

1. Factory refrigerant charge of the product: see unit name plate


2. Additional refrigerant amount charged in the field
3. Total refrigerant charge
4. Contains fluorinated greenhouse gases covered by the Kyoto Protocol
5. Outdoor unit
6. Refrigerant cylinder and manifold for charging

%QXGTKPFF 
Contents
Section 1: OUTLINE OF 3WAY SYSTEM ................................................................................1-1
1. Line-up ................................................................................................................. 1-2
2. Features of 3WAY SYSTEM ................................................................................ 1-4
3. MARKINGS FOR DIRECTIVE 97/23/EC (PED) .................................................. 1-7
Section 2: DESIGN OF 3WAY SYSTEM .................................................................................. 2-1
1. Model Selecting and Capacity Calculator ............................................................ 2-2
2. System Design ................................................................................................... 2-16
3. Electrical Wiring ................................................................................................. 2-22
4. Installation Instructions ...................................................................................... 2-33
5. HOW TO PROCESS TUBING ........................................................................... 2-42
6. AIR PURGING ................................................................................................... 2-47
7. Optional Parts .................................................................................................... 2-50
8. Supplement ........................................................................................................ 2-66
Section 3: Control of 3WAY SYSTEM .................................................................................... 3-1
1. Main Operating Functions
2. Wireless Remote Controller
3. Timer Remote Controller (CZ-RTC2)
4. Simplified Remote Controller (CZ-RE2C2, CZ-RELC2)
5. System Controller (CZ-64ESMC2)
6. Schedule Time (CZ-ESWC2)
7. ON/OFF Controller (CZ-ANC2)
8. Intelligent Controller (CZ-256ESMC2)
9. Communication Adaptor (CZ-CFUNC2)
10. Remote Sensor (CZ-CSRC2)
11. LonWorks Interface (CZ-CLNC2)
12. Seri-Para I/O unit for outdoor unit (CZ-CAPDC2)
13. MINI Seri-para I/O Unit (CZ-CAPBC2)
14. Local Adaptor for ON/OFF Controller (CZ-CAPC2)
15. Web Interface (CZ-CWEBC2)
16. Intelligent Management System
* Refer to the 2WAY SYSTEM TECHNICAL DATA (TD831159)
Section 4: 3WAY SYSTEM UNIT SPECIFICATIONS .............................................................. 4-1
1. Outdoor Unit.......................................................................................................... 4-2
2. Indoor Unit
* Refer to the 2WAY SYSTEM TECHNICAL DATA (TD831159)
Section 5: TEST RUN ............................................................................................................... 5-1
1. Preparing for Test Run ......................................................................................... 5-2
2. Test Run Procedure ............................................................................................. 5-3
3. Main Outdoor Unit PCB Setting ........................................................................... 5-4
4. Auto Address Setting ........................................................................................... 5-6
5. Remote Controller Test Run Settings ................................................................ 5-16
6. Caution for Pump Down ..................................................................................... 5-16
7. Meaning of Alarm Messages ............................................................................. 5-17
Section 6: ELECTRICAL DATA ............................................................................................... 6-1
1. Outdoor Unit......................................................................................................... 6-2
2. Indoor Unit
* Refer to the 2WAY SYSTEM TECHNICAL DATA (TD831159)

vi

%QXGTKPFF 
Contents
Section 7: PCB AND FUNCTIONS .......................................................................................... 7-1
1. Outdoor Unit Control PCB .................................................................................... 7-2
2. Indoor Unit Control PCB Switches and Functions
* Refer to the 2WAY SYSTEM TECHNICAL DATA (TD831159)
Section 8: RENEWAL .............................................................................................................. 8-1
1. Precautions on Renewal Design & Installation .................................................... 8-2
2. Reference ...........................................................................................................8-11
3. INSTALLATION INSTRUCTIONS (VRF Renewal Kit)....................................... 8-13
Section 9: CAPACITY TABLE ................................................................................................. 9-1
1. Capacity Ratio of Outdoor Unit ............................................................................ 9-2
2. Cooling Capacity of Indoor Unit ......................................................................... 9-32

vii

%QXGTKPFF 
Outline of 3WAY SYSTEM

Contents

1. OUTLINE OF 3WAY SYSTEM


1. Line-up.................................................................................................................................1-2
2. Features of 3WAY SYSTEM................................................................................................1-4
2-1. Outline of 3WAY SYSTEM............................................................................................1-4
3. MARKINGS FOR DIRECTIVE 97/23/EC (PED)...................................................................1-7

1-1 9

5GEKPFF 
Outline of 3WAY SYSTEM

1. Line-up

Indoor units
Type 22 28 36 45 56 60 73 90 106 140 160
Capacity: kW 2.2 (7,500) 2.8 (9,600) 3.6 (12,000) 4.5 (15,000) 5.6 (19,000) 6.0 (20,500) 7.3 (25,000) 9.0 (30,000) 10.6 (36,000) 14.0 (47,800) 16.0 (54,600)
(BTU/h) Cooling / / / / / / / / / / /
/
Heating 2.5 (8,500) 3.2 (11,000) 4.2 (14,000) 5.0 (17,000) 6.3 (21,000) 7.1 (24,200) 8.0 (27,000) 10.0 (34,000) 11.4 (39,000) 16.0 (54,600) 18.0 (61,500)
4-Way Cassette
Type
(U1 Type)
S-22MU1E51 S-28MU1E51 S-36MU1E51 S-45MU1E51 S-56MU1E51 S-60MU1E51 S-73MU1E51 S-90MU1E51 S-106MU1E51 S-140MU1E51 S-160MU1E51
S-22MU1E5 S-28MU1E5 S-36MU1E5 S-45MU1E5 S-56MU1E5 S-73MU1E5 S-106MU1E5 S-140MU1E5 S-160MU1E5

4-Way Cassette
60×60 Type
(Y1 Type)
S-22MY1E5 S-28MY1E5 S-36MY1E5 S-45MY1E5 S-56MY1E5

2-Way Cassette
Type
(L1 Type)
S-22ML1E5 S-28ML1E5 S-36ML1E5 S-45ML1E5 S-56ML1E5 S-73ML1E5
1 Wall Mounted
Type
(K1 Type) S-22MK1E5 S-28MK1E5 S-36MK1E5 S-45MK1E5 S-56MK1E5 S-73MK1E5 S-106MK1E5

Ceiling Type
(T1 Type)
2 S-36MT1E5 S-45MT1E5 S-56MT1E5 S-73MT1E5 S-106MT1E5 S-140MT1E5

1-Way Cassette
Type (D1 Type)

S-28MD1E5 S-36MD1E5 S-45MD1E5 S-56MD1E5 S-73MD1E5

3 Low Silhouette
Ducted Type
(F1 Type) S-22MF1E5 S-28MF1E5 S-36MF1E5 S-45MF1E5 S-56MF1E5 S-73MF1E5 S-90MF1E5 S-106MF1E5 S-140MF1E5 S-160MF1E5

Low Silhouette
Ducted Type
(F2 Type)
4 S-22MF2E5 S-28MF2E5 S-36MF2E5 S-45MF2E5 S-56MF2E5 S-60MF2E5 S-73MF2E5 S-90MF2E5 S-106MF2E5 S-140MF2E5 S-160MF2E5

Slim Low Static


Ducted Type
(M1 Type)
S-22MM1E5 S-28MM1E5 S-36MM1E5 S-45MM1E5 S-56MM1E5

Floor Standing
5 Type
(P1 Type)
S-22MP1E5 S-28MP1E5 S-36MP1E5 S-45MP1E5 S-56MP1E5 S-71MP1E5

Concealed Floor
Standing Type
(R1 Type)

6 S-22MR1E5 S-28MR1E5 S-36MR1E5 S-45MR1E5 S-56MR1E5 S-71MR1E5

Type 73 106 140 224 280


High Static Pressure
Ducted Type
(E1 Type)
S-73ME1E5 S-106ME1E5 S-140ME1E5 S-224ME1E5 S-280ME1E5
7

9 1-2

5GEKPFF 
Outline of 3WAY SYSTEM

1. Line-up

Outdoor units

Model U-8MF2E8 U-10MF2E8 U-12MF2E8 U-14MF2E8 U-16MF2E8

Cooling 22.4 (76,500) 28.0 (95,600) 33.5 (114,300) 40.0 (136,500) 45.0 (153,600)
Capacity: kW (BTU/h)
Heating 25.0 (85,300) 31.5 (107,500) 37.5 (128,000) 45.0 (153,600) 50.0 (170,600)

unit: mm
Air intake

Air
intake

B
930

A
C
Air
intake

2
18
970
(Installation hole pitch)
1000
Top view
(104)

Air discharge Electrical


component box 3

4
1758
1654

5
856

853
835

363
930
601 7
71 858 71
Side view
Front view

Installation fixing bracket According to the installation site, you may choose the setting position
Installation side in the depth direction of the anchor bolt from "A", "B" or "C". 8
A : 894 (Installation hole pitch) * The tubing is routed out from the front.
B : 730 (Installation hole pitch) * The tubing is routed out from the bottom.
C : 730 (Installation hole pitch)

1-3 9

5GEKPFF 
Outline of 3WAY SYSTEM

2. Features of 3WAY SYSTEM

2-1. Outline of 3WAY SYSTEM


System example

Since all pipings are concentrated


CONCENTRATION into one pipe shaft, you can minimize
piping space and construction labor

* Panasonic makes it possible to link outdoor unit


CONNECTION Solenoid
*1
together for a large capacity (48HP).
valve kit

1 Indoor unit

If indoor/outdoor units need servicing, a ball


valve (optional) cuts off non-operational

2 units to let other units stay running.

ADDITION

If your indoor capacity load


System limitations changes in the future, it’s easy to
add on both indoor and outdoor
3 Maximum number of combined outdoor units 3 units using the same pipings.
Maximum horsepower of combined outdoor units 135kW (48 HP) * If the additional installment of outdoor and indoor units are expected,
the size of refrigerant piping should be decided according to the total capacity
Maximum number of connectable indoor units 52 *2
after the addition.
Indoor/outdoor unit capacity ratio 50~150% *1 The connection between the indoor unit(s) and the solenoid valve kit(s) has
Maximum actual piping length 180 m three (3) types of methods. For further details, refer to the Section 2.
3-4. "Connecting Multiple Indoor Units to a Single Solenoid Valve Kit".
4 Maximum level difference (when outdoor unit is lower)
Maximum total piping length
50 (40) m
500 m
*2 In the case of 26 hp (type 73.0 kW) or smaller units, the number is limited by
the total capacity of the connected indoor units.

Combination of outdoor units


Total horse
5 power
Inverter unit
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48

8 1 1 1 1 1 1 1 1 1
10 1 1
12 1 1 1 1
14 1 1 1 2 1 1 2 1 3 2 1
6 16 1 1 1 2 1 2 1 2 3

Combination of outdoor units (High efficiency combination)


Total horse
power 16 24 26 28 30 32
Inverter unit

7 8
10
2 3 2
1
2 2 1

12 1 2
14 1
16

Maximum number of connectable indoor units when connected with minimum capacity
8 Total horse
power 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48

Number of
15 19 22 27 30 34 38 41 46 49 52 52 52 52 52 52 52 52 52 52 52
indoor units

9 1-4

5GEKPFF 
Outline of 3WAY SYSTEM

2. Features of 3WAY SYSTEM

Dimensions

8, 10, 12, 14, 16 HP


Unit: mm
1000
(Top panel dimension)

8HP U-8MF2E8
10HP U-10MF2E8
12HP U-12MF2E8

B
14HP U-14MF2E8
930

A
C
16HP U-16MF2E8

970 Installation anchor hole


(8 – 15 × 21 elongated holes)
Top view
1
Dimensions of unit combination
*b
2-unit setting (Top panel dimension) Unit: mm
1000 *a 1000
(Top panel dimension) (Top panel dimension)
2

B
930

A
C

3
970 970
(Installation hole pitch)
Installation anchor hole Installation anchor hole
(8 – 15 × 21 elongated holes) (8 – 15 × 21 elongated holes)
Top view 4
3-unit setting
*b Unit: mm

1000
(Top panel dimension)
*a 1000
(Top panel dimension)
*a 1000
(Top panel dimension)
5
B

6
930

A
C

970 970 970


(Installation hole pitch) (Installation hole pitch) (Installation hole pitch) 7
Installation anchor hole Installation anchor hole
(8 – 15 × 21 elongated holes) (8 – 15 × 21 elongated holes)
Top view
• According to the installation site, you may choose the setting position in the depth direction of the anchor bolt from “A”, “B” or “C”.

For 2-unit setting For 3-unit setting


*a *b *a *b 8
A :894 (Installation hole pitch) * The tubing is routed out from the front. 60 2060 60 3120
B :730 (Installation hole pitch) * The tubing is routed out from the bottom. 180 2180 180 3360
C :730 (Installation hole pitch) 180 2180 180 3360

1-5 9

5GEKPFF 
Outline of 3WAY SYSTEM

2. Features of 3WAY SYSTEM

Capacity control
The compressor combination (DC inverter compressor + constant-speed compressor) allows smooth capacity
control from 0.8 HP to 48 HP.

Realization of smooth capacity control from


0.8 HP to 48 HP In case of 16 HP system
Capacity
For the outdoor units of 8, 10, 12, 14 and 16 HP, a DC
16
inverter and a constant-speed compressor both are installed.
Correspondence to capacity control, which is difficult with 12
a constant-speed compressor, is possible smoothly with DC1
a DC inverter. The performance difference at the time of
8
start of a constant-speed compressor also is eliminated. DC1 DC2

4 DC2 AC2
DC1
1 DC1 DC2 AC1 AC1

(Load)
Example of 2 unit connection

Priority selection is included for pairs of DC units (DC1 and DC2).


2 Priority selection is included for pairs of AC units (AC1 and AC2).

In case of 8, 10, 12, 14, 16 HP system

3
DC1

DC1 DC1 AC1 DC2 AC2


AC1
4

9 1-6

5GEKPFF 
Outline of 3WAY SYSTEM

3. MARKINGS FOR DIRECTIVE 97/23/EC (PED)

Rating nameplate figure

A: Model Name Various

B: Various
C:
D:

Operating Spec. Area


Various (Not for the PED)

E: bar (MPa) Various


1
F: bar (MPa) Various
G: kg. Various
Various (Not for the PED)

2
Various YYYY.MM

3
Various (Not for the PED)

5
Tabulation of Various data
A U-8MF2E8 U-10MF2E8 U-12MF2E8 U-14MF2E8 U-16MF2E8
B
C 7.96 kW, 12.6 A 10.6 kW, 16.3 A
380 – 415 V, 3 N~, 50 Hz
13.7 kW, 21.2 A 16.7 kW, 25.7 A 19.0 kW, 29.3 A
6
D 25 A 25 A 35 A 40 A 50 A
E 38.0 bar (3.80 MPa)
F 27.0 bar (2.70 MPa)
G 8.3 kg 8.5 kg 8.8 kg 9.3 kg 9.3 kg
7

1-7 9

5GEKPFF 
– MEMO –

1-8

5GEKPFF 
Design of 3WAY SYSTEM

Contents

2. DESIGN OF 3WAY SYSTEM


1. Model Selecting and Capacity Calculator .......................................................................... 2-2
1-1. Operating Range ............................................................................................................ 2-2
1-2. Procedure for Selecting Models and Calculating Capacity ............................................. 2-3
1-3. Design of Tubing Length.................................................................................................. 2-4
1-4. Check of Limit Density ...................................................................................................2-10
1-5. Calculation of Actual Capacity of Indoor Unit ............................................................... 2-11
2. System Design .................................................................................................................... 2-16
2-1. System Example ............................................................................................................2-16
2-2. Example of Tubing Size Selection for Extension and Additional Charge Amount ......... 2-18
3. Electrical Wiring ..................................................................................................................2-22
3-1. General Precautions on Wiring ..................................................................................... 2-22
3-2. Recommended Wire Length and Wire Diameter for Power Supply System ................. 2-22 1
3-3. Wiring System Diagrams ............................................................................................... 2-23
3-4. Connecting Multiple Indoor Units to a Single Solenoid Valve Kit .................................. 2-25
4. Installation Instructions ..................................................................................................... 2-33
Outdoor Unit ................................................................................................................. 2-33
4-1. Selecting the Installation Site for Outdoor Unit .............................................................. 2-33 2
4-2. Shield for Horizontal Exhaust Discharge ....................................................................... 2-34
4-3. Installing the Outdoor Unit in Heavy Snow Areas ......................................................... 2-34
4-4. Precautions When Installing in Heavy Snow Areas ...................................................... 2-34
4-5. Dimensions of Wind Ducting ......................................................................................... 2-34
4-6. Dimensions of Snow Ducting ........................................................................................ 2-34
3
4-7. Transporting .................................................................................................................. 2-35
4-8. Installing the Outdoor Unit .............................................................................................2-35
4-9. Routing the Tubing......................................................................................................... 2-37
4-10. Prepare the Tubing ......................................................................................................2-38 4
4-11. Connect the Tubing...................................................................................................... 2-38
Indoor Unit
*Refer to the 2WAY SYSTEM TECHNICAL DATA. (TD831159)
5. HOW TO PROCESS TUBING .............................................................................................. 2-42
5-1. Connecting the Refrigerant Tubing ................................................................................2-42 5
5-2. Connecting Tubing Between Indoor and Outdoor Units................................................. 2-43
5-3. Insulating the Refrigerant Tubing .................................................................................. 2-44
5-4. Taping the Tubes ........................................................................................................... 2-46
5-5. Finishing the Installation ................................................................................................2-46
6. AIR PURGING ...................................................................................................................... 2-47
6
Air Purging with a Vacuum Pump (for Test Run) Preparation.................................. 2-47
7. Optional Parts ..................................................................................................................... 2-50
7-1. Distribution Joint Kits
(CZ-P680PH2, P1350PH2, P224BH2, P680BH2, P1350BH2) ..................................... 2-50 7
7-2. Solenoid Valve Kit for 3-Way System (CZ-P56HR3, P160HR3).................................... 2-52
7-3. Solenoid Valve Controller (CZ-CAPE2)......................................................................... 2-56
7-4. Solenoid Valve Controller (CZ-CAPEK2)....................................................................... 2-62
7-5. VRF Renewal Kit (CZ-SLK2) ......................................................................................... 2-65
8. Supplement ......................................................................................................................... 2-66
8
8-1. Dimensions of Wind Ducting ......................................................................................... 2-66
8-2. Dimensions of Snow Ducting ........................................................................................ 2-78

2-1 9

5GEKPFF 
Design of 3WAY SYSTEM

1. Model Selecting and Capacity Calculator

1-1. Operating Range

Cooling Heating
50 25

46
45 20
18

40 15

Outdoor air intake temp. °C (WB)


35 10
Outdoor air intake temp. °C (DB)

30 5

Operating
25 0 range

20 Operating –5
1 range

15 –10

10 –15

–20
2 5
10 15 20 25 30 35

0 Indoor air intake temp. °C (DB)

–5

3 –10
10
14
15 20 25 30

Indoor air intake temp. °C (WB)

9 2-2

5GEKPFF 
Design of 3WAY SYSTEM

1. Model Selecting and Capacity Calculator

1-2. Procedure for Selecting Models and Calculating Capacity


Model Selection Procedure
Select the model and calculate the capacity for each refrigerant system according to the procedure shown below.
Calculation of the indoor air-conditioning load
Calculate the maximum air-conditioning load for each room or zone.
Selection of an air conditioning system
Select the ideal air conditioning system for air conditioning of each room or zone.
Design of the control system
Design a suitable control system for the selected air conditioning system.
Preliminary selection of indoor and outdoor units
Make preliminary selections that are within the allowable range for the system. ............ 2-4 ~ 2-10
Check of the tubing length and elevation difference
Check that the length of refrigerant tubing and the elevation difference are within the allowable
ranges. ....................................................................................................................................... 2-4 1
Calculation of the corrected outdoor unit capacity
Capacity correction coefficient for model. .................................................................... 2-11, 13, 14
Capacity correction coefficient for outdoor temperature conditions. .................................. 2-11, 13
Capacity correction coefficient for tubing length and elevation difference. ........................ 2-11, 14
Heating capacity correction coefficient for frosting/defrosting. ........................................... 2-11, 13 2
Calculation of the corrected capacity for each indoor unit
Capacity correction coefficient for indoor temperature conditions. .................................... 2-11, 14
Capacity distribution ratio based on the tubing length and elevation difference. ............... 2-11, 14
Calculation of the actual capacity for each indoor unit
Calculate the corrected indoor/outdoor capacity ratio, based on the corrected outdoor unit
capacity and the total corrected capacity of all indoor units in the same system. Use the result
3
to calculate the capacity correction coefficient for the indoor units. ............................. 2-11 ~ 2-14
Multiply the corrected capacity of each indoor unit by the capacity correction coefficient to
calculate the actual capacity for each indoor unit. ................................................................... 2-12
Recheck of the actual capacity for each indoor unit 4
If the capacity is inadequate, reexamine the unit combinations.
Example 1: Increasing the outdoor unit capacity. .................................................................... 2-18
Example 2: Increasing the indoor unit capacity. ...................................................................... 2-19
• Increasing the tubing size. ....................................................................................................... 2-20
Design of tubing
Create a tubing design which minimizes the amount of additional refrigerant charge as much
5
as possible. ...................................................................................................................... 2-4 ~ 2-6
If tubing extension is expected in the future, create the tubing design with adequate considera-
tion for this extension.
Select the tubing size for the main tube (LA) up to the No. 1 distribution joint based on the rated
cooling capacity of the outdoor unit. Select tubing sizes after the distribution point based on the 6
total rated cooling capacity of the connected indoor units.
Increasing the tubing size of the wide tubes can reduce the loss of capacity caused by longer
tubing lengths. (Only the main wide tube with the largest tube diameter (main tube LA and main
tubes after the distribution point that are the same size as LA) can be changed.) In this case,
it is necessary to recalculate the actual indoor unit capacities. ................................................ 2-20
7
Calculation of additional refrigerant charge amount
Calculate the additional refrigerant charge from the diameters and lengths of the refrigerant tub-
ing. Even if the wide tubing diameter was increased, determine the additional refrigerant charge
based only on the narrow tubing size. ...................................................................................... 2-21
Check the minimum indoor capacity (limit density) with respect to the amount of refrigerant. If the
limit density is exceeded, be sure to install ventilation equipment or take other corrective steps. .. 2-22
8
Design of electrical wiring capacity
Select a wiring capacity according to the method of power supply. ......................................... 2-24

2-3 9

5GEKPFF 
Design of 3WAY SYSTEM

1. Model Selecting and Capacity Calculator

1-3. Design of Tubing Length


Select the installation location so that the length and size of refrigerant tubing are within the allowable range shown
in the figure below.
1. Main tubing length LM = LA + LB …
2. Main distribution tubes LC – LH are selected according to the capacity after the
distribution joint.
3. The outdoor connection main tubing (LO portion) is determined by the total capacity of the outdoor
units that are connected to the tube ends.
4. Sizes of indoor unit connection tubing 1 – 40 are determined by the connection
tubing sizes on the indoor units.

T-joint tubing
(header joint system)
1 Balance tubing

For

2 Explanation of symbols
Max. 40cm
extension

For
extension *1
Max. 40cm Solenoid valve kit
Distribution joint
(CZ: purchased separately)

3 Ball valve (field supply)

T-joint (field supply)


Solidly welded shut R410A distribution joint
(pinch weld)

Note: Do not use commercially available T-joints for the liquid tubing and parts.
4 * Be sure to use special R410A distribution joints (CZ: purchased separately) for outdoor unit connections and tubing branches.
*1 The connection between the indoor unit(s) and the solenoid valve kit(s) has three (3) types of methods. For further details,
refer to the Section 2. 3-4. "Connecting Multiple Indoor Units to a Single Solenoid Valve Kit".

Ranges that Apply to Refrigerant Tubing Lengths and to Differences in Installation Heights

5 Items Marks Contents Length (m)


Actual length ≤ 180
L1 Max. tubing length
Equivalent length ≤ 200 *1
Difference between max. length and min. length from the No. 1
ΔL (L2 – L4) ≤ 40
distribution joint
6 Allowable tubing length LM Max. length of main tubing (at max. diameter) _ *2

1, 2... 40 Max. length of each distribution tube ≤ 30


L1+ 1+ 2... 39+ Total max. tubing length including length of each distribution tube (only ≤ 500 *3
A+ B+LF+LG+LH liquid tubing)
L5 Distance between outdoor units ≤ 10
7 H1
When outdoor unit is installed higher than indoor unit ≤ 50
When outdoor unit is installed lower than indoor unit ≤ 40
Allowable elevation difference
H2 Max. difference between indoor units ≤ 15
H3 Max. difference between outdoor units ≤4

8 Allowable length of joint tubing L3


T-joint tubing (field-supply); Max. tubing length between the first T-joint
and solidly welded-shut end point
≤2

L = Length, H = Height

9 2-4

5GEKPFF 
Design of 3WAY SYSTEM

1. Model Selecting and Capacity Calculator

NOTE

*1: If the longest tubing length (L1) exceeds 90 m (equivalent length), increase the sizes of the main tubes (LM) by
1 rank for the discharge tubes, suction tubes, and narrow tubes. (field supplied)
*2: If the longest main tube length (LM) exceeds 50 m, increase the main tube size at the portion before 50 m by 1
rank for the suction tubes and discharge tubes. (field supplied)
(For the portion that exceeds 50 m, set based on the main tube sizes (LA) listed in the table on the following page.)
*3: 24hp - 30hp of high efficiency combination is 300m.

Refrigerant Charge Amount at Shipment (for outdoor unit)


U-8MF2E8 U-10MF2E8 U-12MF2E8 U-14MF2E8 U-16MF2E8
8.3 kg 8.5 kg 8.8 kg 9.3 kg 9.3 kg

Additional Refrigerant Charge


1
Additional refrigerant charge amount is calculated from the liquid tubing total length as follows.
Required amount of additional refrigerant charge
= [ (Amount of additional refrigerant charge per meter of each size of liquid tube × its tube length) + (...) + (...)]
+ [(Necessary amount of additional refrigerant charge per outdoor unit + (...) + (...)]
+ [(Necessary amount of additional refrigerant charge per refrigerant circuit for 3 way system) + (...) + (...)]
2
* Always charge accurately using a scale for weighing.
* If the existing tubing is used and the amount of on-site refrigerant charge exceeds the value listed below, change the size
of the tubing to reduce the amount of refrigerant.
Total amount of refrigerant for the system with 1 outdoor unit : 50 kg
Total amount of refrigerant for the system with 2 outdoor units : 80 kg
3
Total amount of refrigerant for the system with 3 outdoor units : 100 kg (However, 24hp - 30hp of high efficiency combination
is 80kg.)
Amount of Additional Refrigerant Charge Per Meter, According to Liquid Tubing Size

Liquid tubing size 6.35 9.52 12.7 15.88 19.05 22.22 25.4 4
Amount of additional refrigerant charge/m (g/m) 26 56 128 185 259 366 490

Necessary Amount of Additional Refrigerant Charge Per Outdoor Unit


U-8MF2E8 U-10MF2E8 U-12MF2E8 U-14MF2E8 U-16MF2E8
5
8.0 kg 8.3 kg 8.5 kg 9.0 kg 9.0 kg

Necessary amount of additional refrigerant charge per refrigerant circuit for 3 way system
(per 1 refrigerant circuit system)
Total actual tubing length 100m or less 200m or less 300m or less 400m or less 500m or less 6
Amount of additional
--- 2.0 kg 3.0 kg 5.0 kg 6.0 kg
refrigerant charge/system

System Limitations
Max. No. allowable connected outdoor units 3 *2 7
Max. capacity allowable connected outdoor units 135 kW (48 hp)
Max. connectable indoor units 52 *1
Max. allowable indoor/outdoor capacity ratio 50 – 150 % *3

*1: In the case of 22 hp (type 61.5 kW) or smaller units, the number is limited by the total capacity of the connected indoor units. 8
*2: Up to 3 units can be connected if the system has been extended.
*3: It is strongly recommended that you choose the unit so the load can become between 50 and 130%.

2-5 9

5GEKPFF 
Design of 3WAY SYSTEM

1. Model Selecting and Capacity Calculator

Tubing size
Main Tubing Size (LA) Unit: mm

kW 22.4 28.0 33.5 40.0 45.0 50.4 56.0 61.5 68.0 73.0 78.5 85.0 90.0 96.0
Total system
8 10 12 14 16 18 20 22 24 26 28 30 32 34
horsepower
* 8 8 8 8 * 12 * * * *
Combined 8 8 8 14 8 16 8 16 8 8
8 10 12 14 16 8 8 14 8 14 8 16 12 12
outdoor units 8 10 12 14 16 14
8 10 12 14 12 14

Suction tubing (mm) ø19.05 ø22.22 ø25.4 ø28.58 ø28.58 ø31.75

Discharge tubing (mm) ø15.88 ø19.05 ø22.22 ø25.4 ø28.58

Liquid tubing (mm) ø9.52 ø12.7 ø15.88 ø19.05

* High efficiency combination


1 kW
Total system
101.0 106.5 113.0 118.0 123.5 130.0 135.0

36 38 40 42 44 46 48
horsepower
Combined 8 8 8 14 14 16 16
outdoor units 14 14 16 14 14 16 16
14 16 16 14 16 14 16

2 Suction tubing (mm)

Discharge tubing (mm) ø28.58


ø38.1

ø31.75
Liquid tubing (mm) ø19.05

*1: If future extension is planned, select the tubing diameter based on the total horsepower after extension.
However extension is not possible if the resulting tubing size is two ranks higher.
3 *2: The balance tube (outdoor unit tube) diameter is ø6.35.
*3: Type 1 tubing should be used for the refrigerant tubes.
*4: If the length of the longest tube (L1) exceeds 90 m (equivalent length), increase the main tube (LM) size by 1 rank for the
suction, discharge, and liquid tubes. (Use field-supply reducers.) (Select from the table above “Main Tubing Size (LA)” and
the next page’s table “Refrigerant tubing”.)

4 *5: If the longest main tube length (LM) exceeds 50 m, increase the main tube size at the portion before 50 m by 1 rank for
the suction tubes and discharge tubes.
(For the portion that exceeds 50 m, set based on the main tube sizes (LA) listed in the table above.)

Size of tubing (LO) between outdoor units


Select the size of tubing between outdoor units based on the main tubing size (LA) as given in the table above.

5 Main Tubing Size After Distribution (LB, LC...) Unit: mm


hp = horsepower
7.1 16.0 25.0 30.0 36.4 42.0 47.6 58.8 70.0
Total capacity Below kW (2.5 hp) (6 hp) (9 hp) (11 hp) (13 hp) (15 hp) (17 hp) (21 hp) (25 hp)
after distribution 7.1 16.0 25.0 30.0 36.4 42.0 47.6 58.8
Over kW – (2.5 hp) (6 hp) (9 hp) (11 hp) (13 hp) (15 hp) (17 hp) (21 hp)
(mm) ø15.88 ø19.05 ø19.05 ø22.22 ø25.4 ø25.4 ø28.58 ø28.58 ø28.58
6 Tubing size
Suction tubing
Discharge tubing (mm) ø12.7 ø15.88 ø15.88 ø19.05 ø19.05 ø22.22 ø22.22 ø22.22 ø25.4
Liquid tubing (mm) ø9.52 ø9.52 ø9.52 ø9.52 ø12.7 ø12.7 ø12.7 ø15.88 ø15.88

75.6 98.0 103.6 –


Total capacity Below kW (27 hp) (35 hp) (37 hp)

7 after distribution
Over kW
70.0
(25 hp)
75.6
(27 hp)
98.0
(35 hp)
103.6
(37 hp)
Suction tubing (mm) ø31.75 ø31.75 ø38.1 ø38.1
Tubing size Discharge tubing (mm) ø25.4 ø28.58 ø28.58 ø31.75
Liquid tubing (mm) ø19.05 ø19.05 ø19.05 ø19.05

8 *1: The outdoor unit connection tubing (LO) is determined by the total capacity of the outdoor units connected to the tube
ends. The tubing size is selected based on the table of main tube sizes after the branch.
*2: If the total capacity of the indoor units connected to the tube ends is different from the total capacity of the outdoor units,
then the main tube size is selected based on the total capacity of the outdoor units.
(For LA, LB, and LF in particular)

9 2-6

5GEKPFF 
Design of 3WAY SYSTEM

1. Model Selecting and Capacity Calculator

Outdoor Unit Tubing Connection Size ( A ~ C) Unit: mm


kW 22.4 28.0 33.5 40.0 45.0
ø19.05 ø22.22 ø25.4 ø28.58
Suction tubing
Brazing connection
ø15.88 ø19.05 ø22.22
Discharge tubing
Flare Brazing connection
ø9.52 ø12.7
Liquid tubing
Flare Brazing Flare Suction tube
ø6.35 Balance tube Discharge tube
Balance tubing
Flare connection
Liquid tube

Indoor Unit Tubing Connection ( 1 ~ 40 ) Unit: mm


Indoor unit type 22 28 36 45 56 60 73 90 106 140 160 224*1 280 *1 1
Distribution Suction tubing ø15.88 ø19.05 ø22.22
joint–
solenoid Discharge tubing ø12.7 ø15.88 ø19.05
valve
kit tubing Liquid tubing ø9.52 ø9.52 ø9.52
Solenoid
Wide tubing ø12.7 ø15.88 ø19.05 ø22.22
2
valve
kit– Indoor
unit tubing Narrow tubing ø6.35 ø9.52 ø9.52 ø9.52
connection

*1: For the solenoid valve kits, use type 160 with parallel specifications. Branch the tubing before and after the solenoid valve kits. 3
Required Copper Tubing Dimensions Unit: mm
Material 0

Copper tubing
Outer diameter 6.35 9.52 12.7 15.88 19.05 22.22 4
Wall thickness 0.8 0.8 0.8 1.0 1.0 1.15

Material 1/2 H, H
Outer diameter 25.4 28.58 31.75 38.1 41.28
Copper tubing
Wall thickness 1.0 1.0 1.1 over1.35 over1.45 5

Refrigerant tubing (Design pressure capability: 3.3 MPa)

Tubing size (mm)


* When bending the tubes, use a bend- 6
Material 0 Material 1/2H • H ing radius that is at least 4 times the
ø6.35 t0.8 ø25.4 t1.0 outer diameter of the tubes.
In addition, take sufficient care to avoid
ø9.52 t0.8 ø28.58 t1.0
crushing or damaging the tubes when
ø12.7 t0.8 ø31.75 t1.1 bending them.
ø15.88 t1.0 ø38.1 over t1.35
7
ø19.05 t1.0 ø41.28 over t1.45
ø22.22 t1.15

* When bending the tubes, use a bending radius that is at least 4 times the outer diameter of the tubes.
In addition, take sufficient care to avoid crushing or damaging the tubes when bending them. 8

2-7 9

5GEKPFF 
Design of 3WAY SYSTEM

1. Model Selecting and Capacity Calculator

Installation standards
Relationship between A/C units and the refrigerant tubing

Outdoor unit 4-tube layout Outdoor unit 3-tube layout Solenoid 2-tube layout Indoor unit
valve kit
Suction tube Suction tube Wide tube (gas)
Discharge tube Discharge tube Narrow tube (liquid)
Narrow tube Narrow tube
Balance tube

Install the solenoid valve kit 30 m or less from the indoor unit.
In quiet locations such as hospitals, libraries, and hotel rooms, the refrigerant noise may be somewhat notice-
able. It is recommended that the solenoid valve kit be installed inside the corridor ceiling, at a location outside
the room.
The solenoid valve kit must be located not less than 2.5m above the floor or that cannot be touched.
Room Room Room Room
1 Indoor unit Indoor unit Indoor unit Indoor unit

Desirable Undesirable

Hallway Hallway
Solenoid
2 Solenoid
valve kit

valve kit
Common solenoid valve kit
Multiple indoor units under group control can utilize a solenoid valve kit in common.
Categories of connected indoor unit capacities are determined by the solenoid valve kit.
3 Type of solenoid valve kit Total capacity of indoor units (kW)
CZ-P160HR3 5.6 < Total capacity 16.0
CZ-P56HR3 2.2 Total capacity 5.6
If the capacity range is exceeded, use 2 solenoid valves connected in parallel.
4 (2) When adding ball valve for outdoor unit
1. Location: Install the ball valve at the main tube of the distribution joint.

Outdoor unit

5 for extension

Ball valve (for extension) Distribution joint


(Planned expansion)
Balance tube

(Suction tube)

6 Discharge tube

Main tube
Main tube of distribution joint

Less than 40 cm Liquid tube


To indoor unit
2. Installation requirements
7 • Be sure to install the ball valve up-grade to prevent the inadvertent flow of oil.
• Install the ball valve at the shortest distance (within 40 cm) from the main tube. If the diameter of the ball valve
is smaller than that of the main tube, use a reducer or the like to reduce the size of the tubing at that location.
NOTE

8 • If the ball valve is installed at the outdoor unit (including extension for outdoor unit), face the service port of
the valve toward the outdoor unit side (see above illustration; dotted line) and allow a distance of over 50 cm
from the outdoor unit. If the ball valve is installed between the indoor unit (including extension for indoor unit)
and the main tube, face the ball valve toward the indoor unit side (see above illustration; dotted line).
• Use a field supply ball valve.
9 2-8

5GEKPFF 
Design of 3WAY SYSTEM

1. Model Selecting and Capacity Calculator

Straight equivalent length of joints


Design the tubing system by referring to the following table for the straight equivalent length of joints.

Straight Equivalent Length of Joints

Wide tubing size (mm) 12.7 15.88 19.05 22.22 25.4 28.58 31.8 38.1

90° elbow 0.3 0.35 0.42 0.48 0.52 0.57 0.7 0.79

45° elbow 0.23 0.26 0.32 0.36 0.39 0.43 0.53 0.59

U-shape tube bent (R60 100 mm) 0.9 1.05 1.26 1.44 1.56 1.71 2.1 2.37

Trap bend 2.3 2.8 3.2 3.8 4.3 4.7 5.0 5.8

Y-branch distribution joint Equivalent length conversion not needed. 1


Ball valve for service Equivalent length conversion not needed.

Capacity loss caused by differences in tubing diameters


2
* Capacity loss will occur if a tubing system that matches the horsepower is not selected (for example, if a tubing
system was determined and installed with no plan for extension and extension occurs later). The loss rate can
be found from the graph below.

Cooling
Heating 3
ø19.05 ø22.22 ø25.4
ø28.58 ø31.75
95
Capacity ratio based on Suction and

96
4
Discharge tubes diameter (%)

97

98

99
5
100
10 12 14 16 18 20 26 30 35 40 45 46 47 48
ø22.22 ø25.4 ø28.58 ø31.75 ø38.1

Recommended Suction and Discharge tubes diameter (mm) 6


(Reading the graph)
<Example 1>
Currently a 20 HP system and ø28.58 Suction & Discharge tubings are used. Subsequently the system is expand-
ed, with 8 HP added to the same tubing system. 7
• Horsepower after extension: 20 + 8 = 28 HP
• From the graph above: Cooling: Capacity ratio is 96.7%. Actual capacity = 28 × 0.967 = 27.1 HP
Heating: Capacity ratio is 98.6%. Actual capacity = 28 × 0.986 = 27.6 HP

2-9 9

5GEKPFF 
Design of 3WAY SYSTEM

1. Model Selecting and Capacity Calculator

1-4. Check of Limit Density


Check of limit density

Always check the gas den-


WARNING sity limit for the room in
which the unit is installed.

When installing an air conditioner in a room, it is neces- Minimum indoor volume and floor area as against the
sary to ensure that even if the refrigerant gas accident- amount of refrigerant is roughly as given in the follow-
ally leaks out, its density does not exceed the limit level ing table.
for that room.
as given in the following table. m2 m3
m2 100m3 270.0
If the density could exceed the limit level, it is neces- 125 337.5
sary to provide an opening between the unit and the 120 95324.0 256.5
adjacent room, or to install mechanical ventilation 115 90310.5 243.0
Range below the
1 which is interlocked with the leak detector.
110 85297.0 229.5

(when the ceiling is 2.7 m high)


105 80283.5 216.0 density limit of
100 270.0 0.3 kg/m3
( Total refrigerant charge amount : kg ) 95 75256.0 202.5 (Countermeasures

Min. indoor volume


( Minimum Indoor volume where indoor unit is installed : m3 ) 90 70243.0 189.0 not needed)
high)
2.7 marea
85 65229.5 175.5 Range below the
Limit density 0.3 (kg/m3) 80 60216.0 162.0 density limit of
0.3 kg/m³
indooris floor

Min. indoor volume


75 202.5
2 55 148.5 (Countermeasures
Min. indoor floor area

The limit density of refrigerant which is used in this unit 70 189.0


not needed) Range above the
65 50175.5 135.0
is 0.3 kg/m3 (ISO 5149).
Min.ceiling

60 45162.0 121.5
density limit of
55 40148.5 108.0 0.3 kg/m3
The shipped outdoor unit comes charged with the Range(Countermeasures
above the
(when the

50 35135.0 94.5
45 121.5 needed)
density limit of 0.3
amount of refrigerant fixed for each type, so add it to
40 30108.0 81.0 kg/m³
the amount that is charged in the field. (For the refriger- (Countermeasures
3 ant charge amount at shipment, refer to the unit’s
35 25 94.5
30 20 81.0
67.5
54.0
needed)

nameplate.) 25 15 67.5 40.5


20 54.0 20 30 40 50 60 70 80 kg
15 40.5 Total amount of refrigerant
Pay special attention to any 10 27.0
CAUTION 5 13.5
location, such as a basement,
0 0.0
4 etc., where leaking refrigerant
can accumulate, since refrig-
0 10 20 30 40 50 60 70 80 90 100 kg
Y1, M1 Types
Total amount of refrigerant
erant gas is heavier than air.

9 2-10

5GEKPFF 
Design of 3WAY SYSTEM

1. Model Selecting and Capacity Calculator

1-5. Calculation of Actual Capacity of Indoor Unit

Calculating the actual capacity of each indoor unit


Because the capacity of a multi air-conditioner changes according to the temperature conditions, tubing length,
elevation difference and other factors, select the correct model after taking into account the various correction values.
When selecting the model, calculate the corrected capacities of the outdoor unit and each indoor unit.
Use the corrected outdoor unit capacity and the total corrected capacity of all the indoor units to calculate the actual final
capacity of each indoor unit.

1. Outdoor unit capacity correction

Outdoor unit capacity correction (kW) = Rated capacity × (A) × (B) × (C) × (D)

(A) Capacity correction for the outdoor unit temperature conditions (%)
Read the capacity correction for outdoor unit temperature, indoor unit temperature and indoor/ outdoor ratio as shown
in the section “9. CAPACITY TABLE”.
1
* Indoor unit temperature is indoor unit rated capacity - weighted average temperature.
Example
Cooling operation
No. (a) Rated capacity (b) Intake temperature (a) × (b) 2
1 2.8 kW 19 WB 53.2
2 3.6 kW 18 WB 64.8
3 4.5 kW 17 WB 76.5
4 5.6 kW 16 WB 89.6
3
((a)×(b))
Rated capacity-weighted average temperature = = 17.2WB
(a)
* The indoor/ outdoor ratio should be selected according to the real rated capacity.
Example
There are 4 indoor units for class 28, 36, 45, 56 and the outdoor unit HP is 8 (22.4kW in the cooling-mode, 25.0kW in the 4
heating-mode).

No. Rated cooling capacity Rated heating capacity


1 2.8 kW 3.2 kW
2 3.6 kW 4.2 kW 5
3 4.5 kW 5.0 kW
4 5.6 kW 6.3 kW
Total 16.5 kW 18.7 kW
I/O ratio 73.7% 74.8 %
6
(B) Capacity correction coefficient for outdoor unit tubing length (%)
From the graph of capacity change characteristics resulting from tubing length and elevation difference on page “ 2-14 ”,
read the capacity correction coefficient.
* Use the lowest capacity changing ratio. Usually, the furthest and highest or the lowest indoor unit is used.
7
(C) Surplus capacity correction coefficient for outdoor unit temperature conditions (%)
From the graph of surplus capacity characteristics resulting from outdoor temperature on page “ 2-13 ”, read the capacity
correction coefficient.
8
(D) Capacity correction coefficient for outdoor unit frosting and defrosting during heating operation (%)
From the outdoor unit heating capacity correction coefficient during frosting / defrosting on page “ 2-13 ”, read the capacity
correction coefficient.

2-11 9

5GEKPFF 
Design of 3WAY SYSTEM

1. Model Selecting and Capacity Calculator

2. Indoor unit capacity correction coefficient

Indoor unit capacity correction (kW) = (G) × (H) × (C) × (D)


* Indoor unit capacity correction ≦ (G)

(E) Capacity correction for the indoor unit temperature conditions (kW)
From the graph of indoor capacity characteristics on page “ 2-14 ”, read the capacity correction coefficient for indoor unit
temperature conditions.
(E) = Capacity correction coefficient for indoor unit temperature conditions × Rated capacity

(F) Calculate the Capacity distribution ratio (%)


(E)
(F) =
1 (E)

(G) Distribute the outdoor unit capacity among each indoor unit (kW)
(G) = (A) × (F)

2 (H) Capacity correction coefficient for tubing length and elevation difference (%)
From the graph of capacity change characteristics resulting from tubing length and elevation difference on page “ 2-14 ”,
read the capacity correction coefficient.

9 2-12

5GEKPFF 
Design of 3WAY SYSTEM

1. Model Selecting and Capacity Calculator

Surplus capacity correction coefficient (%)

cooling heating

Surplus capacity correction coefficient (%)


Surplus capacity correction coefficient (%)

125 125

120 120

115 115

110 110

105 105

100 100

95 95

90
-5 0 5 10 15 20 25 30 35 40 45
90
-25 -20 -15 -10 -5 0 5 10 15 20 25 1
Outdoor air intake temp. ( °C DB) Outdoor air intake temp. ( °C WB)

3. Graph of capacity correction coefficients 2


Outdoor unit heating capacity correction coefficient during frosting/defrosting (1 – (4))

Outdoor intake
air temp. –20 –15 –10 –8 –6 –5 –4 –2 –1 0 1 2 3 4 5 6
(°CWB, RH85%) 3
Correction coefficient 0.97 0.97 0.97 0.96 0.94 0.91 0.89 0.87 0.87 0.87 0.88 0.89 0.91 0.92 0.95 1.0

* To calculate the heating capacity with consideration for frosting/defrosting operation, multiply the heating capacity
found from the capacity graph by the correction coefficient from the table above.
4

2-13 9

5GEKPFF 
Design of 3WAY SYSTEM

1. Model Selecting and Capacity Calculator

Graph of indoor unit capacity characteristics (2 – (2))


Indoor unit cooling capacity characteristics Indoor unit heating capacity characteristics
indicates the rating point. indicates the rating point.

Rate of heating capacity change (%)


140 120
Rate of cooling capacity change (%)

130 115
110
120
105
110 100
100 95

90 90
85
80
80
70 75
60 70
14 15 16 17 18 19 20 21 22 23 24 25 15 16 17 18 19 20 21 22 23 24 25 26 27
Indoor air intake temp. (˚C WB) Indoor air intake temp. (˚C DB)
1 Graph of capacity change characteristics resulting from tubing length and elevation difference (1 / 2 – (3))
(Performance correction coefficients by elevation difference of refrigerant tube length [performance change rate ÷ 100] is
calculated by the following line map.)
<Cooling>
2 Base capacity
change rate 92 90 88 86 84 82 80 78 76 74 72 70 68 66
50

40 94
Elevation difference (m)

96
3 30

20 98

10 100
%
0

4 -10

-20

-30

-40
5 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200
Equivalent length (m)
<Heating>
Base capacity
change rate 94 93 92 91 90 89 88 87 86 85 84 83 82 81 80 79 78 77 76
50 95

6 40
97
96

30
98
Elevation difference (m)

20 99
100
10 %
7 0
-10

-20

8 -30

-40
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200

Equivalent length (m)

9 2-14

5GEKPFF 
Design of 3WAY SYSTEM

1. Model Selecting and Capacity Calculator

The positive side for the elevation difference indicates that the outdoor unit is installed at a higher position than the indoor units.
The negative side indicates the opposite.
The capacity loss that is caused by the tubing length can be reduced by increasing the sizes of the discharge tubes and
suction tubes. Refer to Table 1 and make the appropriate changes. However be sure that the total length does not exceed
the maximum.
* The only sizes which can be increased are the LM (main tube with the largest diameter) discharge tubes and suction tubes,
and the changes are limited to those shown in Table 1.
In addition, note that the additional refrigerant charge is determined only by the liquid tube size.

Table 1. Equivalent Length Correction Coefficient when the Size of the Discharge Tubes and Suction
Tubes (LM) is Increased

Standard tubing diameter


ø12.7 ø15.88 ø19.05 ø22.22 ø25.4 ø28.58 ø31.75 ø38.1
(discharge tube, mm)
Tubing diameter after
change (suction tube, mm)
ø15.88 ø19.05 ø22.22 ø25.4 ø28.58 ø31.75 ø38.1 ø41.28 1
Equivalent length
0.4 0.5 0.6 0.7
correction coefficient

* If the size of the discharge tubes and suction tubes (LM) have been increased, apply the correction coefficient
from Table 1 and calculate the equivalent length of the LM section. 2
Equivalent length of tubing after size increase
= Standard tubing equivalent length × Equivalent length correction coefficient

2-15 9

5GEKPFF 
Design of 3WAY SYSTEM

2. System Design

2-1. System Example


(1) Below are the tables created using the “PAC System Diagram Software.”

Outdoor unit 1 Solenoid valve kit

20m
10m 10m 20m

Elevation
difference: 10 m
10m 10m 5m

Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 4

Selection conditions
Assumes that installation is in a 50 Hz region.
1 Room 1 Room 2 Room 3 Room 4
Outdoor unit (indoor unit 1) (indoor unit 2) (indoor unit 3) (indoor unit 4)
Air condition (DB/WB) 33.0 / 22.5 26.0 / 18.0 26.0 / 18.0 26.0 / 18.0 26.0 / 18.0
Cooling
Max. load (kW) 14.2 12.2 6.2 3.5
Air condition (DB/WB) 3.0 / 2.0 21.0 / 16.0 21.0 / 16.0 21.0 / 16.0 21.0 / 16.0
2 Heating
Max. load (kW) 14.7 13.0 6.3 3.7
Actual tubing length 60 m 30 m 40 m 45 m 60 m
Equivalent length 72 m 36 m 48 m 54 m 72 m

Preliminary selection
3 Outdoor unit Room 1 Room 2 Room 3 Room 4
(indoor unit 1) (indoor unit 2) (indoor unit 3) (indoor unit 4)
Selected model U-14MF2E8 Type 160 Type 140 Type 73 Type 36
Load (cooling/heating) (kW) 14.2 / 14.7 12.2 / 13.0 6.2 / 6.3 3.5 / 3.7
Rated capacity (cooling/heating) (kW) 40.0 / 45.0 16.0 / 18.0 14.0 / 16.0 7.3 / 8.0 3.6 / 4.2
4 Actual capacity (cooling/heating) (kW) 14.5 / 14.9 12.4 / 13.0 6.4 / 6.5 3.0 / 3.3

Calculate the actual capacity results according to the capacity calculation procedure on page"2-11" to "2-15".
Room 1 Room 2 Room 3 Room 4
Outdoor unit (indoor unit 1) (indoor unit 2) (indoor unit 3) (indoor unit 4)
5 Rated capacity (cooling/heating) (kW) 40.0 / 45.0 16.0 / 18.0 14.0 / 16.0 7.3 / 8.0 3.6 / 4.2
(A) Capacity table 38.4 / 44.6
Capacity estimation coefficient
(B) 0.899 / 0.916
: Equivalent tubing length

6 (C)
Capacity estimation coefficient
: Temperature conditions
1.019 / 1.000 1.019 / 1.000 1.019 / 1.000 1.019 / 1.000 1.019 / 1.000

Capacity estimation coefficient


(D) - / 0.89
: Frosting / defrosting
(E) Estimation capacity 14.9 / 17.3 13.1 / 15.4 6.81 / 7.70 3.36 / 4.04
(F) Capacity distribution ratio 0.391 / 0.390 0.342 / 0.346 0.178 / 0.173 0.088 / 0.091
7 (G) = (A) x (F) 15.0 / 17.4 13.1 / 15.4 6.9 / 7.7 3.4 / 4.1
Capacity estimation coefficient
(H) 0.945 / 0.961 0.924 / 0.946 0.914 / 0.939 0.882 / 0.916
: Equivalent tubing length
Actual capacity (cooling / heating) (kW) 14.5 / 14.9 12.4 / 13.0 6.4 / 6.5 3.0 / 3.3

8 Actual capacity = (G) x (H) x (C) x (D)

9 2-16

5GEKPFF 
Design of 3WAY SYSTEM

2. System Design

Indoor unit changes


Increase by one rank because the capacity of the indoor unit 4 is lower than the maximum load.
Calculating the actual capacity in the same way as Preliminary selection

Outdoor unit Room 1 Room 2 Room 3 Room 4


(indoor unit 1) (indoor unit 2) (indoor unit 3) (indoor unit 4)
Selected model U-14MF2E8 Type 160 Type 140 Type 73 Type 45
Load (cooling/heating) (kW) 14.2 / 14.7 12.2 / 13.0 6.2 / 6.3 3.5 / 3.7
Rated capacity (cooling/heating) (kW) 40.0 / 45.0 16.0 / 18.0 14.0 / 16.0 7.3 / 8.0 4.5 / 5.0
Actual capacity (cooling/heating) (kW) 14.5 / 14.6 12.4 / 12.8 6.4 / 6.4 3.8 / 3.9

Outdoor unit changes


The capacity of the indoor units 1 and 2 is lower than the maximum load.
Increase the capacity of the outdoor unit by one rank because of inability to increase the indoor unit 1 by one rank.
Calculating the actual capacity in the same way as Preliminary selection
1
Outdoor unit Room 1 Room 2 Room 3 Room 4
(indoor unit 1) (indoor unit 2) (indoor unit 3) (indoor unit 4)
Selected model U-16MF2E8 Type 160 Type 140 Type 73 Type 45
Load (cooling/heating) (kW) 14.2 / 14.7 12.2 / 13.0 6.2 / 6.3 3.5 / 3.7 2
Rated capacity (cooling/heating) (kW) 45.0 / 50.0 16.0 / 18.0 14.0 / 16.0 7.3 / 8.0 4.5 / 5.0
Actual capacity (cooling/heating) (kW) 14.4 / 14.8 12.3 / 13.0 6.3 / 6.4 3.8 / 3.9

For both cooling and heating in all rooms, actual capacity is now greater than or equal to the maximum load.
Now, the selection is completed.
3

2-17 9

5GEKPFF 
Design of 3WAY SYSTEM

2. System Design

(3) Increasing the size of the refrigerant tubing


Increasing the tubing size of the suction and discharge tubes can reduce the loss of capacity caused by longer
tubing lengths. (Only the main suction and discharge tubes with the largest tube diameter (main tube LA and
main tubes after the distribution point that are the same size as LA) can be changed.)
In this case, it is necessary to recalculate the actual indoor unit capacities. Refer to the table below to increase
the tubing size. However, total tubing length must not exceed the maximum allowable tubing length.

• Correction coefficient for equivalent length when the size of the largest main
wide tube is increased
Standard tube diameter
ø31.75 ø38.1
(suction and discharge tubes, mm)
Tube diameter after change
ø38.1 ø41.28
(suction and discharge tubes, mm)
Equivalent length
0.6 0.7
correction coefficient
1 Tubing equivalent length after size increase
= Standard tubing equivalent length × Equivalent length correction coefficient

2 2-2. Example of Tubing Size Selection for Extension and Additional Charge Amount
• Sample calculation for the system below

Outdoor units
3 10HP 14HP 14HP
10HP: SPW-CR904GDZH8B
10HP: SPW-CR904GDZH8B
8HP: SPW-CR704GDZH8B
Lc Lb La
Extension Extension indoor units
outdoor units LP
Elevation difference
H=4m LA LF
LB LC LD LE1 LE2
4 L1 L2 L3 L4 L5 L6
Elevation difference LN
H=5m Type 106 Type 56 Type 28 Type 106 Type 106 Type 73
LI LJ
LG LH
L8 L9 L10 L11
L7
5 Elevation difference
H=5m LK Type 106
LM
Type 73 Type 73 Type 36 Type 28

LL
Solenoid Valve Kit *
L12 L13 L14 L15

Type 106 Type 106 Type 73 Type 56

6 * The connection between the indoor unit(s) and the solenoid valve kit(s) has three (3) types of methods.
For further details, refer to the Section 2. 3-4. "Connecting Multiple Indoor Units to a Single Solenoid Valve Kit".

9 2-18

5GEKPFF 
Design of 3WAY SYSTEM

2. System Design

Additional refrigerant charge before extension


Liquid tube Tubing length (m) Additional refrigerant charge
(A) × (B) kg (Before extension )
diameter (A) per 1 m (kg/m) (B)
La ø12.7 2 0.128 0.256 Total actual tubing length is 122.4m.
Lb ø12.7 1 0.128 0.128
Lc ø9.52 1 0.056 0.056
LP ø15.88 20 0.185 3.700
LA ø19.05 5 0.259 1.295
LB ø15.88 6 0.185 1.110
LC ø12.7 6 0.128 0.768
LD ø12.7 0.4 0.128 0.051
LE1 ø9.52 5 0.056 0.280
LN ø15.88 3 0.185 0.555
LG ø12.7 3 0.128 0.384
LH ø9.52 4 0.056 0.224
LI
LJ
ø9.52
ø9.52
5
5
0.056
0.056
0.280
0.280 1
LK ø12.7 2 0.128 0.256
LL ø9.52 3 0.056 0.168
LM ø9.52 4 0.056 0.224
L1 ø9.52 3 0.056 0.168
L2 ø6.35 3 0.026 0.078
L3 ø6.35 3 0.026 0.078 2
L7 ø9.52 3 0.056 0.168
L8 ø9.52 3 0.056 0.168
L9 ø9.52 4 0.056 0.224
L10 ø6.35 4 0.026 0.104
L11 ø6.35 6 0.026 0.156
L12
L13
ø9.52
ø9.52
4
4
0.056 0.224
0.224
3
0.056
L14 ø9.52 4 0.056 0.224
L15 ø6.35 6 0.026 0.156
Total (kg) 11.987 11.99 kg

Additional refrigerant charge after extension 4


Liquid tube Tubing length (m) Additional refrigerant charge (Extension )
(A) × (B) kg
diameter (A) per 1 m (kg/m) (B)
Total actual tubing length is 26m.
LE2 ø9.52 4 0.056 0.224
LF ø9.52 5 0.056 0.280
L4 ø9.52 4 0.056 0.224 5
L5 ø9.52 6 0.056 0.336
L6 ø9.52 7 0.056 0.392
Total (kg) 1.4560 1.46 kg

(After extension)
Total actual tubing length is 148.4m. 6
Calculation of additional refrigerant charge for the entire 3-WAY system
(Additional refrigerant charge for entire 3-WAY system)
= (Refrigerant charge at outdoor unit)
+ (Necessary amount of additional refrigerant charge per outdoor unit)
+ (Necessary amount of additional refrigerant charge per refrigerant circuit for 3 way system) 7
+ [Additional total refrigerant charge (before extension + after extension) ]
= [(9.3 + 9.3 + 8.5) refrigerant charge at outdoor unit]
+ [(9.0 + 9.0 + 8.3) necessary amount of additional refrigerant charge per outdoor unit]
+ [(2.0) Necessary amount of additional refrigerant charge per refrigerant circuit for 3 way system]
+ [(11.99+1.46) additional total refrigerant charge]
= 68.85 (after extension) 8
[Before extension : (9.3 + 9.3) + (9.0 + 9.0) + 2.0 + 11.99 = 50.59 kg ]

2-19 9

5GEKPFF 
Design of 3WAY SYSTEM

2. System Design

Checking of limit density


The limit density judgment is made based on the room
with the indoor unit having the smallest capacity in the
system after extension.
The volume of the room where a type 280 indoor unit
is used (connected to tubing L11) is calculated as follows:
floor area 15 m2 × Ceiling height 2.7 m = 40. 5 m3.
From the graph below, the minimum room volume for
68.85 kg of refrigerant is 222.2 m3 (floor area 82.3 m 2 ).
Therefore an opening for ventilation is required.
<Judgment by calculation>
( Total refrigerant charge amount : kg )
( Minimum Indoor volume where indoor unit is installed : m3 )
1
68.85 (kg)
= = 1.7 (kg/m3) > 0.30 (kg/m3)
40.5 (m3) Minimum indoor volume & floor area as against the amount
In this case, an opening is required for ventilation. of refrigerant is roughly as given in the following table.

2 Always check the gas m2 2


125m
m3
337.5 m
as
3
given in the following table.
WARNING density limit for the room in 120100 324.0 270.0
which the unit is installed. 115 95 310.5 256.5
110 90 297.0 243.0
105 85 283.5 229.5 Range below the
100 270.0
(when the ceiling is 2.7 m high)

80 216.0 density limit of


3 Check of Limit Density
95
90 75
256.0
243.0 202.5
0.3 kg/m3
m high)

(Countermeasures
Min. indoor volume

85 70 229.5 189.0 Range below the


When installing an air conditioner in a room, it is necess- not needed)
density limit of
area

80 65 216.0 175.5
ary to ensure that even if the refrigerant gas accidentally 0.3 kg/m³
Min. indoor volume

75 202.5
is 2.7

60 162.0 (Countermeasures
Min. indoor floor area

leaks out, its density does not exceed the limit level for
ceilingfloor

70 189.0
not needed)
that room. 65 55 175.5 148.5
Range above the
indoor

60 50 162.0 135.0
4 If the density could exceed the limit level, it is necessary
to provide an opening between the unit and the adjacent
55 45 148.5 121.5 density limit of
0.3 kg/m
Range above 3
the
the

50 40 135.0 108.0
Min.

45 121.5 density limit of 0.3


(Countermeasures
room, or to install mechanical ventilation which is inter-
(when

40 35 108.0 94.5 kg/m³


needed)
locked with the leak detector. (Countermeasures
35 30 94.5 81.0 needed)
30 25 81.0 67.5
( Total refrigerant charge amount : kg ) 25 20 67.5 54.0
5 ( Minimum Indoor volume where indoor unit is installed : m3 )
20
15
15
54.0
40.5
40.5
20 30 40 50 60 70 80 kg
10 27.0 Total amount of refrigerant
Limit density 0.3 (kg/m3) 5 13.5
0 0.0
Y1, M1 Types0 10 20 30 40 50 60 70 80 90 100 kg
The limit density of refrigerant which is used in this unit
is 0.3 kg/m3 (ISO 5149). m2 Total amount of refrigerant
6 The shipped outdoor unit comes charged with the amount 40
of refrigerant fixed for each type, so add it to the amount Range below
35 the density limit
that is charged in the field. (For the refrigerant charge of 0.3 kg/m3
amount at shipment, refer to the unit's nameplate.) 30 (countermeasures
not needed)
Min. indoor floor space

25
7 CAUTION Pay special attention to any
20
location, such as a basement, Range above
etc., where leaking refrigerant 15 the density limit
can accumulate, since refrige- of 0.3 kg/m3
10 (countermeasures
rant gas is heavier than air. needed)
5
8 0
10 20 30 kg
Total amount of refrigerant

9 2-20

5GEKPFF 
Design of 3WAY SYSTEM

2. System Design

Installing distribution joint


(1) Refer to “HOW TO ATTACH DISTRIBUTION JOINT” Tube branching methods (horizontal use)
enclosed with the optional distribution joint kit (CZ-P
680PH2, CZ-P1350PH2, CZ-P224BH2, CZ-P680BH2,
CZ-P1350BH2).
(2) When creating a branch using a commercially available A
B
T-joint (header joint system), orient the main tubing so Arrow view D
that it is either horizontal (level) or vertical. In order to
Arrow view C

°
prevent accumulation of refrigerant oil in stopped units,

30
15

to
if the main tubing is horizontal then each branch tubing to

15
30
°
length “B” should be at an angle that is greater than
horizontal. If the main tubing is vertical, provide a raised B B
starting portion for each branch. A
Horizontal A
When only one indoor unit is connected to the side of “A”,
install part “A” at a positive angle (15-30°) for the field view D
line View as seen
view C from arrow
1
tubing as shown in the figure.
[Header joint system] Header joint system (Indoor)
Be sure to solidly weld shut the T-joint end (mark- Install at a positive angle
ed by “X” in the figure). In addition, pay attention
to the insertion depth of each connected tube so
Outdoor 2
Indoor
that the flow of refrigerant within the T-joint is not
impeded. Install at a
When using the header joint system, do not make Indoor positive angle
Horizontal (15 – 30°)
further branches in the tubing.
Do not use the header joint system on the outdoor
line
Indoor
3
unit side.
L3 < 2 m Horizontal Solidly welded
(3) If there are height differences between indoor units line shut (X)
or if branch tubing that follows a distribution joint is
connected to only 1 unit, a trap or ball valve must be
added to that distribution joint. (When adding the ball 4
valve, locate it within 40 cm of the distribution joint.) Types of vertical trap specifications
(Consult with the dealer separately concerning the
(When using ball valve)
ball valve.)
Main tubing
If a trap or ball valve is not added, do not oper-
ate the system before repairs to a malfunction- 5
ing unit are completed. (The refrigerant oil sent
through the tubing to the malfunctioning unit Ball valve Indoor unit (more than 2 units)
(BV: purchased (If only 1 unit is connected, a ball
will accumulate and may damage the compres- valve is also needed on this side.)
separately)
sor.)
Indoor unit (1)
6
(When not using ball valve)

Main tubing
Horizontal
Indoor unit (Each unit is
Branch tubing is
directed upward.
connected to tubing
that is either level or 7
is directed
More than downward.)
20 cm

Indoor unit is directed downward

2-21 9

5GEKPFF 
Design of 3WAY SYSTEM

3. Electrical Wiring

3-1. General Precautions on Wiring


(1) Before wiring, confirm the rated voltage of the unit as (7) Regulations on wire diameters differ from locality to
shown on its nameplate, then carry out the wiring closely locality. For field wiring rules, please refer to your
following the wiring diagram. LOCAL ELECTRICAL CODES before beginning.
(2) Provide a power outlet to be used exclusively for each You must ensure that installation complies with all
unit, and a power supply disconnect, circuit breaker and relevant rules and regulations.
earth leakage breaker for overcurrent protection should be (8) To prevent malfunction of the air conditioner caused by
provided in the exclusive line. electrical noise, care must be taken when wiring as
(3) To prevent possible hazards from insulation failure, the unit follows:
must be grounded. The remote control wiring and the inter-unit control wiring
(4) Each wiring connection must be done in accordance with should be wired apart from the inter-unit power wiring.
the wiring system diagram. Wrong wiring may cause the Use shielded wires for inter-unit control wiring between
unit to misoperate or become damaged. units and ground the shield on both sides.

1 (5) Do not allow wiring to touch the refrigerant tubing,


compressor, or any moving parts of the fan.
(9) If the power supply cord of this appliance is damaged,
it must be replaced by a repair shop appointed by the
(6) Unauthorized changes in the internal wiring can be very manufacturer, because special purpose tools are
dangerous. The manufacturer will accept no responsibility required.
for any damage or misoperation that occurs as a result of (10) Use a waterproof conduit for outdoor unit wiring to avoid
2 such unauthorized changes. damaging the wire and to prevent accumulation of liquid
inside the unit.

3-2. Recommended Wire Length and Wire Diameter for Power Supply System
Outdoor unit
3 (A) Power supply Time delay fuse or (A) Power supply Time delay fuse or
Wire size Max. length circuit capacity Wire size Max. length circuit capacity
U-8MF2E8 4 mm 2 65 m 25 A 6 mm2 98 m 35 A
U-10MF2E8 4 mm 2 47 m 25 A 6 mm2 70 m 35 A

4
2
U-12MF2E8 6 mm 2 70 m 35 A or 6 mm 70 m 35 A
U-14MF2E8 10 mm 2 96 m 40 A 10 mm2 96 m 50 A
U-16MF2E8 10 mm 2 84 m 50 A 10 mm2 84 m 50 A

Indoor unit
(B) Power supply Time delay fuse or
5 Type
2.5 mm² circuit capacity
K1 Max. 150 m 10 – 16A
D1, L1, U1, Y1, T1, F1, F2, M1, P1, R1 Max. 130 m 10 – 16A
E1 (73, 106, 140) Max. 60 m 10 – 16A
E1 (224) Max. 50 m 10 – 16A
6 E1 (280) Max. 30 m 10 – 16A

Control wiring

(C) Inter-unit (between outdoor and indoor units) control wiring (D) Remote control wiring

7 0.75 mm² (AWG #18)


Use shielded wiring* or
2.0 mm² (AWG #14)
Use shielded wiring*
0.75 mm² (AWG #18)

Max. 1,000 m Max. 2,000 m Max. 500 m

NOTE * With ring-type wire terminal.

8 (E) Control wiring for group control (F) Inter-outdoor unit control wiring
0.75 mm² (AWG #18)
0.75 mm² (AWG #18)
Use shielded wiring
Max. 200 m (Total) Max. 300 m

9 2-22

5GEKPFF 
Design of 3WAY SYSTEM

3. Electrical Wiring

3-3. Wiring System Diagrams


Indoor unit
(No. 1)
Power supply L L
220 – 240V ~50/60Hz N N
Outdoor unit
INV unit
C A
Ground L1
B L1 Power supply
U1 1 L2
Remote U2 2
L2
L3
380 – 415V, 3 N~, 50Hz
controller D L3
Ground N
N
WHT 1 1 R1 3
R2 4
BLK 2 2
Ground Ground
C
Indoor unit Ground
(No. 2)
L F Inter-outdoor-unit control wiring
Power supply L Ground
220 – 240V ~50/60Hz N N
Outdoor unit
INV unit
Ground B A
U1 Ground L1
L1 Power supply
Remote U2 L2
controller D L2 380 – 415V, 3 N~, 50Hz
3 L3
L3
WHT 1 1 R1
4 N
1
N
BLK 2 2 R2
Ground
C Ground
Group control: Indoor unit
(No. 3) NOTE
Power supply L L
220 – 240V ~50/60Hz N N (1) Refer to Section 3-2. “Recommended Wire Length
Ground
Ground B and Wire Diameter for Power Supply System” for the
E U1
U2 explanation of “A”, “B”, “C”, “D”, “E” and “F” in the 2
R1 above diagram.
R2

Ground (2) The basic connection diagram of the indoor unit shows
C
the 7P terminal board, so the terminal boards in your
equipment may differ from the diagram.
L
Indoor unit
(No. n)
(3) Refrigerant Circuit (R.C.) address should be set before
3
Power supply L
220 – 240V ~50/60Hz N N turning the power on.
Ground
Ground B U1
(4) Address setting can be executed by remote controller
Remote U2
controller D automatically. Refer to section “ 4. Auto Address Setting
WHT 1
BLK 2
1
2
R1
R2 under 5. TEST RUN”. 4
(5) Regarding S-280ME1E5, the power supply is
4P terminal board 220 – 240 V, 50 Hz.

7P terminal board
6P terminal board 5P terminal board 5
L1 L2 L3 N
Power supply
(8 hp, 10 hp and 12 hp)

4P terminal board

L
Power
N U1 U2 R1 R2
Unit Remote
L N U1 U2 R1 R2
Power Unit Remote
L N
Power
U1 U2
Unit 6
supply control control supply control
supply control control wiring
wiring wiring
wiring wiring
T1, F1, E1, D1, L1 Types F2 Type K1 Type

L1 L2 L3 N 6P terminal board 6P terminal board


Power supply
(14 hp, 16 hp) 7
2P terminal board × 2

L N U1 U2 R1 R2 L N U1 U2 R1 R2
Power Unit Remote Power Unit Remote
supply control control supply control control
wiring wiring wiring wiring
U1, Y1, M1, P1, R1 Types
8
U1 U2 1 2 U1 Type

Inter-unit Inter-outdoor
control wiring unit control wiring
MF2 Type
2-23 9

5GEKPFF 
Design of 3WAY SYSTEM

3. Electrical Wiring

CAUTION

(1) When linking outdoor units in a network, see the section “Adjustment of Termination Resistor
(Plug)” under 5. TEST RUN.

(2) Do not install the inter-unit control wiring in a way that forms a loop.

Outdoor unit Outdoor unit Outdoor unit


Prohibited

Prohibited

Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit

1
(3) Do not install inter-unit control wiring such as star branch wiring. Star branch wiring causes
mis-address setting.

Outdoor unit Indoor unit Indoor unit


2
NO Indoor unit Indoor unit
Branch point

(4) If branching the inter-unit control wiring, the number of branch points should be 16 or fewer.
3 (Branches less than 1 m are not included in the total branch number.)

Outdoor unit Outdoor unit Outdoor unit

4
Indoor unit Indoor unit Indoor unit Indoor unit

more than 1 m
Branch
5 point
Indoor unit Indoor unit Indoor unit Indoor unit
16 or fewer
more than 1 m

Indoor unit
6 less than 1 m

Indoor unit

7 (5) Use shielded wires for inter-unit control wiring (c)


Shielded wire
and ground the shield on both sides, otherwise
misoperation from noise may occur.
Connect wiring as shown in Section 3-3.“Wiring Ground Ground
System Diagrams.”
8

9 2-24

5GEKPFF 
Design of 3WAY SYSTEM

3. Electrical Wiring

(6) Use the standard power supply cables for Europe (such as H05RN-F or H07RN-F which conform to
CENELEC (HAR) rating specifications) or use the cables based on IEC standard. (60245 IEC57,
60245 IEC66)
Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 5
or 3 *1.5 mm2 flexible cord. Type designation 60245 IEC 57 (H05RN-F, GP85PCP etc.) or heavier cord.
Loose wiring may cause the terminal to overheat or result in unit malfunction.
WARNING A fire hazard may also occur.
Therefore, ensure that all wiring is tightly connected.

When connecting each power wire to the terminal, follow the instructions on “How to connect wiring to the
terminal” and fasten the wire securely with the fixing screw of the terminal plate.

3-4. Connecting Multiple Indoor Units to a Single Solenoid Valve Kit


It is possible to connect multiple indoor units to one solenoid valve kit. 1
The indoor units can be controlled individually or be operated as a group.
It is possible to adopt multiple units with a common use of the solenoid valve kit per piece of refrigerant.
Categories of connected indoor unit capacities are determined by the solenoid valve kit.

Type of solenoid valve kit Total capacity of indoor units (kW)


2
CZ-P160HR3 5.6 < Total capacity 16.0
CZ-P56HR3 2.2 Total capacity 5.6

* If the capacity range is exceeded, use two solenoid valves connected in parallel. 3
Each Method (General) and Conditions
Method 1 Method 2 Method 3

Method Connecting one indoor unit with Group control is possible by Indoor units can operate
one solenoid valve kit connecting multiple indoor units individually by connecting
to one solenoid valve kit. multiple indoor units to one
4
solenoid valve kit.
Connectable number 1 piece 1 piece Over 2 pieces
of remote controls
Possible operating
functions
Individual control Group control
* Thermostat On/Off function is
Individual control available
* Mixed group control available
5
only individual control (when
selecting the body thermostat).
Possible operating Cool, Dry, Heating, Auto, Fan Cool, Dry, Heating, Auto, Fan Cooling, Dry, Heating, Fan
modes * Auto selection is impossible.
Condition – Mixed cooling and heating is Mixed cooling and heating is
6
impossible. impossible.
Auto selection is impossible.

Method 1 Method 1 Method 2 Method 3 Method 3


7
Solenoid Solenoid Solenoid Solenoid Solenoid Solenoid
valve kit valve kit valve kit valve kit valve kit valve kit

Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit
8
Remote Remote Remote Remote Remote Remote Remote Remote
controller controller controller controller controller controller controller controller

2-25 9

5GEKPFF 
Design of 3WAY SYSTEM

3. Electrical Wiring

Necessity of setting changes by combination of each method

Type of combination: Necessity of setting


Method 1 only: Setting is unnecessary.
Method 2 included: Setting up in common use of a solenoid valve kit from “Remote Control” is necessary. *1
* Method 2 only is set.
* Method 3 excluded
Method 3 included: Setting up in common use of a solenoid valve kit from a specific program settings software
is necessary. *1
* Setting all connected indoor units
*1: Refer to “Test Run” for setting instructions.

Please note the following system example is prohibited and avoid the following connection.

1
Solenoid Solenoid
valve kit valve kit

2 Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit
Method 3 individual control
is possible and group wiring
Remote Remote Remote Remote
controller controller controller controller
should be made by other
solenoid valve kit.

3
System 1 System 2

4 Solenoid
valve kit
Solenoid
valve kit

Indoor unit Indoor unit

Group wiring should be made


Remote by different type of refrigerant.
5 controller

9 2-26

5GEKPFF 
Design of 3WAY SYSTEM

3. Electrical Wiring

Stranded wire
How to connect wiring to the terminal
Ring

Strip 10 mm
pressure
For stranded wiring
terminal
(1) Cut the wire end with cutting pliers, then strip the
insulation to expose the stranded wiring about 10 mm
and tightly twist the wire ends.
(2) Using a Phillips head screwdriver, remove the terminal
screw(s) on the terminal plate.
(3) Using a ring connector fastener or pliers, securely Special
Screw
washer
clamp each stripped wire end with a ring pressure
terminal.
Ring pressure
Screw and
(4) Place the ring pressure terminal, and replace and terminal
Special washer
Terminal plate
tighten the removed terminal screw using a screwdriver. Wire
Ring
1
pressure
terminal

Wire
2
Examples of shield wires
(1) Remove cable coat not to scratch braided shield.
(2) Ravel braided shield carefully and put tightly braided shield
together.
3
Coat with insulation tube or wrap insulation tape after
putting tightly. Insulation tape Shield mesh

(3) Remove coat of signal wire.


(4) Connect signal wire removed coat and shield wire with
8mm 4
pressure terminal.

Insulation tape Shield mesh

Earth wire for power supply 6


The earth wire should be longer than the other lead wires for electrical safety.

2-27 9

5GEKPFF 
Design of 3WAY SYSTEM

3. Electrical Wiring

Wiring sample
Outdoor Unit : MF2 Type
1. 2.

Use this screw when Use this screw when


connecting to ground connecting to ground
for the inter-unit control for the inter-unit control
wiring. wiring.

1 Power Supply
Earth
Inter-unit Control Wiring
Power Supply Inter-unit Control Wiring
Earth
Use this screw when
3. 4.
connecting to ground
for the inter-unit control
wiring.

2 Use this screw when


Use this screw when
connecting to ground
connecting to ground
for the inter-outdoor
for the inter-unit control
unit control wiring.
wiring.

3
Clamper **
(Field supply)
Power Supply Inter-unit Control Wiring Power Supply
Clamper * Inter-outdoor unit Control Wiring
Earth
4 (Field supply)
Earth
Inter-unit Control Wiring
Clamper **
(Field supply)
* First remove the attached resin fixture.
Then lead the clamper (field supply) through the screw hole ** First remove the attached resin fixture.
and fix the power supply wire. Then lead the clamper (field supply) through the screw hole and
square hole from top to bottom or vice versa.
Finally fix each inter-outdoor unit control wire and the inter-unit
5 control wire separately with the clamper (field supply).

NOTE

Fix the wires with the clamper (field supply) to the wiring fixture plates (2 locations)
and do not allow them to touch the refrigerant tubing and compressor.
Use a waterproof conduit for outdoor unit wiring to avoid damaging the wire and to
6 prevent accumulation of liquid inside the unit.

7
Wiring fixture plate
Space for holes on-site
(Max. diameter ø48)

8
Electrical wiring port
(ø60, ø28 knock-out holes for conduit connection)

9 2-28

5GEKPFF 
Design of 3WAY SYSTEM

3. Electrical Wiring

Wiring sample
Indoor Unit : U1 Type Indoor Unit : D1 Type

Clamper*1 Clamper*1 Protective ground screw (External Solenoid Valve Kit for 3WAY)
Remote Control Wiring

Remote Control
Wiring
Inter-unit Control
Wiring Power Supply Inter-unit Control Wiring

Use this screw when connecting to ground


the shield for the Inter-unit control wiring.
Power Supply
Clamper* 1 Use this screw when connecting Functional ground screw (External Electronic
Expansion Valve Kit and Schedule Timer)
1
the shield for the Inter-unit control
Clamping Clip
wiring to ground.
Protective ground screw (External
Solenoid Valve Kit for 3WAY) Functional ground screw
*1 Fasten tightly.
(External Electronic Expansion
Valve Kit and Schedule Timer)
2
Indoor Unit : Y1 Type Indoor Unit : M1 Type
Functional ground screw (External Electronic Clamper inside the box Inter-unit Control Wiring
Expansion Valve Kit and Schedule Timer) for Remote Control Wiring
and Inter-unit Control Wiring Remote Control Wiring

3
L N U1 U2 R1 R2

Power Supply
4
Use this screw when connecting
to ground the shield for the Clamper on the front
Inter-unit control wiring. side for Power Supply
Use this screw when connecting to ground Protective ground screw
Functional ground screw
the shield for the Inter-unit control wiring. (External Solenoid Valve Kit for 3WAY )
(External Electronic
Protective ground screw
(External Solenoid Valve Kit for 3WAY)
Expansion Valve Kit and
Schedule Timer)
5
Inter-unit Control Wiring Remote Control Wiring

Wire Saddle 7
Power Supply
Power Supply
Inter-unit Control Wiring Supplied Clamper *
Clamper
(Field supply) Remote Control Wiring * Route the power supply cord through the ring
of the supplied wire saddle and clamp the cord.
8

2-29 9

5GEKPFF 
Design of 3WAY SYSTEM

3. Electrical Wiring

Wiring sample
Indoor Unit : E1 Type (73, 106, 140) Indoor Unit : E1 Type (224, 280)

Functional ground screw (External Electronic Use this screw when connecting to ground
Expansion Valve Kit and Schedule Timer) the shield for the Inter-unit control wiring.

Use this screw when connecting


to ground the shield for the
Inter-unit control wiring. Remote Control
Wiring Inter-unit
Remote Control Wiring Control Wiring

Power
Supply

Inter-unit Control Wiring


2 Power Supply
Protective ground screw Functional ground screw (External Electronic
(External Solenoid Valve Kit for 3WAY) Expansion Valve Kit and Schedule Timer)

Protective ground screw (External Solenoid


Valve Kit for 3WAY and RAP valve Kit)

3
Indoor Unit : F1 Type Indoor Unit : F2 type
Protective ground screw (External Solenoid Valve Kit for 3WAY)

Functional ground screw (External Electronic


Expansion Valve Kit and Schedule Timer)
4 Functional ground screw
(External Electronic Expansion Valve Kit
and Schedule Timer)
Use this screw when connecting the shield
for the Inter-unit control wiring to ground.

5 L N U1 U2 R1 R2
Remote
Control
Wiring

Inter-unit
Control
Wiring

6
Protective ground screw Power Supply
(External Solenoid Valve Kit for 3WAY)

Power Supply Remote Control Wiring


7 Inter-unit Control Wiring
Use this screw when connecting to ground
the shield for the Inter-unit control wiring.

9 2-30

5GEKPFF 
Design of 3WAY SYSTEM

3. Electrical Wiring

Wiring sample
Indoor Unit : K1 Type (22, 28, 36) Indoor Unit : K1 Type (45, 56, 73, 106)
Use this screw when connecting to ground the shield Functional ground screw (External Electronic
for the Inter-unit control wiring. Expansion Valve Kit and Schedule Timer) *
Protective ground screw (External Solenoid Protective ground screw
Valve Kit for 3WAY) (External Solenoid Valve Kit for 3WAY) *

Fixture screw for resin cover

Resin cover
L1 L2 N U1 U2 R1 R2

L1 L2 N U1U2 1

2
Power Supply
Remote Control Wiring
Inter-unit Control Wiring
Functional ground screw (External Electronic
Expansion Valve Kit and Schedule Timer) 3
Inter-unit Control Wiring
Power Supply Remote Control Wiring
Use this screw when connecting to ground
the shield for the Inter-unit control wiring.
* As to functional ground screw and protective ground screw,
remove the fixture screw and resin cover.
4
Then, carry out earth ground work.

Indoor Unit : L1 Type Indoor Unit : T1 type


Protective ground screw (External Solenoid Valve Kit for 3WAY)
Protective ground screw (External Solenoid Valve Kit for 3WAY)
Remote Control Wiring 5
Functional ground screw (External Electronic
Expansion Valve Kit and Schedule Timer)

Use this screw when connecting to ground


the shield for the Inter-unit control wiring.

6
Power Supply Inter-unit Control Wiring
L N U1 U2 R1 R2
Use this screw when connecting to ground
the shield for the Inter-unit control wiring. 7
Functional ground screw (External Electronic
Expansion Valve Kit and Schedule Timer)

8
Remote Control Wiring
Inter-unit Control Wiring
Power Supply
2-31 9

5GEKPFF 
Design of 3WAY SYSTEM

3. Electrical Wiring

Wiring sample
Indoor Unit : P1 and R1 Types
Protective ground screw (External Solenoid Valve Kit for 3WAY)

Functional ground screw (External Electronic


Expansion Valve Kit and Schedule Timer)

Use this screw when connecting to ground


the shield for the Inter-unit control wiring.

2 Power Supply
Remote Control Wiring

Inter-unit Control Wiring

9 2-32

5GEKPFF 
Design of 3WAY SYSTEM

4. Installation Instructions

Outdoor Unit Example of installation of 2 units


(when 3 sides are open and only 1 side is shuttered)
4-1. Selecting the Installation Site for Outdoor Unit
* More than 300 mm
AVOID:
** More than 50 mm
heat sources, exhaust fans, etc.
damp, humid or uneven locations
indoors (no-ventilation location)
** More than
DO: 50 mm
More than
choose a place as cool as possible. 500 mm
choose a place that is well ventilated.
allow enough room around the unit for air intake/ *** More than 60 mm
exhaust and possible maintenance.
* Make a walk-in space behind the unit to erase maintenance and
servicing.
Exhaust fan
** When setting the anchor bolt to position “B” or “C” (See Fig. 4-3), 1
Hot air make the space between the unit and the wall more than 250 mm
for installation operation.
Heat *** When setting the anchor bolt to position “B” or “C” (See Fig. 4-3),
source
make the space between the outdoor units more than 180 mm for
Out-
door
unit
installation operation.
2
Fig. 4-2

Top view Side view Unit: mm


Fig. 4-1 Installation anchor hole
(8 – 15 × 21 elongated holes)
Installation Space Air intake 3
Install the outdoor unit where there is enough space for
ventilation. Otherwise the unit may not operate properly. Air
intake

1758
Fig. 4-2 shows the minimum space requirement around B
930

A
the outdoor units when 3 sides are open and only 1 side
C

Air
is shuttered, with open space above the unit. intake
4
The mounting base should be concrete or a similar
material that allows for adequate drainage. 970
(Installation hole pitch)
Make provisions for anchor bolts, platform height, and 1000 930
other site-specific installation requirements.

Leave space open above the unit.


* According to the installation site, you may choose the setting position
in the depth direction of the anchor bolt from “A”, “B” or “C”.
5
Construct louvers or other openings A : 894 (Installation hole pitch) * For removing tube forward
CAUTION
in the wall, if necessary, to ensure B : 730 (Installation hole pitch) * For removing the tube downward
adequate ventilation. C : 730 (Installation hole pitch)

NOTE
Fig. 4-3 6
Do not do any wiring or tubing within 30 cm of the front
panel, because this space is needed as a servicing space for
the compressor.
Ensure a base height of 100 mm or more to ensure that
drainage water does not accumulate and freeze around the
7
bottom of the unit.
If installing a drain pan, install the drain pan prior to
installing the outdoor unit.
* Make sure there is at least 150 mm between the outdoor
unit and the ground.
8
Also, the direction of the tubing and electrical wiring should
be from the front of the outdoor unit.

2-33 9

5GEKPFF 
Design of 3WAY SYSTEM

4. Installation Instructions

4-2. Shield for Horizontal Exhaust Discharge


It is necessary to install an air-discharge chamber (field supply)
to direct exhaust from the fan horizontally if it is difficult to
provide a minimum space of 2 m between the air-discharge
outlet and a nearby obstacle. (Fig. 4-4)
In regions with heavy snowfall, the
outdoor unit should be provided with a
CAUTION
solid, raised platform and snow-proof
vents. (Fig. 4-5)

4-3. Installing the Outdoor Unit in Heavy Snow Areas


In locations where wind-blown snow can be a problem, snow-
proof vents should be fitted to the unit and direct exposure to

1 the wind should be avoided as much as possible. (Fig. 4-6)


The following problems may occur if proper countermeasures
are not taken:
Fig. 4-4
The fan in the outdoor unit may stop running, causing the
unit to be damaged. DO
2 There may be no air flow.
The tubing may freeze and burst.
The condenser pressure may drop because of strong wind,
and the indoor unit may freeze.

3 4-4. Precautions When Installing in Heavy Snow


Areas
AVOID
a) The platform should be higher than the maximum snow
depth. (Fig. 4-5)
b) The 2 anchoring feet of the outdoor unit should be used for
4 the platform, and the platform should be installed beneath
the air-intake side of the outdoor unit. Fallen snow
c) The platform foundation must be solid and the unit must be
Without snow-proof vents With snow-proof vents
secured with anchor bolts. (Without platform) (High platform)
d) When installing on a roof subject to strong wind, Fig. 4-5
5 countermeasures must be taken to prevent the unit from
being overturned.

4-5. Dimensions of Wind Ducting

6 Reference diagram for air-discharge chamber


(field supply)
For further details, refer to “8. SUPPLEMENT”.

4-6. Dimensions of Snow Ducting


7 Reference diagram for snow-proof vents
(field supply)
For further details, refer to “8. SUPPLEMENT”.

Fig. 4-6

9 2-34

5GEKPFF 
Design of 3WAY SYSTEM

4. Installation Instructions

4-7. Transporting 4-8. Installing the Outdoor Unit


When transporting the unit, have it delivered as close to the (1) Use four (4) anchor bolts (M12 or similar) to securely
installation site as possible without unpacking. anchor the unit. Regarding the positioning anchor bolts
Use a hook for suspending the unit as shown in Figure 4-7. of the depth direction, select one of three types according
to the installation site. (See Fig. 4-8.)
CAUTION Normally, select the position “A”. When removing the
connection tube in a downward direction, select the
When hoisting the outdoor unit, pass lifting belts through position “B”.
the left and right holes of the bottom plate as shown in (2) When only using a single outdoor unit, see the Figure 4-8.
Figure 4-7. The angle between the lifting belt and top panel In case of the combination with different units, refer to
must be 70° or more so that the lifting belt does not come “SUPPLEMENT”.
into contact with the fan guard. Use two lengths of lifting * When positioning the anchor bolt at “B” or “C”, make a
belt 7.5 meters long or longer. sufficient space bewteen the units or from the wall for
Hang the lifting belt at an oblique angle of the four corners installation.
of the bottom plate. If it is hung at other areas, the lifting
belt becomes loose and the outdoor unit will be damaged
(Make a space between the units wider than 180 mm
and left and right space wider than 250 mm from the
1
or you may be injured. wall.)
Use protective panels or padding at all locations where the (3) The vibration insulator or the like should be kept secure to
lifting belt contacts the outer casing or other parts to prevent satisfy the width and depth of 100 mm for the plate legs.
scratching. In particular, use protective material (such as
cloth or cardboard) to prevent the edges of the top panel
(See the dimensions marked by the asterisk at Fig. 4-10d
- 4-10f.) Use a washer from the upper direction larger
2
from being scratched. than the hole size for fixing the installation.
Be sure to use the same thickness of all vibration
insulators and make adjustment so that they will become
the same height each other.
Lifting belt (Fig. 4-9 and Fig. 4-10a to 4-10f) 3
Top view Installation anchor hole Unit: mm
Fan guard (8 – 15 × 21 elongated holes)
Air intake

Protective Air
4
cardboard intake
or cloth
B
930

A
C

Air
intake
5
970
(Installation hole pitch)
1000
Fig. 4-8
• According to the installation site, you may choose the setting
position in the depth direction of the anchor bolt from “A”, “B” or “C”.
6
A :894 (Installation hole pitch) * The tubing is routed out from the front.
B :730 (Installation hole pitch) * The tubing is routed out from the bottom.
C :730 (Installation hole pitch)

A (Detailed view of anchor hole)


7
8 – 15 × 21 elongated hole
Unit: mm
This is not a lifting lug.
Detailed <Do not attempt to lift the unit by one of the
drawing A legs at each corner of the unit or with hooks
or shackles attached for installing the legs.>
182

Fig. 4-7 8
15 Fig. 4-9
18

• Below shows vibration insulator position when setting


anchor bolt at position A (Fig.4-8).
2-35 9

5GEKPFF 
Design of 3WAY SYSTEM

4. Installation Instructions

Unit: mm Detailed view of “D” & “E”


Plate leg(left)
Unit: mm
Plate leg(right)
D D
Plate leg (left, right)

(Installation hole pitch)


Anchor bolts
Washer
Vibration insulator

A:894
Vibration
Electrical wiring port(bottom) insulator
15

or more
100
Base
*71
D D
Tubing port(bottom) Front view
Fig. 4-10a Fig. 4-10d

• Below shows vibration insulator position when setting anchor Detailed view “E”
1 bolt at position B (Fig.3-2).
Unit: mm Unit: mm
Anchor bolts**
Plate leg(left)
Plate leg(right) Plate leg
D D (left, right or center)
(Installation hole pitch)

Vibration Washer**
2 insulator
B:730

Vibration insulator *100


Base
Electrical wiring port(bottom)

Side view
E Fig. 4-10e
3 E

Tubing port(bottom)
Fig. 4-10b
• Below shows vibration insulator position when setting anchor Detailed view “D”
bolt at position C (Fig.3-2). Unit: mm

4 Plate leg(left)
Unit: mm
Plate leg(right)
Anchor bolts**
Plate leg
(left, right)
E E Vibration
Washer**
insulator
(Installation hole pitch)

*100
or more
100

Base
5 Vibration insulator
C:730

Electrical wiring port(bottom)


Side view
Fig. 4-10f

D D
6 Tubing port(bottom) Fig. 4-10c

9 2-36

5GEKPFF 
Design of 3WAY SYSTEM

4. Installation Instructions

4-9. Routing the Tubing

The tubing can be routed out either from the front or from the bottom. (Fig. 4-11-a)
The connecting valve is contained inside the unit. Therefore, remove the front panel. (Fig. 4-11-b)
(1) If the tubing is routed out from the front, punch out the slit part ( ). (Fig. 4-12-a)
Be careful not to damage the tubing cover.
(2) If the tubing is routed out from the bottom, use cutting pliers or a similar tool to cut out the tubing outlet slit (part indicated
by ) from the tubing cover. (Figs. 4-11-c and 4-12-b)
Be careful not to damage the tubing cover.

Front
1
Bottom
Fig. 4-11-a Remove eight panel
screws from front panel.

2
Fig. 4-11-b
If the tubing is routed out from the front,
punch out in the direction of the arrow.
Tubing cover
3

Fig. 4-12-a 4
Tubing cover
Remove 3 screws
If the tubing is routed out from the bottom,
use cutting pliers or a similar tool to cut out
the tubing outlet slit from the tubing cover.

Tubing cover 5

Fig. 4-11-c
6
Fig. 4-12-b

2-37 9

5GEKPFF 
Design of 3WAY SYSTEM

4. Installation Instructions

4-10. Prepare the Tubing


Material :
Use C1220 phosphorous deoxidized copper as described in JIS H3300, “Copper and Copper Alloy Seamless Pipes and
Tubes.” (For tubes that are ø22.22 or larger, use 1/2H material or H material. For all others use O material.)
Tubing size
Use the tubing size indicated in the table below.
When cutting the tubing, use a tube cutter, and be sure to remove any burrs.
(The same applies to distribution tubing (optional).)
When bending the tubes, bend each tube using a radius that is at least 4 times the outer diameter of the tube.
When bending, use sufficient care to avoid crushing or damaging the tube.
For flaring, use a flare tool, and be sure that flaring is performed correctly.

CAUTION Refrigerant tubing


Tubing size (mm)
1 Use sufficient caution during preparation of the tubing. Outer dia. Thickness Outer dia. Thickness
Seal the tube ends by means of caps or taping to prevent ø6.35 t0.8 ø25.4 t1.0
dust, moisture, or other foreign substances from entering ø9.52 t0.8 ø28.58 t1.0
the tubes. ø12.7 t0.8 ø31.75 t1.1
ø15.88 t1.0 ø38.1 over t1.35
2 ø19.05 t1.0 ø41.28 over t1.45
ø22.22 t1.15

4-11. Connect the Tubing


When operating the refrigerant tube installation in the field, do not apply the flame of welding to the surrounding sheet-metal
3 parts. If necessary, use a wet rag to prevent overheating of the heat exchanger.

Model : 8 hp

4 3 2 1 Refrigerant Connection Supplied


tubing method parts used?

4 1 Suction tubing Brazing No


2 Discharge tubing Flare connection No
3 Liquid tubing Flare connection No
4 Balance tube Flare connection No

5
Model : 10 hp
Refrigerant Supplied
4 3 2 1 tubing Connection method parts used?
1 Suction tubing Brazing No
6 Yes
Service valve
Flare ø15.88
mounted on :
Discharge connection (Flare connection)
2 the unit side
tubing
ø19.05
Tubing side : Brazing
(Brazing)
7 3 Liquid tubing Flare connection No
Supplied 4 Balance tube Flare connection No
tube

9 2-38

5GEKPFF 
Design of 3WAY SYSTEM

4. Installation Instructions

Model : 12 hp
Refrigerant Supplied
4 3 2 1 Connection method
tubing parts used?
1 Suction tubing Brazing No
Yes
Service valve
Flare ø15.88
mounted on :
Discharge connection (Flare connection)
2 the unit side
tubing
Tubing side : Brazing ø19.05
(Brazing)

Service valve Yes


Supplied Supplied Flare
tube tube mounted on : ø15.88
connection (Flare connection)
3 Liquid tubing the unit side

Tubing side : Brazing ø19.05


(Brazing)
In case of 12HP
Flaring process to
4 Balance tube Flare connection No
1
the tip of the
supplied tubes Remove flare nuts attached to the service
valve and reuse them.
Note :
Use the wide area of the
Make sure the service valve is completely closed.
outer tubing surface
of the supplied tubes.
If not, the gas leak will be occurred. 2
• Supplied tubing outer Use the wide area of the outer tubing surface
diameter ø12.7 of the supplied tubes.
• Supplied tubing outer diameter ø19.05
• Local tubing inner
diameter ø12.7 • Local tubing inner diameter ø19.05 3
Flaring process to the
tip of the supplied tubes

Model : 14 hp Refrigerant Supplied


Connection method
4 3 2 1 tubing parts used? 4
1 Suction tubing Brazing No
Yes
Service valve
mounted on : Brazing ø19.05
Discharge the unit side (Brazing)
2
tubing
Tubing side : Brazing ø22.22
5
(Brazing)
3 Liquid tubing Flare connection No
4 Balance tube Flare connection No
Supplied tube
Refrigerant Supplied
6
Connection method
Model : 16 hp tubing parts used?
Yes
4 3 2 1 Service valve
mounted on : Brazing ø25.4
the unit side (Brazing)
1 Suction tubing
ø28.58
7
Tubing side : Brazing
(Brazing)
Yes
Service valve ø19.05
mounted on : Brazing
Discharge (Brazing)
2
tubing
the unit side
ø22.22
8
Tubing side : Brazing (Brazing)
Supplied tube Supplied tube
3 Liquid tubing Flare connection No
4 Balance tube Flare connection No
2-39 9

5GEKPFF 
Design of 3WAY SYSTEM

4. Installation Instructions

Refrigerant tube port


Use caulking, putty, or a similar material to fill any gaps at the refrigerant tube port ( ) in order to prevent rainwater,
dust or foreign substances from entering the unit.
* Perform this work even if the tubing is routed out in a
downward direction.

Tubing routed out through the front side

Tubing cover

* It is possible to route out the balance tube through this


knockout hole.
Then use caulking, putty, or a similar material to fill any
gaps at the tube port the same as described above.
1 Tubing routed out through the bottom

For local tubing connection, bend the liquid and balance tubing
Bottom plate until they reached the outlet of the knockout hole and make pipe
connection.

2
Tighten each cap as specified below.
Tightening torque for each cap
Cap tightening torque
3 Service port cap (width 17 mm) 9 – 11 N · m (90 – 110 kgf · cm)

width 14, 17 mm 20.0 – 25.0 N · m (200 – 250 kgf · cm)


Valve cap width 22 mm 20.6 – 28.4 N · m (206 – 284 kgf · cm)

4 width 30 mm 48.0 – 59.8 N · m (480 – 598 kgf · cm)

(Model : 8 hp) Valve cap


(Model : 10 hp) Valve cap
Valve cap Service port cap (width 30 mm) Valve cap Service port cap (width 30 mm)
(width 22 mm) (width 17 mm) (width 22 mm) (width 17 mm) Valve cap
Valve cap
(width 14 mm) Valve cap (width 17 mm)
5 Valve cap
(width 14 mm) (width 14 mm)

Service port cap Service port cap


(width 17 mm) Service port cap (width 17 mm)
(width 17 mm) Service port cap
Flare nut Flare nut (width 17 mm)

6 (ø6.35 mm)

Flare nut
Flare nut
(ø6.35 mm)

Flare nut Flare nut


(ø15.88 mm)
(ø15.88 mm) (ø9.52 mm)
(ø9.52 mm) ø19.05
ø22.22

(Model : 12 hp) Valve cap (Model : 14 hp, 16 hp) Valve cap


(width 30 mm) (width 14 mm)
7 Valve cap
(width 22 mm)
Service port cap
(width 17 mm) Valve cap
(width 17 mm)
Valve cap
(width 30 mm)
Service port cap
(width 17 mm) Valve cap
Valve cap (width 17 mm)
Valve cap
(width 14 mm) (width 14 mm)

Service port cap


8 (width 17 mm)

Flare nut
Service port cap
(width 17 mm)
Service port cap
(width 17 mm) Service port cap
(width 17 mm)
Flare nut
(ø6.35 mm) (ø6.35 mm)
Flare nut Flare nut
(ø9.32 mm) (ø15.88 mm) Flare nut
ø25.4 (ø12.7 mm)
ø19.05 ø25.4

9 2-40

5GEKPFF 
Design of 3WAY SYSTEM

4. Installation Instructions

Use two adjustable wrenches when removing or installing the Do not apply an adjustable
balance tube flare nut. wrench to the hexagonal part.
In particular, do not apply an adjustable wrench to the
hexagonal part at the top of the valve.
(If force is applied to this part, gas leakage will occur.)
Apply an adjustable wrench to settle the fixing tool as shown
Valve fixing tool
in the figure. If not used, the valve fixing tool will get distorted.

Use two adjustable wrenches, as shown in the figure,


when removing the liquid tube valve flare nut.
1. Do not apply a wrench to the valve cap when removing or
installing the flare nuts. Doing so may damage the valve.
2. If the valve cap is left off for a long period of time, refrigerant
leakage will occur. Therefore, do not leave the valve cap off.
3. Applying refrigerant oil to the flare surface can be effective in 1
preventing gas leakage, however be sure to use a refrigerant
oil which is suitable for the refrigerant that is used in the
system.
(This unit utilizes R410A refrigerant, and the refrigerant oil is
ether oil (synthetic oil). However, hub oil (synthetic oil) can 2
also be used.)

Precautions for brazing Work method


Be sure to replace the air inside the tube with nitrogen to Remote valve
prevent oxide film from forming during the brazing process.
Field-supply tube
3

Nitrogen
Be sure to use a damp cloth or other means to cool the valve
unit during brazing. Brazing locations Taping
Pressure-reducing
valve (regulator)
CAUTION
4
1. Be sure to use nitrogen
(Oxygen, CO2 , and CFC must not be used.)
2. Use a pressure-reducing valve on the nitrogen tank.
3. Do not use agents intended to prevent the formation of oxide
film. They will adversely affect the refrigeration oil, and may 5
cause equipment failure.
4. The balance tube is not used if only 1 outdoor unit is
installed. Use the unit in the same conditions as when it was
shipped from the factory.
6

2-41 9

5GEKPFF 
Design of 3WAY SYSTEM

5. HOW TO PROCESS TUBING

5. HOW TO PROCESS TUBING


The liquid tubing side is connected by a flare nut, and the gas tubing side is connected by brazing.

5-1. Connecting the Refrigerant Tubing Deburring

Use of the Flaring Method Before After

Many of conventional split system air conditioners employ the


flaring method to connect refrigerant tubes which run between
indoor and outdoor units. In this method, the copper tubes are
flared at each end and connected with flare nuts.

Flaring Procedure with a Flare Tool


(1) Cut the copper tube to the required length with a tube
cutter. It is recommended to cut approx. 30 – 50 cm longer
than the tubing length you estimate. Fig. 5-1

1 (2) Remove burrs at the end of the copper tube with a tube
Copper
tubing
reamer or file. This process is important and should be done
carefully to make a good flare.
Be sure to keep any contaminants (moisture, dirt, metal
Reamer
filings, etc.) from entering the tubing. (Figs. 5-1 and 5-2)
2 NOTE
Fig. 5-2
When reaming, hold the tube end downward and be sure that
no copper scraps fall into the tube. (Fig. 5-2)
(3) Remove the flare nut from the unit and be sure to mount it
3 on the copper tube.
Flare nut
Copper
(4) Make a flare at the end of the copper tube with a flare tool. tubing

(Fig. 5-3)
Flare tool
NOTE Fig. 5-3

4 A good flare should have the following characteristics:


Inside surface is glossy and smooth
Edge is smooth
Tapered sides are of uniform length Apply refrigerant
lubricant.
Caution Before Connecting Tubes Tightly Fig. 5-4
5 (1) Apply a sealing cap or water-proof tape to prevent dust or
water from entering the tubes before they are used.
(2) Be sure to apply refrigerant lubricant (ether oil) to the inside
of the flare nut before making piping connections. This is

6 effective for reducing gas leaks. (Fig. 5-4)


(3) For proper connection, align the union tube and flare tube Union
Flare nut
Fig. 5-5
straight with each other, then screw in the flare nut lightly at
first to obtain a smooth match. (Fig. 5-5)
Adjust the shape of the liquid tube using a tube bender at the installation site and connect it to the liquid tubing side valve
7 using a flare.
Cautions During Brazing
Replace air inside the tube with nitrogen gas to prevent copper oxide film from forming during the brazing process.
(Oxygen, carbon dioxide and Freon are not acceptable.)
Do not allow the tubing to get too hot during brazing. The nitrogen gas inside the tubing may overheat, causing
8 refrigerant system valves to become damaged. Therefore allow the tubing to cool when brazing.
Use a reducing valve for the nitrogen cylinder.
Do not use agents intended to prevent the formation of oxide film. These agents adversely affect the refrigerant and
refrigerant oil, and may cause damage or malfunctions.
9 2-42

5GEKPFF 
Design of 3WAY SYSTEM

5. HOW TO PROCESS TUBING

5-2. Connecting Tubing Between Indoor and Outdoor Units

(1) Tightly connect the indoor-side refrigerant tubing extended


Tightening torque,
from the wall with the outdoor-side tubing. Tube diameter Tube thickness
approximate
(2) To fasten the flare nuts, apply specified torque as at right: 14 – 18 N · m
ø6.35 (1/4”) 0.8 mm
(140 – 180 kgf · cm)
When removing the flare nuts from the tubing connections,
34 – 42 N · m
or when tightening them after connecting the tubing, ø9.52 (3/8”) 0.8 mm
(340 – 420 kgf · cm)
be sure to use 2 adjustable wrenches or spanners as shown. 49 – 55 N · m
ø12.7 (1/2”) 0.8 mm
(Fig. 5-6) (490 – 550 kgf · cm)
If the flare nuts are over-tightened, the flare may be damaged, 68 – 82 N · m
ø15.88 (5/8”) 1.0 mm
which could result refrigerant leakage and cause in injury or (680 – 820 kgf · cm)
100 – 120 N · m
asphyxiation to room occupants. ø19.05 (3/4”) 1.0 mm
(1000 – 1200 kgf · cm)
Torque wrench Because the pressure is approximately 1.6 times higher
than conventional refrigerant pressure, the use of ordinary 1
Spanner flare nuts (type 1) or thin-walled tubes may result in tube
Indoor unit rupture, injury, or asphyxiation caused by refrigerant
leakage.

Outdoor unit 2
Fig. 5-6

For the flare nuts at tubing connections, be sure to use


the flare nuts that were supplied with the unit, or else flare
nuts for R410A (type 2).
The refrigerant tubing that is used must be of the correct
3
wall thickness as shown in the table at right.
In order to prevent damage to the flare caused by over-
tightening of the flare nuts, use the table as a guide when
tightening. 4
When tightening the flare nut on the narrow tube, use an
adjustable wrench with a nominal handle length of 200 mm.

2-43 9

5GEKPFF 
Design of 3WAY SYSTEM

5. HOW TO PROCESS TUBING

5-3. Insulating the Refrigerant Tubing Two tubes arranged together


Liquid tubing Gas tubing
Tubing Insulation
Standard Selection of Insulation Material
Under the environment of the high temperature and high
humidity, the surface of the insulation material is easy to Insulation

become condesation. This will result in leakage and dew


drop. Refer to the chart shown below when selecting the
insulation material. In case that the ambient temperature and Three tubes arranged together
Cosmetic
relative humidity are placed above the line of the insulation (finishing) tape Suction tubing
thickness, the condensation may occasionally make a dew Discharge tubing
drop on the surface of the insulation material. In this case,
select the better insulation efficiency.
* However, since the condition will be different due to
1 the sort of the insulaton material and the environmental
Liquid tubing
Insulation
condition of the installation place, see the chart shown
below as a reference when making a selection.

Standard Selection of Tubing Insulation Four tubes arranged together


2 Calculating condition
Cosmetic
(finishing) tape Suction tubing
Polyethylene heat resisting Discharge tubing
Sort of insulation material
material
Thermal conductivity
Based on JIS A9501 Balance tubing
3 of insulation material
Calculating formula used
Based on JIS A9501
when calculating thickness
Insulation Liquid tubing
Refrigerant temperature 2°C Fig. 5-7

4
o6.35 o9.52 o12.7
100 100 100
Ambient relative humidity [%]

Ambient relative humidity [%]

Ambient relative humidity [%]

90 Thickness 90 90
Thickness Thickness
30mm
30mm 30mm
80 Thickness 80 Thickness 80
Thickness
5 70
20mm
70
20mm
70
20mm
Thickness
60 10mm 60 Thickness 60 Thickness
10mm 10mm
50 50 50

40 40 40
6 10 20 30 40
Ambient temperature [°C]
50 10 20 30 40
Ambient temperature [°C]
50 10 20 30 40
Ambient temperature [°C]
50

100
o15.88 100
o19.05 100
o22.22

90 90 90
Ambient relative humidity [%]

Ambient relative humidity [%]

Ambient relative humidity [%]

Thickness Thickness Thickness


80 30mm 80 30mm 80 30mm
7 70
Thickness
20mm 70
Thickness
20mm 70
Thickness
20mm

60 60 60
Thickness Thickness Thickness
10mm 10mm 10mm
50 50 50

8 40
10 20 30 40
Ambient temperature [°C]
50
40
10 20 30 40
Ambient temperature [°C]
50
40
10 20 30 40
Ambient temperature [°C]
50

9 2-44

5GEKPFF 
Design of 3WAY SYSTEM

5. HOW TO PROCESS TUBING

100
o25.4 100
o28.58 100
o31.75

90 90 90
Ambient relative humidity [%]

Ambient relative humidity [%]

Ambient relative humidity [%]


Thickness Thickness Thickness
80 30mm 80 30mm 80 30mm
Thickness Thickness Thickness
70 20mm 70 20mm 70 20mm

60 60 60
Thickness Thickness Thickness
50 10mm 50 10mm 50 10mm

40 40 40
10 20 30 40 50 10 20 30 40 50 10 20 30 40 50
Ambient temperature [°C] Ambient temperature [°C] Ambient temperature [°C]

o38.1 o41.28
100 100
Ambient relative humidity [%]

Ambient relative humidity [%]

90 90
Thickness Thickness
80 80

70
30mm
Thickness
70
30mm
Thickness
20mm
1
20mm
60 60
Thickness Thickness
50 10mm 50 10mm
40
10 20 30 40
Ambient temperature [°C]
50
40
10 20 30 40
Ambient temperature [°C]
50
2
If the exterior of the outdoor unit valves has been finished with a square duct covering,
CAUTION make sure you allow sufficient space to use the valves and to allow the panels to be
attached and removed.
3
Taping the flare nuts
Wind the white insulation tape around the flare nuts at the gas
tube connections. Then cover up the tubing connections with
Refrigerant tubing and insulator
the flare insulator, and fill the gap at the union with the supplied
black insulation tape. Finally, fasten the insulator at both ends
(not supplied)
4
Drain pipe and insulator
with the supplied vinyl clamps. (Fig. 5-8) Drain insulator (not supplied)
and clamp. Large
(supplied)
Insulation material
The material used for insulation must have good insulation
characteristics, be easy to use, be age resistant, and must not
Packing
clamp. Small
5
hose band Insulation
easily absorb moisture. (supplied) tape
Vinyl
After a tube has been insulated, never try Flare clamp
CAUTION to bend it into a narrow curve because it insulator
can cause the tube to break or crack.
Seal
6
Sealer (supplied) Insulation tape (white)(supplied) The procedure used for
installing the insulator
Flare insulator (supplied) for both gas and liquid
tubes is the same.
Tube insulator
(not supplied)
Unit side
insulator Heat resistant
120°C or above
Fig. 5-9 7
Never grasp the drain or refrigerant connecting outlets
Flare nut
Vinyl clamps (supplied) when moving the unit.
Fig. 5-8
8

2-45 9

5GEKPFF 
Design of 3WAY SYSTEM

5. HOW TO PROCESS TUBING

5-4. Taping the Tubes


(1) At this time, the refrigerant tubes (and electrical wiring if
local codes permit) should be taped together with armoring
tape in 1 bundle. To prevent the condensation from
overflowing the drain pan, keep the drain hose separate
from the refrigerant tubing.
(2) Wrap the armoring tape from the bottom of the outdoor
unit to the top of the tubing where it enters the wall. As you
wrap the tubing, overlap half of each previous tape turn. Clamp
Insulated tubes Drain hose
(3) Clamp the tubing bundle to the wall, using 1 clamp approx.
each meter. (Fig. 5-10)

NOTE
Do not wind the armoring tape too tightly since this will
1 decrease the heat insulation effect. Also ensure that the
condensation drain hose splits away from the bundle and drips
clear of the unit and the tubing.
Fig. 5-10

2 5-5. Finishing the Installation


Apply putty here
After finishing insulating and taping over the tubing, use sealing
putty to seal off the hole in the wall to prevent rain and draft
from entering. (Fig. 5-11)

3
Tubing
Fig. 5-11

9 2-46

5GEKPFF 
Design of 3WAY SYSTEM

6. AIR PURGING

6. AIR PURGING Manifold gauge Vacuum pump


Outlet
Air and moisture in the refrigerant system may have undesirable Inlet
effects as indicated below.
pressure in the system rises
operating current rises
cooling (or heating) efficiency drops
moisture in the refrigerant circuit may freeze and block
capillary tubing
Fig. 6-1a Fig. 6-1b
water may lead to corrosion of parts in the refrigerant
system
Therefore, the indoor unit and tubing between the indoor and Valve cap Service port cap Valve cap
outdoor unit must be leak tested and evacuated to remove any Valve cap
Valve cap
noncondensables and moisture from the system. (Figs. 6-1a
and 6-1b) 1
Air Purging with a Vacuum Pump (for Test Run) Service port cap
Preparation Service port cap
Flare nut
Check that each tube between the indoor and outdoor units
has been properly connected and all wiring for the test run has Fig. 6-2 2
been completed. Remove the valve caps from all service ports
Manifold valve
on the outdoor unit (Fig. 6-2). Note that all service valves on the
outdoor unit are kept closed at this stage (Fig. 6-3).
Pressure
The balance tube leak test is not necessary if only 1 outdoor
unit is installed.
gauge 3
Charge hose
Leak test
(1) With the service valves on the outdoor unit closed, remove Cylinder
valve
the 1/4 in. flare nut and its bonnet on the gas tube service Nitrogen gas cylinder 4
valve. (Save for reuse.) (In vertical standing
position)
(2) Attach a manifold valve (with pressure gauges) and dry
nitrogen gas cylinder to this service port with charge hoses.

Use a manifold valve for air purging.


If it is not available, use a stop valve 5
CAUTION for this purpose. Open

The “Hi” knob of the manifold valve Suction tube


must always be kept closed.
Close
(3) Pressurize the system to no more than 3.80 MPa with dry
nitrogen gas and close the cylinder valve when the gauge Open
6
reading reaches 3.80 MPa. Then, test for leaks with liquid
Discharge tube
soap.
Close
To avoid nitrogen entering the refrigerant Outdoor unit
system in a liquid state, the top of the
CAUTION cylinder must be higher than the bottom Open 7
when you pressurize the system.
Usually, the cylinder is used in a vertical Liquid tube
standing position. Close

Open
8
Balance tube

Close
Fig. 6-3

2-47 9

5GEKPFF 
Design of 3WAY SYSTEM

6. AIR PURGING

(4) Do a leak test of all joints of the tubing (both indoor and Manifold valve
outdoor) and all service valves. Bubbles indicate a leak.
Wipe off the soap with a clean cloth after a leak test. Pressure
gauge
(5) After the system is found to be free of leaks, relieve the
nitrogen pressure by loosening the charge hose connector
at the nitrogen cylinder. When the system pressure is
reduced to normal, disconnect the hose from the cylinder.

Evacuation
(1) Attach the charge hose end described in the preceding
Vacuum pump
steps to the vacuum pump to evacuate the tubing and
indoor unit. Confirm that the “Lo” knob of the manifold valve
is open. Then, run the vacuum pump. The operation time
Open
1 for evacuation varies with the tubing length and capacity of
the pump. The following table shows the amount of time for Suction tube
Close
evacuation:

Required time for evacuation Open


when 30 gal/min vacuum pump is used
2 If tubing length is If tubing length is
Discharge tube
Close Outdoor unit
less than 15 m longer than 15 m
45 min. or more 90 min. or more Open
Liquid tube
NOTE Close
3 The required time in the above table is calculated based on the
Open
assumption that the ideal (or target) vacuum condition is less
Balance tube
than –101 kPa (–755 mmHg, 5 Torr). Close
(2) When the desired vacuum is reached, close the “Lo” Fig. 6-4
4 knob of the manifold valve and turn off the vacuum pump.
Please confirm that the gauge pressure is under –101 kPa
(–755 mmHg, 5 Torr) after 4 to 5 minutes of vacuum pump
operation. (Fig. 6-4)

5 CAUTION Use a cylinder designed for use with


R410A respectively.

9 2-48

5GEKPFF 
Design of 3WAY SYSTEM

6. AIR PURGING

Charging additional refrigerant Manifold valve

Charging additional refrigerant (calculated from the liquid


Pressure
tube length as shown in Section “1-8. Additional Refrigerant
gauge
Charge”) using the liquid tube service valve. (Fig. 6-5)
Use a balance to measure the refrigerant accurately. Valve
If the additional refrigerant charge amount cannot be
charged at once, charge the remaining refrigerant in liquid
form by using the suction tube service valve with the system
in cooling mode at the time of test run. (Fig. 6-6)
Close the valve on the cylinder containing R410A. Liquid

Finishing the job R410A


(1) With a hex wrench, turn the liquid tube service valve stem
counter-clockwise to fully open the valve.
(2) Turn the gas tube service valve stem counter-clockwise to
Close
1
Suction tube
fully open the valve. Close

To avoid gas from leaking when


Close
CAUTION removing the charge hose, make sure Outdoor unit
the stem of the gas tube is turned all the
way out (“BACK SEAT” position).
Discharge tube
Close
2
(3) Loosen the charge hose connected to the gas tube service Open
port (1/4 in.) slightly to release the pressure, then remove Liquid tube
the hose.
(4) Replace the 1/4 in. flare nut and its bonnet on the gas
Close 3
Close
tube service port and fasten the flare nut securely with an
adjustable wrench or box wrench. This process is very Balance tube
Fig. 6-5
Close
important to prevent gas from leaking from the system.
(5) Replace the valve caps at both gas and liquid service valves
and fasten them securely.
4
This completes air purging with a vacuum pump. The air
Open
conditioner is now ready for a test run.
Suction tube
Open
5
Close

Discharge tube
Open Outdoor unit

Close
6
Liquid tube
Open

Close
Balance tube 7
Open Fig. 6-6

2-49 9

5GEKPFF 
Design of 3WAY SYSTEM

7. Optional Parts

7-1. Distribution Joint Kits Size of connection point on each part


CZ-P680PH2, CZ-P1350PH2 (for R410A) (Shown are inside diameters of tubing)
Size Part A Part B Part C Part D Part E
How to Attach Distribution Joint mm o38.1 o31.75 o28.58 o25.4 o22.22
1. Accompanying Parts Inch 1-1/2 1-1/4 1-1/8 1 7/8

Check the contents of your distribution joint kit. Size Part F Part G Part H Part I
mm o19.05 o15.88 o12.7 o9.52
2. Distribution Joint Kits (with insulation) Inch 3/4 5/8 1/2 3/8

CZ-P680PH2 USE:For outdoor unit(Capacity after distribution joint is 68.0kW or less.)

Suction Tube Discharge Tube Liquid Tube * Insulators for both the Suction
I tube and the Discharge tube are
H
the same.
300 300 G
#C #D
F * Suction tube and Discharge tube
C C DE F ED C D EF G E
I H GF E EFG HI are similar in sizes and both the
tube entrances have the same
340 diameter. So the both Distribution
#C Reducing #D
1 Distribution
Joint D
E
Joints
E
F
joints can fit into different tubes.
Since the diameter of the tube
F G ends for both Suction and
Discharge tube and different,
take care not to connect the
Insulation Insulation Insulation distribution joint diffrent. See the
"#" marks on the above figures.
2 CZ-P1350PH2 USE : For outdoor unit ( Capacity after distribution joint is greater than 68.0kW and no more than 135.0kW. )
Suction Tube Discharge Tube Liquid Tube
I
H
375 300 G
C DE F F
D C C E
3 B A
B
B A C DEF
I H GF E

340
EFG HI

D
E
F
B
Insulation Insulation
C A
4 D
Insulation

Using a tube cutter, cut the joints at the diameter required to match the outside diameter of the tubing you are connecting.
(This is usually done at the installation site.) The tube diameter depends on the total capacity of the outdoor unit.
Note that you do not have to cut the joints if it already matches the tubing end size. For size selection of the tube diameter,

5 refer to the installation instructions provided with the outdoor unit.


Avoid forceful cutting that may harm the shape of the joints or tubing.
NOTE Stopper(boss) Cutting point
(Inserting the tubing will not be possible if the tube shape is not proper.)
Cut off as far away from stopper as possible.
After cutting the joints, be sure to remove burrs on the inside of the joints.
Make this as long as possible.

6 (If the joints have been squashed or dented badly, reshaped them using
a tube spreader.)
Insertion length of the
connecting tube

Make sure there is no dirt or other foreign substances 15 to 30°


upward slant
Outdoor unit
inside the distribution joint. Side
The distribution joint can be either horizontal or vertical.
Indoor unit
7 In the case of horizontal, the L-shaped tubing must be Side
In case of horizontal position In case of vertical position
slanted slightly upward (15° to 90°). (directed upward or downward)
When brazing, replace air inside the tube with nitrogen Direction of Distribution Joint
gas to prevent copper oxide from forming.
Outdoor Outdoor
To insulate the distribution joint, use the supplied tubing insulation.
8 (If using insulation other than that supplied, make sure that its heat
unit unit

resistance is 120°C or higher.)


For additional details, refer to the installation instructions provided
with the outdoor unit. Direction of Indoor unit
Distributon Joint

9 2-50

5GEKPFF 
Design of 3WAY SYSTEM

7. Optional Parts

Size of connection point on each part


CZ-P224BH2, CZ-P680BH2, CZ-P1350BH2 (for R410A) (Shown are inside diameters of tubing)
Size Part A Part B Part C Part D Part E
How to Attach Distribution Joint mm o38.1 o31.75 o28.58 o25.4 o22.22
1. Accompanying Parts Inch 1-1/2 1-1/4 1-1/8 1 7/8

Check the contents of your distribution joint kit. Size Part F Part G Part H Part I
mm o19.05 o15.88 o12.7 o9.52
2. Distribution Joint Kits (with insulation) Inch 3/4 5/8 1/2 3/8

USE : For Indoor unit USE : For indoor unit (Capacity after distribution joint is
CZ-P224BH2 CZ-P680BH2
(Capacity after distribution joint is 22.4kW or less.) greater than 22.4kW and no more than 68.0kW.)
Suction Tube Discharge Tube Liquid Tube Suction Tube Discharge Tube Unit:mm

210 186 235


300 300
G F F GH I
G H H G H #D E F GH
#C DEF G FED C
FED C
Distribution H I H HI
F
Joint
G
H
Reducing
Joints
G

Insulation
#C #D
1
D E
Insulation Insulation Unit:mm E F
F
Insulation G
USE : For indoor unit G H
CZ-P1350BH2 (Capacity after distribution joint is greater than Insulation
68.0kW and no more than 135.0kW.)
Suction Tube . Discharge Tube Liquid Tube
Liquid Tube
I
H
* Insulators for both the Suction tube 2
H
and the Discharge tube are the same.
I G
G F
E
H F * Suction tube and Discharge tube are
G E
D
F IH GF E EFG HI similar in sizes and both the tube
E entrances have the same diameter.
C IH GF E EFG HI
A
340 So the both Distribution joints can
F E D C A B A C DE F 340
fit into different tubes.
Since the diameter of the tube ends
3
B B for both Suction and Discharge tube
90 are different, take care not to connect
the distribution joint diffrent.
Insulation See the "#" marks on the above figures.
Insulation
Insulation Unit:mm

3. Making Branch Connections


4
Using a tube cutter, cut the joints at the diameter required to match the outside diameter of the tubing you are connecting.
(This is usually done at the installation site.) The tube diameter depends on the total capacity of the indoor unit.
Note that you do not have to cut the joints if it already matches the tubing end size. For size selection of the tube
diameter, refer to the installation instructions provided with the outdoor unit. 5
Avoid forceful cutting that may harm the shape of the joints or tubing.
NOTE
(Inserting the tubing will not be possible if the tube shape is not proper.)
Stopper(boss) Cutting point
Cut off as far away from stopper as possible.
After cutting the joints, be sure to remove burrs on the inside of the joints.
(If the joints have been squashed or dented badly, reshaped them using 6
a tube spreader.) Make this as long as possible.
Insertion length of the
Make sure there is no dirt or other foreign substances inside the distribution joint.
connecting tube
The distribution joint can be either horizontal or vertical.
In the case of horizontal, the L-shaped tubing must be
slanted slightly upward (15゚to 30゚). Outdoor unit
Indoor unit
Side
7
When brazing, replace air inside the tube with nitrogen Side

gas to prevent copper oxide from forming. 15 to 30゚


upward slant
To insulate the distribution joint, use the supplied
In case of horizontal position
tubing insulation.
(If using insulation other than that supplied, make sure
In case of vertical position
(directed upward or downward) 8
that its heat resistance is 120 ゚C or higher.)
For additional details, refer to the installation instructions
provided with the outdoor unit.

2-51 9

5GEKPFF 
Design of 3WAY SYSTEM

7. Optional Parts

7-2. Solenoid Valve Kit for 3-Way System


CZ-P56HR3, CZ-P160HR3 (for R410A)
Installation Instructions
For safety installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices given in this manual.

This symbol refers to a hazard or unsafe practice which can result in severe
WARNING
personal injury or death.

This symbol refers to a hazard or unsafe practice which can result in personal
CAUTION
1 injury or product or property damage.

1. Accessories
Part Name Figure Q’ty Remarks
2 Washer 2 For hanging bolts

Hanging hook 1 Used to hang the solenoid valve kit

3 M4 screw 4 For hanging bolts

2. Positioning for Installation


The solenoid valve kit must be installed at a location within 30 m of the indoor unit.
4 However, the length of wiring provided with the solenoid valve kit is 5 m. If the valve will be used with wiring that
exceeds 5 m in length, use a terminal box (field supply) or similar device to extend the wiring.
Refer to “4. Wiring, Tubing, and Heat Insulation.”
The solenoid valve kit produces some refrigerant noise. If it is to be installed in a quiet place such as a hospital,
library or hotel, it is recommended that the solenoid valve kit be installed in the ceiling of a corridor, etc. apart
5 from the room.
The solenoid valve kit must be located not less than 2.5m above the floor or that cannot be touched.

Room Room Room Room

Indoor unit Indoor unit Indoor unit Indoor unit


6 Recommended
Avoid
installation
Solenoid valve kit
Solenoid valve kit

7 Corridor Corridor

○ ×
8

9 2-52

5GEKPFF 
Design of 3WAY SYSTEM

7. Optional Parts

Be sure to secure the solenoid valve kit with the


hanging bolts not to cause any falling damage,
using the hanging hooks.
Do not place the solenoid valve kit directly on the
ceiling surface. Select a location where the ceiling is
enough to support the weight of the solenoid valve Kit.
When installing the solenoid valve kit, remember to
Up side
install it with the top surface facing upward.
Front side

200 mm or more
(See the figure shown in the subsection “How to use
the fittings” in “3. Valve Dimensions and Hanging
Method.”) Service space
When installing the valve body, install with the top surface
facing up. Secure 200mm or more of space to the front and
150mm space upward so that the service panel can be
removed upward.
Never conduct drilling or welding on the sheet
1
Fig. 7-1 Service space
metal. Place the solenoid valve kit so that it does
not hinder draining. Solenoid Valve Kit Indoor Unit Capacity
Do not cover air holes.
CZ-P56HR3 22 – 56 Type
3. Valve Dimensions and Hanging Method CZ-P160HR3 71 – 160 Type 2
There are 2 types of solenoid valve kits: type 56 CZ-P160HR3 × 2
and type 160. The corresponding indoor unit model or
CZ-P56HR3 × 1 224 Type
capacities are shown in the table at right. +
CZ-P160HR3 × 1
3
CZ-P160HR3 × 2 280 Type

9P connector
Liquid tube ID9.52 Liquid tube
4
Cabtyre cable(5m) Type 160 : ID9.52
Suction tube ID15.88
Hanging hook Type 56 : ID6.35
21
11
17 28
74

5
76
149

Gas tube
110 Front side Type 160 : ID15.88
Discharge tube ID12.7
149 220 149 Type 56 : ID12.7 6
(71)

Service cover

7
240
168
25 38 37

51

8
42

518

Note: This figure shows the unit with suspension fittings attached.

2-53 9

5GEKPFF 
Design of 3WAY SYSTEM

7. Optional Parts

How to use the fittings


Hanging bolt (3/8")
Flat washer
(field supply)
Hanging hook Nut (field supply)

M4 screw(M4×12)
Never use a longer screw
other than the supplied screw.
This may falsely damage the tube
surface, causing refrigerant leakage.

Solenoid
valve kit

1 Be sure to attach the supplied hanging hook.

4. Wiring, Tubing, and Heat Insulation


1. Refrigerant tubing
2 Cool with damp cloth or other means when brazing the joint with a torch.
Otherwise, the solenoid valve will be damaged.

3 Suction tube

4 Liquid tube Liquid tube

Discharge tube

5
Gas tube

When brazing, be sure to perform nitrogen replacement inside the tube so that oxidation coating does not form
inside the tube.
6
2. Wiring
Connect the 9P connector coming from the solenoid valve kit through the power inlet of the indoor unit to the 9P
7 connector (red) of the Solenoid Valve Control PCB (sold separately). (Figs. 7-2-1, 2, 3)
Accessory wire length is 5 m.
In case the wire is not long enough, cut the wire halfway and connect additional wire (field supply) as an extension
using a terminal box (field supply).
Additional wire must be “H05VVF 0.5mm2 ” or “60227 IEC53”.
8 Anchor the cabtyre cable using the binding bands inside the unit.
Do not route the cabtyre cable through the same wiring conduit as the remote controller wiring or inter-unit control
wiring.
If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified
persons in order to avoid a hazard.
9 2-54

5GEKPFF 
Design of 3WAY SYSTEM

7. Optional Parts

NOTE
The wire should be fixed with the clamp inside the indoor unit.
Do not route the wire through a tube together with the remote-control line and inter-unit operation line.
Recommended wire size
6-core cable, 0.5 mm2 or more (300V or more)
Grounding should be done between the indoor unit and solenoid valve kit.

If required wire length is less than 5 m

Protective ground screw

Solenoid Valve Control PCB

1
Solenoid Valve

2
Fig. 7-2-1 Connection

Indoor unit : K1 type (45 ~ 106) Indoor unit : E1 type (224 ~ 280)
3
Protective ground screw
Protective ground screw

* As to protective ground screw,


remove the fixture screw and
resin cover. Then, carry out 4
earth ground work.

5
Solenoid Valve Control PCB

Solenoid Valve Control PCB

6
Front view

Fig. 7-2-2 Connection for S-45 ~ 106MK1E5 Fig. 7-2-3 Connection for S-224 ~ 280ME1E5
7
3. Heat Insulation
(Be sure to insulate the tubing after finishing leak inspection.)
Be sure to insulate the tubing.
Wrap insulators (field supply) having a thickness of 10 mm or more with heat resistance of 120°C or more around
the discharge tubes and gas tubes, and 80°C or more around the suction tubes and liquid tubes. 8
Use the supplied thermal insulation tape to bind the areas where there are seams and gaps between the thermal
insulation that is wrapped around each tube.
Failure to conduct thermal insulation may cause water leakage due to condensation.

2-55 9

5GEKPFF 
Design of 3WAY SYSTEM

7. Optional Parts

7-3. Solenoid Valve Controller


CZ-CAPE2
Installation Instructions
1. Supplied Parts

ԘSolenoid Valve Control PCB ԛOptional board box

ԙPower cables (3 core/2 core)* ԜFastening screws

Screw 4x4-2 (1 pc.) Screw 4x10-2 (2 pcs.)


3P Yellow 3P White
ԝ Cable tie (4 pcs.)

1
3P Yellow 3P White

Ԛ Signal output cables(long/short)* ԞProtective ground screw


for indoor unit

2 Screw 4x8-3 Washer

ԟ Nylon clamp(F7,F14)

5P Black 6P White

3 * Use the long cables and 3 core cables when the solenoid valve controller is installed outside the indoor unit.

2. Wiring Diagram
4 Connect to the indoor control PCB with power cable(2 core/3 core) (Supplied part ԙ) and Signal output cable (Supplied part Ԛ).
The connected solenoid valve is a solenoid valve kit, or a gas pipe valve kit.

Normal installation

5 Protective ground screw


Power cables (3 core) (Supplied part ԙ)
POWER

CN309
OP1 CN002
3P (Yellow) POWER
6 3P (White)
[AC Power Input]
Protective ground screw
Signal output cables
DC12V (long) Protective ground screw
CN81
3WAY (Supplied part Ԛ) Optional parts

7 EP valve
Balance valve CN001 CN003
Solenoid valve
kit or gas pipe
OPTION/3WAY 9P (Red) valve kit
Intake valve
6P (White) [Solenoid valve output]
Output valve
5P (Black)

Indoor control PCB Solenoid valve control PCB


8 Indoor unit Optional board box

9 2-56

5GEKPFF 
Design of 3WAY SYSTEM

7. Optional Parts

Models where installation is possible in indoor unit electrical box

Protective ground screw


Power cables (2 core) (Supplied part ԙ)
POWER

CN309
OP1 CN002
3P (Yellow) POWER
3P (White)
[AC Power Input]
Protective ground screw
Signal output cables
DC12V (short) Protective ground screw
CN81
3WAY (Supplied part Ԛ) Optional parts

EP valve Solenoid valve


Balance valve CN001 CN003 kit or gas pipe
OPTION/3WAY 9P (Red) valve kit
Intake valve
6P (White) [Solenoid valve output]
Output valve
5P (Black)
1
Indoor control PCB Solenoid valve control PCB
Indoor unit Optional board box

3. Installation Procedures
2
Note: See the reverse side for procedures for installation on various indoor units.

Models where installation is possible in indoor unit electrical box


1. Install the spacers for the solenoid valve control PCB in the electrical box.
2. Wire according to the following procedure. 3
Connect the 3P white connector of power cable(2 core) (Supplied part ԙ) to POWER (CN002) on
the solenoid valve control PCB.
Connect the 3P yellow connector to OP1 (CN309) on the indoor control PCB.
Connect the 6P white connector of Signal output cable (the short cable) (Supplied part Ԛ) to OPTION/3WAY
(CN001) on the solenoid valve control PCB.
Connect the 5P black connector to 3WAY (CN81) on the indoor control PCB. 4
Connect the connector from the solenoid valve kit or gas pipe valve kit (9P red) to the 9P red connector (CN003)
on the solenoid valve control PCB.
Connect the ground wire of the solenoid valve kit or gas pipe valve kit to the indoor unit using the screw and
washer (supplied part Ԟ).
* For the connecting location, refer to the indoor unit installation instructions.
3. When you have finished wiring work, check to be sure that there are no nipped portions in the wiring.
5
Optional parts

Solenoid valve
kit or gas pipe
9P Red
valve kit 6
Power cable (2 core) (Supplied part ԙ)
To indoor control PCB
3P White OP1(CN309)
3P Yellow
Signal output cable (short cable) (Supplied part Ԛ)
To indoor control PCB
7
6P White
CN003 3WAY (CN81)
5P Black
9P Red

POWER
(CN002)
3P White
OPTION/3WAY
(CN001) 8
6P White

2-57 9

5GEKPFF 
Design of 3WAY SYSTEM

7. Optional Parts

Models without space inside electrical box


1. Install the solenoid valve control PCB in the optional board box with the following procedure.
Install the board spacers in the holes in the base of the optional board box.
Note: When you do so, be careful of the direction of the solenoid valve conrol PCB(see following figure).
Attach the optional board box to the unit with the supplied screws(4x10).
2. Wire according to the following procedure.
Connect the 3P yellow connector of power cable (Supplied part ԙ) to OP1 (CN309) on the indoor control PCB.
Connect the 5P black connector of signal output cable (Supplied part Ԛ) to 3WAY (CN81) on the indoor control PCB.
Connect the ground wire of the power cables (3 core) to the indoor unit using the screw and washer (supplied part Ԟ).
* For the connecting location, refer to the indoor unit installation instructions.
* When you use the power cables (2 core) for installing inside electrical box, ground connection is unnecessary.
Connect the ground wires of the power cables and solenoid valve kit or gas pipe valve kit to the optional board box.
* When you use the power cables (2 core), only connect the ground wire of the solenoid valve kit or gas pipe valve kit.
Connect the 3P white connector of power cable(Supplied part ԙ) to POWER(CN002) on the solenoid valve control
PCB.
Connect the 6P white connector of signal output cable(Supplied part Ԛ) to OPTION/3WAY(CN001) on the solenoid
1 valve control PCB.
Connect the connector from the solenoid valve kit or gas pipe valve kit (9P red) to the 9P red connector (CN003) on
the solenoid valve control PCB.
Fasten the wires to the optional board box with the cable ties (supplied part ԝ)
3. When you have finished wiring work, secure the cover of the optional board box with the supplied screw (4x4)
2 Note: When you do so, check to be sure that there are no nipped portions in the wiring.

screw 4˜4

3 Optional parts

Solenoid valve
kit or gas pipe
9P Red valve kit

Power cable (3 core/2 core) (Supplied part ԙ )


4 3P White To indoor control PCB
OP1(CN309)
3P Yellow

Signal output cable (long/short) (Supplied part Ԛ )


6P White To indoor control PCB
CN003 3WAY (CN81)
9P Red OPTION/3WAY 5P Black
5 (CN001)
6PWhite
screws 4˜10 (2 locations)

6 Optional board box


POWER
(CN002) Protective ground screw
3P White for power cable (3 core)

Spacers (4 locations) Protective ground screw


7 for solenoid valve kit or gas pipe valve kit

9 2-58

5GEKPFF 
Design of 3WAY SYSTEM

7. Optional Parts

Figure of installation to each Indoor unit

4-Way Cassette (U1 Type)

Protective ground screw


Ceiling (T1 Type)
36-56 Type

73-140 Type
2

4
Protective ground screw

High Static Pressure Ducted (E1 Type)

Protective ground screw


6
73-140 Type

7
(桃)
RC1
(茶)

TRANS−P
DP

ACI

T20

ヒューズ


FAN

TRANS−S
HS

8
TA
FS

PMV
BL
PNL
E1
E2
E3
RC

OC

2-59 9

5GEKPFF 
Design of 3WAY SYSTEM

7. Optional Parts

4-Way Cassette 60x60 (Y1 Type)

Protective ground screw

Slim Low Static Ducted (M1 Type)


1

2
Protective ground screw

3
1-Way Cassette (D1 Type)

5
Protective ground screw

7 2-Way Cassette (L1 Type)


Protective ground screw

LN U
1U
2R
1R
2

9 2-60

5GEKPFF 
Design of 3WAY SYSTEM

7. Optional Parts

Low Silhouette Ducted (F1 Type)


As Viewed from B
Solenoid Valve control PCB

Protective ground screw

As Viewed from A

A
L N U1 U2 R1 R2

1
Low Silhouette Ducted (F2 Type)
As Viewed from A A

3
Solenoid Valve
control PCB

4
Protective ground screw A

Floor Standing (P1 Type)


Concealed Floor Standing (R1 Type)
5
Solenoid Valve Protective ground screw
control PCB

6
3
2

7
1
U2
U1

2-61 9

5GEKPFF 
Design of 3WAY SYSTEM

7. Optional Parts

7-4. Solenoid Valve Controller


CZ-CAPEK2
Installation Instructions
1. Supplied Parts
ԘSolenoid Valve Control PCB ԙPower cables Ԛ Signal output cables

3P Yellow 3P White 5P Black 6P White

2. Wiring Diagram
Connect to the indoor control PCB with Power cable (Supplied part ԙ) and Signal output cable (Supplied part Ԛ)
The connected solenoid valve is a solenoid valve kit.
Power cables (Supplied part ԙ)

1 POWER

CN309
OP1 Solenoid Valve Control PCB (Supplied part Ԙ)
3P (Yellow)
CN002
POWER
3P (White)
[AC Power Input]
2 Optional parts

CN003
DC12V 9P (Red)
CN81 Signal output [Solenoid valve output] Solenoid valve kit
3WAY cables (Supplied part Ԛ)

3 EP valve
Balance valve CN001
OPTION/3WAY
Intake valve
6P (White)
Output valve
5P (Black)

4 Protective ground screw

Indoor control PCB

5 3. Installation
Front panel
3-1. How to remove the grille Screw (on the cover)
Screw (on the front)
Remove the two screw covers bellow
the grille and open the front panel. (Fig.7-3) Terminal block cover

6 Remove the six screws. (Fig.7-3)


Remove the terminal block cover. (Fig.7-3)
Warp the lower flap to take out the pins
Grille
and remove the lower flap. (Fig.7-4)
Screw (on the bottom)
Screw

7 Screw cover Bottom surface


Fig. 7-3

Grille Upper flap


Pin

Lower flap Fig. 7-4

9 2-62

5GEKPFF 
Design of 3WAY SYSTEM

7. Optional Parts

Hold the both sides of the grille and pull upwards to remove from the frame. (Fig.7-5)
Remove the electrical component box cover. (Fig.7-6)

Upper tab
Tab Frame
Electrical component
box cover

Electrical
component box

Lower tab
Fig. 7-5 Fig. 7-6

3-2. How to install the board


Disconnect the CN033 (White), CN103 (Green), CN102 (Red), CN100 (White), CN082 (White)CN104 (Yellow) connectors
1
from the indoor control PCB and take out the indoor control PCB. (Fig.7-7)
* When you take out the indoor control PCB, lift the tab holding the indoor control PCB. (Fig.7-8)
Connect the 3P connector (yellow) of the power cables (supplied part ԙ) to the CN309 OP1 connector (yellow) on the indoor
control PCB. (Fig.7-7)
Connect the 5P connector (black) of the signal output cables (supplied part Ԛ) to the CN081 3WAY connector (black) on the
indoor control PCB. (Fig.7-7)
2
Connect the removed connectors to their original positions on the indoor control PCB and insert the PCB. (Fig.7-7)
* Be sure to connect all the connectors.

3
Indoor control PCB
Tab for holding
Indoor control PCB
CN309(Yellow)

Screw 4
Cover
CN082(White)
CN100(White)
CN102(Red)
CN103(Green)
CN033(White) 5
CN104(Yellow)
Solenoid Valve Control PCB
CN081(Black) Lower tab
mounting position

Fig. 7-7 Fig. 7-8


6
Remove the screw and the cover.(Fig.7-7)
Connect the solenoid valve kit ground wire to the indoor unit ground wire mounting position. Also connect the 9P connector
(red) of the solenoid valve kit to the CN003 9P connector (red) on the solenoid valve control PCB. (Figs.7-9, 10)
Connect the 3P connector (white) of the power cables (supplied part ԙ) to the CN002 POWER connector (white) on the
solenoid valve control PCB (supplied part Ԙ) (Fig.7-9)
Connect the 6P connector (white) of the signal output cables (supplied part Ԛ) to the CN001 3WAY connector (white) on the
7
solenoid valve control PCB.(Fig.7-9)
Insert the solenoid valve control PCB into its mounting position. (Fig.7-8)
* Pay attention to the insertion direction of the solenoid valve control PCB. (Fig.7-9)
Hook the upper tab of the electrical component box cover to the electrical component box first, and then fit the lower tab.
(Figs.7-6, 8) 8
* Pay attention not to catch the wires in the electrical component box cover.
Clamp the wiring from the solenoid valve kit. (Fig.7-10)
Attach the screw and the cover.(Fig.7-7)

2-63 9

5GEKPFF 
Design of 3WAY SYSTEM

7. Optional Parts

Optional parts

Solenoid valve
kit
9P Red

Power cables (supplied part ԙ)


To indoor control PCB
3P White OP1(CN309)
3P Yellow
Signal output cables (supplied part Ԛ)
6P White To indoor control PCB
5P Black 3WAY (CN081)

CN003
9P Red
Board Insertion direction
POWER OPTION/3WAY
1 (CN002)
3P White
(CN001)
6P White
Spacers (4 locations) Fig. 7-9

2
Protective ground screw

6 Clamp position for


Solenoid valve kit wiring Fig. 7-10

7
3-3. How to attach the grille
Fit the grille to the three tabs on the upper part of the frame and attach the grille. (Fig.7-5)
Press the grille to its original position. Attach six screws and two screw covers. (Fig.7-3)
* For the screws on the front, attach screws in turn from the electrical component box side.
8 Warp the lower flap and fit the pins to the grooves on the grille to attach the flap. (Fig.7-4)
Close the front panel. (Fig.7-3)

9 2-64

5GEKPFF 
Design of 3WAY SYSTEM

7. Optional Parts

7-5. VRF Renewal Kit


CZ-SLK2 (for R410A)
Installation Instructions
Check the parts of the VRF Renewal Kit you purchased.

Name Shape Quantity Name Shape Quantity

(1) Filter drier 1 (3) Tube 1 (for ø12.7) 2

(2) Valve 1 (4) Tube 2 (for ø9.52) 2

1. How to attach the VRF Renewal Kit


1-1 Assemble and use parts (1) to (4) in the figure 1-2 Connect each part in accordance with the figure below.
above in accordance with the table below. Unit: mm 1
Charge port
Outdoor Unit Type Parts Quantity
(1), (2) B A A B
1 Indoor
4, 5, 6, 8, 10 HP Outdoor
(3), (4) 2 unit side unit
side
12, 14, 16 HP
(1), (2)
(3)
1
2
445 (12, 14, 16 HP) 2
535 (4, 5, 6, 8, 10 HP)

Connection part dimensions


80
(shows tube inside diameters)
A B
177 ø12.7 ø9.52 3
* Attach the valve to the indoor unit side as viewed from
the filter drier.
* If the tube size does not match the existing tube size,
use a reducer (obtain locally) to adjust the tube diameter. 4
1-3 Attach a VRF Renewal Kit to each outdoor unit.
1-4 Cut the existing tubing on site with a pipe cutter or the like and attach the VRF Renewal Kit according to the rough
indication of the dimensions for attaching the VRF Renewal Kit shown in the figure above.

2. Tightening flare nuts and brazing


Use a tightening torque of 55±6 N·m for the flare nuts. Use a wet cloth or the
5
Be sure to use a wet cloth or the like to cool the valve main part and like to cool these parts.
filter drier when you perform the brazing process.
Also, be sure to replace the air inside the tube with nitrogen to prevent
the formation of an oxide film when you perform the brazing process. 6
There is a risk of system mulfunction through clogging of the strainer
or refrigerant circuit when the brazing is performed without nitrogen
gas replacement in the tube.
3. Opening and closing the valve
The valve is opened at the time of shipment from the factory. 7
Open state Closed state
4. Leak testing
Perform a leak test for the brazing parts and flare connections parts.
For the leak test, refer to " Installation Instructions" supplied with the
outdoor unit.
8
5. Attaching thermal insulation material
Make sure the thermal insulation (obtain locally) covers the entire kit.
Use thermal insulation material with a heat resistance of at least 80°C and thickness of at least 10 mm.

2-65 9

5GEKPFF 
Design of 3WAY SYSTEM

8. Supplement

8-1. Dimensions of Wind Ducting


Reference diagram for air-discharge chamber (field supply)
Can be installed so that the air direction is to the front, right, left or rear direction.
According to the installation site, you may choose the setting position in the depth direction of the anchor bolt from “A”, “B” or “C”.

Model : U-8MF2E8, 10MF2E8, 12MF2E8, 14MF2E8, 16MF2E8


unit: mm

Air direction: Front direction Air direction: Rear direction

Top view Top view

1000 1000
1 978
933 35
930
34 978 34
930
35
(698)

(698)
2
2352

2352
1654

1654
3

Front view Right side view Front view Right side view

9 2-66

5GEKPFF 
Design of 3WAY SYSTEM

8. Supplement

Reference diagram for air-discharge chamber (field supply)


Unit combinations
Can be installed so that the air direction is to the front, right, left or rear direction.
According to the installation site, you may choose the setting position in the depth direction of the anchor bolt from “A”, “B” or “C”.
Diagrams for 2-unit setting unit: mm
*b Air direction: Front direction
1000 *a 1000
For 2-unit setting
*a *b
B

930
A

A : 894 (Installation hole pitch)


C

60 2060
* The tubing is routed out from the front.
B : 730 (Installation hole pitch)
970 970 180 2180
* The tubing is routed out from the bottom.

C : 730 (Installation hole pitch) 180 2180

Top view 1
930
978 978
933 933 35 34

2
(698)
2352

3
1654

Front view Right side view


Diagrams for 3-unit setting
*b
4
1000 *a 1000 *a 1000
unit: mm

Air direction: Front direction


B

930
A

5
C

For 3-unit setting


*a *b
970 970 970 A : 894 (Installation hole pitch)
60 3120
* The tubing is routed out from the front.
B : 730 (Installation hole pitch)
180 3360
* The tubing is routed out from the bottom.
Top view
C : 730 (Installation hole pitch) 180 3360 6
978 978 978 930
933 933 933 35 34

7
(698)
2352
1654

Front view Right side view

2-67 9

5GEKPFF 
Design of 3WAY SYSTEM

8. Supplement

Air Discharge Chamber (field supply)


Reference Diagram for Air-Discharge Chamber
Model : U-8MF2E8, 10MF2E8, 12MF2E8, 14MF2E8, 16MF2E8
unit: mm

Air direction: Front direction Air direction: Rear direction

Top view Top view

1000 930 1000 930


978 978
933 35 34 34 35

1
(698)

(698)
2
2352

2352
1654

1654
3
Front view Right side view Front view Right side view

Necessary Assembling Parts


4
Parts Q’ty Thickness
1 Top cover 1 -
2 Side panel (left) 1 -
5 3 Side panel (right)
4 Rear cover
1
1
-
0.8
5 Bracket A 2 1.2
1 6 Bracket B 2 1.2
Tapping screw (4mm x 12mm) 34 -

6 2
Tap Tight screw (5mm x 10mm) 24 -

896 36
978 860
3

7 4
699

6
5
5
101 180

6
8
1002

9 2-68

5GEKPFF 
Design of 3WAY SYSTEM

8. Supplement

Installation of Air Discharge Chamber

The parts shown below are locally procured parts.


Choose the parts free from rust or rustless material in order to prevent rust and salt-air damage resistance.
The parts are available for use of the air discharge chamber and snow-proof vents.
When using for the snow-proof vents (air discharge duct), first attach this air discharge chamber and then the
snow-proof vents (air intake duct).
Top cover

Side panel (left) Parts Q’ty


Top cover 1
Side panel (left) 1
Side panel (right)
Side panel (right) 1
Rear cover 1
Bracket A 2
Rear cover Bracket B 2 1
Tapping screw (4mm x 12mm) 34
Bracket B
Bracket A Tap Tight screw (5mm x 10mm) 24
Bracket A
Bracket B
NOTE
2
Install the duct where there is well enough for ventilation even if a strong wind is blowing.

Tightening Screws
The screws for fixing parts indicate by number as shown in the chart.
Tighten with the tapping screws (4mm x 12mm) for the number 1 . 3
Tighten with the tap tight screws (5mm x 10mm) for the number 2 .
Remove the screw C tightened to the unit. It is available for reuse.

How to Install Air Discharge Chamber


The installation work must be carried out with a partner for safety.
4
To accomplish the parts assembly, follow the steps below.
If the parts assembly is performed in a different way, installation will not successfully complete.

1. Bracket Attachment
Attach the brackets A and B at each corner post of the unit (as shown below).
5
Tighten with 3 screws respectively per corner post.

1 Bracket B
C
Bracket A
1 Bracket A 6
C
1
1
C
Bracket B 1 7
C

8
Fig. 8-1

2-69 9

5GEKPFF 
Design of 3WAY SYSTEM

8. Supplement

2. Rear Cover Attachment

Attach the rear cover to the upside of brackets A and B.


Tighten with 2 screws from upside. 2
Rear cover
Bracket B
2

Bracket A
Fig. 8-2

1
3. Side Panel Attachment (Left & Right)

Fix one side panel on the top of the unit.


Place the side panels so that the flap of the Flap of the rear cover should fit inside the side
2 rear cover should fit inside the side panels
as shown in the chart.
panels. (Similar to opposite side)

At first, tighten with 2 screws (5mm x 10mm) Side Panel (Right)


respectively from upside marked with an
asterisk as shown in the chart.
Then tighten 10 other locations respectively
* 2
Enlarged view
3 on the sideways of the brackets and rear panel.
Repeat the same procedure as described
*
above for other side panel. 2 . 2

4 1 2

2
2
2
5 Side Panel (Left)
2

Fig. 8-3

4. Top Cover Attachment


6 Fix the top cover, side panels (left and right) and rear cover. Top Cover
Tighten with 20 screws.
1 ×18

7
1 ×2

8
Fig. 8-4

9 2-70

5GEKPFF 
Design of 3WAY SYSTEM

8. Supplement

Reference Diagram for Side Panel (Left) (field supply) : 1107-330

RMK PART NAME Q’ty


1 COV SIDE L 778 1
2 PL MTG 347 1

A unit: mm

1
1
2
40 130×6=780

95
(7)

View A-A A B View B-B


Unite with dowels (fiducial point)
Fig. 8-5

Reference Diagram for Side Panel (Left) (field supply) : COV SIDE L 778
3
20 (O.D.)

unit: mm
5-Ø3.3 protrusion holes
231 231 231 231 13.5
.4

9.2
10

(reverse side)
15
(O

4
.D

View A
.)

2-Ø7
15.1 (O.D.)

holes
10.8

874.4 24.7
View B 859.3 0.3
45°
25

C
D E
(45
°) 5
24

22 (O.D.)
.4

.)

859.6 (O.D.) Detail view E


.D

12
(O
15

2-Ø 7 holes
66

ole

°)
View C (64
6
sid on h

A Ø
3
(re .3 p
rse trusi
e)

ve ro
(re 3 pro

rs tru
e s
675.2 (O.D.)

si ion
B (s
693.6

ig 2-Ø de
.
ve
Ø3

) ho
691

ht 4 le
fa do
ci w
0.3 ng e
7
45°

yo ls 18.4
273.3 (O.D.)
s

holes
274.3 (O.D.)
ole

u)
2-Ø6
25
7h

259.8
4-Ø

(45 25
92 5
5

°)
135.8
113
92

15 40

Detail view D

8
45°

45°

5.2

36 (O.D.) 12.4 (O.D.)


828.4 15.6
704 77.8
500 179.8
Fig. 8-6
NOTE : The contour of bevel except for specific indications shall be C5.
2-71 9

5GEKPFF 
Design of 3WAY SYSTEM

8. Supplement

Reference Diagram for Side Panel (Left) (field supply) : PL MTG 347
unit: mm

10 (O.D.)

858 (O.D.)
35 (O.D.)

853.2
500
26.2 (O.D.)

2.4
18

21.2 (O.D.) 2-Ø4.1 dowel holes

1
2-

830.4
Ø
7

547 45
ho

°
°
le

45
s
40 (O.D.)
27
13.5

NOTE : The contour of bevel except for specific indications shall be C5.

3 Fig. 8-7

9 2-72

5GEKPFF 
Design of 3WAY SYSTEM

8. Supplement

Reference Diagram for Side Panel (Right) (field supply) : 1108-336

RMK PART NAME Q’ty


1 COV SIDE R 500 1
2 PL MTG 347* 1
* Same as Fig. 8-7 B
unit: mm

1
2 1
130×6=780 40

95
(7)
2
View A-A A B View B-B
Unite with dowels (fiducial point)

Fig. 8-8

Reference Diagram for Side Panel (Right) (field supply) : COV SIDE R 500
3
unit: mm
.4

20 (O.D.)
24

5-Ø3.3 protrusion holes (reverse side)


15

2-Ø7 holes
(O

13.5 231 231 231 231


9.2
.D

4
.)
66

View A
View B

24.7 874.4
10

15.1
.4

859.3
.)
.D

2-Ø7 holes
5
(O

Ø3.3 protrusion hole


15

E D (reverse side)
25 (O.D.)
66

22 (O.D.)
View C 859.6 (O.D.) 12
10.8

A
0.3 6
45°

C
le
ho
o n

)
si

de u)
691 (O.D.)
tru

si yo
o

) se ing
693.6

45°
pr

675.2

( r ac
3

ve tf
3.

Detail view D (re h


Ø

sig
els
(
7
s

2-Ø6 18.4
273.3 (O.D.)

w
ole
274.3 (O.D.)

do
135.8 25 99

holes
7h

Ø4
45°

0.3 2-
4-Ø

25
B
5
92 5

113

92
15 40

(45
8
45°
45°

828.4
5.2

°) 15.6
77.8 704
12.4 36 (O.D.)
179.8 500
(O.D.)
Detail view E
Fig. 8-9
NOTE : The contour of bevel except for specific indications shall be C5.
2-73 9

5GEKPFF 
Design of 3WAY SYSTEM

8. Supplement

Reference Diagram for Top Cover (field supply) : 1106-354

RMK PART NAME Q’ty (23.7) C unit: mm


1 COV TOP 492 1 L
(16.7) (15)

20
2 PL MTG 348 1
3 PL MTG 350 1
B
C

1.7 1
3.5

65×14 =910
Unite with dowels

(1001.6)
(fiducial point)

Detail view C
2
1 A A
3
132×7=924 (27.8)
C (8) (978.4)
L
C
L
2
Unite with dowels
(fiducial point)
View B View A-A
Fig. 8-10
3
Reference Diagram for Top Cover (field supply) : COV TOP 492
unit: mm

4 23.7
(7.
10
-Ø 978.4 A 16.7 8)
6h °)
ole (26
s
2-Ø 3.4
41.1
34.2
49.2

(re 4 do
.7)

5
169

ve
rse wels
231

(37

sid 500
e)
18.2 (O.D.)

2-Ø
(re 4 do
ve
rse wels
231

sid
View A e)
500

6
1001.6
988.2

992.9

s
231

le
ho
6
Ø
8-

7
231

)
15.5

4
(2.

38.9 149.1 188 188 188 149.1 38.9

View B 15
27.4 °)
(64
8 958.4
B
(Similar to opposite side)
Fig. 8-11

9 2-74

5GEKPFF 
Design of 3WAY SYSTEM

8. Supplement

Reference Diagram for Top Cover (field supply) : PL MTG 348


24.8 (O.D.)
unit: mm

s
ole
lh

180.5
e
dow
4.1
2-Ø

10 (O.D.)

500
1
950 (O.D.)

3
°6
11

4
20 20

(Similar to opposite side)


NOTE : The contour of bevel except for specific indications shall be C5. Fig. 8-12
5
Reference Diagram for Top Cover (field supply) : PL MTG 350
unit: mm
33.4 (O.D.)

975.2 (O.D.) °)
(45
500 3.2
6
16.4
31

20

es
h ol
el (Similar to opposite side)
w
do
1
4.
2-
Ø 2-Ø
6h
ole
7
s
2.4
17
23.2 (O.D.)

935.2
952.8
8
NOTE : The contour of bevel except for specific indications shall be C5.
Fig. 8-13
2-75 9

5GEKPFF 
Design of 3WAY SYSTEM

8. Supplement

Reference Diagram for Rear Cover (field supply) : 1109-484

unit: mm
950.6
926.8
924.2 6-Ø3.3 protrusion holes
902.2 (reverse side)
899
149.1 188 188 188 149.1 4-Ø3.3 protrusion holes
35 (reverse side)

15 0.8
16.8
(O.D
.)

25

164.8

147.3
174

149

(76

78
76

°)
1

28.6
40.8
1.2

3
9.6
38
932.2 (Similar to opposite side)
921.2 s
899 h ole
Ø7
2 2-
16 (I.D.)
19.4

(13
5°)

3 NOTE : The contour of bevel except for specific indications shall be C5.
Fig. 8-14
Reference Diagram for Bracket A (field supply) : 1136-351
unit: mm
1.2

4 2-Ø4.65 protrusion holes


(reverse side)
62.1

21 30
)
39.1
37.1

(45°

3.6
11.8 A
5
s
le

27
ho
on

37.1
) i
de us
si tr

61.1
e ro
rs p
ve .65
(re -Ø4

50.6 (O.D.) 52 (O.D.)

6
2

22.4
14


40
96.8 (O.D.)
66
111.6

111.6
157.4 (O.D.)

40

7 Ø8 hole

Ø16 hole 2-Ø4.65 protrusion holes


30
30

(sight facing you)

Ø6 hole
6 Ø6 hole
8 15.6

View A
NOTE : The contour of bevel except for specific indications shall be C5. Fig. 8-15

9 2-76

5GEKPFF 
Design of 3WAY SYSTEM

8. Supplement

Reference Diagram for Bracket B (field supply) : 1136-352


unit: mm

2-Ø4.65 protrusion holes (reverse side)

1.2

62.1
21 30

39.1
37.1
(45°
)
A
3.6
11.8
27
37.1
61.1
2-Ø4.65 protrusion holes

52 (O.D.) 50.6 (O.D.)


(reverse side) 1

14
22.4
40
96.8 (O.D.)

66
111.6
157.4 (O.D.)

2
111.6
40

Ø8 hole
Ø16 hole

30
30

Ø6 hole
6

2-Ø4.65 protrusion holes


Ø6 hole 15.6 3
View A
(sight facing you)

NOTE : The contour of bevel except for specific indications shall be C5. 4
Fig. 8-16

2-77 9

5GEKPFF 
Design of 3WAY SYSTEM

8. Supplement

8-2. Dimensions of Snow Ducting


Reference diagram for snow-proof vents (field supply)
Can be installed so that the air direction is to the front, right, left or rear direction.
According to the installation site, you may choose the setting position in the depth direction of the anchor bolt from “A”, “B” or “C”.

Model : U-8MF2E8, 10MF2E8, 12MF2E8, 14MF2E8, 16MF2E8


unit: mm
853 Air direction: Front direction 853 Air direction: Rear direction
744

744
Top view Top view

1
112

978 930 930


933 35 34 34 35
(698)

2 489 489
489 489
2352

600
1654
1338

1338

3
600
529

529
355

355

121

1979 1419
Front view Right side view Front view Right side view
4

9 2-78

5GEKPFF 
Design of 3WAY SYSTEM

8. Supplement

Reference diagram for snow-proof vents (field supply)


Unit combinations
Can be installed so that the air direction is to the front, right, left or rear direction.
According to the installation site, you may choose the setting position in the depth direction of the anchor bolt from “A”, “B” or “C”.

Diagrams for 2-unit setting unit: mm


2180
1000 180 1000
970 970
Air direction: Front direction

930
A: 894 (Installation hole pitch) * The tubing is routed out from the front.
B
A
C

B: 730 (Installation hole pitch) * The tubing is routed out from the bottom.
C: 730 (Installation hole pitch)
2033

1
744
744

Top view
112
112

2180 930
11 202 11 35 34

2
489 489 489
2352
1654
1338

1338

1338

3
529

529

529
355

355
355

1356
405

3159 1419
Front view Right side view unit: mm
Diagrams for 3-unit setting Air direction: Front direction
4
3360
1000 180 1000 180 1000 A: 894 (Installation hole pitch)
970 970 970 * The tubing is routed out from the front.
B: 730 (Installation hole pitch)
930

* The tubing is routed out from the bottom.


B

5
A
C

C: 730 (Installation hole pitch)

3213

6
744

744

Top view
112

112

3360 930
11 202 202 11 35 34

7
489 489 489
2352
1654
1338

1338
1338

8
529
529
529

355

355

355
1356

1356
405

405

1419
4339
Front view Right side view
2-79 9

5GEKPFF 
Design of 3WAY SYSTEM

8. Supplement

Snow-Proof Vents (Air Intake Duct) 1 (field supply)


Reference Diagram for Snow-Proof Vents (air intake duct)
Model : U-8MF2E8, U-10MF2E8, U-12MF2E8, U-14MF2E8, U-16MF2E8
unit: mm
853 Air direction: Front direction 853 Air direction: Rear direction
744

744
Top view Top view
112

978 930
930
1 933 35 34
34 35
(698)

489 489 489


489
2
2352

600
1654
1338

1338
600
529
529
355

3
355

121

1979 1419
Front view Right side view Front view Right side view
Snow-Proof Vents
(air intake duct) 1

4 Necessary Assembling Parts unit: mm

Parts Q’ty Thickness


1 Side panel (left) 1 0.8

5 2 Side panel (right)


3 Top cover
1
1
0.8
0.8
4 Rear cover 1 0.8
5 Unit rear corner panel 2 0.8
Tapping screw (4mm x 12mm) 40 -

6
787
3 744 247
5
1 2
233

7
983
954

5
699

8
174

4
13

765 489

9 2-80

5GEKPFF 
Design of 3WAY SYSTEM

8. Supplement

Installation of Snow-Proof Vents (air intake duct) 1

The parts shown below are locally procured parts.


The number of pieces shown below indicates the number of installed quantity on one sideways of the unit.
(Obtain necessary number of pieces.)
Choose the parts free from rust or rustless material in order to prevent rust and salt-air damage resistance.
First install the air discharge chamber (field supply) and then install this snow-proof vents (air intake duct).
When setting up a multiple-unit installation, Kit for multiple-unit (field supply) is required.

Side panel (left) Top cover


Parts Q’ty
Unit rear corner panel
Side panel (right) Side panel (left) 1
Side panel (right) 1
Top cover 1
Rear cover 1

Unit rear corner panel


Unit rear corner panel 2 1
Tapping screw (4mm x 12mm) 40

Rear cover
NOTE 2
Install the air discharge chamber where there is well enough for ventilation even if a strong wind is blowing.

Tightening Screws
The screws for fixing parts indicate by number as shown in the chart.
Tighten with the tapping screws (4mm x 12mm) for the number 1 . 3
Remove the screw C tightened to the unit. It is available for reuse.

How to Install Snow-Proof Vents (air intake duct) Air-discharge chamber


To accomplish the parts assembly, follow the steps below. 4
If the parts assembly is performed in a different way,
installation will not successfully complete.

1. How to Install the Snow-Proof Vents (air intake duct) E


First install the air-discharge chamber (field supply) 1 ×6
1×3
5
and follow the steps below.
Regarding the air-discharge chamber installation, D
Unit rear 1×3
follow the steps described separately. corner panels
2. Side Panel Attachment (Left & Right)
Attach the side panels (left/right) to the corner post on the 6
side of the unit.
Attach the side panel (left) to the left post and the
1×6
side panel (right) to the right post respectively.
When installing, tighten the foremost upside screw Side panel (right)
temporarily. (See detail chart D, E.)
Side panel (left) 7
Attach the side panel likely to hook to that screw and Firstly tighten
then tighten each panel with 2 other screws screw temporarily
(total 3 screws) securely.
Firstly tighten
screw temporarily 8

Detail view D Detail view E


Fig. 8-17
2-81 9

5GEKPFF 
Design of 3WAY SYSTEM

8. Supplement

3. Unit Rear Corner Panel Attachment

Attach the unit rear corner panel vertically to one side


of the corner post on the rear of the unit.
Make sure the side surface of the packing pasted to the
unit rear corner panel is facing toward the unit to protect
against vibration. Firstly tighten
The number of screws for each part is 6 pieces. screws
See Fig. 8-17 on previous page. temporarily

4. Rear Cover Attachment

Attach the rear cover to the top of both side panels as


described in step 2 above.
When installing, tighten the second upside screws on 1 ×8
1 both side temporarily.
Attach the rear cover likely to hook to that screw and Rear cover
then tighten with 6 other screws (total 8 screws) securely.
See Fig. 8-18. Side panel (left)

2 5. Top Cover Attachment Fig. 8-18

Attach the top cover to upside the rear cover as


described in step 3 above and tighten with 12 screws.
See Fig. 8-19.

3 6. Opposite Side Attachment


Top cover

When installing the snow-proof vents (air intake duct)


and unit rear corner panel to the opposite side of the unit,
1 × 12
follow steps 2 - 5 described above.
4

5
Rear cover

Fig. 8-19

9 2-82

5GEKPFF 
Design of 3WAY SYSTEM

8. Supplement

Reference Diagram for Side Panel (Left) (field supply) : 1107-331

RMK PART NAME Q’ty


1 COV SIDE L 779 1

23 (O.D.)
2 PL MTG 359 1
unit: mm

10
31.2
(4) 338.5

(7.8)
13
125×3 = 375
1
(400)

.4)
(519
(922
.8)
Unite with dowels 2
(12)

(fiducial point)
1 2

Fig. 8-20

Reference Diagram for Side Panel (Left) (field supply) : COV SIDE L 779
3
0.

unit: mm
(3.6)

9
26.8
3

6 6
1. 1.
)
(2.3

1.6 1.6
4
2.1
1.6

11.2 (I.D.) Detail view A Detail view B Detail view C

180.3
3
R

C
E
15

2-Ø
8
R

5
233

6h (60°)
ole
s 3-Ø3.3 protrusion holes
B (reverse side)
(140

D 22 (O.D.)
.1°)

171
2-Ø vers
(re

129
4d es

6
922.8
ow ide

171
els )
699

5-

129

°
Ø
707.3
703.7

.9
3.

(57. 69
3 (rev

8)
pr e

171

10.9
ot rs
(103)

ru e s
sio id

300
n e)

View E
7
ho
le
197.2
(6

171
s
9.9
13

°)

View D
11.2
1.6

A 1.6
(281.7) 66.4 22
8 (O.D.)

517.2
519.4
22.2 32 (O.D.)
8

NOTE : The contour of bevel except for specific indications shall be C5. Fig. 8-21

2-83 9

5GEKPFF 
Design of 3WAY SYSTEM

8. Supplement

Reference Diagram for Side Panel (Left) (field supply) : PL MTG 359

unit: mm

s
le
ho
el
w
do
1
4.
Ø
2-

300
400
1

Fig. 8-22
24.8 (O.D.) 10 (O.D.)
3
NOTE : The contour of bevel except for specific indications shall be C5.

9 2-84

5GEKPFF 
Design of 3WAY SYSTEM

8. Supplement

Reference Diagram for Side Panel (Right) (field supply) : 1108-337

RMK PART NAME Q’ty


1 COV SIDE R 501 1
2 PL MTG 359* 1

23(O.D.)
* Same as Fig. 8-22
unit: mm

10
31.2
(4)

(12)
Unite with dowels (fiducial point)

.8)
(922

(519
125×3 = 375

.4)
(400)

2
13
(7.8)

1 2 338.5
Fig. 8-23

Reference Diagram for Side Panel (Right) (field supply) : COV SIDE R 501
3
(1 unit: mm
1. .6
6 )
3-

)
26.8

(1.6 22 (O.D.)
Ø
3. reve
3
(
(3.6)

pr rse

1.6
3

4
ot s
1.6
2.1

129
ru id

1.6
sio e)
n

Detail view A Detail view B Detail view C


ho
le

129
s

180.3
B
10.9

E
R3

(60°)
5
15

View E
R8
.1°)

233

C
s

D
(140

e) ole
171

sid n h
5-Ø (rev

rs sio
3.3 ers

ve tru

6
922.8

2-
(re pro
pro e sid

Ø
171

6
Ø4
tru

ho
707.3
703.7

2-
sio )

le
s

69
nh

.9° 8)
e

(57.
o
171

(103)
les

699

300
7
197.2
171

°)
9.9
1.6

(6

A
9.6

22 1.6
66.4 (281.7)
32 22.2
517.2
8
13

519.4 11.2 (I.D.)


8

View D

NOTE : The contour of bevel except for specific indications shall be C5. Fig. 8-24
2-85 9

5GEKPFF 
Design of 3WAY SYSTEM

8. Supplement

Reference Diagram for Top Cover (field supply) : 1106-356H0

RMK PART NAME Q’ty unit: mm


1 Top cover (1106-356) 1
2 Packing 643 1
Match the edge of Part No.1 and paste Part No.2

Be aware that Part No.2 does not protrude from Part No.1.
1 (5) (5)

Stick the packing to Part No.2 in order to


2 match the apex of the beveling "C5".
Match the edge of Part No.1

View A
Fig. 8-25
3 Reference Diagram for Top Cover (field supply) : 1106-356
RMK PART NAME Q’ty unit: mm
1 COV TOP 493 1
2 PL MTG 360 1

Unite with dowels (fiducial point) 17.3


C
5 L
1
142.8 (O.D.)

2
132.8
(24.8)

(6)

6
161.2 (O.D.)

(17.5) 125×5 = 625 (17.5) (10)


142

(39.8) (660) (39.8) 16


7 739.5

Fig. 8-26

9 2-86

5GEKPFF 
Design of 3WAY SYSTEM

8. Supplement

Reference Diagram for Top Cover (field supply) : COV TOP 493

unit: mm

739.5
698.7
6-Ø6 holes 200 200 17.3 (O.D.)

161.2 (O.D.) 142.8 (O.D.)


132.8
°)

129
(60
Drooped side

129

142

(140
ls
we )
do side

.1°)
4 e
2-Ø vers
(re A 16 1
13.6

6-Ø
6h
140 140 140 ole
s
698.7

View A
2
NOTE : The contour of bevel except for specific indications shall be C5.
Fig. 8-27
Reference Diagram for Top Cover (field supply) : PL MTG 360

unit: mm
3
2-
Ø

4
4.
1
do
w
el
h
ol
es
660
400

24.8 (O.D.) 10 (O.D.)


6
(Similar to opposite side)

NOTE : The contour of bevel except for specific indications shall be C5.
Fig. 8-28
Reference Diagram for Top Cover (field supply) : Packing 643
(Material : polyethylene foam)
7
Adhesive layer
3

unit: mm

730
8
15

Fig. 8-29
Note : See Fig. 8-25 for the paste area.
2-87 9

5GEKPFF 
Design of 3WAY SYSTEM

8. Supplement

Reference Diagram for Rear Cover (field supply) : 1109-322

RMK PART NAME Q’ty unit: mm


1 COV REAR 485 1
2 PL MTG 360* 2
* Same as Fig. 8-28

(15)
352.9
Unite with dowels
(fiducial point)
2

1 (6) 1

(708.6)
(17.5) 125×5 = 625 (17.5)

171
(6) 2

2 (17.5) 125×5 = 625 (17.5)


(42.2) (660) (42.2)

Unite with dowels


3 (fiducial point)
(744.3) Fig. 8-30

Reference Diagram for Rear Cover (field supply) : COV REAR 485

les unit: mm
4 744.3
r
ion
us e)
ho
t
698.7 pro sid
Ø 3.3 verse
400 -
4 (re
140 140 140 15 (O.D.)
8-Ø6 holes

5
171

3
2-R
4
(re -Ø4
15

ve do
2-R

171

rs w
708.6 (O.D.)

e el
6
8

si s
de
707

)
171

7
171
13.7
8 (O.D.)

Drooped side

8 (Similar to opposite side)

672.7

Fig. 8-31
NOTE : The contour of bevel except for specific indications shall be C5.

9 2-88

5GEKPFF 
Design of 3WAY SYSTEM

8. Supplement

Reference Diagram for Unit Rear Corner Panel (field supply) : 1117-087H0

RMK PART NAME Q’ty Match edges of Part No.2 unit: mm


1 Unit Rear Corner Panel (1117-087) 1 to the dowels.
2 Packing 642 4
Match the edge of Part No.1 and paste Part No.2 (4 pieces)
Be aware that Part No.2 does not protrude from Part No.1.

Match the edge of Part No.1 and paste Part No.2

2
1 2

Paste the packing to the Convex side dowel


Match the edge of Part No.1
and paste Part No.2 1
concave side dowel.

Match edges of Part No.2 Fig. 8-32


to the dowels.

3
Reference Diagram for Unit Rear Corner Panel (field supply) : 1117-087
unit: mm
600
4
291 291 0.8
68
56
32

5
6-Ø

4-Ø

247.5 247.5
4d
6
hole

ow
els

Fig. 8-33
s

NOTE : The contour of bevel except for specific indications shall be C3.
6
Reference Diagram for Unit Rear Corner Panel (field supply) : Packing 642
(Material : polyethylene foam) unit: mm

200 7
15

8
2

Adhesive layer
Fig. 8-34

2-89 9

5GEKPFF 
Design of 3WAY SYSTEM

8. Supplement

Snow-Proof Vents (Air Intake duct) 2 (field supply)


Reference Diagram for Snow-Proof Vents (air intake duct)
Model : U-8MF2E8, 10MF2E8, 12MF2E8, 14MF2E8, 16MF2E8
unit: mm
853 Air direction: Front direction 853 Air direction: Rear direction
Snow-Proof Vents
(air intake duct) 2
744

744
Top view Top view
112

978 930
933 930
1 35 34
34 35
Snow-Proof Vents
(698)

(air intake duct) 2

489 489 489


489
2
2352

600
1654
1338

1338
600
529
529
355

3
355

121

1979 1419
Front view Right side view Front view Right side view

Necessary Assembling Parts


4 unit: mm

Parts Q’ty Thickness


1 Side panel (left) 1 0.8
2 Side panel (right) 1 0.8
5 3 Top cover 1 0.8
4 Rear cover 1 0.8
Tapping screw (4mm x 12mm) 28 -

896
6 3 853 247
233

7
983
954
699

8
174

1 4
13

2 874
489

9 2-90

5GEKPFF 
Design of 3WAY SYSTEM

8. Supplement

Installation of Snow-Proof Vents (air intake duct) 2

The parts shown below are locally procured parts.


The number of pieces shown below indicates the quantity per 1 set.
Choose the parts free from rust or rustless material in order to prevent rust and salt-air damage resistance.
First install the air discharge chamber (field supply) and then install this snow-proof vents
(air intake duct).
When setting up a multiple-unit installation, Kit for multiple-unit (field supply) is required.

Top cover
Side panel (left) Side panel (right) Parts Q’ty
Side panel (left) 1
Side panel (right) 1
Top cover 1
Rear cover 1
Tapping screw (4mm x 12mm) 28 1

Rear cover
NOTE 2
Install the air discharge chamber where there is well enough for ventilation even if a strong wind is blowing.

Tightening Screws
The screws for fixing parts indicate by number as Air-discharge chamber
shown in the chart. 3
Tighten with the tapping screws (4mm x 12mm)
for the number 1 .
Remove the screw C tightened to the unit.
It is available for reuse. A
4
How to Install Snow-Proof Vents (air intake duct)
1
To accomplish the parts assembly, follow the steps
B
below.
If the parts assembly is performed in a different way,
installation will not successfully complete. 5
1. How to Install the Snow-Proof Vents (air intake duct)
First install the air discharge chamber (field supply)
and follow the steps below. Side panel (left)
Regarding the air-discharge chamber installation,
follow the steps described separately.
Side panel (right)
6
Firstly tighten
2. Side Panel Attachment (Left & Right)
Firstly tighten screw temporarily
Attach the side panels (left/right) to the corner post screw temporarily
on the side of the unit.
Attach the side panel (left) to the left post and the 7
side panel (right) to the right post respectively.
When installing, tighten the foremost upside screw
temporarily. (See detail chart A, B.)
Attach the side panel likely to hook to that screw and
then tighten each panel with 2 other screws
(total 3 screws) securely. Detail view A Detail view B 8
Fig. 8-35

2-91 9

5GEKPFF 
Design of 3WAY SYSTEM

8. Supplement

3. Rear Cover Attachment

Attach the rear cover to the top of both side panels as


described in step 2.
When installing, tighten the second upside screws on
both sides temporarily. Firstly tighten
Attach the rear cover likely to hook to that screw and screws
then tighten with 6 other screws (total 8 screws) temporarily
securely. See Fig. 8-36.

1×8
Rear cover
1 Side panel (right)
Fig. 8-36

4. Top Cover Attachment

Attach the top cover to upside the rear cover as described


in step 3 above and tighten with 12 screws securely.
2 See Fig. 8-37.

Top cover

3
1 × 12

Rear cover
4
Fig. 8-37

9 2-92

5GEKPFF 
Design of 3WAY SYSTEM

8. Supplement

Reference Diagram for Side Panel (Left) (field supply) : 1107-331

RMK PART NAME Q’ty


1 COV SIDE L 779* 1
2 PL MTG 359* 1

The parts are the same as Figure 8-20.

Reference Diagram for Side Panel (Right) (field supply) : 1108-337

RMK PART NAME Q’ty


1 COV SIDE R 501* 1
2 PL MTG 359* 1

The parts are the same as Figure 8-23.

Reference Diagram for Top Cover (field supply) : 1106-355H0


RMK PART NAME Q’ty
unit: mm
1
1 Top cover (1106-355) 1
2 Packing 645 1 A
Match the edge of Part No.1 and paste Part No.2
2
1 2

3
Be aware that Part No.2 does not protrude from Part No.1.
(5) (5)

Stick the packing to Part No.2 in order 4


to match the apex of the beveling "C5".

Match the edge of Part No.1


Fig. 8-38
View A
5
Reference Diagram for Top Cover (field Supply) : 1106-355 unit: mm
RMK PART NAME Q’ty
1 COV TOP 495 1
2 PL MTG 362 1

C
L Unite with dowels (fiducial point) 16.9 6
142.8 (O.D.)

2
132.8

(7)
1
(24.8)

7
161.2 (O.D.)

125×6 = 750 (10)


142

(39.2) (770) (39.2) 16 (O.D.)


8
848.4

Fig. 8-39

2-93 9

5GEKPFF 
Design of 3WAY SYSTEM

8. Supplement

Reference Diagram for Top Cover (field supply) : COV TOP 495
unit: mm
6-Ø6 holes
848.4
Drooped side
807.6
600
16.9 (O.D.)
161.2 (O.D.) 142.8 (O.D.)
132.1

129
(60
°)

129
142
°)
0.1
(14

16
A 2-Ø4 dowels (reverse side)
1
6-Ø6 holes

13.6
160.8 162 162 162 160.8
2 View A

NOTE : The contour of bevel except for specific indications shall be C5. Fig. 8-40

Reference Diagram for Top Cover (field supply) : PL MTG 362


3 unit: mm
s
le
ho
el
w

4
do
1
4.
Ø
2-

600
770

6
24.8 (O.D.) 10 (O.D.)
(Similar to opposite side)
NOTE : The contour of bevel except for specific indications shall be C5. Fig. 8-41
Reference Diagram for Top Cover (field supply) : Packing 645
7 (Material : polyethylene foam)
Adhesive layer
3

unit: mm

838
8
15

Fig. 8-42
Note : See Fig. 8-38 for the paste area.
9 2-94

5GEKPFF 
Design of 3WAY SYSTEM

8. Supplement

Reference Diagram for Rear Cover (field supply) : 1109-324

(15 (O.D.))
RMK PART NAME Q’ty unit: mm
1 COV REAR 487 1
2 PL MTG 362* 3
* Same as Fig. 8-41

C Unite with dowels


L
(fiducial point)

181.9
(7)

1 125×6 = 750

171
Unite with dowels
(7)

(708.6 (O.D.))
(fiducial point)

125×6 = 750
1
2

171
(7)

125×6 = 750
(41.6) (770) (41.6) 2
Unite with dowels
(853.2 (O.D.)) (fiducial point)

Fig. 8-43 3
Reference Diagram for Rear Cover (field supply) : COV REAR 486
unit: mm
4-Ø3.3 protrusion holes
(reverse side)
853.2 (O.D.)
600 15 (O.D.) 4
160.8 162 162 162 160.8

CL Drooped side

2-Ø6 holes
5
171
2-
R
3

15
8
2-R

171
708.6 (O.D.)

6
6-Ø6 holes
171

6-Ø
(re 4 d
ve ow 7
171

rse el
sid s
e)
13.7

(Similar to opposite side)


8 (O.D.)

8
781.6

NOTE : The contour of bevel except for specific indications shall be C5. Fig. 8-44
2-95 9

5GEKPFF 
Design of 3WAY SYSTEM

8. Supplement

7. Supplemental Installation Kit for Multiple-Unit (field supply)

This part is the Supplemental Installation Kit for multiple-unit installation.


In order to attach this part, the unit must have been installed within the range as shown in the below chart.
The parts shown below are locally procured parts.
The number of pieces shown below indicates the quantity per 1 set. (Obtain necessary number of pieces.)
Choose the parts free from rust or rustless material in order to prevent rust and salt-air damage resistance.
First install the air discharge chamber (field supply) and then install the snow-proof vents
(air intake duct : field supply).
Installed outdoor unit unit: mm
Corner post pitch : 180
10 10 Air discharge chamber

Snow-proof vents
1 4 3
930

(air intake duct) 2

Anchor bolt pitch : 210 10


Front side
6 2
Tightening Screws
2
The screws for fixing parts indicate by number as
5
shown in the chart.
1
Tighten with the tapping screws (4mm x 12mm)
for the number 1 .
3 Remove the screw D tightened to the snow-proof
vents (air intake duct). It is available for reuse.
Parts
1 Rear Panel (Lower)
Q’ty Thickness
1 0.8
2 Rear Panel (Upper) 1 0.8
How to Install Installation Kit for Multiple-Unit 3 Topside Panel (Left) 1 0.8
4 Topside Panel (Right) 1 0.8
The installation work must be carried out with a partner
5 Frame 2 0.8
4 for safety. To accomplish the parts assembly, follow the
steps below. If the parts assembly is performed in a 6 Front Panel 2 0.8
Tapping screw (4mm x 12mm) 35 -
different way, installation will not successfully complete.
Washer (Screw for 4mm) 19 -

1. Topside Panel (Right) Attachment


5 Attach the topside panel (right) to the corner posts
(2 locations) at the right side between the units. Snow-proof vents (air intake duct) 1
The installed direction of this part is shown in the
chart. Air discharge chamber
When installing, tighten the screw temporarily to the Topside Panel (Right)
corner post on the rear of right side unit (position as
6 in the chart) and insert the topside panel (right) Firstly tighten
between the units. screw temporarily
Attach the topside panel (right) likely to hook to that
1
screw and tighten with the screws to the corner post
of the front side of the unit. Snow-proof vents
(air intake duct) 2
7
Corner post
Topside Panel (Right)

8 1

Enlarged view (front side)


Fig. 8-45
9 2-96

5GEKPFF 
Design of 3WAY SYSTEM

8. Supplement

2. Topside Panel (Left) Attachment


Follow the same procedure as described in step 1 above for attaching topside panel (left).
Attach the topside panel (left) to the corner posts (2 locations) at the left side between the units.
The installed direction of this part is shown in the below chart.
When installing, tighten the screw temporarily to corner post on the rear of left side unit (position as in the below
chart) and insert the topside panel (left) between the units.
Attach the topside panel (left) likely to hook to that screw and tighten with the screws to the corner post of the
front side of the unit.
Topside Panel (Left)
Firstly tighten
screw temporarily
Topside Panel (right)
Topside Panel (Left)

1
Topside Panel (right)
Joint view
Sectioned drawing

Fig. 8-46
2
3. Frame Attachment Left side corner post
Attach the frame to the left and right units respectively.
The installation position is located at the front side corner Right side corner post
post between the units and topside panels (right/left) Topside Panel (right)
Topside Panel (Left)
as described in steps 1 and 2 above.
The frame installed direction should be located so that the Frame
3
notches at the center of the part can face each other. 1
Tighten the corner post to the unit with 4 screws respectively.
Tighten the topside panels (right/left) with 1 screw respectively. 1

Notch
4
1 ×4

1 ×4 Fig. 8-47
Front view
5
4. Front Panel Attachment
Tighten the front panel to the frame (right/left) with 8 screws
respectively as described in step 3 above.
Frame
Attach the front panel vertically.
The installed direction of this part is that the louver inside
6
the front panel is facing outward and the air inlet/outlet port
is facing downward. 1 ×8
Also adjust until the front panel will be positioned at the
center of between the units. Front Panel
7

1 ×8
8
Front view
Fig. 8-48

2-97 9

5GEKPFF 
Design of 3WAY SYSTEM

8. Supplement

5. Rear Panel (Lower) Attachment


Attach the rear panel (lower) to the rear cover of snow-proof vents (air intake duct) which has already been
installed from upside. (See figure 8-49.)
Remove 4 screws respectively on the side between the units attached to the rear cover (left side unit & right
side unit) of snow-proof vents (air intake duct).
Attach the washer to the screw once it was removed.
Using the screw with a washer, attach the rear panel (lower) between the left and right rear covers of
snow-proof vents (air intake duct) and then tighten the rear panel with 8 screws with washers.

6. Rear Panel (Upper) Attachment


Attach the rear panel (upper) to the top cover of snow-proof vents (air intake duct) which has already been
installed from upside. (See figure 8-49.)
Remove 3 screws respectively on the side between the units attached to the top cover (left side unit & right
side unit) of the snow-proof vents (air intake duct).
Attach the washer to the screw once it was removed.
1 Using the screw with a washer, attach the rear panel (upper) between the left and right top covers of
snow-proof vents (air intake duct) and tighten the rear panel with 6 screws.
Using the screw with a washer, tighten the rear panel (upper) with 1 screw respectively to the topside panels
(right/left) as described in steps 1 and 2 above.
Also using 1 screw with a washer, tighten the rear panel (lower) as described in step 5 above.
2
Rear Panel (Upper)
Washer 1
x6 Washer
1
D Washer
3 Top cover
Topside Panel
(Left)
(snow-proof vents) Topside Panel
Rear Panel (Upper) (Right)

4 Top cover
(snow-proof vents)

Rear cover
(snow-proof vents)

1 D
5 Washer
x8

Washer
D
Top cover
(snow-proof vents)
Rear Panel (Lower)
6 Top cover Enlarged view
Rear Panel (Lower) (snow-proof vents) (rear side)
D
Rear cover
(snow-proof vents) Fig. 8-49

9 2-98

5GEKPFF 
Design of 3WAY SYSTEM

8. Supplement

Reference Diagram for Rear Panel (Lower) (field supply) : 2342-950


430 unit: mm
355

14.6
CL

Ø3
.1 h
ole

149
6-R
6

171
675

1
171
171

2
2-37x12 long holes 380

NOTE : The contour of bevel except for specific indications shall be C5. Fig. 8-50
3
Reference Diagram for Rear Panel (Upper) (field supply) : 2342-951
unit: mm
37x12

17
335 long hole
A 41.7

6-37x12 4
long holes
View A
.1°)
(140
142.2 (O.D.)
192
140.5

90°
5
129

2-37x12
18

long holes 100


124
140.9 (O.D.)

View B
140.5
129

6
176.4

(150
°)

206.4
371.4
B
20.5 (O.D.)
7
425

8
NOTE : The contour of bevel except for specific indications shall be C5.
Fig. 8-51

2-99 9

5GEKPFF 
Design of 3WAY SYSTEM

8. Supplement

Reference Diagram for Topside Panel (Right) (field supply) : 1136-356


unit: mm

(135°)

82.5 (O.D.)
868.1
30.3

1.6

836.2

42.5
40

113.3
80.9 (O.D.)

h ole

10
.1

829.2
Ø3

830.8 (O.D.)
860.8
875

1 829.2 (O.D.)

35.8 (I.D.)
805 12.9 9.2 (O.D.)

15 (O.D.)
1.6 1.6

17.2
2-
R3

8.6
2

19.3
le
ho
.1
Ø3
NOTE : The contour of bevel except for specific indications shall be C5. Fig. 8-52

Reference Diagram for Topside Panel (Left) (field supply) : 1136-357


3 unit: mm

(135°)
868.1

30.3
1.6
42.5

836.2

4 hole
40
80.9
Ø3.1
10
82.5 (O.D.)

830.8 (O.D.)
860.8
875
5
829.2
12.9 805
9.2 (O.D.)
15 (O.D.)

1.6
35.8

1.6
3
R
2-

6
8.6

17.2

13
19.3 (O.D.)
Ø3
.1
ho
le

7 NOTE : The contour of bevel except for specific indications shall be C5. Fig. 8-53

9 2-100

5GEKPFF 
Design of 3WAY SYSTEM

8. Supplement

Reference Diagram for Front Panel (field supply) : 2342-952


unit: mm

20 (O.D.)

41.3 (O.D.)
110 8-21×6 long holes

29.3
CL
A

(41.3)
B
139

(19) 20 5 20 5 20 5 20 5 20
120
475.8 (O.D.)

(120)
1

19
139

120
19
139

120
2
A
81
131.2
160 View A-A Detail view B
Fig. 8-54
3
NOTE : The contour of bevel except for specific indications shall be C5.

Reference Diagram for Frame (field supply) : 1136-358


unit: mm

A
4-Ø6 holes 4
CL 26.4 (O.D.)

41.2
(13
5°)

14.8 (O.D.)
6.8

296 296 296


947 5

933
6
139 139 139 59 139 139 139
27.3
12.3

10
10

7
8-Ø3.1 holes View A 2-Ø6 holes

NOTE : The contour of bevel except for specific indications shall be C5. Fig. 8-55

2-101 9

5GEKPFF 
– MEMO –

2-102

5GEKPFF 
Control of 3WAY SYSTEM

Contents

3. Control of 3WAY SYSTEM


1. Main Operating Functions
2. Wireless Remote Controller
3. Timer Remote Controller (CZ-RTC2)
4. Simplified Remote Controller (CZ-RE2C2, CZ-RELC2)
5. System Controller (CZ-64ESMC2)
6. Schedule Timer (CZ-ESWC2)
7. ON/OFF Controller (CZ-ANC2)
8. Intelligent Controller (CZ-256ESMC2)
9. Communication Adaptor (CZ-CFUNC2)
10. Remote Sensor (CZ-CSRC2)
11. LonWorks Interface (CZ-CLNC2)
12. Seri-Para I/O unit for outdoor unit (CZ-CAPDC2)
13. MINI Seri-para I/O Unit (CZ-CAPBC2)
1
14. Local Adaptor for ON/OFF Controller (CZ-CAPC2)
15. Web Interface (CZ-CWEBC2)
16. Intelligent Management System
* Refer to the 2WAY SYSTEM TECHNICAL DATA (TD831159) 2

3-1 9

TD831170-00_3WAY.indb 1 2012/10/15 12:45:43


– MEMO –

3-2

TD831170-00_3WAY.indb 2 2012/10/15 12:45:43


3WAY SYSTEM Unit Specifications

Contents

4. 3WAY SYSTEM UNIT SPECIFICATIONS


1. Outdoor Unit .......................................................................................................................4-2
1-1. Specifications ...............................................................................................................4-2
• Standard Combination..................................................................................................4-2
• High Efficiency Combination ........................................................................................4-9
1-2. Dimensional Data .......................................................................................................4-11
1-3. Multiple Unit Installation Example ..............................................................................4-13
1-4. Refrigerant Flow Diagram...........................................................................................4-14
1-5. Noise Criterion Curves ...............................................................................................4-17
2. Indoor Unit
* Refer to the 2WAY SYSTEM TECHNICAL DATA (TD831159)
1

4-1 9

5GEKPFF 
:$<6<67(08QLW6SHFL¿FDWLRQV

1. Outdoor Unit

1-1. Specifications
Standard Combination
Unit Specifications (1)
Model Name 3WAY System Outdoor Unit
Horsepower 8 10 12

Model No. U-8MF2E8 U-10MF2E8 U-12MF2E8

ø Hz 3ø 50Hz 3ø 50Hz 3ø 50Hz


Power Supply
V 380 400 415 380 400 415 380 400 415
kW 22.4 22.4 22.4 28.0 28.0 28.0 33.5 33.5 33.5
Capacity
BTU/h 76500 76500 76500 95600 95600 95600 114300 114300 114300
Current A 8.60 8.17 7.96 11.3 10.8 10.6 15.1 14.5 14.1
Cooling

Power Input kW 4.98 4.98 4.98 6.83 6.83 6.83 9.05 9.05 9.05
EER — 4.50 4.50 4.50 4.10 4.10 4.10 3.70 3.70 3.70
1 Power Factor
Pressure Level
%
dB-A
88 88 87
57.0 (Quiet mode: 54.0)
92 91 90
59.0 (Quiet mode: 56.0)
91 90 89
60.0 (Quiet mode: 58.0)
Operation Sound
Power Level dB-A 71.5 (Quiet mode: 68.5) 73.5 (Quiet mode: 70.5) 75.5 (Quiet mode: 72.5)
kW 25.0 25.0 25.0 31.5 31.5 31.5 37.5 37.5 37.5
Capacity
BTU/h 85300 85300 85300 107500 107500 107500 128000 128000 128000
Heating

2 Current
Power Input
A
kW
8.95
5.24
8.50
5.24
8.28
5.24
11.6
6.92
11.0
6.92
10.7
6.92
14.7
8.72
14.1
8.72
13.8
8.72
COP — 4.77 4.77 4.77 4.55 4.55 4.55 4.30 4.30 4.30
Power Factor % 89 89 88 91 91 90 90 89 88
MAX Current A 12.6 12.6 12.6 16.3 16.3 16.3 21.2 21.2 21.2
MAX Power Input kW 7.40 7.80 8.00 9.80 10.3 10.6 12.8 13.3 13.7
3 Starting Current A 1 1 1 1 1 1 74 77 80
Comp Motor output kW 4.2 6.0 3.0+4.5
Fan Motor output (No. of poles) kW 0.75 (8P) 0.75 (8P) 0.75 (8P)
External static pressure Pa 80 80 80
Air flow m3/min 158 178 212
4 Refrigerant amount at shipment kg R410A 8.3 R410A 8.5 R410A 8.8
Height mm (inch) 1758 (69-7/32) 1758 (69-7/32) 1758 (69-7/32)
Unit Dimensions Width mm (inch) 1000 (39-3/8) 1000 (39-3/8) 1000 (39-3/8)
Depth mm (inch) 930 (36-39/64) 930 (36-39/64) 930 (36-39/64)
Net weight kg (lbs.) 269 (593) 269 (593) 314 (692)
5 Color
(Approximate value)
Color (Munsell code)
RAL code
Ivory (2.6Y7.6/1.1)
7044
Ivory (2.6Y7.6/1.1)
7044
Ivory (2.6Y7.6/1.1)
7044
Cooling DBT -10°C ~ 46°C -10°C ~ 46°C -10°C ~ 46°C
Operation
Heating WBT -20°C ~ 18°C -20°C ~ 18°C -20°C ~ 18°C
Condition
Cooling & Heating DBT -10°C ~ 24°C -10°C ~ 24°C -10°C ~ 24°C

6 Liquid
Discharge
mm (inch)
mm (inch)
9.52 (3/8)
15.88 (5/8)
9.52 (3/8)
19.05 (3/4)
12.7 (1/2)
19.05 (3/4)
Piping *1
Suction mm (inch) 19.05 (3/4) 22.22 (7/8) 25.4 (1)
Balance mm (inch) 6.35 (1/4) 6.35 (1/4) 6.35 (1/4)
Refrigeration Type FV68S (Ether oil) FV68S (Ether oil) FV68S (Ether oil)
Compressor oil Charge amount L 1.6+3 1.6+3 1.6+1.7+3
7 Crankcase heater W 28 28 28+31

Connection Piping
Connection Piping
Primary Accessories None (ø19.05, ø15.88)
(ø19.05, ø15.88)
(ø12.7, ø9.52)

8 *1 Main Pipe Diameter size-up apply to O.D. to first branch pipe


DATA SUBJECT TO CHANGE WITHOUT NOTICE.

* Performance and electrical characteristics values are based on JIS B8616(EN14511 is only applicable to temperature conditions.) package A/C.
(Cooling : Indoor intake air temp. 27°C DB or 19°C WB. Outdoor intake air temp. 35°C DB.)
(Heating : Indoor intake air temp. 20°C DB. Outdoor intake air temp. 7°C DB or 6°C WB.)

9 4-2

5GEKPFF 
:$<6<67(08QLW6SHFL¿FDWLRQV

1. Outdoor Unit

1-1. Specifications
Standard Combination
Unit Specifications (2)
Model Name 3WAY System Outdoor Unit
Horsepower 14 16 18

U-10MF2E8
Model No. U-14MF2E8 U-16MF2E8
U-8MF2E8

ø Hz 3ø 50Hz 3ø 50Hz 3ø 50Hz


Power Supply
V 380 400 415 380 400 415 380 400 415
kW 40.0 40.0 40.0 45.0 45.0 45.0 50.4 50.4 50.4
Capacity
BTU/h 136500 136500 136500 153600 153600 153600 172000 172000 172000
Current A 19.2 18.4 17.9 22.0 21.1 20.6 19.7 18.9 18.4
Cooling

Power Input kW 11.6 11.6 11.6 13.3 13.3 13.3 11.8 11.8 11.8
EER — 3.45 3.45 3.45 3.38 3.38 3.38 4.27 4.27 4.27
Power Factor
Pressure Level
%
dB-A
92 91
62.0 (Quiet mode: 59.0)
90 92 91
62.0 (Quiet mode: 59.0)
90 91 90
61.0 (Quiet mode: 58.0)
89 1
Operation Sound
Power Level dB-A 76.5 (Quiet mode: 73.5) 76.5 (Quiet mode: 73.5) 75.5 (Quiet mode: 72.5)
kW 45.0 45.0 45.0 50.0 50.0 50.0 56.5 56.5 56.5
Capacity
BTU/h 153600 153600 153600 170600 170600 170600 192800 192800 192800
Heating

Current
Power Input
A
kW
17.0
10.2
16.4
10.2
15.9
10.2
20.7
12.4
19.9
12.4
19.4
12.4
20.4
12.2
19.6
12.2
19.1
12.2
2
COP — 4.41 4.41 4.41 4.03 4.03 4.03 4.63 4.63 4.63
Power Factor % 91 90 89 91 90 89 91 90 89
MAX Current A 25.7 25.7 25.7 29.3 29.3 29.3 28.9 28.9 28.9
MAX Power Input kW 15.6 16.2 16.7 17.8 18.5 19.0 17.2 18.1 18.6
Starting Current A 74 77 80 78 81 85 1 1 1 3
Comp Motor output kW 4.8+4.5 5.7+5.2 4.2+6.0
Fan Motor output (No. of poles) kW 0.75 (8P) 0.75 (8P) 0.75 (8P)×2
External static pressure Pa 80 80 80
Air flow m3/min 212 212 336
Refrigerant amount at shipment kg R410A 9.3 R410A 9.3 R410A 17 4
Height mm (inch) 1758 (69-7/32) 1758 (69-7/32) 1758 (69-7/32)
Unit Dimensions Width mm (inch) 1000 (39-3/8) 1000 (39-3/8) 2060 (81-7/64)
Depth mm (inch) 930 (36-39/64) 930 (36-39/64) 930 (36-39/64)
Net weight kg (lbs.) 322 (710) 322 (710) 538 (1186)
Color
(Approximate value)
Color (Munsell code)
RAL code
Ivory (2.6Y7.6/1.1)
7044
Ivory (2.6Y7.6/1.1)
7044
Ivory (2.6Y7.6/1.1)
7044
5
Cooling DBT -10°C ~ 46°C -10°C ~ 46°C -10°C ~ 46°C
Operation
Heating WBT -20°C ~ 18°C -20°C ~ 18°C -20°C ~ 18°C
Condition
Cooling & Heating DBT -10°C ~ 24°C -10°C ~ 24°C -10°C ~ 24°C
Liquid
Discharge
mm (inch)
mm (inch)
12.7 (1/2)
22.22 (7/8)
12.7 (1/2)
22.22 (7/8)
15.88 (5/8)
22.22 (7/8)
6
Piping *1
Suction mm (inch) 25.4 (1) 28.58 (1-1/8) 28.58 (1-1/8)
Balance mm (inch) 6.35 (1/4) 6.35 (1/4) 6.35 (1/4)
Refrigeration Type FV68S (Ether oil) FV68S (Ether oil) FV68S (Ether oil)
Compressor oil Charge amount L 1.6+1.7+3 1.6+1.7+3 (1.6+3)×2
Crankcase heater W 28+31 28+31 28×2 7
Connection Piping
Connection Piping Connection Piping
Primary Accessories (ø28.58, ø25.4)
(ø22.22, ø19.05) (ø19.05, ø15.88)
(ø22.22, ø19.05)

*1 Main Pipe Diameter size-up apply to O.D. to first branch pipe


DATA SUBJECT TO CHANGE WITHOUT NOTICE.
8
* Performance and electrical characteristics values are based on JIS B8616(EN14511 is only applicable to temperature conditions.) package A/C.
(Cooling : Indoor intake air temp. 27°C DB or 19°C WB. Outdoor intake air temp. 35°C DB.)
(Heating : Indoor intake air temp. 20°C DB. Outdoor intake air temp. 7°C DB or 6°C WB.)

4-3 9

5GEKPFF 
:$<6<67(08QLW6SHFL¿FDWLRQV

1. Outdoor Unit

1-1. Specifications
Standard Combination
Unit Specifications (3)
Model Name 3WAY System Outdoor Unit
Horsepower 20 22 24

U-12MF2E8 U-14MF2E8 U-16MF2E8


Model No.
U-8MF2E8 U-8MF2E8 U-8MF2E8

ø Hz 3ø 50Hz 3ø 50Hz 3ø 50Hz


Power Supply
V 380 400 415 380 400 415 380 400 415
kW 56.0 56.0 56.0 61.5 61.5 61.5 68.0 68.0 68.0
Capacity
BTU/h 191100 191100 191100 209900 209900 209900 232100 232100 232100
Current A 23.8 22.9 22.3 27.0 26.0 25.3 30.9 29.7 28.9
Cooling

Power Input kW 14.1 14.1 14.1 16.2 16.2 16.2 18.5 18.5 18.5
EER — 3.97 3.97 3.97 3.80 3.80 3.80 3.68 3.68 3.68
1 Power Factor
Pressure Level
%
dB-A
90 89 88
62.5 (Quiet mode: 59.5)
91 90 89 91
63.0 (Quiet mode: 60.0)
90 89
63.0 (Quiet mode: 60.0)
Operation Sound
Power Level dB-A 77.0 (Quiet mode: 74.0) 77.5 (Quiet mode: 74.5) 77.5 (Quiet mode: 74.5)
kW 63.0 63.0 63.0 69.0 69.0 69.0 76.5 76.5 76.5
Capacity
BTU/h 215000 215000 215000 235500 235500 235500 261100 261100 261100
Heating

2 Current
Power Input
A
kW
23.8
14.1
22.9
14.1
22.3
14.1
25.2
15.1
24.2
15.1
23.6
15.1
30.4
18.2
29.2
18.2
28.5
18.2
COP — 4.47 4.47 4.47 4.57 4.57 4.57 4.20 4.20 4.20
Power Factor % 90 89 88 91 90 89 91 90 89
MAX Current A 33.8 33.8 33.8 38.3 38.3 38.3 41.9 41.9 41.9
MAX Power Input kW 20.2 21.1 21.7 23.0 24.0 24.7 25.2 26.3 27.0
3 Starting Current A 87 90 93 87 90 93 91 94 98
Comp Motor output kW (3.1+4.5) +4.2 (4.8+4.5) +4.2 (5.7+5.2) +4.2
Fan Motor output (No. of poles) kW 0.75 (8P)×2 0.75 (8P)×2 0.75 (8P)×2
External static pressure Pa 80 80 80
Air flow m3/min 370 370 370
4 Refrigerant amount at shipment kg R410A 17 R410A 18 R410A 18
Height mm (inch) 1758 (69-7/32) 1758 (69-7/32) 1758 (69-7/32)
Unit Dimensions Width mm (inch) 2060 (81-7/64) 2060 (81-7/64) 2060 (81-7/64)
Depth mm (inch) 930 (36-39/64) 930 (36-39/64) 930 (36-39/64)
Net weight kg (lbs.) 583 (1285) 591 (1303) 591 (1303)
5 Color
(Approximate value)
Color (Munsell code)
RAL code
Ivory (2.6Y7.6/1.1)
7044
Ivory (2.6Y7.6/1.1)
7044
Ivory (2.6Y7.6/1.1)
7044
Cooling DBT -10°C ~ 46°C -10°C ~ 46°C -10°C ~ 46°C
Operation
Heating WBT -20°C ~ 18°C -20°C ~ 18°C -20°C ~ 18°C
Condition
Cooling & Heating DBT -10°C ~ 24°C -10°C ~ 24°C -10°C ~ 24°C

6 Liquid
Discharge
mm (inch)
mm (inch)
15.88 (5/8)
22.22 (7/8)
15.88 (5/8)
25.4 (1)
15.88 (5/8)
25.4 (1)
Piping *1
Suction mm (inch) 28.58 (1-1/8) 28.58 (1-1/8) 28.58 (1-1/8)
Balance mm (inch) 6.35 (1/4) 6.35 (1/4) 6.35 (1/4)
Refrigeration Type FV68S (Ether oil) FV68S (Ether oil) FV68S (Ether oil)
Compressor oil Charge amount L (1.6+1.7+3) + (1.6+3) (1.6+1.7+3) + (1.6+3) (1.6+1.7+3) + (1.6+3)
7 Crankcase heater W (28+31) +28 (28+31) +28 (28+31) +28

Connection Piping Connection Piping


Connection Piping
Primary Accessories (ø19.05, ø15.88) (ø28.58, ø25.4)
(ø22.22, ø19.05)
(ø12.7, ø9.52) (ø22.22, ø19.05)

8 *1 Main Pipe Diameter size-up apply to O.D. to first branch pipe


DATA SUBJECT TO CHANGE WITHOUT NOTICE.

* Performance and electrical characteristics values are based on JIS B8616(EN14511 is only applicable to temperature conditions.) package A/C.
(Cooling : Indoor intake air temp. 27°C DB or 19°C WB. Outdoor intake air temp. 35°C DB.)
(Heating : Indoor intake air temp. 20°C DB. Outdoor intake air temp. 7°C DB or 6°C WB.)

9 4-4

5GEKPFF 
:$<6<67(08QLW6SHFL¿FDWLRQV

1. Outdoor Unit

1-1. Specifications
Standard Combination
Unit Specifications (4)
Model Name 3WAY System Outdoor Unit
Horsepower 26 28 30

U-14MF2E8 U-14MF2E8 U-16MF2E8


Model No.
U-12MF2E8 U-14MF2E8 U-14MF2E8

ø Hz 3ø 50Hz 3ø 50Hz 3ø 50Hz


Power Supply
V 380 400 415 380 400 415 380 400 415
kW 73.0 73.0 73.0 78.5 78.5 78.5 85.0 85.0 85.0
Capacity
BTU/h 249100 249100 249100 267900 267900 267900 290100 290100 290100
Current A 33.7 32.4 31.5 37.2 35.7 34.8 41.1 39.5 38.5
Cooling

Power Input kW 20.4 20.4 20.4 22.5 22.5 22.5 24.9 24.9 24.9
EER — 3.58 3.58 3.58 3.49 3.49 3.49 3.41 3.41 3.41
Power Factor
Pressure Level
%
dB-A
92 91 90 92
64.5 (Quiet mode: 61.5)
91 90 92
65.0 (Quiet mode: 62.0)
91 90
65.0 (Quiet mode: 62.0)
1
Operation Sound
Power Level dB-A 79.0 (Quiet mode: 76.0) 79.5 (Quiet mode: 76.5) 79.5 (Quiet mode: 76.5)
kW 81.5 81.5 81.5 87.5 87.5 87.5 95.0 95.0 95.0
Capacity
BTU/h 278200 278200 278200 298600 298600 298600 324200 324200 324200
Heating

Current
Power Input
A
kW
31.1
18.6
29.8
18.6
29.1
18.6
32.6
19.5
31.3
19.5
30.5
19.5
37.7
22.6
36.2
22.6
35.3
22.6
2
COP — 4.38 4.38 4.38 4.49 4.49 4.49 4.20 4.20 4.20
Power Factor % 91 90 89 91 90 89 91 90 89
MAX Current A 46.9 46.9 46.9 51.4 51.4 51.4 55.0 55.0 55.0
MAX Power Input kW 28.4 29.5 30.4 31.2 32.4 33.4 33.4 34.7 35.7
Starting Current A 100 103 106 100 103 106 104 107 111 3
Comp Motor output kW (4.8+4.5) + (3.1+4.5) (4.8+4.5) + (4.8+4.5) (5.7+5.2) + (4.8+4.5)
Fan Motor output (No. of poles) kW 0.75 (8P)×2 0.75 (8P)×2 0.75 (8P)×2
External static pressure Pa 80 80 80
Air flow m3/min 424 424 424
Refrigerant amount at shipment kg R410A 18 R410A 19 R410A 19 4
Height mm (inch) 1758 (69-7/32) 1758 (69-7/32) 1758 (69-7/32)
Unit Dimensions Width mm (inch) 2060 (81-7/64) 2060 (81-7/64) 2060 (81-7/64)
Depth mm (inch) 930 (36-39/64) 930 (36-39/64) 930 (36-39/64)
Net weight kg (lbs.) 636 (1402) 644 (1420) 644 (1420)
Color
(Approximate value)
Color (Munsell code)
RAL code
Ivory (2.6Y7.6/1.1)
7044
Ivory (2.6Y7.6/1.1)
7044
Ivory (2.6Y7.6/1.1)
7044
5
Cooling DBT -10°C ~ 46°C -10°C ~ 46°C -10°C ~ 46°C
Operation
Heating WBT -20°C ~ 18°C -20°C ~ 18°C -20°C ~ 18°C
Condition
Cooling & Heating DBT -10°C ~ 24°C -10°C ~ 24°C -10°C ~ 24°C
Liquid
Discharge
mm (inch)
mm (inch)
19.05 (3/4)
25.4 (1)
19.05 (3/4)
28.58 (1-1/8)
19.05 (3/4)
28.58 (1-1/8)
6
Piping *1
Suction mm (inch) 31.75 (1-1/4) 31.75 (1-1/4) 31.75 (1-1/4)
Balance mm (inch) 6.35 (1/4) 6.35 (1/4) 6.35 (1/4)
Refrigeration Type FV68S (Ether oil) FV68S (Ether oil) FV68S (Ether oil)
Compressor oil Charge amount L (1.6+1.7+3)×2 (1.6+1.7+3) ×2 (1.6+1.7+3)×2
Crankcase heater W (28+31)×2 (28+31)×2 (28+31)×2 7
Connection Piping
Connection Piping
(ø22.22, ø19.05) Connection Piping
Primary Accessories (ø28.58, ø25.4)
(ø19.05, ø15.88) (ø22.22, ø19.05)×2
(ø22.22, ø19.05)×2
(ø12.7, ø9.52)

*1 Main Pipe Diameter size-up apply to O.D. to first branch pipe


DATA SUBJECT TO CHANGE WITHOUT NOTICE.
8
* Performance and electrical characteristics values are based on JIS B8616(EN14511 is only applicable to temperature conditions.) package A/C.
(Cooling : Indoor intake air temp. 27°C DB or 19°C WB. Outdoor intake air temp. 35°C DB.)
(Heating : Indoor intake air temp. 20°C DB. Outdoor intake air temp. 7°C DB or 6°C WB.)

4-5 9

5GEKPFF 
:$<6<67(08QLW6SHFL¿FDWLRQV

1. Outdoor Unit

1-1. Specifications
Standard Combination
Unit Specifications (5)
Model Name 3WAY System Outdoor Unit
Horsepower 32 34 36
U-14MF2E8 U-14MF2E8
U-16MF2E8
Model No. U-12MF2E8 U-14MF2E8
U-16MF2E8
U-8MF2E8 U-8MF2E8
ø Hz 3ø 50Hz 3ø 50Hz 3ø 50Hz
Power Supply
V 380 400 415 380 400 415 380 400 415
kW 90.0 90.0 90.0 96.0 96.0 96.0 101.0 101.0 101.0
Capacity
BTU/h 307200 307200 307200 327600 327600 327600 344700 344700 344700
Current A 43.9 42.2 41.1 42.9 41.2 39.7 46.1 44.3 43.1
Cooling

Power Input kW 26.6 26.6 26.6 25.7 25.7 25.7 27.6 27.6 27.6
EER — 3.38 3.38 3.38 3.74 3.74 3.74 3.66 3.66 3.66
1 Power Factor % 92 91 90 91 90 90 91 90 89
Pressure Level dB-A 65.0 (Quiet mode: 62.0) 65.0 (Quiet mode: 62.0) 65.5 (Quiet mode: 62.5)
Operation Sound
Power Level dB-A 79.5 (Quiet mode: 76.5) 79.5 (Quiet mode: 76.5) 80.0 (Quiet mode: 77.0)
kW 100.0 100.0 100.0 108.0 108.0 108.0 113.0 113.0 113.0
Capacity
BTU/h 341300 341300 341300 368600 368600 368600 385700 385700 385700
Heating

2 Current
Power Input
A
kW
41.7
24.8
40.1
24.8
39.1
24.8
41.0
24.3
39.4
24.3
38.4
24.3
41.6
25.0
39.9
25.0
38.9
25.0
COP — 4.03 4.03 4.03 4.44 4.44 4.44 4.52 4.52 4.52
Power Factor % 90 89 88 90 89 88 91 90 89
MAX Current A 58.6 58.6 58.6 59.5 59.5 59.5 64.0 64.0 64.0
MAX Power Input kW 35.6 37.0 38.0 35.8 37.3 38.4 38.6 40.2 41.4
3 Starting Current A 108 111 115 113 116 119 113 116 119
Comp Motor output kW (5.7+5.2) + (5.7+5.2) (4.8+4.5) + (3.1+4.5) +4.2 (4.8+4.5) + (4.8+4.5) +4.2
Fan Motor output (No. of poles) kW 0.75 (8P)×2 0.75 (8P)×3 0.75 (8P)×3
External static pressure Pa 80 80 80
Air flow 3
m /min 424 582 582
4 Refrigerant amount at shipment kg R410A 19 R410A 26 R410A 27
Height mm (inch) 1758 (69-7/32) 1758 (69-7/32) 1758 (69-7/32)
Unit Dimensions Width mm (inch) 2060 (81-7/64) 3120 (122-53/64) 3120 (122-53/64)
Depth mm (inch) 930 (36-39/64) 930 (36-39/64) 930 (36-39/64)
Net weight kg (lbs.) 644 (1420) 905 (1995) 913 (2013)
5 Color
(Approximate value)
Color (Munsell code) Ivory (2.6Y7.6/1.1) Ivory (2.6Y7.6/1.1) Ivory (2.6Y7.6/1.1)
RAL code 7044 7044 7044
Cooling DBT -10°C ~ 46°C -10°C ~ 46°C -10°C ~ 46°C
Operation
Heating WBT -20°C ~ 18°C -20°C ~ 18°C -20°C ~ 18°C
Condition
Cooling & Heating DBT -10°C ~ 24°C -10°C ~ 24°C -10°C ~ 24°C

6 *1
Liquid
Discharge
mm (inch)
mm (inch)
19.05 (3/4)
28.58 (1-1/8)
19.05 (3/4)
28.58 (1-1/8)
19.05 (3/4)
28.58 (1-1/8)
Piping
Suction mm (inch) 31.75 (1-1/4) 31.75 (1-1/4) 38.1 (1-1/2)
Balance mm (inch) 6.35 (1/4) 6.35 (1/4) 6.35 (1/4)
Refrigeration Type FV68S (Ether oil) FV68S (Ether oil) FV68S (Ether oil)
Compressor oil Charge amount L (1.6+1.7+3)×2 (1.6+1.7+3)×2+ (1.6+3) (1.6+1.7+3)×2+ (1.6+3)
7 Crankcase heater W (28+31)×2 (28+31)×2+28 (28+31)×2+28
Connection Piping
Connection Piping
(ø22.22, ø19.05) Connection Piping
Primary Accessories (ø28.58, ø25.4)×2
(ø19.05, ø15.88) (ø22.22, ø19.05)×2
(ø22.22, ø19.05)×2
(ø12.7, ø9.52)

8 *1 Main Pipe Diameter size-up apply to O.D. to first branch pipe


* Performance and electrical characteristics values are based on JIS B8616(EN14511 is only applicable to temperature conditions.) package A/C.
(Cooling : Indoor intake air temp. 27°C DB or 19°C WB. Outdoor intake air temp. 35°C DB.)
(Heating : Indoor intake air temp. 20°C DB. Outdoor intake air temp. 7°C DB or 6°C WB.)

9 4-6

5GEKPFF 
:$<6<67(08QLW6SHFL¿FDWLRQV

1. Outdoor Unit

1-1. Specifications
Standard Combination
Unit Specifications (6)
Model Name 3WAY System Outdoor Unit
Horsepower 38 40 42
U-16MF2E8 U-16MF2E8 U-14MF2E8
Model No. U-14MF2E8 U-16MF2E8 U-14MF2E8
U-8MF2E8 U-8MF2E8 U-14MF2E8
ø Hz 3ø 50Hz 3ø 50Hz 3ø 50Hz
Power Supply
V 380 400 415 380 400 415 380 400 415
kW 107.0 107.0 107.0 113.0 113.0 113.0 118.0 118.0 118.0
Capacity
BTU/h 365200 365200 365200 385700 385700 385700 402700 402700 402700
Current A 49.6 47.6 46.4 53.1 51.0 49.7 56.0 53.8 52.4
Cooling

Power Input kW 29.7 29.7 29.7 31.8 31.8 31.8 33.9 33.9 33.9
EER — 3.60 3.60 3.60 3.55 3.55 3.55 3.48 3.48 3.48
Power Factor
Pressure Level
%
dB-A
91 90 89
65.5 (Quiet mode: 62.5)
91 90 90 92
65.5 (Quiet mode: 62.5)
91 90
67.0 (Quiet mode: 64.0)
1
Operation Sound
Power Level dB-A 80.0 (Quiet mode: 77.0) 80.0 (Quiet mode: 77.0) 81.5 (Quiet mode: 78.5)
kW 119.0 119.0 119.0 127.0 127.0 127.0 132.0 132.0 132.0
Capacity
BTU/h 406100 406100 406100 433400 433400 433400 450500 450500 450500
Heating

Current
Power Input
A
kW
46.1
27.5
44.3
27.5
43.1
27.5
52.2
30.8
49.6
30.8
47.8
30.8
49.3
29.6
47.3
29.6
46.1
29.6
2
COP — 4.33 4.33 4.33 4.12 4.12 4.12 4.46 4.46 4.46
Power Factor % 91 90 89 90 90 90 91 90 89
MAX Current A 67.6 67.6 67.6 71.2 71.2 71.2 77.1 77.1 77.1
MAX Power Input kW 40.8 42.5 43.7 43.0 44.8 46.0 46.8 48.6 50.1
Starting Current A 116 119 122 120 123 127 126 129 132 3
Comp Motor output kW (5.7+5.2) + (4.8+4.5) +4.2 (5.7+5.2) + (5.7+5.2) +4.2 (4.8+4.5)+(4.8+4.5)+(4.8+4.5)
Fan Motor output (No. of poles) kW 0.75 (8P)×3 0.75 (8P)×3 0.75 (8P)×3
External static pressure Pa 80 80 80
Air flow m3/min 582 582 636
Refrigerant amount at shipment kg R410A 27 R410A 27 R410A 28 4
Height mm (inch) 1758 (69-7/32) 1758 (69-7/32) 1758 (69-7/32)
Unit Dimensions Width mm (inch) 3120 (122-53/64) 3120 (122-53/64) 3120 (122-53/64)
Depth mm (inch) 930 (36-39/64) 930 (36-39/64) 930 (36-39/64)
Net weight kg (lbs.) 913 (2013) 913 (2013) 966 (2130)
Color
(Approximate value)
Color (Munsell code)
RAL code
Ivory (2.6Y7.6/1.1)
7044
Ivory (2.6Y7.6/1.1)
7044
Ivory (2.6Y7.6/1.1)
7044
5
Cooling DBT -10°C ~ 46°C -10°C ~ 46°C -10°C ~ 46°C
Operation
Heating WBT -20°C ~ 18°C -20°C ~ 18°C -20°C ~ 18°C
Condition
Cooling & Heating DBT -10°C ~ 24°C -10°C ~ 24°C -10°C ~ 24°C
Liquid
Discharge
mm (inch)
mm (inch)
19.05 (3/4)
31.75 (1-1/4)
19.05 (3/4)
31.75 (1-1/4)
19.05 (3/4)
31.75 (1-1/4)
6
Piping *1
Suction mm (inch) 38.1 (1-1/2) 38.1 (1-1/2) 38.1 (1-1/2)
Balance mm (inch) 6.35 (1/4) 6.35 (1/4) 6.35 (1/4)
Refrigeration Type FV68S (Ether oil) FV68S (Ether oil) FV68S (Ether oil)
Compressor oil Charge amount L (1.6+1.7+3)×2+ (1.6+3) (1.6+1.7+3)×2+ (1.6+3) (1.6+1.7+3)×3
Crankcase heater W (28+31)×2+28 (28+31)×2+28 (28+31)×3 7
Connection Piping Connection Piping
Connection Piping
Primary Accessories (ø28.58, ø25.4) (ø28.58, ø25.4)×2
(ø22.22, ø19.05)×3
(ø22.22, ø19.05)×2 (ø22.22, ø19.05)×2

*1 Main Pipe Diameter size-up apply to O.D. to first branch pipe


DATA SUBJECT TO CHANGE WITHOUT NOTICE.
8
* Performance and electrical characteristics values are based on JIS B8616(EN14511 is only applicable to temperature conditions.) package A/C.
(Cooling : Indoor intake air temp. 27°C DB or 19°C WB. Outdoor intake air temp. 35°C DB.)
(Heating : Indoor intake air temp. 20°C DB. Outdoor intake air temp. 7°C DB or 6°C WB.)

4-7 9

5GEKPFF 
:$<6<67(08QLW6SHFL¿FDWLRQV

1. Outdoor Unit

1-1. Specifications
Standard Combination
Unit Specifications (7)
Model Name 3WAY System Outdoor Unit
Horsepower 44 46 48
U-16MF2E8 U-16MF2E8 U-16MF2E8
Model No. U-14MF2E8 U-16MF2E8 U-16MF2E8
U-14MF2E8 U-14MF2E8 U-16MF2E8
ø Hz 3ø 50Hz 3ø 50Hz 3ø 50Hz
Power Supply
V 380 400 415 380 400 415 380 400 415
kW 124.0 124.0 124.0 130.0 130.0 130.0 135.0 135.0 135.0
Capacity
BTU/h 423200 423200 423200 443700 443700 443700 460800 460800 460800
Current A 59.6 57.3 55.8 63.8 61.3 59.7 65.9 63.3 61.7
Cooling

Power Input kW 36.1 36.1 36.1 38.2 38.2 38.2 39.9 39.9 39.9
EER — 3.43 3.43 3.43 3.40 3.40 3.40 3.38 3.38 3.38
1 Power Factor
Pressure Level
%
dB-A
92 91 90
67.0 (Quiet mode: 64.0)
91 90 89 92
67.0 (Quiet mode: 64.0)
91 90
67.0 (Quiet mode: 64.0)
Operation Sound
Power Level dB-A 81.5 (Quiet mode: 78.5) 81.5 (Quiet mode: 78.5) 81.5 (Quiet mode: 78.5)
kW 138.0 138.0 138.0 145.0 145.0 145.0 150.0 150.0 150.0
Capacity
BTU/h 471000 471000 471000 494900 494900 494900 511900 511900 511900
Heating

2 Current
Power Input
A
kW
53.8
32.1
51.6
32.1
50.3
32.1
58.8
35.0
56.5
35.0
55.0
35.0
62.6
37.2
60.1
37.2
58.6
37.2
COP — 4.30 4.30 4.30 4.14 4.14 4.14 4.03 4.03 4.03
Power Factor % 91 90 89 90 89 89 90 89 88
MAX Current A 80.7 80.7 80.7 84.3 84.3 84.3 87.9 87.9 87.9
MAX Power Input kW 49.0 50.9 52.4 51.2 53.2 54.7 53.4 55.5 57.0
3 Starting Current A 130 133 137 133 136 140 137 140 144
Comp Motor output kW (5.7+5.2)+(4.8+4.5) +(4.8+4.5) (5.7+5.2)+(5.7+5.2)+(4.8+4.5) (5.7+5.2)+(5.7+5.2)+(5.7+5.2)
Fan Motor output (No. of poles) kW 0.75 (8P)×3 0.75 (8P)×3 0.75 (8P)×3
External static pressure Pa 80 80 80
Air flow m3/min 636 636 636
4 Refrigerant amount at shipment kg R410A 28 R410A 28 R410A 28
Height mm (inch) 1758 (69-7/32) 1758 (69-7/32) 1758 (69-7/32)
Unit Dimensions Width mm (inch) 3120 (122-53/64) 3120 (122-53/64) 3120 (122-53/64)
Depth mm (inch) 930 (36-39/64) 930 (36-39/64) 930 (36-39/64)
Net weight kg (lbs.) 966 (2130) 966 (2130) 966 (2130)
5 Color
(Approximate value)
Color (Munsell code)
RAL code
Ivory (2.6Y7.6/1.1)
7044
Ivory (2.6Y7.6/1.1)
7044
Ivory (2.6Y7.6/1.1)
7044
Cooling DBT -10°C ~ 46°C -10°C ~ 46°C -10°C ~ 46°C
Operation
Heating WBT -20°C ~ 18°C -20°C ~ 18°C -20°C ~ 18°C
Condition
Cooling & Heating DBT -10°C ~ 24°C -10°C ~ 24°C -10°C ~ 24°C

6 Liquid
Discharge
mm (inch)
mm (inch)
19.05 (3/4)
31.75 (1-1/4)
19.05 (3/4)
31.75 (1-1/4)
19.05 (3/4)
31.75 (1-1/4)
Piping*1
Suction mm (inch) 38.1 (1-1/2) 38.1 (1-1/2) 38.1 (1-1/2)
Balance mm (inch) 6.35 (1/4) 6.35 (1/4) 6.35 (1/4)
Refrigeration Type FV68S (Ether oil) FV68S (Ether oil) FV68S (Ether oil)
Compressor oil Charge amount L (1.6+1.7+3)×3 (1.6+1.7+3)×3 (1.6+1.7+3)×3
7 Crankcase heater W (28+31)×3 (28+31)×3 (28+31)×3

Connection Piping Connection Piping Connection Piping


Primary Accessories (ø28.58, ø25.4) (ø28.58, ø25.4)×2 (ø28.58, ø25.4)×3
(ø22.22, ø19.05)×3 (ø22.22, ø19.05)×3 (ø22.22, ø19.05)×3

8 *1 Main Pipe Diameter size-up apply to O.D. to first branch pipe


DATA SUBJECT TO CHANGE WITHOUT NOTICE.

* Performance and electrical characteristics values are based on JIS B8616(EN14511 is only applicable to temperature conditions.) package A/C.
(Cooling : Indoor intake air temp. 27°C DB or 19°C WB. Outdoor intake air temp. 35°C DB.)
(Heating : Indoor intake air temp. 20°C DB. Outdoor intake air temp. 7°C DB or 6°C WB.)

9 4-8

5GEKPFF 
:$<6<67(08QLW6SHFL¿FDWLRQV

1. Outdoor Unit

1-1. Specifications
High Efficiency Combination
Unit Specifications (8)
Model Name 3WAY System Outdoor Unit
Horsepower 16 24 26
U-8MF2E8 U-10MF2E8
U-8MF2E8
Model No. U-8MF2E8 U-8MF2E8
U-8MF2E8
U-8MF2E8 U-8MF2E8
ø Hz 3ø 50Hz 3ø 50Hz 3ø 50Hz
Power Supply
V 380 400 415 380 400 415 380 400 415
kW 45.0 45.0 45.0 68.0 68.0 68.0 73.0 73.0 73.0
Capacity
BTU/h 153600 153600 153600 232100 232100 232100 249100 249100 249100
Current A 17.3 16.4 16.0 26.2 24.9 24.3 28.5 27.4 26.7
Cooling

Power Input kW 10.0 10.0 10.0 15.2 15.2 15.2 16.9 16.9 16.9
EER — 4.50 4.50 4.50 4.47 4.47 4.47 4.32 4.32 4.32
Power Factor
Pressure Level
%
dB-A
88 88 87
60.0 (Quiet mode: 57.0)
88 88 87 90
62.0 (Quiet mode: 59.0)
89 88
62.5 (Quiet mode: 59.5)
1
Operation Sound
Power Level dB-A 74.5 (Quiet mode: 71.5) 76.5 (Quiet mode: 73.5) 77.0 (Quiet mode: 74.0)
kW 50.0 50.0 50.0 76.5 76.5 76.5 81.5 81.5 81.5
Capacity
BTU/h 170600 170600 170600 261100 261100 261100 278200 278200 278200
Heating

Current
Power Input
A
kW
17.9
10.5
17.0
10.5
16.6
10.5
27.7
16.2
26.3
16.2
25.6
16.2
29.4
17.4
27.9
17.4
27.5
17.4
2
COP — 4.76 4.76 4.76 4.72 4.72 4.72 4.68 4.68 4.68
Power Factor % 89 89 88 89 89 88 90 90 88
MAX Current A 25.2 25.2 25.2 37.8 37.8 37.8 41.5 41.5 41.5
MAX Power Input kW 14.8 15.6 16.0 22.2 23.4 23.9 24.5 25.9 26.6
Starting Current A 1 1 1 1 1 1 1 1 1 3
Comp Motor output kW 4.2×2 4.2×3 6.0+4.2+4.2
Fan Motor output (No. of poles) kW 0.75 (8P)×2 0.75 (8P)×3 0.75 (8P)×3
External static pressure Pa 80 80 80
Air flow m3/min 316 474 494
Refrigerant amount at shipment kg R410A 17 R410A 25 R410A 25 4
Height mm (inch) 1758 (69-7/32) 1758 (69-7/32) 1758 (69-7/32)
Unit Dimensions Width mm (inch) 2060 (81-7/64) 3120 (122-53/64) 3120 (122-53/64)
Depth mm (inch) 930 (36-39/64) 930 (36-39/64) 930 (36-39/64)
Net weight kg (lbs.) 538 (1186) 807 (1779) 807 (1779)
Color
(Approximate value)
Color (Munsell code)
RAL code
Ivory (2.6Y7.6/1.1)
7044
Ivory (2.6Y7.6/1.1)
7044
Ivory (2.6Y7.6/1.1)
7044
5
Cooling DBT -10°C ~ 46°C -10°C ~ 46°C -10°C ~ 46°C
Operation
Heating WBT -20°C ~ 18°C -20°C ~ 18°C -20°C ~ 18°C
Condition
Cooling & Heating DBT -10°C ~ 24°C -10°C ~ 24°C -10°C ~ 24°C
Liquid
Discharge
mm (inch)
mm (inch)
12.7 (1/2)
22.22 (7/8)
15.88 (5/8)
25.4 (1)
19.05 (3/4)
25.4 (1)
6
Piping *1
Suction mm (inch) 28.58 (1-1/8) 28.58 (1-1/8) 31.75 (1-1/4)
Balance mm (inch) 6.35 (1/4) 6.35 (1/4) 6.35 (1/4)
Refrigeration Type FV68S (Ether oil) FV68S (Ether oil) FV68S (Ether oil)
Compressor oil Charge amount L (1.6+3)×2 (1.6+3)×3 (1.6+3)×3
Crankcase heater W 28×2 28×3 28×3 7
Connection Piping
Primary Accessories None None
(ø19.05, ø15.88)

*1 Main Pipe Diameter size-up apply to O.D. to first branch pipe


DATA SUBJECT TO CHANGE WITHOUT NOTICE.
8
* Performance and electrical characteristics values are based on JIS B8616(EN14511 is only applicable to temperature conditions.) package A/C.
(Cooling : Indoor intake air temp. 27°C DB or 19°C WB. Outdoor intake air temp. 35°C DB.)
(Heating : Indoor intake air temp. 20°C DB. Outdoor intake air temp. 7°C DB or 6°C WB.)

4-9 9

5GEKPFF 
:$<6<67(08QLW6SHFL¿FDWLRQV

1. Outdoor Unit

1-1. Specifications
High Efficiency Combination
Unit Specifications (9)
Model Name 3WAY System Outdoor Unit
Horsepower 28 30 32
U-12MF2E8 U-14MF2E8 U-12MF2E8
Model No. U-8MF2E8 U-8MF2E8 U-12MF2E8
U-8MF2E8 U-8MF2E8 U-8MF2E8
ø Hz 3ø 50Hz 3ø 50Hz 3ø 50Hz
Power Supply
V 380 400 415 380 400 415 380 400 415
kW 78.5 78.5 78.5 85.0 85.0 85.0 90.0 90.0 90.0
Capacity
BTU/h 267900 267900 267900 290100 290100 290100 307200 307200 307200
Current A 32.2 31.0 30.2 36.5 35.0 34.1 38.9 37.4 36.4
Cooling

Power Input kW 19.1 19.1 19.1 21.6 21.6 21.6 23.3 23.3 23.3
EER — 4.11 4.11 4.11 3.94 3.94 3.94 3.86 3.86 3.86
1 Power Factor
Pressure Level
%
dB-A
90 89 88
63.5 (Quiet mode: 60.5)
90 89 88 91
64.0 (Quiet mode: 61.0)
90 89
65.0 (Quiet mode: 62.0)
Operation Sound
Power Level dB-A 78.0 (Quiet mode: 75.0) 78.5 (Quiet mode: 75.5) 79.5 (Quiet mode: 76.5)
kW 87.5 87.5 87.5 95.0 95.0 95.0 100.0 100.0 100.0
Capacity
BTU/h 298600 298600 298600 324200 324200 324200 341300 341300 341300
Heating

2 Current
Power Input
A
kW
32.4
19.2
31.1
19.2
30.4
19.2
35.0
20.7
33.6
20.7
32.7
20.7
38.3
22.7
36.8
22.7
35.9
22.7
COP — 4.56 4.56 4.56 4.59 4.59 4.59 4.41 4.41 4.41
Power Factor % 90 89 88 90 89 88 90 89 88
MAX Current A 46.4 46.4 46.4 50.9 50.9 50.9 55.0 55.0 55.0
MAX Power Input kW 27.6 28.9 29.7 30.4 31.8 32.7 33.0 34.4 35.4
3 Starting Current A 100 103 106 100 103 106 108 111 114
Comp Motor output kW (3.1+4.5) +4.2+4.2 (4.8+4.5) +4.2+4.2 (3.1+4.5) + (3.1+4.5) +4.2
Fan Motor output (No. of poles) kW 0.75 (8P)×3 0.75 (8P)×3 0.75 (8P)×3
External static pressure Pa 80 80 80
Air flow m3/min 528 528 582
4 Refrigerant amount at shipment kg R410A 25 R410A 26 R410A 26
Height mm (inch) 1758 (69-7/32) 1758 (69-7/32) 1758 (69-7/32)
Unit Dimensions Width mm (inch) 3120 (122-53/64) 3120 (122-53/64) 3120 (122-53/64)
Depth mm (inch) 930 (36-39/64) 930 (36-39/64) 930 (36-39/64)
Net weight kg (lbs.) 852 (1878) 860 (1896) 897 (1978)
5 Color
(Approximate value)
Color (Munsell code)
RAL code
Ivory (2.6Y7.6/1.1)
7044
Ivory (2.6Y7.6/1.1)
7044
Ivory (2.6Y7.6/1.1)
7044
Cooling DBT -10°C ~ 46°C -10°C ~ 46°C -10°C ~ 46°C
Operation
Heating WBT -20°C ~ 18°C -20°C ~ 18°C -20°C ~ 18°C
Condition
Cooling & Heating DBT -10°C ~ 24°C -10°C ~ 24°C -10°C ~ 24°C

6 Liquid
Discharge
mm (inch)
mm (inch)
19.05 (3/4)
28.58 (1-1/8)
19.05 (3/4)
28.58 (1-1/8)
19.05 (3/4)
28.58 (1-1/8)
Piping *1
Suction mm (inch) 31.75 (1-1/4) 31.75 (1-1/4) 31.75 (1-1/4)
Balance mm (inch) 6.35 (1/4) 6.35 (1/4) 6.35 (1/4)
Refrigeration Type FV68S (Ether oil) FV68S (Ether oil) FV68S (Ether oil)
Compressor oil Charge amount L (1.6+1.7+3) + (1.6+3)×2 (1.6+1.7+3) +(1.6+3)×2 (1.6+1.7+3)×2+ (1.6+3)
7 Crankcase heater W (28+31) +28×2 (28+31) +28×2 (28+31)×2+28

Connection Piping Connection Piping


Connection Piping
Primary Accessories (ø19.05, ø15.88) (ø19.05, ø15.88)×2
(ø22.22, ø19.05)
(ø12.7, ø9.52) (ø12.7, ø9.52)×2

8 *1 Main Pipe Diameter size-up apply to O.D. to first branch pipe


DATA SUBJECT TO CHANGE WITHOUT NOTICE.

* Performance and electrical characteristics values are based on JIS B8616(EN14511 is only applicable to temperature conditions.) package A/C.
(Cooling : Indoor intake air temp. 27°C DB or 19°C WB. Outdoor intake air temp. 35°C DB.)
(Heating : Indoor intake air temp. 20°C DB. Outdoor intake air temp. 7°C DB or 6°C WB.)

9 4-10

5GEKPFF 
:$<6<67(08QLW6SHFL¿FDWLRQV

1. Outdoor Unit

1-2. Dimensional Data


ø2
U-8MF2E8, U-10MF2E8, U-12MF2E8 ø6 8
Air intake 0 ( (Kno z view
Kn ck
oc -o
k-o ut
ut ho 9 7
ho le)
le)

B:730*
930 (Max)

A:894*
Air intake
C:730*
Air intake

730

894
730
5 15
970 (Installation hole pitch)
1000 (Top panel dimension)
Top view
13 14 Electrical component box
970
1
(104)

Air discharge

12

11
10 2
Space for creation
of hole on-site 4
(Max, diameter ø48)
3
1758
1654

2
3
1
856

855
619
152
137

74

327
316
314
a

4
92

220
56
66

Refrigerant tubing hole, 355 930


Electrical wiring hole, 363 Z 6
Under panel 522 Right side
582 222 8
Front view 584 * According to the installation site, you may choose the setting position
646
695
in the depth direction of the anchor bolt from "A", "B" or "C".
A : 894 (Installation hole pitch)
5
:Installation fixing bracket 770 * The tubing is routed out from the front.
Installation surface 71 858 71 B : 730 (Installation hole pitch)
* The tubing is routed out from the bottom.
C : 730 (Installation hole pitch)

1 Refrigerant tubing (suction tube) See table at right.


6
56 (PART 4 )
62 (PART 2 )
63 (PART 3 )
65 (PART 1 )

2 Refrigerant tubing (discharge tube) flared connection ø15.88


499 305
3 Refrigerant tubing (liquid tube) flared connection ø9.52 (Opening width)
4 Refrigerant tubing (balance tube) flared connection ø6.35 341 5 5
206
51
41
16
5

Installation holes (4-15×21 elongated holes), anchor bolts M12 or


18

5 larger: use 4 pieces and select an anchor bolt position in the direction
of depth among A, B, C according to the installation location.
182

7
(Opening depth)

6 Refrigerant tubing port (front: knock-out hole)


7 Refrigerant tubing port (bottom: slit hole)
84

8 Electrical wiring port (front: ø60, ø28knock-out holes for conduit connection)
9 Electrical wiring port (bottom: ø60, ø28knock-out holes for conduit connection)
10 Pressure outlet port (for high pressure: ø7.94 Schrader-type connection)
11 Pressure outlet port (for low pressure: ø7.94 Schrader-type connection)
12 Knock-out hole for connecting pressure gauge (optional) a connection 8
13 Terminal board U-8MF2E8 258 Brazed connection ø19.05
14 Inter-unit control wiring, U-10MF2E8
246 Brazed connection ø22.22
Inter-outdoor unit control wiring Terminal board U-12MF2E8

4-11 9

5GEKPFF 
:$<6<67(08QLW6SHFL¿FDWLRQV

1. Outdoor Unit

U-14MF2E8, U-16MF2E8
Air intake ø2
ø6 8(
0 ( Knoc z view
Kn k-o
oc ut
k-o ho 9 7
ut le)
ho

B:730*
le)

930 (Max)

A:894*
Air intake
C:730*
Air intake

730

894
730
15
5
970 (Installation hole pitch)
1000 (Top panel dimension)
Top view
13 14 Electrical component box 970
(104)

1 Air discharge

12

11
10
Space for creation
2 of hole on-site
(Max, diameter ø48)
4
3
1758
1654

1
3
856

855
619
152
137

92 74

319
316
246
238

220
56
66

Refrigerant tubing hole, 355 930


4 Electrical wiring hole,
Under panel
363
522
Z 6

582 222 8
584 Right side
Front view 686
696 * According to the installation site, you may choose the setting position
768 in the depth direction of the anchor bolt from "A", "B" or "C".

5 :Installation fixing bracket 71


Installation surface
858 71 A : 894 (Installation hole pitch)
* The tubing is routed out from the front.
B : 730 (Installation hole pitch)
* The tubing is routed out from the bottom.
C : 730 (Installation hole pitch)
1 Refrigerant tubing (suction tube) brazed connection ø25.4
2 Refrigerant tubing (discharge tube) brazed connection ø19.05
56 (PART 4 )
62 (PART 1 )
63 (PART 3 )
65 (PART 2 )

6 3 Refrigerant tubing (liquid tube)


4 Refrigerant tubing (balance tube)
flared connection ø12.7
flared connection ø6.35 341
499

5
305
(Opening width)
5
15

206
51
41
16
5

Installation holes (4-15×21 elongated holes), anchor bolts M12 or


18

5 larger: use 4 pieces and select an anchor bolt position in the direction
of depth among A, B, C according to the installation location.
182

6 Refrigerant tubing port (front: knock-out hole)


(Opening depth)

7 7 Refrigerant tubing port (bottom: slit hole)


84

8 Electrical wiring port (front: ø60, ø28knock-out holes for conduit connection)
9 Electrical wiring port (bottom: ø60, ø28knock-out holes for conduit connection)
10 Pressure outlet port (for high pressure: ø7.94 Schrader-type connection)
11 Pressure outlet port (for low pressure: ø7.94 Schrader-type connection)
12 Knock-out hole for connecting pressure gauge (optional)
8 13

14
Terminal board
Inter-unit control wiring,
Inter-outdoor unit control wiring terminal board

9 4-12

5GEKPFF 
:$<6<67(08QLW6SHFL¿FDWLRQV

1. Outdoor Unit

1-3. Multiple Unit Installation Example

Diagrams for 2-unit setting (Top view)


Unit: mm
*b
(Top panel dimension)
1000 *a 1000
(Top panel dimension) (Top panel dimension)

B
930

A
C
970 970
1
(Installation hole pitch) (Installation hole pitch)
Installation anchor hole Installation anchor hole
(8 – 15 × 21 elongated holes) (8 – 15 × 21 elongated holes)

• According to the installation site, you may choose the setting position in the depth direction of the anchor bolt from “A”, “B” or “C”.
For 2-unit setting 2
*a *b
A :894 (Installation hole pitch) * The tubing is routed out from the front. 60 2060
B :730 (Installation hole pitch) * The tubing is routed out from the bottom. 180 2180
C :730 (Installation hole pitch) 180 2180
3
Diagrams for 3-unit setting (Top view)
Unit: mm
*b

1000 *a
(Top panel dimension)
1000 *a 1000
4
(Top panel dimension) (Top panel dimension) (Top panel dimension)

5
B
930

A
C

6
970 970 970
(Installation hole pitch) (Installation hole pitch) (Installation hole pitch)
Installation anchor hole Installation anchor hole
(8 – 15 × 21 elongated holes) (8 – 15 × 21 elongated holes)

• According to the installation site, you may choose the setting position in the depth direction of the anchor bolt from “A”, “B” or “C”. 7
For 3-unit setting
*a *b
A :894 (Installation hole pitch) * The tubing is routed out from the front. 60 3120
B :730 (Installation hole pitch) * The tubing is routed out from the bottom. 180 3360
C :730 (Installation hole pitch) 180 3360 8

4-13 9

5GEKPFF 

:$<6<67(08QLW6SHFL¿FDWLRQV

Thermistor
S
Accumulator

HP
INV
Distribution joint kit
Compressor
(not supplied)
Oil separator
S
For low pressure
LPS Low pressure sensor
Balance tube
ø6.35
S Suction tube
8HP : ø19.05
For high 10HP: ø22.22 S S S S S S S S S
pressure

4-14
S S
HPS
High pressure sensor
Indoor unit Indoor unit
4-way valve 4-way valve

Solenoid valve kit


(not supplied)

Solenoid valve kit


(not supplied)
Discharge tube
S S S
ø15.88
Liquid tube
S ø9.52
M M
1-4. Refrigerant Flow Diagram

To outdoor unit
1. Outdoor Unit

M M

-10MF2E8
U-8MF2E8
M

5GEKPFF
1

9

1

9
:$<6<67(08QLW6SHFL¿FDWLRQV

Thermistor
S
HP
Compressor
Accumulator

AC1
Distribution joint kit
HP (not supplied)
INV
Compressor
Oil separator
For low pressure
S LPS Low pressure sensor
Balance tube
ø6.35
Suction tube
S S S S S S S S S S
ø25.4
For high
pressure

4-15
S S HPS High pressure sensor
Indoor unit Indoor unit

Solenoid valve kit


(not supplied)

Solenoid valve kit


(not supplied)
Discharge tube
4-way valve 4-way valve
S S S
ø19.05
Liquid tube
ø12.7
S
M M
1-4. Refrigerant Flow Diagram

To outdoor unit
1. Outdoor Unit

M M

U-12MF2E8
M

5GEKPFF

:$<6<67(08QLW6SHFL¿FDWLRQV

Thermistor
S
HP
Compressor
AC1
Accumulator

Distribution joint kit


(not supplied)
HP
INV
Compressor
Oil separator
For low pressure
S
LPS Low pressure sensor
Balance tube
ø6.35
Suction tube S S S S S S S S S
S
14HP : ø25.4
16HP : ø28.58

4-16
For high pressure
S S S S
HPS High pressure sensor Indoor unit Indoor unit

Solenoid valve kit


(not supplied)

Solenoid valve kit


(not supplied)
4-way valve 4-way valve Discharge tube
ø19.05
S S S
Liquid tube
ø12.7
S
M M
1-4. Refrigerant Flow Diagram

To outdoor unit
1. Outdoor Unit

U-14MF2E8
-16MF2E8
M M
M

5GEKPFF
1

9
:$<6<67(08QLW6SHFL¿FDWLRQV

1. Outdoor Unit

1-5. Noise Criterion Curves


Standard mode
Quiet mode
U-8MF2E8, U-10MF2E8, U-12MF2E8, U-14MF2E8, U-16MF2E8
MODEL : U-8MF2E8 MODEL : U-10MF2E8
SOUND LEVEL : 57.0 SOUND LEVEL 59.0
db (A) db (A) :
(Quiet mode 54.0) (Quiet mode 56.0)
CONDITION : 1 m in front at height of 1.5 m CONDITION : 1 m in front at height of 1.5 m
Sound pressure level (dB) (0dB = 0.0002μbar)

Sound pressure level (dB) (0dB = 0.0002μbar)


80 80

70 70

60 60
NC-60 NC-60

50 50
NC-50 NC-50

40 40
Approximate
NC-40
Approximate
NC-40 1
30 minimum 30 minimum
audible limit for NC-30 audible limit for NC-30
continuous noise continuous noise
20 20
Overall Overall
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Frequency at center of sound pressure band (Hz) Frequency at center of sound pressure band (Hz)
2
MODEL : U-12MF2E8 MODEL : U-14MF2E8
SOUND LEVEL : 61.0 SOUND LEVEL : 62.0
db (A) (Quiet mode 58.0) db (A) (Quiet mode 59.0)
CONDITION : 1 m in front at height of 1.5 m CONDITION : 1 m in front at height of 1.5 m
Sound pressure level (dB) (0dB = 0.0002μbar)

Sound pressure level (dB) (0dB = 0.0002μbar)

80 80
3
70 70

60 60
NC-60 NC-60

50
NC-50
50
NC-50 4
40 40
NC-40 NC-40
Approximate Approximate
30 minimum 30 minimum
audible limit for NC-30 audible limit for NC-30

20
continuous noise
Overall
20
continuous noise
Overall
5
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Frequency at center of sound pressure band (Hz) Frequency at center of sound pressure band (Hz)

MODEL : U-16MF2E8
SOUND LEVEL : 62.0
db (A)
CONDITION
(Quiet mode 59.0)
: 1 m in front at height of 1.5 m
6
Sound pressure level (dB) (0dB = 0.0002μbar)

80

70

60
NC-60
7
50
NC-50
40
NC-40
Approximate
30 minimum
8
audible limit for NC-30
continuous noise
20
Overall
63 125 250 500 1000 2000 4000 8000
Frequency at center of sound pressure band (Hz)

4-17 9

5GEKPFF 
– MEMO –

4-18

5GEKPFF 
Test Run

Contents

5. TEST RUN
1. Preparing for Test Run .......................................................................................................5-2
2. Test Run Procedure ............................................................................................................5-3
3. Main Outdoor Unit PCB Setting.........................................................................................5-4
4. Auto Address Setting .........................................................................................................5-6
5. Remote Controller Test Run Settings .............................................................................5-16
6. Caution for Pump Down...................................................................................................5-16
7. Meaning of Alarm Messages ...........................................................................................5-17

5-1 9

5GEKPFF 
Test Run

1. Preparing for Test Run

1. Preparing for Test Run


Before attempting to start the air conditioner,
check the following.
ON
(1) All loose matter is removed from the cabinet especially
(Power must be turned
steel filings, bits of wire, and clips. ON at least 5 hours
(2) The control wiring is correctly connected and all electrical before attempting test
run)
connections are tight.
(3) The protective spacers for the compressor used for
transportation have been removed. If not, remove them
now.
Power mains switch
(4) The transportation pads for the indoor fan have been
Fig. 5-1
removed. If not, remove them now.
(5) The power has been connected to the unit for at least
1 5 hours before starting the compressor. The bottom of
For 8hp ~ 12hp

the compressor should be warm to the touch and the Valve cap
crankcase heater around the feet of the compressor
should be hot to the touch. (Fig. 5-1)

2 (6) If only 1 outdoor unit is installed, close the service valve


on the balance tubes, and open the service valve on the
other 3 tubes (suction, discharge, and liquid tubes).
If 2 or 3 outdoor units are installed, open the service Balance Discharge
tube Liquid tube
valves on all 4 tubes (suction, discharge, liquid, and tube
3 balance tubes).
Suction
tube
(7) Request that the customer be present for the trial run.
For 14hp & 16hp
Explain the contents of the operating instructions, then
have the customer actually operate the system. Valve cap

4 (8) Be sure to give the operating instructions and warranty


certificate to the customer.
(9) When replacing the control PCB, be sure to make all the
same settings on the new PCB as were in use before
replacement.
5 The existing EEPROM is not changed, and is connected Balance Liquid
tube
to the new control PCB. tube

Discharge Suction
tube tube

6 Fig. 5-2

9 5-2

5GEKPFF 
Test Run

2. Test Run Procedure

2. Test Run Procedure Items to Check Before the Test Run


Recheck the items to check before the test run.
1. Turn the remote power switch on at least 5
hours before the test, in order to energize
the crank case heater.
NO
Have the outdoor sub units been connected? 2. Turn the outdoor service valves (4 locations)
to the full-open positions.
YES
<Outdoor unit control PCB> *1 Use caution when making the settings. If
Unit No. setting switch Set the unit address. there are duplicated system addresses,
(SW5)
or if the settings for the Nos. of the indoor
<Outdoor unit control PCB> units are not consistent, an alarm will
Unit No. setting switch Set the No. of outdoor units.
occur and the system will not start.
(SW6)
These settings are not made on the
<Outdoor unit control PCB> indoor unit PCB.
Unit No. setting switch Set the No. of indoor units.
(SW3 and SW4) *1 The unit with the unit No. set to 1 is the main unit.
All other units are sub units.
Are the inter-unit control wires NO CASE 1
(Check the link wiring.) connected to more than 1 refrigerant

<Outdoor unit control PCB>


system?
YES
1
Unit No. setting switch Set the system address.
(SW1 and SW2) Note:
It is not necessary to remove the
When multiple outdoor main units exist, disconnect the terminals extended socket that is used to short-circuit
Refer to Fig. 5-4 from the shorted plugs (CN67) at all outdoor main unit PCBs except for 2.
Alternatively, move the sockets to the OPEN side. the terminal plugs from the outdoor
See the section “Adjustment of Termination Resistor (Plug)”. sub unit PCBs.
2
Is it possible to turn ON the power only YES CASE 2
for the 1 refrigerant system where the
test run will be performed?
Turn ON the indoor and
NO outdoor unit power for that
refrigerant system only.

NO
Will automatic address setting be
performed in Heating mode?
Make necessary corrections. Short-circuit the automatic address pin
(CN30) on the outdoor main unit PCB
3
for 1 second or longer, then release it.
YES Turn OFF the indoor and
CASE 3B CASE 3A outdoor unit power.
LED 1 and 2 blink alternately
Is it OK to start the compressors? Is it OK to start the compressors? Check the alarm contents. (about 2 or 3 minutes).

*2
Turn ON the indoor and
outdoor unit power.
Turn ON the indoor and
outdoor unit power. NO Are LEDs 1 and 2 on the
4
*2 Make necessary
corrections outdoor unit PCB OFF?
Short-circuit the mode change pin Short-circuit the automatic Refer to “Table of
(CN40 on the outdoor main unit PCB. address pin (CN30) on the Self-Diagnostic Functions and
At the same time, short-circuit the outdoor main unit PCB for Turn OFF the indoor Description of Alarm Displays.” YES
automatic address pin (CN30) for 1 1 second or longer, then and outdoor unit
second or longer, then release it. release it.

*3
Start indoor and outdoor unit
cooling operation.
*3
Start indoor and outdoor unit Check the alarm
5
heating operation. contents.
LED 1 and 2 blink alternately. LED 1 and 2 blink alternately.
*2 A minimum of 5 hours must have passed
after the power was turned ON to the
outdoor unit.
Are LEDs 1 and 2 on the NO
*3 All indoor units operate in all refrigerant
outdoor unit PCB OFF?

YES
systems where the power is ON.
6
*4
Is the solenoid valve kit in the NO
indoor unit shared?

*4 Refer to page 2-8 YES Was the setting change for the NO
“Common solenoid
valve kit”.
shared solenoid valve kit performed?
7
YES Make a setting change.

YES
Check that test run preparation is OK.
(Do not allow the short-circuited pins to remain short-circuited.)

Set the wired remote controller for test run. 8


Refer to the remote NO Check and make corrections according to
controller test-run Does system operate? “Table of Self-Diagnostic Functions.”
settings.
YES
Return remote control to normal mode
End test run. Fig. 5-3
5-3 9

5GEKPFF 

Test Run

CHK (CN23) pin STOP Suction gas temp.


(CN28) pin MODE SW5 Alarm LED (LED1) EEPROM LED (LED3) SCG (CN77) Gas sensor at
A. ADD TEST (CN40) pin
EEPROM heat exchanger 1, 2
(CN30) pin (CN22) pin DEF (CN25) SW6 SW3 SW7 Alarm LED (LED 2) memory IC (IC14) (CN61)
AP (CN24) pin

sensor (CN49)
Low-pressure
RUN (CN27) pin

Comp. discharge 2
sensor (CN56)
SW1
HIC3 (CN43)

Suction temp.
SCT (CN65)

5-4
Comp. discharge 1
sensor (CN55)
SILENT (CN33)
3. Main Outdoor Unit PCB Setting

sensor (CN46)
High-pressure
SW2
1-1. Outdoor Unit Control PCB A747306

sensor (CN54)
Oil detection
SW4

OC (CN76)
DEMAND (CN71)

fuse (FUSE3)
Control circuit
CT2, CT3 (CN35) HIC1 (CN7) Outdoor air sensor RC (CN73) RC1 (CN75)
(TO)(CN53)
FORCED STOP (CN70) CTL1, CTL2 (CN9) Liquid sensor at
HIC2 (CN10) heat exchanger 1, 2 Terminal
(CN67) EMG (CN69)
(CN60)

5GEKPFF
1

9
Test Run

3. Main Outdoor Unit PCB Setting

Examples of the No. of indoor units settings (SW4, SW3)


Indoor unit setting (SW4)
Indoor unit setting (SW3)
No. of indoor units (3P DIP switch, blue)
(Rotary switch, red)
10 20 30
ON ON
1 unit (factory setting) All OFF Set to 1
1 2 3 OFF
ON ON
11 units 1 ON Set to 1
1 2 3 OFF
ON ON
21 units 2 ON Set to 1
1 2 3 OFF
ON ON
31 units 3 ON Set to 1
1 2 3 OFF
ON ON
40 units 1 & 3 ON Set to 0
1 2 3 OFF
ON ON
52 units 2 & 3 ON Set to 2
1 2 3 OFF

Examples of refrigerant circuit (R.C.) address settings (required when link wiring is used) (SW2, SW1)
1
System address (SW2) System address (SW1)
System address No. (2P DIP switch, black) (Rotary switch, black)
10 20
ON ON
System 1 (factory setting) Both OFF Set to 1
1
ON
2 OFF
ON
2
System 11 1 ON Set to 1
1 2 OFF
ON ON
System 21 2 ON Set to 1
1 2 OFF
ON ON
System 30 1 & 2 ON Set to 0
1 2 OFF
3
Examples of the No. of outdoor units settings (SW6)
Outdoor unit setting (SW6)
No. of outdoor units (3P DIP switch, blue)
ON ON
1 unit (factory setting) 1 ON
1
ON
2 3 OFF
ON
4
2 units 2 ON
1 2 3 OFF
ON ON
3 units 1 & 2 ON
1 2 3 OFF

Address setting of main outdoor unit (SW5) 5


Address setting of outdoor unit (SW5)
Unit No. setting
(3P DIP switch, blue)
ON ON
Unit No. 1 (main unit)
(factory setting) 1 ON
1 2 3 OFF

6
Address setting of sub outdoor unit
Address setting of outdoor unit (SW5)
Unit No. setting
(3P DIP switch, blue)
ON ON
Unit No. 2 (sub unit) 2 ON

7
1 2 3 OFF
ON ON
Unit No. 3 (sub unit) 1 & 2 ON
1 2 3 OFF

The sub unit control PCB contains the same switches as the main unit control PCB for No. of indoor units, No. of outdoor units, and
system address. However it is not necessary to set these switches.

5-5 9

5GEKPFF 
Test Run

4. Auto Address Setting

4. Auto Address Setting


Basic wiring diagram: Example (1)
• If link wiring is not used
(The inter-unit control wires are not connected to multiple refrigerant systems.)
Indoor unit addresses can be set without operating the compressors.
No. 1 (main outdoor unit)
settings No. of indoor units
System address (10 units setting)
(system 1 setting) (SW3)
(SW1) (SW2)
ON ON
(SW4)
ON ON
No. 2 (sub unit) No. 3 (sub unit)
1 2 OFF
settings settings
1 2 3 OFF
No. of Unit (SW5) Unit (SW5)
(SW6) Unit number (SW5) ON ON ON ON
outdoor ON ON ON ON number number
units (3units setting setting setting
1 2 3 OFF 1 2 3 OFF
setting) 1 2 3 OFF (Unit No. 1) 1 2 3 OFF (Unit No. 2) (Unit No. 3)

1
Unit Unit Unit
Outdoor Unit No. 1 No. 2 No. 3
(Main) Inter-outdoor unit (Sub) Inter-outdoor unit (Sub)
control wiring control wiring

2 Inter-unit control wiring

Indoor Unit 1-1 1-2 1-3 1-10


Remote control
3 Remote controller communication wiring

"2&
Fig. 5-5
(1) Automatic Address Setting from the Outdoor Unit

 .3)&/43%//1-"*.4.*3$/.31/,$)&$+3)"33)&2623&-"%%1&221/3"1625*3$)!
*22&33/7
9".%3)"33)&

4

25*3$)! *22&33/ 7 9



)&2&"1&3)&2&33*.(2"33)&3*-&/''"$3/162)*0-&.3

 /2&33)&.4-#&1/'*.%//14.*323)"3"1&$/..&$3&%3/3)&/43%//14.*33/
/.3)&/43%//1-"*.4.*3$/.31/,2&3
 
3)&//'*.%//14.*3225*3$)! 3/ 7
9".%2&33)&1/3"1625*3$)! 3/7 9



5  /2&33)&.4-#&1/'/43%//14.*32/.3)&/43%//1-"*.4.*3$/.31/,2&33)&//'/43%//14.*3225*3$)!3/
  
 4.*32".%2&33)&4.*3/25*3$)!3/ 4.*3/
8-"*.





 .3)&/ 24#4.*3$/.31/,2&33)&4.*3/25*3$)!3/ 4.*3/ 



.3)&/ 24#4.*3$/.31/,2&33)&4.*3/25*3$)!3/ 4.*3/ 
6  41.3)&0/5&13/3)&*.%//1".%/43%//14.*32

 .3)&/43%//1-"*.4.*3$/.31/,2)/13$*1$4*33)&"43/-"3*$"%%1&220*. '/1
2&$/.%/1,/.(&13)&.1&,&"2&*3
:
/--4.*$"3*/.'/1"43/-"3*$"%%1&222&33*.(#&(*.2
7 :  /$".$&,"("*.2)/13$*1$4*33)&"43/-"3*$"%%1&220*. '/1
2&$/.%/1,/.(&13)&.1&,&"2&*3
)&3)"3*.%*$"3&23)"3"43/-"3*$"%%1&222&33*.(*2*.01/(1&22341.2".%3)&01/$&22*223/00&%
&241&3/0&1'/1-"43/-"3*$"%%1&222&33*.("("*.
43/-"3*$"%%1&222&33*.(*2$/-0,&3&%5)&.2
".% /.3)&/43%//1-"*.4.*3$/.31/,341.
:
8  0&1"3*/.'1/-3)&1&-/3&$/.31/,,&12*2./50/22*#,&
/0&1'/1-"43/-"3*$"%%1&222&33*.('1/-3)&1&-/3&$/.31/,,&10&1'/1-23&02
3/3)&.42&3)&1&-/3&$/.31/,,&1".%
$/-0,&3&"43/-"3*$"%%1&222&33*.(
&'&13/743/-"3*$%%1&22&33*.('1/-3)&&-/3&/.31/,,&19

9 5-6

5GEKPFF 
Test Run

4. Auto Address Setting

Basic wiring diagram: Example (2)

• If link wiring is used * See the section “Adjustment of Termination Resistor (Plug)”.

No. 1 Refrigerant circuit


No. 1 (main outdoor unit) settings
System address No. of indoor units
(system 1 setting) (13 units setting)
(SW1) (SW2) (SW3)
ON ON
3

1 2 OFF
(SW4)
ON ON

2 3 OFF No. 2 (sub unit) No. 3 (sub unit)


1
No. of settings settings
(SW6) Unit Unit
outdoor units ON (SW5) Unit (SW5) (SW5)
ON number ON
ON
number ON
(3 units setting number ON ON ON
setting
setting) 1 2 3 OFF
(unit No. 1) 1 2 3 OFF setting
(unit No. 2) 1 2 3 OFF (unit No. 3) 1 2 3
OFF
1
Outdoor unit Unit Unit Unit
system 1 No. 1 No. 2 No. 3
(Main) (Sub) (Sub)
Inter-outdoor unit control wiring Inter-outdoor unit control wiring

Inter-unit control wiring


2
Indoor unit 1-1 1-2 1-3 1-13
Remote control
Remote
controller
communication wiring
3
No. 2 No. 1 (main unit) settings
Refrigerant System address No. of indoor units
(system 2 setting) (9 units setting)
circuit
(SW1) (SW2) (SW3)

4
ON ON

1 2 OFF
(SW4)
ON ON

No. 2 (sub unit) settings


1 2 3 OFF
No. of (SW5)
(SW6) (SW5) Unit number ON
outdoor Unit number ON ON
ON ON ON setting (unit
units (2 units setting (unit No. 2)
setting)
5
1 2 3 OFF
1 2 3 OFF No. 1) 1 2 3 OFF

Outdoor unit Unit Unit


system 2 No. 1 No. 2
(Main) (Sub)

Inter-unit control wiring


Inter-outdoor unit control wiring
6
To other system Indoor unit 2-1 2-2 2-9
link wiring
Remote control
Remote communication wiring
controller
Make settings as appropriate for the cases listed below.
7
(Refer to the instructions on the following pages.)

• Indoor and outdoor unit power can be turned ON for each system separately. Case 2

• Indoor and outdoor unit power cannot be turned ON for each system separately.
Automatic address setting in Heating mode Case 3A
8
Automatic address setting in Cooling mode Case 3B

Fig. 5-6

5-7 9

5GEKPFF 
Test Run

4. Auto Address Setting

Case 2 Automatic Address Setting (no compressor operation)


Indoor and outdoor unit power can be turned ON for each system separately.
Indoor unit addresses can be set without operating the compressors.

Automatic Address Setting from Outdoor Unit


1. On the outdoor main unit control PCB, check that the system address rotary switch (SW1) is set to “1” and that the DIP
ON ON
switch (SW2) is set to “0.” .
1 2
OFF
(These are the settings at the time of factory shipment.)
2. To set the number of indoor units that are connected to the outdoor unit to 13, on the outdoor main unit control PCB set
ON ON
the No. of indoor units DIP switch (SW4) to “1” , and set the rotary switch (SW3) to “3.”
1 2 3
OFF

3. To set the number of outdoor units, on the outdoor main unit control PCB set the No. of outdoor units DIP switch (SW6) to
1 ON

1 2
ON

3
(3 units).
OFF
ON
4. On the No. 1 (main) unit control PCB, set the unit No. switch (SW5) to (unit No. 1).
1 2 3

ON
On the No. 2 (sub) unit control PCB, set the unit No. switch (SW5) to (unit No. 2).
2 1 2 3

ON
On the No. 3 (sub) unit control PCB, set the unit No. switch (SW5) to (unit No. 3).
1 2 3

5. At the outdoor main unit where all indoor and outdoor unit power has been turned ON, short-circuit the automatic address
pin (CN30) for 1 second or longer, then release it.
3 ↓
(Communication for automatic address setting begins.)
↓ * To cancel, again short-circuit the automatic address pin (CN30) for 1 second or longer, then release it.
The LED that indicates automatic address setting is in progress turns OFF and the process is stopped.
Be sure to perform automatic address setting again.
4 (Automatic address setting is completed when LEDs 1 and 2 on the outdoor main unit control PCB turn OFF.)

6. Next turn the power ON only for the indoor and outdoor units of the next (different) system. Repeat steps 1 – 5 in the same
way to complete automatic address settings for all systems.

5 7. Operation from the remote controllers is now possible.
* To perform automatic address setting from the remote controller, perform steps 1 – 4, then use the remote controller and
complete automatic address setting.
Refer to “Automatic Address Setting from the Remote Controller.”

9 5-8

5GEKPFF 
Test Run

4. Auto Address Setting

Case 3A Automatic Address Setting in Heating Mode


Indoor and outdoor unit power cannot be turned ON for each system separately.
In the following, automatic setting of indoor unit addresses is not possible if the compressors are not operating.
Therefore perform this process only after completing all refrigerant tubing work.

Automatic Address Setting from Outdoor Unit

1. Perform steps 1 – 4 in the same way as for Case 2 .


5. Turn the indoor and outdoor unit power ON at all systems.

6. To perform automatic address setting in Heating mode , on the outdoor main unit control PCB in the refrigerant system
where you wish to set the addresses, short-circuit the automatic address pin (CN30) for 1 second or longer, then release it.
(Be sure to perform this process for one system at a time. Automatic address settings cannot be performed for more than
one system at the same time.)
1

(Communication for automatic address setting begins, the compressors turn ON, and automatic address setting in
Heating mode begins.)
(All indoor units operate.)
* To cancel, again short-circuit the automatic address pin (CN30) for 1 second or longer, then release it.
2
↓ The LED that indicates automatic address setting is in progress turns OFF and the process is stopped.
Be sure to perform automatic address setting again.

(Automatic address setting is completed when the compressors stop and LEDs 1 and 2 on the main unit control PCB
turn OFF.) 3

7. At the outdoor main unit in the next (different) system, short-circuit the automatic address pin (CN30) for 1 second or longer,
then release it.

(Repeat the same steps to complete automatic address setting for all units.)
4

8. Operation from the remote controllers is now possible.
* To perform automatic address setting from the remote controller, perform steps 1 – 5, then use the remote controller
and complete automatic address setting. 5
Refer to “Automatic Address Setting from Remote Controller.”

5-9 9

5GEKPFF 
Test Run

4. Auto Address Setting

Case 3B Automatic Address Setting in Cooling Mode


Indoor and outdoor unit power cannot be turned ON for each system separately.
In the following, automatic setting of indoor unit addresses is not possible if the compressors are not operating.
Therefore perform this process only after completing all refrigerant tubing work.
Automatic address setting can be performed during Cooling operation.

Automatic Address Setting from Outdoor Unit


1. Perform steps 1 – 4 in the same way as for Case 2 .
5. Turn the indoor and outdoor unit power ON at all systems.

6. To perform automatic address setting in Cooling mode , on the outdoor main unit control PCB in the refrigerant system
where you wish to set the addresses, place the mode select 3P pin (CN40) in the cooling side. At the same time,
short-circuit the automatic address pin (CN30) for 1 second or longer, then release it. (Be sure to perform this process for
.
1 one system at a time Automatic address settings cannot be performed for more than one system at the same time.)

(Communication for automatic address setting begins, the compressors turn ON, and automatic address setting in
Cooling mode begins.)
(All indoor units operate.)
2 * To cancel, again short-circuit the automatic address pin (CN30) for 1 second or longer, then release it.
↓ The LED that indicates automatic address setting is in progress turns OFF and the process is stopped.
Be sure to perform automatic address setting again.

(Automatic address setting is completed when the compressors stop and LEDs 1 and 2 on the outdoor main unit control
3 PCB turn OFF.)

7. At the outdoor main unit in the next (different) system, short-circuit the automatic address pin (CN30) for 1 second or longer,
then release it.

4 (Repeat the same steps to complete automatic address setting for all units.)

8. Operation from the remote controllers is now possible.
* Automatic address setting in Cooling mode cannot be done from the remote controller.

5 Automatic Address Setting* from the Remote Controller


Selecting each refrigerant system individually for automatic address setting
---Automatic address setting for each system: Item code “A1”
1. Press the remote controller timer time button and button at the
same time. (Press and hold for 4 seconds or longer.)
6 2. Next, press either the temperature setting or button.
(Check that the item code is “A1.”)
3. Use either the or button to set the system No. to perform
automatic address setting.
7 4. Then press the button.
(Automatic address setting for one refrigerant system begins.)
(When automatic address setting for one system is completed, the system
returns to normal stopped status.) <Approximately 4 – 5 minutes is
required.> (During automatic address setting, “ SETTING ” is displayed on
8 the remote controller. This message disappears when automatic address
setting is completed.)
5. Repeat the same steps to perform automatic address setting for each
successive system.

9 5-10

5GEKPFF 
Test Run

4. Auto Address Setting

Adjustment of Termination Resistor (Plug)


Communication error will occur if improper adjustment is made.
• When connecting the centralized control system, it is necessary to adjust the termination resistor (terminal
plug: CN67).
Even if no connection is made, confirmation is required for VRF systems.

• Termination resistor is placed on the outdoor unit control PCB.


• Centralized control system : Intelligent Controller (CZ-256ESMC2)
System Controller (CZ-64ESMC2)
Schedule Timer (CZ-ESWC2)
ON/OFF Controller (CZ-ANC2)
P-AIMS Basic software (CZ-CSWKC2)

• If the termination resistor of this inter-outdoor unit control wiring is 1 refrigerant system, short-circuit 1 location 1
(remains unchanged at shipment).
If there are more than 2 refrigerant systems, short-circuit 2 locations (remains unchanged at shipment).
In order to stabilize communication, 2 short circuit locations shall be at both sides (remains unchanged at
shipment). Open-circuit the refrigerant systems except for 2 locations mentioned above.
More than 3 short circuit locations of the termination resistors are prohibited (remains unchanged at shipment). 2
• There is no necessary to adjust the termination resistor (short circuit remained at shipment) because VRF
systems for combination of sub outdoor units are not connected to the control wiring.

If link wiring is not used


Short-circuit 1 termination resistor plug of the unit No.1 main outdoor unit (remains unchanged at shipment). 3
Centralized Unit Unit Unit
control Outdoor unit No. 1 No. 2 No. 3
system (Main) Inter-outdoor unit (Sub) Inter-outdoor unit (Sub)
control wiring control wiring
Inter-unit control wiring 4

Indoor unit 1-1 1-2 1-3 1-10


Remote control
Remote controller communication wiring 5
Setting of terminal plug (CN67)
Outdoor unit control PCB
Unit No. 1 (Main) : short-circuit (at shipment)
Short-circuit 1 termination resistor plug (remains unchanged at shipment).
Unit No. 2 (Sub) : short-circuit (at shipment)
Unit No. 3 (Sub) : short-circuit (at shipment) 6

7
CN67
SHORT

5-11 9

5GEKPFF 
Test Run

4. Auto Address Setting

If link wiring is used


Short-circuit 2 termination resistors plug (remains unchanged at shipment).
In order to stabilize communication, 2 short circuit locations shall be at both sides (remains unchanged at shipment).
Setting of terminal plug (CN67)
Refrigerant circuit No. No. 1 No. 2 to n-1 No. n
Unit No. 1 (Main) short-circuit (at shipment) open-circuit short-circuit (at shipment)
Unit No. 2 (Sub) short-circuit (at shipment) short-circuit (at shipment) short-circuit (at shipment)
Unit No. 3 (Sub) short-circuit (at shipment) short-circuit (at shipment) short-circuit (at shipment)

Centralized Leave the socket that is


control Outdoor unit Unit Unit Unit
No. 1 used to short-circuit the No. 2 No. 3
system system 1
(Main) terminal plug. (Sub) (Sub)
(CN67)
Inter-outdoor unit control wiring Inter-outdoor unit control wiring

1 No. 1
Refrigerant Inter-unit control wiring
circuit
Indoor unit 1-1 1-2 1-3 1-10
Remote control
Remote communication wiring
2 controller

No. 2
Refrigerant Outdoor unit Unit Unit Unit
circuit Move the sockets to the
system 2 No. 1 No. 2 No. 3
(Main) “OPEN” side. (CN67) (Sub) (Sub)

Inter-outdoor control wiring Inter-outdoor unit control wiring


3 Inter-unit control wiring

Indoor unit 2-1 2-2 2-3 2-10


Remote control
Remote
4 controller
communication wiring

No. n
Refrigerant Leave the socket that is
Outdoor unit Unit Unit Unit
circuit No. 1
used to short-circuit the No. 2 No. 3
system n terminal plug.
(Main) (Sub) (Sub)
(CN67)

5 Inter-outdoor unit control wiring Inter-outdoor unit control wiring

Inter-unit control wiring

Indoor unit n-1 n-2 n-3 n-10


Remote control
6 Remote
controller
communication wiring
Between conductors
Final Check Wire
Be sure to check before operation.
Final check must be done under the conditions of inter-outdoor unit control wiring Wire
connected to the centralized control system and the resistor between conductors
7 must be measured by a Megger. Check if it is showing between 30Ω and 120Ω.
If the resistance value is out of range, check adjustment of the termination resistor again. Between wiring and ground
Even if it is out of range, the problem is caused by wiring. Wire
• Is the wiring connection properly completed?
• Are there any scratches or deterioration on the coverage? Wire

8 • Measure between conductors and also between wiring and ground by 500V Megger
insulation resistance tester. Make sure the Megger is showing more than 100MΩ.
When measuring, remove both ends of the wiring from the terminal board. Ground Ground
If not removed, it will be damaged. If it is less than 100MΩ, a new wiring connection
should be made.

9 5-12

5GEKPFF 
Test Run

4. Auto Address Setting

Display during automatic address setting


On outdoor main unit PCB
LED 2 1
* Do not short-circuit the automatic address setting pin (CN30) again while automatic address setting is
in progress. Doing so will cancel the setting operation and will cause LEDs 1 and 2 to turn OFF.
Blink alternately

* When automatic address setting has been successfully completed, both LEDs 1 and 2 turn OFF.
* If automatic address setting is not completed successfully, refer to the table below and correct the problem.
Then perform automaticaddress setting again.

Display details of LEDs 1 and 2 on the outdoor unit control PCB


( : ON : Blinking : OFF)
LED 1 LED 2 Display meaning

After the power is turned ON (and automatic address setting is not in progress), no communication with
the indoor units in that system is possible. 1
After the power is turned ON (and automatic address setting is not in progress), 1 or more indoor units are
confirmed in that system; however, the number of indoor units does not match the number that was set.

Automatic address setting is in progress.


Alternating
Automatic address setting completed.
2
At time of automatic address setting, the number of indoor units did not match the number that was set.
Simultaneous “ ” (when indoor units are operating) indication appears on the display.

Alternating
Refer to “Table of Self-Diagnostic Functions and Description of Alarm Displays.”
3
Note: “ ” indicates that the solenoid is fused or that there is a CT detection current failure (current is detected when the
compressor is OFF).

Remote controller display


SETTING is blinking
4

5-13 9

5GEKPFF 
Test Run

4. Auto Address Setting

Request concerning recording the indoor/outdoor unit combination Nos.


After automatic address setting has been completed, be sure to record them for future reference.
List the outdoor main unit system address and the addresses of the indoor units in that system in an easily visible location
(next to the nameplate), using a permanent marking pen or similar means that cannot be abraded easily.
Example: (Outdoor) 1 – (Indoor) 1-1, 1-2, 1-3…
(Outdoor) 2 – (Indoor) 2-1, 2-2, 2-3…
These numbers are necessary for later maintenance. Please be sure to indicate them.

Checking the indoor unit addresses


Use the remote controller to check the indoor unit address.
<If 1 indoor unit is connected to 1 remote controller>
1. Press and hold the button and button for 4 seconds or longer (simple settings mode).
1 2. The address is displayed for the indoor unit that is connected to the remote controller.
(Only the address of the indoor unit that is connected to the remote controller can be checked.)
3. Press the button again to return to normal remote controller mode.

2 Individual Control of Solenoid Valve kit


How to change the setting for utilizing the solenoid valve kit in the indoor unit in common.
Setting change may be necessary due to the type of connection of the solenoid valve kit and indoor unit as shown below.
Be sure to change according to the following method.

3 Method 1 Method 1 Method 2 Method 3 Method 3


Solenoid Solenoid Solenoid Solenoid Solenoid Solenoid
valve kit valve kit valve kit valve kit valve kit valve kit

Indoor Indoor Indoor Indoor Indoor Indoor Indoor Indoor Indoor Indoor Indoor
Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit

4 Remote
Controller
Remote
Controller
Remote
Controller
Remote Remote
Controller Controller
Remote Remote Remote
Controller Controller Controller

9 5-14

5GEKPFF 
Test Run

4. Auto Address Setting

Chart of setting change according to each method


* An alarm will occur or the air conditioner will not operate properly unless proper setting changes are performed.
Be sure to change the setting as follows.

Shared solenoid Change necessary


Combination valve kit Change of indoor unit How to change
YES/NO
YES/NO
Method 1 only NO NO — —
Method 2 included Method 2 only From indoor unit *1
*method 3 excluded YES YES

Method 3 included YES YES All indoor units From PC *2

*1 How to change the setting from the remote controller


Be sure to make a setting when utilizing the shared solenoid valve kit by Method 2.
• When only utilizing the solenoid valve kit in common, make a setting from the remote controller as described below.
• Be sure to make a setting after auto address setting as described below. 1
1. Press and hold the button and button for 4 seconds or longer (simple settings mode).
2. “ALL” is displayed on the remote controller.
3. Next, press the button.
4. The address is displayed for 1 of the indoor units which is connected to the remote controller. 2
Check that the fan of that indoor unit starts and that air is discharged.
5. Press the button again and check the address of each indoor unit in sequence.
6. Press the button again to return to normal remote controller mode.

Number changes to indicate which


5
indoor unit is currently selected.
Indoor unit address

*2 How to change the setting from PC


Be sure to make a setting from a personal computer when utilizing the shared solenoid valve kit by Method 3. 6
• Setting change must be necessary at all indoor units of same refrigerant system.
• Consult how to change the setting.

5-15 9

5GEKPFF 
Test Run
5. Remote Controller Test Run Settings
6. Caution for Pump Down

5. Remote Controller Test Run Settings

1. Press the remote controller button for 4 seconds or longer. Then press the button.
“ TEST ” appears on the LCD display while the test run is in progress.
The temperature cannot be adjusted when in Test Run mode.
(This mode places a heavy load on the machines. Therefore use it only when performing the test run.)
2. The test run can be performed using the HEAT, COOL, or FAN operation modes.

Note: The outdoor units will not operate for approximately 3 minutes after the power is turned ON and after
operation is stopped.

3. If correct operation is not possible, a code is displayed on the remote controller LCD display.
(Refer to “Table of Self-Diagnostic Functions” and correct the problem.)

4. After the test run is completed, press the button again.


1 Check that “ TEST ” disappears from the LCD display.
(To prevent continuous test runs, this remote controller includes a timer function that cancels the test run after 60 minutes.)

* If the test run is performed using the wired remote controller, operation is possible even if the cassette-type ceiling panel has
not been installed. (“P09” display does not occur.)
2
6. Caution for Pump Down

Pump down means refrigerant gas in the system is returned to the outdoor unit.
Pump down is used when the unit is to be moved, or before servicing the refrigerant circuit. (Refer to the Service Manual)
3
CAUTION

This outdoor unit cannot collect more than the rated refrigerant amount as shown by the nameplate on the back.
If the amount of refrigerant is more than that recommended, do not conduct pump down.
4 In this case use another refrigerant collecting system.

9 5-16

5GEKPFF 
Test Run

7. Meaning of Alarm Messages

7. Meaning of Alarm Messages


Table of Self-Diagnostics Functions and Description of Alarm Displays
Alarm messages are indicated by the blinking of LED 1 and 2 on the outdoor unit PCB.
They are also displayed on the wired remote controller.
Viewing the LED 1 and 2 alarm displays
LED 1 LED 2 Alarm contents
Alarm display
Alternating LED 1 blinks M times, then LED 2 blinks N times. The cycle then repeats.
M = 2: P alarm 3: H alarm 4: E alarm 5: F alarm 6: L alarm
N = Alarm No.
Example: LED 1 blinks 2 times, then LED 2 blinks 17 times. The cycle then repeats.
Alarm is “P17.”
( : Blinking) Connect the outdoor maintenance remote controller to the RC socket on the outdoor main unit control PCB (3P, blue),
and check the Alarm Messages on the remote controller display.
Alarm
Possible cause of malfunction message 1
Serial Remote controller is detecting Error in receiving serial communication signal.
communication error signal from indoor unit. (Signal from main indoor unit in case of group control) <E01>
errors Ex: Auto address is not completed.
Mis-setting Error in transmitting serial communication signal. <E02>
Indoor unit is detecting error signal from remote controller (and system controller). <<E03>>
Indoor unit is detecting error signal Error in receiving serial communication signal.
When turning on the power supply, the number of connected indoor units E04
2
from main outdoor unit.
does not correspond to the number set. (Except R.C. address is “0.”)
Error of the main outdoor unit in receiving serial communication signal from
<E06>
the indoor unit.
Improper setting of indoor unit or Indoor unit address setting is duplicated. E08
remote controller. Remote controller address connector (RCU. ADR) is duplicated.
(Duplication of main remote controller)
<<E09>> 3
During auto address setting, Starting auto address setting is prohibited.
number of connected units does This alarm message shows that the auto address connector CN30 is E12
not correspond to number set. shorted while other RC line is executing auto address operation.
Error in auto address setting. (Number of connected indoor units is less
When turning on the power supply, E15
than the number set.)
number of connected units does
not correspond to number set.
Error in auto address setting. (Number of connected indoor units is more
than the number set.)
E16 4
(Except R.C. address is “0.”)
No indoor unit is connected during auto address setting. E20
Main outdoor unit is detecting error signal from sub outdoor unit. E24
Error of outdoor unit address setting. E25
The number of connected main and sub outdoor units do not correspond to
the number set at main outdoor unit PCB.
Improper wiring between main outdoor unit and sub-unit.
E26

E27
5
Error of sub outdoor unit in receiving serial communication signal from main
E29
outdoor unit.
Serial transmission failure of outdoor unit. E30
Communications trouble between
units
Indoor unit communication error of
Communication failure with MDC

Error of main indoor unit in receiving serial communication signal from sub
E31
6
E18
group control wiring. indoor units.
Improper setting. This alarm message shows when an indoor unit for multiple-use is not
connected to the outdoor unit. L02

Duplication of main indoor unit address setting in group control. <L03>


Duplication of outdoor R.C. address setting.
There are 2 or more indoor unit Priority set remote controller
L04
L05
7
controllers that have operation mode
priority in refrigerant circuit. Non-priority set remote controller L06

Group control wiring is connected to individual control indoor unit. L07


Indoor unit address is not set. L08
Capacity code of indoor unit is not set.
Capacity code of outdoor unit is not set.
<<L09>>
L10
8
Incorrect wiring of remote group control wiring
L11
(in case of shared solenoid valve kit)
Mis-matched connection of outdoor units that have different kinds of L17
refrigerant.

5-17 Continued
9

5GEKPFF 
Test Run

7. Meaning of Alarm Messages

Alarm
Possible cause of malfunction message
Activation of Protective device in indoor unit is Thermal protector in indoor unit fan motor is activated. <<P01>>
protective device activated. Improper wiring connections of ceiling panel. <<P09>>
Float switch is activated. <<P10>>
Operation of protective function of fan inverter. P12
When alarm message in other indoor units occurs in case of group control,
<P31>
unalarmed state of indoor units are inoperative.
Activation of Protective device in outdoor unit is Compressor thermal protector is activated.
protective device activated. Power supply voltage is unusual. (The voltage is more than 260 V or less than P02
160 V between L and N phase.)
Incorrect discharge temperature. (Comp. No. 1) P03
High pressure switch is activated. P04
Negative (defective) phase. P05
O2 sensor (detects low oxygen level) activated P14
1 DCCT overcurrent P16
Incorrect discharge temperature. (Comp. No. 2) P17
Outdoor unit fan motor is unusual. P22
IPM trip (IPM current or temperature) H31
Inverter for compressor is unusual. (DC compressor does not operate.) P29

2 Thermistor fault Indoor thermistor is either open or


damaged.
Indoor coil temp. sensor (E1)
Indoor coil temp. sensor (E2)
<<F01>>
<<F02>>
Indoor coil temp. sensor (E3) <<F03>>
Indoor suction air (room) temp. sensor (TA) <<F10>>
Indoor discharge air temp. sensor (BL) <<F11>>
Outdoor thermistor is either open Comp. No. 1 discharge gas temp. sensor (DISCH1) F04
3 or damaged. Comp. No. 2 discharge gas temp. sensor (DISCH2)
Outdoor No. 1 coil gas temp. sensor (EXG1)
F05
F06
Outdoor No. 1 coil liquid temp. sensor (EXL1) F07
Outdoor air temp. sensor (AIR TEMP) F08
Compressor intake temperature sensor (SCT) F12

4 Temp. sensor at refrigerant gas outlet of dual-tube (SCG)


High pressure sensor failure. High pressure trouble.
F14
F16
Low-pressure sensor failure F17
Outdoor No. 2 coil gas temp. sensor (EXG2) F23
Outdoor No. 2 coil liquid temp. sensor (EXL2) F24
EEPROM on indoor unit PCB failure F29
5 EEPROM on the main or sub outdoor unit PCB has failed.
Compressor No. 1 current trouble (overcurrent)
F31
H01
Protective device Protective device for compressor
for compressor is No. 1 is activated. Current is not detected when comp. No. 1 is ON. H03
activated
Protective device for compressor Compressor No. 2 current trouble (overcurrent) H11
No. 2 is activated. Compressor No. 2 current trouble (locked) H12
Compressor No. 2 CT sensor disconnected or short circuit H13
6 Compressor No. 2 discharge temp. sensor disconnected H15
Low pressure switch is activated. H06
Oil sensor fault. Comp. No. 1 oil sensor H08
(Disconnection, etc.) Comp. No. 2 oil sensor H27

Continued
7

9 5-18

5GEKPFF 
Test Run

7. Meaning of Alarm Messages

Alarm messages displayed on system controller


Serial Error in transmitting serial Indoor or main outdoor unit is not operating correctly.
communication communication signal Mis-wiring of control wiring between indoor unit, main outdoor unit C05
errors and system controller.
Mis-setting Error in receiving serial Indoor or main outdoor unit is not operating correctly.
communication signal Mis-wiring of control wiring between indoor unit, main outdoor unit
C06
and system controller.
CN76 is not connected properly.
Activation of Protective device of sub indoor When using wireless remote controller or system controller, in order
protective unit in group control is to check the alarm message in detail, connect wired remote controller P30
device activated. to indoor unit temporarily.

NOTE

1. Alarm messages in << >> do not affect other indoor unit operations. 1
2. Alarm messages in < > sometimes affect other indoor unit operations depending on the fault.

5-19 9

5GEKPFF 
– MEMO –

5-20

5GEKPFF 
Electrical Data

Contents

6. ELECTRICAL DATA
1. Outdoor Unit .................................................................................................. 6-2
(1) U-8MF2E8/10MF2E8 .................................................................................................. 6-2
(2) U-12MF2E8 ................................................................................................................. 6-4
(3) U-14MF2E8/16MF2E8 ................................................................................................. 6-6

2. Indoor Unit
* Refer to the 2WAY SYSTEM TECHNICAL DATA (TD831159)

6-1
6- 9

名称未設定-1
Sec6.indd 11 2012/10/25
2012/11/22 18:19:35
14:52:46
Electrical Data

1. Outdoor Unit

(1) Electric Wiring Diagram U-8MF2E8/10MF2E8

1
1

2
2

3
3

4
4

5
5

6
6

7
7

8
8

9
9 6-2
6-

Sec6.indd 2 2012/11/22 14:52:46


Electrical Data

1. Outdoor Unit

Schematic Diagram U-8MF2E8/10MF2E8

1
1

2
2

3
3

4
4

5
5

6
6

7
7

8
8

6-3
6- 9
9

Sec6.indd 3 2012/11/22 14:52:47


Electrical Data

1. Outdoor Unit

(2) Electric Wiring Diagram U-12MF2E8

1
1

2
2

3
3

4
4

5
5

6
6

7
7

8
8

9
9 6-4
6-

Sec6.indd 4 2012/11/22 14:52:48


Electrical Data

1. Outdoor Unit

Schematic Diagram U-12MF2E8

1
1

2
2

3
3

4
4

5
5

6
6

7
7

8
8

6-5
6- 9
9

Sec6.indd 5 2012/11/22 14:52:48


Electrical Data

1. Outdoor Unit

(3) Electric Wiring Diagram U-14MF2E8/16MF2E8

1
1

2
2

3
3

4
4

5
5

6
6

7
7

8
8

9
9 6-6
6-

Sec6.indd 6 2012/11/22 14:52:49


Electrical Data

1. Outdoor Unit

Schematic Diagram U-14MF2E8/16MF2E8

6-7
6- 9

Sec6.indd 7 2012/11/22 14:52:50


– MEMO –

6-

Sec6.indd 8 2012/11/22 14:52:50


PCB and Functions

Contents

7. PCB AND FUNCTIONS


1. Outdoor Unit Control PCB .................................................................................................7-2
1-1. Outdoor Unit Control PCB A747306.............................................................................7-2
1-2. Outdoor Unit HIC PCB A747038.................................................................................. 7-3
1-3. Outdoor Unit FIL PCB A747037................................................................................... 7-4
1-4. Functions (for A747306)............................................................................................... 7-5
2. Indoor Unit Control PCB Switches and Functions
* Refer to the 2WAY SYSTEM TECHNICAL DATA (TD831159)

7-1 9

5GEKPFF 

PCB and Functions

CHK (CN23) pin STOP Suction gas temp.


(CN28) pin MODE SW5 Alarm LED (LED1) EEPROM LED (LED3) SCG (CN77) Gas sensor at
A. ADD TEST (CN40) pin
EEPROM heat exchanger 1, 2
(CN30) pin (CN22) pin DEF (CN25) SW6 SW3 SW7 Alarm LED (LED 2) memory IC (IC14) (CN61)
AP (CN24) pin

sensor (CN49)
Low-pressure
RUN (CN27) pin

Comp. discharge 2
sensor (CN56)
SW1
HIC3 (CN43)

Suction temp.
SCT (CN65)

7-2
Comp. discharge 1
sensor (CN55)
SILENT (CN33)

sensor (CN46)
High-pressure
SW2
1. Outdoor Unit Control PCB

1-1. Outdoor Unit Control PCB A747306

sensor (CN54)
Oil detection
SW4

OC (CN76)
DEMAND (CN71)

fuse (FUSE3)
Control circuit
CT2, CT3 (CN35) HIC1 (CN7) Outdoor air sensor RC (CN73) RC1 (CN75)
(TO)(CN53)
FORCED STOP (CN70) CTL1, CTL2 (CN9) Liquid sensor at
HIC2 (CN10) heat exchanger 1, 2 Terminal
(CN67) EMG (CN69)
(CN60)

5GEKPFF
1

9
PCB and Functions

1. Outdoor Unit Control PCB

1-2. Outdoor Unit HIC PCB A747038

NU W V U P

7-3 9

5GEKPFF 
PCB and Functions

1. Outdoor Unit Control PCB

1-3. Outdoor Unit FIL PCB A747037

9 7-4

5GEKPFF 
PCB and Functions

1. Outdoor Unit Control PCB

1-4. Functions (for A747306)

A.ADD 2P plug (white): Automatic address setting pin


(CN30) Short-circuit this pin for 1 second or longer to automatically set the addresses at the
indoor units that are connected to that outdoor unit and are within the same system.
The system address is "1" at the time of shipment. Automatic address setting is
necessary even for communications lines in a single system where the inter-unit control
wiring does not cross to any other systems.
While automatic address setting is in progress, the 2 LEDs (LED1, 2: red) on the
outdoor unit control PCB blink alternately. (Short-circuiting this pin while automatic
address setting is in progress will stop the automatic address setting operation.)

SW1 Rotary switch (10 positions, black): Outdoor system address setting switch
The setting is "1" at the time of shipment. It is not necessary to change the setting if
wiring is connected only to an outdoor unit and indoor units in a single system and the
inter-unit control wiring does not cross multiple systems.
If wiring links the inter-unit control wiring for multiple systems to the same 1
communications lines, then a different address must be set for each refrigerant tubing
system.
If wiring links multiple systems, a maximum of 30 systems (up to 64 indoor units) can be
connected. This setting can be set up to "39," however control will be for 30 systems
even if the setting is set to higher than 30. An alarm will be displayed if system
addresses are duplicated. (For details, refer to Table 1.) 2
SW2 DIP switch (2P, black): Switches for setting system address 10s digit and 20s digit
If 10 systems or more are set, the setting is made by a combination of this DIP switch
and SW1.
If 10 - 19 systems are set, set switch 1 (10s digit) to ON.
If 20 - 29 systems are set, set switch 2 (20s digit) to ON, and set switch 1 (10s digit) to 3
OFF.
If 30 systems are set, set both switch 1 (10s digit) and switch 2 (20s digit) to ON.
(For details concerning SW1 and SW2, refer to Table 1.)

SW3 Rotary switch (10 positions, red): Switch for setting the number of connected indoor units
In order to allow the outdoor unit to manage indoor units in the same refrigerant system, 4
set the number of connected indoor units. (For details, refer to Table 2.)

SW4
DIP switch (3P, blue): Switches for setting the 10s, 20s, and 30s digit for the number of
connected indoor units
If 10 systems or more are set, the setting is made by a combination of this DIP switch
and SW3.
5
If 10 - 19 systems are set, set only switch 1 (10s digit) to ON.
If 20 - 29 systems are set, set switch 2 (20s digit) to ON, and set switch 1 (10s digit) to
OFF.
If 30 - 39 systems are set, set only switch 3 (30s digit) to ON.
(For details concerning SW3 and SW4, refer to Table 2.)
6
SW6 DIP switch (3P, blue): Switch for setting the number of outdoor units
Turn the switches ON according to the number of outdoor units (1 - 3). (For details, refer
to Table 3.)

SW5 DIP switch (3P, blue): Unit No. setting switch 7


The setting is "1" at the time of shipment. (For details, refer to Table 4.)

SW7 DIP switch (4P, black): Backup operation switch


If an INV compressor has malfunctioned, turn INV ON and Back Up SW ON to operate the
outdoor unit using only the constant-speed compressor.
If a constant-speed compressor has malfunctioned, turn AC1 ON and Back Up SW ON to 8
operate the outdoor unit using compressors other than AC1. (Disconnect the wiring from the
malfunctioning constant-speed compressor.)

7-5 9

5GEKPFF 
PCB and Functions

1. Outdoor Unit Control PCB

LED1, 2 LED (red 2)


LED 1 and 2 blink alternately while automatic address setting is in progress.
Display the alarm contents for alarms which were detected by the outdoor unit.

Run 2P plug (black): Start pin


(CN27)
Short-circuit this pin and apply a pulse signal to start all indoor units in that refrigerant system.

Stop 2P plug (black): Stop pin


(CN28)
Short-circuit this pin and apply a pulse signal to stop all indoor units in that refrigerant system.

AP 2P plug (black): Vacuuming pin


(CN24)
To perform vacuuming of the outdoor unit, short-circuit this pin and then turn the power
1 ON. All solenoid valves turn ON and vacuuming begins smoothly. (Do not perform
automatic address setting at this time.)
Release the short-circuit to return the unit to normal status.

Mode 3P plug (black): Indoor unit Heating/Cooling mode change pin


(CN40)
When operating the compressors to perform automatic address setting, operation in
2 Heating mode can be normally used. However, short-circuiting this pin performs
operation in Cooling mode. (Static signal)
Short-circuiting this pin during ordinary operation changes the mode from Cooling to
Heating (if the current mode is Cooling) or from Heating to Cooling (if the current mode
is Heating).

3 Test
(CN22)
2P plug (black)
This pin is used to test the PCB at the factory.
When the power is turned ON after this pin has been short-circuited, all output signals
will be output in sequence. (Sequential output does not occur if this pin is short-circuited
when the power is already ON.) Releasing this pin returns the unit to normal control.

4 CHK 2P plug (black)


(CN23) Short-circuit during the test run operation.
Open the circuit after the test run.

SILENT 2P plug (White) : Socket for silent mode


5 (CN33) Used for installing the external timer for the silent mode.
(Refer to the section 1 “5-6. Silent mode” in service manual.)

DEMAND Plug for Demand Terminal (optional CZ-CAPDC3)


(CN71)
6 FORCED STOP Plug for Demand Terminal (optional CZ-CAPDC3)
(CN70)

9 7-6

5GEKPFF 
PCB and Functions

1. Outdoor Unit Control PCB

Table 1.
Setting the System Address
[SW1: Rotary switch (black), SW2: 2P DIP (black)]
(for A747306)
SW1 SW2 setting SW1 SW2 setting
Outdoor Outdoor
setting setting
system system
(system 1P 2P (system 1P 2P
address address
address (10s digit) (20s digit) address (10s digit) (20s digit)
No. No.
switch) switch)
1 refrigerant 20 0 OFF ON
1 0 OFF OFF
system only 21 1 OFF ON
1 1 OFF OFF 22 2 OFF ON
2 2 OFF OFF 23 3 OFF ON
3 3 OFF OFF 24 4 OFF ON
4 4 OFF OFF Link wiring 25 5 OFF ON
5 5 OFF OFF 26 6 OFF ON
27 7 OFF ON
6
7
6
7
OFF
OFF
OFF
OFF 28 8 OFF ON 1
8 8 OFF OFF 29 9 OFF ON
9 9 OFF OFF 30 0 ON ON
Link wiring 10 0 ON OFF
11 1 ON OFF
12
13
2
3
ON
ON
OFF
OFF
2
14 4 ON OFF
15 5 ON OFF
16 6 ON OFF
17 7 ON OFF
18
19
8
9
ON
ON
OFF
OFF 3
Table 2. Table 3.
Setting the Number of Indoor Units Setting the Number of Outdoor Units
[SW3: Rotary switch (red), SW4: 3P DIP (blue)] [SW6: DIP switch (blue)]
Number of SW4 Setting Number of SW6 Setting
4
SW3 Setting
Indoor Units 1 2 3 Outdoor Units 1 2 3
1 1 OFF OFF OFF 1 ON OFF OFF
2 2 OFF OFF OFF 2 OFF ON OFF
3 3 OFF OFF OFF 3 ON ON OFF

9 9 OFF OFF OFF


5
Table 4.
10 0 ON OFF OFF
Setting the Unit No.
11 1 ON OFF OFF
[SW5: 3P DIP switch (blue)]
19 9 ON OFF OFF SW5 Setting
Unit No.
20
21
0
1
OFF
OFF
ON
ON
OFF
OFF 1
1
ON
2
OFF
3
OFF 6
2 OFF ON OFF
29 9 OFF ON OFF 3 ON ON OFF
30 0 OFF OFF ON
31 1 OFF OFF ON

39 9 OFF OFF ON
7
40 0 ON OFF ON
41 1 ON OFF ON

49 9 ON OFF ON
50
51
0
1
OFF
OFF
ON
ON
ON
ON 8
52 2 OFF ON ON

7-7 9

5GEKPFF 
– MEMO –

7-8

5GEKPFF 
Renewal

Contents

8. RENEWAL
1. Precautions on Renewal Design & Installation................................................................. 8-2
1. General.............................................................................................................................. 8-2
2. Basic Points for Using Existing Tubing............................................................................... 8-2
3. VRF Renewal Kit with High-pressure SW Kit and Sight Glass .......................................... 8-3
4. Procedure for Renewal ...................................................................................................... 8-4
5. Judging Whether Possible to Reuse Existing Tubing: Judgments 1 to 5 ........................... 8-5
6. Heating Test Run and Cooling Test Run .......................................................................... 8-10
2. Reference ........................................................................................................................... 8-11
1. Purposes for Attaching VRF Renewal Kit ........................................................................ 8-11
2. Type of oil......................................................................................................................... 8-11
3. Oil discoloration ............................................................................................................... 8-11
4. Oil color standards for renewal ........................................................................................ 8-12 1
5. Standards for judging refrigerant with sight glass............................................................ 8-12
3. INSTALLATION INSTRUCTIONS (VRF Renewal Kit) ...................................................... 8-13

8-1 9

5GEKPFF 
Renewal

1. Precautions on Renewal Design & Installation

1. General
VRF *1 adopts the refrigerant R410A that has a higher pressure than conventional refrigerants, but it uses high-
precision microcomputer control to enable operation at a "design pressure of 3.3 MPa," which is around the same
as that before the refrigerant R410A was adopted. This means that you can use refrigerant tubing for R22 *2.
Furthermore, if certain conditions are satisfied, you can reuse existing tubing by attaching one VRF Renewal Kit
(CZ-SLK2) to each outdoor unit.
When performing the work, check the "DESIGN of VRF SYSTEM" section together with this section.

NOTE
*1. Systems for 2WAY VRF (ME1E81 series: only 8HP ~ 16HP), MINI VRF and 3WAY VRF.
*2. Refrigerant tubing R22 has a maximum working pressure of 3.45 MPa and can be used for refrigerants such as
R22 and R407C.

2. Basic Points for Using Existing Tubing


For existing tubing to be reused, the condition of the tubing needs to satisfy the basic points of "Safety" and
1 "Cleanliness". First, confirm that the condition of the existing tubing satisfies the following check items.

„ Safety
• The existing unit shall be an air conditioner for use with R22/R407C/R410A refrigerant.
The reuse of existing tubing and the like that has been used for an application other than air conditioning
2 (refrigerating device, etc.) is prohibited because it is difficult to know the situation.
• The tubing shall not be dented, cracked, corroded, etc.
Checking whether existing tubing is damaged, dented, and the like and the reliability of tubing strength is the
responsibility of the installer performing the installation and is not guaranteed by us.
• The maximum working pressure of branches shall be 3.3 MPa or more. Furthermore, the branches shall be
3 our genuine products.
We do not guarantee the tubing strength of any branch that is not a genuine product of us.
• The thermal insulation material shall not be decayed and peeling off.
If there is no thermal insulation installed on the liquid tubing, thermal insulation needs to be installed.

4 „ Cleanliness
• The oil of the existing unit shall be any one of the following.
Mineral oil : Suniso, Freol S and MS
Synthetic fluid : Alkyl benzene-type (HAB, Barrel-freeze), ester-type, ether-type (PVE only)
• The existing tubing shall be connected to the indoor unit and outdoor unit and be air tight.
5 Using tubing that is dirty inside as is may cause a failure of the new equipment.
• Trouble with foreign material contaminating the inside of the tubing shall not have occurred during the period
with which the existing unit was used (layer short in compressor, clogging caused by moisture freezing, oxide
scale, etc.). If such trouble has occurred, appropriate measures shall have been taken.
Using tubing that is dirty inside as is may cause a failure of the new equipment.
6

9 8-2

5GEKPFF 
Renewal

1. Precautions on Renewal Design & Installation

3. VRF Renewal Kit with High-pressure SW Kit and Sight Glass

The following shows an overview of the VRF Renewal Kit (CZ-SLK2) that is required when existing tubing is reused.
If the exact tube length and tube size of the existing tubing are uncertain, attach a sight glass in accordance withthe figure below.
It will be used for checking the amount of additional refrigerant charge (calculating the amount inJudgment 4).

VRF Renewal Kit: CZ-SLK2


Filter Drier Charge Port Unit : mm

B A A B
Outdoor unit side Indoor unit side

445 (12, 14, 16HP)

535 (8, 10HP)


1
Connecting tube dimensions
A : ø12.7 (12, 14, 16HP)
B : ø9.52 (8, 10HP)

NOTE 2
If the tube size does not match that of the existing tubing, use a reducer (field supply) to adjust the tube diameter.

Attaching the VRF Renewal Kit, sight glass and High-pressure SW Kit
Sight glass (field supply)
High-pressure SW Kit
Outdoor Outdoor Outdoor
If the exact tube length and tube size 3
CZ-PSWK2 of the existing tubing are uncertain,
unit unit unit
attach a sight glass to the liquid
tubing, and use it to check whether
there is an appropriate amount of
additional refrigerant charge.
Suction tubing
4
Balance tubing Discharge tubing

Liquid tubing
5
Solenoid Valve Kit
VRF Renewal Kit (CZ-SLK2)
6
• VRF Renewal Kit (CZ-SLK2) shall be attached to the liquid tubing of all outdoor units.
• High-pressure SW Kit (CZ-PSWK2) shall be attached to both liquid and gas tubing of all outdoor units.
• There is no need to remove the VRF Renewal Kit (CZ-SLK2) after a test run is performed because normal operation is
possible while it is attached.
7
• When attaching the VRF Renewal Kit (CZ-SLK2), care shall be taken with regards to the installation location and orientation
of the filter drier and ball valve. If a mistake is made, the refrigerant in the system needs to be recovered when the filter drier
is replaced, which will make maintenance difficult.
• Thermal insulation material (field supply: heat resistance of 80°C or higher and thickness of 10 mm or greater) shall be 8
applied to the VRF Renewal Kit (CZ-SLK2).
• The filter drier of the VRF Renewal Kit (CZ-SLK2) may need to be replaced depending on the condition of the existing unit.
Use a Danfoss DMB 164 as the replacement filter drier.

8-3 9

5GEKPFF 
Renewal

1. Precautions on Renewal Design & Installation

4. Procedure for Renewal


After checking "2. Basic Points for Using Existing Tubing," perform the work in accordance with the renewal flow
below. When performing the work, also check the "DESIGN of VRF SYSTEM" section.

Renewal flow

Judgment 1: Is the existing tubing reusable as refrigerant tubing?


Judgment 2: Are the tubing length and installation height
difference of the existing tubing within the
tolerance ranges of the new system?
Judgment 3: Is the existing tubing within the ranges of reusable
tube size?
Judgment 4: Is the additional refrigerant charge at or below the
upper limit?
Impossible to reuse
1 Can existing tubing New tubing needs
be reused? to be installed.
No problem with Judgments 1 to 4 Cooling is
not possible.
Recover refrigerant
Can the existing unit perform
2 the cooling operation?
with refrigerant
recovery machine
Yes
Perform the cooling operation for at least 15 minutes, and then perform
a pump down to recover refrigerant in the existing unit.

3 Remove the existing indoor and outdoor units


Judgment 5 There is dirt applicable
Is there a problem with dirt to Judgment 5.
inside the existing tubing?
4 No problem
Install the new indoor and outdoor units, and attach the VRF Renewal Kit (CZ-SLK2) and High-pressure
SW Kit (CZ-PSWK2).
If the exact length and the like of existing tubing are uncertain, attach a sight glass.
If the gas tube size of the main tubing is three sizes larger, add oil. (Judgment 3 item)
5 Perform an air-tightness test, air purge, and refrigerant charge.
If the exact tube length and tube size are uncertain, charge with the minimum amount of additional
refrigerant that was calculated in Judgment 4 for the case in which the amount of additional refrigerant
charge becomes the least. Furthermore, determine whether the minimum amount of additional
refrigerant charge resulted in an appropriate amount of refrigerant charge for the whole system when
6 you perform a cooling test run, and make adjustments to the amount of refrigerant as necessary.

Failure
Recheck Is there any history
of a failure of the compressor in Perform a heating test run.
the existing unit?
(1) Operate in the heating test run mode for 30
Cooling was
7 No
not possible.
minutes.
(2) Replace the filter driers of all outdoor units.
Recheck Could the existing
unit perform the cooling * Obtain replacement filter driers separately.
operation?
Yes
8 Perform a cooling test run.
If the minimum amount of additional refrigerant was added when the exact exist tube length and the like were
uncertain, check the condition of flowing refrigerant through the sight glass attached to the liquid tubing, and
add refrigerant to adjust the amount of refrigerant if insufficient amount of refrigerant level is detected.
However, the amount of additional refrigerant charge shall not exceed the maximum level.

9 8-4

5GEKPFF 
Renewal

1. Precautions on Renewal Design & Installation

5. Judging Whether Possible to Reuse Existing Tubing: Judgments 1 to 5


It is necessary to check whether the existing tubing satisfies the following Judgments 1 to 5 while referring to the
figure below. If the existing tubing does not satisfy the following conditions, new tubing needs to be installed.

Sample Image of Tubing of Existing Unit


Indoor unit A
[10]

Solenoid
[5] Valve Kit
Outdoor Indoor unit D
[2]
unit [1] [11] Indoor unit B [13]
[6] Solenoid
First branch [3] Solenoid
Valve Kit [8] Valve Kit

[4] Indoor unit E


[9] [14]
1
Solenoid
[7] Indoor unit C
[12] Valve Kit

Solenoid
Valve Kit
Fig. 8-1 2
Item Applicable Tubing
*1
Main tube [1]
*1
[2][3][4]
Main tube after branch
Between branch tube and solenoid valve kit tube [5][6][7][8][9]
3
Between solenoid valve kit and indoor tube [10][11][12][13][14]

*1: If a main tube after a branch is the same size as the main tubing, it shall be considered to be a main tubing.
For example, if the tube size of [3] is the same as the tube size of [1], the main tubing is [1] + [3]. 4
Judgment 1
Is the refrigerant tubing reusable?
Check whether the existing refrigerant tubing is reusable (the refrigerant tubing is for R22 or has the same or
a higher design pressure than refrigerant tubing for R22). Table 8-1 shows the thickness of reusable refrigerant
tubing. Also check the maximum working pressure for branches separately. 5
Table 8-1 Usable Refrigerant Tubing (JIS B 8607)
Material O Material 1 /2 H, H Material
Outer dia. (mm) 6.35 9.52 12.7 15.88 19.05 19.05 22.22 25.4 28.58 31.75 38.1 41.28 44.45 50.8
Thickness (mm) 0.80 0.80 0.80 1.00 1.00 1.00 1.00 1.00 1.00 1.10 1.15 1.20 1.25 1.40 6
Judgment 2
Are the tubing length and installation height difference of the existing tubing within the tolerance ranges
of the new system?
The refrigerant tubing length and installation height difference must be within the tolerance ranges of the tubing
7
length and installation height difference of the new system.

8-5 9

5GEKPFF 
Renewal

1. Precautions on Renewal Design & Installation

Judgment 3
Is the existing tubing within the reusable tube size ranges?
Check whether the tube sizes of the existing refrigerant tubing are within the usable ranges.
Tables 8-2 to 8-5 show the usable tube size ranges for each of the main tubing, main tubing after branches, and
indoor unit connection tubing.
The existing tube sizes must be checked to determine whether they are within the ranges in these tables.
Furthermore, extra oil may need to be added depending on the gas tube sizes of the main tubing.

Table 8-2 Usable Tube Size Ranges for Main Tubing [1]
Outdoor Unit Suction Tube (mm) Discharge Tube (mm) Liquid Tube (mm)
HP Normal*2 Usable Range Normal *2 Usable Range Normal *2 Usable Range
8 HP 19.05 19.05 to 28.58 *1 15.88 15.88 to 22.22 9.52 9.52 to 25.4
*1
10 HP 22.22 22.22 to 31.75 19.05 19.05 to 25.4 9.52 9.52 to 25.4
12 HP 25.4 25.4 to 38.1 *1 19.05 19.05 to 25.4 12.7 12.7 to 25.4
14 HP 25.4 25.4 to 38.1 *1 22.22 22.22 to 28.58 12.7 12.7 to 25.4
1 16 HP 28.58 28.58 to 41.28 *1 22.22 22.22 to 28.58 12.7 12.7 to 25.4
18 HP 28.58 28.58 to 41.28 *1 22.22 22.22 to 28.58 15.88 15.88 to 25.4
*1
20 HP 28.58 28.58 to 41.28 22.22 22.22 to 28.58 15.88 15.88 to 25.4
22 HP 28.58 28.58 to 41.28 *1 25.4 25.4 to 31.75 15.88 15.88 to 25.4
24 HP 28.58 28.58 to 41.28 *1 25.4 25.4 to 31.75 15.88 15.88 to 25.4
2 26 HP
28 HP
31.75 31.75 to 44.45 *1 25.4
31.75 31.75 to 44.45 *1 28.58
25.4 to 31.75 19.05
28.58 to 38.1 19.05
19.05 to 25.4
19.05 to 25.4
*1
30 HP 31.75 31.75 to 44.45 28.58 28.58 to 38.1 19.05 19.05 to 25.4
32 HP 31.75 31.75 to 44.45 *1 28.58 28.58 to 38.1 19.05 19.05 to 25.4
34 HP 31.75 31.75 to 44.45 *1 28.58 28.58 to 38.1 19.05 19.05 to 25.4
38.1 to 50.8 *1
3 36 HP
38 HP
38.1
38.1 38.1 to 50.8 *1
28.58
31.75
28.58 to 38.1 19.05
31.75 to 41.28 19.05
19.05 to 25.4
19.05 to 25.4
*1
40 HP 38.1 38.1 to 50.8 31.75 31.75 to 41.28 19.05 19.05 to 25.4
42 HP 38.1 38.1 to 50.8 *1 31.75 31.75 to 41.28 19.05 19.05 to 25.4
44 HP 38.1 38.1 to 50.8 *1 31.75 31.75 to 41.28 19.05 19.05 to 25.4
46 HP 38.1 38.1 to 50.8 *1 31.75 31.75 to 41.28 19.05 19.05 to 25.4
4 48 HP 38.1 38.1 to 50.8 *1
31.75 31.75 to 41.28 19.05 19.05 to 25.4
*1: If the gas tube size of the main tubing is three sizes larger than the normal tube size, oil needs to be added.
Add 30 cc of oil for each meter of main tubing.
*2: If the main tubing is the same or smaller than the normal tube size, the size needs to be increased.
5 • If the maximum tube length exceeds 90 m, increase the size of the gas tubing and liquid tubing to one size
larger than the normal tube size.
• If the maximum length of the main tubing exceeds 50 m, increase the size of just 50 m of only the gas tubing
of the main tubing to one size larger than the normal tube size.

9 8-6

5GEKPFF 
Renewal

1. Precautions on Renewal Design & Installation

Table 8-3 Usable Tube Size Ranges for Main Tubing after Branches [2][3][4]
Capacity after Branch*3 Suction Tube (mm) Discharge Tube (mm) Liquid Tube (mm)
(kW) Normal Usable Range Normal Usable Range Normal Usable Range
Up to 7.0 15.88 12.7 to 22.22 *1 12.7 9.52 to 19.05 9.52 9.52 to 25.4
7.1 to 8.9 15.88 15.88 to 25.4 *1 15.88 12.7 to 22.22 9.52 9.52 to 25.4
9.0 to 15.9 15.88 15.88 to 25.4 *1 15.88 12.7 to 22.22 9.52 9.52 to 25.4
16.0 to 24.9 15.88 19.05 to 28.58 *1 15.88 15.88 to 25.4 9.52 9.52 to 25.4
*1
25.0 to 29.9 15.88 22.22 to 31.75 19.05 19.05 to 28.58 9.52 9.52 to 25.4
30.0 to 36.3 15.88 25.4 to 38.1 *1 19.05 19.05 to 28.58 12.7 12.7 to 25.4
36.4 to 41.9 15.88 25.4 to 38.1 *1 22.22 22.22 to 31.75 12.7 12.7 to 25.4
42.0 to 47.5 15.88 28.58 to 41.28 *1 22.22 22.22 to 31.75 12.7 12.7 to 25.4
47.6 to 58.7 15.88 28.58 to 41.28 *1 22.22 22.22 to 31.75 15.88 15.88 to 25.4
*1
58.8 to 69.9 15.88 28.58 to 41.28 25.4 25.4 to 31.75 15.88 15.88 to 25.4
70.0 to 75.5 15.88 31.75 to 44.45 *1 25.4 25.4 to 38.1 19.05 19.05 to 25.4
75.6
98.0
to 97.9
to103.5
15.88
19.05
31.75 to 44.45 *1 28.58
38.1 to 50.8 *1 28.58
28.58 to 38.1
28.58 to 41.28
19.05 19.05 to 25.4
19.05 19.05 to 25.4
1
*1
Over 103.6 - 22.22 38.1 to 50.8 31.75 31.75 to 41.28 19.05 19.05 to 25.4
*3: How to calculate the capacity after branches
The capacity after a branch is the total capacity of all indoor units connected downstream of that branch.
The following table shows examples of calculating the capacity after branches for the case of Fig.8-1. 2
Main Tubing
Capacity after Branches
after Branches
[2] Total capacity of A+B
[3] Total capacity of C+D+E 3
[4] Total capacity of D+E

Table 8-4 Between Branch Tube and Solenoid Valve Kit Tube [5][6][7][8][9]
Indoor Unit
Horsepower (HP)
Suction Tube (mm) Discharge Tube (mm) Liquid Tube (mm) 4
0.8 HP 12.7 to 15.88 9.52 to 12.7 6.35 to 9.52
1.0 HP 12.7 to 15.88 9.52 to 12.7 6.35 to 9.52
1.3 HP 12.7 to 15.88 9.52 to 12.7 6.35 to 9.52
1.6 HP 12.7 to 15.88 9.52 to 12.7 6.35 to 9.52
2.0 HP 12.7 to 15.88 9.52 to 12.7 6.35 to 9.52 5
2.5 HP 15.88 to 15.88 12.7 to 12.7 9.52 to 9.52
3.0 HP 15.88 to 15.88 12.7 to 12.7 9.52 to 9.52
3.2 HP 15.88 to 19.05 12.7 to 15.88 9.52 to 9.52
4.0 HP 15.88 to 19.05 12.7 to 15.88 9.52 to 9.52
5.0 HP 15.88 to 19.05 12.7 to 15.88 9.52 to 9.52 6
6.0 HP 15.88 to 19.05 12.7 to 15.88 9.52 to 9.52
8.0 HP 19.05 to 25.4 15.88 to 22.22 9.52 to 12.7
10.0 HP 22.22 to 28.58 19.05 to 25.4 9.52 to 12.7

8-7 9

5GEKPFF 
Renewal

1. Precautions on Renewal Design & Installation

Table 8-5 Between Solenoid Valve Kit and Indoor Tube [10][11][12][13][14]

Indoor Unit
Gas Tube (mm) Liquid Tube (mm)
Horsepower (HP)
0.8 HP 12.7 to 12.7 6.35 to 9.52
1.0 HP 12.7 to 12.7 6.35 to 9.52
1.3 HP 12.7 to 12.7 6.35 to 9.52
1.6 HP 12.7 to 15.88 6.35 to 9.52
2.0 HP 12.7 to 15.88 6.35 to 9.52
2.5 HP 15.88 to 15.88 6.35 *4 to 9.52
3.0 HP 15.88 to 15.88 6.35 *4 to 9.52
*4
3.2 HP 15.88 to 19.05 6.35 to 9.52
4.0 HP 15.88 to 19.05 9.52 to 9.52
5.0 HP 15.88 to 19.05 9.52 to 9.52
6.0 HP 15.88 to 19.05 9.52 to 9.52
1 8.0 HP 19.05 to 25.4 9.52 to 12.7
10.0 HP 22.22 to 28.58 9.52 to 12.7
*4: If the existing liquid tube size is ø6.35, this existing tube is capable of using less than 10m in length.
If the existing liquid tube length exceeds 10m, this existing tube is incapable of using as-is.
2 Change the tube size to ø9.52 and replace with a new liquid tube.

9 8-8

5GEKPFF 
Renewal

1. Precautions on Renewal Design & Installation

Judgment 4
Is the additional refrigerant charge at or below the upper limit?
Check that the amount of additional refrigerant charge for the existing refrigerant tubing is at or below the upper
limit that is determined from the number of outdoor unit connections.
Calculate the amount of additional refrigerant charge from the liquid tubing size and total tubing length using the
same criteria as for standard units (VRF).
Table 8-6 shows the calculation formula for the amount of additional refrigerant charge.
Check the existing liquid tubing size and total tubing length of each size, and calculate the amount of additional
refrigerant charge from that result.
Also, check that the calculation result is at or below the upper limit for the amount of additional refrigerant charge
determined by the number of outdoor unit connections that is shown in Table 8-7.

If the exact tube length and tube size of the existing tubing are uncertain:
If the exact tube length and tube size of the existing tubing are uncertain, assume the case in which the
amount of additional refrigerant charge becomes the most (liquid tube = thick and tube length = long)
1
and conversely, the case in which the amount of additional refrigerant charge becomes the least
(liquid tube = thin and tube length = short), and calculate the amount of additional refrigerant charge for
each case. When you determine the amount of refrigerant, the result calculated for the maximum amount of
additional refrigerant charge must be at or below the upper limit. 2
Furthermore, make sure you calculate the minimum amount of additional refrigerant for the case in which
the amount of additional refrigerant charge becomes the least because it will be required when the actual
renewal work is performed.

Table 8-6 Calculation of Amount of Additional Refrigerant Charge 3


Liquid Tube Total Tube Amount of Additional
Sub-total (g)
Size (mm) Length (m) Refrigerant Charge (g/m)
ø 6.35 X 26 =
ø 9.52 X 56 =
ø 12.7 X 128 = Total (kg) 4
ø 15.88 X 185 =
ø 19.05 X 259 =
ø 22.22 X 366 =
ø 25.4 X 490 =
5
Table 8-7 Number of Outdoor Unit Connections and Upper Limit for Amount of Additional Refrigerant Charge
Upper Limit for Amount of Additional Refrigerant Charge
Number of Outdoor Units
3WAY VRF
1 28 kg 6
2 50 kg
3 60 kg

„ Judgment 5
Is there a problem with dirt inside the existing tubing?
7
After the existing units are removed, new tubing needs to be installed if the existing tubing is in any of the following
situations.
• There is apparently a large amount of discolored oil remaining inside the existing tubing.
Refer to the item "4. Oil color standards for renewal" in the chapter 2 "Reference".
8
• There is apparently a large amount of residue or wear debris remaining inside the existing tubing.
Oil collected with a finger feels gritty or looks glittery.

8-9 9

5GEKPFF 
Renewal

1. Precautions on Renewal Design & Installation

6. Heating Test Run and Cooling Test Run


If refrigerant recovery (pump down) could not be implemented by performing the cooling operation with the existing
unit or if there is history of a failure of the compressor in the existing unit, perform the tubing cleaning operation with
a heating test run.
• Depending on the outdoor unit type to be used for renewal installation, one additional setting has to be changed
properly before starting a test-run operation of the new system. The renewal system operating condition (design
pressure: 3.3MPa) will be set by this parameter change. Refer to the following table and be sure to change the
parameter accordingly. A maintenance remote controller for the outdoor unit is required to change the relevant
parameter. (See the maintenance remote controller’s instruction manual for further details on connections and
usage methods.)

Required Parameter setting for the renewal system


Model type Item Code Setting Data Remarks
3WAY VRF SYSTEM 4B Set to 0001 = Renewal system Setting only for Master unit
1 operation (Factory set = 0000)

a) Heating Test Run


If refrigerant recovery (pump down) could not be implemented by performing the cooling operation with the existing
unit or if there is history of a failure of the compressor in the existing unit, perform the tubing cleaning operation with
a heating test run.
2 Furthermore, it is necessary to replace the filter drier of the VRF Renewal Kit (CZ-SLK2) after you perform
the tubing cleaning operation.
Obtain and prepare a replacement filter drier in advance.

Step 1 : Perform a heating test run for 30 minutes.


3 • If a heating test run cannot be performed because there is an insufficient amount of refrigerant, add the
required minimum amount of refrigerant.

Step 2 : Stop the outdoor units manually.


Step 3 : Need to replace all filter driers of the VRF Renewal Kit (CZ-SLK2).
4 The tubing cleaning operation with the heating test run is now complete.

b) Cooling Test Run


If the exact tube length and tube size of the existing tubing are uncertain, the current condition should be one in
which the additional charging of the minimum amount of refrigerant calculated in Judgment 4 has been performed.
5 Under the condition, perform a cooling test run, adjust the appropriate amount of system refrigerant while checking
the condition of flowing refrigerant with the sight glass.

Step 1 : Start the cooling test run, and wait until the operating condition of the system stabilizes.
Step 2 : After operation stabilizes, visually observe the flowing refrigerant through the sight glass attached to the
liquid tubing. If flashing becomes visible, add refrigerant by degrees until flashing disappears.
6 • Add refrigerant in increments of approximately 1 kg.
• Check flashing after adding refrigerant when operation has stabilized after approximately 10 minutes has
elapsed.
• The amount of additional refrigerant must not exceed the maximum amount of additional refrigerant
7 calculated in Judgment 4.

Step 3 : For when maintenance is performed, fill in the total amount of additional refrigerant charge on the label
inside the outdoor unit.

8 The adjustment of the system refrigerant charge amount with the cooling test run is now complete.

9 8-10

5GEKPFF 
Renewal

2. Reference

1. Purposes for Attaching VRF Renewal Kit (CZ-SLK2)


The VRF Renewal Kit: CZ-SLK2 has functions for collecting small wear debris and residue that pass through the
strainer and absorbing moisture.
When existing tubing is reused, the VRF Renewal Kit can be used in addition to the strainer attached to the outdoor
unit to collect the wear debris and residue that remains inside the existing tubing in order to prevent them entering
inside the outdoor unit.
Furthermore, perform the tubing cleaning operation with a heating test run if there is the possibility of residue
remaining inside the existing tubing (heating test run in flow for judging whether to reuse existing tubing).
However, if the tubing cleaning operation is performed, the filter drier of the VRF Renewal Kit must be replaced after
the cleaning operation is performed.
Furthermore, it has been verified that a small amount of residue and the like is not a problem if a VRF Renewal Kit
is attached, but if there is apparently a large amount of discolored oil or residue, the existing tubing cannot be used
because there is danger of the strainer and VRF Renewal Kit becoming clogged (Judgment 5 in flow for judging
whether to reuse existing tubing).

2. Type of oil 1
The type of oil differs depending on the application and refrigerant to be used.
Furthermore, the recent diversification of compressor types as well as the severe conditions of use mean that the
additives may differ even if the type is the same.
When reusing existing tubing, the old oil remaining inside the tubing will mix with the oil for the new unit, so perform
an evaluation test by mixing an oil for R22 shown below to check that there is no problem. 2
Mineral oil : Suniso, Freol S and MS
Synthetic fluid : Alkyl benzene-type (HAB, Barrel-freeze), ester-type, ether-type (PVE only)

VRF series are filled with oil at the time of shipment.


3
3. Oil discoloration
There are two causes of oil discoloration.
1. Oxide scale or minute wear debris floating in the oil results in the oil appearing discolored.
The quality of the oil itself has not changed, so the oil can be sufficiently cleaned with the VRF Renewal Kit if
there is just a little bit of dirt. 4
However, if the oil contains a large amount of wear debris and feels gritty when touched with a fingertip or there
is apparently a large amount of residue, the existing piping cannot be used.

2. The oil is exposed to high temperatures for long periods of time resulting in the oil itself becoming discolored.
Lubrication of the compressor has deteriorated because the lubrication performance of the oil itself has been
greatly reduced. Therefore, the existing tubing cannot be used. 5
However, it has been verified that there is no adverse effect on the lubrication performance of the new system
when there is only a small amount of oil that is discolored as described above.

Remark :
Residual chlorine that causes metal to corrode may sometimes be included in the old oil.
As a countermeasure, add additives for catching the chlorine content into the oil in the VRF series so that no
6
problem occurs.

8-11 9

5GEKPFF 
Renewal

2. Reference

4. Oil color standards for renewal


In a test tube with a diameter of approximately 2 cm, collect a sample of 3 to 5 cm of oil for renewal, and then
check the oil comparing with the pattern of colors below.

Applicable Oil
Mineral oil : Suniso, Freol S and MS
Synthetic fluid : Alkyl benzene-type (HAB, Barrel-freeze), ester-type, ether-type (PVE only)

2 Tube cleaning not necessary

If moisture is mixed with the oil, an increase in friction (abnormal friction) or rusting may result in damage to the
system.
3 If moisture is mixed with the oil and the oil is whitish, it is necessary to clean the tubing or install a new tubing.

New Oil Oil Containing Moisture


New oil is transparent. If moisture mixes with the oil, the oil
emulsifies and the level of transparency is reduced, so it
becomes difficult to see through to the other side of the test
4 tube.

5. Standards for judging refrigerant with sight glass


If the exact tube length and tube size of existing tubing are uncertain, you can check with the sight glass whether
there is an appropriate amount of additional refrigerant charge.
5 Check the condition after operation has stabilized during the cooling test run.
Outdoor unit stopped Outdoor unit activated
Refrigerant not activated : Flashing : A few bubbles occur :
As the refrigerant is The amount of refrigerant is not There seems to be nothing inside
transparent, the bottom of satisfied with the standard level. the sight glass because the
6 the sight glass is visible. The refrigerant forms bubbles and refrigerant is transparent and full.
seems whitish overall. When the operating condition
Add refrigerant until the changes, a few bubbles occur.
appropriate level is reached. No additional refrigerant charge
required.
7

9 8-12

5GEKPFF 
Renewal

3. INSTALLATION INSTRUCTIONS (VRF Renewal Kit)

Check the parts of the VRF Renewal Kit (CZ-SLK2) you purchased.
Name Shape Quantity Name Shape Quantity
(1) Filter drier 1 (3) Tube 1 (for ø12.7) 2

(2) Valve 1 (4) Tube 2 (for ø9.52) 2

1. How to attach the VRF Renewal Kit (CZ-SLK2)


1-1. Assemble and use parts (1) to (4) in the figure above in accordance with the table below.
Outdoor Unit Type Parts Quantity Outdoor Unit Type Parts Quantity
(1), (2) 1 (1), (2) 1
4, 5, 6, 8, 10 HP 12, 14, 16 HP
(3), (4) 2 (3) 2

1-2. Connect each part in accordance with the figure below.


Charge port Unit: mm
B A A B
1

80
Outdoor unit Indoor unit
side side
445 (12, 14, 16 HP) 177
535 (4, 5, 6, 8, 10 HP)

A B
Connection part dimensions (shows tube inside diameters)
ø12.7 ø9.52
2
Attach the valve to the indoor unit side as viewed from the filter drier.
If the tube size does not match the existing tube size, use a reducer (field supply) to adjust the tube
diameter.
1-3. Attach the VRF Renewal Kit to each outdoor unit.
3
1-4. Cut the existing tubing on site with a pipe cutter or the like and attach the VRF Renewal Kit according to the
rough indication of the dimensions for attaching the VRF Renewal Kit shown in the figure above.

2. Tightening flare nuts and brazing


Use a tightening torque of 55±6 N·m for the flare nuts.
Be sure to use a wet cloth or the like to cool the valve main part and filter drier when you perform the
4
brazing process.
Also, be sure to replace the air inside the tube with nitrogen to Use a wet cloth or the like to
cool these parts.
prevent the formation of an oxide film when you perform the
brazing process.
There is a risk of system malfunction through clogging of the 5
strainer or refrigerant circuit when the brazing is performed
without nitrogen gas replacement in the tube.

3. Opening and closing the valve


6
Open state Closed state
The valve is opened at the time
of shipment from the factory.

7
4. Leak testing
Perform a leak test for the brazing parts and flare connections parts.
For the leak test, refer to " Installation Instructions" supplied with the outdoor unit.
8
5. Attaching thermal insulation material
Make sure the thermal insulation (field supply) covers the entire kit.
Use thermal insulation material with a heat resistance of at least 80 °C and thickness of at least 10 mm.

8-13 9

5GEKPFF 
– MEMO –

8-14

5GEKPFF 
Capacity Table

Contents

9. CAPACITY TABLE

1. Capacity Ratio of Outdoor Unit .........................................................................................9-2


1-1. U-8MF2E8 (Cooling) ....................................................................................................9-2
1-2. U-8MF2E8 (Heating) ....................................................................................................9-5
1-3. U-10MF2E8 (Cooling) ..................................................................................................9-8
1-4. U-10MF2E8 (Heating) ................................................................................................9-11
1-5. U-12MF2E8 (Cooling) ................................................................................................9-14
1-6. U-12MF2E8 (Heating) ................................................................................................9-17
1-7. U-14MF2E8 (Cooling) ................................................................................................9-20
1-8. U-14MF2E8 (Heating) ................................................................................................9-23
1-9. U-16MF2E8 (Cooling) ................................................................................................9-26
1-10. U-16MF2E8 (Heating) ..............................................................................................9-29 1
2. Cooling Capacity of Indoor Unit......................................................................................9-32
2-1. 4-Way Cassette Type (U1 Type) .................................................................................9-32
2-2. 4-Way Cassette 60×60 Type (Y1 Type) ......................................................................9-52
2-3. 2-Way Cassette Type (L1 Type) ..................................................................................9-57 2
2-4. Wall Mounted Type (K1 Type) .....................................................................................9-63
2-5. Ceiling Type (T1 Type) ................................................................................................9-70
2-6. Low Silhouette Ducted Type (F1 Type) .......................................................................9-76
2-7. Low Silhouette Ducted Type (F2 Type) .......................................................................9-86 3
2-8. High Static Pressure Ducted Type (E1 Type)..............................................................9-97
2-9. Floor Standing Type (P1 Type) .................................................................................9-102
2-10. Concealed Floor Standing Type (R1 Type) .............................................................9-108
2-11. 1-Way Cassette Type (D1 Type) .............................................................................9-114
2-12. Slim Low Static Ducted Type (M1 Type) .................................................................9-119 4

9-1 9

5GEKPFF 
Capacity Table

1. Capacity Ratio of Outdoor Unit

1-1. U-8MF2E8 (Cooling) Capacity Ratio 20-130%


TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp䋮䋺㷄WB
Combination(%) Outdoor 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 20.9 3.42 24.1 3.95 24.1 3.95 24.1 3.95 27.3 4.48 30.5 5.00 33.7 5.52
-5.0 20.9 3.43 24.1 3.95 24.1 3.95 24.1 3.95 27.3 4.48 30.5 5.00 33.7 5.52
0.0 20.9 3.43 24.1 3.96 24.1 3.96 24.1 3.96 27.3 4.48 30.5 5.00 33.7 5.53
5.0 20.9 3.43 24.1 3.96 24.1 3.96 24.1 3.96 27.3 4.49 30.5 5.01 33.7 5.53
10.0 20.9 3.43 24.1 3.97 24.1 3.97 24.1 3.97 27.3 4.50 30.5 5.02 33.7 5.54
15.0 20.9 3.44 24.1 3.98 24.1 3.98 24.1 3.98 27.3 4.52 30.5 5.04 33.7 5.57
130% 20.0 20.9 3.46 24.1 4.02 24.1 4.02 24.1 4.02 27.3 4.55 30.5 5.08 33.7 5.61
25.0 20.9 3.52 24.1 4.10 24.1 4.10 24.1 4.10 27.3 4.65 30.5 5.18 33.7 5.70
30.0 20.9 3.86 24.1 4.41 24.1 4.41 24.1 4.41 27.3 4.94 30.5 5.46 33.7 5.95
35.0 20.9 4.83 24.1 5.49 24.1 5.49 24.1 5.49 27.3 6.15 30.5 6.81 32.5 6.97
40.0 20.9 5.86 24.1 6.65 24.1 6.65 24.1 6.65 26.2 6.97 27.6 6.97 29.2 6.97
43.0 20.9 6.47 23.1 6.97 23.1 6.97 23.1 6.97 24.5 6.97 25.9 6.97 27.3 6.97
46.0 20.9 6.47 21.7 6.97 21.7 6.97 21.7 6.97 22.9 6.97 24.1 6.91 24.1 6.32
1 Indoor air temp䋮䋺㷄WB
Combination(%) Outdoor 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 18.8 3.09 22.6 3.71 23.5 3.86 23.5 3.86 26.7 4.37 29.8 4.89 32.9 5.39

2 -5.0
0.0
18.8
18.8
3.09
3.09
22.6
22.6
3.71
3.71
23.5
23.5
3.86
3.86
23.5
23.5
3.86
3.86
26.7
26.7
4.38
4.38
29.8
29.8
4.89
4.89
32.9
32.9
5.39
5.40
5.0 18.8 3.09 22.6 3.71 23.5 3.87 23.5 3.87 26.7 4.38 29.8 4.90 32.9 5.40
10.0 18.8 3.10 22.6 3.72 23.5 3.88 23.5 3.88 26.7 4.39 29.8 4.91 32.9 5.42
15.0 18.8 3.10 22.6 3.73 23.5 3.89 23.5 3.89 26.7 4.41 29.8 4.93 32.9 5.44
120% 20.0 18.8 3.12 22.6 3.75 23.5 3.92 23.5 3.92 26.7 4.44 29.8 4.97 32.9 5.48
25.0 18.8 3.18 22.6 3.82 23.5 4.00 23.5 4.00 26.7 4.53 29.8 5.05 32.9 5.57

3 30.0
35.0
18.8
18.8
3.50
4.37
22.6
22.6
4.12
5.14
23.5
23.5
4.29
5.32
23.5
23.5
4.29
5.32
26.7
26.7
4.81
5.95
29.8
29.8
5.32
6.58
32.9
32.3
5.81
6.97
40.0 18.8 5.29 22.6 6.23 23.5 6.44 23.5 6.44 26.1 6.97 27.5 6.97 29.0 6.97
43.0 18.8 5.88 22.6 6.47 23.0 6.97 23.0 6.97 24.4 6.97 25.8 6.97 27.2 6.97
46.0 18.8 6.47 21.6 6.97 21.6 6.97 21.6 6.97 22.8 6.97 24.1 6.95 24.1 6.36

Indoor air temp䋮䋺㷄WB


4 Combination(%) Outdoor
:Indoor/outdoor air temp. TC
14.0
PI TC
16.0
PI TC
18.0
PI TC
19.0
PI TC
21.0
PI TC
23.0
PI TC
25.0
PI
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 16.8 2.76 20.2 3.32 23.0 3.77 23.0 3.77 26.0 4.27 29.1 4.77 32.1 5.26
-5.0 16.8 2.76 20.2 3.32 23.0 3.77 23.0 3.77 26.0 4.27 29.1 4.77 32.1 5.26
0.0 16.8 2.76 20.2 3.32 23.0 3.77 23.0 3.77 26.0 4.27 29.1 4.77 32.1 5.27
5.0 16.8 2.77 20.2 3.32 23.0 3.77 23.0 3.77 26.0 4.28 29.1 4.78 32.1 5.28
5 10.0
15.0
16.8
16.8
2.77
2.78
20.2
20.2
3.33
3.34
23.0
23.0
3.78
3.79
23.0
23.0
3.78
3.79
26.0
26.0
4.29
4.30
29.1
29.1
4.79
4.81
32.1
32.1
5.29
5.31
110% 20.0 16.8 2.79 20.2 3.36 23.0 3.82 23.0 3.82 26.0 4.33 29.1 4.84 32.1 5.35
25.0 16.8 2.85 20.2 3.42 23.0 3.90 23.0 3.90 26.0 4.42 29.1 4.93 32.1 5.43
30.0 16.8 3.14 20.2 3.71 23.0 4.17 23.0 4.17 26.0 4.67 29.1 5.17 32.1 5.67
35.0 16.8 3.94 20.2 4.62 23.0 5.15 23.0 5.15 26.0 5.75 29.1 6.35 32.1 6.94
40.0 16.8 4.76 20.2 5.59 23.0 6.24 23.0 6.24 25.8 6.93 27.4 6.97 28.9 6.97
6 43.0
46.0
16.8
16.8
5.28
5.84
20.2
20.2
6.22
6.47
23.0
21.5
6.95
6.97
23.0
21.5
6.95
6.97
24.3
22.8
6.97
6.97
25.7
24.1
6.97
6.97
27.1
24.1
6.97
6.40

Indoor air temp䋮䋺㷄WB


Combination(%) Outdoor 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
7 -10.0
kW
14.9
kW
2.45
kW
17.9
kW
2.94
kW
20.9
kW
3.43
kW
22.4
kW
3.68
kW
25.4
kW
4.16
kW
28.4
kW
4.65
kW
31.4
kW
5.13
-5.0 14.9 2.45 17.9 2.94 20.9 3.44 22.4 3.68 25.4 4.17 28.4 4.65 31.4 5.14
0.0 14.9 2.46 17.9 2.94 20.9 3.44 22.4 3.68 25.4 4.17 28.4 4.66 31.4 5.14
5.0 14.9 2.46 17.9 2.95 20.9 3.44 22.4 3.69 25.4 4.17 28.4 4.66 31.4 5.15
10.0 14.9 2.46 17.9 2.95 20.9 3.45 22.4 3.69 25.4 4.18 28.4 4.67 31.4 5.16
15.0 14.9 2.47 17.9 2.96 20.9 3.46 22.4 3.71 25.4 4.20 28.4 4.69 31.4 5.17
8 100% 20.0
25.0
14.9
14.9
2.48
2.53
17.9
17.9
2.98
3.04
20.9
20.9
3.48
3.55
22.4
22.4
3.73
3.80
25.4
25.4
4.23
4.30
28.4
28.4
4.72
4.80
31.4
31.4
5.21
5.29
30.0 14.9 2.80 17.9 3.31 20.9 3.80 22.4 4.05 25.4 4.54 28.4 5.03 31.4 5.51
35.0 14.9 3.52 17.9 4.10 20.9 4.69 22.4 4.98 25.4 5.56 28.4 6.11 31.4 6.65
40.0 14.9 4.25 17.9 4.98 20.9 5.69 22.4 6.05 25.4 6.75 27.3 6.97 28.8 6.97
43.0 14.9 4.71 17.9 5.53 20.9 6.33 22.4 6.73 24.2 6.97 25.6 6.97 27.0 6.97
46.0 14.9 5.20 17.9 6.11 20.8 6.97 21.4 6.97 22.7 6.97 23.9 6.97 24.1 6.45
9 9-2

5GEKPFF 
Capacity Table

1. Capacity Ratio of Outdoor Unit

U-8MF2E8 (Cooling) Capacity Ratio 20-130%


TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp䋮䋺㷄WB
Combination(%) Outdoor 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 13.4 2.21 16.1 2.65 18.8 3.09 20.2 3.31 22.8 3.75 25.5 4.18 28.2 4.62
-5.0 13.4 2.21 16.1 2.65 18.8 3.09 20.2 3.31 22.8 3.75 25.5 4.19 28.2 4.62
0.0 13.4 2.21 16.1 2.65 18.8 3.09 20.2 3.31 22.8 3.75 25.5 4.19 28.2 4.63
5.0 13.4 2.21 16.1 2.65 18.8 3.09 20.2 3.32 22.8 3.75 25.5 4.19 28.2 4.63
10.0 13.4 2.21 16.1 2.65 18.8 3.10 20.2 3.32 22.8 3.76 25.5 4.20 28.2 4.64
15.0 13.4 2.22 16.1 2.66 18.8 3.11 20.2 3.33 22.8 3.77 25.5 4.21 28.2 4.65
90% 20.0 13.4 2.23 16.1 2.68 18.8 3.13 20.2 3.35 22.8 3.79 25.5 4.24 28.2 4.68
25.0 13.4 2.27 16.1 2.72 18.8 3.17 20.2 3.40 22.8 3.85 25.5 4.30 28.2 4.74
30.0 13.4 2.47 16.1 2.92 18.8 3.36 20.2 3.59 22.8 4.03 25.5 4.47 28.2 4.90
35.0 13.4 3.13 16.1 3.63 18.8 4.11 20.2 4.35 22.8 4.82 25.5 5.27 28.2 5.71
40.0 13.4 3.78 16.1 4.39 18.8 4.99 20.2 5.29 22.8 5.87 25.5 6.43 28.0 6.93
43.0 13.4 4.19 16.1 4.88 18.8 5.56 20.2 5.89 22.8 6.54 25.0 6.97 26.4 6.97
46.0 13.4 4.62 16.1 5.39 18.8 6.16 20.2 6.53 22.2 6.97 23.5 6.97 24.1 6.66

Indoor air temp䋮䋺㷄WB


1
Combination(%) Outdoor 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 11.9 1.96 14.3 2.36 16.7 2.74 17.9 2.94 20.3 3.33 22.7 3.72 25.1 4.11
-5.0 11.9 1.96 14.3 2.36 16.7 2.75 17.9 2.94 20.3 3.33 22.7 3.72 25.1 4.11
0.0
5.0
11.9
11.9
1.96
1.96
14.3
14.3
2.36
2.36
16.7
16.7
2.75
2.75
17.9
17.9
2.94
2.95
20.3
20.3
3.34
3.34
22.7
22.7
3.73
3.73
25.1
25.1
4.11
4.11
2
10.0 11.9 1.97 14.3 2.36 16.7 2.75 17.9 2.95 20.3 3.34 22.7 3.73 25.1 4.12
15.0 11.9 1.97 14.3 2.37 16.7 2.76 17.9 2.96 20.3 3.35 22.7 3.74 25.1 4.13
80% 20.0 11.9 1.98 14.3 2.38 16.7 2.77 17.9 2.97 20.3 3.37 22.7 3.76 25.1 4.15
25.0 11.9 2.01 14.3 2.41 16.7 2.81 17.9 3.01 20.3 3.41 22.7 3.80 25.1 4.19
30.0 11.9 2.15 14.3 2.54 16.7 2.94 17.9 3.14 20.3 3.53 22.7 3.92 25.1 4.31
35.0
40.0
11.9
11.9
2.76
3.33
14.3
14.3
3.17
3.84
16.7
16.7
3.57
4.34
17.9
17.9
3.75
4.58
20.3
20.3
4.13
5.04
22.7
22.7
4.49
5.50
25.1
25.1
4.83
5.94
3
43.0 11.9 3.69 14.3 4.27 16.7 4.83 17.9 5.10 20.3 5.63 22.7 6.15 25.1 6.64
46.0 11.9 4.07 14.3 4.72 16.7 5.34 17.9 5.65 20.3 6.25 22.7 6.84 24.1 6.93

Indoor air temp䋮䋺㷄WB


Combination(%) Outdoor
:Indoor/outdoor air temp.
TC
14.0
PI TC
16.0
PI TC
18.0
PI TC
19.0
PI TC
21.0
PI TC
23.0
PI TC
25.0
PI
4
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 10.5 1.71 12.5 2.06 14.6 2.40 15.7 2.57 17.8 2.91 19.9 3.25 22.0 3.59
-5.0 10.5 1.72 12.5 2.06 14.6 2.41 15.7 2.57 17.8 2.91 19.9 3.26 22.0 3.60
0.0 10.5 1.72 12.5 2.06 14.6 2.41 15.7 2.57 17.8 2.92 19.9 3.26 22.0 3.60
5.0 10.5 1.72 12.5 2.06 14.6 2.41 15.7 2.58 17.8 2.92 19.9 3.26 22.0 3.60
10.0
15.0
10.5
10.5
1.72
1.72
12.5
12.5
2.07
2.07
14.6
14.6
2.41
2.42
15.7
15.7
2.58
2.58
17.8
17.8
2.92
2.93
19.9
19.9
3.26
3.27
22.0
22.0
3.60
3.61
5
70% 20.0 10.5 1.73 12.5 2.08 14.6 2.42 15.7 2.59 17.8 2.94 19.9 3.28 22.0 3.63
25.0 10.5 1.75 12.5 2.10 14.6 2.45 15.7 2.62 17.8 2.96 19.9 3.31 22.0 3.66
30.0 10.5 1.85 12.5 2.19 14.6 2.53 15.7 2.71 17.8 3.05 19.9 3.39 22.0 3.74
35.0 10.5 2.42 12.5 2.74 14.6 3.06 15.7 3.21 17.8 3.50 19.9 3.77 22.0 4.05
40.0 10.5 2.90 12.5 3.32 14.6 3.72 15.7 3.91 17.8 4.28 19.9 4.63 22.0 4.97
43.0
46.0
10.5
10.5
3.22
3.54
12.5
12.5
3.69
4.07
14.6
14.6
4.14
4.58
15.7
15.7
4.36
4.83
17.8
17.8
4.78
5.31
19.9
19.9
5.18
5.77
22.0
22.0
5.57
6.21
6
Indoor air temp䋮䋺㷄WB
Combination(%) Outdoor 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
-10.0
kW
9.0
kW
1.47
kW
10.8
kW
1.76
kW
12.5
kW
2.06
kW
13.4
kW
2.21
kW
15.2
kW
2.50
kW
17.0
kW
2.79
kW
18.8
kW
3.08 7
-5.0 9.0 1.47 10.8 1.77 12.5 2.06 13.4 2.21 15.2 2.50 17.0 2.79 18.8 3.08
0.0 9.0 1.47 10.8 1.77 12.5 2.06 13.4 2.21 15.2 2.50 17.0 2.79 18.8 3.08
5.0 9.0 1.47 10.8 1.77 12.5 2.06 13.4 2.21 15.2 2.50 17.0 2.79 18.8 3.09
10.0 9.0 1.47 10.8 1.77 12.5 2.06 13.4 2.21 15.2 2.50 17.0 2.80 18.8 3.09
15.0 9.0 1.48 10.8 1.77 12.5 2.07 13.4 2.22 15.2 2.51 17.0 2.80 18.8 3.09
60% 20.0
25.0
9.0
9.0
1.48
1.49
10.8
10.8
1.78
1.79
12.5
12.5
2.07
2.09
13.4
13.4
2.22
2.24
15.2
15.2
2.51
2.53
17.0
17.0
2.81
2.83
18.8
18.8
3.11
3.13 8
30.0 9.0 1.55 10.8 1.85 12.5 2.15 13.4 2.30 15.2 2.59 17.0 2.90 18.8 3.20
35.0 9.0 2.08 10.8 2.34 12.5 2.58 13.4 2.70 15.2 2.92 17.0 3.18 18.8 3.45
40.0 9.0 2.50 10.8 2.83 12.5 3.15 13.4 3.29 15.2 3.58 17.0 3.84 18.8 4.09
43.0 9.0 2.76 10.8 3.14 12.5 3.50 13.4 3.67 15.2 3.99 17.0 4.30 18.8 4.59
46.0 9.0 3.04 10.8 3.47 12.5 3.87 13.4 4.06 15.2 4.43 17.0 4.79 18.8 5.11
9-3 9

5GEKPFF 
Capacity Table

1. Capacity Ratio of Outdoor Unit

U-8MF2E8 (Cooling) Capacity Ratio 20-130%


TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp䋮䋺㷄WB
Combination(%) Outdoor 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 7.5 1.23 9.0 1.47 10.5 1.72 11.2 1.84 12.7 2.08 14.2 2.33 15.7 2.56
-5.0 7.5 1.23 9.0 1.47 10.5 1.72 11.2 1.84 12.7 2.08 14.2 2.33 15.7 2.57
0.0 7.5 1.23 9.0 1.47 10.5 1.72 11.2 1.84 12.7 2.08 14.2 2.33 15.7 2.57
5.0 7.5 1.23 9.0 1.47 10.5 1.72 11.2 1.84 12.7 2.09 14.2 2.33 15.7 2.57
10.0 7.5 1.23 9.0 1.47 10.5 1.72 11.2 1.84 12.7 2.09 14.2 2.33 15.7 2.57
15.0 7.5 1.23 9.0 1.47 10.5 1.72 11.2 1.85 12.7 2.09 14.2 2.34 15.7 2.58
50% 20.0 7.5 1.24 9.0 1.48 10.5 1.73 11.2 1.85 12.7 2.10 14.2 2.34 15.7 2.59
25.0 7.5 1.24 9.0 1.49 10.5 1.74 11.2 1.86 12.7 2.11 14.2 2.36 15.7 2.60
30.0 7.5 1.28 9.0 1.52 10.5 1.78 11.2 1.91 12.7 2.16 14.2 2.41 15.7 2.65
35.0 7.5 1.77 9.0 1.97 10.5 2.10 11.2 2.20 12.7 2.40 14.2 2.62 15.7 2.84
40.0 7.5 2.12 9.0 2.37 10.5 2.61 11.2 2.72 12.7 2.93 14.2 3.12 15.7 3.29
43.0 7.5 2.33 9.0 2.62 10.5 2.90 11.2 3.03 12.7 3.27 14.2 3.49 15.7 3.70
46.0 7.5 2.55 9.0 2.89 10.5 3.20 11.2 3.35 12.7 3.63 14.2 3.88 15.7 4.12
1 Indoor air temp䋮䋺㷄WB
Combination(%) Outdoor 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 6.0 0.98 7.2 1.18 8.4 1.37 9.0 1.47 10.1 1.67 11.4 1.86 12.5 2.05

2 -5.0
0.0
6.0
6.0
0.98
0.98
7.2
7.2
1.18
1.18
8.4
8.4
1.37
1.37
9.0
9.0
1.47
1.47
10.1
10.1
1.67
1.67
11.4
11.4
1.86
1.86
12.5
12.5
2.06
2.06
5.0 6.0 0.98 7.2 1.18 8.4 1.37 9.0 1.47 10.1 1.67 11.4 1.86 12.5 2.06
10.0 6.0 0.98 7.2 1.18 8.4 1.37 9.0 1.47 10.1 1.67 11.4 1.87 12.5 2.06
15.0 6.0 0.99 7.2 1.18 8.4 1.38 9.0 1.48 10.1 1.67 11.4 1.87 12.5 2.06
40% 20.0 6.0 0.99 7.2 1.19 8.4 1.38 9.0 1.48 10.1 1.68 11.4 1.87 12.5 2.07
25.0 6.0 0.99 7.2 1.19 8.4 1.39 9.0 1.49 10.1 1.69 11.4 1.89 12.5 2.08

3 30.0
35.0
6.0
6.0
1.01
1.48
7.2
7.2
1.22
1.51
8.4
8.4
1.42
1.64
9.0
9.0
1.52
1.71
10.1
10.1
1.72
1.88
11.4
11.4
1.92
2.06
12.5
12.5
2.12
2.24
40.0 6.0 1.75 7.2 1.94 8.4 2.11 9.0 2.19 10.1 2.34 11.4 2.47 12.5 2.58
43.0 6.0 1.92 7.2 2.14 8.4 2.34 9.0 2.43 10.1 2.60 11.4 2.75 12.5 2.89
46.0 6.0 2.10 7.2 2.35 8.4 2.57 9.0 2.68 10.1 2.88 11.4 3.06 12.5 3.22

Indoor air temp䋮䋺㷄WB


4 Combination(%) Outdoor
:Indoor/outdoor air temp.
TC
14.0
PI TC
16.0
PI TC
18.0
PI TC
19.0
PI TC
21.0
PI TC
23.0
PI TC
25.0
PI
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 4.5 0.74 5.4 0.88 6.3 1.03 6.7 1.11 7.6 1.25 8.5 1.39 9.4 1.54
-5.0 4.5 0.74 5.4 0.88 6.3 1.03 6.7 1.11 7.6 1.25 8.5 1.39 9.4 1.54
0.0 4.5 0.74 5.4 0.88 6.3 1.03 6.7 1.11 7.6 1.25 8.5 1.39 9.4 1.54
5.0 4.5 0.74 5.4 0.89 6.3 1.03 6.7 1.11 7.6 1.25 8.5 1.40 9.4 1.54
5 10.0
15.0
4.5
4.5
0.74
0.74
5.4
5.4
0.89
0.89
6.3
6.3
1.03
1.04
6.7
6.7
1.11
1.11
7.6
7.6
1.25
1.25
8.5
8.5
1.40
1.40
9.4
9.4
1.54
1.55
30% 20.0 4.5 0.74 5.4 0.89 6.3 1.04 6.7 1.11 7.6 1.26 8.5 1.40 9.4 1.55
25.0 4.5 0.74 5.4 0.89 6.3 1.04 6.7 1.12 7.6 1.26 8.5 1.41 9.4 1.56
30.0 4.5 0.76 5.4 0.91 6.3 1.06 6.7 1.14 7.6 1.28 8.5 1.43 9.4 1.58
35.0 4.5 1.03 5.4 1.08 6.3 1.19 6.7 1.25 7.6 1.38 8.5 1.51 9.4 1.65
40.0 4.5 1.40 5.4 1.53 6.3 1.65 6.7 1.70 7.6 1.80 8.5 2.53 9.4 2.24
6 43.0
46.0
4.5
4.5
1.53
1.66
5.4
5.4
1.68
1.84
6.3
6.3
1.82
1.99
6.7
6.7
1.88
2.07
7.6
7.6
1.99
2.20
8.5
8.5
2.09
2.32
9.4
9.4
2.18
2.42

Indoor air temp䋮䋺㷄WB


Combination(%) Outdoor 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp. TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
7 -10.0
kW
3.0
kW
0.49
kW
3.6
kW
0.59
kW
4.2
kW
0.69
kW
4.5
kW
0.74
kW
5.1
kW
0.83
kW
5.7
kW
0.93
kW
6.3
kW
1.03
-5.0 3.0 0.49 3.6 0.59 4.2 0.69 4.5 0.74 5.1 0.83 5.7 0.93 6.3 1.03
0.0 3.0 0.49 3.6 0.59 4.2 0.69 4.5 0.74 5.1 0.83 5.7 0.93 6.3 1.03
5.0 3.0 0.49 3.6 0.59 4.2 0.69 4.5 0.74 5.1 0.84 5.7 0.93 6.3 1.03
10.0 3.0 0.49 3.6 0.59 4.2 0.69 4.5 0.74 5.1 0.84 5.7 0.93 6.3 1.03
15.0 3.0 0.49 3.6 0.59 4.2 0.69 4.5 0.74 5.1 0.84 5.7 0.94 6.3 1.03

8 20% 20.0
25.0
3.0
3.0
0.49
0.49
3.6
3.6
0.59
0.59
4.2
4.2
0.69
0.69
4.5
4.5
0.74
0.74
5.1
5.1
0.84
0.84
5.7
5.7
0.94
0.94
6.3
6.3
1.04
1.04
30.0 3.0 0.50 3.6 0.60 4.2 0.70 4.5 0.75 5.1 0.85 5.7 0.95 6.3 1.05
35.0 3.0 0.62 3.6 0.68 4.2 0.76 4.5 0.80 5.1 0.89 5.7 0.99 6.3 1.08
40.0 3.0 1.08 3.6 1.16 4.2 1.23 4.5 1.26 5.1 1.90 5.7 1.41 6.3 1.33
43.0 3.0 1.17 3.6 1.26 4.2 1.34 4.5 1.37 5.1 1.44 5.7 1.49 6.3 1.53
46.0 3.0 1.25 3.6 1.36 4.2 1.45 4.5 1.49 5.1 1.57 5.7 1.64 6.3 1.69

9 9-4

5GEKPFF 
Capacity Table

1. Capacity Ratio of Outdoor Unit

1-2. U-8MF2E8 (Heating) Capacity Ratio 20-130%


TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp䋮䋺㷄DB
Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 20.4 6.48 18.8 6.01 17.6 5.68 17.6 5.68 17.6 5.68 17.6 5.83 15.2 5.20
-14.7 -15.0 21.7 6.64 19.9 6.16 18.8 5.83 18.8 5.83 18.8 5.83 18.7 5.96 16.2 5.30
-9.6 -10.0 23.2 6.86 21.4 6.36 20.2 6.02 20.2 6.02 20.2 6.02 20.2 6.02 17.5 5.44
-4.4 -5.0 25.3 7.11 23.3 6.59 22.0 6.24 22.0 6.24 22.0 6.24 22.0 6.24 19.2 5.62
-1.8 -2.5 26.5 7.21 24.5 6.69 23.1 6.33 23.1 6.33 23.1 6.33 23.1 6.33 20.3 5.71
0.8 0.0 28.0 7.32 25.9 6.80 24.5 6.44 24.5 6.44 24.5 6.44 24.5 6.44 21.7 5.83
130% 2.8 2.0 29.3 7.34 27.4 6.92 25.9 6.57 25.9 6.57 25.9 6.57 25.9 6.57 22.0 5.60
6.0 5.0 31.5 7.34 28.9 6.74 26.9 6.25 26.9 6.25 26.9 6.25 25.9 5.89 22.0 5.00
7.0 6.0 31.9 7.18 28.9 6.46 26.9 5.98 26.9 5.98 26.9 5.98 25.9 5.64 22.0 4.79
8.6 7.5 31.9 6.68 28.9 6.01 26.9 5.58 26.9 5.58 26.9 5.58 25.9 5.28 22.0 4.49
11.2 10.0 31.9 5.88 28.9 5.31 26.9 4.94 26.9 4.94 26.9 4.94 25.9 4.71 22.0 4.02
16.4 15.0 31.9 4.46 28.9 4.07 26.9 3.80 26.9 3.80 26.9 3.80 25.9 3.68 22.0 3.18
24.0 18.0 31.9 4.03 28.9 3.68 26.9 3.44 26.9 3.44 26.9 3.44 25.9 3.32 22.0 2.86

Indoor air temp䋮䋺㷄DB


1
Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 20.5 6.44 18.8 5.98 17.7 5.66 17.7 5.66 17.7 5.66 16.2 5.39 14.0 4.83
-14.7 -15.0 21.7 6.61 20.0 6.13 18.8 5.81 18.8 5.81 18.8 5.81 17.3 5.51 14.9 4.92
-9.6
-4.4
-10.0
-5.0
23.3
25.3
6.83
7.06
21.4
23.4
6.34
6.56
20.2
22.0
5.99
6.20
20.2
22.0
5.99
6.20
20.2
22.0
5.99
6.20
18.7
20.4
5.67
5.87
16.1
17.7
5.04
5.20
2
-1.8 -2.5 26.6 7.16 24.6 6.65 23.2 6.29 23.2 6.29 23.2 6.29 21.6 5.96 18.7 5.28
0.8 0.0 28.1 7.27 26.0 6.76 24.5 6.40 24.5 6.40 24.5 6.40 23.0 6.08 19.8 5.32
120% 2.8 2.0 29.4 7.34 27.4 6.88 25.9 6.53 25.9 6.53 25.9 6.53 23.3 5.86 19.8 5.02
6.0 5.0 31.1 7.16 28.2 6.45 26.3 5.99 26.3 5.99 26.3 5.99 23.3 5.26 19.8 4.47
7.0 6.0 31.1 6.85 28.2 6.17 26.3 5.73 26.3 5.73 26.3 5.73 23.3 5.04 19.8 4.29
8.6
11.2
7.5
10.0
31.1
31.1
6.37
5.60
28.2
28.2
5.75
5.07
26.3
26.3
5.34
4.73
26.3
26.3
5.34
4.73
26.3
26.3
5.34
4.73
23.3
23.3
4.71
4.20
19.8
19.8
4.02
3.60
3
16.4 15.0 31.1 4.24 28.2 3.87 26.3 3.63 26.3 3.63 26.3 3.63 23.3 3.29 19.8 2.85
24.0 18.0 31.1 3.95 28.2 3.60 26.3 3.37 26.3 3.37 26.3 3.37 23.3 3.02 19.8 2.60

Indoor air temp䋮䋺㷄DB


Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor
capacity ratio
air temp.
㷄DB 㷄WB
TC
kW
PI
kW
TC
kW
PI
kW
TC
kW
PI
kW
TC
kW
PI
kW
TC
kW
PI
kW
TC
kW
PI
kW
TC
kW
PI
kW
4
-19.8 -20.0 20.5 6.41 18.8 5.95 17.7 5.64 17.7 5.64 16.9 5.48 14.9 4.96 12.8 4.45
-14.7 -15.0 21.8 6.58 20.0 6.11 18.8 5.78 18.8 5.78 18.0 5.62 15.9 5.07 13.7 4.53
-9.6 -10.0 23.3 6.80 21.5 6.31 20.2 5.98 20.2 5.98 19.4 5.79 17.1 5.21 14.8 4.63
-4.4 -5.0 25.4 7.02 23.4 6.52 22.0 6.17 22.0 6.17 21.2 5.99 18.7 5.39 16.2 4.78
-1.8 -2.5 26.6 7.12 24.6 6.61 23.2 6.26 23.2 6.26 22.3 6.07 19.8 5.47 17.1 4.85
0.8 0.0 28.1 7.23 26.0 6.72 24.6 6.37 24.6 6.37 23.7 6.19 20.9 5.51 17.8 4.75 5
110% 2.8 2.0 29.6 7.34 27.4 6.85 25.6 6.39 25.6 6.39 24.0 5.96 20.9 5.21 17.8 4.47
6.0 5.0 30.4 6.83 27.5 6.17 25.6 5.74 25.6 5.74 24.0 5.35 20.9 4.66 17.8 3.98
7.0 6.0 30.4 6.53 27.5 5.90 25.6 5.49 25.6 5.49 24.0 5.12 20.9 4.47 17.8 3.82
8.6 7.5 30.4 6.06 27.5 5.49 25.6 5.11 25.6 5.11 24.0 4.78 20.9 4.18 17.8 3.58
11.2 10.0 30.4 5.33 27.5 4.84 25.6 4.52 25.6 4.52 24.0 4.24 20.9 3.73 17.8 3.21
16.4 15.0 30.4 4.01 27.5 3.68 25.6 3.46 25.6 3.46 24.0 3.29 20.9 2.92 17.8 2.54
24.0 18.0 30.4 3.86 27.5 3.52 25.6 3.30 25.6 3.30 24.0 3.10 20.9 2.73 17.8 2.36 6
Indoor air temp䋮䋺㷄DB
Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8
-14.7
-20.0
-15.0
20.6
21.8
6.39
6.56
18.9
20.1
5.93
6.09
17.8
18.9
5.62
5.77
16.6
17.6
5.31
5.45
15.4
16.4
5.00
5.12
13.6
14.5
4.53
4.63
11.7
12.5
4.08
4.14
7
-9.6 -10.0 23.4 6.78 21.6 6.29 20.3 5.96 19.0 5.62 17.6 5.28 15.6 4.76 13.5 4.23
-4.4 -5.0 25.5 6.98 23.5 6.49 22.1 6.15 20.7 5.80 19.3 5.45 17.0 4.92 14.8 4.36
-1.8 -2.5 26.7 7.07 24.6 6.58 23.2 6.24 21.8 5.88 20.3 5.52 18.0 4.98 15.6 4.42
0.8 0.0 28.2 7.19 26.1 6.69 24.6 6.35 23.1 5.99 21.3 5.54 18.5 4.86 15.8 4.20
100% 2.8 2.0 29.6 7.28 26.9 6.58 25.0 6.13 23.2 5.67 21.3 5.23 18.5 4.59 15.8 3.96
6.0
7.0
5.0
6.0
29.6
29.6
6.51
6.22
26.9
26.9
5.90
5.64
25.0
25.0
5.49
5.24
23.2
23.2
5.09
4.87
21.3
21.3
4.70
4.50
18.5
18.5
4.10
3.93
15.8
15.8
3.52
3.37
8
8.6 7.5 29.6 5.77 26.9 5.24 25.0 4.89 23.2 4.54 21.3 4.20 18.5 3.68 15.8 3.16
11.2 10.0 29.6 5.06 26.9 4.62 25.0 4.32 23.2 4.02 21.3 3.73 18.5 3.28 15.8 2.83
16.4 15.0 29.6 3.80 26.9 3.50 25.0 3.30 23.2 3.09 21.3 2.89 18.5 2.57 15.8 2.24
24.0 18.0 29.6 3.77 26.9 3.44 25.0 3.22 23.2 3.00 21.3 2.78 18.5 2.45 15.8 2.12

9-5 9

5GEKPFF 
Capacity Table

1. Capacity Ratio of Outdoor Unit

U-8MF2E8 (Heating) Capacity Ratio 20-130%


TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp䋮䋺㷄DB
Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 20.9 6.32 19.2 5.90 18.0 5.60 16.8 5.31 15.6 5.01 13.7 4.58 11.8 4.14
-14.7 -15.0 22.2 6.51 20.4 6.06 19.1 5.75 17.9 5.45 16.6 5.14 14.6 4.67 12.6 4.20
-9.6 -10.0 23.8 6.70 21.9 6.25 20.5 5.94 19.2 5.62 17.8 5.29 15.7 4.79 13.6 4.28
-4.4 -5.0 25.9 6.88 23.8 6.41 22.4 6.09 20.8 5.74 19.2 5.33 16.7 4.75 14.2 4.17
-1.8 -2.5 26.7 6.81 24.2 6.21 22.5 5.82 20.8 5.43 19.2 5.05 16.7 4.49 14.2 3.94
0.8 0.0 26.7 6.37 24.2 5.82 22.5 5.45 20.8 5.09 19.2 4.74 16.7 4.21 14.2 3.68
90% 2.8 2.0 26.7 5.98 24.2 5.47 22.5 5.13 20.8 4.79 19.2 4.46 16.7 3.96 14.2 3.43
6.0 5.0 26.7 5.31 24.2 4.87 22.5 4.57 20.8 4.27 19.2 3.97 16.7 3.51 14.2 3.04
7.0 6.0 26.7 5.06 24.2 4.64 22.5 4.36 20.8 4.08 19.2 3.79 16.7 3.36 14.2 2.91
8.6 7.5 26.7 4.68 24.2 4.31 22.5 4.05 20.8 3.79 19.2 3.53 16.7 3.14 14.2 2.73
11.2 10.0 26.7 4.08 24.2 3.77 22.5 3.56 20.8 3.35 19.2 3.13 16.7 2.79 14.2 2.44
16.4 15.0 26.7 3.42 24.2 3.12 22.5 2.92 20.8 2.72 19.2 2.53 16.7 2.23 14.2 1.93
24.0 18.0 26.7 3.42 24.2 3.12 22.5 2.92 20.8 2.72 19.2 2.53 16.7 2.23 14.2 1.93
1 Combination(%) Outdoor
Indoor air temp䋮䋺㷄DB
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 21.5 6.37 19.6 5.96 18.4 5.68 17.2 5.40 15.9 5.12 14.0 4.70 12.0 4.28
-14.7 -15.0 22.8 6.56 20.9 6.13 19.6 5.84 18.3 5.54 16.9 5.24 14.8 4.76 12.6 4.24
2 -9.6
-4.4
-10.0
-5.0
23.7
23.7
6.46
5.88
21.5
21.5
5.96
5.43
20.0
20.0
5.63
5.14
18.5
18.5
5.30
4.84
17.0
17.0
4.98
4.54
14.8
14.8
4.47
4.10
12.6
12.6
3.97
3.65
-1.8 -2.5 23.7 5.54 21.5 5.12 20.0 4.85 18.5 4.56 17.0 4.29 14.8 3.87 12.6 3.44
0.8 0.0 23.7 5.16 21.5 4.78 20.0 4.52 18.5 4.27 17.0 4.00 14.8 3.61 12.6 3.18
80% 2.8 2.0 23.7 4.83 21.5 4.48 20.0 4.24 18.5 4.00 17.0 3.76 14.8 3.37 12.6 2.94
6.0 5.0 23.7 4.26 21.5 3.96 20.0 3.75 18.5 3.53 17.0 3.31 14.8 2.96 12.6 2.60
7.0 6.0 23.7 4.05 21.5 3.77 20.0 3.57 18.5 3.37 17.0 3.16 14.8 2.83 12.6 2.49
3 8.6
11.2
7.5
10.0
23.7
23.7
3.73
3.22
21.5
21.5
3.48
3.03
20.0
20.0
3.31
2.89
18.5
18.5
3.12
2.74
17.0
17.0
2.94
2.59
14.8
14.8
2.64
2.34
12.6
12.6
2.33
2.08
16.4 15.0 23.7 3.07 21.5 2.80 20.0 2.63 18.5 2.45 17.0 2.27 14.8 2.01 12.6 1.74
24.0 18.0 23.7 3.07 21.5 2.80 20.0 2.63 18.5 2.45 17.0 2.27 14.8 2.01 12.6 1.74

Indoor air temp䋮䋺㷄DB


Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
4 :Indoor/outdoor
capacity ratio
air temp.
㷄DB 㷄WB
TC
kW
PI
kW
TC
kW
PI
kW
TC
kW
PI
kW
TC
kW
PI
kW
TC
kW
PI
kW
TC
kW
PI
kW
TC
kW
PI
kW
-19.8 -20.0 20.8 5.98 18.8 5.58 17.5 5.30 16.2 5.03 14.9 4.76 13.0 4.36 11.0 3.96
-14.7 -15.0 20.8 5.63 18.8 5.28 17.5 5.04 16.2 4.79 14.9 4.52 13.0 4.12 11.0 3.72
-9.6 -10.0 20.8 5.22 18.8 4.90 17.5 4.68 16.2 4.46 14.9 4.23 13.0 3.87 11.0 3.46
-4.4 -5.0 20.8 4.73 18.8 4.44 17.5 4.24 16.2 4.04 14.9 3.84 13.0 3.51 11.0 3.17

5 -1.8
0.8
-2.5
0.0
20.8
20.8
4.44
4.11
18.8
18.8
4.17
3.87
17.5
17.5
3.99
3.70
16.2
16.2
3.80
3.53
14.9
14.9
3.61
3.35
13.0
13.0
3.30
3.04
11.0
11.0
2.94
2.68
70% 2.8 2.0 20.8 3.83 18.8 3.61 17.5 3.46 16.2 3.30 14.9 3.11 13.0 2.80 11.0 2.48
6.0 5.0 20.8 3.35 18.8 3.15 17.5 3.02 16.2 2.87 14.9 2.71 13.0 2.46 11.0 2.19
7.0 6.0 20.8 3.16 18.8 2.99 17.5 2.87 16.2 2.73 14.9 2.59 13.0 2.35 11.0 2.10
8.6 7.5 20.8 2.90 18.8 2.76 17.5 2.65 16.2 2.53 14.9 2.40 13.0 2.20 11.0 1.97
11.2 10.0 20.8 2.71 18.8 2.48 17.5 2.33 16.2 2.21 14.9 2.11 13.0 1.94 11.0 1.75

6 16.4
24.0
15.0
18.0
20.8
20.8
2.71
2.71
18.8
18.8
2.48
2.48
17.5
17.5
2.33
2.33
16.2
16.2
2.17
2.17
14.9
14.9
2.02
2.02
13.0
13.0
1.79
1.79
11.0
11.0
1.56
1.56

Indoor air temp䋮䋺㷄DB


Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
7 -19.8
-14.7
-20.0
-15.0
17.8
17.8
4.83
4.53
16.1
16.1
4.61
4.32
15.0
15.0
4.44
4.17
13.9
13.9
4.24
4.01
12.8
12.8
4.04
3.84
11.1
11.1
3.74
3.53
9.5
9.5
3.43
3.21
-9.6 -10.0 17.8 4.18 16.1 3.99 15.0 3.86 13.9 3.71 12.8 3.56 11.1 3.30 9.5 2.99
-4.4 -5.0 17.8 3.75 16.1 3.58 15.0 3.47 13.9 3.34 12.8 3.20 11.1 2.98 9.5 2.67
-1.8 -2.5 17.8 3.50 16.1 3.35 15.0 3.24 13.9 3.12 12.8 3.00 11.1 2.76 9.5 2.44
0.8 0.0 17.8 3.22 16.1 3.09 15.0 3.00 13.9 2.89 12.8 2.74 11.1 2.49 9.5 2.23
60% 2.8 2.0 17.8 2.98 16.1 2.87 15.0 2.76 13.9 2.64 12.8 2.51 11.1 2.30 9.5 2.05
8 6.0
7.0
5.0
6.0
17.8
17.8
2.56
2.41
16.1
16.1
2.46
2.33
15.0
15.0
2.37
2.25
13.9
13.9
2.28
2.17
12.8
12.8
2.19
2.08
11.1
11.1
2.01
1.92
9.5
9.5
1.81
1.74
8.6 7.5 17.8 2.36 16.1 2.16 15.0 2.08 13.9 2.01 12.8 1.93 11.1 1.79 9.5 1.62
11.2 10.0 17.8 2.36 16.1 2.16 15.0 2.03 13.9 1.90 12.8 1.77 11.1 1.58 9.5 1.45
16.4 15.0 17.8 2.36 16.1 2.16 15.0 2.03 13.9 1.90 12.8 1.77 11.1 1.57 9.5 1.37
24.0 18.0 17.8 2.36 16.1 2.16 15.0 2.03 13.9 1.90 12.8 1.77 11.1 1.57 9.5 1.37

9 9-6

5GEKPFF 
Capacity Table

1. Capacity Ratio of Outdoor Unit

U-8MF2E8 (Heating) Capacity Ratio 20-130%


TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp䋮䋺㷄DB
Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 14.8 3.86 13.4 3.74 12.5 3.65 11.6 3.53 10.7 3.38 9.3 3.15 7.9 2.92
-14.7 -15.0 14.8 3.61 13.4 3.50 12.5 3.42 11.6 3.32 10.7 3.20 9.3 2.97 7.9 2.72
-9.6 -10.0 14.8 3.30 13.4 3.21 12.5 3.14 11.6 3.05 10.7 2.95 9.3 2.77 7.9 2.53
-4.4 -5.0 14.8 2.93 13.4 2.86 12.5 2.80 11.6 2.72 10.7 2.64 9.3 2.42 7.9 2.16
-1.8 -2.5 14.8 2.71 13.4 2.65 12.5 2.60 11.6 2.52 10.7 2.40 9.3 2.21 7.9 1.99
0.8 0.0 14.8 2.48 13.4 2.42 12.5 2.34 11.6 2.26 10.7 2.16 9.3 2.00 7.9 1.81
50% 2.8 2.0 14.8 2.26 13.4 2.19 12.5 2.13 11.6 2.06 10.7 1.98 9.3 1.83 7.9 1.67
6.0 5.0 14.8 2.01 13.4 1.86 12.5 1.82 11.6 1.78 10.7 1.71 9.3 1.61 7.9 1.47
7.0 6.0 14.8 2.01 13.4 1.84 12.5 1.73 11.6 1.68 10.7 1.63 9.3 1.54 7.9 1.41
8.6 7.5 14.8 2.01 13.4 1.84 12.5 1.73 11.6 1.62 10.7 1.51 9.3 1.43 7.9 1.32
11.2 10.0 14.8 2.01 13.4 1.84 12.5 1.73 11.6 1.62 10.7 1.51 9.3 1.35 7.9 1.18
16.4 15.0 14.8 2.01 13.4 1.84 12.5 1.73 11.6 1.62 10.7 1.51 9.3 1.35 7.9 1.18
24.0 18.0 14.8 2.01 13.4 1.84 12.5 1.73 11.6 1.62 10.7 1.51 9.3 1.35 7.9 1.18

Indoor air temp䋮䋺㷄DB


1
Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 11.9 3.05 10.8 3.00 10.0 2.94 9.3 2.87 8.5 2.76 7.4 2.60 6.3 2.42
-14.7 -15.0 11.9 2.83 10.8 2.79 10.0 2.75 9.3 2.69 8.5 2.61 7.4 2.44 6.3 2.25
-9.6
-4.4
-10.0
-5.0
11.9
11.9
2.57
2.25
10.8
10.8
2.55
2.24
10.0
10.0
2.51
2.19
9.3
9.3
2.46
2.11
8.5
8.5
2.39
2.03
7.4
7.4
2.23
1.88
6.3
6.3
2.00
1.70
2
-1.8 -2.5 11.9 2.06 10.8 2.01 10.0 1.97 9.3 1.91 8.5 1.83 7.4 1.71 6.3 1.56
0.8 0.0 11.9 1.81 10.8 1.78 10.0 1.75 9.3 1.71 8.5 1.65 7.4 1.55 6.3 1.43
40% 2.8 2.0 11.9 1.66 10.8 1.61 10.0 1.59 9.3 1.55 8.5 1.51 7.4 1.43 6.3 1.32
6.0 5.0 11.9 1.66 10.8 1.52 10.0 1.44 9.3 1.35 8.5 1.31 7.4 1.25 6.3 1.17
7.0 6.0 11.9 1.66 10.8 1.52 10.0 1.44 9.3 1.35 8.5 1.26 7.4 1.19 6.3 1.12
8.6
11.2
7.5
10.0
11.9
11.9
1.66
1.66
10.8
10.8
1.52
1.52
10.0
10.0
1.44
1.44
9.3
9.3
1.35
1.35
8.5
8.5
1.26
1.26
7.4
7.4
1.13
1.13
6.3
6.3
1.05
1.00
3
16.4 15.0 11.9 1.66 10.8 1.52 10.0 1.44 9.3 1.35 8.5 1.26 7.4 1.13 6.3 1.00
24.0 18.0 11.9 1.66 10.8 1.52 10.0 1.44 9.3 1.35 8.5 1.26 7.4 1.13 6.3 1.00

Indoor air temp䋮䋺㷄DB


Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor
capacity ratio
air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI 4
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 8.9 2.34 8.1 2.32 7.5 2.29 7.0 2.23 6.4 2.16 5.6 2.04 4.7 1.92
-14.7 -15.0 8.9 2.16 8.1 2.15 7.5 2.13 7.0 2.10 6.4 2.04 5.6 1.90 4.7 1.71
-9.6 -10.0 8.9 1.95 8.1 1.94 7.5 1.90 7.0 1.84 6.4 1.77 5.6 1.65 4.7 1.50
-4.4 -5.0 8.9 1.61 8.1 1.59 7.5 1.56 7.0 1.52 6.4 1.48 5.6 1.39 4.7 1.28
-1.8
0.8
-2.5
0.0
8.9
8.9
1.43
1.30
8.1
8.1
1.41
1.25
7.5
7.5
1.40
1.25
7.0
7.0
1.37
1.23
6.4
6.4
1.34
1.21
5.6
5.6
1.27
1.15
4.7
4.7
1.18
1.08 5
30% 2.8 2.0 8.9 1.30 8.1 1.21 7.5 1.14 7.0 1.12 6.4 1.11 5.6 1.06 4.7 1.00
6.0 5.0 8.9 1.30 8.1 1.21 7.5 1.14 7.0 1.07 6.4 1.01 5.6 0.93 4.7 0.89
7.0 6.0 8.9 1.30 8.1 1.21 7.5 1.14 7.0 1.07 6.4 1.01 5.6 0.91 4.7 0.85
8.6 7.5 8.9 1.30 8.1 1.21 7.5 1.14 7.0 1.07 6.4 1.01 5.6 0.91 4.7 0.81
11.2 10.0 8.9 1.30 8.1 1.21 7.5 1.14 7.0 1.07 6.4 1.01 5.6 0.91 4.7 0.81
16.4
24.0
15.0
18.0
8.9
8.9
1.30
1.30
8.1
8.1
1.21
1.21
7.5
7.5
1.14
1.14
7.0
7.0
1.07
1.07
6.4
6.4
1.01
1.01
5.6
5.6
0.91
0.91
4.7
4.7
0.81
0.81 6
Indoor air temp䋮䋺㷄DB
Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8
-14.7
-20.0
-15.0
5.9
5.9
1.68
1.54
5.4
5.4
1.67
1.50
5.0
5.0
1.65
1.47
4.6
4.6
1.61
1.44
4.3
4.3
1.56
1.38
3.7
3.7
1.47
1.29
3.2
3.2
1.35
1.18
7
-9.6 -10.0 5.9 1.27 5.4 1.26 5.0 1.24 4.6 1.22 4.3 1.18 3.7 1.12 3.2 1.04
-4.4 -5.0 5.9 1.03 5.4 1.03 5.0 1.03 4.6 1.02 4.3 1.00 3.7 0.96 3.2 0.90
-1.8 -2.5 5.9 0.95 5.4 0.93 5.0 0.93 4.6 0.92 4.3 0.91 3.7 0.88 3.2 0.83
0.8 0.0 5.9 0.95 5.4 0.89 5.0 0.84 4.6 0.83 4.3 0.83 3.7 0.80 3.2 0.77
20% 2.8 2.0 5.9 0.95 5.4 0.89 5.0 0.84 4.6 0.80 4.3 0.76 3.7 0.74 3.2 0.72
6.0
7.0
5.0
6.0
5.9
5.9
0.95
0.95
5.4
5.4
0.89
0.89
5.0
5.0
0.84
0.84
4.6
4.6
0.80
0.80
4.3
4.3
0.75
0.75
3.7
3.7
0.69
0.69
3.2
3.2
0.64
0.62
8
8.6 7.5 5.9 0.95 5.4 0.89 5.0 0.84 4.6 0.80 4.3 0.75 3.7 0.69 3.2 0.62
11.2 10.0 5.9 0.95 5.4 0.89 5.0 0.84 4.6 0.80 4.3 0.75 3.7 0.69 3.2 0.62
16.4 15.0 5.9 0.95 5.4 0.89 5.0 0.84 4.6 0.80 4.3 0.75 3.7 0.69 3.2 0.62
24.0 18.0 5.9 0.95 5.4 0.89 5.0 0.84 4.6 0.80 4.3 0.75 3.7 0.69 3.2 0.62

9-7 9

5GEKPFF 
Capacity Table

1. Capacity Ratio of Outdoor Unit

1-3. U-10MF2E8 (Cooling) Capacity Ratio 20-130%


TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp䋮䋺㷄WB
Combination(%) Outdoor 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 26.1 4.06 30.1 4.69 30.1 4.69 30.1 4.69 34.1 5.31 38.1 5.94 42.1 6.56
-5.0 26.1 4.06 30.1 4.69 30.1 4.69 30.1 4.69 34.1 5.32 38.1 5.94 42.1 6.56
0.0 26.1 4.06 30.1 4.70 30.1 4.70 30.1 4.70 34.1 5.33 38.1 5.96 42.1 6.58
5.0 26.1 4.06 30.1 4.71 30.1 4.71 30.1 4.71 34.1 5.33 38.1 5.97 42.1 6.59
10.0 26.1 4.07 30.1 4.73 30.1 4.73 30.1 4.73 34.1 5.35 38.1 5.99 42.1 6.61
15.0 26.1 4.09 30.1 4.76 30.1 4.76 30.1 4.76 34.1 5.40 38.1 6.04 42.1 6.66
130% 20.0 26.1 4.13 30.1 4.84 30.1 4.84 30.1 4.84 34.1 5.49 38.1 6.14 42.1 6.76
25.0 26.1 4.29 30.1 5.07 30.1 5.07 30.1 5.07 34.1 5.75 38.1 6.41 42.1 7.01
30.0 26.1 5.13 30.1 6.16 30.1 6.16 30.1 6.16 34.1 7.05 38.1 7.96 42.1 8.91
35.0 26.1 6.33 30.1 7.55 30.1 7.55 30.1 7.55 34.1 8.62 37.7 9.56 39.6 9.56
40.0 26.1 7.61 30.1 9.04 30.1 9.04 30.1 9.04 32.6 9.56 34.3 9.56 36.0 9.56
43.0 26.1 8.44 29.2 9.56 29.2 9.56 29.2 9.56 30.8 9.56 32.4 9.56 33.7 9.42
46.0 26.1 8.88 26.6 9.04 26.6 9.04 26.6 9.04 26.6 8.29 26.6 7.60 26.6 6.97
1 Indoor air temp䋮䋺㷄WB
Combination(%) Outdoor 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 23.5 3.66 28.2 4.39 29.4 4.58 29.4 4.58 33.3 5.19 37.2 5.80 41.2 6.41
-5.0 23.5 3.66 28.2 4.39 29.4 4.58 29.4 4.58 33.3 5.20 37.2 5.81 41.2 6.41
2 0.0
5.0
23.5
23.5
3.66
3.67
28.2
28.2
4.40
4.41
29.4
29.4
4.59
4.60
29.4
29.4
4.59
4.60
33.3
33.3
5.20
5.21
37.2
37.2
5.81
5.83
41.2
41.2
6.42
6.43
10.0 23.5 3.67 28.2 4.41 29.4 4.61 29.4 4.61 33.3 5.23 37.2 5.85 41.2 6.46
15.0 23.5 3.69 28.2 4.43 29.4 4.64 29.4 4.64 33.3 5.27 37.2 5.89 41.2 6.51
120% 20.0 23.5 3.73 28.2 4.49 29.4 4.72 29.4 4.72 33.3 5.35 37.2 6.00 41.2 6.60
25.0 23.5 3.88 28.2 4.67 29.4 4.94 29.4 4.94 33.3 5.60 37.2 6.26 41.2 6.85
30.0 23.5 4.64 28.2 5.57 29.4 5.96 29.4 5.96 33.3 6.80 37.2 7.68 41.2 8.57
3 35.0
40.0
23.5
23.5
5.72
6.87
28.2
28.2
6.86
8.25
29.4
29.4
7.30
8.76
29.4
29.4
7.30
8.76
33.3
32.5
8.33
9.56
37.2
34.1
9.38
9.56
39.3
35.8
9.56
9.56
43.0 23.5 7.61 28.2 8.88 29.1 9.56 29.1 9.56 30.6 9.56 32.2 9.56 33.7 9.51
46.0 23.5 8.39 26.6 9.10 26.6 9.10 26.6 9.10 26.6 8.35 26.6 7.66 26.6 7.01

Indoor air temp䋮䋺㷄WB


Combination(%) Outdoor
4 :Indoor/outdoor air temp.
TC
14.0
PI TC
16.0
PI TC
18.0
PI TC
19.0
PI TC
21.0
PI TC
23.0
PI TC
25.0
PI
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 21.1 3.27 25.3 3.93 28.7 4.47 28.7 4.47 32.5 5.07 36.3 5.66 40.2 6.26
-5.0 21.1 3.28 25.3 3.93 28.7 4.47 28.7 4.47 32.5 5.07 36.3 5.67 40.2 6.26
0.0 21.1 3.28 25.3 3.93 28.7 4.48 28.7 4.48 32.5 5.07 36.3 5.68 40.2 6.27
5.0 21.1 3.28 25.3 3.94 28.7 4.49 28.7 4.49 32.5 5.09 36.3 5.69 40.2 6.28
5 10.0
15.0
21.1
21.1
3.29
3.31
25.3
25.3
3.95
3.97
28.7
28.7
4.50
4.53
28.7
28.7
4.50
4.53
32.5
32.5
5.10
5.14
36.3
36.3
5.71
5.75
40.2
40.2
6.30
6.35
110% 20.0 21.1 3.34 25.3 4.02 28.7 4.60 28.7 4.60 32.5 5.22 36.3 5.84 40.2 6.45
25.0 21.1 3.48 25.3 4.19 28.7 4.81 28.7 4.81 32.5 5.45 36.3 6.09 40.2 6.69
30.0 21.1 4.18 25.3 4.99 28.7 5.76 28.7 5.76 32.5 6.56 36.3 7.39 40.2 8.24
35.0 21.1 5.14 25.3 6.15 28.7 7.06 28.7 7.06 32.5 8.05 36.3 9.05 39.1 9.56
40.0 21.1 6.17 25.3 7.38 28.7 8.48 28.7 8.48 32.3 9.56 33.9 9.56 35.6 9.56
6 43.0
46.0
21.1
21.1
6.82
7.52
25.3
25.3
8.18
8.88
28.7
26.6
9.39
9.17
28.7
26.6
9.39
9.17
30.5
26.6
9.56
8.41
32.0
26.6
9.56
7.72
33.6
26.6
9.56
7.07

Indoor air temp䋮䋺㷄WB


Combination(%) Outdoor 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
7 -10.0
kW
18.7
kW
2.90
kW
22.4
kW
3.49
kW
26.1
kW
4.07
kW
28.0
kW
4.36
kW
31.7
kW
4.94
kW
35.5
kW
5.53
kW
39.2
kW
6.11
-5.0 18.7 2.90 22.4 3.49 26.1 4.07 28.0 4.36 31.7 4.94 35.5 5.53 39.2 6.11
0.0 18.7 2.91 22.4 3.49 26.1 4.08 28.0 4.37 31.7 4.95 35.5 5.53 39.2 6.12
5.0 18.7 2.91 22.4 3.50 26.1 4.08 28.0 4.38 31.7 4.96 35.5 5.55 39.2 6.13
10.0 18.7 2.92 22.4 3.50 26.1 4.10 28.0 4.39 31.7 4.98 35.5 5.57 39.2 6.15
15.0 18.7 2.93 22.4 3.52 26.1 4.12 28.0 4.42 31.7 5.01 35.5 5.61 39.2 6.19

8 100% 20.0
25.0
18.7
18.7
2.96
3.09
22.4
22.4
3.57
3.73
26.1
26.1
4.18
4.36
28.0
28.0
4.48
4.68
31.7
31.7
5.09
5.30
35.5
35.5
5.69
5.92
39.2
39.2
6.29
6.53
30.0 18.7 3.74 22.4 4.45 26.1 5.18 28.0 5.56 31.7 6.33 35.5 7.12 39.2 7.92
35.0 18.7 4.58 22.4 5.46 26.1 6.37 28.0 6.83 31.7 7.75 35.5 8.67 38.9 9.56
40.0 18.7 5.50 22.4 6.56 26.1 7.64 28.0 8.20 31.7 9.32 33.7 9.56 35.4 9.56
43.0 18.7 6.08 22.4 7.26 26.1 8.47 28.0 9.08 30.3 9.56 31.9 9.56 33.5 9.56
46.0 18.7 6.69 22.4 8.00 26.1 9.36 26.6 9.23 26.6 8.48 26.6 7.78 26.6 7.13
9 9-8

5GEKPFF 
Capacity Table

1. Capacity Ratio of Outdoor Unit

U-10MF2E8 (Cooling) Capacity Ratio 20-130%


TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp䋮䋺㷄WB
Combination(%) Outdoor 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 16.8 2.62 20.2 3.13 23.5 3.66 25.2 3.93 28.6 4.45 31.9 4.97 35.3 5.49
-5.0 16.8 2.62 20.2 3.14 23.5 3.67 25.2 3.93 28.6 4.45 31.9 4.97 35.3 5.50
0.0 16.8 2.62 20.2 3.14 23.5 3.67 25.2 3.93 28.6 4.45 31.9 4.98 35.3 5.50
5.0 16.8 2.62 20.2 3.15 23.5 3.67 25.2 3.93 28.6 4.46 31.9 4.99 35.3 5.51
10.0 16.8 2.62 20.2 3.16 23.5 3.68 25.2 3.95 28.6 4.47 31.9 5.00 35.3 5.53
15.0 16.8 2.64 20.2 3.17 23.5 3.70 25.2 3.97 28.6 4.50 31.9 5.03 35.3 5.56
90% 20.0 16.8 2.66 20.2 3.20 23.5 3.74 25.2 4.02 28.6 4.56 31.9 5.10 35.3 5.63
25.0 16.8 2.76 20.2 3.32 23.5 3.88 25.2 4.16 28.6 4.71 31.9 5.27 35.3 5.81
30.0 16.8 3.31 20.2 3.90 23.5 4.51 25.2 4.82 28.6 5.44 31.9 6.07 35.3 6.71
35.0 16.8 4.06 20.2 4.81 23.5 5.56 25.2 5.94 28.6 6.70 31.9 7.48 35.3 8.27
40.0 16.8 4.87 20.2 5.77 23.5 6.68 25.2 7.14 28.6 8.07 31.9 9.01 34.5 9.56
43.0 16.8 5.39 20.2 6.39 23.5 7.40 25.2 7.92 28.6 8.95 31.1 9.56 32.6 9.56
46.0 16.8 5.93 20.2 7.04 23.5 8.18 25.2 8.75 26.6 8.79 26.6 8.07 26.6 7.39

Indoor air temp䋮䋺㷄WB


1
Combination(%) Outdoor 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 14.9 2.32 17.9 2.79 20.9 3.26 22.4 3.49 25.4 3.95 28.4 4.42 31.4 4.88
-5.0 14.9 2.32 17.9 2.79 20.9 3.26 22.4 3.49 25.4 3.95 28.4 4.42 31.4 4.88
0.0 14.9 2.33 17.9 2.79 20.9 3.26 22.4 3.49 25.4 3.96 28.4 4.43 31.4 4.89 2
5.0 14.9 2.33 17.9 2.79 20.9 3.26 22.4 3.50 25.4 3.96 28.4 4.43 31.4 4.90
10.0 14.9 2.33 17.9 2.80 20.9 3.27 22.4 3.50 25.4 3.98 28.4 4.44 31.4 4.91
15.0 14.9 2.34 17.9 2.81 20.9 3.29 22.4 3.52 25.4 3.99 28.4 4.46 31.4 4.93
80% 20.0 14.9 2.36 17.9 2.83 20.9 3.31 22.4 3.55 25.4 4.03 28.4 4.51 31.4 4.98
25.0 14.9 2.42 17.9 2.92 20.9 3.41 22.4 3.65 25.4 4.15 28.4 4.63 31.4 5.11
30.0 14.9 2.91 17.9 3.39 20.9 3.88 22.4 4.13 25.4 4.62 28.4 5.12 31.4 5.62
35.0 14.9 3.57 17.9 4.18 20.9 4.79 22.4 5.10 25.4 5.72 28.4 6.35 31.4 6.97 3
40.0 14.9 4.28 17.9 5.03 20.9 5.77 22.4 6.15 25.4 6.90 28.4 7.66 31.4 8.41
43.0 14.9 4.73 17.9 5.56 20.9 6.40 22.4 6.82 25.4 7.66 28.4 8.51 31.4 9.36
46.0 14.9 5.20 17.9 6.13 20.9 7.07 22.4 7.53 25.4 8.48 26.6 8.44 26.6 7.73

Indoor air temp䋮䋺㷄WB


Combination(%) Outdoor
:Indoor/outdoor air temp.
TC
14.0
PI TC
16.0
PI TC
18.0
PI TC
19.0
PI TC
21.0
PI TC
23.0
PI TC
25.0
PI
4
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 13.1 2.04 15.7 2.44 18.3 2.85 19.6 3.05 22.2 3.46 24.8 3.87 27.4 4.27
-5.0 13.1 2.04 15.7 2.44 18.3 2.85 19.6 3.05 22.2 3.46 24.8 3.87 27.4 4.27
0.0 13.1 2.04 15.7 2.45 18.3 2.85 19.6 3.05 22.2 3.46 24.8 3.87 27.4 4.28
5.0 13.1 2.04 15.7 2.45 18.3 2.85 19.6 3.06 22.2 3.46 24.8 3.87 27.4 4.28
10.0
15.0
13.1
13.1
2.04
2.04
15.7
15.7
2.45
2.46
18.3
18.3
2.85
2.87
19.6
19.6
3.06
3.07
22.2
22.2
3.47
3.48
24.8
24.8
3.88
3.89
27.4
27.4
4.29
4.30
5
70% 20.0 13.1 2.06 15.7 2.47 18.3 2.89 19.6 3.09 22.2 3.51 24.8 3.93 27.4 4.34
25.0 13.1 2.10 15.7 2.53 18.3 2.96 19.6 3.17 22.2 3.59 24.8 4.01 27.4 4.43
30.0 13.1 2.43 15.7 2.85 18.3 3.27 19.6 3.48 22.2 3.89 24.8 4.30 27.4 4.71
35.0 13.1 3.10 15.7 3.60 18.3 4.09 19.6 4.34 22.2 4.82 24.8 5.30 27.4 5.78
40.0 13.1 3.72 15.7 4.32 18.3 4.93 19.6 5.23 22.2 5.83 24.8 6.42 27.4 7.01
43.0
46.0
13.1
13.1
4.10
4.51
15.7
15.7
4.79
5.27
18.3
18.3
5.46
6.03
19.6
19.6
5.81
6.41
22.2
22.2
6.47
7.16
24.8
24.8
7.14
7.91
27.4
26.6
7.80
8.20
6
Indoor air temp䋮䋺㷄WB
Combination(%) Outdoor 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
-10.0
kW
11.2
kW
1.74
kW
13.4
kW
2.09
kW
15.7
kW
2.44
kW
16.8
kW
2.62
kW
19.0
kW
2.96
kW
21.3
kW
3.31
kW
23.5
kW
3.66 7
-5.0 11.2 1.74 13.4 2.09 15.7 2.45 16.8 2.62 19.0 2.96 21.3 3.31 23.5 3.66
0.0 11.2 1.74 13.4 2.10 15.7 2.45 16.8 2.62 19.0 2.96 21.3 3.31 23.5 3.66
5.0 11.2 1.75 13.4 2.10 15.7 2.45 16.8 2.62 19.0 2.97 21.3 3.32 23.5 3.67
10.0 11.2 1.75 13.4 2.10 15.7 2.45 16.8 2.62 19.0 2.97 21.3 3.33 23.5 3.67
15.0 11.2 1.75 13.4 2.10 15.7 2.45 16.8 2.63 19.0 2.98 21.3 3.33 23.5 3.68
60% 20.0
25.0
11.2
11.2
1.76
1.79
13.4
13.4
2.12
2.15
15.7
15.7
2.47
2.51
16.8
16.8
2.64
2.69
19.0
19.0
3.00
3.05
21.3
21.3
3.35
3.41
23.5
23.5
3.70
3.76 8
30.0 11.2 2.00 13.4 2.36 15.7 2.71 16.8 2.89 19.0 3.24 21.3 3.59 23.5 3.94
35.0 11.2 2.66 13.4 3.05 15.7 3.44 16.8 3.63 19.0 4.00 21.3 4.36 23.5 4.71
40.0 11.2 3.18 13.4 3.67 15.7 4.15 16.8 4.38 19.0 4.84 21.3 5.29 23.5 5.74
43.0 11.2 3.50 13.4 4.06 15.7 4.59 16.8 4.86 19.0 5.38 21.3 5.89 23.5 6.39
46.0 11.2 3.85 13.4 4.47 15.7 5.07 16.8 5.36 19.0 5.95 21.3 6.52 23.5 7.09
9-9 9

5GEKPFF 
Capacity Table

1. Capacity Ratio of Outdoor Unit

U-10MF2E8 (Cooling) Capacity Ratio 20-130%


TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp䋮䋺㷄WB
Combination(%) Outdoor 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 9.3 1.45 11.2 1.74 13.1 2.04 14.0 2.18 15.9 2.47 17.7 2.76 19.6 3.05
-5.0 9.3 1.45 11.2 1.74 13.1 2.04 14.0 2.18 15.9 2.47 17.7 2.76 19.6 3.05
0.0 9.3 1.45 11.2 1.74 13.1 2.04 14.0 2.18 15.9 2.47 17.7 2.76 19.6 3.05
5.0 9.3 1.45 11.2 1.75 13.1 2.04 14.0 2.19 15.9 2.47 17.7 2.77 19.6 3.05
10.0 9.3 1.45 11.2 1.75 13.1 2.04 14.0 2.19 15.9 2.48 17.7 2.77 19.6 3.06
15.0 9.3 1.46 11.2 1.75 13.1 2.04 14.0 2.19 15.9 2.48 17.7 2.77 19.6 3.07
50% 20.0 9.3 1.46 11.2 1.76 13.1 2.05 14.0 2.20 15.9 2.49 17.7 2.79 19.6 3.08
25.0 9.3 1.48 11.2 1.78 13.1 2.08 14.0 2.23 15.9 2.52 17.7 2.81 19.6 3.11
30.0 9.3 1.61 11.2 1.91 13.1 2.20 14.0 2.34 15.9 2.64 17.7 2.93 19.6 3.22
35.0 9.3 2.25 11.2 2.55 13.1 2.83 14.0 2.98 15.9 3.25 17.7 3.51 19.6 3.76
40.0 9.3 2.68 11.2 3.05 13.1 3.42 14.0 3.59 15.9 3.93 17.7 4.27 19.6 4.59
43.0 9.3 2.94 11.2 3.37 13.1 3.78 14.0 3.98 15.9 4.37 17.7 4.75 19.6 5.12
46.0 9.3 3.22 11.2 3.70 13.1 4.17 14.0 4.39 15.9 4.83 17.7 5.26 19.6 5.67
1 Indoor air temp䋮䋺㷄WB
Combination(%) Outdoor 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 7.5 1.16 9.0 1.39 10.4 1.63 11.2 1.74 12.7 1.97 14.2 2.21 15.7 2.44

2 -5.0
0.0
7.5
7.5
1.16
1.16
9.0
9.0
1.39
1.39
10.4
10.4
1.63
1.63
11.2
11.2
1.74
1.74
12.7
12.7
1.97
1.97
14.2
14.2
2.21
2.21
15.7
15.7
2.44
2.44
5.0 7.5 1.16 9.0 1.39 10.4 1.63 11.2 1.75 12.7 1.98 14.2 2.21 15.7 2.45
10.0 7.5 1.16 9.0 1.40 10.4 1.63 11.2 1.75 12.7 1.98 14.2 2.21 15.7 2.45
15.0 7.5 1.17 9.0 1.40 10.4 1.63 11.2 1.75 12.7 1.98 14.2 2.22 15.7 2.45
40% 20.0 7.5 1.17 9.0 1.41 10.4 1.64 11.2 1.76 12.7 1.99 14.2 2.23 15.7 2.46
25.0 7.5 1.18 9.0 1.41 10.4 1.65 11.2 1.77 12.7 2.01 14.2 2.24 15.7 2.48

3 30.0
35.0
7.5
7.5
1.24
1.86
9.0
9.0
1.48
2.08
10.4
10.4
1.71
2.29
11.2
11.2
1.83
2.38
12.7
12.7
2.06
2.57
14.2
14.2
2.30
2.72
15.7
15.7
2.54
2.90
40.0 7.5 2.20 9.0 2.48 10.4 2.74 11.2 2.87 12.7 3.11 14.2 3.34 15.7 3.56
43.0 7.5 2.41 9.0 2.73 10.4 3.03 11.2 3.18 12.7 3.45 14.2 3.72 15.7 3.97
46.0 7.5 2.63 9.0 2.99 10.4 3.33 11.2 3.49 12.7 3.81 14.2 4.11 15.7 4.40

Indoor air temp䋮䋺㷄WB


4 Combination(%) Outdoor
:Indoor/outdoor air temp.
TC
14.0
PI TC
16.0
PI TC
18.0
PI TC
19.0
PI TC
21.0
PI TC
23.0
PI TC
25.0
PI
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 5.6 0.87 6.7 1.04 7.8 1.22 8.4 1.30 9.5 1.48 10.6 1.65 11.8 1.83
-5.0 5.6 0.87 6.7 1.04 7.8 1.22 8.4 1.30 9.5 1.48 10.6 1.66 11.8 1.83
0.0 5.6 0.87 6.7 1.04 7.8 1.22 8.4 1.31 9.5 1.48 10.6 1.66 11.8 1.83
5.0 5.6 0.87 6.7 1.04 7.8 1.22 8.4 1.31 9.5 1.48 10.6 1.66 11.8 1.83
5 10.0
15.0
5.6
5.6
0.87
0.87
6.7
6.7
1.04
1.05
7.8
7.8
1.22
1.22
8.4
8.4
1.31
1.31
9.5
9.5
1.48
1.49
10.6
10.6
1.66
1.66
11.8
11.8
1.84
1.84
30% 20.0 5.6 0.87 6.7 1.05 7.8 1.23 8.4 1.32 9.5 1.49 10.6 1.67 11.8 1.84
25.0 5.6 0.88 6.7 1.06 7.8 1.24 8.4 1.33 9.5 1.50 10.6 1.68 11.8 1.85
30.0 5.6 0.91 6.7 1.09 7.8 1.26 8.4 1.35 9.5 1.53 10.6 1.71 11.8 1.89
35.0 5.6 1.50 6.7 1.65 7.8 1.73 8.4 1.74 9.5 1.82 10.6 1.95 11.8 2.09
40.0 5.6 1.75 6.7 1.94 7.8 2.12 8.4 2.21 9.5 2.36 10.6 2.51 11.8 2.65
6 43.0
46.0
5.6
5.6
1.91
2.07
6.7
6.7
2.12
2.32
7.8
7.8
2.34
2.55
8.4
8.4
2.43
2.66
9.5
9.5
2.62
2.88
10.6
10.6
2.79
3.07
11.8
11.8
2.94
3.26

Indoor air temp䋮䋺㷄WB


Combination(%) Outdoor 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp. TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
7 -10.0
kW
3.7
kW
0.58
kW
4.5
kW
0.70
kW
5.2
kW
0.81
kW
5.6
kW
0.87
kW
6.4
kW
0.99
kW
7.1
kW
1.11
kW
7.8
kW
1.22
-5.0 3.7 0.58 4.5 0.70 5.2 0.81 5.6 0.87 6.4 0.99 7.1 1.11 7.8 1.22
0.0 3.7 0.58 4.5 0.70 5.2 0.81 5.6 0.87 6.4 0.99 7.1 1.11 7.8 1.22
5.0 3.7 0.58 4.5 0.70 5.2 0.81 5.6 0.87 6.4 0.99 7.1 1.11 7.8 1.22
10.0 3.7 0.58 4.5 0.70 5.2 0.81 5.6 0.87 6.4 0.99 7.1 1.11 7.8 1.22
15.0 3.7 0.58 4.5 0.70 5.2 0.82 5.6 0.87 6.4 0.99 7.1 1.11 7.8 1.22

8 20% 20.0
25.0
3.7
3.7
0.58
0.59
4.5
4.5
0.70
0.70
5.2
5.2
0.82
0.82
5.6
5.6
0.87
0.88
6.4
6.4
1.00
1.00
7.1
7.1
1.11
1.11
7.8
7.8
1.23
1.23
30.0 3.7 0.59 4.5 0.72 5.2 0.83 5.6 0.89 6.4 1.01 7.1 1.13 7.8 1.25
35.0 3.7 1.17 4.5 1.05 5.2 1.02 5.6 1.05 6.4 1.13 7.1 1.23 7.8 1.33
40.0 3.7 1.33 4.5 1.45 5.2 1.56 5.6 1.61 6.4 1.69 7.1 1.78 7.8 1.85
43.0 3.7 1.43 4.5 1.57 5.2 1.69 5.6 1.75 6.4 1.86 7.1 1.95 7.8 2.04
46.0 3.7 1.54 4.5 1.69 5.2 1.84 5.6 1.91 6.4 2.03 7.1 2.14 7.8 2.24
9 9-10

5GEKPFF 
Capacity Table

1. Capacity Ratio of Outdoor Unit

1-4. U-10MF2E8 (Heating) Capacity Ratio 20-130%


TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp䋮䋺㷄DB
Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB ?WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 26.7 9.00 24.6 8.31 23.2 7.84 23.2 7.84 23.2 7.84 23.2 7.84 20.0 6.97
-14.7 -15.0 28.4 9.20 26.1 8.50 24.6 8.02 24.6 8.02 24.6 8.02 24.6 8.02 21.4 7.12
-9.6 -10.0 30.4 9.47 28.1 8.76 26.5 8.28 26.5 8.28 26.5 8.28 26.5 8.28 23.2 7.33
-4.4 -5.0 32.8 9.69 30.7 9.13 29.0 8.62 29.0 8.62 29.0 8.62 29.0 8.62 25.6 7.61
-1.8 -2.5 33.9 9.69 32.3 9.35 30.5 8.84 30.5 8.84 30.5 8.84 30.5 8.84 27.1 7.81
0.8 0.0 35.5 9.69 34.2 9.58 32.4 9.05 32.4 9.05 32.4 9.05 32.4 9.05 27.7 7.58
130% 2.8 2.0 37.0 9.69 35.9 9.69 33.9 9.11 33.9 9.11 33.9 9.11 32.6 8.46 27.7 7.18
6.0 5.0 39.5 9.69 36.4 8.91 33.9 8.23 33.9 8.23 33.9 8.23 32.6 7.65 27.7 6.48
7.0 6.0 40.1 9.55 36.4 8.54 33.9 7.90 33.9 7.90 33.9 7.90 32.6 7.34 27.7 6.22
8.6 7.5 40.1 8.91 36.4 7.98 33.9 7.38 33.9 7.38 33.9 7.38 32.6 6.88 27.7 5.84
11.2 10.0 40.1 7.87 36.4 7.07 33.9 6.56 33.9 6.56 33.9 6.56 32.6 6.15 27.7 5.25
16.4 15.0 40.1 6.04 36.4 5.47 33.9 5.09 33.9 5.09 33.9 5.09 32.6 4.86 27.7 4.18
24.0 18.0 40.1 5.10 36.4 4.66 33.9 4.37 33.9 4.37 33.9 4.37 32.6 4.23 27.7 3.66

Indoor air temp䋮䋺㷄DB


1
Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 26.8 8.93 24.6 8.25 23.2 7.79 23.2 7.79 23.2 7.79 21.4 7.28 18.5 6.46
-14.7 -15.0 28.4 9.13 26.2 8.44 24.6 7.97 24.6 7.97 24.6 7.97 22.8 7.45 19.8 6.59
-9.6
-4.4
-10.0
-5.0
30.5
32.9
9.41
9.69
28.1
30.7
8.71
9.07
26.5
29.0
8.22
8.57
26.5
29.0
8.22
8.57
26.5
29.0
8.22
8.57
24.7
27.1
7.68
7.99
21.4
23.6
6.77
7.03
2
-1.8 -2.5 34.1 9.69 32.3 9.29 30.5 8.78 30.5 8.78 30.5 8.78 28.6 8.19 24.9 7.20
0.8 0.0 35.7 9.69 34.2 9.50 32.4 8.98 32.4 8.98 32.4 8.98 29.4 7.99 25.0 6.82
120% 2.8 2.0 37.3 9.69 35.5 9.47 33.1 8.75 33.1 8.75 33.1 8.75 29.4 7.57 25.0 6.45
6.0 5.0 39.2 9.52 35.5 8.53 33.1 7.89 33.1 7.89 33.1 7.89 29.4 6.84 25.0 5.81
7.0 6.0 39.2 9.11 35.5 8.17 33.1 7.56 33.1 7.56 33.1 7.56 29.4 6.57 25.0 5.58
8.6
11.2
7.5
10.0
39.2
39.2
8.49
7.50
35.5
35.5
7.63
6.76
33.1
33.1
7.07
6.28
33.1
33.1
7.07
6.28
33.1
33.1
7.07
6.28
29.4
29.4
6.15
5.50
25.0
25.0
5.25
4.71
3
16.4 15.0 39.2 5.74 35.5 5.21 33.1 4.86 33.1 4.86 33.1 4.86 29.4 4.35 25.0 3.76
24.0 18.0 39.2 4.99 35.5 4.57 33.1 4.28 33.1 4.28 33.1 4.28 29.4 3.85 25.0 3.35

Indoor air temp䋮䋺㷄DB


Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor
capacity ratio
air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI 4
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 26.8 8.86 24.7 8.19 23.2 7.74 23.2 7.74 22.2 7.45 19.6 6.68 16.9 5.94
-14.7 -15.0 28.4 9.07 26.2 8.39 24.7 7.92 24.7 7.92 23.7 7.63 20.9 6.84 18.1 6.07
-9.6 -10.0 30.5 9.35 28.2 8.65 26.6 8.17 26.6 8.17 25.5 7.87 22.6 7.04 19.6 6.23
-4.4 -5.0 33.1 9.69 30.7 9.01 29.0 8.51 29.0 8.51 27.9 8.19 24.8 7.33 21.5 6.46
-1.8
0.8
-2.5
0.0
34.3
35.9
9.69
9.69
32.3
34.2
9.23
9.43
30.6
32.3
8.72
8.87
30.6
32.3
8.72
8.87
29.5
30.2
8.39
8.19
26.2
26.3
7.50
7.11
22.4
22.4
6.46
6.09 5
110% 2.8 2.0 37.4 9.69 34.7 9.07 32.3 8.39 32.3 8.39 30.2 7.75 26.3 6.73 22.4 5.76
6.0 5.0 38.3 9.08 34.7 8.16 32.3 7.56 32.3 7.56 30.2 7.00 26.3 6.08 22.4 5.18
7.0 6.0 38.3 8.69 34.7 7.81 32.3 7.25 32.3 7.25 30.2 6.71 26.3 5.83 22.4 4.98
8.6 7.5 38.3 8.09 34.7 7.29 32.3 6.77 32.3 6.77 30.2 6.28 26.3 5.47 22.4 4.68
11.2 10.0 38.3 7.14 34.7 6.45 32.3 6.01 32.3 6.01 30.2 5.60 26.3 4.89 22.4 4.21
16.4
24.0
15.0
18.0
38.3
38.3
5.44
4.89
34.7
34.7
4.96
4.47
32.3
32.3
4.64
4.19
32.3
32.3
4.64
4.19
30.2
30.2
4.38
3.96
26.3
26.3
3.87
3.50
22.4
22.4
3.36
3.04 6
Indoor air temp䋮䋺㷄DB
Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8
-14.7
-20.0
-15.0
26.9
28.5
8.80
9.01
24.7
26.2
8.14
8.34
23.2
24.7
7.69
7.87
21.7
23.1
7.23
7.41
20.2
21.5
6.78
6.94
17.8
19.0
6.10
6.24
15.4
16.5
5.44
5.54
7
-9.6 -10.0 30.6 9.29 28.2 8.60 26.6 8.13 24.9 7.65 23.2 7.16 20.5 6.43 17.8 5.69
-4.4 -5.0 33.3 9.67 30.8 8.96 29.0 8.46 27.2 7.96 25.4 7.45 22.5 6.67 19.6 5.89
-1.8 -2.5 34.5 9.69 32.4 9.17 30.6 8.66 28.7 8.14 26.8 7.62 23.3 6.66 19.8 5.73
0.8 0.0 36.1 9.69 33.8 9.18 31.5 8.50 29.2 7.85 26.8 7.20 23.3 6.28 19.8 5.40
100% 2.8 2.0 37.3 9.65 33.8 8.67 31.5 8.03 29.2 7.42 26.8 6.82 23.3 5.94 19.8 5.11
6.0
7.0
5.0
6.0
37.3
37.3
8.66
8.28
33.8
33.8
7.79
7.47
31.5
31.5
7.24
6.92
29.2
29.2
6.69
6.41
26.8
26.8
6.15
5.90
23.3
23.3
5.37
5.15
19.8
19.8
4.59
4.41
8
8.6 7.5 37.3 7.70 33.8 6.95 31.5 6.47 29.2 5.99 26.8 5.52 23.3 4.83 19.8 4.15
11.2 10.0 37.3 6.79 33.8 6.15 31.5 5.74 29.2 5.33 26.8 4.92 23.3 4.33 19.8 3.73
16.4 15.0 37.3 5.16 33.8 4.72 31.5 4.43 29.2 4.15 26.8 3.85 23.3 3.43 19.8 2.99
24.0 18.0 37.3 4.77 33.8 4.37 31.5 4.10 29.2 3.83 26.8 3.56 23.3 3.16 19.8 2.75

9-11 9

5GEKPFF 
Capacity Table

1. Capacity Ratio of Outdoor Unit

U-10MF2E8 (Heating) Capacity Ratio 20-130%


TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp䋮䋺㷄DB
Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 27.2 8.59 24.9 7.96 23.4 7.54 21.9 7.12 20.3 6.70 17.9 6.07 15.4 5.45
-14.7 -15.0 28.8 8.81 26.5 8.17 24.9 7.74 23.3 7.30 21.6 6.86 19.1 6.20 16.5 5.54
-9.6 -10.0 30.9 9.11 28.4 8.44 26.8 7.99 25.0 7.53 23.3 7.07 20.6 6.37 17.8 5.67
-4.4 -5.0 33.6 9.47 30.5 8.57 28.4 8.00 26.2 7.43 24.2 6.87 21.0 6.07 17.9 5.29
-1.8 -2.5 33.6 8.98 30.5 8.14 28.4 7.58 26.2 7.05 24.2 6.53 21.0 5.76 17.9 5.03
0.8 0.0 33.6 8.42 30.5 7.64 28.4 7.13 26.2 6.63 24.2 6.14 21.0 5.43 17.9 4.73
90% 2.8 2.0 33.6 7.92 30.5 7.20 28.4 6.73 26.2 6.26 24.2 5.80 21.0 5.13 17.9 4.46
6.0 5.0 33.6 7.07 30.5 6.44 28.4 6.03 26.2 5.62 24.2 5.21 21.0 4.59 17.9 3.98
7.0 6.0 33.6 6.75 30.5 6.16 28.4 5.77 26.2 5.38 24.2 4.99 21.0 4.41 17.9 3.83
8.6 7.5 33.6 6.26 30.5 5.73 28.4 5.37 26.2 5.02 24.2 4.66 21.0 4.13 17.9 3.59
11.2 10.0 33.6 5.49 30.5 5.04 28.4 4.75 26.2 4.45 24.2 4.15 21.0 3.70 17.9 3.23
16.4 15.0 33.6 4.35 30.5 3.98 28.4 3.74 26.2 3.49 24.2 3.25 21.0 2.91 17.9 2.59
24.0 18.0 33.6 4.35 30.5 3.98 28.4 3.74 26.2 3.49 24.2 3.25 21.0 2.89 17.9 2.52
1 Indoor air temp䋮䋺㷄DB
Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 27.7 8.48 25.4 7.90 23.8 7.50 22.2 7.11 20.6 6.71 18.1 6.12 15.6 5.54
-14.7 -15.0 29.4 8.72 26.9 8.11 25.2 7.67 23.3 7.18 21.5 6.71 18.7 6.01 15.9 5.34
2 -9.6
-4.4
-10.0
-5.0
29.9
29.9
8.43
7.71
27.1
27.1
7.72
7.07
25.2
25.2
7.26
6.65
23.3
23.3
6.80
6.24
21.5
21.5
6.34
5.83
18.7
18.7
5.67
5.23
15.9
15.9
5.00
4.64
-1.8 -2.5 29.9 7.29 27.1 6.69 25.2 6.30 23.3 5.91 21.5 5.53 18.7 4.95 15.9 4.39
0.8 0.0 29.9 6.82 27.1 6.27 25.2 5.90 23.3 5.54 21.5 5.19 18.7 4.65 15.9 4.12
80% 2.8 2.0 29.9 6.39 27.1 5.89 25.2 5.56 23.3 5.22 21.5 4.89 18.7 4.38 15.9 3.84
6.0 5.0 29.9 5.67 27.1 5.25 25.2 4.95 23.3 4.66 21.5 4.36 18.7 3.90 15.9 3.42
7.0 6.0 29.9 5.41 27.1 5.00 25.2 4.73 23.3 4.45 21.5 4.17 18.7 3.73 15.9 3.28
3 8.6
11.2
7.5
10.0
29.9
29.9
5.00
4.35
27.1
27.1
4.64
4.07
25.2
25.2
4.40
3.87
23.3
23.3
4.15
3.66
21.5
21.5
3.89
3.45
18.7
18.7
3.49
3.12
15.9
15.9
3.08
2.77
16.4 15.0 29.9 3.91 27.1 3.58 25.2 3.37 23.3 3.16 21.5 2.94 18.7 2.62 15.9 2.29
24.0 18.0 29.9 3.91 27.1 3.58 25.2 3.37 23.3 3.16 21.5 2.94 18.7 2.62 15.9 2.29

Indoor air temp䋮䋺㷄DB


Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
4 :Indoor/outdoor
capacity ratio
air temp.
㷄DB 㷄WB
TC
kW
PI
kW
TC
kW
PI
kW
TC
kW
PI
kW
TC
kW
PI
kW
TC
kW
PI
kW
TC
kW
PI
kW
TC
kW
PI
kW
-19.8 -20.0 26.1 7.67 23.7 7.11 22.1 6.73 20.4 6.37 18.8 6.01 16.3 5.47 13.9 4.95
-14.7 -15.0 26.1 7.29 23.7 6.77 22.1 6.44 20.4 6.08 18.8 5.72 16.3 5.19 13.9 4.66
-9.6 -10.0 26.1 6.79 23.7 6.32 22.1 6.01 20.4 5.69 18.8 5.38 16.3 4.89 13.9 4.37
-4.4 -5.0 26.1 6.18 23.7 5.76 22.1 5.47 20.4 5.20 18.8 4.91 16.3 4.47 13.9 4.03

5 -1.8
0.8
-2.5
0.0
26.1
26.1
5.82
5.43
23.7
23.7
5.43
5.07
22.1
22.1
5.17
4.83
20.4
20.4
4.91
4.59
18.8
18.8
4.64
4.34
16.3
16.3
4.23
3.95
13.9
13.9
3.80
3.51
70% 2.8 2.0 26.1 5.07 23.7 4.75 22.1 4.53 20.4 4.30 18.8 4.07 16.3 3.69 13.9 3.26
6.0 5.0 26.1 4.47 23.7 4.20 22.1 4.01 20.4 3.81 18.8 3.59 16.3 3.25 13.9 2.89
7.0 6.0 26.1 4.25 23.7 4.00 22.1 3.82 20.4 3.63 18.8 3.43 16.3 3.11 13.9 2.78
8.6 7.5 26.1 3.91 23.7 3.70 22.1 3.54 20.4 3.38 18.8 3.20 16.3 2.92 13.9 2.62
11.2 10.0 26.1 3.48 23.7 3.22 22.1 3.10 20.4 2.97 18.8 2.83 16.3 2.60 13.9 2.35

6 16.4
24.0
15.0
18.0
26.1
26.1
3.48
3.48
23.7
23.7
3.20
3.20
22.1
22.1
3.00
3.00
20.4
20.4
2.82
2.82
18.8
18.8
2.63
2.63
16.3
16.3
2.35
2.35
13.9
13.9
2.06
2.06

Indoor air temp䋮䋺㷄DB


Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
7 -19.8
-14.7
-20.0
-15.0
22.4
22.4
6.19
5.82
20.3
20.3
5.85
5.51
18.9
18.9
5.61
5.29
17.5
17.5
5.34
5.08
16.1
16.1
5.08
4.84
14.0
14.0
4.68
4.44
11.9
11.9
4.28
4.03
-9.6 -10.0 22.4 5.39 20.3 5.11 18.9 4.92 17.5 4.71 16.1 4.50 14.0 4.17 11.9 3.79
-4.4 -5.0 22.4 4.87 20.3 4.63 18.9 4.46 17.5 4.28 16.1 4.09 14.0 3.79 11.9 3.46
-1.8 -2.5 22.4 4.57 20.3 4.35 18.9 4.19 17.5 4.03 16.1 3.85 14.0 3.56 11.9 3.20
0.8 0.0 22.4 4.24 20.3 4.04 18.9 3.90 17.5 3.74 16.1 3.58 14.0 3.28 11.9 2.93
60% 2.8 2.0 22.4 3.95 20.3 3.77 18.9 3.64 17.5 3.49 16.1 3.32 14.0 3.03 11.9 2.72
8 6.0
7.0
5.0
6.0
22.4
22.4
3.45
3.26
20.3
20.3
3.29
3.13
18.9
18.9
3.18
3.02
17.5
17.5
3.04
2.91
16.1
16.1
2.91
2.77
14.0
14.0
2.68
2.57
11.9
11.9
2.42
2.33
8.6 7.5 22.4 3.04 20.3 2.88 18.9 2.80 17.5 2.70 16.1 2.59 14.0 2.40 11.9 2.19
11.2 10.0 22.4 3.04 20.3 2.80 18.9 2.64 17.5 2.48 16.1 2.32 14.0 2.14 11.9 1.97
16.4 15.0 22.4 3.04 20.3 2.80 18.9 2.64 17.5 2.48 16.1 2.32 14.0 2.08 11.9 1.83
24.0 18.0 22.4 3.04 20.3 2.80 18.9 2.64 17.5 2.48 16.1 2.32 14.0 2.08 11.9 1.83

9 9-12

5GEKPFF 
Capacity Table

1. Capacity Ratio of Outdoor Unit

U-10MF2E8 (Heating) Capacity Ratio 20-130%


TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp䋮䋺㷄DB
Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 18.7 4.90 16.9 4.73 15.8 4.59 14.6 4.44 13.4 4.25 11.7 3.97 9.9 3.66
-14.7 -15.0 18.7 4.59 16.9 4.44 15.8 4.32 14.6 4.19 13.4 4.03 11.7 3.75 9.9 3.45
-9.6 -10.0 18.7 4.24 16.9 4.10 15.8 3.99 14.6 3.87 13.4 3.74 11.7 3.52 9.9 3.22
-4.4 -5.0 18.7 3.79 16.9 3.68 15.8 3.59 14.6 3.49 13.4 3.37 11.7 3.17 9.9 2.85
-1.8 -2.5 18.7 3.54 16.9 3.44 15.8 3.36 14.6 3.27 13.4 3.16 11.7 2.91 9.9 2.62
0.8 0.0 18.7 3.26 16.9 3.18 15.8 3.10 14.6 3.00 13.4 2.86 11.7 2.65 9.9 2.40
50% 2.8 2.0 18.7 3.02 16.9 2.93 15.8 2.84 14.6 2.75 13.4 2.64 11.7 2.45 9.9 2.23
6.0 5.0 18.7 2.62 16.9 2.51 15.8 2.46 14.6 2.39 13.4 2.31 11.7 2.17 9.9 1.99
7.0 6.0 18.7 2.62 16.9 2.42 15.8 2.34 14.6 2.28 13.4 2.21 11.7 2.08 9.9 1.91
8.6 7.5 18.7 2.62 16.9 2.42 15.8 2.28 14.6 2.14 13.4 2.06 11.7 1.94 9.9 1.80
11.2 10.0 18.7 2.62 16.9 2.42 15.8 2.28 14.6 2.14 13.4 2.01 11.7 1.81 9.9 1.62
16.4 15.0 18.7 2.62 16.9 2.42 15.8 2.28 14.6 2.14 13.4 2.01 11.7 1.81 9.9 1.60
24.0 18.0 18.7 2.62 16.9 2.42 15.8 2.28 14.6 2.14 13.4 2.01 11.7 1.81 9.9 1.60

Indoor air temp䋮䋺㷄DB


1
Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 14.9 3.85 13.5 3.77 12.6 3.71 11.7 3.62 10.7 3.49 9.3 3.28 7.9 3.06
-14.7 -15.0 14.9 3.59 13.5 3.53 12.6 3.47 11.7 3.40 10.7 3.31 9.3 3.10 7.9 2.87
-9.6
-4.4
-10.0
-5.0
14.9
14.9
3.29
2.91
13.5
13.5
3.24
2.89
12.6
12.6
3.19
2.85
11.7
11.7
3.13
2.80
10.7
10.7
3.05
2.68
9.3
9.3
2.90
2.49
7.9
7.9
2.63
2.27
2
-1.8 -2.5 14.9 2.70 13.5 2.68 12.6 2.62 11.7 2.54 10.7 2.44 9.3 2.28 7.9 2.09
0.8 0.0 14.9 2.45 13.5 2.40 12.6 2.35 11.7 2.29 10.7 2.21 9.3 2.08 7.9 1.92
40% 2.8 2.0 14.9 2.21 13.5 2.18 12.6 2.15 11.7 2.10 10.7 2.04 9.3 1.93 7.9 1.79
6.0 5.0 14.9 2.18 13.5 2.02 12.6 1.91 11.7 1.83 10.7 1.79 9.3 1.71 7.9 1.60
7.0 6.0 14.9 2.18 13.5 2.02 12.6 1.91 11.7 1.81 10.7 1.71 9.3 1.64 7.9 1.54
8.6
11.2
7.5
10.0
14.9
14.9
2.18
2.18
13.5
13.5
2.02
2.02
12.6
12.6
1.91
1.91
11.7
11.7
1.81
1.81
10.7
10.7
1.70
1.70
9.3
9.3
1.54
1.54
7.9
7.9
1.45
1.37
3
16.4 15.0 14.9 2.18 13.5 2.02 12.6 1.91 11.7 1.81 10.7 1.70 9.3 1.54 7.9 1.37
24.0 18.0 14.9 2.18 13.5 2.02 12.6 1.91 11.7 1.81 10.7 1.70 9.3 1.54 7.9 1.37

Indoor air temp䋮䋺㷄DB


Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor
capacity ratio
air temp.
㷄DB 㷄WB
TC
kW
PI
kW
TC
kW
PI
kW
TC
kW
PI
kW
TC
kW
PI
kW
TC
kW
PI
kW
TC
kW
PI
kW
TC
kW
PI
kW
4
-19.8 -20.0 11.2 2.97 10.1 2.94 9.5 2.91 8.8 2.85 8.1 2.76 7.0 2.62 6.0 2.46
-14.7 -15.0 11.2 2.76 10.1 2.75 9.5 2.72 8.8 2.68 8.1 2.62 7.0 2.47 6.0 2.26
-9.6 -10.0 11.2 2.51 10.1 2.51 9.5 2.49 8.8 2.44 8.1 2.35 7.0 2.19 6.0 2.01
-4.4 -5.0 11.2 2.17 10.1 2.14 9.5 2.10 8.8 2.05 8.1 1.99 7.0 1.88 6.0 1.74
-1.8
0.8
-2.5
0.0
11.2
11.2
1.94
1.75
10.1
10.1
1.92
1.72
9.5
9.5
1.90
1.71
8.8
8.8
1.86
1.69
8.1
8.1
1.82
1.65
7.0
7.0
1.73
1.58
6.0
6.0
1.61
1.49 5
30% 2.8 2.0 11.2 1.75 10.1 1.63 9.5 1.56 8.8 1.55 8.1 1.53 7.0 1.47 6.0 1.39
6.0 5.0 11.2 1.75 10.1 1.63 9.5 1.55 8.8 1.47 8.1 1.38 7.0 1.31 6.0 1.25
7.0 6.0 11.2 1.75 10.1 1.63 9.5 1.55 8.8 1.47 8.1 1.38 7.0 1.27 6.0 1.21
8.6 7.5 11.2 1.75 10.1 1.63 9.5 1.55 8.8 1.47 8.1 1.38 7.0 1.27 6.0 1.15
11.2 10.0 11.2 1.75 10.1 1.63 9.5 1.55 8.8 1.47 8.1 1.38 7.0 1.27 6.0 1.14
16.4
24.0
15.0
18.0
11.2
11.2
1.75
1.75
10.1
10.1
1.63
1.63
9.5
9.5
1.55
1.55
8.8
8.8
1.47
1.47
8.1
8.1
1.38
1.38
7.0
7.0
1.27
1.27
6.0
6.0
1.14
1.14 6
Indoor air temp䋮䋺㷄DB
Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8
-14.7
-20.0
-15.0
7.5
7.5
2.18
2.02
6.8
6.8
2.17
2.02
6.3
6.3
2.15
1.98
5.8
5.8
2.10
1.92
5.4
5.4
2.04
1.87
4.7
4.7
1.95
1.74
4.0
4.0
1.82
1.61
7
-9.6 -10.0 7.5 1.74 6.8 1.72 6.3 1.70 5.8 1.66 5.4 1.62 4.7 1.54 4.0 1.44
-4.4 -5.0 7.5 1.43 6.8 1.44 6.3 1.43 5.8 1.41 5.4 1.39 4.7 1.34 4.0 1.26
-1.8 -2.5 7.5 1.31 6.8 1.30 6.3 1.30 5.8 1.29 5.4 1.28 4.7 1.24 4.0 1.18
0.8 0.0 7.5 1.31 6.8 1.24 6.3 1.18 5.8 1.18 5.4 1.18 4.7 1.15 4.0 1.10
20% 2.8 2.0 7.5 1.31 6.8 1.24 6.3 1.18 5.8 1.13 5.4 1.09 4.7 1.07 4.0 1.04
6.0
7.0
5.0
6.0
7.5
7.5
1.31
1.31
6.8
6.8
1.24
1.24
6.3
6.3
1.18
1.18
5.8
5.8
1.13
1.13
5.4
5.4
1.07
1.07
4.7
4.7
1.00
1.00
4.0
4.0
0.95
0.92
8
8.6 7.5 7.5 1.31 6.8 1.24 6.3 1.18 5.8 1.13 5.4 1.07 4.7 1.00 4.0 0.91
11.2 10.0 7.5 1.31 6.8 1.24 6.3 1.18 5.8 1.13 5.4 1.07 4.7 1.00 4.0 0.91
16.4 15.0 7.5 1.31 6.8 1.24 6.3 1.18 5.8 1.13 5.4 1.07 4.7 1.00 4.0 0.91
24.0 18.0 7.5 1.31 6.8 1.24 6.3 1.18 5.8 1.13 5.4 1.07 4.7 1.00 4.0 0.91

9-13 9

5GEKPFF 
Capacity Table

1. Capacity Ratio of Outdoor Unit

1-5. U-12MF2E8 (Cooling) Capacity Ratio 20-130%


TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp䋮䋺㷄WB
Combination(%) Outdoor 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 31.2 4.19 36.0 4.84 36.0 4.84 36.0 4.84 40.8 5.49 45.6 6.14 50.4 6.80
-5.0 31.2 4.19 36.0 4.85 36.0 4.85 36.0 4.85 40.8 5.50 45.6 6.16 50.4 6.81
0.0 31.2 4.20 36.0 4.87 36.0 4.87 36.0 4.87 40.8 5.52 45.6 6.18 50.4 6.83
5.0 31.2 4.21 36.0 4.89 36.0 4.89 36.0 4.89 40.8 5.56 45.6 6.22 50.4 6.87
10.0 31.2 4.23 36.0 4.94 36.0 4.94 36.0 4.94 40.8 5.62 45.6 6.30 50.4 6.96
15.0 31.2 4.27 36.0 5.06 36.0 5.06 36.0 5.06 40.8 5.78 45.6 6.48 50.4 7.14
130% 20.0 31.2 4.42 36.0 5.41 36.0 5.41 36.0 5.41 40.8 6.37 45.6 7.49 50.4 8.72
25.0 31.2 5.16 36.0 6.79 36.0 6.79 36.0 6.79 40.8 8.04 45.6 9.38 50.4 10.84
30.0 31.2 6.43 36.0 8.34 36.0 8.34 36.0 8.34 40.8 9.82 45.6 11.42 49.6 12.67
35.0 31.2 7.80 36.0 9.99 36.0 9.99 36.0 9.99 40.8 11.75 44.1 12.67 45.9 12.67
40.0 31.2 9.27 36.0 11.80 36.0 11.80 36.0 11.80 39.0 12.67 40.7 12.67 42.4 12.67
43.0 31.2 10.21 35.5 12.67 35.5 12.67 35.5 12.67 36.6 12.33 36.6 11.33 36.6 10.41
46.0 28.9 9.64 28.9 9.64 28.9 9.64 28.9 9.64 28.9 8.87 28.9 8.15 28.9 7.49
1 Indoor air temp䋮䋺㷄WB
Combination(%) Outdoor 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 28.1 3.77 33.8 4.53 35.2 4.73 35.2 4.73 39.9 5.37 44.6 6.00 49.2 6.63
-5.0 28.1 3.78 33.8 4.54 35.2 4.74 35.2 4.74 39.9 5.38 44.6 6.02 49.2 6.65
2 0.0
5.0
28.1
28.1
3.78
3.79
33.8
33.8
4.54
4.56
35.2
35.2
4.75
4.78
35.2
35.2
4.75
4.78
39.9
39.9
5.39
5.42
44.6
44.6
6.04
6.07
49.2
49.2
6.67
6.72
10.0 28.1 3.81 33.8 4.59 35.2 4.82 35.2 4.82 39.9 5.48 44.6 6.15 49.2 6.80
15.0 28.1 3.86 33.8 4.65 35.2 4.93 35.2 4.93 39.9 5.63 44.6 6.33 49.2 6.98
120% 20.0 28.1 3.99 33.8 4.86 35.2 5.27 35.2 5.27 39.9 6.14 44.6 7.20 49.2 8.36
25.0 28.1 4.67 33.8 5.81 35.2 6.56 35.2 6.56 39.9 7.76 44.6 9.04 49.2 10.43
30.0 28.1 5.82 33.8 7.21 35.2 8.05 35.2 8.05 39.9 9.48 44.6 11.01 49.2 12.65
3 35.0
40.0
28.1
28.1
7.04
8.36
33.8
33.8
8.72
10.34
35.2
35.2
9.67 35.2 9.67 39.9 11.35
11.43 35.2 11.43 38.7 12.67
43.8 12.67
40.4 12.67
45.5 12.67
42.1 12.67
43.0 28.1 9.21 33.8 11.38 35.2 12.57 35.2 12.57 36.6 12.47 36.6 11.48 36.6 10.54
46.0 28.1 10.10 28.9 9.73 28.9 9.73 28.9 9.73 28.9 8.96 28.9 8.24 28.9 7.57

Indoor air temp䋮䋺㷄WB


Combination(%) Outdoor
4 :Indoor/outdoor air temp. TC
14.0
PI TC
16.0
PI TC
18.0
PI TC
19.0
PI TC
21.0
PI TC
23.0
PI TC
25.0
PI
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 25.2 3.38 30.2 4.05 34.3 4.62 34.3 4.62 38.9 5.24 43.5 5.86 48.1 6.48
-5.0 25.2 3.38 30.2 4.06 34.3 4.62 34.3 4.62 38.9 5.25 43.5 5.87 48.1 6.49
0.0 25.2 3.38 30.2 4.07 34.3 4.63 34.3 4.63 38.9 5.27 43.5 5.89 48.1 6.52
5.0 25.2 3.39 30.2 4.08 34.3 4.66 34.3 4.66 38.9 5.29 43.5 5.93 48.1 6.55
5 10.0
15.0
25.2
25.2
3.41
3.45
30.2
30.2
4.11
4.17
34.3
34.3
4.71
4.81
34.3
34.3
4.71
4.81
38.9
38.9
5.35
5.48
43.5
43.5
6.01
6.18
48.1
48.1
6.63
6.81
110% 20.0 25.2 3.58 30.2 4.36 34.3 5.11 34.3 5.11 38.9 5.91 43.5 6.91 48.1 8.02
25.0 25.2 4.21 30.2 5.21 34.3 6.34 34.3 6.34 38.9 7.48 43.5 8.71 48.1 10.03
30.0 25.2 5.23 30.2 6.46 34.3 7.79 34.3 7.79 38.9 9.15 43.5 10.62 48.1 12.18
35.0 25.2 6.33 30.2 7.79 34.3 9.36 34.3 9.36 38.9 10.96 43.3 12.59 45.2 12.67
40.0 25.2 7.50 30.2 9.24 34.3 11.06 34.3 11.06 38.5 12.67 40.1 12.67 41.8 12.67
6 43.0
46.0
25.2
25.2
8.25
9.05
30.2
28.9
10.16
9.83
34.3
28.9
12.16 34.3 12.16 36.6 12.63
9.83 28.9 9.83 28.9 9.05
36.6 11.62
28.9 8.33
36.6 10.68
28.9 7.65

Indoor air temp䋮䋺㷄WB


Combination(%) Outdoor 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
7 -10.0
kW
22.3
kW
3.00
kW
26.8
kW
3.60
kW
31.3
kW
4.20
kW
33.5
kW
4.51
kW
38.0
kW
5.11
kW
42.4
kW
5.72
kW
46.9
kW
6.32
-5.0 22.3 3.00 26.8 3.60 31.3 4.21 33.5 4.52 38.0 5.12 42.4 5.73 46.9 6.34
0.0 22.3 3.00 26.8 3.61 31.3 4.22 33.5 4.53 38.0 5.13 42.4 5.75 46.9 6.35
5.0 22.3 3.01 26.8 3.62 31.3 4.24 33.5 4.54 38.0 5.16 42.4 5.78 46.9 6.40
10.0 22.3 3.03 26.8 3.65 31.3 4.27 33.5 4.58 38.0 5.21 42.4 5.86 46.9 6.47
15.0 22.3 3.07 26.8 3.70 31.3 4.35 33.5 4.68 38.0 5.34 42.4 6.01 46.9 6.65

8 100% 20.0
25.0
22.3
22.3
3.19
3.77
26.8
26.8
3.89
4.64
31.3
31.3
4.61
5.60
33.5
33.5
4.97
6.11
38.0
38.0
5.71
7.19
42.4
42.4
6.64
8.37
46.9
46.9
7.68
9.63
30.0 22.3 4.68 26.8 5.75 31.3 6.91 33.5 7.53 38.0 8.82 42.4 10.22 46.9 11.71
35.0 22.3 5.63 26.8 6.92 31.3 8.31 33.5 9.05 37.8 10.53 42.4 12.14 44.9 12.67
40.0 22.3 6.69 26.8 8.20 31.3 9.84 33.5 10.69 38.0 12.50 39.8 12.67 41.5 12.67
43.0 22.3 7.35 26.8 9.02 31.3 10.81 33.5 11.77 36.4 12.67 36.6 11.78 36.6 10.82
46.0 22.3 8.05 26.8 9.89 28.9 10.34 28.9 9.93 28.9 9.14 28.9 8.41 28.9 7.73
9 9-14

5GEKPFF 
Capacity Table

1. Capacity Ratio of Outdoor Unit

U-12MF2E8 (Cooling) Capacity Ratio 20-130%


TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp䋮䋺㷄WB
Combination(%) Outdoor 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 20.1 2.70 24.1 3.24 28.1 3.78 30.2 4.05 34.2 4.60 38.2 5.14 42.2 5.68
-5.0 20.1 2.70 24.1 3.24 28.1 3.78 30.2 4.05 34.2 4.61 38.2 5.15 42.2 5.70
0.0 20.1 2.71 24.1 3.25 28.1 3.79 30.2 4.06 34.2 4.62 38.2 5.17 42.2 5.72
5.0 20.1 2.71 24.1 3.26 28.1 3.81 30.2 4.08 34.2 4.63 38.2 5.19 42.2 5.75
10.0 20.1 2.72 24.1 3.28 28.1 3.83 30.2 4.11 34.2 4.68 38.2 5.24 42.2 5.81
15.0 20.1 2.75 24.1 3.32 28.1 3.89 30.2 4.18 34.2 4.77 38.2 5.36 42.2 5.95
90% 20.0 20.1 2.84 24.1 3.45 28.1 4.08 30.2 4.40 34.2 5.04 38.2 5.69 42.2 6.44
25.0 20.1 3.32 24.1 4.06 28.1 4.85 30.2 5.28 34.2 6.16 38.2 7.11 42.2 8.14
30.0 20.1 4.14 24.1 5.04 28.1 6.01 30.2 6.52 34.2 7.59 38.2 8.73 42.2 9.96
35.0 20.1 5.00 24.1 6.08 28.1 7.24 30.2 7.86 34.2 9.13 38.2 10.49 42.2 11.92
40.0 20.1 5.92 24.1 7.20 28.1 8.58 30.2 9.29 34.2 10.80 38.2 12.40 40.2 12.67
43.0 20.1 6.51 24.1 7.93 28.1 9.44 30.2 10.23 34.2 11.88 36.6 12.52 36.6 11.52
46.0 20.1 7.12 24.1 8.69 28.1 10.35 28.9 10.41 28.9 9.59 28.9 8.82 28.9 8.12

Indoor air temp䋮䋺㷄WB


1
Combination(%) Outdoor 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp. TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 17.9 2.40 21.4 2.88 25.0 3.36 26.8 3.60 30.4 4.08 33.9 4.57 37.5 5.05
-5.0
0.0
17.9
17.9
2.40
2.40
21.4
21.4
2.88
2.89
25.0
25.0
3.37
3.37
26.8
26.8
3.60
3.61
30.4
30.4
4.09
4.10
33.9
33.9
4.57
4.59
37.5
37.5
5.06
5.08 2
5.0 17.9 2.41 21.4 2.89 25.0 3.38 26.8 3.62 30.4 4.11 33.9 4.61 37.5 5.10
10.0 17.9 2.42 21.4 2.91 25.0 3.39 26.8 3.65 30.4 4.14 33.9 4.64 37.5 5.14
15.0 17.9 2.43 21.4 2.93 25.0 3.44 26.8 3.69 30.4 4.21 33.9 4.72 37.5 5.25
80% 20.0 17.9 2.50 21.4 3.03 25.0 3.57 26.8 3.85 30.4 4.41 33.9 4.97 37.5 5.53
25.0 17.9 2.84 21.4 3.51 25.0 4.16 26.8 4.51 30.4 5.21 33.9 5.98 37.5 6.79
30.0
35.0
17.9
17.9
3.63
4.38
21.4
21.4
4.37
5.29
25.0
25.0
5.17
6.24
26.8
26.8
5.58
6.74
30.4
30.4
6.46
7.79
33.9
33.9
7.38
8.89
37.5 8.35
37.5 10.05 3
40.0 17.9 5.19 21.4 6.26 25.0 7.40 26.8 8.00 30.4 9.23 33.9 10.53 37.5 11.89
43.0 17.9 5.70 21.4 6.89 25.0 8.15 26.8 8.80 30.4 10.16 33.9 11.59 36.6 12.43
46.0 17.9 6.24 21.4 7.55 25.0 8.93 26.8 9.66 28.9 10.17 28.9 9.38 28.9 8.62

Indoor air temp䋮䋺㷄WB


Combination(%) Outdoor
:Indoor/outdoor air temp.
TC
14.0
PI TC
16.0
PI TC
18.0
PI TC
19.0
PI TC
21.0
PI TC
23.0
PI TC
25.0
PI
4
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 15.6 2.10 18.8 2.52 21.9 2.94 23.5 3.15 26.6 3.57 29.7 3.99 32.8 4.42
-5.0 15.6 2.10 18.8 2.52 21.9 2.94 23.5 3.15 26.6 3.57 29.7 4.00 32.8 4.43
0.0 15.6 2.10 18.8 2.52 21.9 2.95 23.5 3.16 26.6 3.58 29.7 4.01 32.8 4.43
5.0 15.6 2.11 18.8 2.52 21.9 2.95 23.5 3.17 26.6 3.59 29.7 4.02 32.8 4.45
10.0
15.0
15.6
15.6
2.11
2.13
18.8
18.8
2.53
2.56
21.9
21.9
2.97
3.00
23.5
23.5
3.18
3.21
26.6
26.6
3.61
3.66
29.7
29.7
4.05
4.10
32.8
32.8
4.48
4.55
5
70% 20.0 15.6 2.17 18.8 2.62 21.9 3.09 23.5 3.32 26.6 3.79 29.7 4.27 32.8 4.75
25.0 15.6 2.40 18.8 2.95 21.9 3.51 23.5 3.79 26.6 4.36 29.7 4.95 32.8 5.58
30.0 15.6 3.15 18.8 3.76 21.9 4.40 23.5 4.73 26.6 5.42 29.7 6.15 32.8 6.91
35.0 15.6 3.80 18.8 4.54 21.9 5.32 23.5 5.72 26.6 6.56 29.7 7.43 32.8 8.34
40.0 15.6 4.50 18.8 5.38 21.9 6.31 23.5 6.79 26.6 7.78 29.7 8.81 32.8 9.89
43.0
46.0
15.6
15.6
4.93
5.40
18.8
18.8
5.92
6.48
21.9
21.9
6.94
7.61
23.5
23.5
7.48
8.20
26.6
26.6
8.57
9.40
29.7 9.71
28.9 10.12
32.8 10.90
28.9 9.31
6
Indoor air temp䋮䋺㷄WB
Combination(%) Outdoor 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
-10.0
kW
13.4
kW
1.80
kW
16.1
kW
2.16
kW
18.8
kW
2.52
kW
20.1
kW
2.70
kW
22.8
kW
3.06
kW
25.5
kW
3.42
kW
28.1
kW
3.78
7
-5.0 13.4 1.80 16.1 2.16 18.8 2.52 20.1 2.71 22.8 3.07 25.5 3.43 28.1 3.79
0.0 13.4 1.80 16.1 2.16 18.8 2.52 20.1 2.71 22.8 3.07 25.5 3.43 28.1 3.79
5.0 13.4 1.80 16.1 2.16 18.8 2.52 20.1 2.71 22.8 3.08 25.5 3.44 28.1 3.80
10.0 13.4 1.81 16.1 2.17 18.8 2.53 20.1 2.72 22.8 3.09 25.5 3.46 28.1 3.83
15.0 13.4 1.82 16.1 2.18 18.8 2.55 20.1 2.74 22.8 3.11 25.5 3.49 28.1 3.87
60% 20.0
25.0
13.4
13.4
1.85
1.99
16.1
16.1
2.23
2.43
18.8
18.8
2.62
2.89
20.1
20.1
2.81
3.11
22.8
22.8
3.20
3.57
25.5
25.5
3.60
4.03
28.1
28.1
4.00
4.51
8
30.0 13.4 2.71 16.1 3.19 18.8 3.68 20.1 3.95 22.8 4.48 25.5 5.04 28.1 5.62
35.0 13.4 3.26 16.1 3.85 18.8 4.46 20.1 4.78 22.8 5.43 25.5 6.11 28.1 6.81
40.0 13.4 3.84 16.1 4.55 18.8 5.29 20.1 5.67 22.8 6.45 25.5 7.25 28.1 8.08
43.0 13.4 4.22 16.1 5.00 18.8 5.82 20.1 6.24 22.8 7.10 25.5 7.99 28.1 8.91
46.0 13.4 4.61 16.1 5.48 18.8 6.38 20.1 6.84 22.8 7.79 25.5 8.78 28.1 9.79
9-15 9

5GEKPFF 
Capacity Table

1. Capacity Ratio of Outdoor Unit

U-12MF2E8 (Cooling) Capacity Ratio 20-130%


TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp䋮䋺㷄WB
Combination(%) Outdoor 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 11.2 1.50 13.4 1.80 15.6 2.10 16.8 2.25 19.0 2.55 21.2 2.85 23.5 3.15
-5.0 11.2 1.50 13.4 1.80 15.6 2.10 16.8 2.25 19.0 2.55 21.2 2.85 23.5 3.16
0.0 11.2 1.50 13.4 1.80 15.6 2.10 16.8 2.25 19.0 2.55 21.2 2.86 23.5 3.16
5.0 11.2 1.50 13.4 1.80 15.6 2.11 16.8 2.25 19.0 2.56 21.2 2.86 23.5 3.17
10.0 11.2 1.50 13.4 1.81 15.6 2.11 16.8 2.26 19.0 2.57 21.2 2.87 23.5 3.18
15.0 11.2 1.51 13.4 1.82 15.6 2.12 16.8 2.27 19.0 2.59 21.2 2.90 23.5 3.20
50% 20.0 11.2 1.53 13.4 1.84 15.6 2.15 16.8 2.32 19.0 2.63 21.2 2.96 23.5 3.28
25.0 11.2 1.62 13.4 1.96 15.6 2.32 16.8 2.50 19.0 2.85 21.2 3.21 23.5 3.57
30.0 11.2 2.30 13.4 2.66 15.6 3.04 16.8 3.23 19.0 3.63 21.2 4.05 23.5 4.46
35.0 11.2 2.74 13.4 3.20 15.6 3.67 16.8 3.91 19.0 4.40 21.2 4.91 23.5 5.42
40.0 11.2 3.22 13.4 3.78 15.6 4.34 16.8 4.64 19.0 5.23 21.2 5.84 23.5 6.45
43.0 11.2 3.53 13.4 4.14 15.6 4.78 16.8 5.10 19.0 5.76 21.2 6.43 23.5 7.11
46.0 11.2 3.85 13.4 4.53 15.6 5.23 16.8 5.59 19.0 6.32 21.2 7.05 23.5 7.81
1 Indoor air temp䋮䋺㷄WB
Combination(%) Outdoor 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 8.9 1.19 10.7 1.44 12.5 1.68 13.4 1.80 15.2 2.04 17.0 2.28 18.8 2.52

2 -5.0
0.0
8.9
8.9
1.19
1.20
10.7
10.7
1.44
1.44
12.5
12.5
1.68
1.68
13.4
13.4
1.80
1.80
15.2
15.2
2.05
2.05
17.0
17.0
2.28
2.28
18.8
18.8
2.52
2.52
5.0 8.9 1.20 10.7 1.44 12.5 1.68 13.4 1.80 15.2 2.05 17.0 2.29 18.8 2.52
10.0 8.9 1.20 10.7 1.45 12.5 1.68 13.4 1.81 15.2 2.05 17.0 2.29 18.8 2.53
15.0 8.9 1.20 10.7 1.45 12.5 1.69 13.4 1.82 15.2 2.06 17.0 2.31 18.8 2.55
40% 20.0 8.9 1.21 10.7 1.47 12.5 1.71 13.4 1.84 15.2 2.08 17.0 2.33 18.8 2.59
25.0 8.9 1.27 10.7 1.53 12.5 1.79 13.4 1.93 15.2 2.20 17.0 2.47 18.8 2.74

3 30.0
35.0
8.9
8.9
1.91
2.26
10.7
10.7
2.18
2.61
12.5
12.5
2.45
2.95
13.4
13.4
2.59
3.12
15.2
15.2
2.87
3.48
17.0
17.0
3.16
3.83
18.8
18.8
3.45
4.19
40.0 8.9 2.64 10.7 3.06 12.5 3.48 13.4 3.69 15.2 4.12 17.0 4.55 18.8 4.99
43.0 8.9 2.89 10.7 3.35 12.5 3.81 13.4 4.05 15.2 4.53 17.0 5.00 18.8 5.49
46.0 8.9 3.14 10.7 3.65 12.5 4.17 13.4 4.43 15.2 4.96 17.0 5.49 18.8 6.04

Indoor air temp䋮䋺㷄WB


4 Combination(%) Outdoor
:Indoor/outdoor air temp.
TC
14.0
PI TC
16.0
PI TC
18.0
PI TC
19.0
PI TC
21.0
PI TC
23.0
PI TC
25.0
PI
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 6.7 0.90 8.0 1.08 9.4 1.26 10.1 1.35 11.4 1.53 12.7 1.71 14.1 1.89
-5.0 6.7 0.90 8.0 1.08 9.4 1.26 10.1 1.35 11.4 1.53 12.7 1.71 14.1 1.89
0.0 6.7 0.90 8.0 1.08 9.4 1.26 10.1 1.35 11.4 1.53 12.7 1.71 14.1 1.89
5.0 6.7 0.90 8.0 1.08 9.4 1.26 10.1 1.35 11.4 1.53 12.7 1.71 14.1 1.89
5 10.0
15.0
6.7
6.7
0.91
0.91
8.0
8.0
1.09
1.09
9.4
9.4
1.27
1.27
10.1
10.1
1.36
1.36
11.4
11.4
1.54
1.54
12.7
12.7
1.72
1.72
14.1
14.1
1.90
1.91
30% 20.0 6.7 0.91 8.0 1.10 9.4 1.28 10.1 1.37 11.4 1.56 12.7 1.74 14.1 1.92
25.0 6.7 0.93 8.0 1.12 9.4 1.31 10.1 1.41 11.4 1.60 12.7 1.79 14.1 1.99
30.0 6.7 1.44 8.0 1.66 9.4 1.86 10.1 1.96 11.4 2.17 12.7 2.38 14.1 2.57
35.0 6.7 1.82 8.0 2.05 9.4 2.29 10.1 2.41 11.4 2.63 12.7 2.87 14.1 3.10
40.0 6.7 2.10 8.0 2.39 9.4 2.68 10.1 2.82 11.4 3.10 12.7 3.39 14.1 3.68
6 43.0
46.0
6.7
6.7
2.28
2.46
8.0
8.0
2.60
2.82
9.4
9.4
2.92
3.19
10.1
10.1
3.09
3.36
11.4
11.4
3.40
3.72
12.7
12.7
3.73
4.08
14.1
14.1
4.05
4.44

Indoor air temp䋮䋺㷄WB


Combination(%) Outdoor 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp. TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
7 -10.0
kW
4.5
kW
0.60
kW
5.4
kW
0.71
kW
6.3
kW
0.84
kW
6.7
kW
0.90
kW
7.6
kW
1.02
kW
8.5
kW
1.14
kW
9.4
kW
1.26
-5.0 4.5 0.60 5.4 0.72 6.3 0.84 6.7 0.90 7.6 1.02 8.5 1.14 9.4 1.26
0.0 4.5 0.60 5.4 0.72 6.3 0.84 6.7 0.90 7.6 1.02 8.5 1.14 9.4 1.26
5.0 4.5 0.60 5.4 0.72 6.3 0.84 6.7 0.91 7.6 1.02 8.5 1.14 9.4 1.27
10.0 4.5 0.60 5.4 0.72 6.3 0.84 6.7 0.91 7.6 1.02 8.5 1.14 9.4 1.27
15.0 4.5 0.61 5.4 0.72 6.3 0.84 6.7 0.91 7.6 1.02 8.5 1.15 9.4 1.27

8 20% 20.0
25.0
4.5
4.5
0.61
0.62
5.4
5.4
0.72
0.73
6.3
6.3
0.85
0.86
6.7
6.7
0.91
0.92
7.6
7.6
1.03
1.05
8.5
8.5
1.15
1.17
9.4
9.4
1.28
1.29
30.0 4.5 0.77 5.4 0.91 6.3 1.03 6.7 1.10 7.6 1.22 8.5 1.35 9.4 1.48
35.0 4.5 1.40 5.4 1.55 6.3 1.69 6.7 1.76 7.6 1.89 8.5 2.03 9.4 2.16
40.0 4.5 1.59 5.4 1.76 6.3 1.95 6.7 2.03 7.6 2.20 8.5 2.37 9.4 2.53
43.0 4.5 1.71 5.4 1.91 6.3 2.10 6.7 2.20 7.6 2.40 8.5 2.59 9.4 2.77
46.0 4.5 1.83 5.4 2.05 6.3 2.27 6.7 2.38 7.6 2.60 8.5 2.81 9.4 3.02

9 9-16

5GEKPFF 
Capacity Table

1. Capacity Ratio of Outdoor Unit

1-6. U-12MF2E8 (Heating) Capacity Ratio 20-130%


TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp䋮䋺㷄DB
Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 30.4 10.83 28.1 9.91 26.5 9.30 26.5 9.30 26.5 9.30 26.5 9.30 23.1 7.94
-14.7 -15.0 32.3 11.00 29.9 10.09 28.2 9.48 28.2 9.48 28.2 9.48 28.2 9.48 24.8 8.13
-9.6 -10.0 34.6 11.27 32.1 10.36 30.3 9.75 30.3 9.75 30.3 9.75 30.3 9.75 27.0 8.40
-4.4 -5.0 37.8 11.68 35.1 10.77 33.3 10.15 33.3 10.15 33.3 10.15 33.3 10.15 29.9 8.78
-1.8 -2.5 39.8 11.95 37.1 11.04 35.2 10.41 35.2 10.41 35.2 10.41 35.2 10.41 31.8 9.03
0.8 0.0 42.1 12.21 39.4 11.35 37.4 10.72 37.4 10.72 37.4 10.72 37.4 10.72 33.0 9.02
130% 2.8 2.0 43.7 12.21 41.6 11.66 39.6 11.01 39.6 11.01 39.6 11.01 38.8 10.27 33.0 8.60
6.0 5.0 46.6 12.21 43.3 11.31 40.3 10.36 40.3 10.36 40.3 10.36 38.8 9.34 33.0 7.82
7.0 6.0 47.6 12.21 43.3 10.87 40.3 9.96 40.3 9.96 40.3 9.96 38.8 8.99 33.0 7.53
8.6 7.5 47.8 11.53 43.3 10.19 40.3 9.35 40.3 9.35 40.3 9.35 38.8 8.46 33.0 7.09
11.2 10.0 47.8 10.30 43.3 9.12 40.3 8.38 40.3 8.38 40.3 8.38 38.8 7.60 33.0 6.39
16.4 15.0 47.8 8.05 43.3 7.17 40.3 6.61 40.3 6.61 40.3 6.61 38.8 6.08 33.0 5.15
24.0 18.0 47.8 6.88 43.3 6.17 40.3 5.70 40.3 5.70 40.3 5.70 38.8 5.29 33.0 4.53

Combination(%) Outdoor
Indoor air temp䋮䋺㷄DB
1
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 30.5 10.70 28.1 9.81 26.5 9.21 26.5 9.21 26.5 9.21 24.6 8.39 21.3 7.34
-14.7 -15.0 32.3 10.88 29.9 9.99 28.2 9.39 28.2 9.39 28.2 9.39 26.4 8.58 22.9 7.51
-9.6
-4.4
-10.0
-5.0
34.7
37.8
11.16
11.57
32.1 10.27
35.2 10.68
30.4 9.66 30.4 9.66 30.4
33.3 10.06 33.3 10.06 33.3 10.06
9.66 28.6
31.5
8.87
9.27
24.9
27.6
7.75
8.10
2
-1.8 -2.5 39.9 11.85 37.1 10.94 35.2 10.32 35.2 10.32 35.2 10.32 33.4 9.52 29.3 8.33
0.8 0.0 42.3 12.17 39.5 11.27 37.4 10.63 37.4 10.63 37.4 10.63 35.0 9.62 29.7 8.12
120% 2.8 2.0 44.0 12.21 41.6 11.55 39.4 10.87 39.4 10.87 39.4 10.87 35.0 9.19 29.7 7.72
6.0 5.0 46.6 12.21 42.3 10.82 39.4 9.92 39.4 9.92 39.4 9.92 35.0 8.35 29.7 7.02
7.0 6.0 46.7 11.75 42.3 10.39 39.4 9.54 39.4 9.54 39.4 9.54 35.0 8.04 29.7 6.76
8.6
11.2
7.5
10.0
46.7
46.7
11.00
9.80
42.3
42.3
9.75
8.71
39.4
39.4
8.96
8.01
39.4
39.4
8.96
8.01
39.4
39.4
8.96
8.01
35.0
35.0
7.57
6.80
29.7
29.7
6.37
5.75
3
16.4 15.0 46.7 7.65 42.3 6.84 39.4 6.31 39.4 6.31 39.4 6.31 35.0 5.44 29.7 4.64
24.0 18.0 46.7 6.52 42.3 5.87 39.4 5.44 39.4 5.44 39.4 5.44 35.0 4.74 29.7 4.07

Indoor air temp䋮䋺㷄DB


Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor
capacity ratio
air temp.
㷄DB 㷄WB
TC
kW
PI
kW
TC
kW
PI
kW
TC
kW
PI
kW
TC
kW
PI
kW
TC
kW
PI
kW
TC
kW
PI
kW
TC
kW
PI
kW
4
-19.8 -20.0 30.6 10.59 28.2 9.71 26.6 9.12 26.6 9.12 25.5 8.66 22.6 7.69 19.6 6.75
-14.7 -15.0 32.4 10.77 29.9 9.91 28.2 9.31 28.2 9.31 27.2 8.86 24.2 7.87 21.0 6.90
-9.6 -10.0 34.8 11.06 32.2 10.18 30.4 9.58 30.4 9.58 29.4 9.14 26.2 8.13 22.8 7.12
-4.4 -5.0 38.0 11.48 35.2 10.59 33.3 9.98 33.3 9.98 32.3 9.54 28.9 8.48 25.2 7.43
-1.8
0.8
-2.5
0.0
39.9
42.3
11.75
12.07
37.2
39.5
10.86
11.16
35.2
37.4
10.24 35.2 10.24 34.2
10.54 37.4 10.54 36.0
9.79
9.97
30.6
31.3
8.71
8.57
26.6
26.6
7.60
7.26 5
110% 2.8 2.0 44.2 12.21 41.3 11.34 38.4 10.45 38.4 10.45 36.0 9.53 31.3 8.17 26.6 6.90
6.0 5.0 45.6 11.66 41.3 10.34 38.4 9.50 38.4 9.50 36.0 8.65 31.3 7.43 26.6 6.27
7.0 6.0 45.6 11.19 41.3 9.93 38.4 9.13 38.4 9.13 36.0 8.32 31.3 7.15 26.6 6.03
8.6 7.5 45.6 10.47 41.3 9.30 38.4 8.56 38.4 8.56 36.0 7.81 31.3 6.72 26.6 5.69
11.2 10.0 45.6 9.32 41.3 8.31 38.4 7.66 38.4 7.66 36.0 7.01 31.3 6.05 26.6 5.14
16.4
24.0
15.0
18.0
45.6
45.6
7.26
6.18
41.3
41.3
6.51
5.57
38.4
38.4
6.03
5.19
38.4
38.4
6.03
5.19
36.0
36.0
5.56
4.82
31.3
31.3
4.85
4.23
26.6
26.6
4.15
3.65 6
Indoor air temp䋮䋺㷄DB
Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8
-14.7
-20.0
-15.0
30.6
32.5
10.47
10.66
28.2
30.0
9.61
9.81
26.6
28.3
9.03
9.23
24.9
26.5
8.45
8.64
23.2
24.7
7.87
8.05
20.5
21.9
7.00
7.17
17.8
19.1
6.17
6.30
7
-9.6 -10.0 34.8 10.95 32.3 10.09 30.5 9.50 28.6 8.91 26.7 8.31 23.8 7.39 20.7 6.50
-4.4 -5.0 38.0 11.38 35.3 10.51 33.4 9.90 31.4 9.29 29.4 8.66 26.2 7.72 22.8 6.77
-1.8 -2.5 40.0 11.65 37.2 10.77 35.2 10.15 33.2 9.53 31.1 8.89 27.8 7.93 23.6 6.74
0.8 0.0 42.4 11.97 39.5 11.07 37.4 10.45 34.7 9.63 32.0 8.79 27.8 7.59 23.6 6.44
100% 2.8 2.0 44.4 12.20 40.3 10.88 37.5 10.04 34.7 9.19 32.0 8.38 27.8 7.21 23.6 6.11
6.0
7.0
5.0
6.0
44.4
44.4
11.11
10.66
40.3
40.3
9.87
9.48
37.5
37.5
9.09
8.72
34.7
34.7
8.34
8.01
32.0
32.0
7.60
7.32
27.8
27.8
6.56
6.31
23.6
23.6
5.56
5.35
8
8.6 7.5 44.4 9.97 40.3 8.89 37.5 8.19 34.7 7.53 32.0 6.87 27.8 5.94 23.6 5.05
11.2 10.0 44.4 8.86 40.3 7.92 37.5 7.32 34.7 6.73 32.0 6.17 27.8 5.35 23.6 4.56
16.4 15.0 44.4 6.88 40.3 6.19 37.5 5.75 34.7 5.32 32.0 4.90 27.8 4.29 23.6 3.70
24.0 18.0 44.4 5.85 40.3 5.29 37.5 4.94 34.7 4.59 32.0 4.25 27.8 3.75 23.6 3.26

9-17 9

5GEKPFF 
Capacity Table

1. Capacity Ratio of Outdoor Unit

U-12MF2E8 (Heating) Capacity Ratio 20-130%


TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp䋮䋺㷄DB
Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 30.9 10.05 28.4 9.26 26.7 8.73 25.0 8.19 23.3 7.66 20.6 6.86 17.7 6.10
-14.7 -15.0 32.7 10.27 30.2 9.48 28.4 8.93 26.6 8.39 24.8 7.84 21.9 7.02 19.0 6.22
-9.6 -10.0 35.1 10.59 32.4 9.77 30.6 9.22 28.7 8.65 26.7 8.08 23.7 7.23 20.6 6.38
-4.4 -5.0 38.3 11.01 35.4 10.18 33.4 9.59 31.2 8.96 28.8 8.22 25.0 7.17 21.3 6.17
-1.8 -2.5 40.0 11.20 36.3 10.05 33.8 9.31 31.2 8.60 28.8 7.90 25.0 6.89 21.3 5.93
0.8 0.0 40.0 10.66 36.3 9.56 33.8 8.84 31.2 8.15 28.8 7.48 25.0 6.51 21.3 5.61
90% 2.8 2.0 40.0 10.06 36.3 9.03 33.8 8.36 31.2 7.72 28.8 7.09 25.0 6.18 21.3 5.32
6.0 5.0 40.0 9.05 36.3 8.14 33.8 7.56 31.2 6.98 28.8 6.43 25.0 5.61 21.3 4.81
7.0 6.0 40.0 8.67 36.3 7.81 33.8 7.26 31.2 6.71 28.8 6.17 25.0 5.39 21.3 4.63
8.6 7.5 40.0 8.08 36.3 7.29 33.8 6.78 31.2 6.28 28.8 5.79 25.0 5.07 21.3 4.36
11.2 10.0 40.0 7.15 36.3 6.48 33.8 6.03 31.2 5.61 28.8 5.18 25.0 4.55 21.3 3.94
16.4 15.0 40.0 5.48 36.3 5.01 33.8 4.71 31.2 4.40 28.8 4.10 25.0 3.64 21.3 3.19
24.0 18.0 40.0 4.93 36.3 4.52 33.8 4.25 31.2 3.99 28.8 3.71 25.0 3.31 21.3 2.90
1 Combination(%) Outdoor
Indoor air temp䋮䋺㷄DB
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 31.2 9.71 28.7 8.98 26.9 8.49 25.2 8.00 23.4 7.51 20.6 6.78 17.8 6.08
-14.7 -15.0 33.1 9.97 30.5 9.22 28.6 8.71 26.8 8.20 24.9 7.69 22.0 6.93 18.9 6.15
2 -9.6
-4.4
-10.0
-5.0
35.5
35.6
10.29
9.62
32.2
32.2
9.34
8.72
30.0
30.0
8.71
8.13
27.8
27.8
8.09
7.55
25.5
25.5
7.48
6.99
22.2
22.2
6.61
6.18
18.9
18.9
5.78
5.40
-1.8 -2.5 35.6 9.15 32.2 8.28 30.0 7.73 27.8 7.19 25.5 6.65 22.2 5.88 18.9 5.14
0.8 0.0 35.6 8.59 32.2 7.80 30.0 7.27 27.8 6.77 25.5 6.27 22.2 5.55 18.9 4.85
80% 2.8 2.0 35.6 8.09 32.2 7.36 30.0 6.88 27.8 6.40 25.5 5.94 22.2 5.26 18.9 4.59
6.0 5.0 35.6 7.25 32.2 6.61 30.0 6.19 27.8 5.77 25.5 5.35 22.2 4.74 18.9 4.12
7.0 6.0 35.6 6.92 32.2 6.32 30.0 5.93 27.8 5.53 25.5 5.14 22.2 4.55 18.9 3.97
3 8.6
11.2
7.5
10.0
35.6
35.6
6.44
5.67
32.2
32.2
5.89
5.21
30.0
30.0
5.54
4.91
27.8
27.8
5.17
4.60
25.5
25.5
4.81
4.30
22.2
22.2
4.27
3.84
18.9
18.9
3.74
3.37
16.4 15.0 35.6 4.45 32.2 4.09 30.0 3.85 27.8 3.61 25.5 3.38 22.2 3.07 18.9 2.74
24.0 18.0 35.6 4.45 32.2 4.09 30.0 3.85 27.8 3.61 25.5 3.37 22.2 3.01 18.9 2.65

Indoor air temp䋮䋺㷄DB


Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
4 :Indoor/outdoor
capacity ratio
air temp.
㷄DB 㷄WB
TC
kW
PI
kW
TC
kW
PI
kW
TC
kW
PI
kW
TC
kW
PI
kW
TC
kW
PI
kW
TC
kW
PI
kW
TC
kW
PI
kW
-19.8 -20.0 31.1 9.27 28.2 8.49 26.3 7.99 24.3 7.49 22.4 7.01 19.5 6.31 16.5 5.64
-14.7 -15.0 31.1 8.83 28.2 8.09 26.3 7.61 24.3 7.13 22.4 6.67 19.5 5.99 16.5 5.34
-9.6 -10.0 31.1 8.35 28.2 7.66 26.3 7.21 24.3 6.77 22.4 6.31 19.5 5.66 16.5 5.01
-4.4 -5.0 31.1 7.66 28.2 7.04 26.3 6.63 24.3 6.23 22.4 5.82 19.5 5.24 16.5 4.67

5 -1.8
0.8
-2.5
0.0
31.1
31.1
7.26
6.79
28.2
28.2
6.67
6.26
26.3
26.3
6.29
5.90
24.3
24.3
5.90
5.55
22.4
22.4
5.53
5.21
19.5
19.5
4.97
4.68
16.5
16.5
4.42
4.16
70% 2.8 2.0 31.1 6.38 28.2 5.89 26.3 5.56 24.3 5.24 22.4 4.91 19.5 4.42 16.5 3.91
6.0 5.0 31.1 5.69 28.2 5.27 26.3 4.99 24.3 4.70 22.4 4.40 19.5 3.95 16.5 3.49
7.0 6.0 31.1 5.42 28.2 5.03 26.3 4.77 24.3 4.50 22.4 4.22 19.5 3.79 16.5 3.36
8.6 7.5 31.1 5.03 28.2 4.68 26.3 4.44 24.3 4.20 22.4 3.95 19.5 3.57 16.5 3.17
11.2 10.0 31.1 4.39 28.2 4.12 26.3 3.92 24.3 3.73 22.4 3.52 19.5 3.20 16.5 2.86

6 16.4
24.0
15.0
18.0
31.1
31.1
3.97
3.97
28.2
28.2
3.65
3.65
26.3
26.3
3.44
3.44
24.3
24.3
3.24
3.24
22.4
22.4
3.03
3.03
19.5
19.5
2.71
2.71
16.5
16.5
2.40
2.40

Indoor air temp䋮䋺㷄DB


Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

7 -19.8
-14.7
-20.0
-15.0
26.7
26.7
7.41
7.03
24.2
24.2
6.88
6.56
22.5
22.5
6.53
6.24
20.9
20.9
6.18
5.91
19.2
19.2
5.85
5.58
16.7
16.7
5.35
5.08
14.2
14.2
4.86
4.60
-9.6 -10.0 26.7 6.55 24.2 6.12 22.5 5.83 20.9 5.55 19.2 5.25 16.7 4.80 14.2 4.33
-4.4 -5.0 26.7 5.97 24.2 5.59 22.5 5.33 20.9 5.08 19.2 4.80 16.7 4.40 14.2 3.99
-1.8 -2.5 26.7 5.63 24.2 5.28 22.5 5.04 20.9 4.80 19.2 4.55 16.7 4.17 14.2 3.78
0.8 0.0 26.7 5.26 24.2 4.94 22.5 4.72 20.9 4.49 19.2 4.26 16.7 3.91 14.2 3.50
60% 2.8 2.0 26.7 4.93 24.2 4.64 22.5 4.44 20.9 4.23 19.2 4.01 16.7 3.65 14.2 3.26
8 6.0
7.0
5.0
6.0
26.7
26.7
4.36
4.15
24.2
24.2
4.12
3.92
22.5
22.5
3.94
3.77
20.9
20.9
3.76
3.59
19.2
19.2
3.56
3.41
16.7
16.7
3.25
3.12
14.2
14.2
2.92
2.81
8.6 7.5 26.7 3.84 24.2 3.64 22.5 3.50 20.9 3.35 19.2 3.19 16.7 2.93 14.2 2.65
11.2 10.0 26.7 3.49 24.2 3.22 22.5 3.09 20.9 2.96 19.2 2.84 16.7 2.63 14.2 2.40
16.4 15.0 26.7 3.49 24.2 3.22 22.5 3.04 20.9 2.86 19.2 2.69 16.7 2.42 14.2 2.15
24.0 18.0 26.7 3.49 24.2 3.22 22.5 3.04 20.9 2.86 19.2 2.69 16.7 2.42 14.2 2.15

9 9-18

5GEKPFF 
Capacity Table

1. Capacity Ratio of Outdoor Unit

U-12MF2E8 (Heating) Capacity Ratio 20-130%


TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp䋮䋺㷄DB
Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp. TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 22.2 5.78 20.1 5.50 18.8 5.31 17.4 5.08 16.0 4.85 13.9 4.50 11.8 4.14
-14.7 -15.0 22.2 5.45 20.1 5.19 18.8 5.01 17.4 4.82 16.0 4.63 13.9 4.27 11.8 3.91
-9.6 -10.0 22.2 5.06 20.1 4.82 18.8 4.67 17.4 4.49 16.0 4.31 13.9 4.02 11.8 3.68
-4.4 -5.0 22.2 4.58 20.1 4.38 18.8 4.24 17.4 4.09 16.0 3.92 13.9 3.66 11.8 3.37
-1.8 -2.5 22.2 4.30 20.1 4.12 18.8 3.99 17.4 3.85 16.0 3.71 13.9 3.45 11.8 3.12
0.8 0.0 22.2 3.99 20.1 3.84 18.8 3.71 17.4 3.59 16.0 3.45 13.9 3.18 11.8 2.87
50% 2.8 2.0 22.2 3.73 20.1 3.58 18.8 3.48 17.4 3.35 16.0 3.20 13.9 2.95 11.8 2.68
6.0 5.0 22.2 3.26 20.1 3.14 18.8 3.05 17.4 2.94 16.0 2.83 13.9 2.62 11.8 2.40
7.0 6.0 22.2 3.10 20.1 2.99 18.8 2.90 17.4 2.82 16.0 2.70 13.9 2.52 11.8 2.31
8.6 7.5 22.2 3.01 20.1 2.79 18.8 2.70 17.4 2.62 16.0 2.53 13.9 2.37 11.8 2.19
11.2 10.0 22.2 3.01 20.1 2.79 18.8 2.63 17.4 2.49 16.0 2.34 13.9 2.14 11.8 1.99
16.4 15.0 22.2 3.01 20.1 2.79 18.8 2.63 17.4 2.49 16.0 2.34 13.9 2.12 11.8 1.89
24.0 18.0 22.2 3.01 20.1 2.79 18.8 2.63 17.4 2.49 16.0 2.34 13.9 2.12 11.8 1.89

Indoor air temp䋮䋺㷄DB


1
Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 17.8 4.45 16.1 4.33 15.0 4.23 13.9 4.12 12.8 3.96 11.1 3.71 9.5 3.46
-14.7 -15.0 17.8 4.18 16.1 4.07 15.0 3.98 13.9 3.88 12.8 3.77 11.1 3.53 9.5 3.27
-9.6
-4.4
-10.0
-5.0
17.8
17.8
3.85
3.46
16.1
16.1
3.76
3.38
15.0
15.0
3.69
3.32
13.9
13.9
3.60
3.25
12.8
12.8
3.50
3.17
11.1
11.1
3.31
2.96
9.5
9.5
3.07
2.69
2
-1.8 -2.5 17.8 3.24 16.1 3.17 15.0 3.11 13.9 3.05 12.8 2.94 11.1 2.73 9.5 2.49
0.8 0.0 17.8 2.98 16.1 2.93 15.0 2.87 13.9 2.78 12.8 2.68 11.1 2.50 9.5 2.30
40% 2.8 2.0 17.8 2.76 16.1 2.69 15.0 2.63 13.9 2.56 12.8 2.48 11.1 2.33 9.5 2.15
6.0 5.0 17.8 2.53 16.1 2.35 15.0 2.30 13.9 2.25 12.8 2.19 11.1 2.08 9.5 1.94
7.0 6.0 17.8 2.53 16.1 2.35 15.0 2.23 13.9 2.15 12.8 2.10 11.1 2.01 9.5 1.87
8.6
11.2
7.5
10.0
17.8
17.8
2.53
2.53
16.1
16.1
2.35
2.35
15.0
15.0
2.23
2.23
13.9
13.9
2.12
2.12
12.8
12.8
2.00
2.00
11.1
11.1
1.88
1.81
9.5
9.5
1.78
1.64
3
16.4 15.0 17.8 2.53 16.1 2.35 15.0 2.23 13.9 2.12 12.8 2.00 11.1 1.81 9.5 1.64
24.0 18.0 17.8 2.53 16.1 2.35 15.0 2.23 13.9 2.12 12.8 2.00 11.1 1.81 9.5 1.64

Indoor air temp䋮䋺㷄DB


Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor
capacity ratio
air temp.
㷄DB 㷄WB
TC
kW
PI
kW
TC
kW
PI
kW
TC
kW
PI
kW
TC
kW
PI
kW
TC
kW
PI
kW
TC
kW
PI
kW
TC
kW
PI
kW
4
-19.8 -20.0 13.4 3.39 12.1 3.35 11.3 3.30 10.4 3.24 9.6 3.15 8.3 2.98 7.1 2.81
-14.7 -15.0 13.4 3.17 12.1 3.14 11.3 3.10 10.4 3.05 9.6 2.99 8.3 2.83 7.1 2.64
-9.6 -10.0 13.4 2.90 12.1 2.90 11.3 2.87 10.4 2.83 9.6 2.76 8.3 2.60 7.1 2.38
-4.4 -5.0 13.4 2.58 12.1 2.58 11.3 2.53 10.4 2.47 9.6 2.39 8.3 2.25 7.1 2.08
-1.8
0.8
-2.5
0.0
13.4
13.4
2.38
2.14
12.1
12.1
2.35
2.12
11.3
11.3
2.30
2.09
10.4
10.4
2.26
2.06
9.6
9.6
2.19
2.01
8.3
8.3
2.08
1.92
7.1
7.1
1.94
1.80 5
30% 2.8 2.0 13.4 2.06 12.1 1.94 11.3 1.93 10.4 1.90 9.6 1.87 8.3 1.79 7.1 1.69
6.0 5.0 13.4 2.06 12.1 1.92 11.3 1.83 10.4 1.74 9.6 1.66 8.3 1.61 7.1 1.53
7.0 6.0 13.4 2.06 12.1 1.92 11.3 1.83 10.4 1.74 9.6 1.65 8.3 1.55 7.1 1.48
8.6 7.5 13.4 2.06 12.1 1.92 11.3 1.83 10.4 1.74 9.6 1.65 8.3 1.52 7.1 1.41
11.2 10.0 13.4 2.06 12.1 1.92 11.3 1.83 10.4 1.74 9.6 1.65 8.3 1.52 7.1 1.39
16.4
24.0
15.0
18.0
13.4
13.4
2.06
2.06
12.1
12.1
1.92
1.92
11.3
11.3
1.83
1.83
10.4
10.4
1.74
1.74
9.6
9.6
1.65
1.65
8.3
8.3
1.52
1.52
7.1
7.1
1.39
1.39 6
Indoor air temp䋮䋺㷄DB
Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8
-14.7
-20.0
-15.0
8.9
8.9
2.49
2.33
8.1
8.1
2.49
2.33
7.5
7.5
2.46
2.31
6.9
6.9
2.42
2.28
6.4
6.4
2.35
2.21
5.6
5.6
2.25
2.08
4.7
4.7
2.14
1.91
7
-9.6 -10.0 8.9 2.10 8.1 2.07 7.5 2.04 6.9 2.00 6.4 1.94 5.6 1.85 4.7 1.73
-4.4 -5.0 8.9 1.76 8.1 1.75 7.5 1.74 6.9 1.72 6.4 1.68 5.6 1.62 4.7 1.53
-1.8 -2.5 8.9 1.60 8.1 1.60 7.5 1.60 6.9 1.59 6.4 1.56 5.6 1.51 4.7 1.44
0.8 0.0 8.9 1.58 8.1 1.49 7.5 1.46 6.9 1.46 6.4 1.45 5.6 1.40 4.7 1.35
20% 2.8 2.0 8.9 1.58 8.1 1.49 7.5 1.43 6.9 1.37 6.4 1.35 5.6 1.33 4.7 1.28
6.0
7.0
5.0
6.0
8.9
8.9
1.58
1.58
8.1
8.1
1.49
1.49
7.5
7.5
1.43
1.43
6.9
6.9
1.37
1.37
6.4
6.4
1.31
1.31
5.6
5.6
1.22
1.22
4.7
4.7
1.18
1.15
8
8.6 7.5 8.9 1.58 8.1 1.49 7.5 1.43 6.9 1.37 6.4 1.31 5.6 1.22 4.7 1.12
11.2 10.0 8.9 1.58 8.1 1.49 7.5 1.43 6.9 1.37 6.4 1.31 5.6 1.22 4.7 1.12
16.4 15.0 8.9 1.58 8.1 1.49 7.5 1.43 6.9 1.37 6.4 1.31 5.6 1.22 4.7 1.12
24.0 18.0 8.9 1.58 8.1 1.49 7.5 1.43 6.9 1.37 6.4 1.31 5.6 1.22 4.7 1.12

9-19 9

5GEKPFF 
Capacity Table

1. Capacity Ratio of Outdoor Unit

1-7. U-14MF2E8 (Cooling) Capacity Ratio 20-130%


TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp䋮䋺㷄WB
Combination(%) Outdoor
14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 37.3 5.23 43.0 6.05 43.0 6.05 43.0 6.05 48.7 6.86 54.5 7.68 60.2 8.48
-5.0 37.3 5.23 43.0 6.06 43.0 6.06 43.0 6.06 48.7 6.89 54.5 7.69 60.2 8.50
0.0 37.3 5.24 43.0 6.09 43.0 6.09 43.0 6.09 48.7 6.91 54.5 7.73 60.2 8.54
5.0 37.3 5.25 43.0 6.12 43.0 6.12 43.0 6.12 48.7 6.96 54.5 7.77 60.2 8.59
10.0 37.3 5.29 43.0 6.21 43.0 6.21 43.0 6.21 48.7 7.07 54.5 7.88 60.2 8.69
15.0 37.3 5.36 43.0 6.37 43.0 6.37 43.0 6.37 48.7 7.27 54.5 8.08 60.2 8.91
130% 20.0 37.3 5.57 43.0 7.02 43.0 7.02 43.0 7.02 48.7 8.42 54.5 9.96 60.2 11.65
25.0 37.3 6.59 43.0 8.83 43.0 8.83 43.0 8.83 48.7 10.52 54.5 12.35 60.2 14.34
30.0 37.3 8.20 43.0 10.78 43.0 10.78 43.0 10.78 48.7 12.78 54.5 14.94 56.8 15.08
35.0 37.3 9.91 43.0 12.89 43.0 12.89 43.0 12.89 48.4 15.08 50.4 15.08 52.5 15.08
40.0 37.3 11.78 42.8 15.08 42.8 15.08 42.8 15.08 42.9 13.96 42.9 12.82 42.9 11.75
43.0 35.3 11.67 35.3 11.67 35.3 11.67 35.3 11.67 35.3 10.73 35.3 9.85 35.3 9.03
46.0 27.9 8.68 27.9 8.68 27.9 8.68 27.9 8.68 27.9 7.98 27.9 7.33 27.9 6.73
1 Indoor air temp䋮䋺㷄WB
Combination(%) Outdoor
14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 33.6 4.71 40.3 5.66 42.0 5.92 42.0 5.92 47.6 6.71 53.2 7.50 58.8 8.29

2 -5.0
0.0
33.6
33.6
4.72
4.72
40.3
40.3
5.67
5.68
42.0
42.0
5.93
5.94
42.0
42.0
5.93
5.94
47.6
47.6
6.73
6.76
53.2
53.2
7.52
7.54
58.8
58.8
8.31
8.34
5.0 33.6 4.75 40.3 5.70 42.0 5.98 42.0 5.98 47.6 6.79 53.2 7.59 58.8 8.38
10.0 33.6 4.77 40.3 5.74 42.0 6.05 42.0 6.05 47.6 6.89 53.2 7.69 58.8 8.49
15.0 33.6 4.83 40.3 5.85 42.0 6.21 42.0 6.21 47.6 7.09 53.2 7.90 58.8 8.70
120% 20.0 33.6 5.03 40.3 6.14 42.0 6.74 42.0 6.74 47.6 8.08 53.2 9.54 58.8 11.13
25.0 33.6 5.94 40.3 7.47 42.0 8.51 42.0 8.51 47.6 10.12 53.2 11.86 58.8 13.74

3 30.0
35.0
33.6
33.6
7.38
8.92
40.3
40.3
9.23
11.12
42.0
42.0
10.39
12.45
42.0 10.39
42.0 12.45
47.6 12.31
47.6 14.70
53.2 14.37
50.2 15.08
56.4 15.08
52.2 15.08
40.0 33.6 10.59 40.3 13.18 42.0 14.71 42.0 14.71 42.9 14.11 42.9 12.95 42.9 11.88
43.0 33.6 11.66 35.3 11.78 35.3 11.78 35.3 11.78 35.3 10.82 35.3 9.93 35.3 9.10
46.0 27.9 8.73 27.9 8.73 27.9 8.73 27.9 8.73 27.9 8.02 27.9 7.38 27.9 6.77

Indoor air temp䋮䋺㷄WB


Combination(%) Outdoor
4 :Indoor/outdoor
capacity ratio
air temp.
㷄DB
TC
14.0
PI TC
16.0
PI TC
18.0
PI TC
19.0
PI TC
21.0
PI TC
23.0
PI TC
25.0
PI
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 30.1 4.22 36.1 5.07 41.0 5.76 41.0 5.76 46.5 6.54 51.9 7.32 57.4 8.08
-5.0 30.1 4.22 36.1 5.07 41.0 5.78 41.0 5.78 46.5 6.57 51.9 7.34 57.4 8.11
0.0 30.1 4.23 36.1 5.08 41.0 5.80 41.0 5.80 46.5 6.59 51.9 7.37 57.4 8.14
5.0 30.1 4.25 36.1 5.11 41.0 5.84 41.0 5.84 46.5 6.64 51.9 7.41 57.4 8.19
5 10.0
15.0
30.1
30.1
4.27
4.34
36.1
36.1
5.15
5.24
41.0
41.0
5.91
6.04
41.0
41.0
5.91
6.04
46.5
46.5
6.72
6.90
51.9
51.9
7.52
7.71
57.4
57.4
8.30
8.50
110% 20.0 30.1 4.52 36.1 5.51 41.0 6.48 41.0 6.48 46.5 7.75 51.9 9.14 57.4 10.64
25.0 30.1 5.32 36.1 6.67 41.0 8.19 41.0 8.19 46.5 9.72 51.9 11.38 57.4 13.17
30.0 30.1 6.61 36.1 8.24 41.0 10.02 41.0 10.02 46.5 11.84 51.9 13.80 56.0 15.08
35.0 30.1 7.98 36.1 9.91 41.0 12.01 41.0 12.01 46.5 14.15 49.8 15.08 51.9 15.08
40.0 30.1 9.47 36.1 11.75 41.0 14.18 41.0 14.18 42.9 14.27 42.9 13.11 42.9 12.02
6 43.0
46.0
30.1
27.9
10.42
8.80
35.3
27.9
11.88
8.80
35.3
27.9
11.88
8.80
35.3 11.88
27.9 8.80
35.3 10.93
27.9 8.08
35.3 10.02
27.9 7.44
35.3
27.9
9.20
6.82

Indoor air temp䋮䋺㷄WB


Combination(%) Outdoor
14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
7 -10.0
-5.0
26.7
26.7
3.74
3.74
32.0
32.0
4.50
4.50
37.3
37.3
5.25
5.25
40.0
40.0
5.62
5.63
45.3
45.3
6.39
6.40
50.7
50.7
7.15
7.15
56.0
56.0
7.90
7.92
0.0 26.7 3.76 32.0 4.51 37.3 5.27 40.0 5.66 45.3 6.42 50.7 7.19 56.0 7.94
5.0 26.7 3.77 32.0 4.53 37.3 5.30 40.0 5.68 45.3 6.46 50.7 7.24 56.0 7.99
10.0 26.7 3.79 32.0 4.57 37.3 5.36 40.0 5.75 45.3 6.54 50.7 7.33 56.0 8.08
15.0 26.7 3.85 32.0 4.65 37.3 5.48 40.0 5.88 45.3 6.72 50.7 7.53 56.0 8.30
100%
8 20.0
25.0
26.7
26.7
4.03
4.76
32.0
32.0
4.90
5.92
37.3
37.3
5.80
7.19
40.0
40.0
6.25
7.88
45.3
45.3
7.43
9.34
50.7 8.73
50.7 10.92
56.0 10.16
56.0 12.61
30.0 26.7 5.88 32.0 7.30 37.3 8.84 40.0 9.65 45.3 11.40 50.7 13.25 55.7 15.08
35.0 26.7 7.09 32.0 8.77 37.3 10.56 40.0 11.60 45.3 13.53 49.5 15.08 51.5 15.08
40.0 26.7 8.41 32.0 10.39 37.3 12.54 40.0 13.69 42.9 14.43 42.9 13.26 42.9 12.16
43.0 26.7 9.24 32.0 11.43 35.3 12.51 35.3 11.99 35.3 11.03 35.3 10.13 35.3 9.29
46.0 26.7 10.14 27.9 10.03 27.9 9.24 27.9 8.86 27.9 8.16 27.9 7.50 27.9 6.88

9 9-20

5GEKPFF 
Capacity Table

1. Capacity Ratio of Outdoor Unit

U-14MF2E8 (Cooling) Capacity Ratio 20-130%


TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp䋮䋺㷄WB
Combination(%) Outdoor
14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 24.0 3.36 28.8 4.05 33.6 4.72 36.0 5.07 40.8 5.74 45.6 6.42 50.4 7.11
-5.0 24.0 3.37 28.8 4.05 33.6 4.74 36.0 5.07 40.8 5.75 45.6 6.43 50.4 7.13
0.0 24.0 3.37 28.8 4.06 33.6 4.75 36.0 5.08 40.8 5.76 45.6 6.46 50.4 7.15
5.0 24.0 3.38 28.8 4.07 33.6 4.76 36.0 5.11 40.8 5.80 45.6 6.49 50.4 7.19
10.0 24.0 3.40 28.8 4.09 33.6 4.81 36.0 5.15 40.8 5.86 45.6 6.58 50.4 7.28
15.0 24.0 3.44 28.8 4.16 33.6 4.88 36.0 5.25 40.8 5.99 45.6 6.73 50.4 7.47
90% 20.0 24.0 3.58 28.8 4.35 33.6 5.13 36.0 5.52 40.8 6.33 45.6 7.26 50.4 8.37
25.0 24.0 4.15 28.8 5.11 33.6 6.15 36.0 6.71 40.8 7.89 45.6 9.15 50.4 10.51
30.0 24.0 5.15 28.8 6.33 33.6 7.59 36.0 8.26 40.8 9.67 45.6 11.18 50.4 12.78
35.0 24.0 6.22 28.8 7.63 33.6 9.14 36.0 9.94 40.8 11.61 45.6 13.38 50.0 15.08
40.0 24.0 7.38 28.8 9.05 33.6 10.83 36.0 11.77 40.8 13.74 42.9 13.99 42.9 12.84
43.0 24.0 8.12 28.8 9.95 33.6 11.92 35.3 12.53 35.3 11.53 35.3 10.59 35.3 9.72
46.0 24.0 8.90 27.9 10.37 27.9 9.56 27.9 9.17 27.9 8.44 27.9 7.76 27.9 7.13

Indoor air temp䋮䋺㷄WB


1
Combination(%) Outdoor
14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 21.3 2.99 25.6 3.60 29.9 4.20 32.0 4.50 36.3 5.11 40.5 5.70 44.8 6.31
-5.0
0.0
21.3
21.3
2.99
3.00
25.6
25.6
3.60
3.61
29.9
29.9
4.20
4.21
32.0
32.0
4.50
4.51
36.3
36.3
5.11
5.13
40.5
40.5
5.72
5.73
44.8
44.8
6.33
6.35 2
5.0 21.3 3.00 25.6 3.62 29.9 4.22 32.0 4.53 36.3 5.14 40.5 5.75 44.8 6.38
10.0 21.3 3.01 25.6 3.63 29.9 4.26 32.0 4.56 36.3 5.19 40.5 5.81 44.8 6.43
15.0 21.3 3.05 25.6 3.67 29.9 4.32 32.0 4.64 36.3 5.27 40.5 5.93 44.8 6.58
80% 20.0 21.3 3.14 25.6 3.82 29.9 4.49 32.0 4.83 36.3 5.52 40.5 6.21 44.8 6.90
25.0 21.3 3.56 25.6 4.36 29.9 5.21 32.0 5.65 36.3 6.58 40.5 7.57 44.8 8.63
30.0
35.0
21.3
21.3
4.46
5.41
25.6
25.6
5.43
6.57
29.9
29.9
6.46
7.80
32.0
32.0
7.00
8.43
36.3
36.3
8.12
9.78
40.5 9.32
40.5 11.19
44.8 10.58
44.8 12.69 3
40.0 21.3 6.40 25.6 7.78 29.9 9.24 32.0 10.01 36.3 11.60 40.5 13.29 42.9 13.74
43.0 21.3 7.06 25.6 8.57 29.9 10.19 32.0 11.03 35.3 12.17 35.3 11.19 35.3 10.27
46.0 21.3 7.73 25.6 9.41 27.9 9.96 27.9 9.57 27.9 8.80 27.9 8.10 27.9 7.44

Indoor air temp䋮䋺㷄WB


Combination(%) Outdoor
:Indoor/outdoor
capacity ratio
air temp.
㷄DB
TC
14.0
PI TC
16.0
PI TC
18.0
PI TC
19.0
PI TC
21.0
PI TC
23.0
PI TC
25.0
PI 4
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 18.7 2.62 22.4 3.14 26.1 3.67 28.0 3.93 31.7 4.46 35.5 4.99 39.2 5.52
-5.0 18.7 2.62 22.4 3.14 26.1 3.67 28.0 3.95 31.7 4.46 35.5 5.00 39.2 5.52
0.0 18.7 2.62 22.4 3.16 26.1 3.67 28.0 3.95 31.7 4.47 35.5 5.01 39.2 5.55
5.0 18.7 2.63 22.4 3.16 26.1 3.68 28.0 3.96 31.7 4.49 35.5 5.02 39.2 5.57
10.0
15.0
18.7
18.7
2.63
2.66
22.4
22.4
3.17
3.20
26.1
26.1
3.71
3.74
28.0
28.0
3.98
4.03
31.7
31.7
4.52
4.58
35.5
35.5
5.06
5.14
39.2
39.2
5.61
5.69
5
70% 20.0 18.7 2.73 22.4 3.29 26.1 3.87 28.0 4.16 31.7 4.75 35.5 5.33 39.2 5.93
25.0 18.7 3.00 22.4 3.67 26.1 4.34 28.0 4.69 31.7 5.41 35.5 6.16 39.2 6.96
30.0 18.7 3.84 22.4 4.60 26.1 5.42 28.0 5.84 31.7 6.72 35.5 7.64 39.2 8.61
35.0 18.7 4.64 22.4 5.57 26.1 6.55 28.0 7.07 31.7 8.12 35.5 9.22 39.2 10.38
40.0 18.7 5.50 22.4 6.61 26.1 7.78 28.0 8.40 31.7 9.65 35.5 10.97 39.2 12.33
43.0
46.0
18.7
18.7
6.05
6.62
22.4
22.4
7.28
7.99
26.1
26.1
8.59
9.43
28.0
27.9 10.10
9.26 31.7 10.63
27.9 9.30
35.3 12.01
27.9 8.56
35.3 11.03
27.9 7.88
6
Indoor air temp䋮䋺㷄WB
Combination(%) Outdoor
14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0
-5.0
16.0
16.0
2.24
2.25
19.2
19.2
2.69
2.69
22.4
22.4
3.14
3.14
24.0
24.0
3.37
3.37
27.2
27.2
3.83
3.83
30.4
30.4
4.28
4.28
33.6
33.6
4.74
4.74
7
0.0 16.0 2.25 19.2 2.70 22.4 3.16 24.0 3.37 27.2 3.83 30.4 4.29 33.6 4.75
5.0 16.0 2.25 19.2 2.70 22.4 3.16 24.0 3.38 27.2 3.84 30.4 4.30 33.6 4.76
10.0 16.0 2.26 19.2 2.71 22.4 3.17 24.0 3.40 27.2 3.86 30.4 4.33 33.6 4.78
15.0 16.0 2.27 19.2 2.74 22.4 3.20 24.0 3.43 27.2 3.90 30.4 4.38 33.6 4.84
60% 20.0 16.0 2.31 19.2 2.80 22.4 3.28 24.0 3.52 27.2 4.01 30.4 4.50 33.6 4.99
25.0 16.0 2.50 19.2 3.03 22.4 3.58 24.0 3.84 27.2 4.39 30.4 4.92 33.6 5.51 8
30.0 16.0 3.25 19.2 3.85 22.4 4.46 24.0 4.79 27.2 5.46 30.4 6.15 33.6 6.86
35.0 16.0 3.92 19.2 4.66 22.4 5.43 24.0 5.82 27.2 6.62 30.4 7.46 33.6 8.32
40.0 16.0 4.65 19.2 5.54 22.4 6.45 24.0 6.92 27.2 7.89 30.4 8.89 33.6 9.90
43.0 16.0 5.12 19.2 6.09 22.4 7.11 24.0 7.63 27.2 8.70 30.4 9.81 33.6 10.95
46.0 16.0 5.61 19.2 6.68 22.4 7.81 24.0 8.38 27.2 9.57 27.9 9.21 27.9 8.48
9-21 9

5GEKPFF 
Capacity Table

1. Capacity Ratio of Outdoor Unit

U-14MF2E8 (Cooling) Capacity Ratio 20-130%


TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp䋮䋺㷄WB
Combination(%) Outdoor
14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 13.3 1.87 16.0 2.25 18.7 2.62 20.0 2.81 22.7 3.19 25.3 3.56 28.0 3.93
-5.0 13.3 1.87 16.0 2.25 18.7 2.62 20.0 2.81 22.7 3.19 25.3 3.56 28.0 3.95
0.0 13.3 1.87 16.0 2.25 18.7 2.62 20.0 2.82 22.7 3.19 25.3 3.58 28.0 3.95
5.0 13.3 1.88 16.0 2.25 18.7 2.63 20.0 2.82 22.7 3.20 25.3 3.58 28.0 3.96
10.0 13.3 1.88 16.0 2.26 18.7 2.63 20.0 2.83 22.7 3.22 25.3 3.59 28.0 3.97
15.0 13.3 1.89 16.0 2.27 18.7 2.66 20.0 2.85 22.7 3.24 25.3 3.62 28.0 4.01
50%
20.0 13.3 1.91 16.0 2.31 18.7 2.70 20.0 2.90 22.7 3.29 25.3 3.68 28.0 4.09
25.0 13.3 2.02 16.0 2.45 18.7 2.88 20.0 3.09 22.7 3.52 25.3 3.95 28.0 4.38
30.0 13.3 2.71 16.0 3.16 18.7 3.62 20.0 3.86 22.7 4.34 25.3 4.83 28.0 5.35
35.0 13.3 3.28 16.0 3.83 18.7 4.40 20.0 4.69 22.7 5.29 25.3 5.90 28.0 6.52
40.0 13.3 3.86 16.0 4.53 18.7 5.23 20.0 5.58 22.7 6.30 25.3 7.03 28.0 7.77
43.0 13.3 4.23 16.0 4.99 18.7 5.76 20.0 6.15 22.7 6.95 25.3 7.76 28.0 8.59
46.0 13.3 4.63 16.0 5.46 18.7 6.33 20.0 6.76 22.7 7.63 25.3 8.54 27.9 9.40
1 Indoor air temp䋮䋺㷄WB
Combination(%) Outdoor
14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 10.7 1.50 12.8 1.79 14.9 2.10 16.0 2.25 18.1 2.55 20.3 2.86 22.4 3.14
-5.0 10.7 1.50 12.8 1.79 14.9 2.10 16.0 2.25 18.1 2.55 20.3 2.86 22.4 3.16
2 0.0 10.7 1.50 12.8 1.79 14.9 2.10 16.0 2.25 18.1 2.55 20.3 2.86 22.4 3.16
5.0 10.7 1.50 12.8 1.79 14.9 2.10 16.0 2.25 18.1 2.55 20.3 2.86 22.4 3.16
10.0 10.7 1.50 12.8 1.79 14.9 2.12 16.0 2.26 18.1 2.56 20.3 2.87 22.4 3.17
15.0 10.7 1.51 12.8 1.81 14.9 2.12 16.0 2.26 18.1 2.57 20.3 2.88 22.4 3.19
40%
20.0 10.7 1.52 12.8 1.83 14.9 2.13 16.0 2.30 18.1 2.61 20.3 2.92 22.4 3.24
25.0 10.7 1.58 12.8 1.90 14.9 2.22 16.0 2.40 18.1 2.73 20.3 3.05 22.4 3.37

3 30.0
35.0
10.7
10.7
2.22
2.66
12.8
12.8
2.54
3.06
14.9
14.9
2.87
3.47
16.0
16.0
3.03
3.67
18.1
18.1
3.36
4.09
20.3
20.3
3.70
4.51
22.4
22.4
4.04
4.94
40.0 10.7 3.12 12.8 3.62 14.9 4.11 16.0 4.38 18.1 4.87 20.3 5.38 22.4 5.91
43.0 10.7 3.42 12.8 3.97 14.9 4.53 16.0 4.82 18.1 5.37 20.3 5.94 22.4 6.52
46.0 10.7 3.72 12.8 4.34 14.9 4.96 16.0 5.27 18.1 5.91 20.3 6.54 22.4 7.18

Indoor air temp䋮䋺㷄WB


Combination(%) Outdoor
4 :Indoor/outdoor
capacity ratio
air temp.
㷄DB
TC
14.0
PI TC
16.0
PI TC
18.0
PI TC
19.0
PI TC
21.0
PI TC
23.0
PI TC
25.0
PI
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 8.0 1.12 9.6 1.35 11.2 1.58 12.0 1.69 13.6 1.91 15.2 2.13 16.8 2.37
-5.0 8.0 1.12 9.6 1.35 11.2 1.58 12.0 1.69 13.6 1.91 15.2 2.13 16.8 2.37
0.0 8.0 1.12 9.6 1.35 11.2 1.58 12.0 1.69 13.6 1.91 15.2 2.13 16.8 2.37
5.0 8.0 1.12 9.6 1.35 11.2 1.58 12.0 1.70 13.6 1.91 15.2 2.14 16.8 2.37
5 10.0
15.0
8.0
8.0
1.12
1.12
9.6
9.6
1.35
1.35
11.2
11.2
1.58
1.58
12.0
12.0
1.70
1.70
13.6
13.6
1.91
1.93
15.2
15.2
2.14
2.14
16.8
16.8
2.37
2.38
30%
20.0 8.0 1.14 9.6 1.36 11.2 1.59 12.0 1.71 13.6 1.94 15.2 2.17 16.8 2.40
25.0 8.0 1.16 9.6 1.39 11.2 1.64 12.0 1.75 13.6 1.98 15.2 2.22 16.8 2.46
30.0 8.0 1.50 9.6 1.74 11.2 1.98 12.0 2.10 13.6 2.33 15.2 2.56 16.8 2.80
35.0 8.0 2.10 9.6 2.37 11.2 2.64 12.0 2.77 13.6 3.04 15.2 3.30 16.8 3.58
40.0 8.0 2.44 9.6 2.77 11.2 3.11 12.0 3.29 13.6 3.61 15.2 3.95 16.8 4.27
6 43.0
46.0
8.0
8.0
2.66
2.89
9.6
9.6
3.04
3.30
11.2
11.2
3.41
3.72
12.0
12.0
3.60
3.93
13.6
13.6
3.98
4.35
15.2
15.2
4.34
4.77
16.8
16.8
4.71
5.18

Indoor air temp䋮䋺㷄WB


Combination(%) Outdoor
14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
7 -10.0
-5.0
5.3
5.3
0.74
0.74
6.4
6.4
0.90
0.90
7.5
7.5
1.04
1.04
8.0
8.0
1.12
1.12
9.1
9.1
1.28
1.28
10.1
10.1
1.42
1.42
11.2
11.2
1.58
1.58
0.0 5.3 0.75 6.4 0.90 7.5 1.04 8.0 1.12 9.1 1.24 10.1 1.42 11.2 1.58
5.0 5.3 0.75 6.4 0.91 7.5 1.04 8.0 1.12 9.1 1.28 10.1 1.42 11.2 1.58
10.0 5.3 0.75 6.4 0.91 7.5 1.05 8.0 1.12 9.1 1.28 10.1 1.42 11.2 1.58
15.0 5.3 0.75 6.4 0.91 7.5 1.05 8.0 1.12 9.1 1.28 10.1 1.42 11.2 1.58
20%
20.0 5.3 0.75 6.4 0.91 7.5 1.05 8.0 1.14 9.1 1.29 10.1 1.44 11.2 1.59
8 25.0
30.0
5.3
5.3
0.77
0.87
6.4
6.4
0.92
1.02
7.5
7.5
1.06
1.18
8.0
8.0
1.15
1.26
9.1
9.1
1.30
1.40
10.1
10.1
1.45
1.57
11.2
11.2
1.61
1.72
35.0 5.3 1.59 6.4 1.75 7.5 1.90 8.0 1.98 9.1 2.13 10.1 2.27 11.2 2.43
40.0 5.3 1.81 6.4 2.02 7.5 2.21 8.0 2.31 9.1 2.51 10.1 2.69 11.2 2.87
43.0 5.3 1.95 6.4 2.18 7.5 2.40 8.0 2.51 9.1 2.74 10.1 2.94 11.2 3.14
46.0 5.3 2.10 6.4 2.36 7.5 2.61 8.0 2.74 9.1 2.98 10.1 3.22 11.2 3.44

9 9-22

5GEKPFF 
Capacity Table

1. Capacity Ratio of Outdoor Unit

1-8. U-14MF2E8 (Heating) Capacity Ratio 20-130%


TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp䋮䋺㷄DB
Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 34.3 11.76 31.7 10.78 29.9 10.12 29.9 10.12 29.9 10.12 29.9 10.12 26.2 8.66
-14.7 -15.0 36.4 11.93 33.7 10.97 31.8 10.31 31.8 10.31 31.8 10.31 31.8 10.31 28.1 8.87
-9.6 -10.0 39.1 12.21 36.2 11.25 34.3 10.60 34.3 10.60 34.3 10.60 34.3 10.60 30.6 9.18
-4.4 -5.0 42.7 12.66 39.7 11.69 37.7 11.04 37.7 11.04 37.7 11.04 37.7 11.04 33.9 9.62
-1.8 -2.5 45.0 12.95 41.9 11.99 39.8 11.32 39.8 11.32 39.8 11.32 39.8 11.32 36.0 9.90
0.8 0.0 47.6 13.26 44.6 12.34 42.3 11.66 42.3 11.66 42.3 11.66 42.3 11.66 38.7 10.28
130% 2.8 2.0 49.5 13.26 47.1 12.67 44.8 11.99 44.8 11.99 44.8 11.99 44.8 11.99 39.6 10.06
6.0 5.0 53.1 13.26 51.8 13.26 48.4 12.17 48.4 12.17 48.4 12.17 46.6 10.94 39.6 9.13
7.0 6.0 54.7 13.26 52.0 12.78 48.4 11.69 48.4 11.69 48.4 11.69 46.6 10.53 39.6 8.78
8.6 7.5 56.7 13.26 52.0 11.96 48.4 10.95 48.4 10.95 48.4 10.95 46.6 9.88 39.6 8.25
11.2 10.0 57.3 12.07 52.0 10.67 48.4 9.77 48.4 9.77 48.4 9.77 46.6 8.85 39.6 7.42
16.4 15.0 57.3 9.35 52.0 8.31 48.4 7.65 48.4 7.65 48.4 7.65 46.6 7.02 39.6 5.93
24.0 18.0 57.3 7.95 52.0 7.10 48.4 6.55 48.4 6.55 48.4 6.55 46.6 6.07 39.6 5.16

Indoor air temp䋮䋺㷄DB


1
Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 34.4 11.63 31.8 10.67 29.9 10.02 29.9 10.02 29.9 10.02 27.9 9.16 24.2 8.00
-14.7 -15.0 36.5 11.81 33.8 10.86 31.9 10.22 31.9 10.22 31.9 10.22 29.8 9.37 25.9 8.19
-9.6
-4.4
-10.0
-5.0
39.2 12.11
42.8 12.55
36.3 11.16
39.8 11.60
34.3 10.51 34.3 10.51 34.3 10.51
37.7 10.94 37.7 10.94 37.7 10.94
32.3 9.68
35.7 10.14
28.2
31.2
8.47
8.85
2
-1.8 -2.5 45.0 12.84 42.0 11.89 39.8 11.23 39.8 11.23 39.8 11.23 37.9 10.42 33.2 9.12
0.8 0.0 47.8 13.20 44.6 12.23 42.3 11.57 42.3 11.57 42.3 11.57 40.5 10.79 35.6 9.46
120% 2.8 2.0 49.7 13.26 47.1 12.57 44.8 11.89 44.8 11.89 44.8 11.89 42.0 10.77 35.7 9.01
6.0 5.0 53.5 13.26 50.8 12.72 47.3 11.65 47.3 11.65 47.3 11.65 42.0 9.77 35.7 8.17
7.0 6.0 54.8 13.26 50.8 12.21 47.3 11.19 47.3 11.19 47.3 11.19 42.0 9.39 35.7 7.86
8.6
11.2
7.5
10.0
56.0 12.91
56.0 11.48
50.8 11.42
50.8 10.17
47.3 10.48 47.3 10.48 47.3 10.48
47.3 9.34 47.3 9.34 47.3 9.34
42.0
42.0
8.81
7.89
35.7
35.7
7.40
6.64
3
16.4 15.0 56.0 8.87 50.8 7.91 47.3 7.29 47.3 7.29 47.3 7.29 42.0 6.26 35.7 5.30
24.0 18.0 56.0 7.52 50.8 6.74 47.3 6.24 47.3 6.24 47.3 6.24 42.0 5.42 35.7 4.63

Indoor air temp䋮䋺㷄DB


Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor
capacity ratio
air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI 4
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 34.5 11.50 31.8 10.56 30.0 9.92 30.0 9.92 28.8 9.45 25.5 8.38 22.1 7.34
-14.7 -15.0 36.6 11.69 33.8 10.76 31.9 10.13 31.9 10.13 30.7 9.66 27.3 8.58 23.8 7.52
-9.6 -10.0 39.2 12.00 36.4 11.06 34.4 10.42 34.4 10.42 33.3 9.97 29.6 8.86 25.8 7.76
-4.4 -5.0 42.8 12.44 39.8 11.51 37.7 10.85 37.7 10.85 36.6 10.40 32.7 9.26 28.6 8.11
-1.8
0.8
-2.5
0.0
45.1
47.8
12.74
13.10
42.0
44.6
11.79
12.14
39.8
42.3
11.14 39.8 11.14 38.7 10.69
11.46 42.3 11.46 41.3 11.04
34.7
37.0
9.53
9.85
30.3
32.0
8.33
8.45 5
110% 2.8 2.0 50.0 13.26 47.1 12.45 44.7 11.79 44.7 11.79 43.2 11.18 37.6 9.55 32.0 8.02
6.0 5.0 53.7 13.26 49.5 12.15 46.1 11.14 46.1 11.14 43.2 10.12 37.6 8.66 32.0 7.27
7.0 6.0 54.7 13.16 49.5 11.65 46.1 10.70 46.1 10.70 43.2 9.72 37.6 8.32 32.0 7.00
8.6 7.5 54.7 12.29 49.5 10.89 46.1 10.02 46.1 10.02 43.2 9.12 37.6 7.81 32.0 6.58
11.2 10.0 54.7 10.90 49.5 9.69 46.1 8.91 46.1 8.91 43.2 8.14 37.6 7.00 32.0 5.91
16.4
24.0
15.0
18.0
54.7
54.7
8.40
7.11
49.5
49.5
7.52
6.40
46.1
46.1
6.95
5.94
46.1
46.1
6.95
5.94
43.2
43.2
6.41
5.51
37.6
37.6
5.55
4.80
32.0
32.0
4.73
4.12 6
Indoor air temp䋮䋺㷄DB
Combination(%) Outdoor 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8
-14.7
-20.0
-15.0
34.6
36.6
11.37
11.58
31.9
33.8
10.46
10.66
30.0
32.0
9.83 28.1
10.04 30.0
9.20
9.40
26.2
27.9
8.57
8.76
23.2
24.8
7.62
7.79
20.1
21.6
6.69
6.84
7
-9.6 -10.0 39.3 11.88 36.4 10.97 34.4 10.33 32.4 9.69 30.2 9.04 26.9 8.05 23.4 7.06
-4.4 -5.0 42.9 12.34 39.9 11.41 37.7 10.77 35.5 10.11 33.3 9.44 29.7 8.40 25.9 7.36
-1.8 -2.5 45.2 12.64 42.0 11.70 39.8 11.05 37.5 10.37 35.1 9.69 31.4 8.64 27.5 7.57
0.8 0.0 47.9 12.98 44.6 12.04 42.3 11.37 39.9 10.69 37.4 10.00 33.3 8.85 28.4 7.47
100% 2.8 2.0 50.3 13.26 47.1 12.35 44.7 11.68 41.7 10.78 38.3 9.80 33.3 8.39 28.4 7.09
6.0
7.0
5.0
6.0
53.3
53.3
13.06
12.52
48.3
48.3
11.59
11.11
45.0
45.0
10.65 41.7
10.20 41.7
9.74
9.35
38.3
38.3
8.87
8.53
33.3
33.3
7.62
7.32
28.4
28.4
6.43
6.18
8
8.6 7.5 53.3 11.68 48.3 10.38 45.0 9.56 41.7 8.76 38.3 7.99 33.3 6.87 28.4 5.81
11.2 10.0 53.3 10.35 48.3 9.22 45.0 8.51 41.7 7.81 38.3 7.13 33.3 6.16 28.4 5.22
16.4 15.0 53.3 7.96 48.3 7.14 45.0 6.62 41.7 6.11 38.3 5.61 33.3 4.89 28.4 4.18
24.0 18.0 53.3 6.71 48.3 6.06 45.0 5.64 41.7 5.23 38.3 4.82 33.3 4.23 28.4 3.65

9-23 9

5GEKPFF 
Capacity Table

1. Capacity Ratio of Outdoor Unit

U-14MF2E8 (Heating) Capacity Ratio 20-130%


TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp䋮䋺㷄DB
Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 34.8 10.90 32.1 10.07 30.2 9.49 28.3 8.90 26.3 8.32 23.2 7.45 20.1 6.60
-14.7 -15.0 37.0 11.15 34.1 10.29 32.1 9.71 30.1 9.12 28.0 8.52 24.8 7.62 21.5 6.74
-9.6 -10.0 39.6 11.48 36.6 10.61 34.6 10.02 32.4 9.40 30.2 8.79 26.8 7.85 23.3 6.93
-4.4 -5.0 43.2 11.94 40.0 11.05 37.8 10.43 35.5 9.80 33.2 9.16 29.5 8.18 25.5 7.15
-1.8 -2.5 45.5 12.24 42.1 11.32 39.8 10.70 37.4 10.05 34.5 9.24 30.0 8.02 25.5 6.85
0.8 0.0 48.0 12.54 43.5 11.21 40.5 10.36 37.5 9.53 34.5 8.72 30.0 7.57 25.5 6.48
90% 2.8 2.0 48.0 11.82 43.5 10.58 40.5 9.78 37.5 9.01 34.5 8.25 30.0 7.17 25.5 6.13
6.0 5.0 48.0 10.60 43.5 9.51 40.5 8.81 37.5 8.12 34.5 7.46 30.0 6.48 25.5 5.53
7.0 6.0 48.0 10.14 43.5 9.11 40.5 8.45 37.5 7.79 34.5 7.15 30.0 6.22 25.5 5.31
8.6 7.5 48.0 9.44 43.5 8.49 40.5 7.87 37.5 7.27 34.5 6.69 30.0 5.83 25.5 4.99
11.2 10.0 48.0 8.30 43.5 7.50 40.5 6.98 37.5 6.47 34.5 5.96 30.0 5.21 25.5 4.49
16.4 15.0 48.0 6.30 43.5 5.74 40.5 5.38 37.5 5.02 34.5 4.65 30.0 4.12 25.5 3.58
24.0 18.0 48.0 5.67 43.5 5.19 40.5 4.87 37.5 4.55 34.5 4.22 30.0 3.74 25.5 3.25
1 Indoor air temp䋮䋺㷄DB
Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp. TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 35.2 10.53 32.4 9.74 30.4 9.22 28.4 8.68 26.4 8.14 23.3 7.34 20.1 6.57
-14.7 -15.0 37.4 10.79 34.4 10.00 32.4 9.45 30.2 8.89 28.1 8.34 24.8 7.51 21.5 6.69
2 -9.6
-4.4
-10.0
-5.0
40.1
42.7
11.15
11.29
36.9
38.7
10.32
10.22
34.7
36.0
9.75
9.51
32.5
33.3
9.18
8.81
30.3
30.6
8.60
8.14
26.7
26.7
7.68
7.16
22.7
22.7
6.68
6.22
-1.8 -2.5 42.7 10.72 38.7 9.69 36.0 9.03 33.3 8.37 30.6 7.73 26.7 6.80 22.7 5.92
0.8 0.0 42.7 10.06 38.7 9.10 36.0 8.48 33.3 7.86 30.6 7.27 26.7 6.41 22.7 5.57
80% 2.8 2.0 42.7 9.46 38.7 8.58 36.0 8.00 33.3 7.43 30.6 6.87 26.7 6.06 22.7 5.25
6.0 5.0 42.7 8.44 38.7 7.67 36.0 7.17 33.3 6.67 30.6 6.18 26.7 5.44 22.7 4.70
7.0 6.0 42.7 8.05 38.7 7.33 36.0 6.85 33.3 6.39 30.6 5.92 26.7 5.21 22.7 4.52
3 8.6
11.2
7.5
10.0
42.7
42.7
7.47
6.54
38.7
38.7
6.81
6.00
36.0
36.0
6.39
5.63
33.3
33.3
5.96
5.27
30.6
30.6
5.53
4.91
26.7
26.7
4.89
4.36
22.7
22.7
4.24
3.80
16.4 15.0 42.7 5.10 38.7 4.67 36.0 4.39 33.3 4.10 30.6 3.81 26.7 3.43 22.7 3.04
24.0 18.0 42.7 5.10 38.7 4.67 36.0 4.39 33.3 4.10 30.6 3.81 26.7 3.38 22.7 2.95

Indoor air temp䋮䋺㷄DB


Combination(%) Outdoor
4 :Indoor/outdoor
capacity ratio
air temp. TC
15.0
PI TC
18.0
PI TC
20.0
PI TC
22.0
PI TC
24.0
PI TC
27.0
PI TC
30.0
PI
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 35.8 10.30 32.9 9.58 30.8 9.09 28.8 8.59 26.7 8.10 23.4 7.30 19.8 6.50
-14.7 -15.0 37.4 10.35 33.8 9.47 31.5 8.88 29.2 8.30 26.8 7.74 23.4 6.93 19.8 6.14
-9.6 -10.0 37.4 9.77 33.8 8.95 31.5 8.40 29.2 7.86 26.8 7.32 23.4 6.54 19.8 5.76
-4.4 -5.0 37.4 8.95 33.8 8.19 31.5 7.70 29.2 7.22 26.8 6.74 23.4 6.03 19.8 5.33

5 -1.8
0.8
-2.5
0.0
37.4
37.4
8.46
7.89
33.8
33.8
7.75
7.25
31.5
31.5
7.29
6.83
29.2
29.2
6.83
6.41
26.8
26.8
6.39
5.99
23.4
23.4
5.71
5.37
19.8
19.8
5.05
4.74
70% 2.8 2.0 37.4 7.41 33.8 6.82 31.5 6.43 29.2 6.04 26.8 5.64 23.4 5.06 19.8 4.45
6.0 5.0 37.4 6.57 33.8 6.07 31.5 5.73 29.2 5.39 26.8 5.04 23.4 4.50 19.8 3.95
7.0 6.0 37.4 6.25 33.8 5.78 31.5 5.47 29.2 5.15 26.8 4.81 23.4 4.31 19.8 3.79
8.6 7.5 37.4 5.77 33.8 5.37 31.5 5.08 29.2 4.79 26.8 4.49 23.4 4.03 19.8 3.56
11.2 10.0 37.4 5.02 33.8 4.69 31.5 4.46 29.2 4.22 26.8 3.98 23.4 3.60 19.8 3.19

6 16.4
24.0
15.0
18.0
37.4
37.4
4.53
4.53
33.8
33.8
4.15
4.15
31.5
31.5
3.90
3.90
29.2
29.2
3.65
3.65
26.8
26.8
3.40
3.40
23.4
23.4
3.02
3.02
19.8
19.8
2.64
2.64

Indoor air temp䋮䋺㷄DB


Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
7 -19.8
-14.7
-20.0
-15.0
32.0
32.0
8.64
8.18
29.0
29.0
8.00
7.61
27.0
27.0
7.58
7.23
25.0
25.0
7.16
6.84
23.0
23.0
6.75
6.44
20.0
20.0
6.15
5.84
17.0
17.0
5.56
5.25
-9.6 -10.0 32.0 7.61 29.0 7.09 27.0 6.74 25.0 6.40 23.0 6.04 20.0 5.51 17.0 4.94
-4.4 -5.0 32.0 6.92 29.0 6.46 27.0 6.14 25.0 5.83 23.0 5.52 20.0 5.03 17.0 4.53
-1.8 -2.5 32.0 6.51 29.0 6.09 27.0 5.79 25.0 5.51 23.0 5.21 20.0 4.75 17.0 4.27
0.8 0.0 32.0 6.06 29.0 5.67 27.0 5.42 25.0 5.14 23.0 4.87 20.0 4.44 17.0 3.96
60% 2.8 2.0 32.0 5.66 29.0 5.31 27.0 5.07 25.0 4.82 23.0 4.57 20.0 4.15 17.0 3.67
8 6.0
7.0
5.0
6.0
32.0
32.0
4.99
4.73
29.0
29.0
4.69
4.46
27.0
27.0
4.49
4.27
25.0
25.0
4.26
4.07
23.0
23.0
4.03
3.85
20.0
20.0
3.66
3.51
17.0
17.0
3.26
3.13
8.6 7.5 32.0 4.35 29.0 4.12 27.0 3.96 25.0 3.77 23.0 3.58 20.0 3.27 17.0 2.94
11.2 10.0 32.0 3.96 29.0 3.63 27.0 3.46 25.0 3.32 23.0 3.16 20.0 2.92 17.0 2.64
16.4 15.0 32.0 3.96 29.0 3.63 27.0 3.42 25.0 3.20 23.0 2.99 20.0 2.66 17.0 2.35
24.0 18.0 32.0 3.96 29.0 3.63 27.0 3.42 25.0 3.20 23.0 2.99 20.0 2.66 17.0 2.35

9 9-24

5GEKPFF 
Capacity Table

1. Capacity Ratio of Outdoor Unit

U-14MF2E8 (Heating) Capacity Ratio 20-130%


TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp䋮䋺㷄DB
Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 26.7 6.67 24.2 6.33 22.5 6.10 20.8 5.83 19.2 5.56 16.7 5.13 14.2 4.70
-14.7 -15.0 26.7 6.27 24.2 5.97 22.5 5.75 20.8 5.53 19.2 5.29 16.7 4.88 14.2 4.44
-9.6 -10.0 26.7 5.80 24.2 5.53 22.5 5.33 20.8 5.13 19.2 4.92 16.7 4.57 14.2 4.16
-4.4 -5.0 26.7 5.23 24.2 5.00 22.5 4.82 20.8 4.65 19.2 4.46 16.7 4.14 14.2 3.79
-1.8 -2.5 26.7 4.91 24.2 4.69 22.5 4.54 20.8 4.37 19.2 4.19 16.7 3.90 14.2 3.51
0.8 0.0 26.7 4.54 24.2 4.36 22.5 4.21 20.8 4.06 19.2 3.90 16.7 3.58 14.2 3.20
50% 2.8 2.0 26.7 4.22 24.2 4.05 22.5 3.93 20.8 3.78 19.2 3.60 16.7 3.30 14.2 2.98
6.0 5.0 26.7 3.67 24.2 3.53 22.5 3.42 20.8 3.29 19.2 3.15 16.7 2.92 14.2 2.64
7.0 6.0 26.7 3.47 24.2 3.35 22.5 3.24 20.8 3.13 19.2 3.01 16.7 2.79 14.2 2.54
8.6 7.5 26.7 3.38 24.2 3.11 22.5 3.00 20.8 2.91 19.2 2.79 16.7 2.61 14.2 2.39
11.2 10.0 26.7 3.38 24.2 3.11 22.5 2.93 20.8 2.75 19.2 2.57 16.7 2.33 14.2 2.14
16.4 15.0 26.7 3.38 24.2 3.11 22.5 2.93 20.8 2.75 19.2 2.57 16.7 2.31 14.2 2.04
24.0 18.0 26.7 3.38 24.2 3.11 22.5 2.93 20.8 2.75 19.2 2.57 16.7 2.31 14.2 2.04

Indoor air temp䋮䋺㷄DB


1
Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 21.3 5.08 19.4 4.93 18.0 4.81 16.7 4.68 15.3 4.50 13.3 4.20 11.3 3.90
-14.7 -15.0 21.3 4.75 19.4 4.62 18.0 4.52 16.7 4.40 15.3 4.26 13.3 3.99 11.3 3.67
-9.6
-4.4
-10.0
-5.0
21.3
21.3
4.37
3.90
19.4
19.4
4.25
3.80
18.0
18.0
4.16
3.73
16.7
16.7
4.06
3.65
15.3
15.3
3.94
3.55
13.3
13.3
3.72
3.33
11.3
11.3
3.44
3.00
2
-1.8 -2.5 21.3 3.63 19.4 3.55 18.0 3.49 16.7 3.41 15.3 3.29 13.3 3.04 11.3 2.76
0.8 0.0 21.3 3.34 19.4 3.27 18.0 3.20 16.7 3.10 15.3 2.98 13.3 2.77 11.3 2.53
40% 2.8 2.0 21.3 3.07 19.4 2.99 18.0 2.93 16.7 2.84 15.3 2.73 13.3 2.56 11.3 2.35
6.0 5.0 21.3 2.81 19.4 2.59 18.0 2.52 16.7 2.47 15.3 2.40 13.3 2.26 11.3 2.09
7.0 6.0 21.3 2.81 19.4 2.59 18.0 2.45 16.7 2.35 15.3 2.28 13.3 2.16 11.3 2.02
8.6
11.2
7.5
10.0
21.3
21.3
2.81
2.81
19.4
19.4
2.59
2.59
18.0
18.0
2.45
2.45
16.7
16.7
2.31
2.31
15.3
15.3
2.16
2.16
13.3
13.3
2.03
1.95
11.3
11.3
1.90
1.73
3
16.4 15.0 21.3 2.81 19.4 2.59 18.0 2.45 16.7 2.31 15.3 2.16 13.3 1.95 11.3 1.73
24.0 18.0 21.3 2.81 19.4 2.59 18.0 2.45 16.7 2.31 15.3 2.16 13.3 1.95 11.3 1.73

Indoor air temp䋮䋺㷄DB


Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor
capacity ratio
air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI 4
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 16.0 3.80 14.5 3.76 13.5 3.71 12.5 3.64 11.5 3.52 10.0 3.33 8.5 3.12
-14.7 -15.0 16.0 3.54 14.5 3.51 13.5 3.47 12.5 3.41 11.5 3.34 10.0 3.14 8.5 2.92
-9.6 -10.0 16.0 3.23 14.5 3.21 13.5 3.18 12.5 3.14 11.5 3.07 10.0 2.89 8.5 2.62
-4.4 -5.0 16.0 2.85 14.5 2.85 13.5 2.81 12.5 2.72 11.5 2.63 10.0 2.46 8.5 2.26
-1.8
0.8
-2.5
0.0
16.0
16.0
2.62
2.33
14.5
14.5
2.58
2.31
13.5
13.5
2.53
2.27
12.5
12.5
2.47
2.23
11.5
11.5
2.40
2.17
10.0
10.0
2.25
2.06
8.5
8.5
2.09
1.92 5
30% 2.8 2.0 16.0 2.23 14.5 2.09 13.5 2.07 12.5 2.05 11.5 2.00 10.0 1.92 8.5 1.80
6.0 5.0 16.0 2.23 14.5 2.07 13.5 1.97 12.5 1.86 11.5 1.75 10.0 1.70 8.5 1.61
7.0 6.0 16.0 2.23 14.5 2.07 13.5 1.97 12.5 1.86 11.5 1.75 10.0 1.63 8.5 1.55
8.6 7.5 16.0 2.23 14.5 2.07 13.5 1.97 12.5 1.86 11.5 1.75 10.0 1.59 8.5 1.47
11.2 10.0 16.0 2.23 14.5 2.07 13.5 1.97 12.5 1.86 11.5 1.75 10.0 1.59 8.5 1.43
16.4
24.0
15.0
18.0
16.0
16.0
2.23
2.23
14.5
14.5
2.07
2.07
13.5
13.5
1.97
1.97
12.5
12.5
1.86
1.86
11.5
11.5
1.75
1.75
10.0
10.0
1.59
1.59
8.5
8.5
1.43
1.43 6
Indoor air temp䋮䋺㷄DB
Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8
-14.7
-20.0
-15.0
10.7
10.7
2.74
2.55
9.7
9.7
2.73
2.55
9.0
9.0
2.71
2.53
8.3
8.3
2.65
2.50
7.7
7.7
2.58
2.43
6.7
6.7
2.46
2.25
5.7
5.7
2.33
2.06
7
-9.6 -10.0 10.7 2.28 9.7 2.25 9.0 2.21 8.3 2.16 7.7 2.10 6.7 1.98 5.7 1.84
-4.4 -5.0 10.7 1.88 9.7 1.87 9.0 1.86 8.3 1.83 7.7 1.79 6.7 1.71 5.7 1.60
-1.8 -2.5 10.7 1.68 9.7 1.69 9.0 1.68 8.3 1.67 7.7 1.64 6.7 1.58 5.7 1.49
0.8 0.0 10.7 1.66 9.7 1.55 9.0 1.52 8.3 1.52 7.7 1.50 6.7 1.46 5.7 1.39
20% 2.8 2.0 10.7 1.66 9.7 1.55 9.0 1.48 8.3 1.41 7.7 1.39 6.7 1.36 5.7 1.31
6.0
7.0
5.0
6.0
10.7
10.7
1.66
1.66
9.7
9.7
1.55
1.55
9.0
9.0
1.48
1.48
8.3
8.3
1.41
1.41
7.7
7.7
1.34
1.34
6.7
6.7
1.23
1.23
5.7
5.7
1.18
1.14
8
8.6 7.5 10.7 1.66 9.7 1.55 9.0 1.48 8.3 1.41 7.7 1.34 6.7 1.23 5.7 1.12
11.2 10.0 10.7 1.66 9.7 1.55 9.0 1.48 8.3 1.41 7.7 1.34 6.7 1.23 5.7 1.12
16.4 15.0 10.7 1.66 9.7 1.55 9.0 1.48 8.3 1.41 7.7 1.34 6.7 1.23 5.7 1.12
24.0 18.0 10.7 1.66 9.7 1.55 9.0 1.48 8.3 1.41 7.7 1.34 6.7 1.23 5.7 1.12

9-25 9

5GEKPFF 
Capacity Table

1. Capacity Ratio of Outdoor Unit

1-9. U-16MF2E8 (Cooling) Capacity Ratio 20-130%


TC: Total capacity (kW), PI: Power input (kW)

Indoor air temp䋮䋺㷄WB


Combination(%) Outdoor
14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 41.9 5.46 48.4 6.32 48.4 6.32 48.4 6.32 54.8 7.17 61.3 8.01 67.7 8.86
-5.0 41.9 5.46 48.4 6.33 48.4 6.33 48.4 6.33 54.8 7.18 61.3 8.03 67.7 8.88
0.0 41.9 5.47 48.4 6.36 48.4 6.36 48.4 6.36 54.8 7.22 61.3 8.08 67.7 8.93
5.0 41.9 5.50 48.4 6.42 48.4 6.42 48.4 6.42 54.8 7.29 61.3 8.16 67.7 9.01
10.0 41.9 5.54 48.4 6.51 48.4 6.51 48.4 6.51 54.8 7.43 61.3 8.30 67.7 9.15
15.0 41.9 5.62 48.4 6.77 48.4 6.77 48.4 6.77 54.8 7.86 61.3 9.53 67.7 11.38
130% 20.0 41.9 5.95 48.4 8.26 48.4 8.26 48.4 8.26 54.8 10.05 61.3 12.05 67.7 14.25
25.0 41.9 7.41 48.4 10.28 48.4 10.28 48.4 10.28 54.8 12.41 61.3 14.75 67.6 17.26
30.0 41.9 9.15 48.4 12.45 48.4 12.45 48.4 12.45 54.8 14.95 60.6 17.29 62.9 17.29
35.0 41.9 11.02 48.4 14.81 48.4 14.81 48.4 14.81 54.1 17.29 56.3 17.29 58.5 17.29
40.0 41.9 13.07 45.6 15.47 45.6 15.47 45.6 15.47 45.6 14.22 45.6 13.07 45.6 11.98
43.0 37.5 11.79 37.5 11.79 37.5 11.79 37.5 11.79 37.5 10.86 37.5 9.97 37.5 9.13
46.0 29.6 8.71 29.6 8.71 29.6 8.71 29.6 8.71 29.6 8.01 29.6 7.35 29.6 6.75
1 Indoor air temp䋮䋺㷄WB
Combination(%) Outdoor
14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 37.8 4.92 45.4 5.91 47.3 6.17 47.3 6.17 53.6 6.99 59.9 7.82 66.2 8.65

2 -5.0
0.0
37.8
37.8
4.92
4.94
45.4
45.4
5.92
5.94
47.3
47.3
6.18
6.21
47.3
47.3
6.18
6.21
53.6
53.6
7.02
7.06
59.9
59.9
7.84
7.88
66.2
66.2
8.67
8.71
5.0 37.8 4.95 45.4 5.96 47.3 6.25 47.3 6.25 53.6 7.13 59.9 7.95 66.2 8.79
10.0 37.8 4.99 45.4 6.01 47.3 6.36 47.3 6.36 53.6 7.27 59.9 8.10 66.2 8.94
15.0 37.8 5.09 45.4 6.16 47.3 6.60 47.3 6.60 53.6 7.57 59.9 9.09 66.2 10.86
120% 20.0 37.8 5.39 45.4 6.72 47.3 7.94 47.3 7.94 53.6 9.64 59.9 11.54 66.2 13.63
25.0 37.8 6.66 45.4 8.53 47.3 9.90 47.3 9.90 53.6 11.93 59.9 14.16 66.2 16.62

3 30.0
35.0
37.8
37.8
8.23
9.91
45.4
45.4
10.45
12.54
47.3
47.3
12.00
14.29
47.3 12.00
47.3 14.29
53.6 14.40
53.6 17.07
59.9 17.01
55.9 17.29
62.5 17.29
58.1 17.29
40.0 37.8 11.74 45.4 14.81 45.6 15.64 45.6 15.64 45.6 14.40 45.6 13.22 45.6 12.12
43.0 37.5 11.92 37.5 11.92 37.5 11.92 37.5 11.92 37.5 10.96 37.5 10.05 37.5 9.21
46.0 29.6 8.78 29.6 8.78 29.6 8.78 29.6 8.78 29.6 8.06 29.6 7.41 29.6 6.80

Indoor air temp䋮䋺㷄WB


Combination(%) Outdoor
4 :Indoor/outdoor
capacity ratio
air temp.
㷄DB
TC
14.0
PI TC
16.0
PI TC
18.0
PI TC
19.0
PI TC
21.0
PI TC
23.0
PI TC
25.0
PI
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 33.8 4.40 40.6 5.28 46.1 6.02 46.1 6.02 52.3 6.84 58.4 7.64 64.6 8.45
-5.0 33.8 4.40 40.6 5.29 46.1 6.03 46.1 6.03 52.3 6.85 58.4 7.66 64.6 8.47
0.0 33.8 4.42 40.6 5.31 46.1 6.05 46.1 6.05 52.3 6.88 58.4 7.70 64.6 8.51
5.0 33.8 4.43 40.6 5.33 46.1 6.10 46.1 6.10 52.3 6.94 58.4 7.76 64.6 8.58
5 10.0
15.0
33.8
33.8
4.47
4.55
40.6
40.6
5.39
5.52
46.1
46.1
6.20
6.43
46.1
46.1
6.20
6.43
52.3
52.3
7.08
7.36
58.4
58.4
7.91
8.68
64.6 8.72
64.6 10.35
110% 20.0 33.8 4.84 40.6 5.99 46.1 7.62 46.1 7.62 52.3 9.24 58.4 11.05 64.6 13.02
25.0 33.8 5.96 40.6 7.60 46.1 9.53 46.1 9.53 52.3 11.45 58.4 13.58 64.6 15.91
30.0 33.8 7.35 40.6 9.31 46.1 11.56 46.1 11.56 52.3 13.83 58.4 16.33 62.0 17.29
35.0 33.8 8.86 40.6 11.16 46.1 13.77 46.1 13.77 52.3 16.44 55.5 17.29 57.7 17.29
40.0 33.8 10.46 40.6 13.16 45.6 15.82 45.6 15.82 45.6 14.56 45.6 13.38 45.6 12.27
6 43.0
46.0
33.8
29.6
11.50
8.84
37.5
29.6
12.04
8.84
37.5
29.6
12.04
8.84
37.5 12.04
29.6 8.84
37.5 11.07
29.6 8.13
37.5 10.16
29.6 7.46
37.5
29.6
9.32
6.85

Indoor air temp䋮䋺㷄WB


Combination(%) Outdoor
14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
7 -10.0
-5.0
30.0
30.0
3.89
3.91
36.0
36.0
4.69
4.69
42.0
42.0
5.48
5.50
45.0
45.0
5.87
5.88
51.0
51.0
6.66
6.68
57.0
57.0
7.45
7.47
63.0
63.0
8.23
8.26
0.0 30.0 3.91 36.0 4.70 42.0 5.51 45.0 5.91 51.0 6.72 57.0 7.51 63.0 8.30
5.0 30.0 3.94 36.0 4.73 42.0 5.54 45.0 5.95 51.0 6.77 57.0 7.58 63.0 8.38
10.0 30.0 3.96 36.0 4.79 42.0 5.61 45.0 6.03 51.0 6.88 57.0 7.72 63.0 8.53
15.0 30.0 4.04 36.0 4.91 42.0 5.80 45.0 6.24 51.0 7.16 57.0 8.28 63.0 9.86
100%
8 20.0
25.0
30.0
30.0
4.31
5.29
36.0
36.0
5.31
6.72
42.0
42.0
6.60
8.30
45.0
45.0
7.32
9.15
51.0 8.86
51.0 11.00
57.0 10.57
57.0 13.02
63.0 12.44
63.0 15.22
30.0 30.0 6.53 36.0 8.23 42.0 10.11 45.0 11.13 51.0 13.30 57.0 15.67 61.6 17.29
35.0 30.0 7.84 36.0 9.83 42.0 12.01 45.0 13.30 51.0 15.71 55.2 17.29 57.3 17.29
40.0 30.0 9.27 36.0 11.64 42.0 14.23 45.0 15.63 45.6 14.74 45.6 13.55 45.6 12.44
43.0 30.0 10.19 36.0 12.79 37.5 12.67 37.5 12.16 37.5 11.19 37.5 10.27 37.5 9.42
46.0 29.6 10.94 29.6 10.08 29.6 9.28 29.6 8.91 29.6 8.20 29.6 7.53 29.6 6.91

9 9-26

5GEKPFF 
Capacity Table

1. Capacity Ratio of Outdoor Unit

U-16MF2E8 (Cooling) Capacity Ratio 20-130%


TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp䋮䋺㷄WB
Combination(%) Outdoor
14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 27.0 3.51 32.4 4.21 37.8 4.92 40.5 5.28 45.9 5.99 51.3 6.70 56.7 7.41
-5.0 27.0 3.51 32.4 4.22 37.8 4.94 40.5 5.29 45.9 5.99 51.3 6.72 56.7 7.43
0.0 27.0 3.52 32.4 4.22 37.8 4.95 40.5 5.31 45.9 6.02 51.3 6.76 56.7 7.47
5.0 27.0 3.54 32.4 4.25 37.8 4.98 40.5 5.33 45.9 6.06 51.3 6.81 56.7 7.54
10.0 27.0 3.55 32.4 4.29 37.8 5.03 40.5 5.40 45.9 6.16 51.3 6.91 56.7 7.68
15.0 27.0 3.62 32.4 4.39 37.8 5.16 40.5 5.55 45.9 6.36 51.3 7.17 56.7 8.02
90% 20.0 27.0 3.81 32.4 4.66 37.8 5.58 40.5 6.16 45.9 7.41 51.3 8.76 56.7 10.27
25.0 27.0 4.61 32.4 5.77 37.8 7.08 40.5 7.76 45.9 9.27 51.3 10.89 56.7 12.66
30.0 27.0 5.69 32.4 7.10 37.8 8.65 40.5 9.50 45.9 11.27 51.3 13.19 56.7 15.27
35.0 27.0 6.87 32.4 8.54 37.8 10.39 40.5 11.35 45.9 13.45 51.3 15.70 55.5 17.29
40.0 27.0 8.12 32.4 10.09 37.8 12.25 40.5 13.40 45.6 15.62 45.6 14.35 45.6 13.18
43.0 27.0 8.93 32.4 11.09 37.5 13.27 37.5 12.74 37.5 11.72 37.5 10.78 37.5 9.90
46.0 27.0 9.78 29.6 10.46 29.6 9.64 29.6 9.24 29.6 8.51 29.6 7.82 29.6 7.18

Indoor air temp䋮䋺㷄WB


1
Combination(%) Outdoor
14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 24.0 3.13 28.8 3.76 33.6 4.37 36.0 4.69 40.8 5.32 45.6 5.96 50.4 6.58
-5.0 24.0 3.13 28.8 3.76 33.6 4.39 36.0 4.69 40.8 5.33 45.6 5.96 50.4 6.60
0.0 24.0 3.13 28.8 3.77 33.6 4.39 36.0 4.70 40.8 5.35 45.6 5.99 50.4 6.62 2
5.0 24.0 3.14 28.8 3.77 33.6 4.42 36.0 4.73 40.8 5.37 45.6 6.02 50.4 6.68
10.0 24.0 3.15 28.8 3.80 33.6 4.46 36.0 4.77 40.8 5.44 45.6 6.10 50.4 6.79
15.0 24.0 3.19 28.8 3.87 33.6 4.55 36.0 4.89 40.8 5.58 45.6 6.29 50.4 7.01
80% 20.0 24.0 3.33 28.8 4.07 33.6 4.83 36.0 5.21 40.8 6.10 45.6 7.17 50.4 8.32
25.0 24.0 3.96 28.8 4.92 33.6 5.96 36.0 6.51 40.8 7.72 45.6 9.01 50.4 10.39
30.0
35.0
24.0
24.0
4.92
5.94
28.8
28.8
6.08
7.32
33.6
33.6
7.34
8.82
36.0
36.0
8.01
9.61
40.8 9.43
40.8 11.30
45.6 10.96
45.6 13.08
50.4 12.60
50.4 15.01 3
40.0 24.0 7.02 28.8 8.65 33.6 10.42 36.0 11.35 40.8 13.33 45.6 15.43 45.6 14.18
43.0 24.0 7.73 28.8 9.53 33.6 11.46 36.0 12.49 37.5 12.44 37.5 11.44 37.5 10.50
46.0 24.0 8.46 28.8 10.45 29.6 10.08 29.6 9.68 29.6 8.91 29.6 8.20 29.6 7.53

Indoor air temp䋮䋺㷄WB


Combination(%) Outdoor
:Indoor/outdoor
capacity ratio
air temp.
㷄DB
TC
14.0
PI TC
16.0
PI TC
18.0
PI TC
19.0
PI TC
21.0
PI TC
23.0
PI TC
25.0
PI 4
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 21.0 2.73 25.2 3.29 29.4 3.83 31.5 4.10 35.7 4.66 39.9 5.20 44.1 5.76
-5.0 21.0 2.73 25.2 3.29 29.4 3.83 31.5 4.11 35.7 4.66 39.9 5.21 44.1 5.77
0.0 21.0 2.74 25.2 3.29 29.4 3.84 31.5 4.11 35.7 4.66 39.9 5.22 44.1 5.79
5.0 21.0 2.74 25.2 3.30 29.4 3.85 31.5 4.14 35.7 4.69 39.9 5.25 44.1 5.83
10.0
15.0
21.0
21.0
2.76
2.78
25.2
25.2
3.32
3.36
29.4
29.4
3.88
3.94
31.5
31.5
4.17
4.24
35.7
35.7
4.73
4.83
39.9
39.9
5.31
5.44
44.1
44.1
5.89
6.03
5
70% 20.0 21.0 2.88 25.2 3.50 29.4 4.14 31.5 4.47 35.7 5.12 39.9 5.79 44.1 6.64
25.0 21.0 3.39 25.2 4.14 29.4 4.95 31.5 5.39 35.7 6.32 39.9 7.31 44.1 8.36
30.0 21.0 4.21 25.2 5.12 29.4 6.13 31.5 6.66 35.7 7.76 39.9 8.97 44.1 10.23
35.0 21.0 5.07 25.2 6.18 29.4 7.38 31.5 8.02 35.7 9.34 39.9 10.75 44.1 12.23
40.0 21.0 5.99 25.2 7.32 29.4 8.75 31.5 9.50 35.7 11.05 39.9 12.70 44.1 14.45
43.0
46.0
21.0
21.0
6.60
7.24
25.2
25.2
8.06
8.84
29.4
29.4
9.63
10.56
31.5 10.44
29.6 10.27
35.7 12.16
29.6 9.46
37.5 12.33
29.6 8.69
37.5 11.34
29.6 7.99
6
Indoor air temp䋮䋺㷄WB
Combination(%) Outdoor
14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0
-5.0
18.0
18.0
2.34
2.34
21.6
21.6
2.81
2.81
25.2
25.2
3.29
3.29
27.0
27.0
3.51
3.52
30.6
30.6
3.99
3.99
34.2
34.2
4.46
4.47
37.8
37.8
4.94
4.94
7
0.0 18.0 2.34 21.6 2.82 25.2 3.29 27.0 3.52 30.6 4.00 34.2 4.47 37.8 4.95
5.0 18.0 2.36 21.6 2.82 25.2 3.30 27.0 3.54 30.6 4.02 34.2 4.50 37.8 4.98
10.0 18.0 2.36 21.6 2.84 25.2 3.32 27.0 3.55 30.6 4.04 34.2 4.52 37.8 5.02
15.0 18.0 2.38 21.6 2.86 25.2 3.35 27.0 3.61 30.6 4.10 34.2 4.61 37.8 5.10
60% 20.0 18.0 2.44 21.6 2.95 25.2 3.48 27.0 3.76 30.6 4.28 34.2 4.84 37.8 5.39
25.0 18.0 2.77 21.6 3.42 25.2 4.06 27.0 4.37 30.6 5.09 34.2 5.81 37.8 6.60 8
30.0 18.0 3.54 21.6 4.25 25.2 5.03 27.0 5.44 30.6 6.29 34.2 7.18 37.8 8.13
35.0 18.0 4.27 21.6 5.14 25.2 6.08 27.0 6.57 30.6 7.58 34.2 8.65 37.8 9.78
40.0 18.0 5.06 21.6 6.10 25.2 7.21 27.0 7.79 30.6 8.99 34.2 10.26 37.8 11.57
43.0 18.0 5.55 21.6 6.72 25.2 7.94 27.0 8.58 30.6 9.90 34.2 11.30 37.5 12.54
46.0 18.0 6.08 21.6 7.35 25.2 8.71 27.0 9.41 29.6 10.23 29.6 9.42 29.6 8.67
9-27 9

5GEKPFF 
Capacity Table

1. Capacity Ratio of Outdoor Unit

U-16MF2E8 (Cooling) Capacity Ratio 20-130%


TC: Total capacity (kW), PI: Power input (kW)

Indoor air temp䋮䋺㷄WB


Combination(%) Outdoor
14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 15.0 1.96 18.0 2.34 21.0 2.73 22.5 2.92 25.5 3.33 28.5 3.71 31.5 4.11
-5.0 15.0 1.96 18.0 2.34 21.0 2.74 22.5 2.92 25.5 3.33 28.5 3.71 31.5 4.11
0.0 15.0 1.96 18.0 2.34 21.0 2.74 22.5 2.94 25.5 3.33 28.5 3.73 31.5 4.13
5.0 15.0 1.96 18.0 2.36 21.0 2.74 22.5 2.94 25.5 3.33 28.5 3.74 31.5 4.14
10.0 15.0 1.96 18.0 2.36 21.0 2.76 22.5 2.95 25.5 3.35 28.5 3.76 31.5 4.17
15.0 15.0 1.97 18.0 2.37 21.0 2.78 22.5 2.98 25.5 3.39 28.5 3.80 31.5 4.21
50% 20.0 15.0 2.00 18.0 2.43 21.0 2.85 22.5 3.07 25.5 3.50 28.5 3.94 31.5 4.37
25.0 15.0 2.19 18.0 2.70 21.0 3.21 22.5 3.46 25.5 3.99 28.5 4.52 31.5 5.07
30.0 15.0 2.92 18.0 3.47 21.0 4.04 22.5 4.35 25.5 4.96 28.5 5.61 31.5 6.31
35.0 15.0 3.52 18.0 4.19 21.0 4.89 22.5 5.27 25.5 6.01 28.5 6.80 31.5 7.61
40.0 15.0 4.17 18.0 4.98 21.0 5.81 22.5 6.25 25.5 7.14 28.5 8.08 31.5 9.03
43.0 15.0 4.58 18.0 5.47 21.0 6.40 22.5 6.87 25.5 7.86 28.5 8.88 31.5 9.97
46.0 15.0 5.00 18.0 5.99 21.0 7.01 22.5 7.54 25.5 8.64 28.5 9.76 29.6 9.68
1 Indoor air temp䋮䋺㷄WB
Combination(%) Outdoor
14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 12.0 1.55 14.4 1.88 16.8 2.18 18.0 2.34 20.4 2.66 22.8 2.96 25.2 3.29

2 -5.0
0.0
12.0
12.0
1.55
1.55
14.4
14.4
1.88
1.88
16.8
16.8
2.18
2.19
18.0
18.0
2.34
2.34
20.4
20.4
2.66
2.66
22.8
22.8
2.96
2.98
25.2
25.2
3.29
3.29
5.0 12.0 1.56 14.4 1.88 16.8 2.19 18.0 2.36 20.4 2.66 22.8 2.98 25.2 3.30
10.0 12.0 1.56 14.4 1.88 16.8 2.19 18.0 2.36 20.4 2.67 22.8 2.99 25.2 3.32
15.0 12.0 1.56 14.4 1.89 16.8 2.21 18.0 2.37 20.4 2.69 22.8 3.02 25.2 3.33
40% 20.0 12.0 1.59 14.4 1.92 16.8 2.25 18.0 2.43 20.4 2.76 22.8 3.09 25.2 3.43
25.0 12.0 1.69 14.4 2.06 16.8 2.44 18.0 2.62 20.4 3.00 22.8 3.39 25.2 3.77

3 30.0
35.0
12.0
12.0
2.37
2.84
14.4
14.4
2.76
3.33
16.8
16.8
3.17
3.83
18.0
18.0
3.37
4.09
20.4
20.4
3.80
4.62
22.8
22.8
4.25
5.16
25.2
25.2
4.70
5.72
40.0 12.0 3.33 14.4 3.94 16.8 4.54 18.0 4.85 20.4 5.50 22.8 6.14 25.2 6.81
43.0 12.0 3.66 14.4 4.32 16.8 4.99 18.0 5.33 20.4 6.03 22.8 6.77 25.2 7.50
46.0 12.0 3.99 14.4 4.72 16.8 5.47 18.0 5.85 20.4 6.62 22.8 7.42 25.2 8.24

Indoor air temp䋮䋺㷄WB


Combination(%) Outdoor
4 :Indoor/outdoor
capacity ratio
air temp.
㷄DB
TC
14.0
PI TC
16.0
PI TC
18.0
PI TC
19.0
PI TC
21.0
PI TC
23.0
PI TC
25.0
PI
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 9.0 1.17 10.8 1.41 12.6 1.63 13.5 1.76 15.3 2.00 17.1 2.22 18.9 2.46
-5.0 9.0 1.17 10.8 1.41 12.6 1.63 13.5 1.76 15.3 2.00 17.1 2.22 18.9 2.46
0.0 9.0 1.17 10.8 1.41 12.6 1.63 13.5 1.76 15.3 2.00 17.1 2.23 18.9 2.46
5.0 9.0 1.17 10.8 1.41 12.6 1.65 13.5 1.76 15.3 2.00 17.1 2.23 18.9 2.47
5 10.0
15.0
9.0
9.0
1.17
1.18
10.8
10.8
1.41
1.41
12.6
12.6
1.65
1.65
13.5
13.5
1.77
1.77
15.3
15.3
2.00
2.00
17.1
17.1
2.23
2.25
18.9
18.9
2.47
2.48
30% 20.0 9.0 1.18 10.8 1.43 12.6 1.66 13.5 1.80 15.3 2.03 17.1 2.28 18.9 2.52
25.0 9.0 1.23 10.8 1.49 12.6 1.76 13.5 1.88 15.3 2.14 17.1 2.41 18.9 2.67
30.0 9.0 1.86 10.8 2.13 12.6 2.40 13.5 2.52 15.3 2.81 17.1 3.09 18.9 3.36
35.0 9.0 2.21 10.8 2.54 12.6 2.88 13.5 3.04 15.3 3.39 17.1 3.74 18.9 4.10
40.0 9.0 2.58 10.8 2.98 12.6 3.39 13.5 3.61 15.3 4.02 17.1 4.44 18.9 4.87
6 43.0
46.0
9.0
9.0
2.82
3.06
10.8
10.8
3.26
3.56
12.6
12.6
3.73
4.07
13.5
13.5
3.95
4.32
15.3
15.3
4.42
4.84
17.1
17.1
4.89
5.36
18.9
18.9
5.37
5.89

Indoor air temp䋮䋺㷄WB


Combination(%) Outdoor
14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio 㷄DB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
7 -10.0
-5.0
6.0
6.0
0.78
0.78
7.2
7.2
0.93
0.93
8.4
8.4
1.10
1.10
9.0
9.0
1.17
1.17
10.2
10.2
1.33
1.33
11.4
11.4
1.49
1.49
12.6
12.6
1.63
1.63
0.0 6.0 0.78 7.2 0.93 8.4 1.10 9.0 1.17 10.2 1.33 11.4 1.49 12.6 1.63
5.0 6.0 0.78 7.2 0.93 8.4 1.10 9.0 1.17 10.2 1.33 11.4 1.49 12.6 1.65
10.0 6.0 0.78 7.2 0.95 8.4 1.10 9.0 1.17 10.2 1.33 11.4 1.49 12.6 1.65
15.0 6.0 0.78 7.2 0.95 8.4 1.11 9.0 1.18 10.2 1.33 11.4 1.49 12.6 1.65
20%
8 20.0
25.0
6.0
6.0
0.78
0.80
7.2
7.2
0.95
0.97
8.4
8.4
1.11
1.13
9.0
9.0
1.18
1.21
10.2
10.2
1.34
1.38
11.4
11.4
1.51
1.55
12.6
12.6
1.66
1.71
30.0 6.0 1.17 7.2 1.34 8.4 1.53 9.0 1.61 10.2 1.78 11.4 1.96 12.6 2.13
35.0 6.0 1.63 7.2 1.84 8.4 2.03 9.0 2.13 10.2 2.33 11.4 2.51 12.6 2.71
40.0 6.0 1.88 7.2 2.13 8.4 2.37 9.0 2.48 10.2 2.73 11.4 2.96 12.6 3.22
43.0 6.0 2.03 7.2 2.30 8.4 2.58 9.0 2.71 10.2 2.99 11.4 3.26 12.6 3.52
46.0 6.0 2.19 7.2 2.50 8.4 2.81 9.0 2.95 10.2 3.26 11.4 3.56 12.6 3.85

9 9-28

5GEKPFF 
Capacity Table

1. Capacity Ratio of Outdoor Unit

1-10. U-16MF2E8 (Heating) Capacity Ratio 20-130%


TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp䋮䋺㷄DB
Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 37.3 13.70 34.4 12.60 32.4 11.87 32.4 11.87 32.4 11.87 32.4 11.87 28.4 10.27
-14.7 -15.0 39.5 13.91 36.5 12.83 34.5 12.09 34.5 12.09 34.5 12.09 34.5 12.09 30.4 10.50
-9.6 -10.0 42.4 14.24 39.3 13.16 37.2 12.42 37.2 12.42 37.2 12.42 37.2 12.42 33.1 10.85
-4.4 -5.0 46.3 14.76 43.0 13.66 40.8 12.92 40.8 12.92 40.8 12.92 40.8 12.92 36.7 11.33
-1.8 -2.5 48.8 15.09 45.4 14.01 43.1 13.24 43.1 13.24 43.1 13.24 43.1 13.24 38.9 11.66
0.8 0.0 51.7 15.50 48.3 14.40 45.8 13.64 45.8 13.64 45.8 13.64 45.8 13.64 41.8 12.08
130% 2.8 2.0 54.5 15.87 51.0 14.77 48.5 14.01 48.5 14.01 48.5 14.01 48.5 14.01 44.0 12.24
6.0 5.0 59.0 16.12 56.1 15.40 53.6 14.67 53.6 14.67 53.6 14.67 51.8 13.29 44.0 11.14
7.0 6.0 60.8 16.12 57.8 15.44 53.8 14.16 53.8 14.16 53.8 14.16 51.8 12.80 44.0 10.73
8.6 7.5 63.2 16.12 57.8 14.48 53.8 13.29 53.8 13.29 53.8 13.29 51.8 12.04 44.0 10.11
11.2 10.0 63.7 14.62 57.8 12.96 53.8 11.90 53.8 11.90 53.8 11.90 51.8 10.83 44.0 9.11
16.4 15.0 63.7 11.42 57.8 10.19 53.8 9.40 53.8 9.40 53.8 9.40 51.8 8.66 44.0 7.35
24.0 18.0 63.7 9.77 57.8 8.75 53.8 8.11 53.8 8.11 53.8 8.11 51.8 7.54 44.0 6.45

Indoor air temp䋮䋺㷄DB


1
Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 37.3 13.55 34.4 12.49 32.5 11.76 32.5 11.76 32.5 11.76 30.2 10.81 26.2 9.51
-14.7 -15.0 39.6 13.78 36.6 12.71 34.6 11.99 34.6 11.99 34.6 11.99 32.3 11.06 28.1 9.72
-9.6
-4.4
-10.0
-5.0
42.5 14.12
46.4 14.63
39.4 13.06
43.1 13.57
37.2 12.33 37.2 12.33 37.2 12.33
40.8 12.82 40.8 12.82 40.8 12.82
35.0 11.41
38.6 11.92
30.5 10.03
33.8 10.47
2
-1.8 -2.5 48.8 14.98 45.5 13.89 43.1 13.14 43.1 13.14 43.1 13.14 40.9 12.25 35.8 10.76
0.8 0.0 51.8 15.38 48.3 14.28 45.8 13.53 45.8 13.53 45.8 13.53 43.7 12.66 38.4 11.12
120% 2.8 2.0 54.6 15.75 50.9 14.66 48.4 13.89 48.4 13.89 48.4 13.89 46.6 13.03 39.7 11.00
6.0 5.0 59.4 16.12 56.1 15.25 52.5 14.11 52.5 14.11 52.5 14.11 46.7 11.89 39.7 10.01
7.0 6.0 61.1 16.12 56.4 14.77 52.5 13.57 52.5 13.57 52.5 13.57 46.7 11.45 39.7 9.63
8.6
11.2
7.5
10.0
62.2 15.61
62.2 13.91
56.4 13.85
56.4 12.38
52.5 12.73 52.5 12.73 52.5 12.73
52.5 11.40 52.5 11.40 52.5 11.40
46.7 10.78
46.7 9.68
39.7
39.7
9.08
8.20
3
16.4 15.0 62.2 10.85 56.4 9.71 52.5 8.99 52.5 8.99 52.5 8.99 46.7 7.75 39.7 6.62
24.0 18.0 62.2 9.26 56.4 8.33 52.5 7.74 52.5 7.74 52.5 7.74 46.7 6.76 39.7 5.82

Indoor air temp䋮䋺㷄DB


Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor
capacity ratio
air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI 4
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 37.4 13.42 34.5 12.36 32.5 11.64 32.5 11.64 31.2 11.12 27.7 9.93 24.0 8.75
-14.7 -15.0 39.7 13.64 36.7 12.60 34.6 11.88 34.6 11.88 33.3 11.37 29.6 10.16 25.7 8.95
-9.6 -10.0 42.6 14.00 39.4 12.95 37.3 12.23 37.3 12.23 36.0 11.73 32.0 10.48 27.9 9.23
-4.4 -5.0 46.5 14.52 43.1 13.45 40.8 12.72 40.8 12.72 39.6 12.23 35.4 10.92 30.9 9.61
-1.8
0.8
-2.5
0.0
48.9
51.8
14.86
15.26
45.5
48.3
13.79
14.17
43.1
45.8
13.04 43.1 13.04 41.9 12.55
13.42 45.8 13.42 44.6 12.93
37.4 11.22
40.0 11.57
32.7 9.87
35.1 10.19 5
110% 2.8 2.0 54.6 15.62 50.9 14.52 48.4 13.75 48.4 13.75 47.3 13.27 41.8 11.63 35.5 9.82
6.0 5.0 59.7 16.12 55.1 14.69 51.3 13.52 51.3 13.52 48.0 12.31 41.8 10.58 35.5 8.94
7.0 6.0 60.8 15.88 55.1 14.11 51.3 12.98 51.3 12.98 48.0 11.84 41.8 10.18 35.5 8.61
8.6 7.5 60.8 14.87 55.1 13.23 51.3 12.18 51.3 12.18 48.0 11.12 41.8 9.59 35.5 8.12
11.2 10.0 60.8 13.24 55.1 11.80 51.3 10.89 51.3 10.89 48.0 9.97 41.8 8.62 35.5 7.33
16.4
24.0
15.0
18.0
60.8
60.8
10.30
8.78
55.1
55.1
9.25
7.92
51.3
51.3
8.58
7.38
51.3
51.3
8.58
7.38
48.0
48.0
7.92
6.87
41.8
41.8
6.91
6.04
35.5
35.5
5.94
5.22 6
Indoor air temp䋮䋺㷄DB
Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8
-14.7
-20.0
-15.0
37.5
39.8
13.28
13.52
34.6
36.7
12.25
12.49
32.5
34.6
11.54 30.5 10.84 28.4 10.12
11.79 32.5 11.07 30.3 10.35
25.1
26.9
9.05
9.26
21.8
23.3
8.01
8.18
7
-9.6 -10.0 42.7 13.88 39.5 12.85 37.3 12.14 35.0 11.41 32.7 10.68 29.1 9.55 25.3 8.43
-4.4 -5.0 46.5 14.40 43.2 13.35 40.9 12.62 38.5 11.88 36.0 11.12 32.1 9.96 28.0 8.77
-1.8 -2.5 49.0 14.74 45.5 13.68 43.1 12.95 40.6 12.19 38.0 11.41 34.0 10.22 29.7 9.00
0.8 0.0 51.9 15.14 48.3 14.06 45.8 13.32 43.2 12.55 40.5 11.74 36.3 10.52 31.5 9.18
100% 2.8 2.0 54.6 15.49 50.9 14.38 48.3 13.62 45.7 12.83 42.6 11.92 37.1 10.27 31.5 8.72
6.0
7.0
5.0
6.0
59.3
59.3
15.77
15.13
53.7
53.7
14.04
13.48
50.0
50.0
12.93 46.3 11.85 42.6 10.83
12.40 46.3 11.41 42.6 10.42
37.1
37.1
9.35
9.00
31.5
31.5
7.94
7.64
8
8.6 7.5 59.3 14.15 53.7 12.62 50.0 11.64 46.3 10.70 42.6 9.78 37.1 8.47 31.5 7.20
11.2 10.0 59.3 12.59 53.7 11.26 50.0 10.40 46.3 9.59 42.6 8.78 37.1 7.63 31.5 6.52
16.4 15.0 59.3 9.77 53.7 8.80 50.0 8.18 46.3 7.58 42.6 6.98 37.1 6.13 31.5 5.29
24.0 18.0 59.3 8.31 53.7 7.54 50.0 7.03 46.3 6.55 42.6 6.06 37.1 5.36 31.5 4.66

9-29 9

5GEKPFF 
Capacity Table

1. Capacity Ratio of Outdoor Unit

U-16MF2E8 (Heating) Capacity Ratio 20-130%


TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp䋮䋺㷄DB
Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 37.8 12.77 34.8 11.82 32.7 11.17 30.6 10.52 28.5 9.86 25.2 8.88 21.7 7.92
-14.7 -15.0 40.1 13.06 37.0 12.09 34.8 11.43 32.6 10.76 30.4 10.09 26.9 9.08 23.3 8.07
-9.6 -10.0 43.0 13.44 39.7 12.46 37.5 11.78 35.1 11.10 32.7 10.40 29.0 9.35 25.2 8.30
-4.4 -5.0 46.8 13.97 43.4 12.96 40.9 12.26 38.4 11.54 35.9 10.81 31.9 9.71 27.7 8.58
-1.8 -2.5 49.3 14.31 45.6 13.27 43.1 12.56 40.5 11.83 37.8 11.09 33.4 9.82 28.4 8.46
0.8 0.0 52.1 14.63 48.3 13.57 45.0 12.57 41.7 11.61 38.4 10.65 33.4 9.29 28.4 8.00
90% 2.8 2.0 53.4 14.31 48.4 12.85 45.0 11.90 41.7 10.99 38.4 10.09 33.4 8.82 28.4 7.59
6.0 5.0 53.4 12.86 48.4 11.58 45.0 10.75 41.7 9.94 38.4 9.15 33.4 8.00 28.4 6.87
7.0 6.0 53.4 12.33 48.4 11.11 45.0 10.32 41.7 9.55 38.4 8.79 33.4 7.69 28.4 6.62
8.6 7.5 53.4 11.49 48.4 10.38 45.0 9.66 41.7 8.94 38.4 8.25 33.4 7.23 28.4 6.24
11.2 10.0 53.4 10.17 48.4 9.21 45.0 8.59 41.7 7.99 38.4 7.39 33.4 6.51 28.4 5.64
16.4 15.0 53.4 7.80 48.4 7.14 45.0 6.71 41.7 6.27 38.4 5.85 33.4 5.21 28.4 4.58
24.0 18.0 53.4 7.04 48.4 6.47 45.0 6.09 41.7 5.70 38.4 5.33 33.4 4.75 28.4 4.18
1 Indoor air temp䋮䋺㷄DB
Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 38.2 12.38 35.1 11.49 33.0 10.89 30.8 10.29 28.6 9.68 25.2 8.79 21.8 7.91
-14.7 -15.0 40.5 12.69 37.3 11.78 35.1 11.16 32.8 10.54 30.5 9.91 26.9 8.97 23.3 8.04
2 -9.6
-4.4
-10.0
-5.0
43.5
47.3
13.09
13.63
40.0
43.0
12.15
12.41
37.7
40.0
11.52 35.3 10.86 32.8 10.21
11.58 37.1 10.76 34.1 9.97
29.0
29.7
9.21
8.82
25.1
25.2
8.22
7.71
-1.8 -2.5 47.4 13.01 43.0 11.79 40.0 11.01 37.1 10.23 34.1 9.49 29.7 8.39 25.2 7.34
0.8 0.0 47.4 12.21 43.0 11.10 40.0 10.37 37.1 9.65 34.1 8.94 29.7 7.92 25.2 6.93
80% 2.8 2.0 47.4 11.52 43.0 10.48 40.0 9.80 37.1 9.13 34.1 8.47 29.7 7.50 25.2 6.56
6.0 5.0 47.4 10.30 43.0 9.41 40.0 8.82 37.1 8.22 34.1 7.64 29.7 6.77 25.2 5.90
7.0 6.0 47.4 9.86 43.0 9.01 40.0 8.44 37.1 7.89 34.1 7.33 29.7 6.50 25.2 5.68
3 8.6
11.2
7.5
10.0
47.4
47.4
9.16
8.07
43.0
43.0
8.39
7.43
40.0
40.0
7.89
7.01
37.1
37.1
7.38
6.57
34.1
34.1
6.87
6.14
29.7
29.7
6.11
5.49
25.2
25.2
5.34
4.84
16.4 15.0 47.4 6.36 43.0 5.85 40.0 5.52 37.1 5.18 34.1 4.85 29.7 4.39 25.2 3.93
24.0 18.0 47.4 6.36 43.0 5.85 40.0 5.52 37.1 5.18 34.1 4.84 29.7 4.33 25.2 3.82

Indoor air temp䋮䋺㷄DB


Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
4 :Indoor/outdoor
capacity ratio
air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 38.9 12.15 35.7 11.33 33.5 10.78 31.3 10.23 29.0 9.67 25.5 8.84 22.0 8.02
-14.7 -15.0 41.3 12.49 37.6 11.53 35.0 10.84 32.4 10.17 29.8 9.51 26.0 8.54 22.1 7.61
-9.6 -10.0 41.5 11.89 37.6 10.91 35.0 10.28 32.4 9.65 29.8 9.01 26.0 8.08 22.1 7.17
-4.4 -5.0 41.5 10.90 37.6 10.03 35.0 9.45 32.4 8.88 29.8 8.31 26.0 7.49 22.1 6.67

5 -1.8
0.8
-2.5
0.0
41.5
41.5
10.33
9.67
37.6
37.6
9.50
8.92
35.0
35.0
8.97
8.42
32.4
32.4
8.42
7.92
29.8
29.8
7.89
7.43
26.0
26.0
7.11
6.70
22.1
22.1
6.32
5.95
70% 2.8 2.0 41.5 9.09 37.6 8.39 35.0 7.94 32.4 7.48 29.8 7.02 26.0 6.32 22.1 5.59
6.0 5.0 41.5 8.10 37.6 7.51 35.0 7.12 32.4 6.71 29.8 6.30 26.0 5.65 22.1 5.00
7.0 6.0 41.5 7.73 37.6 7.18 35.0 6.81 32.4 6.42 29.8 6.03 26.0 5.43 22.1 4.81
8.6 7.5 41.5 7.17 37.6 6.68 35.0 6.35 32.4 6.00 29.8 5.65 26.0 5.11 22.1 4.54
11.2 10.0 41.5 6.27 37.6 5.89 35.0 5.62 32.4 5.33 29.8 5.05 26.0 4.59 22.1 4.10

6 16.4
24.0
15.0
18.0
41.5
41.5
5.69
5.69
37.6
37.6
5.25
5.25
35.0
35.0
4.95
4.95
32.4
32.4
4.65
4.65
29.8
29.8
4.35
4.35
26.0
26.0
3.91
3.91
22.1
22.1
3.46
3.46

Indoor air temp䋮䋺㷄DB


Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
7 -19.8
-14.7
-20.0
-15.0
35.6
35.6
10.55
10.01
32.2
32.2
9.81
9.35
30.0
30.0
9.31
8.90
27.8
27.8
8.83
8.44
25.6
25.6
8.35
7.97
22.2
22.2
7.64
7.27
18.9
18.9
6.94
6.57
-9.6 -10.0 35.6 9.34 32.2 8.73 30.0 8.32 27.8 7.91 25.6 7.50 22.2 6.87 18.9 6.19
-4.4 -5.0 35.6 8.52 32.2 7.97 30.0 7.61 27.8 7.24 25.6 6.87 22.2 6.30 18.9 5.72
-1.8 -2.5 35.6 8.04 32.2 7.54 30.0 7.20 27.8 6.86 25.6 6.51 22.2 5.96 18.9 5.41
0.8 0.0 35.6 7.50 32.2 7.06 30.0 6.75 27.8 6.42 25.6 6.10 22.2 5.59 18.9 5.02
60% 2.8 2.0 35.6 7.03 32.2 6.62 30.0 6.34 27.8 6.04 25.6 5.74 22.2 5.23 18.9 4.67
8 6.0
7.0
5.0
6.0
35.6
35.6
6.22
5.93
32.2
32.2
5.89
5.62
30.0
30.0
5.64
5.38
27.8
27.8
5.37
5.15
25.6
25.6
5.10
4.89
22.2
22.2
4.66
4.48
18.9
18.9
4.19
4.03
8.6 7.5 35.6 5.48 32.2 5.21 30.0 5.01 27.8 4.80 25.6 4.58 22.2 4.20 18.9 3.81
11.2 10.0 35.6 5.01 32.2 4.63 30.0 4.43 27.8 4.25 25.6 4.08 22.2 3.78 18.9 3.46
16.4 15.0 35.6 5.01 32.2 4.63 30.0 4.38 27.8 4.12 25.6 3.86 22.2 3.48 18.9 3.10
24.0 18.0 35.6 5.01 32.2 4.63 30.0 4.38 27.8 4.12 25.6 3.86 22.2 3.48 18.9 3.10

9 9-30

5GEKPFF 
Capacity Table

1. Capacity Ratio of Outdoor Unit

U-16MF2E8 (Heating) Capacity Ratio 20-130%


TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp䋮䋺㷄DB
Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 29.7 8.25 26.9 7.86 25.0 7.58 23.2 7.27 21.3 6.93 18.5 6.44 15.8 5.93
-14.7 -15.0 29.7 7.77 26.9 7.42 25.0 7.15 23.2 6.89 21.3 6.62 18.5 6.11 15.8 5.60
-9.6 -10.0 29.7 7.22 26.9 6.89 25.0 6.66 23.2 6.42 21.3 6.18 18.5 5.75 15.8 5.27
-4.4 -5.0 29.7 6.53 26.9 6.26 25.0 6.06 23.2 5.85 21.3 5.62 18.5 5.25 15.8 4.84
-1.8 -2.5 29.7 6.14 26.9 5.89 25.0 5.70 23.2 5.52 21.3 5.31 18.5 4.96 15.8 4.48
0.8 0.0 29.7 5.72 26.9 5.49 25.0 5.32 23.2 5.15 21.3 4.95 18.5 4.56 15.8 4.13
50% 2.8 2.0 29.7 5.33 26.9 5.13 25.0 4.98 23.2 4.80 21.3 4.59 18.5 4.24 15.8 3.84
6.0 5.0 29.7 4.67 26.9 4.50 25.0 4.38 23.2 4.23 21.3 4.05 18.5 3.78 15.8 3.46
7.0 6.0 29.7 4.43 26.9 4.29 25.0 4.17 23.2 4.04 21.3 3.89 18.5 3.63 15.8 3.34
8.6 7.5 29.7 4.33 26.9 4.01 25.0 3.88 23.2 3.77 21.3 3.65 18.5 3.42 15.8 3.15
11.2 10.0 29.7 4.33 26.9 4.01 25.0 3.79 23.2 3.58 21.3 3.37 18.5 3.08 15.8 2.86
16.4 15.0 29.7 4.33 26.9 4.01 25.0 3.79 23.2 3.58 21.3 3.37 18.5 3.05 15.8 2.74
24.0 18.0 29.7 4.33 26.9 4.01 25.0 3.79 23.2 3.58 21.3 3.37 18.5 3.05 15.8 2.74

Indoor air temp䋮䋺㷄DB


1
Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 23.7 6.36 21.5 6.19 20.0 6.05 18.5 5.89 17.1 5.68 14.8 5.33 12.6 4.97
-14.7 -15.0 23.7 5.98 21.5 5.83 20.0 5.70 18.5 5.56 17.1 5.39 14.8 5.06 12.6 4.69
-9.6
-4.4
-10.0
-5.0
23.7
23.7
5.52
4.96
21.5
21.5
5.38
4.86
20.0
20.0
5.28
4.77
18.5
18.5
5.16
4.66
17.1
17.1
5.01
4.54
14.8
14.8
4.75
4.27
12.6
12.6
4.40
3.87
2
-1.8 -2.5 23.7 4.64 21.5 4.55 20.0 4.48 18.5 4.38 17.1 4.22 14.8 3.93 12.6 3.60
0.8 0.0 23.7 4.28 21.5 4.22 20.0 4.12 18.5 3.99 17.1 3.86 14.8 3.61 12.6 3.32
40% 2.8 2.0 23.7 3.97 21.5 3.87 20.0 3.78 18.5 3.68 17.1 3.57 14.8 3.36 12.6 3.11
6.0 5.0 23.7 3.65 21.5 3.40 20.0 3.31 18.5 3.25 17.1 3.16 14.8 3.00 12.6 2.80
7.0 6.0 23.7 3.65 21.5 3.40 20.0 3.22 18.5 3.10 17.1 3.04 14.8 2.89 12.6 2.72
8.6
11.2
7.5
10.0
23.7
23.7
3.65
3.65
21.5
21.5
3.40
3.40
20.0
20.0
3.22
3.22
18.5
18.5
3.05
3.05
17.1
17.1
2.89
2.89
14.8
14.8
2.73
2.63
12.6
12.6
2.57
2.38
3
16.4 15.0 23.7 3.65 21.5 3.40 20.0 3.22 18.5 3.05 17.1 2.89 14.8 2.63 12.6 2.38
24.0 18.0 23.7 3.65 21.5 3.40 20.0 3.22 18.5 3.05 17.1 2.89 14.8 2.63 12.6 2.38

Indoor air temp䋮䋺㷄DB


Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor
capacity ratio
air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI 4
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 17.8 4.86 16.1 4.81 15.0 4.75 13.9 4.66 12.8 4.51 11.1 4.29 9.5 4.03
-14.7 -15.0 17.8 4.55 16.1 4.51 15.0 4.46 13.9 4.39 12.8 4.29 11.1 4.07 9.5 3.79
-9.6 -10.0 17.8 4.17 16.1 4.15 15.0 4.12 13.9 4.05 12.8 3.98 11.1 3.74 9.5 3.43
-4.4 -5.0 17.8 3.72 16.1 3.72 15.0 3.65 13.9 3.55 12.8 3.43 11.1 3.24 9.5 3.00
-1.8
0.8
-2.5
0.0
17.8
17.8
3.43
3.08
16.1
16.1
3.37
3.05
15.0
15.0
3.32
3.01
13.9
13.9
3.25
2.96
12.8
12.8
3.16
2.90
11.1
11.1
3.00
2.77
9.5
9.5
2.80
2.60 5
30% 2.8 2.0 17.8 2.98 16.1 2.80 15.0 2.78 13.9 2.75 12.8 2.69 11.1 2.59 9.5 2.44
6.0 5.0 17.8 2.98 16.1 2.78 15.0 2.65 13.9 2.53 12.8 2.41 11.1 2.33 9.5 2.23
7.0 6.0 17.8 2.98 16.1 2.78 15.0 2.65 13.9 2.53 12.8 2.39 11.1 2.26 9.5 2.16
8.6 7.5 17.8 2.98 16.1 2.78 15.0 2.65 13.9 2.53 12.8 2.39 11.1 2.21 9.5 2.06
11.2 10.0 17.8 2.98 16.1 2.78 15.0 2.65 13.9 2.53 12.8 2.39 11.1 2.21 9.5 2.02
16.4
24.0
15.0
18.0
17.8
17.8
2.98
2.98
16.1
16.1
2.78
2.78
15.0
15.0
2.65
2.65
13.9
13.9
2.53
2.53
12.8
12.8
2.39
2.39
11.1
11.1
2.21
2.21
9.5
9.5
2.02
2.02 6
Indoor air temp䋮䋺㷄DB
Combination(%) Outdoor
15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
㷄DB 㷄WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8
-14.7
-20.0
-15.0
11.9
11.9
3.60
3.36
10.8
10.8
3.58
3.36
10.0
10.0
3.55
3.34
9.3
9.3
3.48
3.30
8.5
8.5
3.39
3.20
7.4
7.4
3.25
2.99
6.3
6.3
3.09
2.77
7
-9.6 -10.0 11.9 3.04 10.8 2.99 10.0 2.94 9.3 2.88 8.5 2.81 7.4 2.67 6.3 2.50
-4.4 -5.0 11.9 2.54 10.8 2.54 10.0 2.52 9.3 2.49 8.5 2.44 7.4 2.34 6.3 2.22
-1.8 -2.5 11.9 2.32 10.8 2.33 10.0 2.32 9.3 2.29 8.5 2.27 7.4 2.19 6.3 2.10
0.8 0.0 11.9 2.29 10.8 2.16 10.0 2.13 9.3 2.12 8.5 2.10 7.4 2.05 6.3 1.96
20% 2.8 2.0 11.9 2.29 10.8 2.16 10.0 2.08 9.3 2.00 8.5 1.97 7.4 1.93 6.3 1.87
6.0
7.0
5.0
6.0
11.9
11.9
2.29
2.29
10.8
10.8
2.16
2.16
10.0
10.0
2.08
2.08
9.3
9.3
2.00
2.00
8.5
8.5
1.91
1.91
7.4
7.4
1.79
1.79
6.3
6.3
1.72
1.69
8
8.6 7.5 11.9 2.29 10.8 2.16 10.0 2.08 9.3 2.00 8.5 1.91 7.4 1.79 6.3 1.65
11.2 10.0 11.9 2.29 10.8 2.16 10.0 2.08 9.3 2.00 8.5 1.91 7.4 1.79 6.3 1.65
16.4 15.0 11.9 2.29 10.8 2.16 10.0 2.08 9.3 2.00 8.5 1.91 7.4 1.79 6.3 1.65
24.0 18.0 11.9 2.29 10.8 2.16 10.0 2.08 9.3 2.00 8.5 1.91 7.4 1.79 6.3 1.65

9-31 9

5GEKPFF 
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, HIGH EFFICIENCY (Cooling)


16 HP (U-8MF2E8 & U-8MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 41.9 6.87 48.4 7.94 48.4 7.94 48.4 7.94 54.8 8.99 61.3 10.04 67.7 11.08

-5.0 41.9 6.88 48.4 7.94 48.4 7.94 48.4 7.94 54.8 9.00 61.3 10.04 67.7 11.09

0.0 41.9 6.88 48.4 7.95 48.4 7.95 48.4 7.95 54.8 9.00 61.3 10.05 67.7 11.10

5.0 41.9 6.89 48.4 7.96 48.4 7.96 48.4 7.96 54.8 9.01 61.3 10.07 67.7 11.11

10.0 41.9 6.89 48.4 7.97 48.4 7.97 48.4 7.97 54.8 9.03 61.3 10.09 67.7 11.13

15.0 41.9 6.91 48.4 8.00 48.4 8.00 48.4 8.00 54.8 9.07 61.3 10.13 67.7 11.18

130% 20.0 41.9 6.95 48.4 8.07 48.4 8.07 48.4 8.07 54.8 9.14 61.3 10.21 67.7 11.26

25.0 41.9 7.07 48.4 8.24 48.4 8.24 48.4 8.24 54.8 9.33 61.3 10.40 67.7 11.44

30.0 41.9 7.75 48.4 8.86 48.4 8.86 48.4 8.86 54.8 9.92 61.3 10.97 67.7 11.94

35.0 41.9 9.70 48.4 11.03 48.4 11.03 48.4 11.03 54.8 12.35 61.3 13.68 65.3 14.00

40.0 41.9 11.76 48.4 13.35 48.4 13.35 48.4 13.35 52.6 14.00 55.5 14.00 58.6 14.00

43.0 41.9 13.00 46.5 14.00 46.5 14.00 46.5 14.00 49.2 14.00 52.0 14.00 54.9 14.00

46.0 41.9 13.00 43.5 14.00 43.5 14.00 43.5 14.00 46.1 14.00 48.5 13.87 48.5 12.69

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 37.8 6.20 45.4 7.44 47.3 7.75 47.3 7.75 53.6 8.78 59.9 9.81 66.2 10.83

-5.0 37.8 6.20 45.4 7.44 47.3 7.76 47.3 7.76 53.6 8.79 59.9 9.81 66.2 10.83

0.0 37.8 6.21 45.4 7.45 47.3 7.76 47.3 7.76 53.6 8.79 59.9 9.82 66.2 10.84

5.0 37.8 6.21 45.4 7.45 47.3 7.77 47.3 7.77 53.6 8.80 59.9 9.83 66.2 10.85

10.0 37.8 6.22 45.4 7.46 47.3 7.79 47.3 7.79 53.6 8.82 59.9 9.85 66.2 10.88

15.0 37.8 6.23 45.4 7.49 47.3 7.81 47.3 7.81 53.6 8.85 59.9 9.89 66.2 10.92
120% 20.0 37.8 6.27 45.4 7.53 47.3 7.87 47.3 7.87 53.6 8.92 59.9 9.97 66.2 11.00

25.0 37.8 6.39 45.4 7.67 47.3 8.03 47.3 8.03 53.6 9.09 59.9 10.15 66.2 11.18

30.0 37.8 7.02 45.4 8.28 47.3 8.61 47.3 8.61 53.6 9.65 59.9 10.68 66.2 11.67

35.0 37.8 8.78 45.4 10.33 47.3 10.68 47.3 10.68 53.6 11.95 59.9 13.21 65.0 14.00

40.0 37.8 10.63 45.4 12.52 47.3 12.94 47.3 12.94 52.4 14.00 55.3 14.00 58.3 14.00

43.0 37.8 11.81 45.4 13.00 46.3 14.00 46.3 14.00 49.0 14.00 51.8 14.00 54.7 14.00

46.0 37.8 13.00 43.3 14.00 43.3 14.00 43.3 14.00 45.9 14.00 48.5 13.96 48.5 12.77

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 33.8 5.55 40.6 6.66 46.1 7.57 46.1 7.57 52.3 8.57 58.4 9.57 64.6 10.57

-5.0 33.8 5.55 40.6 6.66 46.1 7.57 46.1 7.57 52.3 8.58 58.4 9.58 64.6 10.57

0.0 33.8 5.55 40.6 6.67 46.1 7.58 46.1 7.58 52.3 8.58 58.4 9.58 64.6 10.58

5.0 33.8 5.56 40.6 6.67 46.1 7.58 46.1 7.58 52.3 8.59 58.4 9.60 64.6 10.60

10.0 33.8 5.57 40.6 6.68 46.1 7.60 46.1 7.60 52.3 8.61 58.4 9.62 64.6 10.62

15.0 33.8 5.58 40.6 6.70 46.1 7.62 46.1 7.62 52.3 8.64 58.4 9.65 64.6 10.66

110% 20.0 33.8 5.61 40.6 6.74 46.1 7.68 46.1 7.68 52.3 8.70 58.4 9.72 64.6 10.74

25.0 33.8 5.72 40.6 6.87 46.1 7.83 46.1 7.83 52.3 8.87 58.4 9.89 64.6 10.91

30.0 33.8 6.31 40.6 7.44 46.1 8.37 46.1 8.37 52.3 9.38 58.4 10.39 64.6 11.39

35.0 33.8 7.91 40.6 9.27 46.1 10.34 46.1 10.34 52.3 11.55 58.4 12.75 64.6 13.94

40.0 33.8 9.56 40.6 11.22 46.1 12.54 46.1 12.54 51.9 13.91 55.0 14.00 58.1 14.00

43.0 33.8 10.61 40.6 12.48 46.1 13.96 46.1 13.96 48.8 14.00 51.6 14.00 54.4 14.00

46.0 33.8 11.72 40.6 13.00 43.2 14.00 43.2 14.00 45.7 14.00 48.3 14.00 48.5 12.86

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 30.0 4.92 36.0 5.91 42.0 6.89 45.0 7.38 51.0 8.36 57.0 9.34 63.0 10.31

-5.0 30.0 4.92 36.0 5.91 42.0 6.90 45.0 7.39 51.0 8.37 57.0 9.34 63.0 10.32

0.0 30.0 4.93 36.0 5.91 42.0 6.90 45.0 7.39 51.0 8.37 57.0 9.35 63.0 10.32

5.0 30.0 4.93 36.0 5.92 42.0 6.91 45.0 7.40 51.0 8.38 57.0 9.36 63.0 10.34

10.0 30.0 4.94 36.0 5.93 42.0 6.92 45.0 7.41 51.0 8.40 57.0 9.38 63.0 10.36

15.0 30.0 4.95 36.0 5.95 42.0 6.94 45.0 7.44 51.0 8.43 57.0 9.41 63.0 10.39

100% 20.0 30.0 4.98 36.0 5.99 42.0 6.99 45.0 7.49 51.0 8.49 57.0 9.48 63.0 10.47

25.0 30.0 5.09 36.0 6.11 42.0 7.12 45.0 7.63 51.0 8.64 57.0 9.64 63.0 10.63

30.0 30.0 5.63 36.0 6.64 42.0 7.63 45.0 8.13 51.0 9.12 57.0 10.10 63.0 11.07

35.0 30.0 7.06 36.0 8.24 42.0 9.41 45.0 10.00 51.0 11.16 57.0 12.27 62.8 13.36

40.0 30.0 8.53 36.0 9.99 42.0 11.43 45.0 12.14 51.0 13.56 54.8 14.00 57.8 14.00

43.0 30.0 9.46 36.0 11.10 42.0 12.71 45.0 13.52 48.6 14.00 51.3 14.00 54.2 14.00

9 46.0 30.0 10.44 36.0 12.27 41.8 14.00 43.0 14.00 45.5 14.00 48.1 14.00 48.5 12.95
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, HIGH EFFICIENCY (Cooling)


16 HP (U-8MF2E8 & U-8MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 27.0 4.43 32.4 5.32 37.8 6.20 40.5 6.64 45.9 7.53 51.3 8.40 56.7 9.28

-5.0 27.0 4.43 32.4 5.32 37.8 6.21 40.5 6.65 45.9 7.53 51.3 8.41 56.7 9.28

0.0 27.0 4.43 32.4 5.32 37.8 6.21 40.5 6.65 45.9 7.53 51.3 8.41 56.7 9.29

5.0 27.0 4.44 32.4 5.33 37.8 6.21 40.5 6.66 45.9 7.54 51.3 8.42 56.7 9.30

10.0 27.0 4.44 32.4 5.33 37.8 6.22 40.5 6.67 45.9 7.55 51.3 8.44 56.7 9.31

15.0 27.0 4.45 32.4 5.35 37.8 6.24 40.5 6.69 45.9 7.57 51.3 8.46 56.7 9.34

90% 20.0 27.0 4.48 32.4 5.38 37.8 6.28 40.5 6.72 45.9 7.62 51.3 8.51 56.7 9.39

25.0 27.0 4.55 32.4 5.47 37.8 6.37 40.5 6.83 45.9 7.73 51.3 8.63 56.7 9.52

30.0 27.0 4.96 32.4 5.86 37.8 6.75 40.5 7.20 45.9 8.09 51.3 8.97 56.7 9.84

35.0 27.0 6.29 32.4 7.29 37.8 8.26 40.5 8.73 45.9 9.67 51.3 10.58 56.7 11.47

40.0 27.0 7.59 32.4 8.82 37.8 10.03 40.5 10.62 45.9 11.78 51.3 12.92 56.3 13.92

43.0 27.0 8.41 32.4 9.80 37.8 11.16 40.5 11.82 45.9 13.14 50.3 14.00 53.1 14.00

46.0 27.0 9.28 32.4 10.83 37.8 12.36 40.5 13.11 44.7 14.00 47.2 14.00 48.5 13.37

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 24.0 3.94 28.8 4.73 33.6 5.51 36.0 5.91 40.8 6.69 45.6 7.47 50.4 8.25

-5.0 24.0 3.94 28.8 4.73 33.6 5.52 36.0 5.91 40.8 6.69 45.6 7.47 50.4 8.25

0.0 24.0 3.94 28.8 4.73 33.6 5.52 36.0 5.91 40.8 6.70 45.6 7.48 50.4 8.25

5.0 24.0 3.94 28.8 4.73 33.6 5.52 36.0 5.92 40.8 6.70 45.6 7.48 50.4 8.26

10.0 24.0 3.95 28.8 4.74 33.6 5.53 36.0 5.92 40.8 6.71 45.6 7.49 50.4 8.27

15.0 24.0 3.96 28.8 4.75 33.6 5.54 36.0 5.94 40.8 6.73 45.6 7.51 50.4 8.29

80% 20.0 24.0 3.97 28.8 4.77 33.6 5.57 36.0 5.96 40.8 6.76 45.6 7.55 50.4 8.33

25.0 24.0 4.03 28.8 4.83 33.6 5.64 36.0 6.04 40.8 6.84 45.6 7.63 50.4 8.42

30.0 24.0 4.32 28.8 5.11 33.6 5.91 36.0 6.30 40.8 7.09 45.6 7.87 50.4 8.65

35.0 24.0 5.55 28.8 6.37 33.6 7.16 36.0 7.54 40.8 8.29 45.6 9.01 50.4 9.70

40.0 24.0 6.69 28.8 7.72 33.6 8.71 36.0 9.19 40.8 10.13 45.6 11.04 50.4 11.92

43.0 24.0 7.41 28.8 8.57 33.6 9.69 36.0 10.24 40.8 11.30 45.6 12.34 50.4 13.34

46.0 24.0 8.17 28.8 9.47 33.6 10.73 36.0 11.35 40.8 12.55 45.6 13.73 48.5 13.91

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 21.0 3.44 25.2 4.13 29.4 4.82 31.5 5.17 35.7 5.85 39.9 6.53 44.1 7.21

-5.0 21.0 3.45 25.2 4.14 29.4 4.83 31.5 5.17 35.7 5.85 39.9 6.54 44.1 7.22

0.0 21.0 3.45 25.2 4.14 29.4 4.83 31.5 5.17 35.7 5.86 39.9 6.54 44.1 7.22

5.0 21.0 3.45 25.2 4.14 29.4 4.83 31.5 5.18 35.7 5.86 39.9 6.55 44.1 7.23

10.0 21.0 3.45 25.2 4.15 29.4 4.84 31.5 5.18 35.7 5.87 39.9 6.55 44.1 7.23

15.0 21.0 3.46 25.2 4.15 29.4 4.85 31.5 5.19 35.7 5.88 39.9 6.57 44.1 7.25

70% 20.0 21.0 3.47 25.2 4.17 29.4 4.86 31.5 5.21 35.7 5.90 39.9 6.59 44.1 7.28

25.0 21.0 3.51 25.2 4.21 29.4 4.91 31.5 5.26 35.7 5.95 39.9 6.65 44.1 7.34

30.0 21.0 3.71 25.2 4.40 29.4 5.09 31.5 5.44 35.7 6.13 39.9 6.81 44.1 7.51

35.0 21.0 4.85 25.2 5.51 29.4 6.14 31.5 6.44 35.7 7.02 39.9 7.57 44.1 8.14

40.0 21.0 5.83 25.2 6.67 29.4 7.47 31.5 7.86 35.7 8.60 39.9 9.30 44.1 9.97

43.0 21.0 6.46 25.2 7.41 29.4 8.31 31.5 8.75 35.7 9.60 39.9 10.41 44.1 11.18

46.0 21.0 7.11 25.2 8.18 29.4 9.20 31.5 9.70 35.7 10.66 39.9 11.58 44.1 12.47

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 18.0 2.95 21.6 3.54 25.2 4.13 27.0 4.43 30.6 5.02 34.2 5.60 37.8 6.18

-5.0 18.0 2.95 21.6 3.55 25.2 4.14 27.0 4.43 30.6 5.02 34.2 5.60 37.8 6.19

0.0 18.0 2.96 21.6 3.55 25.2 4.14 27.0 4.43 30.6 5.02 34.2 5.61 37.8 6.19

5.0 18.0 2.96 21.6 3.55 25.2 4.14 27.0 4.44 30.6 5.02 34.2 5.61 37.8 6.20

10.0 18.0 2.96 21.6 3.55 25.2 4.14 27.0 4.44 30.6 5.03 34.2 5.62 37.8 6.20

15.0 18.0 2.97 21.6 3.56 25.2 4.15 27.0 4.45 30.6 5.04 34.2 5.63 37.8 6.21

60% 20.0 18.0 2.97 21.6 3.57 25.2 4.16 27.0 4.46 30.6 5.05 34.2 5.65 37.8 6.24

25.0 18.0 3.00 21.6 3.60 25.2 4.19 27.0 4.49 30.6 5.09 34.2 5.69 37.8 6.28

30.0 18.0 3.12 21.6 3.72 25.2 4.31 27.0 4.61 30.6 5.21 34.2 5.82 37.8 6.42

35.0 18.0 4.18 21.6 4.70 25.2 5.19 27.0 5.42 30.6 5.87 34.2 6.39 37.8 6.92

40.0 18.0 5.02 21.6 5.69 25.2 6.32 27.0 6.61 30.6 7.18 34.2 7.71 37.8 8.21

43.0 18.0 5.55 21.6 6.31 25.2 7.03 27.0 7.37 30.6 8.02 34.2 8.63 37.8 9.21

46.0 18.0 6.10 21.6 6.96 25.2 7.77 27.0 8.16 30.6 8.90 34.2 9.61 37.8 10.27

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, HIGH EFFICIENCY (Cooling)


16 HP (U-8MF2E8 & U-8MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 15.0 2.46 18.0 2.95 21.0 3.45 22.5 3.69 25.5 4.18 28.5 4.67 31.5 5.15

-5.0 15.0 2.46 18.0 2.95 21.0 3.45 22.5 3.69 25.5 4.18 28.5 4.67 31.5 5.16

0.0 15.0 2.46 18.0 2.96 21.0 3.45 22.5 3.69 25.5 4.18 28.5 4.67 31.5 5.16

5.0 15.0 2.46 18.0 2.96 21.0 3.45 22.5 3.70 25.5 4.19 28.5 4.68 31.5 5.16

10.0 15.0 2.47 18.0 2.96 21.0 3.45 22.5 3.70 25.5 4.19 28.5 4.68 31.5 5.17

15.0 15.0 2.47 18.0 2.96 21.0 3.46 22.5 3.71 25.5 4.20 28.5 4.69 31.5 5.18

50% 20.0 15.0 2.48 18.0 2.97 21.0 3.47 22.5 3.72 25.5 4.21 28.5 4.70 31.5 5.20

25.0 15.0 2.49 18.0 2.99 21.0 3.49 22.5 3.74 25.5 4.24 28.5 4.74 31.5 5.23

30.0 15.0 2.57 18.0 3.06 21.0 3.57 22.5 3.83 25.5 4.33 28.5 4.83 31.5 5.33

35.0 15.0 3.56 18.0 3.95 21.0 4.22 22.5 4.41 25.5 4.82 28.5 5.26 31.5 5.71

40.0 15.0 4.25 18.0 4.76 21.0 5.24 22.5 5.46 25.5 5.88 28.5 6.26 31.5 6.61

43.0 15.0 4.68 18.0 5.27 21.0 5.82 22.5 6.08 25.5 6.56 28.5 7.01 31.5 7.42

46.0 15.0 5.13 18.0 5.80 21.0 6.43 22.5 6.72 25.5 7.28 28.5 7.80 31.5 8.28

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 12.0 1.97 14.4 2.36 16.8 2.76 18.0 2.95 20.4 3.35 22.8 3.74 25.2 4.12

-5.0 12.0 1.97 14.4 2.36 16.8 2.76 18.0 2.95 20.4 3.35 22.8 3.74 25.2 4.13

0.0 12.0 1.97 14.4 2.36 16.8 2.76 18.0 2.96 20.4 3.35 22.8 3.74 25.2 4.13

5.0 12.0 1.97 14.4 2.37 16.8 2.76 18.0 2.96 20.4 3.35 22.8 3.74 25.2 4.13

10.0 12.0 1.97 14.4 2.37 16.8 2.76 18.0 2.96 20.4 3.35 22.8 3.75 25.2 4.14

15.0 12.0 1.98 14.4 2.37 16.8 2.77 18.0 2.97 20.4 3.36 22.8 3.75 25.2 4.14

40% 20.0 12.0 1.98 14.4 2.38 16.8 2.77 18.0 2.97 20.4 3.37 22.8 3.76 25.2 4.15

25.0 12.0 1.99 14.4 2.39 16.8 2.79 18.0 2.99 20.4 3.39 22.8 3.79 25.2 4.18

30.0 12.0 2.03 14.4 2.44 16.8 2.85 18.0 3.05 20.4 3.45 22.8 3.85 25.2 4.25

35.0 12.0 2.97 14.4 3.03 16.8 3.29 18.0 3.44 20.4 3.78 22.8 4.14 25.2 4.50

40.0 12.0 3.51 14.4 3.89 16.8 4.24 18.0 4.40 20.4 4.69 22.8 4.95 25.2 5.18

43.0 12.0 3.86 14.4 4.30 16.8 4.70 18.0 4.88 20.4 5.23 22.8 5.53 25.2 5.81

46.0 12.0 4.21 14.4 4.72 16.8 5.17 18.0 5.39 20.4 5.79 22.8 6.15 25.2 6.47

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 9.0 1.48 10.8 1.77 12.6 2.07 13.5 2.22 15.3 2.51 17.1 2.80 18.9 3.09

-5.0 9.0 1.48 10.8 1.77 12.6 2.07 13.5 2.22 15.3 2.51 17.1 2.80 18.9 3.10

0.0 9.0 1.48 10.8 1.77 12.6 2.07 13.5 2.22 15.3 2.51 17.1 2.80 18.9 3.10

5.0 9.0 1.48 10.8 1.78 12.6 2.07 13.5 2.22 15.3 2.51 17.1 2.81 18.9 3.10

10.0 9.0 1.48 10.8 1.78 12.6 2.07 13.5 2.22 15.3 2.52 17.1 2.81 18.9 3.10

15.0 9.0 1.48 10.8 1.78 12.6 2.08 13.5 2.22 15.3 2.52 17.1 2.81 18.9 3.11
30% 20.0 9.0 1.49 10.8 1.78 12.6 2.08 13.5 2.23 15.3 2.53 17.1 2.82 18.9 3.11

25.0 9.0 1.49 10.8 1.79 12.6 2.09 13.5 2.24 15.3 2.54 17.1 2.83 18.9 3.13

30.0 9.0 1.52 10.8 1.82 12.6 2.12 13.5 2.28 15.3 2.58 17.1 2.87 18.9 3.17

35.0 9.0 2.07 10.8 2.16 12.6 2.38 13.5 2.50 15.3 2.77 17.1 3.04 18.9 3.32

40.0 9.0 2.82 10.8 3.08 12.6 3.31 13.5 3.42 15.3 3.61 17.1 5.09 18.9 4.50

43.0 9.0 3.08 10.8 3.38 12.6 3.65 13.5 3.78 15.3 4.00 17.1 4.20 18.9 4.37

46.0 9.0 3.34 10.8 3.69 12.6 4.00 13.5 4.15 15.3 4.41 17.1 4.65 18.9 4.85

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, HIGH EFFICIENCY (Cooling)


24 HP (U-8MF2E8 & U-8MF2E8 & U-8MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 63.4 10.44 73.1 12.07 73.1 12.07 73.1 12.07 82.8 13.66 92.6 15.26 102.3 16.84

-5.0 63.4 10.46 73.1 12.07 73.1 12.07 73.1 12.07 82.8 13.68 92.6 15.26 102.3 16.86

0.0 63.4 10.46 73.1 12.08 73.1 12.08 73.1 12.08 82.8 13.68 92.6 15.28 102.3 16.87

5.0 63.4 10.47 73.1 12.10 73.1 12.10 73.1 12.10 82.8 13.70 92.6 15.31 102.3 16.89

10.0 63.4 10.47 73.1 12.11 73.1 12.11 73.1 12.11 82.8 13.73 92.6 15.34 102.3 16.92

15.0 63.4 10.50 73.1 12.16 73.1 12.16 73.1 12.16 82.8 13.79 92.6 15.40 102.3 16.99

130% 20.0 63.4 10.56 73.1 12.27 73.1 12.27 73.1 12.27 82.8 13.89 92.6 15.52 102.3 17.12

25.0 63.4 10.75 73.1 12.52 73.1 12.52 73.1 12.52 82.8 14.18 92.6 15.81 102.3 17.39

30.0 63.4 11.78 73.1 13.47 73.1 13.47 73.1 13.47 82.8 15.08 92.6 16.67 102.3 18.15

35.0 63.4 14.74 73.1 16.77 73.1 16.77 73.1 16.77 82.8 18.77 92.6 20.79 98.7 21.28

40.0 63.4 17.88 73.1 20.29 73.1 20.29 73.1 20.29 79.4 21.28 83.9 21.28 88.5 21.28

43.0 63.4 19.76 70.2 21.28 70.2 21.28 70.2 21.28 74.4 21.28 78.6 21.28 83.0 21.28

46.0 63.4 19.76 65.8 21.28 65.8 21.28 65.8 21.28 69.6 21.28 73.2 21.08 73.2 19.29

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 57.1 9.42 68.5 11.31 71.4 11.78 71.4 11.78 80.9 13.35 90.4 14.91 100.0 16.46

-5.0 57.1 9.42 68.5 11.31 71.4 11.80 71.4 11.80 80.9 13.36 90.4 14.91 100.0 16.46

0.0 57.1 9.44 68.5 11.32 71.4 11.80 71.4 11.80 80.9 13.36 90.4 14.93 100.0 16.48

5.0 57.1 9.44 68.5 11.32 71.4 11.81 71.4 11.81 80.9 13.38 90.4 14.94 100.0 16.49

10.0 57.1 9.45 68.5 11.34 71.4 11.84 71.4 11.84 80.9 13.41 90.4 14.97 100.0 16.54

15.0 57.1 9.47 68.5 11.38 71.4 11.87 71.4 11.87 80.9 13.45 90.4 15.03 100.0 16.60
120% 20.0 57.1 9.53 68.5 11.45 71.4 11.96 71.4 11.96 80.9 13.56 90.4 15.15 100.0 16.72

25.0 57.1 9.71 68.5 11.66 71.4 12.21 71.4 12.21 80.9 13.82 90.4 15.43 100.0 16.99

30.0 57.1 10.67 68.5 12.59 71.4 13.09 71.4 13.09 80.9 14.67 90.4 16.23 100.0 17.74

35.0 57.1 13.35 68.5 15.70 71.4 16.23 71.4 16.23 80.9 18.16 90.4 20.08 98.2 21.28

40.0 57.1 16.16 68.5 19.03 71.4 19.67 71.4 19.67 79.2 21.28 83.6 21.28 88.1 21.28

43.0 57.1 17.95 68.5 19.76 70.0 21.28 70.0 21.28 74.1 21.28 78.3 21.28 82.6 21.28

46.0 57.1 19.76 65.5 21.28 65.5 21.28 65.5 21.28 69.4 21.28 73.2 21.22 73.2 19.41

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 51.1 8.44 61.3 10.12 69.7 11.51 69.7 11.51 79.0 13.03 88.3 14.55 97.6 16.07

-5.0 51.1 8.44 61.3 10.12 69.7 11.51 69.7 11.51 79.0 13.04 88.3 14.56 97.6 16.07

0.0 51.1 8.44 61.3 10.14 69.7 11.52 69.7 11.52 79.0 13.04 88.3 14.56 97.6 16.08

5.0 51.1 8.45 61.3 10.14 69.7 11.52 69.7 11.52 79.0 13.06 88.3 14.59 97.6 16.11

10.0 51.1 8.47 61.3 10.15 69.7 11.55 69.7 11.55 79.0 13.09 88.3 14.62 97.6 16.14

15.0 51.1 8.48 61.3 10.18 69.7 11.58 69.7 11.58 79.0 13.13 88.3 14.67 97.6 16.20

110% 20.0 51.1 8.53 61.3 10.24 69.7 11.67 69.7 11.67 79.0 13.22 88.3 14.77 97.6 16.32

25.0 51.1 8.69 61.3 10.44 69.7 11.90 69.7 11.90 79.0 13.48 88.3 15.03 97.6 16.58

30.0 51.1 9.59 61.3 11.31 69.7 12.72 69.7 12.72 79.0 14.26 88.3 15.79 97.6 17.31

35.0 51.1 12.02 61.3 14.09 69.7 15.72 69.7 15.72 79.0 17.56 88.3 19.38 97.6 21.19

40.0 51.1 14.53 61.3 17.05 69.7 19.06 69.7 19.06 78.5 21.14 83.2 21.28 87.7 21.28

43.0 51.1 16.13 61.3 18.97 69.7 21.22 69.7 21.22 73.7 21.28 77.9 21.28 82.2 21.28

46.0 51.1 17.81 61.3 19.76 65.2 21.28 65.2 21.28 69.1 21.28 73.0 21.28 73.2 19.55

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 45.4 7.48 54.4 8.98 63.4 10.47 68.0 11.22 77.0 12.71 86.2 14.20 95.2 15.67

-5.0 45.4 7.48 54.4 8.98 63.4 10.49 68.0 11.23 77.0 12.72 86.2 14.20 95.2 15.69

0.0 45.4 7.49 54.4 8.98 63.4 10.49 68.0 11.23 77.0 12.72 86.2 14.21 95.2 15.69

5.0 45.4 7.49 54.4 9.00 63.4 10.50 68.0 11.25 77.0 12.74 86.2 14.23 95.2 15.72

10.0 45.4 7.51 54.4 9.01 63.4 10.52 68.0 11.26 77.0 12.77 86.2 14.26 95.2 15.75

15.0 45.4 7.52 54.4 9.04 63.4 10.55 68.0 11.31 77.0 12.81 86.2 14.30 95.2 15.79

100% 20.0 45.4 7.57 54.4 9.10 63.4 10.62 68.0 11.38 77.0 12.90 86.2 14.41 95.2 15.91

25.0 45.4 7.74 54.4 9.29 63.4 10.82 68.0 11.60 77.0 13.13 86.2 14.65 95.2 16.16

30.0 45.4 8.56 54.4 10.09 63.4 11.60 68.0 12.36 77.0 13.86 86.2 15.35 95.2 16.83

35.0 45.4 10.73 54.4 12.52 63.4 14.30 68.0 15.20 77.0 16.96 86.0 18.65 94.9 20.31

40.0 45.4 12.97 54.4 15.18 63.4 17.37 68.0 18.45 77.0 20.61 82.8 21.28 87.3 21.28

43.0 45.4 14.38 54.4 16.87 63.4 19.32 68.0 20.55 73.4 21.28 77.6 21.28 81.9 21.28

9 46.0 45.4 15.87 54.4 18.65 63.1 21.28 65.0 21.28 68.8 21.28 72.7 21.28 73.2 19.68
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, HIGH EFFICIENCY (Cooling)


24 HP (U-8MF2E8 & U-8MF2E8 & U-8MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 40.8 6.73 49.0 8.09 57.1 9.42 61.2 10.09 69.4 11.45 77.5 12.77 85.7 14.11

-5.0 40.8 6.73 49.0 8.09 57.1 9.44 61.2 10.11 69.4 11.45 77.5 12.78 85.7 14.11

0.0 40.8 6.73 49.0 8.09 57.1 9.44 61.2 10.11 69.4 11.45 77.5 12.78 85.7 14.12

5.0 40.8 6.75 49.0 8.10 57.1 9.44 61.2 10.12 69.4 11.46 77.5 12.80 85.7 14.14

10.0 40.8 6.75 49.0 8.10 57.1 9.45 61.2 10.14 69.4 11.48 77.5 12.83 85.7 14.15

15.0 40.8 6.76 49.0 8.13 57.1 9.48 61.2 10.17 69.4 11.51 77.5 12.86 85.7 14.20

90% 20.0 40.8 6.81 49.0 8.18 57.1 9.55 61.2 10.21 69.4 11.58 77.5 12.94 85.7 14.27

25.0 40.8 6.92 49.0 8.31 57.1 9.68 61.2 10.38 69.4 11.75 77.5 13.12 85.7 14.47

30.0 40.8 7.54 49.0 8.91 57.1 10.26 61.2 10.94 69.4 12.30 77.5 13.63 85.7 14.96

35.0 40.8 9.56 49.0 11.08 57.1 12.56 61.2 13.27 69.4 14.70 77.5 16.08 85.7 17.43

40.0 40.8 11.54 49.0 13.41 57.1 15.25 61.2 16.14 69.4 17.91 77.5 19.64 85.1 21.16

43.0 40.8 12.78 49.0 14.90 57.1 16.96 61.2 17.97 69.4 19.97 76.0 21.28 80.2 21.28

46.0 40.8 14.11 49.0 16.46 57.1 18.79 61.2 19.93 67.5 21.28 71.3 21.28 73.2 20.32

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 36.2 5.99 43.5 7.19 50.8 8.38 54.4 8.98 61.7 10.17 68.9 11.35 76.2 12.54

-5.0 36.2 5.99 43.5 7.19 50.8 8.39 54.4 8.98 61.7 10.17 68.9 11.35 76.2 12.54

0.0 36.2 5.99 43.5 7.19 50.8 8.39 54.4 8.98 61.7 10.18 68.9 11.37 76.2 12.54

5.0 36.2 5.99 43.5 7.19 50.8 8.39 54.4 9.00 61.7 10.18 68.9 11.37 76.2 12.56

10.0 36.2 6.00 43.5 7.20 50.8 8.41 54.4 9.00 61.7 10.20 68.9 11.38 76.2 12.57

15.0 36.2 6.02 43.5 7.22 50.8 8.42 54.4 9.03 61.7 10.23 68.9 11.42 76.2 12.60

80% 20.0 36.2 6.03 43.5 7.25 50.8 8.47 54.4 9.06 61.7 10.28 68.9 11.48 76.2 12.66

25.0 36.2 6.13 43.5 7.34 50.8 8.57 54.4 9.18 61.7 10.40 68.9 11.60 76.2 12.80

30.0 36.2 6.57 43.5 7.77 50.8 8.98 54.4 9.58 61.7 10.78 68.9 11.96 76.2 13.15

35.0 36.2 8.44 43.5 9.68 50.8 10.88 54.4 11.46 61.7 12.60 68.9 13.70 76.2 14.74

40.0 36.2 10.17 43.5 11.73 50.8 13.24 54.4 13.97 61.7 15.40 68.9 16.78 76.2 18.12

43.0 36.2 11.26 43.5 13.03 50.8 14.73 54.4 15.56 61.7 17.18 68.9 18.76 76.2 20.28

46.0 36.2 12.42 43.5 14.39 50.8 16.31 54.4 17.25 61.7 19.08 68.9 20.87 73.2 21.14

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 31.8 5.23 38.1 6.28 44.4 7.33 47.6 7.86 53.9 8.89 60.3 9.93 66.6 10.96

-5.0 31.8 5.24 38.1 6.29 44.4 7.34 47.6 7.86 53.9 8.89 60.3 9.94 66.6 10.97

0.0 31.8 5.24 38.1 6.29 44.4 7.34 47.6 7.86 53.9 8.91 60.3 9.94 66.6 10.97

5.0 31.8 5.24 38.1 6.29 44.4 7.34 47.6 7.87 53.9 8.91 60.3 9.96 66.6 10.99

10.0 31.8 5.24 38.1 6.31 44.4 7.36 47.6 7.87 53.9 8.92 60.3 9.96 66.6 10.99

15.0 31.8 5.26 38.1 6.31 44.4 7.37 47.6 7.89 53.9 8.94 60.3 9.99 66.6 11.02

70% 20.0 31.8 5.27 38.1 6.34 44.4 7.39 47.6 7.92 53.9 8.97 60.3 10.02 66.6 11.07

25.0 31.8 5.34 38.1 6.40 44.4 7.46 47.6 8.00 53.9 9.04 60.3 10.11 66.6 11.16

30.0 31.8 5.64 38.1 6.69 44.4 7.74 47.6 8.27 53.9 9.32 60.3 10.35 66.6 11.42

35.0 31.8 7.37 38.1 8.38 44.4 9.33 47.6 9.79 53.9 10.67 60.3 11.51 66.6 12.37

40.0 31.8 8.86 38.1 10.14 44.4 11.35 47.6 11.95 53.9 13.07 60.3 14.14 66.6 15.15

43.0 31.8 9.82 38.1 11.26 44.4 12.63 47.6 13.30 53.9 14.59 60.3 15.82 66.6 16.99

46.0 31.8 10.81 38.1 12.43 44.4 13.98 47.6 14.74 53.9 16.20 60.3 17.60 66.6 18.95

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 27.2 4.48 32.6 5.38 38.1 6.28 40.8 6.73 46.2 7.63 51.7 8.51 57.1 9.39

-5.0 27.2 4.48 32.6 5.40 38.1 6.29 40.8 6.73 46.2 7.63 51.7 8.51 57.1 9.41

0.0 27.2 4.50 32.6 5.40 38.1 6.29 40.8 6.73 46.2 7.63 51.7 8.53 57.1 9.41

5.0 27.2 4.50 32.6 5.40 38.1 6.29 40.8 6.75 46.2 7.63 51.7 8.53 57.1 9.42

10.0 27.2 4.50 32.6 5.40 38.1 6.29 40.8 6.75 46.2 7.65 51.7 8.54 57.1 9.42

15.0 27.2 4.51 32.6 5.41 38.1 6.31 40.8 6.76 46.2 7.66 51.7 8.56 57.1 9.44

60% 20.0 27.2 4.51 32.6 5.43 38.1 6.32 40.8 6.78 46.2 7.68 51.7 8.59 57.1 9.48

25.0 27.2 4.56 32.6 5.47 38.1 6.37 40.8 6.82 46.2 7.74 51.7 8.65 57.1 9.55

30.0 27.2 4.74 32.6 5.65 38.1 6.55 40.8 7.01 46.2 7.92 51.7 8.85 57.1 9.76

35.0 27.2 6.35 32.6 7.14 38.1 7.89 40.8 8.24 46.2 8.92 51.7 9.71 57.1 10.52

40.0 27.2 7.63 32.6 8.65 38.1 9.61 40.8 10.05 46.2 10.91 51.7 11.72 57.1 12.48

43.0 27.2 8.44 32.6 9.59 38.1 10.69 40.8 11.20 46.2 12.19 51.7 13.12 57.1 14.00

46.0 27.2 9.27 32.6 10.58 38.1 11.81 40.8 12.40 46.2 13.53 51.7 14.61 57.1 15.61

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, HIGH EFFICIENCY (Cooling)


24 HP (U-8MF2E8 & U-8MF2E8 & U-8MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 22.6 3.74 27.2 4.48 31.8 5.24 34.0 5.61 38.6 6.35 43.0 7.10 47.6 7.83

-5.0 22.6 3.74 27.2 4.48 31.8 5.24 34.0 5.61 38.6 6.35 43.0 7.10 47.6 7.84

0.0 22.6 3.74 27.2 4.50 31.8 5.24 34.0 5.61 38.6 6.35 43.0 7.10 47.6 7.84

5.0 22.6 3.74 27.2 4.50 31.8 5.24 34.0 5.62 38.6 6.37 43.0 7.11 47.6 7.84

10.0 22.6 3.75 27.2 4.50 31.8 5.24 34.0 5.62 38.6 6.37 43.0 7.11 47.6 7.86

15.0 22.6 3.75 27.2 4.50 31.8 5.26 34.0 5.64 38.6 6.38 43.0 7.13 47.6 7.87

50% 20.0 22.6 3.77 27.2 4.51 31.8 5.27 34.0 5.65 38.6 6.40 43.0 7.14 47.6 7.90

25.0 22.6 3.78 27.2 4.54 31.8 5.30 34.0 5.68 38.6 6.44 43.0 7.20 47.6 7.95

30.0 22.6 3.91 27.2 4.65 31.8 5.43 34.0 5.82 38.6 6.58 43.0 7.34 47.6 8.10

35.0 22.6 5.41 27.2 6.00 31.8 6.41 34.0 6.70 38.6 7.33 43.0 8.00 47.6 8.68

40.0 22.6 6.46 27.2 7.24 31.8 7.96 34.0 8.30 38.6 8.94 43.0 9.52 47.6 10.05

43.0 22.6 7.11 27.2 8.01 31.8 8.85 34.0 9.24 38.6 9.97 43.0 10.66 47.6 11.28

46.0 22.6 7.80 27.2 8.82 31.8 9.77 34.0 10.21 38.6 11.07 43.0 11.86 47.6 12.59

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 18.2 2.99 21.8 3.59 25.4 4.20 27.2 4.48 30.8 5.09 34.5 5.68 38.1 6.26

-5.0 18.2 2.99 21.8 3.59 25.4 4.20 27.2 4.48 30.8 5.09 34.5 5.68 38.1 6.28

0.0 18.2 2.99 21.8 3.59 25.4 4.20 27.2 4.50 30.8 5.09 34.5 5.68 38.1 6.28

5.0 18.2 2.99 21.8 3.60 25.4 4.20 27.2 4.50 30.8 5.09 34.5 5.68 38.1 6.28

10.0 18.2 2.99 21.8 3.60 25.4 4.20 27.2 4.50 30.8 5.09 34.5 5.70 38.1 6.29

15.0 18.2 3.01 21.8 3.60 25.4 4.21 27.2 4.51 30.8 5.11 34.5 5.70 38.1 6.29

40% 20.0 18.2 3.01 21.8 3.62 25.4 4.21 27.2 4.51 30.8 5.12 34.5 5.72 38.1 6.31

25.0 18.2 3.02 21.8 3.63 25.4 4.24 27.2 4.54 30.8 5.15 34.5 5.76 38.1 6.35

30.0 18.2 3.09 21.8 3.71 25.4 4.33 27.2 4.64 30.8 5.24 34.5 5.85 38.1 6.46

35.0 18.2 4.51 21.8 4.61 25.4 5.00 27.2 5.23 30.8 5.75 34.5 6.29 38.1 6.84

40.0 18.2 5.34 21.8 5.91 25.4 6.44 27.2 6.69 30.8 7.13 34.5 7.52 38.1 7.87

43.0 18.2 5.87 21.8 6.54 25.4 7.14 27.2 7.42 30.8 7.95 34.5 8.41 38.1 8.83

46.0 18.2 6.40 21.8 7.17 25.4 7.86 27.2 8.19 30.8 8.80 34.5 9.35 38.1 9.83

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 13.6 2.25 16.3 2.69 19.0 3.15 20.4 3.37 23.1 3.82 25.8 4.26 28.6 4.70

-5.0 13.6 2.25 16.3 2.69 19.0 3.15 20.4 3.37 23.1 3.82 25.8 4.26 28.6 4.71

0.0 13.6 2.25 16.3 2.69 19.0 3.15 20.4 3.37 23.1 3.82 25.8 4.26 28.6 4.71

5.0 13.6 2.25 16.3 2.71 19.0 3.15 20.4 3.37 23.1 3.82 25.8 4.27 28.6 4.71

10.0 13.6 2.25 16.3 2.71 19.0 3.15 20.4 3.37 23.1 3.83 25.8 4.27 28.6 4.71

15.0 13.6 2.25 16.3 2.71 19.0 3.16 20.4 3.37 23.1 3.83 25.8 4.27 28.6 4.73
30% 20.0 13.6 2.26 16.3 2.71 19.0 3.16 20.4 3.39 23.1 3.85 25.8 4.29 28.6 4.73

25.0 13.6 2.26 16.3 2.72 19.0 3.18 20.4 3.40 23.1 3.86 25.8 4.30 28.6 4.76

30.0 13.6 2.31 16.3 2.77 19.0 3.22 20.4 3.47 23.1 3.92 25.8 4.36 28.6 4.82

35.0 13.6 3.15 16.3 3.28 19.0 3.62 20.4 3.80 23.1 4.21 25.8 4.62 28.6 5.05

40.0 13.6 4.29 16.3 4.68 19.0 5.03 20.4 5.20 23.1 5.49 25.8 7.74 28.6 6.84

43.0 13.6 4.68 16.3 5.14 19.0 5.55 20.4 5.75 23.1 6.08 25.8 6.38 28.6 6.64

46.0 13.6 5.08 16.3 5.61 19.0 6.08 20.4 6.31 23.1 6.70 25.8 7.07 28.6 7.37

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, HIGH EFFICIENCY (Cooling)


26 HP (U-8MF2E8 & U-8MF2E8 & U-10MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 68.0 10.97 78.5 12.68 78.5 12.68 78.5 12.68 88.9 14.37 99.4 16.04 109.9 17.71

-5.0 68.0 10.99 78.5 12.69 78.5 12.69 78.5 12.69 88.9 14.37 99.4 16.06 109.9 17.73

0.0 68.0 10.99 78.5 12.69 78.5 12.69 78.5 12.69 88.9 14.38 99.4 16.07 109.9 17.75

5.0 68.0 11.00 78.5 12.71 78.5 12.71 78.5 12.71 88.9 14.42 99.4 16.09 109.9 17.78

10.0 68.0 11.00 78.5 12.74 78.5 12.74 78.5 12.74 88.9 14.45 99.4 16.14 109.9 17.81

15.0 68.0 11.04 78.5 12.81 78.5 12.81 78.5 12.81 88.9 14.52 99.4 16.22 109.9 17.90

130% 20.0 68.0 11.12 78.5 12.95 78.5 12.95 78.5 12.95 88.9 14.67 99.4 16.41 109.9 18.07

25.0 68.0 11.39 78.5 13.32 78.5 13.32 78.5 13.32 88.9 15.09 99.4 16.83 109.9 18.47

30.0 68.0 12.96 78.5 15.07 78.5 15.07 78.5 15.07 88.9 17.02 99.4 19.00 109.9 21.01

35.0 68.0 16.11 78.5 18.64 78.5 18.64 78.5 18.64 88.9 21.06 99.4 23.49 104.8 23.66

40.0 68.0 19.45 78.5 22.48 78.5 22.48 78.5 22.48 85.3 23.66 89.8 23.66 94.5 23.66

43.0 68.0 21.60 75.8 23.66 75.8 23.66 75.8 23.66 80.0 23.66 84.4 23.66 88.9 23.66

46.0 68.0 21.97 71.1 23.66 71.1 23.66 71.1 23.66 74.8 23.46 74.8 21.50 74.8 19.67

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 61.3 9.90 73.6 11.88 76.7 12.39 76.7 12.39 86.9 14.03 97.1 15.67 107.3 17.31

-5.0 61.3 9.90 73.6 11.88 76.7 12.39 76.7 12.39 86.9 14.04 97.1 15.68 107.3 17.31

0.0 61.3 9.90 73.6 11.90 76.7 12.40 76.7 12.40 86.9 14.04 97.1 15.70 107.3 17.34

5.0 61.3 9.92 73.6 11.90 76.7 12.42 76.7 12.42 86.9 14.08 97.1 15.72 107.3 17.36

10.0 61.3 9.94 73.6 11.93 76.7 12.44 76.7 12.44 86.9 14.11 97.1 15.77 107.3 17.41

15.0 61.3 9.95 73.6 11.97 76.7 12.51 76.7 12.51 86.9 14.18 97.1 15.84 107.3 17.49
120% 20.0 61.3 10.04 73.6 12.07 76.7 12.62 76.7 12.62 86.9 14.31 97.1 16.00 107.3 17.66

25.0 61.3 10.29 73.6 12.35 76.7 12.98 76.7 12.98 86.9 14.70 97.1 16.41 107.3 18.05

30.0 61.3 11.75 73.6 13.89 76.7 14.58 76.7 14.58 86.9 16.44 97.1 18.32 107.3 20.21

35.0 61.3 14.57 73.6 17.27 76.7 18.07 76.7 18.07 86.9 20.36 97.1 22.68 104.2 23.66

40.0 61.3 17.58 73.6 20.85 76.7 21.78 76.7 21.78 84.8 23.66 89.4 23.66 94.1 23.66

43.0 61.3 19.50 73.6 21.97 75.5 23.66 75.5 23.66 79.6 23.66 84.0 23.66 88.5 23.66

46.0 61.3 21.53 70.8 23.66 70.8 23.66 70.8 23.66 74.8 23.61 74.8 21.63 74.8 19.81

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 54.9 8.86 65.8 10.63 74.8 12.08 74.8 12.08 84.8 13.69 94.8 15.29 104.8 16.90

-5.0 54.9 8.86 65.8 10.65 74.8 12.10 74.8 12.10 84.8 13.71 94.8 15.31 104.8 16.90

0.0 54.9 8.87 65.8 10.65 74.8 12.10 74.8 12.10 84.8 13.71 94.8 15.33 104.8 16.92

5.0 54.9 8.87 65.8 10.66 74.8 12.12 74.8 12.12 84.8 13.74 94.8 15.35 104.8 16.95

10.0 54.9 8.89 65.8 10.68 74.8 12.15 74.8 12.15 84.8 13.77 94.8 15.38 104.8 16.98

15.0 54.9 8.92 65.8 10.71 74.8 12.20 74.8 12.20 84.8 13.82 94.8 15.46 104.8 17.07

110% 20.0 54.9 8.99 65.8 10.80 74.8 12.32 74.8 12.32 84.8 13.98 94.8 15.62 104.8 17.24

25.0 54.9 9.23 65.8 11.09 74.8 12.66 74.8 12.66 84.8 14.33 94.8 15.99 104.8 17.63

30.0 54.9 10.58 65.8 12.47 74.8 14.11 74.8 14.11 84.8 15.87 94.8 17.64 104.8 19.45

35.0 54.9 13.10 65.8 15.48 74.8 17.47 74.8 17.47 84.8 19.67 94.8 21.87 103.7 23.66

40.0 54.9 15.78 65.8 18.69 74.8 21.09 74.8 21.09 84.2 23.58 89.0 23.66 93.6 23.66

43.0 54.9 17.51 65.8 20.74 74.8 23.44 74.8 23.44 79.3 23.66 83.6 23.66 88.0 23.66

46.0 54.9 19.32 65.8 21.97 70.5 23.66 70.5 23.66 74.5 23.66 74.8 21.78 74.8 19.96

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 48.7 7.86 58.4 9.43 68.1 11.00 73.0 11.80 82.7 13.37 92.5 14.92 102.2 16.48

-5.0 48.7 7.86 58.4 9.43 68.1 11.02 73.0 11.80 82.7 13.37 92.5 14.92 102.2 16.49

0.0 48.7 7.88 58.4 9.45 68.1 11.02 73.0 11.81 82.7 13.38 92.5 14.94 102.2 16.51

5.0 48.7 7.88 58.4 9.45 68.1 11.04 73.0 11.81 82.7 13.40 92.5 14.97 102.2 16.53

10.0 48.7 7.89 58.4 9.48 68.1 11.05 73.0 11.85 82.7 13.44 92.5 15.01 102.2 16.58

15.0 48.7 7.91 58.4 9.51 68.1 11.10 73.0 11.90 82.7 13.49 92.5 15.07 102.2 16.65

100% 20.0 48.7 7.98 58.4 9.60 68.1 11.20 73.0 12.02 82.7 13.62 92.5 15.21 102.2 16.82

25.0 48.7 8.20 58.4 9.85 68.1 11.49 73.0 12.32 82.7 13.94 92.5 15.56 102.2 17.17

30.0 48.7 9.48 58.4 11.14 68.1 12.79 73.0 13.64 82.7 15.31 92.5 17.00 102.2 18.69

35.0 48.7 11.68 58.4 13.76 68.1 15.85 73.0 16.90 82.7 18.98 92.2 21.02 101.8 23.07

40.0 48.7 14.09 58.4 16.61 68.1 19.15 73.0 20.42 82.7 22.97 88.5 23.66 93.1 23.66

43.0 48.7 15.60 58.4 18.44 68.1 21.26 73.0 22.70 78.9 23.66 83.2 23.66 87.6 23.66

9 46.0 48.7 17.20 58.4 20.36 68.1 23.54 70.2 23.66 74.2 23.66 74.8 21.95 74.8 20.09
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, HIGH EFFICIENCY (Cooling)


26 HP (U-8MF2E8 & U-8MF2E8 & U-10MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 43.8 7.06 52.6 8.48 61.3 9.90 65.7 10.61 74.5 12.02 83.2 13.44 92.0 14.82

-5.0 43.8 7.08 52.6 8.50 61.3 9.90 65.7 10.61 74.5 12.03 83.2 13.44 92.0 14.84

0.0 43.8 7.08 52.6 8.50 61.3 9.92 65.7 10.63 74.5 12.03 83.2 13.45 92.0 14.86

5.0 43.8 7.08 52.6 8.50 61.3 9.92 65.7 10.63 74.5 12.05 83.2 13.47 92.0 14.87

10.0 43.8 7.10 52.6 8.52 61.3 9.94 65.7 10.66 74.5 12.07 83.2 13.49 92.0 14.91

15.0 43.8 7.11 52.6 8.55 61.3 9.97 65.7 10.70 74.5 12.12 83.2 13.54 92.0 14.96

90% 20.0 43.8 7.17 52.6 8.60 61.3 10.06 65.7 10.78 74.5 12.22 83.2 13.66 92.0 15.07

25.0 43.8 7.32 52.6 8.80 61.3 10.28 65.7 11.00 74.5 12.46 83.2 13.91 92.0 15.35

30.0 43.8 8.28 52.6 9.73 61.3 11.17 65.7 11.88 74.5 13.32 83.2 14.74 92.0 16.14

35.0 43.8 10.41 52.6 12.15 61.3 13.87 65.7 14.74 74.5 16.44 83.2 18.13 92.0 19.81

40.0 43.8 12.52 52.6 14.65 61.3 16.78 65.7 17.83 74.5 19.93 83.2 22.00 91.0 23.66

43.0 43.8 13.86 52.6 16.26 61.3 18.62 65.7 19.81 74.5 22.17 81.4 23.66 85.7 23.66

46.0 43.8 15.28 52.6 17.95 61.3 20.62 65.7 21.94 72.7 23.66 74.8 22.70 74.8 20.79

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 38.9 6.29 46.7 7.54 54.5 8.80 58.4 9.43 66.2 10.68 73.9 11.93 81.8 13.18

-5.0 38.9 6.29 46.7 7.55 54.5 8.80 58.4 9.43 66.2 10.70 73.9 11.95 81.8 13.18

0.0 38.9 6.29 46.7 7.55 54.5 8.80 58.4 9.45 66.2 10.70 73.9 11.95 81.8 13.20

5.0 38.9 6.30 46.7 7.55 54.5 8.82 58.4 9.45 66.2 10.71 73.9 11.97 81.8 13.22

10.0 38.9 6.30 46.7 7.57 54.5 8.84 58.4 9.46 66.2 10.73 73.9 11.98 81.8 13.23

15.0 38.9 6.32 46.7 7.59 54.5 8.86 58.4 9.50 66.2 10.75 73.9 12.02 81.8 13.27

80% 20.0 38.9 6.35 46.7 7.64 54.5 8.91 58.4 9.55 66.2 10.82 73.9 12.10 81.8 13.35

25.0 38.9 6.47 46.7 7.77 54.5 9.06 58.4 9.72 66.2 11.00 73.9 12.29 81.8 13.55

30.0 38.9 7.15 46.7 8.43 54.5 9.70 58.4 10.34 66.2 11.61 73.9 12.86 81.8 14.11

35.0 38.9 9.16 46.7 10.60 54.5 12.00 58.4 12.71 66.2 14.06 73.9 15.41 81.8 16.71

40.0 38.9 11.02 46.7 12.79 54.5 14.53 58.4 15.40 66.2 17.10 73.9 18.76 81.8 20.40

43.0 38.9 12.18 46.7 14.20 54.5 16.16 58.4 17.12 66.2 19.03 73.9 20.92 81.8 22.78

46.0 38.9 13.44 46.7 15.67 54.5 17.86 58.4 18.96 66.2 21.11 73.9 23.24 74.8 21.68

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 34.1 5.49 40.9 6.61 47.7 7.71 51.1 8.25 57.9 9.35 64.8 10.44 71.5 11.53

-5.0 34.1 5.51 40.9 6.61 47.7 7.71 51.1 8.25 57.9 9.35 64.8 10.44 71.5 11.54

0.0 34.1 5.51 40.9 6.61 47.7 7.71 51.1 8.26 57.9 9.36 64.8 10.46 71.5 11.54

5.0 34.1 5.51 40.9 6.61 47.7 7.72 51.1 8.26 57.9 9.36 64.8 10.46 71.5 11.56

10.0 34.1 5.51 40.9 6.62 47.7 7.72 51.1 8.28 57.9 9.38 64.8 10.48 71.5 11.58

15.0 34.1 5.53 40.9 6.64 47.7 7.74 51.1 8.30 57.9 9.40 64.8 10.49 71.5 11.59

70% 20.0 34.1 5.56 40.9 6.68 47.7 7.77 51.1 8.33 57.9 9.45 64.8 10.55 71.5 11.66

25.0 34.1 5.63 40.9 6.76 47.7 7.89 51.1 8.45 57.9 9.57 64.8 10.68 71.5 11.78

30.0 34.1 6.10 40.9 7.22 47.7 8.31 51.1 8.87 57.9 9.99 64.8 11.09 71.5 12.17

35.0 34.1 7.98 40.9 9.14 47.7 10.28 51.1 10.82 57.9 11.88 64.8 12.91 71.5 13.91

40.0 34.1 9.58 40.9 11.04 47.7 12.46 51.1 13.15 57.9 14.48 64.8 15.78 71.5 17.04

43.0 34.1 10.60 40.9 12.24 47.7 13.84 51.1 14.62 57.9 16.14 64.8 17.61 71.5 19.05

46.0 34.1 11.66 40.9 13.50 47.7 15.29 51.1 16.17 57.9 17.88 64.8 19.55 71.5 21.19

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 29.2 4.72 35.0 5.66 40.9 6.61 43.8 7.06 49.6 8.01 55.5 8.96 61.3 9.89

-5.0 29.2 4.72 35.0 5.66 40.9 6.61 43.8 7.08 49.6 8.01 55.5 8.96 61.3 9.89

0.0 29.2 4.72 35.0 5.66 40.9 6.61 43.8 7.08 49.6 8.03 55.5 8.96 61.3 9.89

5.0 29.2 4.72 35.0 5.66 40.9 6.61 43.8 7.08 49.6 8.03 55.5 8.96 61.3 9.90

10.0 29.2 4.73 35.0 5.68 40.9 6.62 43.8 7.10 49.6 8.03 55.5 8.97 61.3 9.90

15.0 29.2 4.73 35.0 5.68 40.9 6.62 43.8 7.10 49.6 8.04 55.5 8.99 61.3 9.94

60% 20.0 29.2 4.75 35.0 5.71 40.9 6.66 43.8 7.13 49.6 8.08 55.5 9.02 61.3 9.97

25.0 29.2 4.80 35.0 5.76 40.9 6.73 43.8 7.20 49.6 8.16 55.5 9.11 61.3 10.06

30.0 29.2 5.10 35.0 6.05 40.9 7.00 43.8 7.47 49.6 8.42 55.5 9.36 61.3 10.31

35.0 29.2 6.88 35.0 7.79 40.9 8.67 43.8 9.08 49.6 9.89 55.5 10.66 61.3 11.37

40.0 29.2 8.23 35.0 9.40 40.9 10.51 43.8 11.04 49.6 12.07 55.5 13.05 61.3 13.99

43.0 29.2 9.09 35.0 10.41 40.9 11.66 43.8 12.27 49.6 13.45 55.5 14.57 61.3 15.65

46.0 29.2 9.99 35.0 11.48 40.9 12.89 43.8 13.57 49.6 14.91 55.5 16.19 61.3 17.42

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, HIGH EFFICIENCY (Cooling)


26 HP (U-8MF2E8 & U-8MF2E8 & U-10MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 24.3 3.92 29.2 4.72 34.1 5.49 36.5 5.90 41.4 6.68 46.2 7.45 51.1 8.23

-5.0 24.3 3.92 29.2 4.72 34.1 5.51 36.5 5.90 41.4 6.68 46.2 7.45 51.1 8.25

0.0 24.3 3.94 29.2 4.72 34.1 5.51 36.5 5.90 41.4 6.68 46.2 7.47 51.1 8.25

5.0 24.3 3.94 29.2 4.72 34.1 5.51 36.5 5.90 41.4 6.69 46.2 7.47 51.1 8.25

10.0 24.3 3.94 29.2 4.73 34.1 5.51 36.5 5.92 41.4 6.69 46.2 7.47 51.1 8.26

15.0 24.3 3.94 29.2 4.73 34.1 5.53 36.5 5.92 41.4 6.71 46.2 7.49 51.1 8.28

50% 20.0 24.3 3.95 29.2 4.75 34.1 5.54 36.5 5.93 41.4 6.73 46.2 7.52 51.1 8.30

25.0 24.3 3.99 29.2 4.78 34.1 5.58 36.5 5.98 41.4 6.78 46.2 7.57 51.1 8.37

30.0 24.3 4.16 29.2 4.95 34.1 5.75 36.5 6.13 41.4 6.95 46.2 7.76 51.1 8.55

35.0 24.3 5.83 29.2 6.52 34.1 7.18 36.5 7.49 41.4 8.01 46.2 8.67 51.1 9.35

40.0 24.3 6.95 29.2 7.84 34.1 8.69 36.5 9.09 41.4 9.85 46.2 10.56 51.1 11.24

43.0 24.3 7.66 29.2 8.67 34.1 9.63 36.5 10.11 41.4 10.99 46.2 11.81 51.1 12.57

46.0 24.3 8.40 29.2 9.55 34.1 10.63 36.5 11.15 41.4 12.15 46.2 13.10 51.1 13.99

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 19.5 3.14 23.4 3.77 27.2 4.39 29.2 4.72 33.1 5.34 37.0 5.97 40.9 6.59

-5.0 19.5 3.14 23.4 3.77 27.2 4.39 29.2 4.72 33.1 5.34 37.0 5.97 40.9 6.59

0.0 19.5 3.14 23.4 3.77 27.2 4.41 29.2 4.72 33.1 5.34 37.0 5.97 40.9 6.59

5.0 19.5 3.14 23.4 3.77 27.2 4.41 29.2 4.72 33.1 5.36 37.0 5.98 40.9 6.61

10.0 19.5 3.14 23.4 3.79 27.2 4.41 29.2 4.73 33.1 5.36 37.0 5.98 40.9 6.61

15.0 19.5 3.16 23.4 3.79 27.2 4.41 29.2 4.73 33.1 5.36 37.0 6.00 40.9 6.62

40% 20.0 19.5 3.16 23.4 3.80 27.2 4.43 29.2 4.75 33.1 5.37 37.0 6.02 40.9 6.64

25.0 19.5 3.18 23.4 3.82 27.2 4.46 29.2 4.78 33.1 5.41 37.0 6.05 40.9 6.68

30.0 19.5 3.28 23.4 3.90 27.2 4.56 29.2 4.88 33.1 5.53 37.0 6.17 40.9 6.81

35.0 19.5 4.85 23.4 5.36 27.2 5.56 29.2 5.76 33.1 6.25 37.0 6.78 40.9 7.33

40.0 19.5 5.73 23.4 6.41 27.2 7.01 29.2 7.30 33.1 7.82 37.0 8.31 40.9 8.77

43.0 19.5 6.29 23.4 7.05 27.2 7.76 29.2 8.10 33.1 8.72 37.0 9.30 40.9 9.82

46.0 19.5 6.88 23.4 7.74 27.2 8.53 29.2 8.92 33.1 9.63 37.0 10.29 40.9 10.90

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 14.6 2.35 17.5 2.82 20.4 3.30 21.9 3.53 24.8 4.01 27.7 4.48 30.7 4.93

-5.0 14.6 2.35 17.5 2.82 20.4 3.30 21.9 3.53 24.8 4.01 27.7 4.48 30.7 4.95

0.0 14.6 2.37 17.5 2.84 20.4 3.31 21.9 3.53 24.8 4.01 27.7 4.48 30.7 4.95

5.0 14.6 2.37 17.5 2.84 20.4 3.31 21.9 3.55 24.8 4.01 27.7 4.48 30.7 4.95

10.0 14.6 2.37 17.5 2.84 20.4 3.31 21.9 3.55 24.8 4.02 27.7 4.50 30.7 4.95

15.0 14.6 2.37 17.5 2.84 20.4 3.31 21.9 3.55 24.8 4.02 27.7 4.50 30.7 4.97
30% 20.0 14.6 2.37 17.5 2.84 20.4 3.33 21.9 3.57 24.8 4.04 27.7 4.51 30.7 4.97

25.0 14.6 2.38 17.5 2.86 20.4 3.35 21.9 3.58 24.8 4.06 27.7 4.53 30.7 5.00

30.0 14.6 2.43 17.5 2.91 20.4 3.40 21.9 3.63 24.8 4.12 27.7 4.60 30.7 5.07

35.0 14.6 3.94 17.5 3.73 20.4 3.97 21.9 4.14 24.8 4.53 27.7 4.95 30.7 5.37

40.0 14.6 4.60 17.5 5.05 20.4 5.46 21.9 5.64 24.8 6.00 27.7 6.30 30.7 6.57

43.0 14.6 5.00 17.5 5.53 20.4 6.02 21.9 6.24 24.8 6.64 27.7 7.01 30.7 7.33

46.0 14.6 5.44 17.5 6.03 20.4 6.59 21.9 6.84 24.8 7.32 27.7 7.74 30.7 8.13

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, HIGH EFFICIENCY (Cooling)


28 HP (U-8MF2E8 & U-8MF2E8 & U-12MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 73.2 11.06 84.4 12.78 84.4 12.78 84.4 12.78 95.6 14.48 106.9 16.20 118.1 17.88

-5.0 73.2 11.06 84.4 12.80 84.4 12.80 84.4 12.80 95.6 14.50 106.9 16.22 118.1 17.90

0.0 73.2 11.06 84.4 12.80 84.4 12.80 84.4 12.80 95.6 14.52 106.9 16.24 118.1 17.93

5.0 73.2 11.08 84.4 12.84 84.4 12.84 84.4 12.84 95.6 14.55 106.9 16.27 118.1 17.97

10.0 73.2 11.10 84.4 12.87 84.4 12.87 84.4 12.87 95.6 14.61 106.9 16.35 118.1 18.05

15.0 73.2 11.15 84.4 12.99 84.4 12.99 84.4 12.99 95.6 14.75 106.9 16.48 118.1 18.18

130% 20.0 73.2 11.29 84.4 13.24 84.4 13.24 84.4 13.24 95.6 15.03 106.9 16.83 118.1 18.51

25.0 73.2 11.78 84.4 14.02 84.4 14.02 84.4 14.02 95.6 15.89 106.9 17.84 118.1 20.06

30.0 73.2 14.29 84.4 17.25 84.4 17.25 84.4 17.25 95.6 19.77 106.9 22.39 118.1 25.10

35.0 73.2 17.57 84.4 21.07 84.4 21.07 84.4 21.07 95.6 24.12 105.7 26.74 110.8 26.74

40.0 73.2 21.11 84.4 25.21 84.4 25.21 84.4 25.21 91.6 26.74 96.2 26.74 100.9 26.74

43.0 73.2 23.38 82.2 26.74 82.2 26.74 82.2 26.74 86.4 26.74 90.8 26.74 95.4 26.74

46.0 73.2 24.83 76.3 26.03 76.3 26.03 76.3 26.03 76.3 23.91 76.3 21.93 76.3 20.11

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 65.9 9.97 79.1 11.98 82.4 12.47 82.4 12.47 93.4 14.15 104.4 15.81 115.4 17.48

-5.0 65.9 9.97 79.1 11.98 82.4 12.49 82.4 12.49 93.4 14.15 104.4 15.83 115.4 17.50

0.0 65.9 9.97 79.1 11.98 82.4 12.51 82.4 12.51 93.4 14.17 104.4 15.85 115.4 17.51

5.0 65.9 9.99 79.1 11.99 82.4 12.53 82.4 12.53 93.4 14.21 104.4 15.89 115.4 17.55

10.0 65.9 10.01 79.1 12.03 82.4 12.57 82.4 12.57 93.4 14.27 104.4 15.97 115.4 17.63

15.0 65.9 10.07 79.1 12.09 82.4 12.68 82.4 12.68 93.4 14.38 104.4 16.10 115.4 17.76
120% 20.0 65.9 10.18 79.1 12.26 82.4 12.91 82.4 12.91 93.4 14.67 104.4 16.43 115.4 18.09

25.0 65.9 10.66 79.1 12.85 82.4 13.64 82.4 13.64 93.4 15.47 104.4 17.29 115.4 19.27

30.0 65.9 12.93 79.1 15.55 82.4 16.69 82.4 16.69 93.4 19.10 104.4 21.60 115.4 24.16

35.0 65.9 15.89 79.1 19.12 82.4 20.40 82.4 20.40 93.4 23.32 104.4 26.32 110.1 26.74

40.0 65.9 19.06 79.1 22.94 82.4 24.43 82.4 24.43 91.1 26.74 95.6 26.74 100.3 26.74

43.0 65.9 21.11 79.1 24.83 81.8 26.74 81.8 26.74 86.0 26.74 90.4 26.74 94.8 26.74

46.0 65.9 23.24 76.3 26.22 76.3 26.22 76.3 26.22 76.3 24.10 76.3 22.10 76.3 20.27

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 59.0 8.92 70.8 10.72 80.5 12.19 80.5 12.19 91.2 13.81 101.9 15.43 112.6 17.06

-5.0 59.0 8.92 70.8 10.72 80.5 12.19 80.5 12.19 91.2 13.83 101.9 15.45 112.6 17.08

0.0 59.0 8.94 70.8 10.73 80.5 12.20 80.5 12.20 91.2 13.85 101.9 15.47 112.6 17.09

5.0 59.0 8.94 70.8 10.73 80.5 12.22 80.5 12.22 91.2 13.87 101.9 15.51 112.6 17.13

10.0 59.0 8.96 70.8 10.77 80.5 12.28 80.5 12.28 91.2 13.92 101.9 15.57 112.6 17.21

15.0 59.0 9.02 70.8 10.83 80.5 12.36 80.5 12.36 91.2 14.04 101.9 15.70 112.6 17.34

110% 20.0 59.0 9.13 70.8 10.98 80.5 12.59 80.5 12.59 91.2 14.29 101.9 16.01 112.6 17.67

25.0 59.0 9.57 70.8 11.54 80.5 13.26 80.5 13.26 91.2 15.05 101.9 16.81 112.6 18.47

30.0 59.0 11.65 70.8 13.96 80.5 16.14 80.5 16.14 91.2 18.43 101.9 20.82 112.6 23.26

35.0 59.0 14.31 70.8 17.13 80.5 19.75 80.5 19.75 91.2 22.54 101.9 25.40 109.4 26.74

40.0 59.0 17.13 70.8 20.53 80.5 23.65 80.5 23.65 90.6 26.74 95.1 26.74 99.7 26.74

43.0 59.0 18.93 70.8 22.73 80.5 26.19 80.5 26.19 85.6 26.74 89.9 26.74 94.3 26.74

46.0 59.0 20.84 70.8 24.83 76.3 26.43 76.3 26.43 76.3 24.30 76.3 22.29 76.3 20.44

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 52.4 7.91 62.8 9.51 73.2 11.10 78.5 11.88 88.9 13.47 99.5 15.05 109.9 16.64

-5.0 52.4 7.93 62.8 9.51 73.2 11.10 78.5 11.90 88.9 13.48 99.5 15.07 109.9 16.66

0.0 52.4 7.93 62.8 9.51 73.2 11.12 78.5 11.90 88.9 13.50 99.5 15.09 109.9 16.67

5.0 52.4 7.93 62.8 9.53 73.2 11.14 78.5 11.94 88.9 13.52 99.5 15.13 109.9 16.71

10.0 52.4 7.95 62.8 9.55 73.2 11.17 78.5 11.98 88.9 13.58 99.5 15.18 109.9 16.79

15.0 52.4 8.00 62.8 9.61 73.2 11.23 78.5 12.05 88.9 13.68 99.5 15.32 109.9 16.92

100% 20.0 52.4 8.10 62.8 9.76 73.2 11.42 78.5 12.26 88.9 13.92 99.5 15.59 109.9 17.23

25.0 52.4 8.52 62.8 10.28 73.2 12.01 78.5 12.89 88.9 14.63 99.5 16.35 109.9 18.03

30.0 52.4 10.45 62.8 12.45 73.2 14.54 78.5 15.60 88.9 17.78 99.5 20.06 109.9 22.37

35.0 52.4 12.74 62.8 15.22 73.2 17.78 78.5 19.10 88.9 21.72 99.5 24.37 108.6 26.74

40.0 52.4 15.28 62.8 18.26 73.2 21.32 78.5 22.88 88.9 26.07 94.5 26.74 99.1 26.74

43.0 52.4 16.88 62.8 20.19 73.2 23.59 78.5 25.35 85.1 26.74 89.3 26.74 93.7 26.74

9 46.0 52.4 18.57 62.8 22.23 73.2 26.03 76.3 26.66 76.3 24.51 76.3 22.48 76.3 20.63
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, HIGH EFFICIENCY (Cooling)


28 HP (U-8MF2E8 & U-8MF2E8 & U-12MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 47.1 7.12 56.5 8.56 65.9 9.99 70.7 10.70 80.1 12.13 89.5 13.54 98.9 14.97

-5.0 47.1 7.12 56.5 8.56 65.9 9.99 70.7 10.70 80.1 12.13 89.5 13.56 98.9 14.99

0.0 47.1 7.12 56.5 8.56 65.9 9.99 70.7 10.72 80.1 12.15 89.5 13.58 98.9 15.01

5.0 47.1 7.14 56.5 8.58 65.9 10.01 70.7 10.73 80.1 12.17 89.5 13.60 98.9 15.03

10.0 47.1 7.16 56.5 8.60 65.9 10.05 70.7 10.75 80.1 12.20 89.5 13.64 98.9 15.09

15.0 47.1 7.18 56.5 8.63 65.9 10.08 70.7 10.83 80.1 12.28 89.5 13.73 98.9 15.18

90% 20.0 47.1 7.26 56.5 8.75 65.9 10.24 70.7 10.96 80.1 12.45 89.5 13.94 98.9 15.41

25.0 47.1 7.56 56.5 9.11 65.9 10.68 70.7 11.44 80.1 12.99 89.5 14.50 98.9 16.02

30.0 47.1 9.26 56.5 10.94 65.9 12.66 70.7 13.54 80.1 15.32 89.5 17.15 98.9 19.00

35.0 47.1 11.35 56.5 13.43 65.9 15.55 70.7 16.64 80.1 18.83 89.5 21.07 98.9 23.32

40.0 47.1 13.56 56.5 16.08 65.9 18.66 70.7 19.96 80.1 22.60 89.5 25.29 96.4 26.74

43.0 47.1 14.97 56.5 17.78 65.9 20.65 70.7 22.10 80.1 25.04 87.1 26.74 91.3 26.74

46.0 47.1 16.46 56.5 19.60 65.9 22.77 70.7 24.39 76.3 25.48 76.3 23.40 76.3 21.47

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 41.8 6.32 50.2 7.60 58.6 8.86 62.8 9.51 71.2 10.77 79.5 12.03 87.9 13.31

-5.0 41.8 6.34 50.2 7.60 58.6 8.88 62.8 9.51 71.2 10.77 79.5 12.05 87.9 13.31

0.0 41.8 6.34 50.2 7.60 58.6 8.88 62.8 9.51 71.2 10.79 79.5 12.05 87.9 13.33

5.0 41.8 6.34 50.2 7.62 58.6 8.90 62.8 9.53 71.2 10.81 79.5 12.07 87.9 13.35

10.0 41.8 6.36 50.2 7.64 58.6 8.92 62.8 9.55 71.2 10.83 79.5 12.11 87.9 13.39

15.0 41.8 6.38 50.2 7.66 58.6 8.96 62.8 9.59 71.2 10.89 79.5 12.19 87.9 13.47

80% 20.0 41.8 6.44 50.2 7.74 58.6 9.05 62.8 9.70 71.2 11.02 79.5 12.32 87.9 13.64

25.0 41.8 6.65 50.2 8.00 58.6 9.36 62.8 10.05 71.2 11.38 79.5 12.72 87.9 14.06

30.0 41.8 8.16 50.2 9.53 58.6 10.93 62.8 11.63 71.2 13.06 79.5 14.50 87.9 15.97

35.0 41.8 9.97 50.2 11.71 58.6 13.45 62.8 14.34 71.2 16.10 79.5 17.90 87.9 19.69

40.0 41.8 11.92 50.2 14.04 58.6 16.16 62.8 17.23 71.2 19.37 79.5 21.54 87.9 23.72

43.0 41.8 13.16 50.2 15.51 58.6 17.88 62.8 19.08 71.2 21.49 79.5 23.91 87.9 26.36

46.0 41.8 14.46 50.2 17.08 58.6 19.73 62.8 21.05 71.2 23.74 76.3 24.56 76.3 22.56

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 36.7 5.54 44.0 6.65 51.3 7.75 55.0 8.31 62.3 9.44 69.6 10.54 76.9 11.65

-5.0 36.7 5.54 44.0 6.65 51.3 7.77 55.0 8.33 62.3 9.44 69.6 10.54 76.9 11.65

0.0 36.7 5.54 44.0 6.67 51.3 7.77 55.0 8.33 62.3 9.44 69.6 10.54 76.9 11.65

5.0 36.7 5.56 44.0 6.67 51.3 7.77 55.0 8.33 62.3 9.45 69.6 10.56 76.9 11.67

10.0 36.7 5.56 44.0 6.67 51.3 7.79 55.0 8.35 62.3 9.47 69.6 10.58 76.9 11.71

15.0 36.7 5.58 44.0 6.70 51.3 7.81 55.0 8.38 62.3 9.51 69.6 10.62 76.9 11.75

70% 20.0 36.7 5.62 44.0 6.74 51.3 7.89 55.0 8.46 62.3 9.59 69.6 10.73 76.9 11.86

25.0 36.7 5.77 44.0 6.93 51.3 8.10 55.0 8.69 62.3 9.84 69.6 11.00 76.9 12.15

30.0 36.7 6.93 44.0 8.10 51.3 9.24 55.0 9.82 62.3 10.94 69.6 12.07 76.9 13.20

35.0 36.7 8.69 44.0 10.10 51.3 11.50 55.0 12.20 62.3 13.60 69.6 15.01 76.9 16.41

40.0 36.7 10.37 44.0 12.09 51.3 13.83 55.0 14.69 62.3 16.39 69.6 18.11 76.9 19.81

43.0 36.7 11.44 44.0 13.37 51.3 15.30 55.0 16.25 62.3 18.18 69.6 20.09 76.9 22.02

46.0 36.7 12.55 44.0 14.71 51.3 16.87 55.0 17.93 62.3 20.09 69.6 22.23 76.3 24.03

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 31.4 4.76 37.7 5.69 44.0 6.65 47.1 7.12 53.4 8.08 59.7 9.03 65.9 9.97

-5.0 31.4 4.76 37.7 5.71 44.0 6.65 47.1 7.12 53.4 8.08 59.7 9.03 65.9 9.99

0.0 31.4 4.76 37.7 5.71 44.0 6.67 47.1 7.14 53.4 8.08 59.7 9.03 65.9 9.99

5.0 31.4 4.76 37.7 5.71 44.0 6.67 47.1 7.14 53.4 8.10 59.7 9.05 65.9 10.01

10.0 31.4 4.76 37.7 5.71 44.0 6.67 47.1 7.14 53.4 8.12 59.7 9.05 65.9 10.01

15.0 31.4 4.78 37.7 5.73 44.0 6.69 47.1 7.16 53.4 8.14 59.7 9.09 65.9 10.05

60% 20.0 31.4 4.79 37.7 5.77 44.0 6.74 47.1 7.22 53.4 8.19 59.7 9.15 65.9 10.12

25.0 31.4 4.89 37.7 5.88 44.0 6.88 47.1 7.37 53.4 8.35 59.7 9.34 65.9 10.31

30.0 31.4 5.65 37.7 6.63 44.0 7.60 47.1 8.10 53.4 9.05 59.7 10.03 65.9 10.98

35.0 31.4 7.47 37.7 8.60 44.0 9.68 47.1 10.24 53.4 11.31 59.7 12.38 65.9 13.41

40.0 31.4 8.90 37.7 10.28 44.0 11.63 47.1 12.32 53.4 13.66 59.7 14.96 65.9 16.25

43.0 31.4 9.80 37.7 11.35 44.0 12.87 47.1 13.64 53.4 15.13 59.7 16.62 65.9 18.07

46.0 31.4 10.73 37.7 12.47 44.0 14.19 47.1 15.03 53.4 16.71 59.7 18.37 65.9 20.02

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, HIGH EFFICIENCY (Cooling)


28 HP (U-8MF2E8 & U-8MF2E8 & U-12MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 26.1 3.95 31.4 4.76 36.7 5.54 39.3 5.94 44.5 6.72 49.7 7.53 55.0 8.31

-5.0 26.1 3.95 31.4 4.76 36.7 5.54 39.3 5.94 44.5 6.74 49.7 7.53 55.0 8.31

0.0 26.1 3.95 31.4 4.76 36.7 5.54 39.3 5.94 44.5 6.74 49.7 7.53 55.0 8.33

5.0 26.1 3.95 31.4 4.76 36.7 5.56 39.3 5.96 44.5 6.74 49.7 7.54 55.0 8.33

10.0 26.1 3.97 31.4 4.76 36.7 5.56 39.3 5.96 44.5 6.76 49.7 7.54 55.0 8.35

15.0 26.1 3.97 31.4 4.78 36.7 5.58 39.3 5.98 44.5 6.76 49.7 7.56 55.0 8.37

50% 20.0 26.1 3.99 31.4 4.79 36.7 5.60 39.3 6.00 44.5 6.80 49.7 7.60 55.0 8.40

25.0 26.1 4.05 31.4 4.87 36.7 5.67 39.3 6.09 44.5 6.90 49.7 7.72 55.0 8.52

30.0 26.1 4.49 31.4 5.31 36.7 6.11 39.3 6.51 44.5 7.32 49.7 8.12 55.0 8.92

35.0 26.1 6.32 31.4 7.18 36.7 8.02 39.3 8.42 44.5 9.23 49.7 9.99 55.0 10.73

40.0 26.1 7.51 31.4 8.58 36.7 9.61 39.3 10.12 44.5 11.14 49.7 12.09 55.0 13.05

43.0 26.1 8.23 31.4 9.45 36.7 10.62 39.3 11.21 44.5 12.34 49.7 13.43 55.0 14.50

46.0 26.1 9.02 31.4 10.37 36.7 11.69 39.3 12.34 44.5 13.60 49.7 14.84 55.0 16.06

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 21.0 3.17 25.1 3.80 29.3 4.43 31.4 4.76 35.6 5.39 39.8 6.02 44.0 6.65

-5.0 21.0 3.17 25.1 3.80 29.3 4.43 31.4 4.76 35.6 5.39 39.8 6.02 44.0 6.65

0.0 21.0 3.17 25.1 3.80 29.3 4.43 31.4 4.76 35.6 5.39 39.8 6.02 44.0 6.65

5.0 21.0 3.17 25.1 3.80 29.3 4.43 31.4 4.76 35.6 5.39 39.8 6.04 44.0 6.67

10.0 21.0 3.17 25.1 3.80 29.3 4.45 31.4 4.76 35.6 5.41 39.8 6.04 44.0 6.67

15.0 21.0 3.17 25.1 3.82 29.3 4.45 31.4 4.78 35.6 5.41 39.8 6.04 44.0 6.69

40% 20.0 21.0 3.19 25.1 3.82 29.3 4.47 31.4 4.79 35.6 5.42 39.8 6.07 44.0 6.70

25.0 21.0 3.23 25.1 3.88 29.3 4.51 31.4 4.83 35.6 5.48 39.8 6.11 44.0 6.76

30.0 21.0 3.46 25.1 4.11 29.3 4.74 31.4 5.06 35.6 5.69 39.8 6.34 44.0 6.97

35.0 21.0 5.25 25.1 5.88 29.3 6.47 31.4 6.78 35.6 7.33 39.8 7.85 44.0 8.37

40.0 21.0 6.19 25.1 6.97 29.3 7.74 31.4 8.12 35.6 8.82 39.8 9.51 44.0 10.16

43.0 21.0 6.76 25.1 7.66 29.3 8.54 31.4 8.96 35.6 9.76 39.8 10.54 44.0 11.29

46.0 21.0 7.37 25.1 8.38 29.3 9.36 31.4 9.84 35.6 10.75 39.8 11.63 44.0 12.49

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 15.7 2.37 18.8 2.85 22.0 3.32 23.6 3.57 26.7 4.03 29.8 4.51 33.0 4.99

-5.0 15.7 2.37 18.8 2.85 22.0 3.32 23.6 3.57 26.7 4.05 29.8 4.51 33.0 4.99

0.0 15.7 2.37 18.8 2.85 22.0 3.32 23.6 3.57 26.7 4.05 29.8 4.51 33.0 4.99

5.0 15.7 2.37 18.8 2.85 22.0 3.32 23.6 3.57 26.7 4.05 29.8 4.53 33.0 5.00

10.0 15.7 2.39 18.8 2.87 22.0 3.32 23.6 3.57 26.7 4.05 29.8 4.53 33.0 5.00

15.0 15.7 2.39 18.8 2.87 22.0 3.34 23.6 3.57 26.7 4.05 29.8 4.53 33.0 5.00
30% 20.0 15.7 2.39 18.8 2.87 22.0 3.34 23.6 3.59 26.7 4.07 29.8 4.55 33.0 5.02

25.0 15.7 2.41 18.8 2.88 22.0 3.36 23.6 3.61 26.7 4.09 29.8 4.56 33.0 5.06

30.0 15.7 2.50 18.8 3.00 22.0 3.48 23.6 3.71 26.7 4.18 29.8 4.68 33.0 5.18

35.0 15.7 4.26 18.8 4.68 22.0 5.08 23.6 5.27 26.7 5.39 29.8 5.62 33.0 5.92

40.0 15.7 4.95 18.8 5.50 22.0 6.02 23.6 6.26 26.7 6.72 29.8 7.18 33.0 7.58

43.0 15.7 5.37 18.8 6.00 22.0 6.59 23.6 6.88 26.7 7.43 29.8 7.93 33.0 8.42

46.0 15.7 5.83 18.8 6.53 22.0 7.20 23.6 7.53 26.7 8.14 29.8 8.73 33.0 9.28

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, HIGH EFFICIENCY (Cooling)


30 HP (U-8MF2E8 & U-8MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 79.2 12.25 91.4 14.15 91.4 14.15 91.4 14.15 103.5 16.05 115.8 17.93 127.9 19.81

-5.0 79.2 12.25 91.4 14.17 91.4 14.17 91.4 14.17 103.5 16.07 115.8 17.95 127.9 19.83

0.0 79.2 12.27 91.4 14.19 91.4 14.19 91.4 14.19 103.5 16.09 115.8 17.97 127.9 19.85

5.0 79.2 12.27 91.4 14.23 91.4 14.23 91.4 14.23 103.5 16.14 115.8 18.01 127.9 19.89

10.0 79.2 12.31 91.4 14.30 91.4 14.30 91.4 14.30 103.5 16.22 115.8 18.10 127.9 19.98

15.0 79.2 12.38 91.4 14.43 91.4 14.43 91.4 14.43 103.5 16.37 115.8 18.27 127.9 20.15

130% 20.0 79.2 12.55 91.4 14.73 91.4 14.73 91.4 14.73 103.5 16.74 115.8 18.64 127.9 20.50

25.0 79.2 13.18 91.4 15.68 91.4 15.68 91.4 15.68 103.5 18.04 115.8 20.58 127.9 23.24

30.0 79.2 16.07 91.4 19.63 91.4 19.63 91.4 19.63 103.5 22.59 115.8 25.70 126.1 28.08

35.0 79.2 19.74 91.4 23.91 91.4 23.91 91.4 23.91 103.5 27.48 109.7 28.08 114.9 28.08

40.0 79.2 23.70 90.4 28.08 90.4 28.08 90.4 28.08 94.9 28.08 99.7 28.08 104.6 28.08

43.0 79.2 26.22 85.2 28.08 85.2 28.08 85.2 28.08 89.6 28.08 93.5 27.71 93.5 25.38

46.0 73.8 24.49 73.8 24.49 73.8 24.49 73.8 24.49 73.8 22.49 73.8 20.63 73.8 18.90

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 71.4 11.04 85.7 13.26 89.3 13.82 89.3 13.82 101.2 15.66 113.1 17.52 125.0 19.33

-5.0 71.4 11.04 85.7 13.26 89.3 13.85 89.3 13.85 101.2 15.68 113.1 17.54 125.0 19.35

0.0 71.4 11.06 85.7 13.28 89.3 13.87 89.3 13.87 101.2 15.70 113.1 17.56 125.0 19.40

5.0 71.4 11.08 85.7 13.31 89.3 13.89 89.3 13.89 101.2 15.75 113.1 17.60 125.0 19.44

10.0 71.4 11.10 85.7 13.35 89.3 13.95 89.3 13.95 101.2 15.83 113.1 17.69 125.0 19.53

15.0 71.4 11.17 85.7 13.41 89.3 14.08 89.3 14.08 101.2 15.98 113.1 17.84 125.0 19.68

120% 20.0 71.4 11.32 85.7 13.63 89.3 14.36 89.3 14.36 101.2 16.33 113.1 18.21 125.0 20.02

25.0 71.4 11.90 85.7 14.36 89.3 15.25 89.3 15.25 101.2 17.37 113.1 19.79 125.0 22.31

30.0 71.4 14.52 85.7 17.56 89.3 18.96 89.3 18.96 101.2 21.79 113.1 24.73 125.0 27.80

35.0 71.4 17.82 85.7 21.54 89.3 23.11 89.3 23.11 101.2 26.52 109.1 28.08 114.2 28.08

40.0 71.4 21.36 85.7 25.81 89.3 27.65 89.3 27.65 94.5 28.08 99.2 28.08 104.0 28.08

43.0 71.4 23.63 84.8 28.08 84.8 28.08 84.8 28.08 89.3 28.08 93.5 27.95 93.5 25.60

46.0 71.4 26.05 73.8 24.67 73.8 24.67 73.8 24.67 73.8 22.64 73.8 20.78 73.8 19.03

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 63.9 9.87 76.7 11.86 87.1 13.50 87.1 13.50 98.8 15.29 110.3 17.09 122.0 18.88

-5.0 63.9 9.89 76.7 11.88 87.1 13.50 87.1 13.50 98.8 15.31 110.3 17.11 122.0 18.90

0.0 63.9 9.89 76.7 11.88 87.1 13.52 87.1 13.52 98.8 15.34 110.3 17.15 122.0 18.92

5.0 63.9 9.91 76.7 11.90 87.1 13.56 87.1 13.56 98.8 15.38 110.3 17.19 122.0 18.99

10.0 63.9 9.94 76.7 11.94 87.1 13.61 87.1 13.61 98.8 15.44 110.3 17.26 122.0 19.05

15.0 63.9 10.00 76.7 12.03 87.1 13.74 87.1 13.74 98.8 15.60 110.3 17.43 122.0 19.22

110% 20.0 63.9 10.15 76.7 12.23 87.1 14.00 87.1 14.00 98.8 15.90 110.3 17.78 122.0 19.55

25.0 63.9 10.69 76.7 12.90 87.1 14.84 87.1 14.84 98.8 16.80 110.3 19.01 122.0 21.38

30.0 63.9 13.05 76.7 15.72 87.1 18.32 87.1 18.32 98.8 21.02 110.3 23.80 122.0 26.72

35.0 63.9 16.01 76.7 19.27 87.1 22.33 87.1 22.33 98.8 25.60 108.5 28.08 113.6 28.08

40.0 63.9 19.16 76.7 23.07 87.1 26.72 87.1 26.72 94.0 28.08 98.7 28.08 103.5 28.08

43.0 63.9 21.17 76.7 25.53 84.4 28.08 84.4 28.08 88.7 28.08 93.2 28.08 93.5 25.81

46.0 63.9 23.33 73.8 24.84 73.8 24.84 73.8 24.84 73.8 22.81 73.8 20.91 73.8 19.18

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 56.7 8.77 68.0 10.52 79.3 12.29 85.0 13.15 96.3 14.93 107.7 16.68 119.0 18.42

-5.0 56.7 8.77 68.0 10.54 79.3 12.29 85.0 13.18 96.3 14.93 107.7 16.70 119.0 18.45

0.0 56.7 8.77 68.0 10.54 79.3 12.31 85.0 13.20 96.3 14.97 107.7 16.72 119.0 18.47

5.0 56.7 8.79 68.0 10.56 79.3 12.33 85.0 13.22 96.3 14.99 107.7 16.76 119.0 18.51

10.0 56.7 8.81 68.0 10.61 79.3 12.38 85.0 13.28 96.3 15.06 107.7 16.85 119.0 18.60

15.0 56.7 8.88 68.0 10.67 79.3 12.48 85.0 13.39 96.3 15.18 107.7 17.00 119.0 18.75

100% 20.0 56.7 9.01 68.0 10.86 79.3 12.72 85.0 13.63 96.3 15.49 107.7 17.34 119.0 19.09

25.0 56.7 9.53 68.0 11.49 79.3 13.44 85.0 14.41 96.3 16.33 107.7 18.25 119.0 20.50

30.0 56.7 11.66 68.0 14.00 79.3 16.42 85.0 17.67 96.3 20.24 107.7 22.90 119.0 25.66

35.0 56.7 14.23 68.0 17.11 79.3 20.07 85.0 21.60 96.1 24.58 107.2 27.71 113.0 28.08

40.0 56.7 17.06 68.0 20.48 79.3 24.02 85.0 25.83 93.5 28.08 98.2 28.08 102.9 28.08

43.0 56.7 18.84 68.0 22.64 79.3 26.59 84.0 28.08 88.3 28.08 92.8 28.08 93.5 26.07

9 46.0 56.7 20.74 68.0 24.95 73.8 26.09 73.8 25.01 73.8 22.96 73.8 21.06 73.8 19.31
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, HIGH EFFICIENCY (Cooling)


30 HP (U-8MF2E8 & U-8MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 51.0 7.88 61.2 9.48 71.4 11.06 76.5 11.84 86.7 13.44 96.9 15.01 107.1 16.59

-5.0 51.0 7.88 61.2 9.48 71.4 11.06 76.5 11.86 86.7 13.44 96.9 15.01 107.1 16.59

0.0 51.0 7.91 61.2 9.48 71.4 11.08 76.5 11.86 86.7 13.46 96.9 15.03 107.1 16.61

5.0 51.0 7.91 61.2 9.50 71.4 11.10 76.5 11.88 86.7 13.48 96.9 15.08 107.1 16.65

10.0 51.0 7.93 61.2 9.53 71.4 11.12 76.5 11.92 86.7 13.52 96.9 15.12 107.1 16.72

15.0 51.0 7.97 61.2 9.59 71.4 11.19 76.5 12.01 86.7 13.63 96.9 15.25 107.1 16.87

90% 20.0 51.0 8.08 61.2 9.72 71.4 11.38 76.5 12.20 86.7 13.85 96.9 15.51 107.1 17.15

25.0 51.0 8.45 61.2 10.20 71.4 11.90 76.5 12.77 86.7 14.47 96.9 16.18 107.1 17.86

30.0 51.0 10.30 61.2 12.23 71.4 14.21 76.5 15.25 86.7 17.32 96.9 19.46 107.1 21.64

35.0 51.0 12.61 61.2 14.99 71.4 17.45 76.5 18.68 86.7 21.23 96.9 23.82 107.1 26.48

40.0 51.0 15.08 61.2 17.95 71.4 20.91 76.5 22.40 86.7 25.47 95.9 28.08 100.4 28.08

43.0 51.0 16.65 61.2 19.87 71.4 23.16 76.5 24.82 86.4 28.08 90.7 28.08 93.5 27.22

46.0 51.0 18.32 61.2 21.88 71.4 25.55 73.8 25.83 73.8 23.74 73.8 21.79 73.8 19.98

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 45.3 7.02 54.4 8.42 63.5 9.83 68.0 10.52 77.1 11.92 86.1 13.33 95.2 14.73

-5.0 45.3 7.02 54.4 8.42 63.5 9.83 68.0 10.54 77.1 11.94 86.1 13.35 95.2 14.75

0.0 45.3 7.02 54.4 8.42 63.5 9.85 68.0 10.54 77.1 11.94 86.1 13.35 95.2 14.75

5.0 45.3 7.02 54.4 8.45 63.5 9.85 68.0 10.56 77.1 11.97 86.1 13.39 95.2 14.80

10.0 45.3 7.04 54.4 8.47 63.5 9.87 68.0 10.58 77.1 12.01 86.1 13.44 95.2 14.84

15.0 45.3 7.06 54.4 8.49 63.5 9.94 68.0 10.65 77.1 12.07 86.1 13.50 95.2 14.93

80% 20.0 45.3 7.15 54.4 8.60 63.5 10.04 68.0 10.78 77.1 12.25 86.1 13.69 95.2 15.14

25.0 45.3 7.41 54.4 8.92 63.5 10.43 68.0 11.19 77.1 12.68 86.1 14.17 95.2 15.64

30.0 45.3 9.01 54.4 10.58 63.5 12.20 68.0 13.00 77.1 14.67 86.1 16.33 95.2 18.04

35.0 45.3 11.04 54.4 13.00 63.5 15.01 68.0 16.03 77.1 18.06 86.1 20.11 95.2 22.20

40.0 45.3 13.20 54.4 15.60 63.5 18.01 68.0 19.22 77.1 21.71 86.1 24.19 95.2 26.74

43.0 45.3 14.58 54.4 17.24 63.5 19.94 68.0 21.32 77.1 24.06 86.1 26.87 92.4 28.08

46.0 45.3 16.03 54.4 19.01 63.5 22.01 68.0 23.54 73.8 24.73 73.8 22.70 73.8 20.82

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 39.7 6.13 47.6 7.37 55.5 8.60 59.5 9.20 67.4 10.43 75.4 11.66 83.3 12.90

-5.0 39.7 6.13 47.6 7.37 55.5 8.60 59.5 9.22 67.4 10.45 75.4 11.66 83.3 12.90

0.0 39.7 6.13 47.6 7.37 55.5 8.60 59.5 9.22 67.4 10.45 75.4 11.69 83.3 12.92

5.0 39.7 6.16 47.6 7.39 55.5 8.62 59.5 9.24 67.4 10.48 75.4 11.71 83.3 12.94

10.0 39.7 6.16 47.6 7.39 55.5 8.64 59.5 9.24 67.4 10.50 75.4 11.73 83.3 12.96

15.0 39.7 6.18 47.6 7.43 55.5 8.66 59.5 9.29 67.4 10.54 75.4 11.79 83.3 13.02

70% 20.0 39.7 6.22 47.6 7.50 55.5 8.75 59.5 9.40 67.4 10.65 75.4 11.90 83.3 13.18

25.0 39.7 6.42 47.6 7.71 55.5 9.01 59.5 9.66 67.4 10.95 75.4 12.25 83.3 13.52

30.0 39.7 7.75 47.6 9.07 55.5 10.35 59.5 10.97 67.4 12.25 75.4 13.52 83.3 14.82

35.0 39.7 9.57 47.6 11.15 55.5 12.74 59.5 13.54 67.4 15.14 75.4 16.74 83.3 18.34

40.0 39.7 11.43 47.6 13.37 55.5 15.31 59.5 16.29 67.4 18.25 75.4 20.20 83.3 22.16

43.0 39.7 12.61 47.6 14.80 55.5 16.98 59.5 18.06 67.4 20.24 75.4 22.44 83.3 24.62

46.0 39.7 13.85 47.6 16.29 55.5 18.73 59.5 19.94 67.4 22.38 73.8 23.95 73.8 21.99

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 34.0 5.25 40.8 6.31 47.6 7.37 51.0 7.88 57.8 8.94 64.6 10.00 71.4 11.04

-5.0 34.0 5.27 40.8 6.31 47.6 7.37 51.0 7.91 57.8 8.94 64.6 10.00 71.4 11.06

0.0 34.0 5.27 40.8 6.33 47.6 7.37 51.0 7.91 57.8 8.96 64.6 10.00 71.4 11.06

5.0 34.0 5.27 40.8 6.33 47.6 7.39 51.0 7.91 57.8 8.96 64.6 10.02 71.4 11.08

10.0 34.0 5.27 40.8 6.33 47.6 7.39 51.0 7.93 57.8 8.99 64.6 10.04 71.4 11.10

15.0 34.0 5.29 40.8 6.35 47.6 7.41 51.0 7.95 57.8 9.01 64.6 10.09 71.4 11.15

60% 20.0 34.0 5.31 40.8 6.39 47.6 7.47 51.0 8.01 57.8 9.09 64.6 10.15 71.4 11.23

25.0 34.0 5.44 40.8 6.54 47.6 7.65 51.0 8.19 57.8 9.29 64.6 10.37 71.4 11.45

30.0 34.0 6.31 40.8 7.39 47.6 8.47 51.0 9.01 57.8 10.07 64.6 11.15 71.4 12.20

35.0 34.0 8.16 40.8 9.44 47.6 10.67 51.0 11.28 57.8 12.51 64.6 13.69 71.4 14.88

40.0 34.0 9.74 40.8 11.30 47.6 12.83 51.0 13.59 57.8 15.08 64.6 16.57 71.4 18.04

43.0 34.0 10.76 40.8 12.48 47.6 14.21 51.0 15.06 57.8 16.74 64.6 18.40 71.4 20.07

46.0 34.0 11.79 40.8 13.74 47.6 15.66 51.0 16.61 57.8 18.51 64.6 20.37 71.4 22.25

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, HIGH EFFICIENCY (Cooling)


30 HP (U-8MF2E8 & U-8MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 28.3 4.38 34.0 5.27 39.7 6.13 42.5 6.59 48.2 7.45 53.8 8.34 59.5 9.20

-5.0 28.3 4.38 34.0 5.27 39.7 6.13 42.5 6.59 48.2 7.45 53.8 8.34 59.5 9.20

0.0 28.3 4.38 34.0 5.27 39.7 6.13 42.5 6.59 48.2 7.45 53.8 8.34 59.5 9.22

5.0 28.3 4.38 34.0 5.27 39.7 6.16 42.5 6.59 48.2 7.47 53.8 8.34 59.5 9.22

10.0 28.3 4.38 34.0 5.27 39.7 6.16 42.5 6.61 48.2 7.47 53.8 8.36 59.5 9.24

15.0 28.3 4.41 34.0 5.29 39.7 6.18 42.5 6.61 48.2 7.50 53.8 8.38 59.5 9.27

50% 20.0 28.3 4.43 34.0 5.31 39.7 6.20 42.5 6.65 48.2 7.54 53.8 8.42 59.5 9.31

25.0 28.3 4.49 34.0 5.40 39.7 6.31 42.5 6.76 48.2 7.65 53.8 8.55 59.5 9.44

30.0 28.3 5.01 34.0 5.90 39.7 6.80 42.5 7.24 48.2 8.12 53.8 9.01 59.5 9.89

35.0 28.3 6.89 34.0 7.84 39.7 8.77 42.5 9.22 48.2 10.11 53.8 10.97 59.5 11.79

40.0 28.3 8.16 34.0 9.37 39.7 10.52 42.5 11.10 48.2 12.20 53.8 13.28 59.5 14.34

43.0 28.3 8.99 34.0 10.35 39.7 11.64 42.5 12.29 48.2 13.54 53.8 14.77 59.5 15.96

46.0 28.3 9.85 34.0 11.36 39.7 12.83 42.5 13.54 48.2 14.95 53.8 16.33 59.5 17.69

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 22.7 3.50 27.2 4.21 31.7 4.90 34.0 5.27 38.5 5.96 43.1 6.65 47.6 7.37

-5.0 22.7 3.50 27.2 4.21 31.7 4.90 34.0 5.27 38.5 5.96 43.1 6.67 47.6 7.37

0.0 22.7 3.50 27.2 4.21 31.7 4.92 34.0 5.27 38.5 5.96 43.1 6.67 47.6 7.37

5.0 22.7 3.52 27.2 4.21 31.7 4.92 34.0 5.27 38.5 5.98 43.1 6.67 47.6 7.37

10.0 22.7 3.52 27.2 4.21 31.7 4.92 34.0 5.27 38.5 5.98 43.1 6.67 47.6 7.39

15.0 22.7 3.52 27.2 4.23 31.7 4.92 34.0 5.29 38.5 5.98 43.1 6.70 47.6 7.39

40% 20.0 22.7 3.54 27.2 4.23 31.7 4.95 34.0 5.31 38.5 6.00 43.1 6.72 47.6 7.43

25.0 22.7 3.56 27.2 4.30 31.7 5.01 34.0 5.36 38.5 6.07 43.1 6.78 47.6 7.50

30.0 22.7 3.84 27.2 4.56 31.7 5.27 34.0 5.62 38.5 6.33 43.1 7.02 47.6 7.73

35.0 22.7 5.68 27.2 6.37 31.7 7.02 34.0 7.34 38.5 7.95 43.1 8.53 47.6 9.09

40.0 22.7 6.70 27.2 7.58 31.7 8.40 34.0 8.81 38.5 9.61 43.1 10.35 47.6 11.06

43.0 22.7 7.34 27.2 8.34 31.7 9.29 34.0 9.74 38.5 10.65 43.1 11.49 47.6 12.31

46.0 22.7 8.01 27.2 9.14 31.7 10.20 34.0 10.71 38.5 11.73 43.1 12.70 47.6 13.63

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 17.0 2.64 20.4 3.15 23.8 3.67 25.5 3.95 28.9 4.47 32.3 4.99 35.7 5.53

-5.0 17.0 2.64 20.4 3.15 23.8 3.69 25.5 3.95 28.9 4.47 32.3 4.99 35.7 5.53

0.0 17.0 2.64 20.4 3.15 23.8 3.69 25.5 3.95 28.9 4.47 32.3 5.01 35.7 5.53

5.0 17.0 2.64 20.4 3.15 23.8 3.69 25.5 3.95 28.9 4.47 32.3 5.01 35.7 5.53

10.0 17.0 2.64 20.4 3.15 23.8 3.69 25.5 3.95 28.9 4.49 32.3 5.01 35.7 5.53

15.0 17.0 2.64 20.4 3.18 23.8 3.69 25.5 3.95 28.9 4.49 32.3 5.01 35.7 5.55
30% 20.0 17.0 2.66 20.4 3.18 23.8 3.72 25.5 3.97 28.9 4.49 32.3 5.03 35.7 5.57

25.0 17.0 2.66 20.4 3.20 23.8 3.74 25.5 4.00 28.9 4.54 32.3 5.08 35.7 5.59

30.0 17.0 2.79 20.4 3.33 23.8 3.84 25.5 4.10 28.9 4.64 32.3 5.21 35.7 5.72

35.0 17.0 4.56 20.4 5.01 23.8 5.46 25.5 5.66 28.9 5.77 32.3 6.09 35.7 6.50

40.0 17.0 5.31 20.4 5.92 23.8 6.48 25.5 6.74 28.9 7.26 32.3 7.73 35.7 8.19

43.0 17.0 5.79 20.4 6.48 23.8 7.11 25.5 7.43 28.9 8.01 32.3 8.58 35.7 9.09

46.0 17.0 6.29 20.4 7.06 23.8 7.78 25.5 8.14 28.9 8.81 32.3 9.44 35.7 10.02

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, HIGH EFFICIENCY (Cooling)


32 HP (U-8MF2E8 & U-12MF2E8 & U-12MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 83.9 11.88 96.8 13.75 96.8 13.75 96.8 13.75 109.6 15.59 122.6 17.43 135.5 19.27

-5.0 83.9 11.88 96.8 13.77 96.8 13.77 96.8 13.77 109.6 15.61 122.6 17.45 135.5 19.29

0.0 83.9 11.91 96.8 13.79 96.8 13.79 96.8 13.79 109.6 15.66 122.6 17.50 135.5 19.34

5.0 83.9 11.93 96.8 13.84 96.8 13.84 96.8 13.84 109.6 15.70 122.6 17.57 135.5 19.41

10.0 83.9 11.95 96.8 13.93 96.8 13.93 96.8 13.93 109.6 15.82 122.6 17.71 135.5 19.55

15.0 83.9 12.05 96.8 14.14 96.8 14.14 96.8 14.14 109.6 16.08 122.6 18.01 135.5 19.85

130% 20.0 83.9 12.30 96.8 14.68 96.8 14.68 96.8 14.68 109.6 16.75 122.6 18.76 135.5 20.60

25.0 83.9 13.47 96.8 17.15 96.8 17.15 96.8 17.15 109.6 20.06 122.6 23.16 135.5 26.47

30.0 83.9 16.94 96.8 21.30 96.8 21.30 96.8 21.30 109.6 24.79 122.6 28.52 135.5 32.43

35.0 83.9 20.67 96.8 25.72 96.8 25.72 96.8 25.72 109.6 29.89 119.5 32.62 124.7 32.62

40.0 83.9 24.65 96.8 30.55 96.8 30.55 96.8 30.55 104.9 32.62 109.7 32.62 114.7 32.62

43.0 83.9 27.21 95.0 32.62 95.0 32.62 95.0 32.62 99.5 32.62 103.4 32.15 103.4 29.50

46.0 81.6 27.61 81.6 27.61 81.6 27.61 81.6 27.61 81.6 25.40 81.6 23.32 81.6 21.41

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 75.6 10.72 90.7 12.86 94.5 13.42 94.5 13.42 107.1 15.21 119.7 17.03 132.3 18.83

-5.0 75.6 10.72 90.7 12.88 94.5 13.44 94.5 13.44 107.1 15.24 119.7 17.06 132.3 18.85

0.0 75.6 10.74 90.7 12.88 94.5 13.47 94.5 13.47 107.1 15.28 119.7 17.10 132.3 18.90

5.0 75.6 10.74 90.7 12.91 94.5 13.51 94.5 13.51 107.1 15.33 119.7 17.17 132.3 18.97

10.0 75.6 10.79 90.7 12.98 94.5 13.58 94.5 13.58 107.1 15.45 119.7 17.31 132.3 19.11

15.0 75.6 10.86 90.7 13.09 94.5 13.79 94.5 13.79 107.1 15.68 119.7 17.59 132.3 19.41
120% 20.0 75.6 11.11 90.7 13.44 94.5 14.31 94.5 14.31 107.1 16.31 119.7 18.34 132.3 20.13

25.0 75.6 12.21 90.7 14.96 94.5 16.59 94.5 16.59 107.1 19.34 119.7 22.30 132.3 25.44

30.0 75.6 15.33 90.7 18.76 94.5 20.60 94.5 20.60 107.1 23.95 119.7 27.49 132.3 31.25

35.0 75.6 18.66 90.7 22.81 94.5 24.91 94.5 24.91 107.1 28.89 118.7 32.62 123.9 32.62

40.0 75.6 22.27 90.7 27.19 94.5 29.59 94.5 29.59 104.2 32.62 109.0 32.62 113.9 32.62

43.0 75.6 24.56 90.7 30.01 94.1 32.46 94.1 32.46 98.9 32.62 103.4 32.53 103.4 29.85

46.0 75.6 26.98 81.6 27.84 81.6 27.84 81.6 27.84 81.6 25.63 81.6 23.53 81.6 21.60

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 67.7 9.60 81.2 11.51 92.3 13.09 92.3 13.09 104.6 14.87 116.8 16.61 129.2 18.38

-5.0 67.7 9.60 81.2 11.53 92.3 13.12 92.3 13.12 104.6 14.89 116.8 16.64 129.2 18.41

0.0 67.7 9.60 81.2 11.53 92.3 13.14 92.3 13.14 104.6 14.91 116.8 16.68 129.2 18.43

5.0 67.7 9.62 81.2 11.56 92.3 13.19 92.3 13.19 104.6 14.96 116.8 16.75 129.2 18.52

10.0 67.7 9.65 81.2 11.60 92.3 13.26 92.3 13.26 104.6 15.08 116.8 16.87 129.2 18.66

15.0 67.7 9.74 81.2 11.72 92.3 13.44 92.3 13.44 104.6 15.28 116.8 17.15 129.2 18.94

110% 20.0 67.7 9.95 81.2 12.05 92.3 13.93 92.3 13.93 104.6 15.89 116.8 17.85 129.2 19.64

25.0 67.7 10.97 81.2 13.42 92.3 16.01 92.3 16.01 104.6 18.64 116.8 21.46 129.2 24.44

30.0 67.7 13.79 81.2 16.82 92.3 19.92 92.3 19.92 104.6 23.11 116.8 26.49 129.2 30.08

35.0 67.7 16.78 81.2 20.43 92.3 24.09 92.3 24.09 104.6 27.91 116.8 31.92 123.0 32.62

40.0 67.7 19.99 81.2 24.33 92.3 28.64 92.3 28.64 103.5 32.62 108.3 32.62 113.1 32.62

43.0 67.7 22.04 81.2 26.84 92.3 31.57 92.3 31.57 98.3 32.62 102.9 32.62 103.4 30.22

46.0 67.7 24.19 81.2 29.50 81.6 28.10 81.6 28.10 81.6 25.86 81.6 23.77 81.6 21.81

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 60.0 8.50 72.0 10.23 84.0 11.93 90.0 12.79 102.0 14.49 114.0 16.22 126.0 17.92

-5.0 60.0 8.50 72.0 10.23 84.0 11.93 90.0 12.79 102.0 14.52 114.0 16.24 126.0 17.94

0.0 60.0 8.53 72.0 10.23 84.0 11.95 90.0 12.82 102.0 14.54 114.0 16.26 126.0 17.99

5.0 60.0 8.55 72.0 10.25 84.0 12.00 90.0 12.86 102.0 14.59 114.0 16.33 126.0 18.06

10.0 60.0 8.57 72.0 10.30 84.0 12.05 90.0 12.93 102.0 14.70 114.0 16.45 126.0 18.20

15.0 60.0 8.64 72.0 10.42 84.0 12.21 90.0 13.09 102.0 14.91 114.0 16.71 126.0 18.48

100% 20.0 60.0 8.85 72.0 10.72 84.0 12.61 90.0 13.54 102.0 15.45 114.0 17.36 126.0 19.18

25.0 60.0 9.81 72.0 11.98 84.0 14.26 90.0 15.45 102.0 17.96 114.0 20.64 126.0 23.49

30.0 60.0 12.35 72.0 14.98 84.0 17.78 90.0 19.25 102.0 22.30 114.0 25.54 126.0 28.92

35.0 60.0 14.94 72.0 18.15 84.0 21.53 90.0 23.30 102.0 26.84 113.5 30.59 122.1 32.62

40.0 60.0 17.80 72.0 21.60 84.0 25.61 90.0 27.70 102.0 32.01 107.6 32.62 112.3 32.62

43.0 60.0 19.62 72.0 23.81 84.0 28.24 90.0 30.55 97.7 32.62 102.2 32.62 103.4 30.59

9 46.0 60.0 21.53 72.0 26.17 81.6 29.57 81.6 28.38 81.6 26.12 81.6 24.00 81.6 22.02
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, HIGH EFFICIENCY (Cooling)


32 HP (U-8MF2E8 & U-12MF2E8 & U-12MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 54.0 7.67 64.8 9.20 75.6 10.74 81.0 11.51 91.8 13.05 102.6 14.59 113.4 16.12

-5.0 54.0 7.67 64.8 9.20 75.6 10.74 81.0 11.51 91.8 13.05 102.6 14.61 113.4 16.15

0.0 54.0 7.67 64.8 9.20 75.6 10.76 81.0 11.53 91.8 13.07 102.6 14.63 113.4 16.19

5.0 54.0 7.69 64.8 9.23 75.6 10.79 81.0 11.56 91.8 13.12 102.6 14.68 113.4 16.24

10.0 54.0 7.71 64.8 9.27 75.6 10.83 81.0 11.60 91.8 13.19 102.6 14.77 113.4 16.36

15.0 54.0 7.76 64.8 9.34 75.6 10.93 81.0 11.74 91.8 13.35 102.6 14.96 113.4 16.57

90% 20.0 54.0 7.92 64.8 9.55 75.6 11.23 81.0 12.07 91.8 13.75 102.6 15.45 113.4 17.13

25.0 54.0 8.62 64.8 10.49 75.6 12.37 81.0 13.33 91.8 15.38 102.6 17.54 113.4 19.81

30.0 54.0 10.93 64.8 13.14 75.6 15.47 81.0 16.68 91.8 19.20 102.6 21.83 113.4 24.58

35.0 54.0 13.28 64.8 15.96 75.6 18.78 81.0 20.25 91.8 23.28 102.6 26.42 113.4 29.71

40.0 54.0 15.77 64.8 18.99 75.6 22.37 81.0 24.12 91.8 27.70 102.6 31.46 109.0 32.62

43.0 54.0 17.38 64.8 20.95 75.6 24.67 81.0 26.61 91.8 30.57 99.3 32.62 103.4 32.41

46.0 54.0 19.06 64.8 23.00 75.6 27.12 81.0 29.26 81.6 27.28 81.6 25.09 81.6 23.04

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 48.0 6.80 57.6 8.18 67.2 9.53 72.0 10.23 81.6 11.60 91.2 12.95 100.8 14.33

-5.0 48.0 6.80 57.6 8.18 67.2 9.55 72.0 10.23 81.6 11.60 91.2 12.98 100.8 14.35

0.0 48.0 6.83 57.6 8.18 67.2 9.55 72.0 10.25 81.6 11.63 91.2 13.00 100.8 14.38

5.0 48.0 6.83 57.6 8.20 67.2 9.58 72.0 10.28 81.6 11.65 91.2 13.02 100.8 14.42

10.0 48.0 6.85 57.6 8.22 67.2 9.60 72.0 10.30 81.6 11.70 91.2 13.09 100.8 14.49

15.0 48.0 6.87 57.6 8.27 67.2 9.69 72.0 10.39 81.6 11.81 91.2 13.23 100.8 14.66

80% 20.0 48.0 6.99 57.6 8.43 67.2 9.90 72.0 10.62 81.6 12.09 91.2 13.58 100.8 15.05

25.0 48.0 7.50 57.6 9.09 67.2 10.69 72.0 11.51 81.6 13.12 91.2 14.73 100.8 16.52

30.0 48.0 9.60 57.6 11.42 67.2 13.33 72.0 14.31 81.6 16.33 91.2 18.45 100.8 20.64

35.0 48.0 11.65 57.6 13.89 67.2 16.22 72.0 17.43 81.6 19.87 91.2 22.44 100.8 25.07

40.0 48.0 13.84 57.6 16.54 67.2 19.34 72.0 20.76 81.6 23.70 91.2 26.75 100.8 29.87

43.0 48.0 15.26 57.6 18.24 67.2 21.34 72.0 22.93 81.6 26.17 91.2 29.54 100.2 32.62

46.0 48.0 16.73 57.6 20.04 67.2 23.44 72.0 25.21 81.6 28.82 81.6 26.52 81.6 24.37

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 42.0 5.96 50.4 7.15 58.8 8.34 63.0 8.95 71.4 10.14 79.8 11.35 88.2 12.54

-5.0 42.0 5.96 50.4 7.15 58.8 8.34 63.0 8.95 71.4 10.16 79.8 11.35 88.2 12.54

0.0 42.0 5.96 50.4 7.15 58.8 8.36 63.0 8.95 71.4 10.16 79.8 11.37 88.2 12.56

5.0 42.0 5.96 50.4 7.18 58.8 8.36 63.0 8.97 71.4 10.18 79.8 11.39 88.2 12.58

10.0 42.0 5.99 50.4 7.18 58.8 8.39 63.0 8.99 71.4 10.21 79.8 11.42 88.2 12.65

15.0 42.0 6.01 50.4 7.22 58.8 8.46 63.0 9.06 71.4 10.30 79.8 11.51 88.2 12.75

70% 20.0 42.0 6.08 50.4 7.34 58.8 8.60 63.0 9.23 71.4 10.49 79.8 11.77 88.2 13.02

25.0 42.0 6.43 50.4 7.78 58.8 9.13 63.0 9.83 71.4 11.18 79.8 12.54 88.2 13.89

30.0 42.0 8.36 50.4 9.83 58.8 11.35 63.0 12.14 71.4 13.75 79.8 15.38 88.2 17.08

35.0 42.0 10.14 50.4 11.95 58.8 13.84 63.0 14.80 71.4 16.75 79.8 18.78 88.2 20.83

40.0 42.0 12.02 50.4 14.24 58.8 16.50 63.0 17.66 71.4 20.01 79.8 22.41 88.2 24.88

43.0 42.0 13.23 50.4 15.68 58.8 18.20 63.0 19.50 71.4 22.11 79.8 24.79 88.2 27.54

46.0 42.0 14.49 50.4 17.22 58.8 20.01 63.0 21.44 71.4 24.33 79.8 27.31 81.6 26.19

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 36.0 5.10 43.2 6.13 50.4 7.15 54.0 7.67 61.2 8.69 68.4 9.72 75.6 10.74

-5.0 36.0 5.10 43.2 6.13 50.4 7.15 54.0 7.67 61.2 8.69 68.4 9.72 75.6 10.74

0.0 36.0 5.10 43.2 6.13 50.4 7.15 54.0 7.67 61.2 8.71 68.4 9.74 75.6 10.76

5.0 36.0 5.13 43.2 6.15 50.4 7.18 54.0 7.69 61.2 8.71 68.4 9.74 75.6 10.79

10.0 36.0 5.13 43.2 6.15 50.4 7.18 54.0 7.71 61.2 8.74 68.4 9.79 75.6 10.81

15.0 36.0 5.15 43.2 6.17 50.4 7.22 54.0 7.74 61.2 8.78 68.4 9.83 75.6 10.88

60% 20.0 36.0 5.20 43.2 6.24 50.4 7.32 54.0 7.85 61.2 8.92 68.4 10.00 75.6 11.07

25.0 36.0 5.41 43.2 6.55 50.4 7.67 54.0 8.22 61.2 9.37 68.4 10.49 75.6 11.60

30.0 36.0 7.20 43.2 8.34 50.4 9.53 54.0 10.14 61.2 11.37 68.4 12.63 75.6 13.89

35.0 36.0 8.69 43.2 10.16 50.4 11.63 54.0 12.37 61.2 13.91 68.4 15.45 75.6 17.03

40.0 36.0 10.30 43.2 12.07 50.4 13.86 54.0 14.77 61.2 16.61 68.4 18.48 75.6 20.36

43.0 36.0 11.30 43.2 13.28 50.4 15.28 54.0 16.31 61.2 18.36 68.4 20.43 75.6 22.53

46.0 36.0 12.37 43.2 14.56 50.4 16.80 54.0 17.92 61.2 20.20 68.4 22.51 75.6 24.86

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, HIGH EFFICIENCY (Cooling)


32 HP (U-8MF2E8 & U-12MF2E8 & U-12MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 30.0 4.24 36.0 5.10 42.0 5.96 45.0 6.38 51.0 7.25 57.0 8.09 63.0 8.95

-5.0 30.0 4.26 36.0 5.10 42.0 5.96 45.0 6.38 51.0 7.25 57.0 8.11 63.0 8.95

0.0 30.0 4.26 36.0 5.10 42.0 5.96 45.0 6.38 51.0 7.25 57.0 8.11 63.0 8.97

5.0 30.0 4.26 36.0 5.13 42.0 5.96 45.0 6.41 51.0 7.27 57.0 8.11 63.0 8.97

10.0 30.0 4.26 36.0 5.13 42.0 5.99 45.0 6.41 51.0 7.27 57.0 8.13 63.0 8.99

15.0 30.0 4.29 36.0 5.15 42.0 6.01 45.0 6.43 51.0 7.29 57.0 8.18 63.0 9.04

50% 20.0 30.0 4.31 36.0 5.17 42.0 6.06 45.0 6.50 51.0 7.39 57.0 8.25 63.0 9.13

25.0 30.0 4.45 36.0 5.36 42.0 6.27 45.0 6.73 51.0 7.64 57.0 8.55 63.0 9.46

30.0 30.0 6.10 36.0 6.99 42.0 7.88 45.0 8.34 51.0 9.23 57.0 10.14 63.0 11.07

35.0 30.0 7.34 36.0 8.46 42.0 9.60 45.0 10.16 51.0 11.30 57.0 12.44 63.0 13.61

40.0 30.0 8.64 36.0 10.04 42.0 11.42 45.0 12.12 51.0 13.51 57.0 14.89 63.0 16.31

43.0 30.0 9.48 36.0 11.04 42.0 12.58 45.0 13.35 51.0 14.91 57.0 16.47 63.0 18.03

46.0 30.0 10.37 36.0 12.09 42.0 13.79 45.0 14.66 51.0 16.40 57.0 18.13 63.0 19.87

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 24.0 3.40 28.8 4.08 33.6 4.78 36.0 5.10 40.8 5.80 45.6 6.48 50.4 7.15

-5.0 24.0 3.40 28.8 4.08 33.6 4.78 36.0 5.10 40.8 5.80 45.6 6.48 50.4 7.15

0.0 24.0 3.40 28.8 4.08 33.6 4.78 36.0 5.10 40.8 5.80 45.6 6.48 50.4 7.18

5.0 24.0 3.40 28.8 4.10 33.6 4.78 36.0 5.13 40.8 5.80 45.6 6.50 50.4 7.18

10.0 24.0 3.40 28.8 4.10 33.6 4.78 36.0 5.13 40.8 5.80 45.6 6.50 50.4 7.18

15.0 24.0 3.43 28.8 4.10 33.6 4.80 36.0 5.15 40.8 5.83 45.6 6.52 50.4 7.20

40% 20.0 24.0 3.45 28.8 4.12 33.6 4.82 36.0 5.17 40.8 5.87 45.6 6.57 50.4 7.27

25.0 24.0 3.52 28.8 4.22 33.6 4.94 36.0 5.29 40.8 6.01 45.6 6.73 50.4 7.43

30.0 24.0 4.40 28.8 5.13 33.6 5.85 36.0 6.20 40.8 6.92 45.6 7.62 50.4 8.32

35.0 24.0 6.08 28.8 6.90 33.6 7.74 36.0 8.13 40.8 8.95 45.6 9.74 50.4 10.53

40.0 24.0 7.11 28.8 8.13 33.6 9.16 36.0 9.67 40.8 10.67 45.6 11.65 50.4 12.65

43.0 24.0 7.78 28.8 8.92 33.6 10.07 36.0 10.62 40.8 11.77 45.6 12.86 50.4 13.98

46.0 24.0 8.46 28.8 9.74 33.6 11.02 36.0 11.65 40.8 12.91 45.6 14.14 50.4 15.40

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 18.0 2.54 21.6 3.05 25.2 3.56 27.0 3.82 30.6 4.33 34.2 4.85 37.8 5.36

-5.0 18.0 2.56 21.6 3.08 25.2 3.56 27.0 3.82 30.6 4.33 34.2 4.85 37.8 5.36

0.0 18.0 2.56 21.6 3.08 25.2 3.59 27.0 3.84 30.6 4.36 34.2 4.87 37.8 5.38

5.0 18.0 2.56 21.6 3.08 25.2 3.59 27.0 3.84 30.6 4.36 34.2 4.87 37.8 5.38

10.0 18.0 2.56 21.6 3.08 25.2 3.59 27.0 3.84 30.6 4.36 34.2 4.87 37.8 5.38

15.0 18.0 2.56 21.6 3.08 25.2 3.59 27.0 3.84 30.6 4.36 34.2 4.87 37.8 5.41
30% 20.0 18.0 2.56 21.6 3.10 25.2 3.61 27.0 3.87 30.6 4.38 34.2 4.89 37.8 5.43

25.0 18.0 2.61 21.6 3.12 25.2 3.66 27.0 3.91 30.6 4.45 34.2 4.96 37.8 5.50

30.0 18.0 3.01 21.6 3.52 25.2 4.05 27.0 4.31 30.6 4.85 34.2 5.36 37.8 5.87

35.0 18.0 4.89 21.6 5.48 25.2 6.01 27.0 6.29 30.6 6.83 34.2 7.34 37.8 7.85

40.0 18.0 5.66 21.6 6.38 25.2 7.08 27.0 7.41 30.6 8.09 34.2 8.74 37.8 9.39

43.0 18.0 6.15 21.6 6.97 25.2 7.74 27.0 8.13 30.6 8.88 34.2 9.62 37.8 10.35

46.0 18.0 6.66 21.6 7.55 25.2 8.43 27.0 8.88 30.6 9.72 34.2 10.55 37.8 11.37

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, HIGH EFFICIENCY (Heating)


16 HP (U-8MF2E8 & U-8MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 40.8 12.98 37.5 12.03 35.3 11.38 35.3 11.38 35.3 11.38 35.1 11.68 30.3 10.43

-14.7 -15.0 43.3 13.30 39.9 12.34 37.5 11.68 37.5 11.68 37.5 11.68 37.5 11.95 32.4 10.63

-9.6 -10.0 46.5 13.74 42.8 12.75 40.3 12.05 40.3 12.05 40.3 12.05 40.3 12.05 35.0 10.90

-4.4 -5.0 50.5 14.24 46.7 13.21 44.0 12.50 44.0 12.50 44.0 12.50 44.0 12.50 38.4 11.27

-1.8 -2.5 53.1 14.45 49.0 13.41 46.3 12.68 46.3 12.68 46.3 12.68 46.3 12.68 40.6 11.45

0.8 0.0 56.1 14.67 51.9 13.63 49.0 12.90 49.0 12.90 49.0 12.90 49.0 12.90 43.4 11.69

130% 2.8 2.0 58.5 14.70 54.7 13.87 51.8 13.17 51.8 13.17 51.8 13.17 51.8 13.17 44.0 11.21

6.0 5.0 63.0 14.70 57.8 13.50 53.8 12.52 53.8 12.52 53.8 12.52 51.8 11.80 44.0 10.02

7.0 6.0 63.7 14.39 57.8 12.94 53.8 11.99 53.8 11.99 53.8 11.99 51.8 11.31 44.0 9.60

8.6 7.5 63.7 13.38 57.8 12.04 53.8 11.18 53.8 11.18 53.8 11.18 51.8 10.57 44.0 9.00

11.2 10.0 63.7 11.79 57.8 10.65 53.8 9.90 53.8 9.90 53.8 9.90 51.8 9.43 44.0 8.05

16.4 15.0 63.7 8.95 57.8 8.15 53.8 7.62 53.8 7.62 53.8 7.62 51.8 7.38 44.0 6.36

24.0 18.0 63.7 8.09 57.8 7.37 53.8 6.90 53.8 6.90 53.8 6.90 51.8 6.66 44.0 5.73

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 40.9 12.90 37.6 11.98 35.3 11.34 35.3 11.34 35.3 11.34 32.5 10.80 28.0 9.67

-14.7 -15.0 43.4 13.24 40.0 12.29 37.6 11.63 37.6 11.63 37.6 11.63 34.6 11.05 29.9 9.85

-9.6 -10.0 46.6 13.68 42.9 12.69 40.4 12.01 40.4 12.01 40.4 12.01 37.3 11.37 32.3 10.09

-4.4 -5.0 50.6 14.14 46.7 13.14 44.0 12.43 44.0 12.43 44.0 12.43 40.9 11.77 35.4 10.42

-1.8 -2.5 53.2 14.35 49.1 13.32 46.3 12.61 46.3 12.61 46.3 12.61 43.1 11.94 37.4 10.57

0.8 0.0 56.2 14.56 52.0 13.55 49.1 12.83 49.1 12.83 49.1 12.83 46.0 12.19 39.7 10.67
120% 2.8 2.0 58.9 14.70 54.8 13.79 51.8 13.09 51.8 13.09 51.8 13.09 46.7 11.75 39.7 10.06

6.0 5.0 62.2 14.35 56.4 12.93 52.5 12.00 52.5 12.00 52.5 12.00 46.7 10.54 39.7 8.97

7.0 6.0 62.2 13.72 56.4 12.37 52.5 11.49 52.5 11.49 52.5 11.49 46.7 10.09 39.7 8.60

8.6 7.5 62.2 12.76 56.4 11.52 52.5 10.71 52.5 10.71 52.5 10.71 46.7 9.44 39.7 8.06

11.2 10.0 62.2 11.22 56.4 10.16 52.5 9.47 52.5 9.47 52.5 9.47 46.7 8.41 39.7 7.21

16.4 15.0 62.2 8.49 56.4 7.76 52.5 7.28 52.5 7.28 52.5 7.28 46.7 6.59 39.7 5.70

24.0 18.0 62.2 7.91 56.4 7.21 52.5 6.75 52.5 6.75 52.5 6.75 46.7 6.06 39.7 5.22

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 41.1 12.84 37.7 11.93 35.4 11.30 35.4 11.30 33.8 10.98 29.8 9.94 25.7 8.91

-14.7 -15.0 43.6 13.19 40.0 12.24 37.7 11.59 37.7 11.59 36.0 11.26 31.8 10.16 27.4 9.07

-9.6 -10.0 46.7 13.63 43.0 12.65 40.5 11.98 40.5 11.98 38.7 11.60 34.2 10.45 29.6 9.28

-4.4 -5.0 50.8 14.06 46.8 13.06 44.1 12.37 44.1 12.37 42.3 12.00 37.5 10.80 32.4 9.58

-1.8 -2.5 53.3 14.26 49.2 13.25 46.4 12.55 46.4 12.55 44.6 12.17 39.5 10.95 34.3 9.71

0.8 0.0 56.3 14.48 52.1 13.47 49.1 12.77 49.1 12.77 47.4 12.40 41.8 11.05 35.5 9.51

110% 2.8 2.0 59.2 14.70 54.9 13.72 51.3 12.80 51.3 12.80 48.0 11.94 41.8 10.44 35.5 8.97

6.0 5.0 60.8 13.69 55.1 12.37 51.3 11.50 51.3 11.50 48.0 10.72 41.8 9.35 35.5 7.98

7.0 6.0 60.8 13.08 55.1 11.82 51.3 11.00 51.3 11.00 48.0 10.27 41.8 8.96 35.5 7.65

8.6 7.5 60.8 12.15 55.1 11.00 51.3 10.25 51.3 10.25 48.0 9.59 41.8 8.38 35.5 7.17

11.2 10.0 60.8 10.68 55.1 9.70 51.3 9.06 51.3 9.06 48.0 8.51 41.8 7.47 35.5 6.43

16.4 15.0 60.8 8.04 55.1 7.38 51.3 6.94 51.3 6.94 48.0 6.59 41.8 5.85 35.5 5.08

24.0 18.0 60.8 7.73 55.1 7.06 51.3 6.60 51.3 6.60 48.0 6.22 41.8 5.47 35.5 4.73

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 41.2 12.80 37.8 11.89 35.5 11.27 33.2 10.65 30.8 10.02 27.1 9.08 23.4 8.17

-14.7 -15.0 43.7 13.14 40.2 12.20 37.7 11.56 35.3 10.92 32.8 10.27 28.9 9.28 25.0 8.31

-9.6 -10.0 46.8 13.59 43.1 12.61 40.5 11.95 37.9 11.27 35.3 10.58 31.2 9.53 26.9 8.48

-4.4 -5.0 50.9 13.99 46.9 13.00 44.2 12.32 41.4 11.62 38.5 10.92 34.1 9.85 29.5 8.75

-1.8 -2.5 53.4 14.18 49.3 13.18 46.5 12.50 43.5 11.78 40.6 11.07 36.0 9.98 31.2 8.86

0.8 0.0 56.4 14.41 52.2 13.40 49.2 12.72 46.2 12.00 42.6 11.11 37.1 9.74 31.5 8.42

100% 2.8 2.0 59.3 14.60 53.7 13.19 50.0 12.27 46.3 11.37 42.6 10.49 37.1 9.20 31.5 7.94

6.0 5.0 59.3 13.04 53.7 11.81 50.0 11.00 46.3 10.21 42.6 9.41 37.1 8.22 31.5 7.05

7.0 6.0 59.3 12.46 53.7 11.30 50.0 10.50 46.3 9.77 42.6 9.01 37.1 7.88 31.5 6.76

8.6 7.5 59.3 11.56 53.7 10.50 50.0 9.80 46.3 9.10 42.6 8.41 37.1 7.37 31.5 6.34

11.2 10.0 59.3 10.14 53.7 9.25 50.0 8.65 46.3 8.05 42.6 7.47 37.1 6.57 31.5 5.68

16.4 15.0 59.3 7.61 53.7 7.01 50.0 6.60 46.3 6.20 42.6 5.79 37.1 5.15 31.5 4.49

9 24.0 18.0 59.3 7.56 53.7 6.90 50.0 6.45 46.3 6.01 42.6 5.57 37.1 4.90 31.5 4.24
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, HIGH EFFICIENCY (Heating)


16 HP (U-8MF2E8 & U-8MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 41.8 12.67 38.4 11.81 36.0 11.22 33.6 10.64 31.2 10.05 27.4 9.18 23.6 8.30

-14.7 -15.0 44.4 13.04 40.8 12.14 38.3 11.53 35.7 10.92 33.2 10.29 29.2 9.36 25.2 8.41

-9.6 -10.0 47.6 13.43 43.7 12.53 41.1 11.91 38.4 11.26 35.7 10.59 31.5 9.60 27.1 8.57

-4.4 -5.0 51.7 13.79 47.6 12.85 44.7 12.21 41.7 11.50 38.4 10.69 33.4 9.51 28.4 8.35

-1.8 -2.5 53.4 13.65 48.4 12.44 45.0 11.66 41.7 10.88 38.4 10.12 33.4 9.00 28.4 7.90

0.8 0.0 53.4 12.77 48.4 11.66 45.0 10.93 41.7 10.21 38.4 9.49 33.4 8.43 28.4 7.38

90% 2.8 2.0 53.4 11.98 48.4 10.96 45.0 10.28 41.7 9.61 38.4 8.94 33.4 7.93 28.4 6.88

6.0 5.0 53.4 10.65 48.4 9.75 45.0 9.16 41.7 8.56 38.4 7.95 33.4 7.02 28.4 6.09

7.0 6.0 53.4 10.14 48.4 9.30 45.0 8.75 41.7 8.17 38.4 7.60 33.4 6.73 28.4 5.84

8.6 7.5 53.4 9.39 48.4 8.63 45.0 8.12 41.7 7.60 38.4 7.08 33.4 6.29 28.4 5.47

11.2 10.0 53.4 8.18 48.4 7.56 45.0 7.14 41.7 6.71 38.4 6.27 33.4 5.59 28.4 4.89

16.4 15.0 53.4 6.85 48.4 6.26 45.0 5.86 41.7 5.46 38.4 5.06 33.4 4.46 28.4 3.86

24.0 18.0 53.4 6.85 48.4 6.26 45.0 5.86 41.7 5.46 38.4 5.06 33.4 4.46 28.4 3.86

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 42.9 12.76 39.3 11.94 36.8 11.38 34.4 10.83 31.8 10.26 28.0 9.42 24.0 8.58

-14.7 -15.0 45.6 13.14 41.8 12.29 39.2 11.70 36.6 11.10 33.9 10.50 29.7 9.53 25.2 8.51

-9.6 -10.0 47.4 12.94 43.0 11.94 40.0 11.29 37.1 10.63 34.1 9.98 29.7 8.96 25.2 7.95

-4.4 -5.0 47.4 11.78 43.0 10.88 40.0 10.29 37.1 9.69 34.1 9.10 29.7 8.21 25.2 7.32

-1.8 -2.5 47.4 11.10 43.0 10.27 40.0 9.71 37.1 9.15 34.1 8.59 29.7 7.75 25.2 6.89

0.8 0.0 47.4 10.34 43.0 9.58 40.0 9.06 37.1 8.55 34.1 8.02 29.7 7.23 25.2 6.36

80% 2.8 2.0 47.4 9.68 43.0 8.98 40.0 8.49 37.1 8.01 34.1 7.53 29.7 6.75 25.2 5.89

6.0 5.0 47.4 8.54 43.0 7.94 40.0 7.52 37.1 7.08 34.1 6.63 29.7 5.93 25.2 5.21

7.0 6.0 47.4 8.12 43.0 7.55 40.0 7.15 37.1 6.75 34.1 6.33 29.7 5.67 25.2 4.99

8.6 7.5 47.4 7.48 43.0 6.97 40.0 6.63 37.1 6.26 34.1 5.89 29.7 5.29 25.2 4.67

11.2 10.0 47.4 6.46 43.0 6.07 40.0 5.79 37.1 5.49 34.1 5.19 29.7 4.69 25.2 4.17

16.4 15.0 47.4 6.14 43.0 5.62 40.0 5.26 37.1 4.90 34.1 4.56 29.7 4.02 25.2 3.50

24.0 18.0 47.4 6.14 43.0 5.62 40.0 5.26 37.1 4.90 34.1 4.56 29.7 4.02 25.2 3.50

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 41.5 11.99 37.6 11.17 35.0 10.63 32.4 10.08 29.8 9.53 26.0 8.74 22.1 7.93

-14.7 -15.0 41.5 11.29 37.6 10.58 35.0 10.10 32.4 9.60 29.8 9.06 26.0 8.25 22.1 7.44

-9.6 -10.0 41.5 10.47 37.6 9.82 35.0 9.38 32.4 8.94 29.8 8.47 26.0 7.76 22.1 6.94

-4.4 -5.0 41.5 9.47 37.6 8.89 35.0 8.51 32.4 8.10 29.8 7.69 26.0 7.04 22.1 6.35

-1.8 -2.5 41.5 8.89 37.6 8.36 35.0 7.99 32.4 7.61 29.8 7.22 26.0 6.62 22.1 5.89

0.8 0.0 41.5 8.24 37.6 7.76 35.0 7.42 32.4 7.08 29.8 6.72 26.0 6.10 22.1 5.38

70% 2.8 2.0 41.5 7.68 37.6 7.23 35.0 6.93 32.4 6.60 29.8 6.24 26.0 5.62 22.1 4.97

6.0 5.0 41.5 6.71 37.6 6.32 35.0 6.05 32.4 5.75 29.8 5.44 26.0 4.94 22.1 4.39

7.0 6.0 41.5 6.34 37.6 6.00 35.0 5.74 32.4 5.47 29.8 5.19 26.0 4.71 22.1 4.20

8.6 7.5 41.5 5.82 37.6 5.52 35.0 5.30 32.4 5.07 29.8 4.81 26.0 4.40 22.1 3.94

11.2 10.0 41.5 5.44 37.6 4.98 35.0 4.66 32.4 4.43 29.8 4.22 26.0 3.89 22.1 3.51

16.4 15.0 41.5 5.44 37.6 4.98 35.0 4.66 32.4 4.36 29.8 4.04 26.0 3.58 22.1 3.12

24.0 18.0 41.5 5.44 37.6 4.98 35.0 4.66 32.4 4.36 29.8 4.04 26.0 3.58 22.1 3.12

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 35.6 9.68 32.2 9.23 30.0 8.89 27.8 8.49 25.6 8.10 22.2 7.49 18.9 6.87

-14.7 -15.0 35.6 9.08 32.2 8.66 30.0 8.36 27.8 8.04 25.6 7.69 22.2 7.07 18.9 6.43

-9.6 -10.0 35.6 8.37 32.2 7.99 30.0 7.73 27.8 7.43 25.6 7.13 22.2 6.62 18.9 5.99

-4.4 -5.0 35.6 7.51 32.2 7.18 30.0 6.95 27.8 6.70 25.6 6.42 22.2 5.96 18.9 5.34

-1.8 -2.5 35.6 7.01 32.2 6.71 30.0 6.50 27.8 6.26 25.6 6.01 22.2 5.52 18.9 4.89

0.8 0.0 35.6 6.46 32.2 6.20 30.0 6.01 27.8 5.79 25.6 5.49 22.2 5.00 18.9 4.46

60% 2.8 2.0 35.6 5.97 32.2 5.74 30.0 5.53 27.8 5.29 25.6 5.03 22.2 4.60 18.9 4.12

6.0 5.0 35.6 5.12 32.2 4.92 30.0 4.76 27.8 4.58 25.6 4.38 22.2 4.03 18.9 3.63

7.0 6.0 35.6 4.83 32.2 4.66 30.0 4.52 27.8 4.35 25.6 4.17 22.2 3.85 18.9 3.49

8.6 7.5 35.6 4.73 32.2 4.34 30.0 4.16 27.8 4.02 25.6 3.86 22.2 3.58 18.9 3.26

11.2 10.0 35.6 4.73 32.2 4.34 30.0 4.06 27.8 3.80 25.6 3.54 22.2 3.17 18.9 2.91

16.4 15.0 35.6 4.73 32.2 4.34 30.0 4.06 27.8 3.80 25.6 3.54 22.2 3.14 18.9 2.74

24.0 18.0 35.6 4.73 32.2 4.34 30.0 4.06 27.8 3.80 25.6 3.54 22.2 3.14 18.9 2.74

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, HIGH EFFICIENCY (Heating)


16 HP (U-8MF2E8 & U-8MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 29.7 7.74 26.9 7.50 25.0 7.32 23.2 7.07 21.3 6.77 18.5 6.32 15.8 5.85

-14.7 -15.0 29.7 7.22 26.9 7.01 25.0 6.85 23.2 6.65 21.3 6.42 18.5 5.95 15.8 5.46

-9.6 -10.0 29.7 6.62 26.9 6.44 25.0 6.29 23.2 6.11 21.3 5.91 18.5 5.55 15.8 5.06

-4.4 -5.0 29.7 5.87 26.9 5.72 25.0 5.61 23.2 5.46 21.3 5.29 18.5 4.85 15.8 4.34

-1.8 -2.5 29.7 5.44 26.9 5.31 25.0 5.21 23.2 5.05 21.3 4.81 18.5 4.42 15.8 3.98

0.8 0.0 29.7 4.98 26.9 4.85 25.0 4.69 23.2 4.53 21.3 4.34 18.5 4.00 15.8 3.62

50% 2.8 2.0 29.7 4.53 26.9 4.39 25.0 4.26 23.2 4.13 21.3 3.97 18.5 3.68 15.8 3.35

6.0 5.0 29.7 4.02 26.9 3.73 25.0 3.65 23.2 3.56 21.3 3.43 18.5 3.22 15.8 2.95

7.0 6.0 29.7 4.02 26.9 3.70 25.0 3.48 23.2 3.37 21.3 3.27 18.5 3.08 15.8 2.84

8.6 7.5 29.7 4.02 26.9 3.70 25.0 3.48 23.2 3.26 21.3 3.03 18.5 2.87 15.8 2.65

11.2 10.0 29.7 4.02 26.9 3.70 25.0 3.48 23.2 3.26 21.3 3.03 18.5 2.70 15.8 2.37

16.4 15.0 29.7 4.02 26.9 3.70 25.0 3.48 23.2 3.26 21.3 3.03 18.5 2.70 15.8 2.37

24.0 18.0 29.7 4.02 26.9 3.70 25.0 3.48 23.2 3.26 21.3 3.03 18.5 2.70 15.8 2.37

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 23.7 6.11 21.5 6.01 20.0 5.90 18.5 5.74 17.1 5.53 14.8 5.21 12.6 4.84

-14.7 -15.0 23.7 5.67 21.5 5.59 20.0 5.50 18.5 5.39 17.1 5.23 14.8 4.88 12.6 4.52

-9.6 -10.0 23.7 5.16 21.5 5.10 20.0 5.03 18.5 4.92 17.1 4.80 14.8 4.46 12.6 4.01

-4.4 -5.0 23.7 4.52 21.5 4.48 20.0 4.38 18.5 4.23 17.1 4.06 14.8 3.77 12.6 3.41

-1.8 -2.5 23.7 4.14 21.5 4.03 20.0 3.94 18.5 3.82 17.1 3.68 14.8 3.43 12.6 3.13

0.8 0.0 23.7 3.63 21.5 3.57 20.0 3.51 18.5 3.42 17.1 3.31 14.8 3.11 12.6 2.86

40% 2.8 2.0 23.7 3.32 21.5 3.22 20.0 3.18 18.5 3.11 17.1 3.02 14.8 2.86 12.6 2.64

6.0 5.0 23.7 3.32 21.5 3.06 20.0 2.88 18.5 2.70 17.1 2.63 14.8 2.50 12.6 2.34

7.0 6.0 23.7 3.32 21.5 3.06 20.0 2.88 18.5 2.70 17.1 2.52 14.8 2.39 12.6 2.24

8.6 7.5 23.7 3.32 21.5 3.06 20.0 2.88 18.5 2.70 17.1 2.52 14.8 2.26 12.6 2.10

11.2 10.0 23.7 3.32 21.5 3.06 20.0 2.88 18.5 2.70 17.1 2.52 14.8 2.26 12.6 2.00

16.4 15.0 23.7 3.32 21.5 3.06 20.0 2.88 18.5 2.70 17.1 2.52 14.8 2.26 12.6 2.00

24.0 18.0 23.7 3.32 21.5 3.06 20.0 2.88 18.5 2.70 17.1 2.52 14.8 2.26 12.6 2.00

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 17.8 4.69 16.1 4.65 15.0 4.59 13.9 4.47 12.8 4.34 11.1 4.10 9.5 3.84

-14.7 -15.0 17.8 4.34 16.1 4.32 15.0 4.27 13.9 4.20 12.8 4.08 11.1 3.80 9.5 3.42

-9.6 -10.0 17.8 3.92 16.1 3.90 15.0 3.80 13.9 3.69 12.8 3.55 11.1 3.30 9.5 3.01

-4.4 -5.0 17.8 3.22 16.1 3.18 15.0 3.13 13.9 3.06 12.8 2.96 11.1 2.79 9.5 2.57

-1.8 -2.5 17.8 2.86 16.1 2.84 15.0 2.80 13.9 2.75 12.8 2.69 11.1 2.54 9.5 2.36

0.8 0.0 17.8 2.61 16.1 2.51 15.0 2.50 13.9 2.47 12.8 2.42 11.1 2.31 9.5 2.16

30% 2.8 2.0 17.8 2.61 16.1 2.42 15.0 2.28 13.9 2.25 12.8 2.22 11.1 2.13 9.5 2.01

6.0 5.0 17.8 2.61 16.1 2.42 15.0 2.28 13.9 2.14 12.8 2.02 11.1 1.87 9.5 1.79

7.0 6.0 17.8 2.61 16.1 2.42 15.0 2.28 13.9 2.14 12.8 2.02 11.1 1.82 9.5 1.71

8.6 7.5 17.8 2.61 16.1 2.42 15.0 2.28 13.9 2.14 12.8 2.02 11.1 1.82 9.5 1.62

11.2 10.0 17.8 2.61 16.1 2.42 15.0 2.28 13.9 2.14 12.8 2.02 11.1 1.82 9.5 1.62

16.4 15.0 17.8 2.61 16.1 2.42 15.0 2.28 13.9 2.14 12.8 2.02 11.1 1.82 9.5 1.62

24.0 18.0 17.8 2.61 16.1 2.42 15.0 2.28 13.9 2.14 12.8 2.02 11.1 1.82 9.5 1.62

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, HIGH EFFICIENCY (Heating)


24 HP (U-8MF2E8 & U-8MF2E8 & U-8MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 62.4 20.02 57.4 18.57 53.9 17.56 53.9 17.56 53.9 17.56 53.7 18.01 46.4 16.09

-14.7 -15.0 66.2 20.53 61.0 19.04 57.4 18.01 57.4 18.01 57.4 18.01 57.3 18.44 49.5 16.39

-9.6 -10.0 71.1 21.21 65.5 19.67 61.7 18.60 61.7 18.60 61.7 18.60 61.7 18.60 53.5 16.82

-4.4 -5.0 77.3 21.97 71.4 20.38 67.2 19.28 67.2 19.28 67.2 19.28 67.2 19.28 58.7 17.38

-1.8 -2.5 81.2 22.29 75.0 20.69 70.8 19.57 70.8 19.57 70.8 19.57 70.8 19.57 62.0 17.66

0.8 0.0 85.8 22.63 79.3 21.03 75.0 19.91 75.0 19.91 75.0 19.91 75.0 19.91 66.4 18.03

130% 2.8 2.0 89.5 22.68 83.7 21.40 79.2 20.31 79.2 20.31 79.2 20.31 79.2 20.31 67.3 17.30

6.0 5.0 96.4 22.68 88.4 20.83 82.2 19.31 82.2 19.31 82.2 19.31 79.2 18.21 67.3 15.45

7.0 6.0 97.5 22.19 88.4 19.96 82.2 18.50 82.2 18.50 82.2 18.50 79.2 17.45 67.3 14.81

8.6 7.5 97.5 20.64 88.4 18.58 82.2 17.25 82.2 17.25 82.2 17.25 79.2 16.31 67.3 13.88

11.2 10.0 97.5 18.19 88.4 16.43 82.2 15.28 82.2 15.28 82.2 15.28 79.2 14.55 67.3 12.43

16.4 15.0 97.5 13.80 88.4 12.57 82.2 11.76 82.2 11.76 82.2 11.76 79.2 11.39 67.3 9.82

24.0 18.0 97.5 12.47 88.4 11.37 82.2 10.64 82.2 10.64 82.2 10.64 79.2 10.27 67.3 8.85

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 62.6 19.91 57.5 18.48 54.0 17.50 54.0 17.50 54.0 17.50 49.6 16.67 42.8 14.92

-14.7 -15.0 66.4 20.43 61.1 18.95 57.5 17.95 57.5 17.95 57.5 17.95 52.9 17.04 45.7 15.20

-9.6 -10.0 71.2 21.11 65.6 19.59 61.7 18.53 61.7 18.53 61.7 18.53 57.1 17.54 49.3 15.57

-4.4 -5.0 77.4 21.82 71.5 20.27 67.3 19.18 67.3 19.18 67.3 19.18 62.5 18.16 54.2 16.07

-1.8 -2.5 81.3 22.15 75.1 20.56 70.8 19.46 70.8 19.46 70.8 19.46 65.9 18.42 57.2 16.31

0.8 0.0 85.9 22.47 79.5 20.90 75.0 19.80 75.0 19.80 75.0 19.80 70.3 18.81 60.7 16.46
120% 2.8 2.0 90.0 22.68 83.8 21.27 79.3 20.20 79.3 20.20 79.3 20.20 71.4 18.13 60.7 15.52

6.0 5.0 95.2 22.15 86.3 19.94 80.3 18.52 80.3 18.52 80.3 18.52 71.4 16.26 60.7 13.83

7.0 6.0 95.2 21.17 86.3 19.08 80.3 17.72 80.3 17.72 80.3 17.72 71.4 15.57 60.7 13.27

8.6 7.5 95.2 19.68 86.3 17.77 80.3 16.52 80.3 16.52 80.3 16.52 71.4 14.56 60.7 12.44

11.2 10.0 95.2 17.32 86.3 15.68 80.3 14.61 80.3 14.61 80.3 14.61 71.4 12.98 60.7 11.13

16.4 15.0 95.2 13.11 86.3 11.97 80.3 11.23 80.3 11.23 80.3 11.23 71.4 10.17 60.7 8.80

24.0 18.0 95.2 12.20 86.3 11.13 80.3 10.42 80.3 10.42 80.3 10.42 71.4 9.35 60.7 8.05

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 62.8 19.81 57.6 18.40 54.2 17.43 54.2 17.43 51.6 16.95 45.5 15.34 39.2 13.75

-14.7 -15.0 66.6 20.35 61.2 18.89 57.6 17.88 57.6 17.88 55.0 17.37 48.6 15.68 41.9 14.00

-9.6 -10.0 71.4 21.03 65.7 19.52 61.9 18.48 61.9 18.48 59.2 17.90 52.3 16.12 45.3 14.32

-4.4 -5.0 77.6 21.69 71.6 20.15 67.4 19.08 67.4 19.08 64.7 18.52 57.3 16.67 49.6 14.77

-1.8 -2.5 81.5 22.00 75.2 20.44 70.9 19.36 70.9 19.36 68.2 18.78 60.4 16.90 52.4 14.99

0.8 0.0 86.1 22.34 79.6 20.78 75.1 19.70 75.1 19.70 72.4 19.13 63.9 17.04 54.3 14.68

110% 2.8 2.0 90.5 22.68 83.9 21.17 78.4 19.75 78.4 19.75 73.4 18.42 63.9 16.10 54.3 13.83

6.0 5.0 92.9 21.12 84.2 19.08 78.4 17.74 78.4 17.74 73.4 16.54 63.9 14.42 54.3 12.31

7.0 6.0 92.9 20.19 84.2 18.24 78.4 16.98 78.4 16.98 73.4 15.84 63.9 13.82 54.3 11.81

8.6 7.5 92.9 18.74 84.2 16.98 78.4 15.81 78.4 15.81 73.4 14.79 63.9 12.93 54.3 11.06

11.2 10.0 92.9 16.48 84.2 14.97 78.4 13.98 78.4 13.98 73.4 13.12 63.9 11.52 54.3 9.91

16.4 15.0 92.9 12.41 84.2 11.39 78.4 10.71 78.4 10.71 73.4 10.17 63.9 9.02 54.3 7.84

24.0 18.0 92.9 11.92 84.2 10.89 78.4 10.19 78.4 10.19 73.4 9.59 63.9 8.44 54.3 7.29

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 63.0 19.75 57.8 18.34 54.3 17.38 50.7 16.43 47.0 15.45 41.5 14.01 35.7 12.60

-14.7 -15.0 66.8 20.27 61.4 18.82 57.7 17.84 53.9 16.85 50.1 15.84 44.2 14.32 38.2 12.81

-9.6 -10.0 71.6 20.96 65.9 19.46 62.0 18.44 58.0 17.38 53.9 16.33 47.7 14.71 41.2 13.09

-4.4 -5.0 77.9 21.58 71.8 20.06 67.5 19.00 63.3 17.93 58.9 16.85 52.1 15.20 45.1 13.49

-1.8 -2.5 81.7 21.87 75.4 20.33 71.1 19.28 66.6 18.18 62.0 17.07 55.0 15.39 47.7 13.67

0.8 0.0 86.3 22.23 79.8 20.67 75.3 19.62 70.7 18.52 65.2 17.14 56.7 15.03 48.2 12.99

100% 2.8 2.0 90.7 22.52 82.2 20.35 76.5 18.94 70.8 17.54 65.2 16.18 56.7 14.19 48.2 12.25

6.0 5.0 90.7 20.12 82.2 18.23 76.5 16.98 70.8 15.75 65.2 14.52 56.7 12.68 48.2 10.87

7.0 6.0 90.7 19.23 82.2 17.43 76.5 16.20 70.8 15.07 65.2 13.90 56.7 12.15 48.2 10.43

8.6 7.5 90.7 17.84 82.2 16.20 76.5 15.11 70.8 14.05 65.2 12.98 56.7 11.37 48.2 9.78

11.2 10.0 90.7 15.65 82.2 14.27 76.5 13.35 70.8 12.43 65.2 11.52 56.7 10.14 48.2 8.76

16.4 15.0 90.7 11.75 82.2 10.82 76.5 10.19 70.8 9.56 65.2 8.93 56.7 7.94 48.2 6.93

9 24.0 18.0 90.7 11.66 82.2 10.64 76.5 9.95 70.8 9.27 65.2 8.59 56.7 7.57 48.2 6.54
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, HIGH EFFICIENCY (Heating)


24 HP (U-8MF2E8 & U-8MF2E8 & U-8MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 64.0 19.55 58.7 18.23 55.1 17.32 51.3 16.41 47.7 15.50 41.9 14.16 36.0 12.80

-14.7 -15.0 67.9 20.12 62.3 18.73 58.5 17.79 54.6 16.85 50.7 15.88 44.7 14.43 38.5 12.98

-9.6 -10.0 72.8 20.72 66.9 19.33 62.8 18.37 58.8 17.37 54.5 16.35 48.1 14.81 41.5 13.22

-4.4 -5.0 79.1 21.27 72.8 19.83 68.4 18.84 63.7 17.74 58.7 16.49 51.0 14.68 43.4 12.88

-1.8 -2.5 81.6 21.06 74.0 19.20 68.9 17.98 63.7 16.78 58.7 15.62 51.0 13.88 43.4 12.18

0.8 0.0 81.6 19.70 74.0 17.98 68.9 16.86 63.7 15.75 58.7 14.64 51.0 13.01 43.4 11.39

90% 2.8 2.0 81.6 18.48 74.0 16.91 68.9 15.86 63.7 14.82 58.7 13.79 51.0 12.23 43.4 10.61

6.0 5.0 81.6 16.43 74.0 15.05 68.9 14.13 63.7 13.20 58.7 12.26 51.0 10.84 43.4 9.40

7.0 6.0 81.6 15.65 74.0 14.35 68.9 13.49 63.7 12.60 58.7 11.73 51.0 10.38 43.4 9.01

8.6 7.5 81.6 14.48 74.0 13.32 68.9 12.52 63.7 11.73 58.7 10.92 51.0 9.70 43.4 8.44

11.2 10.0 81.6 12.62 74.0 11.66 68.9 11.02 63.7 10.35 58.7 9.67 51.0 8.62 43.4 7.55

16.4 15.0 81.6 10.56 74.0 9.66 68.9 9.04 63.7 8.42 58.7 7.81 51.0 6.89 43.4 5.96

24.0 18.0 81.6 10.56 74.0 9.66 68.9 9.04 63.7 8.42 58.7 7.81 51.0 6.89 43.4 5.96

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 65.6 19.68 60.1 18.42 56.3 17.56 52.6 16.70 48.7 15.83 42.8 14.53 36.7 13.24

-14.7 -15.0 69.7 20.27 63.9 18.95 59.9 18.05 55.9 17.12 51.8 16.20 45.4 14.71 38.6 13.12

-9.6 -10.0 72.5 19.96 65.7 18.42 61.2 17.42 56.7 16.39 52.1 15.39 45.4 13.82 38.6 12.26

-4.4 -5.0 72.5 18.18 65.7 16.78 61.2 15.88 56.7 14.95 52.1 14.05 45.4 12.67 38.6 11.29

-1.8 -2.5 72.5 17.12 65.7 15.84 61.2 14.99 56.7 14.11 52.1 13.25 45.4 11.96 38.6 10.63

0.8 0.0 72.5 15.96 65.7 14.77 61.2 13.98 56.7 13.19 52.1 12.38 45.4 11.16 38.6 9.82

80% 2.8 2.0 72.5 14.94 65.7 13.85 61.2 13.11 56.7 12.36 52.1 11.62 45.4 10.42 38.6 9.09

6.0 5.0 72.5 13.17 65.7 12.25 61.2 11.60 56.7 10.92 52.1 10.22 45.4 9.15 38.6 8.04

7.0 6.0 72.5 12.52 65.7 11.65 61.2 11.03 56.7 10.42 52.1 9.77 45.4 8.75 38.6 7.70

8.6 7.5 72.5 11.53 65.7 10.76 61.2 10.22 56.7 9.66 52.1 9.09 45.4 8.16 38.6 7.21

11.2 10.0 72.5 9.96 65.7 9.36 61.2 8.93 56.7 8.47 52.1 8.00 45.4 7.24 38.6 6.43

16.4 15.0 72.5 9.48 65.7 8.67 61.2 8.12 56.7 7.57 52.1 7.03 45.4 6.20 38.6 5.39

24.0 18.0 72.5 9.48 65.7 8.67 61.2 8.12 56.7 7.57 52.1 7.03 45.4 6.20 38.6 5.39

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 63.5 18.50 57.5 17.24 53.6 16.39 49.6 15.55 45.6 14.71 39.7 13.48 33.7 12.23

-14.7 -15.0 63.5 17.42 57.5 16.33 53.6 15.58 49.6 14.81 45.6 13.98 39.7 12.73 33.7 11.49

-9.6 -10.0 63.5 16.15 57.5 15.15 53.6 14.47 49.6 13.79 45.6 13.07 39.7 11.97 33.7 10.71

-4.4 -5.0 63.5 14.61 57.5 13.72 53.6 13.12 49.6 12.49 45.6 11.86 39.7 10.85 33.7 9.80

-1.8 -2.5 63.5 13.72 57.5 12.90 53.6 12.33 49.6 11.75 45.6 11.15 39.7 10.21 33.7 9.09

0.8 0.0 63.5 12.72 57.5 11.97 53.6 11.45 49.6 10.92 45.6 10.37 39.7 9.41 33.7 8.29

70% 2.8 2.0 63.5 11.84 57.5 11.16 53.6 10.69 49.6 10.19 45.6 9.62 39.7 8.67 33.7 7.66

6.0 5.0 63.5 10.35 57.5 9.75 53.6 9.33 49.6 8.88 45.6 8.39 39.7 7.61 33.7 6.77

7.0 6.0 63.5 9.78 57.5 9.25 53.6 8.86 49.6 8.44 45.6 8.00 39.7 7.27 33.7 6.48

8.6 7.5 63.5 8.97 57.5 8.52 53.6 8.18 49.6 7.82 45.6 7.42 39.7 6.79 33.7 6.08

11.2 10.0 63.5 8.39 57.5 7.68 53.6 7.19 49.6 6.84 45.6 6.51 39.7 5.99 33.7 5.41

16.4 15.0 63.5 8.39 57.5 7.68 53.6 7.19 49.6 6.72 45.6 6.24 39.7 5.52 33.7 4.81

24.0 18.0 63.5 8.39 57.5 7.68 53.6 7.19 49.6 6.72 45.6 6.24 39.7 5.52 33.7 4.81

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 54.4 14.94 49.3 14.24 45.9 13.72 42.5 13.11 39.1 12.49 34.0 11.55 28.9 10.59

-14.7 -15.0 54.4 14.01 49.3 13.37 45.9 12.90 42.5 12.41 39.1 11.86 34.0 10.90 28.9 9.91

-9.6 -10.0 54.4 12.91 49.3 12.33 45.9 11.92 42.5 11.47 39.1 11.00 34.0 10.21 28.9 9.23

-4.4 -5.0 54.4 11.58 49.3 11.08 45.9 10.72 42.5 10.34 39.1 9.90 34.0 9.20 28.9 8.25

-1.8 -2.5 54.4 10.82 49.3 10.35 45.9 10.03 42.5 9.66 39.1 9.27 34.0 8.52 28.9 7.55

0.8 0.0 54.4 9.96 49.3 9.56 45.9 9.27 42.5 8.93 39.1 8.47 34.0 7.71 28.9 6.89

60% 2.8 2.0 54.4 9.22 49.3 8.86 45.9 8.54 42.5 8.16 39.1 7.76 34.0 7.10 28.9 6.35

6.0 5.0 54.4 7.91 49.3 7.60 45.9 7.34 42.5 7.06 39.1 6.76 34.0 6.22 28.9 5.61

7.0 6.0 54.4 7.45 49.3 7.19 45.9 6.97 42.5 6.71 39.1 6.43 34.0 5.95 28.9 5.38

8.6 7.5 54.4 7.29 49.3 6.69 45.9 6.42 42.5 6.20 39.1 5.96 34.0 5.52 28.9 5.02

11.2 10.0 54.4 7.29 49.3 6.69 45.9 6.27 42.5 5.86 39.1 5.46 34.0 4.89 28.9 4.49

16.4 15.0 54.4 7.29 49.3 6.69 45.9 6.27 42.5 5.86 39.1 5.46 34.0 4.84 28.9 4.23

24.0 18.0 54.4 7.29 49.3 6.69 45.9 6.27 42.5 5.86 39.1 5.46 34.0 4.84 28.9 4.23

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, HIGH EFFICIENCY (Heating)


24 HP (U-8MF2E8 & U-8MF2E8 & U-8MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 45.4 11.94 41.1 11.57 38.3 11.29 35.4 10.90 32.6 10.45 28.3 9.75 24.1 9.02

-14.7 -15.0 45.4 11.15 41.1 10.82 38.3 10.56 35.4 10.25 32.6 9.90 28.3 9.19 24.1 8.42

-9.6 -10.0 45.4 10.21 41.1 9.93 38.3 9.70 35.4 9.43 32.6 9.12 28.3 8.57 24.1 7.81

-4.4 -5.0 45.4 9.06 41.1 8.83 38.3 8.65 35.4 8.42 32.6 8.16 28.3 7.48 24.1 6.69

-1.8 -2.5 45.4 8.39 41.1 8.20 38.3 8.04 35.4 7.79 32.6 7.42 28.3 6.82 24.1 6.14

0.8 0.0 45.4 7.68 41.1 7.48 38.3 7.24 35.4 6.98 32.6 6.69 28.3 6.17 24.1 5.59

50% 2.8 2.0 45.4 6.98 41.1 6.77 38.3 6.58 35.4 6.37 32.6 6.12 28.3 5.67 24.1 5.17

6.0 5.0 45.4 6.20 41.1 5.75 38.3 5.64 35.4 5.49 32.6 5.30 28.3 4.97 24.1 4.55

7.0 6.0 45.4 6.20 41.1 5.70 38.3 5.36 35.4 5.20 32.6 5.04 28.3 4.75 24.1 4.37

8.6 7.5 45.4 6.20 41.1 5.70 38.3 5.36 35.4 5.02 32.6 4.68 28.3 4.42 24.1 4.08

11.2 10.0 45.4 6.20 41.1 5.70 38.3 5.36 35.4 5.02 32.6 4.68 28.3 4.16 24.1 3.66

16.4 15.0 45.4 6.20 41.1 5.70 38.3 5.36 35.4 5.02 32.6 4.68 28.3 4.16 24.1 3.66

24.0 18.0 45.4 6.20 41.1 5.70 38.3 5.36 35.4 5.02 32.6 4.68 28.3 4.16 24.1 3.66

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 36.3 9.43 32.9 9.27 30.6 9.10 28.3 8.86 26.1 8.54 22.6 8.04 19.3 7.47

-14.7 -15.0 36.3 8.75 32.9 8.62 30.6 8.49 28.3 8.31 26.1 8.07 22.6 7.53 19.3 6.97

-9.6 -10.0 36.3 7.95 32.9 7.87 30.6 7.76 28.3 7.60 26.1 7.40 22.6 6.89 19.3 6.19

-4.4 -5.0 36.3 6.97 32.9 6.92 30.6 6.76 28.3 6.53 26.1 6.27 22.6 5.82 19.3 5.27

-1.8 -2.5 36.3 6.38 32.9 6.22 30.6 6.08 28.3 5.90 26.1 5.67 22.6 5.30 19.3 4.83

0.8 0.0 36.3 5.61 32.9 5.51 30.6 5.41 28.3 5.28 26.1 5.10 22.6 4.80 19.3 4.41

40% 2.8 2.0 36.3 5.12 32.9 4.97 30.6 4.91 28.3 4.80 26.1 4.67 22.6 4.41 19.3 4.07

6.0 5.0 36.3 5.12 32.9 4.71 30.6 4.44 28.3 4.16 26.1 4.05 22.6 3.86 19.3 3.61

7.0 6.0 36.3 5.12 32.9 4.71 30.6 4.44 28.3 4.16 26.1 3.89 22.6 3.69 19.3 3.45

8.6 7.5 36.3 5.12 32.9 4.71 30.6 4.44 28.3 4.16 26.1 3.89 22.6 3.48 19.3 3.24

11.2 10.0 36.3 5.12 32.9 4.71 30.6 4.44 28.3 4.16 26.1 3.89 22.6 3.48 19.3 3.08

16.4 15.0 36.3 5.12 32.9 4.71 30.6 4.44 28.3 4.16 26.1 3.89 22.6 3.48 19.3 3.08

24.0 18.0 36.3 5.12 32.9 4.71 30.6 4.44 28.3 4.16 26.1 3.89 22.6 3.48 19.3 3.08

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 27.2 7.24 24.6 7.18 23.0 7.08 21.3 6.90 19.6 6.69 17.0 6.32 14.5 5.93

-14.7 -15.0 27.2 6.69 24.6 6.66 23.0 6.59 21.3 6.48 19.6 6.30 17.0 5.86 14.5 5.28

-9.6 -10.0 27.2 6.04 24.6 6.01 23.0 5.86 21.3 5.69 19.6 5.48 17.0 5.09 14.5 4.65

-4.4 -5.0 27.2 4.97 24.6 4.91 23.0 4.83 21.3 4.71 19.6 4.57 17.0 4.31 14.5 3.97

-1.8 -2.5 27.2 4.41 24.6 4.37 23.0 4.33 21.3 4.24 19.6 4.15 17.0 3.92 14.5 3.65

0.8 0.0 27.2 4.03 24.6 3.87 23.0 3.86 21.3 3.81 19.6 3.73 17.0 3.56 14.5 3.34

30% 2.8 2.0 27.2 4.03 24.6 3.73 23.0 3.52 21.3 3.47 19.6 3.42 17.0 3.29 14.5 3.09

6.0 5.0 27.2 4.03 24.6 3.73 23.0 3.52 21.3 3.30 19.6 3.11 17.0 2.88 14.5 2.75

7.0 6.0 27.2 4.03 24.6 3.73 23.0 3.52 21.3 3.30 19.6 3.11 17.0 2.80 14.5 2.64

8.6 7.5 27.2 4.03 24.6 3.73 23.0 3.52 21.3 3.30 19.6 3.11 17.0 2.80 14.5 2.49

11.2 10.0 27.2 4.03 24.6 3.73 23.0 3.52 21.3 3.30 19.6 3.11 17.0 2.80 14.5 2.49

16.4 15.0 27.2 4.03 24.6 3.73 23.0 3.52 21.3 3.30 19.6 3.11 17.0 2.80 14.5 2.49

24.0 18.0 27.2 4.03 24.6 3.73 23.0 3.52 21.3 3.30 19.6 3.11 17.0 2.80 14.5 2.49

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, HIGH EFFICIENCY (Heating)


26 HP (U-8MF2E8 & U-8MF2E8 & U-10MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 67.5 21.91 62.1 20.27 58.4 19.16 58.4 19.16 58.4 19.16 58.2 19.51 50.3 17.35

-14.7 -15.0 71.6 22.43 65.9 20.78 62.1 19.63 62.1 19.63 62.1 19.63 62.1 19.63 53.8 17.70

-9.6 -10.0 76.8 23.12 70.8 21.44 66.7 20.27 66.7 20.27 66.7 20.27 66.7 20.27 58.1 18.17

-4.4 -5.0 83.6 24.10 77.3 22.34 72.9 21.11 72.9 21.11 72.9 21.11 72.9 21.11 63.9 18.83

-1.8 -2.5 87.4 24.36 81.3 22.74 76.7 21.51 76.7 21.51 76.7 21.51 76.7 21.51 67.6 19.19

0.8 0.0 91.5 24.36 86.0 23.14 81.3 21.89 81.3 21.89 81.3 21.89 81.3 21.89 71.7 19.44

130% 2.8 2.0 95.5 24.36 90.6 23.56 85.8 22.32 85.8 22.32 85.8 22.32 84.4 21.56 71.7 18.37

6.0 5.0 102.5 24.36 94.1 22.39 87.6 20.72 87.6 20.72 87.6 20.72 84.4 19.42 71.7 16.48

7.0 6.0 103.8 23.91 94.1 21.45 87.6 19.85 87.6 19.85 87.6 19.85 84.4 18.62 71.7 15.80

8.6 7.5 103.8 22.25 94.1 19.99 87.6 18.53 87.6 18.53 87.6 18.53 84.4 17.43 71.7 14.82

11.2 10.0 103.8 19.64 94.1 17.70 87.6 16.44 87.6 16.44 87.6 16.44 84.4 15.56 71.7 13.28

16.4 15.0 103.8 14.96 94.1 13.61 87.6 12.70 87.6 12.70 87.6 12.70 84.4 12.23 71.7 10.54

24.0 18.0 103.8 13.17 94.1 12.02 87.6 11.26 87.6 11.26 87.6 11.26 84.4 10.88 71.7 9.40

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 67.6 21.75 62.2 20.15 58.4 19.07 58.4 19.07 58.4 19.07 53.8 18.03 46.4 16.08

-14.7 -15.0 71.8 22.29 66.1 20.65 62.2 19.54 62.2 19.54 62.2 19.54 57.4 18.44 49.6 16.39

-9.6 -10.0 76.9 23.00 71.0 21.33 66.8 20.17 66.8 20.17 66.8 20.17 61.9 18.98 53.6 16.81

-4.4 -5.0 83.8 23.94 77.3 22.20 72.9 21.00 72.9 21.00 72.9 21.00 67.9 19.73 58.8 17.40

-1.8 -2.5 88.0 24.36 81.3 22.57 76.8 21.35 76.8 21.35 76.8 21.35 71.6 20.08 62.3 17.71

0.8 0.0 92.1 24.36 86.1 22.97 81.3 21.73 81.3 21.73 81.3 21.73 76.0 20.39 64.6 17.45
120% 2.8 2.0 96.1 24.36 90.7 23.39 85.6 22.06 85.6 22.06 85.6 22.06 76.0 19.28 64.6 16.50

6.0 5.0 101.4 23.84 91.9 21.44 85.6 19.87 85.6 19.87 85.6 19.87 76.0 17.37 64.6 14.77

7.0 6.0 101.4 22.81 91.9 20.51 85.6 19.04 85.6 19.04 85.6 19.04 76.0 16.63 64.6 14.16

8.6 7.5 101.4 21.23 91.9 19.12 85.6 17.75 85.6 17.75 85.6 17.75 76.0 15.57 64.6 13.29

11.2 10.0 101.4 18.71 91.9 16.91 85.6 15.73 85.6 15.73 85.6 15.73 76.0 13.90 64.6 11.90

16.4 15.0 101.4 14.22 91.9 12.96 85.6 12.13 85.6 12.13 85.6 12.13 76.0 10.93 64.6 9.45

24.0 18.0 101.4 12.89 91.9 11.76 85.6 11.01 85.6 11.01 85.6 11.01 76.0 9.90 64.6 8.56

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 67.8 21.63 62.3 20.06 58.5 18.97 58.5 18.97 55.9 18.37 49.3 16.58 42.5 14.81

-14.7 -15.0 72.0 22.19 66.2 20.55 62.3 19.45 62.3 19.45 59.6 18.83 52.6 16.95 45.5 15.10

-9.6 -10.0 77.2 22.90 71.1 21.23 66.9 20.08 66.9 20.08 64.1 19.42 56.8 17.45 49.1 15.47

-4.4 -5.0 83.9 23.80 77.5 22.08 73.0 20.88 73.0 20.88 70.2 20.17 62.2 18.10 54.0 15.99

-1.8 -2.5 88.2 24.19 81.4 22.43 76.9 21.21 76.9 21.21 73.9 20.50 65.6 18.39 57.0 16.27

0.8 0.0 92.6 24.36 86.1 22.81 81.3 21.59 81.3 21.59 78.2 20.81 68.1 18.13 57.9 15.57

110% 2.8 2.0 96.6 24.36 89.7 22.81 83.5 21.16 83.5 21.16 78.2 19.66 68.1 17.14 57.9 14.72

6.0 5.0 99.0 22.74 89.7 20.50 83.5 19.04 83.5 19.04 78.2 17.70 68.1 15.42 57.9 13.15

7.0 6.0 99.0 21.75 89.7 19.61 83.5 18.22 83.5 18.22 78.2 16.97 68.1 14.77 57.9 12.62

8.6 7.5 99.0 20.22 89.7 18.27 83.5 17.00 83.5 17.00 78.2 15.85 68.1 13.83 57.9 11.85

11.2 10.0 99.0 17.80 89.7 16.13 83.5 15.05 83.5 15.05 78.2 14.09 68.1 12.34 57.9 10.61

16.4 15.0 99.0 13.47 89.7 12.34 83.5 11.57 83.5 11.57 78.2 10.96 68.1 9.71 57.9 8.44

24.0 18.0 99.0 12.60 89.7 11.50 83.5 10.79 83.5 10.79 78.2 10.16 68.1 8.96 57.9 7.76

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 68.0 21.51 62.4 19.96 58.7 18.90 54.8 17.82 50.9 16.74 44.9 15.14 38.7 13.57

-14.7 -15.0 72.1 22.06 66.3 20.46 62.3 19.38 58.4 18.27 54.2 17.16 47.9 15.47 41.3 13.82

-9.6 -10.0 77.3 22.79 71.2 21.14 67.1 20.01 62.8 18.86 58.4 17.68 51.7 15.92 44.7 14.15

-4.4 -5.0 84.1 23.65 77.6 21.94 73.1 20.76 68.5 19.56 63.8 18.34 56.6 16.50 49.0 14.60

-1.8 -2.5 88.3 24.01 81.6 22.29 76.9 21.09 72.1 19.87 67.2 18.62 59.7 16.74 51.3 14.69

0.8 0.0 93.2 24.36 86.3 22.65 81.5 21.47 75.5 19.85 69.4 18.29 60.4 15.99 51.3 13.80

100% 2.8 2.0 96.6 24.22 87.5 21.84 81.5 20.29 75.5 18.76 69.4 17.28 60.4 15.12 51.3 13.03

6.0 5.0 96.6 21.68 87.5 19.59 81.5 18.22 75.5 16.88 69.4 15.54 60.4 13.59 51.3 11.64

7.0 6.0 96.6 20.71 87.5 18.74 81.5 17.40 75.5 16.16 69.4 14.89 60.4 13.02 51.3 11.17

8.6 7.5 96.6 19.24 87.5 17.43 81.5 16.25 75.5 15.07 69.4 13.92 60.4 12.20 51.3 10.47

11.2 10.0 96.6 16.91 87.5 15.38 81.5 14.37 75.5 13.36 69.4 12.37 60.4 10.88 51.3 9.40

16.4 15.0 96.6 12.75 87.5 11.71 81.5 11.03 75.5 10.34 69.4 9.62 60.4 8.56 51.3 7.48

9 24.0 18.0 96.6 12.32 87.5 11.26 81.5 10.54 75.5 9.83 69.4 9.12 60.4 8.06 51.3 6.99
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, HIGH EFFICIENCY (Heating)


26 HP (U-8MF2E8 & U-8MF2E8 & U-10MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 68.9 21.18 63.2 19.70 59.3 18.71 55.4 17.70 51.4 16.69 45.2 15.19 39.0 13.71

-14.7 -15.0 73.1 21.77 67.2 20.24 63.1 19.21 58.9 18.15 54.7 17.09 48.2 15.50 41.6 13.92

-9.6 -10.0 78.4 22.52 72.0 20.93 67.7 19.84 63.3 18.72 58.8 17.61 51.9 15.90 44.8 14.20

-4.4 -5.0 85.2 23.18 78.4 21.56 73.4 20.27 67.9 18.90 62.5 17.54 54.4 15.56 46.2 13.62

-1.8 -2.5 87.0 22.59 78.8 20.55 73.4 19.21 67.9 17.90 62.5 16.62 54.4 14.74 46.2 12.89

0.8 0.0 87.0 21.16 78.8 19.26 73.4 18.03 67.9 16.81 62.5 15.61 54.4 13.83 46.2 12.09

90% 2.8 2.0 87.0 19.89 78.8 18.13 73.4 16.98 67.9 15.85 62.5 14.72 54.4 13.03 46.2 11.34

6.0 5.0 87.0 17.70 78.8 16.18 73.4 15.17 67.9 14.16 62.5 13.15 54.4 11.61 46.2 10.06

7.0 6.0 87.0 16.88 78.8 15.45 73.4 14.49 67.9 13.54 62.5 12.58 54.4 11.12 46.2 9.66

8.6 7.5 87.0 15.63 78.8 14.34 73.4 13.49 67.9 12.62 62.5 11.73 54.4 10.41 46.2 9.07

11.2 10.0 87.0 13.66 78.8 12.60 73.4 11.87 67.9 11.14 62.5 10.41 54.4 9.27 46.2 8.11

16.4 15.0 87.0 11.17 78.8 10.21 73.4 9.59 67.9 8.94 62.5 8.30 54.4 7.34 46.2 6.44

24.0 18.0 87.0 11.17 78.8 10.21 73.4 9.59 67.9 8.94 62.5 8.30 54.4 7.34 46.2 6.39

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 70.5 21.16 64.5 19.75 60.6 18.81 56.5 17.87 52.3 16.91 46.0 15.49 39.5 14.08

-14.7 -15.0 74.8 21.78 68.6 20.32 64.4 19.31 60.1 18.32 55.5 17.24 48.3 15.50 41.1 13.82

-9.6 -10.0 77.3 21.33 70.0 19.63 65.2 18.51 60.4 17.40 55.5 16.29 48.3 14.60 41.1 12.93

-4.4 -5.0 77.3 19.45 70.0 17.92 65.2 16.91 60.4 15.90 55.5 14.91 48.3 13.42 41.1 11.94

-1.8 -2.5 77.3 18.36 70.0 16.93 65.2 15.97 60.4 15.03 55.5 14.09 48.3 12.68 41.1 11.26

0.8 0.0 77.3 17.14 70.0 15.83 65.2 14.95 60.4 14.08 55.5 13.19 48.3 11.87 41.1 10.49

80% 2.8 2.0 77.3 16.04 70.0 14.84 65.2 14.04 60.4 13.22 55.5 12.39 48.3 11.14 41.1 9.73

6.0 5.0 77.3 14.20 70.0 13.17 65.2 12.46 60.4 11.73 55.5 10.98 48.3 9.81 41.1 8.61

7.0 6.0 77.3 13.50 70.0 12.55 65.2 11.87 60.4 11.19 55.5 10.49 48.3 9.40 41.1 8.27

8.6 7.5 77.3 12.46 70.0 11.61 65.2 11.01 60.4 10.41 55.5 9.76 48.3 8.79 41.1 7.74

11.2 10.0 77.3 10.81 70.0 10.13 65.2 9.66 60.4 9.15 55.5 8.63 48.3 7.81 41.1 6.93

16.4 15.0 77.3 10.04 70.0 9.19 65.2 8.61 60.4 8.06 55.5 7.48 48.3 6.63 41.1 5.78

24.0 18.0 77.3 10.04 70.0 9.19 65.2 8.61 60.4 8.06 55.5 7.48 48.3 6.63 41.1 5.78

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 67.6 19.64 61.3 18.25 57.1 17.33 52.8 16.41 48.6 15.50 42.3 14.18 35.9 12.84

-14.7 -15.0 67.6 18.55 61.3 17.33 57.1 16.50 52.8 15.64 48.6 14.74 42.3 13.42 35.9 12.08

-9.6 -10.0 67.6 17.23 61.3 16.10 57.1 15.35 52.8 14.60 48.6 13.83 42.3 12.63 35.9 11.29

-4.4 -5.0 67.6 15.63 61.3 14.63 57.1 13.95 52.8 13.28 48.6 12.56 42.3 11.48 35.9 10.35

-1.8 -2.5 67.6 14.69 61.3 13.76 57.1 13.14 52.8 12.49 48.6 11.85 42.3 10.82 35.9 9.71

0.8 0.0 67.6 13.64 61.3 12.81 57.1 12.23 52.8 11.64 48.6 11.03 42.3 10.07 35.9 8.87

70% 2.8 2.0 67.6 12.74 61.3 11.97 57.1 11.45 52.8 10.89 48.6 10.32 42.3 9.29 35.9 8.21

6.0 5.0 67.6 11.17 61.3 10.51 57.1 10.04 52.8 9.55 48.6 9.01 42.3 8.18 35.9 7.27

7.0 6.0 67.6 10.58 61.3 9.99 57.1 9.55 52.8 9.10 48.6 8.61 42.3 7.83 35.9 6.98

8.6 7.5 67.6 9.71 61.3 9.20 57.1 8.84 52.8 8.44 48.6 8.00 42.3 7.31 35.9 6.54

11.2 10.0 67.6 8.91 61.3 8.16 57.1 7.71 52.8 7.40 48.6 7.05 42.3 6.49 35.9 5.85

16.4 15.0 67.6 8.91 61.3 8.16 57.1 7.66 52.8 7.17 48.6 6.66 42.3 5.92 35.9 5.17

24.0 18.0 67.6 8.91 61.3 8.16 57.1 7.66 52.8 7.17 48.6 6.66 42.3 5.92 35.9 5.17

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 57.9 15.83 52.5 15.03 48.9 14.48 45.3 13.82 41.6 13.15 36.2 12.15 30.8 11.14

-14.7 -15.0 57.9 14.86 52.5 14.15 48.9 13.62 45.3 13.10 41.6 12.51 36.2 11.48 30.8 10.46

-9.6 -10.0 57.9 13.73 52.5 13.08 48.9 12.62 45.3 12.13 41.6 11.61 36.2 10.77 30.8 9.76

-4.4 -5.0 57.9 12.35 52.5 11.80 48.9 11.38 45.3 10.96 41.6 10.49 36.2 9.74 30.8 8.82

-1.8 -2.5 57.9 11.55 52.5 11.05 48.9 10.67 45.3 10.27 41.6 9.83 36.2 9.12 30.8 8.09

0.8 0.0 57.9 10.68 52.5 10.21 48.9 9.88 45.3 9.52 41.6 9.10 36.2 8.28 30.8 7.38

60% 2.8 2.0 57.9 9.92 52.5 9.50 48.9 9.19 45.3 8.79 41.6 8.35 36.2 7.62 30.8 6.84

6.0 5.0 57.9 8.56 52.5 8.21 48.9 7.93 45.3 7.62 41.6 7.27 36.2 6.70 30.8 6.06

7.0 6.0 57.9 8.09 52.5 7.78 48.9 7.53 45.3 7.26 41.6 6.94 36.2 6.40 30.8 5.81

8.6 7.5 57.9 7.76 52.5 7.15 48.9 6.94 45.3 6.72 41.6 6.44 36.2 5.99 30.8 5.45

11.2 10.0 57.9 7.76 52.5 7.13 48.9 6.70 45.3 6.28 41.6 5.85 36.2 5.31 30.8 4.87

16.4 15.0 57.9 7.76 52.5 7.13 48.9 6.70 45.3 6.28 41.6 5.85 36.2 5.20 30.8 4.58

24.0 18.0 57.9 7.76 52.5 7.13 48.9 6.70 45.3 6.28 41.6 5.85 36.2 5.20 30.8 4.58

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, HIGH EFFICIENCY (Heating)


26 HP (U-8MF2E8 & U-8MF2E8 & U-10MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 48.3 12.62 43.8 12.20 40.8 11.88 37.7 11.48 34.7 11.00 30.2 10.27 25.7 9.50

-14.7 -15.0 48.3 11.80 43.8 11.41 40.8 11.14 37.7 10.81 34.7 10.44 30.2 9.69 25.7 8.89

-9.6 -10.0 48.3 10.82 43.8 10.51 40.8 10.25 37.7 9.97 34.7 9.64 30.2 9.05 25.7 8.28

-4.4 -5.0 48.3 9.64 43.8 9.40 40.8 9.17 37.7 8.93 34.7 8.65 30.2 8.02 25.7 7.19

-1.8 -2.5 48.3 8.96 43.8 8.73 40.8 8.54 37.7 8.32 34.7 7.97 30.2 7.33 25.7 6.59

0.8 0.0 48.3 8.21 43.8 8.02 40.8 7.81 37.7 7.52 34.7 7.19 30.2 6.65 25.7 6.02

50% 2.8 2.0 48.3 7.55 43.8 7.31 40.8 7.10 37.7 6.87 34.7 6.59 30.2 6.12 25.7 5.57

6.0 5.0 48.3 6.63 43.8 6.23 40.8 6.11 37.7 5.93 34.7 5.74 30.2 5.38 25.7 4.94

7.0 6.0 48.3 6.63 43.8 6.09 40.8 5.79 37.7 5.64 34.7 5.46 30.2 5.15 25.7 4.73

8.6 7.5 48.3 6.63 43.8 6.09 40.8 5.74 37.7 5.39 34.7 5.08 30.2 4.80 25.7 4.44

11.2 10.0 48.3 6.63 43.8 6.09 40.8 5.74 37.7 5.39 34.7 5.03 30.2 4.51 25.7 3.98

16.4 15.0 48.3 6.63 43.8 6.09 40.8 5.74 37.7 5.39 34.7 5.03 30.2 4.51 25.7 3.97

24.0 18.0 48.3 6.63 43.8 6.09 40.8 5.74 37.7 5.39 34.7 5.03 30.2 4.51 25.7 3.97

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 38.6 9.94 35.0 9.76 32.6 9.59 30.2 9.34 27.8 9.01 24.1 8.47 20.5 7.90

-14.7 -15.0 38.6 9.24 35.0 9.10 32.6 8.96 30.2 8.77 27.8 8.53 24.1 7.99 20.5 7.38

-9.6 -10.0 38.6 8.42 35.0 8.32 32.6 8.21 30.2 8.04 27.8 7.83 24.1 7.38 20.5 6.63

-4.4 -5.0 38.6 7.41 35.0 7.36 32.6 7.27 30.2 7.03 27.8 6.73 24.1 6.25 20.5 5.67

-1.8 -2.5 38.6 6.84 35.0 6.72 32.6 6.54 30.2 6.35 27.8 6.12 24.1 5.71 20.5 5.22

0.8 0.0 38.6 6.09 35.0 5.97 32.6 5.85 30.2 5.71 27.8 5.52 24.1 5.19 20.5 4.77

40% 2.8 2.0 38.6 5.50 35.0 5.39 32.6 5.32 30.2 5.20 27.8 5.06 24.1 4.79 20.5 4.42

6.0 5.0 38.6 5.50 35.0 5.06 32.6 4.79 30.2 4.51 27.8 4.40 24.1 4.21 20.5 3.93

7.0 6.0 38.6 5.50 35.0 5.06 32.6 4.79 30.2 4.51 27.8 4.21 24.1 4.02 20.5 3.78

8.6 7.5 38.6 5.50 35.0 5.06 32.6 4.79 30.2 4.51 27.8 4.21 24.1 3.79 20.5 3.55

11.2 10.0 38.6 5.50 35.0 5.06 32.6 4.79 30.2 4.51 27.8 4.21 24.1 3.79 20.5 3.36

16.4 15.0 38.6 5.50 35.0 5.06 32.6 4.79 30.2 4.51 27.8 4.21 24.1 3.79 20.5 3.36

24.0 18.0 38.6 5.50 35.0 5.06 32.6 4.79 30.2 4.51 27.8 4.21 24.1 3.79 20.5 3.36

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 29.0 7.66 26.2 7.59 24.5 7.50 22.7 7.31 20.9 7.08 18.1 6.72 15.4 6.30

-14.7 -15.0 29.0 7.08 26.2 7.05 24.5 6.98 22.7 6.86 20.9 6.70 18.1 6.28 15.4 5.69

-9.6 -10.0 29.0 6.42 26.2 6.42 24.5 6.32 22.7 6.11 20.9 5.88 18.1 5.48 15.4 5.01

-4.4 -5.0 29.0 5.39 26.2 5.31 24.5 5.22 22.7 5.10 20.9 4.94 18.1 4.66 15.4 4.32

-1.8 -2.5 29.0 4.79 26.2 4.77 24.5 4.70 22.7 4.61 20.9 4.51 18.1 4.26 15.4 3.97

0.8 0.0 29.0 4.35 26.2 4.23 24.5 4.21 22.7 4.16 20.9 4.07 18.1 3.90 15.4 3.64

30% 2.8 2.0 29.0 4.35 26.2 4.04 24.5 3.83 22.7 3.79 20.9 3.74 18.1 3.60 15.4 3.39

6.0 5.0 29.0 4.35 26.2 4.04 24.5 3.83 22.7 3.62 20.9 3.39 18.1 3.18 15.4 3.03

7.0 6.0 29.0 4.35 26.2 4.04 24.5 3.83 22.7 3.62 20.9 3.39 18.1 3.08 15.4 2.92

8.6 7.5 29.0 4.35 26.2 4.04 24.5 3.83 22.7 3.62 20.9 3.39 18.1 3.08 15.4 2.77

11.2 10.0 29.0 4.35 26.2 4.04 24.5 3.83 22.7 3.62 20.9 3.39 18.1 3.08 15.4 2.77

16.4 15.0 29.0 4.35 26.2 4.04 24.5 3.83 22.7 3.62 20.9 3.39 18.1 3.08 15.4 2.77

24.0 18.0 29.0 4.35 26.2 4.04 24.5 3.83 22.7 3.62 20.9 3.39 18.1 3.08 15.4 2.77

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, HIGH EFFICIENCY (Heating)


28 HP (U-8MF2E8 & U-8MF2E8 & U-12MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 71.1 23.52 65.5 21.72 61.6 20.47 61.6 20.47 61.6 20.47 61.6 20.47 53.4 18.18

-14.7 -15.0 75.5 24.04 69.7 22.21 65.6 20.95 65.6 20.95 65.6 20.95 65.6 20.95 57.1 18.57

-9.6 -10.0 80.9 24.75 74.8 22.89 70.6 21.60 70.6 21.60 70.6 21.60 70.6 21.60 61.9 19.10

-4.4 -5.0 88.3 25.75 81.7 23.83 77.2 22.50 77.2 22.50 77.2 22.50 77.2 22.50 68.2 19.87

-1.8 -2.5 92.8 26.38 86.0 24.42 81.4 23.08 81.4 23.08 81.4 23.08 81.4 23.08 72.2 20.37

0.8 0.0 97.7 26.88 91.2 25.04 86.3 23.65 86.3 23.65 86.3 23.65 86.3 23.65 77.0 20.83

130% 2.8 2.0 101.9 26.88 96.1 25.52 91.1 24.15 91.1 24.15 91.1 24.15 90.6 23.33 77.0 19.74

6.0 5.0 109.6 26.88 101.1 24.79 94.1 22.85 94.1 22.85 94.1 22.85 90.6 21.10 77.0 17.80

7.0 6.0 111.5 26.67 101.1 23.77 94.1 21.93 94.1 21.93 94.1 21.93 90.6 20.26 77.0 17.11

8.6 7.5 111.5 24.90 101.1 22.23 94.1 20.51 94.1 20.51 94.1 20.51 90.6 19.01 77.0 16.07

11.2 10.0 111.5 22.06 101.1 19.76 94.1 18.26 94.1 18.26 94.1 18.26 90.6 16.99 77.0 14.42

16.4 15.0 111.5 16.99 101.1 15.32 94.1 14.23 94.1 14.23 94.1 14.23 90.6 13.44 77.0 11.52

24.0 18.0 111.5 14.38 101.1 13.04 94.1 12.17 94.1 12.17 94.1 12.17 90.6 11.64 77.0 10.02

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 71.3 23.33 65.6 21.54 61.7 20.33 61.7 20.33 61.7 20.33 57.0 18.99 49.3 16.82

-14.7 -15.0 75.6 23.85 69.7 22.04 65.6 20.81 65.6 20.81 65.6 20.81 60.8 19.43 52.7 17.18

-9.6 -10.0 81.1 24.58 74.9 22.73 70.6 21.47 70.6 21.47 70.6 21.47 65.8 20.04 57.1 17.66

-4.4 -5.0 88.4 25.57 81.8 23.67 77.3 22.37 77.3 22.37 77.3 22.37 72.3 20.85 62.8 18.34

-1.8 -2.5 92.9 26.21 86.1 24.27 81.4 22.92 81.4 22.92 81.4 22.92 76.3 21.39 66.4 18.80

0.8 0.0 98.3 26.82 91.2 24.83 86.3 23.46 86.3 23.46 86.3 23.46 81.4 21.91 69.4 18.70
120% 2.8 2.0 102.5 26.88 96.1 25.31 91.1 23.94 91.1 23.94 91.1 23.94 81.6 20.85 69.4 17.70

6.0 5.0 108.9 26.55 98.7 23.71 91.9 21.89 91.9 21.89 91.9 21.89 81.6 18.85 69.4 15.96

7.0 6.0 108.9 25.44 98.7 22.75 91.9 21.00 91.9 21.00 91.9 21.00 81.6 18.11 69.4 15.34

8.6 7.5 108.9 23.73 98.7 21.25 91.9 19.64 91.9 19.64 91.9 19.64 81.6 16.97 69.4 14.40

11.2 10.0 108.9 21.00 98.7 18.85 91.9 17.47 91.9 17.47 91.9 17.47 81.6 15.19 69.4 12.94

16.4 15.0 108.9 16.15 98.7 14.59 91.9 13.59 91.9 13.59 91.9 13.59 81.6 12.02 69.4 10.33

24.0 18.0 108.9 13.61 98.7 12.40 91.9 11.60 91.9 11.60 91.9 11.60 81.6 10.41 69.4 9.00

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 71.4 23.16 65.7 21.39 61.8 20.20 61.8 20.20 59.2 19.43 52.2 17.43 45.2 15.49

-14.7 -15.0 75.8 23.67 69.8 21.89 65.7 20.68 65.7 20.68 63.0 19.91 55.7 17.84 48.3 15.80

-9.6 -10.0 81.3 24.40 75.0 22.60 70.7 21.33 70.7 21.33 68.0 20.54 60.3 18.39 52.2 16.24

-4.4 -5.0 88.6 25.42 81.9 23.54 77.3 22.23 77.3 22.23 74.5 21.39 66.2 19.12 57.5 16.84

-1.8 -2.5 93.0 26.04 86.1 24.12 81.4 22.77 81.4 22.77 78.5 21.91 69.8 19.58 60.8 17.22

0.8 0.0 98.4 26.59 91.2 24.61 86.3 23.27 86.3 23.27 83.5 22.41 73.1 19.56 62.1 16.68

110% 2.8 2.0 103.1 26.88 96.2 25.09 89.7 23.25 89.7 23.25 84.0 21.41 73.1 18.53 62.1 15.80

6.0 5.0 106.3 25.32 96.3 22.68 89.7 20.97 89.7 20.97 84.0 19.33 73.1 16.74 62.1 14.23

7.0 6.0 106.3 24.25 96.3 21.73 89.7 20.12 89.7 20.12 84.0 18.57 73.1 16.07 62.1 13.67

8.6 7.5 106.3 22.60 96.3 20.29 89.7 18.80 89.7 18.80 84.0 17.38 73.1 15.07 62.1 12.84

11.2 10.0 106.3 19.99 96.3 17.99 89.7 16.70 89.7 16.70 84.0 15.49 73.1 13.50 62.1 11.54

16.4 15.0 106.3 15.30 96.3 13.88 89.7 12.96 89.7 12.96 84.0 12.15 73.1 10.68 62.1 9.24

24.0 18.0 106.3 13.19 96.3 12.06 89.7 11.31 89.7 11.31 84.0 10.68 73.1 9.43 62.1 8.18

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 71.6 22.96 65.8 21.25 61.9 20.06 57.9 18.89 53.8 17.68 47.5 15.90 41.0 14.17

-14.7 -15.0 76.0 23.52 69.9 21.77 65.8 20.56 61.6 19.33 57.3 18.11 50.8 16.26 43.8 14.44

-9.6 -10.0 81.5 24.25 75.2 22.46 70.8 21.22 66.3 19.97 61.8 18.68 54.8 16.74 47.4 14.82

-4.4 -5.0 88.6 25.27 82.0 23.39 77.4 22.10 72.5 20.79 67.6 19.45 60.0 17.41 52.2 15.34

-1.8 -2.5 93.2 25.86 86.2 23.94 81.4 22.62 76.4 21.25 71.3 19.87 63.4 17.80 55.1 15.67

0.8 0.0 98.4 26.36 91.3 24.42 86.3 23.08 81.0 21.68 74.6 19.87 64.8 17.26 55.1 14.78

100% 2.8 2.0 103.6 26.80 94.0 24.06 87.5 22.25 81.0 20.51 74.6 18.80 64.8 16.34 55.1 14.00

6.0 5.0 103.7 24.12 94.0 21.66 87.5 20.06 81.0 18.51 74.6 16.99 64.8 14.76 55.1 12.60

7.0 6.0 103.7 23.10 94.0 20.76 87.5 19.20 81.0 17.76 74.6 16.30 64.8 14.17 55.1 12.10

8.6 7.5 103.7 21.50 94.0 19.37 87.5 17.97 81.0 16.61 74.6 15.26 64.8 13.29 55.1 11.37

11.2 10.0 103.7 18.99 94.0 17.15 87.5 15.96 81.0 14.76 74.6 13.61 64.8 11.90 55.1 10.23

16.4 15.0 103.7 14.50 94.0 13.21 87.5 12.35 81.0 11.52 74.6 10.68 64.8 9.43 55.1 8.20

9 24.0 18.0 103.7 12.90 94.0 11.79 87.5 11.06 81.0 10.33 74.6 9.58 64.8 8.49 55.1 7.37
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, HIGH EFFICIENCY (Heating)


28 HP (U-8MF2E8 & U-8MF2E8 & U-12MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 72.4 22.41 66.4 20.77 62.4 19.68 58.3 18.57 54.2 17.47 47.7 15.80 41.1 14.19

-14.7 -15.0 76.7 23.00 70.5 21.31 66.3 20.18 62.0 19.03 57.7 17.88 50.8 16.15 43.9 14.44

-9.6 -10.0 82.3 23.77 75.8 22.04 71.3 20.85 66.7 19.64 62.0 18.43 54.9 16.59 47.4 14.76

-4.4 -5.0 89.5 24.73 82.5 22.92 77.7 21.68 72.8 20.41 67.1 18.89 58.4 16.63 49.6 14.44

-1.8 -2.5 93.4 24.92 84.6 22.52 78.8 20.97 72.9 19.43 67.1 17.95 58.4 15.80 49.6 13.75

0.8 0.0 93.4 23.39 84.6 21.16 78.8 19.70 72.9 18.28 67.1 16.90 58.4 14.88 49.6 12.92

90% 2.8 2.0 93.4 22.02 84.6 19.95 78.8 18.60 72.9 17.26 67.1 15.97 58.4 14.05 49.6 12.19

6.0 5.0 93.4 19.68 84.6 17.88 78.8 16.68 72.9 15.51 67.1 14.36 58.4 12.61 49.6 10.89

7.0 6.0 93.4 18.80 84.6 17.11 78.8 15.97 72.9 14.86 67.1 13.75 58.4 12.10 49.6 10.44

8.6 7.5 93.4 17.45 84.6 15.92 78.8 14.88 72.9 13.86 67.1 12.84 58.4 11.33 49.6 9.81

11.2 10.0 93.4 15.32 84.6 14.04 78.8 13.17 72.9 12.31 67.1 11.44 58.4 10.14 49.6 8.83

16.4 15.0 93.4 11.73 84.6 10.73 78.8 10.10 72.9 9.50 67.1 8.91 58.4 7.99 49.6 7.05

24.0 18.0 93.4 11.73 84.6 10.73 78.8 10.06 72.9 9.41 67.1 8.74 58.4 7.76 49.6 6.76

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 73.6 22.12 67.5 20.58 63.4 19.55 59.1 18.53 54.8 17.49 48.2 15.96 41.5 14.42

-14.7 -15.0 78.1 22.75 71.7 21.16 67.3 20.08 62.8 18.99 58.4 17.89 51.4 16.26 44.1 14.53

-9.6 -10.0 83.0 23.27 75.2 21.25 70.0 19.93 64.8 18.62 59.6 17.34 51.9 15.46 44.1 13.63

-4.4 -5.0 83.0 21.35 75.2 19.53 70.0 18.34 64.8 17.16 59.6 15.99 51.9 14.30 44.1 12.63

-1.8 -2.5 83.0 20.18 75.2 18.49 70.0 17.36 64.8 16.24 59.6 15.17 51.9 13.56 44.1 11.96

0.8 0.0 83.0 18.89 75.2 17.32 70.0 16.28 64.8 15.26 59.6 14.25 51.9 12.73 44.1 11.21

80% 2.8 2.0 83.0 17.74 75.2 16.28 70.0 15.32 64.8 14.36 59.6 13.42 51.9 11.98 44.1 10.48

6.0 5.0 83.0 15.76 75.2 14.52 70.0 13.69 64.8 12.83 59.6 11.98 51.9 10.66 44.1 9.31

7.0 6.0 83.0 15.03 75.2 13.86 70.0 13.08 64.8 12.27 59.6 11.44 51.9 10.21 44.1 8.93

8.6 7.5 83.0 13.90 75.2 12.86 70.0 12.15 64.8 11.42 59.6 10.69 51.9 9.56 44.1 8.39

11.2 10.0 83.0 12.13 75.2 11.27 70.0 10.69 64.8 10.10 59.6 9.48 51.9 8.52 44.1 7.55

16.4 15.0 83.0 10.54 75.2 9.66 70.0 9.08 64.8 8.49 59.6 7.89 51.9 7.01 44.1 6.12

24.0 18.0 83.0 10.54 75.2 9.66 70.0 9.08 64.8 8.49 59.6 7.89 51.9 7.01 44.1 6.12

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 72.6 21.10 65.8 19.51 61.3 18.45 56.7 17.41 52.2 16.42 45.4 14.92 38.6 13.46

-14.7 -15.0 72.6 20.10 65.8 18.62 61.3 17.61 56.7 16.61 52.2 15.61 45.4 14.13 38.6 12.67

-9.6 -10.0 72.6 18.74 65.8 17.38 61.3 16.49 56.7 15.59 52.2 14.71 45.4 13.32 38.6 11.88

-4.4 -5.0 72.6 17.07 65.8 15.86 61.3 15.05 56.7 14.25 52.2 13.42 45.4 12.19 38.6 10.94

-1.8 -2.5 72.6 16.07 65.8 14.96 61.3 14.21 56.7 13.44 52.2 12.69 45.4 11.52 38.6 10.33

0.8 0.0 72.6 14.98 65.8 13.96 61.3 13.27 56.7 12.58 52.2 11.87 45.4 10.77 38.6 9.54

70% 2.8 2.0 72.6 14.02 65.8 13.09 61.3 12.44 56.7 11.81 52.2 11.14 45.4 10.06 38.6 8.85

6.0 5.0 72.6 12.38 65.8 11.58 61.3 11.02 56.7 10.44 52.2 9.83 45.4 8.87 38.6 7.87

7.0 6.0 72.6 11.77 65.8 11.02 61.3 10.50 56.7 9.96 52.2 9.39 45.4 8.51 38.6 7.55

8.6 7.5 72.6 10.85 65.8 10.20 61.3 9.73 56.7 9.25 52.2 8.76 45.4 7.95 38.6 7.08

11.2 10.0 72.6 9.39 65.8 8.89 61.3 8.54 56.7 8.16 52.2 7.74 45.4 7.08 38.6 6.36

16.4 15.0 72.6 9.37 65.8 8.60 61.3 8.08 56.7 7.56 52.2 7.05 45.4 6.28 38.6 5.51

24.0 18.0 72.6 9.37 65.8 8.60 61.3 8.08 56.7 7.56 52.2 7.05 45.4 6.28 38.6 5.51

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 62.2 16.99 56.4 16.01 52.5 15.30 48.7 14.57 44.7 13.84 38.9 12.75 33.1 11.64

-14.7 -15.0 62.2 15.99 56.4 15.11 52.5 14.50 48.7 13.86 44.7 13.17 38.9 12.08 33.1 10.94

-9.6 -10.0 62.2 14.82 56.4 14.02 52.5 13.46 48.7 12.88 44.7 12.29 38.9 11.35 33.1 10.25

-4.4 -5.0 62.2 13.40 56.4 12.69 52.5 12.21 48.7 11.69 44.7 11.16 38.9 10.31 33.1 9.37

-1.8 -2.5 62.2 12.58 56.4 11.92 52.5 11.48 48.7 11.00 44.7 10.50 38.9 9.70 33.1 8.68

0.8 0.0 62.2 11.67 56.4 11.08 52.5 10.68 48.7 10.23 44.7 9.77 38.9 8.93 33.1 7.95

60% 2.8 2.0 62.2 10.87 56.4 10.35 52.5 9.96 48.7 9.56 44.7 9.06 38.9 8.24 33.1 7.37

6.0 5.0 62.2 9.48 56.4 9.04 52.5 8.70 48.7 8.33 44.7 7.93 38.9 7.28 33.1 6.55

7.0 6.0 62.2 8.99 56.4 8.58 52.5 8.28 48.7 7.93 44.7 7.56 38.9 6.97 33.1 6.28

8.6 7.5 62.2 8.24 56.4 7.91 52.5 7.66 48.7 7.37 44.7 7.05 38.9 6.51 33.1 5.91

11.2 10.0 62.2 8.20 56.4 7.53 52.5 7.08 48.7 6.64 44.7 6.22 38.9 5.80 33.1 5.30

16.4 15.0 62.2 8.20 56.4 7.53 52.5 7.08 48.7 6.64 44.7 6.20 38.9 5.55 33.1 4.88

24.0 18.0 62.2 8.20 56.4 7.53 52.5 7.08 48.7 6.64 44.7 6.20 38.9 5.55 33.1 4.88

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, HIGH EFFICIENCY (Heating)


28 HP (U-8MF2E8 & U-8MF2E8 & U-12MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 51.9 13.40 47.0 12.90 43.8 12.52 40.5 12.06 37.3 11.54 32.4 10.75 27.6 9.93

-14.7 -15.0 51.9 12.58 47.0 12.10 43.8 11.77 40.5 11.39 37.3 10.96 32.4 10.16 27.6 9.31

-9.6 -10.0 51.9 11.58 47.0 11.17 43.8 10.87 40.5 10.52 37.3 10.16 32.4 9.52 27.6 8.70

-4.4 -5.0 51.9 10.39 47.0 10.04 43.8 9.77 40.5 9.48 37.3 9.16 32.4 8.58 27.6 7.70

-1.8 -2.5 51.9 9.68 47.0 9.39 43.8 9.14 40.5 8.87 37.3 8.58 32.4 7.87 27.6 7.08

0.8 0.0 51.9 8.93 47.0 8.66 43.8 8.45 40.5 8.16 37.3 7.78 32.4 7.16 27.6 6.47

50% 2.8 2.0 51.9 8.26 47.0 8.01 43.8 7.76 40.5 7.47 37.3 7.16 32.4 6.62 27.6 6.01

6.0 5.0 51.9 7.07 47.0 6.87 43.8 6.70 40.5 6.49 37.3 6.26 32.4 5.84 27.6 5.36

7.0 6.0 51.9 7.01 47.0 6.51 43.8 6.36 40.5 6.18 37.3 5.97 32.4 5.59 27.6 5.15

8.6 7.5 51.9 7.01 47.0 6.47 43.8 6.09 40.5 5.72 37.3 5.55 32.4 5.24 27.6 4.84

11.2 10.0 51.9 7.01 47.0 6.47 43.8 6.09 40.5 5.72 37.3 5.36 32.4 4.80 27.6 4.34

16.4 15.0 51.9 7.01 47.0 6.47 43.8 6.09 40.5 5.72 37.3 5.36 32.4 4.80 27.6 4.24

24.0 18.0 51.9 7.01 47.0 6.47 43.8 6.09 40.5 5.72 37.3 5.36 32.4 4.80 27.6 4.24

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 41.5 10.48 37.6 10.25 35.0 10.06 32.4 9.79 29.8 9.43 25.9 8.87 22.1 8.26

-14.7 -15.0 41.5 9.77 37.6 9.58 35.0 9.41 32.4 9.20 29.8 8.95 25.9 8.37 22.1 7.74

-9.6 -10.0 41.5 8.95 37.6 8.79 35.0 8.66 32.4 8.47 29.8 8.26 25.9 7.81 22.1 7.08

-4.4 -5.0 41.5 7.93 37.6 7.83 35.0 7.72 32.4 7.58 29.8 7.26 25.9 6.72 22.1 6.11

-1.8 -2.5 41.5 7.33 37.6 7.26 35.0 7.10 32.4 6.87 29.8 6.60 25.9 6.14 22.1 5.63

0.8 0.0 41.5 6.66 37.6 6.51 35.0 6.37 32.4 6.20 29.8 5.99 25.9 5.61 22.1 5.15

40% 2.8 2.0 41.5 6.01 37.6 5.91 35.0 5.82 32.4 5.66 29.8 5.51 25.9 5.18 22.1 4.78

6.0 5.0 41.5 5.84 37.6 5.40 35.0 5.11 32.4 4.93 29.8 4.82 25.9 4.59 22.1 4.28

7.0 6.0 41.5 5.84 37.6 5.40 35.0 5.11 32.4 4.80 29.8 4.59 25.9 4.40 22.1 4.11

8.6 7.5 41.5 5.84 37.6 5.40 35.0 5.11 32.4 4.80 29.8 4.51 25.9 4.11 22.1 3.88

11.2 10.0 41.5 5.84 37.6 5.40 35.0 5.11 32.4 4.80 29.8 4.51 25.9 4.07 22.1 3.63

16.4 15.0 41.5 5.84 37.6 5.40 35.0 5.11 32.4 4.80 29.8 4.51 25.9 4.07 22.1 3.63

24.0 18.0 41.5 5.84 37.6 5.40 35.0 5.11 32.4 4.80 29.8 4.51 25.9 4.07 22.1 3.63

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 31.2 8.03 28.2 7.95 26.3 7.85 24.3 7.68 22.4 7.43 19.4 7.05 16.5 6.62

-14.7 -15.0 31.2 7.45 28.2 7.41 26.3 7.33 24.3 7.22 22.4 7.05 19.4 6.62 16.5 6.09

-9.6 -10.0 31.2 6.78 28.2 6.78 26.3 6.72 24.3 6.57 22.4 6.32 19.4 5.89 16.5 5.38

-4.4 -5.0 31.2 5.86 28.2 5.76 26.3 5.64 24.3 5.51 22.4 5.34 19.4 5.03 16.5 4.65

-1.8 -2.5 31.2 5.24 28.2 5.18 26.3 5.11 24.3 5.01 22.4 4.88 19.4 4.63 16.5 4.30

0.8 0.0 31.2 4.67 28.2 4.63 26.3 4.59 24.3 4.51 22.4 4.42 19.4 4.22 16.5 3.96

30% 2.8 2.0 31.2 4.67 28.2 4.32 26.3 4.19 24.3 4.15 22.4 4.07 19.4 3.92 16.5 3.69

6.0 5.0 31.2 4.67 28.2 4.32 26.3 4.11 24.3 3.88 22.4 3.67 19.4 3.49 16.5 3.32

7.0 6.0 31.2 4.67 28.2 4.32 26.3 4.11 24.3 3.88 22.4 3.67 19.4 3.34 16.5 3.21

8.6 7.5 31.2 4.67 28.2 4.32 26.3 4.11 24.3 3.88 22.4 3.67 19.4 3.34 16.5 3.03

11.2 10.0 31.2 4.67 28.2 4.32 26.3 4.11 24.3 3.88 22.4 3.67 19.4 3.34 16.5 3.00

16.4 15.0 31.2 4.67 28.2 4.32 26.3 4.11 24.3 3.88 22.4 3.67 19.4 3.34 16.5 3.00

24.0 18.0 31.2 4.67 28.2 4.32 26.3 4.11 24.3 3.88 22.4 3.67 19.4 3.34 16.5 3.00

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, HIGH EFFICIENCY (Heating)


30 HP (U-8MF2E8 & U-8MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 75.1 24.55 69.2 22.71 65.1 21.42 65.1 21.42 65.1 21.42 65.1 21.42 56.4 19.11

-14.7 -15.0 79.7 25.07 73.5 23.20 69.3 21.92 69.3 21.92 69.3 21.92 69.3 21.92 60.4 19.52

-9.6 -10.0 85.5 25.79 79.0 23.91 74.6 22.60 74.6 22.60 74.6 22.60 74.6 22.60 65.5 20.08

-4.4 -5.0 93.2 26.81 86.4 24.88 81.6 23.54 81.6 23.54 81.6 23.54 81.6 23.54 72.1 20.89

-1.8 -2.5 96.7 26.91 90.9 25.48 86.0 24.12 86.0 24.12 86.0 24.12 86.0 24.12 76.4 21.38

0.8 0.0 101.4 26.91 96.3 26.02 91.2 24.61 91.2 24.61 91.2 24.61 91.2 24.61 81.8 21.92

130% 2.8 2.0 105.8 26.91 101.6 26.45 96.3 25.07 96.3 25.07 96.3 25.07 96.3 25.07 83.6 21.32

6.0 5.0 114.3 26.91 109.7 26.66 102.1 24.59 102.1 24.59 102.1 24.59 98.3 22.77 83.6 19.25

7.0 6.0 117.2 26.91 109.7 25.59 102.1 23.62 102.1 23.62 102.1 23.62 98.3 21.88 83.6 18.51

8.6 7.5 121.0 26.74 109.7 23.91 102.1 22.09 102.1 22.09 102.1 22.09 98.3 20.51 83.6 17.39

11.2 10.0 121.0 23.68 109.7 21.24 102.1 19.67 102.1 19.67 102.1 19.67 98.3 18.36 83.6 15.61

16.4 15.0 121.0 18.24 109.7 16.48 102.1 15.32 102.1 15.32 102.1 15.32 98.3 14.53 83.6 12.48

24.0 18.0 121.0 15.40 109.7 14.01 102.1 13.10 102.1 13.10 102.1 13.10 98.3 12.56 83.6 10.89

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 75.3 24.34 69.3 22.52 65.2 21.28 65.2 21.28 65.2 21.28 60.2 19.93 52.1 17.70

-14.7 -15.0 79.9 24.88 73.6 23.04 69.4 21.78 69.4 21.78 69.4 21.78 64.3 20.41 55.7 18.07

-9.6 -10.0 85.7 25.61 79.1 23.74 74.7 22.46 74.7 22.46 74.7 22.46 69.5 21.03 60.3 18.59

-4.4 -5.0 93.4 26.64 86.5 24.72 81.6 23.39 81.6 23.39 81.6 23.39 76.4 21.88 66.4 19.29

-1.8 -2.5 97.3 26.91 91.0 25.30 86.0 23.93 86.0 23.93 86.0 23.93 80.8 22.38 70.3 19.73

0.8 0.0 101.9 26.91 96.3 25.77 91.2 24.38 91.2 24.38 91.2 24.38 86.1 22.89 75.3 20.20
120% 2.8 2.0 106.4 26.91 101.6 26.21 96.2 24.84 96.2 24.84 96.2 24.84 88.6 22.52 75.3 19.17

6.0 5.0 114.7 26.91 107.2 25.52 99.8 23.60 99.8 23.60 99.8 23.60 88.6 20.37 75.3 17.28

7.0 6.0 117.2 26.91 107.2 24.49 99.8 22.63 99.8 22.63 99.8 22.63 88.6 19.56 75.3 16.60

8.6 7.5 118.2 25.50 107.2 22.87 99.8 21.16 99.8 21.16 99.8 21.16 88.6 18.34 75.3 15.61

11.2 10.0 118.2 22.56 107.2 20.29 99.8 18.82 99.8 18.82 99.8 18.82 88.6 16.42 75.3 14.03

16.4 15.0 118.2 17.31 107.2 15.69 99.8 14.63 99.8 14.63 99.8 14.63 88.6 13.00 75.3 11.22

24.0 18.0 118.2 14.70 107.2 13.46 99.8 12.63 99.8 12.63 99.8 12.63 88.6 11.36 75.3 9.87

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 75.4 24.16 69.4 22.38 65.3 21.13 65.3 21.13 62.5 20.39 55.2 18.32 47.7 16.31

-14.7 -15.0 80.0 24.70 73.7 22.89 69.4 21.65 69.4 21.65 66.6 20.87 58.9 18.73 51.0 16.64

-9.6 -10.0 85.9 25.46 79.2 23.60 74.7 22.31 74.7 22.31 71.8 21.53 63.7 19.31 55.2 17.10

-4.4 -5.0 93.5 26.48 86.5 24.57 81.7 23.25 81.7 23.25 78.8 22.42 69.9 20.08 60.8 17.72

-1.8 -2.5 97.9 26.91 91.0 25.09 86.0 23.74 86.0 23.74 83.0 22.87 73.9 20.49 64.3 18.09

0.8 0.0 102.5 26.91 96.4 25.56 91.2 24.18 91.2 24.18 88.3 23.35 78.8 20.95 67.5 18.07

110% 2.8 2.0 107.1 26.91 101.6 25.98 96.2 24.63 96.2 24.63 91.2 23.10 79.3 20.04 67.5 17.12

6.0 5.0 114.7 26.91 104.6 24.41 97.4 22.60 97.4 22.60 91.2 20.89 79.3 18.11 67.5 15.42

7.0 6.0 115.4 26.06 104.6 23.41 97.4 21.67 97.4 21.67 91.2 20.04 79.3 17.39 67.5 14.82

8.6 7.5 115.4 24.30 104.6 21.84 97.4 20.27 97.4 20.27 91.2 18.75 79.3 16.31 67.5 13.93

11.2 10.0 115.4 21.47 104.6 19.35 97.4 17.99 97.4 17.99 91.2 16.73 79.3 14.61 67.5 12.52

16.4 15.0 115.4 16.42 104.6 14.95 97.4 13.97 97.4 13.97 91.2 13.12 79.3 11.57 67.5 10.04

24.0 18.0 115.4 14.39 104.6 13.17 97.4 12.36 97.4 12.36 91.2 11.65 79.3 10.33 67.5 8.98

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 75.6 23.99 69.5 22.21 65.4 21.01 61.2 19.79 56.8 18.57 50.3 16.73 43.3 14.92

-14.7 -15.0 80.2 24.53 73.9 22.75 69.5 21.51 65.1 20.27 60.6 19.00 53.6 17.10 46.4 15.24

-9.6 -10.0 86.0 25.30 79.3 23.45 74.8 22.19 70.1 20.91 65.4 19.60 57.9 17.62 50.2 15.63

-4.4 -5.0 93.7 26.33 86.6 24.43 81.7 23.10 76.7 21.76 71.5 20.39 63.6 18.30 55.2 16.17

-1.8 -2.5 98.4 26.83 91.1 24.90 86.1 23.56 80.8 22.19 75.4 20.78 67.1 18.65 58.3 16.50

0.8 0.0 103.2 26.91 96.4 25.34 91.2 23.99 85.8 22.60 80.2 21.20 70.4 18.67 59.9 16.02

100% 2.8 2.0 107.6 26.91 101.7 25.77 95.0 23.99 88.0 22.13 80.9 20.31 70.4 17.70 59.9 15.17

6.0 5.0 112.6 25.94 102.0 23.33 95.0 21.63 88.0 19.98 80.9 18.36 70.4 15.98 59.9 13.66

7.0 6.0 112.6 24.84 102.0 22.36 95.0 20.70 88.0 19.17 80.9 17.62 70.4 15.36 59.9 13.14

8.6 7.5 112.6 23.12 102.0 20.84 95.0 19.38 88.0 17.93 80.9 16.50 70.4 14.41 59.9 12.36

11.2 10.0 112.6 20.41 102.0 18.46 95.0 17.20 88.0 15.94 80.9 14.72 70.4 12.90 59.9 11.12

16.4 15.0 112.6 15.57 102.0 14.22 95.0 13.33 88.0 12.44 80.9 11.55 70.4 10.25 59.9 8.94

9 24.0 18.0 112.6 14.08 102.0 12.88 95.0 12.09 88.0 11.30 80.9 10.49 70.4 9.32 59.9 8.11
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, HIGH EFFICIENCY (Heating)


30 HP (U-8MF2E8 & U-8MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 76.4 23.37 70.1 21.71 65.9 20.60 61.6 19.46 57.2 18.32 50.4 16.62 43.4 14.95

-14.7 -15.0 81.0 23.97 74.5 22.27 70.1 21.11 65.6 19.93 60.9 18.75 53.8 16.97 46.4 15.19

-9.6 -10.0 86.8 24.76 80.0 23.00 75.2 21.80 70.5 20.56 65.6 19.31 58.0 17.43 50.1 15.55

-4.4 -5.0 94.5 25.65 87.1 23.83 82.1 22.58 77.0 21.30 71.6 20.00 63.4 18.01 53.9 15.67

-1.8 -2.5 99.2 26.04 91.6 24.18 85.5 22.63 79.1 20.99 72.9 19.42 63.4 17.12 53.9 14.90

0.8 0.0 101.4 25.19 91.9 22.81 85.5 21.26 79.1 19.75 72.9 18.28 63.4 16.13 53.9 14.03

90% 2.8 2.0 101.4 23.72 91.9 21.51 85.5 20.08 79.1 18.67 72.9 17.28 63.4 15.24 53.9 13.25

6.0 5.0 101.4 21.20 91.9 19.29 85.5 18.03 79.1 16.79 72.9 15.55 63.4 13.70 53.9 11.84

7.0 6.0 101.4 20.24 91.9 18.44 85.5 17.26 79.1 16.06 72.9 14.88 63.4 13.12 53.9 11.39

8.6 7.5 101.4 18.80 91.9 17.16 85.5 16.08 79.1 15.01 72.9 13.93 63.4 12.32 53.9 10.70

11.2 10.0 101.4 16.50 91.9 15.13 85.5 14.22 79.1 13.31 72.9 12.40 63.4 11.01 53.9 9.63

16.4 15.0 101.4 12.79 91.9 11.74 85.5 11.01 79.1 10.31 72.9 9.67 63.4 8.71 53.9 7.72

24.0 18.0 101.4 12.79 91.9 11.74 85.5 11.01 79.1 10.31 72.9 9.58 63.4 8.53 53.9 7.45

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 77.7 23.06 71.3 21.51 66.8 20.43 62.4 19.38 57.9 18.32 50.9 16.73 43.8 15.15

-14.7 -15.0 82.5 23.70 75.6 22.07 71.1 20.97 66.4 19.85 61.6 18.73 54.2 17.06 46.7 15.36

-9.6 -10.0 88.4 24.47 81.2 22.81 76.0 21.55 70.4 20.16 64.7 18.77 56.3 16.77 47.9 14.80

-4.4 -5.0 90.1 23.02 81.6 21.09 76.0 19.81 70.4 18.57 64.7 17.33 56.3 15.50 47.9 13.72

-1.8 -2.5 90.1 21.78 81.6 19.95 76.0 18.77 70.4 17.60 64.7 16.42 56.3 14.70 47.9 13.00

0.8 0.0 90.1 20.39 81.6 18.71 76.0 17.62 70.4 16.52 64.7 15.42 56.3 13.81 47.9 12.19

80% 2.8 2.0 90.1 19.15 81.6 17.60 76.0 16.58 70.4 15.57 64.7 14.55 56.3 13.02 47.9 11.43

6.0 5.0 90.1 17.02 81.6 15.69 76.0 14.80 70.4 13.91 64.7 13.00 56.3 11.59 47.9 10.16

7.0 6.0 90.1 16.23 81.6 14.99 76.0 14.14 70.4 13.29 64.7 12.44 56.3 11.12 47.9 9.75

8.6 7.5 90.1 15.01 81.6 13.91 76.0 13.17 70.4 12.40 64.7 11.61 56.3 10.41 47.9 9.17

11.2 10.0 90.1 13.10 81.6 12.21 76.0 11.59 70.4 10.97 64.7 10.31 56.3 9.29 47.9 8.26

16.4 15.0 90.1 11.53 81.6 10.58 76.0 9.96 70.4 9.32 64.7 8.67 56.3 7.72 47.9 6.77

24.0 18.0 90.1 11.53 81.6 10.58 76.0 9.96 70.4 9.32 64.7 8.67 56.3 7.72 47.9 6.77

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 78.9 22.79 71.4 21.09 66.5 19.98 61.6 18.86 56.6 17.76 49.3 16.17 41.9 14.59

-14.7 -15.0 78.9 21.71 71.4 20.14 66.5 19.06 61.6 17.99 56.6 16.91 49.3 15.34 41.9 13.77

-9.6 -10.0 78.9 20.22 71.4 18.80 66.5 17.84 61.6 16.89 56.6 15.94 49.3 14.47 41.9 12.92

-4.4 -5.0 78.9 18.44 71.4 17.16 66.5 16.29 61.6 15.42 56.6 14.55 49.3 13.25 41.9 11.90

-1.8 -2.5 78.9 17.39 71.4 16.19 66.5 15.38 61.6 14.57 56.6 13.77 49.3 12.52 41.9 11.24

0.8 0.0 78.9 16.21 71.4 15.11 66.5 14.39 61.6 13.64 56.6 12.88 49.3 11.72 41.9 10.43

70% 2.8 2.0 78.9 15.17 71.4 14.18 66.5 13.50 61.6 12.81 56.6 12.11 49.3 10.95 41.9 9.69

6.0 5.0 78.9 13.39 71.4 12.56 66.5 11.96 61.6 11.34 56.6 10.70 49.3 9.69 41.9 8.61

7.0 6.0 78.9 12.73 71.4 11.96 66.5 11.41 61.6 10.83 56.6 10.23 49.3 9.27 41.9 8.28

8.6 7.5 78.9 11.74 71.4 11.07 66.5 10.60 61.6 10.08 56.6 9.54 49.3 8.69 41.9 7.78

11.2 10.0 78.9 10.27 71.4 9.67 66.5 9.29 61.6 8.88 56.6 8.47 49.3 7.76 41.9 7.00

16.4 15.0 78.9 10.27 71.4 9.44 66.5 8.88 61.6 8.32 56.6 7.76 49.3 6.93 41.9 6.11

24.0 18.0 78.9 10.27 71.4 9.44 66.5 8.88 61.6 8.32 56.6 7.76 49.3 6.93 41.9 6.11

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 67.5 18.36 61.2 17.33 57.0 16.58 52.8 15.79 48.5 15.01 42.2 13.83 35.9 12.65

-14.7 -15.0 67.5 17.31 61.2 16.35 57.0 15.69 52.8 15.03 48.5 14.30 42.2 13.12 35.9 11.92

-9.6 -10.0 67.5 16.04 61.2 15.17 57.0 14.59 52.8 13.97 48.5 13.35 42.2 12.34 35.9 11.18

-4.4 -5.0 67.5 14.53 61.2 13.77 57.0 13.25 52.8 12.69 48.5 12.13 42.2 11.22 35.9 10.23

-1.8 -2.5 67.5 13.64 61.2 12.94 57.0 12.46 52.8 11.94 48.5 11.43 42.2 10.56 35.9 9.50

0.8 0.0 67.5 12.65 61.2 12.05 57.0 11.59 52.8 11.14 48.5 10.64 42.2 9.75 35.9 8.71

60% 2.8 2.0 67.5 11.80 61.2 11.24 57.0 10.83 52.8 10.41 48.5 9.87 42.2 9.03 35.9 8.09

6.0 5.0 67.5 10.31 61.2 9.83 57.0 9.48 52.8 9.09 48.5 8.67 42.2 7.97 35.9 7.20

7.0 6.0 67.5 9.77 61.2 9.36 57.0 9.03 52.8 8.67 48.5 8.28 42.2 7.64 35.9 6.91

8.6 7.5 67.5 9.00 61.2 8.63 57.0 8.36 52.8 8.05 48.5 7.72 42.2 7.16 35.9 6.50

11.2 10.0 67.5 9.00 61.2 8.28 57.0 7.80 52.8 7.33 48.5 6.85 42.2 6.38 35.9 5.86

16.4 15.0 67.5 9.00 61.2 8.28 57.0 7.80 52.8 7.33 48.5 6.85 42.2 6.15 35.9 5.42

24.0 18.0 67.5 9.00 61.2 8.28 57.0 7.80 52.8 7.33 48.5 6.85 42.2 6.15 35.9 5.42

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, HIGH EFFICIENCY (Heating)


30 HP (U-8MF2E8 & U-8MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 56.3 14.53 51.0 13.99 47.5 13.58 44.0 13.10 40.5 12.54 35.2 11.70 29.9 10.81

-14.7 -15.0 56.3 13.62 51.0 13.14 47.5 12.77 44.0 12.38 40.5 11.92 35.2 11.07 29.9 10.16

-9.6 -10.0 56.3 12.56 51.0 12.15 47.5 11.82 44.0 11.45 40.5 11.05 35.2 10.37 29.9 9.52

-4.4 -5.0 56.3 11.28 51.0 10.93 47.5 10.64 44.0 10.33 40.5 9.98 35.2 9.38 29.9 8.45

-1.8 -2.5 56.3 10.54 51.0 10.23 47.5 9.96 44.0 9.69 40.5 9.36 35.2 8.63 29.9 7.78

0.8 0.0 56.3 9.73 51.0 9.44 47.5 9.21 44.0 8.92 40.5 8.53 35.2 7.87 29.9 7.14

50% 2.8 2.0 56.3 9.00 51.0 8.74 47.5 8.49 44.0 8.18 40.5 7.85 35.2 7.29 29.9 6.62

6.0 5.0 56.3 7.72 51.0 7.51 47.5 7.35 44.0 7.14 40.5 6.89 35.2 6.44 29.9 5.92

7.0 6.0 56.3 7.72 51.0 7.14 47.5 6.98 44.0 6.79 40.5 6.58 35.2 6.17 29.9 5.69

8.6 7.5 56.3 7.72 51.0 7.12 47.5 6.73 44.0 6.33 40.5 6.13 35.2 5.80 29.9 5.36

11.2 10.0 56.3 7.72 51.0 7.12 47.5 6.73 44.0 6.33 40.5 5.94 35.2 5.34 29.9 4.84

16.4 15.0 56.3 7.72 51.0 7.12 47.5 6.73 44.0 6.33 40.5 5.94 35.2 5.34 29.9 4.76

24.0 18.0 56.3 7.72 51.0 7.12 47.5 6.73 44.0 6.33 40.5 5.94 35.2 5.34 29.9 4.76

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 45.0 11.39 40.9 11.16 38.0 10.95 35.2 10.68 32.4 10.29 28.1 9.69 23.9 9.03

-14.7 -15.0 45.0 10.64 40.9 10.43 38.0 10.27 35.2 10.04 32.4 9.75 28.1 9.15 23.9 8.49

-9.6 -10.0 45.0 9.73 40.9 9.58 38.0 9.44 35.2 9.25 32.4 9.03 28.1 8.57 23.9 7.78

-4.4 -5.0 45.0 8.65 40.9 8.55 38.0 8.45 35.2 8.28 32.4 7.97 28.1 7.39 23.9 6.73

-1.8 -2.5 45.0 8.03 40.9 7.95 38.0 7.78 35.2 7.56 32.4 7.27 28.1 6.79 23.9 6.21

0.8 0.0 45.0 7.33 40.9 7.16 38.0 7.02 35.2 6.81 32.4 6.60 28.1 6.19 23.9 5.71

40% 2.8 2.0 45.0 6.60 40.9 6.52 38.0 6.40 35.2 6.25 32.4 6.09 28.1 5.73 23.9 5.32

6.0 5.0 45.0 6.46 40.9 5.98 38.0 5.67 35.2 5.46 32.4 5.34 28.1 5.09 23.9 4.76

7.0 6.0 45.0 6.46 40.9 5.98 38.0 5.67 35.2 5.34 32.4 5.11 28.1 4.89 23.9 4.60

8.6 7.5 45.0 6.46 40.9 5.98 38.0 5.67 35.2 5.34 32.4 5.03 28.1 4.60 23.9 4.33

11.2 10.0 45.0 6.46 40.9 5.98 38.0 5.67 35.2 5.34 32.4 5.03 28.1 4.55 23.9 4.08

16.4 15.0 45.0 6.46 40.9 5.98 38.0 5.67 35.2 5.34 32.4 5.03 28.1 4.55 23.9 4.08

24.0 18.0 45.0 6.46 40.9 5.98 38.0 5.67 35.2 5.34 32.4 5.03 28.1 4.55 23.9 4.08

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 33.8 8.78 30.6 8.69 28.5 8.59 26.4 8.42 24.3 8.16 21.1 7.74 18.0 7.27

-14.7 -15.0 33.8 8.16 30.6 8.11 28.5 8.03 26.4 7.91 24.3 7.72 21.1 7.29 18.0 6.71

-9.6 -10.0 33.8 7.43 30.6 7.43 28.5 7.37 26.4 7.25 24.3 6.98 21.1 6.50 18.0 5.96

-4.4 -5.0 33.8 6.48 30.6 6.35 28.5 6.25 26.4 6.09 24.3 5.92 21.1 5.59 18.0 5.18

-1.8 -2.5 33.8 5.80 30.6 5.73 28.5 5.65 26.4 5.55 24.3 5.40 21.1 5.13 18.0 4.78

0.8 0.0 33.8 5.20 30.6 5.13 28.5 5.09 26.4 5.03 24.3 4.93 21.1 4.72 18.0 4.43

30% 2.8 2.0 33.8 5.20 30.6 4.82 28.5 4.68 26.4 4.64 24.3 4.55 21.1 4.39 18.0 4.14

6.0 5.0 33.8 5.20 30.6 4.82 28.5 4.60 26.4 4.35 24.3 4.12 21.1 3.91 18.0 3.75

7.0 6.0 33.8 5.20 30.6 4.82 28.5 4.60 26.4 4.35 24.3 4.12 21.1 3.77 18.0 3.62

8.6 7.5 33.8 5.20 30.6 4.82 28.5 4.60 26.4 4.35 24.3 4.12 21.1 3.77 18.0 3.44

11.2 10.0 33.8 5.20 30.6 4.82 28.5 4.60 26.4 4.35 24.3 4.12 21.1 3.77 18.0 3.39

16.4 15.0 33.8 5.20 30.6 4.82 28.5 4.60 26.4 4.35 24.3 4.12 21.1 3.77 18.0 3.39

24.0 18.0 33.8 5.20 30.6 4.82 28.5 4.60 26.4 4.35 24.3 4.12 21.1 3.77 18.0 3.39

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, HIGH EFFICIENCY (Heating)


32 HP (U-8MF2E8 & U-12MF2E8 & U-12MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 81.2 27.94 74.9 25.67 70.5 24.15 70.5 24.15 70.5 24.15 70.5 24.15 61.4 20.95

-14.7 -15.0 86.1 28.47 79.6 26.20 75.0 24.65 75.0 24.65 75.0 24.65 75.0 24.65 65.8 21.43

-9.6 -10.0 92.4 29.21 85.6 26.94 80.8 25.38 80.8 25.38 80.8 25.38 80.8 25.38 71.4 22.11

-4.4 -5.0 100.8 30.35 93.6 28.03 88.6 26.45 88.6 26.45 88.6 26.45 88.6 26.45 79.0 23.09

-1.8 -2.5 106.2 31.08 98.7 28.74 93.5 27.13 93.5 27.13 93.5 27.13 93.5 27.13 83.8 23.72

0.8 0.0 112.1 31.78 104.7 29.56 99.3 27.92 99.3 27.92 99.3 27.92 99.3 27.92 88.0 23.97

130% 2.8 2.0 116.3 31.78 110.5 30.35 104.9 28.72 104.9 28.72 104.9 28.72 103.5 27.08 88.0 22.77

6.0 5.0 124.6 31.78 115.5 29.37 107.5 26.97 107.5 26.97 107.5 26.97 103.5 24.56 88.0 20.63

7.0 6.0 127.3 31.78 115.5 28.22 107.5 25.92 107.5 25.92 107.5 25.92 103.5 23.63 88.0 19.86

8.6 7.5 127.4 29.78 115.5 26.42 107.5 24.31 107.5 24.31 107.5 24.31 103.5 22.20 88.0 18.68

11.2 10.0 127.4 26.51 115.5 23.59 107.5 21.70 107.5 21.70 107.5 21.70 103.5 19.91 88.0 16.82

16.4 15.0 127.4 20.59 115.5 18.43 107.5 17.05 107.5 17.05 107.5 17.05 103.5 15.84 88.0 13.51

24.0 18.0 127.4 17.52 115.5 15.78 107.5 14.66 107.5 14.66 107.5 14.66 103.5 13.76 88.0 11.80

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 81.3 27.67 75.0 25.45 70.6 23.93 70.6 23.93 70.6 23.93 65.4 22.04 56.6 19.39

-14.7 -15.0 86.3 28.19 79.7 25.97 75.1 24.45 75.1 24.45 75.1 24.45 69.9 22.56 60.7 19.82

-9.6 -10.0 92.6 28.97 85.7 26.74 80.9 25.20 80.9 25.20 80.9 25.20 75.7 23.29 65.9 20.45

-4.4 -5.0 101.0 30.10 93.7 27.83 88.6 26.24 88.6 26.24 88.6 26.24 83.4 24.31 72.7 21.29

-1.8 -2.5 106.3 30.83 98.8 28.53 93.5 26.92 93.5 26.92 93.5 26.92 88.3 24.97 77.1 21.86

0.8 0.0 112.6 31.69 104.7 29.33 99.3 27.72 99.3 27.72 99.3 27.72 93.3 25.49 79.3 21.54
120% 2.8 2.0 116.9 31.78 110.4 30.12 104.8 28.49 104.8 28.49 104.8 28.49 93.3 24.22 79.3 20.43

6.0 5.0 124.4 31.64 112.8 28.10 105.0 25.86 105.0 25.86 105.0 25.86 93.3 21.97 79.3 18.52

7.0 6.0 124.4 30.35 112.8 26.99 105.0 24.83 105.0 24.83 105.0 24.83 93.3 21.13 79.3 17.82

8.6 7.5 124.4 28.38 112.8 25.27 105.0 23.27 105.0 23.27 105.0 23.27 93.3 19.86 79.3 16.78

11.2 10.0 124.4 25.24 112.8 22.52 105.0 20.77 105.0 20.77 105.0 20.77 93.3 17.82 79.3 15.10

16.4 15.0 124.4 19.57 112.8 17.57 105.0 16.30 105.0 16.30 105.0 16.30 93.3 14.19 79.3 12.14

24.0 18.0 124.4 16.62 112.8 15.00 105.0 13.98 105.0 13.98 105.0 13.98 93.3 12.33 79.3 10.62

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 81.5 27.40 75.1 25.22 70.7 23.74 70.7 23.74 67.8 22.68 60.0 20.23 51.9 17.84

-14.7 -15.0 86.5 27.94 79.8 25.76 75.2 24.27 75.2 24.27 72.3 23.20 64.1 20.70 55.6 18.23

-9.6 -10.0 92.7 28.74 85.8 26.54 81.0 25.02 81.0 25.02 78.1 23.95 69.4 21.36 60.3 18.77

-4.4 -5.0 101.2 29.87 93.8 27.60 88.7 26.06 88.7 26.06 85.7 24.97 76.3 22.25 66.5 19.52

-1.8 -2.5 106.5 30.60 98.8 28.31 93.5 26.72 93.5 26.72 90.5 25.63 80.7 22.84 70.5 20.04

0.8 0.0 112.7 31.44 104.7 29.10 99.2 27.49 99.2 27.49 96.0 26.33 83.5 22.68 71.0 19.23

110% 2.8 2.0 117.5 31.78 110.1 29.74 102.5 27.38 102.5 27.38 96.0 25.02 83.5 21.52 71.0 18.25

6.0 5.0 121.5 30.17 110.1 26.88 102.5 24.77 102.5 24.77 96.0 22.65 83.5 19.52 71.0 16.53

7.0 6.0 121.5 28.92 110.1 25.79 102.5 23.77 102.5 23.77 96.0 21.79 83.5 18.77 71.0 15.89

8.6 7.5 121.5 27.04 110.1 24.13 102.5 22.27 102.5 22.27 96.0 20.43 83.5 17.64 71.0 14.96

11.2 10.0 121.5 23.99 110.1 21.47 102.5 19.86 102.5 19.86 96.0 18.27 83.5 15.82 71.0 13.48

16.4 15.0 121.5 18.55 110.1 16.73 102.5 15.55 102.5 15.55 96.0 14.44 83.5 12.62 71.0 10.85

24.0 18.0 121.5 15.73 110.1 14.28 102.5 13.32 102.5 13.32 96.0 12.46 83.5 10.96 71.0 9.51

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 81.7 27.13 75.2 24.99 70.8 23.54 66.3 22.09 61.6 20.61 54.5 18.43 47.2 16.30

-14.7 -15.0 86.6 27.69 79.9 25.54 75.3 24.08 70.6 22.59 65.7 21.09 58.3 18.86 50.5 16.66

-9.6 -10.0 92.9 28.51 85.9 26.33 81.1 24.83 76.1 23.31 71.0 21.77 63.0 19.43 54.7 17.14

-4.4 -5.0 101.3 29.65 93.9 27.42 88.7 25.86 83.4 24.29 77.9 22.68 69.3 20.25 60.3 17.80

-1.8 -2.5 106.6 30.37 98.9 28.10 93.5 26.51 87.9 24.90 82.2 23.27 73.3 20.77 63.0 17.96

0.8 0.0 112.8 31.21 104.8 28.90 99.2 27.29 92.6 25.38 85.2 23.18 74.1 20.02 63.0 17.05

100% 2.8 2.0 118.2 31.78 107.4 28.44 100.0 26.22 92.6 24.06 85.2 21.97 74.1 18.98 63.0 16.16

6.0 5.0 118.5 28.74 107.4 25.67 100.0 23.70 92.6 21.77 85.2 19.91 74.1 17.23 63.0 14.64

7.0 6.0 118.5 27.56 107.4 24.63 100.0 22.70 92.6 20.93 85.2 19.14 74.1 16.57 63.0 14.10

8.6 7.5 118.5 25.72 107.4 23.02 100.0 21.29 92.6 19.59 85.2 17.96 74.1 15.57 63.0 13.26

11.2 10.0 118.5 22.81 107.4 20.48 100.0 18.95 92.6 17.50 85.2 16.07 74.1 13.98 63.0 11.96

16.4 15.0 118.5 17.59 107.4 15.91 100.0 14.82 92.6 13.76 85.2 12.69 74.1 11.17 63.0 9.65

9 24.0 18.0 118.5 14.89 107.4 13.55 100.0 12.67 92.6 11.83 85.2 10.96 74.1 9.72 63.0 8.47
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, HIGH EFFICIENCY (Heating)


32 HP (U-8MF2E8 & U-12MF2E8 & U-12MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 82.4 26.20 75.7 24.22 71.2 22.88 66.6 21.52 61.9 20.18 54.6 18.16 47.1 16.19

-14.7 -15.0 87.4 26.83 80.5 24.81 75.7 23.43 70.9 22.04 65.9 20.63 58.3 18.57 50.4 16.50

-9.6 -10.0 93.7 27.69 86.4 25.61 81.4 24.20 76.3 22.75 71.1 21.29 62.9 19.09 54.5 16.93

-4.4 -5.0 102.0 28.85 94.2 26.67 88.9 25.20 83.3 23.65 76.7 21.77 66.7 19.07 56.7 16.46

-1.8 -2.5 106.7 29.35 96.7 26.45 90.0 24.54 83.3 22.68 76.7 20.86 66.7 18.25 56.7 15.75

0.8 0.0 106.7 27.72 96.7 24.92 90.0 23.13 83.3 21.36 76.7 19.68 66.7 17.21 56.7 14.87

90% 2.8 2.0 106.7 26.13 96.7 23.54 90.0 21.86 83.3 20.23 76.7 18.61 66.7 16.30 56.7 14.07

6.0 5.0 106.7 23.45 96.7 21.18 90.0 19.70 83.3 18.25 76.7 16.82 66.7 14.73 56.7 12.67

7.0 6.0 106.7 22.43 96.7 20.27 90.0 18.89 83.3 17.50 76.7 16.14 66.7 14.14 56.7 12.19

8.6 7.5 106.7 20.86 96.7 18.91 90.0 17.64 83.3 16.37 76.7 15.12 66.7 13.28 56.7 11.46

11.2 10.0 106.7 18.41 96.7 16.75 90.0 15.64 83.3 14.57 76.7 13.51 66.7 11.92 56.7 10.33

16.4 15.0 106.7 14.01 96.7 12.87 90.0 12.12 83.3 11.37 76.7 10.60 66.7 9.47 56.7 8.33

24.0 18.0 106.7 13.26 96.7 12.14 90.0 11.42 83.3 10.67 76.7 9.94 66.7 8.83 56.7 7.74

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 83.5 25.54 76.6 23.70 71.9 22.45 67.2 21.20 62.4 19.95 54.9 18.09 47.3 16.28

-14.7 -15.0 88.6 26.24 81.4 24.33 76.5 23.02 71.5 21.72 66.4 20.43 58.6 18.48 50.4 16.48

-9.6 -10.0 94.8 27.08 85.9 24.61 80.0 23.00 74.1 21.43 68.1 19.89 59.3 17.64 50.4 15.48

-4.4 -5.0 94.8 25.15 85.9 22.86 80.0 21.36 74.1 19.91 68.1 18.50 59.3 16.41 50.4 14.41

-1.8 -2.5 94.8 23.81 85.9 21.68 80.0 20.27 74.1 18.91 68.1 17.55 59.3 15.59 50.4 13.69

0.8 0.0 94.8 22.34 85.9 20.36 80.0 19.07 74.1 17.77 68.1 16.53 59.3 14.69 50.4 12.87

80% 2.8 2.0 94.8 21.02 85.9 19.18 80.0 17.98 74.1 16.80 68.1 15.62 59.3 13.87 50.4 12.17

6.0 5.0 94.8 18.77 85.9 17.18 80.0 16.14 74.1 15.07 68.1 14.03 59.3 12.44 50.4 10.85

7.0 6.0 94.8 17.91 85.9 16.43 80.0 15.44 74.1 14.44 68.1 13.44 59.3 11.94 50.4 10.42

8.6 7.5 94.8 16.62 85.9 15.28 80.0 14.39 74.1 13.48 68.1 12.58 59.3 11.19 50.4 9.81

11.2 10.0 94.8 14.57 85.9 13.48 80.0 12.73 74.1 11.96 68.1 11.21 59.3 10.03 50.4 8.83

16.4 15.0 94.8 11.94 85.9 10.96 80.0 10.31 74.1 9.65 68.1 9.01 59.3 8.04 50.4 7.13

24.0 18.0 94.8 11.94 85.9 10.96 80.0 10.31 74.1 9.65 68.1 9.01 59.3 8.04 50.4 7.04

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 83.0 24.43 75.2 22.47 70.0 21.18 64.8 19.93 59.6 18.70 51.9 16.91 44.1 15.16

-14.7 -15.0 83.0 23.31 75.2 21.43 70.0 20.20 64.8 18.98 59.6 17.80 51.9 16.03 44.1 14.32

-9.6 -10.0 83.0 21.91 75.2 20.18 70.0 19.07 64.8 17.93 59.6 16.84 51.9 15.14 44.1 13.46

-4.4 -5.0 83.0 20.02 75.2 18.48 70.0 17.46 64.8 16.46 59.6 15.44 51.9 13.96 44.1 12.46

-1.8 -2.5 83.0 18.93 75.2 17.48 70.0 16.53 64.8 15.57 59.6 14.64 51.9 13.21 44.1 11.78

0.8 0.0 83.0 17.68 75.2 16.37 70.0 15.50 64.8 14.62 59.6 13.73 51.9 12.42 44.1 11.05

70% 2.8 2.0 83.0 16.59 75.2 15.39 70.0 14.57 64.8 13.76 59.6 12.94 51.9 11.69 44.1 10.28

6.0 5.0 83.0 14.73 75.2 13.71 70.0 13.01 64.8 12.28 59.6 11.53 51.9 10.37 44.1 9.17

7.0 6.0 83.0 14.03 75.2 13.08 70.0 12.42 64.8 11.74 59.6 11.03 51.9 9.94 44.1 8.83

8.6 7.5 83.0 12.98 75.2 12.14 70.0 11.55 64.8 10.94 59.6 10.31 51.9 9.33 44.1 8.31

11.2 10.0 83.0 11.30 75.2 10.65 70.0 10.17 64.8 9.67 59.6 9.17 51.9 8.35 44.1 7.49

16.4 15.0 83.0 10.65 75.2 9.78 70.0 9.22 64.8 8.65 59.6 8.06 51.9 7.22 44.1 6.36

24.0 18.0 83.0 10.65 75.2 9.78 70.0 9.22 64.8 8.65 59.6 8.06 51.9 7.22 44.1 6.36

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 71.1 19.61 64.4 18.32 60.0 17.43 55.6 16.55 51.1 15.66 44.4 14.37 37.8 13.10

-14.7 -15.0 71.1 18.52 64.4 17.37 60.0 16.59 55.6 15.80 51.1 14.94 44.4 13.64 37.8 12.35

-9.6 -10.0 71.1 17.23 64.4 16.19 60.0 15.46 55.6 14.73 51.1 14.01 44.4 12.87 37.8 11.60

-4.4 -5.0 71.1 15.66 64.4 14.73 60.0 14.10 55.6 13.44 51.1 12.78 44.4 11.76 37.8 10.67

-1.8 -2.5 71.1 14.73 64.4 13.89 60.0 13.30 55.6 12.69 51.1 12.08 44.4 11.10 37.8 10.06

0.8 0.0 71.1 13.73 64.4 12.94 60.0 12.42 55.6 11.85 51.1 11.28 44.4 10.37 37.8 9.22

60% 2.8 2.0 71.1 12.83 64.4 12.12 60.0 11.62 55.6 11.12 51.1 10.58 44.4 9.62 37.8 8.58

6.0 5.0 71.1 11.30 64.4 10.71 60.0 10.28 55.6 9.81 51.1 9.31 44.4 8.51 37.8 7.65

7.0 6.0 71.1 10.74 64.4 10.19 60.0 9.78 55.6 9.38 51.1 8.90 44.4 8.17 37.8 7.35

8.6 7.5 71.1 9.87 64.4 9.42 60.0 9.08 55.6 8.72 51.1 8.31 44.4 7.65 37.8 6.92

11.2 10.0 71.1 9.33 64.4 8.60 60.0 8.10 55.6 7.70 51.1 7.38 44.4 6.86 37.8 6.27

16.4 15.0 71.1 9.33 64.4 8.60 60.0 8.10 55.6 7.63 51.1 7.13 44.4 6.40 37.8 5.65

24.0 18.0 71.1 9.33 64.4 8.60 60.0 8.10 55.6 7.63 51.1 7.13 44.4 6.40 37.8 5.65

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, HIGH EFFICIENCY (Heating)


32 HP (U-8MF2E8 & U-12MF2E8 & U-12MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 59.3 15.37 53.7 14.69 50.0 14.21 46.3 13.64 42.6 13.03 37.0 12.10 31.5 11.17

-14.7 -15.0 59.3 14.44 53.7 13.82 50.0 13.39 46.3 12.92 42.6 12.42 37.0 11.49 31.5 10.51

-9.6 -10.0 59.3 13.37 53.7 12.80 50.0 12.42 46.3 11.99 42.6 11.53 37.0 10.78 31.5 9.85

-4.4 -5.0 59.3 12.05 53.7 11.58 50.0 11.24 46.3 10.87 42.6 10.46 37.0 9.78 31.5 8.92

-1.8 -2.5 59.3 11.28 53.7 10.87 50.0 10.56 46.3 10.22 42.6 9.83 37.0 9.15 31.5 8.22

0.8 0.0 59.3 10.46 53.7 10.08 50.0 9.81 46.3 9.49 42.6 9.10 37.0 8.35 31.5 7.56
50% 2.8 2.0 59.3 9.72 53.7 9.40 50.0 9.13 46.3 8.76 42.6 8.38 37.0 7.74 31.5 7.04

6.0 5.0 59.3 8.42 53.7 8.15 50.0 7.92 46.3 7.67 42.6 7.38 37.0 6.88 31.5 6.29

7.0 6.0 59.3 8.04 53.7 7.74 50.0 7.56 46.3 7.31 42.6 7.06 37.0 6.58 31.5 6.04

8.6 7.5 59.3 8.04 53.7 7.42 50.0 7.01 46.3 6.81 42.6 6.58 37.0 6.17 31.5 5.70

11.2 10.0 59.3 8.04 53.7 7.42 50.0 7.01 46.3 6.61 42.6 6.20 37.0 5.58 31.5 5.15

16.4 15.0 59.3 8.04 53.7 7.42 50.0 7.01 46.3 6.61 42.6 6.20 37.0 5.58 31.5 4.97

24.0 18.0 59.3 8.04 53.7 7.42 50.0 7.01 46.3 6.61 42.6 6.20 37.0 5.58 31.5 4.97

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 47.4 11.89 43.0 11.60 40.0 11.37 37.0 11.08 34.1 10.65 29.6 10.01 25.2 9.33

-14.7 -15.0 47.4 11.15 43.0 10.90 40.0 10.67 37.0 10.42 34.1 10.12 29.6 9.49 25.2 8.76

-9.6 -10.0 47.4 10.24 43.0 10.03 40.0 9.85 37.0 9.62 34.1 9.35 29.6 8.88 25.2 8.17

-4.4 -5.0 47.4 9.15 43.0 8.99 40.0 8.85 37.0 8.67 34.1 8.44 29.6 7.81 25.2 7.11

-1.8 -2.5 47.4 8.51 43.0 8.38 40.0 8.26 37.0 8.04 34.1 7.72 29.6 7.17 25.2 6.56

0.8 0.0 47.4 7.83 43.0 7.67 40.0 7.49 37.0 7.26 34.1 7.01 29.6 6.56 25.2 6.04

40% 2.8 2.0 47.4 7.15 43.0 7.01 40.0 6.86 37.0 6.70 34.1 6.47 29.6 6.08 25.2 5.63

6.0 5.0 47.4 6.72 43.0 6.22 40.0 5.97 37.0 5.86 34.1 5.70 29.6 5.43 25.2 5.06

7.0 6.0 47.4 6.72 43.0 6.22 40.0 5.90 37.0 5.58 34.1 5.45 29.6 5.20 25.2 4.88

8.6 7.5 47.4 6.72 43.0 6.22 40.0 5.90 37.0 5.58 34.1 5.24 29.6 4.90 25.2 4.61

11.2 10.0 47.4 6.72 43.0 6.22 40.0 5.90 37.0 5.58 34.1 5.24 29.6 4.77 25.2 4.27

16.4 15.0 47.4 6.72 43.0 6.22 40.0 5.90 37.0 5.58 34.1 5.24 29.6 4.77 25.2 4.27

24.0 18.0 47.4 6.72 43.0 6.22 40.0 5.90 37.0 5.58 34.1 5.24 29.6 4.77 25.2 4.27

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 35.6 9.08 32.2 8.99 30.0 8.88 27.8 8.72 25.6 8.42 22.2 7.99 18.9 7.51

-14.7 -15.0 35.6 8.47 32.2 8.42 30.0 8.33 27.8 8.19 25.6 7.99 22.2 7.56 18.9 7.04

-9.6 -10.0 35.6 7.74 32.2 7.72 30.0 7.65 27.8 7.54 25.6 7.35 22.2 6.86 18.9 6.27

-4.4 -5.0 35.6 6.86 32.2 6.76 30.0 6.63 27.8 6.45 25.6 6.27 22.2 5.88 18.9 5.45

-1.8 -2.5 35.6 6.20 32.2 6.11 30.0 6.02 27.8 5.90 25.6 5.72 22.2 5.43 18.9 5.06

0.8 0.0 35.6 5.52 32.2 5.49 30.0 5.45 27.8 5.36 25.6 5.22 22.2 4.99 18.9 4.68

30% 2.8 2.0 35.6 5.43 32.2 5.04 30.0 4.99 27.8 4.93 25.6 4.84 22.2 4.65 18.9 4.38

6.0 5.0 35.6 5.43 32.2 5.04 30.0 4.81 27.8 4.56 25.6 4.31 22.2 4.15 18.9 3.97

7.0 6.0 35.6 5.43 32.2 5.04 30.0 4.81 27.8 4.56 25.6 4.31 22.2 4.02 18.9 3.84

8.6 7.5 35.6 5.43 32.2 5.04 30.0 4.81 27.8 4.56 25.6 4.31 22.2 3.95 18.9 3.63

11.2 10.0 35.6 5.43 32.2 5.04 30.0 4.81 27.8 4.56 25.6 4.31 22.2 3.95 18.9 3.59

16.4 15.0 35.6 5.43 32.2 5.04 30.0 4.81 27.8 4.56 25.6 4.31 22.2 3.95 18.9 3.59

24.0 18.0 35.6 5.43 32.2 5.04 30.0 4.81 27.8 4.56 25.6 4.31 22.2 3.95 18.9 3.59

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


18 HP (U-8MF2E8 & U-10MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 47.0 7.47 54.2 8.64 54.2 8.64 54.2 8.64 61.4 9.78 68.6 10.93 75.9 12.07

-5.0 47.0 7.48 54.2 8.64 54.2 8.64 54.2 8.64 61.4 9.79 68.6 10.94 75.9 12.08

0.0 47.0 7.48 54.2 8.65 54.2 8.65 54.2 8.65 61.4 9.81 68.6 10.95 75.9 12.10

5.0 47.0 7.49 54.2 8.66 54.2 8.66 54.2 8.66 61.4 9.82 68.6 10.97 75.9 12.11

10.0 47.0 7.50 54.2 8.68 54.2 8.68 54.2 8.68 61.4 9.84 68.6 11.01 75.9 12.14

15.0 47.0 7.53 54.2 8.73 54.2 8.73 54.2 8.73 61.4 9.90 68.6 11.07 75.9 12.21
130% 20.0 47.0 7.59 54.2 8.84 54.2 8.84 54.2 8.84 61.4 10.03 68.6 11.21 75.9 12.34

25.0 47.0 7.79 54.2 9.13 54.2 9.13 54.2 9.13 61.4 10.35 68.6 11.55 75.9 12.65

30.0 47.0 8.99 54.2 10.56 54.2 10.56 54.2 10.56 61.4 11.97 68.6 13.40 75.9 14.87

35.0 47.0 11.15 54.2 13.03 54.2 13.03 54.2 13.03 61.4 14.75 68.3 16.43 72.0 16.52
40.0 47.0 13.45 54.2 15.67 54.2 15.67 54.2 15.67 58.8 16.52 61.9 16.52 65.1 16.52

43.0 47.0 14.93 52.4 16.52 52.4 16.52 52.4 16.52 55.3 16.52 58.3 16.52 61.3 16.52

46.0 47.0 15.34 49.2 16.52 49.2 16.52 49.2 16.52 50.5 15.78 50.5 14.46 50.5 13.24

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 42.3 6.74 50.8 8.09 52.9 8.44 52.9 8.44 60.0 9.56 67.0 10.68 74.1 11.79

-5.0 42.3 6.74 50.8 8.09 52.9 8.44 52.9 8.44 60.0 9.56 67.0 10.68 74.1 11.80

0.0 42.3 6.75 50.8 8.09 52.9 8.45 52.9 8.45 60.0 9.57 67.0 10.69 74.1 11.81

5.0 42.3 6.75 50.8 8.11 52.9 8.46 52.9 8.46 60.0 9.58 67.0 10.71 74.1 11.84

10.0 42.3 6.76 50.8 8.12 52.9 8.48 52.9 8.48 60.0 9.62 67.0 10.75 74.1 11.86

15.0 42.3 6.79 50.8 8.15 52.9 8.52 52.9 8.52 60.0 9.66 67.0 10.81 74.1 11.93
120% 20.0 42.3 6.84 50.8 8.22 52.9 8.63 52.9 8.63 60.0 9.78 67.0 10.94 74.1 12.06
25.0 42.3 7.03 50.8 8.46 52.9 8.90 52.9 8.90 60.0 10.08 67.0 11.26 74.1 12.37

30.0 42.3 8.14 50.8 9.68 52.9 10.22 52.9 10.22 60.0 11.55 67.0 12.92 74.1 14.31

35.0 42.3 10.09 50.8 12.00 52.9 12.61 52.9 12.61 60.0 14.27 67.0 15.94 71.6 16.52

40.0 42.3 12.15 50.8 14.48 52.9 15.19 52.9 15.19 58.6 16.52 61.6 16.52 64.8 16.52
43.0 42.3 13.48 50.8 15.34 52.2 16.52 52.2 16.52 55.0 16.52 58.0 16.52 61.0 16.52

46.0 42.3 14.88 49.0 16.52 49.0 16.52 49.0 16.52 50.5 15.88 50.5 14.55 50.5 13.32

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 37.9 6.03 45.5 7.25 51.7 8.24 51.7 8.24 58.6 9.33 65.4 10.42 72.3 11.51
-5.0 37.9 6.03 45.5 7.25 51.7 8.24 51.7 8.24 58.6 9.33 65.4 10.43 72.3 11.52

0.0 37.9 6.04 45.5 7.25 51.7 8.25 51.7 8.25 58.6 9.35 65.4 10.44 72.3 11.53
5.0 37.9 6.04 45.5 7.26 51.7 8.26 51.7 8.26 58.6 9.36 65.4 10.45 72.3 11.55

10.0 37.9 6.05 45.5 7.27 51.7 8.27 51.7 8.27 58.6 9.38 65.4 10.49 72.3 11.59
15.0 37.9 6.08 45.5 7.30 51.7 8.32 51.7 8.32 58.6 9.43 65.4 10.54 72.3 11.65

110% 20.0 37.9 6.12 45.5 7.38 51.7 8.41 51.7 8.41 58.6 9.53 65.4 10.67 72.3 11.78

25.0 37.9 6.31 45.5 7.59 51.7 8.67 51.7 8.67 58.6 9.82 65.4 10.96 72.3 12.07

30.0 37.9 7.34 45.5 8.68 51.7 9.88 51.7 9.88 58.6 11.15 65.4 12.45 72.3 13.76

35.0 37.9 9.07 45.5 10.76 51.7 12.20 51.7 12.20 58.6 13.78 65.4 15.38 71.2 16.52
40.0 37.9 10.92 45.5 12.96 51.7 14.70 51.7 14.70 58.2 16.47 61.3 16.52 64.5 16.52

43.0 37.9 12.10 45.5 14.38 51.7 16.33 51.7 16.33 54.8 16.52 57.7 16.52 60.7 16.52
46.0 37.9 13.35 45.5 15.34 48.8 16.52 48.8 16.52 50.5 15.99 50.5 14.66 50.5 13.43

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 33.6 5.35 40.3 6.42 47.0 7.49 50.4 8.04 57.1 9.10 63.9 10.17 70.6 11.23

-5.0 33.6 5.36 40.3 6.43 47.0 7.50 50.4 8.04 57.1 9.11 63.9 10.17 70.6 11.23

0.0 33.6 5.36 40.3 6.43 47.0 7.50 50.4 8.05 57.1 9.11 63.9 10.18 70.6 11.25

5.0 33.6 5.37 40.3 6.44 47.0 7.52 50.4 8.06 57.1 9.13 63.9 10.20 70.6 11.27
10.0 33.6 5.37 40.3 6.45 47.0 7.53 50.4 8.07 57.1 9.16 63.9 10.23 70.6 11.30

15.0 33.6 5.39 40.3 6.48 47.0 7.56 50.4 8.11 57.1 9.19 63.9 10.28 70.6 11.36

100% 20.0 33.6 5.44 40.3 6.55 47.0 7.65 50.4 8.20 57.1 9.30 63.9 10.40 70.6 11.48
25.0 33.6 5.61 40.3 6.75 47.0 7.88 50.4 8.44 57.1 9.56 63.9 10.67 70.6 11.78

30.0 33.6 6.57 40.3 7.75 47.0 8.94 50.4 9.55 57.1 10.76 63.9 11.99 70.6 13.23

35.0 33.6 8.08 40.3 9.56 47.0 11.04 50.4 11.80 57.1 13.29 63.7 14.76 70.3 16.26

40.0 33.6 9.74 40.3 11.53 47.0 13.32 50.4 14.23 57.1 16.06 61.0 16.52 64.1 16.52

43.0 33.6 10.79 40.3 12.78 47.0 14.79 50.4 15.80 54.5 16.52 57.4 16.52 60.4 16.52

9 46.0 33.6 11.88 40.3 14.10 47.0 16.35 48.6 16.52 50.5 16.11 50.5 14.77 50.5 13.52
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


18 HP (U-8MF2E8 & U-10MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 30.2 4.81 36.3 5.78 42.3 6.75 45.4 7.23 51.4 8.19 57.5 9.15 63.5 10.10

-5.0 30.2 4.81 36.3 5.78 42.3 6.75 45.4 7.23 51.4 8.19 57.5 9.16 63.5 10.11

0.0 30.2 4.83 36.3 5.79 42.3 6.75 45.4 7.23 51.4 8.20 57.5 9.16 63.5 10.12

5.0 30.2 4.83 36.3 5.79 42.3 6.76 45.4 7.25 51.4 8.21 57.5 9.17 63.5 10.14

10.0 30.2 4.84 36.3 5.81 42.3 6.77 45.4 7.26 51.4 8.22 57.5 9.19 63.5 10.16

15.0 30.2 4.85 36.3 5.83 42.3 6.80 45.4 7.29 51.4 8.26 57.5 9.23 63.5 10.21
90% 20.0 30.2 4.89 36.3 5.88 42.3 6.86 45.4 7.35 51.4 8.33 57.5 9.32 63.5 10.29

25.0 30.2 5.00 36.3 6.02 42.3 7.03 45.4 7.53 51.4 8.53 57.5 9.52 63.5 10.51

30.0 30.2 5.78 36.3 6.77 42.3 7.76 45.4 8.27 51.4 9.26 57.5 10.24 63.5 11.22

35.0 30.2 7.20 36.3 8.43 42.3 9.66 45.4 10.28 51.4 11.51 57.5 12.73 63.5 13.96
40.0 30.2 8.65 36.3 10.16 42.3 11.66 45.4 12.41 51.4 13.91 57.5 15.42 62.6 16.52

43.0 30.2 9.57 36.3 11.26 42.3 12.94 45.4 13.78 51.4 15.47 56.1 16.52 59.0 16.52

46.0 30.2 10.55 36.3 12.43 42.3 14.31 45.4 15.26 50.2 16.52 50.5 15.28 50.5 14.01

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 26.9 4.28 32.3 5.13 37.6 5.99 40.3 6.42 45.7 7.28 51.1 8.13 56.4 8.98

-5.0 26.9 4.28 32.3 5.14 37.6 5.99 40.3 6.43 45.7 7.28 51.1 8.13 56.4 8.98

0.0 26.9 4.28 32.3 5.14 37.6 6.01 40.3 6.43 45.7 7.29 51.1 8.14 56.4 8.99

5.0 26.9 4.28 32.3 5.14 37.6 6.01 40.3 6.44 45.7 7.29 51.1 8.15 56.4 9.00

10.0 26.9 4.30 32.3 5.16 37.6 6.02 40.3 6.44 45.7 7.30 51.1 8.17 56.4 9.02

15.0 26.9 4.31 32.3 5.17 37.6 6.04 40.3 6.47 45.7 7.33 51.1 8.19 56.4 9.05
80% 20.0 26.9 4.33 32.3 5.20 37.6 6.08 40.3 6.51 45.7 7.39 51.1 8.25 56.4 9.12
25.0 26.9 4.43 32.3 5.31 37.6 6.20 40.3 6.64 45.7 7.53 51.1 8.40 56.4 9.27

30.0 26.9 4.97 32.3 5.85 37.6 6.73 40.3 7.15 45.7 8.02 51.1 8.89 56.4 9.74

35.0 26.9 6.32 32.3 7.35 37.6 8.35 40.3 8.85 45.7 9.84 51.1 10.81 56.4 11.78

40.0 26.9 7.60 32.3 8.86 37.6 10.10 40.3 10.71 45.7 11.93 51.1 13.13 56.4 14.33
43.0 26.9 8.41 32.3 9.82 37.6 11.21 40.3 11.91 45.7 13.28 51.1 14.63 56.4 15.98

46.0 26.9 9.26 32.3 10.84 37.6 12.40 40.3 13.17 45.7 14.71 50.5 15.94 50.5 14.62

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 23.5 3.74 28.2 4.50 32.9 5.25 35.3 5.62 40.0 6.37 44.7 7.12 49.4 7.86
-5.0 23.5 3.74 28.2 4.50 32.9 5.25 35.3 5.63 40.0 6.37 44.7 7.12 49.4 7.86

0.0 23.5 3.75 28.2 4.50 32.9 5.25 35.3 5.63 40.0 6.37 44.7 7.12 49.4 7.87
5.0 23.5 3.75 28.2 4.51 32.9 5.25 35.3 5.63 40.0 6.38 44.7 7.13 49.4 7.87

10.0 23.5 3.75 28.2 4.51 32.9 5.26 35.3 5.64 40.0 6.38 44.7 7.14 49.4 7.88
15.0 23.5 3.76 28.2 4.52 32.9 5.27 35.3 5.65 40.0 6.41 44.7 7.16 49.4 7.91

70% 20.0 23.5 3.79 28.2 4.54 32.9 5.31 35.3 5.69 40.0 6.44 44.7 7.20 49.4 7.95

25.0 23.5 3.85 28.2 4.61 32.9 5.38 35.3 5.77 40.0 6.54 44.7 7.30 49.4 8.06

30.0 23.5 4.22 28.2 4.98 32.9 5.75 35.3 6.12 40.0 6.88 44.7 7.62 49.4 8.38

35.0 23.5 5.51 28.2 6.34 32.9 7.14 35.3 7.54 40.0 8.31 44.7 9.06 49.4 9.79
40.0 23.5 6.61 28.2 7.65 32.9 8.65 35.3 9.13 40.0 10.10 44.7 11.03 49.4 11.95

43.0 23.5 7.32 28.2 8.47 32.9 9.59 35.3 10.15 40.0 11.25 44.7 12.31 49.4 13.35
46.0 23.5 8.05 28.2 9.33 32.9 10.61 35.3 11.23 40.0 12.45 44.7 13.65 49.4 14.84

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 20.2 3.21 24.2 3.86 28.2 4.50 30.2 4.81 34.3 5.46 38.3 6.10 42.3 6.74

-5.0 20.2 3.21 24.2 3.86 28.2 4.50 30.2 4.81 34.3 5.46 38.3 6.10 42.3 6.74

0.0 20.2 3.21 24.2 3.86 28.2 4.50 30.2 4.83 34.3 5.46 38.3 6.10 42.3 6.74

5.0 20.2 3.21 24.2 3.86 28.2 4.51 30.2 4.83 34.3 5.46 38.3 6.11 42.3 6.75
10.0 20.2 3.22 24.2 3.86 28.2 4.51 30.2 4.83 34.3 5.48 38.3 6.11 42.3 6.75

15.0 20.2 3.22 24.2 3.87 28.2 4.52 30.2 4.84 34.3 5.49 38.3 6.12 42.3 6.77

60% 20.0 20.2 3.23 24.2 3.88 28.2 4.53 30.2 4.86 34.3 5.51 38.3 6.15 42.3 6.80
25.0 20.2 3.28 24.2 3.93 28.2 4.59 30.2 4.92 34.3 5.57 38.3 6.22 42.3 6.87

30.0 20.2 3.52 24.2 4.17 28.2 4.81 30.2 5.14 34.3 5.78 38.3 6.43 42.3 7.07

35.0 20.2 4.74 24.2 5.39 28.2 6.02 30.2 6.32 34.3 6.90 38.3 7.47 42.3 8.00

40.0 20.2 5.68 24.2 6.49 28.2 7.28 30.2 7.67 34.3 8.41 38.3 9.12 42.3 9.81

43.0 20.2 6.27 24.2 7.19 28.2 8.08 30.2 8.52 34.3 9.36 38.3 10.17 42.3 10.96

46.0 20.2 6.88 24.2 7.92 28.2 8.93 30.2 9.42 34.3 10.37 38.3 11.29 42.3 12.18

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


18 HP (U-8MF2E8 & U-10MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 16.8 2.68 20.2 3.21 23.5 3.74 25.2 4.01 28.6 4.54 31.9 5.09 35.3 5.62

-5.0 16.8 2.68 20.2 3.21 23.5 3.75 25.2 4.01 28.6 4.55 31.9 5.09 35.3 5.62

0.0 16.8 2.68 20.2 3.21 23.5 3.75 25.2 4.01 28.6 4.55 31.9 5.09 35.3 5.62

5.0 16.8 2.68 20.2 3.22 23.5 3.75 25.2 4.02 28.6 4.55 31.9 5.09 35.3 5.62

10.0 16.8 2.68 20.2 3.22 23.5 3.75 25.2 4.02 28.6 4.55 31.9 5.10 35.3 5.63

15.0 16.8 2.69 20.2 3.22 23.5 3.76 25.2 4.04 28.6 4.57 31.9 5.10 35.3 5.64

50% 20.0 16.8 2.69 20.2 3.23 23.5 3.78 25.2 4.05 28.6 4.58 31.9 5.12 35.3 5.65

25.0 16.8 2.71 20.2 3.27 23.5 3.81 25.2 4.07 28.6 4.61 31.9 5.16 35.3 5.70

30.0 16.8 2.87 20.2 3.40 23.5 3.94 25.2 4.21 28.6 4.74 31.9 5.30 35.3 5.84

35.0 16.8 4.01 20.2 4.52 23.5 4.98 25.2 5.20 28.6 5.63 31.9 6.02 35.3 6.47

40.0 16.8 4.79 20.2 5.42 23.5 6.02 25.2 6.30 28.6 6.86 31.9 7.38 35.3 7.87

43.0 16.8 5.27 20.2 5.99 23.5 6.68 25.2 7.00 28.6 7.63 31.9 8.24 35.3 8.80

46.0 16.8 5.78 20.2 6.58 23.5 7.36 25.2 7.73 28.6 8.45 31.9 9.13 35.3 9.77

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 13.5 2.14 16.1 2.57 18.8 3.00 20.2 3.21 22.8 3.63 25.6 4.06 28.2 4.48

-5.0 13.5 2.14 16.1 2.57 18.8 3.00 20.2 3.21 22.8 3.63 25.6 4.07 28.2 4.50

0.0 13.5 2.14 16.1 2.57 18.8 3.00 20.2 3.21 22.8 3.65 25.6 4.07 28.2 4.50

5.0 13.5 2.15 16.1 2.57 18.8 3.00 20.2 3.22 22.8 3.65 25.6 4.07 28.2 4.50

10.0 13.5 2.15 16.1 2.57 18.8 3.01 20.2 3.22 22.8 3.65 25.6 4.07 28.2 4.50
15.0 13.5 2.15 16.1 2.58 18.8 3.01 20.2 3.22 22.8 3.66 25.6 4.08 28.2 4.51

40% 20.0 13.5 2.16 16.1 2.58 18.8 3.02 20.2 3.23 22.8 3.66 25.6 4.09 28.2 4.52

25.0 13.5 2.17 16.1 2.60 18.8 3.03 20.2 3.26 22.8 3.69 25.6 4.12 28.2 4.55

30.0 13.5 2.24 16.1 2.68 18.8 3.10 20.2 3.33 22.8 3.78 25.6 4.21 28.2 4.65

35.0 13.5 3.34 16.1 3.71 18.8 3.94 20.2 4.05 22.8 4.34 25.6 4.70 28.2 5.06
40.0 13.5 3.94 16.1 4.41 18.8 4.85 20.2 5.05 22.8 5.44 25.6 5.81 28.2 6.12

43.0 13.5 4.33 16.1 4.86 18.8 5.36 20.2 5.61 22.8 6.05 25.6 6.47 28.2 6.86
46.0 13.5 4.73 16.1 5.33 18.8 5.90 20.2 6.17 22.8 6.68 25.6 7.16 28.2 7.61

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 10.1 1.60 12.1 1.92 14.1 2.25 15.1 2.41 17.1 2.73 19.2 3.04 21.2 3.36
-5.0 10.1 1.60 12.1 1.92 14.1 2.25 15.1 2.41 17.1 2.73 19.2 3.04 21.2 3.36

0.0 10.1 1.60 12.1 1.92 14.1 2.25 15.1 2.41 17.1 2.73 19.2 3.06 21.2 3.37

5.0 10.1 1.60 12.1 1.92 14.1 2.25 15.1 2.41 17.1 2.74 19.2 3.06 21.2 3.37

10.0 10.1 1.60 12.1 1.94 14.1 2.25 15.1 2.42 17.1 2.74 19.2 3.06 21.2 3.37

15.0 10.1 1.60 12.1 1.94 14.1 2.25 15.1 2.42 17.1 2.74 19.2 3.06 21.2 3.39

30% 20.0 10.1 1.62 12.1 1.94 14.1 2.27 15.1 2.42 17.1 2.75 19.2 3.07 21.2 3.39

25.0 10.1 1.63 12.1 1.95 14.1 2.28 15.1 2.43 17.1 2.76 19.2 3.09 21.2 3.41

30.0 10.1 1.65 12.1 1.98 14.1 2.31 15.1 2.48 17.1 2.81 19.2 3.14 21.2 3.46

35.0 10.1 2.70 12.1 2.69 14.1 2.80 15.1 2.89 17.1 3.14 19.2 3.41 21.2 3.71

40.0 10.1 3.15 12.1 3.48 14.1 3.76 15.1 3.91 17.1 4.15 19.2 4.39 21.2 4.59

43.0 10.1 3.43 12.1 3.81 14.1 4.15 15.1 4.31 17.1 4.60 19.2 4.87 21.2 5.11

46.0 10.1 3.73 12.1 4.15 14.1 4.54 15.1 4.72 17.1 5.06 19.2 5.38 21.2 5.66

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


20 HP (U-8MF2E8 & U-12MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 52.2 7.63 60.2 8.83 60.2 8.83 60.2 8.83 68.2 10.00 76.3 11.18 84.3 12.35

-5.0 52.2 7.63 60.2 8.83 60.2 8.83 60.2 8.83 68.2 10.01 76.3 11.20 84.3 12.37

0.0 52.2 7.64 60.2 8.84 60.2 8.84 60.2 8.84 68.2 10.03 76.3 11.21 84.3 12.39

5.0 52.2 7.64 60.2 8.87 60.2 8.87 60.2 8.87 68.2 10.07 76.3 11.25 84.3 12.44

10.0 52.2 7.67 60.2 8.91 60.2 8.91 60.2 8.91 68.2 10.12 76.3 11.32 84.3 12.51

15.0 52.2 7.71 60.2 9.01 60.2 9.01 60.2 9.01 68.2 10.24 76.3 11.46 84.3 12.65
130% 20.0 52.2 7.84 60.2 9.26 60.2 9.26 60.2 9.26 68.2 10.55 76.3 11.80 84.3 12.97

25.0 52.2 8.36 60.2 10.25 60.2 10.25 60.2 10.25 68.2 11.89 76.3 13.63 84.3 15.45
30.0 52.2 10.39 60.2 12.82 60.2 12.82 60.2 12.82 68.2 14.82 76.3 16.92 84.3 19.12

35.0 52.2 12.72 60.2 15.57 60.2 15.57 60.2 15.57 68.2 17.95 74.8 19.74 78.2 19.74

40.0 52.2 15.23 60.2 18.54 60.2 18.54 60.2 18.54 65.3 19.74 68.4 19.74 71.6 19.74

43.0 52.2 16.84 58.9 19.74 58.9 19.74 58.9 19.74 61.8 19.74 64.8 19.74 66.4 18.92
46.0 52.2 18.33 52.4 17.82 52.4 17.82 52.4 17.82 52.4 16.38 52.4 15.04 52.4 13.80

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 47.0 6.88 56.4 8.26 58.8 8.62 58.8 8.62 66.6 9.77 74.5 10.93 82.3 12.07

-5.0 47.0 6.88 56.4 8.26 58.8 8.63 58.8 8.63 66.6 9.79 74.5 10.94 82.3 12.08
0.0 47.0 6.88 56.4 8.28 58.8 8.63 58.8 8.63 66.6 9.80 74.5 10.96 82.3 12.11

5.0 47.0 6.89 56.4 8.29 58.8 8.66 58.8 8.66 66.6 9.83 74.5 11.00 82.3 12.14

10.0 47.0 6.91 56.4 8.32 58.8 8.70 58.8 8.70 66.6 9.88 74.5 11.05 82.3 12.21

15.0 47.0 6.95 56.4 8.38 58.8 8.80 58.8 8.80 66.6 10.00 74.5 11.20 82.3 12.35
120% 20.0 47.0 7.08 56.4 8.53 58.8 9.02 58.8 9.02 66.6 10.28 74.5 11.52 82.3 12.68
25.0 47.0 7.56 56.4 9.15 58.8 9.91 58.8 9.91 66.6 11.46 74.5 13.13 82.3 14.86

30.0 47.0 9.40 56.4 11.42 58.8 12.41 58.8 12.41 66.6 14.31 74.5 16.33 82.3 18.41

35.0 47.0 11.51 56.4 13.94 58.8 15.06 58.8 15.06 66.6 17.36 74.1 19.63 77.7 19.74

40.0 47.0 13.75 56.4 16.67 58.8 17.96 58.8 17.96 64.9 19.74 68.0 19.74 71.2 19.74

43.0 47.0 15.19 56.4 18.33 58.5 19.73 58.5 19.73 61.5 19.74 64.5 19.74 66.4 19.13

46.0 47.0 16.71 52.4 17.98 52.4 17.98 52.4 17.98 52.4 16.53 52.4 15.17 52.4 13.92

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 42.1 6.16 50.5 7.39 57.4 8.40 57.4 8.40 65.1 9.53 72.7 10.66 80.4 11.79
-5.0 42.1 6.16 50.5 7.40 57.4 8.42 57.4 8.42 65.1 9.55 72.7 10.67 80.4 11.80

0.0 42.1 6.16 50.5 7.40 57.4 8.43 57.4 8.43 65.1 9.56 72.7 10.69 80.4 11.82
5.0 42.1 6.18 50.5 7.42 57.4 8.45 57.4 8.45 65.1 9.59 72.7 10.73 80.4 11.86

10.0 42.1 6.19 50.5 7.44 57.4 8.49 57.4 8.49 65.1 9.64 72.7 10.79 80.4 11.93

15.0 42.1 6.23 50.5 7.50 57.4 8.57 57.4 8.57 65.1 9.74 72.7 10.91 80.4 12.06

110% 20.0 42.1 6.35 50.5 7.66 57.4 8.80 57.4 8.80 65.1 10.01 72.7 11.22 80.4 12.38

25.0 42.1 6.80 50.5 8.23 57.4 9.57 57.4 9.57 65.1 11.05 72.7 12.62 80.4 14.28

30.0 42.1 8.46 50.5 10.24 57.4 12.00 57.4 12.00 65.1 13.82 72.7 15.74 80.4 17.72

35.0 42.1 10.34 50.5 12.49 57.4 14.58 57.4 14.58 65.1 16.76 72.7 19.06 77.2 19.74
40.0 42.1 12.34 50.5 14.92 57.4 17.39 57.4 17.39 64.5 19.74 67.6 19.74 70.7 19.74

43.0 42.1 13.62 50.5 16.48 57.4 19.20 57.4 19.20 61.1 19.74 64.1 19.74 66.4 19.35
46.0 42.1 14.99 50.5 18.15 52.4 18.13 52.4 18.13 52.4 16.67 52.4 15.31 52.4 14.04

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 37.4 5.46 44.8 6.56 52.2 7.66 56.0 8.21 63.4 9.31 71.0 10.41 78.4 11.49
-5.0 37.4 5.47 44.8 6.56 52.2 7.66 56.0 8.21 63.4 9.31 71.0 10.41 78.4 11.51

0.0 37.4 5.47 44.8 6.57 52.2 7.67 56.0 8.22 63.4 9.32 71.0 10.43 78.4 11.53

5.0 37.4 5.48 44.8 6.58 52.2 7.68 56.0 8.25 63.4 9.35 71.0 10.46 78.4 11.56

10.0 37.4 5.50 44.8 6.60 52.2 7.73 56.0 8.28 63.4 9.40 71.0 10.52 78.4 11.63

15.0 37.4 5.53 44.8 6.66 52.2 7.78 56.0 8.36 63.4 9.50 71.0 10.65 78.4 11.76

100% 20.0 37.4 5.63 44.8 6.80 52.2 7.98 56.0 8.56 63.4 9.74 71.0 10.93 78.4 12.07

25.0 37.4 6.05 44.8 7.33 52.2 8.62 56.0 9.26 63.4 10.65 71.0 12.14 78.4 13.71

30.0 37.4 7.59 44.8 9.12 52.2 10.74 56.0 11.59 63.4 13.34 71.0 15.16 78.4 17.05
35.0 37.4 9.21 44.8 11.10 52.2 13.07 56.0 14.10 63.4 16.14 70.7 18.27 76.7 19.74

40.0 37.4 11.01 44.8 13.25 52.2 15.61 56.0 16.82 63.4 19.32 67.1 19.74 70.3 19.74

43.0 37.4 12.14 44.8 14.64 52.2 17.24 56.0 18.58 60.8 19.74 63.7 19.74 66.4 19.58

9 46.0 37.4 13.34 44.8 16.10 52.2 18.99 52.4 18.30 52.4 16.82 52.4 15.45 52.4 14.18
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


20 HP (U-8MF2E8 & U-12MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 33.6 4.92 40.3 5.89 47.0 6.89 50.4 7.39 57.1 8.38 63.8 9.36 70.6 10.35

-5.0 33.6 4.92 40.3 5.91 47.0 6.89 50.4 7.39 57.1 8.38 63.8 9.36 70.6 10.35

0.0 33.6 4.92 40.3 5.91 47.0 6.89 50.4 7.40 57.1 8.39 63.8 9.38 70.6 10.38

5.0 33.6 4.92 40.3 5.92 47.0 6.91 50.4 7.42 57.1 8.40 63.8 9.40 70.6 10.41

10.0 33.6 4.94 40.3 5.94 47.0 6.94 50.4 7.44 57.1 8.45 63.8 9.45 70.6 10.45

15.0 33.6 4.96 40.3 5.98 47.0 6.99 50.4 7.50 57.1 8.52 63.8 9.53 70.6 10.56
90% 20.0 33.6 5.05 40.3 6.08 47.0 7.12 50.4 7.64 57.1 8.70 63.8 9.74 70.6 10.80

25.0 33.6 5.36 40.3 6.47 47.0 7.60 50.4 8.16 57.1 9.28 63.8 10.38 70.6 11.56

30.0 33.6 6.71 40.3 8.01 47.0 9.36 50.4 10.05 57.1 11.48 63.8 12.96 70.6 14.49

35.0 33.6 8.19 40.3 9.77 47.0 11.42 50.4 12.27 57.1 14.00 63.8 15.78 70.6 17.63
40.0 33.6 9.76 40.3 11.67 47.0 13.65 50.4 14.65 57.1 16.72 63.8 18.87 68.3 19.74

43.0 33.6 10.76 40.3 12.89 47.0 15.07 50.4 16.20 57.1 18.50 61.9 19.74 64.8 19.74

46.0 33.6 11.82 40.3 14.17 47.0 16.60 50.4 17.85 52.4 17.54 52.4 16.12 52.4 14.81

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 29.8 4.37 35.8 5.25 41.8 6.12 44.8 6.56 50.8 7.44 56.7 8.32 62.7 9.19

-5.0 29.8 4.37 35.8 5.25 41.8 6.12 44.8 6.57 50.8 7.44 56.7 8.32 62.7 9.19

0.0 29.8 4.37 35.8 5.25 41.8 6.13 44.8 6.57 50.8 7.44 56.7 8.33 62.7 9.21

5.0 29.8 4.39 35.8 5.26 41.8 6.15 44.8 6.58 50.8 7.46 56.7 8.35 62.7 9.24

10.0 29.8 4.39 35.8 5.27 41.8 6.16 44.8 6.60 50.8 7.49 56.7 8.38 62.7 9.26

15.0 29.8 4.41 35.8 5.30 41.8 6.19 44.8 6.64 50.8 7.54 56.7 8.45 62.7 9.35
80% 20.0 29.8 4.46 35.8 5.37 41.8 6.29 44.8 6.75 50.8 7.67 56.7 8.60 62.7 9.52
25.0 29.8 4.68 35.8 5.65 41.8 6.63 44.8 7.12 50.8 8.09 56.7 9.05 62.7 10.01

30.0 29.8 5.91 35.8 6.97 41.8 8.07 44.8 8.63 50.8 9.77 56.7 10.96 62.7 12.17

35.0 29.8 7.19 35.8 8.52 41.8 9.87 44.8 10.56 50.8 11.97 56.7 13.41 62.7 14.88

40.0 29.8 8.57 35.8 10.17 41.8 11.80 44.8 12.63 50.8 14.33 56.7 16.05 62.7 17.82
43.0 29.8 9.45 35.8 11.22 41.8 13.04 44.8 13.97 50.8 15.85 56.7 17.77 62.6 19.68

46.0 29.8 10.38 35.8 12.34 41.8 14.35 44.8 15.38 50.8 17.48 52.4 16.99 52.4 15.61

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 26.2 3.82 31.4 4.58 36.6 5.36 39.2 5.74 44.4 6.50 49.7 7.28 54.9 8.04
-5.0 26.2 3.82 31.4 4.60 36.6 5.36 39.2 5.74 44.4 6.51 49.7 7.28 54.9 8.05

0.0 26.2 3.82 31.4 4.60 36.6 5.36 39.2 5.75 44.4 6.51 49.7 7.29 54.9 8.05
5.0 26.2 3.84 31.4 4.60 36.6 5.37 39.2 5.75 44.4 6.53 49.7 7.30 54.9 8.07

10.0 26.2 3.84 31.4 4.61 36.6 5.39 39.2 5.77 44.4 6.54 49.7 7.32 54.9 8.09
15.0 26.2 3.85 31.4 4.62 36.6 5.41 39.2 5.80 44.4 6.58 49.7 7.36 54.9 8.15

70% 20.0 26.2 3.89 31.4 4.68 36.6 5.47 39.2 5.87 44.4 6.67 49.7 7.46 54.9 8.26

25.0 26.2 4.03 31.4 4.88 36.6 5.71 39.2 6.12 44.4 6.95 49.7 7.78 54.9 8.60

30.0 26.2 5.15 31.4 6.01 36.6 6.88 39.2 7.32 44.4 8.22 49.7 9.14 54.9 10.07

35.0 26.2 6.26 31.4 7.33 36.6 8.43 39.2 8.98 44.4 10.10 49.7 11.24 54.9 12.38
40.0 26.2 7.44 31.4 8.76 36.6 10.08 39.2 10.76 44.4 12.10 49.7 13.47 54.9 14.86

43.0 26.2 8.21 31.4 9.66 36.6 11.14 39.2 11.89 44.4 13.40 49.7 14.92 54.9 16.47
46.0 26.2 9.00 31.4 10.62 36.6 12.27 39.2 13.10 44.4 14.78 49.7 16.47 52.4 16.71

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 22.4 3.27 26.9 3.93 31.4 4.60 33.6 4.92 38.1 5.57 42.6 6.23 47.0 6.89

-5.0 22.4 3.27 26.9 3.93 31.4 4.60 33.6 4.92 38.1 5.58 42.6 6.23 47.0 6.89

0.0 22.4 3.29 26.9 3.93 31.4 4.60 33.6 4.92 38.1 5.58 42.6 6.25 47.0 6.89

5.0 22.4 3.29 26.9 3.95 31.4 4.60 33.6 4.94 38.1 5.58 42.6 6.25 47.0 6.91
10.0 22.4 3.29 26.9 3.95 31.4 4.61 33.6 4.94 38.1 5.60 42.6 6.26 47.0 6.92

15.0 22.4 3.30 26.9 3.96 31.4 4.62 33.6 4.96 38.1 5.63 42.6 6.29 47.0 6.97

60% 20.0 22.4 3.33 26.9 3.99 31.4 4.67 33.6 5.01 38.1 5.68 42.6 6.36 47.0 7.04
25.0 22.4 3.41 26.9 4.12 31.4 4.82 33.6 5.16 38.1 5.87 42.6 6.56 47.0 7.25

30.0 22.4 4.40 26.9 5.10 31.4 5.78 33.6 6.13 38.1 6.81 42.6 7.50 47.0 8.19

35.0 22.4 5.37 26.9 6.23 31.4 7.09 33.6 7.53 38.1 8.39 42.6 9.25 47.0 10.12

40.0 22.4 6.39 26.9 7.43 31.4 8.49 33.6 9.01 38.1 10.07 42.6 11.12 47.0 12.17

43.0 22.4 7.02 26.9 8.19 31.4 9.38 33.6 9.95 38.1 11.14 42.6 12.31 47.0 13.49

46.0 22.4 7.68 26.9 9.00 31.4 10.31 33.6 10.96 38.1 12.28 42.6 13.59 47.0 14.92

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


20 HP (U-8MF2E8 & U-12MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 18.6 2.74 22.4 3.27 26.2 3.82 28.0 4.10 31.8 4.65 35.4 5.19 39.2 5.74

-5.0 18.6 2.74 22.4 3.27 26.2 3.82 28.0 4.10 31.8 4.65 35.4 5.20 39.2 5.74

0.0 18.6 2.74 22.4 3.29 26.2 3.84 28.0 4.10 31.8 4.65 35.4 5.20 39.2 5.75

5.0 18.6 2.74 22.4 3.29 26.2 3.84 28.0 4.10 31.8 4.65 35.4 5.20 39.2 5.75

10.0 18.6 2.74 22.4 3.29 26.2 3.84 28.0 4.12 31.8 4.67 35.4 5.22 39.2 5.77

15.0 18.6 2.75 22.4 3.30 26.2 3.85 28.0 4.13 31.8 4.68 35.4 5.23 39.2 5.78

50% 20.0 18.6 2.76 22.4 3.31 26.2 3.88 28.0 4.16 31.8 4.71 35.4 5.27 39.2 5.82

25.0 18.6 2.82 22.4 3.38 26.2 3.96 28.0 4.24 31.8 4.82 35.4 5.39 39.2 5.95

30.0 18.6 3.40 22.4 3.98 26.2 4.54 28.0 4.82 31.8 5.39 35.4 5.94 39.2 6.50

35.0 18.6 4.55 22.4 5.20 26.2 5.85 28.0 6.18 31.8 6.82 35.4 7.46 39.2 8.09

40.0 18.6 5.37 22.4 6.19 26.2 6.99 28.0 7.40 31.8 8.19 35.4 8.98 39.2 9.76

43.0 18.6 5.89 22.4 6.81 26.2 7.71 28.0 8.16 31.8 9.05 35.4 9.94 39.2 10.81

46.0 18.6 6.44 22.4 7.47 26.2 8.47 28.0 8.98 31.8 9.98 35.4 10.97 39.2 11.94

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 15.0 2.19 17.9 2.62 20.9 3.06 22.4 3.29 25.4 3.72 28.4 4.16 31.4 4.60

-5.0 15.0 2.19 17.9 2.62 20.9 3.06 22.4 3.29 25.4 3.72 28.4 4.16 31.4 4.60

0.0 15.0 2.19 17.9 2.62 20.9 3.06 22.4 3.29 25.4 3.72 28.4 4.16 31.4 4.60

5.0 15.0 2.19 17.9 2.62 20.9 3.06 22.4 3.29 25.4 3.72 28.4 4.16 31.4 4.60

10.0 15.0 2.19 17.9 2.62 20.9 3.07 22.4 3.29 25.4 3.72 28.4 4.17 31.4 4.61
15.0 15.0 2.20 17.9 2.64 20.9 3.07 22.4 3.30 25.4 3.74 28.4 4.17 31.4 4.61

40% 20.0 15.0 2.20 17.9 2.65 20.9 3.09 22.4 3.31 25.4 3.75 28.4 4.20 31.4 4.64

25.0 15.0 2.24 17.9 2.68 20.9 3.13 22.4 3.36 25.4 3.81 28.4 4.26 31.4 4.71

30.0 15.0 2.54 17.9 2.99 20.9 3.44 22.4 3.67 25.4 4.10 28.4 4.55 31.4 4.99

35.0 15.0 3.76 17.9 4.26 20.9 4.72 22.4 4.96 25.4 5.41 28.4 5.85 31.4 6.29
40.0 15.0 4.43 17.9 5.03 20.9 5.63 22.4 5.91 25.4 6.49 28.4 7.04 31.4 7.59

43.0 15.0 4.84 17.9 5.51 20.9 6.19 22.4 6.51 25.4 7.16 28.4 7.78 31.4 8.40
46.0 15.0 5.27 17.9 6.03 20.9 6.78 22.4 7.15 25.4 7.87 28.4 8.57 31.4 9.26

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 11.2 1.64 13.4 1.96 15.7 2.30 16.8 2.45 19.0 2.79 21.3 3.12 23.5 3.44
-5.0 11.2 1.64 13.4 1.96 15.7 2.30 16.8 2.45 19.0 2.79 21.3 3.12 23.5 3.44

0.0 11.2 1.64 13.4 1.97 15.7 2.30 16.8 2.47 19.0 2.79 21.3 3.12 23.5 3.44

5.0 11.2 1.64 13.4 1.97 15.7 2.30 16.8 2.47 19.0 2.79 21.3 3.12 23.5 3.45

10.0 11.2 1.64 13.4 1.97 15.7 2.30 16.8 2.47 19.0 2.79 21.3 3.13 23.5 3.45

15.0 11.2 1.65 13.4 1.97 15.7 2.30 16.8 2.47 19.0 2.81 21.3 3.13 23.5 3.45

30% 20.0 11.2 1.65 13.4 1.99 15.7 2.31 16.8 2.48 19.0 2.81 21.3 3.14 23.5 3.47

25.0 11.2 1.66 13.4 2.00 15.7 2.33 16.8 2.50 19.0 2.83 21.3 3.17 23.5 3.50

30.0 11.2 1.80 13.4 2.13 15.7 2.47 16.8 2.64 19.0 2.96 21.3 3.30 23.5 3.62

35.0 11.2 3.05 13.4 3.37 15.7 3.69 16.8 3.85 19.0 4.15 21.3 4.43 23.5 4.70

40.0 11.2 3.53 13.4 3.95 15.7 4.36 16.8 4.55 19.0 4.94 21.3 5.29 23.5 5.64

43.0 11.2 3.84 13.4 4.31 15.7 4.77 16.8 4.99 19.0 5.43 21.3 5.84 23.5 6.25

46.0 11.2 4.15 13.4 4.68 15.7 5.20 16.8 5.46 19.0 5.94 21.3 6.42 23.5 6.87

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


22 HP (U-8MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 57.3 8.59 66.1 9.93 66.1 9.93 66.1 9.93 74.9 11.26 83.8 12.59 92.6 13.90

-5.0 57.3 8.59 66.1 9.95 66.1 9.95 66.1 9.95 74.9 11.28 83.8 12.60 92.6 13.92

0.0 57.3 8.60 66.1 9.96 66.1 9.96 66.1 9.96 74.9 11.31 83.8 12.64 92.6 13.95

5.0 57.3 8.62 66.1 10.00 66.1 10.00 66.1 10.00 74.9 11.34 83.8 12.67 92.6 14.00

10.0 57.3 8.63 66.1 10.06 66.1 10.06 66.1 10.06 74.9 11.42 83.8 12.75 92.6 14.08

15.0 57.3 8.70 66.1 10.19 66.1 10.19 66.1 10.19 74.9 11.58 83.8 12.91 92.6 14.24
130% 20.0 57.3 8.86 66.1 10.50 66.1 10.50 66.1 10.50 74.9 11.96 83.8 13.27 92.6 14.58

25.0 57.3 9.51 66.1 11.91 66.1 11.91 66.1 11.91 74.9 13.90 83.8 16.01 92.6 18.23

30.0 57.3 11.87 66.1 14.82 66.1 14.82 66.1 14.82 74.9 17.22 83.8 19.75 90.0 21.06

35.0 57.3 14.52 66.1 17.95 66.1 17.95 66.1 17.95 74.9 20.80 78.8 21.06 82.3 21.06
40.0 57.3 17.37 65.5 21.06 65.5 21.06 65.5 21.06 68.7 21.06 72.0 21.06 75.3 21.06

43.0 57.3 19.20 61.9 21.06 61.9 21.06 61.9 21.06 63.3 20.07 63.3 18.40 63.3 16.86

46.0 50.0 16.26 50.0 16.26 50.0 16.26 50.0 16.26 50.0 14.94 50.0 13.71 50.0 12.56

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 51.7 7.74 62.0 9.30 64.6 9.70 64.6 9.70 73.2 11.00 81.8 12.30 90.4 13.58

-5.0 51.7 7.74 62.0 9.32 64.6 9.72 64.6 9.72 73.2 11.02 81.8 12.31 90.4 13.59

0.0 51.7 7.76 62.0 9.32 64.6 9.74 64.6 9.74 73.2 11.03 81.8 12.33 90.4 13.62

5.0 51.7 7.78 62.0 9.33 64.6 9.75 64.6 9.75 73.2 11.08 81.8 12.38 90.4 13.67

10.0 51.7 7.79 62.0 9.38 64.6 9.82 64.6 9.82 73.2 11.15 81.8 12.46 90.4 13.75

15.0 51.7 7.86 62.0 9.46 64.6 9.93 64.6 9.93 73.2 11.29 81.8 12.62 90.4 13.90
120% 20.0 51.7 8.00 62.0 9.67 64.6 10.22 64.6 10.22 73.2 11.65 81.8 12.98 90.4 14.26
25.0 51.7 8.60 62.0 10.42 64.6 11.49 64.6 11.49 73.2 13.38 81.8 15.37 90.4 17.48

30.0 51.7 10.72 62.0 13.11 64.6 14.32 64.6 14.32 73.2 16.61 81.8 19.02 89.4 21.06

35.0 51.7 13.09 62.0 15.97 64.6 17.35 64.6 17.35 73.2 20.07 78.4 21.06 81.9 21.06

40.0 51.7 15.65 62.0 19.07 64.6 20.67 64.6 20.67 68.3 21.06 71.6 21.06 75.0 21.06
43.0 51.7 17.29 61.7 21.06 61.7 21.06 61.7 21.06 63.3 20.25 63.3 18.57 63.3 17.01

46.0 50.0 16.36 50.0 16.36 50.0 16.36 50.0 16.36 49.9 15.03 50.0 13.80 50.0 12.65

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 46.2 6.93 55.5 8.33 63.0 9.48 63.0 9.48 71.5 10.74 79.8 12.00 88.3 13.27
-5.0 46.2 6.93 55.5 8.33 63.0 9.48 63.0 9.48 71.5 10.76 79.8 12.02 88.3 13.28

0.0 46.2 6.95 55.5 8.34 63.0 9.49 63.0 9.49 71.5 10.77 79.8 12.04 88.3 13.30
5.0 46.2 6.95 55.5 8.36 63.0 9.53 63.0 9.53 71.5 10.81 79.8 12.09 88.3 13.35

10.0 46.2 6.98 55.5 8.39 63.0 9.57 63.0 9.57 71.5 10.87 79.8 12.17 88.3 13.43
15.0 46.2 7.03 55.5 8.47 63.0 9.69 63.0 9.69 71.5 11.02 79.8 12.31 88.3 13.58

110% 20.0 46.2 7.18 55.5 8.67 63.0 9.96 63.0 9.96 71.5 11.34 79.8 12.67 88.3 13.92

25.0 46.2 7.73 55.5 9.36 63.0 11.06 63.0 11.06 71.5 12.86 79.8 14.76 88.3 16.77

30.0 46.2 9.62 55.5 11.71 63.0 13.82 63.0 13.82 71.5 16.01 79.8 18.29 88.3 20.69

35.0 46.2 11.75 55.5 14.27 63.0 16.75 63.0 16.75 71.5 19.36 77.9 21.06 81.4 21.06
40.0 46.2 14.01 55.5 17.03 63.0 19.97 63.0 19.97 68.0 21.06 71.2 21.06 74.5 21.06

43.0 46.2 15.47 55.5 18.82 61.4 21.06 61.4 21.06 63.3 20.43 63.3 18.74 63.3 17.17
46.0 46.2 17.03 50.0 16.48 50.0 16.48 50.0 16.48 50.0 15.15 50.0 13.90 50.0 12.73

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 41.0 6.16 49.2 7.39 57.4 8.62 61.5 9.23 69.7 10.48 77.9 11.71 86.1 12.94

-5.0 41.0 6.16 49.2 7.39 57.4 8.63 61.5 9.25 69.7 10.48 77.9 11.73 86.1 12.96

0.0 41.0 6.16 49.2 7.40 57.4 8.63 61.5 9.27 69.7 10.51 77.9 11.75 86.1 12.98

5.0 41.0 6.17 49.2 7.42 57.4 8.67 61.5 9.28 69.7 10.55 77.9 11.79 86.1 13.02
10.0 41.0 6.19 49.2 7.45 57.4 8.72 61.5 9.33 69.7 10.59 77.9 11.87 86.1 13.11

15.0 41.0 6.24 49.2 7.52 57.4 8.80 61.5 9.44 69.7 10.72 77.9 12.02 86.1 13.25

100% 20.0 41.0 6.38 49.2 7.70 57.4 9.04 61.5 9.70 69.7 11.03 77.9 12.36 86.1 13.58
25.0 41.0 6.90 49.2 8.34 57.4 9.85 61.5 10.66 69.7 12.36 77.9 14.16 86.1 16.05

30.0 41.0 8.59 49.2 10.42 57.4 12.33 61.5 13.33 69.7 15.41 77.9 17.58 86.1 19.86

35.0 41.0 10.45 49.2 12.65 57.4 14.95 61.5 16.20 69.4 18.55 77.4 21.06 80.9 21.06

40.0 41.0 12.47 49.2 15.10 57.4 17.87 61.5 19.29 67.6 21.06 70.8 21.06 74.1 21.06

43.0 41.0 13.75 49.2 16.67 57.4 19.73 61.0 21.06 63.3 20.62 63.3 18.92 63.3 17.33

9 46.0 41.0 15.11 49.2 18.35 50.0 17.32 50.0 16.61 50.0 15.26 50.0 14.00 50.0 12.83
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


22 HP (U-8MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 36.9 5.54 44.3 6.64 51.7 7.76 55.4 8.31 62.7 9.43 70.1 10.53 77.5 11.65

-5.0 36.9 5.54 44.3 6.64 51.7 7.76 55.4 8.33 62.7 9.43 70.1 10.55 77.5 11.66

0.0 36.9 5.54 44.3 6.66 51.7 7.78 55.4 8.33 62.7 9.44 70.1 10.56 77.5 11.68

5.0 36.9 5.56 44.3 6.67 51.7 7.79 55.4 8.34 62.7 9.48 70.1 10.59 77.5 11.71

10.0 36.9 5.57 44.3 6.69 51.7 7.82 55.4 8.39 62.7 9.53 70.1 10.66 77.5 11.78

15.0 36.9 5.61 44.3 6.74 51.7 7.89 55.4 8.47 62.7 9.61 70.1 10.76 77.5 11.92
90% 20.0 36.9 5.70 44.3 6.89 51.7 8.07 55.4 8.65 62.7 9.83 70.1 11.02 77.5 12.20

25.0 36.9 6.09 44.3 7.35 51.7 8.63 55.4 9.25 62.7 10.50 70.1 11.92 77.5 13.41

30.0 36.9 7.57 44.3 9.07 51.7 10.66 55.4 11.47 62.7 13.15 70.1 14.92 77.5 16.73

35.0 36.9 9.22 44.3 11.06 51.7 12.99 55.4 13.98 62.7 16.01 70.1 18.11 77.5 20.30
40.0 36.9 11.00 44.3 13.20 51.7 15.50 55.4 16.69 62.7 19.12 69.1 21.06 72.2 21.06

43.0 36.9 12.13 44.3 14.60 51.7 17.14 55.4 18.47 62.5 21.06 63.3 19.76 63.3 18.11

46.0 36.9 13.33 44.3 16.05 50.0 17.90 50.0 17.16 50.0 15.78 50.0 14.48 50.0 13.28

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 32.8 4.92 39.4 5.91 45.9 6.90 49.2 7.39 55.8 8.38 62.3 9.36 68.9 10.35

-5.0 32.8 4.92 39.4 5.91 45.9 6.90 49.2 7.39 55.8 8.38 62.3 9.36 68.9 10.35

0.0 32.8 4.92 39.4 5.91 45.9 6.90 49.2 7.40 55.8 8.39 62.3 9.38 68.9 10.37

5.0 32.8 4.92 39.4 5.93 45.9 6.92 49.2 7.42 55.8 8.41 62.3 9.41 68.9 10.40

10.0 32.8 4.94 39.4 5.95 45.9 6.93 49.2 7.44 55.8 8.44 62.3 9.44 68.9 10.45

15.0 32.8 4.97 39.4 5.98 45.9 6.98 49.2 7.50 55.8 8.51 62.3 9.53 68.9 10.55
80% 20.0 32.8 5.04 39.4 6.08 45.9 7.11 49.2 7.63 55.8 8.67 62.3 9.70 68.9 10.74
25.0 32.8 5.31 39.4 6.42 45.9 7.52 49.2 8.07 55.8 9.15 62.3 10.22 68.9 11.31

30.0 32.8 6.59 39.4 7.84 45.9 9.10 49.2 9.77 55.8 11.11 62.3 12.49 68.9 13.92

35.0 32.8 8.05 39.4 9.57 45.9 11.15 49.2 11.94 55.8 13.58 62.3 15.26 68.9 16.98

40.0 32.8 9.61 39.4 11.44 45.9 13.33 49.2 14.29 55.8 16.25 62.3 18.26 68.9 20.33
43.0 32.8 10.59 39.4 12.64 45.9 14.74 49.2 15.81 55.8 18.00 62.3 20.25 63.3 19.13

46.0 32.8 11.65 39.4 13.92 45.9 16.23 49.2 17.43 49.9 16.44 49.9 15.11 50.0 13.87

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 28.7 4.31 34.4 5.17 40.2 6.03 43.1 6.46 48.8 7.32 54.6 8.18 60.3 9.06
-5.0 28.7 4.31 34.4 5.17 40.2 6.04 43.1 6.46 48.8 7.34 54.6 8.20 60.3 9.06

0.0 28.7 4.31 34.4 5.17 40.2 6.04 43.1 6.48 48.8 7.34 54.6 8.20 60.3 9.07
5.0 28.7 4.31 34.4 5.18 40.2 6.04 43.1 6.48 48.8 7.35 54.6 8.21 60.3 9.09

10.0 28.7 4.33 34.4 5.20 40.2 6.06 43.1 6.50 48.8 7.37 54.6 8.25 60.3 9.12
15.0 28.7 4.34 34.4 5.22 40.2 6.09 43.1 6.54 48.8 7.42 54.6 8.29 60.3 9.19

70% 20.0 28.7 4.39 34.4 5.28 40.2 6.19 43.1 6.63 48.8 7.53 54.6 8.42 60.3 9.33

25.0 28.7 4.57 34.4 5.52 40.2 6.45 43.1 6.92 48.8 7.86 54.6 8.78 60.3 9.70

30.0 28.7 5.70 34.4 6.69 40.2 7.70 43.1 8.21 48.8 9.25 54.6 10.32 60.3 11.39

35.0 28.7 6.95 34.4 8.18 40.2 9.44 43.1 10.08 48.8 11.36 54.6 12.67 60.3 13.98
40.0 28.7 8.29 34.4 9.78 40.2 11.31 43.1 12.07 48.8 13.62 54.6 15.20 60.3 16.78

43.0 28.7 9.14 34.4 10.81 40.2 12.51 43.1 13.35 48.8 15.08 54.6 16.85 60.3 18.63
46.0 28.7 10.04 34.4 11.89 40.2 13.77 43.1 14.73 48.8 16.65 50.0 15.96 50.0 14.64

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 24.6 3.69 29.5 4.42 34.4 5.17 36.9 5.54 41.8 6.29 46.7 7.01 51.7 7.76

-5.0 24.6 3.69 29.5 4.42 34.4 5.17 36.9 5.54 41.8 6.29 46.7 7.01 51.7 7.76

0.0 24.6 3.69 29.5 4.44 34.4 5.17 36.9 5.54 41.8 6.29 46.7 7.03 51.7 7.76

5.0 24.6 3.69 29.5 4.44 34.4 5.18 36.9 5.56 41.8 6.30 46.7 7.03 51.7 7.78
10.0 24.6 3.71 29.5 4.44 34.4 5.18 36.9 5.56 41.8 6.32 46.7 7.06 51.7 7.81

15.0 24.6 3.71 29.5 4.47 34.4 5.22 36.9 5.59 41.8 6.33 46.7 7.10 51.7 7.84

60% 20.0 24.6 3.74 29.5 4.50 34.4 5.27 36.9 5.65 41.8 6.42 46.7 7.18 51.7 7.94
25.0 24.6 3.87 29.5 4.65 34.4 5.44 36.9 5.83 41.8 6.63 46.7 7.40 51.7 8.18

30.0 24.6 4.88 29.5 5.64 34.4 6.42 36.9 6.80 41.8 7.58 46.7 8.36 51.7 9.15

35.0 24.6 5.93 29.5 6.90 34.4 7.87 36.9 8.36 41.8 9.35 46.7 10.32 51.7 11.31

40.0 24.6 7.06 29.5 8.25 34.4 9.43 36.9 10.03 41.8 11.23 46.7 12.43 51.7 13.62

43.0 24.6 7.78 29.5 9.10 34.4 10.43 36.9 11.10 41.8 12.43 46.7 13.77 51.7 15.11

46.0 24.6 8.52 29.5 10.01 34.4 11.49 36.9 12.23 41.8 13.72 46.7 15.21 50.0 15.75

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


22 HP (U-8MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 20.5 3.08 24.6 3.69 28.7 4.31 30.8 4.62 34.9 5.23 38.9 5.85 43.1 6.46

-5.0 20.5 3.08 24.6 3.69 28.7 4.31 30.8 4.62 34.9 5.23 38.9 5.85 43.1 6.46

0.0 20.5 3.08 24.6 3.69 28.7 4.31 30.8 4.62 34.9 5.23 38.9 5.85 43.1 6.46

5.0 20.5 3.08 24.6 3.69 28.7 4.31 30.8 4.62 34.9 5.25 38.9 5.86 43.1 6.48

10.0 20.5 3.08 24.6 3.71 28.7 4.33 30.8 4.63 34.9 5.25 38.9 5.86 43.1 6.50

15.0 20.5 3.09 24.6 3.71 28.7 4.34 30.8 4.65 34.9 5.27 38.9 5.90 43.1 6.51

50% 20.0 20.5 3.11 24.6 3.74 28.7 4.37 30.8 4.68 34.9 5.31 38.9 5.95 43.1 6.56

25.0 20.5 3.18 24.6 3.82 28.7 4.47 30.8 4.80 34.9 5.44 38.9 6.08 43.1 6.71

30.0 20.5 3.77 24.6 4.42 28.7 5.05 30.8 5.38 34.9 5.99 38.9 6.63 43.1 7.24

35.0 20.5 4.97 24.6 5.72 28.7 6.45 30.8 6.80 34.9 7.52 38.9 8.23 43.1 8.93

40.0 20.5 5.90 24.6 6.80 28.7 7.71 30.8 8.16 34.9 9.04 38.9 9.93 43.1 10.79

43.0 20.5 6.48 24.6 7.52 28.7 8.52 30.8 9.02 34.9 10.01 38.9 11.00 43.1 11.97

46.0 20.5 7.10 24.6 8.25 28.7 9.38 30.8 9.93 34.9 11.05 38.9 12.15 43.1 13.25

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 16.4 2.46 19.7 2.95 22.9 3.45 24.6 3.69 27.9 4.18 31.2 4.68 34.4 5.17

-5.0 16.4 2.46 19.7 2.95 22.9 3.45 24.6 3.69 27.9 4.18 31.2 4.68 34.4 5.17

0.0 16.4 2.46 19.7 2.95 22.9 3.45 24.6 3.69 27.9 4.20 31.2 4.68 34.4 5.17

5.0 16.4 2.46 19.7 2.96 22.9 3.45 24.6 3.69 27.9 4.20 31.2 4.68 34.4 5.18

10.0 16.4 2.46 19.7 2.96 22.9 3.45 24.6 3.71 27.9 4.20 31.2 4.70 34.4 5.18
15.0 16.4 2.48 19.7 2.96 22.9 3.47 24.6 3.71 27.9 4.21 31.2 4.70 34.4 5.20

40% 20.0 16.4 2.48 19.7 2.98 22.9 3.48 24.6 3.73 27.9 4.23 31.2 4.73 34.4 5.23

25.0 16.4 2.53 19.7 3.03 22.9 3.53 24.6 3.79 27.9 4.29 31.2 4.80 34.4 5.30

30.0 16.4 2.84 19.7 3.34 22.9 3.84 24.6 4.10 27.9 4.58 31.2 5.09 34.4 5.59

35.0 16.4 4.08 19.7 4.62 22.9 5.14 24.6 5.39 27.9 5.90 31.2 6.38 34.4 6.85
40.0 16.4 4.81 19.7 5.49 22.9 6.14 24.6 6.46 27.9 7.08 31.2 7.70 34.4 8.28

43.0 16.4 5.28 19.7 6.03 22.9 6.77 24.6 7.13 27.9 7.84 31.2 8.52 34.4 9.20
46.0 16.4 5.75 19.7 6.61 22.9 7.44 24.6 7.84 27.9 8.63 31.2 9.40 34.4 10.16

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 12.3 1.85 14.8 2.22 17.2 2.58 18.5 2.77 20.9 3.14 23.4 3.50 25.8 3.87
-5.0 12.3 1.85 14.8 2.22 17.2 2.59 18.5 2.77 20.9 3.14 23.4 3.52 25.8 3.87

0.0 12.3 1.85 14.8 2.22 17.2 2.59 18.5 2.77 20.9 3.14 23.4 3.52 25.8 3.87

5.0 12.3 1.85 14.8 2.22 17.2 2.59 18.5 2.77 20.9 3.14 23.4 3.52 25.8 3.89

10.0 12.3 1.85 14.8 2.22 17.2 2.59 18.5 2.77 20.9 3.14 23.4 3.52 25.8 3.89

15.0 12.3 1.85 14.8 2.22 17.2 2.59 18.5 2.79 20.9 3.16 23.4 3.52 25.8 3.89

30% 20.0 12.3 1.86 14.8 2.24 17.2 2.61 18.5 2.79 20.9 3.16 23.4 3.53 25.8 3.90

25.0 12.3 1.88 14.8 2.25 17.2 2.62 18.5 2.82 20.9 3.19 23.4 3.56 25.8 3.94

30.0 12.3 2.01 14.8 2.38 17.2 2.77 18.5 2.95 20.9 3.32 23.4 3.69 25.8 4.07

35.0 12.3 3.26 14.8 3.63 17.2 3.97 18.5 4.13 20.9 4.46 23.4 4.75 25.8 4.99

40.0 12.3 3.81 14.8 4.26 17.2 4.70 18.5 4.91 20.9 5.31 23.4 5.70 25.8 6.08

43.0 12.3 4.15 14.8 4.67 17.2 5.17 18.5 5.39 20.9 5.86 23.4 6.32 25.8 6.74

46.0 12.3 4.50 14.8 5.09 17.2 5.64 18.5 5.91 20.9 6.45 23.4 6.95 25.8 7.44

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


24 HP (U-8MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 63.4 8.94 73.1 10.34 73.1 10.34 73.1 10.34 82.8 11.75 92.6 13.12 102.3 14.50

-5.0 63.4 8.95 73.1 10.36 73.1 10.36 73.1 10.36 82.8 11.77 92.6 13.14 102.3 14.52

0.0 63.4 8.95 73.1 10.40 73.1 10.40 73.1 10.40 82.8 11.78 92.6 13.17 102.3 14.56

5.0 63.4 8.97 73.1 10.43 73.1 10.43 73.1 10.43 82.8 11.86 92.6 13.25 102.3 14.63

10.0 63.4 9.01 73.1 10.53 73.1 10.53 73.1 10.53 82.8 11.97 92.6 13.36 102.3 14.74

15.0 63.4 9.10 73.1 10.71 73.1 10.71 73.1 10.71 82.8 12.21 92.6 13.60 102.3 14.99
130% 20.0 63.4 9.34 73.1 11.23 73.1 11.23 73.1 11.23 82.8 12.95 92.6 15.23 102.3 17.67

25.0 63.4 10.56 73.1 13.88 73.1 13.88 73.1 13.88 82.8 16.41 92.6 19.13 102.3 22.05

30.0 63.4 13.25 73.1 17.08 73.1 17.08 73.1 17.08 82.8 20.09 92.6 23.33 97.6 24.05

35.0 63.4 16.10 73.1 20.54 73.1 20.54 73.1 20.54 82.5 23.94 86.2 24.05 90.0 24.05
40.0 63.4 19.18 72.6 24.05 72.6 24.05 72.6 24.05 75.9 24.05 78.7 23.72 78.7 21.74

43.0 63.4 21.18 64.8 21.55 64.8 21.55 64.8 21.55 64.8 19.80 64.8 18.17 64.8 16.63

46.0 51.2 15.95 51.2 15.95 51.2 15.95 51.2 15.95 51.2 14.65 51.2 13.45 51.2 12.34

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 57.1 8.07 68.5 9.68 71.4 10.10 71.4 10.10 80.9 11.47 90.4 12.82 100.0 14.17

-5.0 57.1 8.07 68.5 9.69 71.4 10.12 71.4 10.12 80.9 11.49 90.4 12.84 100.0 14.19

0.0 57.1 8.08 68.5 9.71 71.4 10.14 71.4 10.14 80.9 11.51 90.4 12.88 100.0 14.23

5.0 57.1 8.10 68.5 9.73 71.4 10.19 71.4 10.19 80.9 11.56 90.4 12.93 100.0 14.28

10.0 57.1 8.14 68.5 9.79 71.4 10.27 71.4 10.27 80.9 11.67 90.4 13.04 100.0 14.41

15.0 57.1 8.21 68.5 9.90 71.4 10.45 71.4 10.45 80.9 11.91 90.4 13.28 100.0 14.65
120% 20.0 57.1 8.45 68.5 10.23 71.4 10.93 71.4 10.93 80.9 12.49 90.4 14.58 100.0 16.89
25.0 57.1 9.53 68.5 11.88 71.4 13.38 71.4 13.38 80.9 15.78 90.4 18.37 100.0 21.15

30.0 57.1 11.93 68.5 14.80 71.4 16.48 71.4 16.48 80.9 19.35 90.4 22.44 97.0 24.05

35.0 57.1 14.50 68.5 17.93 71.4 19.83 71.4 19.83 80.9 23.24 85.7 24.05 89.4 24.05

40.0 57.1 17.28 68.5 21.33 71.4 23.51 71.4 23.51 75.5 24.05 78.7 23.98 78.7 21.98
43.0 57.1 19.06 64.8 21.74 64.8 21.74 64.8 21.74 64.8 19.98 64.8 18.33 64.8 16.80

46.0 51.2 16.06 51.2 16.06 51.2 16.06 51.2 16.06 51.2 14.76 51.2 13.54 51.2 12.43

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 51.1 7.22 61.3 8.68 69.7 9.86 69.7 9.86 79.0 11.19 88.3 12.51 97.6 13.82
-5.0 51.1 7.22 61.3 8.68 69.7 9.88 69.7 9.88 79.0 11.21 88.3 12.52 97.6 13.86

0.0 51.1 7.23 61.3 8.70 69.7 9.90 69.7 9.90 79.0 11.23 88.3 12.56 97.6 13.89
5.0 51.1 7.25 61.3 8.71 69.7 9.93 69.7 9.93 79.0 11.29 88.3 12.64 97.6 13.95

10.0 51.1 7.29 61.3 8.77 69.7 10.03 69.7 10.03 79.0 11.40 88.3 12.75 97.6 14.06
15.0 51.1 7.36 61.3 8.88 69.7 10.19 69.7 10.19 79.0 11.60 88.3 12.99 97.6 14.30

110% 20.0 51.1 7.57 61.3 9.18 69.7 10.64 69.7 10.64 79.0 12.14 88.3 13.97 97.6 16.15

25.0 51.1 8.55 61.3 10.60 69.7 12.88 69.7 12.88 79.0 15.17 88.3 17.63 97.6 20.28

30.0 51.1 10.69 61.3 13.21 69.7 15.89 69.7 15.89 79.0 18.63 88.3 21.57 96.4 24.05

35.0 51.1 12.97 61.3 16.00 69.7 19.15 69.7 19.15 79.0 22.40 85.2 24.05 88.9 24.05
40.0 51.1 15.45 61.3 19.02 69.7 22.72 69.7 22.72 75.1 24.05 78.4 24.05 78.7 22.24

43.0 51.1 17.04 61.3 20.98 64.8 21.94 64.8 21.94 64.8 20.17 64.8 18.50 64.8 16.96
46.0 51.1 18.72 51.2 16.19 51.2 16.19 51.2 16.19 51.2 14.87 51.2 13.65 51.2 12.52

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 45.4 6.40 54.4 7.70 63.4 8.97 68.0 9.62 77.0 10.92 86.2 12.21 95.2 13.49

-5.0 45.4 6.40 54.4 7.70 63.4 8.99 68.0 9.64 77.0 10.93 86.2 12.23 95.2 13.51

0.0 45.4 6.42 54.4 7.71 63.4 9.01 68.0 9.66 77.0 10.95 86.2 12.27 95.2 13.54

5.0 45.4 6.44 54.4 7.73 63.4 9.05 68.0 9.69 77.0 11.01 86.2 12.32 95.2 13.62
10.0 45.4 6.46 54.4 7.77 63.4 9.10 68.0 9.77 77.0 11.10 86.2 12.43 95.2 13.73

15.0 45.4 6.53 54.4 7.88 63.4 9.25 68.0 9.93 77.0 11.30 86.2 12.67 95.2 13.95

100% 20.0 45.4 6.73 54.4 8.16 63.4 9.62 68.0 10.34 77.0 11.80 86.2 13.36 95.2 15.43
25.0 45.4 7.62 54.4 9.42 63.4 11.36 68.0 12.40 77.0 14.58 86.2 16.91 95.2 19.41

30.0 45.4 9.51 54.4 11.71 63.4 14.08 68.0 15.32 77.0 17.93 86.2 20.72 95.2 23.68

35.0 45.4 11.53 54.4 14.17 63.4 16.93 68.0 18.50 76.7 21.42 84.7 24.05 88.3 24.05

40.0 45.4 13.71 54.4 16.84 63.4 20.17 68.0 21.92 74.6 24.05 77.9 24.05 78.7 22.51

43.0 45.4 15.11 54.4 18.56 63.4 22.24 64.8 22.16 64.8 20.37 64.8 18.69 64.8 17.13

9 46.0 45.4 16.59 51.2 18.48 51.2 17.00 51.2 16.32 51.2 14.99 51.2 13.76 51.2 12.62
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


24 HP (U-8MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 40.8 5.75 49.0 6.92 57.1 8.08 61.2 8.66 69.4 9.82 77.5 10.99 85.7 12.14

-5.0 40.8 5.77 49.0 6.92 57.1 8.08 61.2 8.68 69.4 9.82 77.5 10.99 85.7 12.15

0.0 40.8 5.77 49.0 6.94 57.1 8.10 61.2 8.68 69.4 9.86 77.5 11.03 85.7 12.19

5.0 40.8 5.79 49.0 6.96 57.1 8.12 61.2 8.71 69.4 9.90 77.5 11.06 85.7 12.25

10.0 40.8 5.81 49.0 6.99 57.1 8.18 61.2 8.77 69.4 9.95 77.5 11.16 85.7 12.36

15.0 40.8 5.86 49.0 7.07 57.1 8.27 61.2 8.88 69.4 10.10 77.5 11.34 85.7 12.56

90% 20.0 40.8 6.01 49.0 7.27 57.1 8.55 61.2 9.19 69.4 10.47 77.5 11.77 85.7 13.06

25.0 40.8 6.66 49.0 8.14 57.1 9.73 61.2 10.56 69.4 12.32 77.5 14.21 85.7 16.21

30.0 40.8 8.34 49.0 10.18 57.1 12.12 61.2 13.14 69.4 15.28 77.5 17.54 85.7 19.91

35.0 40.8 10.14 49.0 12.34 57.1 14.67 61.2 15.89 69.4 18.44 77.5 21.13 85.7 23.94

40.0 40.8 12.06 49.0 14.69 57.1 17.46 61.2 18.91 69.4 21.92 75.9 24.05 78.8 23.83

43.0 40.8 13.28 49.0 16.19 57.1 19.26 61.2 20.87 64.8 21.31 64.8 19.57 64.8 17.95

46.0 40.8 14.60 49.0 17.80 51.2 17.61 51.2 16.89 51.2 15.54 51.2 14.26 51.2 13.08

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 36.2 5.12 43.5 6.14 50.8 7.18 54.4 7.70 61.7 8.73 68.9 9.75 76.2 10.79

-5.0 36.2 5.12 43.5 6.16 50.8 7.18 54.4 7.70 61.7 8.73 68.9 9.77 76.2 10.80

0.0 36.2 5.12 43.5 6.16 50.8 7.20 54.4 7.71 61.7 8.75 68.9 9.79 76.2 10.82

5.0 36.2 5.14 43.5 6.18 50.8 7.22 54.4 7.73 61.7 8.77 68.9 9.82 76.2 10.86

10.0 36.2 5.16 43.5 6.20 50.8 7.25 54.4 7.77 61.7 8.82 68.9 9.88 76.2 10.93

15.0 36.2 5.20 43.5 6.25 50.8 7.33 54.4 7.86 61.7 8.94 68.9 10.01 76.2 11.08
80% 20.0 36.2 5.29 43.5 6.40 50.8 7.51 54.4 8.08 61.7 9.19 68.9 10.32 76.2 11.45

25.0 36.2 5.75 43.5 6.99 50.8 8.23 54.4 8.92 61.7 10.30 68.9 11.77 76.2 13.32

30.0 36.2 7.25 43.5 8.75 50.8 10.32 54.4 11.16 61.7 12.86 68.9 14.63 76.2 16.50

35.0 36.2 8.82 43.5 10.64 50.8 12.54 54.4 13.52 61.7 15.58 68.9 17.72 76.2 19.94

40.0 36.2 10.49 43.5 12.67 50.8 14.95 54.4 16.11 61.7 18.56 68.9 21.09 76.2 23.75

43.0 36.2 11.56 43.5 13.97 50.8 16.48 54.4 17.80 61.7 20.50 64.8 20.70 64.8 19.00

46.0 36.2 12.69 43.5 15.36 50.8 18.15 51.2 17.65 51.2 16.22 51.2 14.91 51.2 13.69

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 31.8 4.48 38.1 5.38 44.4 6.27 47.6 6.73 53.9 7.64 60.3 8.53 66.6 9.44

-5.0 31.8 4.48 38.1 5.38 44.4 6.29 47.6 6.73 53.9 7.64 60.3 8.55 66.6 9.44

0.0 31.8 4.50 38.1 5.38 44.4 6.29 47.6 6.75 53.9 7.64 60.3 8.55 66.6 9.45

5.0 31.8 4.50 38.1 5.40 44.4 6.31 47.6 6.75 53.9 7.66 60.3 8.58 66.6 9.49

10.0 31.8 4.50 38.1 5.42 44.4 6.33 47.6 6.79 53.9 7.70 60.3 8.62 66.6 9.55

15.0 31.8 4.53 38.1 5.46 44.4 6.38 47.6 6.85 53.9 7.77 60.3 8.71 66.6 9.64

70% 20.0 31.8 4.61 38.1 5.55 44.4 6.51 47.6 6.99 53.9 7.96 60.3 8.92 66.6 9.88
25.0 31.8 4.92 38.1 5.96 44.4 7.01 47.6 7.53 53.9 8.57 60.3 9.60 66.6 10.77

30.0 31.8 6.23 38.1 7.44 44.4 8.68 47.6 9.32 53.9 10.66 60.3 12.04 66.6 13.47

35.0 31.8 7.59 38.1 9.05 44.4 10.58 47.6 11.36 53.9 12.97 60.3 14.63 66.6 16.35

40.0 31.8 9.03 38.1 10.79 44.4 12.62 47.6 13.56 53.9 15.48 60.3 17.46 66.6 19.54

43.0 31.8 9.93 38.1 11.90 44.4 13.93 47.6 14.97 53.9 17.11 60.3 19.31 64.8 20.44

46.0 31.8 10.92 38.1 13.08 44.4 15.32 47.6 16.48 51.2 17.17 51.2 15.80 51.2 14.50

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 27.2 3.85 32.6 4.61 38.1 5.38 40.8 5.77 46.2 6.55 51.7 7.31 57.1 8.08

-5.0 27.2 3.85 32.6 4.61 38.1 5.38 40.8 5.77 46.2 6.55 51.7 7.31 57.1 8.08

0.0 27.2 3.85 32.6 4.63 38.1 5.38 40.8 5.77 46.2 6.55 51.7 7.33 57.1 8.10

5.0 27.2 3.85 32.6 4.63 38.1 5.40 40.8 5.79 46.2 6.57 51.7 7.34 57.1 8.12

10.0 27.2 3.85 32.6 4.64 38.1 5.42 40.8 5.81 46.2 6.59 51.7 7.36 57.1 8.16

15.0 27.2 3.87 32.6 4.66 38.1 5.44 40.8 5.85 46.2 6.62 51.7 7.42 57.1 8.21

60% 20.0 27.2 3.92 32.6 4.72 38.1 5.53 40.8 5.94 46.2 6.75 51.7 7.57 57.1 8.38

25.0 27.2 4.13 32.6 4.98 38.1 5.85 40.8 6.27 46.2 7.14 51.7 7.99 57.1 8.84

30.0 27.2 5.29 32.6 6.22 38.1 7.18 40.8 7.68 46.2 8.68 51.7 9.71 57.1 10.79

35.0 27.2 6.42 32.6 7.59 38.1 8.77 40.8 9.38 46.2 10.62 51.7 11.88 57.1 13.17
40.0 27.2 7.64 32.6 9.05 38.1 10.47 40.8 11.21 46.2 12.69 51.7 14.21 57.1 15.76

43.0 27.2 8.42 32.6 9.97 38.1 11.56 40.8 12.38 46.2 14.02 51.7 15.73 57.1 17.45

46.0 27.2 9.23 32.6 10.95 38.1 12.73 40.8 13.62 46.2 15.47 51.2 17.02 51.2 15.65

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


24 HP (U-8MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 22.6 3.20 27.2 3.85 31.8 4.48 34.0 4.81 38.6 5.46 43.0 6.09 47.6 6.73

-5.0 22.6 3.20 27.2 3.85 31.8 4.50 34.0 4.81 38.6 5.46 43.0 6.09 47.6 6.73

0.0 22.6 3.20 27.2 3.85 31.8 4.50 34.0 4.81 38.6 5.46 43.0 6.11 47.6 6.75

5.0 22.6 3.20 27.2 3.85 31.8 4.50 34.0 4.81 38.6 5.46 43.0 6.11 47.6 6.75

10.0 22.6 3.22 27.2 3.87 31.8 4.51 34.0 4.83 38.6 5.48 43.0 6.12 47.6 6.77

15.0 22.6 3.22 27.2 3.87 31.8 4.53 34.0 4.85 38.6 5.51 43.0 6.16 47.6 6.81

50% 20.0 22.6 3.26 27.2 3.90 31.8 4.57 34.0 4.90 38.6 5.57 43.0 6.23 47.6 6.90

25.0 22.6 3.37 27.2 4.07 31.8 4.75 34.0 5.11 38.6 5.81 43.0 6.49 47.6 7.20

30.0 22.6 4.42 27.2 5.12 31.8 5.83 34.0 6.20 38.6 6.92 43.0 7.66 47.6 8.42

35.0 22.6 5.35 27.2 6.23 31.8 7.14 34.0 7.59 38.6 8.49 43.0 9.42 47.6 10.34

40.0 22.6 6.35 27.2 7.42 31.8 8.51 34.0 9.07 38.6 10.18 43.0 11.29 47.6 12.41

43.0 22.6 6.97 27.2 8.18 31.8 9.40 34.0 10.01 38.6 11.25 43.0 12.49 47.6 13.75

46.0 22.6 7.64 27.2 8.97 31.8 10.32 34.0 11.01 38.6 12.38 43.0 13.76 47.6 15.17

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 18.2 2.55 21.8 3.07 25.4 3.59 27.2 3.85 30.8 4.37 34.5 4.87 38.1 5.38

-5.0 18.2 2.55 21.8 3.07 25.4 3.59 27.2 3.85 30.8 4.37 34.5 4.87 38.1 5.38

0.0 18.2 2.55 21.8 3.07 25.4 3.59 27.2 3.85 30.8 4.37 34.5 4.88 38.1 5.38

5.0 18.2 2.57 21.8 3.07 25.4 3.59 27.2 3.85 30.8 4.37 34.5 4.88 38.1 5.40

10.0 18.2 2.57 21.8 3.09 25.4 3.61 27.2 3.87 30.8 4.37 34.5 4.88 38.1 5.40
15.0 18.2 2.57 21.8 3.09 25.4 3.61 27.2 3.87 30.8 4.38 34.5 4.90 38.1 5.44

40% 20.0 18.2 2.59 21.8 3.11 25.4 3.64 27.2 3.90 30.8 4.42 34.5 4.96 38.1 5.48

25.0 18.2 2.65 21.8 3.20 25.4 3.74 27.2 4.01 30.8 4.55 34.5 5.09 38.1 5.62

30.0 18.2 3.37 21.8 3.92 25.4 4.46 27.2 4.74 30.8 5.25 34.5 5.79 38.1 6.31

35.0 18.2 4.37 21.8 5.00 25.4 5.64 27.2 5.96 30.8 6.60 34.5 7.23 38.1 7.86
40.0 18.2 5.14 21.8 5.94 25.4 6.72 27.2 7.12 30.8 7.90 34.5 8.68 38.1 9.45

43.0 18.2 5.64 21.8 6.53 25.4 7.40 27.2 7.84 30.8 8.73 34.5 9.60 38.1 10.47
46.0 18.2 6.16 21.8 7.14 25.4 8.14 27.2 8.62 30.8 9.60 34.5 10.58 38.1 11.54

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 13.6 1.92 16.3 2.31 19.0 2.68 20.4 2.89 23.1 3.27 25.8 3.64 28.6 4.03
-5.0 13.6 1.92 16.3 2.31 19.0 2.68 20.4 2.89 23.1 3.27 25.8 3.66 28.6 4.03

0.0 13.6 1.92 16.3 2.31 19.0 2.70 20.4 2.89 23.1 3.27 25.8 3.66 28.6 4.05

5.0 13.6 1.92 16.3 2.31 19.0 2.70 20.4 2.89 23.1 3.27 25.8 3.66 28.6 4.05

10.0 13.6 1.92 16.3 2.31 19.0 2.70 20.4 2.89 23.1 3.27 25.8 3.66 28.6 4.05

15.0 13.6 1.92 16.3 2.31 19.0 2.70 20.4 2.90 23.1 3.29 25.8 3.68 28.6 4.07

30% 20.0 13.6 1.94 16.3 2.33 19.0 2.72 20.4 2.90 23.1 3.31 25.8 3.70 28.6 4.09

25.0 13.6 1.96 16.3 2.37 19.0 2.76 20.4 2.96 23.1 3.35 25.8 3.76 28.6 4.14

30.0 13.6 2.28 16.3 2.68 19.0 3.07 20.4 3.27 23.1 3.66 25.8 4.05 28.6 4.44

35.0 13.6 3.44 16.3 3.89 19.0 4.29 20.4 4.51 23.1 4.92 25.8 5.33 28.6 5.72

40.0 13.6 4.01 16.3 4.57 19.0 5.09 20.4 5.35 23.1 5.86 25.8 6.38 28.6 6.86

43.0 13.6 4.38 16.3 5.00 19.0 5.59 20.4 5.88 23.1 6.48 25.8 7.03 28.6 7.60

46.0 13.6 4.77 16.3 5.46 19.0 6.12 20.4 6.46 23.1 7.10 25.8 7.73 28.6 8.36

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


26 HP (U-12MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 68.0 9.42 78.5 10.91 78.5 10.91 78.5 10.91 88.9 12.36 99.4 13.83 109.9 15.28

-5.0 68.0 9.42 78.5 10.91 78.5 10.91 78.5 10.91 88.9 12.40 99.4 13.85 109.9 15.32

0.0 68.0 9.45 78.5 10.95 78.5 10.95 78.5 10.95 88.9 12.44 99.4 13.89 109.9 15.36

5.0 68.0 9.47 78.5 11.02 78.5 11.02 78.5 11.02 88.9 12.53 99.4 13.99 109.9 15.44

10.0 68.0 9.51 78.5 11.14 78.5 11.14 78.5 11.14 88.9 12.67 99.4 14.16 109.9 15.63

15.0 68.0 9.63 78.5 11.40 78.5 11.40 78.5 11.40 88.9 13.04 99.4 14.50 109.9 15.99
130% 20.0 68.0 9.98 78.5 12.18 78.5 12.18 78.5 12.18 88.9 14.52 99.4 17.10 109.9 19.91

25.0 68.0 11.63 78.5 15.38 78.5 15.38 78.5 15.38 88.9 18.26 99.4 21.36 109.9 24.70

30.0 68.0 14.48 78.5 18.85 78.5 18.85 78.5 18.85 88.9 22.26 99.4 25.93 104.4 26.52

35.0 68.0 17.56 78.5 22.60 78.5 22.60 78.5 22.60 88.5 26.42 92.5 26.52 96.4 26.52
40.0 68.0 20.87 78.1 26.52 78.1 26.52 78.1 26.52 81.6 26.52 85.3 26.52 87.2 25.50

43.0 68.0 22.99 71.8 24.91 71.8 24.91 71.8 24.91 71.8 22.91 71.8 21.05 71.8 19.30

46.0 56.6 18.26 56.6 18.26 56.6 18.26 56.6 18.26 56.6 16.79 56.6 15.44 56.6 14.18

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 61.3 8.49 73.6 10.20 76.7 10.65 76.7 10.65 86.9 12.08 97.1 13.50 107.3 14.93

-5.0 61.3 8.51 73.6 10.22 76.7 10.67 76.7 10.67 86.9 12.10 97.1 13.53 107.3 14.95

0.0 61.3 8.51 73.6 10.24 76.7 10.69 76.7 10.69 86.9 12.14 97.1 13.59 107.3 15.01

5.0 61.3 8.53 73.6 10.26 76.7 10.75 76.7 10.75 86.9 12.22 97.1 13.67 107.3 15.10

10.0 61.3 8.59 73.6 10.32 76.7 10.87 76.7 10.87 86.9 12.36 97.1 13.83 107.3 15.26

15.0 61.3 8.69 73.6 10.49 76.7 11.12 76.7 11.12 86.9 12.69 97.1 14.18 107.3 15.63
120% 20.0 61.3 9.02 73.6 10.95 76.7 11.83 76.7 11.83 86.9 13.95 97.1 16.40 107.3 19.07
25.0 61.3 10.51 73.6 13.12 76.7 14.85 76.7 14.85 86.9 17.58 97.1 20.54 107.3 23.73

30.0 61.3 13.08 73.6 16.26 76.7 18.22 76.7 18.22 86.9 21.46 97.1 24.97 103.7 26.52

35.0 61.3 15.83 73.6 19.65 76.7 21.85 76.7 21.85 86.9 25.68 91.9 26.52 95.7 26.52

40.0 61.3 18.81 73.6 23.30 76.7 25.81 76.7 25.81 81.2 26.52 84.7 26.52 87.2 25.83
43.0 61.3 20.71 71.8 25.15 71.8 25.15 71.8 25.15 71.8 23.15 71.8 21.26 71.8 19.50

46.0 56.6 18.40 56.6 18.40 56.6 18.40 56.6 18.40 56.6 16.93 56.6 15.57 56.6 14.28

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 54.9 7.61 65.8 9.14 74.8 10.40 74.8 10.40 84.8 11.79 94.8 13.18 104.8 14.57
-5.0 54.9 7.61 65.8 9.14 74.8 10.40 74.8 10.40 84.8 11.81 94.8 13.22 104.8 14.61

0.0 54.9 7.63 65.8 9.16 74.8 10.44 74.8 10.44 84.8 11.85 94.8 13.26 104.8 14.65
5.0 54.9 7.65 65.8 9.18 74.8 10.49 74.8 10.49 84.8 11.91 94.8 13.34 104.8 14.73

10.0 54.9 7.69 65.8 9.26 74.8 10.59 74.8 10.59 84.8 12.06 94.8 13.50 104.8 14.89
15.0 54.9 7.77 65.8 9.40 74.8 10.83 74.8 10.83 84.8 12.36 94.8 13.83 104.8 15.26

110% 20.0 54.9 8.08 65.8 9.83 74.8 11.51 74.8 11.51 84.8 13.40 94.8 15.73 104.8 18.26

25.0 54.9 9.45 65.8 11.73 74.8 14.32 74.8 14.32 84.8 16.91 94.8 19.73 104.8 22.77

30.0 54.9 11.73 65.8 14.55 74.8 17.58 74.8 17.58 84.8 20.69 94.8 24.01 102.9 26.52

35.0 54.9 14.20 65.8 17.54 74.8 21.09 74.8 21.09 84.8 24.77 91.3 26.52 95.0 26.52
40.0 54.9 16.85 65.8 20.79 74.8 24.95 74.8 24.95 80.7 26.52 84.2 26.52 87.2 26.17

43.0 54.9 18.54 65.8 22.89 71.8 25.42 71.8 25.42 71.8 23.40 71.8 21.50 71.8 19.73
46.0 54.9 20.34 56.6 18.56 56.6 18.56 56.6 18.56 56.6 17.07 56.6 15.69 56.6 14.40

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 48.7 6.75 58.4 8.10 68.1 9.47 73.0 10.14 82.7 11.51 92.5 12.87 102.2 14.22

-5.0 48.7 6.75 58.4 8.12 68.1 9.47 73.0 10.16 82.7 11.53 92.5 12.89 102.2 14.24

0.0 48.7 6.75 58.4 8.12 68.1 9.49 73.0 10.18 82.7 11.57 92.5 12.93 102.2 14.30

5.0 48.7 6.77 58.4 8.16 68.1 9.53 73.0 10.24 82.7 11.63 92.5 13.02 102.2 14.38
10.0 48.7 6.81 58.4 8.22 68.1 9.63 73.0 10.32 82.7 11.75 92.5 13.16 102.2 14.55

15.0 48.7 6.92 58.4 8.34 68.1 9.81 73.0 10.55 82.7 12.04 92.5 13.50 102.2 14.87

100% 20.0 48.7 7.20 58.4 8.75 68.1 10.36 73.0 11.18 82.7 12.87 92.5 15.08 102.2 17.48
25.0 48.7 8.45 58.4 10.44 68.1 12.63 73.0 13.79 82.7 16.28 92.5 18.95 102.2 21.83

30.0 48.7 10.47 58.4 12.91 68.1 15.57 73.0 16.95 82.7 19.93 92.5 23.09 101.9 26.38

35.0 48.7 12.63 58.4 15.54 68.1 18.65 73.0 20.40 82.3 23.70 90.6 26.52 94.4 26.52

40.0 48.7 14.97 58.4 18.42 68.1 22.13 73.0 24.09 80.2 26.52 83.6 26.52 87.2 26.52

43.0 48.7 16.46 58.4 20.28 68.1 24.36 71.8 25.70 71.8 23.66 71.8 21.75 71.8 19.95

9 46.0 48.7 18.05 56.6 21.18 56.6 19.50 56.6 18.73 56.6 17.24 56.6 15.83 56.6 14.55
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


26 HP (U-12MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 43.8 6.08 52.6 7.28 61.3 8.51 65.7 9.12 74.5 10.34 83.2 11.57 92.0 12.79

-5.0 43.8 6.08 52.6 7.30 61.3 8.53 65.7 9.14 74.5 10.36 83.2 11.59 92.0 12.83

0.0 43.8 6.08 52.6 7.30 61.3 8.55 65.7 9.16 74.5 10.38 83.2 11.63 92.0 12.87

5.0 43.8 6.10 52.6 7.32 61.3 8.57 65.7 9.18 74.5 10.44 83.2 11.69 92.0 12.95

10.0 43.8 6.12 52.6 7.36 61.3 8.63 65.7 9.26 74.5 10.53 83.2 11.81 92.0 13.10

15.0 43.8 6.20 52.6 7.47 61.3 8.77 65.7 9.42 74.5 10.75 83.2 12.08 92.0 13.40
90% 20.0 43.8 6.41 52.6 7.77 61.3 9.18 65.7 9.89 74.5 11.32 83.2 12.75 92.0 14.50

25.0 43.8 7.41 52.6 9.08 61.3 10.87 65.7 11.81 74.5 13.83 83.2 15.99 92.0 18.30

30.0 43.8 9.22 52.6 11.26 61.3 13.44 65.7 14.61 74.5 17.03 83.2 19.62 92.0 22.36

35.0 43.8 11.14 52.6 13.59 61.3 16.22 65.7 17.58 74.5 20.48 83.2 23.54 91.5 26.52
40.0 43.8 13.20 52.6 16.12 61.3 19.22 65.7 20.83 74.5 24.24 81.2 26.52 84.6 26.52

43.0 43.8 14.52 52.6 17.73 61.3 21.15 65.7 22.95 71.8 24.89 71.8 22.89 71.8 21.03

46.0 43.8 15.91 52.6 19.46 56.6 20.30 56.6 19.48 56.6 17.93 56.6 16.48 56.6 15.16

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 38.9 5.39 46.7 6.49 54.5 7.57 58.4 8.10 66.2 9.20 73.9 10.28 81.8 11.36

-5.0 38.9 5.41 46.7 6.49 54.5 7.57 58.4 8.12 66.2 9.20 73.9 10.30 81.8 11.38

0.0 38.9 5.41 46.7 6.49 54.5 7.59 58.4 8.12 66.2 9.22 73.9 10.32 81.8 11.42

5.0 38.9 5.41 46.7 6.51 54.5 7.61 58.4 8.16 66.2 9.26 73.9 10.36 81.8 11.46

10.0 38.9 5.43 46.7 6.53 54.5 7.65 58.4 8.20 66.2 9.32 73.9 10.44 81.8 11.59

15.0 38.9 5.49 46.7 6.61 54.5 7.75 58.4 8.32 66.2 9.47 73.9 10.63 81.8 11.81
80% 20.0 38.9 5.63 46.7 6.83 54.5 8.04 58.4 8.65 66.2 9.89 73.9 11.12 81.8 12.38
25.0 38.9 6.34 46.7 7.79 54.5 9.26 58.4 10.02 66.2 11.63 73.9 13.34 81.8 15.16

30.0 38.9 8.04 46.7 9.71 54.5 11.51 58.4 12.44 66.2 14.40 73.9 16.46 81.8 18.65

35.0 38.9 9.71 46.7 11.75 54.5 13.89 58.4 15.01 66.2 17.36 73.9 19.81 81.8 22.40

40.0 38.9 11.53 46.7 13.93 54.5 16.50 58.4 17.83 66.2 20.58 73.9 23.50 81.5 26.46
43.0 38.9 12.67 46.7 15.34 54.5 18.18 58.4 19.62 66.2 22.68 71.8 24.40 71.8 22.44

46.0 38.9 13.89 46.7 16.83 54.5 19.95 56.6 20.46 56.6 18.85 56.6 17.34 56.6 15.95

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 34.1 4.71 40.9 5.67 47.7 6.61 51.1 7.10 57.9 8.04 64.8 9.00 71.5 9.93
-5.0 34.1 4.73 40.9 5.67 47.7 6.63 51.1 7.10 57.9 8.06 64.8 9.00 71.5 9.96

0.0 34.1 4.73 40.9 5.67 47.7 6.63 51.1 7.10 57.9 8.06 64.8 9.02 71.5 9.98
5.0 34.1 4.73 40.9 5.69 47.7 6.65 51.1 7.12 57.9 8.08 64.8 9.06 71.5 10.02

10.0 34.1 4.75 40.9 5.71 47.7 6.67 51.1 7.16 57.9 8.14 64.8 9.10 71.5 10.08
15.0 34.1 4.77 40.9 5.75 47.7 6.75 51.1 7.24 57.9 8.24 64.8 9.24 71.5 10.24

70% 20.0 34.1 4.88 40.9 5.90 47.7 6.94 51.1 7.47 57.9 8.51 64.8 9.57 71.5 10.63

25.0 34.1 5.37 40.9 6.57 47.7 7.77 51.1 8.36 57.9 9.63 64.8 10.95 71.5 12.34

30.0 34.1 6.94 40.9 8.28 47.7 9.71 51.1 10.47 57.9 12.00 64.8 13.61 71.5 15.30

35.0 34.1 8.38 40.9 10.04 47.7 11.77 51.1 12.67 57.9 14.52 64.8 16.44 71.5 18.46
40.0 34.1 9.93 40.9 11.91 47.7 13.97 51.1 15.06 57.9 17.24 64.8 19.54 71.5 21.93

43.0 34.1 10.93 40.9 13.12 47.7 15.40 51.1 16.59 57.9 19.01 64.8 21.54 71.5 24.19
46.0 34.1 11.95 40.9 14.38 47.7 16.89 51.1 18.20 56.6 20.09 56.6 18.50 56.6 17.03

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 29.2 4.04 35.0 4.86 40.9 5.67 43.8 6.08 49.6 6.90 55.5 7.71 61.3 8.53

-5.0 29.2 4.04 35.0 4.86 40.9 5.67 43.8 6.08 49.6 6.90 55.5 7.71 61.3 8.53

0.0 29.2 4.06 35.0 4.86 40.9 5.67 43.8 6.08 49.6 6.90 55.5 7.73 61.3 8.55

5.0 29.2 4.06 35.0 4.88 40.9 5.69 43.8 6.10 49.6 6.92 55.5 7.73 61.3 8.57
10.0 29.2 4.06 35.0 4.88 40.9 5.71 43.8 6.12 49.6 6.96 55.5 7.77 61.3 8.61

15.0 29.2 4.08 35.0 4.92 40.9 5.75 43.8 6.18 49.6 7.02 55.5 7.85 61.3 8.71

60% 20.0 29.2 4.16 35.0 5.02 40.9 5.88 43.8 6.32 49.6 7.20 55.5 8.08 61.3 8.96
25.0 29.2 4.47 35.0 5.43 40.9 6.41 43.8 6.90 49.6 7.87 55.5 8.85 61.3 9.83

30.0 29.2 5.92 35.0 6.98 40.9 8.08 43.8 8.65 49.6 9.83 55.5 11.06 61.3 12.32

35.0 29.2 7.14 35.0 8.45 40.9 9.81 43.8 10.51 49.6 11.93 55.5 13.40 61.3 14.93

40.0 29.2 8.45 35.0 10.02 40.9 11.65 43.8 12.48 49.6 14.20 55.5 15.95 61.3 17.77

43.0 29.2 9.28 35.0 11.04 40.9 12.83 43.8 13.77 49.6 15.65 55.5 17.61 61.3 19.62

46.0 29.2 10.16 35.0 12.10 40.9 14.08 43.8 15.10 49.6 17.20 55.5 19.36 56.6 18.54

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


26 HP (U-12MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 24.3 3.37 29.2 4.04 34.1 4.73 36.5 5.06 41.4 5.73 46.2 6.43 51.1 7.10

-5.0 24.3 3.37 29.2 4.04 34.1 4.73 36.5 5.06 41.4 5.75 46.2 6.43 51.1 7.10

0.0 24.3 3.37 29.2 4.06 34.1 4.73 36.5 5.08 41.4 5.75 46.2 6.43 51.1 7.12

5.0 24.3 3.39 29.2 4.06 34.1 4.73 36.5 5.08 41.4 5.75 46.2 6.45 51.1 7.12

10.0 24.3 3.39 29.2 4.06 34.1 4.75 36.5 5.10 41.4 5.77 46.2 6.47 51.1 7.16

15.0 24.3 3.41 29.2 4.08 34.1 4.77 36.5 5.12 41.4 5.81 46.2 6.51 51.1 7.20

50% 20.0 24.3 3.43 29.2 4.14 34.1 4.86 36.5 5.20 41.4 5.92 46.2 6.65 51.1 7.36

25.0 24.3 3.63 29.2 4.39 34.1 5.16 36.5 5.55 41.4 6.32 46.2 7.10 51.1 7.87

30.0 24.3 4.98 29.2 5.77 34.1 6.61 36.5 7.04 41.4 7.89 46.2 8.77 51.1 9.69

35.0 24.3 5.98 29.2 6.98 34.1 8.02 36.5 8.53 41.4 9.61 46.2 10.69 51.1 11.81

40.0 24.3 7.06 29.2 8.26 34.1 9.51 36.5 10.14 41.4 11.42 46.2 12.73 51.1 14.08

43.0 24.3 7.73 29.2 9.10 34.1 10.47 36.5 11.18 41.4 12.61 46.2 14.06 51.1 15.54

46.0 24.3 8.45 29.2 9.96 34.1 11.49 36.5 12.26 41.4 13.83 46.2 15.44 51.1 17.10

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 19.5 2.69 23.4 3.24 27.2 3.77 29.2 4.04 33.1 4.59 37.0 5.14 40.9 5.67

-5.0 19.5 2.69 23.4 3.24 27.2 3.77 29.2 4.06 33.1 4.59 37.0 5.14 40.9 5.67

0.0 19.5 2.69 23.4 3.24 27.2 3.77 29.2 4.06 33.1 4.59 37.0 5.14 40.9 5.69

5.0 19.5 2.69 23.4 3.24 27.2 3.79 29.2 4.06 33.1 4.61 37.0 5.14 40.9 5.69

10.0 19.5 2.71 23.4 3.24 27.2 3.79 29.2 4.06 33.1 4.61 37.0 5.16 40.9 5.71
15.0 19.5 2.71 23.4 3.26 27.2 3.81 29.2 4.08 33.1 4.63 37.0 5.18 40.9 5.73

40% 20.0 19.5 2.73 23.4 3.28 27.2 3.86 29.2 4.12 33.1 4.69 37.0 5.24 40.9 5.81

25.0 19.5 2.84 23.4 3.43 27.2 4.02 29.2 4.30 33.1 4.90 37.0 5.49 40.9 6.08

30.0 19.5 4.12 23.4 4.69 27.2 5.28 29.2 5.57 33.1 6.18 37.0 6.79 40.9 7.41

35.0 19.5 4.90 23.4 5.63 27.2 6.39 29.2 6.75 33.1 7.51 37.0 8.26 40.9 9.04
40.0 19.5 5.75 23.4 6.65 27.2 7.55 29.2 8.02 33.1 8.94 37.0 9.85 40.9 10.79

43.0 19.5 6.28 23.4 7.28 27.2 8.30 29.2 8.81 33.1 9.83 37.0 10.85 40.9 11.89
46.0 19.5 6.83 23.4 7.96 27.2 9.08 29.2 9.65 33.1 10.79 37.0 11.93 40.9 13.10

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 14.6 2.02 17.5 2.43 20.4 2.84 21.9 3.04 24.8 3.45 27.7 3.86 30.7 4.26
-5.0 14.6 2.02 17.5 2.43 20.4 2.84 21.9 3.04 24.8 3.45 27.7 3.86 30.7 4.26

0.0 14.6 2.02 17.5 2.43 20.4 2.84 21.9 3.04 24.8 3.45 27.7 3.86 30.7 4.26

5.0 14.6 2.02 17.5 2.43 20.4 2.84 21.9 3.04 24.8 3.45 27.7 3.86 30.7 4.26

10.0 14.6 2.02 17.5 2.43 20.4 2.84 21.9 3.04 24.8 3.45 27.7 3.86 30.7 4.26

15.0 14.6 2.04 17.5 2.45 20.4 2.86 21.9 3.06 24.8 3.47 27.7 3.88 30.7 4.28

30% 20.0 14.6 2.04 17.5 2.45 20.4 2.88 21.9 3.08 24.8 3.49 27.7 3.90 30.7 4.32

25.0 14.6 2.08 17.5 2.51 20.4 2.94 21.9 3.16 24.8 3.59 27.7 4.02 30.7 4.45

30.0 14.6 2.79 17.5 3.24 20.4 3.67 21.9 3.90 24.8 4.32 27.7 4.75 30.7 5.18

35.0 14.6 3.92 17.5 4.41 20.4 4.90 21.9 5.14 24.8 5.65 27.7 6.14 30.7 6.63

40.0 14.6 4.53 17.5 5.14 20.4 5.75 21.9 6.08 24.8 6.67 27.7 7.28 30.7 7.89

43.0 14.6 4.92 17.5 5.61 20.4 6.30 21.9 6.65 24.8 7.34 27.7 8.02 30.7 8.69

46.0 14.6 5.32 17.5 6.10 20.4 6.87 21.9 7.26 24.8 8.02 27.7 8.79 30.7 9.55

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


28 HP (U-14MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 73.2 10.37 84.4 12.02 84.4 12.02 84.4 12.02 95.6 13.64 106.9 15.23 118.1 16.83

-5.0 73.2 10.40 84.4 12.04 84.4 12.04 84.4 12.04 95.6 13.66 106.9 15.26 118.1 16.88

0.0 73.2 10.40 84.4 12.08 84.4 12.08 84.4 12.08 95.6 13.70 106.9 15.32 118.1 16.92

5.0 73.2 10.42 84.4 12.15 84.4 12.15 84.4 12.15 95.6 13.79 106.9 15.41 118.1 17.03

10.0 73.2 10.49 84.4 12.29 84.4 12.29 84.4 12.29 95.6 13.97 106.9 15.59 118.1 17.21

15.0 73.2 10.62 84.4 12.58 84.4 12.58 84.4 12.58 95.6 14.36 106.9 15.98 118.1 17.57
130% 20.0 73.2 10.98 84.4 13.48 84.4 13.48 84.4 13.48 95.6 16.16 106.9 19.06 118.1 22.21

25.0 73.2 12.83 84.4 17.06 84.4 17.06 84.4 17.06 95.6 20.25 106.9 23.74 118.1 27.47

30.0 73.2 15.98 84.4 20.86 84.4 20.86 84.4 20.86 95.6 24.66 106.9 28.78 111.9 29.25

35.0 73.2 19.35 84.4 25.00 84.4 25.00 84.4 25.00 95.1 29.25 99.2 29.25 103.3 29.25
40.0 73.2 23.00 83.9 29.25 83.9 29.25 83.9 29.25 86.5 28.51 86.5 26.17 86.5 23.99

43.0 71.2 23.83 71.2 23.83 71.2 23.83 71.2 23.83 71.2 21.89 71.2 20.09 71.2 18.43

46.0 56.2 17.69 56.2 17.69 56.2 17.69 56.2 17.69 56.2 16.25 56.2 14.94 56.2 13.70

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 65.9 9.36 79.1 11.23 82.4 11.72 82.4 11.72 93.4 13.30 104.4 14.87 115.4 16.45

-5.0 65.9 9.36 79.1 11.25 82.4 11.75 82.4 11.75 93.4 13.34 104.4 14.92 115.4 16.47

0.0 65.9 9.38 79.1 11.27 82.4 11.79 82.4 11.79 93.4 13.39 104.4 14.96 115.4 16.54

5.0 65.9 9.41 79.1 11.32 82.4 11.86 82.4 11.86 93.4 13.48 104.4 15.05 115.4 16.63

10.0 65.9 9.45 79.1 11.39 82.4 11.97 82.4 11.97 93.4 13.64 104.4 15.23 115.4 16.81

15.0 65.9 9.59 79.1 11.57 82.4 12.26 82.4 12.26 93.4 13.97 104.4 15.59 115.4 17.17
120% 20.0 65.9 9.92 79.1 12.06 82.4 13.01 82.4 13.01 93.4 15.50 104.4 18.25 115.4 21.24
25.0 65.9 11.57 79.1 14.49 82.4 16.43 82.4 16.43 93.4 19.49 104.4 22.79 115.4 26.35

30.0 65.9 14.40 79.1 17.96 82.4 20.12 82.4 20.12 93.4 23.76 104.4 27.65 111.2 29.25

35.0 65.9 17.42 79.1 21.67 82.4 24.12 82.4 24.12 93.4 28.42 98.6 29.25 102.7 29.25

40.0 65.9 20.70 79.1 25.70 82.4 28.55 82.4 28.55 86.5 28.82 86.5 26.46 86.5 24.26
43.0 65.9 22.82 71.2 24.03 71.2 24.03 71.2 24.03 71.2 22.10 71.2 20.27 71.2 18.59

46.0 56.2 17.80 56.2 17.80 56.2 17.80 56.2 17.80 56.2 16.38 56.2 15.03 56.2 13.79

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 59.0 8.37 70.8 10.06 80.5 11.45 80.5 11.45 91.2 12.98 101.9 14.54 112.6 16.04
-5.0 59.0 8.39 70.8 10.08 80.5 11.48 80.5 11.48 91.2 13.01 101.9 14.56 112.6 16.09

0.0 59.0 8.39 70.8 10.08 80.5 11.50 80.5 11.50 91.2 13.05 101.9 14.60 112.6 16.13
5.0 59.0 8.42 70.8 10.13 80.5 11.57 80.5 11.57 91.2 13.14 101.9 14.69 112.6 16.22

10.0 59.0 8.46 70.8 10.19 80.5 11.68 80.5 11.68 91.2 13.30 101.9 14.87 112.6 16.40
15.0 59.0 8.57 70.8 10.37 80.5 11.95 80.5 11.95 91.2 13.61 101.9 15.23 112.6 16.79

110% 20.0 59.0 8.91 70.8 10.85 80.5 12.62 80.5 12.62 91.2 14.85 101.9 17.48 112.6 20.32

25.0 59.0 10.37 70.8 12.94 80.5 15.82 80.5 15.82 91.2 18.72 101.9 21.87 112.6 25.25

30.0 59.0 12.89 70.8 16.02 80.5 19.40 80.5 19.40 91.2 22.86 101.9 26.57 110.4 29.25

35.0 59.0 15.59 70.8 19.33 80.5 23.29 80.5 23.29 91.2 27.38 98.0 29.25 102.1 29.25
40.0 59.0 18.52 70.8 22.91 80.5 27.54 80.5 27.54 86.5 29.14 86.5 26.78 86.5 24.55

43.0 59.0 20.39 70.8 25.22 71.2 24.26 71.2 24.26 71.2 22.30 71.2 20.48 71.2 18.77
46.0 56.2 17.93 56.2 17.93 56.2 17.93 56.2 17.93 56.2 16.49 56.2 15.14 56.2 13.91

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 52.4 7.43 62.8 8.93 73.2 10.42 78.5 11.16 88.9 12.67 99.5 14.18 109.9 15.66

-5.0 52.4 7.43 62.8 8.93 73.2 10.44 78.5 11.18 88.9 12.69 99.5 14.20 109.9 15.71

0.0 52.4 7.45 62.8 8.96 73.2 10.46 78.5 11.23 88.9 12.74 99.5 14.24 109.9 15.75

5.0 52.4 7.47 62.8 8.98 73.2 10.51 78.5 11.27 88.9 12.80 99.5 14.33 109.9 15.84
10.0 52.4 7.52 62.8 9.05 73.2 10.60 78.5 11.39 88.9 12.96 99.5 14.51 109.9 16.02

15.0 52.4 7.63 62.8 9.20 73.2 10.82 78.5 11.63 88.9 13.25 99.5 14.87 109.9 16.38

100% 20.0 52.4 7.92 62.8 9.65 73.2 11.39 78.5 12.26 88.9 14.24 99.5 16.72 109.9 19.40
25.0 52.4 9.25 62.8 11.48 73.2 13.93 78.5 15.23 88.9 18.00 99.5 20.97 109.9 24.17

30.0 52.4 11.48 62.8 14.20 73.2 17.15 78.5 18.70 88.9 21.98 99.5 25.54 109.5 29.14

35.0 52.4 13.86 62.8 17.08 73.2 20.52 78.5 22.50 88.5 26.17 97.3 29.25 101.4 29.25

40.0 52.4 16.45 62.8 20.27 73.2 24.39 78.5 26.57 86.1 29.25 86.5 27.09 86.5 24.84

43.0 52.4 18.09 62.8 22.32 71.2 25.52 71.2 24.48 71.2 22.52 71.2 20.68 71.2 18.95

9 46.0 52.4 19.85 56.2 20.45 56.2 18.83 56.2 18.07 56.2 16.63 56.2 15.26 56.2 14.02
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


28 HP (U-14MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 47.1 6.68 56.5 8.03 65.9 9.38 70.7 10.06 80.1 11.41 89.5 12.76 98.9 14.11

-5.0 47.1 6.68 56.5 8.03 65.9 9.38 70.7 10.06 80.1 11.41 89.5 12.78 98.9 14.13

0.0 47.1 6.71 56.5 8.06 65.9 9.41 70.7 10.08 80.1 11.45 89.5 12.80 98.9 14.18

5.0 47.1 6.71 56.5 8.08 65.9 9.45 70.7 10.13 80.1 11.50 89.5 12.87 98.9 14.27

10.0 47.1 6.75 56.5 8.12 65.9 9.52 70.7 10.22 80.1 11.61 89.5 13.01 98.9 14.42

15.0 47.1 6.82 56.5 8.24 65.9 9.68 70.7 10.40 80.1 11.84 89.5 13.28 98.9 14.76
90% 20.0 47.1 7.07 56.5 8.57 65.9 10.10 70.7 10.87 80.1 12.42 89.5 13.97 98.9 16.00

25.0 47.1 8.10 56.5 9.92 65.9 11.90 70.7 12.96 80.1 15.21 89.5 17.60 98.9 20.16

30.0 47.1 10.06 56.5 12.31 65.9 14.74 70.7 16.02 80.1 18.70 89.5 21.56 98.9 24.59

35.0 47.1 12.17 56.5 14.87 65.9 17.78 70.7 19.31 80.1 22.48 89.5 25.88 98.4 29.25
40.0 47.1 14.45 56.5 17.66 65.9 21.08 70.7 22.88 80.1 26.66 86.5 28.60 86.5 26.26

43.0 47.1 15.89 56.5 19.44 65.9 23.22 70.7 25.22 71.2 23.54 71.2 21.62 71.2 19.85

46.0 47.1 17.44 56.2 21.15 56.2 19.49 56.2 18.70 56.2 17.21 56.2 15.82 56.2 14.51

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 41.8 5.94 50.2 7.13 58.6 8.33 62.8 8.93 71.2 10.13 79.5 11.32 87.9 12.53

-5.0 41.8 5.94 50.2 7.13 58.6 8.35 62.8 8.93 71.2 10.15 79.5 11.34 87.9 12.53

0.0 41.8 5.96 50.2 7.16 58.6 8.35 62.8 8.96 71.2 10.17 79.5 11.36 87.9 12.58

5.0 41.8 5.96 50.2 7.18 58.6 8.37 62.8 8.98 71.2 10.19 79.5 11.41 87.9 12.65

10.0 41.8 5.99 50.2 7.20 58.6 8.44 62.8 9.05 71.2 10.28 79.5 11.52 87.9 12.76

15.0 41.8 6.05 50.2 7.29 58.6 8.55 62.8 9.18 71.2 10.44 79.5 11.70 87.9 12.98
80% 20.0 41.8 6.21 50.2 7.52 58.6 8.84 62.8 9.52 71.2 10.85 79.5 12.20 87.9 13.57
25.0 41.8 6.93 50.2 8.48 58.6 10.08 62.8 10.94 71.2 12.69 79.5 14.58 87.9 16.56

30.0 41.8 8.73 50.2 10.58 58.6 12.56 62.8 13.57 71.2 15.73 79.5 17.98 87.9 20.36

35.0 41.8 10.58 50.2 12.80 58.6 15.17 62.8 16.40 71.2 18.97 79.5 21.67 87.9 24.50

40.0 41.8 12.56 50.2 15.21 58.6 18.02 62.8 19.49 71.2 22.52 79.5 25.72 86.5 28.10
43.0 41.8 13.82 50.2 16.76 58.6 19.87 62.8 21.47 71.2 24.84 71.2 22.86 71.2 20.99

46.0 41.8 15.14 50.2 18.41 56.2 20.34 56.2 19.53 56.2 17.98 56.2 16.52 56.2 15.17

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 36.7 5.20 44.0 6.23 51.3 7.29 55.0 7.81 62.3 8.87 69.6 9.90 76.9 10.96
-5.0 36.7 5.20 44.0 6.26 51.3 7.29 55.0 7.81 62.3 8.87 69.6 9.92 76.9 10.96

0.0 36.7 5.20 44.0 6.26 51.3 7.31 55.0 7.83 62.3 8.89 69.6 9.92 76.9 10.98
5.0 36.7 5.22 44.0 6.26 51.3 7.31 55.0 7.85 62.3 8.91 69.6 9.97 76.9 11.03

10.0 36.7 5.22 44.0 6.30 51.3 7.36 55.0 7.90 62.3 8.96 69.6 10.04 76.9 11.12
15.0 36.7 5.27 44.0 6.35 51.3 7.43 55.0 7.97 62.3 9.07 69.6 10.17 76.9 11.27

70% 20.0 36.7 5.38 44.0 6.50 51.3 7.63 55.0 8.21 62.3 9.36 69.6 10.51 76.9 11.66

25.0 36.7 5.87 44.0 7.16 51.3 8.44 55.0 9.09 62.3 10.44 69.6 11.88 76.9 13.39

30.0 36.7 7.52 44.0 8.98 51.3 10.53 55.0 11.34 62.3 13.03 69.6 14.78 76.9 16.61

35.0 36.7 9.09 44.0 10.89 51.3 12.78 55.0 13.75 62.3 15.77 69.6 17.87 76.9 20.05
40.0 36.7 10.78 44.0 12.94 51.3 15.19 55.0 16.36 62.3 18.77 69.6 21.26 76.9 23.85

43.0 36.7 11.88 44.0 14.27 51.3 16.76 55.0 18.05 62.3 20.70 69.6 23.47 71.2 22.57
46.0 36.7 13.01 44.0 15.66 51.3 18.41 55.0 19.85 56.2 18.99 56.2 17.48 56.2 16.07

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 31.4 4.46 37.7 5.36 44.0 6.26 47.1 6.68 53.4 7.58 59.7 8.48 65.9 9.38

-5.0 31.4 4.46 37.7 5.36 44.0 6.26 47.1 6.71 53.4 7.58 59.7 8.48 65.9 9.38

0.0 31.4 4.46 37.7 5.36 44.0 6.26 47.1 6.71 53.4 7.61 59.7 8.51 65.9 9.41

5.0 31.4 4.48 37.7 5.36 44.0 6.28 47.1 6.73 53.4 7.63 59.7 8.53 65.9 9.43
10.0 31.4 4.48 37.7 5.38 44.0 6.28 47.1 6.75 53.4 7.65 59.7 8.57 65.9 9.47

15.0 31.4 4.50 37.7 5.42 44.0 6.35 47.1 6.80 53.4 7.72 59.7 8.66 65.9 9.59

60% 20.0 31.4 4.57 37.7 5.51 44.0 6.48 47.1 6.95 53.4 7.92 59.7 8.87 65.9 9.83
25.0 31.4 4.88 37.7 5.94 44.0 6.98 47.1 7.52 53.4 8.55 59.7 9.61 65.9 10.62

30.0 31.4 6.37 37.7 7.52 44.0 8.71 47.1 9.34 53.4 10.60 59.7 11.90 65.9 13.28

35.0 31.4 7.70 37.7 9.11 44.0 10.60 47.1 11.34 53.4 12.89 59.7 14.47 65.9 16.11

40.0 31.4 9.14 37.7 10.85 44.0 12.60 47.1 13.50 53.4 15.35 59.7 17.26 65.9 19.22

43.0 31.4 10.04 37.7 11.95 44.0 13.91 47.1 14.90 53.4 16.94 59.7 19.06 65.9 21.24

46.0 31.4 11.00 37.7 13.10 44.0 15.26 47.1 16.38 53.4 18.65 56.2 18.81 56.2 17.30

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


28 HP (U-14MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 26.1 3.71 31.4 4.46 36.7 5.20 39.3 5.58 44.5 6.32 49.7 7.07 55.0 7.81

-5.0 26.1 3.71 31.4 4.46 36.7 5.20 39.3 5.58 44.5 6.32 49.7 7.07 55.0 7.83

0.0 26.1 3.71 31.4 4.46 36.7 5.22 39.3 5.58 44.5 6.32 49.7 7.09 55.0 7.83

5.0 26.1 3.71 31.4 4.48 36.7 5.22 39.3 5.58 44.5 6.35 49.7 7.09 55.0 7.85

10.0 26.1 3.74 31.4 4.48 36.7 5.22 39.3 5.60 44.5 6.37 49.7 7.11 55.0 7.88

15.0 26.1 3.74 31.4 4.50 36.7 5.27 39.3 5.65 44.5 6.41 49.7 7.18 55.0 7.94

50% 20.0 26.1 3.78 31.4 4.57 36.7 5.33 39.3 5.74 44.5 6.50 49.7 7.29 55.0 8.08

25.0 26.1 3.98 31.4 4.82 36.7 5.65 39.3 6.05 44.5 6.89 49.7 7.72 55.0 8.55

30.0 26.1 5.33 31.4 6.19 36.7 7.07 39.3 7.52 44.5 8.44 49.7 9.38 55.0 10.35

35.0 26.1 6.41 31.4 7.49 36.7 8.60 39.3 9.16 44.5 10.31 49.7 11.45 55.0 12.65

40.0 26.1 7.58 31.4 8.89 36.7 10.24 39.3 10.91 44.5 12.29 49.7 13.68 55.0 15.10

43.0 26.1 8.33 31.4 9.79 36.7 11.27 39.3 12.04 44.5 13.55 49.7 15.10 55.0 16.70

46.0 26.1 9.11 31.4 10.73 36.7 12.38 39.3 13.21 44.5 14.92 49.7 16.63 55.0 18.38

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 21.0 2.97 25.1 3.56 29.3 4.16 31.4 4.46 35.6 5.06 39.8 5.65 44.0 6.26

-5.0 21.0 2.97 25.1 3.58 29.3 4.16 31.4 4.46 35.6 5.06 39.8 5.65 44.0 6.26

0.0 21.0 2.97 25.1 3.58 29.3 4.16 31.4 4.46 35.6 5.06 39.8 5.67 44.0 6.26

5.0 21.0 2.97 25.1 3.58 29.3 4.16 31.4 4.48 35.6 5.06 39.8 5.67 44.0 6.28

10.0 21.0 2.97 25.1 3.58 29.3 4.19 31.4 4.48 35.6 5.09 39.8 5.67 44.0 6.28
15.0 21.0 2.99 25.1 3.60 29.3 4.19 31.4 4.50 35.6 5.11 39.8 5.72 44.0 6.32

40% 20.0 21.0 3.02 25.1 3.62 29.3 4.23 31.4 4.55 35.6 5.15 39.8 5.78 44.0 6.39

25.0 21.0 3.11 25.1 3.76 29.3 4.39 31.4 4.73 35.6 5.36 39.8 6.01 44.0 6.64

30.0 21.0 4.37 25.1 4.97 29.3 5.60 31.4 5.92 35.6 6.55 39.8 7.18 44.0 7.83

35.0 21.0 5.22 25.1 6.01 29.3 6.80 31.4 7.20 35.6 7.99 39.8 8.80 44.0 9.59
40.0 21.0 6.14 25.1 7.11 29.3 8.08 31.4 8.55 35.6 9.52 39.8 10.51 44.0 11.48

43.0 21.0 6.73 25.1 7.81 29.3 8.89 31.4 9.43 35.6 10.51 39.8 11.59 44.0 12.69
46.0 21.0 7.34 25.1 8.53 29.3 9.74 31.4 10.33 35.6 11.54 39.8 12.76 44.0 13.97

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 15.7 2.23 18.8 2.68 22.0 3.13 23.6 3.35 26.7 3.78 29.8 4.23 33.0 4.68
-5.0 15.7 2.23 18.8 2.68 22.0 3.13 23.6 3.35 26.7 3.80 29.8 4.23 33.0 4.68

0.0 15.7 2.23 18.8 2.68 22.0 3.13 23.6 3.35 26.7 3.80 29.8 4.25 33.0 4.68

5.0 15.7 2.23 18.8 2.68 22.0 3.13 23.6 3.35 26.7 3.80 29.8 4.25 33.0 4.70

10.0 15.7 2.23 18.8 2.68 22.0 3.13 23.6 3.35 26.7 3.80 29.8 4.25 33.0 4.70

15.0 15.7 2.25 18.8 2.68 22.0 3.13 23.6 3.35 26.7 3.83 29.8 4.28 33.0 4.73

30% 20.0 15.7 2.25 18.8 2.70 22.0 3.15 23.6 3.38 26.7 3.85 29.8 4.30 33.0 4.75

25.0 15.7 2.30 18.8 2.77 22.0 3.22 23.6 3.47 26.7 3.94 29.8 4.39 33.0 4.86

30.0 15.7 2.86 18.8 3.33 22.0 3.80 23.6 4.03 26.7 4.48 29.8 4.95 33.0 5.40

35.0 15.7 4.12 18.8 4.66 22.0 5.18 23.6 5.45 26.7 5.96 29.8 6.46 33.0 6.95

40.0 15.7 4.82 18.8 5.47 22.0 6.12 23.6 6.44 26.7 7.07 29.8 7.70 33.0 8.33

43.0 15.7 5.24 18.8 5.96 22.0 6.71 23.6 7.07 26.7 7.79 29.8 8.48 33.0 9.18

46.0 15.7 5.67 18.8 6.50 22.0 7.31 23.6 7.72 26.7 8.53 29.8 9.32 33.0 10.10

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


30 HP (U-14MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 79.2 10.78 91.4 12.47 91.4 12.47 91.4 12.47 103.5 14.17 115.8 15.84 127.9 17.50

-5.0 79.2 10.78 91.4 12.52 91.4 12.52 91.4 12.52 103.5 14.19 115.8 15.86 127.9 17.55

0.0 79.2 10.81 91.4 12.55 91.4 12.55 91.4 12.55 103.5 14.27 115.8 15.94 127.9 17.60

5.0 79.2 10.83 91.4 12.65 91.4 12.65 91.4 12.65 103.5 14.39 115.8 16.06 127.9 17.75

10.0 79.2 10.91 91.4 12.82 91.4 12.82 91.4 12.82 103.5 14.62 115.8 16.28 127.9 17.98

15.0 79.2 11.08 91.4 13.22 91.4 13.22 91.4 13.22 103.5 15.11 115.8 17.13 127.9 20.32
130% 20.0 79.2 11.58 91.4 15.21 91.4 15.21 91.4 15.21 103.5 18.40 115.8 21.89 127.9 25.70

25.0 79.2 14.02 91.4 19.07 91.4 19.07 91.4 19.07 103.5 22.86 115.8 26.99 127.9 31.50

30.0 79.2 17.38 91.4 23.21 91.4 23.21 91.4 23.21 103.5 27.66 115.3 32.35 119.9 32.37

35.0 79.2 20.99 91.4 27.69 91.4 27.69 91.4 27.69 102.6 32.37 106.8 32.37 111.1 32.37
40.0 79.2 24.90 89.4 31.32 89.4 31.32 89.4 31.32 89.4 28.78 89.4 26.44 89.4 24.25

43.0 73.6 23.98 73.6 23.98 73.6 23.98 73.6 23.98 73.6 22.04 73.6 20.22 73.6 18.55

46.0 58.1 17.73 58.1 17.73 58.1 17.73 58.1 17.73 58.1 16.31 58.1 14.96 58.1 13.74

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 71.4 9.71 85.7 11.68 89.3 12.20 89.3 12.20 101.2 13.84 113.1 15.46 125.0 17.11

-5.0 71.4 9.74 85.7 11.70 89.3 12.23 89.3 12.23 101.2 13.87 113.1 15.51 125.0 17.13

0.0 71.4 9.74 85.7 11.73 89.3 12.25 89.3 12.25 101.2 13.92 113.1 15.56 125.0 17.21

5.0 71.4 9.79 85.7 11.75 89.3 12.35 89.3 12.35 101.2 14.04 113.1 15.69 125.0 17.33

10.0 71.4 9.84 85.7 11.85 89.3 12.50 89.3 12.50 101.2 14.24 113.1 15.91 125.0 17.58

15.0 71.4 9.98 85.7 12.10 89.3 12.87 89.3 12.87 101.2 14.74 113.1 16.43 125.0 19.37
120% 20.0 71.4 10.48 85.7 12.80 89.3 14.62 89.3 14.62 101.2 17.65 113.1 20.97 125.0 24.60
25.0 71.4 12.62 85.7 15.99 89.3 18.38 89.3 18.38 101.2 21.99 113.1 25.92 125.0 30.18

30.0 71.4 15.64 85.7 19.70 89.3 22.36 89.3 22.36 101.2 26.64 113.1 31.27 119.1 32.37

35.0 71.4 18.87 85.7 23.70 89.3 26.72 89.3 26.72 101.2 31.72 106.2 32.37 110.4 32.37

40.0 71.4 22.39 85.7 28.04 89.3 31.52 89.3 31.52 89.4 29.11 89.4 26.74 89.4 24.53
43.0 71.4 24.65 73.6 24.20 73.6 24.20 73.6 24.20 73.6 22.24 73.6 20.42 73.6 18.72

46.0 58.1 17.88 58.1 17.88 58.1 17.88 58.1 17.88 58.1 16.43 58.1 15.09 58.1 13.84

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 63.9 8.69 76.7 10.46 87.1 11.90 87.1 11.90 98.8 13.50 110.3 15.09 122.0 16.68
-5.0 63.9 8.72 76.7 10.46 87.1 11.93 87.1 11.93 98.8 13.55 110.3 15.14 122.0 16.73

0.0 63.9 8.72 76.7 10.48 87.1 11.98 87.1 11.98 98.8 13.60 110.3 15.21 122.0 16.81
5.0 63.9 8.76 76.7 10.53 87.1 12.05 87.1 12.05 98.8 13.70 110.3 15.31 122.0 16.93

10.0 63.9 8.81 76.7 10.63 87.1 12.20 87.1 12.20 98.8 13.89 110.3 15.54 122.0 17.16
15.0 63.9 8.96 76.7 10.83 87.1 12.55 87.1 12.55 98.8 14.34 110.3 16.04 122.0 18.45

110% 20.0 63.9 9.41 76.7 11.48 87.1 14.04 87.1 14.04 98.8 16.91 110.3 20.07 122.0 23.51

25.0 63.9 11.30 76.7 14.27 87.1 17.68 87.1 17.68 98.8 21.12 110.3 24.85 122.0 28.91

30.0 63.9 13.99 76.7 17.55 87.1 21.56 87.1 21.56 98.8 25.62 110.3 30.03 118.2 32.37

35.0 63.9 16.88 76.7 21.12 87.1 25.77 87.1 25.77 98.8 30.55 105.5 32.37 109.7 32.37
40.0 63.9 19.99 76.7 24.97 87.1 30.40 87.1 30.40 89.4 29.46 89.4 27.07 89.4 24.83

43.0 63.9 22.01 73.6 24.43 73.6 24.43 73.6 24.43 73.6 22.46 73.6 20.62 73.6 18.90
46.0 58.1 18.00 58.1 18.00 58.1 18.00 58.1 18.00 58.1 16.56 58.1 15.21 58.1 13.94

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 56.7 7.72 68.0 9.26 79.3 10.83 85.0 11.60 96.3 13.17 107.7 14.74 119.0 16.28

-5.0 56.7 7.72 68.0 9.29 79.3 10.86 85.0 11.63 96.3 13.20 107.7 14.77 119.0 16.33

0.0 56.7 7.74 68.0 9.31 79.3 10.88 85.0 11.68 96.3 13.25 107.7 14.84 119.0 16.38

5.0 56.7 7.77 68.0 9.34 79.3 10.93 85.0 11.73 96.3 13.35 107.7 14.94 119.0 16.51
10.0 56.7 7.82 68.0 9.44 79.3 11.06 85.0 11.88 96.3 13.55 107.7 15.16 119.0 16.73

15.0 56.7 7.97 68.0 9.64 79.3 11.35 85.0 12.20 96.3 13.94 107.7 15.66 119.0 17.58

100% 20.0 56.7 8.37 68.0 10.23 79.3 12.23 85.0 13.50 96.3 16.21 107.7 19.20 119.0 22.46
25.0 56.7 10.06 68.0 12.62 79.3 15.49 85.0 17.01 96.3 20.27 107.7 23.83 119.0 27.69

30.0 56.7 12.45 68.0 15.54 79.3 18.95 85.0 20.77 96.3 24.63 107.7 28.83 117.4 32.37

35.0 56.7 14.96 68.0 18.63 79.3 22.58 85.0 24.90 95.9 29.18 104.7 32.37 108.9 32.37

40.0 56.7 17.73 68.0 22.09 79.3 26.79 85.0 29.33 89.4 29.83 89.4 27.39 89.4 25.15

43.0 56.7 19.50 68.0 24.28 73.6 25.72 73.6 24.68 73.6 22.68 73.6 20.84 73.6 19.10

9 46.0 56.7 21.41 58.1 20.54 58.1 18.90 58.1 18.15 58.1 16.68 58.1 15.34 58.1 14.07
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


30 HP (U-14MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 51.0 6.95 61.2 8.34 71.4 9.74 76.5 10.43 86.7 11.85 96.9 13.25 107.1 14.67

-5.0 51.0 6.95 61.2 8.34 71.4 9.76 76.5 10.46 86.7 11.88 96.9 13.27 107.1 14.69

0.0 51.0 6.97 61.2 8.37 71.4 9.79 76.5 10.48 86.7 11.90 96.9 13.32 107.1 14.77

5.0 51.0 6.97 61.2 8.39 71.4 9.84 76.5 10.53 86.7 11.98 96.9 13.42 107.1 14.87

10.0 51.0 7.02 61.2 8.47 71.4 9.91 76.5 10.63 86.7 12.10 96.9 13.60 107.1 15.06

15.0 51.0 7.12 61.2 8.62 71.4 10.13 76.5 10.88 86.7 12.43 96.9 13.99 107.1 15.54
90% 20.0 51.0 7.42 61.2 9.06 71.4 10.73 76.5 11.58 86.7 13.57 96.9 15.94 107.1 18.53

25.0 51.0 8.76 61.2 10.88 71.4 13.22 76.5 14.47 86.7 17.11 96.9 19.97 107.1 23.06

30.0 51.0 10.88 61.2 13.45 71.4 16.26 76.5 17.75 86.7 20.92 96.9 24.30 107.1 27.94

35.0 51.0 13.12 61.2 16.21 71.4 19.55 76.5 21.31 86.7 25.02 96.9 29.03 105.7 32.37
40.0 51.0 15.54 61.2 19.20 71.4 23.11 76.5 25.17 86.7 29.58 89.4 28.98 89.4 26.62

43.0 51.0 17.11 61.2 21.12 71.4 25.45 73.6 25.82 73.6 23.75 73.6 21.84 73.6 20.02

46.0 51.0 18.75 58.1 21.26 58.1 19.60 58.1 18.80 58.1 17.31 58.1 15.89 58.1 14.59

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 45.3 6.18 54.4 7.42 63.5 8.67 68.0 9.29 77.1 10.53 86.1 11.78 95.2 13.02

-5.0 45.3 6.18 54.4 7.42 63.5 8.67 68.0 9.29 77.1 10.53 86.1 11.78 95.2 13.05

0.0 45.3 6.18 54.4 7.42 63.5 8.69 68.0 9.31 77.1 10.56 86.1 11.83 95.2 13.10

5.0 45.3 6.20 54.4 7.45 63.5 8.72 68.0 9.34 77.1 10.61 86.1 11.90 95.2 13.17

10.0 45.3 6.23 54.4 7.49 63.5 8.79 68.0 9.41 77.1 10.71 86.1 12.03 95.2 13.32

15.0 45.3 6.30 54.4 7.59 63.5 8.94 68.0 9.59 77.1 10.93 86.1 12.30 95.2 13.67
80% 20.0 45.3 6.52 54.4 7.92 63.5 9.36 68.0 10.08 77.1 11.55 86.1 13.02 95.2 15.04
25.0 45.3 7.59 54.4 9.29 63.5 11.16 68.0 12.15 77.1 14.27 86.1 16.51 95.2 18.92

30.0 45.3 9.41 54.4 11.53 63.5 13.79 68.0 15.01 77.1 17.53 86.1 20.22 95.2 23.11

35.0 45.3 11.38 54.4 13.92 63.5 16.63 68.0 18.08 77.1 21.07 86.1 24.25 95.2 27.64

40.0 45.3 13.50 54.4 16.51 63.5 19.72 68.0 21.39 77.1 24.92 86.1 28.68 89.4 28.56
43.0 45.3 14.84 54.4 18.15 63.5 21.69 68.0 23.56 73.6 25.15 73.6 23.13 73.6 21.24

46.0 45.3 16.26 54.4 19.92 58.1 20.47 58.1 19.65 58.1 18.10 58.1 16.63 58.1 15.29

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 39.7 5.40 47.6 6.47 55.5 7.57 59.5 8.12 67.4 9.21 75.4 10.28 83.3 11.38
-5.0 39.7 5.40 47.6 6.50 55.5 7.57 59.5 8.12 67.4 9.21 75.4 10.31 83.3 11.40

0.0 39.7 5.40 47.6 6.50 55.5 7.59 59.5 8.14 67.4 9.24 75.4 10.33 83.3 11.43
5.0 39.7 5.43 47.6 6.52 55.5 7.62 59.5 8.17 67.4 9.26 75.4 10.38 83.3 11.48

10.0 39.7 5.43 47.6 6.55 55.5 7.64 59.5 8.22 67.4 9.34 75.4 10.46 83.3 11.58
15.0 39.7 5.48 47.6 6.62 55.5 7.77 59.5 8.34 67.4 9.49 75.4 10.66 83.3 11.83

70% 20.0 39.7 5.63 47.6 6.82 55.5 8.04 59.5 8.67 67.4 9.91 75.4 11.16 83.3 12.40

25.0 39.7 6.37 47.6 7.84 55.5 9.31 59.5 10.08 67.4 11.70 75.4 13.42 83.3 15.29

30.0 39.7 8.07 47.6 9.76 55.5 11.55 59.5 12.50 67.4 14.49 75.4 16.58 83.3 18.77

35.0 39.7 9.74 47.6 11.80 55.5 13.97 59.5 15.11 67.4 17.45 75.4 19.94 83.3 22.58
40.0 39.7 11.55 47.6 13.99 55.5 16.58 59.5 17.93 67.4 20.72 75.4 23.66 83.3 26.77

43.0 39.7 12.70 47.6 15.41 55.5 18.25 59.5 19.75 67.4 22.81 73.6 24.88 73.6 22.88
46.0 39.7 13.92 47.6 16.91 55.5 20.04 58.1 20.79 58.1 19.17 58.1 17.63 58.1 16.21

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 34.0 4.63 40.8 5.55 47.6 6.50 51.0 6.95 57.8 7.89 64.6 8.81 71.4 9.76

-5.0 34.0 4.63 40.8 5.55 47.6 6.50 51.0 6.95 57.8 7.89 64.6 8.81 71.4 9.76

0.0 34.0 4.63 40.8 5.58 47.6 6.50 51.0 6.97 57.8 7.89 64.6 8.84 71.4 9.79

5.0 34.0 4.63 40.8 5.58 47.6 6.52 51.0 6.97 57.8 7.92 64.6 8.86 71.4 9.81
10.0 34.0 4.66 40.8 5.60 47.6 6.55 51.0 7.02 57.8 7.97 64.6 8.91 71.4 9.89

15.0 34.0 4.68 40.8 5.65 47.6 6.60 51.0 7.10 57.8 8.07 64.6 9.04 71.4 10.03

60% 20.0 34.0 4.78 40.8 5.78 47.6 6.80 51.0 7.32 57.8 8.34 64.6 9.36 71.4 10.41
25.0 34.0 5.25 40.8 6.42 47.6 7.59 51.0 8.19 57.8 9.44 64.6 10.71 71.4 12.08

30.0 34.0 6.80 40.8 8.12 47.6 9.51 51.0 10.23 57.8 11.75 64.6 13.32 71.4 14.96

35.0 34.0 8.22 40.8 9.84 47.6 11.53 51.0 12.40 57.8 14.22 64.6 16.11 71.4 18.08

40.0 34.0 9.74 40.8 11.68 47.6 13.70 51.0 14.74 57.8 16.91 64.6 19.15 71.4 21.49

43.0 34.0 10.71 40.8 12.85 47.6 15.09 51.0 16.26 57.8 18.63 64.6 21.12 71.4 23.70

46.0 34.0 11.73 40.8 14.09 47.6 16.56 51.0 17.83 57.8 20.47 58.1 19.05 58.1 17.53

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


30 HP (U-14MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 28.3 3.86 34.0 4.63 39.7 5.40 42.5 5.80 48.2 6.57 53.8 7.35 59.5 8.12

-5.0 28.3 3.86 34.0 4.63 39.7 5.40 42.5 5.80 48.2 6.57 53.8 7.35 59.5 8.12

0.0 28.3 3.86 34.0 4.63 39.7 5.40 42.5 5.80 48.2 6.57 53.8 7.37 59.5 8.14

5.0 28.3 3.86 34.0 4.63 39.7 5.43 42.5 5.80 48.2 6.60 53.8 7.37 59.5 8.17

10.0 28.3 3.88 34.0 4.66 39.7 5.43 42.5 5.83 48.2 6.62 53.8 7.42 59.5 8.19

15.0 28.3 3.88 34.0 4.68 39.7 5.48 42.5 5.88 48.2 6.67 53.8 7.47 59.5 8.29

50% 20.0 28.3 3.96 34.0 4.76 39.7 5.58 42.5 6.00 48.2 6.85 53.8 7.67 59.5 8.52

25.0 28.3 4.23 34.0 5.15 39.7 6.08 42.5 6.52 48.2 7.47 53.8 8.39 59.5 9.31

30.0 28.3 5.65 34.0 6.65 39.7 7.69 42.5 8.22 48.2 9.31 53.8 10.46 59.5 11.63

35.0 28.3 6.82 34.0 8.04 39.7 9.31 42.5 9.98 48.2 11.30 53.8 12.70 59.5 14.12

40.0 28.3 8.07 34.0 9.54 39.7 11.08 42.5 11.85 48.2 13.47 53.8 15.11 59.5 16.81

43.0 28.3 8.86 34.0 10.51 39.7 12.20 42.5 13.07 48.2 14.84 53.8 16.68 59.5 18.55

46.0 28.3 9.69 34.0 11.50 39.7 13.40 42.5 14.34 48.2 16.31 53.8 18.33 58.1 19.50

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 22.7 3.09 27.2 3.71 31.7 4.33 34.0 4.63 38.5 5.25 43.1 5.88 47.6 6.50

-5.0 22.7 3.09 27.2 3.71 31.7 4.33 34.0 4.63 38.5 5.25 43.1 5.88 47.6 6.50

0.0 22.7 3.09 27.2 3.71 31.7 4.33 34.0 4.63 38.5 5.25 43.1 5.88 47.6 6.50

5.0 22.7 3.09 27.2 3.71 31.7 4.33 34.0 4.66 38.5 5.28 43.1 5.90 47.6 6.52

10.0 22.7 3.09 27.2 3.71 31.7 4.33 34.0 4.66 38.5 5.28 43.1 5.90 47.6 6.55
15.0 22.7 3.11 27.2 3.74 31.7 4.36 34.0 4.68 38.5 5.30 43.1 5.95 47.6 6.57

40% 20.0 22.7 3.14 27.2 3.78 31.7 4.43 34.0 4.76 38.5 5.40 43.1 6.05 47.6 6.70

25.0 22.7 3.29 27.2 3.98 31.7 4.68 34.0 5.03 38.5 5.73 43.1 6.42 47.6 7.12

30.0 22.7 4.61 27.2 5.33 31.7 6.05 34.0 6.42 38.5 7.17 43.1 7.94 47.6 8.74

35.0 22.7 5.53 27.2 6.42 31.7 7.32 34.0 7.79 38.5 8.74 43.1 9.69 47.6 10.66
40.0 22.7 6.50 27.2 7.59 31.7 8.69 34.0 9.26 38.5 10.38 43.1 11.55 47.6 12.72

43.0 22.7 7.12 27.2 8.34 31.7 9.56 34.0 10.18 38.5 11.45 43.1 12.72 47.6 14.04
46.0 22.7 7.77 27.2 9.11 31.7 10.48 34.0 11.18 38.5 12.57 43.1 13.99 47.6 15.44

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 17.0 2.32 20.4 2.79 23.8 3.24 25.5 3.49 28.9 3.93 32.3 4.41 35.7 4.88
-5.0 17.0 2.32 20.4 2.79 23.8 3.24 25.5 3.49 28.9 3.93 32.3 4.41 35.7 4.88

0.0 17.0 2.32 20.4 2.79 23.8 3.24 25.5 3.49 28.9 3.93 32.3 4.41 35.7 4.88

5.0 17.0 2.32 20.4 2.79 23.8 3.24 25.5 3.49 28.9 3.96 32.3 4.41 35.7 4.88

10.0 17.0 2.32 20.4 2.79 23.8 3.26 25.5 3.49 28.9 3.96 32.3 4.43 35.7 4.88

15.0 17.0 2.32 20.4 2.79 23.8 3.26 25.5 3.49 28.9 3.96 32.3 4.43 35.7 4.91

30% 20.0 17.0 2.34 20.4 2.81 23.8 3.29 25.5 3.54 28.9 4.01 32.3 4.48 35.7 4.96

25.0 17.0 2.42 20.4 2.91 23.8 3.41 25.5 3.66 28.9 4.16 32.3 4.66 35.7 5.15

30.0 17.0 3.54 20.4 4.08 23.8 4.61 25.5 4.86 28.9 5.33 32.3 5.80 35.7 6.30

35.0 17.0 4.33 20.4 4.93 23.8 5.53 25.5 5.85 28.9 6.45 32.3 7.07 35.7 7.67

40.0 17.0 5.05 20.4 5.80 23.8 6.55 25.5 6.90 28.9 7.67 32.3 8.42 35.7 9.16

43.0 17.0 5.50 20.4 6.32 23.8 7.17 25.5 7.59 28.9 8.42 32.3 9.26 35.7 10.11

46.0 17.0 5.98 20.4 6.90 23.8 7.84 25.5 8.29 28.9 9.24 32.3 10.16 35.7 11.11

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


32 HP (U-16MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 83.9 10.91 96.8 12.64 96.8 12.64 96.8 12.64 109.6 14.34 122.6 16.01 135.5 17.72

-5.0 83.9 10.91 96.8 12.66 96.8 12.66 96.8 12.66 109.6 14.36 122.6 16.07 135.5 17.77

0.0 83.9 10.93 96.8 12.71 96.8 12.71 96.8 12.71 109.6 14.44 122.6 16.15 135.5 17.85

5.0 83.9 10.99 96.8 12.82 96.8 12.82 96.8 12.82 109.6 14.58 122.6 16.31 135.5 18.01

10.0 83.9 11.07 96.8 13.03 96.8 13.03 96.8 13.03 109.6 14.87 122.6 16.60 135.5 18.30

15.0 83.9 11.25 96.8 13.54 96.8 13.54 96.8 13.54 109.6 15.72 122.6 19.07 135.5 22.77
130% 20.0 83.9 11.89 96.8 16.52 96.8 16.52 96.8 16.52 109.6 20.11 122.6 24.10 135.5 28.49

25.0 83.9 14.82 96.8 20.56 96.8 20.56 96.8 20.56 109.6 24.82 122.6 29.50 135.2 34.53

30.0 83.9 18.30 96.8 24.90 96.8 24.90 96.8 24.90 109.6 29.90 121.2 34.58 125.7 34.58

35.0 83.9 22.05 96.8 29.61 96.8 29.61 96.8 29.61 108.3 34.58 112.6 34.58 116.9 34.58
40.0 83.9 26.12 91.2 30.94 91.2 30.94 91.2 30.94 91.2 28.44 91.2 26.12 91.2 23.97

43.0 75.0 23.59 75.0 23.59 75.0 23.59 75.0 23.59 75.0 21.71 75.0 19.92 75.0 18.27

46.0 59.2 17.42 59.2 17.42 59.2 17.42 59.2 17.42 59.2 16.01 59.2 14.71 59.2 13.49

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 75.6 9.84 90.7 11.81 94.5 12.34 94.5 12.34 107.1 13.99 119.7 15.64 132.3 17.29

-5.0 75.6 9.84 90.7 11.84 94.5 12.37 94.5 12.37 107.1 14.04 119.7 15.69 132.3 17.34

0.0 75.6 9.87 90.7 11.86 94.5 12.42 94.5 12.42 107.1 14.12 119.7 15.77 132.3 17.42

5.0 75.6 9.90 90.7 11.92 94.5 12.50 94.5 12.50 107.1 14.26 119.7 15.91 132.3 17.58

10.0 75.6 9.98 90.7 12.02 94.5 12.71 94.5 12.71 107.1 14.52 119.7 16.20 132.3 17.88

15.0 75.6 10.16 90.7 12.32 94.5 13.19 94.5 13.19 107.1 15.14 119.7 18.19 132.3 21.71
120% 20.0 75.6 10.77 90.7 13.43 94.5 15.88 94.5 15.88 107.1 19.29 119.7 23.09 132.3 27.27
25.0 75.6 13.33 90.7 17.05 94.5 19.79 94.5 19.79 107.1 23.86 119.7 28.33 132.3 33.22

30.0 75.6 16.47 90.7 20.91 94.5 23.99 94.5 23.99 107.1 28.78 119.7 34.02 124.9 34.58

35.0 75.6 19.82 90.7 25.08 94.5 28.57 94.5 28.57 107.1 34.15 111.9 34.58 116.2 34.58

40.0 75.6 23.46 90.7 29.61 91.2 31.28 91.2 31.28 91.2 28.78 91.2 26.44 91.2 24.23
43.0 75.0 23.83 75.0 23.83 75.0 23.83 75.0 23.83 75.0 21.92 75.0 20.11 75.0 18.43

46.0 59.2 17.56 59.2 17.56 59.2 17.56 59.2 17.56 59.2 16.12 59.2 14.82 59.2 13.59

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 67.7 8.80 81.2 10.56 92.3 12.05 92.3 12.05 104.6 13.67 116.8 15.27 129.2 16.89
-5.0 67.7 8.80 81.2 10.59 92.3 12.08 92.3 12.08 104.6 13.70 116.8 15.32 129.2 16.94

0.0 67.7 8.83 81.2 10.61 92.3 12.10 92.3 12.10 104.6 13.78 116.8 15.40 129.2 17.02
5.0 67.7 8.86 81.2 10.67 92.3 12.21 92.3 12.21 104.6 13.89 116.8 15.53 129.2 17.16

10.0 67.7 8.94 81.2 10.77 92.3 12.40 92.3 12.40 104.6 14.15 116.8 15.83 129.2 17.45
15.0 67.7 9.10 81.2 11.04 92.3 12.85 92.3 12.85 104.6 14.74 116.8 17.37 129.2 20.69

110% 20.0 67.7 9.68 81.2 11.97 92.3 15.24 92.3 15.24 104.6 18.49 116.8 22.10 129.2 26.04

25.0 67.7 11.92 81.2 15.19 92.3 19.05 92.3 19.05 104.6 22.90 116.8 27.16 129.2 31.81

30.0 67.7 14.71 81.2 18.62 92.3 23.12 92.3 23.12 104.6 27.66 116.8 32.66 124.0 34.58

35.0 67.7 17.72 81.2 22.32 92.3 27.53 92.3 27.53 104.6 32.88 111.1 34.58 115.4 34.58
40.0 67.7 20.93 81.2 26.33 91.2 31.65 91.2 31.65 91.2 29.13 91.2 26.76 91.2 24.55

43.0 67.7 23.01 75.0 24.07 75.0 24.07 75.0 24.07 75.0 22.13 75.1 20.32 75.0 18.65
46.0 59.2 17.69 59.2 17.69 59.2 17.69 59.2 17.69 59.2 16.25 59.2 14.92 59.2 13.70

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 60.0 7.79 72.0 9.39 84.0 10.96 90.0 11.73 102.0 13.33 114.0 14.90 126.0 16.47

-5.0 60.0 7.82 72.0 9.39 84.0 10.99 90.0 11.76 102.0 13.35 114.0 14.95 126.0 16.52

0.0 60.0 7.82 72.0 9.42 84.0 11.01 90.0 11.81 102.0 13.43 114.0 15.03 126.0 16.60

5.0 60.0 7.87 72.0 9.47 84.0 11.09 90.0 11.89 102.0 13.54 114.0 15.16 126.0 16.76
10.0 60.0 7.93 72.0 9.58 84.0 11.23 90.0 12.08 102.0 13.78 114.0 15.43 126.0 17.05

15.0 60.0 8.09 72.0 9.82 84.0 11.60 90.0 12.48 102.0 14.31 114.0 16.57 126.0 19.71

100% 20.0 60.0 8.62 72.0 10.61 84.0 13.19 90.0 14.63 102.0 17.72 114.0 21.15 126.0 24.87
25.0 60.0 10.59 72.0 13.43 84.0 16.60 90.0 18.30 102.0 22.00 114.0 26.04 126.0 30.43

30.0 60.0 13.06 72.0 16.47 84.0 20.22 90.0 22.26 102.0 26.60 114.0 31.33 123.1 34.58

35.0 60.0 15.69 72.0 19.66 84.0 24.02 90.0 26.60 101.6 31.41 110.3 34.58 114.6 34.58

40.0 60.0 18.54 72.0 23.28 84.0 28.46 90.0 31.26 91.2 29.47 91.2 27.11 91.2 24.87

43.0 60.0 20.38 72.0 25.59 75.0 25.35 75.0 24.31 75.0 22.37 75.0 20.54 75.0 18.83

9 46.0 59.2 21.89 59.2 20.16 59.2 18.57 59.2 17.82 59.2 16.39 59.2 15.06 59.2 13.83
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


32 HP (U-16MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 54.0 7.02 64.8 8.43 75.6 9.84 81.0 10.56 91.8 11.97 102.6 13.41 113.4 14.82

-5.0 54.0 7.02 64.8 8.46 75.6 9.87 81.0 10.59 91.8 12.00 102.6 13.43 113.4 14.87

0.0 54.0 7.05 64.8 8.46 75.6 9.90 81.0 10.61 91.8 12.05 102.6 13.51 113.4 14.95

5.0 54.0 7.08 64.8 8.51 75.6 9.95 81.0 10.67 91.8 12.13 102.6 13.62 113.4 15.08

10.0 54.0 7.10 64.8 8.59 75.6 10.05 81.0 10.80 91.8 12.32 102.6 13.83 113.4 15.35

15.0 54.0 7.24 64.8 8.78 75.6 10.32 81.0 11.12 91.8 12.71 102.6 14.34 113.4 16.04
90% 20.0 54.0 7.63 64.8 9.34 75.6 11.17 81.0 12.32 91.8 14.82 102.6 17.53 113.4 20.54

25.0 54.0 9.20 64.8 11.54 75.6 14.15 81.0 15.53 91.8 18.54 102.6 21.79 113.4 25.32

30.0 54.0 11.38 64.8 14.20 75.6 17.32 81.0 18.99 91.8 22.53 102.6 26.39 113.4 30.54

35.0 54.0 13.73 64.8 17.08 75.6 20.77 81.0 22.72 91.8 26.89 102.6 31.39 111.1 34.58
40.0 54.0 16.23 64.8 20.19 75.6 24.50 81.0 26.79 91.2 31.23 91.2 28.70 91.2 26.36

43.0 54.0 17.85 64.8 22.18 75.0 26.55 75.0 25.48 75.0 23.43 75.0 21.55 75.0 19.79

46.0 54.0 19.55 59.2 20.93 59.2 19.29 59.2 18.49 59.2 17.02 59.2 15.64 59.2 14.36

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 48.0 6.25 57.6 7.50 67.2 8.75 72.0 9.39 81.6 10.64 91.2 11.92 100.8 13.17

-5.0 48.0 6.25 57.6 7.50 67.2 8.78 72.0 9.39 81.6 10.67 91.2 11.92 100.8 13.19

0.0 48.0 6.25 57.6 7.53 67.2 8.78 72.0 9.42 81.6 10.69 91.2 11.97 100.8 13.25

5.0 48.0 6.28 57.6 7.55 67.2 8.83 72.0 9.47 81.6 10.75 91.2 12.05 100.8 13.35

10.0 48.0 6.30 57.6 7.61 67.2 8.91 72.0 9.55 81.6 10.88 91.2 12.21 100.8 13.57

15.0 48.0 6.38 57.6 7.74 67.2 9.10 72.0 9.79 81.6 11.17 91.2 12.58 100.8 14.02
80% 20.0 48.0 6.68 57.6 8.14 67.2 9.66 72.0 10.43 81.6 12.21 91.2 14.34 100.8 16.65
25.0 48.0 7.93 57.6 9.84 67.2 11.92 72.0 13.03 81.6 15.43 91.2 18.01 100.8 20.77

30.0 48.0 9.84 57.6 12.16 67.2 14.68 72.0 16.01 81.6 18.86 91.2 21.92 100.8 25.19

35.0 48.0 11.86 57.6 14.63 67.2 17.64 72.0 19.23 81.6 22.58 91.2 26.17 100.8 30.03

40.0 48.0 14.04 57.6 17.32 67.2 20.85 72.0 22.72 81.6 26.65 91.2 30.86 91.2 28.36
43.0 48.0 15.45 57.6 19.05 67.2 22.93 72.0 24.98 75.0 24.87 75.0 22.88 75.0 21.01

46.0 48.0 16.92 57.6 20.91 59.2 20.16 59.2 19.36 59.2 17.82 59.2 16.39 59.2 15.06

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 42.0 5.45 50.4 6.57 58.8 7.66 63.0 8.19 71.4 9.31 79.8 10.40 88.2 11.52
-5.0 42.0 5.45 50.4 6.57 58.8 7.66 63.0 8.22 71.4 9.31 79.8 10.43 88.2 11.54

0.0 42.0 5.48 50.4 6.57 58.8 7.69 63.0 8.22 71.4 9.34 79.8 10.45 88.2 11.57
5.0 42.0 5.48 50.4 6.60 58.8 7.71 63.0 8.27 71.4 9.39 79.8 10.51 88.2 11.65

10.0 42.0 5.51 50.4 6.62 58.8 7.77 63.0 8.33 71.4 9.47 79.8 10.61 88.2 11.78
15.0 42.0 5.56 50.4 6.73 58.8 7.87 63.0 8.49 71.4 9.66 79.8 10.88 88.2 12.08

70% 20.0 42.0 5.75 50.4 7.00 58.8 8.27 63.0 8.94 71.4 10.24 79.8 11.57 88.2 13.27

25.0 42.0 6.78 50.4 8.27 58.8 9.90 63.0 10.77 71.4 12.64 79.8 14.60 88.2 16.73

30.0 42.0 8.41 50.4 10.24 58.8 12.26 63.0 13.33 71.4 15.53 79.8 17.93 88.2 20.46

35.0 42.0 10.13 50.4 12.37 58.8 14.76 63.0 16.04 71.4 18.67 79.8 21.49 88.2 24.47
40.0 42.0 12.00 50.4 14.66 58.8 17.50 63.0 18.99 71.4 22.10 79.8 25.40 88.2 28.91

43.0 42.0 13.19 50.4 16.12 58.8 19.26 63.0 20.88 71.4 24.31 75.0 24.66 75.0 22.69
46.0 42.0 14.47 50.4 17.69 58.8 21.12 59.2 20.54 59.2 18.91 59.2 17.40 59.2 15.99

Indoor air temp.:℃WB

Combination(%) Outdoor air temp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/outdoor capacity ratio ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 36.0 4.68 43.2 5.61 50.4 6.57 54.0 7.02 61.2 7.98 68.4 8.91 75.6 9.87

-5.0 36.0 4.68 43.2 5.61 50.4 6.57 54.0 7.05 61.2 7.98 68.4 8.94 75.6 9.87

0.0 36.0 4.68 43.2 5.64 50.4 6.57 54.0 7.05 61.2 8.01 68.4 8.94 75.6 9.90

5.0 36.0 4.71 43.2 5.64 50.4 6.60 54.0 7.08 61.2 8.03 68.4 8.99 75.6 9.95
10.0 36.0 4.71 43.2 5.67 50.4 6.62 54.0 7.10 61.2 8.09 68.4 9.04 75.6 10.03

15.0 36.0 4.76 43.2 5.72 50.4 6.70 54.0 7.21 61.2 8.19 68.4 9.20 75.6 10.21

60% 20.0 36.0 4.87 43.2 5.91 50.4 6.97 54.0 7.50 61.2 8.57 68.4 9.68 75.6 10.77
25.0 36.0 5.53 43.2 6.84 50.4 8.11 54.0 8.75 61.2 10.16 68.4 11.62 75.6 13.19

30.0 36.0 7.08 43.2 8.51 50.4 10.05 54.0 10.88 61.2 12.58 68.4 14.36 75.6 16.25

35.0 36.0 8.54 43.2 10.29 50.4 12.16 54.0 13.14 61.2 15.16 68.4 17.32 75.6 19.55

40.0 36.0 10.11 43.2 12.21 50.4 14.42 54.0 15.59 61.2 17.98 68.4 20.51 75.6 23.14

43.0 36.0 11.12 43.2 13.43 50.4 15.88 54.0 17.16 61.2 19.79 68.4 22.58 75.0 25.08

46.0 36.0 12.16 43.2 14.71 50.4 17.42 54.0 18.81 59.2 20.46 59.2 18.83 59.2 17.34

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


32 HP (U-16MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 30.0 3.91 36.0 4.68 42.0 5.45 45.0 5.85 51.0 6.65 57.0 7.42 63.0 8.22
-5.0 30.0 3.91 36.0 4.68 42.0 5.48 45.0 5.85 51.0 6.65 57.0 7.42 63.0 8.22

0.0 30.0 3.91 36.0 4.68 42.0 5.48 45.0 5.88 51.0 6.65 57.0 7.45 63.0 8.25
5.0 30.0 3.91 36.0 4.71 42.0 5.48 45.0 5.88 51.0 6.68 57.0 7.47 63.0 8.27

10.0 30.0 3.91 36.0 4.71 42.0 5.51 45.0 5.91 51.0 6.70 57.0 7.50 63.0 8.33
15.0 30.0 3.94 36.0 4.73 42.0 5.56 45.0 5.96 51.0 6.78 57.0 7.61 63.0 8.43

50% 20.0 30.0 4.02 36.0 4.84 42.0 5.69 45.0 6.14 51.0 7.00 57.0 7.87 63.0 8.75

25.0 30.0 4.39 36.0 5.40 42.0 6.41 45.0 6.92 51.0 7.98 57.0 9.04 63.0 10.13
30.0 30.0 5.85 36.0 6.94 42.0 8.09 45.0 8.70 51.0 9.92 57.0 11.23 63.0 12.61

35.0 30.0 7.05 36.0 8.38 42.0 9.79 45.0 10.53 51.0 12.02 57.0 13.59 63.0 15.22

40.0 30.0 8.33 36.0 9.95 42.0 11.62 45.0 12.50 51.0 14.28 57.0 16.15 63.0 18.06

43.0 30.0 9.15 36.0 10.93 42.0 12.79 45.0 13.75 51.0 15.72 57.0 17.77 63.0 19.92
46.0 30.0 10.00 36.0 11.97 42.0 14.02 45.0 15.08 51.0 17.26 57.0 19.52 59.2 19.36

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 24.0 3.11 28.8 3.75 33.6 4.36 36.0 4.68 40.8 5.32 45.6 5.93 50.4 6.57
-5.0 24.0 3.11 28.8 3.75 33.6 4.36 36.0 4.68 40.8 5.32 45.6 5.93 50.4 6.57

0.0 24.0 3.11 28.8 3.75 33.6 4.39 36.0 4.68 40.8 5.32 45.6 5.96 50.4 6.57

5.0 24.0 3.14 28.8 3.75 33.6 4.39 36.0 4.71 40.8 5.32 45.6 5.96 50.4 6.60

10.0 24.0 3.14 28.8 3.75 33.6 4.39 36.0 4.71 40.8 5.35 45.6 5.99 50.4 6.62

15.0 24.0 3.14 28.8 3.78 33.6 4.42 36.0 4.73 40.8 5.37 45.6 6.04 50.4 6.68

40% 20.0 24.0 3.19 28.8 3.83 33.6 4.50 36.0 4.84 40.8 5.51 45.6 6.17 50.4 6.86

25.0 24.0 3.38 28.8 4.12 33.6 4.87 36.0 5.24 40.8 6.01 45.6 6.78 50.4 7.55
30.0 24.0 4.73 28.8 5.51 33.6 6.33 36.0 6.76 40.8 7.61 45.6 8.51 50.4 9.42

35.0 24.0 5.67 28.8 6.65 33.6 7.66 36.0 8.17 40.8 9.23 45.6 10.32 50.4 11.44

40.0 24.0 6.68 28.8 7.87 33.6 9.07 36.0 9.71 40.8 10.99 45.6 12.29 50.4 13.62

43.0 24.0 7.32 28.8 8.65 33.6 9.98 36.0 10.67 40.8 12.08 45.6 13.54 50.4 15.00

46.0 24.0 7.98 28.8 9.44 33.6 10.93 36.0 11.70 40.8 13.25 45.6 14.84 50.4 16.49

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 18.0 2.34 21.6 2.82 25.2 3.27 27.0 3.51 30.6 3.99 34.2 4.44 37.8 4.92

-5.0 18.0 2.34 21.6 2.82 25.2 3.27 27.0 3.51 30.6 3.99 34.2 4.44 37.8 4.92

0.0 18.0 2.34 21.6 2.82 25.2 3.27 27.0 3.51 30.6 3.99 34.2 4.47 37.8 4.92

5.0 18.0 2.34 21.6 2.82 25.2 3.30 27.0 3.51 30.6 3.99 34.2 4.47 37.8 4.95
10.0 18.0 2.34 21.6 2.82 25.2 3.30 27.0 3.54 30.6 3.99 34.2 4.47 37.8 4.95

15.0 18.0 2.37 21.6 2.82 25.2 3.30 27.0 3.54 30.6 4.02 34.2 4.50 37.8 4.97

30% 20.0 18.0 2.37 21.6 2.85 25.2 3.33 27.0 3.59 30.6 4.07 34.2 4.55 37.8 5.05

25.0 18.0 2.47 21.6 2.98 25.2 3.51 27.0 3.75 30.6 4.28 34.2 4.81 37.8 5.35

30.0 18.0 3.72 21.6 4.26 25.2 4.79 27.0 5.05 30.6 5.61 34.2 6.17 37.8 6.73
35.0 18.0 4.42 21.6 5.08 25.2 5.75 27.0 6.09 30.6 6.78 34.2 7.47 37.8 8.19

40.0 18.0 5.16 21.6 5.96 25.2 6.78 27.0 7.21 30.6 8.03 34.2 8.88 37.8 9.74

43.0 18.0 5.64 21.6 6.52 25.2 7.45 27.0 7.90 30.6 8.83 34.2 9.79 37.8 10.75

46.0 18.0 6.12 21.6 7.13 25.2 8.14 27.0 8.65 30.6 9.68 34.2 10.72 37.8 11.78

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


34 HP (U-8MF2E8 & U-12MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 89.5 13.00 103.2 15.03 103.2 15.03 103.2 15.03 116.9 17.04 130.8 19.04 144.5 21.05

-5.0 89.5 13.00 103.2 15.06 103.2 15.06 103.2 15.06 116.9 17.06 130.8 19.10 144.5 21.10

0.0 89.5 13.00 103.2 15.09 103.2 15.09 103.2 15.09 116.9 17.12 130.8 19.12 144.5 21.13

5.0 89.5 13.03 103.2 15.14 103.2 15.14 103.2 15.14 116.9 17.19 130.8 19.20 144.5 21.23

10.0 89.5 13.08 103.2 15.24 103.2 15.24 103.2 15.24 116.9 17.32 130.8 19.35 144.5 21.38

15.0 89.5 13.18 103.2 15.50 103.2 15.50 103.2 15.50 116.9 17.63 130.8 19.66 144.5 21.69

130% 20.0 89.5 13.49 103.2 16.11 103.2 16.11 103.2 16.11 116.9 18.38 130.8 20.41 144.5 23.44

25.0 89.5 14.80 103.2 19.04 103.2 19.04 103.2 19.04 116.9 22.33 130.8 25.85 144.5 29.58

30.0 89.5 18.63 103.2 23.57 103.2 23.57 103.2 23.57 116.9 27.52 130.8 31.71 139.5 33.41

35.0 89.5 22.72 103.2 28.45 103.2 28.45 103.2 28.45 116.9 33.13 122.6 33.41 128.1 33.41

40.0 89.5 27.11 102.4 33.41 102.4 33.41 102.4 33.41 107.3 33.41 112.3 33.41 117.5 33.41

43.0 89.5 29.91 97.1 33.41 97.1 33.41 97.1 33.41 100.9 32.84 100.9 30.15 100.9 27.65

46.0 79.6 26.29 79.6 26.29 79.6 26.29 79.6 26.29 79.6 24.16 79.6 22.18 79.6 20.35

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 80.6 11.72 96.8 14.06 100.8 14.67 100.8 14.67 114.2 16.65 127.7 18.61 141.1 20.56

-5.0 80.6 11.72 96.8 14.08 100.8 14.70 100.8 14.70 114.2 16.68 127.7 18.63 141.1 20.61

0.0 80.6 11.74 96.8 14.11 100.8 14.73 100.8 14.73 114.2 16.71 127.7 18.68 141.1 20.64

5.0 80.6 11.77 96.8 14.14 100.8 14.78 100.8 14.78 114.2 16.78 127.7 18.76 141.1 20.74

10.0 80.6 11.80 96.8 14.19 100.8 14.88 100.8 14.88 114.2 16.91 127.7 18.92 141.1 20.87

15.0 80.6 11.90 96.8 14.34 100.8 15.11 100.8 15.11 114.2 17.19 127.7 19.20 141.1 21.18

120% 20.0 80.6 12.18 96.8 14.75 100.8 15.70 100.8 15.70 114.2 17.91 127.7 19.94 141.1 22.44

25.0 80.6 13.42 96.8 16.53 100.8 18.38 100.8 18.38 114.2 21.51 127.7 24.85 141.1 28.40

30.0 80.6 16.83 96.8 20.69 100.8 22.77 100.8 22.77 114.2 26.55 127.7 30.56 138.6 33.41

35.0 80.6 20.51 96.8 25.13 100.8 27.50 100.8 27.50 114.2 32.00 121.8 33.41 127.3 33.41

40.0 80.6 24.44 96.8 29.94 100.8 32.66 100.8 32.66 106.8 33.41 111.7 33.41 116.8 33.41

43.0 80.6 26.96 96.6 33.41 96.6 33.41 96.6 33.41 100.9 33.18 100.9 30.45 100.9 27.94

46.0 79.6 26.50 79.6 26.50 79.6 26.50 79.6 26.50 79.6 24.34 79.6 22.36 79.6 20.51

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 72.2 10.49 86.6 12.59 98.4 14.34 98.4 14.34 111.6 16.24 124.6 18.17 137.8 20.07

-5.0 72.2 10.49 86.6 12.59 98.4 14.34 98.4 14.34 111.6 16.27 124.6 18.20 137.8 20.12

0.0 72.2 10.51 86.6 12.62 98.4 14.37 98.4 14.37 111.6 16.32 124.6 18.25 137.8 20.15

5.0 72.2 10.54 86.6 12.64 98.4 14.42 98.4 14.42 111.6 16.37 124.6 18.32 137.8 20.23

10.0 72.2 10.56 86.6 12.72 98.4 14.52 98.4 14.52 111.6 16.50 124.6 18.45 137.8 20.38

15.0 72.2 10.67 86.6 12.85 98.4 14.73 98.4 14.73 111.6 16.76 124.6 18.76 137.8 20.69

110% 20.0 72.2 10.92 86.6 13.24 98.4 15.27 98.4 15.27 111.6 17.42 124.6 19.48 137.8 21.38

25.0 72.2 12.08 86.6 14.80 98.4 17.73 98.4 17.73 111.6 20.71 124.6 23.88 137.8 27.27

30.0 72.2 15.14 86.6 18.50 98.4 22.00 98.4 22.00 111.6 25.60 124.6 29.40 137.5 33.31

35.0 72.2 18.40 86.6 22.46 98.4 26.57 98.4 26.57 111.6 30.87 121.1 33.41 126.4 33.41

40.0 72.2 21.90 86.6 26.75 98.4 31.59 98.4 31.59 106.1 33.41 111.1 33.41 116.1 33.41

43.0 72.2 24.16 86.6 29.50 96.1 33.41 96.1 33.41 100.7 33.41 100.9 30.76 100.9 28.22

46.0 72.2 26.55 79.6 26.70 79.6 26.70 79.6 26.70 79.6 24.54 79.6 22.54 79.6 20.69

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 64.0 9.30 76.8 11.18 89.6 13.06 96.0 13.98 108.8 15.86 121.6 17.73 134.4 19.58

-5.0 64.0 9.30 76.8 11.18 89.6 13.06 96.0 14.01 108.8 15.88 121.6 17.76 134.4 19.61

0.0 64.0 9.33 76.8 11.21 89.6 13.08 96.0 14.03 108.8 15.91 121.6 17.81 134.4 19.66

5.0 64.0 9.33 76.8 11.23 89.6 13.13 96.0 14.06 108.8 15.96 121.6 17.86 134.4 19.74

10.0 64.0 9.38 76.8 11.28 89.6 13.21 96.0 14.16 108.8 16.09 121.6 18.02 134.4 19.89

15.0 64.0 9.46 76.8 11.41 89.6 13.36 96.0 14.34 108.8 16.32 121.6 18.30 134.4 20.17

100% 20.0 64.0 9.71 76.8 11.77 89.6 13.83 96.0 14.85 108.8 16.94 121.6 19.02 134.4 20.87

25.0 64.0 10.77 76.8 13.18 89.6 15.73 96.0 17.09 108.8 19.92 121.6 22.92 134.4 26.14

30.0 64.0 13.52 76.8 16.45 89.6 19.58 96.0 21.23 108.8 24.67 121.6 28.30 134.4 32.10

35.0 64.0 16.37 76.8 19.94 89.6 23.67 96.0 25.70 108.4 29.61 120.3 33.41 125.6 33.41

40.0 64.0 19.51 76.8 23.72 89.6 28.19 96.0 30.53 105.5 33.41 110.3 33.41 115.4 33.41

43.0 64.0 21.49 76.8 26.16 89.6 31.10 95.5 33.41 100.1 33.41 100.9 31.12 100.9 28.53

9 46.0 64.0 23.59 76.8 28.76 79.6 28.06 79.6 26.93 79.6 24.75 79.6 22.74 79.6 20.87
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


34 HP (U-8MF2E8 & U-12MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 57.6 8.38 69.1 10.05 80.6 11.74 86.4 12.57 97.9 14.26 109.4 15.96 121.0 17.63

-5.0 57.6 8.38 69.1 10.05 80.6 11.74 86.4 12.59 97.9 14.29 109.4 15.96 121.0 17.66

0.0 57.6 8.38 69.1 10.07 80.6 11.77 86.4 12.62 97.9 14.31 109.4 16.01 121.0 17.71

5.0 57.6 8.40 69.1 10.10 80.6 11.80 86.4 12.64 97.9 14.34 109.4 16.06 121.0 17.76

10.0 57.6 8.43 69.1 10.13 80.6 11.85 86.4 12.72 97.9 14.44 109.4 16.17 121.0 17.89

15.0 57.6 8.48 69.1 10.23 80.6 11.98 86.4 12.85 97.9 14.62 109.4 16.37 121.0 18.14

90% 20.0 57.6 8.69 69.1 10.49 80.6 12.31 86.4 13.24 97.9 15.06 109.4 16.91 121.0 18.76

25.0 57.6 9.46 69.1 11.51 80.6 13.54 86.4 14.67 97.9 16.96 109.4 19.38 121.0 21.92

30.0 57.6 11.92 69.1 14.37 80.6 16.96 86.4 18.32 97.9 21.13 109.4 24.08 121.0 27.14

35.0 57.6 14.47 69.1 17.45 80.6 20.59 86.4 22.23 97.9 25.57 109.4 29.09 121.0 32.77

40.0 57.6 17.22 69.1 20.79 80.6 24.52 86.4 26.45 97.9 30.45 107.3 33.41 112.1 33.41

43.0 57.6 18.97 69.1 22.92 80.6 27.06 86.4 29.20 97.5 33.41 100.9 32.69 100.9 29.99

46.0 57.6 20.82 69.1 25.19 79.6 29.14 79.6 27.96 79.6 25.73 79.6 23.64 79.6 21.72

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 51.2 7.45 61.4 8.94 71.7 10.43 76.8 11.18 87.1 12.67 97.2 14.16 107.5 15.68

-5.0 51.2 7.45 61.4 8.94 71.7 10.43 76.8 11.18 87.1 12.70 97.2 14.19 107.5 15.68

0.0 51.2 7.45 61.4 8.94 71.7 10.46 76.8 11.21 87.1 12.70 97.2 14.21 107.5 15.70

5.0 51.2 7.45 61.4 8.97 71.7 10.49 76.8 11.23 87.1 12.75 97.2 14.24 107.5 15.75

10.0 51.2 7.48 61.4 9.00 71.7 10.51 76.8 11.28 87.1 12.80 97.2 14.31 107.5 15.86

15.0 51.2 7.53 61.4 9.07 71.7 10.61 76.8 11.39 87.1 12.93 97.2 14.47 107.5 16.04

80% 20.0 51.2 7.66 61.4 9.25 71.7 10.85 76.8 11.64 87.1 13.26 97.2 14.85 107.5 16.47

25.0 51.2 8.22 61.4 9.97 71.7 11.72 76.8 12.59 87.1 14.34 97.2 16.17 107.5 18.14

30.0 51.2 10.41 61.4 12.44 71.7 14.55 76.8 15.63 87.1 17.89 97.2 20.23 107.5 22.67

35.0 51.2 12.67 61.4 15.14 71.7 17.71 76.8 19.02 87.1 21.74 97.2 24.57 107.5 27.47

40.0 51.2 15.06 61.4 18.02 71.7 21.10 76.8 22.69 87.1 25.93 97.2 29.30 107.5 32.79

43.0 51.2 16.60 61.4 19.89 71.7 23.28 76.8 25.06 87.1 28.66 97.2 32.38 100.9 31.92

46.0 51.2 18.20 61.4 21.85 71.7 25.62 76.8 27.58 79.6 26.99 79.6 24.83 79.6 22.80

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 44.8 6.50 53.8 7.81 62.7 9.12 67.2 9.79 76.1 11.08 85.2 12.39 94.1 13.70

-5.0 44.8 6.50 53.8 7.81 62.7 9.12 67.2 9.79 76.1 11.10 85.2 12.41 94.1 13.72

0.0 44.8 6.53 53.8 7.84 62.7 9.15 67.2 9.79 76.1 11.10 85.2 12.41 94.1 13.75

5.0 44.8 6.53 53.8 7.84 62.7 9.15 67.2 9.82 76.1 11.13 85.2 12.44 94.1 13.78

10.0 44.8 6.55 53.8 7.86 62.7 9.17 67.2 9.84 76.1 11.18 85.2 12.49 94.1 13.83

15.0 44.8 6.58 53.8 7.92 62.7 9.25 67.2 9.92 76.1 11.26 85.2 12.62 94.1 13.96

70% 20.0 44.8 6.66 53.8 8.04 62.7 9.41 67.2 10.10 76.1 11.49 85.2 12.88 94.1 14.26

25.0 44.8 7.04 53.8 8.53 62.7 10.00 67.2 10.74 76.1 12.21 85.2 13.70 94.1 15.14

30.0 44.8 9.02 53.8 10.64 62.7 12.31 67.2 13.18 76.1 14.93 85.2 16.76 94.1 18.63

35.0 44.8 10.95 53.8 12.95 62.7 15.03 67.2 16.09 76.1 18.25 85.2 20.46 94.1 22.72

40.0 44.8 13.03 53.8 15.45 62.7 17.94 67.2 19.20 76.1 21.77 85.2 24.42 94.1 27.14

43.0 44.8 14.34 53.8 17.04 62.7 19.79 67.2 21.20 76.1 24.08 85.2 27.01 94.1 30.04

46.0 44.8 15.73 53.8 18.71 62.7 21.77 67.2 23.34 76.1 26.52 79.6 26.39 79.6 24.26

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 38.4 5.58 46.1 6.71 53.8 7.81 57.6 8.38 65.3 9.51 73.0 10.61 80.6 11.74

-5.0 38.4 5.58 46.1 6.71 53.8 7.81 57.6 8.38 65.3 9.51 73.0 10.64 80.6 11.74

0.0 38.4 5.58 46.1 6.71 53.8 7.84 57.6 8.40 65.3 9.51 73.0 10.64 80.6 11.77

5.0 38.4 5.60 46.1 6.71 53.8 7.84 57.6 8.40 65.3 9.53 73.0 10.67 80.6 11.80

10.0 38.4 5.60 46.1 6.73 53.8 7.86 57.6 8.43 65.3 9.56 73.0 10.69 80.6 11.82

15.0 38.4 5.63 46.1 6.76 53.8 7.89 57.6 8.48 65.3 9.61 73.0 10.77 80.6 11.90

60% 20.0 38.4 5.68 46.1 6.84 53.8 7.99 57.6 8.58 65.3 9.77 73.0 10.92 80.6 12.10

25.0 38.4 5.94 46.1 7.14 53.8 8.38 57.6 9.00 65.3 10.23 73.0 11.46 80.6 12.67

30.0 38.4 7.74 46.1 9.00 53.8 10.28 57.6 10.95 65.3 12.28 73.0 13.65 80.6 15.03

35.0 38.4 9.35 46.1 10.95 53.8 12.57 57.6 13.39 65.3 15.03 73.0 16.73 80.6 18.43

40.0 38.4 11.10 46.1 13.03 53.8 14.98 57.6 15.99 65.3 17.99 73.0 20.02 80.6 22.08

43.0 38.4 12.21 46.1 14.37 53.8 16.55 57.6 17.66 65.3 19.89 73.0 22.15 80.6 24.44

46.0 38.4 13.36 46.1 15.75 53.8 18.20 57.6 19.40 65.3 21.90 73.0 24.42 79.6 26.34

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


34 HP (U-8MF2E8 & U-12MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 32.0 4.65 38.4 5.58 44.8 6.53 48.0 6.99 54.4 7.92 60.8 8.84 67.2 9.79

-5.0 32.0 4.65 38.4 5.58 44.8 6.53 48.0 6.99 54.4 7.92 60.8 8.87 67.2 9.79

0.0 32.0 4.65 38.4 5.58 44.8 6.53 48.0 6.99 54.4 7.92 60.8 8.87 67.2 9.79

5.0 32.0 4.65 38.4 5.60 44.8 6.53 48.0 6.99 54.4 7.94 60.8 8.87 67.2 9.82

10.0 32.0 4.68 38.4 5.60 44.8 6.55 48.0 7.02 54.4 7.94 60.8 8.89 67.2 9.84

15.0 32.0 4.68 38.4 5.63 44.8 6.58 48.0 7.04 54.4 7.99 60.8 8.94 67.2 9.89

50% 20.0 32.0 4.70 38.4 5.68 44.8 6.63 48.0 7.12 54.4 8.07 60.8 9.05 67.2 10.00

25.0 32.0 4.86 38.4 5.86 44.8 6.86 48.0 7.35 54.4 8.35 60.8 9.35 67.2 10.33

30.0 32.0 6.45 38.4 7.48 44.8 8.43 48.0 8.92 54.4 9.89 60.8 10.87 67.2 11.87

35.0 32.0 7.86 38.4 9.07 44.8 10.31 48.0 10.92 54.4 12.13 60.8 13.36 67.2 14.60

40.0 32.0 9.30 38.4 10.79 44.8 12.28 48.0 13.03 54.4 14.52 60.8 16.04 67.2 17.53

43.0 32.0 10.20 38.4 11.87 44.8 13.54 48.0 14.39 54.4 16.06 60.8 17.73 67.2 19.43

46.0 32.0 11.15 38.4 13.00 44.8 14.88 48.0 15.81 54.4 17.68 60.8 19.56 67.2 21.43

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 25.6 3.73 30.7 4.47 35.8 5.22 38.4 5.58 43.5 6.32 48.7 7.07 53.8 7.81

-5.0 25.6 3.73 30.7 4.47 35.8 5.22 38.4 5.58 43.5 6.35 48.7 7.09 53.8 7.84

0.0 25.6 3.73 30.7 4.47 35.8 5.22 38.4 5.60 43.5 6.35 48.7 7.09 53.8 7.84

5.0 25.6 3.73 30.7 4.47 35.8 5.22 38.4 5.60 43.5 6.35 48.7 7.09 53.8 7.84

10.0 25.6 3.73 30.7 4.47 35.8 5.24 38.4 5.60 43.5 6.35 48.7 7.09 53.8 7.86

15.0 25.6 3.75 30.7 4.50 35.8 5.24 38.4 5.63 43.5 6.37 48.7 7.12 53.8 7.89

40% 20.0 25.6 3.75 30.7 4.52 35.8 5.27 38.4 5.65 43.5 6.43 48.7 7.17 53.8 7.94

25.0 25.6 3.83 30.7 4.63 35.8 5.40 38.4 5.78 43.5 6.55 48.7 7.35 53.8 8.12

30.0 25.6 4.68 30.7 5.47 35.8 6.25 38.4 6.63 43.5 7.40 48.7 8.17 53.8 8.92

35.0 25.6 6.48 30.7 7.35 35.8 8.25 38.4 8.66 43.5 9.53 48.7 10.38 53.8 11.23

40.0 25.6 7.61 30.7 8.71 35.8 9.79 38.4 10.33 43.5 11.41 48.7 12.46 53.8 13.49

43.0 25.6 8.30 30.7 9.56 35.8 10.77 38.4 11.39 43.5 12.59 48.7 13.78 53.8 14.93

46.0 25.6 9.05 30.7 10.43 35.8 11.80 38.4 12.49 43.5 13.83 48.7 15.16 53.8 16.47

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 19.2 2.80 23.0 3.34 26.9 3.91 28.8 4.19 32.6 4.75 36.5 5.32 40.3 5.86

-5.0 19.2 2.80 23.0 3.34 26.9 3.91 28.8 4.19 32.6 4.75 36.5 5.32 40.3 5.86

0.0 19.2 2.80 23.0 3.34 26.9 3.91 28.8 4.19 32.6 4.75 36.5 5.32 40.3 5.89

5.0 19.2 2.80 23.0 3.37 26.9 3.91 28.8 4.19 32.6 4.75 36.5 5.32 40.3 5.89

10.0 19.2 2.80 23.0 3.37 26.9 3.93 28.8 4.19 32.6 4.75 36.5 5.32 40.3 5.89

15.0 19.2 2.80 23.0 3.37 26.9 3.93 28.8 4.21 32.6 4.78 36.5 5.35 40.3 5.89
30% 20.0 19.2 2.83 23.0 3.37 26.9 3.93 28.8 4.21 32.6 4.81 36.5 5.37 40.3 5.94

25.0 19.2 2.85 23.0 3.42 26.9 4.01 28.8 4.29 32.6 4.86 36.5 5.42 40.3 6.01

30.0 19.2 3.21 23.0 3.80 26.9 4.37 28.8 4.65 32.6 5.22 36.5 5.78 40.3 6.35

35.0 19.2 5.19 23.0 5.78 26.9 6.37 28.8 6.66 32.6 7.22 36.5 7.76 40.3 8.30

40.0 19.2 6.01 23.0 6.76 26.9 7.50 28.8 7.86 32.6 8.58 36.5 9.28 40.3 9.95

43.0 19.2 6.53 23.0 7.40 26.9 8.22 28.8 8.64 32.6 9.43 36.5 10.23 40.3 10.97

46.0 19.2 7.09 23.0 8.04 26.9 9.00 28.8 9.46 32.6 10.36 36.5 11.23 40.3 12.08

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


36 HP (U-8MF2E8 & U-14MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 94.1 13.86 108.6 16.04 108.6 16.04 108.6 16.04 123.0 18.19 137.6 20.31 152.0 22.44

-5.0 94.1 13.86 108.6 16.06 108.6 16.06 108.6 16.06 123.0 18.22 137.6 20.34 152.0 22.49

0.0 94.1 13.88 108.6 16.09 108.6 16.09 108.6 16.09 123.0 18.24 137.6 20.40 152.0 22.52

5.0 94.1 13.91 108.6 16.15 108.6 16.15 108.6 16.15 123.0 18.33 137.6 20.48 152.0 22.63

10.0 94.1 13.97 108.6 16.28 108.6 16.28 108.6 16.28 123.0 18.49 137.6 20.64 152.0 22.80

15.0 94.1 14.08 108.6 16.53 108.6 16.53 108.6 16.53 123.0 18.82 137.6 20.98 152.0 23.13

130% 20.0 94.1 14.41 108.6 17.22 108.6 17.22 108.6 17.22 123.0 19.65 137.6 22.14 152.0 25.56

25.0 94.1 15.90 108.6 20.56 108.6 20.56 108.6 20.56 123.0 24.15 137.6 28.01 152.0 32.13

30.0 94.1 19.98 108.6 25.39 108.6 25.39 108.6 25.39 123.0 29.73 137.6 34.31 146.1 35.88

35.0 94.1 24.34 108.6 30.61 108.6 30.61 108.6 30.61 123.0 35.74 128.7 35.88 134.3 35.88

40.0 94.1 29.04 107.7 35.88 107.7 35.88 107.7 35.88 112.8 35.88 118.0 35.88 120.0 33.95

43.0 94.1 32.04 98.8 33.81 98.8 33.81 98.8 33.81 98.8 31.05 98.8 28.48 98.8 26.11

46.0 78.0 25.12 78.0 25.12 78.0 25.12 78.0 25.12 78.0 23.07 78.0 21.20 78.0 19.43

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 84.8 12.50 101.8 14.99 106.1 15.65 106.1 15.65 120.2 17.75 134.3 19.84 148.5 21.91

-5.0 84.8 12.50 101.8 15.01 106.1 15.68 106.1 15.68 120.2 17.77 134.3 19.87 148.5 21.97

0.0 84.8 12.50 101.8 15.04 106.1 15.70 106.1 15.70 120.2 17.83 134.3 19.93 148.5 22.02

5.0 84.8 12.53 101.8 15.07 106.1 15.76 106.1 15.76 120.2 17.91 134.3 20.01 148.5 22.11

10.0 84.8 12.59 101.8 15.15 106.1 15.90 106.1 15.90 120.2 18.05 134.3 20.18 148.5 22.27

15.0 84.8 12.70 101.8 15.32 106.1 16.15 106.1 16.15 120.2 18.35 134.3 20.51 148.5 22.60

120% 20.0 84.8 13.03 101.8 15.76 106.1 16.75 106.1 16.75 120.2 19.13 134.3 21.28 148.5 24.43

25.0 84.8 14.38 101.8 17.75 106.1 19.82 106.1 19.82 120.2 23.24 134.3 26.91 148.5 30.80

30.0 84.8 18.02 101.8 22.19 106.1 24.51 106.1 24.51 120.2 28.62 134.3 33.01 145.2 35.88

35.0 84.8 21.94 101.8 26.94 106.1 29.56 106.1 29.56 120.2 34.47 128.0 35.88 133.5 35.88

40.0 84.8 26.14 101.8 32.10 106.1 35.13 106.1 35.13 112.2 35.88 117.4 35.88 120.0 34.33

43.0 84.8 28.87 98.8 34.09 98.8 34.09 98.8 34.09 98.8 31.33 98.8 28.73 98.8 26.33

46.0 78.0 25.28 78.0 25.28 78.0 25.28 78.0 25.28 78.0 23.24 78.0 21.33 78.0 19.57

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 76.0 11.18 91.1 13.41 103.5 15.29 103.5 15.29 117.4 17.33 131.1 19.38 144.9 21.42

-5.0 76.0 11.18 91.1 13.44 103.5 15.29 103.5 15.29 117.4 17.36 131.1 19.40 144.9 21.45

0.0 76.0 11.21 91.1 13.47 103.5 15.32 103.5 15.32 117.4 17.39 131.1 19.46 144.9 21.50

5.0 76.0 11.23 91.1 13.50 103.5 15.40 103.5 15.40 117.4 17.47 131.1 19.54 144.9 21.58

10.0 76.0 11.26 91.1 13.55 103.5 15.48 103.5 15.48 117.4 17.61 131.1 19.71 144.9 21.75

15.0 76.0 11.37 91.1 13.72 103.5 15.73 103.5 15.73 117.4 17.88 131.1 20.01 144.9 22.05

110% 20.0 76.0 11.67 91.1 14.13 103.5 16.31 103.5 16.31 117.4 18.60 131.1 20.78 144.9 23.35

25.0 76.0 12.89 91.1 15.87 103.5 19.10 103.5 19.10 117.4 22.36 131.1 25.83 144.9 29.53

30.0 76.0 16.17 91.1 19.84 103.5 23.65 103.5 23.65 117.4 27.57 131.1 31.74 144.3 35.88

35.0 76.0 19.65 91.1 24.07 103.5 28.57 103.5 28.57 117.4 33.23 127.2 35.88 132.7 35.88

40.0 76.0 23.40 91.1 28.65 103.5 33.95 103.5 33.95 111.6 35.88 116.7 35.88 120.0 34.72

43.0 76.0 25.81 91.1 31.60 98.8 34.42 98.8 34.42 98.8 31.60 98.8 29.01 98.8 26.58

46.0 76.0 28.37 78.0 25.47 78.0 25.47 78.0 25.47 78.0 23.40 78.0 21.47 78.0 19.71

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 67.4 9.91 80.8 11.92 94.2 13.91 101.0 14.90 114.4 16.89 128.0 18.91 141.4 20.89

-5.0 67.4 9.94 80.8 11.92 94.2 13.91 101.0 14.93 114.4 16.92 128.0 18.93 141.4 20.92

0.0 67.4 9.94 80.8 11.95 94.2 13.94 101.0 14.96 114.4 16.97 128.0 18.99 141.4 20.98

5.0 67.4 9.96 80.8 11.98 94.2 13.99 101.0 15.01 114.4 17.03 128.0 19.07 141.4 21.06

10.0 67.4 9.99 80.8 12.03 94.2 14.08 101.0 15.10 114.4 17.17 128.0 19.21 141.4 21.20

15.0 67.4 10.10 80.8 12.17 94.2 14.27 101.0 15.32 114.4 17.44 128.0 19.54 141.4 21.53

100% 20.0 67.4 10.38 80.8 12.56 94.2 14.77 101.0 15.87 114.4 18.08 128.0 20.29 141.4 22.25

25.0 67.4 11.51 80.8 14.10 94.2 16.89 101.0 18.38 114.4 21.47 128.0 24.78 141.4 28.29

30.0 67.4 14.41 80.8 17.61 94.2 21.03 101.0 22.80 114.4 26.55 128.0 30.50 141.4 34.67

35.0 67.4 17.47 80.8 21.33 94.0 25.34 101.0 27.60 113.9 31.80 126.4 35.88 131.9 35.88

40.0 67.4 20.81 80.8 25.39 94.2 30.22 101.0 32.76 110.9 35.88 116.0 35.88 120.0 35.13

43.0 67.4 22.94 80.8 27.99 94.2 33.37 98.8 34.72 98.8 31.91 98.8 29.28 98.8 26.85

9 46.0 67.4 25.20 78.0 29.06 78.0 26.74 78.0 25.67 78.0 23.57 78.0 21.64 78.0 19.87
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


36 HP (U-8MF2E8 & U-14MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 60.6 8.91 72.7 10.71 84.8 12.50 90.9 13.41 103.0 15.21 115.1 17.00 127.3 18.80

-5.0 60.6 8.94 72.7 10.74 84.8 12.53 90.9 13.41 103.0 15.24 115.1 17.03 127.3 18.82

0.0 60.6 8.94 72.7 10.74 84.8 12.56 90.9 13.44 103.0 15.26 115.1 17.06 127.3 18.88

5.0 60.6 8.97 72.7 10.76 84.8 12.59 90.9 13.50 103.0 15.29 115.1 17.11 127.3 18.96

10.0 60.6 9.00 72.7 10.82 84.8 12.64 90.9 13.55 103.0 15.40 115.1 17.25 127.3 19.10

15.0 60.6 9.05 72.7 10.93 84.8 12.78 90.9 13.72 103.0 15.59 115.1 17.47 127.3 19.38

90% 20.0 60.6 9.27 72.7 11.21 84.8 13.17 90.9 14.13 103.0 16.09 115.1 18.05 127.3 20.01

25.0 60.6 10.10 72.7 12.28 84.8 14.52 90.9 15.70 103.0 18.19 115.1 20.84 127.3 23.60

30.0 60.6 12.67 72.7 15.32 84.8 18.13 90.9 19.60 103.0 22.63 115.1 25.83 127.3 29.17

35.0 60.6 15.40 72.7 18.60 84.8 22.00 90.9 23.76 103.0 27.41 115.1 31.22 127.3 35.19

40.0 60.6 18.33 72.7 22.16 84.8 26.19 90.9 28.29 103.0 32.62 113.0 35.88 118.1 35.88

43.0 60.6 20.20 72.7 24.45 84.8 28.92 90.9 31.24 98.8 33.31 98.8 30.61 98.8 28.07

46.0 60.6 22.19 72.7 26.88 78.0 27.66 78.0 26.55 78.0 24.40 78.0 22.41 78.0 20.56

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 53.8 7.92 64.6 9.52 75.4 11.12 80.8 11.92 91.6 13.50 102.3 15.10 113.1 16.70

-5.0 53.8 7.95 64.6 9.52 75.4 11.12 80.8 11.92 91.6 13.52 102.3 15.12 113.1 16.73

0.0 53.8 7.95 64.6 9.55 75.4 11.15 80.8 11.95 91.6 13.55 102.3 15.15 113.1 16.75

5.0 53.8 7.95 64.6 9.55 75.4 11.18 80.8 11.98 91.6 13.58 102.3 15.21 113.1 16.81

10.0 53.8 7.98 64.6 9.60 75.4 11.21 80.8 12.03 91.6 13.66 102.3 15.29 113.1 16.92

15.0 53.8 8.03 64.6 9.66 75.4 11.32 80.8 12.14 91.6 13.80 102.3 15.46 113.1 17.11

80% 20.0 53.8 8.17 64.6 9.88 75.4 11.56 80.8 12.42 91.6 14.13 102.3 15.84 113.1 17.55

25.0 53.8 8.78 64.6 10.63 75.4 12.48 80.8 13.41 91.6 15.24 102.3 17.28 113.1 19.43

30.0 53.8 11.04 64.6 13.19 75.4 15.48 80.8 16.64 91.6 19.07 102.3 21.61 113.1 24.23

35.0 53.8 13.41 64.6 16.06 75.4 18.85 80.8 20.26 91.6 23.18 102.3 26.22 113.1 29.37

40.0 53.8 15.98 64.6 19.15 75.4 22.47 80.8 24.15 91.6 27.66 102.3 31.27 113.1 35.05

43.0 53.8 17.61 64.6 21.14 75.4 24.81 80.8 26.69 91.6 30.58 98.8 32.32 98.8 29.67

46.0 53.8 19.32 64.6 23.24 75.4 27.30 78.0 27.68 78.0 25.45 78.0 23.40 78.0 21.47

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 47.2 6.93 56.6 8.34 66.0 9.72 70.7 10.43 80.1 11.81 89.6 13.22 99.0 14.60

-5.0 47.2 6.96 56.6 8.34 66.0 9.74 70.7 10.43 80.1 11.84 89.6 13.22 99.0 14.63

0.0 47.2 6.96 56.6 8.34 66.0 9.74 70.7 10.43 80.1 11.84 89.6 13.25 99.0 14.66

5.0 47.2 6.96 56.6 8.36 66.0 9.77 70.7 10.46 80.1 11.87 89.6 13.28 99.0 14.68

10.0 47.2 6.98 56.6 8.39 66.0 9.80 70.7 10.49 80.1 11.92 89.6 13.33 99.0 14.74

15.0 47.2 7.01 56.6 8.45 66.0 9.85 70.7 10.57 80.1 12.01 89.6 13.44 99.0 14.88

70% 20.0 47.2 7.12 56.6 8.58 66.0 10.05 70.7 10.76 80.1 12.25 89.6 13.72 99.0 15.21

25.0 47.2 7.51 56.6 9.08 66.0 10.65 70.7 11.45 80.1 13.00 89.6 14.55 99.0 16.09

30.0 47.2 9.52 56.6 11.23 66.0 13.03 70.7 13.97 80.1 15.84 89.6 17.80 99.0 19.79

35.0 47.2 11.56 56.6 13.72 66.0 15.93 70.7 17.06 80.1 19.35 89.6 21.72 99.0 24.12

40.0 47.2 13.77 56.6 16.34 66.0 19.02 70.7 20.37 80.1 23.13 89.6 25.94 99.0 28.87

43.0 47.2 15.15 56.6 18.05 66.0 21.00 70.7 22.49 80.1 25.56 89.6 28.73 98.8 31.82

46.0 47.2 16.64 56.6 19.84 66.0 23.10 70.7 24.78 78.0 26.88 78.0 24.70 78.0 22.71

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 40.4 5.93 48.5 7.15 56.6 8.34 60.6 8.94 68.7 10.13 76.8 11.32 84.8 12.50

-5.0 40.4 5.96 48.5 7.15 56.6 8.34 60.6 8.94 68.7 10.13 76.8 11.32 84.8 12.53

0.0 40.4 5.96 48.5 7.15 56.6 8.34 60.6 8.94 68.7 10.16 76.8 11.34 84.8 12.53

5.0 40.4 5.96 48.5 7.15 56.6 8.36 60.6 8.97 68.7 10.16 76.8 11.37 84.8 12.56

10.0 40.4 5.96 48.5 7.18 56.6 8.39 60.6 9.00 68.7 10.18 76.8 11.40 84.8 12.61

15.0 40.4 5.99 48.5 7.20 56.6 8.42 60.6 9.03 68.7 10.27 76.8 11.48 84.8 12.70

60% 20.0 40.4 6.07 48.5 7.29 56.6 8.53 60.6 9.16 68.7 10.41 76.8 11.65 84.8 12.89

25.0 40.4 6.32 48.5 7.62 56.6 8.94 60.6 9.58 68.7 10.90 76.8 12.17 84.8 13.47

30.0 40.4 8.11 48.5 9.44 56.6 10.82 60.6 11.54 68.7 12.94 76.8 14.41 84.8 15.87

35.0 40.4 9.83 48.5 11.54 56.6 13.25 60.6 14.10 68.7 15.87 76.8 17.66 84.8 19.46

40.0 40.4 11.70 48.5 13.74 56.6 15.81 60.6 16.86 68.7 18.99 76.8 21.14 84.8 23.32

43.0 40.4 12.86 48.5 15.15 56.6 17.47 60.6 18.66 68.7 21.00 76.8 23.40 84.8 25.86

46.0 40.4 14.10 48.5 16.64 56.6 19.24 60.6 20.53 68.7 23.16 76.8 25.86 78.0 24.43

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


36 HP (U-8MF2E8 & U-14MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 33.6 4.97 40.4 5.96 47.2 6.96 50.5 7.45 57.3 8.45 63.9 9.44 70.7 10.43

-5.0 33.6 4.97 40.4 5.96 47.2 6.96 50.5 7.45 57.3 8.45 63.9 9.44 70.7 10.43

0.0 33.6 4.97 40.4 5.96 47.2 6.96 50.5 7.45 57.3 8.45 63.9 9.44 70.7 10.43

5.0 33.6 4.97 40.4 5.96 47.2 6.96 50.5 7.45 57.3 8.45 63.9 9.47 70.7 10.46

10.0 33.6 4.97 40.4 5.96 47.2 6.98 50.5 7.48 57.3 8.47 63.9 9.49 70.7 10.49

15.0 33.6 5.00 40.4 5.99 47.2 7.01 50.5 7.51 57.3 8.53 63.9 9.52 70.7 10.54

50% 20.0 33.6 5.02 40.4 6.04 47.2 7.07 50.5 7.59 57.3 8.61 63.9 9.63 70.7 10.65

25.0 33.6 5.19 40.4 6.24 47.2 7.31 50.5 7.84 57.3 8.89 63.9 9.94 70.7 10.98

30.0 33.6 6.68 40.4 7.76 47.2 8.83 50.5 9.36 57.3 10.38 63.9 11.40 70.7 12.42

35.0 33.6 8.22 40.4 9.52 47.2 10.79 50.5 11.45 57.3 12.75 63.9 14.02 70.7 15.32

40.0 33.6 9.74 40.4 11.32 47.2 12.89 50.5 13.69 57.3 15.26 63.9 16.84 70.7 18.44

43.0 33.6 10.71 40.4 12.48 47.2 14.24 50.5 15.12 57.3 16.89 63.9 18.66 70.7 20.42

46.0 33.6 11.73 40.4 13.69 47.2 15.65 50.5 16.64 57.3 18.60 63.9 20.59 70.7 22.55

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 27.0 3.97 32.3 4.75 37.7 5.55 40.4 5.96 45.8 6.76 51.2 7.53 56.6 8.34

-5.0 27.0 3.97 32.3 4.77 37.7 5.55 40.4 5.96 45.8 6.76 51.2 7.53 56.6 8.34

0.0 27.0 3.97 32.3 4.77 37.7 5.58 40.4 5.96 45.8 6.76 51.2 7.56 56.6 8.34

5.0 27.0 3.97 32.3 4.77 37.7 5.58 40.4 5.96 45.8 6.76 51.2 7.56 56.6 8.36

10.0 27.0 3.97 32.3 4.77 37.7 5.58 40.4 5.96 45.8 6.76 51.2 7.56 56.6 8.36

15.0 27.0 3.97 32.3 4.77 37.7 5.60 40.4 5.99 45.8 6.79 51.2 7.59 56.6 8.39

40% 20.0 27.0 4.00 32.3 4.83 37.7 5.63 40.4 6.04 45.8 6.84 51.2 7.65 56.6 8.47

25.0 27.0 4.08 32.3 4.91 37.7 5.74 40.4 6.15 45.8 6.98 51.2 7.81 56.6 8.64

30.0 27.0 4.89 32.3 5.71 37.7 6.54 40.4 6.96 45.8 7.76 51.2 8.56 56.6 9.38

35.0 27.0 6.73 32.3 7.67 37.7 8.58 40.4 9.05 45.8 9.94 51.2 10.82 56.6 11.70

40.0 27.0 7.92 32.3 9.08 37.7 10.24 40.4 10.79 45.8 11.92 51.2 13.00 56.6 14.10

43.0 27.0 8.69 32.3 9.99 37.7 11.26 40.4 11.90 45.8 13.17 51.2 14.41 56.6 15.62

46.0 27.0 9.47 32.3 10.93 37.7 12.36 40.4 13.08 45.8 14.49 51.2 15.87 56.6 17.22

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 20.2 2.98 24.2 3.56 28.3 4.17 30.3 4.47 34.3 5.05 38.4 5.66 42.4 6.27

-5.0 20.2 2.98 24.2 3.56 28.3 4.17 30.3 4.47 34.3 5.05 38.4 5.66 42.4 6.27

0.0 20.2 2.98 24.2 3.56 28.3 4.17 30.3 4.47 34.3 5.08 38.4 5.66 42.4 6.27

5.0 20.2 2.98 24.2 3.59 28.3 4.17 30.3 4.47 34.3 5.08 38.4 5.66 42.4 6.27

10.0 20.2 2.98 24.2 3.59 28.3 4.17 30.3 4.47 34.3 5.08 38.4 5.69 42.4 6.27

15.0 20.2 2.98 24.2 3.59 28.3 4.20 30.3 4.50 34.3 5.08 38.4 5.69 42.4 6.29
30% 20.0 20.2 3.01 24.2 3.59 28.3 4.20 30.3 4.50 34.3 5.11 38.4 5.71 42.4 6.32

25.0 20.2 3.04 24.2 3.64 28.3 4.25 30.3 4.55 34.3 5.19 38.4 5.80 42.4 6.40

30.0 20.2 3.39 24.2 4.00 28.3 4.61 30.3 4.91 34.3 5.52 38.4 6.10 42.4 6.71

35.0 20.2 5.35 24.2 5.99 28.3 6.60 30.3 6.90 34.3 7.45 38.4 8.03 42.4 8.56

40.0 20.2 6.24 24.2 7.04 28.3 7.81 30.3 8.17 34.3 8.91 38.4 9.60 42.4 10.29

43.0 20.2 6.79 24.2 7.70 28.3 8.56 30.3 8.97 34.3 9.80 38.4 10.63 42.4 11.40

46.0 20.2 7.37 24.2 8.39 28.3 9.36 30.3 9.83 34.3 10.76 38.4 11.67 42.4 12.56

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


38 HP (U-8MF2E8 & U-14MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 99.7 14.11 115.0 16.34 115.0 16.34 115.0 16.34 130.3 18.53 145.7 20.70 161.0 22.87

-5.0 99.7 14.11 115.0 16.36 115.0 16.36 115.0 16.36 130.3 18.56 145.7 20.73 161.0 22.93

0.0 99.7 14.14 115.0 16.39 115.0 16.39 115.0 16.39 130.3 18.62 145.7 20.79 161.0 22.99

5.0 99.7 14.17 115.0 16.48 115.0 16.48 115.0 16.48 130.3 18.71 145.7 20.91 161.0 23.11

10.0 99.7 14.23 115.0 16.63 115.0 16.63 115.0 16.63 130.3 18.92 145.7 21.12 161.0 23.31

15.0 99.7 14.37 115.0 16.96 115.0 16.96 115.0 16.96 130.3 19.33 145.7 21.53 161.0 23.73

130% 20.0 99.7 14.82 115.0 17.88 115.0 17.88 115.0 17.88 130.3 21.00 145.7 24.71 161.0 28.72

25.0 99.7 16.96 115.0 22.36 115.0 22.36 115.0 22.36 130.3 26.49 145.7 30.95 161.0 35.73

30.0 99.7 21.21 115.0 27.47 115.0 27.47 115.0 27.47 130.3 32.37 145.7 37.63 153.2 38.61

35.0 99.7 25.72 115.0 32.97 115.0 32.97 115.0 32.97 129.8 38.52 135.6 38.61 141.2 38.61

40.0 99.7 30.65 114.3 38.61 114.3 38.61 114.3 38.61 119.4 38.61 121.7 36.71 121.7 33.65

43.0 99.7 33.80 100.2 33.38 100.2 33.38 100.2 33.38 100.2 30.68 100.2 28.13 100.2 25.78

46.0 79.1 24.74 79.1 24.74 79.1 24.74 79.1 24.74 79.1 22.72 79.1 20.88 79.1 19.13

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 89.9 12.71 107.9 15.27 112.4 15.95 112.4 15.95 127.3 18.09 142.3 20.23 157.3 22.33

-5.0 89.9 12.74 107.9 15.30 112.4 15.98 112.4 15.98 127.3 18.12 142.3 20.26 157.3 22.39

0.0 89.9 12.74 107.9 15.33 112.4 16.01 112.4 16.01 127.3 18.18 142.3 20.31 157.3 22.45

5.0 89.9 12.77 107.9 15.35 112.4 16.10 112.4 16.10 127.3 18.27 142.3 20.43 157.3 22.57

10.0 89.9 12.83 107.9 15.44 112.4 16.25 112.4 16.25 127.3 18.47 142.3 20.64 157.3 22.78

15.0 89.9 12.98 107.9 15.65 112.4 16.54 112.4 16.54 127.3 18.86 142.3 21.06 157.3 23.20

120% 20.0 89.9 13.39 107.9 16.25 112.4 17.37 112.4 17.37 127.3 20.14 142.3 23.67 157.3 27.47

25.0 89.9 15.30 107.9 19.10 112.4 21.53 112.4 21.53 127.3 25.48 142.3 29.73 157.3 34.24

30.0 89.9 19.10 107.9 23.73 112.4 26.49 112.4 26.49 127.3 31.19 142.3 36.20 152.3 38.61

35.0 89.9 23.17 107.9 28.72 112.4 31.84 112.4 31.84 127.3 37.39 134.7 38.61 140.4 38.61

40.0 89.9 27.56 107.9 34.13 112.4 37.72 112.4 37.72 118.8 38.61 121.7 37.13 121.7 34.04

43.0 89.9 30.41 100.2 33.68 100.2 33.68 100.2 33.68 100.2 30.95 100.2 28.39 100.2 26.02

46.0 79.1 24.92 79.1 24.92 79.1 24.92 79.1 24.92 79.1 22.90 79.1 21.03 79.1 19.28

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 80.5 11.38 96.5 13.66 109.7 15.56 109.7 15.56 124.3 17.64 138.9 19.75 153.5 21.83

-5.0 80.5 11.40 96.5 13.69 109.7 15.59 109.7 15.59 124.3 17.67 138.9 19.78 153.5 21.86

0.0 80.5 11.40 96.5 13.72 109.7 15.62 109.7 15.62 124.3 17.73 138.9 19.84 153.5 21.92

5.0 80.5 11.43 96.5 13.75 109.7 15.71 109.7 15.71 124.3 17.82 138.9 19.93 153.5 22.04

10.0 80.5 11.49 96.5 13.84 109.7 15.83 109.7 15.83 124.3 18.00 138.9 20.14 153.5 22.22

15.0 80.5 11.61 96.5 14.02 109.7 16.13 109.7 16.13 124.3 18.38 138.9 20.55 153.5 22.63

110% 20.0 80.5 12.00 96.5 14.55 109.7 16.90 109.7 16.90 124.3 19.33 138.9 22.66 153.5 26.25

25.0 80.5 13.72 96.5 17.05 109.7 20.76 109.7 20.76 124.3 24.50 138.9 28.51 153.5 32.82

30.0 80.5 17.11 96.5 21.18 109.7 25.54 109.7 25.54 124.3 30.03 138.9 34.81 151.3 38.61

35.0 80.5 20.73 96.5 25.60 109.7 30.74 109.7 30.74 124.3 36.03 133.9 38.61 139.5 38.61

40.0 80.5 24.65 96.5 30.41 109.7 36.41 109.7 36.41 118.1 38.61 121.7 37.54 121.7 34.42

43.0 80.5 27.18 96.5 33.53 100.2 34.01 100.2 34.01 100.2 31.24 100.2 28.66 100.2 26.28

46.0 79.1 25.10 79.1 25.10 79.1 25.10 79.1 25.10 79.1 23.05 79.1 21.18 79.1 19.42

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 71.4 10.10 85.6 12.12 99.8 14.17 107.0 15.18 121.2 17.23 135.6 19.25 149.8 21.29

-5.0 71.4 10.10 85.6 12.15 99.8 14.20 107.0 15.21 121.2 17.26 135.6 19.31 149.8 21.32

0.0 71.4 10.13 85.6 12.18 99.8 14.23 107.0 15.24 121.2 17.29 135.6 19.36 149.8 21.38

5.0 71.4 10.16 85.6 12.21 99.8 14.29 107.0 15.30 121.2 17.37 135.6 19.45 149.8 21.50

10.0 71.4 10.22 85.6 12.30 99.8 14.37 107.0 15.44 121.2 17.55 135.6 19.66 149.8 21.68

15.0 71.4 10.34 85.6 12.47 99.8 14.61 107.0 15.71 121.2 17.88 135.6 20.05 149.8 22.10

100% 20.0 71.4 10.69 85.6 12.95 99.8 15.27 107.0 16.42 121.2 18.77 135.6 21.68 149.8 25.07

25.0 71.4 12.24 85.6 15.12 99.8 18.30 107.0 19.96 121.2 23.52 135.6 27.35 149.8 31.42

30.0 71.4 15.24 85.6 18.77 99.8 22.60 107.0 24.62 121.2 28.87 135.6 33.41 149.8 38.25

35.0 71.4 18.41 85.6 22.66 99.8 27.15 107.0 29.70 120.7 34.45 133.0 38.61 138.7 38.61

40.0 71.4 21.89 85.6 26.94 99.8 32.31 107.0 35.14 117.4 38.61 121.7 38.02 121.7 34.87

43.0 71.4 24.12 85.6 29.67 99.8 35.64 100.2 34.33 100.2 31.54 100.2 28.96 100.2 26.55

9 46.0 71.4 26.49 79.1 28.63 79.1 26.37 79.1 25.27 79.1 23.26 79.1 21.32 79.1 19.57
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


38 HP (U-8MF2E8 & U-14MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 64.2 9.09 77.0 10.93 89.9 12.74 96.3 13.66 109.1 15.50 122.0 17.32 134.8 19.16

-5.0 64.2 9.09 77.0 10.93 89.9 12.77 96.3 13.69 109.1 15.50 122.0 17.34 134.8 19.19

0.0 64.2 9.12 77.0 10.93 89.9 12.77 96.3 13.69 109.1 15.56 122.0 17.40 134.8 19.25

5.0 64.2 9.12 77.0 10.96 89.9 12.83 96.3 13.75 109.1 15.62 122.0 17.46 134.8 19.33

10.0 64.2 9.18 77.0 11.02 89.9 12.89 96.3 13.84 109.1 15.74 122.0 17.61 134.8 19.54

15.0 64.2 9.27 77.0 11.17 89.9 13.10 96.3 14.05 109.1 15.98 122.0 17.94 134.8 19.90

90% 20.0 64.2 9.50 77.0 11.52 89.9 13.57 96.3 14.58 109.1 16.66 122.0 18.71 134.8 20.79

25.0 64.2 10.66 77.0 13.07 89.9 15.65 96.3 17.02 109.1 19.90 122.0 22.96 134.8 26.23

30.0 64.2 13.37 77.0 16.31 89.9 19.45 96.3 21.12 109.1 24.59 122.0 28.27 134.8 32.14

35.0 64.2 16.19 77.0 19.75 89.9 23.52 96.3 25.51 109.1 29.64 122.0 34.01 134.3 38.34

40.0 64.2 19.25 77.0 23.46 89.9 27.95 96.3 30.29 109.1 35.19 119.3 38.61 121.7 36.86

43.0 64.2 21.21 77.0 25.87 89.9 30.83 96.3 33.41 100.2 33.00 100.2 30.29 100.2 27.80

46.0 64.2 23.26 77.0 28.42 79.1 27.29 79.1 26.20 79.1 24.09 79.1 22.13 79.1 20.29

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 57.0 8.08 68.5 9.71 79.9 11.32 85.6 12.15 97.0 13.75 108.4 15.38 119.8 17.02

-5.0 57.0 8.08 68.5 9.71 79.9 11.35 85.6 12.15 97.0 13.78 108.4 15.41 119.8 17.05

0.0 57.0 8.08 68.5 9.71 79.9 11.35 85.6 12.18 97.0 13.81 108.4 15.44 119.8 17.08

5.0 57.0 8.11 68.5 9.74 79.9 11.38 85.6 12.21 97.0 13.84 108.4 15.50 119.8 17.17

10.0 57.0 8.14 68.5 9.77 79.9 11.43 85.6 12.27 97.0 13.93 108.4 15.59 119.8 17.29

15.0 57.0 8.20 68.5 9.89 79.9 11.58 85.6 12.41 97.0 14.11 108.4 15.83 119.8 17.55

80% 20.0 57.0 8.38 68.5 10.13 79.9 11.91 85.6 12.80 97.0 14.58 108.4 16.39 119.8 18.18

25.0 57.0 9.21 68.5 11.20 79.9 13.28 85.6 14.35 97.0 16.63 108.4 19.04 119.8 21.56

30.0 57.0 11.61 68.5 14.02 79.9 16.57 85.6 17.91 97.0 20.67 108.4 23.58 119.8 26.64

35.0 57.0 14.08 68.5 17.02 79.9 20.11 85.6 21.71 97.0 25.01 108.4 28.48 119.8 32.14

40.0 57.0 16.75 68.5 20.26 79.9 23.91 85.6 25.81 97.0 29.76 108.4 33.89 119.8 38.25

43.0 57.0 18.44 68.5 22.30 79.9 26.37 85.6 28.48 97.0 32.85 100.2 32.05 100.2 29.43

46.0 57.0 20.26 68.5 24.50 79.1 28.48 79.1 27.35 79.1 25.16 79.1 23.11 79.1 21.24

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 50.0 7.07 59.9 8.49 69.9 9.92 74.9 10.63 84.9 12.03 94.9 13.45 104.9 14.88

-5.0 50.0 7.07 59.9 8.49 69.9 9.92 74.9 10.63 84.9 12.06 94.9 13.48 104.9 14.91

0.0 50.0 7.07 59.9 8.49 69.9 9.92 74.9 10.63 84.9 12.06 94.9 13.48 104.9 14.94

5.0 50.0 7.10 59.9 8.52 69.9 9.95 74.9 10.66 84.9 12.09 94.9 13.54 104.9 14.97

10.0 50.0 7.10 59.9 8.55 69.9 9.98 74.9 10.72 84.9 12.15 94.9 13.60 104.9 15.06

15.0 50.0 7.16 59.9 8.61 69.9 10.07 74.9 10.81 84.9 12.30 94.9 13.75 104.9 15.24

70% 20.0 50.0 7.28 59.9 8.79 69.9 10.31 74.9 11.08 84.9 12.62 94.9 14.14 104.9 15.68

25.0 50.0 7.84 59.9 9.50 69.9 11.20 74.9 12.03 84.9 13.69 94.9 15.50 104.9 17.43

30.0 50.0 9.98 59.9 11.91 69.9 13.93 74.9 14.97 84.9 17.14 94.9 19.39 104.9 21.74

35.0 50.0 12.12 59.9 14.46 69.9 16.93 74.9 18.21 84.9 20.82 94.9 23.52 104.9 26.34

40.0 50.0 14.40 59.9 17.23 69.9 20.20 74.9 21.71 84.9 24.83 94.9 28.04 104.9 31.39

43.0 50.0 15.86 59.9 19.01 69.9 22.28 74.9 23.97 84.9 27.41 94.9 31.01 100.2 31.66

46.0 50.0 17.37 59.9 20.88 69.9 24.50 74.9 26.34 79.1 26.61 79.1 24.47 79.1 22.48

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 42.8 6.06 51.4 7.28 59.9 8.49 64.2 9.09 72.8 10.31 81.3 11.52 89.9 12.74

-5.0 42.8 6.06 51.4 7.28 59.9 8.49 64.2 9.12 72.8 10.34 81.3 11.55 89.9 12.77

0.0 42.8 6.06 51.4 7.28 59.9 8.49 64.2 9.12 72.8 10.34 81.3 11.55 89.9 12.77

5.0 42.8 6.06 51.4 7.31 59.9 8.52 64.2 9.12 72.8 10.37 81.3 11.58 89.9 12.80

10.0 42.8 6.09 51.4 7.31 59.9 8.55 64.2 9.15 72.8 10.40 81.3 11.64 89.9 12.86

15.0 42.8 6.12 51.4 7.37 59.9 8.61 64.2 9.24 72.8 10.48 81.3 11.73 89.9 12.98

60% 20.0 42.8 6.21 51.4 7.48 59.9 8.76 64.2 9.39 72.8 10.69 81.3 11.97 89.9 13.28

25.0 42.8 6.56 51.4 7.93 59.9 9.33 64.2 10.01 72.8 11.38 81.3 12.77 89.9 14.14

30.0 42.8 8.46 51.4 9.95 59.9 11.52 64.2 12.33 72.8 13.96 81.3 15.65 89.9 17.37

35.0 42.8 10.28 51.4 12.12 59.9 14.05 64.2 15.03 72.8 17.02 81.3 19.10 89.9 21.21

40.0 42.8 12.18 51.4 14.43 59.9 16.75 64.2 17.94 72.8 20.34 81.3 22.78 89.9 25.30

43.0 42.8 13.42 51.4 15.92 59.9 18.50 64.2 19.81 72.8 22.45 81.3 25.22 89.9 28.01

46.0 42.8 14.70 51.4 17.46 59.9 20.31 64.2 21.77 72.8 24.74 79.1 26.37 79.1 24.26

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


38 HP (U-8MF2E8 & U-14MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 35.6 5.05 42.8 6.06 50.0 7.07 53.5 7.57 60.7 8.58 67.7 9.62 74.9 10.63

-5.0 35.6 5.05 42.8 6.06 50.0 7.07 53.5 7.57 60.7 8.61 67.7 9.62 74.9 10.63

0.0 35.6 5.05 42.8 6.06 50.0 7.10 53.5 7.60 60.7 8.61 67.7 9.62 74.9 10.63

5.0 35.6 5.05 42.8 6.09 50.0 7.10 53.5 7.60 60.7 8.61 67.7 9.65 74.9 10.66

10.0 35.6 5.08 42.8 6.09 50.0 7.10 53.5 7.63 60.7 8.64 67.7 9.68 74.9 10.69

15.0 35.6 5.08 42.8 6.12 50.0 7.13 53.5 7.66 60.7 8.70 67.7 9.74 74.9 10.75

50% 20.0 35.6 5.14 42.8 6.18 50.0 7.22 53.5 7.75 60.7 8.82 67.7 9.86 74.9 10.93

25.0 35.6 5.35 42.8 6.44 50.0 7.57 53.5 8.11 60.7 9.24 67.7 10.34 74.9 11.43

30.0 35.6 7.07 42.8 8.20 50.0 9.36 53.5 9.95 60.7 11.14 67.7 12.33 74.9 13.57

35.0 35.6 8.55 42.8 9.98 50.0 11.40 53.5 12.15 60.7 13.63 67.7 15.12 74.9 16.63

40.0 35.6 10.13 42.8 11.85 50.0 13.60 53.5 14.49 60.7 16.28 67.7 18.09 74.9 19.93

43.0 35.6 11.14 42.8 13.07 50.0 15.00 53.5 16.01 60.7 18.00 67.7 20.02 74.9 22.04

46.0 35.6 12.18 42.8 14.32 50.0 16.48 53.5 17.58 60.7 19.81 67.7 22.04 74.9 24.32

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 28.6 4.04 34.2 4.84 39.9 5.67 42.8 6.06 48.5 6.86 54.2 7.69 59.9 8.49

-5.0 28.6 4.04 34.2 4.84 39.9 5.67 42.8 6.06 48.5 6.89 54.2 7.69 59.9 8.49

0.0 28.6 4.04 34.2 4.84 39.9 5.67 42.8 6.06 48.5 6.89 54.2 7.69 59.9 8.49

5.0 28.6 4.04 34.2 4.87 39.9 5.67 42.8 6.09 48.5 6.89 54.2 7.69 59.9 8.52

10.0 28.6 4.04 34.2 4.87 39.9 5.67 42.8 6.09 48.5 6.89 54.2 7.72 59.9 8.52

15.0 28.6 4.07 34.2 4.87 39.9 5.70 42.8 6.12 48.5 6.92 54.2 7.75 59.9 8.58

40% 20.0 28.6 4.10 34.2 4.93 39.9 5.73 42.8 6.15 48.5 7.01 54.2 7.84 59.9 8.67

25.0 28.6 4.19 34.2 5.05 39.9 5.91 42.8 6.36 48.5 7.22 54.2 8.08 59.9 8.94

30.0 28.6 5.52 34.2 6.39 39.9 7.25 42.8 7.69 48.5 8.52 54.2 9.39 59.9 10.22

35.0 28.6 6.95 34.2 7.99 39.9 9.03 42.8 9.53 48.5 10.57 54.2 11.61 59.9 12.65

40.0 28.6 8.20 34.2 9.47 39.9 10.75 42.8 11.38 48.5 12.65 54.2 13.90 59.9 15.18

43.0 28.6 9.00 34.2 10.40 39.9 11.82 42.8 12.53 48.5 13.96 54.2 15.38 59.9 16.78

46.0 28.6 9.80 34.2 11.40 39.9 12.98 42.8 13.78 48.5 15.35 54.2 16.93 59.9 18.50

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 21.4 3.03 25.7 3.62 30.0 4.25 32.1 4.54 36.4 5.17 40.7 5.76 44.9 6.36

-5.0 21.4 3.03 25.7 3.62 30.0 4.25 32.1 4.54 36.4 5.17 40.7 5.76 44.9 6.39

0.0 21.4 3.03 25.7 3.65 30.0 4.25 32.1 4.54 36.4 5.17 40.7 5.76 44.9 6.39

5.0 21.4 3.03 25.7 3.65 30.0 4.25 32.1 4.54 36.4 5.17 40.7 5.76 44.9 6.39

10.0 21.4 3.03 25.7 3.65 30.0 4.25 32.1 4.57 36.4 5.17 40.7 5.79 44.9 6.39

15.0 21.4 3.03 25.7 3.65 30.0 4.28 32.1 4.57 36.4 5.20 40.7 5.79 44.9 6.42
30% 20.0 21.4 3.06 25.7 3.68 30.0 4.28 32.1 4.60 36.4 5.23 40.7 5.82 44.9 6.44

25.0 21.4 3.12 25.7 3.74 30.0 4.37 32.1 4.69 36.4 5.32 40.7 5.94 44.9 6.56

30.0 21.4 3.68 25.7 4.31 30.0 4.96 32.1 5.26 36.4 5.88 40.7 6.50 44.9 7.13

35.0 21.4 5.49 25.7 6.21 30.0 6.89 32.1 7.22 36.4 7.87 40.7 8.52 44.9 9.18

40.0 21.4 6.42 25.7 7.28 30.0 8.14 32.1 8.55 36.4 9.39 40.7 10.22 44.9 11.02

43.0 21.4 6.98 25.7 7.96 30.0 8.94 32.1 9.41 36.4 10.34 40.7 11.26 44.9 12.18

46.0 21.4 7.60 25.7 8.70 30.0 9.77 32.1 10.31 36.4 11.35 40.7 12.38 44.9 13.39

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


40 HP (U-8MF2E8 & U-16MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 105.3 14.37 121.5 16.63 121.5 16.63 121.5 16.63 137.6 18.89 153.9 21.12 170.1 23.34

-5.0 105.3 14.41 121.5 16.66 121.5 16.66 121.5 16.66 137.6 18.92 153.9 21.15 170.1 23.37

0.0 105.3 14.41 121.5 16.73 121.5 16.73 121.5 16.73 137.6 18.98 153.9 21.21 170.1 23.47

5.0 105.3 14.44 121.5 16.82 121.5 16.82 121.5 16.82 137.6 19.11 153.9 21.37 170.1 23.60

10.0 105.3 14.53 121.5 17.01 121.5 17.01 121.5 17.01 137.6 19.37 153.9 21.62 170.1 23.85

15.0 105.3 14.69 121.5 17.43 121.5 17.43 121.5 17.43 137.6 19.91 153.9 22.16 170.1 24.39

130% 20.0 105.3 15.23 121.5 19.14 121.5 19.14 121.5 19.14 137.6 23.02 153.9 27.25 170.1 31.90

25.0 105.3 17.97 121.5 24.14 121.5 24.14 121.5 24.14 137.6 28.81 153.9 33.87 170.1 39.34

30.0 105.3 22.39 121.5 29.51 121.5 29.51 121.5 29.51 137.6 35.01 153.9 40.99 160.3 41.34

35.0 105.3 27.13 121.5 35.33 121.5 35.33 121.5 35.33 136.7 41.34 142.5 41.34 148.4 41.34

40.0 105.3 32.25 120.8 41.34 120.8 41.34 120.8 41.34 123.7 39.81 123.7 36.54 123.7 33.49

43.0 101.8 33.14 101.8 33.14 101.8 33.14 101.8 33.14 101.8 30.43 101.8 27.92 101.8 25.60

46.0 80.3 24.49 80.3 24.49 80.3 24.49 80.3 24.49 80.3 22.51 80.3 20.67 80.3 18.95

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 94.9 12.97 113.9 15.58 118.7 16.25 118.7 16.25 134.5 18.44 150.3 20.61 166.1 22.80

-5.0 94.9 12.97 113.9 15.58 118.7 16.28 118.7 16.28 134.5 18.48 150.3 20.67 166.1 22.83

0.0 94.9 13.01 113.9 15.61 118.7 16.35 118.7 16.35 134.5 18.54 150.3 20.73 166.1 22.93

5.0 94.9 13.04 113.9 15.68 118.7 16.41 118.7 16.41 134.5 18.67 150.3 20.86 166.1 23.06

10.0 94.9 13.10 113.9 15.77 118.7 16.60 118.7 16.60 134.5 18.89 150.3 21.12 166.1 23.31

15.0 94.9 13.26 113.9 16.03 118.7 16.98 118.7 16.98 134.5 19.40 150.3 21.66 166.1 23.85

120% 20.0 94.9 13.77 113.9 16.76 118.7 18.41 118.7 18.41 134.5 22.07 150.3 26.11 166.1 30.50

25.0 94.9 16.19 113.9 20.42 118.7 23.28 118.7 23.28 134.5 27.70 150.3 32.53 166.1 37.71

30.0 94.9 20.16 113.9 25.25 118.7 28.46 118.7 28.46 134.5 33.74 150.3 39.43 159.3 41.34

35.0 94.9 24.42 113.9 30.46 118.7 34.12 118.7 34.12 134.5 40.32 141.6 41.34 147.5 41.34

40.0 94.9 29.00 113.9 36.12 118.7 40.32 118.7 40.32 123.7 40.26 123.7 36.95 123.7 33.90

43.0 94.9 31.96 101.8 33.42 101.8 33.42 101.8 33.42 101.8 30.72 101.8 28.21 101.8 25.85

46.0 80.3 24.68 80.3 24.68 80.3 24.68 80.3 24.68 80.3 22.67 80.3 20.80 80.3 19.08

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 85.0 11.61 101.9 13.93 115.8 15.87 115.8 15.87 131.3 18.00 146.7 20.13 162.2 22.26

-5.0 85.0 11.61 101.9 13.96 115.8 15.90 115.8 15.90 131.3 18.03 146.7 20.16 162.2 22.29

0.0 85.0 11.64 101.9 13.99 115.8 15.93 115.8 15.93 131.3 18.09 146.7 20.26 162.2 22.36

5.0 85.0 11.67 101.9 14.02 115.8 16.03 115.8 16.03 131.3 18.22 146.7 20.38 162.2 22.51

10.0 85.0 11.73 101.9 14.12 115.8 16.19 115.8 16.19 131.3 18.41 146.7 20.61 162.2 22.74

15.0 85.0 11.89 101.9 14.37 115.8 16.57 115.8 16.57 131.3 18.89 146.7 21.15 162.2 23.28

110% 20.0 85.0 12.37 101.9 15.04 115.8 17.68 115.8 17.68 131.3 21.18 146.7 24.99 162.2 29.16

25.0 85.0 14.50 101.9 18.19 115.8 22.39 115.8 22.39 131.3 26.62 146.7 31.20 162.2 36.12

30.0 85.0 18.06 101.9 22.51 115.8 27.44 115.8 27.44 131.3 32.47 146.7 37.87 158.3 41.34

35.0 85.0 21.81 101.9 27.16 115.8 32.91 115.8 32.91 131.3 38.83 140.7 41.34 146.4 41.34

40.0 85.0 25.92 101.9 32.21 115.8 38.92 115.8 38.92 123.7 40.70 123.7 37.40 123.7 34.28

43.0 85.0 28.52 101.8 33.74 101.8 33.74 101.8 33.74 101.8 31.04 101.8 28.46 101.8 26.11

46.0 80.3 24.87 80.3 24.87 80.3 24.87 80.3 24.87 80.3 22.83 80.3 20.96 80.3 19.24

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 75.4 10.30 90.4 12.37 105.4 14.44 113.0 15.49 128.0 17.55 143.2 19.65 158.2 21.72

-5.0 75.4 10.30 90.4 12.37 105.4 14.47 113.0 15.52 128.0 17.59 143.2 19.68 158.2 21.75

0.0 75.4 10.34 90.4 12.40 105.4 14.50 113.0 15.55 128.0 17.65 143.2 19.75 158.2 21.81

5.0 75.4 10.37 90.4 12.47 105.4 14.56 113.0 15.61 128.0 17.74 143.2 19.88 158.2 21.94

10.0 75.4 10.40 90.4 12.56 105.4 14.69 113.0 15.77 128.0 17.97 143.2 20.10 158.2 22.20

15.0 75.4 10.56 90.4 12.75 105.4 15.01 113.0 16.12 128.0 18.38 143.2 20.64 158.2 22.71

100% 20.0 75.4 11.00 90.4 13.39 105.4 15.84 113.0 17.08 128.0 20.29 143.2 23.91 158.2 27.86

25.0 75.4 12.94 90.4 16.12 105.4 19.65 113.0 21.56 128.0 25.57 143.2 29.92 158.2 34.60

30.0 75.4 16.06 90.4 19.94 105.4 24.20 113.0 26.46 128.0 31.23 143.2 36.38 157.2 41.34

35.0 75.4 19.37 90.4 24.01 105.4 28.94 113.0 31.80 127.5 37.11 139.8 41.34 145.4 41.34

40.0 75.4 22.99 90.4 28.46 105.4 34.41 113.0 37.52 123.7 41.21 123.7 37.87 123.7 34.73

43.0 75.4 25.31 90.4 31.35 101.8 35.55 101.8 34.09 101.8 31.32 101.8 28.78 101.8 26.36

9 46.0 75.4 27.76 80.3 28.37 80.3 26.11 80.3 25.06 80.3 23.02 80.3 21.15 80.3 19.40
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


40 HP (U-8MF2E8 & U-16MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 67.8 9.25 81.4 11.13 94.9 13.01 101.7 13.93 115.3 15.80 128.8 17.68 142.4 19.53

-5.0 67.8 9.29 81.4 11.13 94.9 13.01 101.7 13.93 115.3 15.80 128.8 17.71 142.4 19.59

0.0 67.8 9.29 81.4 11.16 94.9 13.04 101.7 13.96 115.3 15.87 128.8 17.74 142.4 19.65

5.0 67.8 9.32 81.4 11.19 94.9 13.07 101.7 14.02 115.3 15.93 128.8 17.84 142.4 19.78

10.0 67.8 9.35 81.4 11.26 94.9 13.17 101.7 14.15 115.3 16.09 128.8 18.03 142.4 20.00

15.0 67.8 9.44 81.4 11.42 94.9 13.39 101.7 14.41 115.3 16.41 128.8 18.44 142.4 20.48

90% 20.0 67.8 9.79 81.4 11.89 94.9 14.02 101.7 15.11 115.3 17.27 128.8 19.88 142.4 22.96

25.0 67.8 11.29 81.4 13.93 94.9 16.79 101.7 18.35 115.3 21.59 128.8 25.09 142.4 28.84

30.0 67.8 14.06 81.4 17.27 94.9 20.80 101.7 22.64 115.3 26.52 128.8 30.69 142.4 35.14

35.0 67.8 16.98 81.4 20.89 94.9 25.06 101.7 27.25 115.3 31.86 128.8 36.79 141.1 41.34

40.0 67.8 20.16 81.4 24.77 94.9 29.70 101.7 32.31 115.3 37.75 123.7 40.07 123.7 36.79

43.0 67.8 22.20 81.4 27.28 94.9 32.72 101.7 35.58 101.8 32.82 101.8 30.15 101.8 27.67

46.0 67.8 24.36 80.3 29.38 80.3 27.06 80.3 25.95 80.3 23.88 80.3 21.94 80.3 20.13

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 60.2 8.24 72.3 9.89 84.4 11.54 90.4 12.37 102.5 14.02 114.5 15.71 126.6 17.36

-5.0 60.2 8.24 72.3 9.89 84.4 11.54 90.4 12.40 102.5 14.06 114.5 15.71 126.6 17.39

0.0 60.2 8.24 72.3 9.92 84.4 11.58 90.4 12.40 102.5 14.09 114.5 15.74 126.6 17.43

5.0 60.2 8.27 72.3 9.92 84.4 11.61 90.4 12.47 102.5 14.12 114.5 15.84 126.6 17.52

10.0 60.2 8.30 72.3 9.99 84.4 11.67 90.4 12.53 102.5 14.25 114.5 15.96 126.6 17.68

15.0 60.2 8.36 72.3 10.11 84.4 11.83 90.4 12.72 102.5 14.47 114.5 16.25 126.6 18.03

80% 20.0 60.2 8.62 72.3 10.43 84.4 12.27 90.4 13.23 102.5 15.11 114.5 16.98 126.6 18.89

25.0 60.2 9.70 72.3 11.89 84.4 14.21 90.4 15.42 102.5 18.00 114.5 20.77 126.6 23.69

30.0 60.2 12.18 72.3 14.82 84.4 17.65 90.4 19.14 102.5 22.29 114.5 25.60 126.6 29.10

35.0 60.2 14.76 72.3 17.94 84.4 21.37 90.4 23.15 102.5 26.87 114.5 30.78 126.6 34.95

40.0 60.2 17.52 72.3 21.34 84.4 25.38 90.4 27.48 102.5 31.86 114.5 36.51 123.7 39.46

43.0 60.2 19.30 72.3 23.50 84.4 27.95 90.4 30.27 101.8 34.73 101.8 31.93 101.8 29.32

46.0 60.2 21.15 72.3 25.79 80.3 28.27 80.3 27.16 80.3 24.96 80.3 22.96 80.3 21.08

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 52.8 7.22 63.3 8.65 73.8 10.11 79.1 10.81 89.6 12.27 100.2 13.74 110.7 15.17

-5.0 52.8 7.22 63.3 8.65 73.8 10.11 79.1 10.84 89.6 12.27 100.2 13.74 110.7 15.20

0.0 52.8 7.22 63.3 8.68 73.8 10.11 79.1 10.84 89.6 12.31 100.2 13.77 110.7 15.23

5.0 52.8 7.22 63.3 8.68 73.8 10.14 79.1 10.88 89.6 12.34 100.2 13.80 110.7 15.30

10.0 52.8 7.25 63.3 8.71 73.8 10.21 79.1 10.94 89.6 12.40 100.2 13.90 110.7 15.39

15.0 52.8 7.31 63.3 8.81 73.8 10.30 79.1 11.07 89.6 12.56 100.2 14.09 110.7 15.65

70% 20.0 52.8 7.47 63.3 9.03 73.8 10.62 79.1 11.42 89.6 13.01 100.2 14.60 110.7 16.22

25.0 52.8 8.20 63.3 10.02 73.8 11.86 79.1 12.82 89.6 14.79 100.2 16.92 110.7 19.14

30.0 52.8 10.43 63.3 12.56 73.8 14.82 79.1 16.00 89.6 18.44 100.2 20.99 110.7 23.69

35.0 52.8 12.66 63.3 15.23 73.8 17.97 79.1 19.37 89.6 22.29 100.2 25.38 110.7 28.59

40.0 52.8 15.01 63.3 18.13 73.8 21.37 79.1 23.06 89.6 26.52 100.2 30.15 110.7 33.96

43.0 52.8 16.54 63.3 19.97 73.8 23.56 79.1 25.41 89.6 29.26 100.2 33.29 101.8 31.61

46.0 52.8 18.13 63.3 21.91 73.8 25.89 79.1 27.92 80.3 26.46 80.3 24.33 80.3 22.36

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 45.2 6.17 54.2 7.41 63.3 8.65 67.8 9.29 76.8 10.53 85.9 11.77 94.9 13.01

-5.0 45.2 6.17 54.2 7.41 63.3 8.65 67.8 9.29 76.8 10.53 85.9 11.77 94.9 13.01

0.0 45.2 6.17 54.2 7.41 63.3 8.68 67.8 9.29 76.8 10.53 85.9 11.80 94.9 13.04

5.0 45.2 6.20 54.2 7.44 63.3 8.68 67.8 9.32 76.8 10.56 85.9 11.83 94.9 13.07

10.0 45.2 6.20 54.2 7.47 63.3 8.71 67.8 9.35 76.8 10.62 85.9 11.86 94.9 13.13

15.0 45.2 6.23 54.2 7.50 63.3 8.78 67.8 9.41 76.8 10.72 85.9 11.99 94.9 13.29

60% 20.0 45.2 6.33 54.2 7.66 63.3 8.97 67.8 9.64 76.8 11.00 85.9 12.34 94.9 13.67

25.0 45.2 6.81 54.2 8.30 63.3 9.76 67.8 10.53 76.8 11.99 85.9 13.52 94.9 15.14

30.0 45.2 8.81 54.2 10.49 63.3 12.21 67.8 13.10 76.8 14.98 85.9 16.89 94.9 18.92

35.0 45.2 10.68 54.2 12.72 63.3 14.85 67.8 15.96 76.8 18.19 85.9 20.51 94.9 22.93

40.0 45.2 12.69 54.2 15.14 63.3 17.68 67.8 18.98 76.8 21.69 85.9 24.45 94.9 27.32

43.0 45.2 13.96 54.2 16.70 63.3 19.49 67.8 20.96 76.8 23.91 85.9 27.00 94.9 30.18

46.0 45.2 15.30 54.2 18.32 63.3 21.43 67.8 23.02 76.8 26.30 80.3 26.27 80.3 24.17

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


40 HP (U-8MF2E8 & U-16MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 37.6 5.15 45.2 6.17 52.8 7.22 56.5 7.73 64.1 8.78 71.5 9.79 79.1 10.84

-5.0 37.6 5.15 45.2 6.17 52.8 7.22 56.5 7.73 64.1 8.78 71.5 9.79 79.1 10.84

0.0 37.6 5.15 45.2 6.20 52.8 7.22 56.5 7.73 64.1 8.78 71.5 9.83 79.1 10.84

5.0 37.6 5.15 45.2 6.20 52.8 7.22 56.5 7.76 64.1 8.78 71.5 9.83 79.1 10.88

10.0 37.6 5.15 45.2 6.20 52.8 7.25 56.5 7.76 64.1 8.81 71.5 9.86 79.1 10.91

15.0 37.6 5.18 45.2 6.23 52.8 7.28 56.5 7.82 64.1 8.87 71.5 9.95 79.1 11.00

50% 20.0 37.6 5.25 45.2 6.33 52.8 7.41 56.5 7.95 64.1 9.03 71.5 10.14 79.1 11.23

25.0 37.6 5.53 45.2 6.71 52.8 7.89 56.5 8.46 64.1 9.64 71.5 10.81 79.1 11.99

30.0 37.6 7.35 45.2 8.59 52.8 9.89 56.5 10.53 64.1 11.89 71.5 13.29 79.1 14.72

35.0 37.6 8.87 45.2 10.43 52.8 12.02 56.5 12.85 64.1 14.50 71.5 16.22 79.1 17.94

40.0 37.6 10.49 45.2 12.40 52.8 14.31 56.5 15.30 64.1 17.30 71.5 19.33 79.1 21.43

43.0 37.6 11.54 45.2 13.64 52.8 15.80 56.5 16.89 64.1 19.11 71.5 21.37 79.1 23.69

46.0 37.6 12.62 45.2 14.98 52.8 17.33 56.5 18.54 64.1 20.99 71.5 23.53 79.1 26.11

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 30.2 4.10 36.2 4.93 42.1 5.76 45.2 6.17 51.2 7.00 57.3 7.82 63.3 8.65

-5.0 30.2 4.10 36.2 4.93 42.1 5.76 45.2 6.17 51.2 7.00 57.3 7.85 63.3 8.68

0.0 30.2 4.13 36.2 4.96 42.1 5.79 45.2 6.20 51.2 7.03 57.3 7.85 63.3 8.68

5.0 30.2 4.13 36.2 4.96 42.1 5.79 45.2 6.20 51.2 7.03 57.3 7.85 63.3 8.68

10.0 30.2 4.13 36.2 4.96 42.1 5.79 45.2 6.20 51.2 7.03 57.3 7.89 63.3 8.71

15.0 30.2 4.13 36.2 4.99 42.1 5.82 45.2 6.23 51.2 7.06 57.3 7.92 63.3 8.75

40% 20.0 30.2 4.17 36.2 5.02 42.1 5.88 45.2 6.30 51.2 7.16 57.3 8.01 63.3 8.87

25.0 30.2 4.32 36.2 5.22 42.1 6.11 45.2 6.58 51.2 7.47 57.3 8.36 63.3 9.29

30.0 30.2 5.98 36.2 6.90 42.1 7.79 45.2 8.24 51.2 9.19 57.3 10.11 63.3 11.07

35.0 30.2 7.19 36.2 8.33 42.1 9.48 45.2 10.05 51.2 11.23 57.3 12.40 63.3 13.58

40.0 30.2 8.49 36.2 9.86 42.1 11.26 45.2 11.96 51.2 13.39 57.3 14.82 63.3 16.25

43.0 30.2 9.29 36.2 10.84 42.1 12.40 45.2 13.20 51.2 14.76 57.3 16.35 63.3 17.97

46.0 30.2 10.14 36.2 11.86 42.1 13.61 45.2 14.47 51.2 16.22 57.3 18.00 63.3 19.78

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 22.6 3.08 27.1 3.72 31.6 4.32 33.9 4.64 38.4 5.25 42.9 5.88 47.5 6.49

-5.0 22.6 3.08 27.1 3.72 31.6 4.32 33.9 4.64 38.4 5.25 42.9 5.88 47.5 6.49

0.0 22.6 3.08 27.1 3.72 31.6 4.32 33.9 4.64 38.4 5.25 42.9 5.88 47.5 6.49

5.0 22.6 3.08 27.1 3.72 31.6 4.32 33.9 4.64 38.4 5.28 42.9 5.88 47.5 6.52

10.0 22.6 3.08 27.1 3.72 31.6 4.32 33.9 4.64 38.4 5.28 42.9 5.88 47.5 6.52

15.0 22.6 3.12 27.1 3.72 31.6 4.36 33.9 4.67 38.4 5.28 42.9 5.91 47.5 6.55
30% 20.0 22.6 3.12 27.1 3.75 31.6 4.39 33.9 4.71 38.4 5.34 42.9 5.95 47.5 6.58

25.0 22.6 3.18 27.1 3.85 31.6 4.48 33.9 4.80 38.4 5.47 42.9 6.11 47.5 6.77

30.0 22.6 4.13 27.1 4.83 31.6 5.47 33.9 5.82 38.4 6.46 42.9 7.09 47.5 7.73

35.0 22.6 5.66 27.1 6.42 31.6 7.19 33.9 7.54 38.4 8.30 42.9 9.06 47.5 9.79

40.0 22.6 6.58 27.1 7.54 31.6 8.49 33.9 8.94 38.4 9.89 42.9 10.81 47.5 11.73

43.0 22.6 7.19 27.1 8.27 31.6 9.32 33.9 9.83 38.4 10.88 42.9 11.93 47.5 12.94

46.0 22.6 7.82 27.1 9.00 31.6 10.18 33.9 10.78 38.4 11.93 42.9 13.10 47.5 14.25

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


42 HP (U-14MF2E8 & U-14MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 110.0 15.63 126.9 18.10 126.9 18.10 126.9 18.10 143.7 20.54 160.7 22.95 177.6 25.36

-5.0 110.0 15.66 126.9 18.14 126.9 18.14 126.9 18.14 143.7 20.58 160.7 22.98 177.6 25.43

0.0 110.0 15.66 126.9 18.20 126.9 18.20 126.9 18.20 143.7 20.65 160.7 23.09 177.6 25.49

5.0 110.0 15.70 126.9 18.31 126.9 18.31 126.9 18.31 143.7 20.78 160.7 23.22 177.6 25.66

10.0 110.0 15.80 126.9 18.51 126.9 18.51 126.9 18.51 143.7 21.05 160.7 23.49 177.6 25.93

15.0 110.0 16.00 126.9 18.95 126.9 18.95 126.9 18.95 143.7 21.63 160.7 24.07 177.6 26.48

130% 20.0 110.0 16.54 126.9 20.31 126.9 20.31 126.9 20.31 143.7 24.34 160.7 28.71 177.6 33.46

25.0 110.0 19.32 126.9 25.70 126.9 25.70 126.9 25.70 143.7 30.51 160.7 35.76 177.6 41.39

30.0 110.0 24.07 126.9 31.43 126.9 31.43 126.9 31.43 143.7 37.15 160.7 43.36 168.2 44.07

35.0 110.0 29.15 126.9 37.66 126.9 37.66 126.9 37.66 143.0 44.07 149.2 44.07 155.3 44.07

40.0 110.0 34.65 126.1 44.07 126.1 44.07 126.1 44.07 130.0 42.95 130.0 39.43 130.0 36.14

43.0 107.0 35.90 107.0 35.90 107.0 35.90 107.0 35.90 107.0 32.98 107.0 30.27 107.0 27.76

46.0 84.5 26.65 84.5 26.65 84.5 26.65 84.5 26.65 84.5 24.48 84.5 22.51 84.5 20.65

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 99.1 14.10 118.9 16.92 123.9 17.66 123.9 17.66 140.4 20.03 156.9 22.41 173.5 24.78

-5.0 99.1 14.10 118.9 16.95 123.9 17.70 123.9 17.70 140.4 20.10 156.9 22.48 173.5 24.81

0.0 99.1 14.14 118.9 16.98 123.9 17.76 123.9 17.76 140.4 20.17 156.9 22.54 173.5 24.92

5.0 99.1 14.17 118.9 17.05 123.9 17.87 123.9 17.87 140.4 20.31 156.9 22.68 173.5 25.05

10.0 99.1 14.24 118.9 17.15 123.9 18.03 123.9 18.03 140.4 20.54 156.9 22.95 173.5 25.32

15.0 99.1 14.44 118.9 17.42 123.9 18.48 123.9 18.48 140.4 21.05 156.9 23.49 173.5 25.87

120% 20.0 99.1 14.95 118.9 18.17 123.9 19.59 123.9 19.59 140.4 23.36 156.9 27.49 173.5 32.00

25.0 99.1 17.42 118.9 21.83 123.9 24.75 123.9 24.75 140.4 29.36 156.9 34.34 173.5 39.70

30.0 99.1 21.70 118.9 27.05 123.9 30.31 123.9 30.31 140.4 35.80 156.9 41.66 167.1 44.07

35.0 99.1 26.24 118.9 32.65 123.9 36.34 123.9 36.34 140.4 42.82 148.2 44.07 154.3 44.07

40.0 99.1 31.19 118.9 38.71 123.9 43.02 123.9 43.02 130.0 43.43 130.0 39.87 130.0 36.54

43.0 99.1 34.37 107.0 36.21 107.0 36.21 107.0 36.21 107.0 33.29 107.0 30.54 107.0 28.00

46.0 84.5 26.81 84.5 26.81 84.5 26.81 84.5 26.81 84.5 24.68 84.5 22.65 84.5 20.78

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 88.7 12.61 106.4 15.15 121.0 17.26 121.0 17.26 137.1 19.56 153.2 21.90 169.3 24.17

-5.0 88.7 12.64 106.4 15.19 121.0 17.29 121.0 17.29 137.1 19.59 153.2 21.93 169.3 24.24

0.0 88.7 12.64 106.4 15.19 121.0 17.32 121.0 17.32 137.1 19.66 153.2 22.00 169.3 24.31

5.0 88.7 12.68 106.4 15.26 121.0 17.42 121.0 17.42 137.1 19.80 153.2 22.14 169.3 24.44

10.0 88.7 12.75 106.4 15.36 121.0 17.59 121.0 17.59 137.1 20.03 153.2 22.41 169.3 24.71

15.0 88.7 12.92 106.4 15.63 121.0 18.00 121.0 18.00 137.1 20.51 153.2 22.95 169.3 25.29

110% 20.0 88.7 13.42 106.4 16.34 121.0 19.02 121.0 19.02 137.1 22.37 153.2 26.34 169.3 30.61

25.0 88.7 15.63 106.4 19.49 121.0 23.83 121.0 23.83 137.1 28.20 153.2 32.95 169.3 38.04

30.0 88.7 19.42 106.4 24.14 121.0 29.22 121.0 29.22 137.1 34.44 153.2 40.04 166.0 44.07

35.0 88.7 23.49 106.4 29.12 121.0 35.09 121.0 35.09 137.1 41.26 147.3 44.07 153.4 44.07

40.0 88.7 27.90 106.4 34.51 121.0 41.49 121.0 41.49 130.0 43.90 130.0 40.34 130.0 36.98

43.0 88.7 30.71 106.4 38.00 107.0 36.54 107.0 36.54 107.0 33.59 107.0 30.85 107.0 28.27

46.0 84.5 27.02 84.5 27.02 84.5 27.02 84.5 27.02 84.5 24.85 84.5 22.81 84.5 20.95

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 78.7 11.19 94.4 13.46 110.1 15.70 118.0 16.81 133.7 19.09 149.5 21.36 165.2 23.59

-5.0 78.7 11.19 94.4 13.46 110.1 15.73 118.0 16.85 133.7 19.12 149.5 21.39 165.2 23.66

0.0 78.7 11.22 94.4 13.49 110.1 15.76 118.0 16.92 133.7 19.19 149.5 21.46 165.2 23.73

5.0 78.7 11.25 94.4 13.53 110.1 15.83 118.0 16.98 133.7 19.29 149.5 21.59 165.2 23.87

10.0 78.7 11.32 94.4 13.63 110.1 15.97 118.0 17.15 133.7 19.53 149.5 21.87 165.2 24.14

15.0 78.7 11.49 94.4 13.87 110.1 16.31 118.0 17.53 133.7 19.97 149.5 22.41 165.2 24.68

100% 20.0 78.7 11.93 94.4 14.54 110.1 17.15 118.0 18.48 133.7 21.46 149.5 25.19 165.2 29.22

25.0 78.7 13.93 94.4 17.29 110.1 20.98 118.0 22.95 133.7 27.12 149.5 31.59 165.2 36.41

30.0 78.7 17.29 94.4 21.39 110.1 25.83 118.0 28.17 133.7 33.12 149.5 38.48 164.6 43.90

35.0 78.7 20.88 94.4 25.73 110.1 30.92 118.0 33.90 133.1 39.43 146.3 44.07 152.5 44.07

40.0 78.7 24.78 94.4 30.54 110.1 36.75 118.0 40.04 129.4 44.07 130.0 40.82 130.0 37.43

43.0 78.7 27.26 94.4 33.63 107.0 38.44 107.0 36.88 107.0 33.93 107.0 31.15 107.0 28.54

9 46.0 78.7 29.90 84.5 30.82 84.5 28.37 84.5 27.22 84.5 25.05 84.5 22.98 84.5 21.12
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


42 HP (U-14MF2E8 & U-14MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 70.8 10.07 85.0 12.10 99.1 14.14 106.2 15.15 120.4 17.19 134.5 19.22 148.7 21.26

-5.0 70.8 10.07 85.0 12.10 99.1 14.14 106.2 15.15 120.4 17.19 134.5 19.26 148.7 21.29

0.0 70.8 10.10 85.0 12.14 99.1 14.17 106.2 15.19 120.4 17.26 134.5 19.29 148.7 21.36

5.0 70.8 10.10 85.0 12.17 99.1 14.24 106.2 15.26 120.4 17.32 134.5 19.39 148.7 21.49

10.0 70.8 10.17 85.0 12.24 99.1 14.34 106.2 15.39 120.4 17.49 134.5 19.59 148.7 21.73

15.0 70.8 10.27 85.0 12.41 99.1 14.58 106.2 15.66 120.4 17.83 134.5 20.00 148.7 22.24

90% 20.0 70.8 10.64 85.0 12.92 99.1 15.22 106.2 16.37 120.4 18.71 134.5 21.05 148.7 24.10

25.0 70.8 12.20 85.0 14.95 99.1 17.93 106.2 19.53 120.4 22.92 134.5 26.51 148.7 30.37

30.0 70.8 15.15 85.0 18.54 99.1 22.20 106.2 24.14 120.4 28.17 134.5 32.48 148.7 37.05

35.0 70.8 18.34 85.0 22.41 99.1 26.78 106.2 29.09 120.4 33.87 134.5 38.99 148.0 44.07

40.0 70.8 21.76 85.0 26.61 99.1 31.76 106.2 34.48 120.4 40.17 130.0 43.09 130.0 39.56

43.0 70.8 23.93 85.0 29.29 99.1 34.98 106.2 38.00 107.0 35.46 107.0 32.58 107.0 29.90

46.0 70.8 26.27 84.5 31.87 84.5 29.36 84.5 28.17 84.5 25.93 84.5 23.83 84.5 21.87

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 62.9 8.95 75.5 10.75 88.1 12.54 94.4 13.46 107.0 15.26 119.5 17.05 132.2 18.88

-5.0 62.9 8.95 75.5 10.75 88.1 12.58 94.4 13.46 107.0 15.29 119.5 17.09 132.2 18.88

0.0 62.9 8.98 75.5 10.78 88.1 12.58 94.4 13.49 107.0 15.32 119.5 17.12 132.2 18.95

5.0 62.9 8.98 75.5 10.81 88.1 12.61 94.4 13.53 107.0 15.36 119.5 17.19 132.2 19.05

10.0 62.9 9.02 75.5 10.85 88.1 12.71 94.4 13.63 107.0 15.49 119.5 17.36 132.2 19.22

15.0 62.9 9.12 75.5 10.98 88.1 12.88 94.4 13.83 107.0 15.73 119.5 17.63 132.2 19.56

80% 20.0 62.9 9.36 75.5 11.32 88.1 13.32 94.4 14.34 107.0 16.34 119.5 18.37 132.2 20.44

25.0 62.9 10.44 75.5 12.78 88.1 15.19 94.4 16.48 107.0 19.12 119.5 21.97 132.2 24.95

30.0 62.9 13.15 75.5 15.93 88.1 18.92 94.4 20.44 107.0 23.70 119.5 27.09 132.2 30.68

35.0 62.9 15.93 75.5 19.29 88.1 22.85 94.4 24.71 107.0 28.58 119.5 32.65 132.2 36.92

40.0 62.9 18.92 75.5 22.92 88.1 27.15 94.4 29.36 107.0 33.93 119.5 38.75 130.0 42.34

43.0 62.9 20.81 75.5 25.26 88.1 29.93 94.4 32.34 107.0 37.43 107.0 34.44 107.0 31.63

46.0 62.9 22.81 75.5 27.73 84.5 30.65 84.5 29.43 84.5 27.09 84.5 24.88 84.5 22.85

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 55.1 7.83 66.1 9.39 77.1 10.98 82.6 11.76 93.6 13.36 104.7 14.92 115.6 16.51

-5.0 55.1 7.83 66.1 9.42 77.1 10.98 82.6 11.76 93.6 13.36 104.7 14.95 115.6 16.51

0.0 55.1 7.83 66.1 9.42 77.1 11.02 82.6 11.80 93.6 13.39 104.7 14.95 115.6 16.54

5.0 55.1 7.86 66.1 9.42 77.1 11.02 82.6 11.83 93.6 13.42 104.7 15.02 115.6 16.61

10.0 55.1 7.86 66.1 9.49 77.1 11.09 82.6 11.90 93.6 13.49 104.7 15.12 115.6 16.75

15.0 55.1 7.93 66.1 9.56 77.1 11.19 82.6 12.00 93.6 13.66 104.7 15.32 115.6 16.98

70% 20.0 55.1 8.10 66.1 9.80 77.1 11.49 82.6 12.37 93.6 14.10 104.7 15.83 115.6 17.56

25.0 55.1 8.85 66.1 10.78 77.1 12.71 82.6 13.70 93.6 15.73 104.7 17.90 115.6 20.17

30.0 55.1 11.32 66.1 13.53 77.1 15.87 82.6 17.09 93.6 19.63 104.7 22.27 115.6 25.02

35.0 55.1 13.70 66.1 16.41 77.1 19.26 82.6 20.71 93.6 23.76 104.7 26.92 115.6 30.20

40.0 55.1 16.24 66.1 19.49 77.1 22.88 82.6 24.65 93.6 28.27 104.7 32.04 115.6 35.93

43.0 55.1 17.90 66.1 21.49 77.1 25.26 82.6 27.19 93.6 31.19 104.7 35.36 107.0 34.00

46.0 55.1 19.59 66.1 23.59 77.1 27.73 82.6 29.90 84.5 28.61 84.5 26.34 84.5 24.20

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 47.2 6.71 56.6 8.07 66.1 9.42 70.8 10.07 80.2 11.42 89.7 12.78 99.1 14.14

-5.0 47.2 6.71 56.6 8.07 66.1 9.42 70.8 10.10 80.2 11.42 89.7 12.78 99.1 14.14

0.0 47.2 6.71 56.6 8.07 66.1 9.42 70.8 10.10 80.2 11.46 89.7 12.81 99.1 14.17

5.0 47.2 6.75 56.6 8.07 66.1 9.46 70.8 10.14 80.2 11.49 89.7 12.85 99.1 14.20

10.0 47.2 6.75 56.6 8.10 66.1 9.46 70.8 10.17 80.2 11.53 89.7 12.92 99.1 14.27

15.0 47.2 6.78 56.6 8.17 66.1 9.56 70.8 10.24 80.2 11.63 89.7 13.05 99.1 14.44

60% 20.0 47.2 6.88 56.6 8.31 66.1 9.76 70.8 10.48 80.2 11.93 89.7 13.36 99.1 14.81

25.0 47.2 7.36 56.6 8.95 66.1 10.51 70.8 11.32 80.2 12.88 89.7 14.48 99.1 16.00

30.0 47.2 9.59 56.6 11.32 66.1 13.12 70.8 14.07 80.2 15.97 89.7 17.93 99.1 20.00

35.0 47.2 11.59 56.6 13.73 66.1 15.97 70.8 17.09 80.2 19.42 89.7 21.80 99.1 24.27

40.0 47.2 13.76 56.6 16.34 66.1 18.98 70.8 20.34 80.2 23.12 89.7 26.00 99.1 28.95

43.0 47.2 15.12 56.6 18.00 66.1 20.95 70.8 22.44 80.2 25.53 89.7 28.71 99.1 32.00

46.0 47.2 16.58 56.6 19.73 66.1 22.98 70.8 24.68 80.2 28.10 84.5 28.34 84.5 26.07

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


42 HP (U-14MF2E8 & U-14MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 39.3 5.59 47.2 6.71 55.1 7.83 59.0 8.41 66.9 9.53 74.7 10.64 82.6 11.76

-5.0 39.3 5.59 47.2 6.71 55.1 7.83 59.0 8.41 66.9 9.53 74.7 10.64 82.6 11.80

0.0 39.3 5.59 47.2 6.71 55.1 7.86 59.0 8.41 66.9 9.53 74.7 10.68 82.6 11.80

5.0 39.3 5.59 47.2 6.75 55.1 7.86 59.0 8.41 66.9 9.56 74.7 10.68 82.6 11.83

10.0 39.3 5.63 47.2 6.75 55.1 7.86 59.0 8.44 66.9 9.59 74.7 10.71 82.6 11.87

15.0 39.3 5.63 47.2 6.78 55.1 7.93 59.0 8.51 66.9 9.66 74.7 10.81 82.6 11.97

50% 20.0 39.3 5.70 47.2 6.88 55.1 8.03 59.0 8.64 66.9 9.80 74.7 10.98 82.6 12.17

25.0 39.3 6.00 47.2 7.25 55.1 8.51 59.0 9.12 66.9 10.37 74.7 11.63 82.6 12.88

30.0 39.3 8.03 47.2 9.32 55.1 10.64 59.0 11.32 66.9 12.71 74.7 14.14 82.6 15.59

35.0 39.3 9.66 47.2 11.29 55.1 12.95 59.0 13.80 66.9 15.53 74.7 17.26 82.6 19.05

40.0 39.3 11.42 47.2 13.39 55.1 15.42 59.0 16.44 66.9 18.51 74.7 20.61 82.6 22.75

43.0 39.3 12.54 47.2 14.75 55.1 16.98 59.0 18.14 66.9 20.41 74.7 22.75 82.6 25.15

46.0 39.3 13.73 47.2 16.17 55.1 18.65 59.0 19.90 66.9 22.48 74.7 25.05 82.6 27.70

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 31.5 4.47 37.8 5.36 44.0 6.27 47.2 6.71 53.5 7.63 59.8 8.51 66.1 9.42

-5.0 31.5 4.47 37.8 5.39 44.0 6.27 47.2 6.71 53.5 7.63 59.8 8.51 66.1 9.42

0.0 31.5 4.47 37.8 5.39 44.0 6.27 47.2 6.71 53.5 7.63 59.8 8.54 66.1 9.42

5.0 31.5 4.47 37.8 5.39 44.0 6.27 47.2 6.75 53.5 7.63 59.8 8.54 66.1 9.46

10.0 31.5 4.47 37.8 5.39 44.0 6.31 47.2 6.75 53.5 7.66 59.8 8.54 66.1 9.46

15.0 31.5 4.51 37.8 5.42 44.0 6.31 47.2 6.78 53.5 7.70 59.8 8.61 66.1 9.53

40% 20.0 31.5 4.54 37.8 5.46 44.0 6.37 47.2 6.85 53.5 7.76 59.8 8.71 66.1 9.63

25.0 31.5 4.68 37.8 5.66 44.0 6.61 47.2 7.12 53.5 8.07 59.8 9.05 66.1 10.00

30.0 31.5 6.58 37.8 7.49 44.0 8.44 47.2 8.92 53.5 9.86 59.8 10.81 66.1 11.80

35.0 31.5 7.86 37.8 9.05 44.0 10.24 47.2 10.85 53.5 12.03 59.8 13.25 66.1 14.44

40.0 31.5 9.25 37.8 10.71 44.0 12.17 47.2 12.88 53.5 14.34 59.8 15.83 66.1 17.29

43.0 31.5 10.14 37.8 11.76 44.0 13.39 47.2 14.20 53.5 15.83 59.8 17.46 66.1 19.12

46.0 31.5 11.05 37.8 12.85 44.0 14.68 47.2 15.56 53.5 17.39 59.8 19.22 66.1 21.05

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 23.6 3.36 28.3 4.03 33.0 4.71 35.4 5.05 40.1 5.70 44.8 6.37 49.6 7.05

-5.0 23.6 3.36 28.3 4.03 33.0 4.71 35.4 5.05 40.1 5.73 44.8 6.37 49.6 7.05

0.0 23.6 3.36 28.3 4.03 33.0 4.71 35.4 5.05 40.1 5.73 44.8 6.41 49.6 7.05

5.0 23.6 3.36 28.3 4.03 33.0 4.71 35.4 5.05 40.1 5.73 44.8 6.41 49.6 7.09

10.0 23.6 3.36 28.3 4.03 33.0 4.71 35.4 5.05 40.1 5.73 44.8 6.41 49.6 7.09

15.0 23.6 3.39 28.3 4.03 33.0 4.71 35.4 5.05 40.1 5.76 44.8 6.44 49.6 7.12
30% 20.0 23.6 3.39 28.3 4.07 33.0 4.75 35.4 5.09 40.1 5.80 44.8 6.47 49.6 7.15

25.0 23.6 3.46 28.3 4.17 33.0 4.85 35.4 5.22 40.1 5.93 44.8 6.61 49.6 7.32

30.0 23.6 4.31 28.3 5.02 33.0 5.73 35.4 6.07 40.1 6.75 44.8 7.46 49.6 8.14

35.0 23.6 6.20 28.3 7.02 33.0 7.80 35.4 8.20 40.1 8.98 44.8 9.73 49.6 10.48

40.0 23.6 7.25 28.3 8.24 33.0 9.22 35.4 9.70 40.1 10.64 44.8 11.59 49.6 12.54

43.0 23.6 7.90 28.3 8.98 33.0 10.10 35.4 10.64 40.1 11.73 44.8 12.78 49.6 13.83

46.0 23.6 8.54 28.3 9.80 33.0 11.02 35.4 11.63 40.1 12.85 44.8 14.03 49.6 15.22

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


44 HP (U-14MF2E8 & U-14MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 115.6 15.96 133.3 18.45 133.3 18.45 133.3 18.45 151.0 20.94 168.9 23.43 186.6 25.88

-5.0 115.6 15.96 133.3 18.52 133.3 18.52 133.3 18.52 151.0 21.01 168.9 23.47 186.6 25.96

0.0 115.6 15.99 133.3 18.56 133.3 18.56 133.3 18.56 151.0 21.08 168.9 23.57 186.6 26.03

5.0 115.6 16.03 133.3 18.70 133.3 18.70 133.3 18.70 151.0 21.26 168.9 23.72 186.6 26.21

10.0 115.6 16.14 133.3 18.92 133.3 18.92 133.3 18.92 151.0 21.55 168.9 24.04 186.6 26.53

15.0 115.6 16.35 133.3 19.46 133.3 19.46 133.3 19.46 151.0 22.27 168.9 24.76 186.6 28.92

130% 20.0 115.6 17.04 133.3 21.91 133.3 21.91 133.3 21.91 151.0 26.43 168.9 31.37 186.6 36.75

25.0 115.6 20.40 133.3 27.54 133.3 27.54 133.3 27.54 151.0 32.92 168.9 38.81 186.6 45.16

30.0 115.6 25.34 133.3 33.57 133.3 33.57 133.3 33.57 151.0 39.93 168.3 46.57 175.5 46.93

35.0 115.6 30.65 133.3 40.14 133.3 40.14 133.3 40.14 149.9 46.93 156.1 46.93 162.4 46.93

40.0 115.6 36.35 132.4 46.75 132.4 46.75 132.4 46.75 132.4 42.96 132.4 39.46 132.4 36.17

43.0 109.0 35.81 109.0 35.81 109.0 35.81 109.0 35.81 109.0 32.92 109.0 30.22 109.0 27.69

46.0 86.1 26.53 86.1 26.53 86.1 26.53 86.1 26.53 86.1 24.40 86.1 22.38 86.1 20.54

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 104.2 14.37 125.0 17.26 130.2 18.05 130.2 18.05 147.6 20.47 164.9 22.89 182.3 25.27

-5.0 104.2 14.40 125.0 17.29 130.2 18.09 130.2 18.09 147.6 20.50 164.9 22.92 182.3 25.34

0.0 104.2 14.40 125.0 17.33 130.2 18.12 130.2 18.12 147.6 20.58 164.9 23.03 182.3 25.45

5.0 104.2 14.48 125.0 17.40 130.2 18.23 130.2 18.23 147.6 20.76 164.9 23.18 182.3 25.59

10.0 104.2 14.55 125.0 17.54 130.2 18.48 130.2 18.48 147.6 21.05 164.9 23.50 182.3 25.92

15.0 104.2 14.76 125.0 17.83 130.2 18.99 130.2 18.99 147.6 21.70 164.9 24.19 182.3 27.58

120% 20.0 104.2 15.41 125.0 18.77 130.2 21.08 130.2 21.08 147.6 25.34 164.9 30.04 182.3 35.16

25.0 104.2 18.37 125.0 23.21 130.2 26.53 130.2 26.53 147.6 31.66 164.9 37.26 182.3 43.28

30.0 104.2 22.82 125.0 28.63 130.2 32.38 130.2 32.38 147.6 38.45 164.9 45.02 174.2 46.93

35.0 104.2 27.54 125.0 34.48 130.2 38.74 130.2 38.74 147.6 45.88 155.1 46.93 161.4 46.93

40.0 104.2 32.71 125.0 40.83 130.2 45.74 130.2 45.74 132.4 43.46 132.4 39.89 132.4 36.61

43.0 104.2 35.99 109.0 36.14 109.0 36.14 109.0 36.14 109.0 33.21 109.0 30.50 109.0 27.98

46.0 86.1 26.71 86.1 26.71 86.1 26.71 86.1 26.71 86.1 24.55 86.1 22.56 86.1 20.72

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 93.2 12.85 111.8 15.45 127.1 17.62 127.1 17.62 144.1 19.96 161.0 22.35 177.9 24.69

-5.0 93.2 12.89 111.8 15.49 127.1 17.62 127.1 17.62 144.1 20.00 161.0 22.38 177.9 24.73

0.0 93.2 12.89 111.8 15.52 127.1 17.69 127.1 17.69 144.1 20.11 161.0 22.49 177.9 24.84

5.0 93.2 12.96 111.8 15.56 127.1 17.80 127.1 17.80 144.1 20.22 161.0 22.63 177.9 25.02

10.0 93.2 13.03 111.8 15.70 127.1 18.01 127.1 18.01 144.1 20.50 161.0 22.96 177.9 25.31

15.0 93.2 13.21 111.8 15.99 127.1 18.48 127.1 18.48 144.1 21.12 161.0 23.61 177.9 25.99

110% 20.0 93.2 13.83 111.8 16.86 127.1 20.25 127.1 20.25 144.1 24.30 161.0 28.77 177.9 33.61

25.0 93.2 16.46 111.8 20.69 127.1 25.56 127.1 25.56 144.1 30.43 161.0 35.74 177.9 41.48

30.0 93.2 20.43 111.8 25.52 127.1 31.23 127.1 31.23 144.1 37.00 161.0 43.25 173.1 46.93

35.0 93.2 24.66 111.8 30.72 127.1 37.36 127.1 37.36 144.1 44.19 154.1 46.93 160.3 46.93

40.0 93.2 29.20 111.8 36.39 127.1 44.11 127.1 44.11 132.4 43.97 132.4 40.36 132.4 37.04

43.0 93.2 32.17 109.0 36.50 109.0 36.50 109.0 36.50 109.0 33.54 109.0 30.79 109.0 28.23

46.0 86.1 26.93 86.1 26.93 86.1 26.93 86.1 26.93 86.1 24.73 86.1 22.74 86.1 20.87

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 82.7 11.41 99.2 13.72 115.7 16.03 124.0 17.18 140.5 19.49 157.1 21.77 173.6 24.08

-5.0 82.7 11.44 99.2 13.72 115.7 16.03 124.0 17.18 140.5 19.53 157.1 21.84 173.6 24.15

0.0 82.7 11.44 99.2 13.75 115.7 16.10 124.0 17.26 140.5 19.60 157.1 21.91 173.6 24.22

5.0 82.7 11.48 99.2 13.83 115.7 16.17 124.0 17.36 140.5 19.71 157.1 22.09 173.6 24.40

10.0 82.7 11.55 99.2 13.93 115.7 16.35 124.0 17.54 140.5 19.96 157.1 22.38 173.6 24.69

15.0 82.7 11.77 99.2 14.22 115.7 16.71 124.0 17.98 140.5 20.54 157.1 23.07 173.6 25.38

100% 20.0 82.7 12.31 99.2 15.02 115.7 17.80 124.0 19.46 140.5 23.28 157.1 27.51 173.6 32.09

25.0 82.7 14.66 99.2 18.34 115.7 22.42 124.0 24.58 140.5 29.24 157.1 34.26 173.6 39.71

30.0 82.7 18.16 99.2 22.60 115.7 27.47 124.0 30.07 140.5 35.59 157.1 41.52 171.9 46.93

35.0 82.7 21.88 99.2 27.15 115.7 32.78 124.0 36.10 139.9 42.20 153.1 46.93 159.2 46.93

40.0 82.7 25.92 99.2 32.17 115.7 38.95 124.0 42.56 132.4 44.48 132.4 40.87 132.4 37.51

43.0 82.7 28.52 99.2 35.38 109.0 38.41 109.0 36.86 109.0 33.86 109.0 31.12 109.0 28.52

9 46.0 82.7 31.30 86.1 30.69 86.1 28.27 86.1 27.11 86.1 24.95 86.1 22.92 86.1 21.05
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


44 HP (U-14MF2E8 & U-14MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 74.4 10.29 89.3 12.35 104.2 14.40 111.6 15.45 126.5 17.51 141.4 19.60 156.2 21.66

-5.0 74.4 10.29 89.3 12.35 104.2 14.44 111.6 15.45 126.5 17.54 141.4 19.64 156.2 21.73

0.0 74.4 10.29 89.3 12.38 104.2 14.48 111.6 15.52 126.5 17.62 141.4 19.71 156.2 21.80

5.0 74.4 10.32 89.3 12.42 104.2 14.51 111.6 15.60 126.5 17.69 141.4 19.82 156.2 21.95

10.0 74.4 10.40 89.3 12.49 104.2 14.66 111.6 15.74 126.5 17.91 141.4 20.07 156.2 22.24

15.0 74.4 10.51 89.3 12.71 104.2 14.95 111.6 16.06 126.5 18.30 141.4 20.58 156.2 22.85

90% 20.0 74.4 10.94 89.3 13.32 104.2 15.74 111.6 16.97 126.5 19.49 141.4 22.85 156.2 26.50

25.0 74.4 12.82 89.3 15.81 104.2 19.13 111.6 20.90 126.5 24.69 141.4 28.74 156.2 33.07

30.0 74.4 15.88 89.3 19.60 104.2 23.61 111.6 25.74 126.5 30.22 141.4 35.05 156.2 40.18

35.0 74.4 19.17 89.3 23.61 104.2 28.37 111.6 30.90 126.5 36.21 141.4 41.91 154.5 46.93

40.0 74.4 22.74 89.3 27.98 104.2 33.61 111.6 36.57 126.5 42.85 132.4 43.21 132.4 39.67

43.0 74.4 25.02 89.3 30.79 104.2 37.00 109.0 38.52 109.0 35.45 109.0 32.56 109.0 29.89

46.0 74.4 27.44 86.1 31.77 86.1 29.28 86.1 28.12 86.1 25.85 86.1 23.75 86.1 21.80

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 66.1 9.13 79.4 10.97 92.6 12.82 99.2 13.72 112.5 15.56 125.6 17.40 138.9 19.24

-5.0 66.1 9.13 79.4 10.97 92.6 12.82 99.2 13.75 112.5 15.60 125.6 17.44 138.9 19.28

0.0 66.1 9.13 79.4 10.97 92.6 12.85 99.2 13.75 112.5 15.63 125.6 17.47 138.9 19.35

5.0 66.1 9.17 79.4 11.01 92.6 12.89 99.2 13.83 112.5 15.70 125.6 17.58 138.9 19.46

10.0 66.1 9.21 79.4 11.08 92.6 12.96 99.2 13.93 112.5 15.81 125.6 17.73 138.9 19.67

15.0 66.1 9.31 79.4 11.23 92.6 13.18 99.2 14.15 112.5 16.14 125.6 18.12 138.9 20.11

80% 20.0 66.1 9.60 79.4 11.66 92.6 13.75 99.2 14.80 112.5 16.93 125.6 19.10 138.9 21.52

25.0 66.1 11.01 79.4 13.50 92.6 16.17 99.2 17.58 112.5 20.58 125.6 23.75 138.9 27.18

30.0 66.1 13.75 79.4 16.79 92.6 20.04 99.2 21.77 112.5 25.34 125.6 29.17 138.9 33.25

35.0 66.1 16.64 79.4 20.29 92.6 24.19 99.2 26.24 112.5 30.50 125.6 35.02 138.9 39.82

40.0 66.1 19.75 79.4 24.08 92.6 28.66 99.2 31.08 112.5 36.14 125.6 41.48 132.4 42.56

43.0 66.1 21.73 79.4 26.50 92.6 31.59 99.2 34.26 109.0 37.51 109.0 34.48 109.0 31.70

46.0 66.1 23.79 79.4 29.10 86.1 30.58 86.1 29.35 86.1 27.04 86.1 24.84 86.1 22.82

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 57.9 7.98 69.4 9.60 81.0 11.19 86.8 11.99 98.3 13.61 110.0 15.23 121.5 16.82

-5.0 57.9 7.98 69.4 9.60 81.0 11.19 86.8 12.02 98.3 13.61 110.0 15.23 121.5 16.86

0.0 57.9 8.01 69.4 9.60 81.0 11.23 86.8 12.02 98.3 13.65 110.0 15.27 121.5 16.89

5.0 57.9 8.01 69.4 9.64 81.0 11.26 86.8 12.06 98.3 13.68 110.0 15.34 121.5 16.97

10.0 57.9 8.05 69.4 9.67 81.0 11.30 86.8 12.13 98.3 13.79 110.0 15.45 121.5 17.11

15.0 57.9 8.12 69.4 9.78 81.0 11.44 86.8 12.31 98.3 14.01 110.0 15.70 121.5 17.44

70% 20.0 57.9 8.30 69.4 10.07 81.0 11.84 86.8 12.74 98.3 14.55 110.0 16.35 121.5 18.19

25.0 57.9 9.28 69.4 11.37 81.0 13.50 86.8 14.58 98.3 16.89 110.0 19.35 121.5 21.95

30.0 57.9 11.80 69.4 14.22 81.0 16.79 86.8 18.16 98.3 20.97 110.0 23.93 121.5 27.04

35.0 57.9 14.26 69.4 17.22 81.0 20.32 86.8 21.95 98.3 25.31 110.0 28.84 121.5 32.56

40.0 57.9 16.93 69.4 20.43 81.0 24.15 86.8 26.06 98.3 30.04 110.0 34.22 121.5 38.63

43.0 57.9 18.63 69.4 22.49 81.0 26.61 86.8 28.70 98.3 33.14 109.0 37.07 109.0 34.11

46.0 57.9 20.40 69.4 24.69 81.0 29.20 86.1 31.05 86.1 28.59 86.1 26.32 86.1 24.19

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 49.6 6.86 59.5 8.23 69.4 9.60 74.4 10.29 84.3 11.66 94.2 13.03 104.2 14.40

-5.0 49.6 6.86 59.5 8.23 69.4 9.60 74.4 10.29 84.3 11.66 94.2 13.07 104.2 14.44

0.0 49.6 6.86 59.5 8.23 69.4 9.60 74.4 10.29 84.3 11.70 94.2 13.07 104.2 14.48

5.0 49.6 6.86 59.5 8.23 69.4 9.64 74.4 10.32 84.3 11.73 94.2 13.10 104.2 14.51

10.0 49.6 6.90 59.5 8.27 69.4 9.67 74.4 10.36 84.3 11.77 94.2 13.18 104.2 14.62

15.0 49.6 6.93 59.5 8.34 69.4 9.75 74.4 10.47 84.3 11.91 94.2 13.36 104.2 14.80

60% 20.0 49.6 7.08 59.5 8.52 69.4 10.00 74.4 10.76 84.3 12.27 94.2 13.79 104.2 15.31

25.0 49.6 7.69 59.5 9.35 69.4 11.05 74.4 11.91 84.3 13.61 94.2 15.45 104.2 17.33

30.0 49.6 9.96 59.5 11.88 69.4 13.86 74.4 14.87 84.3 17.04 94.2 19.24 104.2 21.59

35.0 49.6 12.06 59.5 14.37 69.4 16.82 74.4 18.05 84.3 20.65 94.2 23.32 104.2 26.10

40.0 49.6 14.30 59.5 17.08 69.4 19.96 74.4 21.48 84.3 24.55 94.2 27.72 104.2 31.05

43.0 49.6 15.70 59.5 18.81 69.4 22.02 74.4 23.68 84.3 27.08 94.2 30.58 104.2 34.26

46.0 49.6 17.22 59.5 20.61 69.4 24.15 74.4 25.99 84.3 29.75 86.1 28.41 86.1 26.14

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


44 HP (U-14MF2E8 & U-14MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 41.3 5.70 49.6 6.86 57.9 7.98 62.0 8.56 70.3 9.71 78.5 10.87 86.8 12.02

-5.0 41.3 5.70 49.6 6.86 57.9 8.01 62.0 8.56 70.3 9.71 78.5 10.87 86.8 12.02

0.0 41.3 5.70 49.6 6.86 57.9 8.01 62.0 8.59 70.3 9.75 78.5 10.90 86.8 12.02

5.0 41.3 5.70 49.6 6.86 57.9 8.01 62.0 8.59 70.3 9.75 78.5 10.90 86.8 12.06

10.0 41.3 5.74 49.6 6.90 57.9 8.05 62.0 8.63 70.3 9.78 78.5 10.94 86.8 12.13

15.0 41.3 5.74 49.6 6.93 57.9 8.09 62.0 8.70 70.3 9.86 78.5 11.05 86.8 12.24

50% 20.0 41.3 5.85 49.6 7.04 57.9 8.23 62.0 8.84 70.3 10.07 78.5 11.30 86.8 12.53

25.0 41.3 6.21 49.6 7.54 57.9 8.84 62.0 9.53 70.3 10.87 78.5 12.20 86.8 13.54

30.0 41.3 8.30 49.6 9.75 57.9 11.19 62.0 11.95 70.3 13.50 78.5 15.13 86.8 16.79

35.0 41.3 10.00 49.6 11.77 57.9 13.61 62.0 14.55 70.3 16.43 78.5 18.41 86.8 20.40

40.0 41.3 11.84 49.6 13.97 57.9 16.17 62.0 17.29 70.3 19.57 78.5 21.91 86.8 24.33

43.0 41.3 13.00 49.6 15.38 57.9 17.80 62.0 19.06 70.3 21.59 78.5 24.19 86.8 26.86

46.0 41.3 14.22 49.6 16.86 57.9 19.53 62.0 20.94 70.3 23.72 78.5 26.61 86.1 29.06

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 33.1 4.55 39.7 5.49 46.3 6.39 49.6 6.86 56.2 7.76 62.9 8.70 69.4 9.60

-5.0 33.1 4.55 39.7 5.49 46.3 6.39 49.6 6.86 56.2 7.76 62.9 8.70 69.4 9.60

0.0 33.1 4.58 39.7 5.49 46.3 6.39 49.6 6.86 56.2 7.80 62.9 8.70 69.4 9.60

5.0 33.1 4.58 39.7 5.49 46.3 6.43 49.6 6.86 56.2 7.80 62.9 8.70 69.4 9.64

10.0 33.1 4.58 39.7 5.49 46.3 6.43 49.6 6.90 56.2 7.80 62.9 8.74 69.4 9.67

15.0 33.1 4.58 39.7 5.52 46.3 6.46 49.6 6.93 56.2 7.87 62.9 8.77 69.4 9.71

40% 20.0 33.1 4.62 39.7 5.60 46.3 6.53 49.6 7.00 56.2 7.98 62.9 8.92 69.4 9.89

25.0 33.1 4.84 39.7 5.85 46.3 6.86 49.6 7.36 56.2 8.38 62.9 9.39 69.4 10.40

30.0 33.1 6.79 39.7 7.80 46.3 8.84 49.6 9.35 56.2 10.43 62.9 11.52 69.4 12.64

35.0 33.1 8.12 39.7 9.42 46.3 10.72 49.6 11.37 56.2 12.71 62.9 14.08 69.4 15.45

40.0 33.1 9.57 39.7 11.12 46.3 12.71 49.6 13.50 56.2 15.13 62.9 16.79 69.4 18.41

43.0 33.1 10.47 39.7 12.20 46.3 13.97 49.6 14.87 56.2 16.68 62.9 18.52 69.4 20.36

46.0 33.1 11.41 39.7 13.36 46.3 15.31 49.6 16.32 56.2 18.30 62.9 20.36 69.4 22.38

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 24.8 3.43 29.8 4.12 34.7 4.80 37.2 5.13 42.2 5.81 47.1 6.50 52.1 7.18

-5.0 24.8 3.43 29.8 4.12 34.7 4.80 37.2 5.13 42.2 5.81 47.1 6.53 52.1 7.22

0.0 24.8 3.43 29.8 4.12 34.7 4.80 37.2 5.16 42.2 5.85 47.1 6.53 52.1 7.22

5.0 24.8 3.43 29.8 4.12 34.7 4.80 37.2 5.16 42.2 5.85 47.1 6.53 52.1 7.22

10.0 24.8 3.43 29.8 4.12 34.7 4.80 37.2 5.16 42.2 5.85 47.1 6.53 52.1 7.22

15.0 24.8 3.43 29.8 4.12 34.7 4.84 37.2 5.16 42.2 5.88 47.1 6.57 52.1 7.26
30% 20.0 24.8 3.47 29.8 4.15 34.7 4.87 37.2 5.20 42.2 5.92 47.1 6.61 52.1 7.33

25.0 24.8 3.54 29.8 4.26 34.7 5.02 37.2 5.38 42.2 6.10 47.1 6.82 52.1 7.54

30.0 24.8 4.87 29.8 5.63 34.7 6.39 37.2 6.75 42.2 7.51 47.1 8.23 52.1 8.92

35.0 24.8 6.39 29.8 7.26 34.7 8.12 37.2 8.56 42.2 9.42 47.1 10.29 52.1 11.15

40.0 24.8 7.44 29.8 8.52 34.7 9.57 37.2 10.11 42.2 11.19 47.1 12.24 52.1 13.28

43.0 24.8 8.12 29.8 9.31 34.7 10.51 37.2 11.12 42.2 12.31 47.1 13.50 52.1 14.66

46.0 24.8 8.81 29.8 10.14 34.7 11.48 37.2 12.13 42.2 13.47 47.1 14.80 52.1 16.14

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


46 HP (U-14MF2E8 & U-16MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 121.2 16.24 139.8 18.79 139.8 18.79 139.8 18.79 158.3 21.32 177.1 23.84 195.7 26.36

-5.0 121.2 16.24 139.8 18.83 139.8 18.83 139.8 18.83 158.3 21.39 177.1 23.91 195.7 26.40

0.0 121.2 16.27 139.8 18.91 139.8 18.91 139.8 18.91 158.3 21.47 177.1 23.99 195.7 26.51

5.0 121.2 16.31 139.8 19.06 139.8 19.06 139.8 19.06 158.3 21.66 177.1 24.18 195.7 26.74

10.0 121.2 16.43 139.8 19.33 139.8 19.33 139.8 19.33 158.3 22.04 177.1 24.56 195.7 27.12

15.0 121.2 16.69 139.8 19.98 139.8 19.98 139.8 19.98 158.3 22.88 177.1 26.66 195.7 31.71

130% 20.0 121.2 17.53 139.8 23.49 139.8 23.49 139.8 23.49 158.3 28.46 177.1 33.96 195.7 39.96

25.0 121.2 21.43 139.8 29.34 139.8 29.34 139.8 29.34 158.3 35.26 177.1 41.75 195.7 48.82

30.0 121.2 26.55 139.8 35.64 139.8 35.64 139.8 35.64 158.3 42.63 175.9 49.66 182.7 49.66

35.0 121.2 32.01 139.8 42.48 139.8 42.48 139.8 42.48 156.8 49.66 163.0 49.66 169.5 49.66

40.0 121.2 37.97 134.9 46.76 134.9 46.76 134.9 46.76 134.9 42.98 134.9 39.46 134.9 36.18

43.0 111.0 35.76 111.0 35.76 111.0 35.76 111.0 35.76 111.0 32.85 111.0 30.14 111.0 27.66

46.0 87.6 26.43 87.6 26.43 87.6 26.43 87.6 26.43 87.6 24.30 87.6 22.31 87.8 20.48

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 109.2 14.63 131.0 17.57 136.5 18.34 136.5 18.34 154.7 20.82 172.9 23.26 191.1 25.75

-5.0 109.2 14.63 131.0 17.61 136.5 18.41 136.5 18.41 154.7 20.90 172.9 23.34 191.1 25.79

0.0 109.2 14.67 131.0 17.65 136.5 18.45 136.5 18.45 154.7 20.97 172.9 23.45 191.1 25.90

5.0 109.2 14.71 131.0 17.72 136.5 18.60 136.5 18.60 154.7 21.16 172.9 23.65 191.1 26.13

10.0 109.2 14.82 131.0 17.88 136.5 18.87 136.5 18.87 154.7 21.51 172.9 24.03 191.1 26.51

15.0 109.2 15.09 131.0 18.26 136.5 19.48 136.5 19.48 154.7 22.31 172.9 25.44 191.1 30.22

120% 20.0 109.2 15.85 131.0 19.37 136.5 22.58 136.5 22.58 154.7 27.31 172.9 32.51 191.1 38.24

25.0 109.2 19.29 131.0 24.52 136.5 28.27 136.5 28.27 154.7 33.88 172.9 40.07 191.1 46.80

30.0 109.2 23.88 131.0 30.14 136.5 34.38 136.5 34.38 154.7 41.03 172.9 48.28 181.5 49.66

35.0 109.2 28.80 131.0 36.25 136.5 40.99 136.5 40.99 154.7 48.82 162.1 49.66 168.5 49.66

40.0 109.2 34.11 131.0 42.86 134.9 47.25 134.9 47.25 134.9 43.47 134.9 39.92 134.9 36.60

43.0 109.2 37.55 111.0 36.06 111.0 36.06 111.0 36.06 111.0 33.16 111.0 30.45 111.0 27.92

46.0 87.6 26.63 87.6 26.63 87.6 26.63 87.6 26.63 87.6 24.49 87.6 22.46 87.8 20.63

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 97.8 13.10 117.3 15.74 133.3 17.92 133.3 17.92 151.1 20.32 168.7 22.73 186.6 25.14

-5.0 97.8 13.10 117.3 15.74 133.3 17.95 133.3 17.95 151.1 20.36 168.7 22.81 186.6 25.17

0.0 97.8 13.14 117.3 15.78 133.3 18.03 133.3 18.03 151.1 20.48 168.7 22.88 186.6 25.29

5.0 97.8 13.18 117.3 15.85 133.3 18.15 133.3 18.15 151.1 20.63 168.7 23.07 186.6 25.48

10.0 97.8 13.26 117.3 16.01 133.3 18.37 133.3 18.37 151.1 20.97 168.7 23.45 186.6 25.86

15.0 97.8 13.52 117.3 16.35 133.3 18.95 133.3 18.95 151.1 21.70 168.7 24.26 186.6 28.80

110% 20.0 97.8 14.25 117.3 17.42 133.3 21.66 133.3 21.66 151.1 26.17 168.7 31.13 186.6 36.52

25.0 97.8 17.27 117.3 21.85 133.3 27.20 133.3 27.20 151.1 32.58 168.7 38.43 186.6 44.81

30.0 97.8 21.35 117.3 26.85 133.3 33.12 133.3 33.12 151.1 39.46 168.7 46.37 180.2 49.66

35.0 97.8 25.75 117.3 32.28 133.3 39.54 133.3 39.54 151.1 46.99 160.9 49.66 167.3 49.66

40.0 97.8 30.48 117.3 38.16 133.3 46.64 133.3 46.64 134.9 43.97 134.9 40.42 134.9 37.05

43.0 97.8 33.50 111.0 36.44 111.0 36.44 111.0 36.44 111.0 33.50 111.0 30.75 111.0 28.19

46.0 87.8 26.82 87.8 26.82 87.8 26.82 87.8 26.82 87.6 24.64 87.6 22.65 87.6 20.78

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 86.7 11.61 104.0 13.94 121.3 16.31 130.0 17.46 147.3 19.83 164.7 22.16 182.0 24.52

-5.0 86.7 11.65 104.0 13.98 121.3 16.31 130.0 17.50 147.3 19.86 164.7 22.23 182.0 24.56

0.0 86.7 11.65 104.0 14.02 121.3 16.39 130.0 17.57 147.3 19.94 164.7 22.35 182.0 24.68

5.0 86.7 11.69 104.0 14.10 121.3 16.46 130.0 17.69 147.3 20.09 164.7 22.54 182.0 24.87

10.0 86.7 11.77 104.0 14.21 121.3 16.66 130.0 17.92 147.3 20.40 164.7 22.88 182.0 25.25

15.0 86.7 11.99 104.0 14.55 121.3 17.11 130.0 18.45 147.3 21.09 164.7 23.68 182.0 27.43

100% 20.0 86.7 12.68 104.0 15.55 121.3 18.83 130.0 20.82 147.3 25.06 164.7 29.76 182.0 34.91

25.0 86.7 15.36 104.0 19.33 121.3 23.76 130.0 26.17 147.3 31.29 164.7 36.86 182.0 42.90

30.0 86.7 18.95 104.0 23.76 121.3 29.07 130.0 31.90 147.3 37.93 164.7 44.50 178.9 49.66

35.0 86.7 22.81 104.0 28.46 121.3 34.57 130.0 38.20 146.6 44.89 159.9 49.66 166.1 49.66

40.0 86.7 27.01 104.0 33.69 121.3 41.03 130.0 44.96 134.9 44.54 134.9 40.91 134.9 37.55

43.0 86.7 29.68 104.0 37.05 111.0 38.35 111.0 36.79 111.0 33.85 111.0 31.06 111.0 28.50

9 46.0 86.7 32.58 87.8 30.60 87.6 28.19 87.6 27.05 87.6 24.87 87.6 22.84 87.6 20.97
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


46 HP (U-14MF2E8 & U-16MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 78.0 10.47 93.6 12.57 109.2 14.67 117.0 15.70 132.6 17.84 148.2 19.94 163.8 22.08

-5.0 78.0 10.47 93.6 12.57 109.2 14.67 117.0 15.74 132.6 17.88 148.2 19.98 163.8 22.12

0.0 78.0 10.47 93.6 12.61 109.2 14.71 117.0 15.78 132.6 17.92 148.2 20.09 163.8 22.23

5.0 78.0 10.51 93.6 12.64 109.2 14.78 117.0 15.85 132.6 18.03 148.2 20.21 163.8 22.39

10.0 78.0 10.58 93.6 12.76 109.2 14.94 117.0 16.04 132.6 18.26 148.2 20.51 163.8 22.73

15.0 78.0 10.73 93.6 12.99 109.2 15.28 117.0 16.43 132.6 18.76 148.2 21.16 163.8 23.49

90% 20.0 78.0 11.23 93.6 13.71 109.2 16.27 117.0 17.57 132.6 20.97 148.2 24.72 163.8 28.80

25.0 78.0 13.37 93.6 16.66 109.2 20.28 117.0 22.23 132.6 26.40 148.2 30.87 163.8 35.72

30.0 78.0 16.58 93.6 20.55 109.2 24.94 117.0 27.24 132.6 32.16 148.2 37.51 163.8 43.20

35.0 78.0 19.98 93.6 24.75 109.2 29.91 117.0 32.66 132.6 38.47 148.2 44.73 161.2 49.66

40.0 78.0 23.65 93.6 29.26 109.2 35.37 117.0 38.58 132.6 45.42 134.9 43.32 134.9 39.77

43.0 78.0 26.01 93.6 32.20 109.2 38.93 111.0 38.51 111.0 35.45 111.0 32.58 111.0 29.91

46.0 78.0 28.54 87.8 31.71 87.8 29.22 87.6 28.04 87.6 25.79 87.8 23.68 87.8 21.77

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 69.3 9.28 83.2 11.15 97.1 13.03 104.0 13.98 117.9 15.85 131.7 17.72 145.6 19.60

-5.0 69.3 9.28 83.2 11.15 97.1 13.03 104.0 13.98 117.9 15.85 131.7 17.76 145.6 19.63

0.0 69.3 9.32 83.2 11.19 97.1 13.06 104.0 14.02 117.9 15.89 131.7 17.80 145.6 19.71

5.0 69.3 9.32 83.2 11.23 97.1 13.10 104.0 14.06 117.9 16.01 131.7 17.92 145.6 19.83

10.0 69.3 9.40 83.2 11.31 97.1 13.22 104.0 14.21 117.9 16.16 131.7 18.11 145.6 20.09

15.0 69.3 9.51 83.2 11.46 97.1 13.48 104.0 14.48 117.9 16.50 131.7 18.57 145.6 20.67

80% 20.0 69.3 9.86 83.2 11.99 97.1 14.17 104.0 15.28 117.9 17.53 131.7 20.21 145.6 23.38

25.0 69.3 11.54 83.2 14.21 97.1 17.11 104.0 18.68 117.9 21.97 131.7 25.52 145.6 29.34

30.0 69.3 14.33 83.2 17.61 97.1 21.12 104.0 23.00 117.9 26.97 131.7 31.17 145.6 35.72

35.0 69.3 17.30 83.2 21.24 97.1 25.44 104.0 27.70 117.9 32.36 131.7 37.36 145.6 42.67

40.0 69.3 20.51 83.2 25.17 97.1 30.14 104.0 32.74 117.9 38.24 131.7 44.12 134.9 42.71

43.0 69.3 22.54 83.2 27.66 97.1 33.16 104.0 36.06 111.0 37.55 111.0 34.53 111.0 31.71

46.0 69.3 24.72 83.2 30.37 87.8 30.52 87.8 29.30 87.8 26.97 87.8 24.83 87.8 22.81

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 60.7 8.14 72.8 9.74 84.9 11.38 91.0 12.22 103.1 13.87 115.3 15.47 127.4 17.11

-5.0 60.7 8.14 72.8 9.78 84.9 11.42 91.0 12.22 103.1 13.87 115.3 15.51 127.4 17.15

0.0 60.7 8.14 72.8 9.78 84.9 11.42 91.0 12.26 103.1 13.90 115.3 15.55 127.4 17.23

5.0 60.7 8.17 72.8 9.82 84.9 11.46 91.0 12.30 103.1 13.94 115.3 15.62 127.4 17.30

10.0 60.7 8.17 72.8 9.86 84.9 11.54 91.0 12.38 103.1 14.06 115.3 15.78 127.4 17.46

15.0 60.7 8.25 72.8 9.97 84.9 11.69 91.0 12.57 103.1 14.33 115.3 16.08 127.4 17.84

70% 20.0 60.7 8.52 72.8 10.31 84.9 12.19 91.0 13.14 103.1 15.01 115.3 16.92 127.4 18.87

25.0 60.7 9.74 72.8 11.96 84.9 14.25 91.0 15.47 103.1 18.03 115.3 20.74 127.4 23.65

30.0 60.7 12.26 72.8 14.86 84.9 17.69 91.0 19.18 103.1 22.27 115.3 25.56 127.4 29.03

35.0 60.7 14.82 72.8 17.99 84.9 21.35 91.0 23.11 103.1 26.82 115.3 30.71 127.4 34.80

40.0 60.7 17.57 72.8 21.32 84.9 25.33 91.0 27.43 103.1 31.74 115.3 36.37 127.4 41.22

43.0 60.7 19.33 72.8 23.45 84.9 27.89 91.0 30.18 103.1 34.99 111.0 37.21 111.0 34.19

46.0 60.7 21.16 72.8 25.75 84.9 30.60 87.6 31.06 87.8 28.61 87.8 26.32 87.8 24.18

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 52.0 6.95 62.4 8.37 72.8 9.78 78.0 10.47 88.4 11.88 98.8 13.26 109.2 14.67

-5.0 52.0 6.95 62.4 8.37 72.8 9.78 78.0 10.47 88.4 11.88 98.8 13.29 109.2 14.71

0.0 52.0 6.99 62.4 8.37 72.8 9.78 78.0 10.51 88.4 11.88 98.8 13.29 109.2 14.71

5.0 52.0 6.99 62.4 8.40 72.8 9.82 78.0 10.51 88.4 11.92 98.8 13.37 109.2 14.78

10.0 52.0 6.99 62.4 8.44 72.8 9.86 78.0 10.58 88.4 11.99 98.8 13.45 109.2 14.90

15.0 52.0 7.07 62.4 8.52 72.8 9.97 78.0 10.70 88.4 12.15 98.8 13.64 109.2 15.13

60% 20.0 52.0 7.22 62.4 8.75 72.8 10.28 78.0 11.04 88.4 12.61 98.8 14.21 109.2 15.78

25.0 52.0 8.02 62.4 9.82 72.8 11.65 78.0 12.61 88.4 14.52 98.8 16.54 109.2 18.68

30.0 52.0 10.35 62.4 12.38 72.8 14.55 78.0 15.70 88.4 18.03 98.8 20.51 109.2 23.11

35.0 52.0 12.49 62.4 14.97 72.8 17.61 78.0 18.99 88.4 21.81 98.8 24.75 109.2 27.85

40.0 52.0 14.78 62.4 17.80 72.8 20.93 78.0 22.54 88.4 25.90 98.8 29.38 109.2 33.04

43.0 52.0 16.27 62.4 19.56 72.8 23.03 78.0 24.83 88.4 28.54 98.8 32.39 109.2 36.44

46.0 52.0 17.80 62.4 21.47 72.8 25.25 78.0 27.24 87.6 30.87 87.6 28.42 87.8 26.17

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


46 HP (U-14MF2E8 & U-16MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 43.3 5.81 52.0 6.95 60.7 8.14 65.0 8.71 73.7 9.89 82.3 11.04 91.0 12.22

-5.0 43.3 5.81 52.0 6.99 60.7 8.14 65.0 8.71 73.7 9.89 82.3 11.08 91.0 12.22

0.0 43.3 5.81 52.0 6.99 60.7 8.14 65.0 8.75 73.7 9.89 82.3 11.08 91.0 12.26

5.0 43.3 5.81 52.0 6.99 60.7 8.17 65.0 8.75 73.7 9.93 82.3 11.12 91.0 12.30

10.0 43.3 5.84 52.0 6.99 60.7 8.17 65.0 8.79 73.7 9.97 82.3 11.15 91.0 12.34

15.0 43.3 5.84 52.0 7.07 60.7 8.25 65.0 8.86 73.7 10.05 82.3 11.27 91.0 12.49

50% 20.0 43.3 5.96 52.0 7.18 60.7 8.44 65.0 9.05 73.7 10.31 82.3 11.61 91.0 12.87

25.0 43.3 6.42 52.0 7.83 60.7 9.24 65.0 9.97 73.7 11.42 82.3 12.87 91.0 14.36

30.0 43.3 8.60 52.0 10.12 60.7 11.73 65.0 12.57 73.7 14.29 82.3 16.08 91.0 17.92

35.0 43.3 10.35 52.0 12.22 60.7 14.21 65.0 15.24 73.7 17.34 82.3 19.48 91.0 21.74

40.0 43.3 12.22 52.0 14.52 60.7 16.88 65.0 18.11 73.7 20.59 82.3 23.19 91.0 25.86

43.0 43.3 13.41 52.0 15.97 60.7 18.60 65.0 19.94 73.7 22.69 82.3 25.56 91.0 28.50

46.0 43.3 14.67 52.0 17.50 60.7 20.40 65.0 21.89 73.7 24.94 82.3 28.08 87.6 29.15

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 34.7 4.66 41.6 5.58 48.5 6.49 52.0 6.99 58.9 7.91 65.9 8.82 72.8 9.78

-5.0 34.7 4.66 41.6 5.58 48.5 6.49 52.0 6.99 58.9 7.91 65.9 8.86 72.8 9.78

0.0 34.7 4.66 41.6 5.58 48.5 6.53 52.0 6.99 58.9 7.91 65.9 8.86 72.8 9.78

5.0 34.7 4.66 41.6 5.58 48.5 6.53 52.0 6.99 58.9 7.95 65.9 8.86 72.8 9.82

10.0 34.7 4.66 41.6 5.62 48.5 6.53 52.0 6.99 58.9 7.95 65.9 8.90 72.8 9.86

15.0 34.7 4.66 41.6 5.62 48.5 6.57 52.0 7.03 58.9 7.98 65.9 8.98 72.8 9.93

40% 20.0 34.7 4.74 41.6 5.69 48.5 6.69 52.0 7.14 58.9 8.14 65.9 9.13 72.8 10.12

25.0 34.7 4.97 41.6 6.04 48.5 7.11 52.0 7.64 58.9 8.71 65.9 9.78 72.8 10.89

30.0 34.7 6.99 41.6 8.06 48.5 9.21 52.0 9.78 58.9 10.96 65.9 12.19 72.8 13.45

35.0 34.7 8.37 41.6 9.74 48.5 11.15 52.0 11.88 58.9 13.33 65.9 14.86 72.8 16.39

40.0 34.7 9.82 41.6 11.50 48.5 13.22 52.0 14.10 58.9 15.89 65.9 17.69 72.8 19.52

43.0 34.7 10.77 41.6 12.64 48.5 14.55 52.0 15.51 58.9 17.50 65.9 19.48 72.8 21.54

46.0 34.7 11.77 41.6 13.83 48.5 15.93 52.0 17.04 58.9 19.21 65.9 21.43 72.8 23.68

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 26.0 3.48 31.2 4.16 36.4 4.89 39.0 5.23 44.2 5.92 49.4 6.61 54.6 7.33

-5.0 26.0 3.48 31.2 4.16 36.4 4.89 39.0 5.23 44.2 5.92 49.4 6.65 54.6 7.33

0.0 26.0 3.48 31.2 4.20 36.4 4.89 39.0 5.23 44.2 5.92 49.4 6.65 54.6 7.33

5.0 26.0 3.48 31.2 4.20 36.4 4.89 39.0 5.23 44.2 5.96 49.4 6.65 54.6 7.33

10.0 26.0 3.48 31.2 4.20 36.4 4.89 39.0 5.23 44.2 5.96 49.4 6.65 54.6 7.37

15.0 26.0 3.51 31.2 4.20 36.4 4.93 39.0 5.27 44.2 5.96 49.4 6.69 54.6 7.41
30% 20.0 26.0 3.51 31.2 4.24 36.4 4.97 39.0 5.31 44.2 6.04 49.4 6.76 54.6 7.49

25.0 26.0 3.63 31.2 4.39 36.4 5.16 39.0 5.54 44.2 6.30 49.4 7.07 54.6 7.79

30.0 26.0 5.54 31.2 6.26 36.4 6.99 39.0 7.37 44.2 8.14 49.4 8.90 54.6 9.66

35.0 26.0 6.53 31.2 7.49 36.4 8.40 39.0 8.90 44.2 9.86 49.4 10.81 54.6 11.77

40.0 26.0 7.64 31.2 8.79 36.4 9.93 39.0 10.51 44.2 11.69 49.4 12.84 54.6 14.02

43.0 26.0 8.33 31.2 9.59 36.4 10.89 39.0 11.54 44.2 12.84 49.4 14.13 54.6 15.47

46.0 26.0 9.05 31.2 10.47 36.4 11.92 39.0 12.61 44.2 14.06 49.4 15.51 54.6 17.00

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


48 HP (U-16MF2E8 & U-16MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 125.8 16.36 145.1 18.95 145.1 18.95 145.1 18.95 164.4 21.51 183.9 24.02 203.2 26.57

-5.0 125.8 16.36 145.1 18.99 145.1 18.99 145.1 18.99 164.4 21.55 183.9 24.10 203.2 26.65

0.0 125.8 16.40 145.1 19.07 145.1 19.07 145.1 19.07 164.4 21.67 183.9 24.22 203.2 26.77

5.0 125.8 16.48 145.1 19.23 145.1 19.23 145.1 19.23 164.4 21.87 183.9 24.46 203.2 27.01

10.0 125.8 16.60 145.1 19.55 145.1 19.55 145.1 19.55 164.4 22.30 183.9 24.90 203.2 27.45

15.0 125.8 16.88 145.1 20.31 145.1 20.31 145.1 20.31 164.4 23.58 183.9 28.61 203.2 34.15

130% 20.0 125.8 17.84 145.1 24.78 145.1 24.78 145.1 24.78 164.4 30.16 183.9 36.15 203.2 42.73

25.0 125.8 22.22 145.1 30.84 145.1 30.84 145.1 30.84 164.4 37.23 183.9 44.25 202.8 51.79

30.0 125.8 27.45 145.1 37.35 145.1 37.35 145.1 37.35 164.4 44.85 181.8 51.87 188.6 51.87

35.0 125.8 33.08 145.1 44.41 145.1 44.41 145.1 44.41 162.4 51.87 168.9 51.87 175.4 51.87

40.0 125.8 39.18 136.8 46.40 136.8 46.40 136.8 46.40 136.8 42.65 136.8 39.18 136.8 35.95

43.0 112.5 35.39 112.5 35.39 112.5 35.39 112.5 35.39 112.5 32.56 112.5 29.89 112.5 27.41

46.0 88.8 26.13 88.8 26.13 88.8 26.13 88.8 26.13 88.8 24.02 88.8 22.06 88.8 20.23

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 113.4 14.76 136.1 17.72 141.8 18.51 141.8 18.51 160.7 20.99 179.6 23.46 198.5 25.94

-5.0 113.4 14.76 136.1 17.76 141.8 18.55 141.8 18.55 160.7 21.07 179.6 23.54 198.5 26.01

0.0 113.4 14.80 136.1 17.80 141.8 18.63 141.8 18.63 160.7 21.19 179.6 23.66 198.5 26.13

5.0 113.4 14.84 136.1 17.88 141.8 18.75 141.8 18.75 160.7 21.39 179.6 23.86 198.5 26.37

10.0 113.4 14.96 136.1 18.03 141.8 19.07 141.8 19.07 160.7 21.79 179.6 24.30 198.5 26.81

15.0 113.4 15.24 136.1 18.47 141.8 19.79 141.8 19.79 160.7 22.70 179.6 27.29 198.5 32.56

120% 20.0 113.4 16.16 136.1 20.15 141.8 23.82 141.8 23.82 160.7 28.93 179.6 34.63 198.5 40.90

25.0 113.4 19.99 136.1 25.58 141.8 29.69 141.8 29.69 160.7 35.79 179.6 42.49 198.5 49.84

30.0 113.4 24.70 136.1 31.36 141.8 35.99 141.8 35.99 160.7 43.17 179.6 51.03 187.4 51.87

35.0 113.4 29.73 136.1 37.63 141.8 42.85 141.8 42.85 160.7 51.23 167.8 51.87 174.3 51.87

40.0 113.4 35.19 136.1 44.41 136.8 46.92 136.8 46.92 136.8 43.17 136.8 39.66 136.8 36.35

43.0 112.5 35.75 112.5 35.75 112.5 35.75 112.5 35.75 112.5 32.88 112.5 30.16 112.5 27.65

46.0 88.8 26.33 88.8 26.33 88.8 26.33 88.8 26.33 88.8 24.18 88.8 22.22 88.8 20.39

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 101.5 13.21 121.8 15.84 138.4 18.07 138.4 18.07 156.9 20.51 175.2 22.90 193.7 25.34

-5.0 101.5 13.21 121.8 15.88 138.4 18.11 138.4 18.11 156.9 20.55 175.2 22.98 193.7 25.42

0.0 101.5 13.25 121.8 15.92 138.4 18.15 138.4 18.15 156.9 20.67 175.2 23.10 193.7 25.54

5.0 101.5 13.29 121.8 16.00 138.4 18.31 138.4 18.31 156.9 20.83 175.2 23.30 193.7 25.74

10.0 101.5 13.41 121.8 16.16 138.4 18.59 138.4 18.59 156.9 21.23 175.2 23.74 193.7 26.17

15.0 101.5 13.65 121.8 16.56 138.4 19.27 138.4 19.27 156.9 22.10 175.2 26.05 193.7 31.04

110% 20.0 101.5 14.52 121.8 17.96 138.4 22.86 138.4 22.86 156.9 27.73 175.2 33.16 193.7 39.06

25.0 101.5 17.88 121.8 22.78 138.4 28.57 138.4 28.57 156.9 34.35 175.2 40.74 193.7 47.72

30.0 101.5 22.06 121.8 27.93 138.4 34.67 138.4 34.67 156.9 41.50 175.2 49.00 186.0 51.87

35.0 101.5 26.57 121.8 33.48 138.4 41.30 138.4 41.30 156.9 49.32 166.6 51.87 173.1 51.87

40.0 101.5 31.40 121.8 39.50 136.8 47.48 136.8 47.48 136.8 43.69 136.8 40.14 136.8 36.83

43.0 101.5 34.51 112.5 36.11 112.5 36.11 112.5 36.11 112.5 33.20 112.6 30.48 112.5 27.97

46.0 88.8 26.53 88.8 26.53 88.8 26.53 88.8 26.53 88.8 24.38 88.8 22.38 88.8 20.55

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 90.0 11.69 108.0 14.08 126.0 16.44 135.0 17.60 153.0 19.99 171.0 22.34 189.0 24.70

-5.0 90.0 11.73 108.0 14.08 126.0 16.48 135.0 17.64 153.0 20.03 171.0 22.42 189.0 24.78

0.0 90.0 11.73 108.0 14.12 126.0 16.52 135.0 17.72 153.0 20.15 171.0 22.54 189.0 24.90

5.0 90.0 11.81 108.0 14.20 126.0 16.64 135.0 17.84 153.0 20.31 171.0 22.74 189.0 25.14

10.0 90.0 11.89 108.0 14.36 126.0 16.84 135.0 18.11 153.0 20.67 171.0 23.14 189.0 25.58

15.0 90.0 12.13 108.0 14.72 126.0 17.40 135.0 18.71 153.0 21.47 171.0 24.86 189.0 29.57

100% 20.0 90.0 12.93 108.0 15.92 126.0 19.79 135.0 21.95 153.0 26.57 171.0 31.72 189.0 37.31

25.0 90.0 15.88 108.0 20.15 126.0 24.90 135.0 27.45 153.0 33.00 171.0 39.06 189.0 45.65

30.0 90.0 19.59 108.0 24.70 126.0 30.32 135.0 33.40 153.0 39.90 171.0 47.00 184.7 51.87

35.0 90.0 23.54 108.0 29.49 126.0 36.03 135.0 39.90 152.4 47.12 165.5 51.87 171.9 51.87

40.0 90.0 27.81 108.0 34.91 126.0 42.69 135.0 46.88 136.8 44.21 136.8 40.66 136.8 37.31

43.0 90.0 30.56 108.0 38.38 112.5 38.02 112.5 36.47 112.5 33.56 112.5 30.80 112.5 28.25

9 46.0 88.8 32.84 88.8 30.24 88.8 27.85 88.8 26.73 88.8 24.58 88.8 22.58 88.8 20.75
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


48 HP (U-16MF2E8 & U-16MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 81.0 10.53 97.2 12.65 113.4 14.76 121.5 15.84 137.7 17.96 153.9 20.11 170.1 22.22

-5.0 81.0 10.53 97.2 12.69 113.4 14.80 121.5 15.88 137.7 17.99 153.9 20.15 170.1 22.30

0.0 81.0 10.57 97.2 12.69 113.4 14.84 121.5 15.92 137.7 18.07 153.9 20.27 170.1 22.42

5.0 81.0 10.61 97.2 12.77 113.4 14.92 121.5 16.00 137.7 18.19 153.9 20.43 170.1 22.62

10.0 81.0 10.65 97.2 12.89 113.4 15.08 121.5 16.20 137.7 18.47 153.9 20.75 170.1 23.02

15.0 81.0 10.85 97.2 13.17 113.4 15.48 121.5 16.68 137.7 19.07 153.9 21.51 170.1 24.06

90% 20.0 81.0 11.45 97.2 14.00 113.4 16.76 121.5 18.47 137.7 22.22 153.9 26.29 170.1 30.80

25.0 81.0 13.81 97.2 17.32 113.4 21.23 121.5 23.30 137.7 27.81 153.9 32.68 170.1 37.98

30.0 81.0 17.08 97.2 21.31 113.4 25.97 121.5 28.49 137.7 33.80 153.9 39.58 170.1 45.81

35.0 81.0 20.59 97.2 25.62 113.4 31.16 121.5 34.07 137.7 40.34 153.9 47.08 166.6 51.87

40.0 81.0 24.34 97.2 30.28 113.4 36.75 121.5 40.18 136.8 46.84 136.8 43.05 136.8 39.54

43.0 81.0 26.77 97.2 33.28 112.5 39.82 112.5 38.22 112.5 35.15 112.5 32.32 112.5 29.69

46.0 81.0 29.33 88.8 31.40 88.8 28.93 88.8 27.73 88.8 25.54 88.8 23.46 88.8 21.55

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 72.0 9.38 86.4 11.25 100.8 13.13 108.0 14.08 122.4 15.96 136.8 17.88 151.2 19.75

-5.0 72.0 9.38 86.4 11.25 100.8 13.17 108.0 14.08 122.4 16.00 136.8 17.88 151.2 19.79

0.0 72.0 9.38 86.4 11.29 100.8 13.17 108.0 14.12 122.4 16.04 136.8 17.96 151.2 19.87

5.0 72.0 9.42 86.4 11.33 100.8 13.25 108.0 14.20 122.4 16.12 136.8 18.07 151.2 20.03

10.0 72.0 9.46 86.4 11.41 100.8 13.37 108.0 14.32 122.4 16.32 136.8 18.31 151.2 20.35

15.0 72.0 9.58 86.4 11.61 100.8 13.65 108.0 14.68 122.4 16.76 136.8 18.87 151.2 21.03

80% 20.0 72.0 10.01 86.4 12.21 100.8 14.48 108.0 15.64 122.4 18.31 136.8 21.51 151.2 24.98

25.0 72.0 11.89 86.4 14.76 100.8 17.88 108.0 19.55 122.4 23.14 136.8 27.01 151.2 31.16

30.0 72.0 14.76 86.4 18.23 100.8 22.02 108.0 24.02 122.4 28.29 136.8 32.88 151.2 37.79

35.0 72.0 17.80 86.4 21.95 100.8 26.45 108.0 28.85 122.4 33.88 136.8 39.26 151.2 45.05

40.0 72.0 21.07 86.4 25.97 100.8 31.28 108.0 34.07 122.4 39.98 136.8 46.28 136.8 42.53

43.0 72.0 23.18 86.4 28.57 100.8 34.39 108.0 37.47 112.5 37.31 112.5 34.31 112.5 31.52

46.0 72.0 25.38 86.4 31.36 88.8 30.24 88.8 29.05 88.8 26.73 88.8 24.58 88.8 22.58

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 63.0 8.18 75.6 9.86 88.2 11.49 94.5 12.29 107.1 13.97 119.7 15.60 132.3 17.28

-5.0 63.0 8.18 75.6 9.86 88.2 11.49 94.5 12.33 107.1 13.97 119.7 15.64 132.3 17.32

0.0 63.0 8.22 75.6 9.86 88.2 11.53 94.5 12.33 107.1 14.00 119.7 15.68 132.3 17.36

5.0 63.0 8.22 75.6 9.90 88.2 11.57 94.5 12.41 107.1 14.08 119.7 15.76 132.3 17.48

10.0 63.0 8.26 75.6 9.94 88.2 11.65 94.5 12.49 107.1 14.20 119.7 15.92 132.3 17.68

15.0 63.0 8.34 75.6 10.09 88.2 11.81 94.5 12.73 107.1 14.48 119.7 16.32 132.3 18.11

70% 20.0 63.0 8.62 75.6 10.49 88.2 12.41 94.5 13.41 107.1 15.36 119.7 17.36 132.3 19.91

25.0 63.0 10.17 75.6 12.41 88.2 14.84 94.5 16.16 107.1 18.95 119.7 21.91 132.3 25.10

30.0 63.0 12.61 75.6 15.36 88.2 18.39 94.5 19.99 107.1 23.30 119.7 26.89 132.3 30.68

35.0 63.0 15.20 75.6 18.55 88.2 22.14 94.5 24.06 107.1 28.01 119.7 32.24 132.3 36.71

40.0 63.0 17.99 75.6 21.98 88.2 26.25 94.5 28.49 107.1 33.16 119.7 38.10 132.3 43.37

43.0 63.0 19.79 75.6 24.18 88.2 28.89 94.5 31.32 107.1 36.47 112.5 36.99 112.5 34.03

46.0 63.0 21.71 75.6 26.53 88.2 31.68 88.8 30.80 88.8 28.37 88.8 26.09 88.8 23.98

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 54.0 7.02 64.8 8.42 75.6 9.86 81.0 10.53 91.8 11.97 102.6 13.37 113.4 14.80

-5.0 54.0 7.02 64.8 8.42 75.6 9.86 81.0 10.57 91.8 11.97 102.6 13.41 113.4 14.80

0.0 54.0 7.02 64.8 8.46 75.6 9.86 81.0 10.57 91.8 12.01 102.6 13.41 113.4 14.84

5.0 54.0 7.06 64.8 8.46 75.6 9.90 81.0 10.61 91.8 12.05 102.6 13.49 113.4 14.92

10.0 54.0 7.06 64.8 8.50 75.6 9.94 81.0 10.65 91.8 12.13 102.6 13.57 113.4 15.04

15.0 54.0 7.14 64.8 8.58 75.6 10.05 81.0 10.81 91.8 12.29 102.6 13.81 113.4 15.32

60% 20.0 54.0 7.30 64.8 8.86 75.6 10.45 81.0 11.25 91.8 12.85 102.6 14.52 113.4 16.16

25.0 54.0 8.30 64.8 10.25 75.6 12.17 81.0 13.13 91.8 15.24 102.6 17.44 113.4 19.79

30.0 54.0 10.61 64.8 12.77 75.6 15.08 81.0 16.32 91.8 18.87 102.6 21.55 113.4 24.38

35.0 54.0 12.81 64.8 15.44 75.6 18.23 81.0 19.71 91.8 22.74 102.6 25.97 113.4 29.33

40.0 54.0 15.16 64.8 18.31 75.6 21.63 81.0 23.38 91.8 26.97 102.6 30.76 113.4 34.71

43.0 54.0 16.68 64.8 20.15 75.6 23.82 81.0 25.74 91.8 29.69 102.6 33.88 112.5 37.63

46.0 54.0 18.23 64.8 22.06 75.6 26.13 81.0 28.21 88.8 30.68 88.8 28.25 88.8 26.01

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Cooling)


48 HP (U-16MF2E8 & U-16MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 45.0 5.87 54.0 7.02 63.0 8.18 67.5 8.78 76.5 9.98 85.5 11.13 94.5 12.33

-5.0 45.0 5.87 54.0 7.02 63.0 8.22 67.5 8.78 76.5 9.98 85.5 11.13 94.5 12.33

0.0 45.0 5.87 54.0 7.02 63.0 8.22 67.5 8.82 76.5 9.98 85.5 11.17 94.5 12.37

5.0 45.0 5.87 54.0 7.06 63.0 8.22 67.5 8.82 76.5 10.01 85.5 11.21 94.5 12.41

10.0 45.0 5.87 54.0 7.06 63.0 8.26 67.5 8.86 76.5 10.05 85.5 11.25 94.5 12.49

15.0 45.0 5.91 54.0 7.10 63.0 8.34 67.5 8.94 76.5 10.17 85.5 11.41 94.5 12.65

50% 20.0 45.0 6.02 54.0 7.26 63.0 8.54 67.5 9.22 76.5 10.49 85.5 11.81 94.5 13.13

25.0 45.0 6.58 54.0 8.10 63.0 9.62 67.5 10.37 76.5 11.97 85.5 13.57 94.5 15.20

30.0 45.0 8.78 54.0 10.41 63.0 12.13 67.5 13.05 76.5 14.88 85.5 16.84 94.5 18.91

35.0 45.0 10.57 54.0 12.57 63.0 14.68 67.5 15.80 76.5 18.03 85.5 20.39 94.5 22.82

40.0 45.0 12.49 54.0 14.92 63.0 17.44 67.5 18.75 76.5 21.43 85.5 24.22 94.5 27.09

43.0 45.0 13.73 54.0 16.40 63.0 19.19 67.5 20.63 76.5 23.58 85.5 26.65 94.5 29.89

46.0 45.0 15.00 54.0 17.96 63.0 21.03 67.5 22.62 76.5 25.90 85.5 29.29 88.8 29.05

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 36.0 4.67 43.2 5.63 50.4 6.54 54.0 7.02 61.2 7.98 68.4 8.90 75.6 9.86

-5.0 36.0 4.67 43.2 5.63 50.4 6.54 54.0 7.02 61.2 7.98 68.4 8.90 75.6 9.86

0.0 36.0 4.67 43.2 5.63 50.4 6.58 54.0 7.02 61.2 7.98 68.4 8.94 75.6 9.86

5.0 36.0 4.71 43.2 5.63 50.4 6.58 54.0 7.06 61.2 7.98 68.4 8.94 75.6 9.90

10.0 36.0 4.71 43.2 5.63 50.4 6.58 54.0 7.06 61.2 8.02 68.4 8.98 75.6 9.94

15.0 36.0 4.71 43.2 5.67 50.4 6.62 54.0 7.10 61.2 8.06 68.4 9.06 75.6 10.01

40% 20.0 36.0 4.79 43.2 5.75 50.4 6.74 54.0 7.26 61.2 8.26 68.4 9.26 75.6 10.29

25.0 36.0 5.07 43.2 6.18 50.4 7.30 54.0 7.86 61.2 9.02 68.4 10.17 75.6 11.33

30.0 36.0 7.10 43.2 8.26 50.4 9.50 54.0 10.13 61.2 11.41 68.4 12.77 75.6 14.12

35.0 36.0 8.50 43.2 9.98 50.4 11.49 54.0 12.25 61.2 13.85 68.4 15.48 75.6 17.16

40.0 36.0 10.01 43.2 11.81 50.4 13.61 54.0 14.56 61.2 16.48 68.4 18.43 75.6 20.43

43.0 36.0 10.97 43.2 12.97 50.4 14.96 54.0 16.00 61.2 18.11 68.4 20.31 75.6 22.50

46.0 36.0 11.97 43.2 14.16 50.4 16.40 54.0 17.56 61.2 19.87 68.4 22.26 75.6 24.74

Indoor air t emp.:℃WB

Combinat ion(%) Out door air t emp. 14.0 16.0 18.0 19.0 21.0 23.0 25.0
:Indoor/ out door capacit y rat io ℃DB
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-10.0 27.0 3.51 32.4 4.23 37.8 4.91 40.5 5.27 45.9 5.99 51.3 6.66 56.7 7.38

-5.0 27.0 3.51 32.4 4.23 37.8 4.91 40.5 5.27 45.9 5.99 51.3 6.66 56.7 7.38

0.0 27.0 3.51 32.4 4.23 37.8 4.91 40.5 5.27 45.9 5.99 51.3 6.70 56.7 7.38

5.0 27.0 3.51 32.4 4.23 37.8 4.95 40.5 5.27 45.9 5.99 51.3 6.70 56.7 7.42

10.0 27.0 3.51 32.4 4.23 37.8 4.95 40.5 5.31 45.9 5.99 51.3 6.70 56.7 7.42

15.0 27.0 3.55 32.4 4.23 37.8 4.95 40.5 5.31 45.9 6.02 51.3 6.74 56.7 7.46
30% 20.0 27.0 3.55 32.4 4.27 37.8 4.99 40.5 5.39 45.9 6.10 51.3 6.82 56.7 7.58

25.0 27.0 3.71 32.4 4.47 37.8 5.27 40.5 5.63 45.9 6.42 51.3 7.22 56.7 8.02

30.0 27.0 5.59 32.4 6.38 37.8 7.18 40.5 7.58 45.9 8.42 51.3 9.26 56.7 10.09

35.0 27.0 6.62 32.4 7.62 37.8 8.62 40.5 9.14 45.9 10.17 51.3 11.21 56.7 12.29

40.0 27.0 7.74 32.4 8.94 37.8 10.17 40.5 10.81 45.9 12.05 51.3 13.33 56.7 14.60

43.0 27.0 8.46 32.4 9.78 37.8 11.17 40.5 11.85 45.9 13.25 51.3 14.68 56.7 16.12

46.0 27.0 9.18 32.4 10.69 37.8 12.21 40.5 12.97 45.9 14.52 51.3 16.08 56.7 17.68

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


18 HP (U-8MF2E8 & U-10MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 47.1 15.49 43.3 14.32 40.7 13.54 40.7 13.54 40.7 13.54 40.7 13.73 35.1 12.19

-14.7 -15.0 49.9 15.85 46.0 14.68 43.3 13.86 43.3 13.86 43.3 13.86 43.3 13.86 37.6 12.44

-9.6 -10.0 53.6 16.35 49.4 15.14 46.6 14.31 46.6 14.31 46.6 14.31 46.6 14.31 40.7 12.79

-4.4 -5.0 58.4 17.02 54.0 15.76 50.9 14.91 50.9 14.91 50.9 14.91 50.9 14.91 44.7 13.25

-1.8 -2.5 60.6 17.08 56.8 16.12 53.6 15.23 53.6 15.23 53.6 15.23 53.6 15.23 47.3 13.54

0.8 0.0 63.5 17.08 60.1 16.41 56.8 15.52 56.8 15.52 56.8 15.52 56.8 15.52 49.7 13.55

130% 2.8 2.0 66.3 17.08 63.3 16.70 60.0 15.82 60.0 15.82 60.0 15.82 58.5 15.05 49.7 12.82

6.0 5.0 71.0 17.08 65.3 15.70 60.7 14.52 60.7 14.52 60.7 14.52 58.5 13.58 49.7 11.50

7.0 6.0 72.0 16.78 65.3 15.04 60.7 13.92 60.7 13.92 60.7 13.92 58.5 13.03 49.7 11.05

8.6 7.5 72.0 15.63 65.3 14.03 60.7 13.01 60.7 13.01 60.7 13.01 58.5 12.20 49.7 10.37

11.2 10.0 72.0 13.80 65.3 12.43 60.7 11.54 60.7 11.54 60.7 11.54 58.5 10.89 49.7 9.30

16.4 15.0 72.0 10.54 65.3 9.56 60.7 8.93 60.7 8.93 60.7 8.93 58.5 8.58 49.7 7.38

24.0 18.0 72.0 9.16 65.3 8.37 60.7 7.84 60.7 7.84 60.7 7.84 58.5 7.58 49.7 6.55

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 47.2 15.38 43.4 14.24 40.8 13.46 40.8 13.46 40.8 13.46 37.6 12.69 32.4 11.30

-14.7 -15.0 50.1 15.75 46.1 14.59 43.4 13.79 43.4 13.79 43.4 13.79 40.1 12.98 34.7 11.52

-9.6 -10.0 53.7 16.25 49.6 15.05 46.7 14.24 46.7 14.24 46.7 14.24 43.3 13.37 37.5 11.82

-4.4 -5.0 58.5 16.93 54.0 15.68 51.0 14.82 51.0 14.82 51.0 14.82 47.5 13.90 41.2 12.25

-1.8 -2.5 61.0 17.08 56.8 15.99 53.6 15.12 53.6 15.12 53.6 15.12 50.1 14.18 43.6 12.49

0.8 0.0 63.9 17.08 60.1 16.29 56.8 15.40 56.8 15.40 56.8 15.40 52.7 14.24 44.8 12.18

120% 2.8 2.0 66.7 17.08 63.4 16.58 59.3 15.46 59.3 15.46 59.3 15.46 52.7 13.47 44.8 11.50

6.0 5.0 70.3 16.74 63.7 15.03 59.3 13.92 59.3 13.92 59.3 13.92 52.7 12.14 44.8 10.32

7.0 6.0 70.3 16.02 63.7 14.40 59.3 13.35 59.3 13.35 59.3 13.35 52.7 11.64 44.8 9.91

8.6 7.5 70.3 14.91 63.7 13.42 59.3 12.46 59.3 12.46 59.3 12.46 52.7 10.91 44.8 9.30

11.2 10.0 70.3 13.14 63.7 11.87 59.3 11.04 59.3 11.04 59.3 11.04 52.7 9.74 44.8 8.33

16.4 15.0 70.3 10.00 63.7 9.11 59.3 8.53 59.3 8.53 59.3 8.53 52.7 7.66 44.8 6.62

24.0 18.0 70.3 8.97 63.7 8.19 59.3 7.67 59.3 7.67 59.3 7.67 52.7 6.91 44.8 5.97

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 47.3 15.29 43.5 14.16 40.8 13.38 40.8 13.38 39.0 12.94 34.5 11.66 29.7 10.41

-14.7 -15.0 50.2 15.66 46.2 14.51 43.4 13.73 43.4 13.73 41.6 13.26 36.8 11.93 31.8 10.61

-9.6 -10.0 53.8 16.17 49.6 14.98 46.7 14.16 46.7 14.16 44.8 13.68 39.7 12.29 34.4 10.88

-4.4 -5.0 58.6 16.84 54.1 15.60 51.0 14.75 51.0 14.75 49.0 14.24 43.5 12.75 37.7 11.25

-1.8 -2.5 61.4 17.08 56.9 15.87 53.7 15.01 53.7 15.01 51.7 14.48 45.9 12.98 39.9 11.47

0.8 0.0 64.2 17.08 60.2 16.15 56.8 15.29 56.8 15.29 54.2 14.54 47.2 12.66 40.1 10.87

110% 2.8 2.0 67.0 17.08 62.2 15.99 57.9 14.82 57.9 14.82 54.2 13.75 47.2 11.98 40.1 10.27

6.0 5.0 68.6 15.96 62.2 14.37 57.9 13.35 57.9 13.35 54.2 12.40 47.2 10.78 40.1 9.20

7.0 6.0 68.6 15.27 62.2 13.76 57.9 12.77 57.9 12.77 54.2 11.88 47.2 10.33 40.1 8.83

8.6 7.5 68.6 14.20 62.2 12.82 57.9 11.92 57.9 11.92 54.2 11.10 47.2 9.69 40.1 8.30

11.2 10.0 68.6 12.51 62.2 11.33 57.9 10.55 57.9 10.55 54.2 9.88 47.2 8.65 40.1 7.44

16.4 15.0 68.6 9.49 62.2 8.67 57.9 8.14 57.9 8.14 54.2 7.70 47.2 6.81 40.1 5.92

24.0 18.0 68.6 8.77 62.2 8.02 57.9 7.52 57.9 7.52 54.2 7.08 47.2 6.25 40.1 5.42

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 47.4 15.19 43.6 14.08 41.0 13.32 38.3 12.57 35.5 11.80 31.4 10.65 27.1 9.53

-14.7 -15.0 50.3 15.58 46.3 14.43 43.6 13.66 40.7 12.87 37.9 12.08 33.4 10.89 28.9 9.71

-9.6 -10.0 54.0 16.09 49.7 14.91 46.8 14.10 43.8 13.29 40.8 12.46 36.1 11.20 31.2 9.94

-4.4 -5.0 58.7 16.73 54.2 15.51 51.1 14.66 47.9 13.81 44.6 12.94 39.6 11.61 34.2 10.27

-1.8 -2.5 61.6 17.01 57.0 15.77 53.7 14.92 50.4 14.04 47.0 13.16 41.7 11.81 35.6 10.24

0.8 0.0 64.6 17.08 60.2 16.04 56.5 15.04 52.3 13.90 48.1 12.79 41.9 11.18 35.6 9.63

100% 2.8 2.0 67.0 16.98 60.7 15.30 56.5 14.20 52.3 13.13 48.1 12.09 41.9 10.57 35.6 9.10

6.0 5.0 67.0 15.21 60.7 13.74 56.5 12.77 52.3 11.82 48.1 10.88 41.9 9.50 35.6 8.14

7.0 6.0 67.0 14.54 60.7 13.14 56.5 12.20 52.3 11.32 48.1 10.43 41.9 9.11 35.6 7.82

8.6 7.5 67.0 13.52 60.7 12.24 56.5 11.39 52.3 10.57 48.1 9.75 41.9 8.54 35.6 7.34

11.2 10.0 67.0 11.88 60.7 10.80 56.5 10.09 52.3 9.38 48.1 8.67 41.9 7.63 35.6 6.59

16.4 15.0 67.0 8.98 60.7 8.25 56.5 7.75 52.3 7.26 48.1 6.76 41.9 6.01 35.6 5.26

9 24.0 18.0 67.0 8.58 60.7 7.83 56.5 7.34 52.3 6.86 48.1 6.36 41.9 5.62 35.6 4.88
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


18 HP (U-8MF2E8 & U-10MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 48.0 14.92 44.1 13.87 41.4 13.16 38.6 12.44 35.8 11.72 31.6 10.66 27.2 9.60

-14.7 -15.0 51.0 15.32 46.8 14.24 44.0 13.51 41.1 12.76 38.2 12.00 33.7 10.88 29.0 9.76

-9.6 -10.0 54.6 15.86 50.2 14.73 47.2 13.94 44.2 13.16 41.1 12.37 36.3 11.16 31.3 9.96

-4.4 -5.0 59.4 16.37 54.6 15.19 50.9 14.19 47.1 13.20 43.3 12.24 37.7 10.85 32.0 9.49

-1.8 -2.5 60.3 15.84 54.6 14.38 50.9 13.44 47.1 12.52 43.3 11.60 37.7 10.28 32.0 8.99

0.8 0.0 60.3 14.84 54.6 13.49 50.9 12.61 47.1 11.76 43.3 10.91 37.7 9.66 32.0 8.44

90% 2.8 2.0 60.3 13.94 54.6 12.70 50.9 11.90 47.1 11.09 43.3 10.30 37.7 9.11 32.0 7.93

6.0 5.0 60.3 12.42 54.6 11.35 50.9 10.64 47.1 9.92 43.3 9.21 37.7 8.14 32.0 7.05

7.0 6.0 60.3 11.85 54.6 10.85 50.9 10.16 47.1 9.49 43.3 8.81 37.7 7.80 32.0 6.76

8.6 7.5 60.3 10.98 54.6 10.07 50.9 9.46 47.1 8.85 43.3 8.22 37.7 7.30 32.0 6.34

11.2 10.0 60.3 9.60 54.6 8.85 50.9 8.33 47.1 7.82 43.3 7.30 37.7 6.50 32.0 5.70

16.4 15.0 60.3 7.78 54.6 7.12 50.9 6.69 47.1 6.23 43.3 5.80 37.7 5.14 32.0 4.53

24.0 18.0 60.3 7.78 54.6 7.12 50.9 6.69 47.1 6.23 43.3 5.80 37.7 5.14 32.0 4.47

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 49.0 14.86 44.9 13.86 42.1 13.19 39.3 12.52 36.4 11.85 32.0 10.83 27.6 9.83

-14.7 -15.0 52.0 15.29 47.7 14.25 44.8 13.54 41.8 12.83 38.5 12.02 33.5 10.80 28.5 9.60

-9.6 -10.0 53.6 14.92 48.5 13.71 45.2 12.92 41.9 12.14 38.5 11.35 33.5 10.16 28.5 8.99

-4.4 -5.0 53.6 13.63 48.5 12.54 45.2 11.82 41.9 11.10 38.5 10.41 33.5 9.36 28.5 8.31

-1.8 -2.5 53.6 12.87 48.5 11.85 45.2 11.18 41.9 10.50 38.5 9.83 33.5 8.85 28.5 7.84

0.8 0.0 53.6 12.02 48.5 11.08 45.2 10.46 41.9 9.85 38.5 9.22 33.5 8.28 28.5 7.33

80% 2.8 2.0 53.6 11.26 48.5 10.41 45.2 9.83 41.9 9.25 38.5 8.66 33.5 7.78 28.5 6.81

6.0 5.0 53.6 9.97 48.5 9.24 45.2 8.74 41.9 8.22 38.5 7.69 33.5 6.88 28.5 6.04

7.0 6.0 53.6 9.49 48.5 8.80 45.2 8.33 41.9 7.84 38.5 7.34 33.5 6.59 28.5 5.78

8.6 7.5 53.6 8.76 48.5 8.15 45.2 7.73 41.9 7.30 38.5 6.86 33.5 6.16 28.5 5.43

11.2 10.0 53.6 7.60 48.5 7.12 45.2 6.78 41.9 6.43 38.5 6.06 33.5 5.48 28.5 4.87

16.4 15.0 53.6 7.00 48.5 6.41 45.2 6.01 41.9 5.62 38.5 5.23 33.5 4.64 28.5 4.05

24.0 18.0 53.6 7.00 48.5 6.41 45.2 6.01 41.9 5.62 38.5 5.23 33.5 4.64 28.5 4.05

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 46.9 13.70 42.5 12.71 39.6 12.07 36.6 11.42 33.7 10.78 29.3 9.86 24.9 8.92

-14.7 -15.0 46.9 12.96 42.5 12.09 39.6 11.50 36.6 10.89 33.7 10.26 29.3 9.33 24.9 8.39

-9.6 -10.0 46.9 12.04 42.5 11.25 39.6 10.71 36.6 10.17 33.7 9.63 29.3 8.78 24.9 7.86

-4.4 -5.0 46.9 10.94 42.5 10.22 39.6 9.75 36.6 9.26 33.7 8.76 29.3 8.00 24.9 7.21

-1.8 -2.5 46.9 10.28 42.5 9.63 39.6 9.19 36.6 8.72 33.7 8.26 29.3 7.54 24.9 6.80

0.8 0.0 46.9 9.56 42.5 8.97 39.6 8.56 36.6 8.14 33.7 7.71 29.3 7.04 24.9 6.21

70% 2.8 2.0 46.9 8.93 42.5 8.38 39.6 8.00 36.6 7.63 33.7 7.21 29.3 6.51 24.9 5.76

6.0 5.0 46.9 7.84 42.5 7.38 39.6 7.05 36.6 6.70 33.7 6.33 29.3 5.73 24.9 5.10

7.0 6.0 46.9 7.44 42.5 7.02 39.6 6.71 36.6 6.38 33.7 6.04 29.3 5.49 24.9 4.89

8.6 7.5 46.9 6.83 42.5 6.48 39.6 6.21 36.6 5.93 33.7 5.62 29.3 5.12 24.9 4.59

11.2 10.0 46.9 6.21 42.5 5.70 39.6 5.42 36.6 5.20 33.7 4.95 29.3 4.56 24.9 4.11

16.4 15.0 46.9 6.21 42.5 5.70 39.6 5.36 36.6 5.00 33.7 4.66 29.3 4.15 24.9 3.64

24.0 18.0 46.9 6.21 42.5 5.70 39.6 5.36 36.6 5.00 33.7 4.66 29.3 4.15 24.9 3.64

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 40.2 11.04 36.4 10.48 33.9 10.07 31.4 9.60 28.9 9.14 25.1 8.44 21.4 7.73

-14.7 -15.0 40.2 10.37 36.4 9.86 33.9 9.49 31.4 9.11 28.9 8.70 25.1 7.99 21.4 7.27

-9.6 -10.0 40.2 9.60 36.4 9.13 33.9 8.80 31.4 8.44 28.9 8.09 25.1 7.50 21.4 6.80

-4.4 -5.0 40.2 8.64 36.4 8.24 33.9 7.94 31.4 7.64 28.9 7.32 25.1 6.78 21.4 6.17

-1.8 -2.5 40.2 8.09 36.4 7.72 33.9 7.45 31.4 7.17 28.9 6.87 25.1 6.37 21.4 5.66

0.8 0.0 40.2 7.49 36.4 7.15 33.9 6.92 31.4 6.65 28.9 6.37 25.1 5.80 21.4 5.17

60% 2.8 2.0 40.2 6.95 36.4 6.65 33.9 6.43 31.4 6.16 28.9 5.86 25.1 5.34 21.4 4.79

6.0 5.0 40.2 6.03 36.4 5.77 33.9 5.58 31.4 5.36 28.9 5.11 25.1 4.71 21.4 4.25

7.0 6.0 40.2 5.69 36.4 5.47 33.9 5.29 31.4 5.10 28.9 4.88 25.1 4.50 21.4 4.07

8.6 7.5 40.2 5.43 36.4 5.03 33.9 4.88 31.4 4.72 28.9 4.53 25.1 4.21 21.4 3.83

11.2 10.0 40.2 5.43 36.4 4.98 33.9 4.68 31.4 4.39 28.9 4.10 25.1 3.73 21.4 3.43

16.4 15.0 40.2 5.43 36.4 4.98 33.9 4.68 31.4 4.39 28.9 4.10 25.1 3.66 21.4 3.21

24.0 18.0 40.2 5.43 36.4 4.98 33.9 4.68 31.4 4.39 28.9 4.10 25.1 3.66 21.4 3.21

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


18 HP (U-8MF2E8 & U-10MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 33.5 8.78 30.3 8.49 28.3 8.26 26.2 7.98 24.1 7.65 20.9 7.14 17.8 6.60

-14.7 -15.0 33.5 8.22 30.3 7.95 28.3 7.75 26.2 7.52 24.1 7.26 20.9 6.75 17.8 6.19

-9.6 -10.0 33.5 7.55 30.3 7.32 28.3 7.15 26.2 6.94 24.1 6.71 20.9 6.31 17.8 5.77

-4.4 -5.0 33.5 6.73 30.3 6.55 28.3 6.41 26.2 6.23 24.1 6.03 20.9 5.61 17.8 5.03

-1.8 -2.5 33.5 6.27 30.3 6.11 28.3 5.97 26.2 5.82 24.1 5.59 20.9 5.14 17.8 4.62

0.8 0.0 33.5 5.76 30.3 5.62 28.3 5.48 26.2 5.27 24.1 5.05 20.9 4.66 17.8 4.22

50% 2.8 2.0 33.5 5.31 30.3 5.14 28.3 4.99 26.2 4.82 24.1 4.64 20.9 4.31 17.8 3.92

6.0 5.0 33.5 4.64 30.3 4.39 28.3 4.29 26.2 4.18 24.1 4.04 20.9 3.78 17.8 3.48

7.0 6.0 33.5 4.64 30.3 4.27 28.3 4.07 26.2 3.98 24.1 3.86 20.9 3.62 17.8 3.34

8.6 7.5 33.5 4.64 30.3 4.27 28.3 4.03 26.2 3.78 24.1 3.57 20.9 3.38 17.8 3.14

11.2 10.0 33.5 4.64 30.3 4.27 28.3 4.03 26.2 3.78 24.1 3.53 20.9 3.16 17.8 2.82

16.4 15.0 33.5 4.64 30.3 4.27 28.3 4.03 26.2 3.78 24.1 3.53 20.9 3.16 17.8 2.79

24.0 18.0 33.5 4.64 30.3 4.27 28.3 4.03 26.2 3.78 24.1 3.53 20.9 3.16 17.8 2.79

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 26.8 6.92 24.3 6.78 22.6 6.67 20.9 6.50 19.3 6.27 16.7 5.89 14.2 5.50

-14.7 -15.0 26.8 6.44 24.3 6.33 22.6 6.23 20.9 6.10 19.3 5.93 16.7 5.56 14.2 5.14

-9.6 -10.0 26.8 5.87 24.3 5.80 22.6 5.72 20.9 5.60 19.3 5.47 16.7 5.17 14.2 4.65

-4.4 -5.0 26.8 5.19 24.3 5.14 22.6 5.08 20.9 4.93 19.3 4.73 16.7 4.39 14.2 3.99

-1.8 -2.5 26.8 4.78 24.3 4.71 22.6 4.60 20.9 4.47 19.3 4.29 16.7 4.01 14.2 3.67

0.8 0.0 26.8 4.28 24.3 4.20 22.6 4.12 20.9 4.01 19.3 3.88 16.7 3.65 14.2 3.36

40% 2.8 2.0 26.8 3.86 24.3 3.81 22.6 3.75 20.9 3.67 19.3 3.56 16.7 3.37 14.2 3.12

6.0 5.0 26.8 3.86 24.3 3.55 22.6 3.36 20.9 3.17 19.3 3.11 16.7 2.96 14.2 2.78

7.0 6.0 26.8 3.86 24.3 3.55 22.6 3.36 20.9 3.16 19.3 2.96 16.7 2.84 14.2 2.67

8.6 7.5 26.8 3.86 24.3 3.55 22.6 3.36 20.9 3.16 19.3 2.96 16.7 2.67 14.2 2.51

11.2 10.0 26.8 3.86 24.3 3.55 22.6 3.36 20.9 3.16 19.3 2.96 16.7 2.67 14.2 2.38

16.4 15.0 26.8 3.86 24.3 3.55 22.6 3.36 20.9 3.16 19.3 2.96 16.7 2.67 14.2 2.38

24.0 18.0 26.8 3.86 24.3 3.55 22.6 3.36 20.9 3.16 19.3 2.96 16.7 2.67 14.2 2.38

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 20.1 5.32 18.2 5.28 17.0 5.22 15.7 5.10 14.5 4.94 12.5 4.68 10.7 4.39

-14.7 -15.0 20.1 4.94 18.2 4.92 17.0 4.87 15.7 4.78 14.5 4.67 12.5 4.39 10.7 3.99

-9.6 -10.0 20.1 4.48 18.2 4.48 17.0 4.43 15.7 4.29 14.5 4.14 12.5 3.86 10.7 3.53

-4.4 -5.0 20.1 3.79 18.2 3.73 17.0 3.67 15.7 3.59 14.5 3.48 12.5 3.28 10.7 3.04

-1.8 -2.5 20.1 3.38 18.2 3.36 17.0 3.32 15.7 3.26 14.5 3.17 12.5 3.01 10.7 2.79

0.8 0.0 20.1 3.06 18.2 2.99 17.0 2.96 15.7 2.93 14.5 2.87 12.5 2.75 10.7 2.57

30% 2.8 2.0 20.1 3.06 18.2 2.84 17.0 2.71 15.7 2.68 14.5 2.65 12.5 2.55 10.7 2.40

6.0 5.0 20.1 3.06 18.2 2.84 17.0 2.70 15.7 2.55 14.5 2.40 12.5 2.26 10.7 2.15

7.0 6.0 20.1 3.06 18.2 2.84 17.0 2.70 15.7 2.55 14.5 2.40 12.5 2.18 10.7 2.07

8.6 7.5 20.1 3.06 18.2 2.84 17.0 2.70 15.7 2.55 14.5 2.40 12.5 2.18 10.7 1.96

11.2 10.0 20.1 3.06 18.2 2.84 17.0 2.70 15.7 2.55 14.5 2.40 12.5 2.18 10.7 1.95

16.4 15.0 20.1 3.06 18.2 2.84 17.0 2.70 15.7 2.55 14.5 2.40 12.5 2.18 10.7 1.95

24.0 18.0 20.1 3.06 18.2 2.84 17.0 2.70 15.7 2.55 14.5 2.40 12.5 2.18 10.7 1.95

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


20 HP (U-8MF2E8 & U-12MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 51.2 17.30 47.2 15.93 44.4 15.00 44.4 15.00 44.4 15.00 44.4 15.00 38.6 13.16

-14.7 -15.0 54.3 17.64 50.1 16.27 47.3 15.33 47.3 15.33 47.3 15.33 47.3 15.33 41.3 13.45

-9.6 -10.0 58.3 18.15 53.9 16.76 50.9 15.81 50.9 15.81 50.9 15.81 50.9 15.81 44.8 13.86

-4.4 -5.0 63.6 18.87 58.9 17.44 55.7 16.47 55.7 16.47 55.7 16.47 55.7 16.47 49.5 14.44

-1.8 -2.5 66.8 19.32 62.1 17.88 58.7 16.88 58.7 16.88 58.7 16.88 58.7 16.88 52.4 14.82

0.8 0.0 70.5 19.74 65.8 18.39 62.4 17.37 62.4 17.37 62.4 17.37 62.4 17.37 55.4 15.07

130% 2.8 2.0 73.3 19.74 69.4 18.82 65.8 17.79 65.8 17.79 65.8 17.79 65.2 16.95 55.4 14.30

6.0 5.0 78.7 19.74 72.8 18.22 67.7 16.76 67.7 16.76 67.7 16.76 65.2 15.37 55.4 12.94

7.0 6.0 80.3 19.67 72.8 17.50 67.7 16.10 67.7 16.10 67.7 16.10 65.2 14.78 55.4 12.44

8.6 7.5 80.3 18.40 72.8 16.37 67.7 15.09 67.7 15.09 67.7 15.09 65.2 13.86 55.4 11.69

11.2 10.0 80.3 16.34 72.8 14.58 67.7 13.45 67.7 13.45 67.7 13.45 65.2 12.42 55.4 10.50

16.4 15.0 80.3 12.65 72.8 11.36 67.7 10.53 67.7 10.53 67.7 10.53 65.2 9.86 55.4 8.42

24.0 18.0 80.3 10.74 72.8 9.70 67.7 9.02 67.7 9.02 67.7 9.02 65.2 8.54 55.4 7.35

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 51.3 17.15 47.3 15.79 44.5 14.89 44.5 14.89 44.5 14.89 41.1 13.79 35.6 12.18

-14.7 -15.0 54.4 17.50 50.2 16.14 47.3 15.21 47.3 15.21 47.3 15.21 43.9 14.13 38.1 12.44

-9.6 -10.0 58.3 18.01 53.9 16.62 50.9 15.69 50.9 15.69 50.9 15.69 47.6 14.57 41.3 12.82

-4.4 -5.0 63.6 18.72 59.0 17.31 55.8 16.34 55.8 16.34 55.8 16.34 52.3 15.19 45.5 13.32

-1.8 -2.5 67.0 19.18 62.1 17.75 58.8 16.76 58.8 16.76 58.8 16.76 55.3 15.59 48.2 13.68

0.8 0.0 70.9 19.70 65.8 18.26 62.3 17.26 62.3 17.26 62.3 17.26 58.8 15.99 50.0 13.54

120% 2.8 2.0 73.6 19.74 69.4 18.65 65.8 17.64 65.8 17.64 65.8 17.64 58.8 15.16 50.0 12.83

6.0 5.0 78.4 19.57 71.1 17.44 66.2 16.06 66.2 16.06 66.2 16.06 58.8 13.73 50.0 11.60

7.0 6.0 78.4 18.77 71.1 16.74 66.2 15.43 66.2 15.43 66.2 15.43 58.8 13.20 50.0 11.15

8.6 7.5 78.4 17.54 71.1 15.65 66.2 14.44 66.2 14.44 66.2 14.44 58.8 12.39 50.0 10.49

11.2 10.0 78.4 15.57 71.1 13.92 66.2 12.87 66.2 12.87 66.2 12.87 58.8 11.11 50.0 9.43

16.4 15.0 78.4 12.01 71.1 10.83 66.2 10.05 66.2 10.05 66.2 10.05 58.8 8.81 50.0 7.56

24.0 18.0 78.4 10.18 71.1 9.22 66.2 8.60 66.2 8.60 66.2 8.60 58.8 7.64 50.0 6.61

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 51.3 16.99 47.3 15.67 44.5 14.78 44.5 14.78 42.7 14.16 37.7 12.66 32.6 11.21

-14.7 -15.0 54.5 17.36 50.3 16.02 47.3 15.12 47.3 15.12 45.4 14.49 40.3 12.96 34.9 11.45

-9.6 -10.0 58.5 17.86 54.1 16.51 51.0 15.58 51.0 15.58 49.1 14.96 43.5 13.37 37.8 11.77

-4.4 -5.0 63.8 18.60 59.0 17.20 55.8 16.23 55.8 16.23 53.8 15.59 47.9 13.92 41.6 12.22

-1.8 -2.5 67.0 19.05 62.1 17.63 58.7 16.64 58.7 16.64 56.8 15.99 50.6 14.27 44.1 12.53

0.8 0.0 70.9 19.57 65.8 18.12 62.3 17.10 62.3 17.10 60.4 16.44 52.6 14.21 44.7 12.08

110% 2.8 2.0 74.1 19.74 69.4 18.49 64.6 17.03 64.6 17.03 60.5 15.61 52.6 13.48 44.7 11.45

6.0 5.0 76.5 18.67 69.4 16.67 64.6 15.38 64.6 15.38 60.5 14.13 52.6 12.21 44.7 10.35

7.0 6.0 76.5 17.89 69.4 15.99 64.6 14.78 64.6 14.78 60.5 13.58 52.6 11.73 44.7 9.95

8.6 7.5 76.5 16.71 69.4 14.95 64.6 13.82 64.6 13.82 60.5 12.72 52.6 11.01 44.7 9.36

11.2 10.0 76.5 14.81 69.4 13.28 64.6 12.30 64.6 12.30 60.5 11.36 52.6 9.87 44.7 8.42

16.4 15.0 76.5 11.39 69.4 10.31 64.6 9.59 64.6 9.59 60.5 8.94 52.6 7.84 44.7 6.75

24.0 18.0 76.5 9.63 69.4 8.77 64.6 8.19 64.6 8.19 60.5 7.71 52.6 6.81 44.7 5.91

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 51.5 16.85 47.4 15.55 44.5 14.66 41.7 13.78 38.8 12.87 34.3 11.55 29.6 10.25

-14.7 -15.0 54.6 17.22 50.3 15.90 47.4 15.00 44.4 14.10 41.3 13.18 36.6 11.82 31.7 10.45

-9.6 -10.0 58.6 17.74 54.1 16.40 51.0 15.48 47.8 14.55 44.6 13.59 39.6 12.17 34.3 10.74

-4.4 -5.0 63.8 18.46 59.0 17.08 55.8 16.13 52.4 15.16 48.9 14.17 43.5 12.66 37.7 11.14

-1.8 -2.5 67.1 18.92 62.2 17.50 58.8 16.53 55.2 15.54 51.6 14.52 45.9 12.99 39.7 11.32

0.8 0.0 71.0 19.42 65.8 17.96 62.3 16.96 58.3 15.83 53.7 14.48 46.7 12.53 39.7 10.70

100% 2.8 2.0 74.5 19.74 67.7 17.67 63.0 16.31 58.3 14.99 53.7 13.72 46.7 11.89 39.7 10.15

6.0 5.0 74.7 17.79 67.7 15.93 63.0 14.72 58.3 13.56 53.7 12.42 46.7 10.77 39.7 9.17

7.0 6.0 74.7 17.05 67.7 15.27 63.0 14.10 58.3 13.01 53.7 11.93 46.7 10.35 39.7 8.81

8.6 7.5 74.7 15.90 67.7 14.27 63.0 13.21 58.3 12.18 53.7 11.18 46.7 9.71 39.7 8.29

11.2 10.0 74.7 14.07 67.7 12.66 63.0 11.75 58.3 10.86 53.7 9.98 46.7 8.71 39.7 7.47

16.4 15.0 74.7 10.80 67.7 9.80 63.0 9.14 58.3 8.50 53.7 7.87 46.7 6.92 39.7 6.01

9 24.0 18.0 74.7 9.24 67.7 8.46 63.0 7.92 58.3 7.40 53.7 6.88 46.7 6.11 39.7 5.32
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


20 HP (U-8MF2E8 & U-12MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 52.0 16.34 47.8 15.13 44.9 14.30 42.0 13.48 38.9 12.65 34.3 11.42 29.7 10.22

-14.7 -15.0 55.1 16.75 50.7 15.51 47.7 14.66 44.6 13.80 41.5 12.94 36.7 11.67 31.7 10.39

-9.6 -10.0 59.1 17.29 54.5 16.02 51.3 15.14 48.0 14.24 44.7 13.35 39.6 12.00 34.2 10.65

-4.4 -5.0 64.3 18.02 59.3 16.68 55.9 15.76 52.5 14.82 48.3 13.69 42.0 12.01 35.7 10.39

-1.8 -2.5 67.2 18.29 60.9 16.48 56.7 15.31 52.5 14.17 48.3 13.06 42.0 11.45 35.7 9.93

0.8 0.0 67.2 17.19 60.9 15.50 56.7 14.41 52.5 13.34 48.3 12.30 42.0 10.80 35.7 9.35

90% 2.8 2.0 67.2 16.20 60.9 14.64 56.7 13.61 52.5 12.62 48.3 11.63 42.0 10.22 35.7 8.84

6.0 5.0 67.2 14.51 60.9 13.14 56.7 12.25 52.5 11.36 48.3 10.49 42.0 9.21 35.7 7.92

7.0 6.0 67.2 13.87 60.9 12.58 56.7 11.73 52.5 10.89 48.3 10.07 42.0 8.83 35.7 7.61

8.6 7.5 67.2 12.90 60.9 11.72 56.7 10.94 52.5 10.18 48.3 9.42 42.0 8.28 35.7 7.16

11.2 10.0 67.2 11.35 60.9 10.35 56.7 9.70 52.5 9.04 48.3 8.39 42.0 7.42 35.7 6.44

16.4 15.0 67.2 8.60 60.9 7.92 56.7 7.47 52.5 7.02 48.3 6.57 42.0 5.88 35.7 5.17

24.0 18.0 67.2 8.40 60.9 7.70 56.7 7.23 52.5 6.75 48.3 6.29 42.0 5.58 35.7 4.88

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 52.7 16.02 48.4 14.88 45.4 14.11 42.4 13.34 39.3 12.58 34.7 11.44 29.8 10.31

-14.7 -15.0 55.9 16.45 51.4 15.28 48.3 14.48 45.1 13.68 41.9 12.87 36.9 11.67 31.8 10.43

-9.6 -10.0 59.7 16.93 54.1 15.43 50.4 14.44 46.7 13.47 42.9 12.52 37.4 11.12 31.8 9.79

-4.4 -5.0 59.7 15.64 54.1 14.26 50.4 13.35 46.7 12.46 42.9 11.60 37.4 10.34 31.8 9.09

-1.8 -2.5 59.7 14.81 54.1 13.51 50.4 12.66 46.7 11.83 42.9 11.00 37.4 9.80 31.8 8.63

0.8 0.0 59.7 13.87 54.1 12.68 50.4 11.89 46.7 11.11 42.9 10.35 37.4 9.22 31.8 8.11

80% 2.8 2.0 59.7 13.04 54.1 11.94 50.4 11.21 46.7 10.49 42.9 9.77 37.4 8.70 31.8 7.61

6.0 5.0 59.7 11.62 54.1 10.67 50.4 10.04 46.7 9.39 42.9 8.76 37.4 7.77 31.8 6.78

7.0 6.0 59.7 11.08 54.1 10.19 50.4 9.59 46.7 8.98 42.9 8.38 37.4 7.46 31.8 6.51

8.6 7.5 59.7 10.28 54.1 9.48 50.4 8.93 46.7 8.38 42.9 7.83 37.4 6.98 31.8 6.12

11.2 10.0 59.7 9.00 54.1 8.33 50.4 7.88 46.7 7.43 42.9 6.97 37.4 6.25 31.8 5.51

16.4 15.0 59.7 7.57 54.1 6.94 50.4 6.53 46.7 6.11 42.9 5.68 37.4 5.06 31.8 4.43

24.0 18.0 59.7 7.57 54.1 6.94 50.4 6.53 46.7 6.11 42.9 5.68 37.4 5.06 31.8 4.43

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 52.3 15.31 47.4 14.11 44.1 13.32 40.8 12.56 37.5 11.80 32.7 10.70 27.8 9.63

-14.7 -15.0 52.3 14.62 47.4 13.48 44.1 12.72 40.8 11.97 37.5 11.24 32.7 10.15 27.8 9.08

-9.6 -10.0 52.3 13.68 47.4 12.63 44.1 11.96 40.8 11.28 37.5 10.62 32.7 9.57 27.8 8.52

-4.4 -5.0 52.3 12.48 47.4 11.55 44.1 10.93 40.8 10.32 37.5 9.71 32.7 8.80 27.8 7.87

-1.8 -2.5 52.3 11.77 47.4 10.91 44.1 10.34 40.8 9.77 37.5 9.19 32.7 8.32 27.8 7.43

0.8 0.0 52.3 11.00 47.4 10.21 44.1 9.67 40.8 9.15 37.5 8.62 32.7 7.80 27.8 6.94

70% 2.8 2.0 52.3 10.29 47.4 9.57 44.1 9.09 40.8 8.60 37.5 8.09 32.7 7.32 27.8 6.44

6.0 5.0 52.3 9.12 47.4 8.52 44.1 8.08 40.8 7.64 37.5 7.19 32.7 6.47 27.8 5.74

7.0 6.0 52.3 8.69 47.4 8.11 44.1 7.71 40.8 7.30 37.5 6.88 32.7 6.20 27.8 5.51

8.6 7.5 52.3 8.02 47.4 7.52 44.1 7.16 40.8 6.80 37.5 6.42 32.7 5.81 27.8 5.17

11.2 10.0 52.3 6.97 47.4 6.57 44.1 6.29 40.8 6.01 37.5 5.70 32.7 5.19 27.8 4.65

16.4 15.0 52.3 6.73 47.4 6.18 44.1 5.82 40.8 5.46 37.5 5.09 32.7 4.54 27.8 3.99

24.0 18.0 52.3 6.73 47.4 6.18 44.1 5.82 40.8 5.46 37.5 5.09 32.7 4.54 27.8 3.99

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 44.8 12.31 40.6 11.56 37.8 11.01 35.0 10.46 32.2 9.93 28.0 9.12 23.8 8.32

-14.7 -15.0 44.8 11.60 40.6 10.91 37.8 10.45 35.0 9.98 32.2 9.46 28.0 8.64 23.8 7.84

-9.6 -10.0 44.8 10.79 40.6 10.15 37.8 9.73 35.0 9.29 32.2 8.84 28.0 8.15 23.8 7.35

-4.4 -5.0 44.8 9.79 40.6 9.22 37.8 8.84 35.0 8.46 32.2 8.05 28.0 7.42 23.8 6.74

-1.8 -2.5 44.8 9.19 40.6 8.69 37.8 8.33 35.0 7.97 32.2 7.59 28.0 6.99 23.8 6.30

0.8 0.0 44.8 8.54 40.6 8.08 37.8 7.77 35.0 7.43 32.2 7.08 28.0 6.50 23.8 5.78

60% 2.8 2.0 44.8 7.98 40.6 7.56 37.8 7.26 35.0 6.95 32.2 6.61 28.0 6.01 23.8 5.37

6.0 5.0 44.8 6.99 40.6 6.64 37.8 6.39 35.0 6.11 32.2 5.80 28.0 5.32 23.8 4.78

7.0 6.0 44.8 6.64 40.6 6.32 37.8 6.08 35.0 5.82 32.2 5.54 28.0 5.09 23.8 4.60

8.6 7.5 44.8 6.11 40.6 5.84 37.8 5.64 35.0 5.41 32.2 5.17 28.0 4.77 23.8 4.31

11.2 10.0 44.8 5.89 40.6 5.43 37.8 5.12 35.0 4.79 32.2 4.58 28.0 4.26 23.8 3.89

16.4 15.0 44.8 5.89 40.6 5.43 37.8 5.12 35.0 4.79 32.2 4.48 28.0 4.02 23.8 3.54

24.0 18.0 44.8 5.89 40.6 5.43 37.8 5.12 35.0 4.79 32.2 4.48 28.0 4.02 23.8 3.54

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


20 HP (U-8MF2E8 & U-12MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 37.4 9.67 33.8 9.28 31.5 8.98 29.2 8.64 26.8 8.26 23.3 7.68 19.8 7.09

-14.7 -15.0 37.4 9.08 33.8 8.71 31.5 8.46 29.2 8.18 26.8 7.87 23.3 7.28 19.8 6.67

-9.6 -10.0 37.4 8.39 33.8 8.07 31.5 7.83 29.2 7.57 26.8 7.29 23.3 6.82 19.8 6.25

-4.4 -5.0 37.4 7.54 33.8 7.28 31.5 7.06 29.2 6.84 26.8 6.60 23.3 6.18 19.8 5.58

-1.8 -2.5 37.4 7.05 33.8 6.81 31.5 6.63 29.2 6.42 26.8 6.19 23.3 5.74 19.8 5.15

0.8 0.0 37.4 6.53 33.8 6.30 31.5 6.13 29.2 5.95 26.8 5.68 23.3 5.23 19.8 4.72

50% 2.8 2.0 37.4 6.05 33.8 5.87 31.5 5.68 29.2 5.47 26.8 5.23 23.3 4.84 19.8 4.39

6.0 5.0 37.4 5.22 33.8 5.05 31.5 4.92 29.2 4.77 26.8 4.58 23.3 4.27 19.8 3.92

7.0 6.0 37.4 5.06 33.8 4.79 31.5 4.68 29.2 4.54 26.8 4.39 23.3 4.10 19.8 3.76

8.6 7.5 37.4 5.06 33.8 4.67 31.5 4.41 29.2 4.22 26.8 4.09 23.3 3.84 19.8 3.55

11.2 10.0 37.4 5.06 33.8 4.67 31.5 4.41 29.2 4.15 26.8 3.89 23.3 3.50 19.8 3.20

16.4 15.0 37.4 5.06 33.8 4.67 31.5 4.41 29.2 4.15 26.8 3.89 23.3 3.50 19.8 3.10

24.0 18.0 37.4 5.06 33.8 4.67 31.5 4.41 29.2 4.15 26.8 3.89 23.3 3.50 19.8 3.10

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 29.9 7.53 27.1 7.35 25.2 7.21 23.3 7.02 21.5 6.75 18.6 6.35 15.9 5.92

-14.7 -15.0 29.9 7.04 27.1 6.88 25.2 6.75 23.3 6.60 21.5 6.42 18.6 6.01 15.9 5.56

-9.6 -10.0 29.9 6.44 27.1 6.33 25.2 6.22 23.3 6.09 21.5 5.92 18.6 5.61 15.9 5.13

-4.4 -5.0 29.9 5.74 27.1 5.65 25.2 5.57 23.3 5.46 21.5 5.29 18.6 4.89 15.9 4.44

-1.8 -2.5 29.9 5.33 27.1 5.26 25.2 5.19 23.3 5.02 21.5 4.82 18.6 4.48 15.9 4.10

0.8 0.0 29.9 4.89 27.1 4.78 25.2 4.67 23.3 4.53 21.5 4.37 18.6 4.09 15.9 3.76

40% 2.8 2.0 29.9 4.43 27.1 4.34 25.2 4.26 23.3 4.16 21.5 4.03 18.6 3.79 15.9 3.51

6.0 5.0 29.9 4.23 27.1 3.91 25.2 3.71 23.3 3.62 21.5 3.54 18.6 3.37 15.9 3.14

7.0 6.0 29.9 4.23 27.1 3.91 25.2 3.71 23.3 3.50 21.5 3.38 18.6 3.23 15.9 3.03

8.6 7.5 29.9 4.23 27.1 3.91 25.2 3.71 23.3 3.50 21.5 3.29 18.6 3.03 15.9 2.85

11.2 10.0 29.9 4.23 27.1 3.91 25.2 3.71 23.3 3.50 21.5 3.29 18.6 2.98 15.9 2.66

16.4 15.0 29.9 4.23 27.1 3.91 25.2 3.71 23.3 3.50 21.5 3.29 18.6 2.98 15.9 2.66

24.0 18.0 29.9 4.23 27.1 3.91 25.2 3.71 23.3 3.50 21.5 3.29 18.6 2.98 15.9 2.66

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 22.4 5.75 20.3 5.70 18.9 5.63 17.5 5.51 16.1 5.34 14.0 5.06 11.9 4.75

-14.7 -15.0 22.4 5.36 20.3 5.33 18.9 5.26 17.5 5.17 16.1 5.06 14.0 4.78 11.9 4.41

-9.6 -10.0 22.4 4.88 20.3 4.88 18.9 4.84 17.5 4.77 16.1 4.60 14.0 4.29 11.9 3.92

-4.4 -5.0 22.4 4.30 20.3 4.22 18.9 4.13 17.5 4.03 16.1 3.91 14.0 3.68 11.9 3.40

-1.8 -2.5 22.4 3.85 20.3 3.81 18.9 3.75 17.5 3.67 16.1 3.57 14.0 3.38 11.9 3.14

0.8 0.0 22.4 3.41 20.3 3.41 18.9 3.37 17.5 3.33 16.1 3.24 14.0 3.10 11.9 2.90

30% 2.8 2.0 22.4 3.38 20.3 3.16 18.9 3.09 17.5 3.06 16.1 3.00 14.0 2.89 11.9 2.72

6.0 5.0 22.4 3.38 20.3 3.16 18.9 3.00 17.5 2.85 16.1 2.68 14.0 2.58 11.9 2.45

7.0 6.0 22.4 3.38 20.3 3.16 18.9 3.00 17.5 2.85 16.1 2.68 14.0 2.48 11.9 2.37

8.6 7.5 22.4 3.38 20.3 3.16 18.9 3.00 17.5 2.85 16.1 2.68 14.0 2.45 11.9 2.24

11.2 10.0 22.4 3.38 20.3 3.16 18.9 3.00 17.5 2.85 16.1 2.68 14.0 2.45 11.9 2.21

16.4 15.0 22.4 3.38 20.3 3.16 18.9 3.00 17.5 2.85 16.1 2.68 14.0 2.45 11.9 2.21

24.0 18.0 22.4 3.38 20.3 3.16 18.9 3.00 17.5 2.85 16.1 2.68 14.0 2.45 11.9 2.21

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


22 HP (U-8MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 54.0 17.70 49.7 16.35 46.9 15.43 46.9 15.43 46.9 15.43 46.9 15.43 40.7 13.64

-14.7 -15.0 57.3 18.04 52.9 16.69 49.9 15.76 49.9 15.76 49.9 15.76 49.9 15.76 43.6 13.94

-9.6 -10.0 61.5 18.53 56.9 17.17 53.7 16.23 53.7 16.23 53.7 16.23 53.7 16.23 47.3 14.36

-4.4 -5.0 67.0 19.25 62.2 17.86 58.8 16.90 58.8 16.90 58.8 16.90 58.8 16.90 52.2 14.95

-1.8 -2.5 70.3 19.63 65.6 18.30 62.0 17.32 62.0 17.32 62.0 17.32 62.0 17.32 55.3 15.34

0.8 0.0 73.3 19.63 69.5 18.77 65.8 17.77 65.8 17.77 65.8 17.77 65.8 17.77 59.3 15.76

130% 2.8 2.0 76.6 19.63 73.3 19.12 69.6 18.10 69.6 18.10 69.6 18.10 69.6 18.10 60.7 15.37

6.0 5.0 82.7 19.63 79.7 19.46 74.2 17.92 74.2 17.92 74.2 17.92 71.4 16.49 60.7 13.94

7.0 6.0 84.9 19.63 79.7 18.68 74.2 17.21 74.2 17.21 74.2 17.21 71.4 15.86 60.7 13.39

8.6 7.5 87.9 19.60 79.7 17.49 74.2 16.13 74.2 16.13 74.2 16.13 71.4 14.89 60.7 12.59

11.2 10.0 87.9 17.40 79.7 15.55 74.2 14.38 74.2 14.38 74.2 14.38 71.4 13.33 60.7 11.33

16.4 15.0 87.9 13.44 79.7 12.11 74.2 11.25 74.2 11.25 74.2 11.25 71.4 10.59 60.7 9.08

24.0 18.0 87.9 11.39 79.7 10.33 74.2 9.63 74.2 9.63 74.2 9.63 71.4 9.18 60.7 7.93

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 54.1 17.55 49.8 16.22 46.9 15.31 46.9 15.31 46.9 15.31 43.4 14.27 37.5 12.62

-14.7 -15.0 57.4 17.89 52.9 16.56 49.9 15.64 49.9 15.64 49.9 15.64 46.4 14.59 40.2 12.90

-9.6 -10.0 61.5 18.39 56.9 17.05 53.8 16.13 53.8 16.13 53.8 16.13 50.2 15.05 43.6 13.29

-4.4 -5.0 67.1 19.12 62.2 17.74 58.9 16.79 58.9 16.79 58.9 16.79 55.2 15.69 48.1 13.82

-1.8 -2.5 70.7 19.58 65.6 18.17 62.0 17.20 62.0 17.20 62.0 17.20 58.4 16.08 51.0 14.16

0.8 0.0 73.8 19.63 69.5 18.62 65.8 17.61 65.8 17.61 65.8 17.61 62.3 16.47 54.6 14.53

120% 2.8 2.0 77.0 19.63 73.3 18.94 69.5 17.94 69.5 17.94 69.5 17.94 64.4 16.28 54.7 13.82

6.0 5.0 83.1 19.63 77.8 18.63 72.5 17.20 72.5 17.20 72.5 17.20 64.4 14.77 54.7 12.52

7.0 6.0 85.0 19.63 77.8 17.88 72.5 16.50 72.5 16.50 72.5 16.50 64.4 14.19 54.7 12.03

8.6 7.5 85.8 18.69 77.8 16.72 72.5 15.45 72.5 15.45 72.5 15.45 64.4 13.32 54.7 11.31

11.2 10.0 85.8 16.56 77.8 14.86 72.5 13.76 72.5 13.76 72.5 13.76 64.4 11.94 54.7 10.18

16.4 15.0 85.8 12.77 77.8 11.54 72.5 10.75 72.5 10.75 72.5 10.75 64.4 9.48 54.7 8.18

24.0 18.0 85.8 10.80 77.8 9.83 72.5 9.20 72.5 9.20 72.5 9.20 64.4 8.23 54.7 7.16

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 54.2 17.40 49.9 16.10 47.0 15.19 47.0 15.19 45.0 14.60 39.8 13.11 34.4 11.64

-14.7 -15.0 57.5 17.76 53.1 16.44 50.0 15.54 50.0 15.54 48.0 14.95 42.5 13.41 36.8 11.88

-9.6 -10.0 61.7 18.27 57.0 16.94 53.8 16.02 53.8 16.02 51.8 15.42 46.0 13.82 40.0 12.22

-4.4 -5.0 67.2 18.98 62.2 17.62 58.9 16.67 58.9 16.67 56.8 16.07 50.6 14.39 44.0 12.68

-1.8 -2.5 70.7 19.45 65.6 18.06 62.0 17.08 62.0 17.08 60.0 16.46 53.5 14.74 46.6 12.99

0.8 0.0 74.2 19.63 69.5 18.44 65.8 17.44 65.8 17.44 63.8 16.82 57.0 15.07 49.0 13.03

110% 2.8 2.0 77.5 19.63 73.2 18.75 69.4 17.77 69.4 17.77 66.2 16.75 57.6 14.50 49.0 12.35

6.0 5.0 83.1 19.63 76.0 17.82 70.7 16.47 70.7 16.47 66.2 15.16 57.6 13.14 49.0 11.17

7.0 6.0 83.8 19.09 76.0 17.09 70.7 15.81 70.7 15.81 66.2 14.57 57.6 12.62 49.0 10.75

8.6 7.5 83.8 17.80 76.0 15.98 70.7 14.78 70.7 14.78 66.2 13.65 57.6 11.85 49.0 10.12

11.2 10.0 83.8 15.76 76.0 14.18 70.7 13.17 70.7 13.17 66.2 12.20 57.6 10.63 49.0 9.11

16.4 15.0 83.8 12.11 76.0 10.99 70.7 10.25 70.7 10.25 66.2 9.60 57.6 8.46 49.0 7.32

24.0 18.0 83.8 10.28 76.0 9.42 70.7 8.85 70.7 8.85 66.2 8.37 57.6 7.41 49.0 6.48

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 54.3 17.24 50.0 15.96 47.0 15.08 44.0 14.19 40.9 13.30 36.2 11.96 31.3 10.66

-14.7 -15.0 57.6 17.62 53.1 16.32 50.0 15.43 46.9 14.53 43.6 13.61 38.6 12.23 33.5 10.87

-9.6 -10.0 61.8 18.15 57.1 16.82 53.8 15.92 50.5 14.98 47.1 14.04 41.8 12.61 36.2 11.17

-4.4 -5.0 67.3 18.86 62.3 17.50 58.9 16.56 55.3 15.60 51.6 14.62 45.9 13.11 39.9 11.58

-1.8 -2.5 70.8 19.31 65.6 17.92 62.0 16.96 58.3 15.96 54.4 14.95 48.5 13.39 42.2 11.84

0.8 0.0 74.7 19.63 69.5 18.27 65.8 17.29 61.9 16.28 57.9 15.27 51.1 13.50 43.5 11.57

100% 2.8 2.0 78.0 19.63 73.2 18.57 69.0 17.47 63.9 16.08 58.8 14.74 51.1 12.80 43.5 10.96

6.0 5.0 81.8 18.98 74.1 17.03 69.0 15.78 63.9 14.54 58.8 13.35 51.1 11.60 43.5 9.92

7.0 6.0 81.8 18.18 74.1 16.32 69.0 15.10 63.9 13.97 58.8 12.82 51.1 11.16 43.5 9.54

8.6 7.5 81.8 16.96 74.1 15.25 69.0 14.15 63.9 13.06 58.8 12.02 51.1 10.48 43.5 8.98

11.2 10.0 81.8 14.99 74.1 13.53 69.0 12.58 63.9 11.64 58.8 10.74 51.1 9.41 43.5 8.09

16.4 15.0 81.8 11.49 74.1 10.46 69.0 9.78 63.9 9.12 58.8 8.47 51.1 7.49 43.5 6.52

9 24.0 18.0 81.8 10.07 74.1 9.23 69.0 8.67 63.9 8.11 58.8 7.55 51.1 6.70 43.5 5.86
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


22 HP (U-8MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 54.8 16.73 50.4 15.54 47.3 14.72 44.2 13.89 41.1 13.06 36.2 11.82 31.3 10.62

-14.7 -15.0 58.2 17.15 53.5 15.93 50.3 15.08 47.1 14.24 43.8 13.38 38.7 12.08 33.5 10.81

-9.6 -10.0 62.4 17.70 57.5 16.43 54.1 15.57 50.7 14.68 47.2 13.79 41.7 12.43 36.2 11.07

-4.4 -5.0 67.8 18.39 62.7 17.08 59.1 16.17 55.3 15.25 51.6 14.30 45.7 12.88 39.1 11.25

-1.8 -2.5 71.3 18.69 65.8 17.35 62.1 16.43 57.5 15.22 52.9 14.06 46.0 12.35 39.1 10.74

0.8 0.0 73.6 18.39 66.7 16.61 62.1 15.46 57.5 14.35 52.9 13.24 46.0 11.66 39.1 10.12

90% 2.8 2.0 73.6 17.32 66.7 15.67 62.1 14.62 57.5 13.56 52.9 12.53 46.0 11.02 39.1 9.57

6.0 5.0 73.6 15.51 66.7 14.09 62.1 13.15 57.5 12.22 52.9 11.31 46.0 9.95 39.1 8.59

7.0 6.0 73.6 14.83 66.7 13.48 62.1 12.59 57.5 11.72 52.9 10.84 46.0 9.54 39.1 8.27

8.6 7.5 73.6 13.79 66.7 12.55 62.1 11.75 57.5 10.95 52.9 10.15 46.0 8.95 39.1 7.78

11.2 10.0 73.6 12.13 66.7 11.10 62.1 10.42 57.5 9.72 52.9 9.04 46.0 8.03 39.1 7.02

16.4 15.0 73.6 9.18 66.7 8.49 62.1 8.03 57.5 7.57 52.9 7.10 46.0 6.39 39.1 5.65

24.0 18.0 73.6 9.17 66.7 8.41 62.1 7.91 57.5 7.40 52.9 6.90 46.0 6.15 39.1 5.39

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 55.6 16.40 51.0 15.28 47.9 14.51 44.7 13.76 41.5 12.99 36.5 11.84 31.5 10.71

-14.7 -15.0 59.0 16.85 54.2 15.69 50.9 14.89 47.5 14.09 44.2 13.29 38.9 12.06 33.6 10.86

-9.6 -10.0 63.3 17.43 58.2 16.20 54.6 15.37 51.1 14.51 47.0 13.50 40.9 12.03 34.8 10.60

-4.4 -5.0 65.4 16.76 59.3 15.31 55.2 14.36 51.1 13.42 47.0 12.50 40.9 11.16 34.8 9.86

-1.8 -2.5 65.4 15.87 59.3 14.51 55.2 13.62 51.1 12.73 47.0 11.87 40.9 10.60 34.8 9.35

0.8 0.0 65.4 14.87 59.3 13.62 55.2 12.79 51.1 11.97 47.0 11.17 40.9 9.97 34.8 8.79

80% 2.8 2.0 65.4 13.98 59.3 12.82 55.2 12.06 51.1 11.29 47.0 10.54 40.9 9.42 34.8 8.27

6.0 5.0 65.4 12.46 59.3 11.46 55.2 10.80 51.1 10.13 47.0 9.45 40.9 8.43 34.8 7.38

7.0 6.0 65.4 11.88 59.3 10.96 55.2 10.33 51.1 9.69 47.0 9.06 40.9 8.09 34.8 7.10

8.6 7.5 65.4 11.02 59.3 10.18 55.2 9.62 51.1 9.04 47.0 8.47 40.9 7.58 34.8 6.67

11.2 10.0 65.4 9.63 59.3 8.95 55.2 8.50 51.1 8.02 47.0 7.53 40.9 6.80 34.8 6.02

16.4 15.0 65.4 8.27 59.3 7.60 55.2 7.16 51.1 6.70 47.0 6.25 40.9 5.59 34.8 4.91

24.0 18.0 65.4 8.27 59.3 7.60 55.2 7.16 51.1 6.70 47.0 6.25 40.9 5.59 34.8 4.91

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 57.0 16.37 51.9 15.19 48.3 14.36 44.7 13.54 41.1 12.74 35.8 11.57 30.4 10.42

-14.7 -15.0 57.3 15.72 51.9 14.53 48.3 13.71 44.7 12.91 41.1 12.14 35.8 10.98 30.4 9.85

-9.6 -10.0 57.3 14.68 51.9 13.61 48.3 12.88 44.7 12.17 41.1 11.46 35.8 10.37 30.4 9.26

-4.4 -5.0 57.3 13.41 51.9 12.43 48.3 11.78 44.7 11.14 41.1 10.49 35.8 9.53 30.4 8.55

-1.8 -2.5 57.3 12.65 51.9 11.76 48.3 11.14 44.7 10.54 41.1 9.94 35.8 9.01 30.4 8.09

0.8 0.0 57.3 11.82 51.9 10.99 48.3 10.45 44.7 9.89 41.1 9.32 35.8 8.46 30.4 7.57

70% 2.8 2.0 57.3 11.08 51.9 10.33 48.3 9.82 44.7 9.30 41.1 8.77 35.8 7.96 30.4 7.04

6.0 5.0 57.3 9.82 51.9 9.18 48.3 8.74 44.7 8.27 41.1 7.81 35.8 7.05 30.4 6.27

7.0 6.0 57.3 9.35 51.9 8.76 48.3 8.34 44.7 7.91 41.1 7.46 35.8 6.76 30.4 6.02

8.6 7.5 57.3 8.64 51.9 8.12 48.3 7.75 44.7 7.37 41.1 6.98 35.8 6.34 30.4 5.68

11.2 10.0 57.3 7.50 51.9 7.11 48.3 6.83 44.7 6.52 41.1 6.19 35.8 5.68 30.4 5.12

16.4 15.0 57.3 7.38 51.9 6.80 48.3 6.40 44.7 6.01 41.1 5.62 35.8 5.03 30.4 4.44

24.0 18.0 57.3 7.38 51.9 6.80 48.3 6.40 44.7 6.01 41.1 5.62 35.8 5.03 30.4 4.44

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 49.1 13.26 44.4 12.47 41.4 11.90 38.4 11.31 35.3 10.74 30.6 9.88 26.1 9.03

-14.7 -15.0 49.1 12.50 44.4 11.78 41.4 11.28 38.4 10.78 35.3 10.24 30.6 9.39 26.1 8.52

-9.6 -10.0 49.1 11.61 44.4 10.96 41.4 10.51 38.4 10.04 35.3 9.57 30.6 8.85 26.1 8.00

-4.4 -5.0 49.1 10.54 44.4 9.97 41.4 9.57 38.4 9.15 35.3 8.73 30.6 8.06 26.1 7.35

-1.8 -2.5 49.1 9.92 44.4 9.39 41.4 9.01 38.4 8.64 35.3 8.24 30.6 7.61 26.1 6.89

0.8 0.0 49.1 9.23 44.4 8.74 41.4 8.41 38.4 8.06 35.3 7.69 30.6 7.10 26.1 6.33

60% 2.8 2.0 49.1 8.61 44.4 8.18 41.4 7.88 38.4 7.55 35.3 7.20 30.6 6.57 26.1 5.89

6.0 5.0 49.1 7.57 44.4 7.20 41.4 6.95 38.4 6.64 35.3 6.33 30.6 5.81 26.1 5.25

7.0 6.0 49.1 7.19 44.4 6.86 41.4 6.61 38.4 6.34 35.3 6.06 30.6 5.59 26.1 5.06

8.6 7.5 49.1 6.61 44.4 6.34 41.4 6.13 38.4 5.90 35.3 5.65 30.6 5.24 26.1 4.77

11.2 10.0 49.1 6.48 44.4 5.98 41.4 5.63 38.4 5.30 35.3 5.01 30.6 4.68 26.1 4.30

16.4 15.0 49.1 6.48 44.4 5.98 41.4 5.63 38.4 5.30 35.3 4.97 30.6 4.47 26.1 3.96

24.0 18.0 49.1 6.48 44.4 5.98 41.4 5.63 38.4 5.30 35.3 4.97 30.6 4.47 26.1 3.96

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


22 HP (U-8MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 40.9 10.45 37.1 10.03 34.5 9.72 31.9 9.38 29.4 8.97 25.5 8.35 21.7 7.72

-14.7 -15.0 40.9 9.82 37.1 9.44 34.5 9.17 31.9 8.86 29.4 8.55 25.5 7.93 21.7 7.28

-9.6 -10.0 40.9 9.08 37.1 8.74 34.5 8.49 31.9 8.23 29.4 7.93 25.5 7.44 21.7 6.83

-4.4 -5.0 40.9 8.17 37.1 7.88 34.5 7.67 31.9 7.44 29.4 7.19 25.5 6.75 21.7 6.13

-1.8 -2.5 40.9 7.66 37.1 7.40 34.5 7.20 31.9 6.99 29.4 6.75 25.5 6.28 21.7 5.66

0.8 0.0 40.9 7.08 37.1 6.86 34.5 6.69 31.9 6.49 29.4 6.22 25.5 5.74 21.7 5.19

50% 2.8 2.0 40.9 6.58 37.1 6.39 34.5 6.21 31.9 5.98 29.4 5.74 25.5 5.32 21.7 4.85

6.0 5.0 40.9 5.68 37.1 5.53 34.5 5.39 31.9 5.22 29.4 5.04 25.5 4.73 21.7 4.33

7.0 6.0 40.9 5.59 37.1 5.25 34.5 5.13 31.9 5.00 29.4 4.83 25.5 4.53 21.7 4.18

8.6 7.5 40.9 5.59 37.1 5.16 34.5 4.88 31.9 4.64 29.4 4.50 25.5 4.26 21.7 3.94

11.2 10.0 40.9 5.59 37.1 5.16 34.5 4.88 31.9 4.61 29.4 4.32 25.5 3.90 21.7 3.56

16.4 15.0 40.9 5.59 37.1 5.16 34.5 4.88 31.9 4.61 29.4 4.32 25.5 3.90 21.7 3.49

24.0 18.0 40.9 5.59 37.1 5.16 34.5 4.88 31.9 4.61 29.4 4.32 25.5 3.90 21.7 3.49

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 32.7 8.17 29.7 7.99 27.6 7.84 25.5 7.64 23.5 7.37 20.4 6.93 17.4 6.48

-14.7 -15.0 32.7 7.64 29.7 7.49 27.6 7.35 25.5 7.19 23.5 6.99 20.4 6.57 17.4 6.09

-9.6 -10.0 32.7 7.01 29.7 6.90 27.6 6.80 25.5 6.64 23.5 6.48 20.4 6.15 17.4 5.65

-4.4 -5.0 32.7 6.27 29.7 6.18 27.6 6.09 25.5 5.98 23.5 5.80 20.4 5.39 17.4 4.91

-1.8 -2.5 32.7 5.83 29.7 5.75 27.6 5.68 25.5 5.51 23.5 5.30 20.4 4.95 17.4 4.55

0.8 0.0 32.7 5.35 29.7 5.24 27.6 5.13 25.5 5.00 23.5 4.83 20.4 4.53 17.4 4.18

40% 2.8 2.0 32.7 4.86 29.7 4.79 27.6 4.70 25.5 4.59 23.5 4.45 20.4 4.21 17.4 3.91

6.0 5.0 32.7 4.68 29.7 4.35 27.6 4.12 25.5 4.02 23.5 3.93 20.4 3.74 17.4 3.52

7.0 6.0 32.7 4.68 29.7 4.35 27.6 4.12 25.5 3.90 23.5 3.76 20.4 3.61 17.4 3.38

8.6 7.5 32.7 4.68 29.7 4.35 27.6 4.12 25.5 3.90 23.5 3.68 20.4 3.40 17.4 3.20

11.2 10.0 32.7 4.68 29.7 4.35 27.6 4.12 25.5 3.90 23.5 3.68 20.4 3.34 17.4 3.00

16.4 15.0 32.7 4.68 29.7 4.35 27.6 4.12 25.5 3.90 23.5 3.68 20.4 3.34 17.4 3.00

24.0 18.0 32.7 4.68 29.7 4.35 27.6 4.12 25.5 3.90 23.5 3.68 20.4 3.34 17.4 3.00

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 24.6 6.30 22.2 6.24 20.7 6.16 19.2 6.04 17.7 5.86 15.3 5.56 13.0 5.24

-14.7 -15.0 24.6 5.86 22.2 5.83 20.7 5.77 19.2 5.68 17.7 5.56 15.3 5.25 13.0 4.89

-9.6 -10.0 24.6 5.36 22.2 5.35 20.7 5.32 19.2 5.24 17.7 5.07 15.3 4.74 13.0 4.35

-4.4 -5.0 24.6 4.74 22.2 4.65 20.7 4.58 19.2 4.45 17.7 4.33 15.3 4.09 13.0 3.79

-1.8 -2.5 24.6 4.26 22.2 4.21 20.7 4.15 19.2 4.08 17.7 3.97 15.3 3.78 13.0 3.52

0.8 0.0 24.6 3.81 22.2 3.79 20.7 3.76 19.2 3.70 17.7 3.62 15.3 3.47 13.0 3.26

30% 2.8 2.0 24.6 3.79 22.2 3.53 20.7 3.46 19.2 3.41 17.7 3.37 15.3 3.25 13.0 3.07

6.0 5.0 24.6 3.79 22.2 3.53 20.7 3.37 19.2 3.20 17.7 3.04 15.3 2.91 13.0 2.78

7.0 6.0 24.6 3.79 22.2 3.53 20.7 3.37 19.2 3.20 17.7 3.04 15.3 2.81 13.0 2.69

8.6 7.5 24.6 3.79 22.2 3.53 20.7 3.37 19.2 3.20 17.7 3.04 15.3 2.78 13.0 2.55

11.2 10.0 24.6 3.79 22.2 3.53 20.7 3.37 19.2 3.20 17.7 3.04 15.3 2.78 13.0 2.54

16.4 15.0 24.6 3.79 22.2 3.53 20.7 3.37 19.2 3.20 17.7 3.04 15.3 2.78 13.0 2.54

24.0 18.0 24.6 3.79 22.2 3.53 20.7 3.37 19.2 3.20 17.7 3.04 15.3 2.78 13.0 2.54

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


24 HP (U-8MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 58.7 20.75 54.1 19.15 50.9 18.04 50.9 18.04 50.9 18.04 50.9 18.04 44.3 15.87

-14.7 -15.0 62.3 21.13 57.5 19.53 54.2 18.42 54.2 18.42 54.2 18.42 54.2 18.42 47.4 16.23

-9.6 -10.0 66.9 21.71 61.8 20.09 58.4 18.98 58.4 18.98 58.4 18.98 58.4 18.98 51.5 16.73

-4.4 -5.0 72.9 22.55 67.6 20.89 64.0 19.77 64.0 19.77 64.0 19.77 64.0 19.77 56.9 17.44

-1.8 -2.5 76.7 23.08 71.3 21.42 67.5 20.26 67.5 20.26 67.5 20.26 67.5 20.26 60.4 17.89

0.8 0.0 81.1 23.66 75.6 22.02 71.7 20.82 71.7 20.82 71.7 20.82 71.7 20.82 64.6 18.42

130% 2.8 2.0 84.5 23.66 79.7 22.44 75.7 21.26 75.7 21.26 75.7 21.26 75.7 21.26 67.3 18.36

6.0 5.0 91.1 23.66 87.9 23.35 82.2 21.62 82.2 21.62 82.2 21.62 79.2 19.78 67.3 16.65

7.0 6.0 93.9 23.66 88.4 22.59 82.2 20.78 82.2 20.78 82.2 20.78 79.2 19.02 67.3 16.00

8.6 7.5 97.2 23.66 88.4 21.15 82.2 19.47 82.2 19.47 82.2 19.47 79.2 17.85 67.3 15.05

11.2 10.0 97.5 21.15 88.4 18.86 82.2 17.38 82.2 17.38 82.2 17.38 79.2 16.02 67.3 13.54

16.4 15.0 97.5 16.40 88.4 14.71 82.2 13.63 82.2 13.63 82.2 13.63 79.2 12.72 67.3 10.87

24.0 18.0 97.5 13.94 88.4 12.58 82.2 11.70 82.2 11.70 82.2 11.70 79.2 11.05 67.3 9.50

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 58.8 20.55 54.2 18.98 51.0 17.89 51.0 17.89 51.0 17.89 47.2 16.63 40.9 14.69

-14.7 -15.0 62.4 20.95 57.6 19.38 54.3 18.29 54.3 18.29 54.3 18.29 50.5 17.02 43.8 15.02

-9.6 -10.0 66.9 21.55 61.9 19.95 58.4 18.84 58.4 18.84 58.4 18.84 54.6 17.56 47.5 15.47

-4.4 -5.0 73.0 22.39 67.7 20.77 64.0 19.62 64.0 19.62 64.0 19.62 60.1 18.29 52.4 16.09

-1.8 -2.5 76.8 22.91 71.3 21.26 67.5 20.11 67.5 20.11 67.5 20.11 63.6 18.78 55.5 16.51

0.8 0.0 81.3 23.53 75.6 21.84 71.6 20.64 71.6 20.64 71.6 20.64 67.9 19.27 59.4 16.96

120% 2.8 2.0 85.0 23.66 79.7 22.24 75.7 21.06 75.7 21.06 75.7 21.06 71.4 19.51 60.7 16.49

6.0 5.0 91.6 23.66 86.3 22.51 80.3 20.73 80.3 20.73 80.3 20.73 71.4 17.69 60.7 14.94

7.0 6.0 93.9 23.66 86.3 21.60 80.3 19.91 80.3 19.91 80.3 19.91 71.4 17.00 60.7 14.36

8.6 7.5 95.2 22.68 86.3 20.22 80.3 18.66 80.3 18.66 80.3 18.66 71.4 15.96 60.7 13.52

11.2 10.0 95.2 20.13 86.3 18.00 80.3 16.63 80.3 16.63 80.3 16.63 71.4 14.32 60.7 12.16

16.4 15.0 95.2 15.58 86.3 14.01 80.3 13.01 80.3 13.01 80.3 13.01 71.4 11.39 60.7 9.77

24.0 18.0 95.2 13.21 86.3 11.96 80.3 11.16 80.3 11.16 80.3 11.16 71.4 9.88 60.7 8.55

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 58.9 20.37 54.2 18.82 51.1 17.76 51.1 17.76 49.0 17.05 43.3 15.27 37.5 13.52

-14.7 -15.0 62.5 20.78 57.7 19.24 54.3 18.16 54.3 18.16 52.2 17.44 46.3 15.63 40.1 13.81

-9.6 -10.0 67.1 21.39 62.0 19.80 58.5 18.71 58.5 18.71 56.4 18.00 50.0 16.11 43.5 14.21

-4.4 -5.0 73.1 22.22 67.8 20.60 64.0 19.49 64.0 19.49 61.9 18.75 55.1 16.78 47.9 14.78

-1.8 -2.5 76.9 22.75 71.4 21.11 67.5 19.97 67.5 19.97 65.3 19.24 58.2 17.20 50.8 15.14

0.8 0.0 81.4 23.33 75.7 21.64 71.6 20.46 71.6 20.46 69.5 19.69 62.1 17.64 54.3 15.52

110% 2.8 2.0 85.5 23.66 79.7 22.02 75.6 20.86 75.6 20.86 73.4 20.11 63.9 17.34 54.3 14.72

6.0 5.0 92.0 23.66 84.2 21.51 78.4 19.86 78.4 19.86 73.4 18.22 63.9 15.72 54.3 13.34

7.0 6.0 92.9 23.13 84.2 20.66 78.4 19.06 78.4 19.06 73.4 17.51 63.9 15.11 54.3 12.81

8.6 7.5 92.9 21.60 84.2 19.31 78.4 17.84 78.4 17.84 73.4 16.42 63.9 14.20 54.3 12.07

11.2 10.0 92.9 19.15 84.2 17.16 78.4 15.89 78.4 15.89 73.4 14.67 63.9 12.74 54.3 10.87

16.4 15.0 92.9 14.78 84.2 13.34 78.4 12.43 78.4 12.43 73.4 11.58 63.9 10.14 54.3 8.74

24.0 18.0 92.9 12.50 84.2 11.38 78.4 10.63 78.4 10.63 73.4 9.97 63.9 8.81 54.3 7.66

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 59.1 20.18 54.3 18.67 51.2 17.64 47.9 16.58 44.5 15.51 39.4 13.92 34.0 12.38

-14.7 -15.0 62.7 20.62 57.8 19.09 54.4 18.04 50.9 16.96 47.5 15.89 42.1 14.25 36.4 12.63

-9.6 -10.0 67.2 21.22 62.1 19.67 58.6 18.58 54.9 17.49 51.3 16.38 45.5 14.69 39.5 12.99

-4.4 -5.0 73.2 22.08 67.8 20.48 64.0 19.36 60.2 18.22 56.2 17.05 50.0 15.27 43.5 13.49

-1.8 -2.5 77.0 22.60 71.4 20.97 67.5 19.84 63.5 18.67 59.3 17.47 52.8 15.63 46.1 13.80

0.8 0.0 81.5 23.11 75.7 21.44 71.5 20.27 67.4 19.07 63.0 17.85 56.3 16.02 48.2 13.76

100% 2.8 2.0 85.7 23.48 79.7 21.82 75.6 20.66 70.8 19.33 65.2 17.67 56.7 15.31 48.2 13.05

6.0 5.0 90.7 22.99 82.2 20.57 76.5 19.00 70.8 17.49 65.2 16.02 56.7 13.87 48.2 11.81

7.0 6.0 90.7 22.02 82.2 19.73 76.5 18.20 70.8 16.80 65.2 15.38 56.7 13.34 48.2 11.36

8.6 7.5 90.7 20.55 82.2 18.44 76.5 17.05 70.8 15.72 65.2 14.43 56.7 12.52 48.2 10.70

11.2 10.0 90.7 18.20 82.2 16.36 76.5 15.18 70.8 14.03 65.2 12.90 56.7 11.25 48.2 9.65

16.4 15.0 90.7 14.00 82.2 12.69 76.5 11.85 70.8 11.01 65.2 10.19 56.7 8.97 48.2 7.77

9 24.0 18.0 90.7 11.85 82.2 10.85 76.5 10.17 70.8 9.52 65.2 8.85 56.7 7.86 48.2 6.86
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


24 HP (U-8MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 59.6 19.57 54.8 18.15 51.5 17.18 48.1 16.20 44.7 15.22 39.5 13.76 34.0 12.32

-14.7 -15.0 63.2 20.04 58.1 18.58 54.7 17.60 51.3 16.60 47.7 15.58 42.1 14.05 36.3 12.54

-9.6 -10.0 67.8 20.68 62.5 19.18 58.8 18.16 55.2 17.11 51.3 16.05 45.4 14.45 39.3 12.85

-4.4 -5.0 73.7 21.53 68.1 19.97 64.3 18.89 60.2 17.80 56.2 16.69 49.8 15.00 43.1 13.27

-1.8 -2.5 77.5 21.93 71.6 20.33 67.5 19.24 63.4 18.11 58.7 16.80 51.0 14.72 43.4 12.76

0.8 0.0 81.6 22.19 74.0 20.00 68.9 18.58 63.7 17.18 58.7 15.83 51.0 13.89 43.4 12.03

90% 2.8 2.0 81.6 20.91 74.0 18.87 68.9 17.54 63.7 16.25 58.7 15.00 51.0 13.16 43.4 11.38

6.0 5.0 81.6 18.75 74.0 16.98 68.9 15.82 63.7 14.67 58.7 13.54 51.0 11.87 43.4 10.23

7.0 6.0 81.6 17.95 74.0 16.25 68.9 15.14 63.7 14.07 58.7 12.98 51.0 11.39 43.4 9.83

8.6 7.5 81.6 16.69 74.0 15.14 68.9 14.14 63.7 13.14 58.7 12.16 51.0 10.70 43.4 9.25

11.2 10.0 81.6 14.71 74.0 13.40 68.9 12.54 63.7 11.68 58.7 10.85 51.0 9.59 43.4 8.34

16.4 15.0 81.6 11.16 74.0 10.28 68.9 9.70 63.7 9.10 58.7 8.52 51.0 7.63 43.4 6.72

24.0 18.0 81.6 10.77 74.0 9.88 68.9 9.28 63.7 8.68 58.7 8.10 51.0 7.19 43.4 6.30

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 60.4 19.15 55.5 17.82 52.0 16.91 48.6 16.00 45.1 15.09 39.7 13.74 34.2 12.41

-14.7 -15.0 64.1 19.66 58.9 18.29 55.3 17.34 51.7 16.40 48.0 15.45 42.4 14.03 36.5 12.59

-9.6 -10.0 68.7 20.33 63.2 18.89 59.4 17.91 55.6 16.91 51.6 15.91 45.4 14.29 38.6 12.56

-4.4 -5.0 72.5 20.18 65.7 18.38 61.2 17.20 56.7 16.05 52.1 14.92 45.4 13.29 38.6 11.68

-1.8 -2.5 72.5 19.11 65.7 17.42 61.2 16.31 56.7 15.23 52.1 14.16 45.4 12.61 38.6 11.08

0.8 0.0 72.5 17.91 65.7 16.36 61.2 15.32 56.7 14.32 52.1 13.32 45.4 11.87 38.6 10.43

80% 2.8 2.0 72.5 16.85 65.7 15.42 61.2 14.45 56.7 13.52 52.1 12.59 45.4 11.21 38.6 9.83

6.0 5.0 72.5 15.03 65.7 13.78 61.2 12.96 56.7 12.12 52.1 11.30 45.4 10.03 38.6 8.75

7.0 6.0 72.5 14.34 65.7 13.18 61.2 12.39 56.7 11.61 52.1 10.83 45.4 9.63 38.6 8.43

8.6 7.5 72.5 13.30 65.7 12.25 61.2 11.56 56.7 10.83 52.1 10.12 45.4 9.03 38.6 7.92

11.2 10.0 72.5 11.65 65.7 10.79 61.2 10.21 56.7 9.61 52.1 9.01 45.4 8.08 38.6 7.13

16.4 15.0 72.5 9.72 65.7 8.92 61.2 8.39 56.7 7.86 52.1 7.33 45.4 6.53 38.6 5.75

24.0 18.0 72.5 9.72 65.7 8.92 61.2 8.39 56.7 7.86 52.1 7.33 45.4 6.53 38.6 5.73

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 61.9 19.06 56.7 17.80 53.2 16.96 49.6 16.13 45.6 15.14 39.7 13.72 33.7 12.32

-14.7 -15.0 63.5 18.80 57.5 17.31 53.6 16.33 49.6 15.36 45.6 14.41 39.7 13.01 33.7 11.63

-9.6 -10.0 63.5 17.62 57.5 16.27 53.6 15.38 49.6 14.51 45.6 13.63 39.7 12.29 33.7 10.94

-4.4 -5.0 63.5 16.09 57.5 14.89 53.6 14.07 49.6 13.29 45.6 12.49 39.7 11.30 33.7 10.10

-1.8 -2.5 63.5 15.20 57.5 14.07 53.6 13.32 49.6 12.58 45.6 11.83 39.7 10.70 33.7 9.56

0.8 0.0 63.5 14.20 57.5 13.18 53.6 12.49 49.6 11.79 45.6 11.08 39.7 10.03 33.7 8.95

70% 2.8 2.0 63.5 13.30 57.5 12.38 53.6 11.74 49.6 11.08 45.6 10.45 39.7 9.45 33.7 8.32

6.0 5.0 63.5 11.81 57.5 11.01 53.6 10.45 49.6 9.88 45.6 9.30 39.7 8.37 33.7 7.41

7.0 6.0 63.5 11.25 57.5 10.50 53.6 9.97 49.6 9.45 45.6 8.90 39.7 8.03 33.7 7.13

8.6 7.5 63.5 10.39 57.5 9.74 53.6 9.28 49.6 8.81 45.6 8.30 39.7 7.53 33.7 6.72

11.2 10.0 63.5 9.05 57.5 8.54 53.6 8.17 49.6 7.79 45.6 7.37 39.7 6.73 33.7 6.04

16.4 15.0 63.5 8.66 57.5 7.95 53.6 7.50 49.6 7.03 45.6 6.57 39.7 5.86 33.7 5.17

24.0 18.0 63.5 8.66 57.5 7.95 53.6 7.50 49.6 7.03 45.6 6.57 39.7 5.86 33.7 5.17

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 54.4 15.83 49.3 14.83 45.9 14.12 42.5 13.41 39.1 12.72 34.0 11.68 28.9 10.65

-14.7 -15.0 54.4 14.94 49.3 14.03 45.9 13.43 42.5 12.79 39.1 12.12 34.0 11.08 28.9 10.05

-9.6 -10.0 54.4 13.89 49.3 13.07 45.9 12.50 42.5 11.94 39.1 11.36 34.0 10.45 28.9 9.43

-4.4 -5.0 54.4 12.61 49.3 11.88 45.9 11.39 42.5 10.88 39.1 10.36 34.0 9.54 28.9 8.66

-1.8 -2.5 54.4 11.87 49.3 11.19 45.9 10.74 42.5 10.26 39.1 9.77 34.0 8.99 28.9 8.14

0.8 0.0 54.4 11.03 49.3 10.43 45.9 10.01 42.5 9.57 39.1 9.12 34.0 8.39 28.9 7.46

60% 2.8 2.0 54.4 10.32 49.3 9.77 45.9 9.37 42.5 8.97 39.1 8.54 34.0 7.77 28.9 6.95

6.0 5.0 54.4 9.06 49.3 8.61 45.9 8.26 42.5 7.90 39.1 7.52 34.0 6.88 28.9 6.19

7.0 6.0 54.4 8.61 49.3 8.19 45.9 7.88 42.5 7.55 39.1 7.19 34.0 6.61 28.9 5.95

8.6 7.5 54.4 7.92 49.3 7.57 45.9 7.32 42.5 7.03 39.1 6.70 34.0 6.19 28.9 5.61

11.2 10.0 54.4 7.59 49.3 6.99 45.9 6.59 42.5 6.21 39.1 5.95 34.0 5.53 28.9 5.06

16.4 15.0 54.4 7.59 49.3 6.99 45.9 6.59 42.5 6.21 39.1 5.81 34.0 5.21 28.9 4.60

24.0 18.0 54.4 7.59 49.3 6.99 45.9 6.59 42.5 6.21 39.1 5.81 34.0 5.21 28.9 4.60

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


24 HP (U-8MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 45.4 12.43 41.1 11.90 38.3 11.52 35.4 11.08 32.6 10.59 28.3 9.85 24.1 9.08

-14.7 -15.0 45.4 11.68 41.1 11.19 38.3 10.85 35.4 10.48 32.6 10.08 28.3 9.34 24.1 8.55

-9.6 -10.0 45.4 10.79 41.1 10.37 38.3 10.06 35.4 9.74 32.6 9.37 28.3 8.77 24.1 8.03

-4.4 -5.0 45.4 9.72 41.1 9.37 38.3 9.10 35.4 8.81 32.6 8.48 28.3 7.95 24.1 7.23

-1.8 -2.5 45.4 9.10 41.1 8.79 38.3 8.54 35.4 8.26 32.6 7.97 28.3 7.41 24.1 6.66

0.8 0.0 45.4 8.43 41.1 8.14 38.3 7.92 35.4 7.68 32.6 7.35 28.3 6.77 24.1 6.12

50% 2.8 2.0 45.4 7.83 41.1 7.59 38.3 7.35 35.4 7.08 32.6 6.77 28.3 6.26 24.1 5.70

6.0 5.0 45.4 6.77 41.1 6.57 38.3 6.39 35.4 6.19 32.6 5.95 28.3 5.55 24.1 5.10

7.0 6.0 45.4 6.53 41.1 6.24 38.3 6.08 35.4 5.90 32.6 5.70 28.3 5.33 24.1 4.90

8.6 7.5 45.4 6.53 41.1 6.02 38.3 5.70 35.4 5.50 32.6 5.31 28.3 5.01 24.1 4.62

11.2 10.0 45.4 6.53 41.1 6.02 38.3 5.70 35.4 5.37 32.6 5.04 28.3 4.53 24.1 4.17

16.4 15.0 45.4 6.53 41.1 6.02 38.3 5.70 35.4 5.37 32.6 5.04 28.3 4.53 24.1 4.04

24.0 18.0 45.4 6.53 41.1 6.02 38.3 5.70 35.4 5.37 32.6 5.04 28.3 4.53 24.1 4.04

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 36.3 9.66 32.9 9.43 30.6 9.25 28.3 9.01 26.1 8.66 22.6 8.15 19.3 7.59

-14.7 -15.0 36.3 9.03 32.9 8.85 30.6 8.68 28.3 8.46 26.1 8.23 22.6 7.72 19.3 7.13

-9.6 -10.0 36.3 8.30 32.9 8.14 30.6 8.01 28.3 7.83 26.1 7.61 22.6 7.23 19.3 6.62

-4.4 -5.0 36.3 7.41 32.9 7.30 30.6 7.17 28.3 7.03 26.1 6.84 22.6 6.33 19.3 5.75

-1.8 -2.5 36.3 6.90 32.9 6.79 30.6 6.70 28.3 6.50 26.1 6.24 22.6 5.82 19.3 5.31

0.8 0.0 36.3 6.33 32.9 6.21 30.6 6.06 28.3 5.88 26.1 5.68 22.6 5.31 19.3 4.90

40% 2.8 2.0 36.3 5.77 32.9 5.66 30.6 5.55 28.3 5.41 26.1 5.24 22.6 4.93 19.3 4.57

6.0 5.0 36.3 5.46 32.9 5.08 30.6 4.80 28.3 4.73 26.1 4.60 22.6 4.39 19.3 4.10

7.0 6.0 36.3 5.46 32.9 5.08 30.6 4.80 28.3 4.53 26.1 4.40 22.6 4.22 19.3 3.95

8.6 7.5 36.3 5.46 32.9 5.08 30.6 4.80 28.3 4.53 26.1 4.28 22.6 3.97 19.3 3.73

11.2 10.0 36.3 5.46 32.9 5.08 30.6 4.80 28.3 4.53 26.1 4.28 22.6 3.88 19.3 3.48

16.4 15.0 36.3 5.46 32.9 5.08 30.6 4.80 28.3 4.53 26.1 4.28 22.6 3.88 19.3 3.48

24.0 18.0 36.3 5.46 32.9 5.08 30.6 4.80 28.3 4.53 26.1 4.28 22.6 3.88 19.3 3.48

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 27.2 7.39 24.6 7.32 23.0 7.24 21.3 7.10 19.6 6.86 17.0 6.52 14.5 6.12

-14.7 -15.0 27.2 6.90 24.6 6.84 23.0 6.77 21.3 6.66 19.6 6.52 17.0 6.15 14.5 5.71

-9.6 -10.0 27.2 6.30 24.6 6.28 23.0 6.22 21.3 6.13 19.6 5.97 17.0 5.55 14.5 5.10

-4.4 -5.0 27.2 5.57 24.6 5.48 23.0 5.37 21.3 5.22 19.6 5.08 17.0 4.77 14.5 4.42

-1.8 -2.5 27.2 5.01 24.6 4.95 23.0 4.88 21.3 4.77 19.6 4.64 17.0 4.40 14.5 4.10

0.8 0.0 27.2 4.46 24.6 4.44 23.0 4.40 21.3 4.33 19.6 4.24 17.0 4.04 14.5 3.79

30% 2.8 2.0 27.2 4.40 24.6 4.11 23.0 4.04 21.3 3.99 19.6 3.93 17.0 3.77 14.5 3.55

6.0 5.0 27.2 4.40 24.6 4.11 23.0 3.91 21.3 3.71 19.6 3.51 17.0 3.37 14.5 3.22

7.0 6.0 27.2 4.40 24.6 4.11 23.0 3.91 21.3 3.71 19.6 3.51 17.0 3.26 14.5 3.11

8.6 7.5 27.2 4.40 24.6 4.11 23.0 3.91 21.3 3.71 19.6 3.51 17.0 3.20 14.5 2.95

11.2 10.0 27.2 4.40 24.6 4.11 23.0 3.91 21.3 3.71 19.6 3.51 17.0 3.20 14.5 2.91

16.4 15.0 27.2 4.40 24.6 4.11 23.0 3.91 21.3 3.71 19.6 3.51 17.0 3.20 14.5 2.91

24.0 18.0 27.2 4.40 24.6 4.11 23.0 3.91 21.3 3.71 19.6 3.51 17.0 3.20 14.5 2.91

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


26 HP (U-12MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 64.1 22.13 59.1 20.33 55.7 19.12 55.7 19.12 55.7 19.12 55.7 19.12 48.7 16.48

-14.7 -15.0 68.0 22.47 62.8 20.70 59.3 19.47 59.3 19.47 59.3 19.47 59.3 19.47 52.3 16.85

-9.6 -10.0 72.9 23.01 67.6 21.24 63.9 20.03 63.9 20.03 63.9 20.03 63.9 20.03 56.9 17.41

-4.4 -5.0 79.5 23.85 74.0 22.06 70.2 20.83 70.2 20.83 70.2 20.83 70.2 20.83 63.1 18.21

-1.8 -2.5 83.4 24.18 78.2 22.62 74.1 21.37 74.1 21.37 74.1 21.37 74.1 21.37 67.0 18.71

0.8 0.0 87.0 24.18 83.0 23.25 78.8 21.99 78.8 21.99 78.8 21.99 78.8 21.99 71.7 19.38

130% 2.8 2.0 90.4 24.18 87.6 23.86 83.4 22.60 83.4 22.60 83.4 22.60 83.4 22.60 71.7 18.43

6.0 5.0 97.3 24.18 94.1 24.07 87.6 22.08 87.6 22.08 87.6 22.08 84.4 19.98 71.7 16.78

7.0 6.0 99.7 24.18 94.1 23.12 87.6 21.22 87.6 21.22 87.6 21.22 84.4 19.23 71.7 16.14

8.6 7.5 103.2 24.18 94.1 21.69 87.6 19.92 87.6 19.92 87.6 19.92 84.4 18.10 71.7 15.21

11.2 10.0 103.8 21.84 94.1 19.38 87.6 17.84 87.6 17.84 87.6 17.84 84.4 16.26 71.7 13.73

16.4 15.0 103.8 17.02 94.1 15.21 87.6 14.06 87.6 14.06 87.6 14.06 84.4 12.98 71.7 11.07

24.0 18.0 103.8 14.55 94.1 13.06 87.6 12.13 87.6 12.13 87.6 12.13 84.4 11.31 71.7 9.71

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 64.2 21.89 59.3 20.13 55.8 18.93 55.8 18.93 55.8 18.93 51.9 17.37 45.0 15.25

-14.7 -15.0 68.1 22.25 62.9 20.52 59.4 19.31 59.4 19.31 59.4 19.31 55.5 17.76 48.2 15.61

-9.6 -10.0 73.0 22.80 67.7 21.07 64.0 19.86 64.0 19.86 64.0 19.86 60.1 18.34 52.4 16.09

-4.4 -5.0 79.7 23.64 74.1 21.89 70.2 20.66 70.2 20.66 70.2 20.66 66.4 19.16 58.0 16.80

-1.8 -2.5 83.9 24.18 78.2 22.43 74.2 21.20 74.2 21.20 74.2 21.20 70.4 19.68 61.6 17.26

0.8 0.0 87.5 24.18 83.0 23.06 78.8 21.82 78.8 21.82 78.8 21.82 75.2 20.35 64.6 17.43

120% 2.8 2.0 90.9 24.18 87.6 23.66 83.3 22.41 83.3 22.41 83.3 22.41 76.0 19.68 64.6 16.57

6.0 5.0 97.6 24.18 91.9 23.03 85.6 21.17 85.6 21.17 85.6 21.17 76.0 17.89 64.6 15.08

7.0 6.0 99.8 24.18 91.9 22.12 85.6 20.33 85.6 20.33 85.6 20.33 76.0 17.22 64.6 14.53

8.6 7.5 101.4 23.34 91.9 20.74 85.6 19.08 85.6 19.08 85.6 19.08 76.0 16.20 64.6 13.69

11.2 10.0 101.4 20.79 91.9 18.51 85.6 17.06 85.6 17.06 85.6 17.06 76.0 14.56 64.6 12.35

16.4 15.0 101.4 16.18 91.9 14.51 85.6 13.43 85.6 13.43 85.6 13.43 76.0 11.64 64.6 9.97

24.0 18.0 101.4 13.78 91.9 12.44 85.6 11.57 85.6 11.57 85.6 11.57 76.0 10.16 64.6 8.76

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 64.3 21.67 59.3 19.94 55.9 18.77 55.9 18.77 53.6 17.89 47.5 15.94 41.2 14.04

-14.7 -15.0 68.2 22.04 63.1 20.33 59.5 19.16 59.5 19.16 57.3 18.28 50.9 16.31 44.2 14.36

-9.6 -10.0 73.2 22.60 67.8 20.89 64.1 19.72 64.1 19.72 61.9 18.86 55.1 16.83 48.0 14.81

-4.4 -5.0 79.9 23.45 74.2 21.71 70.3 20.52 70.3 20.52 68.1 19.68 60.8 17.56 53.1 15.42

-1.8 -2.5 84.1 24.01 78.2 22.25 74.2 21.04 74.2 21.04 72.0 20.20 64.4 18.02 56.3 15.85

0.8 0.0 88.0 24.18 83.0 22.88 78.8 21.63 78.8 21.63 76.7 20.83 68.1 18.41 57.9 15.59

110% 2.8 2.0 91.4 24.18 87.6 23.47 83.2 22.25 83.2 22.25 78.2 20.37 68.1 17.50 57.9 14.82

6.0 5.0 97.7 24.18 89.7 22.02 83.5 20.27 83.5 20.27 78.2 18.49 68.1 15.92 57.9 13.49

7.0 6.0 99.0 23.77 89.7 21.15 83.5 19.47 83.5 19.47 78.2 17.78 68.1 15.33 57.9 12.98

8.6 7.5 99.0 22.25 89.7 19.81 83.5 18.27 83.5 18.27 78.2 16.70 68.1 14.42 57.9 12.24

11.2 10.0 99.0 19.79 89.7 17.67 83.5 16.31 83.5 16.31 78.2 14.97 68.1 12.96 57.9 11.05

16.4 15.0 99.0 15.36 89.7 13.82 83.5 12.83 83.5 12.83 78.2 11.89 68.1 10.40 57.9 8.95

24.0 18.0 99.0 13.08 89.7 11.83 83.5 11.03 83.5 11.03 78.2 10.29 68.1 9.06 57.9 7.87

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 64.5 21.43 59.4 19.75 56.0 18.60 52.4 17.45 48.8 16.28 43.2 14.55 37.4 12.85

-14.7 -15.0 68.4 21.84 63.2 20.14 59.6 18.99 55.8 17.82 52.1 16.65 46.2 14.88 40.1 13.13

-9.6 -10.0 73.4 22.41 67.9 20.72 64.1 19.55 60.2 18.36 56.3 17.17 50.0 15.35 43.5 13.52

-4.4 -5.0 80.0 23.27 74.2 21.54 70.3 20.35 66.1 19.12 61.9 17.89 55.2 16.00 48.1 14.08

-1.8 -2.5 84.3 23.83 78.3 22.08 74.2 20.87 69.8 19.62 65.4 18.34 58.4 16.41 51.0 14.43

0.8 0.0 88.6 24.18 83.0 22.69 78.7 21.46 74.2 20.20 69.4 18.86 60.4 16.28 51.3 13.84

100% 2.8 2.0 91.9 24.18 87.5 23.27 81.5 21.43 75.5 19.64 69.4 17.93 60.4 15.48 51.3 13.15

6.0 5.0 96.6 23.60 87.5 21.04 81.5 19.40 75.5 17.82 69.4 16.28 60.4 14.08 51.3 11.98

7.0 6.0 96.6 22.64 87.5 20.20 81.5 18.60 75.5 17.13 69.4 15.66 60.4 13.54 51.3 11.53

8.6 7.5 96.6 21.17 87.5 18.92 81.5 17.47 75.5 16.07 69.4 14.71 60.4 12.76 51.3 10.88

11.2 10.0 96.6 18.80 87.5 16.85 81.5 15.59 75.5 14.38 69.4 13.19 60.4 11.48 51.3 9.84

16.4 15.0 96.6 14.56 87.5 13.15 81.5 12.24 75.5 11.35 69.4 10.49 60.4 9.21 51.3 7.98

9 24.0 18.0 96.6 12.37 87.5 11.23 81.5 10.51 75.5 9.80 69.4 9.10 60.4 8.05 51.3 7.05
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


26 HP (U-12MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 65.0 20.61 59.8 19.05 56.2 17.99 52.6 16.91 49.0 15.85 43.3 14.25 37.4 12.70

-14.7 -15.0 68.9 21.06 63.6 19.49 59.8 18.41 56.1 17.32 52.2 16.22 46.2 14.56 40.0 12.95

-9.6 -10.0 74.0 21.69 68.3 20.09 64.4 18.97 60.4 17.86 56.3 16.72 50.0 15.01 43.3 13.30

-4.4 -5.0 80.6 22.56 74.6 20.89 70.4 19.75 66.1 18.58 61.7 17.39 54.4 15.42 46.2 13.32

-1.8 -2.5 84.7 23.10 78.5 21.41 73.4 19.96 67.9 18.45 62.5 16.96 54.4 14.81 46.2 12.78

0.8 0.0 87.0 22.71 78.8 20.40 73.4 18.90 67.9 17.45 62.5 16.03 54.4 14.01 46.2 12.09

90% 2.8 2.0 87.0 21.45 78.8 19.27 73.4 17.87 67.9 16.52 62.5 15.20 54.4 13.30 46.2 11.46

6.0 5.0 87.0 19.27 78.8 17.37 73.4 16.14 67.9 14.95 62.5 13.78 54.4 12.05 46.2 10.38

7.0 6.0 87.0 18.45 78.8 16.67 73.4 15.49 67.9 14.36 62.5 13.24 54.4 11.59 46.2 9.99

8.6 7.5 87.0 17.21 78.8 15.55 73.4 14.49 67.9 13.45 62.5 12.41 54.4 10.90 46.2 9.43

11.2 10.0 87.0 15.21 78.8 13.80 73.4 12.89 67.9 12.00 62.5 11.10 54.4 9.80 46.2 8.52

16.4 15.0 87.0 11.64 78.8 10.70 73.4 10.04 67.9 9.43 62.5 8.80 54.4 7.85 46.2 6.92

24.0 18.0 87.0 10.71 78.8 9.84 73.4 9.26 67.9 8.69 62.5 8.11 54.4 7.24 46.2 6.38

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 65.7 19.96 60.4 18.51 56.7 17.52 53.0 16.55 49.2 15.57 43.4 14.10 37.4 12.67

-14.7 -15.0 69.7 20.46 64.1 18.97 60.3 17.97 56.4 16.94 52.4 15.92 46.3 14.40 40.0 12.89

-9.6 -10.0 74.7 21.11 68.9 19.59 64.8 18.53 60.4 17.37 55.5 16.09 48.3 14.25 41.1 12.48

-4.4 -5.0 77.3 20.57 70.0 18.66 65.2 17.43 60.4 16.20 55.5 15.03 48.3 13.32 41.1 11.66

-1.8 -2.5 77.3 19.53 70.0 17.73 65.2 16.55 60.4 15.42 55.5 14.28 48.3 12.67 41.1 11.10

0.8 0.0 77.3 18.34 70.0 16.67 65.2 15.59 60.4 14.53 55.5 13.49 48.3 11.96 41.1 10.47

80% 2.8 2.0 77.3 17.28 70.0 15.74 65.2 14.73 60.4 13.75 55.5 12.76 48.3 11.33 41.1 9.91

6.0 5.0 77.3 15.46 70.0 14.14 65.2 13.26 60.4 12.39 55.5 11.51 48.3 10.21 41.1 8.91

7.0 6.0 77.3 14.77 70.0 13.52 65.2 12.70 60.4 11.87 55.5 11.05 48.3 9.82 41.1 8.57

8.6 7.5 77.3 13.73 70.0 12.61 65.2 11.85 60.4 11.10 55.5 10.36 48.3 9.23 41.1 8.09

11.2 10.0 77.3 12.09 70.0 11.14 65.2 10.53 60.4 9.90 55.5 9.26 48.3 8.30 41.1 7.33

16.4 15.0 77.3 9.67 70.0 8.91 65.2 8.39 60.4 7.89 55.5 7.37 48.3 6.64 41.1 5.95

24.0 18.0 77.3 9.67 70.0 8.91 65.2 8.39 60.4 7.89 55.5 7.37 48.3 6.60 41.1 5.82

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 66.9 19.59 61.3 18.21 57.1 17.15 52.8 16.11 48.6 15.08 42.3 13.60 35.9 12.18

-14.7 -15.0 67.6 18.93 61.3 17.37 57.1 16.35 52.8 15.35 48.6 14.36 42.3 12.93 35.9 11.53

-9.6 -10.0 67.6 17.87 61.3 16.44 57.1 15.49 52.8 14.55 48.6 13.62 42.3 12.22 35.9 10.86

-4.4 -5.0 67.6 16.39 61.3 15.08 57.1 14.23 52.8 13.39 48.6 12.56 42.3 11.31 35.9 10.10

-1.8 -2.5 67.6 15.51 61.3 14.30 57.1 13.50 52.8 12.70 48.6 11.90 42.3 10.73 35.9 9.58

0.8 0.0 67.6 14.53 61.3 13.41 57.1 12.69 52.8 11.94 48.6 11.22 42.3 10.12 35.9 9.02

70% 2.8 2.0 67.6 13.65 61.3 12.63 57.1 11.96 52.8 11.27 48.6 10.58 42.3 9.56 35.9 8.46

6.0 5.0 67.6 12.16 61.3 11.29 57.1 10.71 52.8 10.12 48.6 9.50 42.3 8.56 35.9 7.57

7.0 6.0 67.6 11.61 61.3 10.81 57.1 10.25 52.8 9.67 48.6 9.10 42.3 8.22 35.9 7.29

8.6 7.5 67.6 10.75 61.3 10.04 57.1 9.54 52.8 9.04 48.6 8.52 42.3 7.72 35.9 6.88

11.2 10.0 67.6 9.41 61.3 8.85 57.1 8.44 52.8 8.04 48.6 7.61 42.3 6.94 35.9 6.23

16.4 15.0 67.6 8.65 61.3 7.98 57.1 7.53 52.8 7.09 48.6 6.62 42.3 5.95 35.9 5.28

24.0 18.0 67.6 8.65 61.3 7.98 57.1 7.53 52.8 7.09 48.6 6.62 42.3 5.95 35.9 5.28

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 57.9 15.92 52.5 14.81 48.9 14.08 45.3 13.34 41.6 12.63 36.2 11.57 30.8 10.51

-14.7 -15.0 57.9 15.08 52.5 14.10 48.9 13.43 45.3 12.76 41.6 12.05 36.2 11.01 30.8 9.95

-9.6 -10.0 57.9 14.06 52.5 13.15 48.9 12.56 45.3 11.94 41.6 11.33 36.2 10.40 30.8 9.37

-4.4 -5.0 57.9 12.83 52.5 12.03 48.9 11.48 45.3 10.94 41.6 10.38 36.2 9.54 30.8 8.65

-1.8 -2.5 57.9 12.09 52.5 11.36 48.9 10.86 45.3 10.36 41.6 9.84 36.2 9.04 30.8 8.20

0.8 0.0 57.9 11.29 52.5 10.62 48.9 10.17 45.3 9.71 41.6 9.23 36.2 8.48 30.8 7.61

60% 2.8 2.0 57.9 10.58 52.5 9.99 48.9 9.56 45.3 9.13 41.6 8.69 36.2 7.94 30.8 7.09

6.0 5.0 57.9 9.37 52.5 8.87 48.9 8.50 45.3 8.13 41.6 7.72 36.2 7.07 30.8 6.36

7.0 6.0 57.9 8.93 52.5 8.46 48.9 8.13 45.3 7.77 41.6 7.38 36.2 6.79 30.8 6.12

8.6 7.5 57.9 8.24 52.5 7.85 48.9 7.55 45.3 7.25 41.6 6.92 36.2 6.38 30.8 5.78

11.2 10.0 57.9 7.63 52.5 7.05 48.9 6.68 45.3 6.44 41.6 6.18 36.2 5.73 30.8 5.25

16.4 15.0 57.9 7.63 52.5 7.05 48.9 6.66 45.3 6.27 41.6 5.90 36.2 5.32 30.8 4.74

24.0 18.0 57.9 7.63 52.5 7.05 48.9 6.66 45.3 6.27 41.6 5.90 36.2 5.32 30.8 4.74

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


26 HP (U-12MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 48.3 12.44 43.8 11.87 40.8 11.46 37.7 10.99 34.7 10.49 30.2 9.75 25.7 8.98

-14.7 -15.0 48.3 11.74 43.8 11.20 40.8 10.83 37.7 10.43 34.7 10.03 30.2 9.28 25.7 8.50

-9.6 -10.0 48.3 10.88 43.8 10.42 40.8 10.08 37.7 9.71 34.7 9.34 30.2 8.72 25.7 8.00

-4.4 -5.0 48.3 9.86 43.8 9.45 40.8 9.17 37.7 8.85 34.7 8.52 30.2 7.96 25.7 7.35

-1.8 -2.5 48.3 9.26 43.8 8.89 40.8 8.63 37.7 8.33 34.7 8.04 30.2 7.51 25.7 6.81

0.8 0.0 48.3 8.61 43.8 8.30 40.8 8.05 37.7 7.79 34.7 7.50 30.2 6.92 25.7 6.27

50% 2.8 2.0 48.3 8.05 43.8 7.76 40.8 7.53 37.7 7.27 34.7 6.96 30.2 6.44 25.7 5.86

6.0 5.0 48.3 7.05 43.8 6.81 40.8 6.62 37.7 6.40 34.7 6.16 30.2 5.73 25.7 5.26

7.0 6.0 48.3 6.70 43.8 6.47 40.8 6.31 37.7 6.12 34.7 5.90 30.2 5.52 25.7 5.08

8.6 7.5 48.3 6.60 43.8 6.12 40.8 5.88 37.7 5.71 34.7 5.52 30.2 5.19 25.7 4.80

11.2 10.0 48.3 6.60 43.8 6.12 40.8 5.80 37.7 5.47 34.7 5.15 30.2 4.69 25.7 4.37

16.4 15.0 48.3 6.60 43.8 6.12 40.8 5.80 37.7 5.47 34.7 5.15 30.2 4.67 25.7 4.19

24.0 18.0 48.3 6.60 43.8 6.12 40.8 5.80 37.7 5.47 34.7 5.15 30.2 4.67 25.7 4.19

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 38.6 9.63 35.0 9.37 32.6 9.17 30.2 8.93 27.8 8.61 24.1 8.09 20.5 7.55

-14.7 -15.0 38.6 9.04 35.0 8.82 32.6 8.63 30.2 8.43 27.8 8.18 24.1 7.70 20.5 7.12

-9.6 -10.0 38.6 8.33 35.0 8.17 32.6 8.00 30.2 7.81 27.8 7.61 24.1 7.22 20.5 6.70

-4.4 -5.0 38.6 7.50 35.0 7.35 32.6 7.24 30.2 7.07 27.8 6.90 24.1 6.47 20.5 5.90

-1.8 -2.5 38.6 7.01 35.0 6.90 32.6 6.77 30.2 6.64 27.8 6.42 24.1 5.97 20.5 5.47

0.8 0.0 38.6 6.47 35.0 6.38 32.6 6.25 30.2 6.06 27.8 5.86 24.1 5.49 20.5 5.06

40% 2.8 2.0 38.6 6.01 35.0 5.86 32.6 5.75 30.2 5.60 27.8 5.43 24.1 5.12 20.5 4.74

6.0 5.0 38.6 5.56 35.0 5.19 32.6 5.02 30.2 4.93 27.8 4.82 24.1 4.58 20.5 4.28

7.0 6.0 38.6 5.56 35.0 5.19 32.6 4.93 30.2 4.72 27.8 4.61 24.1 4.41 20.5 4.15

8.6 7.5 38.6 5.56 35.0 5.19 32.6 4.93 30.2 4.67 27.8 4.41 24.1 4.17 20.5 3.92

11.2 10.0 38.6 5.56 35.0 5.19 32.6 4.93 30.2 4.67 27.8 4.41 24.1 4.04 20.5 3.65

16.4 15.0 38.6 5.56 35.0 5.19 32.6 4.93 30.2 4.67 27.8 4.41 24.1 4.04 20.5 3.65

24.0 18.0 38.6 5.56 35.0 5.19 32.6 4.93 30.2 4.67 27.8 4.41 24.1 4.04 20.5 3.65

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 29.0 7.37 26.2 7.29 24.5 7.22 22.7 7.09 20.9 6.86 18.1 6.51 15.4 6.14

-14.7 -15.0 29.0 6.90 26.2 6.84 24.5 6.77 22.7 6.66 20.9 6.53 18.1 6.19 15.4 5.78

-9.6 -10.0 29.0 6.32 26.2 6.31 24.5 6.27 22.7 6.18 20.9 6.05 18.1 5.69 15.4 5.23

-4.4 -5.0 29.0 5.65 26.2 5.65 24.5 5.54 22.7 5.39 20.9 5.23 18.1 4.95 15.4 4.59

-1.8 -2.5 29.0 5.21 26.2 5.13 24.5 5.06 22.7 4.95 20.9 4.82 18.1 4.58 15.4 4.28

0.8 0.0 29.0 4.69 26.2 4.65 24.5 4.59 22.7 4.52 20.9 4.43 18.1 4.22 15.4 3.98

30% 2.8 2.0 29.0 4.54 26.2 4.26 24.5 4.24 22.7 4.19 20.9 4.11 18.1 3.96 15.4 3.74

6.0 5.0 29.0 4.54 26.2 4.26 24.5 4.05 22.7 3.87 20.9 3.68 18.1 3.57 15.4 3.42

7.0 6.0 29.0 4.54 26.2 4.26 24.5 4.05 22.7 3.87 20.9 3.68 18.1 3.46 15.4 3.31

8.6 7.5 29.0 4.54 26.2 4.26 24.5 4.05 22.7 3.87 20.9 3.68 18.1 3.39 15.4 3.16

11.2 10.0 29.0 4.54 26.2 4.26 24.5 4.05 22.7 3.87 20.9 3.68 18.1 3.39 15.4 3.11

16.4 15.0 29.0 4.54 26.2 4.26 24.5 4.05 22.7 3.87 20.9 3.68 18.1 3.39 15.4 3.11

24.0 18.0 29.0 4.54 26.2 4.26 24.5 4.05 22.7 3.87 20.9 3.68 18.1 3.39 15.4 3.11

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


28 HP (U-14MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 66.9 22.41 61.8 20.63 58.2 19.44 58.2 19.44 58.2 19.44 58.2 19.44 50.9 16.89

-14.7 -15.0 71.0 22.74 65.6 21.00 62.0 19.81 62.0 19.81 62.0 19.81 62.0 19.81 54.6 17.28

-9.6 -10.0 76.1 23.28 70.6 21.55 66.8 20.36 66.8 20.36 66.8 20.36 66.8 20.36 59.4 17.82

-4.4 -5.0 83.1 24.12 77.3 22.37 73.2 21.16 73.2 21.16 73.2 21.16 73.2 21.16 65.8 18.62

-1.8 -2.5 87.6 24.67 81.6 22.91 77.4 21.68 77.4 21.68 77.4 21.68 77.4 21.68 69.9 19.15

0.8 0.0 92.9 25.33 86.7 23.56 82.3 22.33 82.3 22.33 82.3 22.33 82.3 22.33 75.0 19.81

130% 2.8 2.0 96.5 25.35 91.5 24.16 87.1 22.91 87.1 22.91 87.1 22.91 87.1 22.91 77.0 19.42

6.0 5.0 104.0 25.35 100.8 25.10 94.1 23.13 94.1 23.13 94.1 23.13 90.6 21.00 77.0 17.67

7.0 6.0 107.2 25.35 101.1 24.20 94.1 22.23 94.1 22.23 94.1 22.23 90.6 20.22 77.0 17.02

8.6 7.5 111.0 25.35 101.1 22.68 94.1 20.87 94.1 20.87 94.1 20.87 90.6 19.01 77.0 16.03

11.2 10.0 111.5 22.76 101.1 20.26 94.1 18.66 94.1 18.66 94.1 18.66 90.6 17.08 77.0 14.47

16.4 15.0 111.5 17.73 101.1 15.87 94.1 14.70 94.1 14.70 94.1 14.70 90.6 13.65 77.0 11.66

24.0 18.0 111.5 15.11 101.1 13.61 94.1 12.66 94.1 12.66 94.1 12.66 90.6 11.88 77.0 10.24

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 67.0 22.17 61.9 20.44 58.3 19.27 58.3 19.27 58.3 19.27 54.2 17.76 47.0 15.64

-14.7 -15.0 71.1 22.52 65.7 20.83 62.0 19.64 62.0 19.64 62.0 19.64 57.9 18.15 50.4 15.99

-9.6 -10.0 76.3 23.09 70.7 21.37 66.9 20.20 66.9 20.20 66.9 20.20 62.8 18.74 54.8 16.50

-4.4 -5.0 83.3 23.93 77.4 22.19 73.3 21.00 73.3 21.00 73.3 21.00 69.4 19.56 60.6 17.22

-1.8 -2.5 87.8 24.49 81.6 22.74 77.4 21.53 77.4 21.53 77.4 21.53 73.5 20.10 64.3 17.69

0.8 0.0 93.0 25.14 86.7 23.38 82.3 22.15 82.3 22.15 82.3 22.15 78.5 20.75 69.0 18.25

120% 2.8 2.0 97.0 25.35 91.5 23.95 87.0 22.70 87.0 22.70 87.0 22.70 81.6 20.69 69.4 17.47

6.0 5.0 104.7 25.35 98.7 24.10 91.9 22.17 91.9 22.17 91.9 22.17 81.6 18.82 69.4 15.91

7.0 6.0 107.4 25.35 98.7 23.15 91.9 21.31 91.9 21.31 91.9 21.31 81.6 18.12 69.4 15.31

8.6 7.5 108.9 24.38 98.7 21.68 91.9 19.99 91.9 19.99 91.9 19.99 81.6 17.04 69.4 14.43

11.2 10.0 108.9 21.68 98.7 19.34 91.9 17.86 91.9 17.86 91.9 17.86 81.6 15.31 69.4 13.03

16.4 15.0 108.9 16.85 98.7 15.15 91.9 14.06 91.9 14.06 91.9 14.06 81.6 12.25 69.4 10.53

24.0 18.0 108.9 14.33 98.7 12.97 91.9 12.09 91.9 12.09 91.9 12.09 81.6 10.67 69.4 9.24

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 67.2 21.96 62.0 20.26 58.4 19.09 58.4 19.09 56.0 18.25 49.7 16.32 43.1 14.41

-14.7 -15.0 71.2 22.33 65.8 20.63 62.1 19.48 62.1 19.48 59.8 18.66 53.1 16.69 46.1 14.74

-9.6 -10.0 76.5 22.89 70.8 21.20 66.9 20.05 66.9 20.05 64.7 19.25 57.6 17.22 50.1 15.19

-4.4 -5.0 83.4 23.75 77.4 22.04 73.3 20.85 73.3 20.85 71.1 20.05 63.4 17.94 55.4 15.81

-1.8 -2.5 87.9 24.30 81.7 22.56 77.4 21.37 77.4 21.37 75.3 20.57 67.2 18.43 58.8 16.24

0.8 0.0 93.1 24.94 86.7 23.19 82.3 21.98 82.3 21.98 80.2 21.20 71.8 18.97 62.1 16.46

110% 2.8 2.0 97.7 25.35 91.5 23.71 86.9 22.46 86.9 22.46 84.0 21.41 73.1 18.43 62.1 15.64

6.0 5.0 105.1 25.35 96.3 23.05 89.7 21.24 89.7 21.24 84.0 19.42 73.1 16.77 62.1 14.24

7.0 6.0 106.3 24.84 96.3 22.13 89.7 20.42 89.7 20.42 84.0 18.68 73.1 16.15 62.1 13.71

8.6 7.5 106.3 23.22 96.3 20.73 89.7 19.13 89.7 19.13 84.0 17.55 73.1 15.17 62.1 12.91

11.2 10.0 106.3 20.65 96.3 18.47 89.7 17.08 89.7 17.08 84.0 15.72 73.1 13.65 62.1 11.68

16.4 15.0 106.3 15.99 96.3 14.43 89.7 13.42 89.7 13.42 84.0 12.48 73.1 10.94 62.1 9.46

24.0 18.0 106.3 13.59 96.3 12.34 89.7 11.52 89.7 11.52 84.0 10.80 73.1 9.56 62.1 8.33

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 67.3 21.72 62.0 20.07 58.5 18.93 54.8 17.78 51.0 16.63 45.2 14.90 39.1 13.20

-14.7 -15.0 71.4 22.11 66.0 20.46 62.2 19.32 58.4 18.17 54.4 17.00 48.3 15.23 41.9 13.49

-9.6 -10.0 76.6 22.70 70.9 21.02 66.9 19.89 62.9 18.72 58.8 17.53 52.2 15.70 45.5 13.88

-4.4 -5.0 83.6 23.56 77.5 21.86 73.4 20.69 69.0 19.48 64.6 18.25 57.7 16.36 50.2 14.45

-1.8 -2.5 87.9 24.10 81.7 22.39 77.4 21.20 73.0 19.97 68.3 18.72 61.0 16.79 53.3 14.82

0.8 0.0 93.2 24.75 86.7 23.01 82.3 21.80 77.5 20.53 72.7 19.23 64.8 17.16 55.1 14.63

100% 2.8 2.0 98.1 25.25 91.4 23.48 86.8 22.25 81.0 20.63 74.6 18.86 64.8 16.30 55.1 13.90

6.0 5.0 103.7 24.67 94.0 22.04 87.5 20.34 81.0 18.70 74.6 17.12 64.8 14.84 55.1 12.66

7.0 6.0 103.7 23.65 94.0 21.14 87.5 19.50 81.0 17.98 74.6 16.48 64.8 14.27 55.1 12.19

8.6 7.5 103.7 22.11 94.0 19.79 87.5 18.31 81.0 16.87 74.6 15.46 64.8 13.44 55.1 11.51

11.2 10.0 103.7 19.64 94.0 17.63 87.5 16.34 81.0 15.07 74.6 13.86 64.8 12.11 55.1 10.39

16.4 15.0 103.7 15.17 94.0 13.75 87.5 12.81 81.0 11.91 74.6 11.02 64.8 9.73 55.1 8.46

9 24.0 18.0 103.7 12.87 94.0 11.74 87.5 11.00 81.0 10.28 74.6 9.56 64.8 8.50 55.1 7.47
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


28 HP (U-14MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 67.9 20.90 62.5 19.38 58.7 18.33 55.0 17.26 51.1 16.20 45.2 14.61 39.0 13.07

-14.7 -15.0 72.0 21.37 66.3 19.81 62.5 18.74 58.5 17.67 54.5 16.58 48.2 14.94 41.7 13.32

-9.6 -10.0 77.3 22.00 71.3 20.42 67.3 19.32 63.1 18.21 58.8 17.08 52.2 15.37 45.2 13.67

-4.4 -5.0 84.2 22.85 77.9 21.24 73.5 20.10 69.0 18.93 64.4 17.76 57.2 15.97 49.6 14.10

-1.8 -2.5 88.5 23.40 81.9 21.74 77.4 20.57 72.7 19.38 67.1 17.88 58.4 15.64 49.6 13.51

0.8 0.0 93.4 23.79 84.6 21.41 78.8 19.85 72.9 18.35 67.1 16.89 58.4 14.78 49.6 12.79

90% 2.8 2.0 93.4 22.44 84.6 20.22 78.8 18.78 72.9 17.37 67.1 16.01 58.4 14.04 49.6 12.13

6.0 5.0 93.4 20.16 84.6 18.21 78.8 16.97 72.9 15.72 67.1 14.51 58.4 12.73 49.6 11.00

7.0 6.0 93.4 19.31 84.6 17.47 78.8 16.26 72.9 15.09 67.1 13.94 58.4 12.25 49.6 10.59

8.6 7.5 93.4 18.00 84.6 16.30 78.8 15.21 72.9 14.14 67.1 13.07 58.4 11.51 49.6 9.98

11.2 10.0 93.4 15.89 84.6 14.47 78.8 13.53 72.9 12.62 67.1 11.70 58.4 10.35 49.6 9.03

16.4 15.0 93.4 12.17 84.6 11.19 78.8 10.55 72.9 9.91 67.1 9.26 58.4 8.31 49.6 7.35

24.0 18.0 93.4 11.41 84.6 10.49 78.8 9.89 72.9 9.28 67.1 8.66 58.4 7.74 49.6 6.84

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 68.6 20.28 63.0 18.86 59.2 17.88 55.4 16.91 51.4 15.91 45.3 14.47 39.1 13.03

-14.7 -15.0 72.8 20.79 66.9 19.31 63.0 18.31 58.9 17.30 54.8 16.28 48.4 14.76 41.7 13.26

-9.6 -10.0 78.1 21.43 71.9 19.93 67.6 18.90 63.4 17.84 59.0 16.77 51.9 15.07 44.1 13.22

-4.4 -5.0 83.0 21.59 75.2 19.62 70.0 18.33 64.8 17.08 59.6 15.85 51.9 14.08 44.1 12.36

-1.8 -2.5 83.0 20.48 75.2 18.62 70.0 17.41 64.8 16.24 59.6 15.07 51.9 13.40 44.1 11.76

0.8 0.0 83.0 19.23 75.2 17.53 70.0 16.40 64.8 15.31 59.6 14.22 51.9 12.64 44.1 11.10

80% 2.8 2.0 83.0 18.12 75.2 16.54 70.0 15.50 64.8 14.47 59.6 13.46 51.9 11.97 44.1 10.51

6.0 5.0 83.0 16.20 75.2 14.84 70.0 13.94 64.8 13.05 59.6 12.15 51.9 10.82 44.1 9.46

7.0 6.0 83.0 15.48 75.2 14.22 70.0 13.36 64.8 12.52 59.6 11.66 51.9 10.39 44.1 9.11

8.6 7.5 83.0 14.39 75.2 13.24 70.0 12.48 64.8 11.70 59.6 10.94 51.9 9.77 44.1 8.60

11.2 10.0 83.0 12.66 75.2 11.72 70.0 11.08 64.8 10.43 59.6 9.77 51.9 8.79 44.1 7.78

16.4 15.0 83.0 10.32 75.2 9.52 70.0 8.97 64.8 8.42 59.6 7.88 51.9 7.08 44.1 6.34

24.0 18.0 83.0 10.32 75.2 9.52 70.0 8.97 64.8 8.42 59.6 7.88 51.9 7.08 44.1 6.26

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 69.9 19.93 64.1 18.60 60.1 17.71 56.1 16.79 52.1 15.89 45.4 14.39 38.6 12.91

-14.7 -15.0 72.6 19.93 65.8 18.33 61.3 17.26 56.7 16.20 52.2 15.19 45.4 13.69 38.6 12.23

-9.6 -10.0 72.6 18.80 65.8 17.32 61.3 16.32 56.7 15.37 52.2 14.41 45.4 12.95 38.6 11.52

-4.4 -5.0 72.6 17.24 65.8 15.89 61.3 15.02 56.7 14.14 52.2 13.26 45.4 11.97 38.6 10.71

-1.8 -2.5 72.6 16.32 65.8 15.05 61.3 14.24 56.7 13.42 52.2 12.60 45.4 11.39 38.6 10.16

0.8 0.0 72.6 15.27 65.8 14.14 61.3 13.38 56.7 12.62 52.2 11.86 45.4 10.73 38.6 9.57

70% 2.8 2.0 72.6 14.35 65.8 13.30 61.3 12.62 56.7 11.91 52.2 11.19 45.4 10.14 38.6 8.99

6.0 5.0 72.6 12.79 65.8 11.90 61.3 11.29 56.7 10.69 52.2 10.06 45.4 9.07 38.6 8.05

7.0 6.0 72.6 12.21 65.8 11.37 61.3 10.80 56.7 10.24 52.2 9.63 45.4 8.72 38.6 7.76

8.6 7.5 72.6 11.31 65.8 10.59 61.3 10.08 56.7 9.56 52.2 9.03 45.4 8.19 38.6 7.33

11.2 10.0 72.6 9.89 65.8 9.32 61.3 8.91 56.7 8.50 52.2 8.07 45.4 7.37 38.6 6.65

16.4 15.0 72.6 9.24 65.8 8.52 61.3 8.05 56.7 7.59 52.2 7.10 45.4 6.40 38.6 5.69

24.0 18.0 72.6 9.24 65.8 8.52 61.3 8.05 56.7 7.59 52.2 7.10 45.4 6.40 38.6 5.69

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 62.2 16.79 56.4 15.66 52.5 14.88 48.7 14.12 44.7 13.38 38.9 12.27 33.1 11.17

-14.7 -15.0 62.2 15.89 56.4 14.88 52.5 14.20 48.7 13.51 44.7 12.77 38.9 11.68 33.1 10.59

-9.6 -10.0 62.2 14.82 56.4 13.88 52.5 13.26 48.7 12.64 44.7 12.01 38.9 11.04 33.1 9.98

-4.4 -5.0 62.2 13.51 56.4 12.69 52.5 12.15 48.7 11.58 44.7 11.00 38.9 10.12 33.1 9.20

-1.8 -2.5 62.2 12.75 56.4 11.99 52.5 11.49 48.7 10.96 44.7 10.43 38.9 9.59 33.1 8.72

0.8 0.0 62.2 11.90 56.4 11.23 52.5 10.76 48.7 10.28 44.7 9.79 38.9 9.01 33.1 8.11

60% 2.8 2.0 62.2 11.15 56.4 10.55 52.5 10.12 48.7 9.67 44.7 9.20 38.9 8.44 33.1 7.57

6.0 5.0 62.2 9.89 56.4 9.38 52.5 9.01 48.7 8.60 44.7 8.19 38.9 7.51 33.1 6.79

7.0 6.0 62.2 9.42 56.4 8.95 52.5 8.60 48.7 8.23 44.7 7.86 38.9 7.22 33.1 6.55

8.6 7.5 62.2 8.70 56.4 8.31 52.5 8.01 48.7 7.70 44.7 7.35 38.9 6.81 33.1 6.18

11.2 10.0 62.2 8.15 56.4 7.55 52.5 7.14 48.7 6.83 44.7 6.57 38.9 6.12 33.1 5.62

16.4 15.0 62.2 8.15 56.4 7.55 52.5 7.14 48.7 6.73 44.7 6.34 38.9 5.71 33.1 5.11

24.0 18.0 62.2 8.15 56.4 7.55 52.5 7.14 48.7 6.73 44.7 6.34 38.9 5.71 33.1 5.11

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


28 HP (U-14MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 51.9 13.14 47.0 12.56 43.8 12.13 40.5 11.66 37.3 11.15 32.4 10.37 27.6 9.57

-14.7 -15.0 51.9 12.40 47.0 11.86 43.8 11.47 40.5 11.06 37.3 10.63 32.4 9.87 27.6 9.05

-9.6 -10.0 51.9 11.51 47.0 11.02 43.8 10.69 40.5 10.32 37.3 9.93 32.4 9.28 27.6 8.54

-4.4 -5.0 51.9 10.43 47.0 10.02 43.8 9.71 40.5 9.40 37.3 9.05 32.4 8.48 27.6 7.84

-1.8 -2.5 51.9 9.81 47.0 9.44 43.8 9.17 40.5 8.85 37.3 8.54 32.4 8.01 27.6 7.25

0.8 0.0 51.9 9.13 47.0 8.79 43.8 8.54 40.5 8.27 37.3 7.98 32.4 7.39 27.6 6.71

50% 2.8 2.0 51.9 8.52 47.0 8.23 43.8 8.00 40.5 7.74 37.3 7.41 32.4 6.86 27.6 6.26

6.0 5.0 51.9 7.47 47.0 7.23 43.8 7.04 40.5 6.81 37.3 6.57 32.4 6.14 27.6 5.64

7.0 6.0 51.9 7.10 47.0 6.88 43.8 6.71 40.5 6.51 37.3 6.30 32.4 5.91 27.6 5.44

8.6 7.5 51.9 7.08 47.0 6.57 43.8 6.26 40.5 6.08 37.3 5.89 32.4 5.56 27.6 5.17

11.2 10.0 51.9 7.08 47.0 6.57 43.8 6.22 40.5 5.89 37.3 5.56 32.4 5.05 27.6 4.70

16.4 15.0 51.9 7.08 47.0 6.57 43.8 6.22 40.5 5.89 37.3 5.56 32.4 5.05 27.6 4.52

24.0 18.0 51.9 7.08 47.0 6.57 43.8 6.22 40.5 5.89 37.3 5.56 32.4 5.05 27.6 4.52

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 41.5 10.22 37.6 9.95 35.0 9.75 32.4 9.50 29.8 9.17 25.9 8.64 22.1 8.05

-14.7 -15.0 41.5 9.59 37.6 9.36 35.0 9.18 32.4 8.97 29.8 8.72 25.9 8.21 22.1 7.62

-9.6 -10.0 41.5 8.85 37.6 8.68 35.0 8.52 32.4 8.33 29.8 8.11 25.9 7.70 22.1 7.18

-4.4 -5.0 41.5 7.98 37.6 7.82 35.0 7.70 32.4 7.55 29.8 7.35 25.9 6.92 22.1 6.32

-1.8 -2.5 41.5 7.45 37.6 7.33 35.0 7.23 32.4 7.08 29.8 6.84 25.9 6.40 22.1 5.87

0.8 0.0 41.5 6.90 37.6 6.81 35.0 6.67 32.4 6.47 29.8 6.26 25.9 5.87 22.1 5.44

40% 2.8 2.0 41.5 6.40 37.6 6.26 35.0 6.14 32.4 5.99 29.8 5.81 25.9 5.48 22.1 5.09

6.0 5.0 41.5 5.99 37.6 5.58 35.0 5.38 32.4 5.28 29.8 5.17 25.9 4.91 22.1 4.62

7.0 6.0 41.5 5.99 37.6 5.58 35.0 5.30 32.4 5.07 29.8 4.95 25.9 4.74 22.1 4.47

8.6 7.5 41.5 5.99 37.6 5.58 35.0 5.30 32.4 5.05 29.8 4.78 25.9 4.49 22.1 4.25

11.2 10.0 41.5 5.99 37.6 5.58 35.0 5.30 32.4 5.05 29.8 4.78 25.9 4.37 22.1 3.96

16.4 15.0 41.5 5.99 37.6 5.58 35.0 5.30 32.4 5.05 29.8 4.78 25.9 4.37 22.1 3.96

24.0 18.0 41.5 5.99 37.6 5.58 35.0 5.30 32.4 5.05 29.8 4.78 25.9 4.37 22.1 3.96

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 31.2 7.86 28.2 7.78 26.3 7.70 24.3 7.57 22.4 7.35 19.4 6.98 16.5 6.57

-14.7 -15.0 31.2 7.35 28.2 7.31 26.3 7.23 24.3 7.12 22.4 6.98 19.4 6.63 16.5 6.20

-9.6 -10.0 31.2 6.77 28.2 6.75 26.3 6.69 24.3 6.61 22.4 6.47 19.4 6.10 16.5 5.62

-4.4 -5.0 31.2 6.05 28.2 6.05 26.3 5.93 24.3 5.79 22.4 5.62 19.4 5.30 16.5 4.93

-1.8 -2.5 31.2 5.60 28.2 5.52 26.3 5.42 24.3 5.32 22.4 5.19 19.4 4.93 16.5 4.62

0.8 0.0 31.2 5.01 28.2 4.99 26.3 4.93 24.3 4.88 22.4 4.76 19.4 4.56 16.5 4.29

30% 2.8 2.0 31.2 4.91 28.2 4.60 26.3 4.56 24.3 4.52 22.4 4.45 19.4 4.27 16.5 4.06

6.0 5.0 31.2 4.91 28.2 4.60 26.3 4.41 24.3 4.19 22.4 4.00 19.4 3.88 16.5 3.71

7.0 6.0 31.2 4.91 28.2 4.60 26.3 4.41 24.3 4.19 22.4 4.00 19.4 3.74 16.5 3.61

8.6 7.5 31.2 4.91 28.2 4.60 26.3 4.41 24.3 4.19 22.4 4.00 19.4 3.69 16.5 3.43

11.2 10.0 31.2 4.91 28.2 4.60 26.3 4.41 24.3 4.19 22.4 4.00 19.4 3.69 16.5 3.37

16.4 15.0 31.2 4.91 28.2 4.60 26.3 4.41 24.3 4.19 22.4 4.00 19.4 3.69 16.5 3.37

24.0 18.0 31.2 4.91 28.2 4.60 26.3 4.41 24.3 4.19 22.4 4.00 19.4 3.69 16.5 3.37

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


30 HP (U-14MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 71.6 25.45 66.1 23.41 62.3 22.06 62.3 22.06 62.3 22.06 62.3 22.06 54.5 19.10

-14.7 -15.0 75.9 25.83 70.2 23.82 66.3 22.46 66.3 22.46 66.3 22.46 66.3 22.46 58.4 19.55

-9.6 -10.0 81.5 26.44 75.5 24.45 71.4 23.07 71.4 23.07 71.4 23.07 71.4 23.07 63.6 20.18

-4.4 -5.0 88.9 27.37 82.7 25.38 78.5 24.00 78.5 24.00 78.5 24.00 78.5 24.00 70.5 21.09

-1.8 -2.5 93.8 28.00 87.3 26.01 82.8 24.61 82.8 24.61 82.8 24.61 82.8 24.61 74.9 21.70

0.8 0.0 99.5 28.77 92.8 26.74 88.2 25.33 88.2 25.33 88.2 25.33 88.2 25.33 80.4 22.44

130% 2.8 2.0 104.6 29.38 97.9 27.44 93.2 26.01 93.2 26.01 93.2 26.01 93.2 26.01 83.6 22.40

6.0 5.0 112.5 29.38 107.9 28.54 102.1 26.83 102.1 26.83 102.1 26.83 98.3 24.27 83.6 20.39

7.0 6.0 115.8 29.38 109.7 28.09 102.1 25.79 102.1 25.79 102.1 25.79 98.3 23.37 83.6 19.62

8.6 7.5 120.3 29.38 109.7 26.35 102.1 24.20 102.1 24.20 102.1 24.20 98.3 21.97 83.6 18.49

11.2 10.0 121.0 26.53 109.7 23.55 102.1 21.67 102.1 21.67 102.1 21.67 98.3 19.75 83.6 16.68

16.4 15.0 121.0 20.70 109.7 18.49 102.1 17.09 102.1 17.09 102.1 17.09 98.3 15.80 83.6 13.45

24.0 18.0 121.0 17.67 109.7 15.89 102.1 14.74 102.1 14.74 102.1 14.74 98.3 13.74 83.6 11.80

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 71.7 25.18 66.2 23.19 62.4 21.85 62.4 21.85 62.4 21.85 58.0 20.11 50.3 17.70

-14.7 -15.0 76.1 25.58 70.4 23.62 66.4 22.28 66.4 22.28 66.4 22.28 62.0 20.57 54.0 18.10

-9.6 -10.0 81.6 26.22 75.7 24.25 71.5 22.89 71.5 22.89 71.5 22.89 67.3 21.22 58.6 18.67

-4.4 -5.0 89.1 27.17 82.8 25.18 78.5 23.82 78.5 23.82 78.5 23.82 74.3 22.17 64.9 19.48

-1.8 -2.5 93.9 27.80 87.4 25.81 82.8 24.41 82.8 24.41 82.8 24.41 78.8 22.76 68.9 20.02

0.8 0.0 99.6 28.54 92.8 26.53 88.2 25.13 88.2 25.13 88.2 25.13 84.1 23.53 73.9 20.68

120% 2.8 2.0 104.9 29.22 97.9 27.21 93.1 25.79 93.1 25.79 93.1 25.79 88.6 23.89 75.3 20.14

6.0 5.0 113.1 29.38 107.2 27.98 99.8 25.70 99.8 25.70 99.8 25.70 88.6 21.74 75.3 18.33

7.0 6.0 116.3 29.38 107.2 26.87 99.8 24.70 99.8 24.70 99.8 24.70 88.6 20.93 75.3 17.65

8.6 7.5 118.2 28.36 107.2 25.20 99.8 23.19 99.8 23.19 99.8 23.19 88.6 19.68 75.3 16.63

11.2 10.0 118.2 25.27 107.2 22.49 99.8 20.72 99.8 20.72 99.8 20.72 88.6 17.70 75.3 15.01

16.4 15.0 118.2 19.66 107.2 17.63 99.8 16.34 99.8 16.34 99.8 16.34 88.6 14.15 75.3 12.14

24.0 18.0 118.2 16.77 107.2 15.12 99.8 14.06 99.8 14.06 99.8 14.06 88.6 12.34 75.3 10.67

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 71.9 24.91 66.3 22.96 62.5 21.65 62.5 21.65 60.0 20.68 53.2 18.46 46.1 16.29

-14.7 -15.0 76.3 25.33 70.5 23.41 66.5 22.08 66.5 22.08 64.0 21.15 56.8 18.89 49.4 16.66

-9.6 -10.0 81.8 25.99 75.8 24.05 71.6 22.71 71.6 22.71 69.2 21.81 61.7 19.48 53.7 17.18

-4.4 -5.0 89.3 26.96 82.9 25.00 78.6 23.64 78.6 23.64 76.2 22.74 68.0 20.32 59.4 17.90

-1.8 -2.5 94.1 27.57 87.5 25.61 82.9 24.23 82.9 24.23 80.6 23.32 72.0 20.86 63.0 18.37

0.8 0.0 99.7 28.32 92.8 26.33 88.1 24.93 88.1 24.93 85.8 24.05 76.9 21.52 67.5 18.94

110% 2.8 2.0 105.0 29.00 97.9 26.94 93.1 25.54 93.1 25.54 90.9 24.66 79.3 21.27 67.5 17.99

6.0 5.0 113.8 29.38 104.6 26.76 97.4 24.61 97.4 24.61 91.2 22.46 79.3 19.35 67.5 16.39

7.0 6.0 115.4 28.88 104.6 25.70 97.4 23.66 97.4 23.66 91.2 21.61 79.3 18.62 67.5 15.77

8.6 7.5 115.4 27.03 104.6 24.07 97.4 22.19 97.4 22.19 91.2 20.29 79.3 17.52 67.5 14.87

11.2 10.0 115.4 24.05 104.6 21.47 97.4 19.82 97.4 19.82 91.2 18.19 79.3 15.75 67.5 13.42

16.4 15.0 115.4 18.67 104.6 16.79 97.4 15.59 97.4 15.59 91.2 14.44 79.3 12.63 67.5 10.89

24.0 18.0 115.4 15.89 104.6 14.37 97.4 13.42 97.4 13.42 91.2 12.52 79.3 11.03 67.5 9.58

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 72.0 24.63 66.4 22.76 62.6 21.47 58.6 20.16 54.5 18.83 48.4 16.86 41.9 14.92

-14.7 -15.0 76.4 25.11 70.6 23.21 66.6 21.90 62.4 20.59 58.2 19.26 51.7 17.24 44.8 15.26

-9.6 -10.0 82.0 25.76 75.9 23.87 71.7 22.55 67.4 21.20 62.9 19.84 56.0 17.76 48.7 15.71

-4.4 -5.0 89.5 26.74 83.0 24.81 78.6 23.46 73.9 22.08 69.2 20.68 61.7 18.51 53.9 16.34

-1.8 -2.5 94.1 27.37 87.5 25.40 82.9 24.05 78.1 22.65 73.2 21.20 65.3 19.01 57.1 16.75

0.8 0.0 99.8 28.09 92.9 26.13 88.1 24.72 83.0 23.30 77.8 21.81 69.7 19.55 59.9 16.81

100% 2.8 2.0 105.1 28.72 97.9 26.69 93.0 25.27 87.9 23.82 80.9 21.79 70.4 18.80 59.9 15.98

6.0 5.0 112.6 28.68 102.0 25.56 95.0 23.57 88.0 21.65 80.9 19.78 70.4 17.11 59.9 14.55

7.0 6.0 112.6 27.50 102.0 24.54 95.0 22.60 88.0 20.81 80.9 19.03 70.4 16.48 59.9 14.01

8.6 7.5 112.6 25.72 102.0 22.98 95.0 21.22 88.0 19.53 80.9 17.88 70.4 15.50 59.9 13.22

11.2 10.0 112.6 22.85 102.0 20.48 95.0 18.94 88.0 17.47 80.9 16.02 70.4 13.94 59.9 11.96

16.4 15.0 112.6 17.72 102.0 15.98 95.0 14.87 88.0 13.81 80.9 12.75 70.4 11.21 59.9 9.72

9 24.0 18.0 112.6 15.05 102.0 13.67 95.0 12.79 88.0 11.91 80.9 11.05 70.4 9.81 59.9 8.57
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


30 HP (U-14MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 72.7 23.73 66.9 21.97 62.9 20.77 58.8 19.55 54.7 18.35 48.4 16.52 41.8 14.76

-14.7 -15.0 77.0 24.25 71.1 22.46 66.9 21.24 62.7 20.00 58.3 18.76 51.7 16.88 44.7 15.05

-9.6 -10.0 82.7 24.95 76.4 23.14 72.0 21.90 67.5 20.63 62.9 19.35 55.9 17.38 48.5 15.44

-4.4 -5.0 90.1 25.94 83.3 24.07 78.7 22.78 73.9 21.47 69.0 20.11 61.3 18.06 53.3 15.98

-1.8 -2.5 94.7 26.56 87.7 24.66 82.9 23.35 77.9 21.99 72.8 20.59 63.4 17.99 53.9 15.53

0.8 0.0 100.1 27.14 91.9 24.79 85.5 22.96 79.1 21.20 72.9 19.48 63.4 17.02 53.9 14.69

90% 2.8 2.0 101.4 26.06 91.9 23.41 85.5 21.72 79.1 20.07 72.9 18.46 63.4 16.16 53.9 13.94

6.0 5.0 101.4 23.41 91.9 21.11 85.5 19.62 79.1 18.17 72.9 16.75 63.4 14.67 53.9 12.63

7.0 6.0 101.4 22.42 91.9 20.25 85.5 18.83 79.1 17.45 72.9 16.09 63.4 14.10 53.9 12.16

8.6 7.5 101.4 20.91 91.9 18.92 85.5 17.61 79.1 16.34 72.9 15.10 63.4 13.24 53.9 11.46

11.2 10.0 101.4 18.49 91.9 16.79 85.5 15.68 79.1 14.58 72.9 13.51 63.4 11.93 53.9 10.37

16.4 15.0 101.4 14.17 91.9 13.00 85.5 12.23 79.1 11.46 72.9 10.69 63.4 9.56 53.9 8.43

24.0 18.0 101.4 13.02 91.9 11.96 85.5 11.25 79.1 10.55 72.9 9.85 63.4 8.81 53.9 7.75

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 73.4 22.98 67.5 21.36 63.4 20.25 59.3 19.14 55.0 18.01 48.5 16.34 41.8 14.71

-14.7 -15.0 77.9 23.55 71.6 21.88 67.5 20.75 63.1 19.59 58.6 18.42 51.8 16.68 44.7 14.96

-9.6 -10.0 83.6 24.32 77.0 22.58 72.5 21.40 67.8 20.20 63.1 18.98 55.9 17.13 47.9 15.16

-4.4 -5.0 90.1 25.00 81.6 22.67 76.0 21.18 70.4 19.68 64.7 18.26 56.3 16.16 47.9 14.17

-1.8 -2.5 90.1 23.73 81.6 21.54 76.0 20.11 70.4 18.71 64.7 17.36 56.3 15.39 47.9 13.49

0.8 0.0 90.1 22.28 81.6 20.25 76.0 18.94 70.4 17.65 64.7 16.39 56.3 14.53 47.9 12.72

80% 2.8 2.0 90.1 21.00 81.6 19.12 76.0 17.90 70.4 16.70 64.7 15.50 56.3 13.76 47.9 12.07

6.0 5.0 90.1 18.78 81.6 17.18 76.0 16.11 70.4 15.05 64.7 13.99 56.3 12.43 47.9 10.85

7.0 6.0 90.1 17.97 81.6 16.45 76.0 15.44 70.4 14.44 64.7 13.42 56.3 11.93 47.9 10.44

8.6 7.5 90.1 16.70 81.6 15.32 76.0 14.42 70.4 13.49 64.7 12.59 56.3 11.21 47.9 9.85

11.2 10.0 90.1 14.69 81.6 13.56 76.0 12.79 70.4 12.02 64.7 11.25 56.3 10.08 47.9 8.90

16.4 15.0 90.1 11.75 81.6 10.83 76.0 10.22 70.4 9.58 64.7 8.95 56.3 8.07 47.9 7.25

24.0 18.0 90.1 11.75 81.6 10.83 76.0 10.22 70.4 9.58 64.7 8.95 56.3 8.02 47.9 7.10

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 74.8 22.58 68.6 21.06 64.4 20.02 60.0 19.01 55.8 17.97 49.0 16.43 41.9 14.80

-14.7 -15.0 78.9 23.01 71.4 21.11 66.5 19.87 61.6 18.65 56.6 17.45 49.3 15.71 41.9 14.01

-9.6 -10.0 78.9 21.72 71.4 19.98 66.5 18.83 61.6 17.67 56.6 16.54 49.3 14.85 41.9 13.20

-4.4 -5.0 78.9 19.91 71.4 18.33 66.5 17.29 61.6 16.27 56.6 15.26 49.3 13.74 41.9 12.27

-1.8 -2.5 78.9 18.85 71.4 17.38 66.5 16.41 61.6 15.44 56.6 14.49 49.3 13.06 41.9 11.64

0.8 0.0 78.9 17.65 71.4 16.32 66.5 15.41 61.6 14.51 56.6 13.63 49.3 12.29 41.9 10.96

70% 2.8 2.0 78.9 16.59 71.4 15.37 66.5 14.53 61.6 13.70 56.6 12.88 49.3 11.62 41.9 10.31

6.0 5.0 78.9 14.78 71.4 13.74 66.5 13.02 61.6 12.29 56.6 11.55 49.3 10.40 41.9 9.22

7.0 6.0 78.9 14.10 71.4 13.13 66.5 12.45 61.6 11.77 56.6 11.07 49.3 9.99 41.9 8.88

8.6 7.5 78.9 13.09 71.4 12.20 66.5 11.62 61.6 11.01 56.6 10.37 49.3 9.40 41.9 8.38

11.2 10.0 78.9 11.46 71.4 10.76 66.5 10.28 61.6 9.79 56.6 9.27 49.3 8.45 41.9 7.59

16.4 15.0 78.9 10.51 71.4 9.70 66.5 9.15 61.6 8.61 56.6 8.07 49.3 7.25 41.9 6.44

24.0 18.0 78.9 10.51 71.4 9.70 66.5 9.15 61.6 8.61 56.6 8.07 49.3 7.25 41.9 6.44

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 67.5 19.35 61.2 17.99 57.0 17.09 52.8 16.20 48.5 15.32 42.2 14.03 35.9 12.77

-14.7 -15.0 67.5 18.31 61.2 17.13 57.0 16.32 52.8 15.50 48.5 14.64 42.2 13.36 35.9 12.09

-9.6 -10.0 67.5 17.09 61.2 15.98 57.0 15.26 52.8 14.51 48.5 13.79 42.2 12.63 35.9 11.39

-4.4 -5.0 67.5 15.59 61.2 14.62 57.0 13.97 52.8 13.29 48.5 12.61 42.2 11.59 35.9 10.53

-1.8 -2.5 67.5 14.71 61.2 13.81 57.0 13.20 52.8 12.59 48.5 11.96 42.2 10.98 35.9 9.97

0.8 0.0 67.5 13.72 61.2 12.93 57.0 12.36 52.8 11.80 48.5 11.21 42.2 10.31 35.9 9.24

60% 2.8 2.0 67.5 12.86 61.2 12.14 57.0 11.62 52.8 11.10 48.5 10.55 42.2 9.65 35.9 8.63

6.0 5.0 67.5 11.39 61.2 10.78 57.0 10.35 52.8 9.88 48.5 9.38 42.2 8.59 35.9 7.75

7.0 6.0 67.5 10.85 61.2 10.28 57.0 9.88 52.8 9.45 48.5 8.99 42.2 8.25 35.9 7.46

8.6 7.5 67.5 10.03 61.2 9.56 57.0 9.20 52.8 8.81 48.5 8.43 42.2 7.77 35.9 7.05

11.2 10.0 67.5 9.27 61.2 8.57 57.0 8.11 52.8 7.84 48.5 7.50 42.2 6.98 35.9 6.40

16.4 15.0 67.5 9.27 61.2 8.57 57.0 8.11 52.8 7.64 48.5 7.16 42.2 6.46 35.9 5.76

24.0 18.0 67.5 9.27 61.2 8.57 57.0 8.11 52.8 7.64 48.5 7.16 42.2 6.46 35.9 5.76

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


30 HP (U-14MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 56.3 15.12 51.0 14.42 47.5 13.92 44.0 13.36 40.5 12.75 35.2 11.84 29.9 10.92

-14.7 -15.0 56.3 14.26 51.0 13.61 47.5 13.15 44.0 12.68 40.5 12.18 35.2 11.28 29.9 10.33

-9.6 -10.0 56.3 13.24 51.0 12.66 47.5 12.25 44.0 11.82 40.5 11.35 35.2 10.62 29.9 9.74

-4.4 -5.0 56.3 12.00 51.0 11.50 47.5 11.14 44.0 10.76 40.5 10.35 35.2 9.67 29.9 8.93

-1.8 -2.5 56.3 11.28 51.0 10.83 47.5 10.49 44.0 10.15 40.5 9.76 35.2 9.13 29.9 8.27

0.8 0.0 56.3 10.49 51.0 10.08 47.5 9.79 44.0 9.47 40.5 9.11 35.2 8.43 29.9 7.64

50% 2.8 2.0 56.3 9.79 51.0 9.42 47.5 9.18 44.0 8.86 40.5 8.48 35.2 7.82 29.9 7.12

6.0 5.0 56.3 8.59 51.0 8.29 47.5 8.05 44.0 7.80 40.5 7.48 35.2 6.98 29.9 6.42

7.0 6.0 56.3 8.14 51.0 7.89 47.5 7.68 44.0 7.46 40.5 7.19 35.2 6.71 29.9 6.19

8.6 7.5 56.3 8.02 51.0 7.44 47.5 7.14 44.0 6.96 40.5 6.73 35.2 6.33 29.9 5.85

11.2 10.0 56.3 8.02 51.0 7.44 47.5 7.05 44.0 6.67 40.5 6.28 35.2 5.70 29.9 5.33

16.4 15.0 56.3 8.02 51.0 7.44 47.5 7.05 44.0 6.67 40.5 6.28 35.2 5.70 29.9 5.11

24.0 18.0 56.3 8.02 51.0 7.44 47.5 7.05 44.0 6.67 40.5 6.28 35.2 5.70 29.9 5.11

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 45.0 11.71 40.9 11.39 38.0 11.14 35.2 10.85 32.4 10.46 28.1 9.83 23.9 9.18

-14.7 -15.0 45.0 10.98 40.9 10.71 38.0 10.49 35.2 10.24 32.4 9.94 28.1 9.36 23.9 8.66

-9.6 -10.0 45.0 10.15 40.9 9.92 38.0 9.74 35.2 9.51 32.4 9.24 28.1 8.77 23.9 8.16

-4.4 -5.0 45.0 9.13 40.9 8.95 38.0 8.79 35.2 8.61 32.4 8.38 28.1 7.89 23.9 7.19

-1.8 -2.5 45.0 8.54 40.9 8.38 38.0 8.25 35.2 8.09 32.4 7.80 28.1 7.28 23.9 6.67

0.8 0.0 45.0 7.89 40.9 7.77 38.0 7.59 35.2 7.39 32.4 7.12 28.1 6.69 23.9 6.17

40% 2.8 2.0 45.0 7.30 40.9 7.14 38.0 7.01 35.2 6.83 32.4 6.60 28.1 6.22 23.9 5.76

6.0 5.0 45.0 6.78 40.9 6.31 38.0 6.12 35.2 6.01 32.4 5.85 28.1 5.58 23.9 5.22

7.0 6.0 45.0 6.78 40.9 6.31 38.0 6.01 35.2 5.76 32.4 5.63 28.1 5.38 23.9 5.04

8.6 7.5 45.0 6.78 40.9 6.31 38.0 6.01 35.2 5.70 32.4 5.38 28.1 5.06 23.9 4.79

11.2 10.0 45.0 6.78 40.9 6.31 38.0 6.01 35.2 5.70 32.4 5.38 28.1 4.90 23.9 4.45

16.4 15.0 45.0 6.78 40.9 6.31 38.0 6.01 35.2 5.70 32.4 5.38 28.1 4.90 23.9 4.45

24.0 18.0 45.0 6.78 40.9 6.31 38.0 6.01 35.2 5.70 32.4 5.38 28.1 4.90 23.9 4.45

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 33.8 8.97 30.6 8.88 28.5 8.77 26.4 8.61 24.3 8.34 21.1 7.93 18.0 7.48

-14.7 -15.0 33.8 8.38 30.6 8.32 28.5 8.23 26.4 8.11 24.3 7.93 21.1 7.53 18.0 7.05

-9.6 -10.0 33.8 7.71 30.6 7.68 28.5 7.62 26.4 7.50 24.3 7.37 21.1 6.94 18.0 6.37

-4.4 -5.0 33.8 6.87 30.6 6.87 28.5 6.73 26.4 6.58 24.3 6.37 21.1 6.01 18.0 5.58

-1.8 -2.5 33.8 6.35 30.6 6.26 28.5 6.17 26.4 6.03 24.3 5.88 21.1 5.58 18.0 5.22

0.8 0.0 33.8 5.70 30.6 5.67 28.5 5.60 26.4 5.51 24.3 5.40 21.1 5.15 18.0 4.86

30% 2.8 2.0 33.8 5.54 30.6 5.20 28.5 5.18 26.4 5.11 24.3 5.02 21.1 4.84 18.0 4.57

6.0 5.0 33.8 5.54 30.6 5.18 28.5 4.95 26.4 4.72 24.3 4.50 21.1 4.36 18.0 4.18

7.0 6.0 33.8 5.54 30.6 5.18 28.5 4.95 26.4 4.72 24.3 4.47 21.1 4.23 18.0 4.05

8.6 7.5 33.8 5.54 30.6 5.18 28.5 4.95 26.4 4.72 24.3 4.47 21.1 4.14 18.0 3.86

11.2 10.0 33.8 5.54 30.6 5.18 28.5 4.95 26.4 4.72 24.3 4.47 21.1 4.14 18.0 3.77

16.4 15.0 33.8 5.54 30.6 5.18 28.5 4.95 26.4 4.72 24.3 4.47 21.1 4.14 18.0 3.77

24.0 18.0 33.8 5.54 30.6 5.18 28.5 4.95 26.4 4.72 24.3 4.47 21.1 4.14 18.0 3.77

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


32 HP (U-16MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 74.4 27.43 68.7 25.22 64.8 23.73 64.8 23.73 64.8 23.73 64.8 23.73 56.7 20.51

-14.7 -15.0 78.9 27.83 73.0 25.64 68.9 24.18 68.9 24.18 68.9 24.18 68.9 24.18 60.8 21.01

-9.6 -10.0 84.7 28.47 78.5 26.34 74.3 24.85 74.3 24.85 74.3 24.85 74.3 24.85 66.1 21.70

-4.4 -5.0 92.5 29.51 86.0 27.35 81.5 25.84 81.5 25.84 81.5 25.84 81.5 25.84 73.3 22.67

-1.8 -2.5 97.4 30.18 90.8 28.00 86.1 26.49 86.1 26.49 86.1 26.49 86.1 26.49 77.9 23.31

0.8 0.0 103.4 31.00 96.5 28.79 91.7 27.28 91.7 27.28 91.7 27.28 91.7 27.28 83.5 24.16

130% 2.8 2.0 109.0 31.74 101.9 29.54 96.9 28.02 96.9 28.02 96.9 28.02 96.9 28.02 88.0 24.45

6.0 5.0 117.9 32.24 112.2 30.80 107.3 29.36 107.3 29.36 107.3 29.36 103.5 26.56 88.0 22.27

7.0 6.0 121.4 32.24 115.5 30.90 107.5 28.32 107.5 28.32 107.5 28.32 103.5 25.57 88.0 21.43

8.6 7.5 126.4 32.24 115.5 28.97 107.5 26.59 107.5 26.59 107.5 26.59 103.5 24.06 88.0 20.19

11.2 10.0 127.4 29.24 115.5 25.92 107.5 23.81 107.5 23.81 107.5 23.81 103.5 21.63 88.0 18.23

16.4 15.0 127.4 22.87 115.5 20.39 107.5 18.80 107.5 18.80 107.5 18.80 103.5 17.29 88.0 14.71

24.0 18.0 127.4 19.54 115.5 17.51 107.5 16.22 107.5 16.22 107.5 16.22 103.5 15.08 88.0 12.90

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 74.6 27.11 68.8 24.97 64.9 23.51 64.9 23.51 64.9 23.51 60.3 21.63 52.3 19.00

-14.7 -15.0 79.1 27.58 73.1 25.42 69.0 23.98 69.0 23.98 69.0 23.98 64.5 22.12 56.1 19.42

-9.6 -10.0 84.9 28.25 78.7 26.11 74.4 24.65 74.4 24.65 74.4 24.65 69.9 22.82 60.9 20.06

-4.4 -5.0 92.6 29.26 86.1 27.13 81.6 25.64 81.6 25.64 81.6 25.64 77.2 23.83 67.5 20.93

-1.8 -2.5 97.6 29.93 90.9 27.80 86.2 26.29 86.2 26.29 86.2 26.29 81.9 24.50 71.7 21.50

0.8 0.0 103.5 30.75 96.5 28.57 91.6 27.06 91.6 27.06 91.6 27.06 87.5 25.32 76.8 22.25

120% 2.8 2.0 109.1 31.50 101.8 29.31 96.8 27.78 96.8 27.78 96.8 27.78 93.2 26.06 79.3 21.97

6.0 5.0 118.6 32.24 112.2 30.50 105.0 28.22 105.0 28.22 105.0 28.22 93.3 23.78 79.3 20.01

7.0 6.0 122.1 32.24 112.8 29.54 105.0 27.13 105.0 27.13 105.0 27.13 93.3 22.89 79.3 19.27

8.6 7.5 124.4 31.22 112.8 27.70 105.0 25.47 105.0 25.47 105.0 25.47 93.3 21.53 79.3 18.15

11.2 10.0 124.4 27.85 112.8 24.75 105.0 22.79 105.0 22.79 105.0 22.79 93.3 19.37 79.3 16.39

16.4 15.0 124.4 21.72 112.8 19.42 105.0 17.98 105.0 17.98 105.0 17.98 93.3 15.50 79.3 13.24

24.0 18.0 124.4 18.55 112.8 16.67 105.0 15.48 105.0 15.48 105.0 15.48 93.3 13.52 79.3 11.63

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 74.8 26.83 68.9 24.73 65.0 23.31 65.0 23.31 62.4 22.25 55.3 19.84 47.9 17.48

-14.7 -15.0 79.3 27.30 73.2 25.20 69.1 23.76 69.1 23.76 66.6 22.74 59.1 20.29 51.3 17.88

-9.6 -10.0 85.0 28.00 78.8 25.89 74.5 24.45 74.5 24.45 71.9 23.44 64.1 20.93 55.8 18.45

-4.4 -5.0 92.8 29.04 86.2 26.91 81.6 25.44 81.6 25.44 79.2 24.45 70.7 21.85 61.7 19.22

-1.8 -2.5 97.8 29.71 90.9 27.58 86.2 26.09 86.2 26.09 83.7 25.10 74.9 22.44 65.5 19.74

0.8 0.0 103.6 30.53 96.5 28.35 91.6 26.83 91.6 26.83 89.2 25.87 80.0 23.16 70.2 20.39

110% 2.8 2.0 109.1 31.25 101.8 29.04 96.7 27.50 96.7 27.50 94.6 26.56 83.5 23.24 71.0 19.64

6.0 5.0 119.3 32.24 110.1 29.39 102.5 27.03 102.5 27.03 96.0 24.60 83.5 21.15 71.0 17.88

7.0 6.0 121.5 31.79 110.1 28.22 102.5 25.97 102.5 25.97 96.0 23.68 83.5 20.36 71.0 17.21

8.6 7.5 121.5 29.76 110.1 26.46 102.5 24.35 102.5 24.35 96.0 22.25 83.5 19.15 71.0 16.22

11.2 10.0 121.5 26.49 110.1 23.61 102.5 21.77 102.5 21.77 96.0 19.94 83.5 17.24 71.0 14.66

16.4 15.0 121.5 20.61 110.1 18.50 102.5 17.16 102.5 17.16 96.0 15.85 83.5 13.81 71.0 11.85

24.0 18.0 121.5 17.56 110.1 15.85 102.5 14.76 102.5 14.76 96.0 13.74 83.5 12.05 71.0 10.44

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 74.9 26.56 69.0 24.50 65.0 23.09 60.9 21.68 56.7 20.24 50.2 18.10 43.5 16.02

-14.7 -15.0 79.4 27.03 73.4 24.97 69.2 23.58 64.9 22.15 60.5 20.68 53.7 18.50 46.6 16.37

-9.6 -10.0 85.2 27.75 78.9 25.69 74.5 24.25 70.0 22.82 65.4 21.33 58.2 19.10 50.6 16.86

-4.4 -5.0 93.0 28.79 86.3 26.71 81.7 25.25 76.9 23.76 71.9 22.22 64.2 19.89 56.0 17.53

-1.8 -2.5 97.9 29.49 91.0 27.35 86.2 25.89 81.2 24.35 76.0 22.79 67.9 20.41 59.3 18.00

0.8 0.0 103.7 30.28 96.6 28.12 91.5 26.64 86.3 25.07 80.9 23.49 72.5 21.03 63.0 18.33

100% 2.8 2.0 109.2 30.98 101.8 28.77 96.7 27.23 91.3 25.67 85.2 23.83 74.1 20.53 63.0 17.43

6.0 5.0 118.5 31.55 107.4 28.07 100.0 25.87 92.6 23.71 85.2 21.65 74.1 18.67 63.0 15.87

7.0 6.0 118.5 30.26 107.4 26.96 100.0 24.80 92.6 22.82 85.2 20.83 74.1 17.98 63.0 15.28

8.6 7.5 118.5 28.32 107.4 25.25 100.0 23.29 92.6 21.40 85.2 19.57 74.1 16.94 63.0 14.41

11.2 10.0 118.5 25.17 107.4 22.52 100.0 20.81 92.6 19.15 85.2 17.56 74.1 15.25 63.0 13.02

16.4 15.0 118.5 19.54 107.4 17.61 100.0 16.37 92.6 15.15 85.2 13.96 74.1 12.25 63.0 10.59

9 24.0 18.0 118.5 16.62 107.4 15.08 100.0 14.06 92.6 13.07 85.2 12.13 74.1 10.71 63.0 9.32
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


32 HP (U-16MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 75.5 25.54 69.5 23.63 65.4 22.34 61.2 21.03 56.9 19.72 50.3 17.73 43.5 15.82

-14.7 -15.0 80.1 26.09 73.9 24.18 69.5 22.84 65.1 21.53 60.6 20.16 53.7 18.13 46.5 16.14

-9.6 -10.0 85.9 26.86 79.3 24.90 74.8 23.56 70.2 22.17 65.4 20.78 58.0 18.67 50.3 16.57

-4.4 -5.0 93.6 27.92 86.6 25.92 81.8 24.50 76.8 23.09 71.7 21.63 63.7 19.39 55.4 17.16

-1.8 -2.5 98.5 28.62 91.2 26.54 86.2 25.12 81.0 23.66 75.6 22.15 66.7 19.62 56.7 16.89

0.8 0.0 104.1 29.26 96.6 27.13 90.0 25.15 83.3 23.19 76.7 21.30 66.7 18.58 56.7 16.00

90% 2.8 2.0 106.7 28.62 96.7 25.69 90.0 23.81 83.3 21.97 76.7 20.19 66.7 17.61 56.7 15.18

6.0 5.0 106.7 25.74 96.7 23.16 90.0 21.50 83.3 19.89 76.7 18.30 66.7 16.00 56.7 13.74

7.0 6.0 106.7 24.65 96.7 22.22 90.0 20.63 83.3 19.10 76.7 17.58 66.7 15.38 56.7 13.22

8.6 7.5 106.7 22.99 96.7 20.76 90.0 19.29 83.3 17.88 76.7 16.49 66.7 14.46 56.7 12.47

11.2 10.0 106.7 20.34 96.7 18.43 90.0 17.19 83.3 15.97 76.7 14.78 66.7 13.00 56.7 11.26

16.4 15.0 106.7 15.62 96.7 14.28 90.0 13.42 83.3 12.55 76.7 11.71 66.7 10.42 56.7 9.15

24.0 18.0 106.7 14.06 96.7 12.92 90.0 12.15 83.3 11.41 76.7 10.64 66.7 9.50 56.7 8.36

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 76.4 24.73 70.1 22.96 65.9 21.77 61.6 20.56 57.2 19.34 50.4 17.53 43.5 15.77

-14.7 -15.0 81.0 25.35 74.5 23.54 70.1 22.30 65.5 21.06 60.9 19.79 53.8 17.91 46.5 16.05

-9.6 -10.0 86.8 26.16 80.0 24.28 75.3 23.01 70.5 21.70 65.6 20.39 58.0 18.40 50.2 16.42

-4.4 -5.0 94.5 27.23 85.9 24.82 80.0 23.14 74.1 21.50 68.1 19.91 59.3 17.61 50.4 15.40

-1.8 -2.5 94.8 26.02 85.9 23.58 80.0 22.00 74.1 20.46 68.1 18.95 59.3 16.76 50.4 14.66

0.8 0.0 94.8 24.43 85.9 22.20 80.0 20.71 74.1 19.27 68.1 17.88 59.3 15.82 50.4 13.84

80% 2.8 2.0 94.8 23.04 85.9 20.96 80.0 19.59 74.1 18.25 68.1 16.91 59.3 15.00 50.4 13.12

6.0 5.0 94.8 20.63 85.9 18.82 80.0 17.63 74.1 16.44 68.1 15.28 59.3 13.54 50.4 11.78

7.0 6.0 94.8 19.72 85.9 18.00 80.0 16.89 74.1 15.77 68.1 14.66 59.3 13.00 50.4 11.33

8.6 7.5 94.8 18.33 85.9 16.79 80.0 15.77 74.1 14.76 68.1 13.74 59.3 12.23 50.4 10.69

11.2 10.0 94.8 16.14 85.9 14.86 80.0 14.01 74.1 13.14 68.1 12.28 59.3 10.99 50.4 9.67

16.4 15.0 94.8 12.72 85.9 11.71 80.0 11.01 74.1 10.34 68.1 9.70 59.3 8.78 50.4 7.86

24.0 18.0 94.8 12.72 85.9 11.71 80.0 11.01 74.1 10.34 68.1 9.67 59.3 8.66 50.4 7.64

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 77.7 24.28 71.3 22.64 66.9 21.53 62.4 20.41 57.9 19.29 51.0 17.63 43.9 16.00

-14.7 -15.0 82.5 24.95 75.2 23.04 70.0 21.68 64.8 20.34 59.6 19.00 51.9 17.06 44.1 15.20

-9.6 -10.0 83.0 23.78 75.2 21.82 70.0 20.53 64.8 19.27 59.6 18.00 51.9 16.14 44.1 14.33

-4.4 -5.0 83.0 21.80 75.2 20.04 70.0 18.87 64.8 17.73 59.6 16.62 51.9 14.95 44.1 13.32

-1.8 -2.5 83.0 20.66 75.2 19.00 70.0 17.91 64.8 16.84 59.6 15.77 51.9 14.19 44.1 12.62

0.8 0.0 83.0 19.34 75.2 17.83 70.0 16.84 64.8 15.82 59.6 14.86 51.9 13.37 44.1 11.88

70% 2.8 2.0 83.0 18.18 75.2 16.79 70.0 15.87 64.8 14.95 59.6 14.01 51.9 12.62 44.1 11.16

6.0 5.0 83.0 16.19 75.2 15.03 70.0 14.21 64.8 13.42 59.6 12.57 51.9 11.31 44.1 9.99

7.0 6.0 83.0 15.45 75.2 14.36 70.0 13.62 64.8 12.85 59.6 12.05 51.9 10.86 44.1 9.62

8.6 7.5 83.0 14.33 75.2 13.37 70.0 12.67 64.8 12.00 59.6 11.28 51.9 10.19 44.1 9.08

11.2 10.0 83.0 12.55 75.2 11.76 70.0 11.23 64.8 10.66 59.6 10.07 51.9 9.18 44.1 8.21

16.4 15.0 83.0 11.36 75.2 10.47 70.0 9.87 64.8 9.28 59.6 8.68 51.9 7.79 44.1 6.89

24.0 18.0 83.0 11.36 75.2 10.47 70.0 9.87 64.8 9.28 59.6 8.68 51.9 7.79 44.1 6.89

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 71.1 21.10 64.4 19.59 60.0 18.60 55.6 17.63 51.1 16.67 44.4 15.25 37.8 13.86

-14.7 -15.0 71.1 20.01 64.4 18.67 60.0 17.78 55.6 16.86 51.1 15.92 44.4 14.51 37.8 13.12

-9.6 -10.0 71.1 18.67 64.4 17.43 60.0 16.62 55.6 15.80 51.1 14.98 44.4 13.71 37.8 12.35

-4.4 -5.0 71.1 17.04 64.4 15.95 60.0 15.20 55.6 14.46 51.1 13.71 44.4 12.57 37.8 11.41

-1.8 -2.5 71.1 16.07 64.4 15.05 60.0 14.38 55.6 13.69 51.1 13.00 44.4 11.93 37.8 10.79

0.8 0.0 71.1 15.00 64.4 14.09 60.0 13.47 55.6 12.85 51.1 12.18 44.4 11.18 37.8 10.02

60% 2.8 2.0 71.1 14.06 64.4 13.24 60.0 12.67 55.6 12.08 51.1 11.46 44.4 10.47 37.8 9.35

6.0 5.0 71.1 12.45 64.4 11.76 60.0 11.26 55.6 10.74 51.1 10.19 44.4 9.30 37.8 8.38

7.0 6.0 71.1 11.85 64.4 11.21 60.0 10.76 55.6 10.27 51.1 9.77 44.4 8.95 37.8 8.06

8.6 7.5 71.1 10.96 64.4 10.42 60.0 10.02 55.6 9.60 51.1 9.15 44.4 8.41 37.8 7.61

11.2 10.0 71.1 9.99 64.4 9.23 60.0 8.83 55.6 8.51 51.1 8.16 44.4 7.56 37.8 6.89

16.4 15.0 71.1 9.99 64.4 9.23 60.0 8.73 55.6 8.21 51.1 7.71 44.4 6.94 37.8 6.18

24.0 18.0 71.1 9.99 64.4 9.23 60.0 8.73 55.6 8.21 51.1 7.71 44.4 6.94 37.8 6.18

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


32 HP (U-16MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 59.3 16.49 53.7 15.70 50.0 15.13 46.3 14.51 42.6 13.84 37.0 12.85 31.5 11.83

-14.7 -15.0 59.3 15.52 53.7 14.81 50.0 14.28 46.3 13.76 42.6 13.22 37.0 12.23 31.5 11.18

-9.6 -10.0 59.3 14.41 53.7 13.76 50.0 13.32 46.3 12.82 42.6 12.33 37.0 11.51 31.5 10.52

-4.4 -5.0 59.3 13.07 53.7 12.50 50.0 12.10 46.3 11.68 42.6 11.23 37.0 10.49 31.5 9.67

-1.8 -2.5 59.3 12.28 53.7 11.78 50.0 11.41 46.3 11.01 42.6 10.59 37.0 9.90 31.5 8.95

0.8 0.0 59.3 11.41 53.7 10.96 50.0 10.64 46.3 10.27 42.6 9.90 37.0 9.13 31.5 8.23
50% 2.8 2.0 59.3 10.66 53.7 10.27 50.0 9.94 46.3 9.60 42.6 9.18 37.0 8.46 31.5 7.69

6.0 5.0 59.3 9.35 53.7 9.00 50.0 8.73 46.3 8.43 42.6 8.11 37.0 7.54 31.5 6.92

7.0 6.0 59.3 8.85 53.7 8.58 50.0 8.33 46.3 8.06 42.6 7.76 37.0 7.27 31.5 6.67

8.6 7.5 59.3 8.66 53.7 8.01 50.0 7.76 46.3 7.54 42.6 7.27 37.0 6.82 31.5 6.30

11.2 10.0 59.3 8.66 53.7 8.01 50.0 7.59 46.3 7.17 42.6 6.75 37.0 6.15 31.5 5.73

16.4 15.0 59.3 8.66 53.7 8.01 50.0 7.59 46.3 7.17 42.6 6.75 37.0 6.10 31.5 5.46

24.0 18.0 59.3 8.66 53.7 8.01 50.0 7.59 46.3 7.17 42.6 6.75 37.0 6.10 31.5 5.46

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 47.4 12.70 43.0 12.35 40.0 12.08 37.0 11.76 34.1 11.33 29.6 10.64 25.2 9.92

-14.7 -15.0 47.4 11.93 43.0 11.63 40.0 11.38 37.0 11.09 34.1 10.76 29.6 10.12 25.2 9.35

-9.6 -10.0 47.4 11.01 43.0 10.76 40.0 10.54 37.0 10.29 34.1 9.99 29.6 9.47 25.2 8.80

-4.4 -5.0 47.4 9.90 43.0 9.70 40.0 9.52 37.0 9.32 34.1 9.08 29.6 8.51 25.2 7.74

-1.8 -2.5 47.4 9.25 43.0 9.08 40.0 8.93 37.0 8.73 34.1 8.43 29.6 7.84 25.2 7.17

0.8 0.0 47.4 8.56 43.0 8.41 40.0 8.23 37.0 7.99 34.1 7.69 29.6 7.19 25.2 6.62

40% 2.8 2.0 47.4 7.91 43.0 7.74 40.0 7.56 37.0 7.37 34.1 7.12 29.6 6.70 25.2 6.20

6.0 5.0 47.4 7.29 43.0 6.77 40.0 6.62 37.0 6.47 34.1 6.32 29.6 6.00 25.2 5.60

7.0 6.0 47.4 7.29 43.0 6.77 40.0 6.45 37.0 6.20 34.1 6.05 29.6 5.78 25.2 5.41

8.6 7.5 47.4 7.29 43.0 6.77 40.0 6.45 37.0 6.10 34.1 5.75 29.6 5.46 25.2 5.13

11.2 10.0 47.4 7.29 43.0 6.77 40.0 6.45 37.0 6.10 34.1 5.75 29.6 5.26 25.2 4.74

16.4 15.0 47.4 7.29 43.0 6.77 40.0 6.45 37.0 6.10 34.1 5.75 29.6 5.26 25.2 4.74

24.0 18.0 47.4 7.29 43.0 6.77 40.0 6.45 37.0 6.10 34.1 5.75 29.6 5.26 25.2 4.74

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 35.6 9.70 32.2 9.60 30.0 9.47 27.8 9.30 25.6 9.00 22.2 8.56 18.9 8.06

-14.7 -15.0 35.6 9.08 32.2 9.00 30.0 8.90 27.8 8.75 25.6 8.56 22.2 8.11 18.9 7.59

-9.6 -10.0 35.6 8.33 32.2 8.28 30.0 8.21 27.8 8.11 25.6 7.94 22.2 7.46 18.9 6.84

-4.4 -5.0 35.6 7.42 32.2 7.42 30.0 7.27 27.8 7.09 25.6 6.87 22.2 6.47 18.9 6.00

-1.8 -2.5 35.6 6.87 32.2 6.75 30.0 6.65 27.8 6.50 25.6 6.32 22.2 6.00 18.9 5.58

0.8 0.0 35.6 6.15 32.2 6.10 30.0 6.03 27.8 5.93 25.6 5.80 22.2 5.53 18.9 5.18

30% 2.8 2.0 35.6 5.93 32.2 5.60 30.0 5.56 27.8 5.48 25.6 5.38 22.2 5.18 18.9 4.89

6.0 5.0 35.6 5.93 32.2 5.56 30.0 5.31 27.8 5.03 25.6 4.81 22.2 4.66 18.9 4.46

7.0 6.0 35.6 5.93 32.2 5.56 30.0 5.31 27.8 5.03 25.6 4.79 22.2 4.51 18.9 4.32

8.6 7.5 35.6 5.93 32.2 5.56 30.0 5.31 27.8 5.03 25.6 4.79 22.2 4.41 18.9 4.12

11.2 10.0 35.6 5.93 32.2 5.56 30.0 5.31 27.8 5.03 25.6 4.79 22.2 4.41 18.9 4.02

16.4 15.0 35.6 5.93 32.2 5.56 30.0 5.31 27.8 5.03 25.6 4.79 22.2 4.41 18.9 4.02

24.0 18.0 35.6 5.93 32.2 5.56 30.0 5.31 27.8 5.03 25.6 4.79 22.2 4.41 18.9 4.02

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


34 HP (U-8MF2E8 & U-12MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 85.6 29.01 78.9 26.73 74.3 25.15 74.3 25.15 74.3 25.15 74.3 25.15 64.8 21.97

-14.7 -15.0 90.8 29.52 83.9 27.26 79.2 25.69 79.2 25.69 79.2 25.69 79.2 25.69 69.4 22.48

-9.6 -10.0 97.4 30.30 90.2 28.02 85.2 26.44 85.2 26.44 85.2 26.44 85.2 26.44 75.4 23.18

-4.4 -5.0 106.3 31.47 98.7 29.14 93.4 27.53 93.4 27.53 93.4 27.53 93.4 27.53 83.4 24.18

-1.8 -2.5 110.6 31.59 104.1 29.86 98.6 28.24 98.6 28.24 98.6 28.24 98.6 28.24 88.3 24.83

0.8 0.0 115.2 31.59 110.5 30.72 104.8 29.04 104.8 29.04 104.8 29.04 104.8 29.04 94.7 25.64

130% 2.8 2.0 120.0 31.59 116.5 31.47 110.6 29.77 110.6 29.77 110.6 29.77 110.6 29.77 95.0 24.45

6.0 5.0 129.5 31.59 124.7 31.40 116.1 28.84 116.1 28.84 116.1 28.84 111.8 26.34 95.0 22.19

7.0 6.0 132.5 31.59 124.7 30.16 116.1 27.73 116.1 27.73 116.1 27.73 111.8 25.34 95.0 21.34

8.6 7.5 137.3 31.59 124.7 28.24 116.1 26.00 116.1 26.00 116.1 26.00 111.8 23.81 95.0 20.07

11.2 10.0 137.6 28.26 124.7 25.17 116.1 23.21 116.1 23.21 116.1 23.21 111.8 21.36 95.0 18.08

16.4 15.0 137.6 21.92 124.7 19.66 116.1 18.23 116.1 18.23 116.1 18.23 111.8 17.01 95.0 14.53

24.0 18.0 137.6 18.64 124.7 16.82 116.1 15.65 116.1 15.65 116.1 15.65 111.8 14.75 95.0 12.71

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 85.8 28.72 79.1 26.49 74.4 24.96 74.4 24.96 74.4 24.96 69.0 23.06 59.7 20.34

-14.7 -15.0 90.9 29.26 84.0 27.02 79.2 25.49 79.2 25.49 79.2 25.49 73.8 23.62 64.0 20.80

-9.6 -10.0 97.6 30.06 90.4 27.80 85.3 26.24 85.3 26.24 85.3 26.24 79.9 24.37 69.4 21.43

-4.4 -5.0 106.5 31.23 98.8 28.92 93.4 27.34 93.4 27.34 93.4 27.34 88.0 25.42 76.7 22.31

-1.8 -2.5 111.2 31.59 104.1 29.65 98.6 28.02 98.6 28.02 98.6 28.02 93.1 26.10 81.3 22.91

0.8 0.0 115.8 31.59 110.5 30.47 104.7 28.82 104.7 28.82 104.7 28.82 99.4 26.88 85.6 23.16

120% 2.8 2.0 120.7 31.59 116.4 31.18 110.5 29.50 110.5 29.50 110.5 29.50 100.8 25.98 85.6 21.97

6.0 5.0 129.7 31.59 121.8 30.03 113.4 27.65 113.4 27.65 113.4 27.65 100.8 23.57 85.6 19.93

7.0 6.0 132.6 31.59 121.8 28.84 113.4 26.58 113.4 26.58 113.4 26.58 100.8 22.67 85.6 19.17

8.6 7.5 134.4 30.28 121.8 27.00 113.4 24.91 113.4 24.91 113.4 24.91 100.8 21.31 85.6 18.03

11.2 10.0 134.4 26.90 121.8 24.03 113.4 22.21 113.4 22.21 113.4 22.21 100.8 19.12 85.6 16.26

16.4 15.0 134.4 20.83 121.8 18.74 113.4 17.40 113.4 17.40 113.4 17.40 100.8 15.24 85.6 13.07

24.0 18.0 134.4 17.69 121.8 16.01 113.4 14.92 113.4 14.92 113.4 14.92 100.8 13.24 85.6 11.45

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 86.0 28.46 79.2 26.24 74.5 24.74 74.5 24.74 71.5 23.69 63.3 21.19 54.8 18.74

-14.7 -15.0 91.2 29.01 84.1 26.80 79.3 25.30 79.3 25.30 76.2 24.23 67.6 21.68 58.6 19.15

-9.6 -10.0 97.7 29.84 90.5 27.60 85.4 26.05 85.4 26.05 82.3 25.00 73.1 22.36 63.6 19.71

-4.4 -5.0 106.7 31.01 98.9 28.70 93.5 27.12 93.5 27.12 90.4 26.07 80.6 23.28 70.2 20.48

-1.8 -2.5 111.8 31.59 104.2 29.43 98.6 27.80 98.6 27.80 95.5 26.73 85.2 23.89 74.3 21.02

0.8 0.0 116.4 31.59 110.5 30.25 104.7 28.60 104.7 28.60 101.6 27.51 90.2 24.35 76.7 20.68

110% 2.8 2.0 121.4 31.59 116.4 30.89 110.5 29.23 110.5 29.23 103.7 26.80 90.2 23.11 76.7 19.63

6.0 5.0 129.8 31.59 118.9 28.72 110.7 26.49 110.7 26.49 103.7 24.30 90.2 20.97 76.7 17.79

7.0 6.0 131.2 30.89 118.9 27.58 110.7 25.44 110.7 25.44 103.7 23.35 90.2 20.17 76.7 17.11

8.6 7.5 131.2 28.84 118.9 25.78 110.7 23.84 110.7 23.84 103.7 21.89 90.2 18.95 76.7 16.11

11.2 10.0 131.2 25.59 118.9 22.94 110.7 21.24 110.7 21.24 103.7 19.59 90.2 17.01 76.7 14.53

16.4 15.0 131.2 19.76 118.9 17.86 110.7 16.62 110.7 16.62 103.7 15.48 90.2 13.56 76.7 11.71

24.0 18.0 131.2 16.74 118.9 15.24 110.7 14.24 110.7 14.24 103.7 13.37 90.2 11.81 76.7 10.28

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 86.1 28.19 79.3 26.03 74.6 24.54 69.9 23.06 65.0 21.55 57.5 19.32 49.8 17.13

-14.7 -15.0 91.4 28.77 84.2 26.58 79.4 25.10 74.4 23.60 69.3 22.06 61.5 19.76 53.2 17.50

-9.6 -10.0 98.0 29.60 90.6 27.39 85.4 25.88 80.2 24.32 74.8 22.74 66.4 20.36 57.8 18.01

-4.4 -5.0 106.8 30.76 98.9 28.50 93.5 26.95 87.9 25.34 82.1 23.69 73.1 21.19 63.6 18.69

-1.8 -2.5 112.4 31.52 104.2 29.21 98.6 27.60 92.8 25.98 86.7 24.30 77.3 21.75 67.4 19.15

0.8 0.0 117.2 31.59 110.5 30.01 104.5 28.36 98.5 26.66 92.0 24.86 80.0 21.51 68.0 18.35

100% 2.8 2.0 122.1 31.59 116.0 30.42 108.0 28.07 100.0 25.78 92.0 23.57 80.0 20.41 68.0 17.42

6.0 5.0 128.0 30.69 116.0 27.43 108.0 25.37 100.0 23.33 92.0 21.38 80.0 18.52 68.0 15.80

7.0 6.0 128.0 29.43 116.0 26.34 108.0 24.30 100.0 22.43 92.0 20.53 80.0 17.81 68.0 15.19

8.6 7.5 128.0 27.46 116.0 24.62 108.0 22.79 100.0 21.00 92.0 19.27 80.0 16.74 68.0 14.31

11.2 10.0 128.0 24.32 116.0 21.87 108.0 20.29 100.0 18.76 92.0 17.23 80.0 15.04 68.0 12.90

16.4 15.0 128.0 18.74 116.0 16.99 108.0 15.84 100.0 14.73 92.0 13.63 80.0 12.03 68.0 10.42

9 24.0 18.0 128.0 15.84 116.0 14.46 108.0 13.58 100.0 12.71 92.0 11.83 80.0 10.52 68.0 9.21
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


34 HP (U-8MF2E8 & U-12MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 86.8 27.24 79.8 25.22 75.1 23.86 70.2 22.48 65.2 21.09 57.6 19.03 49.7 17.01

-14.7 -15.0 92.1 27.90 84.9 25.86 79.8 24.45 74.7 23.04 69.6 21.60 61.5 19.44 53.1 17.35

-9.6 -10.0 98.8 28.77 91.2 26.66 85.9 25.22 80.5 23.74 75.0 22.26 66.3 20.02 57.5 17.76

-4.4 -5.0 107.6 29.94 99.4 27.75 93.7 26.24 87.9 24.71 82.0 23.13 72.0 20.53 61.2 17.76

-1.8 -2.5 113.1 30.64 104.4 28.36 97.2 26.32 90.0 24.32 82.8 22.40 72.0 19.63 61.2 16.99

0.8 0.0 115.2 29.62 104.4 26.71 97.2 24.79 90.0 22.94 82.8 21.14 72.0 18.52 61.2 16.04

90% 2.8 2.0 115.2 27.95 104.4 25.20 97.2 23.43 90.0 21.70 82.8 20.02 72.0 17.54 61.2 15.19

6.0 5.0 115.2 25.05 104.4 22.67 97.2 21.12 90.0 19.59 82.8 18.08 72.0 15.87 61.2 13.68

7.0 6.0 115.2 23.98 104.4 21.72 97.2 20.24 90.0 18.78 82.8 17.35 72.0 15.24 61.2 13.15

8.6 7.5 115.2 22.31 104.4 20.24 97.2 18.91 90.0 17.57 82.8 16.26 72.0 14.31 61.2 12.39

11.2 10.0 115.2 19.66 104.4 17.93 97.2 16.79 90.0 15.65 82.8 14.51 72.0 12.83 61.2 11.18

16.4 15.0 115.2 14.97 104.4 13.78 97.2 13.00 90.0 12.22 82.8 11.42 72.0 10.23 61.2 9.02

24.0 18.0 115.2 14.36 104.4 13.19 97.2 12.39 90.0 11.62 82.8 10.81 72.0 9.65 61.2 8.46

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 88.0 26.58 80.8 24.69 75.8 23.43 70.8 22.14 65.8 20.87 57.9 18.95 49.9 17.11

-14.7 -15.0 93.4 27.29 85.8 25.34 80.7 24.03 75.4 22.70 70.0 21.36 61.8 19.37 53.2 17.37

-9.6 -10.0 100.1 28.19 92.1 26.17 86.4 24.71 80.0 23.04 73.5 21.41 64.0 19.00 54.4 16.69

-4.4 -5.0 102.4 26.92 92.8 24.52 86.4 22.94 80.0 21.41 73.5 19.88 64.0 17.69 54.4 15.55

-1.8 -2.5 102.4 25.52 92.8 23.26 86.4 21.77 80.0 20.31 73.5 18.88 64.0 16.79 54.4 14.77

0.8 0.0 102.4 23.94 92.8 21.85 86.4 20.46 80.0 19.12 73.5 17.79 64.0 15.82 54.4 13.90

80% 2.8 2.0 102.4 22.53 92.8 20.58 86.4 19.32 80.0 18.05 73.5 16.82 64.0 14.97 54.4 13.15

6.0 5.0 102.4 20.10 92.8 18.44 86.4 17.33 80.0 16.23 73.5 15.11 64.0 13.44 54.4 11.74

7.0 6.0 102.4 19.20 92.8 17.62 86.4 16.57 80.0 15.53 73.5 14.48 64.0 12.88 54.4 11.28

8.6 7.5 102.4 17.81 92.8 16.40 86.4 15.45 80.0 14.51 73.5 13.56 64.0 12.10 54.4 10.62

11.2 10.0 102.4 15.62 92.8 14.46 86.4 13.68 80.0 12.88 73.5 12.08 64.0 10.84 54.4 9.60

16.4 15.0 102.4 12.98 92.8 11.91 86.4 11.23 80.0 10.52 73.5 9.82 64.0 8.77 54.4 7.75

24.0 18.0 102.4 12.98 92.8 11.91 86.4 11.23 80.0 10.52 73.5 9.82 64.0 8.77 54.4 7.70

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 89.6 26.22 81.2 24.13 75.6 22.77 70.0 21.43 64.4 20.12 56.1 18.23 47.6 16.38

-14.7 -15.0 89.6 25.05 81.2 23.04 75.6 21.72 70.0 20.44 64.4 19.17 56.1 17.30 47.6 15.48

-9.6 -10.0 89.6 23.50 81.2 21.70 75.6 20.48 70.0 19.32 64.4 18.13 56.1 16.35 47.6 14.56

-4.4 -5.0 89.6 21.48 81.2 19.85 75.6 18.78 70.0 17.71 64.4 16.65 56.1 15.07 47.6 13.46

-1.8 -2.5 89.6 20.31 81.2 18.78 75.6 17.79 70.0 16.77 64.4 15.77 56.1 14.26 47.6 12.76

0.8 0.0 89.6 18.98 81.2 17.59 75.6 16.67 70.0 15.75 64.4 14.82 56.1 13.41 47.6 11.98

70% 2.8 2.0 89.6 17.81 81.2 16.55 75.6 15.70 70.0 14.82 64.4 13.95 56.1 12.64 47.6 11.15

6.0 5.0 89.6 15.82 81.2 14.73 75.6 14.00 70.0 13.24 64.4 12.44 56.1 11.23 47.6 9.96

7.0 6.0 89.6 15.07 81.2 14.07 75.6 13.37 70.0 12.66 64.4 11.93 56.1 10.76 47.6 9.57

8.6 7.5 89.6 13.92 81.2 13.05 75.6 12.44 70.0 11.81 64.4 11.15 56.1 10.11 47.6 9.02

11.2 10.0 89.6 12.15 81.2 11.45 75.6 10.96 70.0 10.45 64.4 9.91 56.1 9.06 47.6 8.14

16.4 15.0 89.6 11.57 81.2 10.64 75.6 10.04 70.0 9.43 64.4 8.80 56.1 7.90 47.6 6.97

24.0 18.0 89.6 11.57 81.2 10.64 75.6 10.04 70.0 9.43 64.4 8.80 56.1 7.90 47.6 6.97

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 76.8 21.09 69.6 19.73 64.8 18.78 60.0 17.84 55.2 16.91 48.0 15.53 40.8 14.14

-14.7 -15.0 76.8 19.90 69.6 18.69 64.8 17.86 60.0 17.03 55.2 16.14 48.0 14.75 40.8 13.37

-9.6 -10.0 76.8 18.54 69.6 17.40 64.8 16.65 60.0 15.89 55.2 15.11 48.0 13.92 40.8 12.56

-4.4 -5.0 76.8 16.84 69.6 15.87 64.8 15.19 60.0 14.51 55.2 13.80 48.0 12.71 40.8 11.57

-1.8 -2.5 76.8 15.87 69.6 14.97 64.8 14.34 60.0 13.71 55.2 13.05 48.0 12.00 40.8 10.91

0.8 0.0 76.8 14.77 69.6 13.95 64.8 13.39 60.0 12.81 55.2 12.20 48.0 11.23 40.8 10.01

60% 2.8 2.0 76.8 13.80 69.6 13.07 64.8 12.56 60.0 12.00 55.2 11.45 48.0 10.42 40.8 9.33

6.0 5.0 76.8 12.17 69.6 11.57 64.8 11.11 60.0 10.62 55.2 10.08 48.0 9.26 40.8 8.33

7.0 6.0 76.8 11.57 69.6 11.01 64.8 10.59 60.0 10.13 55.2 9.65 48.0 8.87 40.8 8.02

8.6 7.5 76.8 10.64 69.6 10.18 64.8 9.82 60.0 9.45 55.2 9.02 48.0 8.33 40.8 7.56

11.2 10.0 76.8 10.16 69.6 9.38 64.8 8.85 60.0 8.33 55.2 8.02 48.0 7.46 40.8 6.83

16.4 15.0 76.8 10.16 69.6 9.38 64.8 8.85 60.0 8.33 55.2 7.80 48.0 7.02 40.8 6.22

24.0 18.0 76.8 10.16 69.6 9.38 64.8 8.85 60.0 8.33 55.2 7.80 48.0 7.02 40.8 6.22

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


34 HP (U-8MF2E8 & U-12MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 64.0 16.55 58.0 15.84 54.0 15.33 50.0 14.75 46.0 14.09 40.0 13.10 34.0 12.10

-14.7 -15.0 64.0 15.55 58.0 14.92 54.0 14.43 50.0 13.95 46.0 13.41 40.0 12.44 34.0 11.40

-9.6 -10.0 64.0 14.41 58.0 13.83 54.0 13.41 50.0 12.95 46.0 12.49 40.0 11.69 34.0 10.72

-4.4 -5.0 64.0 13.00 58.0 12.51 54.0 12.15 50.0 11.76 46.0 11.32 40.0 10.62 34.0 9.70

-1.8 -2.5 64.0 12.17 58.0 11.74 54.0 11.42 50.0 11.06 46.0 10.67 40.0 9.94 34.0 8.94

0.8 0.0 64.0 11.30 58.0 10.91 54.0 10.62 50.0 10.28 46.0 9.87 40.0 9.09 34.0 8.24

50% 2.8 2.0 64.0 10.50 58.0 10.16 54.0 9.89 50.0 9.53 46.0 9.11 40.0 8.43 34.0 7.68

6.0 5.0 64.0 9.14 58.0 8.85 54.0 8.60 50.0 8.33 46.0 8.02 40.0 7.48 34.0 6.88

7.0 6.0 64.0 8.77 58.0 8.41 54.0 8.19 50.0 7.97 46.0 7.68 40.0 7.19 34.0 6.61

8.6 7.5 64.0 8.77 58.0 8.12 54.0 7.68 50.0 7.41 46.0 7.17 40.0 6.76 34.0 6.25

11.2 10.0 64.0 8.77 58.0 8.12 54.0 7.68 50.0 7.24 46.0 6.80 40.0 6.15 34.0 5.66

16.4 15.0 64.0 8.77 58.0 8.12 54.0 7.68 50.0 7.24 46.0 6.80 40.0 6.15 34.0 5.49

24.0 18.0 64.0 8.77 58.0 8.12 54.0 7.68 50.0 7.24 46.0 6.80 40.0 6.15 34.0 5.49

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 51.2 12.85 46.4 12.54 43.2 12.30 40.0 11.98 36.8 11.54 32.0 10.86 27.2 10.13

-14.7 -15.0 51.2 12.05 46.4 11.79 43.2 11.54 40.0 11.28 36.8 10.96 32.0 10.30 27.2 9.53

-9.6 -10.0 51.2 11.08 46.4 10.86 43.2 10.67 40.0 10.45 36.8 10.16 32.0 9.65 27.2 8.92

-4.4 -5.0 51.2 9.91 46.4 9.74 43.2 9.60 40.0 9.40 36.8 9.16 32.0 8.51 27.2 7.75

-1.8 -2.5 51.2 9.23 46.4 9.11 43.2 8.97 40.0 8.75 36.8 8.41 32.0 7.82 27.2 7.17

0.8 0.0 51.2 8.51 46.4 8.36 43.2 8.16 40.0 7.92 36.8 7.65 32.0 7.17 27.2 6.61

40% 2.8 2.0 51.2 7.78 46.4 7.63 43.2 7.48 40.0 7.29 36.8 7.07 32.0 6.66 27.2 6.17

6.0 5.0 51.2 7.36 46.4 6.83 43.2 6.51 40.0 6.39 36.8 6.25 32.0 5.95 27.2 5.56

7.0 6.0 51.2 7.36 46.4 6.83 43.2 6.49 40.0 6.15 36.8 5.98 32.0 5.71 27.2 5.37

8.6 7.5 51.2 7.36 46.4 6.83 43.2 6.49 40.0 6.15 36.8 5.78 32.0 5.37 27.2 5.08

11.2 10.0 51.2 7.36 46.4 6.83 43.2 6.49 40.0 6.15 36.8 5.78 32.0 5.25 27.2 4.74

16.4 15.0 51.2 7.36 46.4 6.83 43.2 6.49 40.0 6.15 36.8 5.78 32.0 5.25 27.2 4.74

24.0 18.0 51.2 7.36 46.4 6.83 43.2 6.49 40.0 6.15 36.8 5.78 32.0 5.25 27.2 4.74

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 38.4 9.87 34.8 9.77 32.4 9.65 30.0 9.48 27.6 9.19 24.0 8.72 20.4 8.19

-14.7 -15.0 38.4 9.21 34.8 9.14 32.4 9.04 30.0 8.92 27.6 8.72 24.0 8.24 20.4 7.70

-9.6 -10.0 38.4 8.43 34.8 8.41 32.4 8.33 30.0 8.21 27.6 8.02 24.0 7.48 20.4 6.88

-4.4 -5.0 38.4 7.46 34.8 7.39 32.4 7.24 30.0 7.07 27.6 6.85 24.0 6.46 20.4 5.98

-1.8 -2.5 38.4 6.78 34.8 6.68 32.4 6.59 30.0 6.46 27.6 6.29 24.0 5.98 20.4 5.56

0.8 0.0 38.4 6.05 34.8 6.03 32.4 5.95 30.0 5.88 27.6 5.73 24.0 5.49 20.4 5.15

30% 2.8 2.0 38.4 5.95 34.8 5.56 32.4 5.49 30.0 5.42 27.6 5.32 24.0 5.13 20.4 4.84

6.0 5.0 38.4 5.95 34.8 5.56 32.4 5.30 30.0 5.03 27.6 4.79 24.0 4.62 20.4 4.40

7.0 6.0 38.4 5.95 34.8 5.56 32.4 5.30 30.0 5.03 27.6 4.79 24.0 4.45 20.4 4.25

8.6 7.5 38.4 5.95 34.8 5.56 32.4 5.30 30.0 5.03 27.6 4.79 24.0 4.37 20.4 4.06

11.2 10.0 38.4 5.95 34.8 5.56 32.4 5.30 30.0 5.03 27.6 4.79 24.0 4.37 20.4 3.99

16.4 15.0 38.4 5.95 34.8 5.56 32.4 5.30 30.0 5.03 27.6 4.79 24.0 4.37 20.4 3.99

24.0 18.0 38.4 5.95 34.8 5.56 32.4 5.30 30.0 5.03 27.6 4.79 24.0 4.37 20.4 3.99

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


36 HP (U-8MF2E8 & U-14MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 87.7 29.05 80.8 26.83 76.2 25.28 76.2 25.28 76.2 25.28 76.2 25.28 66.3 22.18

-14.7 -15.0 93.0 29.58 85.9 27.35 81.0 25.80 81.0 25.80 81.0 25.80 81.0 25.80 71.1 22.70

-9.6 -10.0 99.8 30.35 92.3 28.10 87.2 26.55 87.2 26.55 87.2 26.55 87.2 26.55 77.2 23.40

-4.4 -5.0 108.8 31.48 101.0 29.23 95.7 27.63 95.7 27.63 95.7 27.63 95.7 27.63 85.3 24.40

-1.8 -2.5 114.6 32.23 106.6 29.93 101.0 28.33 101.0 28.33 101.0 28.33 101.0 28.33 90.5 25.05

0.8 0.0 120.0 32.50 113.1 30.78 107.2 29.15 107.2 29.15 107.2 29.15 107.2 29.15 97.1 25.80

130% 2.8 2.0 125.1 32.50 119.3 31.40 113.3 29.75 113.3 29.75 113.3 29.75 113.3 29.75 99.4 25.23

6.0 5.0 135.0 32.50 130.5 32.25 121.5 29.68 121.5 29.68 121.5 29.68 117.0 27.15 99.4 22.90

7.0 6.0 138.9 32.50 130.5 30.95 121.5 28.50 121.5 28.50 121.5 28.50 117.0 26.13 99.4 22.03

8.6 7.5 143.8 32.50 130.5 29.00 121.5 26.73 121.5 26.73 121.5 26.73 117.0 24.53 99.4 20.73

11.2 10.0 144.0 28.95 130.5 25.83 121.5 23.85 121.5 23.85 121.5 23.85 117.0 22.00 99.4 18.68

16.4 15.0 144.0 22.45 130.5 20.18 121.5 18.73 121.5 18.73 121.5 18.73 117.0 17.53 99.4 15.00

24.0 18.0 144.0 19.08 130.5 17.25 121.5 16.08 121.5 16.08 121.5 16.08 117.0 15.20 99.4 13.13

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 87.8 28.80 80.9 26.58 76.3 25.08 76.3 25.08 76.3 25.08 70.6 23.25 61.1 20.55

-14.7 -15.0 93.1 29.33 86.0 27.13 81.1 25.60 81.1 25.60 81.1 25.60 75.5 23.80 65.5 21.00

-9.6 -10.0 99.9 30.10 92.4 27.90 87.3 26.38 87.3 26.38 87.3 26.38 81.8 24.55 71.2 21.65

-4.4 -5.0 109.0 31.25 101.1 29.00 95.7 27.45 95.7 27.45 95.7 27.45 90.2 25.60 78.6 22.55

-1.8 -2.5 114.8 32.00 106.7 29.73 100.9 28.13 100.9 28.13 100.9 28.13 95.4 26.28 83.3 23.13

0.8 0.0 120.7 32.50 113.1 30.53 107.2 28.90 107.2 28.90 107.2 28.90 101.8 27.00 89.3 23.78

120% 2.8 2.0 125.8 32.50 119.2 31.10 113.2 29.45 113.2 29.45 113.2 29.45 105.4 26.78 89.6 22.70

6.0 5.0 135.8 32.50 127.5 30.88 118.7 28.45 118.7 28.45 118.7 28.45 105.4 24.33 89.6 20.58

7.0 6.0 139.0 32.50 127.5 29.63 118.7 27.33 118.7 27.33 118.7 27.33 105.4 23.38 89.6 19.80

8.6 7.5 140.6 31.08 127.5 27.73 118.7 25.60 118.7 25.60 118.7 25.60 105.4 21.98 89.6 18.65

11.2 10.0 140.6 27.58 127.5 24.68 118.7 22.83 118.7 22.83 118.7 22.83 105.4 19.73 89.6 16.80

16.4 15.0 140.6 21.33 127.5 19.23 118.7 17.88 118.7 17.88 118.7 17.88 105.4 15.70 89.6 13.53

24.0 18.0 140.6 18.08 127.5 16.43 118.7 15.33 118.7 15.33 118.7 15.33 105.4 13.65 89.6 11.85

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 87.9 28.53 81.0 26.35 76.3 24.88 76.3 24.88 73.1 23.88 64.7 21.38 56.0 18.95

-14.7 -15.0 93.3 29.08 86.1 26.90 81.1 25.43 81.1 25.43 78.1 24.40 69.3 21.88 60.0 19.35

-9.6 -10.0 100.1 29.88 92.5 27.68 87.5 26.18 87.5 26.18 84.3 25.18 74.9 22.55 65.1 19.93

-4.4 -5.0 109.2 31.03 101.2 28.80 95.7 27.25 95.7 27.25 92.5 26.23 82.5 23.48 71.9 20.70

-1.8 -2.5 114.9 31.78 106.7 29.50 101.0 27.93 101.0 27.93 97.9 26.90 87.2 24.10 76.2 21.25

0.8 0.0 121.4 32.50 113.1 30.25 107.1 28.63 107.1 28.63 104.1 27.58 93.1 24.70 80.2 21.38

110% 2.8 2.0 126.6 32.50 119.2 30.80 113.1 29.18 113.1 29.18 108.5 27.63 94.4 23.85 80.2 20.28

6.0 5.0 136.1 32.50 124.4 29.53 115.8 27.25 115.8 27.25 108.5 25.03 94.4 21.65 80.2 18.40

7.0 6.0 137.3 31.70 124.4 28.33 115.8 26.18 115.8 26.18 108.5 24.05 94.4 20.83 80.2 17.70

8.6 7.5 137.3 29.60 124.4 26.50 115.8 24.50 115.8 24.50 108.5 22.55 94.4 19.55 80.2 16.68

11.2 10.0 137.3 26.25 124.4 23.55 115.8 21.83 115.8 21.83 108.5 20.18 94.4 17.55 80.2 15.03

16.4 15.0 137.3 20.25 124.4 18.33 115.8 17.08 115.8 17.08 108.5 15.95 94.4 14.00 80.2 12.13

24.0 18.0 137.3 17.13 124.4 15.63 115.8 14.63 115.8 14.63 108.5 13.75 94.4 12.20 80.2 10.65

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 88.1 28.25 81.1 26.15 76.4 24.68 71.5 23.20 66.6 21.73 58.9 19.50 51.0 17.35

-14.7 -15.0 93.5 28.83 86.2 26.70 81.2 25.23 76.2 23.75 71.0 22.23 62.9 19.95 54.6 17.70

-9.6 -10.0 100.3 29.65 92.8 27.48 87.5 26.00 82.2 24.48 76.6 22.93 68.0 20.58 59.1 18.20

-4.4 -5.0 109.4 30.80 101.4 28.60 95.8 27.05 90.1 25.48 84.1 23.88 74.9 21.40 65.2 18.90

-1.8 -2.5 115.0 31.53 106.8 29.28 100.9 27.73 94.9 26.10 88.8 24.48 79.1 21.93 69.0 19.35

0.8 0.0 121.8 32.30 113.1 29.98 107.1 28.35 100.9 26.70 94.5 25.03 83.7 22.20 71.2 18.98

100% 2.8 2.0 127.4 32.50 119.2 30.50 113.0 28.88 104.6 26.55 96.3 24.30 83.7 21.08 71.2 18.03

6.0 5.0 133.9 31.50 121.4 28.23 113.0 26.10 104.6 24.05 96.3 22.05 83.7 19.13 71.2 16.35

7.0 6.0 133.9 30.20 121.4 27.08 113.0 25.00 104.6 23.10 96.3 21.18 83.7 18.40 71.2 15.73

8.6 7.5 133.9 28.18 121.4 25.30 113.0 23.45 104.6 21.63 96.3 19.88 83.7 17.30 71.2 14.83

11.2 10.0 133.9 24.95 121.4 22.48 113.0 20.88 104.6 19.30 96.3 17.78 83.7 15.55 71.2 13.38

16.4 15.0 133.9 19.20 121.4 17.45 113.0 16.30 104.6 15.18 96.3 14.05 83.7 12.43 71.2 10.83

9 24.0 18.0 133.9 16.40 121.4 15.05 113.0 14.15 104.6 13.25 96.3 12.35 83.7 10.98 71.2 9.63
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


36 HP (U-8MF2E8 & U-14MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 88.9 27.33 81.7 25.35 76.8 24.00 71.9 22.65 66.8 21.28 59.0 19.23 50.9 17.23

-14.7 -15.0 94.4 27.98 86.9 25.95 81.7 24.58 76.5 23.18 71.2 21.78 62.9 19.65 54.4 17.55

-9.6 -10.0 101.1 28.83 93.3 26.78 87.9 25.35 82.4 23.90 76.7 22.43 67.9 20.20 58.9 17.98

-4.4 -5.0 110.2 30.00 101.7 27.85 95.9 26.38 90.1 24.85 84.0 23.33 74.5 20.98 64.1 18.40

-1.8 -2.5 115.7 30.58 107.0 28.38 101.0 26.88 94.1 25.10 86.7 23.13 75.4 20.28 64.1 17.60

0.8 0.0 120.6 30.48 109.3 27.48 101.7 25.55 94.1 23.65 86.7 21.80 75.4 19.15 64.1 16.60

90% 2.8 2.0 120.6 28.73 109.3 25.95 101.7 24.15 94.1 22.38 86.7 20.65 75.4 18.15 64.1 15.73

6.0 5.0 120.6 25.75 109.3 23.33 101.7 21.75 94.1 20.20 86.7 18.68 75.4 16.43 64.1 14.18

7.0 6.0 120.6 24.63 109.3 22.35 101.7 20.85 94.1 19.38 86.7 17.93 75.4 15.78 64.1 13.65

8.6 7.5 120.6 22.93 109.3 20.83 101.7 19.48 94.1 18.13 86.7 16.78 75.4 14.80 64.1 12.85

11.2 10.0 120.6 20.20 109.3 18.45 101.7 17.28 94.1 16.13 86.7 15.00 75.4 13.30 64.1 11.60

16.4 15.0 120.6 15.35 109.3 14.18 101.7 13.40 94.1 12.60 86.7 11.80 75.4 10.60 64.1 9.38

24.0 18.0 120.6 14.95 109.3 13.75 101.7 12.93 94.1 12.10 86.7 11.30 75.4 10.08 64.1 8.85

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 90.1 26.68 82.7 24.83 77.6 23.58 72.5 22.30 67.2 21.03 59.3 19.15 51.1 17.30

-14.7 -15.0 95.6 27.38 87.8 25.45 82.5 24.15 77.2 22.85 71.6 21.53 63.3 19.55 54.6 17.58

-9.6 -10.0 102.5 28.28 94.2 26.28 88.7 24.93 82.9 23.55 77.0 22.13 67.0 19.68 57.0 17.30

-4.4 -5.0 107.1 27.73 97.1 25.28 90.4 23.68 83.7 22.10 77.0 20.55 67.0 18.30 57.0 16.13

-1.8 -2.5 107.1 26.28 97.1 23.95 90.4 22.45 83.7 20.98 77.0 19.53 67.0 17.40 57.0 15.33

0.8 0.0 107.1 24.63 97.1 22.50 90.4 21.10 83.7 19.73 77.0 18.38 67.0 16.38 57.0 14.43

80% 2.8 2.0 107.1 23.18 97.1 21.23 90.4 19.93 83.7 18.65 77.0 17.38 67.0 15.50 57.0 13.63

6.0 5.0 107.1 20.68 97.1 19.00 90.4 17.88 83.7 16.75 77.0 15.63 67.0 13.93 57.0 12.20

7.0 6.0 107.1 19.75 97.1 18.18 90.4 17.10 83.7 16.05 77.0 14.98 67.0 13.35 57.0 11.73

8.6 7.5 107.1 18.33 97.1 16.90 90.4 15.95 83.7 15.00 77.0 14.03 67.0 12.55 57.0 11.05

11.2 10.0 107.1 16.08 97.1 14.90 90.4 14.13 83.7 13.33 77.0 12.50 67.0 11.25 57.0 9.98

16.4 15.0 107.1 13.50 97.1 12.43 90.4 11.70 83.7 10.98 77.0 10.25 67.0 9.18 57.0 8.10

24.0 18.0 107.1 13.50 97.1 12.43 90.4 11.70 83.7 10.98 77.0 10.25 67.0 9.18 57.0 8.10

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 92.1 26.43 84.3 24.70 79.1 23.53 73.2 22.15 67.3 20.83 58.6 18.85 49.8 16.95

-14.7 -15.0 93.8 25.85 85.0 23.80 79.1 22.48 73.2 21.15 67.3 19.83 58.6 17.93 49.8 16.05

-9.6 -10.0 93.8 24.23 85.0 22.38 79.1 21.18 73.2 19.95 67.3 18.78 58.6 16.95 49.8 15.10

-4.4 -5.0 93.8 22.15 85.0 20.50 79.1 19.40 73.2 18.30 67.3 17.23 58.6 15.60 49.8 13.98

-1.8 -2.5 93.8 20.93 85.0 19.40 79.1 18.38 73.2 17.35 67.3 16.33 58.6 14.80 49.8 13.25

0.8 0.0 93.8 19.58 85.0 18.18 79.1 17.23 73.2 16.28 67.3 15.33 58.6 13.90 49.8 12.45

70% 2.8 2.0 93.8 18.35 85.0 17.08 79.1 16.23 73.2 15.35 67.3 14.45 58.6 13.10 49.8 11.60

6.0 5.0 93.8 16.30 85.0 15.23 79.1 14.48 73.2 13.70 67.3 12.90 58.6 11.65 49.8 10.38

7.0 6.0 93.8 15.55 85.0 14.53 79.1 13.83 73.2 13.10 67.3 12.35 58.6 11.20 49.8 9.98

8.6 7.5 93.8 14.38 85.0 13.50 79.1 12.88 73.2 12.23 67.3 11.55 58.6 10.50 49.8 9.40

11.2 10.0 93.8 12.53 85.0 11.85 79.1 11.35 73.2 10.83 67.3 10.30 58.6 9.43 49.8 8.50

16.4 15.0 93.8 12.08 85.0 11.13 79.1 10.48 73.2 9.85 67.3 9.23 58.6 8.28 49.8 7.33

24.0 18.0 93.8 12.08 85.0 11.13 79.1 10.48 73.2 9.85 67.3 9.23 58.6 8.28 49.8 7.33

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 80.3 21.78 72.8 20.40 67.8 19.45 62.8 18.48 57.7 17.53 50.2 16.10 42.7 14.68

-14.7 -15.0 80.3 20.55 72.8 19.33 67.8 18.48 62.8 17.63 57.7 16.73 50.2 15.30 42.7 13.88

-9.6 -10.0 80.3 19.13 72.8 18.00 67.8 17.23 62.8 16.45 57.7 15.68 50.2 14.45 42.7 13.08

-4.4 -5.0 80.3 17.40 72.8 16.40 67.8 15.73 62.8 15.03 57.7 14.30 50.2 13.20 42.7 12.03

-1.8 -2.5 80.3 16.38 72.8 15.48 67.8 14.85 62.8 14.20 57.7 13.53 50.2 12.48 42.7 11.35

0.8 0.0 80.3 15.25 72.8 14.45 67.8 13.88 62.8 13.28 57.7 12.65 50.2 11.68 42.7 10.45

60% 2.8 2.0 80.3 14.28 72.8 13.55 67.8 13.00 62.8 12.45 57.7 11.88 50.2 10.85 42.7 9.73

6.0 5.0 80.3 12.60 72.8 11.98 67.8 11.50 62.8 11.03 57.7 10.50 50.2 9.63 42.7 8.70

7.0 6.0 80.3 11.95 72.8 11.40 67.8 10.98 62.8 10.53 57.7 10.05 50.2 9.25 42.7 8.38

8.6 7.5 80.3 11.03 72.8 10.55 67.8 10.20 62.8 9.83 57.7 9.40 50.2 8.70 42.7 7.90

11.2 10.0 80.3 10.63 72.8 9.80 67.8 9.28 62.8 8.73 57.7 8.35 50.2 7.80 42.7 7.15

16.4 15.0 80.3 10.63 72.8 9.80 67.8 9.28 62.8 8.73 57.7 8.18 50.2 7.38 42.7 6.55

24.0 18.0 80.3 10.63 72.8 9.80 67.8 9.28 62.8 8.73 57.7 8.18 50.2 7.38 42.7 6.55

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


36 HP (U-8MF2E8 & U-14MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 67.0 17.10 60.7 16.40 56.5 15.88 52.3 15.30 48.1 14.63 41.8 13.60 35.6 12.58

-14.7 -15.0 67.0 16.10 60.7 15.45 56.5 14.98 52.3 14.48 48.1 13.93 41.8 12.93 35.6 11.88

-9.6 -10.0 67.0 14.90 60.7 14.33 56.5 13.90 52.3 13.45 48.1 12.95 41.8 12.15 35.6 11.15

-4.4 -5.0 67.0 13.45 60.7 12.98 56.5 12.60 52.3 12.20 48.1 11.78 41.8 11.05 35.6 10.13

-1.8 -2.5 67.0 12.63 60.7 12.18 56.5 11.85 52.3 11.48 48.1 11.08 41.8 10.38 35.6 9.35

0.8 0.0 67.0 11.70 60.7 11.33 56.5 11.03 52.3 10.70 48.1 10.28 41.8 9.48 35.6 8.60

50% 2.8 2.0 67.0 10.90 60.7 10.55 56.5 10.28 52.3 9.90 48.1 9.50 41.8 8.80 35.6 8.03

6.0 5.0 67.0 9.48 60.7 9.20 56.5 8.98 52.3 8.70 48.1 8.38 41.8 7.83 35.6 7.20

7.0 6.0 67.0 9.18 60.7 8.75 56.5 8.55 52.3 8.30 48.1 8.03 41.8 7.53 35.6 6.95

8.6 7.5 67.0 9.18 60.7 8.50 56.5 8.05 52.3 7.73 48.1 7.50 41.8 7.08 35.6 6.55

11.2 10.0 67.0 9.18 60.7 8.50 56.5 8.05 52.3 7.60 48.1 7.15 41.8 6.48 35.6 5.95

16.4 15.0 67.0 9.18 60.7 8.50 56.5 8.05 52.3 7.60 48.1 7.15 41.8 6.48 35.6 5.78

24.0 18.0 67.0 9.18 60.7 8.50 56.5 8.05 52.3 7.60 48.1 7.15 41.8 6.48 35.6 5.78

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 53.6 13.35 48.6 13.03 45.2 12.78 41.8 12.48 38.5 12.03 33.4 11.30 28.5 10.55

-14.7 -15.0 53.6 12.50 48.6 12.23 45.2 12.00 41.8 11.73 38.5 11.43 33.4 10.73 28.5 9.95

-9.6 -10.0 53.6 11.50 48.6 11.30 45.2 11.10 41.8 10.88 38.5 10.58 33.4 10.05 28.5 9.30

-4.4 -5.0 53.6 10.30 48.6 10.15 45.2 10.00 41.8 9.80 38.5 9.58 33.4 8.90 28.5 8.13

-1.8 -2.5 53.6 9.60 48.6 9.48 45.2 9.35 41.8 9.13 38.5 8.78 33.4 8.20 28.5 7.53

0.8 0.0 53.6 8.85 48.6 8.73 45.2 8.53 41.8 8.28 38.5 8.00 33.4 7.53 28.5 6.95

40% 2.8 2.0 53.6 8.13 48.6 7.98 45.2 7.83 41.8 7.63 38.5 7.40 33.4 7.00 28.5 6.50

6.0 5.0 53.6 7.73 48.6 7.18 45.2 6.83 41.8 6.70 38.5 6.55 33.4 6.25 28.5 5.85

7.0 6.0 53.6 7.73 48.6 7.18 45.2 6.83 41.8 6.48 38.5 6.28 33.4 6.03 28.5 5.65

8.6 7.5 53.6 7.73 48.6 7.18 45.2 6.83 41.8 6.48 38.5 6.10 33.4 5.68 28.5 5.38

11.2 10.0 53.6 7.73 48.6 7.18 45.2 6.83 41.8 6.48 38.5 6.10 33.4 5.55 28.5 5.03

16.4 15.0 53.6 7.73 48.6 7.18 45.2 6.83 41.8 6.48 38.5 6.10 33.4 5.55 28.5 5.03

24.0 18.0 53.6 7.73 48.6 7.18 45.2 6.83 41.8 6.48 38.5 6.10 33.4 5.55 28.5 5.03

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 40.2 10.28 36.4 10.18 33.9 10.08 31.4 9.88 28.9 9.58 25.1 9.10 21.4 8.58

-14.7 -15.0 40.2 9.60 36.4 9.55 33.9 9.45 31.4 9.30 28.9 9.10 25.1 8.63 21.4 8.05

-9.6 -10.0 40.2 8.80 36.4 8.78 33.9 8.70 31.4 8.60 28.9 8.40 25.1 7.85 21.4 7.20

-4.4 -5.0 40.2 7.80 36.4 7.73 33.9 7.58 31.4 7.40 28.9 7.18 25.1 6.78 21.4 6.30

-1.8 -2.5 40.2 7.10 36.4 7.03 33.9 6.93 31.4 6.78 28.9 6.60 25.1 6.28 21.4 5.88

0.8 0.0 40.2 6.35 36.4 6.33 33.9 6.28 31.4 6.18 28.9 6.05 25.1 5.80 21.4 5.45

30% 2.8 2.0 40.2 6.28 36.4 5.88 33.9 5.78 31.4 5.73 28.9 5.63 25.1 5.43 21.4 5.13

6.0 5.0 40.2 6.28 36.4 5.88 33.9 5.60 31.4 5.33 28.9 5.08 25.1 4.88 21.4 4.68

7.0 6.0 40.2 6.28 36.4 5.88 33.9 5.60 31.4 5.33 28.9 5.08 25.1 4.70 21.4 4.53

8.6 7.5 40.2 6.28 36.4 5.88 33.9 5.60 31.4 5.33 28.9 5.08 25.1 4.65 21.4 4.30

11.2 10.0 40.2 6.28 36.4 5.88 33.9 5.60 31.4 5.33 28.9 5.08 25.1 4.65 21.4 4.25

16.4 15.0 40.2 6.28 36.4 5.88 33.9 5.60 31.4 5.33 28.9 5.08 25.1 4.65 21.4 4.25

24.0 18.0 40.2 6.28 36.4 5.88 33.9 5.60 31.4 5.33 28.9 5.08 25.1 4.65 21.4 4.25

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


38 HP (U-8MF2E8 & U-14MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 91.2 31.43 84.1 28.99 79.3 27.31 79.3 27.31 79.3 27.31 79.3 27.31 69.0 23.90

-14.7 -15.0 96.7 31.98 89.4 29.54 84.3 27.86 84.3 27.86 84.3 27.86 84.3 27.86 74.0 24.45

-9.6 -10.0 103.8 32.81 96.2 30.36 90.8 28.68 90.8 28.68 90.8 28.68 90.8 28.68 80.4 25.22

-4.4 -5.0 113.3 34.05 105.2 31.57 99.6 29.84 99.6 29.84 99.6 29.84 99.6 29.84 88.9 26.32

-1.8 -2.5 119.2 34.84 110.9 32.34 105.1 30.61 105.1 30.61 105.1 30.61 105.1 30.61 94.2 27.03

0.8 0.0 126.3 35.75 117.8 33.25 111.7 31.49 111.7 31.49 111.7 31.49 111.7 31.49 101.0 27.86

130% 2.8 2.0 131.4 35.75 124.2 33.99 117.9 32.20 117.9 32.20 117.9 32.20 117.9 32.20 104.7 27.61

6.0 5.0 141.7 35.75 136.9 35.31 127.9 32.64 127.9 32.64 127.9 32.64 123.2 29.78 104.7 25.08

7.0 6.0 145.9 35.75 137.4 34.13 127.9 31.38 127.9 31.38 127.9 31.38 123.2 28.66 104.7 24.12

8.6 7.5 151.2 35.75 137.4 31.96 127.9 29.43 127.9 29.43 127.9 29.43 123.2 26.92 104.7 22.69

11.2 10.0 151.6 32.01 137.4 28.52 127.9 26.29 127.9 26.29 127.9 26.29 123.2 24.15 104.7 20.43

16.4 15.0 151.6 24.86 137.4 22.30 127.9 20.65 127.9 20.65 127.9 20.65 123.2 19.25 104.7 16.45

24.0 18.0 151.6 21.15 137.4 19.09 127.9 17.74 127.9 17.74 127.9 17.74 123.2 16.72 104.7 14.38

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 91.4 31.13 84.3 28.74 79.4 27.09 79.4 27.09 79.4 27.09 73.5 25.08 63.7 22.14

-14.7 -15.0 96.9 31.71 89.5 29.29 84.4 27.67 84.4 27.67 84.4 27.67 78.7 25.66 68.3 22.63

-9.6 -10.0 104.0 32.56 96.3 30.14 90.9 28.46 90.9 28.46 90.9 28.46 85.2 26.48 74.1 23.32

-4.4 -5.0 113.4 33.80 105.3 31.32 99.6 29.65 99.6 29.65 99.6 29.65 93.9 27.64 81.9 24.28

-1.8 -2.5 119.5 34.60 111.0 32.09 105.1 30.39 105.1 30.39 105.1 30.39 99.4 28.35 86.8 24.94

0.8 0.0 126.5 35.53 117.8 33.00 111.6 31.24 111.6 31.24 111.6 31.24 106.0 29.18 92.9 25.69

120% 2.8 2.0 132.1 35.75 124.1 33.66 117.8 31.87 117.8 31.87 117.8 31.87 111.0 29.37 94.4 24.81

6.0 5.0 142.4 35.75 134.2 33.99 125.0 31.30 125.0 31.30 125.0 31.30 111.0 26.65 94.4 22.52

7.0 6.0 146.1 35.75 134.2 32.64 125.0 30.06 125.0 30.06 125.0 30.06 111.0 25.63 94.4 21.67

8.6 7.5 148.0 34.29 134.2 30.55 125.0 28.19 125.0 28.19 125.0 28.19 111.0 24.09 94.4 20.41

11.2 10.0 148.0 30.47 134.2 27.23 125.0 25.14 125.0 25.14 125.0 25.14 111.0 21.62 94.4 18.37

16.4 15.0 148.0 23.62 134.2 21.26 125.0 19.72 125.0 19.72 125.0 19.72 111.0 17.24 94.4 14.80

24.0 18.0 148.0 20.05 134.2 18.15 125.0 16.94 125.0 16.94 125.0 16.94 111.0 14.99 94.4 12.98

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 91.5 30.83 84.4 28.46 79.4 26.87 79.4 26.87 76.2 25.74 67.4 23.05 58.3 20.41

-14.7 -15.0 97.1 31.43 89.6 29.07 84.5 27.45 84.5 27.45 81.3 26.35 72.1 23.57 62.5 20.85

-9.6 -10.0 104.2 32.29 96.4 29.92 91.0 28.27 91.0 28.27 87.7 27.17 78.1 24.31 67.8 21.45

-4.4 -5.0 113.6 33.55 105.4 31.10 99.7 29.43 99.7 29.43 96.4 28.30 85.9 25.33 74.9 22.33

-1.8 -2.5 119.6 34.35 111.0 31.87 105.1 30.14 105.1 30.14 101.9 29.04 90.9 25.99 79.4 22.91

0.8 0.0 126.6 35.28 117.8 32.73 111.6 30.97 111.6 30.97 108.4 29.81 97.0 26.68 84.5 23.35

110% 2.8 2.0 132.9 35.75 124.1 33.33 117.8 31.57 117.8 31.57 114.2 30.31 99.4 26.13 84.5 22.17

6.0 5.0 143.0 35.75 131.0 32.51 122.0 29.98 122.0 29.98 114.2 27.47 99.4 23.71 84.5 20.13

7.0 6.0 144.6 34.98 131.0 31.21 122.0 28.79 122.0 28.79 114.2 26.40 99.4 22.80 84.5 19.36

8.6 7.5 144.6 32.67 131.0 29.21 122.0 26.98 122.0 26.98 114.2 24.78 99.4 21.42 84.5 18.23

11.2 10.0 144.6 29.01 131.0 25.99 122.0 24.04 122.0 24.04 114.2 22.17 99.4 19.25 84.5 16.45

16.4 15.0 144.6 22.41 131.0 20.24 122.0 18.84 122.0 18.84 114.2 17.52 99.4 15.37 84.5 13.26

24.0 18.0 144.6 19.00 131.0 17.27 122.0 16.14 122.0 16.14 114.2 15.15 99.4 13.37 84.5 11.63

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 91.7 30.55 84.5 28.24 79.5 26.65 74.5 25.05 69.3 23.43 61.3 21.04 53.1 18.67

-14.7 -15.0 97.3 31.16 89.7 28.85 84.6 27.25 79.4 25.63 73.9 23.98 65.5 21.51 56.8 19.06

-9.6 -10.0 104.4 32.04 96.5 29.70 91.2 28.08 85.6 26.40 79.7 24.72 70.9 22.17 61.5 19.61

-4.4 -5.0 113.8 33.30 105.4 30.88 99.7 29.21 93.8 27.50 87.6 25.74 77.9 23.07 67.8 20.38

-1.8 -2.5 119.7 34.10 111.1 31.63 105.1 29.95 98.9 28.19 92.5 26.40 82.5 23.68 71.9 20.87

0.8 0.0 126.7 34.95 117.8 32.42 111.5 30.69 105.1 28.88 98.4 27.03 87.9 24.23 75.0 20.74

100% 2.8 2.0 133.4 35.53 124.1 33.03 117.7 31.27 110.2 29.15 101.4 26.65 88.2 23.07 75.0 19.69

6.0 5.0 141.0 34.73 127.8 31.08 119.0 28.71 110.2 26.40 101.4 24.17 88.2 20.96 75.0 17.85

7.0 6.0 141.0 33.30 127.8 29.81 119.0 27.50 110.2 25.36 101.4 23.24 88.2 20.16 75.0 17.19

8.6 7.5 141.0 31.10 127.8 27.89 119.0 25.80 110.2 23.76 101.4 21.81 88.2 18.95 75.0 16.20

11.2 10.0 141.0 27.58 127.8 24.78 119.0 22.99 110.2 21.23 101.4 19.53 88.2 17.02 75.0 14.60

16.4 15.0 141.0 21.26 127.8 19.25 119.0 17.96 110.2 16.69 101.4 15.46 88.2 13.61 75.0 11.83

9 24.0 18.0 141.0 17.99 127.8 16.42 119.0 15.37 110.2 14.36 101.4 13.37 88.2 11.88 75.0 10.40
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


38 HP (U-8MF2E8 & U-14MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 92.5 29.51 85.1 27.36 80.0 25.91 74.7 24.42 69.5 22.94 61.4 20.71 53.0 18.54

-14.7 -15.0 98.2 30.22 90.4 28.02 85.1 26.51 79.6 25.00 74.1 23.46 65.6 21.15 56.6 18.89

-9.6 -10.0 105.3 31.16 97.1 28.90 91.5 27.36 85.8 25.77 79.8 24.17 70.7 21.78 61.3 19.36

-4.4 -5.0 114.6 32.40 105.9 30.06 100.0 28.46 93.8 26.81 87.3 25.14 77.6 22.58 67.4 19.99

-1.8 -2.5 120.4 33.08 111.4 30.69 105.2 29.04 98.8 27.34 91.3 25.33 79.4 22.17 67.5 19.20

0.8 0.0 127.0 33.55 115.1 30.20 107.1 28.05 99.1 25.93 91.3 23.90 79.4 20.93 67.5 18.12

90% 2.8 2.0 127.0 31.63 115.1 28.52 107.1 26.51 99.1 24.56 91.3 22.63 79.4 19.86 67.5 17.16

6.0 5.0 127.0 28.38 115.1 25.66 107.1 23.90 99.1 22.17 91.3 20.46 79.4 17.96 67.5 15.48

7.0 6.0 127.0 27.14 115.1 24.59 107.1 22.91 99.1 21.26 91.3 19.64 79.4 17.24 67.5 14.88

8.6 7.5 127.0 25.27 115.1 22.94 107.1 21.40 99.1 19.88 91.3 18.40 79.4 16.20 67.5 14.03

11.2 10.0 127.0 22.30 115.1 20.30 107.1 19.00 99.1 17.71 91.3 16.45 79.4 14.55 67.5 12.65

16.4 15.0 127.0 16.97 115.1 15.62 107.1 14.74 99.1 13.83 91.3 12.95 79.4 11.61 67.5 10.23

24.0 18.0 127.0 16.23 115.1 14.88 107.1 14.00 99.1 13.12 91.3 12.24 79.4 10.89 67.5 9.57

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 93.7 28.77 86.0 26.76 80.8 25.41 75.4 24.04 70.0 22.66 61.8 20.60 53.2 18.59

-14.7 -15.0 99.4 29.54 91.4 27.45 85.9 26.04 80.3 24.61 74.6 23.18 65.8 21.04 56.8 18.89

-9.6 -10.0 106.6 30.50 98.1 28.35 92.2 26.87 86.3 25.38 80.3 23.87 70.6 21.45 60.0 18.84

-4.4 -5.0 112.8 30.47 102.2 27.72 95.2 25.93 88.2 24.17 81.0 22.47 70.6 19.97 60.0 17.57

-1.8 -2.5 112.8 28.88 102.2 26.29 95.2 24.61 88.2 22.96 81.0 21.34 70.6 18.98 60.0 16.69

0.8 0.0 112.8 27.09 102.2 24.72 95.2 23.16 88.2 21.62 81.0 20.10 70.6 17.88 60.0 15.70

80% 2.8 2.0 112.8 25.49 102.2 23.29 95.2 21.86 88.2 20.43 81.0 19.00 70.6 16.91 60.0 14.85

6.0 5.0 112.8 22.77 102.2 20.87 95.2 19.61 88.2 18.34 81.0 17.11 70.6 15.21 60.0 13.28

7.0 6.0 112.8 21.73 102.2 19.97 95.2 18.78 88.2 17.57 81.0 16.39 70.6 14.58 60.0 12.76

8.6 7.5 112.8 20.19 102.2 18.59 95.2 17.52 88.2 16.42 81.0 15.35 70.6 13.70 60.0 12.02

11.2 10.0 112.8 17.71 102.2 16.39 95.2 15.51 88.2 14.60 81.0 13.70 70.6 12.29 60.0 10.86

16.4 15.0 112.8 14.63 102.2 13.45 95.2 12.68 88.2 11.88 81.0 11.08 70.6 9.90 60.0 8.77

24.0 18.0 112.8 14.63 102.2 13.45 95.2 12.68 88.2 11.88 81.0 11.08 70.6 9.90 60.0 8.72

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 95.8 28.52 87.7 26.62 82.3 25.36 76.8 24.06 70.9 22.72 61.8 20.54 52.5 18.45

-14.7 -15.0 98.8 28.30 89.5 26.04 83.3 24.53 77.1 23.07 70.9 21.64 61.8 19.53 52.5 17.46

-9.6 -10.0 98.8 26.57 89.5 24.50 83.3 23.16 77.1 21.81 70.9 20.49 61.8 18.45 52.5 16.42

-4.4 -5.0 98.8 24.31 89.5 22.44 83.3 21.23 77.1 20.02 70.9 18.81 61.8 17.00 52.5 15.21

-1.8 -2.5 98.8 22.99 89.5 21.26 83.3 20.10 77.1 18.95 70.9 17.82 61.8 16.12 52.5 14.41

0.8 0.0 98.8 21.48 89.5 19.91 83.3 18.87 77.1 17.79 70.9 16.75 61.8 15.15 52.5 13.53

70% 2.8 2.0 98.8 20.16 89.5 18.73 83.3 17.74 77.1 16.78 70.9 15.79 61.8 14.27 52.5 12.62

6.0 5.0 98.8 17.90 89.5 16.69 83.3 15.84 77.1 14.99 70.9 14.11 61.8 12.71 52.5 11.28

7.0 6.0 98.8 17.08 89.5 15.92 83.3 15.15 77.1 14.33 70.9 13.50 61.8 12.21 52.5 10.84

8.6 7.5 98.8 15.79 89.5 14.80 83.3 14.11 77.1 13.37 70.9 12.62 61.8 11.44 52.5 10.23

11.2 10.0 98.8 13.78 89.5 12.98 83.3 12.43 77.1 11.85 70.9 11.25 61.8 10.26 52.5 9.24

16.4 15.0 98.8 13.06 89.5 12.02 83.3 11.33 77.1 10.64 70.9 9.96 61.8 8.94 52.5 7.89

24.0 18.0 98.8 13.06 89.5 12.02 83.3 11.33 77.1 10.64 70.9 9.96 61.8 8.94 52.5 7.89

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 84.6 23.82 76.6 22.28 71.4 21.20 66.2 20.13 60.8 19.09 52.8 17.52 45.0 15.95

-14.7 -15.0 84.6 22.50 76.6 21.12 71.4 20.19 66.2 19.22 60.8 18.21 52.8 16.64 45.0 15.07

-9.6 -10.0 84.6 20.96 76.6 19.66 71.4 18.81 66.2 17.96 60.8 17.08 52.8 15.70 45.0 14.19

-4.4 -5.0 84.6 19.06 76.6 17.93 71.4 17.16 66.2 16.39 60.8 15.59 52.8 14.36 45.0 13.06

-1.8 -2.5 84.6 17.96 76.6 16.91 71.4 16.20 66.2 15.48 60.8 14.74 52.8 13.59 45.0 12.32

0.8 0.0 84.6 16.72 76.6 15.79 71.4 15.15 66.2 14.47 60.8 13.78 52.8 12.71 45.0 11.33

60% 2.8 2.0 84.6 15.65 76.6 14.80 71.4 14.22 66.2 13.59 60.8 12.95 52.8 11.80 45.0 10.56

6.0 5.0 84.6 13.81 76.6 13.09 71.4 12.57 66.2 12.02 60.8 11.44 52.8 10.48 45.0 9.43

7.0 6.0 84.6 13.12 76.6 12.46 71.4 11.99 66.2 11.50 60.8 10.95 52.8 10.07 45.0 9.10

8.6 7.5 84.6 12.07 76.6 11.55 71.4 11.14 66.2 10.70 60.8 10.23 52.8 9.43 45.0 8.58

11.2 10.0 84.6 11.50 76.6 10.59 71.4 10.01 66.2 9.46 60.8 9.10 52.8 8.47 45.0 7.76

16.4 15.0 84.6 11.50 76.6 10.59 71.4 10.01 66.2 9.41 60.8 8.83 52.8 7.95 45.0 7.07

24.0 18.0 84.6 11.50 76.6 10.59 71.4 10.01 66.2 9.41 60.8 8.83 52.8 7.95 45.0 7.07

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


38 HP (U-8MF2E8 & U-14MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 70.6 18.67 63.9 17.88 59.5 17.30 55.1 16.64 50.7 15.90 44.0 14.77 37.5 13.64

-14.7 -15.0 70.6 17.57 63.9 16.83 59.5 16.31 55.1 15.76 50.7 15.15 44.0 14.05 37.5 12.87

-9.6 -10.0 70.6 16.28 63.9 15.62 59.5 15.15 55.1 14.63 50.7 14.08 44.0 13.20 37.5 12.10

-4.4 -5.0 70.6 14.71 63.9 14.14 59.5 13.72 55.1 13.28 50.7 12.82 44.0 11.99 37.5 10.97

-1.8 -2.5 70.6 13.78 63.9 13.28 59.5 12.90 55.1 12.49 50.7 12.05 44.0 11.25 37.5 10.15

0.8 0.0 70.6 12.79 63.9 12.35 59.5 11.99 55.1 11.63 50.7 11.17 44.0 10.29 37.5 9.32

50% 2.8 2.0 70.6 11.91 63.9 11.52 59.5 11.19 55.1 10.78 50.7 10.31 44.0 9.54 37.5 8.69

6.0 5.0 70.6 10.34 63.9 10.04 59.5 9.76 55.1 9.46 50.7 9.10 44.0 8.50 37.5 7.78

7.0 6.0 70.6 9.90 63.9 9.54 59.5 9.30 55.1 9.02 50.7 8.72 44.0 8.17 37.5 7.51

8.6 7.5 70.6 9.90 63.9 9.19 59.5 8.69 55.1 8.42 50.7 8.14 44.0 7.67 37.5 7.10

11.2 10.0 70.6 9.90 63.9 9.19 59.5 8.69 55.1 8.20 50.7 7.70 44.0 6.96 37.5 6.44

16.4 15.0 70.6 9.90 63.9 9.19 59.5 8.69 55.1 8.20 50.7 7.70 44.0 6.96 37.5 6.22

24.0 18.0 70.6 9.90 63.9 9.19 59.5 8.69 55.1 8.20 50.7 7.70 44.0 6.96 37.5 6.22

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 56.4 14.52 51.2 14.16 47.6 13.89 44.0 13.53 40.6 13.04 35.2 12.27 30.0 11.44

-14.7 -15.0 56.4 13.61 51.2 13.31 47.6 13.04 44.0 12.73 40.6 12.38 35.2 11.63 30.0 10.78

-9.6 -10.0 56.4 12.51 51.2 12.27 47.6 12.07 44.0 11.80 40.6 11.47 35.2 10.89 30.0 10.09

-4.4 -5.0 56.4 11.22 51.2 11.03 47.6 10.86 44.0 10.64 40.6 10.37 35.2 9.65 30.0 8.77

-1.8 -2.5 56.4 10.45 51.2 10.31 47.6 10.15 44.0 9.90 40.6 9.52 35.2 8.88 30.0 8.14

0.8 0.0 56.4 9.63 51.2 9.46 47.6 9.24 44.0 8.99 40.6 8.66 35.2 8.14 30.0 7.51

40% 2.8 2.0 56.4 8.83 51.2 8.66 47.6 8.50 44.0 8.28 40.6 8.03 35.2 7.56 30.0 7.01

6.0 5.0 56.4 8.33 51.2 7.76 47.6 7.40 44.0 7.26 40.6 7.10 35.2 6.77 30.0 6.33

7.0 6.0 56.4 8.33 51.2 7.76 47.6 7.34 44.0 6.96 40.6 6.79 35.2 6.49 30.0 6.11

8.6 7.5 56.4 8.33 51.2 7.76 47.6 7.34 44.0 6.96 40.6 6.57 35.2 6.11 30.0 5.78

11.2 10.0 56.4 8.33 51.2 7.76 47.6 7.34 44.0 6.96 40.6 6.57 35.2 5.97 30.0 5.39

16.4 15.0 56.4 8.33 51.2 7.76 47.6 7.34 44.0 6.96 40.6 6.57 35.2 5.97 30.0 5.39

24.0 18.0 56.4 8.33 51.2 7.76 47.6 7.34 44.0 6.96 40.6 6.57 35.2 5.97 30.0 5.39

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 42.4 11.14 38.3 11.03 35.7 10.89 33.1 10.70 30.5 10.37 26.4 9.85 22.5 9.27

-14.7 -15.0 42.4 10.40 38.3 10.34 35.7 10.23 33.1 10.07 30.5 9.85 26.4 9.32 22.5 8.72

-9.6 -10.0 42.4 9.52 38.3 9.49 35.7 9.43 33.1 9.30 30.5 9.10 26.4 8.50 22.5 7.78

-4.4 -5.0 42.4 8.44 38.3 8.36 35.7 8.20 33.1 8.00 30.5 7.76 26.4 7.32 22.5 6.79

-1.8 -2.5 42.4 7.70 38.3 7.59 35.7 7.48 33.1 7.32 30.5 7.12 26.4 6.77 22.5 6.33

0.8 0.0 42.4 6.88 38.3 6.85 35.7 6.77 33.1 6.66 30.5 6.52 26.4 6.24 22.5 5.86

30% 2.8 2.0 42.4 6.77 38.3 6.33 35.7 6.24 33.1 6.16 30.5 6.05 26.4 5.83 22.5 5.50

6.0 5.0 42.4 6.77 38.3 6.33 35.7 6.02 33.1 5.72 30.5 5.42 26.4 5.25 22.5 5.01

7.0 6.0 42.4 6.77 38.3 6.33 35.7 6.02 33.1 5.72 30.5 5.42 26.4 5.06 22.5 4.84

8.6 7.5 42.4 6.77 38.3 6.33 35.7 6.02 33.1 5.72 30.5 5.42 26.4 4.98 22.5 4.62

11.2 10.0 42.4 6.77 38.3 6.33 35.7 6.02 33.1 5.72 30.5 5.42 26.4 4.98 22.5 4.54

16.4 15.0 42.4 6.77 38.3 6.33 35.7 6.02 33.1 5.72 30.5 5.42 26.4 4.98 22.5 4.54

24.0 18.0 42.4 6.77 38.3 6.33 35.7 6.02 33.1 5.72 30.5 5.42 26.4 4.98 22.5 4.54

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


40 HP (U-8MF2E8 & U-16MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 96.3 34.65 88.8 31.94 83.7 30.09 83.7 30.09 83.7 30.09 83.7 30.09 72.9 26.27

-14.7 -15.0 102.1 35.27 94.4 32.56 89.0 30.71 89.0 30.71 89.0 30.71 89.0 30.71 78.1 26.89

-9.6 -10.0 109.6 36.19 101.5 33.45 95.9 31.60 95.9 31.60 95.9 31.60 95.9 31.60 85.0 27.75

-4.4 -5.0 119.6 37.55 111.1 34.77 105.2 32.89 105.2 32.89 105.2 32.89 105.2 32.89 94.0 28.92

-1.8 -2.5 126.0 38.41 117.1 35.64 111.0 33.73 111.0 33.73 111.0 33.73 111.0 33.73 99.7 29.72

0.8 0.0 133.5 39.45 124.3 36.65 118.0 34.68 118.0 34.68 118.0 34.68 118.0 34.68 106.8 30.68

130% 2.8 2.0 139.8 40.04 131.2 37.51 124.6 35.51 124.6 35.51 124.6 35.51 124.6 35.51 111.8 30.80

6.0 5.0 150.7 40.04 144.5 38.99 136.5 36.59 136.5 36.59 136.5 36.59 131.4 33.26 111.8 27.97

7.0 6.0 155.2 40.04 146.7 38.28 136.5 35.17 136.5 35.17 136.5 35.17 131.4 32.00 111.8 26.89

8.6 7.5 161.0 40.04 146.7 35.88 136.5 32.99 136.5 32.99 136.5 32.99 131.4 30.09 111.8 25.32

11.2 10.0 161.8 36.01 146.7 32.00 136.5 29.48 136.5 29.48 136.5 29.48 131.4 27.01 111.8 22.79

16.4 15.0 161.8 28.00 146.7 25.07 136.5 23.19 136.5 23.19 136.5 23.19 131.4 21.53 111.8 18.33

24.0 18.0 161.8 23.87 146.7 21.47 136.5 19.96 136.5 19.96 136.5 19.96 131.4 18.70 111.8 16.05

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 96.5 34.31 88.9 31.63 83.8 29.85 83.8 29.85 83.8 29.85 77.7 27.60 67.3 24.33

-14.7 -15.0 102.4 34.96 94.5 32.28 89.2 30.46 89.2 30.46 89.2 30.46 83.1 28.24 72.1 24.89

-9.6 -10.0 109.9 35.88 101.6 33.20 96.0 31.35 96.0 31.35 96.0 31.35 89.9 29.14 78.2 25.66

-4.4 -5.0 119.8 37.24 111.3 34.53 105.2 32.65 105.2 32.65 105.2 32.65 99.2 30.40 86.5 26.70

-1.8 -2.5 126.1 38.13 117.2 35.39 111.0 33.45 111.0 33.45 111.0 33.45 105.0 31.20 91.7 27.44

0.8 0.0 133.6 39.15 124.3 36.37 117.9 34.43 117.9 34.43 117.9 34.43 112.0 32.16 98.3 28.27

120% 2.8 2.0 140.7 40.01 131.2 37.18 124.5 35.17 124.5 35.17 124.5 35.17 118.5 32.77 100.7 27.66

6.0 5.0 151.5 40.04 143.3 38.13 133.4 35.05 133.4 35.05 133.4 35.05 118.5 29.75 100.7 25.10

7.0 6.0 155.7 40.04 143.3 36.62 133.4 33.70 133.4 33.70 133.4 33.70 118.5 28.64 100.7 24.15

8.6 7.5 158.0 38.53 143.3 34.28 133.4 31.57 133.4 31.57 133.4 31.57 118.5 26.92 100.7 22.73

11.2 10.0 158.0 34.28 143.3 30.58 133.4 28.21 133.4 28.21 133.4 28.21 118.5 24.15 100.7 20.48

16.4 15.0 158.0 26.61 143.3 23.90 133.4 22.15 133.4 22.15 133.4 22.15 118.5 19.28 100.7 16.51

24.0 18.0 158.0 22.64 143.3 20.45 133.4 19.03 133.4 19.03 133.4 19.03 118.5 16.76 100.7 14.45

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 96.6 33.97 89.0 31.39 83.8 29.60 83.8 29.60 80.4 28.34 71.2 25.35 61.6 22.42

-14.7 -15.0 102.5 34.65 94.6 32.03 89.3 30.21 89.3 30.21 85.9 28.98 76.1 25.93 66.0 22.88

-9.6 -10.0 110.0 35.60 101.7 32.96 96.1 31.14 96.1 31.14 92.7 29.91 82.4 26.73 71.6 23.59

-4.4 -5.0 120.0 36.99 111.3 34.28 105.3 32.40 105.3 32.40 101.9 31.17 90.8 27.87 79.1 24.52

-1.8 -2.5 126.4 37.85 117.2 35.11 111.0 33.20 111.0 33.20 107.6 31.97 96.0 28.61 83.8 25.16

0.8 0.0 133.7 38.87 124.3 36.10 117.9 34.16 117.9 34.16 114.6 32.86 102.5 29.38 89.8 25.87

110% 2.8 2.0 140.7 39.64 131.1 36.81 124.5 34.83 124.5 34.83 121.4 33.66 106.0 29.14 90.2 24.70

6.0 5.0 152.4 40.04 139.8 36.44 130.2 33.57 130.2 33.57 121.9 30.71 106.0 26.46 90.2 22.42

7.0 6.0 154.3 39.27 139.8 34.99 130.2 32.25 130.2 32.25 121.9 29.54 106.0 25.47 90.2 21.56

8.6 7.5 154.3 36.71 139.8 32.77 130.2 30.21 130.2 30.21 121.9 27.72 106.0 23.93 90.2 20.30

11.2 10.0 154.3 32.62 139.8 29.17 130.2 26.95 130.2 26.95 121.9 24.79 106.0 21.50 90.2 18.30

16.4 15.0 154.3 25.26 139.8 22.76 130.2 21.13 130.2 21.13 121.9 19.62 106.0 17.16 90.2 14.78

24.0 18.0 154.3 21.44 139.8 19.43 130.2 18.14 130.2 18.14 121.9 16.97 106.0 14.94 90.2 12.97

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 96.9 33.66 89.2 31.11 83.9 29.35 78.6 27.57 73.2 25.78 64.8 23.13 56.0 20.51

-14.7 -15.0 102.7 34.34 94.7 31.75 89.4 30.00 83.8 28.21 78.0 26.36 69.2 23.65 59.9 20.94

-9.6 -10.0 110.2 35.33 101.9 32.71 96.1 30.92 90.3 29.08 84.2 27.20 74.8 24.36 65.0 21.53

-4.4 -5.0 120.1 36.71 111.4 34.03 105.3 32.19 99.1 30.28 92.5 28.34 82.4 25.38 71.8 22.39

-1.8 -2.5 126.5 37.58 117.3 34.87 111.0 32.99 104.5 31.05 97.7 29.04 87.1 26.03 75.9 22.95

0.8 0.0 133.9 38.56 124.3 35.79 117.7 33.82 111.0 31.85 103.9 29.78 93.0 26.70 80.0 23.07

100% 2.8 2.0 140.8 39.24 131.1 36.44 124.3 34.50 117.3 32.52 108.2 29.78 94.1 25.72 80.0 21.90

6.0 5.0 150.5 38.99 136.4 34.80 127.0 32.12 117.6 29.54 108.2 27.01 94.1 23.38 80.0 19.87

7.0 6.0 150.5 37.39 136.4 33.42 127.0 30.80 117.6 28.37 108.2 25.96 94.1 22.48 80.0 19.13

8.6 7.5 150.5 34.96 136.4 31.26 127.0 28.89 117.6 26.61 108.2 24.36 94.1 21.13 80.0 18.02

11.2 10.0 150.5 30.98 136.4 27.81 127.0 25.75 117.6 23.75 108.2 21.81 94.1 19.00 80.0 16.26

16.4 15.0 150.5 23.93 136.4 21.65 127.0 20.14 117.6 18.70 108.2 17.28 94.1 15.18 80.0 13.15

9 24.0 18.0 150.5 20.27 136.4 18.45 127.0 17.28 117.6 16.11 108.2 14.94 94.1 13.24 80.0 11.58
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


40 HP (U-8MF2E8 & U-16MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 97.7 32.52 89.8 30.12 84.5 28.52 79.0 26.86 73.4 25.23 64.8 22.76 56.0 20.33

-14.7 -15.0 103.6 33.29 95.4 30.86 89.8 29.20 84.1 27.50 78.2 25.81 69.2 23.25 59.8 20.73

-9.6 -10.0 111.1 34.31 102.5 31.82 96.6 30.12 90.6 28.37 84.3 26.61 74.7 23.93 64.8 21.25

-4.4 -5.0 121.0 35.70 111.9 33.11 105.5 31.32 99.1 29.51 92.3 27.66 81.9 24.82 71.1 21.99

-1.8 -2.5 127.1 36.50 117.6 33.85 111.0 32.00 104.3 30.12 97.3 28.21 84.7 24.70 72.0 21.31

0.8 0.0 134.4 37.14 122.8 33.82 114.3 31.35 105.8 28.95 97.4 26.64 84.7 23.32 72.0 20.14

90% 2.8 2.0 135.5 35.45 122.8 31.94 114.3 29.63 105.8 27.41 97.4 25.26 84.7 22.11 72.0 19.07

6.0 5.0 135.5 31.82 122.8 28.74 114.3 26.73 105.8 24.76 97.4 22.82 84.7 19.99 72.0 17.22

7.0 6.0 135.5 30.46 122.8 27.54 114.3 25.63 105.8 23.78 97.4 21.93 84.7 19.22 72.0 16.54

8.6 7.5 135.5 28.37 122.8 25.69 114.3 23.93 105.8 22.24 97.4 20.54 84.7 18.05 72.0 15.58

11.2 10.0 135.5 25.04 122.8 22.76 114.3 21.28 105.8 19.80 97.4 18.36 84.7 16.20 72.0 14.08

16.4 15.0 135.5 19.10 122.8 17.56 114.3 16.51 105.8 15.49 97.4 14.45 84.7 12.91 72.0 11.37

24.0 18.0 135.5 17.93 122.8 16.45 114.3 15.46 105.8 14.48 97.4 13.49 84.7 12.01 72.0 10.53

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 98.9 31.69 90.8 29.44 85.2 27.94 79.6 26.43 73.9 24.89 65.2 22.64 56.1 20.39

-14.7 -15.0 104.9 32.49 96.5 30.21 90.7 28.64 84.7 27.07 78.7 25.47 69.5 23.10 59.9 20.73

-9.6 -10.0 112.5 33.57 103.5 31.20 97.4 29.57 91.2 27.90 84.7 26.24 74.9 23.72 64.0 20.91

-4.4 -5.0 120.4 34.10 109.1 30.98 101.6 28.95 94.1 26.98 86.5 25.04 75.3 22.21 64.0 19.50

-1.8 -2.5 120.4 32.31 109.1 29.38 101.6 27.47 94.1 25.63 86.5 23.78 75.3 21.13 64.0 18.54

0.8 0.0 120.4 30.34 109.1 27.63 101.6 25.84 94.1 24.12 86.5 22.39 75.3 19.90 64.0 17.46

80% 2.8 2.0 120.4 28.55 109.1 26.06 101.6 24.39 94.1 22.79 86.5 21.19 75.3 18.82 64.0 16.51

6.0 5.0 120.4 25.50 109.1 23.35 101.6 21.93 94.1 20.48 86.5 19.07 75.3 16.91 64.0 14.75

7.0 6.0 120.4 24.36 109.1 22.33 101.6 20.97 94.1 19.62 86.5 18.26 75.3 16.23 64.0 14.17

8.6 7.5 120.4 22.61 109.1 20.79 101.6 19.56 94.1 18.33 86.5 17.09 75.3 15.25 64.0 13.37

11.2 10.0 120.4 19.87 109.1 18.36 101.6 17.31 94.1 16.29 86.5 15.25 75.3 13.68 64.0 12.04

16.4 15.0 120.4 16.17 109.1 14.85 101.6 13.98 94.1 13.12 86.5 12.23 75.3 10.93 64.0 9.73

24.0 18.0 120.4 16.17 109.1 14.85 101.6 13.98 94.1 13.12 86.5 12.23 75.3 10.93 64.0 9.61

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 101.1 31.35 92.6 29.26 86.9 27.87 81.0 26.46 75.2 25.04 65.9 22.82 56.0 20.48

-14.7 -15.0 105.4 31.54 95.5 29.01 88.9 27.32 82.3 25.66 75.7 24.05 65.9 21.68 56.0 19.34

-9.6 -10.0 105.4 29.69 95.5 27.35 88.9 25.81 82.3 24.27 75.7 22.76 65.9 20.48 56.0 18.20

-4.4 -5.0 105.4 27.17 95.5 25.07 88.9 23.65 82.3 22.30 75.7 20.91 65.9 18.88 56.0 16.88

-1.8 -2.5 105.4 25.69 95.5 23.72 88.9 22.42 82.3 21.13 75.7 19.84 65.9 17.89 56.0 15.99

0.8 0.0 105.4 24.02 95.5 22.21 88.9 21.04 82.3 19.84 75.7 18.63 65.9 16.82 56.0 15.00

70% 2.8 2.0 105.4 22.55 95.5 20.91 88.9 19.80 82.3 18.70 75.7 17.56 65.9 15.86 56.0 13.98

6.0 5.0 105.4 20.05 95.5 18.63 88.9 17.68 82.3 16.69 75.7 15.68 65.9 14.11 56.0 12.50

7.0 6.0 105.4 19.10 95.5 17.80 88.9 16.88 82.3 15.95 75.7 15.03 65.9 13.55 56.0 12.01

8.6 7.5 105.4 17.68 95.5 16.51 88.9 15.71 82.3 14.91 75.7 14.04 65.9 12.72 56.0 11.33

11.2 10.0 105.4 15.43 95.5 14.51 88.9 13.86 82.3 13.21 75.7 12.50 65.9 11.40 56.0 10.23

16.4 15.0 105.4 14.41 95.5 13.27 88.9 12.50 82.3 11.73 75.7 10.96 65.9 9.83 56.0 8.69

24.0 18.0 105.4 14.41 95.5 13.27 88.9 12.50 82.3 11.73 75.7 10.96 65.9 9.83 56.0 8.69

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 90.3 26.55 81.8 24.76 76.2 23.56 70.6 22.36 64.9 21.19 56.4 19.43 48.0 17.68

-14.7 -15.0 90.3 25.10 81.8 23.50 76.2 22.45 70.6 21.38 64.9 20.20 56.4 18.45 48.0 16.69

-9.6 -10.0 90.3 23.38 81.8 21.90 76.2 20.94 70.6 19.96 64.9 18.97 56.4 17.43 48.0 15.71

-4.4 -5.0 90.3 21.25 81.8 19.99 76.2 19.10 70.6 18.23 64.9 17.31 56.4 15.92 48.0 14.45

-1.8 -2.5 90.3 20.02 81.8 18.85 76.2 18.05 70.6 17.22 64.9 16.35 56.4 15.06 48.0 13.64

0.8 0.0 90.3 18.66 81.8 17.59 76.2 16.85 70.6 16.11 64.9 15.31 56.4 14.08 48.0 12.57

60% 2.8 2.0 90.3 17.46 81.8 16.48 76.2 15.80 70.6 15.12 64.9 14.38 56.4 13.09 48.0 11.70

6.0 5.0 90.3 15.40 81.8 14.60 76.2 13.98 70.6 13.37 64.9 12.69 56.4 11.61 48.0 10.44

7.0 6.0 90.3 14.63 81.8 13.89 76.2 13.34 70.6 12.78 64.9 12.14 56.4 11.15 48.0 10.04

8.6 7.5 90.3 13.49 81.8 12.87 76.2 12.41 70.6 11.89 64.9 11.37 56.4 10.47 48.0 9.49

11.2 10.0 90.3 12.66 81.8 11.67 76.2 11.03 70.6 10.50 64.9 10.10 56.4 9.36 48.0 8.56

16.4 15.0 90.3 12.66 81.8 11.67 76.2 11.03 70.6 10.38 64.9 9.70 56.4 8.75 48.0 7.76

24.0 18.0 90.3 12.66 81.8 11.67 76.2 11.03 70.6 10.38 64.9 9.70 56.4 8.75 48.0 7.76

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


40 HP (U-8MF2E8 & U-16MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 75.3 20.79 68.2 19.87 63.5 19.19 58.8 18.45 54.1 17.62 47.0 16.35 40.0 15.09

-14.7 -15.0 75.3 19.56 68.2 18.70 63.5 18.11 58.8 17.46 54.1 16.79 47.0 15.55 40.0 14.23

-9.6 -10.0 75.3 18.11 68.2 17.37 63.5 16.82 58.8 16.23 54.1 15.62 47.0 14.60 40.0 13.37

-4.4 -5.0 75.3 16.35 68.2 15.71 63.5 15.25 58.8 14.72 54.1 14.20 47.0 13.27 40.0 12.14

-1.8 -2.5 75.3 15.34 68.2 14.75 63.5 14.32 58.8 13.86 54.1 13.34 47.0 12.47 40.0 11.21

0.8 0.0 75.3 14.23 68.2 13.71 63.5 13.31 58.8 12.91 54.1 12.38 47.0 11.40 40.0 10.29

50% 2.8 2.0 75.3 13.24 68.2 12.78 63.5 12.44 58.8 11.95 54.1 11.43 47.0 10.56 40.0 9.61

6.0 5.0 75.3 11.52 68.2 11.15 63.5 10.84 58.8 10.47 54.1 10.07 47.0 9.39 40.0 8.59

7.0 6.0 75.3 10.93 68.2 10.60 63.5 10.32 58.8 10.01 54.1 9.64 47.0 9.02 40.0 8.29

8.6 7.5 75.3 10.93 68.2 10.10 63.5 9.58 58.8 9.30 54.1 9.02 47.0 8.47 40.0 7.82

11.2 10.0 75.3 10.93 68.2 10.10 63.5 9.55 58.8 8.99 54.1 8.47 47.0 7.64 40.0 7.08

16.4 15.0 75.3 10.93 68.2 10.10 63.5 9.55 58.8 8.99 54.1 8.47 47.0 7.64 40.0 6.81

24.0 18.0 75.3 10.93 68.2 10.10 63.5 9.55 58.8 8.99 54.1 8.47 47.0 7.64 40.0 6.81

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 60.2 16.11 54.6 15.71 50.8 15.37 47.0 14.97 43.3 14.41 37.6 13.55 32.0 12.63

-14.7 -15.0 60.2 15.09 54.6 14.75 50.8 14.45 47.0 14.11 43.3 13.71 37.6 12.84 32.0 11.89

-9.6 -10.0 60.2 13.89 54.6 13.61 50.8 13.37 47.0 13.06 43.3 12.69 37.6 12.04 32.0 11.12

-4.4 -5.0 60.2 12.44 54.6 12.20 50.8 12.01 47.0 11.77 43.3 11.46 37.6 10.66 32.0 9.67

-1.8 -2.5 60.2 11.58 54.6 11.40 50.8 11.24 47.0 10.96 43.3 10.53 37.6 9.79 32.0 8.96

0.8 0.0 60.2 10.66 54.6 10.50 50.8 10.23 47.0 9.95 43.3 9.58 37.6 8.96 32.0 8.25

40% 2.8 2.0 60.2 9.79 54.6 9.58 50.8 9.39 47.0 9.15 43.3 8.87 37.6 8.35 32.0 7.73

6.0 5.0 60.2 9.18 54.6 8.50 50.8 8.16 47.0 8.01 43.3 7.82 37.6 7.42 32.0 6.96

7.0 6.0 60.2 9.18 54.6 8.50 50.8 8.07 47.0 7.67 43.3 7.48 37.6 7.15 32.0 6.71

8.6 7.5 60.2 9.18 54.6 8.50 50.8 8.07 47.0 7.64 43.3 7.21 37.6 6.75 32.0 6.34

11.2 10.0 60.2 9.18 54.6 8.50 50.8 8.07 47.0 7.64 43.3 7.21 37.6 6.53 32.0 5.88

16.4 15.0 60.2 9.18 54.6 8.50 50.8 8.07 47.0 7.64 43.3 7.21 37.6 6.53 32.0 5.88

24.0 18.0 60.2 9.18 54.6 8.50 50.8 8.07 47.0 7.64 43.3 7.21 37.6 6.53 32.0 5.88

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 45.2 12.32 40.9 12.20 38.1 12.04 35.3 11.83 32.5 11.43 28.2 10.84 24.0 10.23

-14.7 -15.0 45.2 11.49 40.9 11.43 38.1 11.30 35.3 11.12 32.5 10.87 28.2 10.26 24.0 9.58

-9.6 -10.0 45.2 10.53 40.9 10.50 38.1 10.41 35.3 10.26 32.5 10.04 28.2 9.36 24.0 8.56

-4.4 -5.0 45.2 9.33 40.9 9.24 38.1 9.06 35.3 8.84 32.5 8.56 28.2 8.07 24.0 7.48

-1.8 -2.5 45.2 8.50 40.9 8.38 38.1 8.25 35.3 8.07 32.5 7.85 28.2 7.45 24.0 6.93

0.8 0.0 45.2 7.58 40.9 7.55 38.1 7.45 35.3 7.33 32.5 7.18 28.2 6.87 24.0 6.44

30% 2.8 2.0 45.2 7.42 40.9 6.93 38.1 6.87 35.3 6.78 32.5 6.65 28.2 6.41 24.0 6.04

6.0 5.0 45.2 7.42 40.9 6.93 38.1 6.59 35.3 6.28 32.5 5.94 28.2 5.76 24.0 5.48

7.0 6.0 45.2 7.42 40.9 6.93 38.1 6.59 35.3 6.28 32.5 5.94 28.2 5.54 24.0 5.30

8.6 7.5 45.2 7.42 40.9 6.93 38.1 6.59 35.3 6.28 32.5 5.94 28.2 5.45 24.0 5.05

11.2 10.0 45.2 7.42 40.9 6.93 38.1 6.59 35.3 6.28 32.5 5.94 28.2 5.45 24.0 4.96

16.4 15.0 45.2 7.42 40.9 6.93 38.1 6.59 35.3 6.28 32.5 5.94 28.2 5.45 24.0 4.96

24.0 18.0 45.2 7.42 40.9 6.93 38.1 6.59 35.3 6.28 32.5 5.94 28.2 5.45 24.0 4.96

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


42 HP (U-14MF2E8 & U-14MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 101.0 34.01 93.2 31.32 87.8 29.51 87.8 29.51 87.8 29.51 87.8 29.51 76.8 25.63

-14.7 -15.0 107.1 34.51 99.0 31.88 93.5 30.07 93.5 30.07 93.5 30.07 93.5 30.07 82.4 26.23

-9.6 -10.0 114.8 35.34 106.5 32.71 100.7 30.90 100.7 30.90 100.7 30.90 100.7 30.90 89.6 27.05

-4.4 -5.0 125.4 36.62 116.6 33.95 110.5 32.12 110.5 32.12 110.5 32.12 110.5 32.12 99.3 28.27

-1.8 -2.5 132.1 37.44 123.2 34.78 116.8 32.92 116.8 32.92 116.8 32.92 116.8 32.92 105.5 29.07

0.8 0.0 140.2 38.45 130.8 35.76 124.2 33.89 124.2 33.89 124.2 33.89 124.2 33.89 113.1 30.07

130% 2.8 2.0 145.6 38.48 138.1 36.67 131.3 34.78 131.3 34.78 131.3 34.78 131.3 34.78 116.2 29.48

6.0 5.0 156.9 38.48 152.1 38.10 141.9 35.11 141.9 35.11 141.9 35.11 136.6 31.88 116.2 26.82

7.0 6.0 161.7 38.48 152.5 36.73 141.9 33.74 141.9 33.74 141.9 33.74 136.6 30.70 116.2 25.84

8.6 7.5 167.5 38.48 152.5 34.42 141.9 31.67 141.9 31.67 141.9 31.67 136.6 28.86 116.2 24.33

11.2 10.0 168.2 34.54 152.5 30.75 141.9 28.33 141.9 28.33 141.9 28.33 136.6 25.93 116.2 21.96

16.4 15.0 168.2 26.91 152.5 24.09 141.9 22.32 141.9 22.32 141.9 22.32 136.6 20.72 116.2 17.70

24.0 18.0 168.2 22.94 152.5 20.66 141.9 19.21 141.9 19.21 141.9 19.21 136.6 18.03 116.2 15.54

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 101.1 33.66 93.3 31.02 87.9 29.24 87.9 29.24 87.9 29.24 81.7 26.97 70.9 23.74

-14.7 -15.0 107.2 34.19 99.1 31.61 93.6 29.81 93.6 29.81 93.6 29.81 87.4 27.56 76.0 24.27

-9.6 -10.0 115.1 35.05 106.7 32.44 100.8 30.67 100.8 30.67 100.8 30.67 94.8 28.45 82.6 25.04

-4.4 -5.0 125.7 36.32 116.7 33.68 110.6 31.88 110.6 31.88 110.6 31.88 104.7 29.69 91.5 26.14

-1.8 -2.5 132.4 37.18 123.2 34.51 116.8 32.68 116.8 32.68 116.8 32.68 110.9 30.52 97.0 26.85

0.8 0.0 140.3 38.15 130.8 35.49 124.2 33.63 124.2 33.63 124.2 33.63 118.4 31.49 104.0 27.71

120% 2.8 2.0 146.4 38.48 138.1 36.35 131.2 34.45 131.2 34.45 131.2 34.45 123.2 31.41 104.7 26.52

6.0 5.0 157.9 38.48 148.9 36.59 138.6 33.66 138.6 33.66 138.6 33.66 123.2 28.56 104.7 24.15

7.0 6.0 162.0 38.48 148.9 35.14 138.6 32.35 138.6 32.35 138.6 32.35 123.2 27.50 104.7 23.24

8.6 7.5 164.2 37.00 148.9 32.92 138.6 30.34 138.6 30.34 138.6 30.34 123.2 25.87 104.7 21.90

11.2 10.0 164.2 32.92 148.9 29.36 138.6 27.11 138.6 27.11 138.6 27.11 123.2 23.24 104.7 19.77

16.4 15.0 164.2 25.57 148.9 23.00 138.6 21.34 138.6 21.34 138.6 21.34 123.2 18.59 104.7 15.98

24.0 18.0 164.2 21.76 148.9 19.68 138.6 18.35 138.6 18.35 138.6 18.35 123.2 16.19 104.7 14.03

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 101.4 33.33 93.5 30.75 88.0 28.98 88.0 28.98 84.5 27.71 75.0 24.78 64.9 21.87

-14.7 -15.0 107.4 33.89 99.3 31.32 93.7 29.57 93.7 29.57 90.2 28.33 80.1 25.34 69.6 22.38

-9.6 -10.0 115.4 34.75 106.8 32.18 101.0 30.43 101.0 30.43 97.5 29.22 86.9 26.14 75.6 23.06

-4.4 -5.0 125.8 36.05 116.8 33.45 110.6 31.64 110.6 31.64 107.3 30.43 95.7 27.23 83.6 24.01

-1.8 -2.5 132.5 36.88 123.3 34.25 116.8 32.44 116.8 32.44 113.5 31.23 101.4 27.97 88.7 24.66

0.8 0.0 140.4 37.86 130.8 35.19 124.1 33.36 124.1 33.36 120.9 32.18 108.4 28.80 93.7 24.98

110% 2.8 2.0 147.3 38.48 138.1 35.99 131.1 34.10 131.1 34.10 126.7 32.50 110.2 27.97 93.7 23.74

6.0 5.0 158.5 38.48 145.3 34.99 135.3 32.23 135.3 32.23 126.7 29.48 110.2 25.46 93.7 21.61

7.0 6.0 160.4 37.71 145.3 33.60 135.3 30.99 135.3 30.99 126.7 28.36 110.2 24.51 93.7 20.81

8.6 7.5 160.4 35.25 145.3 31.46 135.3 29.04 135.3 29.04 126.7 26.64 110.2 23.03 93.7 19.60

11.2 10.0 160.4 31.35 145.3 28.03 135.3 25.93 135.3 25.93 126.7 23.86 110.2 20.72 93.7 17.73

16.4 15.0 160.4 24.27 145.3 21.90 135.3 20.36 135.3 20.36 126.7 18.94 110.2 16.61 93.7 14.36

24.0 18.0 160.4 20.63 145.3 18.74 135.3 17.49 135.3 17.49 126.7 16.40 110.2 14.50 93.7 12.64

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 101.5 32.97 93.6 30.46 88.2 28.74 82.6 27.00 77.0 25.25 68.1 22.61 59.0 20.04

-14.7 -15.0 107.7 33.57 99.5 31.05 93.9 29.33 88.0 27.59 82.1 25.81 72.9 23.12 63.2 20.48

-9.6 -10.0 115.5 34.45 106.9 31.91 101.0 30.19 94.9 28.42 88.7 26.61 78.8 23.83 68.6 21.08

-4.4 -5.0 126.1 35.76 117.0 33.18 110.7 31.41 104.1 29.57 97.4 27.71 87.0 24.83 75.8 21.93

-1.8 -2.5 132.7 36.59 123.3 33.98 116.8 32.18 110.1 30.31 103.1 28.42 92.0 25.49 80.4 22.50

0.8 0.0 140.6 37.56 130.8 34.93 124.1 33.09 117.0 31.17 109.7 29.19 97.8 26.05 83.2 22.20

100% 2.8 2.0 148.0 38.33 137.9 35.64 130.9 33.77 122.2 31.32 112.5 28.62 97.8 24.75 83.2 21.10

6.0 5.0 156.4 37.44 141.8 33.45 132.0 30.87 122.2 28.39 112.5 25.99 97.8 22.53 83.2 19.21

7.0 6.0 156.4 35.90 141.8 32.09 132.0 29.60 122.2 27.29 112.5 25.01 97.8 21.67 83.2 18.50

8.6 7.5 156.4 33.57 141.8 30.04 132.0 27.79 122.2 25.60 112.5 23.47 97.8 20.39 83.2 17.46

11.2 10.0 156.4 29.81 141.8 26.76 132.0 24.80 122.2 22.88 112.5 21.05 97.8 18.38 83.2 15.78

16.4 15.0 156.4 23.03 141.8 20.87 132.0 19.45 122.2 18.09 112.5 16.72 97.8 14.77 83.2 12.85

9 24.0 18.0 156.4 19.54 141.8 17.82 132.0 16.69 122.2 15.60 112.5 14.50 97.8 12.91 83.2 11.34
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


42 HP (U-14MF2E8 & U-14MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 102.4 31.73 94.2 29.42 88.6 27.82 82.9 26.20 77.1 24.60 68.1 22.17 58.9 19.83

-14.7 -15.0 108.6 32.44 100.1 30.07 94.2 28.45 88.3 26.82 82.2 25.16 72.7 22.67 63.0 20.22

-9.6 -10.0 116.6 33.39 107.6 30.99 101.5 29.33 95.2 27.65 88.7 25.93 78.7 23.32 68.2 20.75

-4.4 -5.0 127.0 34.69 117.5 32.23 110.9 30.52 104.1 28.74 97.2 26.97 86.3 24.24 74.8 21.40

-1.8 -2.5 133.5 35.52 123.6 33.00 116.8 31.23 109.7 29.42 101.2 27.14 88.0 23.74 74.8 20.51

0.8 0.0 140.8 36.11 127.6 32.50 118.8 30.13 110.0 27.85 101.2 25.63 88.0 22.44 74.8 19.42

90% 2.8 2.0 140.8 34.07 127.6 30.70 118.8 28.50 110.0 26.37 101.2 24.30 88.0 21.31 74.8 18.41

6.0 5.0 140.8 30.61 127.6 27.65 118.8 25.75 110.0 23.86 101.2 22.02 88.0 19.33 74.8 16.69

7.0 6.0 140.8 29.30 127.6 26.52 118.8 24.69 110.0 22.91 101.2 21.16 88.0 18.59 74.8 16.07

8.6 7.5 140.8 27.32 127.6 24.75 118.8 23.09 110.0 21.46 101.2 19.83 88.0 17.46 74.8 15.16

11.2 10.0 140.8 24.12 127.6 21.96 118.8 20.54 110.0 19.15 101.2 17.76 88.0 15.72 74.8 13.70

16.4 15.0 140.8 18.47 127.6 16.99 118.8 16.01 110.0 15.04 101.2 14.06 88.0 12.61 74.8 11.16

24.0 18.0 140.8 17.32 127.6 15.92 118.8 15.01 110.0 14.09 101.2 13.14 88.0 11.75 74.8 10.39

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 103.5 30.78 95.0 28.62 89.4 27.14 83.6 25.66 77.5 24.15 68.4 21.96 59.0 19.77

-14.7 -15.0 109.8 31.55 101.0 29.30 95.0 27.79 88.8 26.26 82.6 24.72 73.0 22.41 63.0 20.13

-9.6 -10.0 117.7 32.53 108.5 30.25 102.0 28.68 95.6 27.08 89.0 25.46 78.3 22.88 66.5 20.07

-4.4 -5.0 125.1 32.77 113.4 29.78 105.6 27.82 97.8 25.93 89.9 24.06 78.3 21.37 66.5 18.77

-1.8 -2.5 125.1 31.08 113.4 28.27 105.6 26.43 97.8 24.66 89.9 22.88 78.3 20.34 66.5 17.85

0.8 0.0 125.1 29.19 113.4 26.61 105.6 24.89 97.8 23.24 89.9 21.58 78.3 19.18 66.5 16.84

80% 2.8 2.0 125.1 27.50 113.4 25.10 105.6 23.53 97.8 21.96 89.9 20.42 78.3 18.17 66.5 15.95

6.0 5.0 125.1 24.60 113.4 22.53 105.6 21.16 97.8 19.80 89.9 18.44 78.3 16.43 66.5 14.36

7.0 6.0 125.1 23.50 113.4 21.58 105.6 20.28 97.8 19.00 89.9 17.70 78.3 15.78 66.5 13.82

8.6 7.5 125.1 21.84 113.4 20.10 105.6 18.94 97.8 17.76 89.9 16.61 78.3 14.83 66.5 13.05

11.2 10.0 125.1 19.21 113.4 17.79 105.6 16.81 97.8 15.84 89.9 14.83 78.3 13.35 66.5 11.81

16.4 15.0 125.1 15.66 113.4 14.44 105.6 13.62 97.8 12.79 89.9 11.96 78.3 10.74 66.5 9.62

24.0 18.0 125.1 15.66 113.4 14.44 105.6 13.62 97.8 12.79 89.9 11.96 78.3 10.74 66.5 9.50

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 105.5 30.25 96.6 28.24 90.7 26.88 84.6 25.49 78.5 24.12 68.5 21.84 58.2 19.60

-14.7 -15.0 109.6 30.25 99.3 27.82 92.4 26.20 85.5 24.60 78.7 23.06 68.5 20.78 58.2 18.56

-9.6 -10.0 109.6 28.53 99.3 26.28 92.4 24.78 85.5 23.32 78.7 21.87 68.5 19.65 58.2 17.49

-4.4 -5.0 109.6 26.17 99.3 24.12 92.4 22.79 85.5 21.46 78.7 20.13 68.5 18.17 58.2 16.25

-1.8 -2.5 109.6 24.78 99.3 22.85 92.4 21.61 85.5 20.36 78.7 19.12 68.5 17.29 58.2 15.42

0.8 0.0 109.6 23.18 99.3 21.46 92.4 20.31 85.5 19.15 78.7 18.00 68.5 16.28 58.2 14.53

70% 2.8 2.0 109.6 21.79 99.3 20.19 92.4 19.15 85.5 18.09 78.7 16.99 68.5 15.39 58.2 13.65

6.0 5.0 109.6 19.42 99.3 18.06 92.4 17.14 85.5 16.22 78.7 15.27 68.5 13.76 58.2 12.22

7.0 6.0 109.6 18.53 99.3 17.26 92.4 16.40 85.5 15.54 78.7 14.62 68.5 13.23 58.2 11.78

8.6 7.5 109.6 17.17 99.3 16.07 92.4 15.30 85.5 14.50 78.7 13.70 68.5 12.43 58.2 11.13

11.2 10.0 109.6 15.01 99.3 14.15 92.4 13.53 85.5 12.91 78.7 12.25 68.5 11.19 58.2 10.09

16.4 15.0 109.6 14.03 99.3 12.94 92.4 12.22 85.5 11.51 78.7 10.77 68.5 9.71 58.2 8.64

24.0 18.0 109.6 14.03 99.3 12.94 92.4 12.22 85.5 11.51 78.7 10.77 68.5 9.71 58.2 8.64

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 93.9 25.49 85.0 23.77 79.2 22.58 73.4 21.43 67.5 20.31 58.6 18.62 49.9 16.96

-14.7 -15.0 93.9 24.12 85.0 22.58 79.2 21.55 73.4 20.51 67.5 19.39 58.6 17.73 49.9 16.07

-9.6 -10.0 93.9 22.50 85.0 21.08 79.2 20.13 73.4 19.18 67.5 18.23 58.6 16.75 49.9 15.16

-4.4 -5.0 93.9 20.51 85.0 19.27 79.2 18.44 73.4 17.58 67.5 16.69 58.6 15.36 49.9 13.97

-1.8 -2.5 93.9 19.36 85.0 18.20 79.2 17.43 73.4 16.64 67.5 15.84 58.6 14.56 49.9 13.23

0.8 0.0 93.9 18.06 85.0 17.05 79.2 16.34 73.4 15.60 67.5 14.86 58.6 13.68 49.9 12.31

60% 2.8 2.0 93.9 16.93 85.0 16.01 79.2 15.36 73.4 14.68 67.5 13.97 58.6 12.82 49.9 11.48

6.0 5.0 93.9 15.01 85.0 14.24 79.2 13.68 73.4 13.05 67.5 12.43 58.6 11.40 49.9 10.30

7.0 6.0 93.9 14.30 85.0 13.59 79.2 13.05 73.4 12.49 67.5 11.93 58.6 10.95 49.9 9.95

8.6 7.5 93.9 13.20 85.0 12.61 79.2 12.17 73.4 11.69 67.5 11.16 58.6 10.33 49.9 9.38

11.2 10.0 93.9 12.37 85.0 11.46 79.2 10.83 73.4 10.36 67.5 9.98 58.6 9.29 49.9 8.52

16.4 15.0 93.9 12.37 85.0 11.46 79.2 10.83 73.4 10.21 67.5 9.62 58.6 8.67 49.9 7.76

24.0 18.0 93.9 12.37 85.0 11.46 79.2 10.83 73.4 10.21 67.5 9.62 58.6 8.67 49.9 7.76

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


42 HP (U-14MF2E8 & U-14MF2E8 & U-14MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 78.3 19.95 70.9 19.06 66.0 18.41 61.1 17.70 56.2 16.93 48.8 15.75 41.6 14.53

-14.7 -15.0 78.3 18.83 70.9 18.00 66.0 17.40 61.1 16.78 56.2 16.13 48.8 14.98 41.6 13.73

-9.6 -10.0 78.3 17.46 70.9 16.72 66.0 16.22 61.1 15.66 56.2 15.07 48.8 14.09 41.6 12.96

-4.4 -5.0 78.3 15.84 70.9 15.21 66.0 14.74 61.1 14.27 56.2 13.73 48.8 12.88 41.6 11.90

-1.8 -2.5 78.3 14.89 70.9 14.33 66.0 13.91 61.1 13.44 56.2 12.96 48.8 12.17 41.6 11.01

0.8 0.0 78.3 13.85 70.9 13.35 66.0 12.96 61.1 12.55 56.2 12.11 48.8 11.22 41.6 10.18

50% 2.8 2.0 78.3 12.94 70.9 12.49 66.0 12.14 61.1 11.75 56.2 11.25 48.8 10.42 41.6 9.50

6.0 5.0 78.3 11.34 70.9 10.98 66.0 10.69 61.1 10.33 56.2 9.98 48.8 9.32 41.6 8.55

7.0 6.0 78.3 10.77 70.9 10.45 66.0 10.18 61.1 9.89 56.2 9.56 48.8 8.97 41.6 8.26

8.6 7.5 78.3 10.74 70.9 9.98 66.0 9.50 61.1 9.24 56.2 8.94 48.8 8.44 41.6 7.84

11.2 10.0 78.3 10.74 70.9 9.98 66.0 9.44 61.1 8.94 56.2 8.44 48.8 7.67 41.6 7.13

16.4 15.0 78.3 10.74 70.9 9.98 66.0 9.44 61.1 8.94 56.2 8.44 48.8 7.67 41.6 6.87

24.0 18.0 78.3 10.74 70.9 9.98 66.0 9.44 61.1 8.94 56.2 8.44 48.8 7.67 41.6 6.87

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 62.6 15.51 56.8 15.10 52.8 14.80 48.8 14.42 45.0 13.91 39.1 13.11 33.3 12.22

-14.7 -15.0 62.6 14.56 56.8 14.21 52.8 13.94 48.8 13.62 45.0 13.23 39.1 12.46 33.3 11.57

-9.6 -10.0 62.6 13.44 56.8 13.17 52.8 12.94 48.8 12.64 45.0 12.31 39.1 11.69 33.3 10.89

-4.4 -5.0 62.6 12.11 56.8 11.87 52.8 11.69 48.8 11.46 45.0 11.16 39.1 10.51 33.3 9.59

-1.8 -2.5 62.6 11.31 56.8 11.13 52.8 10.98 48.8 10.74 45.0 10.39 39.1 9.71 33.3 8.91

0.8 0.0 62.6 10.48 56.8 10.33 52.8 10.12 48.8 9.83 45.0 9.50 39.1 8.91 33.3 8.26

40% 2.8 2.0 62.6 9.71 56.8 9.50 52.8 9.32 48.8 9.09 45.0 8.82 39.1 8.32 33.3 7.73

6.0 5.0 62.6 9.09 56.8 8.47 52.8 8.17 48.8 8.02 45.0 7.84 39.1 7.46 33.3 7.02

7.0 6.0 62.6 9.09 56.8 8.47 52.8 8.05 48.8 7.70 45.0 7.52 39.1 7.19 33.3 6.78

8.6 7.5 62.6 9.09 56.8 8.47 52.8 8.05 48.8 7.67 45.0 7.25 39.1 6.81 33.3 6.45

11.2 10.0 62.6 9.09 56.8 8.47 52.8 8.05 48.8 7.67 45.0 7.25 39.1 6.63 33.3 6.01

16.4 15.0 62.6 9.09 56.8 8.47 52.8 8.05 48.8 7.67 45.0 7.25 39.1 6.63 33.3 6.01

24.0 18.0 62.6 9.09 56.8 8.47 52.8 8.05 48.8 7.67 45.0 7.25 39.1 6.63 33.3 6.01

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 47.0 11.93 42.5 11.81 39.6 11.69 36.7 11.48 33.8 11.16 29.3 10.60 24.9 9.98

-14.7 -15.0 47.0 11.16 42.5 11.10 39.6 10.98 36.7 10.80 33.8 10.60 29.3 10.06 24.9 9.41

-9.6 -10.0 47.0 10.27 42.5 10.24 39.6 10.15 36.7 10.03 33.8 9.83 29.3 9.26 24.9 8.52

-4.4 -5.0 47.0 9.18 42.5 9.18 39.6 9.00 36.7 8.79 33.8 8.52 29.3 8.05 24.9 7.49

-1.8 -2.5 47.0 8.50 42.5 8.38 39.6 8.23 36.7 8.08 33.8 7.87 29.3 7.49 24.9 7.02

0.8 0.0 47.0 7.61 42.5 7.58 39.6 7.49 36.7 7.40 33.8 7.22 29.3 6.93 24.9 6.51

30% 2.8 2.0 47.0 7.46 42.5 6.99 39.6 6.93 36.7 6.87 33.8 6.75 29.3 6.48 24.9 6.16

6.0 5.0 47.0 7.46 42.5 6.99 39.6 6.69 36.7 6.36 33.8 6.07 29.3 5.89 24.9 5.62

7.0 6.0 47.0 7.46 42.5 6.99 39.6 6.69 36.7 6.36 33.8 6.07 29.3 5.68 24.9 5.48

8.6 7.5 47.0 7.46 42.5 6.99 39.6 6.69 36.7 6.36 33.8 6.07 29.3 5.59 24.9 5.21

11.2 10.0 47.0 7.46 42.5 6.99 39.6 6.69 36.7 6.36 33.8 6.07 29.3 5.59 24.9 5.12

16.4 15.0 47.0 7.46 42.5 6.99 39.6 6.69 36.7 6.36 33.8 6.07 29.3 5.59 24.9 5.12

24.0 18.0 47.0 7.46 42.5 6.99 39.6 6.69 36.7 6.36 33.8 6.07 29.3 5.59 24.9 5.12

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


44 HP (U-14MF2E8 & U-14MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 104.5 36.37 96.5 33.48 90.9 31.52 90.9 31.52 90.9 31.52 90.9 31.52 79.5 27.35

-14.7 -15.0 110.8 36.95 102.5 34.09 96.7 32.13 96.7 32.13 96.7 32.13 96.7 32.13 85.3 27.96

-9.6 -10.0 119.0 37.81 110.3 34.96 104.3 33.00 104.3 33.00 104.3 33.00 104.3 33.00 92.7 28.89

-4.4 -5.0 129.9 39.13 120.8 36.31 114.4 34.31 114.4 34.31 114.4 34.31 114.4 34.31 102.8 30.17

-1.8 -2.5 136.8 40.06 127.5 37.17 120.9 35.18 120.9 35.18 120.9 35.18 120.9 35.18 109.3 31.04

0.8 0.0 145.2 41.12 135.4 38.23 128.6 36.21 128.6 36.21 128.6 36.21 128.6 36.21 117.2 32.10

130% 2.8 2.0 151.9 41.73 143.0 39.23 135.9 37.20 135.9 37.20 135.9 37.20 135.9 37.20 121.4 31.88

6.0 5.0 163.7 41.73 157.5 40.80 148.4 38.10 148.4 38.10 148.4 38.10 142.8 34.51 121.4 28.99

7.0 6.0 168.5 41.73 159.4 39.87 148.4 36.63 148.4 36.63 148.4 36.63 142.8 33.22 121.4 27.93

8.6 7.5 174.8 41.73 159.4 37.40 148.4 34.38 148.4 34.38 148.4 34.38 142.8 31.23 121.4 26.29

11.2 10.0 175.8 37.62 159.4 33.42 148.4 30.75 148.4 30.75 148.4 30.75 142.8 28.09 121.4 23.72

16.4 15.0 175.8 29.34 159.4 26.23 148.4 24.27 148.4 24.27 148.4 24.27 142.8 22.44 121.4 19.13

24.0 18.0 175.8 25.04 159.4 22.50 148.4 20.90 148.4 20.90 148.4 20.90 142.8 19.55 121.4 16.79

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 104.7 35.98 96.6 33.16 91.1 31.27 91.1 31.27 91.1 31.27 84.6 28.76 73.4 25.33

-14.7 -15.0 111.1 36.59 102.7 33.77 96.9 31.84 96.9 31.84 96.9 31.84 90.5 29.44 78.7 25.90

-9.6 -10.0 119.1 37.46 110.4 34.67 104.5 32.74 104.5 32.74 104.5 32.74 98.1 30.37 85.6 26.71

-4.4 -5.0 130.0 38.84 120.9 36.02 114.5 34.06 114.5 34.06 114.5 34.06 108.3 31.71 94.7 27.89

-1.8 -2.5 137.0 39.74 127.5 36.88 120.9 34.92 120.9 34.92 120.9 34.92 114.8 32.58 100.6 28.67

0.8 0.0 145.3 40.80 135.5 37.94 128.6 35.92 128.6 35.92 128.6 35.92 122.7 33.64 107.8 29.60

120% 2.8 2.0 152.8 41.73 143.0 38.91 135.9 36.85 135.9 36.85 135.9 36.85 128.8 33.99 109.4 28.67

6.0 5.0 164.6 41.73 155.7 39.71 144.9 36.50 144.9 36.50 144.9 36.50 128.8 30.91 109.4 26.07

7.0 6.0 169.1 41.73 155.7 38.17 144.9 35.09 144.9 35.09 144.9 35.09 128.8 29.76 109.4 25.10

8.6 7.5 171.7 40.22 155.7 35.76 144.9 32.93 144.9 32.93 144.9 32.93 128.8 27.99 109.4 23.66

11.2 10.0 171.7 35.82 155.7 31.91 144.9 29.44 144.9 29.44 144.9 29.44 128.8 25.17 109.4 21.35

16.4 15.0 171.7 27.86 155.7 25.01 144.9 23.18 144.9 23.18 144.9 23.18 128.8 20.13 109.4 17.27

24.0 18.0 171.7 23.75 155.7 21.44 144.9 19.97 144.9 19.97 144.9 19.97 128.8 17.56 109.4 15.15

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 104.9 35.60 96.7 32.84 91.2 30.98 91.2 30.98 87.5 29.60 77.6 26.42 67.2 23.34

-14.7 -15.0 111.2 36.21 102.8 33.48 97.0 31.59 97.0 31.59 93.4 30.24 82.9 27.03 72.0 23.85

-9.6 -10.0 119.4 37.17 110.5 34.41 104.5 32.49 104.5 32.49 101.0 31.20 89.8 27.89 78.2 24.59

-4.4 -5.0 130.3 38.52 121.0 35.73 114.5 33.80 114.5 33.80 111.1 32.52 99.2 29.08 86.7 25.62

-1.8 -2.5 137.2 39.42 127.7 36.59 121.0 34.67 121.0 34.67 117.6 33.35 105.0 29.85 91.9 26.29

0.8 0.0 145.5 40.51 135.5 37.62 128.5 35.66 128.5 35.66 125.2 34.38 112.2 30.78 98.0 26.96

110% 2.8 2.0 153.2 41.44 143.0 38.52 135.8 36.50 135.8 36.50 132.5 35.18 115.2 30.24 98.0 25.62

6.0 5.0 165.5 41.73 151.9 37.97 141.5 34.96 141.5 34.96 132.5 31.94 115.2 27.51 98.0 23.30

7.0 6.0 167.7 40.96 151.9 36.47 141.5 33.61 141.5 33.61 132.5 30.72 115.2 26.48 98.0 22.44

8.6 7.5 167.7 38.33 151.9 34.15 141.5 31.52 141.5 31.52 132.5 28.86 115.2 24.91 98.0 21.15

11.2 10.0 167.7 34.09 151.9 30.46 141.5 28.15 141.5 28.15 132.5 25.87 115.2 22.41 98.0 19.13

16.4 15.0 167.7 26.45 151.9 23.82 141.5 22.15 141.5 22.15 132.5 20.51 115.2 17.98 98.0 15.50

24.0 18.0 167.7 22.50 151.9 20.38 141.5 19.04 141.5 19.04 132.5 17.78 115.2 15.70 98.0 13.64

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 105.2 35.25 96.9 32.55 91.4 30.69 85.6 28.83 79.6 26.93 70.5 24.14 61.1 21.38

-14.7 -15.0 111.5 35.92 102.9 33.19 97.2 31.33 91.1 29.44 85.0 27.54 75.3 24.65 65.4 21.83

-9.6 -10.0 119.6 36.85 110.8 34.12 104.6 32.26 98.3 30.33 91.8 28.38 81.7 25.42 71.1 22.47

-4.4 -5.0 130.5 38.23 121.2 35.47 114.7 33.54 107.9 31.59 100.9 29.56 90.0 26.51 78.5 23.40

-1.8 -2.5 137.4 39.13 127.8 36.34 121.0 34.38 114.0 32.39 106.7 30.33 95.2 27.19 83.2 23.98

0.8 0.0 145.6 40.19 135.5 37.36 128.5 35.37 121.2 33.32 113.6 31.20 101.7 27.96 86.9 23.95

100% 2.8 2.0 153.3 41.02 142.8 38.13 135.7 36.11 127.8 33.93 117.6 30.98 102.3 26.74 86.9 22.76

6.0 5.0 163.5 40.70 148.2 36.27 138.0 33.48 127.8 30.75 117.6 28.12 102.3 24.33 86.9 20.70

7.0 6.0 163.5 39.03 148.2 34.83 138.0 32.10 127.8 29.56 117.6 27.06 102.3 23.43 86.9 19.97

8.6 7.5 163.5 36.50 148.2 32.61 138.0 30.14 127.8 27.73 117.6 25.42 102.3 22.05 86.9 18.81

11.2 10.0 163.5 32.42 148.2 29.05 138.0 26.90 127.8 24.81 117.6 22.79 102.3 19.84 86.9 17.01

16.4 15.0 163.5 25.10 148.2 22.69 138.0 21.12 127.8 19.61 117.6 18.10 102.3 15.95 86.9 13.84

9 24.0 18.0 163.5 21.31 148.2 19.39 138.0 18.14 127.8 16.92 117.6 15.73 102.3 13.93 86.9 12.20
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


44 HP (U-14MF2E8 & U-14MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 106.0 33.93 97.6 31.43 91.8 29.72 85.8 27.99 79.9 26.26 70.5 23.66 61.0 21.12

-14.7 -15.0 112.5 34.67 103.6 32.13 97.6 30.40 91.5 28.63 85.1 26.84 75.3 24.17 65.3 21.54

-9.6 -10.0 120.6 35.70 111.4 33.10 105.0 31.33 98.5 29.50 91.8 27.67 81.4 24.88 70.7 22.12

-4.4 -5.0 131.5 37.11 121.6 34.44 114.8 32.58 107.8 30.72 100.6 28.79 89.4 25.84 77.7 22.89

-1.8 -2.5 138.1 37.97 127.9 35.25 120.9 33.38 113.7 31.43 105.8 29.34 92.0 25.62 78.2 22.12

0.8 0.0 146.1 38.78 133.4 35.21 124.2 32.65 115.0 30.14 105.8 27.70 92.0 24.24 78.2 20.90

90% 2.8 2.0 147.2 36.98 133.4 33.29 124.2 30.88 115.0 28.54 105.8 26.26 92.0 22.98 78.2 19.84

6.0 5.0 147.2 33.22 133.4 29.98 124.2 27.89 115.0 25.84 105.8 23.82 92.0 20.87 78.2 17.98

7.0 6.0 147.2 31.84 133.4 28.76 124.2 26.77 115.0 24.81 105.8 22.89 92.0 20.06 78.2 17.30

8.6 7.5 147.2 29.66 133.4 26.84 124.2 25.01 115.0 23.24 105.8 21.47 92.0 18.87 78.2 16.34

11.2 10.0 147.2 26.23 133.4 23.82 124.2 22.28 115.0 20.74 105.8 19.23 92.0 16.98 78.2 14.77

16.4 15.0 147.2 20.09 133.4 18.46 124.2 17.37 115.0 16.27 105.8 15.22 92.0 13.61 78.2 12.01

24.0 18.0 147.2 18.59 133.4 17.08 124.2 16.08 115.0 15.09 105.8 14.09 92.0 12.58 78.2 11.07

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 107.2 32.87 98.4 30.56 92.5 28.99 86.4 27.38 80.3 25.78 70.8 23.40 61.0 21.09

-14.7 -15.0 113.7 33.71 104.6 31.30 98.4 29.69 92.0 28.02 85.6 26.39 75.5 23.88 65.3 21.44

-9.6 -10.0 121.9 34.76 112.3 32.29 105.7 30.62 98.9 28.89 92.0 27.16 81.4 24.56 69.6 21.60

-4.4 -5.0 130.8 35.50 118.5 32.23 110.4 30.11 102.3 28.02 94.0 25.97 81.8 23.02 69.6 20.19

-1.8 -2.5 130.8 33.71 118.5 30.62 110.4 28.60 102.3 26.64 94.0 24.72 81.8 21.92 69.6 19.23

0.8 0.0 130.8 31.65 118.5 28.79 110.4 26.93 102.3 25.10 94.0 23.30 81.8 20.70 69.6 18.14

80% 2.8 2.0 130.8 29.82 118.5 27.19 110.4 25.46 102.3 23.75 94.0 22.08 81.8 19.61 69.6 17.21

6.0 5.0 130.8 26.68 118.5 24.40 110.4 22.92 102.3 21.41 94.0 19.93 81.8 17.69 69.6 15.47

7.0 6.0 130.8 25.52 118.5 23.37 110.4 21.96 102.3 20.54 94.0 19.13 81.8 17.01 69.6 14.89

8.6 7.5 130.8 23.72 118.5 21.76 110.4 20.48 102.3 19.20 94.0 17.91 81.8 15.99 69.6 14.03

11.2 10.0 130.8 20.87 118.5 19.26 110.4 18.20 102.3 17.11 94.0 16.02 81.8 14.38 69.6 12.71

16.4 15.0 130.8 16.79 118.5 15.47 110.4 14.57 102.3 13.71 94.0 12.81 81.8 11.52 69.6 10.34

24.0 18.0 130.8 16.79 118.5 15.47 110.4 14.57 102.3 13.71 94.0 12.81 81.8 11.49 69.6 10.14

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 109.2 32.29 100.1 30.14 94.0 28.67 87.6 27.19 81.3 25.71 71.6 23.53 60.9 21.09

-14.7 -15.0 114.5 32.71 103.8 30.05 96.6 28.28 89.4 26.55 82.2 24.85 71.6 22.37 60.9 19.97

-9.6 -10.0 114.5 30.88 103.8 28.41 96.6 26.77 89.4 25.17 82.2 23.56 71.6 21.15 60.9 18.81

-4.4 -5.0 114.5 28.31 103.8 26.07 96.6 24.62 89.4 23.14 82.2 21.70 71.6 19.58 60.9 17.49

-1.8 -2.5 114.5 26.80 103.8 24.72 96.6 23.34 89.4 21.99 82.2 20.61 71.6 18.62 60.9 16.60

0.8 0.0 114.5 25.10 103.8 23.21 96.6 21.92 89.4 20.67 82.2 19.42 71.6 17.53 60.9 15.63

70% 2.8 2.0 114.5 23.59 103.8 21.86 96.6 20.67 89.4 19.52 82.2 18.33 71.6 16.56 60.9 14.67

6.0 5.0 114.5 21.03 103.8 19.55 96.6 18.52 89.4 17.49 82.2 16.47 71.6 14.83 60.9 13.16

7.0 6.0 114.5 20.06 103.8 18.68 96.6 17.72 89.4 16.76 82.2 15.76 71.6 14.25 60.9 12.65

8.6 7.5 114.5 18.59 103.8 17.37 96.6 16.53 89.4 15.66 82.2 14.77 71.6 13.39 60.9 11.94

11.2 10.0 114.5 16.27 103.8 15.31 96.6 14.64 89.4 13.93 82.2 13.19 71.6 12.04 60.9 10.82

16.4 15.0 114.5 15.02 103.8 13.87 96.6 13.10 89.4 12.29 82.2 11.52 71.6 10.37 60.9 9.21

24.0 18.0 114.5 15.02 103.8 13.87 96.6 13.10 89.4 12.29 82.2 11.52 71.6 10.37 60.9 9.21

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 98.1 27.54 88.9 25.62 82.8 24.33 76.7 23.08 70.5 21.86 61.3 20.03 52.2 18.23

-14.7 -15.0 98.1 26.07 88.9 24.36 82.8 23.24 76.7 22.08 70.5 20.87 61.3 19.07 52.2 17.27

-9.6 -10.0 98.1 24.30 88.9 22.76 82.8 21.73 76.7 20.67 70.5 19.61 61.3 18.04 52.2 16.27

-4.4 -5.0 98.1 22.18 88.9 20.80 82.8 19.87 76.7 18.94 70.5 17.98 61.3 16.53 52.2 15.02

-1.8 -2.5 98.1 20.93 88.9 19.65 82.8 18.81 76.7 17.91 70.5 17.05 61.3 15.66 52.2 14.22

0.8 0.0 98.1 19.52 88.9 18.39 82.8 17.62 76.7 16.79 70.5 15.99 61.3 14.70 52.2 13.19

60% 2.8 2.0 98.1 18.30 88.9 17.27 82.8 16.56 76.7 15.83 70.5 15.05 61.3 13.77 52.2 12.33

6.0 5.0 98.1 16.21 88.9 15.34 82.8 14.73 76.7 14.06 70.5 13.39 61.3 12.26 52.2 11.04

7.0 6.0 98.1 15.44 88.9 14.64 82.8 14.06 76.7 13.48 70.5 12.81 61.3 11.78 52.2 10.66

8.6 7.5 98.1 14.25 88.9 13.61 82.8 13.10 76.7 12.58 70.5 12.01 61.3 11.07 52.2 10.08

11.2 10.0 98.1 13.26 88.9 12.26 82.8 11.59 76.7 11.17 70.5 10.72 61.3 9.98 52.2 9.15

16.4 15.0 98.1 13.26 88.9 12.26 82.8 11.59 76.7 10.91 70.5 10.27 61.3 9.24 52.2 8.25

24.0 18.0 98.1 13.26 88.9 12.26 82.8 11.59 76.7 10.91 70.5 10.27 61.3 9.24 52.2 8.25

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


44 HP (U-14MF2E8 & U-14MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 81.8 21.54 74.1 20.54 69.0 19.84 63.9 19.04 58.8 18.20 51.1 16.92 43.5 15.60

-14.7 -15.0 81.8 20.29 74.1 19.39 69.0 18.75 63.9 18.07 58.8 17.37 51.1 16.08 43.5 14.77

-9.6 -10.0 81.8 18.84 74.1 18.04 69.0 17.43 63.9 16.82 58.8 16.18 51.1 15.15 43.5 13.90

-4.4 -5.0 81.8 17.08 74.1 16.37 69.0 15.89 63.9 15.34 58.8 14.77 51.1 13.80 43.5 12.74

-1.8 -2.5 81.8 16.05 74.1 15.41 69.0 14.96 63.9 14.48 58.8 13.93 51.1 13.03 43.5 11.81

0.8 0.0 81.8 14.93 74.1 14.38 69.0 13.96 63.9 13.51 58.8 13.00 51.1 12.04 43.5 10.88

50% 2.8 2.0 81.8 13.93 74.1 13.45 69.0 13.06 63.9 12.62 58.8 12.07 51.1 11.17 43.5 10.18

6.0 5.0 81.8 12.23 74.1 11.81 69.0 11.49 63.9 11.11 58.8 10.69 51.1 9.98 43.5 9.15

7.0 6.0 81.8 11.59 74.1 11.24 69.0 10.95 63.9 10.63 58.8 10.24 51.1 9.60 43.5 8.83

8.6 7.5 81.8 11.49 74.1 10.66 69.0 10.21 63.9 9.92 58.8 9.60 51.1 9.05 43.5 8.38

11.2 10.0 81.8 11.49 74.1 10.66 69.0 10.08 63.9 9.53 58.8 8.99 51.1 8.15 43.5 7.61

16.4 15.0 81.8 11.49 74.1 10.66 69.0 10.08 63.9 9.53 58.8 8.99 51.1 8.15 43.5 7.32

24.0 18.0 81.8 11.49 74.1 10.66 69.0 10.08 63.9 9.53 58.8 8.99 51.1 8.15 43.5 7.32

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 65.4 16.66 59.3 16.24 55.2 15.89 51.1 15.50 47.1 14.93 40.8 14.06 34.8 13.10

-14.7 -15.0 65.4 15.66 59.3 15.28 55.2 14.96 51.1 14.61 47.1 14.19 40.8 13.35 34.8 12.39

-9.6 -10.0 65.4 14.45 59.3 14.16 55.2 13.90 51.1 13.58 47.1 13.19 40.8 12.55 34.8 11.65

-4.4 -5.0 65.4 13.00 59.3 12.78 55.2 12.55 51.1 12.29 47.1 11.97 40.8 11.27 34.8 10.27

-1.8 -2.5 65.4 12.17 59.3 11.97 55.2 11.78 51.1 11.52 47.1 11.14 40.8 10.40 34.8 9.53

0.8 0.0 65.4 11.27 59.3 11.07 55.2 10.85 51.1 10.53 47.1 10.18 40.8 9.53 34.8 8.80

40% 2.8 2.0 65.4 10.43 59.3 10.21 55.2 9.98 51.1 9.73 47.1 9.44 40.8 8.89 34.8 8.25

6.0 5.0 65.4 9.69 59.3 9.05 55.2 8.76 51.1 8.60 47.1 8.38 40.8 7.99 34.8 7.48

7.0 6.0 65.4 9.69 59.3 9.05 55.2 8.60 51.1 8.22 47.1 8.06 40.8 7.67 34.8 7.22

8.6 7.5 65.4 9.69 59.3 9.05 55.2 8.60 51.1 8.15 47.1 7.70 40.8 7.25 34.8 6.87

11.2 10.0 65.4 9.69 59.3 9.05 55.2 8.60 51.1 8.15 47.1 7.70 40.8 7.03 34.8 6.39

16.4 15.0 65.4 9.69 59.3 9.05 55.2 8.60 51.1 8.15 47.1 7.70 40.8 7.03 34.8 6.39

24.0 18.0 65.4 9.69 59.3 9.05 55.2 8.60 51.1 8.15 47.1 7.70 40.8 7.03 34.8 6.39

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 49.1 12.81 44.4 12.68 41.4 12.52 38.4 12.29 35.3 11.94 30.6 11.33 26.1 10.69

-14.7 -15.0 49.1 11.97 44.4 11.88 41.4 11.78 38.4 11.59 35.3 11.33 30.6 10.75 26.1 10.08

-9.6 -10.0 49.1 11.01 44.4 10.98 41.4 10.88 38.4 10.72 35.3 10.53 30.6 9.92 26.1 9.12

-4.4 -5.0 49.1 9.82 44.4 9.82 41.4 9.63 38.4 9.41 35.3 9.12 30.6 8.60 26.1 7.99

-1.8 -2.5 49.1 9.08 44.4 8.96 41.4 8.80 38.4 8.63 35.3 8.41 30.6 7.99 26.1 7.48

0.8 0.0 49.1 8.15 44.4 8.09 41.4 8.03 38.4 7.90 35.3 7.70 30.6 7.38 26.1 6.93

30% 2.8 2.0 49.1 7.93 44.4 7.45 41.4 7.42 38.4 7.32 35.3 7.19 30.6 6.90 26.1 6.55

6.0 5.0 49.1 7.93 44.4 7.42 41.4 7.09 38.4 6.77 35.3 6.42 30.6 6.26 26.1 5.97

7.0 6.0 49.1 7.93 44.4 7.42 41.4 7.09 38.4 6.77 35.3 6.42 30.6 6.03 26.1 5.81

8.6 7.5 49.1 7.93 44.4 7.42 41.4 7.09 38.4 6.77 35.3 6.42 30.6 5.94 26.1 5.55

11.2 10.0 49.1 7.93 44.4 7.42 41.4 7.09 38.4 6.77 35.3 6.42 30.6 5.94 26.1 5.42

16.4 15.0 49.1 7.93 44.4 7.42 41.4 7.09 38.4 6.77 35.3 6.42 30.6 5.94 26.1 5.42

24.0 18.0 49.1 7.93 44.4 7.42 41.4 7.09 38.4 6.77 35.3 6.42 30.6 5.94 26.1 5.42

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


46 HP (U-14MF2E8 & U-16MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 108.9 39.17 100.5 36.05 94.7 33.92 94.7 33.92 94.7 33.92 94.7 33.92 82.8 29.37

-14.7 -15.0 115.4 39.76 106.7 36.68 100.8 34.55 100.8 34.55 100.8 34.55 100.8 34.55 88.9 30.03

-9.6 -10.0 123.8 40.71 114.8 37.63 108.6 35.49 108.6 35.49 108.6 35.49 108.6 35.49 96.7 31.01

-4.4 -5.0 135.1 42.14 125.7 39.06 119.2 36.93 119.2 36.93 119.2 36.93 119.2 36.93 107.2 32.41

-1.8 -2.5 142.4 43.12 132.7 40.01 126.0 37.87 126.0 37.87 126.0 37.87 126.0 37.87 113.8 33.36

0.8 0.0 151.1 44.28 141.1 41.13 134.0 38.96 134.0 38.96 134.0 38.96 134.0 38.96 122.1 34.51

130% 2.8 2.0 159.4 45.33 148.9 42.21 141.7 40.04 141.7 40.04 141.7 40.04 141.7 40.04 127.6 34.65

6.0 5.0 171.4 45.50 164.0 43.96 155.9 41.55 155.9 41.55 155.9 41.55 150.1 37.56 127.6 31.50

7.0 6.0 176.6 45.50 167.5 43.54 155.9 39.94 155.9 39.94 155.9 39.94 150.1 36.16 127.6 30.35

8.6 7.5 183.6 45.50 167.5 40.85 155.9 37.49 155.9 37.49 155.9 37.49 150.1 34.02 127.6 28.60

11.2 10.0 184.7 41.16 167.5 36.51 155.9 33.57 155.9 33.57 155.9 33.57 150.1 30.56 127.6 25.80

16.4 15.0 184.7 32.13 167.5 28.70 155.9 26.50 155.9 26.50 155.9 26.50 150.1 24.43 127.6 20.79

24.0 18.0 184.7 27.44 167.5 24.64 155.9 22.86 155.9 22.86 155.9 22.86 150.1 21.28 127.6 18.27

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 109.0 38.75 100.6 35.70 94.8 33.60 94.8 33.60 94.8 33.60 88.2 30.91 76.4 27.20

-14.7 -15.0 115.7 39.38 106.9 36.33 100.9 34.27 100.9 34.27 100.9 34.27 94.3 31.64 81.9 27.83

-9.6 -10.0 124.1 40.32 115.0 37.31 108.8 35.25 108.8 35.25 108.8 35.25 102.2 32.66 89.0 28.70

-4.4 -5.0 135.4 41.83 125.9 38.75 119.2 36.65 119.2 36.65 119.2 36.65 112.8 34.09 98.6 29.96

-1.8 -2.5 142.7 42.77 132.8 39.69 126.0 37.56 126.0 37.56 126.0 37.56 119.6 35.04 104.7 30.77

0.8 0.0 151.4 43.93 141.1 40.81 134.0 38.68 134.0 38.68 134.0 38.68 127.9 36.19 112.2 31.82

120% 2.8 2.0 159.5 44.98 148.9 41.86 141.5 39.66 141.5 39.66 141.5 39.66 135.3 36.96 115.0 31.12

6.0 5.0 172.4 45.50 163.6 43.37 152.3 39.83 152.3 39.83 152.3 39.83 135.3 33.60 115.0 28.32

7.0 6.0 177.5 45.50 163.6 41.65 152.3 38.29 152.3 38.29 152.3 38.29 135.3 32.38 115.0 27.27

8.6 7.5 180.4 43.96 163.6 39.06 152.3 35.91 152.3 35.91 152.3 35.91 135.3 30.45 115.0 25.69

11.2 10.0 180.4 39.20 163.6 34.86 152.3 32.13 152.3 32.13 152.3 32.13 135.3 27.37 115.0 23.21

16.4 15.0 180.4 30.52 163.6 27.34 152.3 25.31 152.3 25.31 152.3 25.31 135.3 21.91 115.0 18.76

24.0 18.0 180.4 26.04 163.6 23.45 152.3 21.81 152.3 21.81 152.3 21.81 135.3 19.11 115.0 16.49

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 109.3 38.33 100.8 35.35 95.0 33.32 95.0 33.32 91.2 31.82 80.8 28.39 70.0 25.06

-14.7 -15.0 115.9 38.99 107.2 36.02 101.1 33.99 101.1 33.99 97.3 32.52 86.4 29.05 75.1 25.62

-9.6 -10.0 124.4 40.01 115.1 37.00 108.9 34.97 108.9 34.97 105.1 33.53 93.7 29.96 81.5 26.39

-4.4 -5.0 135.7 41.48 126.0 38.47 119.3 36.37 119.3 36.37 115.7 34.97 103.4 31.26 90.2 27.51

-1.8 -2.5 143.0 42.46 133.0 39.38 126.0 37.28 126.0 37.28 122.4 35.88 109.5 32.10 95.7 28.25

0.8 0.0 151.5 43.58 141.1 40.50 133.8 38.36 133.8 38.36 130.4 37.00 116.9 33.11 102.5 29.16

110% 2.8 2.0 159.5 44.63 148.9 41.48 141.4 39.31 141.4 39.31 138.2 37.94 121.1 32.90 103.0 27.83

6.0 5.0 173.4 45.50 159.6 41.44 148.6 38.12 148.6 38.12 139.2 34.79 121.1 29.93 103.0 25.31

7.0 6.0 176.2 44.77 159.6 39.80 148.6 36.65 148.6 36.65 139.2 33.46 121.1 28.81 103.0 24.40

8.6 7.5 176.2 41.90 159.6 37.31 148.6 34.37 148.6 34.37 139.2 31.43 121.1 27.09 103.0 23.00

11.2 10.0 176.2 37.28 159.6 33.29 148.6 30.73 148.6 30.73 139.2 28.18 121.1 24.40 103.0 20.76

16.4 15.0 176.2 28.98 159.6 26.04 148.6 24.19 148.6 24.19 139.2 22.37 121.1 19.53 103.0 16.80

24.0 18.0 176.2 24.68 159.6 22.33 148.6 20.79 148.6 20.79 139.2 19.39 121.1 17.05 103.0 14.81

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 109.5 37.94 100.9 35.00 95.1 33.01 89.0 30.98 82.9 28.95 73.4 25.90 63.7 22.93

-14.7 -15.0 116.1 38.64 107.3 35.70 101.2 33.71 94.8 31.64 88.5 29.61 78.6 26.50 68.2 23.42

-9.6 -10.0 124.6 39.66 115.4 36.72 108.9 34.69 102.4 32.62 95.6 30.52 85.1 27.30 74.0 24.12

-4.4 -5.0 136.0 41.16 126.2 38.15 119.3 36.09 112.4 33.95 105.1 31.78 93.8 28.46 81.8 25.10

-1.8 -2.5 143.1 42.11 133.0 39.10 126.0 37.00 118.8 34.83 111.1 32.62 99.3 29.23 86.7 25.76

0.8 0.0 151.7 43.26 141.1 40.18 133.8 38.05 126.2 35.88 118.3 33.57 106.0 30.07 91.4 25.97

100% 2.8 2.0 159.6 44.21 148.8 41.09 141.2 38.89 133.5 36.68 123.5 33.71 107.4 29.05 91.4 24.71

6.0 5.0 171.8 44.45 155.7 39.59 145.0 36.51 134.3 33.50 123.5 30.59 107.4 26.46 91.4 22.47

7.0 6.0 171.8 42.63 155.7 38.01 145.0 35.00 134.3 32.20 123.5 29.44 107.4 25.45 91.4 21.67

8.6 7.5 171.8 39.87 155.7 35.60 145.0 32.87 134.3 30.24 123.5 27.65 107.4 23.98 91.4 20.44

11.2 10.0 171.8 35.46 155.7 31.75 145.0 29.37 134.3 27.06 123.5 24.82 107.4 21.56 91.4 18.48

16.4 15.0 171.8 27.48 155.7 24.78 145.0 23.07 134.3 21.39 123.5 19.74 107.4 17.33 91.4 15.02

9 24.0 18.0 171.8 23.35 155.7 21.21 145.0 19.81 134.3 18.45 123.5 17.12 107.4 15.16 91.4 13.23
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


46 HP (U-14MF2E8 & U-16MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 110.3 36.51 101.6 33.78 95.6 31.96 89.5 30.07 83.2 28.21 73.5 25.41 63.5 22.65

-14.7 -15.0 117.2 37.31 107.9 34.55 101.6 32.69 95.3 30.77 88.6 28.84 78.4 25.97 68.0 23.10

-9.6 -10.0 125.6 38.40 116.0 35.60 109.5 33.67 102.7 31.71 95.7 29.72 84.8 26.74 73.5 23.73

-4.4 -5.0 136.9 39.90 126.6 37.03 119.6 35.04 112.4 33.01 104.8 30.94 93.2 27.76 80.9 24.57

-1.8 -2.5 144.0 40.88 133.3 37.94 126.0 35.91 118.3 33.81 110.6 31.68 96.7 27.83 82.2 23.98

0.8 0.0 152.3 41.76 140.2 38.36 130.5 35.53 120.8 32.80 111.2 30.14 96.7 26.32 82.2 22.68

90% 2.8 2.0 154.7 40.36 140.2 36.26 130.5 33.64 120.8 31.05 111.2 28.56 96.7 24.96 82.2 21.53

6.0 5.0 154.7 36.30 140.2 32.69 130.5 30.38 120.8 28.11 111.2 25.90 96.7 22.65 82.2 19.50

7.0 6.0 154.7 34.76 140.2 31.36 130.5 29.16 120.8 26.99 111.2 24.89 96.7 21.77 82.2 18.76

8.6 7.5 154.7 32.41 140.2 29.30 130.5 27.27 120.8 25.27 111.2 23.35 96.7 20.48 82.2 17.68

11.2 10.0 154.7 28.67 140.2 26.01 130.5 24.26 120.8 22.58 111.2 20.90 96.7 18.41 82.2 16.00

16.4 15.0 154.7 21.98 140.2 20.13 130.5 18.94 120.8 17.75 111.2 16.56 96.7 14.77 82.2 12.99

24.0 18.0 154.7 20.06 140.2 18.41 130.5 17.33 120.8 16.24 111.2 15.19 96.7 13.55 82.2 11.94

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 111.7 35.35 102.5 32.83 96.3 31.15 90.0 29.44 83.5 27.69 73.8 25.13 63.7 22.61

-14.7 -15.0 118.5 36.23 108.9 33.67 102.4 31.89 95.8 30.14 89.0 28.32 78.6 25.66 67.9 23.00

-9.6 -10.0 127.0 37.42 117.0 34.72 110.1 32.90 103.1 31.05 95.8 29.19 84.8 26.36 73.1 23.42

-4.4 -5.0 137.5 38.68 124.6 35.07 116.0 32.76 107.4 30.45 98.7 28.21 86.0 24.99 73.1 21.88

-1.8 -2.5 137.5 36.72 124.6 33.32 116.0 31.12 107.4 28.95 98.7 26.85 86.0 23.77 73.1 20.83

0.8 0.0 137.5 34.51 124.6 31.36 116.0 29.30 107.4 27.30 98.7 25.31 86.0 22.44 73.1 19.64

80% 2.8 2.0 137.5 32.52 124.6 29.61 116.0 27.69 107.4 25.83 98.7 23.98 86.0 21.28 73.1 18.62

6.0 5.0 137.5 29.09 124.6 26.60 116.0 24.92 107.4 23.28 98.7 21.63 86.0 19.18 73.1 16.73

7.0 6.0 137.5 27.83 124.6 25.45 116.0 23.87 107.4 22.33 98.7 20.76 86.0 18.45 73.1 16.10

8.6 7.5 137.5 25.87 124.6 23.73 116.0 22.30 107.4 20.86 98.7 19.46 86.0 17.33 73.1 15.19

11.2 10.0 137.5 22.75 124.6 21.00 116.0 19.81 107.4 18.59 98.7 17.40 86.0 15.58 73.1 13.76

16.4 15.0 137.5 18.13 124.6 16.66 116.0 15.72 107.4 14.77 98.7 13.79 86.0 12.46 73.1 11.17

24.0 18.0 137.5 18.13 124.6 16.66 116.0 15.72 107.4 14.77 98.7 13.79 86.0 12.36 73.1 10.92

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 113.7 34.72 104.3 32.38 97.9 30.80 91.4 29.23 84.7 27.65 74.5 25.27 63.9 22.82

-14.7 -15.0 120.4 35.56 109.0 32.62 101.5 30.70 94.0 28.81 86.4 26.95 75.3 24.22 63.9 21.60

-9.6 -10.0 120.4 33.64 109.0 30.87 101.5 29.09 94.0 27.30 86.4 25.55 75.3 22.93 63.9 20.37

-4.4 -5.0 120.4 30.84 109.0 28.35 101.5 26.74 94.0 25.13 86.4 23.56 75.3 21.21 63.9 18.94

-1.8 -2.5 120.4 29.19 109.0 26.88 101.5 25.38 94.0 23.87 86.4 22.37 75.3 20.16 63.9 17.96

0.8 0.0 120.4 27.34 109.0 25.24 101.5 23.84 94.0 22.44 86.4 21.04 75.3 18.97 63.9 16.91

70% 2.8 2.0 120.4 25.69 109.0 23.77 101.5 22.47 94.0 21.18 86.4 19.88 75.3 17.92 63.9 15.89

6.0 5.0 120.4 22.89 109.0 21.25 101.5 20.13 94.0 19.01 86.4 17.85 75.3 16.07 63.9 14.21

7.0 6.0 120.4 21.84 109.0 20.30 101.5 19.25 94.0 18.20 86.4 17.12 75.3 15.44 63.9 13.69

8.6 7.5 120.4 20.27 109.0 18.90 101.5 17.96 94.0 17.01 86.4 16.03 75.3 14.49 63.9 12.92

11.2 10.0 120.4 17.71 109.0 16.66 101.5 15.89 94.0 15.12 86.4 14.32 75.3 13.02 63.9 11.69

16.4 15.0 120.4 16.21 109.0 14.95 101.5 14.11 94.0 13.27 86.4 12.43 75.3 11.13 63.9 9.87

24.0 18.0 120.4 16.21 109.0 14.95 101.5 14.11 94.0 13.27 86.4 12.43 75.3 11.13 63.9 9.87

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 103.1 29.89 93.4 27.79 87.0 26.39 80.6 25.03 74.1 23.66 64.4 21.67 54.8 19.71

-14.7 -15.0 103.1 28.32 93.4 26.46 87.0 25.20 80.6 23.94 74.1 22.61 64.4 20.62 54.8 18.66

-9.6 -10.0 103.1 26.43 93.4 24.71 87.0 23.56 80.6 22.40 74.1 21.28 64.4 19.50 54.8 17.57

-4.4 -5.0 103.1 24.12 93.4 22.58 87.0 21.56 80.6 20.55 74.1 19.50 64.4 17.89 54.8 16.24

-1.8 -2.5 103.1 22.75 93.4 21.35 87.0 20.41 80.6 19.43 74.1 18.45 64.4 16.94 54.8 15.37

0.8 0.0 103.1 21.25 93.4 19.95 87.0 19.11 80.6 18.20 74.1 17.29 64.4 15.89 54.8 14.28

60% 2.8 2.0 103.1 19.92 93.4 18.76 87.0 17.96 80.6 17.15 74.1 16.28 64.4 14.88 54.8 13.30

6.0 5.0 103.1 17.64 93.4 16.66 87.0 16.00 80.6 15.26 74.1 14.49 64.4 13.27 54.8 11.94

7.0 6.0 103.1 16.77 93.4 15.89 87.0 15.26 80.6 14.60 74.1 13.86 64.4 12.74 54.8 11.48

8.6 7.5 103.1 15.51 93.4 14.77 87.0 14.21 80.6 13.62 74.1 12.99 64.4 11.97 54.8 10.85

11.2 10.0 103.1 14.28 93.4 13.20 87.0 12.53 80.6 12.08 74.1 11.59 64.4 10.78 54.8 9.84

16.4 15.0 103.1 14.28 93.4 13.20 87.0 12.46 80.6 11.76 74.1 11.03 64.4 9.94 54.8 8.86

24.0 18.0 103.1 14.28 93.4 13.20 87.0 12.46 80.6 11.76 74.1 11.03 64.4 9.94 54.8 8.86

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


46 HP (U-14MF2E8 & U-16MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 86.0 23.35 77.9 22.26 72.5 21.49 67.1 20.62 61.8 19.67 53.7 18.27 45.7 16.84

-14.7 -15.0 86.0 22.02 77.9 21.00 72.5 20.30 67.1 19.57 61.8 18.76 53.7 17.40 45.7 15.93

-9.6 -10.0 86.0 20.44 77.9 19.53 72.5 18.90 67.1 18.24 61.8 17.50 53.7 16.38 45.7 14.98

-4.4 -5.0 86.0 18.52 77.9 17.75 72.5 17.19 67.1 16.59 61.8 15.96 53.7 14.91 45.7 13.76

-1.8 -2.5 86.0 17.40 77.9 16.70 72.5 16.21 67.1 15.65 61.8 15.05 53.7 14.11 45.7 12.74

0.8 0.0 86.0 16.21 77.9 15.58 72.5 15.12 67.1 14.60 61.8 14.07 53.7 12.99 45.7 11.76

50% 2.8 2.0 86.0 15.12 77.9 14.56 72.5 14.14 67.1 13.65 61.8 13.06 53.7 12.08 45.7 10.99

6.0 5.0 86.0 13.27 77.9 12.78 72.5 12.43 67.1 12.01 61.8 11.55 53.7 10.75 45.7 9.87

7.0 6.0 86.0 12.57 77.9 12.18 72.5 11.87 67.1 11.48 61.8 11.06 53.7 10.36 45.7 9.52

8.6 7.5 86.0 12.36 77.9 11.45 72.5 11.03 67.1 10.71 61.8 10.36 53.7 9.73 45.7 9.00

11.2 10.0 86.0 12.36 77.9 11.45 72.5 10.85 67.1 10.26 61.8 9.66 53.7 8.79 45.7 8.19

16.4 15.0 86.0 12.36 77.9 11.45 72.5 10.85 67.1 10.26 61.8 9.66 53.7 8.75 45.7 7.84

24.0 18.0 86.0 12.36 77.9 11.45 72.5 10.85 67.1 10.26 61.8 9.66 53.7 8.75 45.7 7.84

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 68.7 18.06 62.4 17.57 58.0 17.19 53.7 16.73 49.4 16.14 42.9 15.16 36.5 14.14

-14.7 -15.0 68.7 16.94 62.4 16.52 58.0 16.17 53.7 15.79 49.4 15.33 42.9 14.42 36.5 13.34

-9.6 -10.0 68.7 15.65 62.4 15.30 58.0 15.02 53.7 14.67 49.4 14.25 42.9 13.51 36.5 12.53

-4.4 -5.0 68.7 14.07 62.4 13.79 58.0 13.55 53.7 13.27 49.4 12.92 42.9 12.15 36.5 11.06

-1.8 -2.5 68.7 13.16 62.4 12.92 58.0 12.71 53.7 12.46 49.4 12.01 42.9 11.20 36.5 10.26

0.8 0.0 68.7 12.18 62.4 11.97 58.0 11.73 53.7 11.38 49.4 10.99 42.9 10.29 36.5 9.49

40% 2.8 2.0 68.7 11.27 62.4 11.03 58.0 10.78 53.7 10.50 49.4 10.19 42.9 9.59 36.5 8.89

6.0 5.0 68.7 10.43 62.4 9.70 58.0 9.45 53.7 9.24 49.4 9.03 42.9 8.58 36.5 8.02

7.0 6.0 68.7 10.43 62.4 9.70 58.0 9.24 53.7 8.86 49.4 8.65 42.9 8.26 36.5 7.77

8.6 7.5 68.7 10.43 62.4 9.70 58.0 9.24 53.7 8.75 49.4 8.26 42.9 7.81 36.5 7.35

11.2 10.0 68.7 10.43 62.4 9.70 58.0 9.24 53.7 8.75 49.4 8.26 42.9 7.53 36.5 6.83

16.4 15.0 68.7 10.43 62.4 9.70 58.0 9.24 53.7 8.75 49.4 8.26 42.9 7.53 36.5 6.83

24.0 18.0 68.7 10.43 62.4 9.70 58.0 9.24 53.7 8.75 49.4 8.26 42.9 7.53 36.5 6.83

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 51.6 13.83 46.7 13.69 43.5 13.51 40.3 13.27 37.1 12.85 32.2 12.22 27.4 11.52

-14.7 -15.0 51.6 12.92 46.7 12.85 43.5 12.71 40.3 12.50 37.1 12.22 32.2 11.59 27.4 10.85

-9.6 -10.0 51.6 11.87 46.7 11.83 43.5 11.73 40.3 11.55 37.1 11.34 32.2 10.68 27.4 9.80

-4.4 -5.0 51.6 10.57 46.7 10.57 43.5 10.40 40.3 10.12 37.1 9.80 32.2 9.24 27.4 8.58

-1.8 -2.5 51.6 9.80 46.7 9.63 43.5 9.49 40.3 9.28 37.1 9.03 32.2 8.58 27.4 8.02

0.8 0.0 51.6 8.79 46.7 8.72 43.5 8.61 40.3 8.47 37.1 8.30 32.2 7.91 27.4 7.46

30% 2.8 2.0 51.6 8.51 46.7 8.02 43.5 7.95 40.3 7.84 37.1 7.70 32.2 7.42 27.4 7.00

6.0 5.0 51.6 8.51 46.7 7.95 43.5 7.60 40.3 7.25 37.1 6.90 32.2 6.69 27.4 6.41

7.0 6.0 51.6 8.51 46.7 7.95 43.5 7.60 40.3 7.25 37.1 6.90 32.2 6.48 27.4 6.20

8.6 7.5 51.6 8.51 46.7 7.95 43.5 7.60 40.3 7.25 37.1 6.90 32.2 6.34 27.4 5.92

11.2 10.0 51.6 8.51 46.7 7.95 43.5 7.60 40.3 7.25 37.1 6.90 32.2 6.34 27.4 5.81

16.4 15.0 51.6 8.51 46.7 7.95 43.5 7.60 40.3 7.25 37.1 6.90 32.2 6.34 27.4 5.81

24.0 18.0 51.6 8.51 46.7 7.95 43.5 7.60 40.3 7.25 37.1 6.90 32.2 6.34 27.4 5.81

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


48 HP (U-16MF2E8 & U-16MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 111.6 41.14 103.1 37.83 97.2 35.60 97.2 35.60 97.2 35.60 97.2 35.60 85.1 30.76

-14.7 -15.0 118.4 41.74 109.5 38.46 103.4 36.27 103.4 36.27 103.4 36.27 103.4 36.27 91.2 31.51

-9.6 -10.0 127.1 42.71 117.8 39.51 111.5 37.27 111.5 37.27 111.5 37.27 111.5 37.27 99.2 32.55

-4.4 -5.0 138.8 44.27 129.0 41.03 122.3 38.76 122.3 38.76 122.3 38.76 122.3 38.76 110.0 34.00

-1.8 -2.5 146.1 45.27 136.2 42.00 129.2 39.73 129.2 39.73 129.2 39.73 129.2 39.73 116.9 34.97

0.8 0.0 155.1 46.50 144.8 43.19 137.6 40.92 137.6 40.92 137.6 40.92 137.6 40.92 125.3 36.23

130% 2.8 2.0 163.5 47.62 152.9 44.31 145.4 42.04 145.4 42.04 145.4 42.04 145.4 42.04 132.0 36.68

6.0 5.0 176.9 48.36 168.3 46.20 161.0 44.04 161.0 44.04 161.0 44.04 155.3 39.84 132.0 33.41

7.0 6.0 182.1 48.36 173.3 46.35 161.3 42.48 161.3 42.48 161.3 42.48 155.3 38.35 132.0 32.14

8.6 7.5 189.6 48.36 173.3 43.45 161.3 39.88 161.3 39.88 161.3 39.88 155.3 36.08 132.0 30.28

11.2 10.0 191.1 43.86 173.3 38.87 161.3 35.71 161.3 35.71 161.3 35.71 155.3 32.44 132.0 27.34

16.4 15.0 191.1 34.30 173.3 30.58 161.3 28.20 161.3 28.20 161.3 28.20 155.3 25.93 132.0 22.06

24.0 18.0 191.1 29.31 173.3 26.26 161.3 24.33 161.3 24.33 161.3 24.33 155.3 22.62 132.0 19.34

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 111.9 40.66 103.2 37.46 97.4 35.27 97.4 35.27 97.4 35.27 90.5 32.44 78.5 28.50

-14.7 -15.0 118.7 41.37 109.7 38.13 103.5 35.97 103.5 35.97 103.5 35.97 96.8 33.18 84.2 29.13

-9.6 -10.0 127.4 42.37 118.1 39.17 111.6 36.98 111.6 36.98 111.6 36.98 104.9 34.22 91.4 30.09

-4.4 -5.0 138.9 43.90 129.2 40.70 122.4 38.46 122.4 38.46 122.4 38.46 115.8 35.75 101.3 31.40

-1.8 -2.5 146.4 44.90 136.4 41.70 129.3 39.43 129.3 39.43 129.3 39.43 122.9 36.75 107.6 32.25

0.8 0.0 155.3 46.13 144.8 42.85 137.4 40.59 137.4 40.59 137.4 40.59 131.3 37.98 115.2 33.37

120% 2.8 2.0 163.7 47.24 152.7 43.97 145.2 41.66 145.2 41.66 145.2 41.66 139.8 39.10 119.0 32.96

6.0 5.0 177.9 48.36 168.3 45.76 157.5 42.33 157.5 42.33 157.5 42.33 140.0 35.67 119.0 30.02

7.0 6.0 183.2 48.36 169.2 44.31 157.5 40.70 157.5 40.70 157.5 40.70 140.0 34.34 119.0 28.90

8.6 7.5 186.6 46.83 169.2 41.55 157.5 38.20 157.5 38.20 157.5 38.20 140.0 32.29 119.0 27.23

11.2 10.0 186.6 41.78 169.2 37.13 157.5 34.19 157.5 34.19 157.5 34.19 140.0 29.05 119.0 24.59

16.4 15.0 186.6 32.59 169.2 29.13 157.5 26.97 157.5 26.97 157.5 26.97 140.0 23.25 119.0 19.86

24.0 18.0 186.6 27.83 169.2 25.00 157.5 23.21 157.5 23.21 157.5 23.21 140.0 20.27 119.0 17.45

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 112.2 40.25 103.4 37.09 97.5 34.97 97.5 34.97 93.6 33.37 83.0 29.76 71.9 26.23

-14.7 -15.0 119.0 40.96 109.8 37.80 103.7 35.64 103.7 35.64 99.9 34.11 88.7 30.43 77.0 26.82

-9.6 -10.0 127.5 42.00 118.2 38.84 111.8 36.68 111.8 36.68 107.9 35.15 96.2 31.40 83.7 27.68

-4.4 -5.0 139.2 43.56 129.3 40.36 122.4 38.17 122.4 38.17 118.8 36.68 106.1 32.77 92.6 28.83

-1.8 -2.5 146.7 44.57 136.4 41.37 129.3 39.13 129.3 39.13 125.6 37.65 112.4 33.67 98.3 29.61

0.8 0.0 155.4 45.79 144.8 42.52 137.4 40.25 137.4 40.25 133.8 38.80 120.0 34.74 105.3 30.58

110% 2.8 2.0 163.7 46.87 152.7 43.56 145.1 41.25 145.1 41.25 141.9 39.84 125.3 34.86 106.5 29.46

6.0 5.0 179.0 48.36 165.2 44.08 153.8 40.55 153.8 40.55 144.0 36.90 125.3 31.73 106.5 26.82

7.0 6.0 182.3 47.69 165.2 42.33 153.8 38.95 153.8 38.95 144.0 35.53 125.3 30.54 106.5 25.82

8.6 7.5 182.3 44.64 165.2 39.69 153.8 36.53 153.8 36.53 144.0 33.37 125.3 28.72 106.5 24.33

11.2 10.0 182.3 39.73 165.2 35.41 153.8 32.66 153.8 32.66 144.0 29.91 125.3 25.85 106.5 21.99

16.4 15.0 182.3 30.91 165.2 27.75 153.8 25.74 153.8 25.74 144.0 23.77 125.3 20.72 106.5 17.78

24.0 18.0 182.3 26.34 165.2 23.77 153.8 22.13 153.8 22.13 144.0 20.61 125.3 18.08 106.5 15.66

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 112.4 39.84 103.5 36.75 97.5 34.63 91.4 32.51 85.1 30.36 75.3 27.16 65.3 24.03

-14.7 -15.0 119.1 40.55 110.1 37.46 103.8 35.38 97.4 33.22 90.8 31.02 80.6 27.75 69.9 24.55

-9.6 -10.0 127.8 41.63 118.4 38.54 111.8 36.38 105.0 34.22 98.1 31.99 87.3 28.64 75.9 25.30

-4.4 -5.0 139.5 43.19 129.5 40.06 122.6 37.87 115.4 35.64 107.9 33.33 96.3 29.83 84.0 26.30

-1.8 -2.5 146.9 44.23 136.5 41.03 129.3 38.84 121.8 36.53 114.0 34.19 101.9 30.62 89.0 27.01

0.8 0.0 155.6 45.42 144.9 42.18 137.3 39.95 129.5 37.61 121.4 35.23 108.8 31.55 94.5 27.49

100% 2.8 2.0 163.8 46.46 152.7 43.15 145.1 40.85 137.0 38.50 127.8 35.75 111.2 30.80 94.5 26.15

6.0 5.0 177.8 47.32 161.1 42.11 150.0 38.80 138.9 35.56 127.8 32.48 111.2 28.01 94.5 23.81

7.0 6.0 177.8 45.38 161.1 40.44 150.0 37.20 138.9 34.22 127.8 31.25 111.2 26.97 94.5 22.92

8.6 7.5 177.8 42.48 161.1 37.87 150.0 34.93 138.9 32.10 127.8 29.35 111.2 25.41 94.5 21.61

11.2 10.0 177.8 37.76 161.1 33.78 150.0 31.21 138.9 28.72 127.8 26.34 111.2 22.88 94.5 19.53

16.4 15.0 177.8 29.31 161.1 26.41 150.0 24.55 138.9 22.73 127.8 20.94 111.2 18.38 94.5 15.88

9 24.0 18.0 177.8 24.92 161.1 22.62 150.0 21.09 138.9 19.60 127.8 18.19 111.2 16.07 94.5 13.99
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


48 HP (U-16MF2E8 & U-16MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 113.3 38.32 104.3 35.45 98.1 33.52 91.8 31.55 85.4 29.57 75.5 26.60 65.3 23.73

-14.7 -15.0 120.2 39.13 110.9 36.27 104.3 34.26 97.7 32.29 90.9 30.24 80.6 27.19 69.8 24.22

-9.6 -10.0 128.9 40.29 119.0 37.35 112.2 35.34 105.3 33.26 98.1 31.17 87.0 28.01 75.5 24.85

-4.4 -5.0 140.4 41.89 129.9 38.87 122.7 36.75 115.2 34.63 107.6 32.44 95.6 29.09 83.1 25.74

-1.8 -2.5 147.8 42.93 136.8 39.80 129.3 37.68 121.5 35.49 113.4 33.22 100.1 29.43 85.1 25.33

0.8 0.0 156.2 43.90 144.9 40.70 135.0 37.72 125.0 34.78 115.1 31.95 100.1 27.86 85.1 23.99

90% 2.8 2.0 160.1 42.93 145.1 38.54 135.0 35.71 125.0 32.96 115.1 30.28 100.1 26.41 85.1 22.77

6.0 5.0 160.1 38.61 145.1 34.74 135.0 32.25 125.0 29.83 115.1 27.45 100.1 23.99 85.1 20.61

7.0 6.0 160.1 36.98 145.1 33.33 135.0 30.95 125.0 28.64 115.1 26.37 100.1 23.06 85.1 19.83

8.6 7.5 160.1 34.48 145.1 31.14 135.0 28.94 125.0 26.82 115.1 24.74 100.1 21.69 85.1 18.71

11.2 10.0 160.1 30.50 145.1 27.64 135.0 25.78 125.0 23.96 115.1 22.17 100.1 19.49 85.1 16.89

16.4 15.0 160.1 23.44 145.1 21.43 135.0 20.13 125.0 18.82 115.1 17.56 100.1 15.62 85.1 13.73

24.0 18.0 160.1 21.09 145.1 19.38 135.0 18.23 125.0 17.11 115.1 15.96 100.1 14.25 85.1 12.54

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 114.6 37.09 105.2 34.45 98.9 32.66 92.4 30.84 85.8 29.02 75.6 26.30 65.3 23.66

-14.7 -15.0 121.5 38.02 111.8 35.30 105.2 33.44 98.3 31.58 91.4 29.69 80.7 26.86 69.8 24.07

-9.6 -10.0 130.2 39.25 120.0 36.42 113.0 34.52 105.8 32.55 98.4 30.58 87.0 27.60 75.3 24.63

-4.4 -5.0 141.8 40.85 128.9 37.24 120.0 34.71 111.2 32.25 102.2 29.87 89.0 26.41 75.6 23.10

-1.8 -2.5 142.2 39.02 128.9 35.38 120.0 33.00 111.2 30.69 102.2 28.42 89.0 25.15 75.6 21.99

0.8 0.0 142.2 36.64 128.9 33.29 120.0 31.06 111.2 28.90 102.2 26.82 89.0 23.73 75.6 20.76

80% 2.8 2.0 142.2 34.56 128.9 31.43 120.0 29.39 111.2 27.38 102.2 25.37 89.0 22.51 75.6 19.68

6.0 5.0 142.2 30.95 128.9 28.23 120.0 26.45 111.2 24.66 102.2 22.92 89.0 20.31 75.6 17.67

7.0 6.0 142.2 29.57 128.9 27.01 120.0 25.33 111.2 23.66 102.2 21.99 89.0 19.49 75.6 17.00

8.6 7.5 142.2 27.49 128.9 25.18 120.0 23.66 111.2 22.13 102.2 20.61 89.0 18.34 75.6 16.03

11.2 10.0 142.2 24.22 128.9 22.28 120.0 21.02 111.2 19.72 102.2 18.41 89.0 16.48 75.6 14.51

16.4 15.0 142.2 19.08 128.9 17.56 120.0 16.52 111.2 15.51 102.2 14.55 89.0 13.17 75.6 11.79

24.0 18.0 142.2 19.08 128.9 17.56 120.0 16.52 111.2 15.51 102.2 14.51 89.0 12.98 75.6 11.46

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 116.6 36.42 107.0 33.96 100.4 32.29 93.6 30.62 86.9 28.94 76.5 26.45 65.9 23.99

-14.7 -15.0 123.8 37.42 112.8 34.56 105.0 32.51 97.2 30.50 89.4 28.50 77.9 25.59 66.2 22.80

-9.6 -10.0 124.5 35.67 112.8 32.74 105.0 30.80 97.2 28.90 89.4 27.01 77.9 24.22 66.2 21.50

-4.4 -5.0 124.5 32.70 112.8 30.06 105.0 28.31 97.2 26.60 89.4 24.92 77.9 22.43 66.2 19.98

-1.8 -2.5 124.5 30.99 112.8 28.50 105.0 26.86 97.2 25.26 89.4 23.66 77.9 21.28 66.2 18.93

0.8 0.0 124.5 29.02 112.8 26.75 105.0 25.26 97.2 23.73 89.4 22.28 77.9 20.05 66.2 17.82

70% 2.8 2.0 124.5 27.27 112.8 25.18 105.0 23.81 97.2 22.43 89.4 21.02 77.9 18.93 66.2 16.74

6.0 5.0 124.5 24.29 112.8 22.54 105.0 21.32 97.2 20.13 89.4 18.86 77.9 16.96 66.2 14.99

7.0 6.0 124.5 23.18 112.8 21.54 105.0 20.42 97.2 19.27 89.4 18.08 77.9 16.29 66.2 14.43

8.6 7.5 124.5 21.50 112.8 20.05 105.0 19.01 97.2 18.00 89.4 16.93 77.9 15.29 66.2 13.62

11.2 10.0 124.5 18.82 112.8 17.63 105.0 16.85 97.2 16.00 89.4 15.10 77.9 13.76 66.2 12.31

16.4 15.0 124.5 17.04 112.8 15.70 105.0 14.81 97.2 13.91 89.4 13.02 77.9 11.68 66.2 10.34

24.0 18.0 124.5 17.04 112.8 15.70 105.0 14.81 97.2 13.91 89.4 13.02 77.9 11.68 66.2 10.34

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 106.7 31.66 96.6 29.39 90.0 27.90 83.4 26.45 76.7 25.00 66.6 22.88 56.7 20.79

-14.7 -15.0 106.7 30.02 96.6 28.01 90.0 26.67 83.4 25.30 76.7 23.88 66.6 21.76 56.7 19.68

-9.6 -10.0 106.7 28.01 96.6 26.15 90.0 24.92 83.4 23.70 76.7 22.47 66.6 20.57 56.7 18.53

-4.4 -5.0 106.7 25.56 96.6 23.92 90.0 22.80 83.4 21.69 76.7 20.57 66.6 18.86 56.7 17.11

-1.8 -2.5 106.7 24.11 96.6 22.58 90.0 21.58 83.4 20.53 76.7 19.49 66.6 17.89 56.7 16.18

0.8 0.0 106.7 22.51 96.6 21.13 90.0 20.20 83.4 19.27 76.7 18.27 66.6 16.78 56.7 15.03

60% 2.8 2.0 106.7 21.09 96.6 19.86 90.0 19.01 83.4 18.12 76.7 17.19 66.6 15.70 56.7 14.02

6.0 5.0 106.7 18.67 96.6 17.63 90.0 16.89 83.4 16.11 76.7 15.29 66.6 13.95 56.7 12.57

7.0 6.0 106.7 17.78 96.6 16.81 90.0 16.14 83.4 15.40 76.7 14.66 66.6 13.43 56.7 12.09

8.6 7.5 106.7 16.44 96.6 15.62 90.0 15.03 83.4 14.40 76.7 13.73 66.6 12.61 56.7 11.42

11.2 10.0 106.7 14.99 96.6 13.84 90.0 13.24 83.4 12.76 76.7 12.24 66.6 11.35 56.7 10.34

16.4 15.0 106.7 14.99 96.6 13.84 90.0 13.09 83.4 12.31 76.7 11.57 66.6 10.42 56.7 9.26

24.0 18.0 106.7 14.99 96.6 13.84 90.0 13.09 83.4 12.31 76.7 11.57 66.6 10.42 56.7 9.26

9
Capacity Table
1. Capacity Ratio of Outdoor Unit

3-PIPE ECOi MF2 SERIES, STANDARD (Heating)


48 HP (U-16MF2E8 & U-16MF2E8 & U-16MF2E8) Capacity Ratio 30-130% TC: Total capacity (kW), PI: Power input (kW)

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 89.0 24.74 80.6 23.55 75.0 22.69 69.5 21.76 63.9 20.76 55.5 19.27 47.3 17.74

-14.7 -15.0 89.0 23.29 80.6 22.21 75.0 21.43 69.5 20.65 63.9 19.83 55.5 18.34 47.3 16.78

-9.6 -10.0 89.0 21.61 80.6 20.65 75.0 19.98 69.5 19.23 63.9 18.49 55.5 17.26 47.3 15.77

-4.4 -5.0 89.0 19.60 80.6 18.75 75.0 18.15 69.5 17.52 63.9 16.85 55.5 15.74 47.3 14.51

-1.8 -2.5 89.0 18.41 80.6 17.67 75.0 17.11 69.5 16.52 63.9 15.88 55.5 14.84 47.3 13.43

0.8 0.0 89.0 17.11 80.6 16.44 75.0 15.96 69.5 15.40 63.9 14.84 55.5 13.69 47.3 12.35
50% 2.8 2.0 89.0 16.00 80.6 15.40 75.0 14.92 69.5 14.40 63.9 13.76 55.5 12.69 47.3 11.53

6.0 5.0 89.0 14.02 80.6 13.50 75.0 13.09 69.5 12.65 63.9 12.16 55.5 11.31 47.3 10.38

7.0 6.0 89.0 13.28 80.6 12.87 75.0 12.50 69.5 12.09 63.9 11.64 55.5 10.90 47.3 10.01

8.6 7.5 89.0 12.98 80.6 12.02 75.0 11.64 69.5 11.31 63.9 10.90 55.5 10.23 47.3 9.45

11.2 10.0 89.0 12.98 80.6 12.02 75.0 11.38 69.5 10.75 63.9 10.12 55.5 9.23 47.3 8.59

16.4 15.0 89.0 12.98 80.6 12.02 75.0 11.38 69.5 10.75 63.9 10.12 55.5 9.15 47.3 8.18

24.0 18.0 89.0 12.98 80.6 12.02 75.0 11.38 69.5 10.75 63.9 10.12 55.5 9.15 47.3 8.18

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 71.1 19.05 64.5 18.53 60.0 18.12 55.5 17.63 51.2 17.00 44.4 15.96 37.8 14.88

-14.7 -15.0 71.1 17.89 64.5 17.45 60.0 17.07 55.5 16.63 51.2 16.14 44.4 15.18 37.8 14.02

-9.6 -10.0 71.1 16.52 64.5 16.14 60.0 15.81 55.5 15.44 51.2 14.99 44.4 14.21 37.8 13.21

-4.4 -5.0 71.1 14.84 64.5 14.55 60.0 14.28 55.5 13.99 51.2 13.62 44.4 12.76 37.8 11.61

-1.8 -2.5 71.1 13.88 64.5 13.62 60.0 13.39 55.5 13.09 51.2 12.65 44.4 11.76 37.8 10.75

0.8 0.0 71.1 12.83 64.5 12.61 60.0 12.35 55.5 11.98 51.2 11.53 44.4 10.79 37.8 9.93

40% 2.8 2.0 71.1 11.87 64.5 11.61 60.0 11.35 55.5 11.05 51.2 10.68 44.4 10.04 37.8 9.30

6.0 5.0 71.1 10.94 64.5 10.16 60.0 9.93 55.5 9.71 51.2 9.49 44.4 9.00 37.8 8.41

7.0 6.0 71.1 10.94 64.5 10.16 60.0 9.67 55.5 9.30 51.2 9.08 44.4 8.67 37.8 8.11

8.6 7.5 71.1 10.94 64.5 10.16 60.0 9.67 55.5 9.15 51.2 8.63 44.4 8.18 37.8 7.70

11.2 10.0 71.1 10.94 64.5 10.16 60.0 9.67 55.5 9.15 51.2 8.63 44.4 7.89 37.8 7.11

16.4 15.0 71.1 10.94 64.5 10.16 60.0 9.67 55.5 9.15 51.2 8.63 44.4 7.89 37.8 7.11

24.0 18.0 71.1 10.94 64.5 10.16 60.0 9.67 55.5 9.15 51.2 8.63 44.4 7.89 37.8 7.11

Indoor air t emp.:℃DB

Combinat ion(%) Out door air t emp. 15.0 18.0 20.0 22.0 24.0 27.0 30.0
:Indoor/ out door capacit y rat io
TC PI TC PI TC PI TC PI TC PI TC PI TC PI

℃DB ℃WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW

-19.8 -20.0 53.4 14.55 48.3 14.40 45.0 14.21 41.7 13.95 38.4 13.50 33.3 12.83 28.4 12.09

-14.7 -15.0 53.4 13.62 48.3 13.50 45.0 13.35 41.7 13.13 38.4 12.83 33.3 12.16 28.4 11.38

-9.6 -10.0 53.4 12.50 48.3 12.42 45.0 12.31 41.7 12.16 38.4 11.90 33.3 11.20 28.4 10.27

-4.4 -5.0 53.4 11.12 48.3 11.12 45.0 10.90 41.7 10.64 38.4 10.30 33.3 9.71 28.4 9.00

-1.8 -2.5 53.4 10.30 48.3 10.12 45.0 9.97 41.7 9.75 38.4 9.49 33.3 9.00 28.4 8.37

0.8 0.0 53.4 9.23 48.3 9.15 45.0 9.04 41.7 8.89 38.4 8.70 33.3 8.30 28.4 7.77

30% 2.8 2.0 53.4 8.89 48.3 8.41 45.0 8.33 41.7 8.22 38.4 8.07 33.3 7.77 28.4 7.33

6.0 5.0 53.4 8.89 48.3 8.33 45.0 7.96 41.7 7.55 38.4 7.22 33.3 6.99 28.4 6.70

7.0 6.0 53.4 8.89 48.3 8.33 45.0 7.96 41.7 7.55 38.4 7.18 33.3 6.77 28.4 6.47

8.6 7.5 53.4 8.89 48.3 8.33 45.0 7.96 41.7 7.55 38.4 7.18 33.3 6.62 28.4 6.18

11.2 10.0 53.4 8.89 48.3 8.33 45.0 7.96 41.7 7.55 38.4 7.18 33.3 6.62 28.4 6.03

16.4 15.0 53.4 8.89 48.3 8.33 45.0 7.96 41.7 7.55 38.4 7.18 33.3 6.62 28.4 6.03

24.0 18.0 53.4 8.89 48.3 8.33 45.0 7.96 41.7 7.55 38.4 7.18 33.3 6.62 28.4 6.03

9
Capacity Table

2. Cooling Capacity of Indoor Unit


2-1. 4-Way Cassette Type (U1 Type)
S-22MU1E51
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 2.2 kW AIR FLOW RATE : 14.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4

21 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
14 23 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
27 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
TC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4

21 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4
15 23 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4
25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4
27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4

1 TC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4

21 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.3
16 23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4
25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4
27 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4
29 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4
TC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.4
2 21 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.1
17 23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.3
25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.4
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.4
29 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.4
TC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8 1.4
3 21 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 0.9
23 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4 1.2
18 25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7 1.4
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8 1.4
29 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8 1.4
31 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8 1.4
4 TC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.8 1.4

21 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 0.9 0.8
23 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.0
19 25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.6 1.3
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.8 1.4
29 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.8 1.4
5 31 SHC
TC
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.1
2.1
1.8
1.8
1.4
1.4

23 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.1 0.9
20 25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.4 1.1
27 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.8 1.7 1.4
29 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.1 1.8 1.4
31 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.1 1.8 1.4
6 TC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.1 1.8 1.4

23 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 0.9 0.7
21 25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.3 1.2 1.0
27 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.5 1.3
29 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.0 1.8 1.4
31 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.1 1.8 1.4
7 TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4 2.1 1.8 1.4

25 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.1 1.0 0.8
22 27 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.5 1.5 1.3 1.1
29 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.8 1.7 1.4
31 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.2 2.1 1.8 1.4
TC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.4 2.1 1.8 1.4
8 23
25 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 1.0 0.9 0.8 0.7
27 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.3 1.3 1.2 1.0
29 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.7 1.6 1.5 1.2
31 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.0 1.9 1.8 1.4

9 9-32

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-28MU1E51
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 2.8 kW AIR FLOW RATE : 14.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8

21 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
14 23 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
TC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8

21 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8
15 23 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8
25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8
TC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
1
21 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.6
16 23 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
25 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
27 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
29 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
TC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 1.8

21 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.4
2
17 23 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.7
25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 1.8
27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 1.8
29 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 1.8
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.3 1.8

21 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4 1.2
3
23 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.8 1.5
18 25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.2 1.8
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.3 1.8
29 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.3 1.8
31 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.3 1.8
TC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.3 1.8
4
21 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.2 1.0
23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.6 1.3
19 25 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.0 1.6
27 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.3 1.8
29 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.3 1.8
31 SHC
TC
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.7
2.7
2.3
2.3
1.8
1.8 5
23 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.4 1.1
20 25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.9 1.8 1.4
27 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.3 2.1 1.8
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.7 2.3 1.8
31 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.7 2.3 1.8
TC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.0 2.7 2.3 1.8 6
23 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.5 1.4 1.4 1.3 1.1 0.9
21 25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.7 1.5 1.3
27 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.1 1.9 1.6
29 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.8 2.7 2.7 2.5 2.3 1.8
31 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.0 2.7 2.3 1.8
TC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.3 3.0 2.7 2.3 1.8 7
25 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.5 1.4 1.3 1.1
22 27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.9 1.7 1.4
29 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.4 2.3 2.1 1.7
31 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.8 2.7 2.3 1.8
TC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.3 3.0 2.7 2.3 1.8

23
25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.3 1.2 1.1 0.9
8
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7 1.6 1.5 1.2
29 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.1 2.0 1.9 1.6
31 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.5 2.5 2.3 1.8

9-33 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-36MU1E51
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 3.6 kW AIR FLOW RATE : 14.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

21 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
14 23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4

21 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.2
15 23 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4
25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4

1 TC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.4

21 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 1.9
16 23 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.2
25 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.4
27 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.4
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.4
TC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.4
2 21 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.6
17 23 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.0
25 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.3
27 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.4
29 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.4
TC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.0 2.4
3 21 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7 1.4
23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.1 1.8
18 25 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.1
27 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0 2.4
29 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.0 2.4
31 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.0 2.4
4 TC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.4 3.0 2.4

21 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.5 1.2
23 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.9 1.5
19 25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.3 1.9
27 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.7 2.3
29 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.4 3.0 2.4
5 31 SHC
TC
3.6
3.8
3.6
3.8
3.6
3.8
3.6
3.8
3.6
3.8
3.6
3.8
3.6
3.8
3.6
3.8
3.6
3.8
3.6
3.8
3.6
3.8
3.6
3.8
3.6
3.8
3.4
3.4
3.0
3.0
2.4
2.4

23 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.8 1.6 1.3
20 25 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.3 2.1 1.7
27 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.7 2.5 2.1
29 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.2 2.9 2.4
31 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.4 3.0 2.4
6 TC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.4 3.0 2.4

23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.6 1.4 1.1
21 25 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.0 1.8 1.5
27 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.4 2.2 1.8
29 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 2.9 2.7 2.2
31 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.5 3.3 3.0 2.4
7 TC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 3.9 3.4 3.0 2.4

25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 1.9 1.7 1.6 1.3
22 27 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.3 2.2 2.0 1.6
29 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.8 2.6 2.4 2.0
31 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.4 3.4 3.2 3.1 2.8 2.4
TC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.5 4.5 4.3 3.9 3.4 3.0 2.4
8 23
25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.9 1.8 1.6 1.5 1.3 1.1
27 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.0 1.9 1.7 1.4
29 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.5 2.4 2.2 1.8
31 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.3 3.1 2.9 2.8 2.6 2.1

9 9-34

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-45MU1E51
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 4.5 kW AIR FLOW RATE : 15.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

21 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
14 23 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
25 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
27 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
TC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0

21 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.5
15 23 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 2.9
25 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0
27 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0
TC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.0
1
21 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.1
16 23 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.5
25 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 2.9
27 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.0
29 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.0
TC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.7 3.0

21 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 1.9
2
17 23 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.3
25 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 2.6
27 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.7 3.0
29 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.7 3.0
TC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.7 3.0

21 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.0 1.6
3
23 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.5 2.0
18 25 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 2.9 2.4
27 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.3 2.8
29 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.7 3.0
31 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.7 3.0
TC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.3 3.7 3.0
4
21 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.8 1.4
23 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.2 1.8
19 25 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.6 2.2
27 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.4 3.1 2.5
29 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.8 3.5 2.9
31 SHC
TC
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.3
4.3
3.7
3.7
3.0
3.0 5
23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.2 1.9 1.6
20 25 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.6 2.4 1.9
27 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.1 2.8 2.3
29 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.5 3.2 2.7
31 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.0 3.7 3.0
TC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 4.8 4.3 3.7 3.0 6
23 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.9 1.7 1.3
21 25 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.5 2.3 2.1 1.7
27 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.8 2.5 2.1
29 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.3 3.0 2.5
31 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.7 3.4 2.8
TC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.3 4.8 4.3 3.7 3.0 7
25 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.2 2.0 1.8 1.5
22 27 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.7 2.5 2.3 1.9
29 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.1 3.0 2.7 2.2
31 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.8 3.6 3.4 3.1 2.6
TC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.4 4.8 4.3 3.7 3.0

23
25 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.9 1.8 1.6 1.3
8
27 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.4 2.2 2.0 1.6
29 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 2.8 2.7 2.4 2.0
31 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.6 3.3 3.1 2.9 2.4

9-35 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-56MU1E51
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 5.6 kW AIR FLOW RATE : 16.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7

21 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2
14 23 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
25 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
27 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
TC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7

21 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.8
15 23 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.2
25 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7
27 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7

1 TC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 3.7

21 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.5
16 23 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 2.9
25 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.3
27 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 3.6
29 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 3.7
TC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.7 3.7
2 21 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.2
17 23 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 2.6
25 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 2.9
27 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.1 3.3
29 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.6 3.7
TC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.7 3.7
3 21 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.4 1.9
23 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 2.9 2.3
18 25 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.3 2.7
27 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7 3.1
29 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.2 3.4
31 SHC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 4.6 3.7
4 TC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.3 4.7 3.7

21 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4 2.1 1.7
23 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.6 2.1
19 25 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.4 3.0 2.5
27 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.8 3.4 2.8
29 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.3 3.9 3.2
5 31 SHC
TC
4.9
6.0
4.9
6.0
4.9
6.0
4.9
6.0
4.9
6.0
4.9
6.0
4.9
6.0
4.9
6.0
4.9
6.0
4.9
6.0
4.9
6.0
4.9
6.0
4.9
6.0
4.7
5.3
4.3
4.7
3.6
3.7

23 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.6 2.3 1.8
20 25 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0 2.7 2.2
27 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.5 3.1 2.6
29 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.0 3.6 3.0
31 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.4 4.0 3.3
6 TC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.0 5.3 4.7 3.7

23 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.5 2.3 2.0 1.6
21 25 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.0 2.7 2.4 2.0
27 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.2 2.9 2.3
29 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.7 3.3 2.7
31 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.4 4.1 3.7 3.1
7 TC 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.5 6.0 5.3 4.7 3.7

25 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.7 2.4 2.1 1.7
22 27 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.1 2.9 2.6 2.1
29 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.6 3.3 3.0 2.5
31 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.3 4.0 3.8 3.5 2.9
TC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 6.7 6.0 5.3 4.7 3.7
8 23
25 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.3 2.1 1.9 1.5
27 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 2.8 2.6 2.3 1.9
29 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.6 3.3 3.0 2.7 2.2
31 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.0 3.7 3.5 3.2 2.6

9 9-36

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-60MU1E51
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 6.0 kW AIR FLOW RATE : 21.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9

21 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9
14 23 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9
25 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9
27 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9
TC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 3.9

21 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.4
15 23 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 3.9
25 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 3.9
27 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 3.9
TC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 3.9
1
21 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.0
16 23 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 3.5
25 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 3.9
27 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 3.9
29 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 3.9
TC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.0 3.9

21 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 2.6
2
17 23 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9 3.1
25 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.5 3.6
27 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.0 3.9
29 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.0 3.9
TC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.0 3.9

21 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.8 2.2
3
23 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.4 2.8
18 25 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.0 3.3
27 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.7 3.9
29 SHC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.0 3.9
31 SHC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.0 3.9
TC 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.7 5.0 3.9
4
21 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.4 1.9
23 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.4 3.0 2.5
19 25 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.0 3.6 3.0
27 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.7 4.3 3.5
29 SHC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.4 4.9 3.9
31 SHC
TC
6.0
6.4
6.0
6.4
6.0
6.4
6.0
6.4
6.0
6.4
6.0
6.4
6.0
6.4
6.0
6.4
6.0
6.4
6.0
6.4
6.0
6.4
6.0
6.4
6.0
6.4
5.7
5.7
5.0
5.0
3.9
3.9 5
23 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 2.9 2.6 2.1
20 25 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.6 3.3 2.7
27 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.3 3.9 3.2
29 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 4.9 4.5 3.8
31 SHC 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.6 5.0 3.9
TC 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.4 5.7 5.0 3.9 6
23 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.5 2.2 1.8
21 25 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.2 2.9 2.3
27 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 3.9 3.5 2.9
29 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.8 4.5 4.1 3.4
31 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.5 5.2 4.8 3.9
TC 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.0 6.4 5.7 5.0 3.9 7
25 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0 2.8 2.5 2.0
22 27 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.7 3.5 3.1 2.6
29 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.3 4.1 3.8 3.1
31 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.3 5.0 4.8 4.4 3.7
TC 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.1 6.4 5.7 5.0 3.9

23
25 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.6 2.4 2.1 1.7
8
27 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.6 3.3 3.0 2.8 2.3
29 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.2 3.9 3.7 3.4 2.8
31 SHC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 4.9 4.6 4.4 4.0 3.3

9-37 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-73MU1E51
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 7.3 kW AIR FLOW RATE : 22.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8

21 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5
14 23 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8
25 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8
27 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8
TC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.8

21 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 3.9
15 23 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.5
25 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.8
27 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.8

1 TC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 4.8

21 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.4
16 23 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 3.9
25 SHC 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 4.5
27 SHC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 4.8
29 SHC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 4.8
TC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.1 4.8
2 21 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.7 3.0
17 23 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.4 3.5
25 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.1 4.1
27 SHC 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.7 4.6
29 SHC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.1 4.8
TC 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.1 4.8
3 21 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.2 2.6
23 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 3.9 3.2
18 25 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.5 3.7
27 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.2 4.3
29 SHC 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 5.8 4.8
31 SHC 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.1 4.8
4 TC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.0 6.1 4.8

21 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.2 2.8 2.3
23 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.5 2.8
19 25 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.6 4.1 3.4
27 SHC 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.2 4.8 3.9
29 SHC 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 5.9 5.4 4.5
5 31 SHC
TC
6.9
7.8
6.9
7.8
6.9
7.8
6.9
7.8
6.9
7.8
6.9
7.8
6.9
7.8
6.9
7.8
6.9
7.8
6.9
7.8
6.9
7.8
6.9
7.8
6.9
7.8
6.6
7.0
6.0
6.1
4.8
4.8

23 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.4 3.1 2.5
20 25 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.1 3.7 3.0
27 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.8 4.3 3.6
29 SHC 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.5 5.0 4.1
31 SHC 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.2 5.6 4.7
6 TC 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 7.8 7.0 6.1 4.8

23 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.3 3.0 2.6 2.1
21 25 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.0 3.7 3.3 2.7
27 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.7 4.4 3.9 3.2
29 SHC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.4 5.0 4.6 3.8
31 SHC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.1 5.7 5.2 4.3
7 TC 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.7 8.5 7.8 7.0 6.1 4.8

25 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.8 3.6 3.2 2.9 2.3
22 27 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.5 4.2 3.9 3.5 2.9
29 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 4.9 4.6 4.2 3.4
31 SHC 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.0 6.0 5.6 5.3 4.8 4.0
TC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 8.7 7.8 7.0 6.1 4.8
8 23
25 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.4 3.1 2.8 2.5 2.0
27 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.1 3.8 3.5 3.1 2.6
29 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.1 4.8 4.4 4.2 3.8 3.1
31 SHC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.7 5.8 5.5 5.1 4.9 4.4 3.7

9 9-38

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-90MU1E51
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 9.0 kW AIR FLOW RATE : 23.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.9

21 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0
14 23 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7
25 SHC 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.9
27 SHC 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.9
TC 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 5.9

21 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.4
15 23 SHC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.0
25 SHC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 5.6
27 SHC 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 5.9
TC 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 5.9
1
21 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 3.9
16 23 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.4
25 SHC 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 5.0
27 SHC 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 5.6
29 SHC 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 5.9
TC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.5 5.9

21 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.3 3.4
2
17 23 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.0 4.0
25 SHC 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.7 4.5
27 SHC 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.3 5.1
29 SHC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.0 5.6
TC 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 7.5 5.9

21 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 3.8 3.1
3
23 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.5 3.6
18 25 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.1 4.2
27 SHC 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 5.8 4.7
29 SHC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 6.4 5.3
31 SHC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.0 5.8
TC 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 8.6 7.5 5.9
4
21 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.4 2.7
23 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.6 4.0 3.3
19 25 SHC 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.2 4.7 3.8
27 SHC 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 5.9 5.3 4.4
29 SHC 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.6 6.0 4.9
31 SHC
TC
7.6
9.6
7.6
9.6
7.6
9.6
7.6
9.6
7.6
9.6
7.6
9.6
7.6
9.6
7.6
9.6
7.6
9.6
7.6
9.6
7.6
9.6
7.6
9.6
7.6
9.6
7.3
8.6
6.6
7.5
5.4
5.9 5
23 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.5 4.6 4.5 4.1 3.6 2.9
20 25 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.3 4.8 4.3 3.4
27 SHC 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 6.0 5.9 5.9 5.4 4.9 4.0
29 SHC 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.7 6.6 6.7 6.1 5.5 4.5
31 SHC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.4 7.3 7.4 6.8 6.2 5.1
TC 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 9.7 8.6 7.5 5.9 6
23 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.1 3.6 3.2 2.5
21 25 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.7 4.3 3.8 3.1
27 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.4 5.0 4.5 3.6
29 SHC 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.1 5.7 5.1 4.2
31 SHC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 6.8 6.3 5.7 4.7
TC 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.5 9.7 8.6 7.5 5.9 7
25 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.6 4.3 3.8 3.4 2.7
22 27 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.3 4.9 4.5 4.0 3.3
29 SHC 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.0 5.6 5.2 4.7 3.8
31 SHC 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.7 6.3 5.9 5.3 4.4
TC 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 10.7 9.7 8.6 7.5 5.9

23
25 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.2 3.8 3.4 3.0 2.4
8
27 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.1 5.1 4.9 4.4 4.0 3.6 2.9
29 SHC 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.8 5.9 5.6 5.1 4.7 4.2 3.5
31 SHC 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.5 6.6 6.3 5.8 5.4 4.9 4.0

9-39 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-106MU1E51
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 10.6 kW AIR FLOW RATE : 33.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0

21 SHC 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.5
14 23 SHC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0
25 SHC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0
27 SHC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0
TC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.0

21 SHC 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 5.6
15 23 SHC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 6.5
25 SHC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.0
27 SHC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.0

1 TC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 7.0

21 SHC 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 4.9
16 23 SHC 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 5.7
25 SHC 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 6.6
27 SHC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 7.0
29 SHC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 7.0
TC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 8.8 7.0
2 21 SHC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.4 4.3
17 23 SHC 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.4 5.1
25 SHC 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.3 5.9
27 SHC 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.3 6.7
29 SHC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 8.8 7.0
TC 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 8.8 7.0
3 21 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.7 3.8
23 SHC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 5.6 4.6
18 25 SHC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 6.6 5.4
27 SHC 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 7.5 6.2
29 SHC 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 8.4 7.0
31 SHC 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 8.8 7.0
4 TC 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.1 8.8 7.0

21 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.6 4.1 3.3
23 SHC 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.6 5.0 4.1
19 25 SHC 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.6 6.0 4.9
27 SHC 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.6 6.9 5.7
29 SHC 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 8.6 7.8 6.5
5 31 SHC
TC
10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 9.6
11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 10.1
8.8
8.8
7.0
7.0

23 SHC 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.0 4.4 3.6
20 25 SHC 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.0 5.4 4.4
27 SHC 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.6 7.5 7.6 7.0 6.3 5.2
29 SHC 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.0 7.2 6.0
31 SHC 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.0 8.2 6.8
6 TC 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 11.4 10.1 8.8 7.0

23 SHC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 4.8 4.3 3.8 3.1
21 25 SHC 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 5.8 5.3 4.8 3.9
27 SHC 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 6.8 6.3 5.7 4.7
29 SHC 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 7.9 7.3 6.6 5.5
31 SHC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 8.9 8.3 7.6 6.3
7 TC 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.4 11.4 10.1 8.8 7.0

25 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.6 5.2 4.7 4.2 3.4
22 27 SHC 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.6 6.1 5.7 5.1 4.2
29 SHC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.6 7.1 6.7 6.1 5.0
31 SHC 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.7 8.1 7.7 7.0 5.8
TC 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4 12.6 11.4 10.1 8.8 7.0
8 23
25 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.2 5.0 4.5 4.1 3.6 2.9
27 SHC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.0 5.5 5.1 4.5 3.7
29 SHC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.0 6.4 6.1 5.5 4.5
31 SHC 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.4 8.1 7.4 7.1 6.4 5.3

9 9-40

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-140MU1E51
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 14.0 kW AIR FLOW RATE : 35.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.2

21 SHC 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.6
14 23 SHC 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.6
25 SHC 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.2
27 SHC 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.2
TC 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 9.2

21 SHC 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 6.7
15 23 SHC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 7.7
25 SHC 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 8.6
27 SHC 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 9.2
TC 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 9.2
1
21 SHC 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 6.0
16 23 SHC 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 6.8
25 SHC 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 7.7
27 SHC 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 8.5
29 SHC 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 9.2
TC 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 11.7 9.2

21 SHC 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 6.7 5.3
2
17 23 SHC 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 7.7 6.1
25 SHC 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 8.7 7.0
27 SHC 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 9.7 7.8
29 SHC 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 10.7 8.6
TC 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 11.7 9.2

21 SHC 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.0 4.8
3
23 SHC 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 6.9 5.6
18 25 SHC 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 7.9 6.4
27 SHC 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 8.8 7.2
29 SHC 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 9.8 8.0
31 SHC 11.9 11.9 11.9 11.9 11.9 11.9 11.9 11.9 11.9 11.9 11.9 11.9 11.9 11.9 10.7 8.9
TC 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 13.3 11.7 9.2
4
21 SHC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.0 5.3 4.2
23 SHC 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.1 6.3 5.0
19 25 SHC 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.1 7.2 5.8
27 SHC 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.1 8.2 6.7
29 SHC 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.1 9.1 7.5
31 SHC
TC
11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.1 10.1
14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 13.3 11.7
8.3
9.2 5
23 SHC 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.1 7.0 7.1 6.3 5.6 4.5
20 25 SHC 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 7.3 6.6 5.3
27 SHC 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.2 8.4 7.5 6.1
29 SHC 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 9.4 8.5 6.9
31 SHC 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.3 11.2 11.3 10.4 9.4 7.7
TC 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.0 13.3 11.7 9.2 6
23 SHC 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.3 5.6 4.9 3.9
21 25 SHC 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.4 6.6 5.9 4.7
27 SHC 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.4 7.6 6.8 5.6
29 SHC 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.4 8.7 7.8 6.4
31 SHC 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.4 9.7 8.8 7.2
TC 16.8 16.8 16.8 16.8 16.8 16.8 16.8 16.8 16.8 16.8 16.7 16.4 15.0 13.3 11.7 9.2 7
25 SHC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.2 6.6 5.9 5.2 4.2
22 27 SHC 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.2 7.6 6.9 6.2 5.0
29 SHC 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.3 8.6 8.0 7.2 5.8
31 SHC 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.3 9.6 9.0 8.1 6.7
TC 17.7 17.7 17.7 17.7 17.7 17.7 17.7 17.7 17.7 17.7 17.7 16.7 15.0 13.3 11.7 9.2

23
25 SHC 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.5 5.9 5.2 4.6 3.7
8
27 SHC 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 7.9 8.0 7.6 6.8 6.2 5.6 4.5
29 SHC 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.1 8.6 7.8 7.3 6.5 5.3
31 SHC 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.0 10.1 9.6 8.8 8.3 7.5 6.1

9-41 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-160MU1E51
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 16.0 kW AIR FLOW RATE : 36.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.5

21 SHC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.4
14 23 SHC 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.4
25 SHC 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.5
27 SHC 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.5
TC 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 10.5

21 SHC 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 7.4
15 23 SHC 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 8.4
25 SHC 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 9.4
27 SHC 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 10.3

1 TC 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 10.5

21 SHC 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 6.6
16 23 SHC 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 7.5
25 SHC 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 8.4
27 SHC 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 9.3
29 SHC 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 10.2
TC 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.3 10.5
2 21 SHC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.5 6.0
17 23 SHC 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.6 6.8
25 SHC 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 9.6 7.6
27 SHC 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 10.6 8.5
29 SHC 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 11.6 9.3
TC 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 13.3 10.5
3 21 SHC 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 6.8 5.4
23 SHC 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 7.7 6.2
18 25 SHC 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 8.7 7.1
27 SHC 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 9.7 7.9
29 SHC 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.8 10.7 8.7
31 SHC 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 11.6 9.6
4 TC 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 15.2 13.3 10.5

21 SHC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 6.9 6.0 4.8
23 SHC 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.0 7.0 5.6
19 25 SHC 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.0 8.0 6.5
27 SHC 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.0 9.0 7.3
29 SHC 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.1 10.0 8.1
5 31 SHC
TC
12.6
17.1
12.6
17.1
12.6
17.1
12.6
17.1
12.6
17.1
12.6
17.1
12.6
17.1
12.6
17.1
12.6
17.1
12.6
17.1
12.6
17.1
12.6
17.1
12.6
17.1
12.1 11.0 9.0
15.2 13.3 10.5

23 SHC 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 7.2 6.3 5.0
20 25 SHC 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 8.2 7.3 5.9
27 SHC 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 9.3 8.3 6.7
29 SHC 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 10.3 9.3 7.6
31 SHC 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.4 11.4 10.2 8.4
6 TC 18.1 18.1 18.1 18.1 18.1 18.1 18.1 18.1 18.1 18.1 18.1 18.1 17.2 15.2 13.3 10.5

23 SHC 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.2 6.4 5.6 4.4
21 25 SHC 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.3 7.5 6.6 5.3
27 SHC 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.4 8.5 7.6 6.1
29 SHC 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.4 9.5 8.6 7.0
31 SHC 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 11.5 10.6 9.5 7.8
7 TC 19.2 19.2 19.2 19.2 19.2 19.2 19.2 19.2 19.2 19.2 19.1 18.7 17.2 15.2 13.3 10.5

25 SHC 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.1 7.5 6.7 5.9 4.7
22 27 SHC 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.4 9.2 8.5 7.8 6.9 5.6
29 SHC 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.3 9.6 8.8 7.9 6.4
31 SHC 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.4 10.6 9.8 8.9 7.2
TC 20.3 20.3 20.3 20.3 20.3 20.3 20.3 20.3 20.3 20.2 20.2 19.1 17.2 15.2 13.3 10.5
8 23
25 SHC 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 7.9 7.5 6.7 6.0 5.2 4.1
27 SHC 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.0 9.0 8.5 7.7 7.0 6.2 5.0
29 SHC 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.1 10.1 9.6 8.7 8.0 7.2 5.8
31 SHC 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 10.7 9.8 9.1 8.2 6.7

9 9-42

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-22MU1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 2.2 kW AIR FLOW RATE : 13.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4

21 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
14 23 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
27 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
TC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4

21 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4
15 23 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4
25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4
27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4
TC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4
1
21 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.2
16 23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4
25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4
27 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4
29 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4
TC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.4

21 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.1
2
17 23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.3
25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.4
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.4
29 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.4
TC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8 1.4

21 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 0.9
3
23 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4 1.2
18 25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7 1.4
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8 1.4
29 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8 1.4
31 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8 1.4
TC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.8 1.4
4
21 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 0.9 0.8
23 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.2 1.0
19 25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.6 1.3
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.8 1.4
29 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.8 1.4
31 SHC
TC
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.1
2.1
1.8
1.8
1.4
1.4 5
23 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.1 0.9
20 25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.4 1.1
27 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.8 1.7 1.4
29 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.1 1.8 1.4
31 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.1 1.8 1.4
TC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.1 1.8 1.4 6
23 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 0.9 0.7
21 25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.3 1.2 1.0
27 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.5 1.3
29 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.0 1.8 1.4
31 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.1 1.8 1.4
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4 2.1 1.8 1.4 7
25 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.1 1.0 0.8
22 27 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.5 1.5 1.3 1.1
29 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.8 1.6 1.4
31 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.2 2.1 1.8 1.4
TC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.4 2.1 1.8 1.4

23
25 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 1.0 0.9 0.8 0.7
8
27 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.3 1.3 1.2 1.0
29 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.7 1.6 1.5 1.2
31 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.0 1.9 1.8 1.4

9-43 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-28MU1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 2.8 kW AIR FLOW RATE : 13.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8

21 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
14 23 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
TC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8

21 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8
15 23 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8
25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8

1 TC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8

21 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.6
16 23 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
25 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
27 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
29 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
TC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 1.8
2 21 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.3
17 23 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.7
25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 1.8
27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 1.8
29 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 1.8
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.3 1.8
3 21 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4 1.2
23 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.8 1.5
18 25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.2 1.8
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.3 1.8
29 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.3 1.8
31 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.3 1.8
4 TC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.3 1.8

21 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.2 1.0
23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.6 1.3
19 25 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.0 1.6
27 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.3 1.8
29 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.3 1.8
5 31 SHC
TC
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.7
2.7
2.3
2.3
1.8
1.8

23 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.4 1.1
20 25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.9 1.7 1.4
27 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.3 2.1 1.8
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.7 2.3 1.8
31 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.7 2.3 1.8
6 TC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.0 2.7 2.3 1.8

23 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.1 0.9
21 25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.7 1.5 1.3
27 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.1 1.9 1.6
29 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.5 2.3 1.8
31 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.0 2.7 2.3 1.8
7 TC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.3 3.0 2.7 2.3 1.8

25 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.5 1.4 1.3 1.1
22 27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.9 1.7 1.4
29 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.3 2.1 1.7
31 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.8 2.7 2.3 1.8
TC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.3 3.0 2.7 2.3 1.8
8 23
25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.3 1.2 1.1 0.9
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.7 1.6 1.5 1.2
29 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.4 2.3 2.1 2.0 1.9 1.5
31 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.5 2.4 2.2 1.8

9 9-44

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-36MU1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 3.6 kW AIR FLOW RATE : 13.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

21 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
14 23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4

21 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.1
15 23 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4
25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4
TC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.4
1
21 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
16 23 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.1
25 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.4
27 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.4
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.4
TC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.4

21 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.6
2
17 23 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 1.9
25 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.2
27 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.4
29 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.4
TC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.0 2.4

21 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7 1.4
3
23 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.1 1.7
18 25 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.4 2.0
27 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.8 2.4
29 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.0 2.4
31 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.0 2.4
TC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.4 3.0 2.4
4
21 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.4 1.2
23 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.8 1.5
19 25 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.2 1.8
27 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.6 2.2
29 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.0 2.4
31 SHC
TC
3.6
3.8
3.6
3.8
3.6
3.8
3.6
3.8
3.6
3.8
3.6
3.8
3.6
3.8
3.6
3.8
3.6
3.8
3.6
3.8
3.6
3.8
3.6
3.8
3.6
3.8
3.4
3.4
3.0
3.0
2.4
2.4 5
23 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.8 1.6 1.3
20 25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.2 2.0 1.6
27 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.4 2.0
29 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.0 2.8 2.3
31 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.7 3.6 3.7 3.4 3.0 2.4
TC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.4 3.0 2.4 6
23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.5 1.4 1.1
21 25 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.9 1.7 1.4
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.3 2.1 1.8
29 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.1 3.0 2.9 2.8 2.5 2.1
31 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.4 3.2 2.9 2.4
TC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 3.9 3.4 3.0 2.4 7
25 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.8 1.7 1.5 1.2
22 27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.2 2.1 1.9 1.6
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.6 2.5 2.3 1.9
31 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.1 2.9 2.7 2.2
TC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.5 4.5 4.3 3.9 3.4 3.0 2.4

23
25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.6 1.4 1.3 1.0
8
27 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.3 2.2 2.0 1.9 1.7 1.4
29 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.4 2.3 2.1 1.7
31 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.8 2.7 2.4 2.0

9-45 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-45MU1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 4.5 kW AIR FLOW RATE : 15.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

21 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9
14 23 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
25 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
27 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
TC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0

21 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.5
15 23 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0
25 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0
27 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0

1 TC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.0

21 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.2
16 23 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 2.6
25 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.0
27 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.0
29 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.0
TC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.7 3.0
2 21 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 1.9
17 23 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.3
25 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.3 2.7
27 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.7 3.0
29 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.7 3.0
TC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.7 3.0
3 21 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.1 1.7
23 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.5 2.1
18 25 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0 2.4
27 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.4 2.8
29 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.7 3.0
31 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.7 3.0
4 TC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.3 3.7 3.0

21 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.8 1.4
23 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.2 1.8
19 25 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.7 2.2
27 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.4 3.1 2.6
29 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.6 3.0
5 31 SHC
TC
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.3
4.3
3.7
3.7
3.0
3.0

23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.2 1.9 1.6
20 25 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.7 2.4 2.0
27 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.1 2.9 2.4
29 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.6 3.3 2.8
31 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.1 3.7 3.0
6 TC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 4.8 4.3 3.7 3.0

23 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.9 1.7 1.3
21 25 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.4 2.1 1.7
27 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 2.8 2.6 2.1
29 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.6 3.3 3.0 2.5
31 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.0 3.8 3.5 2.9
7 TC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.3 4.8 4.3 3.7 3.0

25 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.3 2.1 1.9 1.5
22 27 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.7 2.6 2.3 1.9
29 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.4 3.2 3.0 2.8 2.3
31 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9 3.7 3.5 3.2 2.7
TC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.4 4.8 4.3 3.7 3.0
8 23
25 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.3 2.1 1.9 1.8 1.6 1.3
27 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.4 2.2 2.0 1.7
29 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 3.3 3.1 2.9 2.7 2.5 2.1
31 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.8 3.6 3.4 3.2 2.9 2.4

9 9-46

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-56MU1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 5.6 kW AIR FLOW RATE : 17.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7

21 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.4
14 23 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
25 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
27 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
TC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7

21 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0
15 23 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.4
25 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7
27 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7
TC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 3.7
1
21 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.6
16 23 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.0
25 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.5
27 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 3.7
29 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 3.7
TC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.7 3.7

21 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.8 2.3
2
17 23 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.4 2.7
25 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9 3.1
27 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.4 3.5
29 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.7 3.7
TC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.7 3.7

21 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.5 2.0
3
23 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0 2.4
18 25 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.5 2.8
27 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.0 3.3
29 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.5 3.7
31 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.7 3.7
TC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.3 4.7 3.7
4
21 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.2 1.7
23 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.7 2.2
19 25 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.5 3.1 2.6
27 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.0 3.6 3.0
29 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.5 4.1 3.4
31 SHC
TC
5.3
6.0
5.3
6.0
5.3
6.0
5.3
6.0
5.3
6.0
5.3
6.0
5.3
6.0
5.3
6.0
5.3
6.0
5.3
6.0
5.3
6.0
5.3
6.0
5.3
6.0
5.1
5.3
4.6
4.7
3.7
3.7 5
23 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.6 2.3 1.9
20 25 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.5 3.2 2.8 2.3
27 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.7 3.3 2.7
29 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.2 3.8 3.2
31 SHC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 4.7 4.3 3.6
TC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.0 5.3 4.7 3.7 6
23 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.3 2.0 1.6
21 25 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 2.8 2.5 2.0
27 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.6 3.3 3.0 2.5
29 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.1 3.9 3.5 2.9
31 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.7 4.4 4.0 3.3
TC 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.5 6.0 5.3 4.7 3.7 7
25 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.7 2.5 2.2 1.8
22 27 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.5 3.2 3.0 2.7 2.2
29 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.0 3.8 3.5 3.2 2.6
31 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.3 4.1 3.7 3.1
TC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 6.7 6.0 5.3 4.7 3.7

23
25 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.4 2.2 1.9 1.5
8
27 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 2.9 2.7 2.4 2.0
29 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.7 3.4 3.2 2.9 2.4
31 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.2 3.9 3.7 3.4 2.8

9-47 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-73MU1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 7.3 kW AIR FLOW RATE : 21.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8

21 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.4
14 23 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8
25 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8
27 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8
TC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.8

21 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 3.9
15 23 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.5
25 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.8
27 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.8

1 TC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 4.8

21 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.4
16 23 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 3.9
25 SHC 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 4.5
27 SHC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 4.8
29 SHC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 4.8
TC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.1 4.8
2 21 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.7 3.0
17 23 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.4 3.5
25 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.1 4.0
27 SHC 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.7 4.6
29 SHC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.1 4.8
TC 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.1 4.8
3 21 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.2 2.6
23 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 3.9 3.2
18 25 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.5 3.7
27 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.2 4.3
29 SHC 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 5.8 4.8
31 SHC 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.1 4.8
4 TC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.0 6.1 4.8

21 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 2.8 2.3
23 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.5 2.8
19 25 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.6 4.1 3.4
27 SHC 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.2 4.8 3.9
29 SHC 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 5.9 5.4 4.5
5 31 SHC
TC
6.9
7.8
6.9
7.8
6.9
7.8
6.9
7.8
6.9
7.8
6.9
7.8
6.9
7.8
6.9
7.8
6.9
7.8
6.9
7.8
6.9
7.8
6.9
7.8
6.9
7.8
6.6
7.0
6.0
6.1
4.8
4.8

23 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.4 3.0 2.5
20 25 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.1 3.7 3.0
27 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.8 4.3 3.6
29 SHC 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.5 5.0 4.1
31 SHC 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.2 5.6 4.7
6 TC 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 7.8 7.0 6.1 4.8

23 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.3 3.0 2.6 2.1
21 25 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.0 3.7 3.3 2.7
27 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.7 4.4 3.9 3.2
29 SHC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.4 5.0 4.6 3.8
31 SHC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.1 5.7 5.2 4.3
7 TC 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.7 8.5 7.8 7.0 6.1 4.8

25 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.8 3.6 3.2 2.9 2.3
22 27 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.5 4.2 3.9 3.5 2.9
29 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 4.9 4.6 4.2 3.4
31 SHC 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.6 5.3 4.8 4.0
TC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 8.7 7.8 7.0 6.1 4.8
8 23
25 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.4 3.1 2.8 2.5 2.0
27 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.1 3.8 3.5 3.1 2.5
29 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.1 4.8 4.4 4.2 3.8 3.1
31 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.8 5.5 5.1 4.9 4.4 3.7

9 9-48

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-106MU1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 10.6 kW AIR FLOW RATE : 33.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0

21 SHC 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.5
14 23 SHC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0
25 SHC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0
27 SHC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0
TC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.0

21 SHC 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 5.6
15 23 SHC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 6.5
25 SHC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.0
27 SHC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.0
TC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 7.0
1
21 SHC 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 4.9
16 23 SHC 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 5.7
25 SHC 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 6.6
27 SHC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 7.0
29 SHC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 7.0
TC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 8.8 7.0

21 SHC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.4 4.3
2
17 23 SHC 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.4 5.1
25 SHC 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.3 5.9
27 SHC 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.3 6.7
29 SHC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 8.8 7.0
TC 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 8.8 7.0

21 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.7 3.8
3
23 SHC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 5.6 4.6
18 25 SHC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 6.6 5.4
27 SHC 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 7.5 6.2
29 SHC 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 8.4 7.0
31 SHC 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 8.8 7.0
TC 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.1 8.8 7.0
4
21 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.6 4.1 3.3
23 SHC 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.6 5.0 4.1
19 25 SHC 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.6 6.0 4.9
27 SHC 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.6 6.9 5.7
29 SHC 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 8.6 7.8 6.5
31 SHC
TC
10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 9.6
11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 10.1
8.8
8.8
7.0
7.0 5
23 SHC 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.0 4.4 3.6
20 25 SHC 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.0 5.4 4.4
27 SHC 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.6 7.5 7.6 7.0 6.3 5.2
29 SHC 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.0 7.2 6.0
31 SHC 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.0 8.2 6.8
TC 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 11.4 10.1 8.8 7.0 6
23 SHC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 4.8 4.3 3.8 3.1
21 25 SHC 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 5.8 5.3 4.8 3.9
27 SHC 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 6.8 6.3 5.7 4.7
29 SHC 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 7.9 7.3 6.6 5.5
31 SHC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 8.9 8.3 7.6 6.3
TC 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.4 11.4 10.1 8.8 7.0 7
25 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.6 5.2 4.7 4.2 3.4
22 27 SHC 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.6 6.1 5.7 5.1 4.2
29 SHC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.6 7.1 6.7 6.1 5.0
31 SHC 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.7 8.1 7.7 7.0 5.8
TC 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4 12.6 11.4 10.1 8.8 7.0

23
25 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.2 5.0 4.5 4.1 3.6 2.9
8
27 SHC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.0 5.5 5.1 4.5 3.7
29 SHC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.0 6.4 6.1 5.5 4.5
31 SHC 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.4 8.1 7.4 7.1 6.4 5.3

9-49 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-140MU1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 14.0 kW AIR FLOW RATE : 35.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.2

21 SHC 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.6
14 23 SHC 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.6
25 SHC 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.2
27 SHC 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.2
TC 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 9.2

21 SHC 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 6.7
15 23 SHC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 7.7
25 SHC 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 8.6
27 SHC 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 9.2

1 TC 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 9.2

21 SHC 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 6.0
16 23 SHC 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 6.8
25 SHC 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 7.7
27 SHC 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 8.5
29 SHC 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 9.2
TC 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 11.7 9.2
2 21 SHC 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 6.7 5.3
17 23 SHC 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 7.7 6.1
25 SHC 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 8.7 7.0
27 SHC 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 9.7 7.8
29 SHC 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 10.7 8.6
TC 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 11.7 9.2
3 21 SHC 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.0 4.8
23 SHC 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 6.9 5.6
18 25 SHC 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.8 8.7 8.7 8.7 7.9 6.4
27 SHC 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 8.8 7.2
29 SHC 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 9.8 8.0
31 SHC 11.9 11.9 11.9 11.9 11.9 11.9 11.9 11.9 11.9 11.9 11.9 11.9 11.9 11.9 10.7 8.9
4 TC 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 13.3 11.7 9.2

21 SHC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.0 5.3 4.2
23 SHC 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.1 6.3 5.0
19 25 SHC 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.1 7.2 5.8
27 SHC 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.1 8.2 6.7
29 SHC 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.1 9.1 7.5
5 31 SHC
TC
11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.1 10.1
14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 13.3 11.7
8.3
9.2

23 SHC 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.1 7.0 7.1 6.3 5.6 4.5
20 25 SHC 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 7.3 6.6 5.3
27 SHC 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.2 8.4 7.5 6.1
29 SHC 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 9.4 8.5 6.9
31 SHC 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.3 11.2 11.3 10.4 9.4 7.7
6 TC 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.0 13.3 11.7 9.2

23 SHC 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.3 5.6 4.9 3.9
21 25 SHC 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.4 6.6 5.9 4.7
27 SHC 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.4 7.6 6.8 5.6
29 SHC 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.4 8.7 7.8 6.4
31 SHC 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.4 9.7 8.8 7.2
7 TC 16.8 16.8 16.8 16.8 16.8 16.8 16.8 16.8 16.8 16.8 16.7 16.4 15.0 13.3 11.7 9.2

25 SHC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.2 6.6 5.9 5.2 4.2
22 27 SHC 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.2 7.6 6.9 6.2 5.0
29 SHC 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.3 8.6 8.0 7.2 5.8
31 SHC 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.3 9.6 9.0 8.1 6.7
TC 17.7 17.7 17.7 17.7 17.7 17.7 17.7 17.7 17.7 17.7 17.7 16.7 15.0 13.3 11.7 9.2
8 23
25 SHC 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.5 5.9 5.2 4.6 3.7
27 SHC 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 7.9 8.0 7.6 6.8 6.2 5.6 4.5
29 SHC 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.1 8.6 7.8 7.3 6.5 5.3
31 SHC 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.0 10.1 9.6 8.8 8.3 7.5 6.1

9 9-50

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-160MU1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 16.0 kW AIR FLOW RATE : 36.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.5

21 SHC 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.5
14 23 SHC 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.6
25 SHC 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.5
27 SHC 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.5
TC 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 10.5

21 SHC 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 7.5
15 23 SHC 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 8.5
25 SHC 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 9.5
27 SHC 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 10.5
TC 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 10.5
1
21 SHC 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 6.7
16 23 SHC 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 7.6
25 SHC 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 8.5
27 SHC 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 9.5
29 SHC 12.6 12.6 12.6 12.6 12.6 12.6 12.6 12.6 12.6 12.6 12.6 12.6 12.6 12.6 12.6 10.4
TC 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.3 10.5

21 SHC 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.6 6.0
2
17 23 SHC 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 8.6 6.9
25 SHC 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 9.7 7.8
27 SHC 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 10.8 8.6
29 SHC 12.4 12.4 12.4 12.4 12.4 12.4 12.4 12.4 12.4 12.4 12.4 12.4 12.4 12.4 11.9 9.5
TC 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 13.3 10.5

21 SHC 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 6.8 5.4
3
23 SHC 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 7.8 6.3
18 25 SHC 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 8.8 7.2
27 SHC 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 9.9 8.0
29 SHC 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 10.9 8.9
31 SHC 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 11.9 9.8
TC 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 15.2 13.3 10.5
4
21 SHC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 6.9 6.0 4.8
23 SHC 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.0 7.1 5.7
19 25 SHC 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.1 8.1 6.6
27 SHC 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.2 9.1 7.4
29 SHC 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.3 10.2 8.3
31 SHC
TC
12.9
17.1
12.9
17.1
12.9
17.1
12.9
17.1
12.9
17.1
12.9
17.1
12.9
17.1
12.9
17.1
12.9
17.1
12.9
17.1
12.9
17.1
12.9
17.1
12.9
17.1
12.4 11.2 9.2
15.2 13.3 10.5 5
23 SHC 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 7.2 6.3 5.1
20 25 SHC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 8.3 7.4 6.0
27 SHC 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 9.4 8.4 6.8
29 SHC 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 10.5 9.4 7.7
31 SHC 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.6 12.5 12.6 11.6 10.5 8.6
TC 18.1 18.1 18.1 18.1 18.1 18.1 18.1 18.1 18.1 18.1 18.1 18.1 17.2 15.2 13.3 10.5 6
23 SHC 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.6 7.7 7.2 6.4 5.6 4.5
21 25 SHC 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.3 7.5 6.7 5.3
27 SHC 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.4 8.6 7.7 6.2
29 SHC 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.1 11.0 10.6 9.7 8.7 7.1
31 SHC 12.2 12.2 12.2 12.2 12.2 12.2 12.2 12.2 12.2 12.2 12.2 12.2 11.7 10.8 9.8 8.0
TC 19.2 19.2 19.2 19.2 19.2 19.2 19.2 19.2 19.2 19.2 19.1 18.7 17.2 15.2 13.3 10.5 7
25 SHC 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.3 8.2 7.5 6.7 5.9 4.8
22 27 SHC 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.3 8.6 7.8 7.0 5.6
29 SHC 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.4 9.7 8.9 8.0 6.5
31 SHC 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.7 11.5 10.8 10.0 9.0 7.4
TC 20.3 20.3 20.3 20.3 20.3 20.3 20.3 20.3 20.3 20.2 20.2 19.1 17.2 15.2 13.3 10.5

23
25 SHC 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.4 6.7 6.0 5.2 4.2
8
27 SHC 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 8.6 7.8 7.1 6.3 5.1
29 SHC 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 9.7 8.8 8.2 7.3 5.9
31 SHC 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.3 11.4 10.8 9.9 9.3 8.3 6.8

9-51 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit


2-2. 4-Way Cassette 60×60 Type (Y1 Type)
S-22MY1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 2.2 kW AIR FLOW RATE : 8.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4

21 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
14 23 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
27 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
TC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4

21 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4
15 23 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4
25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4
27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4

1 TC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4

21 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.2
16 23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4
25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4
27 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4
29 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4
TC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.4
2 21 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.0
17 23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.3
25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.4
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.4
29 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.4
TC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8 1.4
3 21 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 0.9
23 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.1
18 25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7 1.4
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8 1.4
29 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8 1.4
31 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8 1.4
4 TC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.8 1.4

21 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 0.9 0.7
23 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.2 1.0
19 25 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.5 1.3
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.8 1.4
29 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.8 1.4
5 31 SHC
TC
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.1
2.1
1.8
1.8
1.4
1.4

23 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.0 0.9
20 25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.3 1.1
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.6 1.4
29 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.8 1.4
31 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.1 1.8 1.4
6 TC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.1 1.8 1.4

23 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 0.9 0.7
21 25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.3 1.2 1.0
27 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.6 1.5 1.2
29 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.9 1.8 1.4
31 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.1 1.8 1.4
7 TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4 2.1 1.8 1.4

25 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.1 1.0 0.8
22 27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.4 1.3 1.1
29 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.8 1.7 1.6 1.3
31 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.1 2.1 1.8 1.4
TC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.4 2.1 1.8 1.4
8 23
25 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 1.0 0.9 0.8 0.7
27 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.3 1.2 1.1 0.9
29 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.6 1.6 1.4 1.2
31 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.9 1.9 1.7 1.4

9 9-52

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-28MY1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 2.8 kW AIR FLOW RATE : 8.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8

21 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
14 23 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
TC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8

21 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4
15 23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.6
25 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.8
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8
TC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
1
21 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.2
16 23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.4
25 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.6
27 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
29 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
TC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 1.8

21 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.1
2
17 23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.3
25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.5
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.6
29 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 1.8
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.3 1.8

21 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.2 1.0
3
23 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4 1.2
18 25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.6 1.3
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.9 1.5
29 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.1 1.7
31 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.3 1.8
TC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.3 1.8
4
21 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.1 0.8
23 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.3 1.0
19 25 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.5 1.2
27 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.7 1.4
29 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.9 1.6
31 SHC
TC
2.4
3.0
2.4
3.0
2.4
3.0
2.4
3.0
2.4
3.0
2.4
3.0
2.4
3.0
2.4
3.0
2.4
3.0
2.4
3.0
2.4
3.0
2.4
3.0
2.4
3.0
2.4
2.7
2.1
2.3
1.8
1.8 5
23 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.1 0.9
20 25 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.5 1.4 1.1
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7 1.6 1.3
29 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.8 1.5
31 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.2 2.0 1.7
TC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.0 2.7 2.3 1.8 6
23 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.1 1.0 0.8
21 25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.4 1.2 1.0
27 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.6 1.4 1.2
29 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.8 1.6 1.4
31 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.0 1.9 1.5
TC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.3 3.0 2.7 2.3 1.8 7
25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.3 1.2 1.1 0.9
22 27 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.4 1.3 1.0
29 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.8 1.7 1.5 1.2
31 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.0 1.9 1.7 1.4
TC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.3 3.0 2.7 2.3 1.8

23
25 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.2 1.1 0.9 0.7
8
27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.4 1.3 1.1 0.9
29 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.9 1.8 1.6 1.5 1.4 1.1
31 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.8 1.7 1.6 1.3

9-53 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-36MY1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 3.6 kW AIR FLOW RATE : 9.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

21 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1
14 23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4

21 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.9
15 23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.1
25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4

1 TC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.4

21 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.6
16 23 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 1.9
25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.2
27 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.4
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.4
TC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.4
2 21 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.4
17 23 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.7
25 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 1.9
27 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.2
29 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.4
TC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.0 2.4
3 21 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.6 1.3
23 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.9 1.5
18 25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.2 1.8
27 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.5 2.0
29 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.8 2.3
31 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.0 2.4
4 TC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.4 3.0 2.4

21 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4 1.1
23 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.7 1.4
19 25 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.0 1.6
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.3 1.9
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.6 2.1
5 31 SHC
TC
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.1
3.4
2.9
3.0
2.4
2.4

23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.9 1.8 1.8 1.7 1.5 1.2
20 25 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.0 1.8 1.4
27 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.3 2.1 1.7
29 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.4 2.0
31 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.2 3.1 3.2 2.9 2.7 2.2
6 TC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.4 3.0 2.4

23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.5 1.3 1.0
21 25 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.8 1.6 1.3
27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.1 1.9 1.5
29 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.4 2.2 1.8
31 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.7 2.5 2.1
7 TC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 3.9 3.4 3.0 2.4

25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7 1.6 1.4 1.1
22 27 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.0 1.9 1.7 1.4
29 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.3 2.2 2.0 1.6
31 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.7 2.5 2.3 1.9
TC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.5 4.5 4.3 3.9 3.4 3.0 2.4
8 23
25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.5 1.4 1.2 1.0
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.8 1.7 1.5 1.2
29 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.1 2.0 1.8 1.5
31 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.8 2.6 2.4 2.3 2.1 1.7

9 9-54

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-45MY1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 4.7 kW AIR FLOW RATE : 10.7 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

21 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
14 23 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7
25 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
27 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
TC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0

21 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.1
15 23 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4
25 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.6
27 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 2.9
TC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.0
1
21 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 1.9
16 23 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.1
25 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.4
27 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 2.6
29 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 2.9
TC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.7 3.0

21 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.7
2
17 23 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 1.9
25 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.2
27 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.4
29 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 2.6
TC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.7 3.0

21 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.9 1.5
3
23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.2 1.8
18 25 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.5 2.0
27 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.7 2.2
29 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.4 3.3 3.3 3.3 3.0 2.5
31 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.3 2.7
TC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.3 3.7 3.0
4
21 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.7 1.3
23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.2 2.0 1.6
19 25 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.5 2.3 1.8
27 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.8 2.5 2.1
29 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.1 2.8 2.3
31 SHC
TC
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.4
4.3
3.1
3.7
2.5
3.0 5
23 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.0 1.8 1.4
20 25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.3 2.1 1.7
27 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.6 2.3 1.9
29 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 2.9 2.6 2.1
31 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.2 2.9 2.4
TC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 4.8 4.3 3.7 3.0 6
23 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.0 1.8 1.6 1.3
21 25 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.3 2.1 1.9 1.5
27 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.4 2.1 1.7
29 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.9 2.7 2.4 2.0
31 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.2 3.0 2.7 2.2
TC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.3 4.8 4.3 3.7 3.0 7
25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.1 1.9 1.7 1.3
22 27 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.4 2.2 1.9 1.6
29 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.7 2.5 2.2 1.8
31 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 3.0 2.8 2.5 2.0
TC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.4 4.8 4.3 3.7 3.0

23
25 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.9 1.7 1.5 1.2
8
27 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.2 2.0 1.8 1.4
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.9 2.7 2.5 2.3 2.0 1.6
31 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.0 2.8 2.6 2.3 1.9

9-55 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-56MY1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 5.6 kW AIR FLOW RATE : 12.5 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7

21 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
14 23 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.4
25 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
27 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
TC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7

21 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.7
15 23 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.0
25 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.4
27 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7

1 TC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 3.7

21 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.4
16 23 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 2.7
25 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.0
27 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.4
29 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 3.7
TC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.7 3.7
2 21 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.1
17 23 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 2.4
25 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.4 2.8
27 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.8 3.1
29 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.2 3.4
TC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.7 3.7
3 21 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.4 1.9
23 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.8 2.2
18 25 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.1 2.5
27 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.5 2.9
29 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 3.9 3.2
31 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.2 3.5
4 TC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.3 4.7 3.7

21 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.1 1.7
23 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.5 2.0
19 25 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.2 2.9 2.3
27 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.6 3.2 2.6
29 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.0 3.6 3.0
5 31 SHC
TC
4.6
6.0
4.6
6.0
4.6
6.0
4.6
6.0
4.6
6.0
4.6
6.0
4.6
6.0
4.6
6.0
4.6
6.0
4.6
6.0
4.6
6.0
4.6
6.0
4.6
6.0
4.4
5.3
4.0
4.7
3.3
3.7

23 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.5 2.2 1.8
20 25 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 2.9 2.6 2.1
27 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.3 3.0 2.4
29 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.7 3.3 2.7
31 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.5 4.4 4.5 4.1 3.7 3.1
6 TC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.0 5.3 4.7 3.7

23 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.5 2.2 2.0 1.6
21 25 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.9 2.6 2.3 1.9
27 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.3 3.0 2.7 2.2
29 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.7 3.4 3.1 2.5
31 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.1 3.8 3.5 2.8
7 TC 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.5 6.0 5.3 4.7 3.7

25 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.6 2.4 2.1 1.7
22 27 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0 2.8 2.5 2.0
29 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7 3.4 3.2 2.8 2.3
31 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 3.8 3.6 3.2 2.6
TC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 6.7 6.0 5.3 4.7 3.7
8 23
25 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.3 2.1 1.8 1.5
27 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.0 2.7 2.5 2.2 1.8
29 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.4 3.1 2.9 2.6 2.1
31 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.8 3.5 3.3 3.0 2.4

9 9-56

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit


2-3. 2-Way Cassette Type (L1 Type)
S-22ML1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 2.2 kW AIR FLOW RATE : 8.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4

21 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
14 23 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
27 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
TC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4

21 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.3
15 23 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4
25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4
27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4
TC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4
1
21 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.1
16 23 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.3
25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4
27 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4
29 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4
TC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.4

21 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.0
2
17 23 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.2
25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.4
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.4
29 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.4
TC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8 1.4

21 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.0 0.8
3
23 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.0
18 25 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.5 1.3
27 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.8 1.4
29 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8 1.4
31 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8 1.4
TC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.8 1.4
4
21 SHC 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 0.9 0.7
23 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.1 0.9
19 25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.4 1.1
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.6 1.3
29 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.8 1.4
31 SHC
TC
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.1
2.1
1.8
1.8
1.4
1.4 5
23 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 1.0 0.8
20 25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.2 1.0
27 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.8 1.7 1.8 1.6 1.5 1.2
29 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.7 1.4
31 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.1 1.8 1.4
TC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.1 1.8 1.4 6
23 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 0.9 0.8 0.7
21 25 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.2 1.1 0.9
27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.3 1.1
29 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.7 1.6 1.3
31 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.0 1.8 1.4
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4 2.1 1.8 1.4 7
25 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 1.0 0.9 0.8
22 27 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.3 1.2 1.0
29 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.6 1.6 1.4 1.2
31 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.9 1.8 1.7 1.4
TC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.4 2.1 1.8 1.4

23
25 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 0.9 0.8 0.6
8
27 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.2 1.2 1.0 0.9
29 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.5 1.4 1.3 1.1
31 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7 1.7 1.5 1.3

9-57 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-28ML1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 2.8 kW AIR FLOW RATE : 9.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8

21 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
14 23 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
TC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8

21 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.5
15 23 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7
25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8

1 TC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8

21 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.3
16 23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.5
25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.7
27 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
29 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
TC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 1.8
2 21 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.1
17 23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.3
25 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.6
27 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 1.8
29 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 1.8
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.3 1.8
3 21 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.2 1.0
23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.5 1.2
18 25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7 1.4
27 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.0 1.6
29 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.2 1.8
31 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.3 1.8
4 TC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.3 1.8

21 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.1 0.9
23 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.3 1.1
19 25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.6 1.3
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.8 1.5
29 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.1 1.7
5 31 SHC
TC
2.6
3.0
2.6
3.0
2.6
3.0
2.6
3.0
2.6
3.0
2.6
3.0
2.6
3.0
2.6
3.0
2.6
3.0
2.6
3.0
2.6
3.0
2.6
3.0
2.6
3.0
2.5
2.7
2.3
2.3
1.8
1.8

23 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.3 1.2 0.9
20 25 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.4 1.2
27 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.8 1.7 1.4
29 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.1 1.9 1.6
31 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.2 1.8
6 TC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.0 2.7 2.3 1.8

23 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.1 1.0 0.8
21 25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.4 1.3 1.0
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.7 1.5 1.2
29 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.9 1.8 1.5
31 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.2 2.0 1.7
7 TC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.3 3.0 2.7 2.3 1.8

25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.2 1.1 0.9
22 27 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.6 1.5 1.4 1.1
29 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.8 1.6 1.3
31 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.1 2.0 1.9 1.5
TC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.3 3.0 2.7 2.3 1.8
8 23
25 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.2 1.1 1.0 0.8
27 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.4 1.3 1.2 1.0
29 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7 1.6 1.4 1.2
31 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.0 1.9 1.7 1.4

9 9-58

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-36ML1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 3.6 kW AIR FLOW RATE : 9.7 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

21 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
14 23 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3
25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4

21 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7
15 23 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.0
25 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.2
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4
TC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.4
1
21 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.5
16 23 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.0
27 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.2
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.4
TC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.4

21 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.4
2
17 23 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.6
25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 1.8
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.0
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.3
TC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.0 2.4

21 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.5 1.2
3
23 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.8 1.4
18 25 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.0 1.7
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.3 1.9
29 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.1
31 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.8 2.3
TC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.4 3.0 2.4
4
21 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4 1.1
23 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.6 1.3
19 25 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.9 1.5
27 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.1 1.7
29 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.4 2.0
31 SHC
TC
3.0
3.8
3.0
3.8
3.0
3.8
3.0
3.8
3.0
3.8
3.0
3.8
3.0
3.8
3.0
3.8
3.0
3.8
3.0
3.8
3.0
3.8
3.0
3.8
3.0
3.8
2.9
3.4
2.6
3.0
2.2
2.4 5
23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.6 1.4 1.2
20 25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.9 1.7 1.4
27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.2 2.0 1.6
29 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.4 2.2 1.8
31 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.7 2.5 2.0
TC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.4 3.0 2.4 6
23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.4 1.3 1.0
21 25 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.7 1.5 1.2
27 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.0 1.8 1.4
29 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.3 2.0 1.7
31 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.5 2.3 1.9
TC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 3.9 3.4 3.0 2.4 7
25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.7 1.5 1.4 1.1
22 27 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.0 1.8 1.6 1.3
29 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.4 2.2 2.1 1.9 1.5
31 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.5 2.3 2.1 1.7
TC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.5 4.5 4.3 3.9 3.4 3.0 2.4

23
25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.5 1.3 1.2 0.9
8
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.9 1.8 1.6 1.4 1.2
29 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.0 1.9 1.7 1.4
31 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.3 2.2 2.0 1.6

9-59 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-45ML1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 4.5 kW AIR FLOW RATE : 11.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

21 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
14 23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
25 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6
27 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
TC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0

21 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.0
15 23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.2
25 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.4
27 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.6

1 TC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.0

21 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
16 23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.0
25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.2
27 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.4
29 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.6
TC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.7 3.0
2 21 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.6
17 23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 1.8
25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.0
27 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.7 2.2
29 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.4
TC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.7 3.0
3 21 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.9 1.5
23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.1 1.7
18 25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.3 1.9
27 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.5 2.0
29 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.8 2.2
31 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0 2.4
4 TC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.3 3.7 3.0

21 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.7 1.4
23 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 1.9 1.5
19 25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4 2.2 1.7
27 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.4 1.9
29 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.6 2.1
5 31 SHC
TC
3.3
4.8
3.3
4.8
3.3
4.8
3.3
4.8
3.3
4.8
3.3
4.8
3.3
4.8
3.3
4.8
3.3
4.8
3.3
4.8
3.3
4.8
3.3
4.8
3.3
4.8
3.1
4.3
2.8
3.7
2.3
3.0

23 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.0 1.8 1.4
20 25 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.3 2.0 1.6
27 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.5 2.2 1.8
29 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.7 2.4 1.9
31 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 2.9 2.6 2.1
6 TC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 4.8 4.3 3.7 3.0

23 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.8 1.6 1.2
21 25 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.3 2.1 1.8 1.4
27 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.3 2.0 1.6
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.5 2.2 1.8
31 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.0 2.7 2.4 2.0
7 TC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.3 4.8 4.3 3.7 3.0

25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.1 1.9 1.6 1.3
22 27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4 2.1 1.9 1.5
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.6 2.3 2.1 1.7
31 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.8 2.6 2.3 1.8
TC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.4 4.8 4.3 3.7 3.0
8 23
25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.3 2.2 1.9 1.7 1.5 1.2
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4 2.2 1.9 1.7 1.3
29 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.4 2.1 1.9 1.5
31 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 3.0 2.9 2.6 2.4 2.1 1.7

9 9-60

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-56ML1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 5.6 kW AIR FLOW RATE : 11.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7

21 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1
14 23 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
25 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
27 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
TC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7

21 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.8
15 23 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.2
25 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.6
27 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7
TC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 3.7
1
21 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.4
16 23 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 2.8
25 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.2
27 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 3.5
29 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 3.7
TC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.7 3.7

21 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.2
2
17 23 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.1 2.5
25 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.6 2.9
27 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.0 3.2
29 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.4 3.6
TC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.7 3.7

21 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.4 1.9
3
23 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.8 2.3
18 25 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.2 2.6
27 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.6 3.0
29 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.1 3.3
31 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.5 3.7
TC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.3 4.7 3.7
4
21 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.1 1.7
23 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.5 2.0
19 25 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.0 2.4
27 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.7 3.4 2.8
29 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.2 3.8 3.1
31 SHC
TC
4.8
6.0
4.8
6.0
4.8
6.0
4.8
6.0
4.8
6.0
4.8
6.0
4.8
6.0
4.8
6.0
4.8
6.0
4.8
6.0
4.8
6.0
4.8
6.0
4.8
6.0
4.6
5.3
4.2
4.7
3.5
3.7 5
23 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.3 1.8
20 25 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0 2.7 2.2
27 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.4 3.1 2.5
29 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.9 3.5 2.9
31 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.7 4.6 4.7 4.3 3.9 3.2
TC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.0 5.3 4.7 3.7 6
23 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.5 2.3 2.0 1.6
21 25 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.7 2.4 1.9
27 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.4 3.1 2.8 2.3
29 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9 3.6 3.2 2.6
31 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.3 4.0 3.6 3.0
TC 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.5 6.0 5.3 4.7 3.7 7
25 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.6 2.4 2.1 1.7
22 27 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.1 2.8 2.5 2.1
29 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.8 3.8 3.5 3.3 3.0 2.4
31 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.0 3.7 3.4 2.8
TC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 6.7 6.0 5.3 4.7 3.7

23
25 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.3 2.1 1.9 1.5
8
27 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 2.8 2.5 2.3 1.8
29 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.5 3.2 3.0 2.7 2.2
31 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.0 3.6 3.4 3.1 2.5

9-61 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-73ML1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 7.3 kW AIR FLOW RATE : 19.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8

21 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9
14 23 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.3
25 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8
27 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8
TC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.8

21 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.4
15 23 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 3.9
25 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.3
27 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 4.8

1 TC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 4.8

21 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.0
16 23 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.5
25 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 3.9
27 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.3
29 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 4.7
TC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.1 4.8
2 21 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.4 2.7
17 23 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.1
25 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.4 3.5
27 SHC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 4.9 3.9
29 SHC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.4 4.3
TC 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.1 4.8
3 21 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.1 2.5
23 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.5 2.9
18 25 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.0 3.2
27 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.5 3.6
29 SHC 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 4.9 4.0
31 SHC 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.4 4.4
4 TC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.0 6.1 4.8

21 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 2.8 2.2
23 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.6 3.2 2.6
19 25 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.1 3.7 3.0
27 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.6 4.1 3.4
29 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.1 4.6 3.8
5 31 SHC
TC
5.8
7.8
5.8
7.8
5.8
7.8
5.8
7.8
5.8
7.8
5.8
7.8
5.8
7.8
5.8
7.8
5.8
7.8
5.8
7.8
5.8
7.8
5.8
7.8
5.8
7.8
5.6
7.0
5.1
6.1
4.2
4.8

23 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.3 2.9 2.3
20 25 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.8 3.3 2.7
27 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.3 3.8 3.1
29 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.7 4.3 3.5
31 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.2 4.7 3.9
6 TC 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 7.8 7.0 6.1 4.8

23 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.3 2.9 2.6 2.0
21 25 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.8 3.4 3.0 2.4
27 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.3 3.9 3.5 2.8
29 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.8 4.4 4.0 3.2
31 SHC 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.3 4.9 4.4 3.6
7 TC 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.7 8.5 7.8 7.0 6.1 4.8

25 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.4 3.1 2.7 2.2
22 27 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 3.9 3.6 3.2 2.6
29 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.7 4.4 4.0 3.6 3.0
31 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.2 4.9 4.5 4.1 3.4
TC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 8.7 7.8 7.0 6.1 4.8
8 23
25 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.4 3.1 2.7 2.4 1.9
27 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.5 3.2 2.8 2.3
29 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.6 4.7 4.4 4.0 3.7 3.3 2.7
31 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.1 5.2 4.9 4.5 4.2 3.8 3.1

9 9-62

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit


2-4. Wall Mounted Type (K1 Type)
S-22MK1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 2.2 kW AIR FLOW RATE : 9.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4

21 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
14 23 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
27 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
TC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4

21 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3
15 23 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4
25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4
27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4
TC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4
1
21 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.1
16 23 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.3
25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4
27 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4
29 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4
TC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.4

21 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.0
2
17 23 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.2
25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.4
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.4
29 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.4
TC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8 1.4

21 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 1.2 1.2 1.2 1.0 0.8
3
23 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.0
18 25 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.5 1.3
27 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.8 1.4
29 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8 1.4
31 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8 1.4
TC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.8 1.4
4
21 SHC 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 0.9 0.7
23 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.1 0.9
19 25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.4 1.1
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.6 1.3
29 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.8 1.4
31 SHC
TC
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.1
2.1
1.8
1.8
1.4
1.4 5
23 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 1.0 0.8
20 25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.2 1.0
27 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.5 1.2
29 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.7 1.4
31 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.1 1.8 1.4
TC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.1 1.8 1.4 6
23 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 0.9 0.8 0.7
21 25 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.2 1.1 0.9
27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.3 1.1
29 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.7 1.6 1.3
31 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.0 1.8 1.4
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4 2.1 1.8 1.4 7
25 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 1.0 0.9 0.8
22 27 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.3 1.2 1.0
29 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.6 1.6 1.4 1.2
31 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 1.9 1.8 1.7 1.4
TC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.4 2.1 1.8 1.4

23
25 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 0.9 0.8 0.6
8
27 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.2 1.1 1.0 0.9
29 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.5 1.4 1.3 1.1
31 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7 1.7 1.5 1.3

9-63 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-28MK1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 2.8 kW AIR FLOW RATE : 9.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8

21 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
14 23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
TC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8

21 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
15 23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.6
25 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.8
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8

1 TC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8

21 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.2
16 23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.4
25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.6
27 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
29 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
TC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 1.8
2 21 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.1
17 23 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.3
25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.4
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.6
29 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 1.8
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.3 1.8
3 21 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.0
23 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4 1.1
18 25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.6 1.3
27 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.8 1.5
29 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.0 1.7
31 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.2 1.8
4 TC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.3 1.8

21 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.1 0.8
23 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.3 1.0
19 25 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.5 1.2
27 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.7 1.4
29 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.9 1.6
5 31 SHC
TC
2.4
3.0
2.4
3.0
2.4
3.0
2.4
3.0
2.4
3.0
2.4
3.0
2.4
3.0
2.4
3.0
2.4
3.0
2.4
3.0
2.4
3.0
2.4
3.0
2.4
3.0
2.3
2.7
2.1
2.3
1.7
1.8

23 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.1 0.9
20 25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.7 1.5 1.3 1.1
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7 1.5 1.3
29 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.9 1.8 1.4
31 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.0 1.6
6 TC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.0 2.7 2.3 1.8

23 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.1 1.0 0.8
21 25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.4 1.2 1.0
27 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.6 1.4 1.2
29 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.8 1.6 1.3
31 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.3 2.2 2.2 2.0 1.8 1.5
7 TC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.3 3.0 2.7 2.3 1.8

25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.3 1.2 1.1 0.9
22 27 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.5 1.4 1.3 1.0
29 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.6 1.5 1.2
31 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.0 1.9 1.7 1.4
TC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.3 3.0 2.7 2.3 1.8
8 23
25 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.2 1.1 0.9 0.7
27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.4 1.3 1.1 0.9
29 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.6 1.5 1.3 1.1
31 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.8 1.7 1.6 1.3

9 9-64

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-36MK1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 3.6 kW AIR FLOW RATE : 10.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

21 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
14 23 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
25 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1
27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4

21 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.6
15 23 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.8
25 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.9
27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.1
TC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.4
1
21 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4
16 23 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.6
25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8
27 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 1.9
29 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.1
TC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.4

21 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.3
2
17 23 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.5
25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.6
27 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 1.8
29 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 1.9
TC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.0 2.4

21 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.5 1.2
3
23 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7 1.3
18 25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.9 1.5
27 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.1 1.7
29 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.2 1.8
31 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.4 2.0
TC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.4 3.0 2.4
4
21 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.4 1.1
23 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.6 1.2
19 25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.7 1.4
27 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 1.9 1.5
29 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.3 2.1 1.7
31 SHC
TC
2.6
3.8
2.6
3.8
2.6
3.8
2.6
3.8
2.6
3.8
2.6
3.8
2.6
3.8
2.6
3.8
2.6
3.8
2.6
3.8
2.6
3.8
2.6
3.8
2.6
3.8
2.5
3.4
2.3
3.0
1.8
2.4 5
23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.6 1.4 1.1
20 25 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.8 1.6 1.3
27 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.0 1.8 1.4
29 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.2 1.9 1.6
31 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4 2.1 1.7
TC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.4 3.0 2.4 6
23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.5 1.3 1.0
21 25 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.7 1.4 1.2
27 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.8 1.6 1.3
29 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.2 2.0 1.8 1.5
31 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4 2.2 2.0 1.6
TC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 3.9 3.4 3.0 2.4 7
25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7 1.5 1.3 1.0
22 27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.9 1.7 1.5 1.2
29 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.1 1.9 1.7 1.3
31 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.3 2.1 1.8 1.5
TC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.5 4.5 4.3 3.9 3.4 3.0 2.4

25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.7 1.5 1.4 1.2 0.9
8
23 27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.9 1.7 1.5 1.4 1.1
29 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.9 1.7 1.5 1.2
31 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.1 1.9 1.7 1.4

9-65 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-45MK1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 4.5 kW AIR FLOW RATE : 12.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

21 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8
14 23 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
25 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
27 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
TC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0

21 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.4
15 23 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.8
25 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0
27 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0

1 TC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.0

21 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.1
16 23 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.4
25 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 2.8
27 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.0
29 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.0
TC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.7 3.0
2 21 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 1.8
17 23 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.2
25 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.1 2.5
27 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.5 2.8
29 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.7 3.0
TC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.7 3.0
3 21 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.0 1.6
23 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.4 1.9
18 25 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.8 2.3
27 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.2 2.6
29 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.6 3.0
31 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.7 3.0
4 TC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.3 3.7 3.0

21 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.7 1.4
23 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.1 1.7
19 25 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.5 2.1
27 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.2 2.9 2.4
29 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.3 2.8
5 31 SHC
TC
4.3
4.8
4.3
4.8
4.3
4.8
4.3
4.8
4.3
4.8
4.3
4.8
4.3
4.8
4.3
4.8
4.3
4.8
4.3
4.8
4.3
4.8
4.3
4.8
4.3
4.8
4.1
4.3
3.7
3.7
3.0
3.0

23 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.1 1.9 1.5
20 25 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.5 2.3 1.9
27 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.0 2.7 2.2
29 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.7 3.6 3.7 3.4 3.1 2.6
31 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.8 3.5 2.9
6 TC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 4.8 4.3 3.7 3.0

23 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.8 1.6 1.3
21 25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.3 2.0 1.7
27 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.7 2.4 2.0
29 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.3 3.1 2.8 2.3
31 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.8 3.5 3.2 2.7
7 TC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.3 4.8 4.3 3.7 3.0

25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.2 2.0 1.8 1.4
22 27 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.6 2.4 2.2 1.8
29 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 3.0 2.8 2.6 2.1
31 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.4 3.3 3.0 2.5
TC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.4 4.8 4.3 3.7 3.0
8 23
25 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.9 1.7 1.5 1.2
27 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.5 2.3 2.2 1.9 1.6
29 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.7 2.6 2.3 1.9
31 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.6 3.4 3.2 3.0 2.7 2.3

9 9-66

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-56MK1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 5.6 kW AIR FLOW RATE : 14.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7

21 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2
14 23 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
25 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
27 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
TC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7

21 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.8
15 23 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.2
25 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7
27 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7
TC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 3.7
1
21 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.5
16 23 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 2.9
25 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.3
27 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 3.7
29 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 3.7
TC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.7 3.7

21 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.2
2
17 23 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 2.6
25 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 2.9
27 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.1 3.3
29 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.6 3.7
TC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.7 3.7

21 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.4 1.9
3
23 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 2.9 2.3
18 25 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.3 2.7
27 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7 3.1
29 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.2 3.4
31 SHC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 4.6 3.7
TC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.3 4.7 3.7
4
21 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.1 1.7
23 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.6 2.1
19 25 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.4 3.0 2.5
27 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.8 3.4 2.8
29 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.3 3.9 3.2
31 SHC
TC
4.9
6.0
4.9
6.0
4.9
6.0
4.9
6.0
4.9
6.0
4.9
6.0
4.9
6.0
4.9
6.0
4.9
6.0
4.9
6.0
4.9
6.0
4.9
6.0
4.9
6.0
4.7
5.3
4.3
4.7
3.6
3.7 5
23 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.6 2.3 1.8
20 25 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0 2.7 2.2
27 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.5 3.2 2.6
29 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.0 3.6 3.0
31 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.4 4.0 3.3
TC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.0 5.3 4.7 3.7 6
23 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.5 2.3 2.0 1.6
21 25 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.0 2.7 2.4 2.0
27 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.2 2.9 2.3
29 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.7 3.3 2.7
31 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.4 4.1 3.7 3.1
TC 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.5 6.0 5.3 4.7 3.7 7
25 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.7 2.4 2.2 1.7
22 27 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.1 2.9 2.6 2.1
29 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.6 3.4 3.0 2.5
31 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.3 4.0 3.8 3.5 2.9
TC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 6.7 6.0 5.3 4.7 3.7

23
25 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.4 2.1 1.9 1.5
8
27 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 2.8 2.6 2.3 1.9
29 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.6 3.3 3.0 2.7 2.2
31 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.0 3.7 3.5 3.2 2.6

9-67 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-73MK1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 7.3 kW AIR FLOW RATE : 18.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8

21 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2
14 23 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8
25 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8
27 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8
TC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.8

21 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7
15 23 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.2
25 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 4.8
27 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.8

1 TC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 4.8

21 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.2
16 23 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 3.7
25 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.2
27 SHC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 4.8
29 SHC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 4.8
TC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.1 4.8
2 21 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.6 2.9
17 23 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.2 3.3
25 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.8 3.8
27 SHC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.4 4.3
29 SHC 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.0 4.8
TC 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.1 4.8
3 21 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.2 2.5
23 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.2 4.2 4.2 3.7 3.0
18 25 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.3 3.5
27 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.9 4.0
29 SHC 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.4 4.5
31 SHC 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.0 4.8
4 TC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.0 6.1 4.8

21 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 2.8 2.2
23 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.8 3.4 2.7
19 25 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.4 3.9 3.2
27 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.0 4.5 3.7
29 SHC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.6 5.1 4.2
5 31 SHC
TC
6.4
7.8
6.4
7.8
6.4
7.8
6.4
7.8
6.4
7.8
6.4
7.8
6.4
7.8
6.4
7.8
6.4
7.8
6.4
7.8
6.4
7.8
6.4
7.8
6.4
7.8
6.2
7.0
5.6
6.1
4.7
4.8

23 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.4 3.0 2.4
20 25 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.0 3.5 2.9
27 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.6 4.1 3.4
29 SHC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.2 4.7 3.9
31 SHC 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 5.8 5.3 4.3
6 TC 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 7.8 7.0 6.1 4.8

23 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.3 3.0 2.6 2.1
21 25 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.6 3.2 2.6
27 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.5 4.2 3.7 3.1
29 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.1 4.8 4.3 3.5
31 SHC 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.8 5.4 4.9 4.0
7 TC 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.7 8.5 7.8 7.0 6.1 4.8

25 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.8 3.5 3.1 2.8 2.3
22 27 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.4 4.1 3.8 3.4 2.7
29 SHC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.0 4.7 4.4 3.9 3.2
31 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.6 5.3 5.0 4.5 3.7
TC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 8.7 7.8 7.0 6.1 4.8
8 23
25 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.4 3.1 2.8 2.4 1.9
27 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.0 3.7 3.4 3.0 2.4
29 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8 4.9 4.6 4.3 4.0 3.6 2.9
31 SHC 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.3 4.8 4.6 4.2 3.4

9 9-68

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-106MK1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 10.6 kW AIR FLOW RATE : 19.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0

21 SHC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.7
14 23 SHC 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.5
25 SHC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0
27 SHC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0
TC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.0

21 SHC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.1
15 23 SHC 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 5.8
25 SHC 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 6.5
27 SHC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.0
TC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 7.0
1
21 SHC 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 4.5
16 23 SHC 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 5.1
25 SHC 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 5.8
27 SHC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 6.4
29 SHC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 7.0
TC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 8.8 7.0

21 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.0 4.0
2
17 23 SHC 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.8 4.6
25 SHC 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.6 5.2
27 SHC 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.3 5.8
29 SHC 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.0 6.5
TC 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 8.8 7.0

21 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.5 3.6
3
23 SHC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.2 4.2
18 25 SHC 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 5.9 4.8
27 SHC 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 6.6 5.4
29 SHC 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 7.4 6.0
31 SHC 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.1 6.6
TC 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.1 8.8 7.0
4
21 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.6 4.0 3.2
23 SHC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.3 4.7 3.8
19 25 SHC 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.1 5.4 4.4
27 SHC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 6.8 6.1 5.0
29 SHC 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.6 6.9 5.6
31 SHC
TC
8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.4
11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 10.1
7.6
8.8
6.2
7.0 5
23 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 4.8 4.2 3.4
20 25 SHC 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 5.5 4.9 4.0
27 SHC 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.3 5.6 4.6
29 SHC 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.1 6.4 5.2
31 SHC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 7.8 7.1 5.8
TC 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 11.4 10.1 8.8 7.0 6
23 SHC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 4.8 4.3 3.7 3.0
21 25 SHC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.6 5.0 4.4 3.6
27 SHC 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.3 5.8 5.2 4.2
29 SHC 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.1 6.5 5.9 4.8
31 SHC 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 7.9 7.3 6.6 5.4
TC 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.4 11.4 10.1 8.8 7.0 7
25 SHC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.5 5.4 5.0 4.5 4.0 3.2
22 27 SHC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.2 5.7 5.2 4.7 3.8
29 SHC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0 6.5 6.0 5.4 4.4
31 SHC 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.8 7.2 6.7 6.1 5.0
TC 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4 12.6 11.4 10.1 8.8 7.0

23
25 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.2 5.2 4.9 4.4 4.0 3.5 2.8
8
27 SHC 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.7 5.2 4.7 4.2 3.4
29 SHC 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.5 5.9 5.5 4.9 4.0
31 SHC 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.3 6.7 6.2 5.6 4.6

9-69 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit


2-5. Ceiling Type (T1 Type)
S-36MT1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 3.6 kW AIR FLOW RATE : 12.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

21 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1
14 23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4

21 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.9
15 23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.1
25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4

1 TC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.4

21 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.6
16 23 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 1.9
25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.2
27 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.4
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.4
TC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.4
2 21 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.4
17 23 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.7
25 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 1.9
27 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.2
29 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.4
TC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.0 2.4
3 21 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.6 1.3
23 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.9 1.5
18 25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.2 1.8
27 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.5 2.0
29 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.8 2.3
31 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.0 2.4
4 TC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.4 3.0 2.4

21 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4 1.1
23 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.7 1.4
19 25 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.0 1.6
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.3 1.9
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.6 2.1
5 31 SHC
TC
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.1
3.4
2.9
3.0
2.4
2.4

23 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.7 1.5 1.2
20 25 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.0 1.8 1.4
27 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.3 2.1 1.7
29 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.4 2.0
31 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 2.9 2.7 2.2
6 TC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.4 3.0 2.4

23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.5 1.3 1.0
21 25 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.8 1.6 1.3
27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.1 1.9 1.5
29 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.4 2.2 1.8
31 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.7 2.5 2.1
7 TC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 3.9 3.4 3.0 2.4

25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7 1.6 1.4 1.1
22 27 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.0 1.9 1.7 1.4
29 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.3 2.2 2.0 1.6
31 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.7 2.5 2.3 1.9
TC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.5 4.5 4.3 3.9 3.4 3.0 2.4
8 23
25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.5 1.4 1.2 1.0
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.8 1.7 1.5 1.2
29 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.1 2.0 1.8 1.5
31 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.4 2.3 2.1 1.7

9 9-70

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-45MT1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 4.5 kW AIR FLOW RATE : 13.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

21 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
14 23 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
25 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
27 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
TC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0

21 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.5
15 23 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 2.9
25 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0
27 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0
TC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.0
1
21 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.1
16 23 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.5
25 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 2.9
27 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.0
29 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.0
TC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.7 3.0

21 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 1.9
2
17 23 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.3
25 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 2.6
27 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.7 3.0
29 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.7 3.0
TC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.7 3.0

21 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.0 1.6
3
23 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.5 2.0
18 25 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 2.9 2.4
27 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.3 2.8
29 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.7 3.0
31 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.7 3.0
TC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.3 3.7 3.0
4
21 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.8 1.4
23 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.2 1.8
19 25 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.9 2.6 2.2
27 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.4 3.1 2.5
29 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.8 3.5 2.9
31 SHC
TC
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.3
4.3
3.7
3.7
3.0
3.0 5
23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.2 1.9 1.6
20 25 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.6 2.4 1.9
27 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.4 3.1 2.8 2.3
29 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.6 3.2 2.7
31 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.0 3.7 3.0
TC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 4.8 4.3 3.7 3.0 6
23 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.9 1.7 1.3
21 25 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.5 2.3 2.1 1.7
27 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.8 2.5 2.1
29 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.3 3.0 2.5
31 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.0 3.7 3.4 2.8
TC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.3 4.8 4.3 3.7 3.0 7
25 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.4 2.2 2.0 1.8 1.5
22 27 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.7 2.5 2.3 1.9
29 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.1 3.0 2.7 2.2
31 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.6 3.4 3.2 2.6
TC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.4 4.8 4.3 3.7 3.0

23
25 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.1 1.9 1.8 1.6 1.3
8
27 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.4 2.2 2.0 1.6
29 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 2.8 2.7 2.4 2.0
31 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.6 3.3 3.2 2.9 2.4

9-71 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-56MT1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 5.6 kW AIR FLOW RATE : 13.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7

21 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
14 23 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
25 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
27 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
TC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7

21 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 2.9
15 23 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.4
25 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7
27 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7

1 TC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 3.7

21 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.5
16 23 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.0
25 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.4
27 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 3.7
29 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 3.7
TC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.7 3.7
2 21 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.2
17 23 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.3 2.7
25 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.8 3.1
27 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.3 3.5
29 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.7 3.7
TC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.7 3.7
3 21 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.8 2.8 2.8 2.5 2.0
23 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 2.9 2.4
18 25 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.4 2.8
27 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 3.9 3.2
29 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.4 3.6
31 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.7 3.7
4 TC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.3 4.7 3.7

21 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4 2.2 1.7
23 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.6 2.1
19 25 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.1 2.5
27 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.0 3.6 3.0
29 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.5 4.1 3.4
5 31 SHC
TC
5.2
6.0
5.2
6.0
5.2
6.0
5.2
6.0
5.2
6.0
5.2
6.0
5.2
6.0
5.2
6.0
5.2
6.0
5.2
6.0
5.2
6.0
5.2
6.0
5.2
6.0
5.0
5.3
4.6
4.7
3.7
3.7

23 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.6 2.3 1.9
20 25 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.1 2.8 2.3
27 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 4.0 3.6 3.3 2.7
29 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.1 3.8 3.1
31 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.7 4.2 3.5
6 TC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.0 5.3 4.7 3.7

23 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.5 2.3 2.0 1.6
21 25 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 2.8 2.5 2.0
27 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.6 3.3 3.0 2.4
29 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.1 3.8 3.5 2.9
31 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.6 4.3 3.9 3.3
7 TC 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.5 6.0 5.3 4.7 3.7

25 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.7 2.5 2.2 1.8
22 27 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.2 3.0 2.7 2.2
29 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.0 4.0 3.7 3.5 3.2 2.6
31 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.5 4.2 4.0 3.6 3.0
TC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 6.7 6.0 5.3 4.7 3.7
8 23
25 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.4 2.1 1.9 1.5
27 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.1 2.9 2.7 2.4 1.9
29 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.4 3.2 2.9 2.3
31 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.3 4.4 4.2 3.9 3.7 3.3 2.8

9 9-72

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-73MT1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 7.3 kW AIR FLOW RATE : 18.5 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8

21 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2
14 23 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8
25 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8
27 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8
TC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.8

21 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7
15 23 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.2
25 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 4.8
27 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.8
TC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 4.8
1
21 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.2
16 23 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 3.7
25 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.2
27 SHC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 4.8
29 SHC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 4.8
TC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.1 4.8

21 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.6 2.8
2
17 23 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.2 3.3
25 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.8 3.8
27 SHC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.4 4.3
29 SHC 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.0 4.8
TC 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.1 4.8

21 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.2 2.5
3
23 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.7 3.0
18 25 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.3 3.5
27 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.9 4.0
29 SHC 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.4 4.5
31 SHC 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.0 4.8
TC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.0 6.1 4.8
4
21 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 2.8 2.2
23 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.8 3.4 2.7
19 25 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.4 3.9 3.2
27 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.0 4.5 3.7
29 SHC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.6 5.1 4.2
31 SHC
TC
6.4
7.8
6.4
7.8
6.4
7.8
6.4
7.8
6.4
7.8
6.4
7.8
6.4
7.8
6.4
7.8
6.4
7.8
6.4
7.8
6.4
7.8
6.4
7.8
6.4
7.8
6.2
7.0
5.6
6.1
4.7
4.8 5
23 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.4 3.0 2.4
20 25 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.4 4.3 4.4 4.0 3.5 2.9
27 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.6 4.1 3.4
29 SHC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.2 4.7 3.9
31 SHC 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 5.8 5.3 4.3
TC 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 7.8 7.0 6.1 4.8 6
23 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.3 3.0 2.6 2.1
21 25 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.6 3.2 2.6
27 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.5 4.2 3.7 3.1
29 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.1 4.8 4.3 3.5
31 SHC 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.8 5.4 4.9 4.0
TC 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.7 8.5 7.8 7.0 6.1 4.8 7
25 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.8 3.5 3.2 2.8 2.3
22 27 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.4 4.1 3.8 3.4 2.8
29 SHC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.0 4.7 4.4 3.9 3.2
31 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.6 5.3 5.0 4.5 3.7
TC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 8.7 7.8 7.0 6.1 4.8

23
25 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.4 3.1 2.8 2.4 1.9
8
27 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.0 3.7 3.4 3.0 2.4
29 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8 4.9 4.6 4.3 4.0 3.6 2.9
31 SHC 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.3 4.8 4.6 4.1 3.4

9-73 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-106MT1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 10.6 kW AIR FLOW RATE : 27.5 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0

21 SHC 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.4
14 23 SHC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0
25 SHC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0
27 SHC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0
TC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.0

21 SHC 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 5.6
15 23 SHC 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 6.5
25 SHC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.0
27 SHC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.0

1 TC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 7.0

21 SHC 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 4.8
16 23 SHC 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 5.7
25 SHC 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 6.5
27 SHC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 7.0
29 SHC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 7.0
TC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 8.8 7.0
2 21 SHC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.4 4.3
17 23 SHC 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.3 5.0
25 SHC 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.3 5.8
27 SHC 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.2 6.6
29 SHC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 8.8 7.0
TC 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 8.8 7.0
3 21 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.7 3.8
23 SHC 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 5.6 4.5
18 25 SHC 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 6.5 5.3
27 SHC 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 7.4 6.1
29 SHC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 8.3 6.9
31 SHC 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 8.8 7.0
4 TC 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.1 8.8 7.0

21 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.6 4.1 3.3
23 SHC 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.6 5.0 4.1
19 25 SHC 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.6 5.9 4.8
27 SHC 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.6 6.8 5.6
29 SHC 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.5 7.8 6.4
5 31 SHC
TC
9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.5
11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 10.1
8.7
8.8
7.0
7.0

23 SHC 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.0 4.4 3.6
20 25 SHC 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 5.9 5.3 4.3
27 SHC 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 6.9 6.3 5.1
29 SHC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 7.9 7.2 5.9
31 SHC 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 8.9 8.1 6.7
6 TC 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 11.4 10.1 8.8 7.0

23 SHC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 4.8 4.3 3.8 3.1
21 25 SHC 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 5.8 5.3 4.7 3.8
27 SHC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 6.8 6.3 5.7 4.6
29 SHC 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 7.8 7.3 6.6 5.4
31 SHC 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 8.8 8.2 7.5 6.2
7 TC 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.4 11.4 10.1 8.8 7.0

25 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.5 5.1 4.7 4.2 3.4
22 27 SHC 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.6 6.1 5.6 5.1 4.2
29 SHC 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.6 7.0 6.6 6.0 5.0
31 SHC 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.6 8.0 7.6 6.9 5.7
TC 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4 12.6 11.4 10.1 8.8 7.0
8 23
25 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.2 5.2 5.0 4.5 4.1 3.6 2.9
27 SHC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.2 6.3 6.0 5.4 5.0 4.5 3.7
29 SHC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.0 6.4 6.0 5.4 4.5
31 SHC 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.0 7.4 7.0 6.4 5.2

9 9-74

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-140MT1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 14.0 kW AIR FLOW RATE : 30.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.2

21 SHC 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.2
14 23 SHC 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.2
25 SHC 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.2
27 SHC 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.2
TC 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 9.2

21 SHC 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.1
15 23 SHC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 8.2
25 SHC 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 9.2
27 SHC 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 9.2
TC 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 9.2
1
21 SHC 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 6.2
16 23 SHC 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 7.2
25 SHC 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 8.2
27 SHC 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 9.2
29 SHC 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 9.2
TC 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 11.7 9.2

21 SHC 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 6.9 5.5
2
17 23 SHC 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.1 6.5
25 SHC 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.3 7.4
27 SHC 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.5 8.4
29 SHC 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 11.6 9.2
TC 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 11.7 9.2

21 SHC 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.1 4.9
3
23 SHC 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 7.2 5.9
18 25 SHC 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 8.3 6.8
27 SHC 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 9.5 7.8
29 SHC 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 10.6 8.7
31 SHC 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 11.7 9.2
TC 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 13.3 11.7 9.2
4
21 SHC 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.1 5.4 4.3
23 SHC 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.3 6.5 5.2
19 25 SHC 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.5 7.6 6.2
27 SHC 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 9.6 8.7 7.1
29 SHC 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 10.8 9.8 8.1
31 SHC
TC
12.5
14.9
12.5
14.9
12.5
14.9
12.5
14.9
12.5
14.9
12.5
14.9
12.5
14.9
12.5
14.9
12.5
14.9
12.5
14.9
12.5
14.9
12.5
14.9
12.5 12.0 11.0
14.9 13.3 11.7
9.1
9.2 5
23 SHC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.2 7.1 7.2 6.5 5.7 4.6
20 25 SHC 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 7.7 6.9 5.6
27 SHC 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 8.9 8.0 6.5
29 SHC 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.0 9.1 7.5
31 SHC 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 11.2 10.2 8.5
TC 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.0 13.3 11.7 9.2 6
23 SHC 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.4 5.7 5.0 4.0
21 25 SHC 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.5 6.9 6.1 5.0
27 SHC 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.2 9.1 8.8 8.1 7.3 5.9
29 SHC 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.0 9.3 8.4 6.9
31 SHC 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.2 10.4 9.5 7.9
TC 16.8 16.8 16.8 16.8 16.8 16.8 16.8 16.8 16.8 16.8 16.7 16.4 15.0 13.3 11.7 9.2 7
25 SHC 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.3 6.7 6.1 5.4 4.4
22 27 SHC 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.6 8.5 7.9 7.3 6.5 5.3
29 SHC 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.7 9.0 8.5 7.7 6.3
31 SHC 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.0 10.2 9.7 8.8 7.3
TC 17.7 17.7 17.7 17.7 17.7 17.7 17.7 17.7 17.7 17.7 17.7 16.7 15.0 13.3 11.7 9.2

23
25 SHC 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.5 5.9 5.3 4.7 3.7
8
27 SHC 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 7.8 7.1 6.5 5.8 4.7
29 SHC 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.3 9.4 9.0 8.2 7.7 6.9 5.7
31 SHC 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.7 10.2 9.4 8.9 8.1 6.7

9-75 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit


2-6. Low Silhouette Ducted Type (F1 Type)
S-22MF1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 2.2 kW AIR FLOW RATE : 10.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4

21 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3
14 23 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
27 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
TC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4

21 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2
15 23 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.3
25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4
27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4

1 TC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4

21 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.0
16 23 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.2
25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4
27 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4
29 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4
TC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.4
2 21 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 0.9
17 23 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.1
25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.2
27 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.4
29 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.4
TC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8 1.4
3 21 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 0.8
23 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 0.9
18 25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.1
27 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.5 1.3
29 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7 1.4
31 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8 1.4
4 TC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.8 1.4

21 SHC 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 0.9 0.7
23 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.0 0.8
19 25 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.2 1.0
27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4 1.2
29 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.6 1.3
5 31 SHC
TC
2.1
2.3
2.1
2.3
2.1
2.3
2.1
2.3
2.1
2.3
2.1
2.3
2.1
2.3
2.1
2.3
2.1
2.3
2.1
2.3
2.1
2.3
2.1
2.3
2.1
2.3
2.0
2.1
1.8
1.8
1.4
1.4

23 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 0.9 0.7
20 25 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.2 1.1 0.9
27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4 1.3 1.1
29 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.6 1.5 1.2
31 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.8 1.7 1.4
6 TC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.1 1.8 1.4

23 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 0.9 0.8 0.6
21 25 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.1 1.0 0.8
27 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.3 1.2 1.0
29 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.5 1.4 1.1
31 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.7 1.6 1.3
7 TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4 2.1 1.8 1.4

25 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 1.0 0.9 0.7
22 27 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.2 1.1 0.9
29 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.4 1.3 1.0
31 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.6 1.4 1.2
TC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.4 2.1 1.8 1.4
8 23
25 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 0.9 0.8 0.8 0.6
27 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.1 1.0 0.9 0.8
29 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.3 1.3 1.1 0.9
31 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.5 1.5 1.3 1.1

9 9-76

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-28MF1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 2.8 kW AIR FLOW RATE : 10.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8

21 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6
14 23 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
TC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8

21 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4
15 23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7
25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8
TC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
1
21 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.3
16 23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.5
25 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.7
27 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
29 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
TC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 1.8

21 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.1
2
17 23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.3
25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.5
27 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.7
29 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 1.8
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.3 1.8

21 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.2 1.0
3
23 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.2
18 25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7 1.4
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.9 1.6
29 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.1 1.8
31 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.3 1.8
TC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.3 1.8
4
21 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.1 0.9
23 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.3 1.1
19 25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.5 1.2
27 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.8 1.4
29 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.0 1.6
31 SHC
TC
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.4
2.7
2.2
2.3
1.8
1.8 5
23 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.2 0.9
20 25 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.5 1.4 1.1
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.6 1.3
29 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.0 1.8 1.5
31 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.1 1.7
TC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.0 2.7 2.3 1.8 6
23 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.1 1.0 0.8
21 25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.4 1.2 1.0
27 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.6 1.5 1.2
29 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.9 1.7 1.4
31 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.1 1.9 1.6
TC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.3 3.0 2.7 2.3 1.8 7
25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.3 1.2 1.1 0.9
22 27 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.5 1.3 1.1
29 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.8 1.7 1.5 1.3
31 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.0 1.8 1.5
TC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.3 3.0 2.7 2.3 1.8

23
25 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.2 1.1 0.9 0.8
8
27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4 1.3 1.2 0.9
29 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.7 1.6 1.4 1.2
31 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.9 1.8 1.6 1.3

9-77 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-36MF1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 3.6 kW AIR FLOW RATE : 10.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

21 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
14 23 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
25 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3
27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4

21 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.6
15 23 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.9
25 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.1
27 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.3

1 TC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.4

21 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.5
16 23 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.7
25 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 1.9
27 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.0
29 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.2
TC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.4
2 21 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.3
17 23 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.5
25 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.7
27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 1.9
29 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.0
TC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.0 2.4
3 21 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.5 1.2
23 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7 1.4
18 25 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.9 1.6
27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.1 1.7
29 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4 1.9
31 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.1
4 TC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.4 3.0 2.4

21 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4 1.1
23 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.6 1.3
19 25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.8 1.4
27 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.0 1.6
29 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.2 1.8
5 31 SHC
TC
2.8
3.8
2.8
3.8
2.8
3.8
2.8
3.8
2.8
3.8
2.8
3.8
2.8
3.8
2.8
3.8
2.8
3.8
2.8
3.8
2.8
3.8
2.8
3.8
2.8
3.8
2.7
3.4
2.4
3.0
2.0
2.4

23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.6 1.4 1.1
20 25 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.8 1.6 1.3
27 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.1 1.8 1.5
29 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.3 2.0 1.7
31 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.5 2.3 1.8
6 TC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.4 3.0 2.4

23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.4 1.3 1.0
21 25 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.7 1.5 1.2
27 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.9 1.7 1.4
29 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.1 1.9 1.5
31 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.5 2.3 2.1 1.7
7 TC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 3.9 3.4 3.0 2.4

25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.7 1.5 1.3 1.1
22 27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.9 1.7 1.5 1.2
29 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.1 1.9 1.7 1.4
31 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.3 2.2 2.0 1.6
TC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.5 4.5 4.3 3.9 3.4 3.0 2.4
8 23
25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.5 1.3 1.2 0.9
27 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.7 1.6 1.4 1.1
29 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.1 2.0 1.8 1.6 1.3
31 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.2 2.0 1.8 1.5

9 9-78

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-45MF1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 4.5 kW AIR FLOW RATE : 12.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

21 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2
14 23 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
25 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7
27 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
TC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0

21 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.0
15 23 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.2
25 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.5
27 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.7
TC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.0
1
21 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
16 23 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.0
25 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.2
27 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.4
29 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 2.7
TC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.7 3.0

21 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.7
2
17 23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 1.9
25 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.1
27 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.3
29 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 2.5
TC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.7 3.0

21 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.9 1.5
3
23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.1 1.7
18 25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4 1.9
27 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.6 2.1
29 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 2.8 2.3
31 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.1 2.5
TC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.3 3.7 3.0
4
21 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.7 1.3
23 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 1.9 1.5
19 25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.2 1.7
27 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.4 2.0
29 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.7 2.2
31 SHC
TC
3.4
4.8
3.4
4.8
3.4
4.8
3.4
4.8
3.4
4.8
3.4
4.8
3.4
4.8
3.4
4.8
3.4
4.8
3.4
4.8
3.4
4.8
3.4
4.8
3.4
4.8
3.2
4.3
2.9
3.7
2.4
3.0 5
23 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.0 1.8 1.4
20 25 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.3 2.0 1.6
27 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.5 2.2 1.8
29 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.8 2.5 2.0
31 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0 2.7 2.2
TC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 4.8 4.3 3.7 3.0 6
23 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.8 1.6 1.2
21 25 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.3 2.1 1.8 1.4
27 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.3 2.1 1.7
29 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.8 2.6 2.3 1.9
31 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 2.8 2.5 2.1
TC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.3 4.8 4.3 3.7 3.0 7
25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.1 1.9 1.6 1.3
22 27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4 2.1 1.9 1.5
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.6 2.4 2.1 1.7
31 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 3.1 2.9 2.6 2.3 1.9
TC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.4 4.8 4.3 3.7 3.0

23
25 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.1 1.9 1.7 1.5 1.2
8
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.4 2.2 1.9 1.7 1.4
29 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.4 2.2 1.9 1.6
31 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.9 2.6 2.4 2.2 1.8

9-79 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-56MF1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 5.6 kW AIR FLOW RATE : 12.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7

21 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7
14 23 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
25 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2
27 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5
TC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7

21 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.4
15 23 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.7
25 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0
27 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.2

1 TC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 3.7

21 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.2
16 23 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.5
25 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 2.7
27 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 2.9
29 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.2
TC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.7 3.7
2 21 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.0
17 23 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.3
25 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.1 2.5
27 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.4 2.7
29 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 2.9
TC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.7 3.7
3 21 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.4 1.9
23 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.6 2.1
18 25 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 2.9 2.3
27 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.1 2.5
29 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.4 2.7
31 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7 3.0
4 TC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.3 4.7 3.7

21 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.2 1.7
23 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.4 1.9
19 25 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.0 2.7 2.1
27 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.3 2.9 2.4
29 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.6 3.2 2.6
5 31 SHC
TC
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
3.9
5.3
3.4
4.7
2.8
3.7

23 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.5 2.2 1.7
20 25 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.8 2.5 2.0
27 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.1 2.7 2.2
29 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.3 3.0 2.4
31 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.6 3.2 2.6
6 TC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.0 5.3 4.7 3.7

23 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.3 2.0 1.6
21 25 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.9 2.6 2.3 1.8
27 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.2 2.8 2.5 2.0
29 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.5 3.1 2.8 2.2
31 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.7 3.4 3.0 2.4
7 TC 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.5 6.0 5.3 4.7 3.7

25 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.7 2.3 2.0 1.6
22 27 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 2.9 2.6 2.3 1.8
29 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.2 2.9 2.6 2.1
31 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.8 3.5 3.2 2.8 2.3
TC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 6.7 6.0 5.3 4.7 3.7
8 23
25 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.7 2.4 2.1 1.8 1.4
27 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.0 2.7 2.4 2.1 1.7
29 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.3 3.0 2.7 2.4 1.9
31 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.6 3.2 2.9 2.6 2.1

9 9-80

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-73MF1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 7.3 kW AIR FLOW RATE : 18.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8

21 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.8
14 23 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.3
25 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8
27 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8
TC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.8

21 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.4
15 23 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 3.9
25 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.3
27 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 4.8
TC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 4.8
1
21 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.0
16 23 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.5
25 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 3.9
27 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.3
29 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 4.7
TC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.1 4.8

21 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.4 2.7
2
17 23 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.1
25 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.4 3.5
27 SHC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 4.9 3.9
29 SHC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.4 4.3
TC 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.1 4.8

21 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.1 2.5
3
23 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.6 2.9
18 25 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.0 3.2
27 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.5 3.6
29 SHC 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 4.9 4.0
31 SHC 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.4 4.4
TC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.0 6.1 4.8
4
21 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 2.8 2.2
23 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.6 3.2 2.6
19 25 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.1 3.7 3.0
27 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.6 4.1 3.4
29 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.1 4.6 3.8
31 SHC
TC
5.8
7.8
5.8
7.8
5.8
7.8
5.8
7.8
5.8
7.8
5.8
7.8
5.8
7.8
5.8
7.8
5.8
7.8
5.8
7.8
5.8
7.8
5.8
7.8
5.8
7.8
5.6
7.0
5.1
6.1
4.2
4.8 5
23 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.3 2.9 2.3
20 25 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.8 3.4 2.7
27 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.3 3.8 3.1
29 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.8 4.3 3.5
31 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.2 4.7 3.9
TC 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 7.8 7.0 6.1 4.8 6
23 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.3 2.9 2.6 2.0
21 25 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.8 3.4 3.0 2.4
27 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.3 3.9 3.5 2.8
29 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.8 4.4 3.9 3.2
31 SHC 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.3 4.9 4.4 3.6
TC 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.7 8.5 7.8 7.0 6.1 4.8 7
25 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.4 3.1 2.7 2.2
22 27 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 3.9 3.6 3.2 2.6
29 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.7 4.4 4.0 3.6 3.0
31 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.2 4.9 4.5 4.1 3.4
TC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 8.7 7.8 7.0 6.1 4.8

23
25 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.4 3.1 2.7 2.4 1.9
8
27 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.5 3.2 2.8 2.3
29 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.4 4.0 3.7 3.3 2.7
31 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.1 5.2 4.9 4.5 4.2 3.8 3.1

9-81 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-90MF1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 9.0 kW AIR FLOW RATE : 20.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9

21 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5
14 23 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9
25 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9
27 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9
TC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 3.9

21 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.1
15 23 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.6
25 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 3.9
27 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 3.9

1 TC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 3.9

21 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 2.7
16 23 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.1
25 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 3.6
27 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 3.9
29 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 3.9
TC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.0 3.9
2 21 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.4
17 23 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 2.8
25 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.0 3.2
27 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.5 3.6
29 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.0 3.9
TC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.0 3.9
3 21 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.6 2.1
23 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.1 2.5
18 25 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.6 2.9
27 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.6 4.5 4.5 4.5 4.1 3.4
29 SHC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 4.6 3.8
31 SHC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.0 3.9
4 TC 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.7 5.0 3.9

21 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.3 1.8
23 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.1 2.8 2.3
19 25 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.3 2.7
27 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.2 3.8 3.1
29 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.7 4.3 3.5
5 31 SHC
TC
5.4
6.4
5.4
6.4
5.4
6.4
5.4
6.4
5.4
6.4
5.4
6.4
5.4
6.4
5.4
6.4
5.4
6.4
5.4
6.4
5.4
6.4
5.4
6.4
5.4
6.4
5.2
5.7
4.8
5.0
3.9
3.9

23 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.8 2.5 2.0
20 25 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.3 3.0 2.4
27 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.8 3.5 2.8
29 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.4 4.0 3.3
31 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.3 5.2 5.3 4.9 4.5 3.7
6 TC 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 9.7 8.6 7.5 5.9

23 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.1 3.7 3.2 2.6
21 25 SHC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 4.9 4.4 4.0 3.2
27 SHC 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.7 5.2 4.7 3.9
29 SHC 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.8 6.7 6.5 6.0 5.5 4.5
31 SHC 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.3 6.8 6.2 5.1
7 TC 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.5 9.7 8.6 7.5 5.9

25 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.7 4.3 3.9 3.5 2.8
22 27 SHC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.5 5.1 4.7 4.2 3.5
29 SHC 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.3 5.9 5.5 5.0 4.1
31 SHC 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.1 6.7 6.3 5.7 4.7
TC 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 10.7 9.7 8.6 7.5 5.9
8 23
25 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.4 4.4 4.2 3.8 3.4 3.0 2.4
27 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.2 5.3 5.0 4.6 4.2 3.8 3.1
29 SHC 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 5.8 5.3 5.0 4.5 3.7
31 SHC 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.6 6.1 5.8 5.3 4.3

9 9-82

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-106MF1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 10.6 kW AIR FLOW RATE : 30.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0

21 SHC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.2
14 23 SHC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0
25 SHC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0
27 SHC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0
TC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.0

21 SHC 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.4
15 23 SHC 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 6.2
25 SHC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.0
27 SHC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.0
TC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 7.0
1
21 SHC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 4.7
16 23 SHC 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 5.5
25 SHC 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 6.3
27 SHC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 7.0
29 SHC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 7.0
TC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 8.8 7.0

21 SHC 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.3 4.2
2
17 23 SHC 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.2 4.9
25 SHC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.1 5.7
27 SHC 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.0 6.4
29 SHC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 8.8 7.0
TC 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 8.8 7.0

21 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.6 3.7
3
23 SHC 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 5.5 4.4
18 25 SHC 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 6.3 5.2
27 SHC 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 7.2 5.9
29 SHC 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.0 6.7
31 SHC 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 8.8 7.0
TC 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.1 8.8 7.0
4
21 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.6 4.0 3.2
23 SHC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.5 4.9 4.0
19 25 SHC 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.4 5.8 4.7
27 SHC 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.3 6.6 5.4
29 SHC 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.2 7.5 6.2
31 SHC
TC
9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.1
11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 10.1
8.3
8.8
6.9
7.0 5
23 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.9 4.3 3.5
20 25 SHC 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 5.8 5.2 4.2
27 SHC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 6.7 6.1 5.0
29 SHC 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 7.6 6.9 5.7
31 SHC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 8.5 7.8 6.5
TC 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 11.4 10.1 8.8 7.0 6
23 SHC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 4.8 4.3 3.8 3.0
21 25 SHC 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.7 5.2 4.7 3.8
27 SHC 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 6.6 6.1 5.5 4.5
29 SHC 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.6 7.0 6.4 5.2
31 SHC 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.5 7.9 7.2 6.0
TC 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.4 11.4 10.1 8.8 7.0 7
25 SHC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.5 5.1 4.6 4.1 3.3
22 27 SHC 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.5 6.0 5.5 5.0 4.0
29 SHC 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.4 6.9 6.4 5.8 4.8
31 SHC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.4 8.3 7.8 7.4 6.7 5.5
TC 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4 12.6 11.4 10.1 8.8 7.0

23
25 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.9 4.5 4.0 3.5 2.9
8
27 SHC 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 5.9 5.4 4.9 4.4 3.6
29 SHC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.2 6.8 6.3 5.9 5.3 4.3
31 SHC 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.0 8.1 7.7 7.1 6.8 6.2 5.1

9-83 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-140MF1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 14.0 kW AIR FLOW RATE : 33.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.2

21 SHC 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.5
14 23 SHC 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.4
25 SHC 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.2
27 SHC 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.2
TC 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 9.2

21 SHC 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 6.6
15 23 SHC 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 7.5
25 SHC 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 8.4
27 SHC 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 9.2

1 TC 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 9.2

21 SHC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 5.9
16 23 SHC 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 6.7
25 SHC 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 7.5
27 SHC 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 8.3
29 SHC 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 9.1
TC 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 11.7 9.2
2 21 SHC 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.6 5.3
17 23 SHC 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.6 6.0
25 SHC 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.5 6.8
27 SHC 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.5 7.6
29 SHC 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.5 8.4
TC 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 11.7 9.2
3 21 SHC 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 5.9 4.7
23 SHC 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 6.8 5.5
18 25 SHC 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 7.8 6.3
27 SHC 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 8.7 7.1
29 SHC 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 9.6 7.8
31 SHC 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 10.5 8.6
4 TC 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 13.3 11.7 9.2

21 SHC 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.0 5.3 4.2
23 SHC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.0 6.2 5.0
19 25 SHC 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.0 7.1 5.8
27 SHC 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 8.9 8.0 6.5
29 SHC 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 9.9 8.9 7.3
5 31 SHC
TC
11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 10.9 9.8
14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 13.3 11.7
8.1
9.2

23 SHC 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 6.3 5.6 4.4
20 25 SHC 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.1 7.3 6.5 5.2
27 SHC 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 8.2 7.4 6.0
29 SHC 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.1 9.2 8.3 6.8
31 SHC 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.1 10.2 9.2 7.6
6 TC 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.0 13.3 11.7 9.2

23 SHC 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.3 5.6 4.9 3.9
21 25 SHC 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.3 6.6 5.8 4.7
27 SHC 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.3 7.6 6.7 5.5
29 SHC 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.3 8.5 7.7 6.2
31 SHC 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.3 9.5 8.6 7.0
7 TC 16.8 16.8 16.8 16.8 16.8 16.8 16.8 16.8 16.8 16.8 16.7 16.4 15.0 13.3 11.7 9.2

25 SHC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.1 6.6 5.9 5.2 4.2
22 27 SHC 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.1 7.5 6.9 6.1 5.0
29 SHC 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.1 8.5 7.8 7.0 5.7
31 SHC 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.2 9.4 8.8 7.9 6.5
TC 17.7 17.7 17.7 17.7 17.7 17.7 17.7 17.7 17.7 17.7 17.7 16.7 15.0 13.3 11.7 9.2
8 23
25 SHC 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 6.9 6.9 6.5 5.9 5.2 4.6 3.6
27 SHC 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 7.9 7.9 7.5 6.8 6.2 5.5 4.4
29 SHC 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 8.9 9.0 8.5 7.8 7.1 6.4 5.2
31 SHC 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 9.9 10.0 9.5 8.7 8.1 7.3 6.0

9 9-84

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-160MF1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 16.0 kW AIR FLOW RATE : 33.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.5

21 SHC 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.2
14 23 SHC 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.5
25 SHC 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.5
27 SHC 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.5
TC 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 10.5

21 SHC 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.0
15 23 SHC 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 9.3
25 SHC 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 10.5
27 SHC 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 10.5
TC 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 10.5
1
21 SHC 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 7.0
16 23 SHC 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 8.2
25 SHC 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 9.3
27 SHC 12.6 12.6 12.6 12.6 12.6 12.6 12.6 12.6 12.6 12.6 12.6 12.6 12.6 12.6 12.6 10.4
29 SHC 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 10.5
TC 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.3 10.5

21 SHC 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 7.9 6.3
2
17 23 SHC 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.2 7.3
25 SHC 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.5 8.4
27 SHC 12.2 12.2 12.2 12.2 12.2 12.2 12.2 12.2 12.2 12.2 12.2 12.2 12.2 12.2 11.8 9.4
29 SHC 13.6 13.6 13.6 13.6 13.6 13.6 13.6 13.6 13.6 13.6 13.6 13.6 13.6 13.6 13.1 10.5
TC 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 13.3 10.5

21 SHC 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 6.9 5.5
3
23 SHC 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 8.2 6.6
18 25 SHC 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.5 10.4 10.4 10.4 9.4 7.7
27 SHC 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.8 10.6 8.7
29 SHC 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 11.9 9.8
31 SHC 14.5 14.5 14.5 14.5 14.5 14.5 14.5 14.5 14.5 14.5 14.5 14.5 14.5 14.5 13.1 10.5
TC 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 15.2 13.3 10.5
4
21 SHC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 6.9 6.1 4.9
23 SHC 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.2 7.3 5.9
19 25 SHC 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 9.6 8.6 7.0
27 SHC 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 10.9 9.8 8.0
29 SHC 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.2 11.1 9.1
31 SHC
TC
14.1
17.1
14.1
17.1
14.1
17.1
14.1
17.1
14.1
17.1
14.1
17.1
14.1
17.1
14.1
17.1
14.1
17.1
14.1
17.1
14.1
17.1
14.1
17.1
14.1
17.1
13.5 12.3 10.2
15.2 13.3 10.5 5
23 SHC 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 7.4 6.5 5.2
20 25 SHC 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 8.7 7.8 6.3
27 SHC 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.0 9.0 7.4
29 SHC 12.2 12.2 12.2 12.2 12.2 12.2 12.2 12.2 12.2 12.2 12.3 12.2 12.3 11.3 10.2 8.4
31 SHC 13.6 13.6 13.6 13.6 13.6 13.6 13.6 13.6 13.6 13.6 13.6 13.6 13.6 12.6 11.5 9.5
TC 18.1 18.1 18.1 18.1 18.1 18.1 18.1 18.1 18.1 18.1 18.1 18.1 17.2 15.2 13.3 10.5 6
23 SHC 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.2 6.5 5.7 4.5
21 25 SHC 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 8.6 7.8 6.9 5.6
27 SHC 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 9.9 9.1 8.2 6.7
29 SHC 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.3 10.4 9.4 7.8
31 SHC 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 12.6 11.7 10.7 8.8
TC 19.2 19.2 19.2 19.2 19.2 19.2 19.2 19.2 19.2 19.2 19.1 18.7 17.2 15.2 13.3 10.5 7
25 SHC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.4 8.3 7.6 6.9 6.1 4.9
22 27 SHC 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.6 8.9 8.2 7.4 6.0
29 SHC 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.0 10.2 9.5 8.6 7.1
31 SHC 12.6 12.6 12.6 12.6 12.6 12.6 12.6 12.6 12.6 12.6 12.5 12.4 11.5 10.9 9.9 8.1
TC 20.3 20.3 20.3 20.3 20.3 20.3 20.3 20.3 20.3 20.2 20.2 19.1 17.2 15.2 13.3 10.5

23
25 SHC 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.5 6.7 6.0 5.3 4.3
8
27 SHC 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.2 9.3 8.8 8.0 7.4 6.6 5.3
29 SHC 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.7 10.2 9.3 8.7 7.8 6.4
31 SHC 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.1 11.5 10.6 10.0 9.1 7.5

9-85 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit


2-7. Low Silhouette Ducted Type (F2 Type)
S-22MF2E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 2.2 kW AIR FLOW RATE : 14.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4

21 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
14 23 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
27 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
TC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4

21 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4
15 23 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4
25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4
27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4

1 TC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4

21 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.3
16 23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4
25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4
27 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4
29 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4
TC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.4
2 21 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.1
17 23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.3
25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.4
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.4
29 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.4
TC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8 1.4
3 21 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 0.9
23 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4 1.2
18 25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7 1.4
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8 1.4
29 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8 1.4
31 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8 1.4
4 TC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.8 1.4

21 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 0.9 0.8
23 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.0
19 25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.6 1.3
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.8 1.4
29 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.8 1.4
5 31 SHC
TC
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.1
2.1
1.8
1.8
1.4
1.4

23 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.1 0.9
20 25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.4 1.1
27 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.8 1.7 1.4
29 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.1 1.8 1.4
31 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.1 1.8 1.4
6 TC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.1 1.8 1.4

23 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 0.9 0.7
21 25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.3 1.2 1.0
27 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.5 1.3
29 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.0 1.8 1.4
31 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.1 1.8 1.4
7 TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4 2.1 1.8 1.4

25 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.1 1.0 0.8
22 27 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.5 1.5 1.3 1.1
29 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.8 1.7 1.4
31 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.2 2.1 1.8 1.4
TC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.4 2.1 1.8 1.4
8 23
25 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 1.0 0.9 0.8 0.7
27 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.3 1.3 1.2 1.0
29 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.7 1.6 1.5 1.2
31 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.0 1.9 1.8 1.4

9 9-86

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-28MF2E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 2.8 kW AIR FLOW RATE : 14.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8

21 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
14 23 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
TC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8

21 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8
15 23 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8
25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8
TC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
1
21 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.6
16 23 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
25 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
27 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
29 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
TC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 1.8

21 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.3
2
17 23 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.7
25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 1.8
27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 1.8
29 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 1.8
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.3 1.8

21 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4 1.2
3
23 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.8 1.5
18 25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.2 1.8
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.3 1.8
29 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.3 1.8
31 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.3 1.8
TC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.3 1.8
4
21 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.2 1.0
23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.6 1.3
19 25 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.0 1.6
27 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.3 1.8
29 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.3 1.8
31 SHC
TC
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.7
2.7
2.3
2.3
1.8
1.8 5
23 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.4 1.1
20 25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.9 1.7 1.4
27 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.3 2.1 1.8
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.7 2.3 1.8
31 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.7 2.3 1.8
TC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.0 2.7 2.3 1.8 6
23 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.5 1.4 1.4 1.3 1.1 0.9
21 25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.7 1.5 1.2
27 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.1 1.9 1.6
29 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.5 2.3 1.8
31 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.2 3.1 3.0 2.7 2.3 1.8
TC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.3 3.0 2.7 2.3 1.8 7
25 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.5 1.4 1.3 1.1
22 27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.9 1.8 1.7 1.4
29 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.3 2.3 2.1 1.7
31 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.8 2.7 2.3 1.8
TC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.3 3.0 2.7 2.3 1.8

23
25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.3 1.2 1.1 0.9
8
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.7 1.6 1.5 1.2
29 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.4 2.3 2.1 2.0 1.8 1.5
31 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.8 2.7 2.5 2.4 2.2 1.8

9-87 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-36MF2E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 3.6 kW AIR FLOW RATE : 14.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

21 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
14 23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4

21 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.2
15 23 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4
25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4

1 TC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.4

21 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 1.9
16 23 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.3
25 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.4
27 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.4
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.4
TC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.4
2 21 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.6
17 23 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.0
25 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.4
27 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.4
29 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.4
TC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.0 2.4
3 21 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7 1.4
23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.2 1.8
18 25 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.6 2.2
27 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.0 2.4
29 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.0 2.4
31 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.0 2.4
4 TC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.4 3.0 2.4

21 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.5 1.2
23 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.9 1.6
19 25 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.4 1.9
27 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 2.8 2.3
29 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.4 3.0 2.4
5 31 SHC
TC
3.6
3.8
3.6
3.8
3.6
3.8
3.6
3.8
3.6
3.8
3.6
3.8
3.6
3.8
3.6
3.8
3.6
3.8
3.6
3.8
3.6
3.8
3.6
3.8
3.6
3.8
3.4
3.4
3.0
3.0
2.4
2.4

23 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.8 1.7 1.4
20 25 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.3 2.1 1.7
27 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.8 2.5 2.1
29 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.3 3.0 2.4
31 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.4 3.0 2.4
6 TC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.4 3.0 2.4

23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.6 1.4 1.1
21 25 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.0 1.8 1.5
27 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.5 2.3 1.9
29 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 3.0 2.7 2.3
31 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.6 3.4 3.0 2.4
7 TC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 3.9 3.4 3.0 2.4

25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.9 1.8 1.6 1.3
22 27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.4 2.2 2.0 1.7
29 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 3.0 2.8 2.7 2.5 2.1
31 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.3 3.2 2.9 2.4
TC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.5 4.5 4.3 3.9 3.4 3.0 2.4
8 23
25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.6 1.5 1.3 1.1
27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.4 2.3 2.1 2.0 1.8 1.4
29 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.5 2.4 2.2 1.8
31 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 3.0 2.9 2.7 2.2

9 9-88

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-45MF2E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 4.5 kW AIR FLOW RATE : 14.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

21 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
14 23 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
25 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
27 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
TC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0

21 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.5
15 23 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 2.9
25 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0
27 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0
TC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.0
1
21 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.1
16 23 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.5
25 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 2.9
27 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.0
29 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.0
TC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.7 3.0

21 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 1.9
2
17 23 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.2
25 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 2.6
27 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.7 3.0
29 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.7 3.0
TC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.7 3.0

21 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.0 1.6
3
23 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.5 2.0
18 25 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 2.9 2.4
27 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.3 2.8
29 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.7 3.0
31 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.7 3.0
TC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.3 3.7 3.0
4
21 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.8 1.4
23 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.2 1.8
19 25 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.6 2.2
27 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.4 3.1 2.5
29 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.8 3.5 2.9
31 SHC
TC
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.3
4.3
3.7
3.7
3.0
3.0 5
23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.2 1.9 1.6
20 25 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.6 2.4 1.9
27 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.1 2.8 2.3
29 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.5 3.2 2.7
31 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.0 3.7 3.0
TC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 4.8 4.3 3.7 3.0 6
23 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.9 1.7 1.3
21 25 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.5 2.3 2.1 1.7
27 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.8 2.5 2.1
29 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.3 3.0 2.5
31 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.7 3.4 2.8
TC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.3 4.8 4.3 3.7 3.0 7
25 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.2 2.0 1.8 1.5
22 27 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.7 2.5 2.3 1.9
29 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.1 3.0 2.7 2.2
31 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.8 3.6 3.4 3.1 2.6
TC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.4 4.8 4.3 3.7 3.0

23
25 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.1 1.9 1.8 1.6 1.3
8
27 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.4 2.2 2.0 1.6
29 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 2.8 2.7 2.4 2.0
31 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.6 3.3 3.2 2.9 2.4

9-89 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-56MF2E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 5.6 kW AIR FLOW RATE : 16.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7

21 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5
14 23 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
25 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
27 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
TC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7

21 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.0
15 23 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.5
25 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7
27 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7

1 TC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 3.7

21 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 2.6
16 23 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.1
25 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 3.5
27 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 3.7
29 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 3.7
TC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.7 3.7
2 21 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.3
17 23 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.4 2.7
25 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.2
27 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.5 3.6
29 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.7 3.7
TC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.7 3.7
3 21 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.5 2.0
23 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0 2.5
18 25 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.5 2.9
27 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.0 3.3
29 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.5 3.7
31 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.7 3.7
4 TC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.3 4.7 3.7

21 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.2 1.7
23 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.7 2.2
19 25 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.5 3.2 2.6
27 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.1 3.7 3.1
29 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.6 4.2 3.5
5 31 SHC
TC
5.4
6.0
5.4
6.0
5.4
6.0
5.4
6.0
5.4
6.0
5.4
6.0
5.4
6.0
5.4
6.0
5.4
6.0
5.4
6.0
5.4
6.0
5.4
6.0
5.4
6.0
5.2
5.3
4.7
4.7
3.7
3.7

23 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.6 2.4 1.9
20 25 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.2 2.9 2.4
27 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.1 4.0 4.1 3.7 3.4 2.8
29 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.3 3.9 3.2
31 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.8 4.4 3.7
6 TC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.0 5.3 4.7 3.7

23 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.3 2.0 1.6
21 25 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.1 2.8 2.6 2.1
27 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.4 3.1 2.5
29 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.2 3.9 3.6 3.0
31 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 5.0 4.9 4.8 4.5 4.1 3.4
7 TC 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.5 6.0 5.3 4.7 3.7

25 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.7 2.5 2.2 1.8
22 27 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.3 3.0 2.7 2.2
29 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.8 3.6 3.3 2.7
31 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.6 4.4 4.1 3.8 3.1
TC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 6.7 6.0 5.3 4.7 3.7
8 23
25 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.4 2.2 1.9 1.5
27 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.4 3.2 2.9 2.7 2.4 2.0
29 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.8 3.4 3.3 2.9 2.4
31 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.3 4.0 3.8 3.5 2.9

9 9-90

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-60MF2E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 6.0 kW AIR FLOW RATE : 21.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9

21 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9
14 23 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9
25 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9
27 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9
TC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 3.9

21 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.5
15 23 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 3.9
25 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 3.9
27 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 3.9
TC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 3.9
1
21 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.0
16 23 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 3.6
25 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 3.9
27 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 3.9
29 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 3.9
TC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.0 3.9

21 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 2.6
2
17 23 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.0 3.2
25 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.7 3.8
27 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.0 3.9
29 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.0 3.9
TC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.0 3.9

21 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.8 2.3
3
23 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.5 2.9
18 25 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.2 3.4
27 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 4.8 3.9
29 SHC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.0 3.9
31 SHC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.0 3.9
TC 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.7 5.0 3.9
4
21 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.4 1.9
23 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.4 3.1 2.5
19 25 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.1 3.8 3.1
27 SHC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 4.8 4.4 3.7
29 SHC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.5 5.0 3.9
31 SHC
TC
6.0
6.4
6.0
6.4
6.0
6.4
6.0
6.4
6.0
6.4
6.0
6.4
6.0
6.4
6.0
6.4
6.0
6.4
6.0
6.4
6.0
6.4
6.0
6.4
6.0
6.4
5.7
5.7
5.0
5.0
3.9
3.9 5
23 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0 2.7 2.2
20 25 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.7 3.4 2.8
27 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.8 4.7 4.8 4.4 4.0 3.3
29 SHC 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.1 4.7 3.9
31 SHC 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 5.7 5.0 3.9
TC 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.4 5.7 5.0 3.9 6
23 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.8 2.6 2.3 1.8
21 25 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.5 3.3 2.9 2.4
27 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.3 4.0 3.6 3.0
29 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.0 4.7 4.3 3.6
31 SHC 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.7 5.4 5.0 3.9
TC 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.0 6.4 5.7 5.0 3.9 7
25 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.1 2.8 2.5 2.1
22 27 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.0 3.8 3.6 3.2 2.6
29 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.5 4.3 3.9 3.2
31 SHC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.5 5.2 5.0 4.6 3.8
TC 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.1 6.4 5.7 5.0 3.9

23
25 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 3.0 2.9 2.6 2.4 2.1 1.7
8
27 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.6 3.3 3.1 2.8 2.3
29 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.6 4.4 4.0 3.8 3.5 2.9
31 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.1 4.7 4.5 4.2 3.5

9-91 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-73MF2E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 7.3 kW AIR FLOW RATE : 21.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8

21 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3
14 23 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8
25 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8
27 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8
TC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.8

21 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7
15 23 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.3
25 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.8
27 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.8

1 TC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 4.8

21 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.3
16 23 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 3.8
25 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.3
27 SHC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 4.8
29 SHC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 4.8
TC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.1 4.8
2 21 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.6 2.9
17 23 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.2 3.4
25 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.8 3.9
27 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.5 4.4
29 SHC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.1 4.8
TC 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.1 4.8
3 21 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.2 2.6
23 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.8 3.1
18 25 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.4 3.6
27 SHC 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 4.9 4.1
29 SHC 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 5.5 4.6
31 SHC 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.1 4.8
4 TC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.0 6.1 4.8

21 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 2.8 2.2
23 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.8 3.4 2.7
19 25 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.4 4.0 3.2
27 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.0 4.6 3.7
29 SHC 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.7 5.1 4.2
5 31 SHC
TC
6.5
7.8
6.5
7.8
6.5
7.8
6.5
7.8
6.5
7.8
6.5
7.8
6.5
7.8
6.5
7.8
6.5
7.8
6.5
7.8
6.5
7.8
6.5
7.8
6.5
7.8
6.3
7.0
5.7
6.1
4.7
4.8

23 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.4 3.0 2.4
20 25 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.0 3.6 2.9
27 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.6 4.2 3.4
29 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.2 4.8 3.9
31 SHC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 5.9 5.3 4.4
6 TC 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 7.8 7.0 6.1 4.8

23 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.3 3.0 2.6 2.1
21 25 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.6 3.2 2.6
27 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.6 4.2 3.8 3.1
29 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.2 4.8 4.4 3.6
31 SHC 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 5.8 5.5 5.0 4.1
7 TC 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.7 8.5 7.8 7.0 6.1 4.8

25 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.8 3.5 3.2 2.8 2.3
22 27 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.4 4.1 3.8 3.4 2.8
29 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.1 4.7 4.4 4.0 3.3
31 SHC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.7 5.3 5.1 4.6 3.8
TC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 8.7 7.8 7.0 6.1 4.8
8 23
25 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.4 3.1 2.8 2.4 2.0
27 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.3 4.0 3.7 3.4 3.0 2.5
29 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.7 4.3 4.0 3.6 3.0
31 SHC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.5 5.6 5.3 4.9 4.6 4.2 3.5

9 9-92

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-90MF2E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 9.0 kW AIR FLOW RATE : 25.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.9

21 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.1
14 23 SHC 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.8
25 SHC 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.9
27 SHC 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.9
TC 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 5.9

21 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.5
15 23 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.1
25 SHC 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 5.8
27 SHC 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 5.9
TC 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 5.9
1
21 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 3.9
16 23 SHC 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 4.5
25 SHC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 5.2
27 SHC 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 5.8
29 SHC 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 5.9
TC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.5 5.9

21 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.4 3.5
2
17 23 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.1 4.1
25 SHC 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 5.8 4.7
27 SHC 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.5 5.2
29 SHC 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.3 5.8
TC 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 7.5 5.9

21 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 3.9 3.1
3
23 SHC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 4.6 3.7
18 25 SHC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.2 4.3
27 SHC 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 5.9 4.9
29 SHC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 6.6 5.4
31 SHC 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 7.3 5.9
TC 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 8.6 7.5 5.9
4
21 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.4 2.7
23 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.6 4.1 3.3
19 25 SHC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.3 4.8 3.9
27 SHC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.1 5.5 4.5
29 SHC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 6.8 6.1 5.1
31 SHC
TC
7.8
9.6
7.8
9.6
7.8
9.6
7.8
9.6
7.8
9.6
7.8
9.6
7.8
9.6
7.8
9.6
7.8
9.6
7.8
9.6
7.8
9.6
7.8
9.6
7.8
9.6
7.5
8.6
6.8
7.5
5.6
5.9 5
23 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.1 3.6 2.9
20 25 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 4.8 4.3 3.5
27 SHC 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 5.6 5.0 4.1
29 SHC 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.3 5.7 4.7
31 SHC 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.0 6.4 5.3
TC 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 9.7 8.6 7.5 5.9 6
23 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.1 3.6 3.2 2.5
21 25 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.8 4.4 3.9 3.1
27 SHC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.5 5.1 4.6 3.7
29 SHC 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.3 5.8 5.2 4.3
31 SHC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.0 6.5 5.9 4.9
TC 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.5 9.7 8.6 7.5 5.9 7
25 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.6 4.3 3.9 3.4 2.8
22 27 SHC 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.4 5.0 4.6 4.1 3.3
29 SHC 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.1 5.7 5.3 4.8 3.9
31 SHC 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 6.9 6.4 6.0 5.5 4.5
TC 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 10.7 9.7 8.6 7.5 5.9

23
25 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.2 3.8 3.4 3.0 2.4
8
27 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.9 4.5 4.1 3.7 3.0
29 SHC 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.7 5.2 4.8 4.4 3.6
31 SHC 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.4 5.9 5.6 5.0 4.2

9-93 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-106MF2E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 10.6 kW AIR FLOW RATE : 32.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0

21 SHC 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.8
14 23 SHC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0
25 SHC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0
27 SHC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0
TC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.0

21 SHC 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 5.9
15 23 SHC 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 6.9
25 SHC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.0
27 SHC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.0

1 TC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 7.0

21 SHC 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 5.1
16 23 SHC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 6.0
25 SHC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 7.0
27 SHC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 7.0
29 SHC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 7.0
TC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 8.8 7.0
2 21 SHC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.6 4.4
17 23 SHC 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.6 5.3
25 SHC 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 7.7 6.2
27 SHC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 8.8 7.0
29 SHC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 8.8 7.0
TC 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 8.8 7.0
3 21 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.8 3.9
23 SHC 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 5.9 4.8
18 25 SHC 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 6.9 5.7
27 SHC 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 7.9 6.6
29 SHC 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 8.8 7.0
31 SHC 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 8.8 7.0
4 TC 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.1 8.8 7.0

21 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.7 4.2 3.3
23 SHC 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 5.8 5.2 4.2
19 25 SHC 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 6.9 6.2 5.1
27 SHC 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.0 7.3 6.0
29 SHC 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.1 8.3 6.9
5 31 SHC
TC
10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.1
11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 10.1
8.8
8.8
7.0
7.0

23 SHC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.1 4.6 3.7
20 25 SHC 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.2 5.6 4.6
27 SHC 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.3 6.6 5.5
29 SHC 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.1 9.0 9.1 8.4 7.7 6.4
31 SHC 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 9.5 8.8 7.0
6 TC 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 11.4 10.1 8.8 7.0

23 SHC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 4.9 4.4 3.9 3.2
21 25 SHC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.0 5.5 5.0 4.0
27 SHC 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.5 7.4 7.1 6.6 6.0 4.9
29 SHC 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.3 7.7 7.1 5.8
31 SHC 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.8 9.7 9.4 8.8 8.1 6.7
7 TC 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.4 11.4 10.1 8.8 7.0

25 SHC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.7 5.3 4.8 4.3 3.5
22 27 SHC 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.8 6.4 5.9 5.4 4.4
29 SHC 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.0 7.5 7.0 6.4 5.3
31 SHC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.1 8.6 8.2 7.5 6.2
TC 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4 12.6 11.4 10.1 8.8 7.0
8 23
25 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.0 4.6 4.1 3.7 3.0
27 SHC 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.4 6.5 6.2 5.7 5.3 4.7 3.9
29 SHC 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.3 6.7 6.4 5.8 4.8
31 SHC 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.7 8.8 8.5 7.8 7.5 6.8 5.7

9 9-94

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-140MF2E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 14.0 kW AIR FLOW RATE : 34.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.2

21 SHC 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.8
14 23 SHC 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 8.9
25 SHC 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.2
27 SHC 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.2
TC 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 9.2

21 SHC 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 6.9
15 23 SHC 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 7.9
25 SHC 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 8.9
27 SHC 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 9.2
TC 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 9.2
1
21 SHC 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 6.1
16 23 SHC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 7.0
25 SHC 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 7.9
27 SHC 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 8.8
29 SHC 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 9.2
TC 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 11.7 9.2

21 SHC 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 6.8 5.4
2
17 23 SHC 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 7.9 6.3
25 SHC 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 8.9 7.1
27 SHC 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.0 8.0
29 SHC 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.1 8.9
TC 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 11.7 9.2

21 SHC 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.0 4.8
3
23 SHC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.0 5.7
18 25 SHC 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.1 6.6
27 SHC 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 9.1 7.4
29 SHC 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 10.1 8.3
31 SHC 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 11.1 9.2
TC 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 13.3 11.7 9.2
4
21 SHC 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.1 5.3 4.2
23 SHC 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.1 6.3 5.1
19 25 SHC 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.2 7.4 6.0
27 SHC 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.3 8.4 6.9
29 SHC 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.4 9.4 7.7
31 SHC
TC
11.9 11.9 11.9 11.9 11.9 11.9 11.9 11.9 11.9 11.9 11.9 11.9 11.9 11.5 10.4
14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 13.3 11.7
8.6
9.2 5
23 SHC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 6.4 5.6 4.5
20 25 SHC 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 7.5 6.7 5.4
27 SHC 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 8.6 7.7 6.3
29 SHC 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.5 10.4 10.5 9.6 8.7 7.2
31 SHC 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 10.7 9.7 8.0
TC 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.0 13.3 11.7 9.2 6
23 SHC 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.3 5.6 5.0 4.0
21 25 SHC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.4 6.7 6.0 4.8
27 SHC 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.5 7.8 7.0 5.7
29 SHC 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.1 10.0 9.6 8.9 8.0 6.6
31 SHC 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 10.7 10.0 9.1 7.5
TC 16.8 16.8 16.8 16.8 16.8 16.8 16.8 16.8 16.8 16.8 16.7 16.4 15.0 13.3 11.7 9.2 7
25 SHC 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.2 6.6 6.0 5.3 4.2
22 27 SHC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.3 7.7 7.1 6.3 5.1
29 SHC 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.4 8.8 8.2 7.4 6.0
31 SHC 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.6 9.8 9.3 8.4 6.9
TC 17.7 17.7 17.7 17.7 17.7 17.7 17.7 17.7 17.7 17.7 17.7 16.7 15.0 13.3 11.7 9.2

23
25 SHC 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.5 5.9 5.2 4.6 3.7
8
27 SHC 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 7.6 6.9 6.3 5.7 4.6
29 SHC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.1 9.2 8.7 8.0 7.4 6.7 5.5
31 SHC 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.2 10.3 9.9 9.1 8.5 7.7 6.3

9-95 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-160MF2E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 16.0 kW AIR FLOW RATE : 36.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.5

21 SHC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.4
14 23 SHC 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.5
25 SHC 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.5
27 SHC 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.5
TC 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 10.5

21 SHC 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 7.5
15 23 SHC 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 8.5
25 SHC 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 9.4
27 SHC 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 10.4

1 TC 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 10.5

21 SHC 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 6.7
16 23 SHC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 7.6
25 SHC 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 8.5
27 SHC 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 9.4
29 SHC 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 10.3
TC 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.3 10.5
2 21 SHC 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.5 6.0
17 23 SHC 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 8.6 6.8
25 SHC 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 9.7 7.7
27 SHC 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 10.7 8.6
29 SHC 12.2 12.2 12.2 12.2 12.2 12.2 12.2 12.2 12.2 12.2 12.2 12.2 12.2 12.2 11.8 9.4
TC 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 13.3 10.5
3 21 SHC 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 6.8 5.4
23 SHC 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 7.8 6.2
18 25 SHC 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 8.8 7.1
27 SHC 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 9.8 8.0
29 SHC 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 10.8 8.8
31 SHC 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 11.8 9.7
4 TC 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 15.2 13.3 10.5

21 SHC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 6.9 6.1 4.8
23 SHC 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.0 7.0 5.6
19 25 SHC 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.0 8.0 6.5
27 SHC 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.1 9.1 7.4
29 SHC 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.2 10.1 8.2
5 31 SHC
TC
12.8
17.1
12.8
17.1
12.8
17.1
12.8
17.1
12.8
17.1
12.8
17.1
12.8
17.1
12.8
17.1
12.8
17.1
12.8
17.1
12.8
17.1
12.8
17.1
12.8
17.1
12.2 11.1 9.1
15.2 13.3 10.5

23 SHC 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 7.2 6.3 5.1
20 25 SHC 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 8.3 7.3 5.9
27 SHC 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 9.3 8.3 6.8
29 SHC 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 10.4 9.3 7.6
31 SHC 12.4 12.4 12.4 12.4 12.4 12.4 12.4 12.4 12.4 12.4 12.5 12.4 12.4 11.4 10.3 8.5
6 TC 18.1 18.1 18.1 18.1 18.1 18.1 18.1 18.1 18.1 18.1 18.1 18.1 17.2 15.2 13.3 10.5

23 SHC 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.2 6.4 5.6 4.4
21 25 SHC 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.3 7.5 6.6 5.3
27 SHC 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.4 8.5 7.6 6.2
29 SHC 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 10.5 9.6 8.6 7.0
31 SHC 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 11.6 10.7 9.6 7.9
7 TC 19.2 19.2 19.2 19.2 19.2 19.2 19.2 19.2 19.2 19.2 19.1 18.7 17.2 15.2 13.3 10.5

25 SHC 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.1 7.5 6.7 5.9 4.7
22 27 SHC 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.3 8.5 7.8 6.9 5.6
29 SHC 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.4 9.6 8.8 7.9 6.5
31 SHC 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.5 10.7 9.9 8.9 7.3
TC 20.3 20.3 20.3 20.3 20.3 20.3 20.3 20.3 20.3 20.2 20.2 19.1 17.2 15.2 13.3 10.5
8 23
25 SHC 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 7.9 7.9 7.5 6.7 6.0 5.2 4.2
27 SHC 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.0 8.6 7.7 7.0 6.2 5.0
29 SHC 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.1 10.2 9.7 8.8 8.1 7.2 5.9
31 SHC 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.2 11.3 10.8 9.8 9.2 8.2 6.8

9 9-96

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit


2-8. High Static Pressure Ducted Type (E1 Type)
S-73ME1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 7.3 kW AIR FLOW RATE : 23.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8

21 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1
14 23 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.7
25 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8
27 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8
TC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.8

21 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.6
15 23 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.2
25 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.7
27 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.8
TC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 4.8
1
21 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.2
16 23 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 3.7
25 SHC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 4.2
27 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 4.7
29 SHC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 4.8
TC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.1 4.8

21 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.6 2.8
2
17 23 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.1 3.3
25 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.7 3.8
27 SHC 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.3 4.2
29 SHC 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 5.9 4.7
TC 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.1 4.8

21 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.1 2.5
3
23 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7 3.0
18 25 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.2 3.5
27 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 4.8 3.9
29 SHC 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.3 4.4
31 SHC 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 5.9 4.8
TC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.0 6.1 4.8
4
21 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 2.8 2.2
23 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.8 3.3 2.7
19 25 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.3 3.9 3.2
27 SHC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 4.9 4.4 3.6
29 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.5 5.0 4.1
31 SHC
TC
6.3
7.8
6.3
7.8
6.3
7.8
6.3
7.8
6.3
7.8
6.3
7.8
6.3
7.8
6.3
7.8
6.3
7.8
6.3
7.8
6.3
7.8
6.3
7.8
6.3
7.8
6.1
7.0
5.5
6.1
4.6
4.8 5
23 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.3 3.0 2.4
20 25 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 3.9 3.5 2.9
27 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.5 4.1 3.3
29 SHC 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.1 4.6 3.8
31 SHC 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 5.7 5.2 4.3
TC 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 7.8 7.0 6.1 4.8 6
23 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.3 2.9 2.6 2.1
21 25 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.5 3.1 2.5
27 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.5 4.1 3.7 3.0
29 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.1 4.7 4.2 3.5
31 SHC 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.7 5.3 4.8 4.0
TC 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.7 8.5 7.8 7.0 6.1 4.8 7
25 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.5 3.1 2.8 2.2
22 27 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.4 4.4 4.0 3.7 3.3 2.7
29 SHC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.0 5.0 4.6 4.3 3.9 3.2
31 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.6 5.2 4.9 4.4 3.7
TC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 8.7 7.8 7.0 6.1 4.8

23
25 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.4 3.1 2.7 2.4 1.9
8
27 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.0 3.6 3.3 3.0 2.4
29 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.6 4.2 3.9 3.5 2.9
31 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.2 4.8 4.5 4.1 3.4

9-97 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-106ME1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 10.6 kW AIR FLOW RATE : 30.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0

21 SHC 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1
14 23 SHC 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 6.9
25 SHC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0
27 SHC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0
TC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.0

21 SHC 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.3
15 23 SHC 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.1
25 SHC 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 6.9
27 SHC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.0

1 TC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 7.0

21 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 4.7
16 23 SHC 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 5.4
25 SHC 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 6.1
27 SHC 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 6.9
29 SHC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 7.0
TC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 8.8 7.0
2 21 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.2 4.1
17 23 SHC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.1 4.8
25 SHC 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 6.9 5.5
27 SHC 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 7.8 6.2
29 SHC 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 8.6 6.9
TC 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 8.8 7.0
3 21 SHC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 4.6 3.7
23 SHC 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.4 4.4
18 25 SHC 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.2 5.1
27 SHC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.0 5.8
29 SHC 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 7.8 6.5
31 SHC 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 8.7 7.0
4 TC 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.1 8.8 7.0

21 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.6 4.0 3.2
23 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.5 4.9 3.9
19 25 SHC 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.3 5.7 4.6
27 SHC 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.2 6.5 5.3
29 SHC 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.1 7.3 6.0
5 31 SHC
TC
9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 8.9
11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 10.1
8.1
8.8
6.7
7.0

23 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.9 4.3 3.5
20 25 SHC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 5.7 5.1 4.2
27 SHC 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 6.6 6.0 4.9
29 SHC 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 7.5 6.8 5.6
31 SHC 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 8.3 7.6 6.3
6 TC 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 11.4 10.1 8.8 7.0

23 SHC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 4.8 4.3 3.8 3.0
21 25 SHC 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.7 5.2 4.6 3.7
27 SHC 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.6 6.0 5.4 4.4
29 SHC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.4 6.9 6.2 5.1
31 SHC 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.7 8.6 8.3 7.7 7.1 5.8
7 TC 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.4 11.4 10.1 8.8 7.0

25 SHC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.5 5.1 4.6 4.1 3.3
22 27 SHC 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.4 5.9 5.5 4.9 4.0
29 SHC 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.3 6.8 6.3 5.7 4.7
31 SHC 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.2 7.6 7.2 6.5 5.4
TC 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4 12.6 11.4 10.1 8.8 7.0
8 23
25 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.9 4.5 4.0 3.5 2.8
27 SHC 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 5.8 5.3 4.9 4.4 3.5
29 SHC 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 6.7 6.2 5.7 5.2 4.2
31 SHC 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 8.0 7.6 7.0 6.6 6.0 4.9

9 9-98

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-140ME1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 14.0 kW AIR FLOW RATE : 36.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.2

21 SHC 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.5
14 23 SHC 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.5
25 SHC 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.2
27 SHC 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.2
TC 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 9.2

21 SHC 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 6.6
15 23 SHC 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 7.5
25 SHC 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 8.4
27 SHC 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 9.2
TC 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 9.2
1
21 SHC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 5.9
16 23 SHC 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 6.7
25 SHC 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 7.5
27 SHC 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 8.3
29 SHC 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 9.2
TC 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 11.7 9.2

21 SHC 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.6 5.3
2
17 23 SHC 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.6 6.0
25 SHC 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.6 6.8
27 SHC 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.5 7.6
29 SHC 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.5 8.4
TC 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 11.7 9.2

21 SHC 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 5.9 4.7
3
23 SHC 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 6.8 5.5
18 25 SHC 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 7.8 6.3
27 SHC 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 8.7 7.1
29 SHC 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 9.6 7.9
31 SHC 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 11.6 10.5 8.6
TC 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 13.3 11.7 9.2
4
21 SHC 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.1 5.3 4.2
23 SHC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.0 6.2 5.0
19 25 SHC 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.0 7.1 5.7
27 SHC 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 8.9 8.0 6.5
29 SHC 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 9.9 8.9 7.3
31 SHC
TC
11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 10.9 9.8
14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 13.3 11.7
8.1
9.2 5
23 SHC 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 6.3 5.6 4.4
20 25 SHC 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 7.3 6.5 5.2
27 SHC 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.1 9.0 9.0 8.3 7.4 6.0
29 SHC 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.1 9.2 8.3 6.8
31 SHC 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.1 11.0 11.0 10.2 9.2 7.6
TC 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.0 13.3 11.7 9.2 6
23 SHC 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.3 5.6 4.9 3.9
21 25 SHC 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.3 6.6 5.8 4.7
27 SHC 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.3 7.5 6.7 5.5
29 SHC 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.3 8.5 7.7 6.3
31 SHC 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.3 9.5 8.6 7.0
TC 16.8 16.8 16.8 16.8 16.8 16.8 16.8 16.8 16.8 16.8 16.7 16.4 15.0 13.3 11.7 9.2 7
25 SHC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.2 6.6 5.9 5.2 4.2
22 27 SHC 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.2 7.5 6.9 6.1 4.9
29 SHC 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.2 8.5 7.8 7.0 5.7
31 SHC 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.1 9.4 8.8 7.9 6.5
TC 17.7 17.7 17.7 17.7 17.7 17.7 17.7 17.7 17.7 17.7 17.7 16.7 15.0 13.3 11.7 9.2

23
25 SHC 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 6.9 6.9 6.5 5.9 5.2 4.6 3.6
8
27 SHC 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 7.9 7.9 7.5 6.8 6.2 5.5 4.4
29 SHC 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 8.9 9.0 8.5 7.8 7.2 6.4 5.2
31 SHC 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 9.9 10.0 9.5 8.7 8.1 7.3 6.0

9-99 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-224ME1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 22.4 kW AIR FLOW RATE : 56.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.7

21 SHC 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.5
14 23 SHC 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.0
25 SHC 14.6 14.6 14.6 14.6 14.6 14.6 14.6 14.6 14.6 14.6 14.6 14.6 14.6 14.6 14.6 14.4
27 SHC 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.7
TC 16.4 16.4 16.4 16.4 16.4 16.4 16.4 16.4 16.4 16.4 16.4 16.4 16.4 16.4 16.4 14.7

21 SHC 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 10.3
15 23 SHC 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 11.6
25 SHC 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 12.9
27 SHC 15.8 15.8 15.8 15.8 15.8 15.8 15.8 15.8 15.8 15.8 15.8 15.8 15.8 15.8 15.8 14.2

1 TC 17.9 17.9 17.9 17.9 17.9 17.9 17.9 17.9 17.9 17.9 17.9 17.9 17.9 17.9 17.9 14.7

21 SHC 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 9.2
16 23 SHC 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 10.4
25 SHC 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 11.6
27 SHC 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 12.8
29 SHC 17.0 17.0 17.0 17.0 17.0 17.0 17.0 17.0 17.0 17.0 17.0 17.0 17.0 17.0 17.0 14.0
TC 19.4 19.4 19.4 19.4 19.4 19.4 19.4 19.4 19.4 19.4 19.4 19.4 19.4 19.4 18.7 14.7
2 21 SHC 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.5 8.3
17 23 SHC 12.4 12.4 12.4 12.4 12.4 12.4 12.4 12.4 12.4 12.4 12.4 12.4 12.4 12.4 11.9 9.4
25 SHC 13.8 13.8 13.8 13.8 13.8 13.8 13.8 13.8 13.8 13.8 13.8 13.8 13.8 13.8 13.3 10.5
27 SHC 15.3 15.3 15.3 15.3 15.3 15.3 15.3 15.3 15.3 15.3 15.3 15.3 15.3 15.3 14.7 11.6
29 SHC 16.7 16.7 16.7 16.7 16.7 16.7 16.7 16.7 16.7 16.7 16.7 16.7 16.7 16.7 16.0 12.7
TC 20.9 20.9 20.9 20.9 20.9 20.9 20.9 20.9 20.9 20.9 20.9 20.9 20.9 20.9 18.7 14.7
3 21 SHC 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 9.4 7.4
23 SHC 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 10.7 8.5
18 25 SHC 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5 12.0 9.5
27 SHC 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 13.3 10.5
29 SHC 16.4 16.4 16.4 16.4 16.4 16.4 16.4 16.4 16.4 16.4 16.4 16.4 16.4 16.4 14.6 11.5
31 SHC 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 15.9 12.6
4 TC 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 21.3 18.7 14.7

21 SHC 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 9.7 8.5 6.7
23 SHC 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.1 9.7 7.7
19 25 SHC 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 12.5 10.9 8.6
27 SHC 14.5 14.5 14.5 14.5 14.5 14.5 14.5 14.5 14.5 14.5 14.5 14.5 14.5 13.9 12.1 9.6
29 SHC 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 15.3 13.3 10.5
5 31 SHC
TC
17.5
23.9
17.5
23.9
17.5
23.9
17.5
23.9
17.5
23.9
17.5
23.9
17.5
23.9
17.5
23.9
17.5
23.9
17.5
23.9
17.5
23.9
17.5
23.9
17.5
23.9
16.6
21.3
14.5 11.5
18.7 14.7

23 SHC 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 10.0 8.8 6.9
20 25 SHC 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 11.3 9.9 7.9
27 SHC 14.2 14.2 14.2 14.2 14.2 14.2 14.2 14.2 14.2 14.2 14.2 14.2 14.2 12.6 11.1 8.8
29 SHC 15.6 15.6 15.6 15.6 15.6 15.6 15.6 15.6 15.6 15.6 15.6 15.6 15.6 13.9 12.3 9.7
31 SHC 17.1 17.1 17.1 17.1 17.1 17.1 17.1 17.1 17.1 17.1 17.1 17.1 17.1 15.2 13.4 10.6
6 TC 25.4 25.4 25.4 25.4 25.4 25.4 25.4 25.4 25.4 25.4 25.4 25.4 24.0 21.3 18.7 14.7

23 SHC 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.2 9.0 7.9 6.2
21 25 SHC 12.2 12.2 12.2 12.2 12.2 12.2 12.2 12.2 12.2 12.2 12.2 12.2 11.6 10.3 9.0 7.1
27 SHC 13.7 13.7 13.7 13.7 13.7 13.7 13.7 13.7 13.7 13.7 13.7 13.7 13.0 11.6 10.2 8.1
29 SHC 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 14.4 12.9 11.3 9.0
31 SHC 16.6 16.6 16.6 16.6 16.6 16.6 16.6 16.6 16.6 16.6 16.6 16.6 15.8 14.2 12.4 9.9
7 TC 26.9 26.9 26.9 26.9 26.9 26.9 26.9 26.9 26.9 26.9 26.8 26.2 24.0 21.3 18.7 14.7

25 SHC 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.4 10.5 9.3 8.2 6.4
22 27 SHC 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.1 12.9 11.9 10.6 9.3 7.3
29 SHC 14.7 14.7 14.7 14.7 14.7 14.7 14.7 14.7 14.7 14.7 14.6 14.3 13.2 11.8 10.4 8.2
31 SHC 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.0 15.8 14.6 13.1 11.5 9.1
TC 28.4 28.4 28.4 28.4 28.4 28.4 28.4 28.4 28.4 28.3 28.3 26.7 24.0 21.3 18.7 14.7
8 23
25 SHC 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.1 10.5 9.4 8.4 7.3 5.8
27 SHC 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.6 12.7 11.9 10.8 9.6 8.4 6.6
29 SHC 14.2 14.2 14.2 14.2 14.2 14.2 14.2 14.2 14.2 14.1 14.1 13.4 12.1 10.8 9.5 7.5
31 SHC 15.6 15.6 15.6 15.6 15.6 15.6 15.6 15.6 15.6 15.5 15.6 14.9 13.5 12.0 10.6 8.4

9 9-100

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-280ME1E5
Power supply :220/230/240V 1phase-50Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 28.0 kW AIR FLOW RATE : 72.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.4

21 SHC 14.6 14.6 14.6 14.6 14.6 14.6 14.6 14.6 14.6 14.6 14.6 14.6 14.6 14.6 14.6 14.4
14 23 SHC 16.4 16.4 16.4 16.4 16.4 16.4 16.4 16.4 16.4 16.4 16.4 16.4 16.4 16.4 16.4 16.2
25 SHC 18.2 18.2 18.2 18.2 18.2 18.2 18.2 18.2 18.2 18.2 18.2 18.2 18.2 18.2 18.2 17.9
27 SHC 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.4
TC 20.5 20.5 20.5 20.5 20.5 20.5 20.5 20.5 20.5 20.5 20.5 20.5 20.5 20.5 20.5 18.4

21 SHC 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 12.8
15 23 SHC 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 14.5
25 SHC 17.9 17.9 17.9 17.9 17.9 17.9 17.9 17.9 17.9 17.9 17.9 17.9 17.9 17.9 17.9 16.1
27 SHC 19.7 19.7 19.7 19.7 19.7 19.7 19.7 19.7 19.7 19.7 19.7 19.7 19.7 19.7 19.7 17.7
TC 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 18.4
1
21 SHC 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 11.5
16 23 SHC 15.8 15.8 15.8 15.8 15.8 15.8 15.8 15.8 15.8 15.8 15.8 15.8 15.8 15.8 15.8 13.0
25 SHC 17.6 17.6 17.6 17.6 17.6 17.6 17.6 17.6 17.6 17.6 17.6 17.6 17.6 17.6 17.6 14.5
27 SHC 19.4 19.4 19.4 19.4 19.4 19.4 19.4 19.4 19.4 19.4 19.4 19.4 19.4 19.4 19.4 16.0
29 SHC 21.2 21.2 21.2 21.2 21.2 21.2 21.2 21.2 21.2 21.2 21.2 21.2 21.2 21.2 21.2 17.4
TC 24.3 24.3 24.3 24.3 24.3 24.3 24.3 24.3 24.3 24.3 24.3 24.3 24.3 24.3 23.3 18.4

21 SHC 13.6 13.6 13.6 13.6 13.6 13.6 13.6 13.6 13.6 13.6 13.6 13.6 13.6 13.6 13.1 10.4
2
17 23 SHC 15.4 15.4 15.4 15.4 15.4 15.4 15.4 15.4 15.4 15.4 15.4 15.4 15.4 15.4 14.8 11.7
25 SHC 17.2 17.2 17.2 17.2 17.2 17.2 17.2 17.2 17.2 17.2 17.2 17.2 17.2 17.2 16.6 13.1
27 SHC 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 18.3 14.5
29 SHC 20.9 20.9 20.9 20.9 20.9 20.9 20.9 20.9 20.9 20.9 20.9 20.9 20.9 20.9 20.0 15.8
TC 26.1 26.1 26.1 26.1 26.1 26.1 26.1 26.1 26.1 26.1 26.1 26.1 26.1 26.1 23.3 18.4

21 SHC 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 11.8 9.3
3
23 SHC 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 13.4 10.6
18 25 SHC 16.8 16.8 16.8 16.8 16.8 16.8 16.8 16.8 16.8 16.8 16.8 16.8 16.8 16.8 15.0 11.9
27 SHC 18.6 18.6 18.6 18.6 18.6 18.6 18.6 18.6 18.6 18.6 18.6 18.6 18.6 18.6 16.6 13.1
29 SHC 20.4 20.4 20.4 20.4 20.4 20.4 20.4 20.4 20.4 20.4 20.4 20.4 20.4 20.4 18.2 14.4
31 SHC 22.2 22.2 22.2 22.2 22.2 22.2 22.2 22.2 22.2 22.2 22.2 22.2 22.2 22.2 19.8 15.7
TC 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 26.7 23.3 18.4
4
21 SHC 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.2 10.6 8.4
23 SHC 14.6 14.6 14.6 14.6 14.6 14.6 14.6 14.6 14.6 14.6 14.6 14.6 14.6 13.9 12.1 9.6
19 25 SHC 16.3 16.3 16.3 16.3 16.3 16.3 16.3 16.3 16.3 16.3 16.3 16.3 16.3 15.6 13.6 10.8
27 SHC 18.2 18.2 18.2 18.2 18.2 18.2 18.2 18.2 18.2 18.2 18.2 18.2 18.2 17.3 15.1 11.9
29 SHC 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 19.1 16.7 13.2
31 SHC
TC
21.8
29.9
21.8
29.9
21.8
29.9
21.8
29.9
21.8
29.9
21.8
29.9
21.8
29.9
21.8
29.9
21.8
29.9
21.8
29.9
21.8
29.9
21.8
29.9
21.8
29.9
20.7
26.7
18.1
23.3
14.3
18.4 5
23 SHC 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 12.5 11.0 8.7
20 25 SHC 15.8 15.8 15.8 15.8 15.8 15.8 15.8 15.8 15.8 15.8 15.8 15.8 15.8 14.2 12.4 9.8
27 SHC 17.7 17.7 17.7 17.7 17.7 17.7 17.7 17.7 17.7 17.7 17.7 17.7 17.7 15.8 13.8 11.0
29 SHC 19.5 19.5 19.5 19.5 19.5 19.5 19.5 19.5 19.5 19.5 19.5 19.5 19.5 17.4 15.3 12.1
31 SHC 21.3 21.3 21.3 21.3 21.3 21.3 21.3 21.3 21.3 21.3 21.3 21.3 21.3 19.0 16.7 13.3
TC 31.7 31.7 31.7 31.7 31.7 31.7 31.7 31.7 31.7 31.7 31.7 31.7 30.0 26.7 23.3 18.4 6
23 SHC 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5 12.8 11.3 9.9 7.8
21 25 SHC 15.3 15.3 15.3 15.3 15.3 15.3 15.3 15.3 15.3 15.3 15.3 15.3 14.5 12.9 11.3 8.9
27 SHC 17.1 17.1 17.1 17.1 17.1 17.1 17.1 17.1 17.1 17.1 17.1 17.1 16.2 14.5 12.7 10.1
29 SHC 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.0 16.1 14.1 11.2
31 SHC 20.7 20.7 20.7 20.7 20.7 20.7 20.7 20.7 20.7 20.7 20.7 20.7 19.7 17.6 15.5 12.3
TC 33.6 33.6 33.6 33.6 33.6 33.6 33.6 33.6 33.6 33.6 33.5 32.7 30.0 26.7 23.3 18.4 7
25 SHC 14.7 14.7 14.7 14.7 14.7 14.7 14.7 14.7 14.7 14.7 14.6 14.3 13.1 11.7 10.2 8.0
22 27 SHC 16.5 16.5 16.5 16.5 16.5 16.5 16.5 16.5 16.5 16.5 16.5 16.1 14.8 13.2 11.6 9.1
29 SHC 18.3 18.3 18.3 18.3 18.3 18.3 18.3 18.3 18.3 18.3 18.2 17.9 16.5 14.8 13.0 10.3
31 SHC 20.1 20.1 20.1 20.1 20.1 20.1 20.1 20.1 20.1 20.1 20.0 19.7 18.2 16.3 14.3 11.4
TC 35.5 35.5 35.5 35.5 35.5 35.5 35.5 35.5 35.5 35.3 35.3 33.3 30.0 26.7 23.3 18.4

23
25 SHC 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.0 13.9 13.1 11.8 10.4 9.1 7.2
8
27 SHC 15.8 15.8 15.8 15.8 15.8 15.8 15.8 15.8 15.8 15.8 15.8 14.9 13.5 12.0 10.5 8.3
29 SHC 17.7 17.7 17.7 17.7 17.7 17.7 17.7 17.7 17.7 17.6 17.6 16.7 15.1 13.5 11.8 9.4
31 SHC 19.5 19.5 19.5 19.5 19.5 19.5 19.5 19.5 19.5 19.4 19.5 18.6 16.8 15.1 13.2 10.5

9-101 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit


2-9. Floor Standing Type (P1 Type)
S-22MP1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 2.2 kW AIR FLOW RATE : 7.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4

21 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2
14 23 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4
25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
27 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
TC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4

21 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1
15 23 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2
25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4

1 TC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4

21 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 0.9
16 23 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.1
25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.2
27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.3
29 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4
TC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.4
2 21 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 0.8
17 23 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.0
25 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.1
27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.2
29 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.4
TC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8 1.4
3 21 SHC 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 0.9 0.7
23 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 0.9
18 25 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.2 1.0
27 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.1
29 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.5 1.3
31 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7 1.4
4 TC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.8 1.4

21 SHC 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 0.8 0.7
23 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 1.0 0.8
19 25 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.1 0.9
27 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.3 1.1
29 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.4 1.2
5 31 SHC
TC
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.1
1.6
1.8
1.3
1.4

23 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 0.9 0.7
20 25 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.0 0.8
27 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.2 1.0
29 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.3 1.1
31 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.6 1.5 1.2
6 TC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.1 1.8 1.4

23 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 0.9 0.8 0.6
21 25 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.0 0.9 0.7
27 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.2 1.1 0.9
29 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.4 1.2 1.0
31 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.5 1.4 1.1
7 TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4 2.1 1.8 1.4

25 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 1.0 0.9 0.8 0.7
22 27 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.1 1.0 0.8
29 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.3 1.1 0.9
31 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.5 1.4 1.3 1.1
TC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.4 2.1 1.8 1.4
8 23
25 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 0.9 0.8 0.7 0.6
27 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.1 1.0 0.9 0.7
29 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.2 1.1 1.0 0.8
31 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.4 1.3 1.2 1.0

9 9-102

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-28MP1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 2.8 kW AIR FLOW RATE : 7.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8

21 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
14 23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
TC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8

21 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.3
15 23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.5
25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8
TC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
1
21 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.2
16 23 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4
25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.5
27 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.7
29 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
TC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 1.8

21 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.1
2
17 23 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.2
25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.4
27 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.5
29 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.7
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.3 1.8

21 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 0.9
3
23 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.1
18 25 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.3
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7 1.4
29 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.9 1.6
31 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.4 2.3 2.3 2.3 2.1 1.7
TC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.3 1.8
4
21 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.1 0.8
23 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.2 1.0
19 25 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.4 1.2
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.6 1.3
29 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.8 1.5
31 SHC
TC
2.3
3.0
2.3
3.0
2.3
3.0
2.3
3.0
2.3
3.0
2.3
3.0
2.3
3.0
2.3
3.0
2.3
3.0
2.3
3.0
2.3
3.0
2.3
3.0
2.3
3.0
2.2
2.7
2.0
2.3
1.6
1.8 5
23 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.1 0.9
20 25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.3 1.1
27 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.5 1.2
29 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.7 1.4
31 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.9 1.5
TC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.0 2.7 2.3 1.8 6
23 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.1 1.0 0.8
21 25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.3 1.2 0.9
27 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.5 1.4 1.1
29 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 2.0 1.9 1.9 1.7 1.5 1.3
31 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.9 1.7 1.4
TC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.3 3.0 2.7 2.3 1.8 7
25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.3 1.2 1.0 0.8
22 27 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.5 1.4 1.2 1.0
29 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.7 1.6 1.4 1.2
31 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.9 1.8 1.6 1.3
TC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.3 3.0 2.7 2.3 1.8

23
25 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.2 1.0 0.9 0.7
8
27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.4 1.2 1.1 0.9
29 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.6 1.4 1.3 1.1
31 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.8 1.6 1.5 1.2

9-103 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-36MP1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 3.6 kW AIR FLOW RATE : 9.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

21 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
14 23 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4

21 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7
15 23 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.9
25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.2
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4

1 TC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.4

21 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.5
16 23 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.7
25 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 1.9
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.1
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.3
TC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.4
2 21 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.4
17 23 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.6
25 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 1.8
27 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.0
29 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.2
TC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.0 2.4
3 21 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.5 1.2
23 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.8 1.4
18 25 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.0 1.6
27 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.2 1.8
29 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.5 2.0
31 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.7 2.2
4 TC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.4 3.0 2.4

21 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4 1.1
23 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.6 1.3
19 25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.8 1.5
27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.1 1.7
29 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.5 2.3 1.9
5 31 SHC
TC
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.8
3.4
2.5
3.0
2.1
2.4

23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.6 1.4 1.1
20 25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.9 1.7 1.3
27 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.1 1.9 1.5
29 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4 2.1 1.7
31 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.4 1.9
6 TC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.4 3.0 2.4

23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.4 1.3 1.0
21 25 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.7 1.5 1.2
27 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.9 1.7 1.4
29 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.2 2.0 1.6
31 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.4 2.2 1.8
7 TC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 3.9 3.4 3.0 2.4

25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.7 1.5 1.3 1.1
22 27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.9 1.8 1.6 1.3
29 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.2 2.0 1.8 1.5
31 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6 2.4 2.3 2.0 1.7
TC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.5 4.5 4.3 3.9 3.4 3.0 2.4
8 23
25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.5 1.3 1.2 0.9
27 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.7 1.6 1.4 1.1
29 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.0 1.8 1.6 1.3
31 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.6 2.4 2.2 2.1 1.9 1.5

9 9-104

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-45MP1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 4.5 kW AIR FLOW RATE : 12.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

21 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1
14 23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3
25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
27 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8
TC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0

21 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.0
15 23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.1
25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.3
27 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.5
TC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.0
1
21 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
16 23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.0
25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.1
27 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.3
29 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.5
TC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.7 3.0

21 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.6
2
17 23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 1.8
25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.0
27 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.1
29 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.3
TC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.7 3.0

21 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.9 1.5
3
23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.1 1.7
18 25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.3 1.8
27 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.5 2.0
29 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.7 2.2
31 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 2.9 2.3
TC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.3 3.7 3.0
4
21 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.7 1.4
23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.2 1.9 1.5
19 25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4 2.1 1.7
27 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.3 1.9
29 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.5 2.0
31 SHC
TC
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.1
4.3
2.7
3.7
2.2
3.0 5
23 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.0 1.8 1.4
20 25 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.3 2.0 1.6
27 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.5 2.2 1.7
29 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.7 2.4 1.9
31 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 2.9 2.6 2.1
TC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 4.8 4.3 3.7 3.0 6
23 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.1 1.9 1.6 1.3
21 25 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.1 1.8 1.4
27 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.3 2.0 1.6
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.5 2.2 1.8
31 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.7 2.4 1.9
TC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.3 4.8 4.3 3.7 3.0 7
25 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.2 1.9 1.6 1.3
22 27 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.4 2.1 1.8 1.5
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.6 2.3 2.0 1.6
31 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.8 2.5 2.2 1.8
TC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.4 4.8 4.3 3.7 3.0

23
25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.2 2.0 1.7 1.5 1.2
8
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4 2.2 1.9 1.7 1.3
29 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.4 2.1 1.9 1.5
31 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 3.0 2.9 2.6 2.3 2.1 1.7

9-105 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-56MP1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 5.6 kW AIR FLOW RATE : 15.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7

21 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1
14 23 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5
25 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
27 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
TC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7

21 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.7
15 23 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.1
25 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.5
27 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7

1 TC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 3.7

21 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.4
16 23 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 2.8
25 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.1
27 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.5
29 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 3.7
TC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.7 3.7
2 21 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.1
17 23 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 2.5
25 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.5 2.8
27 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.2
29 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.4 3.5
TC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.7 3.7
3 21 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.4 1.9
23 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.8 2.2
18 25 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.2 2.6
27 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.6 2.9
29 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.0 3.3
31 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.4 3.6
4 TC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.3 4.7 3.7

21 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.1 1.7
23 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.8 2.5 2.0
19 25 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 2.9 2.4
27 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.3 2.7
29 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.1 3.7 3.0
5 31 SHC
TC
4.7
6.0
4.7
6.0
4.7
6.0
4.7
6.0
4.7
6.0
4.7
6.0
4.7
6.0
4.7
6.0
4.7
6.0
4.7
6.0
4.7
6.0
4.7
6.0
4.7
6.0
4.5
5.3
4.1
4.7
3.4
3.7

23 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.5 2.2 1.8
20 25 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0 2.6 2.1
27 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.4 3.0 2.5
29 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.8 3.4 2.8
31 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.2 3.8 3.2
6 TC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.0 5.3 4.7 3.7

23 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.5 2.3 2.0 1.6
21 25 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.7 2.4 1.9
27 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.4 3.1 2.8 2.3
29 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.8 3.5 3.2 2.6
31 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.2 3.9 3.6 2.9
7 TC 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.5 6.0 5.3 4.7 3.7

25 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.6 2.4 2.1 1.7
22 27 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.1 2.8 2.5 2.0
29 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.5 3.2 2.9 2.4
31 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.9 3.6 3.3 2.7
TC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 6.7 6.0 5.3 4.7 3.7
8 23
25 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.3 2.1 1.8 1.5
27 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.0 2.8 2.5 2.2 1.8
29 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.2 2.9 2.6 2.2
31 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.6 3.4 3.0 2.5

9 9-106

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-71MP1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 7.1 kW AIR FLOW RATE : 17.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7

21 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
14 23 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1
25 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6
27 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7
TC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.7

21 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.3
15 23 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7
25 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.1
27 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.5
TC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 4.7
1
21 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 2.9
16 23 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.3
25 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 3.7
27 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.1
29 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.5
TC 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 5.9 4.7

21 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.3 2.6
2
17 23 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.8 3.0
25 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.2 3.4
27 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.7 3.7
29 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.1 4.1
TC 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 5.9 4.7

21 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.4 3.4 3.4 3.0 2.4
3
23 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.4 2.7
18 25 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 3.8 3.1
27 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.3 3.5
29 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.7 3.8
31 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.1 4.2
TC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 6.8 5.9 4.7
4
21 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 2.7 2.1
23 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.5 3.1 2.5
19 25 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.0 3.5 2.9
27 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.4 4.0 3.2
29 SHC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 4.9 4.4 3.6
31 SHC
TC
5.6
7.6
5.6
7.6
5.6
7.6
5.6
7.6
5.6
7.6
5.6
7.6
5.6
7.6
5.6
7.6
5.6
7.6
5.6
7.6
5.6
7.6
5.6
7.6
5.6
7.6
5.3
6.8
4.8
5.9
3.9
4.7 5
23 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.2 2.8 2.2
20 25 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.6 3.2 2.6
27 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.1 3.6 3.0
29 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.5 4.1 3.3
31 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.0 4.5 3.7
TC 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 7.6 6.8 5.9 4.7 6
23 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.2 2.9 2.5 2.0
21 25 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.7 3.3 2.9 2.3
27 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.1 3.8 3.3 2.7
29 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.6 4.2 3.8 3.1
31 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.1 4.7 4.2 3.4
TC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.3 7.6 6.8 5.9 4.7 7
25 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.6 3.3 3.0 2.6 2.1
22 27 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 3.8 3.4 3.0 2.5
29 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.6 4.6 4.2 3.9 3.5 2.8
31 SHC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.0 4.7 4.3 3.9 3.2
TC 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 8.5 7.6 6.8 5.9 4.7

23
25 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.5 3.3 3.0 2.6 2.3 1.8
8
27 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.8 3.4 3.1 2.7 2.2
29 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.2 3.9 3.5 3.2 2.6
31 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.9 5.0 4.7 4.3 4.0 3.6 2.9

9-107 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit


2-10. Concealed Floor Standing Type (R1 Type)
S-22MR1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 2.2 kW AIR FLOW RATE : 7.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4

21 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2
14 23 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4
25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
27 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
TC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4

21 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1
15 23 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2
25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4

1 TC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4

21 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 0.9
16 23 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.1
25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.2
27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.3
29 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4
TC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.4
2 21 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 0.8
17 23 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.0
25 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.1
27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.2
29 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.4
TC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8 1.4
3 21 SHC 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 0.9 0.7
23 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 0.9
18 25 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.2 1.0
27 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.1
29 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.5 1.3
31 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7 1.4
4 TC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.8 1.4

21 SHC 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 0.8 0.7
23 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 1.0 0.8
19 25 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.1 0.9
27 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.3 1.1
29 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.4 1.2
5 31 SHC
TC
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.1
1.6
1.8
1.3
1.4

23 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 0.9 0.7
20 25 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.0 0.8
27 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.2 1.0
29 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.3 1.1
31 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.6 1.5 1.2
6 TC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.1 1.8 1.4

23 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 0.9 0.8 0.6
21 25 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.0 0.9 0.7
27 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.2 1.1 0.9
29 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.4 1.2 1.0
31 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.5 1.4 1.1
7 TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4 2.1 1.8 1.4

25 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 1.0 0.9 0.8 0.7
22 27 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.1 1.0 0.8
29 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.3 1.1 0.9
31 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.5 1.4 1.3 1.1
TC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.4 2.1 1.8 1.4
8 23
25 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 0.9 0.8 0.7 0.6
27 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.1 1.0 0.9 0.7
29 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.2 1.1 1.0 0.8
31 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.4 1.3 1.2 1.0

9 9-108

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-28MR1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 2.8 kW AIR FLOW RATE : 7.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8

21 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
14 23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
TC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8

21 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.3
15 23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.5
25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8
TC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
1
21 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.2
16 23 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4
25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.5
27 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.7
29 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
TC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 1.8

21 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.1
2
17 23 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.2
25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.4
27 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.5
29 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.7
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.3 1.8

21 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 0.9
3
23 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.1
18 25 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.3
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7 1.4
29 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.9 1.6
31 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.4 2.3 2.3 2.3 2.1 1.7
TC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.3 1.8
4
21 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.1 0.8
23 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.2 1.0
19 25 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.4 1.2
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.6 1.3
29 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.8 1.5
31 SHC
TC
2.3
3.0
2.3
3.0
2.3
3.0
2.3
3.0
2.3
3.0
2.3
3.0
2.3
3.0
2.3
3.0
2.3
3.0
2.3
3.0
2.3
3.0
2.3
3.0
2.3
3.0
2.2
2.7
2.0
2.3
1.6
1.8 5
23 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.1 0.9
20 25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.3 1.1
27 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.5 1.2
29 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.7 1.4
31 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.9 1.5
TC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.0 2.7 2.3 1.8 6
23 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.1 1.0 0.8
21 25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.3 1.2 0.9
27 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.5 1.4 1.1
29 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 2.0 1.9 1.9 1.7 1.5 1.3
31 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.9 1.7 1.4
TC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.3 3.0 2.7 2.3 1.8 7
25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.3 1.2 1.0 0.8
22 27 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.5 1.4 1.2 1.0
29 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.7 1.6 1.4 1.2
31 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.9 1.8 1.6 1.3
TC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.3 3.0 2.7 2.3 1.8

23
25 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.2 1.0 0.9 0.7
8
27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.4 1.2 1.1 0.9
29 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.6 1.4 1.3 1.1
31 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.8 1.6 1.5 1.2

9-109 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-36MR1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 3.6 kW AIR FLOW RATE : 9.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

21 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
14 23 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4

21 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7
15 23 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.9
25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.2
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4

1 TC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.4

21 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.5
16 23 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.7
25 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 1.9
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.1
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.3
TC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.4
2 21 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.4
17 23 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.6
25 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 1.8
27 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.0
29 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.2
TC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.0 2.4
3 21 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.5 1.2
23 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.8 1.4
18 25 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.0 1.6
27 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.2 1.8
29 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.5 2.0
31 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.7 2.2
4 TC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.4 3.0 2.4

21 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4 1.1
23 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.6 1.3
19 25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.8 1.5
27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.1 1.7
29 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.5 2.3 1.9
5 31 SHC
TC
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.8
3.4
2.5
3.0
2.1
2.4

23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.6 1.4 1.1
20 25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.9 1.7 1.3
27 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.1 1.9 1.5
29 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4 2.1 1.7
31 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.4 1.9
6 TC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.4 3.0 2.4

23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.4 1.3 1.0
21 25 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.7 1.5 1.2
27 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.9 1.7 1.4
29 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.2 2.0 1.6
31 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.4 2.2 1.8
7 TC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 3.9 3.4 3.0 2.4

25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.7 1.5 1.3 1.1
22 27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.9 1.8 1.6 1.3
29 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.2 2.0 1.8 1.5
31 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6 2.4 2.3 2.0 1.7
TC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.5 4.5 4.3 3.9 3.4 3.0 2.4
8 23
25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.5 1.3 1.2 0.9
27 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.7 1.6 1.4 1.1
29 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.0 1.8 1.6 1.3
31 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.6 2.4 2.2 2.1 1.9 1.5

9 9-110

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-45MR1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 4.5 kW AIR FLOW RATE : 12.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

21 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1
14 23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3
25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
27 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8
TC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0

21 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.0
15 23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.1
25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.3
27 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.5
TC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.0
1
21 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
16 23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.0
25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.1
27 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.3
29 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.5
TC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.7 3.0

21 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.6
2
17 23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 1.8
25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.0
27 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.1
29 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.3
TC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.7 3.0

21 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.9 1.5
3
23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.1 1.7
18 25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.3 1.8
27 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.5 2.0
29 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.7 2.2
31 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 2.9 2.3
TC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.3 3.7 3.0
4
21 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.7 1.4
23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.2 1.9 1.5
19 25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4 2.1 1.7
27 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.3 1.9
29 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.5 2.0
31 SHC
TC
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.1
4.3
2.7
3.7
2.2
3.0 5
23 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.0 1.8 1.4
20 25 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.3 2.0 1.6
27 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.5 2.2 1.7
29 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.7 2.4 1.9
31 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 2.9 2.6 2.1
TC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 4.8 4.3 3.7 3.0 6
23 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.1 1.9 1.6 1.3
21 25 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.1 1.8 1.4
27 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.3 2.0 1.6
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.5 2.2 1.8
31 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.7 2.4 1.9
TC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.3 4.8 4.3 3.7 3.0 7
25 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.2 1.9 1.6 1.3
22 27 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.4 2.1 1.8 1.5
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.6 2.3 2.0 1.6
31 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.8 2.5 2.2 1.8
TC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.4 4.8 4.3 3.7 3.0

23
25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.2 2.0 1.7 1.5 1.2
8
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4 2.2 1.9 1.7 1.3
29 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.4 2.1 1.9 1.5
31 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 3.0 2.9 2.6 2.3 2.1 1.7

9-111 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-56MR1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 5.6 kW AIR FLOW RATE : 15.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7

21 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1
14 23 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5
25 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
27 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
TC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7

21 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.7
15 23 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.1
25 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.5
27 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7

1 TC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 3.7

21 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.4
16 23 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 2.8
25 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.1
27 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.5
29 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 3.7
TC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.7 3.7
2 21 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.1
17 23 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 2.5
25 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.5 2.8
27 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.2
29 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.4 3.5
TC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.7 3.7
3 21 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.4 1.9
23 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.8 2.2
18 25 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.2 2.6
27 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.6 2.9
29 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.0 3.3
31 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.4 3.6
4 TC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.3 4.7 3.7

21 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.1 1.7
23 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.8 2.5 2.0
19 25 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 2.9 2.4
27 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.3 2.7
29 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.1 3.7 3.0
5 31 SHC
TC
4.7
6.0
4.7
6.0
4.7
6.0
4.7
6.0
4.7
6.0
4.7
6.0
4.7
6.0
4.7
6.0
4.7
6.0
4.7
6.0
4.7
6.0
4.7
6.0
4.7
6.0
4.5
5.3
4.1
4.7
3.4
3.7

23 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.5 2.2 1.8
20 25 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0 2.6 2.1
27 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.4 3.0 2.5
29 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.8 3.4 2.8
31 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.2 3.8 3.2
6 TC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.0 5.3 4.7 3.7

23 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.5 2.3 2.0 1.6
21 25 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.7 2.4 1.9
27 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.4 3.1 2.8 2.3
29 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.8 3.5 3.2 2.6
31 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.2 3.9 3.6 2.9
7 TC 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.5 6.0 5.3 4.7 3.7

25 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.6 2.4 2.1 1.7
22 27 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.1 2.8 2.5 2.0
29 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.5 3.2 2.9 2.4
31 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.9 3.6 3.3 2.7
TC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 6.7 6.0 5.3 4.7 3.7
8 23
25 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.3 2.1 1.8 1.5
27 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.0 2.8 2.5 2.2 1.8
29 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.2 2.9 2.6 2.2
31 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.6 3.4 3.0 2.5

9 9-112

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-71MR1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 7.1 kW AIR FLOW RATE : 17.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7

21 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
14 23 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1
25 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6
27 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7
TC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.7

21 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.3
15 23 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7
25 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.1
27 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.5
TC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 4.7
1
21 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 2.9
16 23 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.3
25 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 3.7
27 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.1
29 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.5
TC 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 5.9 4.7

21 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.3 2.6
2
17 23 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.8 3.0
25 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.2 3.4
27 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.7 3.7
29 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.1 4.1
TC 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 5.9 4.7

21 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.4 3.4 3.4 3.0 2.4
3
23 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.4 2.7
18 25 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 3.8 3.1
27 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.3 3.5
29 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.7 3.8
31 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.1 4.2
TC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 6.8 5.9 4.7
4
21 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 2.7 2.1
23 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.5 3.1 2.5
19 25 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.0 3.5 2.9
27 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.4 4.0 3.2
29 SHC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 4.9 4.4 3.6
31 SHC
TC
5.6
7.6
5.6
7.6
5.6
7.6
5.6
7.6
5.6
7.6
5.6
7.6
5.6
7.6
5.6
7.6
5.6
7.6
5.6
7.6
5.6
7.6
5.6
7.6
5.6
7.6
5.3
6.8
4.8
5.9
3.9
4.7 5
23 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.2 2.8 2.2
20 25 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.6 3.2 2.6
27 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.1 3.6 3.0
29 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.5 4.1 3.3
31 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.0 4.5 3.7
TC 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 7.6 6.8 5.9 4.7 6
23 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.2 2.9 2.5 2.0
21 25 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.7 3.3 2.9 2.3
27 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.1 3.8 3.3 2.7
29 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.6 4.2 3.8 3.1
31 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.1 4.7 4.2 3.4
TC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.3 7.6 6.8 5.9 4.7 7
25 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.6 3.3 3.0 2.6 2.1
22 27 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 3.8 3.4 3.0 2.5
29 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.6 4.6 4.2 3.9 3.5 2.8
31 SHC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.0 4.7 4.3 3.9 3.2
TC 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 8.5 7.6 6.8 5.9 4.7

23
25 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.5 3.3 3.0 2.6 2.3 1.8
8
27 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.8 3.4 3.1 2.7 2.2
29 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.2 3.9 3.5 3.2 2.6
31 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.9 5.0 4.7 4.3 4.0 3.6 2.9

9-113 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit


2-11. 1-Way Cassette Type (D1 Type)
S-28MD1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 2.8 kW AIR FLOW RATE : 12.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8

21 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
14 23 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
TC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8

21 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7
15 23 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8
25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8

1 TC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8

21 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.4
16 23 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.7
25 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
27 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
29 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
TC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 1.8
2 21 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.2
17 23 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.5
25 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 1.8
27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 1.8
29 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 1.8
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.3 1.8
3 21 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.3 1.1
23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.6 1.4
18 25 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.0 1.6
27 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.3 1.8
29 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.3 1.8
31 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.3 1.8
4 TC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.3 1.8

21 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.1 0.9
23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.5 1.2
19 25 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.8 1.5
27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.1 1.7
29 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.3 1.8
5 31 SHC
TC
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.7
2.7
2.3
2.3
1.8
1.8

23 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.3 1.0
20 25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7 1.6 1.3
27 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.3 2.1 1.9 1.6
29 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4 2.2 1.8
31 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 3.0 2.9 3.0 2.7 2.3 1.8
6 TC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.0 2.7 2.3 1.8

23 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.2 1.1 0.9
21 25 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.5 1.4 1.1
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.9 1.7 1.4
29 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.5 2.4 2.2 2.0 1.7
31 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.6 2.3 1.8
7 TC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.3 3.0 2.7 2.3 1.8

25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4 1.3 1.2 1.0
22 27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.7 1.5 1.3
29 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.1 2.0 1.8 1.5
31 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6 2.5 2.4 2.2 1.8
TC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.3 3.0 2.7 2.3 1.8
8 23
25 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.2 1.1 1.0 0.8
27 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.6 1.5 1.3 1.1
29 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.2 2.1 1.9 1.8 1.7 1.4
31 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.2 2.2 2.0 1.6

9 9-114

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-36MD1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 3.6 kW AIR FLOW RATE : 12.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

21 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
14 23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4

21 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.9
15 23 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.2
25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4
TC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.4
1
21 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.7
16 23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 1.9
25 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.2
27 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.4
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.4
TC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.4

21 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.5
2
17 23 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.7
25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.0
27 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.3
29 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.4
TC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.0 2.4

21 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.6 1.3
3
23 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.9 1.6
18 25 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.2 1.8
27 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.5 2.1
29 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 2.9 2.4
31 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.0 2.4
TC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.4 3.0 2.4
4
21 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.4 1.1
23 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.7 1.4
19 25 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.0 1.7
27 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.3 1.9
29 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.7 2.2
31 SHC
TC
3.4
3.8
3.4
3.8
3.4
3.8
3.4
3.8
3.4
3.8
3.4
3.8
3.4
3.8
3.4
3.8
3.4
3.8
3.4
3.8
3.4
3.8
3.4
3.8
3.4
3.8
3.2
3.4
3.0
3.0
2.4
2.4 5
23 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7 1.5 1.2
20 25 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.0 1.8 1.5
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4 2.1 1.8
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.7 2.5 2.0
31 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0 2.8 2.3
TC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.4 3.0 2.4 6
23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.5 1.3 1.0
21 25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.8 1.6 1.3
27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.2 1.9 1.6
29 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.5 2.3 1.9
31 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.8 2.6 2.1
TC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 3.9 3.4 3.0 2.4 7
25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7 1.6 1.4 1.2
22 27 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.1 1.9 1.7 1.4
29 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4 2.3 2.1 1.7
31 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.7 2.6 2.4 2.0
TC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.5 4.5 4.3 3.9 3.4 3.0 2.4

23
25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.5 1.4 1.2 1.0
8
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.9 1.7 1.5 1.3
29 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.2 2.1 1.9 1.5
31 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.5 2.4 2.2 1.8

9-115 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-45MD1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 4.5 kW AIR FLOW RATE : 12.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

21 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9
14 23 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
25 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
27 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
TC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0

21 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.5
15 23 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0
25 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0
27 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0

1 TC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.0

21 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.2
16 23 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.6
25 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.0
27 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.0
29 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.0
TC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.7 3.0
2 21 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 1.9
17 23 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.3
25 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.3 2.7
27 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.7 3.0
29 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.7 3.0
TC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.7 3.0
3 21 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.1 1.7
23 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.5 2.0
18 25 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0 2.4
27 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.4 2.8
29 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.7 3.0
31 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.7 3.0
4 TC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.3 3.7 3.0

21 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.8 1.4
23 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.2 1.8
19 25 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.7 2.2
27 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.4 3.1 2.6
29 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.6 3.0
5 31 SHC
TC
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.5
4.8
4.3
4.3
3.7
3.7
3.0
3.0

23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.2 1.9 1.6
20 25 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.7 2.4 2.0
27 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.1 2.9 2.4
29 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.6 3.3 2.7
31 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.1 3.7 3.0
6 TC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 4.8 4.3 3.7 3.0

23 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.9 1.7 1.3
21 25 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.4 2.1 1.7
27 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 2.8 2.6 2.1
29 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.5 3.3 3.0 2.5
31 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.0 3.8 3.5 2.9
7 TC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.3 4.8 4.3 3.7 3.0

25 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.2 2.1 1.8 1.5
22 27 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.7 2.5 2.3 1.9
29 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.4 3.2 3.0 2.8 2.3
31 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9 3.7 3.5 3.2 2.7
TC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.4 4.8 4.3 3.7 3.0
8 23
25 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.3 2.1 1.9 1.8 1.6 1.3
27 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.8 2.6 2.4 2.2 2.0 1.7
29 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 3.3 3.1 2.9 2.7 2.5 2.0
31 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.8 3.6 3.4 3.2 2.9 2.4

9 9-116

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-56MD1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 5.6 kW AIR FLOW RATE : 13.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7

21 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1
14 23 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5
25 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
27 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
TC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7

21 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.7
15 23 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.1
25 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.5
27 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7
TC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 3.7
1
21 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.4
16 23 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 2.8
25 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.1
27 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.5
29 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 3.7
TC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.7 3.7

21 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.1
2
17 23 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 2.5
25 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.5 2.8
27 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.2
29 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.4 3.5
TC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.7 3.7

21 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.4 1.9
3
23 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.8 2.2
18 25 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.2 2.6
27 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.6 2.9
29 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.0 3.3
31 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.4 3.6
TC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.3 4.7 3.7
4
21 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.1 1.7
23 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.8 2.5 2.0
19 25 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 2.9 2.4
27 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.3 2.7
29 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.1 3.7 3.0
31 SHC
TC
4.7
6.0
4.7
6.0
4.7
6.0
4.7
6.0
4.7
6.0
4.7
6.0
4.7
6.0
4.7
6.0
4.7
6.0
4.7
6.0
4.7
6.0
4.7
6.0
4.7
6.0
4.5
5.3
4.1
4.7
3.4
3.7 5
23 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.5 2.2 1.8
20 25 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0 2.6 2.1
27 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.4 3.0 2.5
29 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.8 3.4 2.8
31 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.2 3.8 3.2
TC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.0 5.3 4.7 3.7 6
23 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.5 2.3 2.0 1.6
21 25 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.7 2.4 1.9
27 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.4 3.1 2.8 2.3
29 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.8 3.5 3.2 2.6
31 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.2 3.9 3.6 2.9
TC 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.5 6.0 5.3 4.7 3.7 7
25 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.6 2.4 2.1 1.7
22 27 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.1 2.8 2.5 2.0
29 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.5 3.2 2.9 2.4
31 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.9 3.6 3.3 2.7
TC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 6.7 6.0 5.3 4.7 3.7

23
25 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.3 2.1 1.8 1.5
8
27 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.0 2.8 2.5 2.2 1.8
29 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.2 2.9 2.6 2.2
31 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.6 3.4 3.0 2.5

9-117 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-73MD1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 7.3 kW AIR FLOW RATE : 18.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8

21 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0
14 23 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.5
25 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8
27 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8
TC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.8

21 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.5
15 23 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.0
25 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.5
27 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.8

1 TC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 4.8

21 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.1
16 23 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 3.6
25 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.0
27 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.5
29 SHC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 4.8
TC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.1 4.8
2 21 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 2.8
17 23 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.0 3.2
25 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.6 3.7
27 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.1 4.1
29 SHC 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.6 4.5
TC 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.1 4.8
3 21 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.1 2.5
23 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.6 2.9
18 25 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.1 3.4
27 SHC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.2 5.1 5.1 5.1 4.6 3.8
29 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.1 4.2
31 SHC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 5.6 4.7
4 TC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.0 6.1 4.8

21 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 2.8 2.2
23 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.7 3.3 2.6
19 25 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.2 3.8 3.1
27 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.8 4.3 3.5
29 SHC 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.3 4.8 3.9
5 31 SHC
TC
6.1
7.8
6.1
7.8
6.1
7.8
6.1
7.8
6.1
7.8
6.1
7.8
6.1
7.8
6.1
7.8
6.1
7.8
6.1
7.8
6.1
7.8
6.1
7.8
6.1
7.8
5.8
7.0
5.3
6.1
4.4
4.8

23 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.3 2.9 2.3
20 25 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.9 3.4 2.8
27 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.4 3.9 3.2
29 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.9 4.4 3.6
31 SHC 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.5 5.0 4.1
6 TC 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 7.8 7.0 6.1 4.8

23 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.3 2.9 2.6 2.0
21 25 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.8 3.5 3.1 2.5
27 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.4 4.0 3.6 2.9
29 SHC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.2 5.1 4.9 4.5 4.1 3.4
31 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.5 5.1 4.6 3.8
7 TC 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.7 8.5 7.8 7.0 6.1 4.8

25 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.4 3.1 2.7 2.2
22 27 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.3 4.0 3.6 3.3 2.6
29 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8 4.5 4.2 3.8 3.1
31 SHC 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.4 5.0 4.7 4.3 3.5
TC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 8.7 7.8 7.0 6.1 4.8
8 23
25 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.4 3.1 2.7 2.4 1.9
27 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.9 3.6 3.3 2.9 2.4
29 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.5 4.1 3.8 3.4 2.8
31 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.1 4.6 4.4 3.9 3.2

9 9-118

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit


2-12. Slim Low Static Ducted Type (M1 Type)
S-22MM1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 2.2 kW AIR FLOW RATE : 8.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4

21 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
14 23 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
27 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
TC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4

21 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4
15 23 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4
25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4
27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4
TC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4
1
21 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.2
16 23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4
25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4
27 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4
29 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.4
TC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.4

21 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.0
2
17 23 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.3
25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.4
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.4
29 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.4
TC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8 1.4

21 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 0.9
3
23 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.1
18 25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.6 1.4
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8 1.4
29 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8 1.4
31 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8 1.4
TC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.8 1.4
4
21 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 0.9 0.7
23 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.2 1.0
19 25 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.5 1.2
27 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.8 1.4
29 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.8 1.4
31 SHC
TC
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.1
2.1
1.8
1.8
1.4
1.4 5
23 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.1 1.0 0.8
20 25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.4 1.3 1.1
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7 1.6 1.3
29 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.0 1.8 1.4
31 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.1 1.8 1.4
TC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.1 1.8 1.4 6
23 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 0.9 0.7
21 25 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.1 0.9
27 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.4 1.2
29 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.7 1.4
31 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.4 2.3 2.3 2.1 1.8 1.4
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4 2.1 1.8 1.4 7
25 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.1 1.0 0.8
22 27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.4 1.3 1.0
29 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.7 1.5 1.3
31 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.0 1.8 1.4
TC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.4 2.1 1.8 1.4

23
25 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 0.9 0.8 0.7
8
27 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.5 1.4 1.3 1.2 1.1 0.9
29 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.6 1.5 1.4 1.1
31 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.9 1.8 1.7 1.4

9-119 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-28MM1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 2.8 kW AIR FLOW RATE : 8.5 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8

21 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
14 23 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
TC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8

21 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.6
15 23 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8
25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8

1 TC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8

21 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.4
16 23 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.7
25 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
27 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
29 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.8
TC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 1.8
2 21 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.2
17 23 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.5
25 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.7
27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 1.8
29 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 1.8
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.3 1.8
3 21 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.3 1.1
23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.6 1.3
18 25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.9 1.6
27 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.2 1.8
29 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.3 1.8
31 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.3 1.8
4 TC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.3 1.8

21 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.1 0.9
23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.4 1.2
19 25 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.7 1.4
27 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.0 1.7
29 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.3 1.8
5 31 SHC
TC
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.8
3.0
2.7
2.7
2.3
2.3
1.8
1.8

23 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.2 1.0
20 25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7 1.5 1.3
27 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.0 1.8 1.5
29 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.2 1.8
31 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.9 2.8 2.9 2.7 2.3 1.8
6 TC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.0 2.7 2.3 1.8

23 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.2 1.1 0.8
21 25 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.5 1.4 1.1
27 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.1 2.0 2.0 1.8 1.7 1.4
29 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.2 2.0 1.6
31 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.5 2.3 1.8
7 TC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.3 3.0 2.7 2.3 1.8

25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.4 1.3 1.2 1.0
22 27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7 1.6 1.5 1.2
29 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.0 1.8 1.5
31 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.4 2.3 2.1 1.7
TC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.3 3.0 2.7 2.3 1.8
8 23
25 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.2 1.1 1.0 0.8
27 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.8 1.7 1.5 1.4 1.3 1.1
29 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.9 1.8 1.6 1.3
31 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.2 2.1 1.9 1.6

9 9-120

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-36MM1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 3.6 kW AIR FLOW RATE : 9.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

21 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2
14 23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4

21 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.9
15 23 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.3
25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4
TC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.4
1
21 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.7
16 23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.0
25 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.3
27 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.4
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.4
TC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.4

21 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.5
2
17 23 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 1.8
25 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.0
27 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.3
29 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.4
TC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.0 2.4

21 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.6 1.3
3
23 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.9 1.6
18 25 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.3 1.9
27 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.6 2.2
29 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 2.9 2.4
31 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.0 2.4
TC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.4 3.0 2.4
4
21 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.4 1.1
23 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.7 1.4
19 25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.1 1.7
27 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.4 2.0
29 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2.7 2.3
31 SHC
TC
3.5
3.8
3.5
3.8
3.5
3.8
3.5
3.8
3.5
3.8
3.5
3.8
3.5
3.8
3.5
3.8
3.5
3.8
3.5
3.8
3.5
3.8
3.5
3.8
3.5
3.8
3.4
3.4
3.0
3.0
2.4
2.4 5
23 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7 1.5 1.2
20 25 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.1 1.9 1.5
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4 2.2 1.8
29 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.8 2.5 2.1
31 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.1 2.9 2.4
TC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.4 3.0 2.4 6
23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.5 1.3 1.1
21 25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.8 1.7 1.3
27 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.2 2.0 1.6
29 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.5 2.3 1.9
31 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 2.9 2.7 2.2
TC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 3.9 3.4 3.0 2.4 7
25 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.8 1.6 1.4 1.2
22 27 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.1 2.0 1.8 1.5
29 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.5 2.3 2.1 1.7
31 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 3.0 2.8 2.7 2.4 2.0
TC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.5 4.5 4.3 3.9 3.4 3.0 2.4

23
25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.5 1.4 1.2 1.0
8
27 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.9 1.8 1.6 1.3
29 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.2 2.1 1.9 1.6
31 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.6 2.5 2.2 1.9

9-121 9

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-45MM1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 4.5 kW AIR FLOW RATE : 10.5 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

21 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7
14 23 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
25 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
27 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
TC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0

21 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.3
15 23 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.7
25 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0
27 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0

1 TC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.0

21 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.0
16 23 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.4
25 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 2.7
27 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.0
29 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.0
TC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.7 3.0
2 21 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 1.8
17 23 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.1
25 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 2.4
27 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.4 2.8
29 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.7 3.0
TC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.7 3.0
3 21 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.0 1.6
23 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4 1.9
18 25 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.7 2.2
27 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.5 3.4 3.4 3.4 3.1 2.6
29 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.5 2.9
31 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 3.7 3.0
4 TC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.3 3.7 3.0

21 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.7 1.4
23 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.1 1.7
19 25 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.5 2.0
27 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 2.9 2.4
29 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.6 3.2 2.7
5 31 SHC
TC
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.0
4.3
3.6
3.7
3.0
3.0

23 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.1 1.9 1.5
20 25 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.5 2.2 1.8
27 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 2.9 2.6 2.1
29 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.3 3.0 2.5
31 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.7 3.4 2.8
6 TC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 4.8 4.3 3.7 3.0

23 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.0 1.8 1.6 1.3
21 25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.2 2.0 1.6
27 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.6 2.4 1.9
29 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.0 2.8 2.3
31 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.4 3.1 2.6
7 TC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.3 4.8 4.3 3.7 3.0

25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.2 2.0 1.8 1.4
22 27 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.4 2.1 1.7
29 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.0 2.8 2.5 2.1
31 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.6 3.4 3.2 2.9 2.4
TC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.4 4.8 4.3 3.7 3.0
8 23
25 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 1.9 1.7 1.5 1.2
27 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.7 2.5 2.3 2.1 1.9 1.5
29 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.9 2.7 2.5 2.3 1.9
31 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.4 3.1 2.9 2.7 2.2

9 9-122

5GEKPFF 
Capacity Table

2. Cooling Capacity of Indoor Unit

S-56MM1E5
Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW)
This data is when the indoor unit connects with 16HP outdoor unit.
RATING CAPACITY: 5.6 kW AIR FLOW RATE : 12.5 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (°C)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 46
TC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7

21 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2
14 23 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
25 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
27 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
TC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7

21 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.8
15 23 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.2
25 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7
27 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7
TC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 3.7
1
21 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.5
16 23 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 2.9
25 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.3
27 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 3.6
29 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 3.7
TC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.7 3.7

21 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.7 2.2
2
17 23 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 2.6
25 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 2.9
27 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.1 3.3
29 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.6 3.7
TC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.7 3.7

21 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.4 1.9
3
23 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 2.9 2.3
18 25 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.3 2.7
27 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.7 3.1
29 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.2 3.4
31 SHC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 4.6 3.7
TC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.3 4.7 3.7
4
21 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.1 1.7
23 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.6 2.1
19 25 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.4 3.0 2.4
27 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.8 3.4 2.8
29 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.3 3.9 3.2
31 SHC
TC
4.9
6.0
4.9
6.0
4.9
6.0
4.9
6.0
4.9
6.0
4.9
6.0
4.9
6.0
4.9
6.0
4.9
6.0
4.9
6.0
4.9
6.0
4.9
6.0
4.9
6.0
4.7
5.3
4.3
4.7
3.6
3.7 5
23 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.6 2.3 1.8
20 25 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.0 2.7 2.2
27 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.5 3.2 2.6
29 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.0 3.6 3.0
31 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.4 4.0 3.3
TC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.0 5.3 4.7 3.7 6
23 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.5 2.3 2.0 1.6
21 25 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.2 3.1 3.0 2.7 2.4 2.0
27 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.2 2.9 2.3
29 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 3.9 3.7 3.3 2.7
31 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.4 4.1 3.7 3.1
TC 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.5 6.0 5.3 4.7 3.7 7
25 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.7 2.4 2.1 1.7
22 27 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.1 2.9 2.6 2.1
29 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.6 3.3 3.0 2.5
31 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.3 4.0 3.8 3.5 2.9
TC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 6.7 6.0 5.3 4.7 3.7

23
25 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.4 2.1 1.9 1.5
8
27 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 2.8 2.6 2.3 1.9
29 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.6 3.3 3.0 2.7 2.2
31 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.0 3.7 3.5 3.2 2.6

9-123 9

5GEKPFF 
– MEMO –

9-124

5GEKPFF 
201301

%QXKPFF 

You might also like