Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

CADANGAN MEMBINA SEBUAH KOMPLEKS BLOK MASJID YANG MENGANDUNGI:

1) SEBUAH BLOK MASJID SATU TINGKAT


2) 1 UNIT BLOK TANDAS DAN WUDHU' SATU TINGKAT
3) 1 UNIT BLOK KULIAH 2 TINGKAT
4) 8 UNIT KUARTERS 4 TINGKAT
5) 1 UNIT KEBUK SAMPAH.
6) 1 UNIT MENARA AZAN
7) 7 UNIT TEMPAT LETAK MOTOSIKAL BERPALANG DAN BERBUMBUNG.

DI NO. 8 (LOT 34476), JALAN BRP 4/1, SEKSYEN U20, BUKIT RAHMAN PUTRA, 40160
SHAH ALAM, SELANGOR DARUL EHSAN.

UNTUK TETUAN: JABATAN AGAMA ISLAM SELANGOR.

HYDRAULIC CALCULATION FOR ‘BLOK TANDAS & WUDHU’

1. DESIGN FLOW RATE


(base on BS6700:2006)
ITEM DESCRIPTION QUANTITY DESIGN TOTAL
FLOW RATE DESIGN
(LTR/S) FLOW RATE
(LTR/S)
1. WC 12 1.5 1.8
(base on flush
valve pump
capacity)
2. TAP 91 0.20 18.2
3. BASIN 8 0.10 0.8
4. SHOWER 4 0.20 0.8
TOTAL 21.6

Total Design Flow Rate = 21.6 Ltr/sec


= 285.12 igpm

The purpose of this report is to find out the available actual pressure head is sufficient to
supply the water at highest level of bib tap at ablution area. If the discharge residual
pressure at the ablution area is greater than 2.0m, hence the proposed pipe size is
satisfied.

(refer SPAN Guideline in Attachment 1)

2. MINIMUM RESIDUAL HEAD.

Min. Residual Head > 2.0 m

Min. Residual Head = Head Available – Head Required > 2.0 m

Head Available = B.W.L at Roof Tank – Level of Lowest Distribution Pipe


= 4.95 m – 0.00 m
= 4.95 m

Head required = static head + pressure drop due to friction in piping

Where ;

Static head = vertical distance between the bip tap level and level of
distribution pipe in floor slab
= 1.05 m

Pressure drop due friction in piping = 1.59 m (refer Attachment 2)


P=( 6.05 x 105 )( L)(Q1.85)
( C1.85) (D4.87)
Where ;
Q = flow rate in Ltr/min
D = pipe dia. in mm
C = pipe constant
L = Equivalent pipe length and fittings in m

Head required = 1.05 m + 1.59 m


= 2.64 m

Hence, Min. Residual Pressure = Head Available – Head Required > 2.0 m
= 4.95 m – 2.64 m > 2.0 m
= 2.31 m > 2.0 m

3. CONCLUSION.

It can be seen that the discharge residual pressure at the highest level of bib tap at
ablution area is 2.31 meter. Since the discharge residual pressure is greater than
2.0 meter, then the proposed pipe size are acceptable.

You might also like