Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

GUPTA POWER INFRASTRUCTURE LIMITED

BHUBANESWAR, ODISHA, INDIA 751006


(AN ISO 9001:2008, ISO 14001:2004 & OHSAS: 18001:2007 COMPANY)

CUSTOMER: ENERFRA PROJECTS (I) PVT LTD


GTP NO: GPIL/ENERFRA/ACSR DOG G/ENQ/200/20181023, REV 0
GURANTEED TECHNICAL CAL PARTICULAR FOR ACSR DOG CONDUCTOR SIZE: 6/4.724.72 MM +7/1.57
+7 MM
S.N. DESCRIPTION PARTICULARS
1.0 Code Name ACSR DOG
2.0 Applicable Standard for Conductor IS 398 (PART--2):1996
3.0 No of Strand x Size, (No. x mm) 6X4.72+7X X1.57
4.0 Approx. Conductor over all diameter, (mm) 14.15
2
5.0 Nominal Aluminium area, (mm ) 100
6.0 Approx. weight, (kg/km) 394
7.0 Minimum Ultimate Breaking load, (kN) 32.41
8.0 Modulus of Elasticity (Final), GN/m² 75
0
9.0 Coefficient of linear expansion, (per C) 19.8 x10-6
10.0 Calculated max. resistance of Conductor at 220°C, Ω/Km 0.2792
11.0 Current carrying capacity of conducto or at ambient 335 Ammp
o
temperature 35 C (Amp.)
12.0 Rise in temperature for the above curr rrent (oC) 40oC
13.0 Standard Length of conductor in km 2.0 ± 5%
14.0 Random Lengths Shall not be less than 1/3rd of standard length
and not more than 10% of the ordered quantity
15.0 Drum Details
Type of Drums Wooden
Drum Dimensions in mm (FXBXT) 1325x600x710
x600x710
16.0 Lay Ratio of conductor Min Max
(6+1) layer St. Wire 13 28
6 layer Al. Wire 10 14
17.0 Particulars of Wires (strands)
Wire Diameter, (mm) Al St
Standard: 4.72 1.57
Maximum: 4.77 1.60
Minimum: 4.67 1.54
Density kg/dm3 2.703 7.80
0 -6
Co-efficient
efficient of Linear expansion (per C) 23.0 x 10 11.5 x 10-6
Cross Sectional area of wire, mm2 17.50 1.936
Approximate Total weight of each strand, (kg/km) 47.30 15.10
Max. Resistance at 20°C Ω/km 1.650 NA
Minimum Breaking Load of each strand, (kN) 2.64 2.57
Min. elongation. % on G.L 200 mm (After stranding) NA 3.5
Min. mass of Zinc coating g/m2(After stranding) NA 180.5
Dip Test NA 2 dips-1 min
Torsion Test 100 times diameter of wire after stranding NA 16 Turns

Page 1 of 2
GUPTA POWER INFRASTRUCTURE LIMITED
BHUBANESWAR, ODISHA, INDIA 751006
(AN ISO 9001:2008, ISO 14001:2004 & OHSAS: 18001:2007 COMPANY)

CUSTOMER: ENERFRA PROJECTS (I) PVT LTD


GTP NO: GPIL/ENERFRA/ACSR DOG G/ENQ/200/20181023, REV 0
GURANTEED TECHNICALCAL PARTICULAR FOR ACSR DOG CONDUCTOR SIZE: 6/4.72 4.72 MM +7/1.57
+7 MM
S.N. DESCRIPTION PARTICULARS
16.0 Makers Name And Address
Aluminium Wire/Rods NALCO,BALCO,HINDALCO,GUPTA POWER,
VEDANTA, KUNJ ALLOY and other imported
sources
Steel Wire/Rods KRITIKA WIRES, HULAS, USHA MARTIN, BALAJI,
BAJARANGI, PRESTRESS, RATLAM WIRES,
KATARIA WIRES, NIRMAL WIRES, SYSTEMATICS
WIRES, VERITAS INDUSTRIES PVT. LTD., HD
WIRES and other BIS approved sources.
17.0 The sample has to pass either the torsion test or elongation test, that is, if the conductor is passing any of
the two tests, the sample should be considered as passing.(As per IS 398(Part 2): 1996)

Page 2 of 2

You might also like