Professional Documents
Culture Documents
2019-Me-58 Hvac Lab Reports
2019-Me-58 Hvac Lab Reports
2019-Me-58 Hvac Lab Reports
LAHORE
Subject:
Heat Ventilation and Air-Conditioning Laboratory
Assessment:
Lab Reports
Submitted To:
Sir Ahmad Naveed
Submitted By:
Rohan Saif
2019-ME-58
Table of Contents
1.1.1 Construction of R514 Heat Pump............................................................................10
1.1.2 Types of heat pump:................................................................................................11
1 Heat pump unit Experiment 1................................................................................................15
1.1 Procedure:.......................................................................................................................15
1.2 Calculations:....................................................................................................................15
1.3 Observations Table:........................................................................................................15
1.4 Specimen Calculations:...................................................................................................15
1.5 Results and Discussion....................................................................................................16
1.5.1 Effect of Condenser Outlet Temperature on COP...................................................16
1.5.2 Compressor Work Input vs Condenser Outlet Temperature...................................17
1.5.3 Condenser Heat transfer Rate vs Condenser Outlet Temperature...........................17
1.6 Conclusion:.....................................................................................................................18
2 heat pump unit Experiment Number 2:.................................................................................19
2.1 Objective:........................................................................................................................19
2.2 Procedure:.......................................................................................................................19
2.3 Calculations:....................................................................................................................19
2.4 Observations Table:........................................................................................................19
2.5 Specimen Calculations:...................................................................................................20
2.6 Energy Balance...............................................................................................................20
2.6.1 ¤Condenser..............................................................................................................20
2.6.2 ¤Compressor............................................................................................................20
2.7 Results and Discussion....................................................................................................21
2.7.1 Ph Diagram of the Experiment................................................................................21
2.8 Energy Balance Across Condenser and Compressor......................................................21
3 heat pump unit Experiment 3.................................................................................................23
3.1 Objective:........................................................................................................................23
3.2 Procedure:.......................................................................................................................23
3.3 Observation Table:..........................................................................................................23
3.4 Specimen Calculations....................................................................................................23
3.5 Results and Discussion....................................................................................................24
3.5.1 COP vs Condenser Outlet Temperature..................................................................24
3.5.2 Heat Transfer in Evaporator vs Condenser Outlet Temperature.............................25
3.5.3 Compressor Work Input vs Condenser Outlet Temperature...................................26
3.5.4 Heat Output Rate vs Condenser Outlet Temperature..............................................26
3.6 Conclusion:.....................................................................................................................27
4 heat pump unit Experiment 4.................................................................................................28
4.1 Objective.........................................................................................................................28
4.2 Procedure........................................................................................................................28
4.3 Observation Tables.........................................................................................................28
4.4 Specimen Calculations....................................................................................................28
4.5 Results and Discussion....................................................................................................29
4.5.1 Volumetric Efficiency vs Pressure Ratio.................................................................29
4.6 Conclusion:.....................................................................................................................30
1.1.3 Single compressor unit:...........................................................................................33
1.1.4 Multi compressor unit:.............................................................................................34
1.1.5 R713 Refrigeration Unit..........................................................................................35
1 refrigeration unit Experiment 1.............................................................................................37
1.1 Objectives:......................................................................................................................37
1.2 Procedure........................................................................................................................37
1.3 Observations:..................................................................................................................37
1.4 Results and Discussion....................................................................................................37
2 refrigeration unit Experiment 2.............................................................................................39
2.1 Objective.........................................................................................................................39
2.2 Procedure........................................................................................................................39
2.3 Calculations:....................................................................................................................39
2.4 Table:..............................................................................................................................39
2.4.1 Energy Balance Across Condenser..........................................................................40
2.4.2 Energy Balance Across Evaporator.........................................................................41
2.5 Specimen Calculations:...................................................................................................41
2.6 Results and Discussion....................................................................................................43
3 refrigeration unit Experiment 3.............................................................................................45
3.1 Objective.........................................................................................................................45
3.2 Procedure........................................................................................................................45
3.3 Observation Tables.........................................................................................................45
3.3.1 For Condensing Temperature of 35 oC....................................................................45
3.3.2 For Condensing Temperature of 40 oC....................................................................46
3.3.3 For Condensing Temperature of 43 oC....................................................................46
3.4 Sample Calculations........................................................................................................46
Table of Figures
Figure 1-2: Carnot cycle..................................................................................................................9
Figure 1-3: T-s diagram of the vapor compression cycle..............................................................10
Figure 1-4: P-h diagram of vapor compression cycle....................................................................10
Figure 1-5 Air source heat pump...................................................................................................11
Figure 1-6 Geothermal heat pump.................................................................................................12
Figure 1-7 Exhaust air pump.........................................................................................................13
Figure 1-8 Solar assisted heat pump..............................................................................................14
Figure 1-9 Hybrid heat pump........................................................................................................14
Figure 11 COP vs Condenser Outlet Temperature........................................................................16
Figure 12 Compressor work input vs Condenser Outlet Temperature..........................................17
Figure 13 Heat Output Rate vs Condenser Outlet Temperature....................................................18
Figure 14 Ideal and Real Cycles on Ph Diagram...........................................................................21
Figure 15 Energy Balance Across Condenser and Compressor....................................................22
Figure 16 COP vs Condenser Outlet Temperature........................................................................25
Figure 17 Heat Transfer in Evaporator vs Condenser Outlet Temperature...................................25
Figure 18 Compressor Work Input vs Condenser Outlet Temperature.........................................26
Figure 19 Heat Output rate vs Condenser Outlet Temperature.....................................................27
Figure 20 Volumetric Efficiency vs Pressure Ratio......................................................................30
Figure 5-2 Refrigeration unit.........................................................................................................33
Figure 5-3 Single compressor unit.................................................................................................34
Figure 5-4 Multi compressor unit..................................................................................................35
Figure 5-5: Schematic diagram of R713 refrigeration unit...........................................................35
Figure 27 Ph Diagram for R134a...................................................................................................38
Figure 28 Ph Diagram for R134a...................................................................................................38
Figure 29 Energy Balance for Evaporator.....................................................................................43
Figure 30 Energy Balance for Condenser......................................................................................44
Figure 31 Refrigeration Duty vs Evaporator Pressure...................................................................47
Figure 32 Power Input...................................................................................................................49
Figure 33 Contour Plot For COP...................................................................................................51
Figure 34: Single zone air-conditioning system............................................................................53
7. Pressure Gauges: To measure the pressure of the condenser and evaporator, pressure
gauges are used. These pressure gauges measure gauge pressure.
8. Electrical Energy Consumption Meter: To measure the energy consumed by the
compressor, an electrical energy meter is used.
9. Fail Safe Device: Different fail-safe devices have been incorporated into the system to
avoid overload of condenser, evaporator and compressor.
installation of vertical heat exchanger piping or the excavation of trenches to install horizontal
heat exchange fluid pipe (water with a little antifreeze).
Thermal heat pumps, which transport heat from a building to the ground when it is extremely hot
outside, may also be used to cool buildings when it is extremely hot outside. It is possible, for
example, to recycle heat underground by installing solar collectors or pipes in parking lots, and
then to use that heat.
The temperature of the surrounding air has an impact on the amount of heat gathered from a
variety of sources by hybrid heat pumps, also known as dual source heat pumps. Rather of use
air when the external ambient temperature is greater than 4-8 degrees Celsius, ground water
should be utilized when the outdoor temperature is less than 4-8 degrees Celsius (40-50 degrees
Celsius) (40-50 degrees Fahrenheit). In addition to storing warmer weather from other sources
through air exchanges or building heat exchangers while the heat pump is not in operation, these
twin-sourcing systems may store warmer weather from other sources while the heat pump is in
operation. The following are two significant advantages of this technique over other
approaches. Second, it increases the soil source temperature while increasing the heat pump
system's energy efficiency by around 4% per degree Celsius rise in soil source temperature. This
is a low-cost interior air conditioning option (if the ground water is relatively stagnant).
1.4SPECIMEN CALCULATIONS:
Calculations have been shown for fourth set of readings with mw = 15 g/s, T6 = 39 oC, T5=23.1oC
and X = 49.3 s
6 3.6 ×10 6
240 rev per kWh=3.6 ×10 Joules 1 rev per kWh= Joules 1 rev per kWh=15000 Joules
240
15000
Power Input= W
X
15000 15000
W comp = = W =0.3043 kW
X 58.1 comp
q con=m w ×C pw × ( T 6−T 5 )q con=( 15 ×1 0−3 ) × ( 4180 ) × ( 39−23.1 )q con=0.9969 kW
q 0.9969
COP= con = COP=3.28
W comp 0.3043
2.3CALCULATIONS:
Heat Transfer ¿ Refrigerant=mref (h 2−h3 )Heat Transfer ¿ Water =m w × C pw × ( T 6−T 5 )
15000
Power input ¿Compressor =
X
Enthalpy Change of R134 a=mref (h2−h1 )
2.4OBSERVATIONS TABLE:
Pressure at Comp Suction (kPa) P1 410
2.5SPECIMEN CALCULATIONS:
Fixing the States
15000
Power input ¿Compressor =
X
15000
¿
49.3
W compressor =304 W
Enthalpy Change of R134 a=mref (h2−h1 )
¿ 5.8 × ( 338−305 )
¿ 191W
2.7RESULTS AND DISCUSSION
2.7.1 PH DIAGRAM OF THE EXPERIMENT
The data obtained after the experiment was used to visualize the state points of the refrigerant on
the Ph diagram. There were two cases which have been analyzed:
and refrigerant which causes turbulence, thus adding to the losses. Moreover, if the mass
flow rate is too high, then proper heat transfer becomes a bit difficult to achieve and all of
the heat energy present in the refrigerant could not be collected by the cooling water.
Compressor which was used in this experiment was rotatory compressor, and it was
operated at 2800 rpm. At such a high value of RPM, the volumetric efficiency of the
compressor comes into play and restricts the compression process. The effect of pressure
ratio on the volumetric efficiency has been analyzed in detail in next experiments. The
point is that due to the limit imposed by volumetric efficiency, not all of the input energy
provided to the compressor is imparted to the refrigerant, some of the energy is lost in the
movable parts of the compressor, and some of the energy is lost due to the compression
not being isentropic. These are the possible causes which make the input and output
energy rates to have a difference between each other.
3.3OBSERVATION TABLE:
Sr No 1 2 3 4
Pressure at 1 P1 390 400 405 410
Pressure at 2 P2 800 860 960 1075
Temperature at 1 T1 18.4 17.2 16.6 13.8
Temperature at 2 T2 45.6 48.3 53.6 39.5
Temperature at 3 T3 27.9 31.7 34.6 39.5
Temperature at 4 T4 9.3 10.2 11 11
Refrigerant Flow Rate mref 6 5.9 5.8 5.8
Time Per Revolution X 58.1 54.1 51.5 49.3
T6 28 31 35 39
Condenser Water Temperature In/Out
T5 21 22 22 23
Heat Transfer in Evaporator qevap 1032 979 899 858
Heat Transfer in Condenser qcond 1164 1139 1090 1079
Compressor Input Wcom 258 277 291 304
COP 4.5 4.1 3.7 3.5
3.4SPECIMEN CALCULATIONS
Draw the state points on p-h diagram as follows by intersection of:
P1 = 410 kPa and T1 = 13.8oC
P2 = 1075 kPa and T2 = 29.3oC
P3 = 1075 kPa and T3 = 39.5oC
T4 = 10.9oC and h3 = h4
The following readings were taken from p-h diagram:
h1 =305 kJ/kg
h2 = 343 kJ/kg
h3 = h4 = 157 kJ/kg
(1) Work input rate across Compressor
wcom = 15000 / X
wcom = 15000 / 49.3
wcom = 304 W
qcon = 1079W
(3) Heat Transfer in Evaporator
qevap = mr x (h1 – h4)
qevap = 5.8*(305-157)
qevap = 858 W
(4) Coefficient of Performance COP = wcom / qcon
COP = 1079/304
COP=3.5
that as we move towards left in the temperature axis, the corresponding work input demand is
observed to be increasing.
4.3OBSERVATION TABLES
Sr No 1 2 3 4
Compressor Suction Pressure (kPa) P1 (kPa) 390 400 405 410
Compressor Suction temperature T1 (oC ) 18.4 17.2 16.6 13.8
Compressor Suction Specific Volume v1 0.054 0.053 0.052 0.051
(m3/kg)
Volume Flow rate at compressor V1 0.000324 0.000313 0.000302 0.000296
Suction(m3/s)
Compressor Delivery Pressure(kPa) P2 800 860 960 1075
Ref Flow Rate kg/s mref 6 5.9 5.8 5.8
Compressor Pressure ratio rp 2.05 2.15 2.37 2.62
Volumetric Efficiency ηv 78.45% 75.71% 73.03% 71.62%
4.4SPECIMEN CALCULATIONS
Volume Flow Rate at Compressor Suction V1 = mrv1 (I)
Compressor Pressure Ratio rP = P2/P1 (II)
Volumetric Efficiency ηv = V1 / Vs (III)
where ‘Vs’ is compressor Swept Volume
State point (1) may be plotted on p-h diagram to read out v1 by using P1 and T1:
Specific Volume comes out to be = 0.054 m3/kgs
Volume Flow Rate at Compressor Suction V1 = mrv1 (IV)
V1 = 0.006×0.054
V1 = 0.000324 m3/s
Compressor Pressure Ratio rP = P2/P1 (V)
rP = 800/390
rP = 2.05
The compressor swept volume rate (assuming that it runs at 2800 rev /min)
REFRIGERAT
ION UNIT
The following is the definition of a 'cooling unit' in terms of energy: "A "cooling unit" is defined
as the system which reduces temperature caused by mechanical action. It is necessary to utilize
an electric engine to power a pump in order to compress coolant to the proper pressure when a
traditional cooling unit is used. When subjected to particular temperatures and pressures, a
substance known as a refrigerant can change its condition from a liquid to a gaseous form. In
response to the reduction in pressure, heat is taken from the liquid and evacuated from the unit.
In addition, the coolant evaporates as a result of the reduction in pressure. In order to complete
the cooling cycle, the heat must be absorbed and the compressor must be returned to its original
position before the cycle can be repeated. A few cooling units, as opposed to the vast majority of
other cooling units, use gas (natural gas or LPG) in a way that does not necessitate the use of a
compressor, as opposed to the vast majority of other cooling systems. The gaseous refrigerant
must be lit and burned in order to heat the chemical solution in which it has been absorbed. The
heating process takes the coolant from the system and condenses it into a liquid state.... After
then, the concentrated refrigerant evaporates and absorbs heat from its surrounding atmosphere.
Afterward, the evaporating coolant is reabsorbed into the chemical solution, and the heat from
the solution is released as waste heat, and the process continues indefinitely as long as the
coolant is in solution. Refrigerators, freezers, and air conditioning systems all have cooling units
as a result of the fact that they are meant to do so.
In a cooling system, the cooling unit is a component that provides the foundation for the whole
system. By utilizing these approaches, it is possible to produce a wide range of temperature
ranges in order to induce cold.
The compressor is a crucial component of the cooling unit's operation and should not be taken
for granted. However, other types of compressors, such as screws or spiral compressors, may
also be used in some situations. The reciprocal compressor is the most common type of
compressor, but other types of compressors, such as screws or spiral compressors, can also be
used in certain cases. Reciprocal compressors are the most commonly encountered form of
compressor. Depending on the operating requirements, single compressor systems or multi-
compressor plants should be designed and constructed. Russia's industrial sector not only has
mastered the repair and maintenance of cooling systems, but it also designs and manufactures
this type of equipment. However, it should be noted that the great bulk of the components still
need to be imported from other countries in order for the system to be fully functional.
Therefore, foreign firms are presently responsible for the vast bulk of compressor production in
the United States.
1.3OBSERVATIONS:
Compressor Compressor Expansion Evaporator
Condense Water
S Evaporato Suction Delivery Valve Inlet Inlet
r Flow
r. r Pressure Temperatur Temperatur Temperatur Temperatur
Pressure Rate
N (kPa) e e e e
(kPa) (g/s)
o (oC) (oC) (oC) (oC)
Pevap Pcom mw T1 T2 T3 T4
1 296 1240 7.6 19.9 76.8 43.1 -2.8
2 296 1240 10.4 17.5 70.7 37.9 -1.8
3 301 1026 18.2 18.9 59.1 31.3 -2.27
4 290 825 75 21.2 62.5 22.5 -2.9
5 148 990 7.8 4.8 61.9 26.7 -20
6 209 990 12.8 11.6 65.1 28.4 -11.9
7 248 993 17.3 16.1 65.8 29.1 -7.6
8 348 1003 38.6 27.1 66.3 29.9 1.7
9 400 1007 52 36.2 68.1 29.7 6.4
1.4RESULTS AND DISCUSSION
From the different ranges of pressures in the evaporator and the condenser, there are different Ph
Diagrams possible one for each combination of pressures. Here we are presenting two of the
cases and their Ph diagrams have been shown in Figure 23 and Figure 24.
For the first case the Condenser was held at saturation pressure of 1240 kPa and evaporator was
at the pressure of 296 kPa, the corresponding saturation temperatures were 47.6 oC and 0.3oC.
For the second diagram the Condenser is at 1388 kPa with saturation temperature of 52 oC and
the evaporator is at 300 kPa with a saturation temperature of 0.7 oC.
The definition of points from 1 to 4 have been done by using the Engineering Equations solver,
and the data has been used to plot the Ph Chart.
2.1OBJECTIVE
In this lab session, a detailed energy balance analysis of all the components of refrigeration cycle
have been conducted.
2.2PROCEDURE
Switch on the refrigeration unit while keeping all of the essential safeguards in mind.
Keep the equipment running to ensure the accuracy of the measurements.
A reading knob is provided for each reading knob so that the evaporator's input may be
adjusted.
To maintain the evaporator pressure constant, the water flow rate is adjusted.
2.3CALCULATIONS:
Qevp =V evp × I evp
Refrigerant Enthalpy Change=mr ×( h1−h 4)
Qcond =mw × C p ×(T 6 −T 5 )
Ps =T × ω
2 × π × Nm
Pf =0.165 × F f ×
60
Pel =V m × I m × cos ϕ
2.4TABLE:
Water Compressor Compressor
Evaporator Condenser Refrigerant
Flow Suction Delivery
Sr.N Pressure Pressure Flow Rate
Rate Temperature Temperature
o (kPa) (kPa) (g/s)
(g/s) (oC) (oC)
Pevap Pcond mw mr T1 T2
1 300 1388 7.6 3.5 19.9 76.8
2 296 1240 10.4 4.6 17.5 70.7
3 301 1026 18.2 5 18.9 59.1
4 290 825 75 5.1 21.2 62.5
5 148 990 7.8 2.3 4.8 61.9
6 209 990 12.8 3.6 11.6 65.1
7 248 993 17.3 4.4 16.1 65.8
8 348 1003 38.6 6.5 27.1 66.3
9 400 1007 52 7.7 36.2 68.1
Expansion
Evaporator Inlet Water Inlet Water Outlet Evaporator Evaporator
Valve Inlet
Temperature Temperature Temperature Volts Amperes
Temperature
(oC) (oC) (oC) (V) (A)
(oC)
T3 T4 T5 T6 Vevap Ievap
43.1 -2.8 16 43.5 158 4.6
37.9 -1.8 14 37.1 171 5
31.3 -2.27 13.6 27.9 183 5.3
22.5 -2.9 13.2 17.1 188 5.4
26.7 -20 15.4 29.2 112 3.25
Energy Balance:
Evaporator
Evaporator Heat Input Qevp = Vevp × Ievp
Qevp = 158 x 4.6
Qevp= 726.8 W
R134a Enthalpy change Rate = mr × (h1 – h4)
= 3.5 x (268-112.8)
= 0.543 kW
Condenser
Heat Transfer to Water Qc = mw Cp × (T6 – T5)
Qc = 7.6 x 4.18 (43.5-16)
Qc = 873.62 W
R134a Enthalpy change Rate = mf × (h2 – h3)
= 3.5 x (305-112.8)
= 0.672 kW
Compressor
Shaft Power Ps = Tω
Ps = 0.165 × F × (2π nm)/60
Ps = 12.88126
Friction Power Pf = 0.165 × Ff × (2π nm)/60
where Ff is the motor load cell reading with compressor suction valve closed i.e., the compressor
doing no net work done on the gas.
Typically, this load is 3 N.
Hence,
Pf = 11.8904
Compressor indicated power Pi = Ps – Pf
Pi = 12.88126- 11.8904
Pi = 0.990866
R134a Enthalpy change Rate = mr × (h2 – h1)
= 3.5x(305-268)
= 140 W
0.800
0.600
0.400
0.200
0.000
1 2 3 4 5 6 7 8 9
Observation Number
1.000
0.800
0.600
0.400
0.200
0.000
1 2 3 4 5 6 7 8 9
Observation Number
3.1OBJECTIVE
The objective of this lab session is to analyze how the refrigeration duty varies with the
condensing temperature.
3.2PROCEDURE
Switch on the refrigeration unit while keeping all of the essential safeguards in mind.
Keep the equipment running to ensure the accuracy of the measurements.
A reading knob is provided for each reading knob so that the evaporator's input may be
adjusted.
To maintain the evaporator pressure constant, the water flow rate is adjusted.
3.3OBSERVATION TABLES
3.3.1 FOR CONDENSING TEMPERATURE OF 35 O C
Condensing Saturation Temperature 35 oC
Evaporator Condenser Evaporator
Evapora Evaporato Refrigera
Sr Saturation Saturation Saturation
tor Volts r Amperes tion Duty
No Pressure Pressure Temperature
kPa kPa (oC) V A W
1 140 900 -29 100 2.8 280
2 178 900 -25 120 3.3 396
3 200 900 -21 140 3.8 532
4 240 900 -17 160 4.3 688
3.3.2 FOR CONDENSING TEMPERATURE OF 40 O C
3.6CONCLUSION
It has been concluded from the experiment that the increasing condensing temperature while
having a fixed evaporator pressure reduces the Refrigeration Duty, and increasing the saturation
temperature of evaporator while holding the condensing temperature constant increases the
Refrigeration Duty.
4.1OBJECTIVE
In this lab session, it will be analyzed what are the effects of evaporation temperature on
electrical, shaft and indicated power of compressor.
4.2PROCEDURE
Switch on the refrigeration unit while keeping all of the essential safeguards in mind.
Keep the equipment running to ensure the accuracy of the measurements.
A reading knob is provided for each reading knob so that the evaporator's input may be
adjusted.
To maintain the evaporator pressure constant, the water flow rate is adjusted.
4.3OBSERVATION TABLES
Evaporator Moto Motor
Evaporator Pressure Saturation Evaporato Evaporato
Sr. r Ampere
(kPa) Temperatur r Volts r Amperes
No. e Volts s
Pevap Tevap Ve Ie Vm Im
1 300 0.7 158 4.6 239 3.7
2 296 0.3 171 5 242 3.78
3 301 0.7 183 5.3 244 3.8
4 290 -0.3 188 5.4 236 3.4
5 148 -17.5 112 3.25 248 3.7
6 209 -9.0 142 4.13 249 3.79
7 248 -4.5 161 4.7 247 3.76
8 348 4.8 202 5.9 246 3.8
9 400 8.9 215 6.6 247 3.84
N Nc Nm W W W W
13.2 480 1478 504 337.1 76.6 260
10.9 480 1478 521 278.4 76.6 202
10.8 480 1478 529 275.8 76.6 199
10.8 480 1478 457 275.8 76.6 199
8.3 480 1478 523 212.0 76.6 135
10.3 480 1478 538 263.0 76.6 186
10.8 480 1478 529 275.8 76.6 199
Power Input
400.0 Shaft Power Friction Power Indicated Power
350.0
300.0
250.0
Watts
200.0
150.0
100.0
50.0
0.0
1 2 3 4 5 6 7 8 9
Observation Number
Figure 28 Power Input
4.5CONCLUSION
It has been concluded from the analysis that a part of shaft power is always lost due to friction
and the indicated power which is actually available for doing useful work is lower than the actual
power input.
1.2 OBJECTIVE:
In this lab session, it will be analyzed what are the effects of evaporation and condensing
temperature on COP
5.1PROCEDURE:
Switch on the refrigeration unit while keeping all of the essential safeguards in mind.
Keep the equipment running to ensure the accuracy of the measurements.
A reading knob is provided for each reading knob so that the evaporator's input may be
adjusted.
To maintain the evaporator pressure constant, the water flow rate is adjusted.
5.2OBSERVATION TABLE
Sr. No 1 2 3 4 5 6 7 8 9
Condenser Pressure (kPa) 1388 1240 1026 825 990 990 993 1003 1007
Evaporator Pressure (kPa) 300 296 301 290 148 209 248 348 400
Evaporator Saturation 0.7 0.3 0.7 -0.3 -17.5 -9.0 -4.5 4.8 8.9
Temperature (oC)
Evaporator Volts (V) 158 171 183 188 112 142 161 202 210
Evaporator Amperes (A) 4.6 5 5.3 5.4 3.25 4.13 4.7 5.9 6.6
Refrigeration Duty (W) 727 855 970 1015 364 586 757 1192 1386
Electric Motor Volts (V) 239 242 244 236 248 249 247 246 247
Electric Motor Amperes (A) 3.7 3.78 3.8 3.4 3.7 3.79 3.76 3.8 3.84
Motor Input (W) 884 915 927 802 918 944 929 935 948
Coefficient of Performance 0.82 0.93 1.05 1.27 0.40 0.62 0.81 1.27 1.46
Air Recirculation
Unit
Following are the different types of air-conditioning system that are used:
1. Single Zone System
2. Terminal Reheat System
3. Dual Duct System
4. Variable Air Volume System
1.2.1 SINGLE ZONE SYSTEM
A single zone air conditioning system shown in consist of following components:
1. Cooling and Dehumidification Coils
2. Heating Coils
3. Supply Fan
4. Humidifier
1.3OBSERVATION TABLE
Dry-Bulb Temperature of fan inlet TAd 24.9
Dry Bulb Temperature after Pre-Heater TBd 28.6
Dry Bulb temperature Before Orifice TDd 26.7
Wet Bulb Temperature before Orifice TDw 23
Orifice Differential Pressure h 3.3
Preheater Input Qp 0.5
Specific heat Capacity Cp 1.35
1.4SPECIMEN CALCULATIONS
For specific volume:
1.5CONCLUSION
The specific heat capacity of the air as measured from the experiments is 1.35 kJ/kg.K
2.3OBSERVATION TABLE
Sr No 1 2 3 4
td 25 25 - -
Intake Temperature (oC)
tw 17 17 - -
td 28 29 33 -
After Preheating Temperature (oC)
tw 18 18 27 -
td - - 24 20
After Cooling Temperature (oC)
tw - - 23 18
td - - - 29
After Reheating (oC)
tw - - - 21
Ref. Flow Rate (g/s) mr - - 14.5 -
0.5 2.2 2.2 2.2 2.2
Preheater Current (A)
1 0 0 0 0
1 0 4.4 0 0
Boiler Current (A)
2 0 8.4 0 0
2 0 8.4 8.4 8.4
Reheater Current (A) 1.5 0 0 0 4.6
0.5 0 0 0 2.2
Intake Orifice Differential mmH2O z 3.4 3.3 3.1 3.2
Fan Current (A) Ir - - - 0.6
Refrigerant Temperature Expansion Valve Inlet
T11 - - 44.1 -
(oC)
Refrigerant Temperature at Evaporator Outlet (oC) T13 - - 15.9 -
Condenser Pressure (kPa) Pc - - 1290 -
Evaporator Pressure (kPa) Pe - - 420 -
2.4SPECIMEN CALCULATIONS
Heating B-C (1 set of readings):
st
At the evaporator:
3 REFERENCES
Imran, M., Pambudi, N. A., & Farooq, M. (2017). Thermal and hydraulic optimization of plate
heat exchanger using multi objective genetic algorithm. Case studies in thermal
engineering, 10, 570-578.
Legg, R. (2017). Chapter 11 - Exhaust Air Heat Recovery. In (pp. 203-211).
Shahzad, M. K., Rehan, M. A., Ali, M., Mustafa, A., Abbas, Z., Mujtaba, M., . . . Yousaf, M. R.
(2019). Cooling Performance Assessment of a Slinky Closed Loop Lake Water Heat
Pump System under the Climate Conditions of Pakistan. Processes, 7(9), 553.
4 APPENDIX
The plots used in this report are made using MATLAB, the MATLAB scripts for these plots are
given below:
4.1SCRIPT 1
%% A) Heat Pump
%% A1) Exp 1
COP = [4.01 3.75 3.55 3.28];
T6 = [27.7 30.9 35.1 39];
Pcomp = [258.2 277.2 291.3 304.3];
Qout = [1036.6 1040.8 1036.7 996.9];
figure
SplinePlot(T6,COP,'Condenser Outlet Temperature (^oC)','COP','COP vs T_6')
figure
SplinePlot(T6,Pcomp,'Condenser Outlet Temperature (^oC)','Compressor Work Input
(kW)','W_{compressor} vs T_6')
figure
SplinePlot(T6,Qout,'Condenser Outlet Temperature (^oC)','Heat Output Rate
(kW)','Q_{condenser} vs T_6')
%% A2) Exp 2
Qcond = [1102 1003];
Qcomp = [191 304];
X = [Qcond;Qcomp];
figure
bar(X)
NAMES ={'Condenser','Compressor'};
xticklabels(NAMES)
legend({'Input Power','Heat Transfer By Refrigerant'})
set(gca,'fontweight','bold')
ylabel('Power Rating (kW)')
title('Energy Balance Accross Condenser and Compressor')
%% A3) Exp 3
COP = [4.5 4.1 3.7 3.5];
T6 = [28 31 35 39];
%% B) Refrigeration Unit
%% B3) Exp 3
Pevap = [140, 178, 200, 240;
142 180 210 240;
160 190 215 250];
Qe = [280, 396, 532, 688;
270 384 532 672;
260 372 518 656];
markers = {'d','v','h'};
for i = 1:3
kkk = linspace(Pevap(i,1),Pevap(i,end));
kk = fit(Pevap(i,:)',Qe(i,:)','spline');
plot(kkk,kk(kkk),'linewidth',1.25)
hold on
end
grid on
box on
xlabel('Evaporator Saturation Pressure (kPa)')
ylabel('Refrigeration Duty (kW)')
title('Refrigeration Duty vs Evaporator Pressure')
legend({'Tsat_{cond} = 35 ^oC','Tsat_{cond} = 40 ^oC' ,'Tsat_{cond} = 43
^oC'},'NumColumns',3,'location','southoutside')
function SplinePlot(x,y,Xlabel,Ylabel,Title)
if nargin<3
Xlabel = "";
Ylabel = "";
Title = "";
end
Lwid = 1.25;
X = linspace(x(1),x(end));
Y = interp1(x,y,X,'spline');
plot(X,Y,'linewidth',Lwid,'color','k')
hold on
plot(x,y,'marker','d','MarkerFaceColor','Yellow','linestyle','none')
set(gca,'fontweight','bold')
xlabel(Xlabel)
ylabel(Ylabel)
title(Title)
box on
grid on
end
function myPlot(x,y,Xlabel,Ylabel,Title)
Lwid = 1.25;
X = linspace(x(1),x(end));
Y = interp1(x,y,X,'linear');
plot(X,Y,'linewidth',Lwid,'color','k')
hold on
plot(x,y,'marker','d','MarkerFaceColor','Yellow','linestyle','none')
set(gca,'fontweight','bold')
xlabel(Xlabel)
ylabel(Ylabel)
title(Title)
box on
grid on
end