SCU 20.Q2.

2 Release Notes

CXP 901 7878/2 R21C

Release Note

Abstract

The intention of the release notes is to supply both internal and external
customers with information about the contents of the delivery. This information
should be used as a reference for software and hardware revisions, changes,
contents, and references to other documents where greater detail is required. The
purpose is not to duplicate information but to flag important information and
where possible reference other documents that need to be studied to ensure
successful implementation of the package.

© Ericsson AB 2020
All rights reserved. The information in this document is the property of
Ericsson. Except as specifically authorized in writing by Ericsson, the receiver
of this document shall keep the information contained herein confidential and
shall protect the same in whole or in part from disclosure and dissemination
to third parties. Disclosure and disseminations to the receiver's employees
shall only be made on a strict need to know basis. The information in this
document is subject to change without notice and Ericsson assumes no
liability for any error or damage of any kind resulting from use of the
information.

2020-12-03 1/109 47-CXP 901 7878/2-5 Uen Rev C


Contents

1 Introduction ........................................................................................................... 3
1.1 General............................................................................................................... 3
1.1.1 Revision History .............................................................................................. 3
1.1.2 Availability ........................................................................................................ 3
1.2 Prerequisites .................................................................................................... 3
2 Release Information ............................................................................................. 3
2.1 SW Identity ...................................................................................................... 3
2.2 Changes since Previous Release ............................................................... 4
2.2.1 New Functionality .......................................................................................... 4
2.2.2 Corrected Trouble Reports .......................................................................... 4
2.2.3 MOM ................................................................................................................... 5
2.2.4 Fault Management ........................................................................................ 5
2.2.5 Performance Management ......................................................................... 5
2.2.6 OAM .................................................................................................................... 6
2.2.7 General Public Licensed Code .................................................................... 6
2.2.8 Security Vulnerabilities in FOSS components ....................................... 6
2.3 Upgrade Paths................................................................................................. 6
2.4 Dependencies .................................................................................................. 7
2.5 License ............................................................................................................... 7
3 Known issues.......................................................................................................... 7
3.1 Open Trouble Reports ................................................................................... 7
3.2 Restrictions ....................................................................................................... 8
3.3 Other Known Issues ...................................................................................... 8

2020-12-03 1/109 47-CXP 901 7878/2-5 Uen Rev C © Ericsson AB 2020 2 (8)
1 Introduction

1.1 General

This document contains all the delivered content of Ericsson Cabinet Controller
SW SCU 09 01 20.Q2.2.

1.1.1 Revision History

Author Revision Date Changes Introduced

EIVALAS A 2020/06/03 First revision

EIVALAS B 2020/10/26 Added TRs HY59106 and


HY63893.

Support for R9A Incell FW.

Manual Mode alarm.

EIVOBRO C 2020/11/30 Added TR HY72881.

1.1.2 Availability

The current release is recommended for all SCU 09 01 customers.

1.2 Prerequisites

There are no prerequisites regarding the Product Customizations or Adaptations


existing on the customer node.

2 Release Information

2.1 SW Identity

Function Designation Ericsson Cabinet Controller SW

Product Number CXP 901 7878/2

R-State R21C

Table 1 SW Identity

2020-12-03 1/109 47-CXP 901 7878/2-5 Uen Rev C © Ericsson AB 2020 3 (8)
2.2 Changes since Previous Release

2.2.1 New Functionality

2.2.1.1 Gen2 6130/6140/6150 Enclosures

Introduced LVD branch handling and energy consumption measurement for


Gen2 6130/6140 and 6150 Enclosures.

More information can be found in SCU 20.Q2.2 Network Impact Report (1/109
48-FGC 101 3492-4 Uen).

2.2.1.2 Incell Smart Batteries

20.Q2.2 introduces support for new firmware of Incell BMS system.

Incell BMS version SCU Revision Designation Status


(timestamp)
R9121 2020-05-05 R8A Added.

R9483 2020-08-21 R9A Added.

Table 2 Incell BMS FW revisions

2.2.2 Corrected Trouble Reports

TR-ID TR Heading Description


HX80833 Incorrect amount of external Possible loss of external alarms from SAU
alarms listed from the SCU board due to error in configuration phase.
09 01

HY36619 ESC: Duplicate instance MO Configurations utilizing smart batteries


after upgrade from R13A to cannot be upgraded from revision R13 to
R20A >=R20A due to error in Equipment MO
handling in upgrade phase.

HY41969 ESC: Wrong battery scan Communication with smart batteries


speed after importing disrupted for >15 mins if importing such
configuration configuration using import config from
ESC user interfaces or apply template
from ESCM.

HY41980 ESC: Load1 and Load2 LVD1 and LVD2 disconnect and
attributes can't be changed reconnect levels cannot be changed if
on HPM disconnectedMethod is set to Time on
E6160 setup.

HY59106 battery tests - no values Disturbances with Battery Test on


presented Megmeet power controllers:

2020-12-03 1/109 47-CXP 901 7878/2-5 Uen Rev C © Ericsson AB 2020 4 (8)
 MC1800D FW version 2.00 and
less
 MC2600 FW version 2.38 and
higher

To find more information please refer to


the SCU 20.Q2.2 Network Impact Report
(1/109 48-FGC 101 3492-4 Uen).

HY63893 ESC - Battery test - Battery Test result values,


measuredCapacity and measuredCapacity and testSoH, become
testSoH values lost after lost if node gets restarted.
ESC restart

HY72881 alarm Unsupported Battery Alarm is raised for all Shoto HW versions
Type except R2B.

Table 3 Corrected Trouble Reports

2.2.3 MOM

No changes.

2.2.4 Fault Management

2.2.4.1 New Alarms

2.2.4.1.1 Manual Mode

eventType equipmentAlarm
probableCause x733EquipmentMalfunction

defaultSeverity warning

perceivedSeverity notSet

managed object PowerSystem

Manual Mode alarm, with additional text “Control method is set as ’Manual’” will
be triggered if the power system is in the manual mode of operation during
regular state. Applicable for MC family of power controllers only.

2.2.5 Performance Management

No changes.

2020-12-03 1/109 47-CXP 901 7878/2-5 Uen Rev C © Ericsson AB 2020 5 (8)
2.2.6 OAM

No changes.

2.2.7 General Public Licensed Code

This release includes Free and Open Source SW (FOSS) under the terms of GNU
General Public License (GPL) and GNU Lesser General Public License (LGPL).

These programs are free software, which can be re-distributed and/or modified
under the terms of GPL respectively LGPL as published by the Free Software
Foundation.

To fulfill the GPL terms, the corresponding source code can be delivered upon
customer request through SW Gateway.

Product in SW Gateway R-State Description


3/CXP 901 7878/2 R5A 3PP Package
Table 4 3PP SW

A list of all included FOSS can be found in document Free and Open Source
Software, included in the CPI library.

2.2.8 Security Vulnerabilities in FOSS components

Monitoring of security vulnerabilities in Free and Open Source Software


components is an ongoing process. Vulnerabilities are typically not addressed by
stepping the version of a component, but by patching the current version of the
component. Therefore, it is not possible to rely on version banners to assess
vulnerability to certain security threats. Please contact PLM Helpdesk for any
specific security related questions.

2.3 Upgrade Paths

Solution From state To state


6150 SB Incell Gen4 R7E* R21C
6150 SB Incell Gen 5 R7F* R21C
6130 SB Shoto
6150 LA R13B R21C
6160 SB Incell Gen 5 R15F R21C
R17D R21C
R19B R21C
R20A R21C
R21A R21C
R21B R21C
*Product Number is CXP 901 7878/1

Table 5 Upgrade Path list

2020-12-03 1/109 47-CXP 901 7878/2-5 Uen Rev C © Ericsson AB 2020 6 (8)
2.4 Dependencies

SCU 09 01 20.Q2.2 shall be used with ENM 19.Q4 and later.

SCU 09 01 20.Q2.2 shall be used with ESCM R13 and later*.

* SCU 09 01 20.Q2.2 will be supported by ESCM until ESCM version released at 21.Q4 as support
needs to be assured for 18 months.

2.5 License

No Licenses are needed.

3 Known issues

3.1 Open Trouble Reports

TR-ID TR Heading Description


HX96408 ESC Full maintenance mode on Even when using IPv6 addressing, full
IPv6 node available only maintenance mode still needs to use IPv4
through IPv4 address addresses.

HY45585 Stuck in Power system in Possible stuck in limited charge mode.


limited charge mode Prerequisites to trigger stuck:
1. limited charge mode to get activated
by one or more battery unit loses
2. user to delete all BatteryUnit MOs

HY44893 maximumBatteryChargeCurent maximumbatteryChargeCurrent might not


is not updated by SCU be set to maximum allowed value in setup
with Gen2 MC2600 and Incell R8A. Possible
delay of reconnecting LVD branches upon
power outage.

HY69005 "Sub-device configuration out Possible sub-device out-of-sync alarm upon


of sync" alarm after battery completion of battery test on 6150
test on 6150 Enclosures.
Workaround: Invoke PowerSystem’s action
sync_from to synchronize node and power
controller configurations.

HY58500 Rectifier alarm and number of Deleted rectifiers with respective rectifier
rectifiers not updated correctly alarms re-appear after deletion.
in SCU-09 Workaround: Delete and re-create
PowerSystem and battery MOs

HY66745 Alarms created / cleared in Alarms created / cleared while in


Maint mode don't get sent to maintenance mode (or full maintenance
OSS or ESCM after mode) don't get sent to OSS or ESCM after
maintenance mode is exited. maintenance mode is exited.
Workaround: Re-sync alarms on OSS and
ESCM.

2020-12-03 1/109 47-CXP 901 7878/2-5 Uen Rev C © Ericsson AB 2020 7 (8)
HY66766 On ESC02* at R18H, SAU SAU External alarm parameter :
External alarm parameter : activeExternalAlarm state is incorrect for
activeExternalAlarm state is alarms when parameter inputActive =
incorrect for alarms when activeWhenOpen.
parameter inputActive = The fault does not affect the actual
activeWhenOpen functioning of the alarm. Alarms are correctly
* also applicable for SCU091 raised, as per the state of the alarm input.

Table 6 Open Trouble Reports

3.2 Restrictions

Battery backup swap – from Smart to Lead-Acid batteries

Battery MO and all its children shall be removed and reconfigured if changing
battery backup type from smart batteries to Lead-Acid.

3.3 Other Known Issues

BatteryLowVoltageDisconnect in limited_charge mode

BLVD cannot be increased higher than 42V when Power System is in limited
charge mode.

2020-12-03 1/109 47-CXP 901 7878/2-5 Uen Rev C © Ericsson AB 2020 8 (8)