2 Release Notes
Release Note
Abstract
The intention of the release notes is to supply both internal and external
customers with information about the contents of the delivery. This information
should be used as a reference for software and hardware revisions, changes,
contents, and references to other documents where greater detail is required. The
purpose is not to duplicate information but to flag important information and
where possible reference other documents that need to be studied to ensure
successful implementation of the package.
© Ericsson AB 2020
All rights reserved. The information in this document is the property of
Ericsson. Except as specifically authorized in writing by Ericsson, the receiver
of this document shall keep the information contained herein confidential and
shall protect the same in whole or in part from disclosure and dissemination
to third parties. Disclosure and disseminations to the receiver's employees
shall only be made on a strict need to know basis. The information in this
document is subject to change without notice and Ericsson assumes no
liability for any error or damage of any kind resulting from use of the
information.
1 Introduction ........................................................................................................... 3
1.1 General............................................................................................................... 3
1.1.1 Revision History .............................................................................................. 3
1.1.2 Availability ........................................................................................................ 3
1.2 Prerequisites .................................................................................................... 3
2 Release Information ............................................................................................. 3
2.1 SW Identity ...................................................................................................... 3
2.2 Changes since Previous Release ............................................................... 4
2.2.1 New Functionality .......................................................................................... 4
2.2.2 Corrected Trouble Reports .......................................................................... 4
2.2.3 MOM ................................................................................................................... 5
2.2.4 Fault Management ........................................................................................ 5
2.2.5 Performance Management ......................................................................... 5
2.2.6 OAM .................................................................................................................... 6
2.2.7 General Public Licensed Code .................................................................... 6
2.2.8 Security Vulnerabilities in FOSS components ....................................... 6
2.3 Upgrade Paths................................................................................................. 6
2.4 Dependencies .................................................................................................. 7
2.5 License ............................................................................................................... 7
3 Known issues.......................................................................................................... 7
3.1 Open Trouble Reports ................................................................................... 7
3.2 Restrictions ....................................................................................................... 8
3.3 Other Known Issues ...................................................................................... 8
2020-12-03 1/109 47-CXP 901 7878/2-5 Uen Rev C © Ericsson AB 2020 2 (8)
1 Introduction
1.1 General
This document contains all the delivered content of Ericsson Cabinet Controller
SW SCU 09 01 20.Q2.2.
1.1.2 Availability
1.2 Prerequisites
2 Release Information
2.1 SW Identity
R-State R21C
Table 1 SW Identity
2020-12-03 1/109 47-CXP 901 7878/2-5 Uen Rev C © Ericsson AB 2020 3 (8)
2.2 Changes since Previous Release
More information can be found in SCU 20.Q2.2 Network Impact Report (1/109
48-FGC 101 3492-4 Uen).
HY41980 ESC: Load1 and Load2 LVD1 and LVD2 disconnect and
attributes can't be changed reconnect levels cannot be changed if
on HPM disconnectedMethod is set to Time on
E6160 setup.
2020-12-03 1/109 47-CXP 901 7878/2-5 Uen Rev C © Ericsson AB 2020 4 (8)
MC1800D FW version 2.00 and
less
MC2600 FW version 2.38 and
higher
HY72881 alarm Unsupported Battery Alarm is raised for all Shoto HW versions
Type except R2B.
2.2.3 MOM
No changes.
eventType equipmentAlarm
probableCause x733EquipmentMalfunction
defaultSeverity warning
perceivedSeverity notSet
Manual Mode alarm, with additional text “Control method is set as ’Manual’” will
be triggered if the power system is in the manual mode of operation during
regular state. Applicable for MC family of power controllers only.
No changes.
2020-12-03 1/109 47-CXP 901 7878/2-5 Uen Rev C © Ericsson AB 2020 5 (8)
2.2.6 OAM
No changes.
This release includes Free and Open Source SW (FOSS) under the terms of GNU
General Public License (GPL) and GNU Lesser General Public License (LGPL).
These programs are free software, which can be re-distributed and/or modified
under the terms of GPL respectively LGPL as published by the Free Software
Foundation.
To fulfill the GPL terms, the corresponding source code can be delivered upon
customer request through SW Gateway.
A list of all included FOSS can be found in document Free and Open Source
Software, included in the CPI library.
2020-12-03 1/109 47-CXP 901 7878/2-5 Uen Rev C © Ericsson AB 2020 6 (8)
2.4 Dependencies
* SCU 09 01 20.Q2.2 will be supported by ESCM until ESCM version released at 21.Q4 as support
needs to be assured for 18 months.
2.5 License
3 Known issues
HY58500 Rectifier alarm and number of Deleted rectifiers with respective rectifier
rectifiers not updated correctly alarms re-appear after deletion.
in SCU-09 Workaround: Delete and re-create
PowerSystem and battery MOs
2020-12-03 1/109 47-CXP 901 7878/2-5 Uen Rev C © Ericsson AB 2020 7 (8)
HY66766 On ESC02* at R18H, SAU SAU External alarm parameter :
External alarm parameter : activeExternalAlarm state is incorrect for
activeExternalAlarm state is alarms when parameter inputActive =
incorrect for alarms when activeWhenOpen.
parameter inputActive = The fault does not affect the actual
activeWhenOpen functioning of the alarm. Alarms are correctly
* also applicable for SCU091 raised, as per the state of the alarm input.
3.2 Restrictions
Battery MO and all its children shall be removed and reconfigured if changing
battery backup type from smart batteries to Lead-Acid.
BLVD cannot be increased higher than 42V when Power System is in limited
charge mode.