Line current =
√ ∗ ∗
∗
=
√ ∗ ∗ ∗.
=485.99 A
Line current and Phase current is same.
𝒔 𝑽𝒓
Voltage Regulation V.R = *100
.
= ∗ 100
= 3.78%
Losses = 3*I2*R
= 3*485.992*4
= 2834235.36W
= 2.83MW
Efficiency η = *100
= *100
.
= 97.24%
According the given condition voltage regulation is less than 15% and efficiency is greater than
95%
So, the above assumed circuit is satisfied.
5) Select suitable compensation equipment to increase the capacity of the line to a
maximum level.
Suitable compensation equipment to increase the capacity of the line to a maximum level
is Shunt capacitive compensation.
Shunt capacitive compensation method is used improve the power factor. Whenever an
inductive load is connected to the transmission line, power factor lags because of lagging
load current. To compensate it, a shunt capacitor is connected, which draws current
leading to the source voltage. The net result is improvement in power factor.
6) Determine the capacity of shunt compensation equipment to improve the receiving
end power factor to 0.95 lagging. You may make suitable assumptions, but they
must be clearly mentioned.