AWP EPC3 - CCTMU incl.

BPS, CAL, AGMU, Test line,


HPPS and Measuring System on Altosonic-5 Flowmeter

Title:
Sewage Tank Data sheet for CAL Area

Document No.: Class: 2


Page 1 of 5
Rev.: D02

Sewage Tank Data sheet for CAL Area


AWP EPC3 - CCTMU incl. BPS, CAL, AGMU, Test line,
HPPS and Measuring System on Altosonic-5 Flowmeter

Title:

Sewage tank Data sheet for CAL Area


Document No.: Class: 2
Page 2 of 5
Rev.: D03

1- Data Sheet for Industrial Effluents and Flammable Liquids Drain Tank
1. GENERAL DATA

1.1 Description Complete underground drain tank

Gathering of industrial effluents and used flammable liquids


1.2 Purpose and application
after laboratory tests
2 TANK CHARACTERISTICS
2.1 Internal volume (capacity), m3 8
2.2 Diameter, mm 2000
2.3 Process pressure, ATM
2.4 Design Pressure 0.07

2.5 Operating temperature,


minimum 0
maximum 47
nominal 26

steaming temperature 120

2.6 Heater and its location None


2.7 Heat treatment necessity (yes, no) No
2.8 Additional internal equipment No
2.9 Type of support Concrete bed
2.10 Back pressure in gas discharge No
2.11 Installation depth from graded surface to top of tank 800
2.12 Parameters to be monitored and controlled Level measurement and indication
2.13 material as per ASME II
2.14. Type of tank bottom tapered
3. LIQUID CHARACTERISTICS
Industrial effluents and used flammable liquids after laboratory tests
3.1 Description (e.g. oil, toluene, nefras, acetone, ethanol, hexane and heptane
solutions)
3.2 Density of liquid in operating conditions (t=20 0
kg/m3 Variable 700~1090
3.3 Kinematic viscosity, cSt Variable, at 20~60 cSt max.

Liquids: H2S CO2 ~0.01mol%


3.4 Mole fraction of each corrosive component, mol. %
Gas: H2S CO2~ 0.47 mol.% ()

Industrial effluents in their composition may contain traces of acid,


3.5 Characteristics of industrial effluents alkali and oil, with a pH value ranging from
6.5 to 8.5
4 OPERATION AND CONTROL

4.1 Required quantity, units 1


AWP EPC3 - CCTMU incl. BPS, CAL, AGMU, Test line,
HPPS and Measuring System on Altosonic-5 Flowmeter

Title:

Sewage tank Data sheet for CAL Area


Document No.: Class: 2
Page 3 of 5
Rev.: D03

4.2 Scope of delivery Complete delivery:


as per this Data Sheet, with piping. The sketch of tank and
the Table of nozzles are shown in in Figure
level meters with 4-20 mA output; bolting;
-80 for truck tank
connection;
a set of spare parts agreed with Company, for setup,
startup and subsequent 2 years operation a set of
documents

4.3 Service life Minimum 25 years


4.4 Tank location
Outdoor, underground
(indoor/outdoor)

4.5 Liquid character:


Explosive category - IEC 60079-12-78 Explosive group IIB- 3
- IEC 60079-4-75,
Hazard class 3
4.6 Pedestal height above the ground, mm its weight, kg, foundation -
dimensions, mm conditions:
4.7 Environmental
climatic zone 2
minimum winter temperature 0
relative humidity in summer 20%
wet bulb temperature in summer 26
dry bulb temperature in summer 47

1. Complete delivery:
- As per this Data Sheet, with piping. The sketch of tank are shown in Figure G.1;
- level gauges with 4-20 mA output
- bolting;
- Dry breack coupling MCP-80 with plug for truck tank connections
- Spare part
- Flame arrester
- Set of documents
2. Design temprature : 0 C~ 120C
3. The tank shall be made of low carbon steel as per ASME II, with internal anticorrosion coating.
4. Corrosion protection of internal surface shall be two layers of epoxy-phenolic paint 150 μm each. Total coating 300 μm.
5. Corrosion protection of external surface:
- zinc rich epoxy primer one layer 50 μm;
- epoxy paint one layer 150 μm;
- UV resistant PU paint one layer 50 μm.
6. Protection from soil corrosion of underground part of the tank shall be performed by Manufacturer as follows:
- abrasion resistant epoxy glue one layer 200 μm;
- abrasion resistant epoxy glue with glass particles
- one layer 250 μm. Total coating 450 μm.
7. Before the beginning of work all surface to be painted shall be checked and prepared for application of anticorrosion coating in
accordance with the paint Manufacturer instruction manual
AWP EPC3 - CCTMU incl. BPS, CAL, AGMU, Test line,
HPPS and Measuring System on Altosonic-5 Flowmeter

Title:

Sewage tank Data sheet for CAL Area


Document No.: Class: 2
Page 4 of 5
Rev.: D03

8. Preparing and application of anticorrosion paints and quality control of paint coat shall be performaed incomplince with the
manufacture s instruction manual and the standards ISO 8504. Quality of paint coat shall be checked after
complete curing.
9. Coating shall provide for pipe and equipment protection against external corrosion during minimum 15 years.
10. Manhole hatch shall be fitted with turn mechanism or hinges.
11. Provision shall be made for attachment of two earthing devices one on each manhole.
12. Tank drawing to mention support dimensions, maximum foundation loads from equipment
13. Documents shall contain tank characteristics, general view drawing, task order for tank foundation design.
14.The full set of documents for the tank shall be submitted to the Company and Design Contractor before the beginning of
manufacture.
15. To provide a fixed or detachable ladder inside the tank.
16. To provide with the tank a set of spare parts agreed with Company, for setup, startup and subsequent 2 years operation.
17. Manufacturer shall submit permits and approvals, operation documents, operation and maintenance.
18. Piping within battery limits shall be supplied in big assemblies including valves, pipes and fittings.
19. Piping and fittings shall be welded. Flanges shall only be installed at piping connection to the tank, valves and other equipment
having companion flanges, and in segments that will require regular dismantling or replacement.
20. Provision shall be made for minimum on site welding.

Pipe lingth,
Letter Diameter,, mm Purpose Quantity, pcs. Remarks.
mm

hinged
A 800 2000 atm Manhole 1
cover

Hatch for water hinged


B 700 2000 atm 1
disposal cover

C 200 200 atm Water inlet 1 -

blind
D 100 2000 4.0 For level gauge 1
flange

companion
E 100 250 1.6 Vent 1
flange

For sediment companion


F 50 200 atm 1
detachment flange

For level blind


G 50 2000 1.6 1
indication flange
AWP EPC3 - CCTMU incl. BPS, CAL, AGMU, Test line,
HPPS and Measuring System on Altosonic-5 Flowmeter

Title:

Sewage tank Data sheet for CAL Area


Document No.: Class: 2
Page 5 of 5
Rev.: D03