F3LC51-2N F3RZ81-0F F3RZ82-0F F3RZ91-0F一般规格(19年 第14版)

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 18

<<Contents>> <<Index>>

General FA-M3
Personal Computer Link Modules
Specifications Modbus Interface Module
UT Link Module
GS 34M06H21-01E Ladder Communication Modules

Contents

F3LC11-1F Personal Computer Link Module ···································································· 3

F3LC12-1F Personal Computer Link Module ···································································· 5

F3LC11-2F Personal Computer Link Module ···································································· 7

F3LC31-2F Modbus Interface Module ············································································· 9

F3LC51-2N UT Link Module ······················································································· 11

F3RZ81-0F Ladder Communication Module (RS-232-C) ··················································· 13

F3RZ82-0F Ladder Communication Module (RS-232-C) ·················································· 15

F3RZ91-0F Ladder Communication Module (RS-422-A/RS-485) ······································· 17

For information on the Discontinued Modules, refer to GS34M06H21-99E.

GS 34M06H21-01E
14th Edition: Mar.15,2019

Yokogawa Electric Corporation


Blank Page
<<Contents>> <<Index>> 3

General F3LC11-1F
Specifications Personal Computer Link Module

General
The F3LC11-1F is connected to a higher-level computer,
such as a personal computer or FA computer, or a
display for RS-232-C communications.
- It enables reading and writing of all FA-M3 devices.
- It does not require a transmission application
program.
- It allows reading and writing of devices even when a
ladder program is not running.
- It enables direct connection to a display having a
programmable controller interface.
- It enables remote running and stopping of programs
on FA-M3.
- It enables loading and saving of programs.
- It enables reading of program-related information Components and Functions
(program name, size, block name, etc.) and error
logs.  Front View
- It supports several types of external modems,
allowing for use of a cellular phone where a 56kbps
RDY RDY indicator
fast communication interface or public telephone line Lit when the internal circuit is
is not available. functioning normally.
LC11-1F C LINK

Specifications
Item Specification
Interface Conforms to the EIA RS-232-C standard
Transmission mode Half-duplex
Synchronization Start-stop synchronization
300, 600, 1200, 2400, 4800, 9600, 14400,
Transmission speed 19200, 28800, 38400, 57.6k, 115.2 kbps
Transmission 15 m max.
distance
Number of ports 1 (not isolated)
Start bit 1 1
Data length 7 or 8 bits
Data format Parity bit None, even or odd
Stop bit 1 or 2 bits
Error detection Parity check, checksum RS-232-C connector
Control line RS always on, ER always on D-sub 9-pin connector
Xon/Xoff control None (M2.6 screw) for
Transmission speed, data format, checksum, connection to a higher
Setup items ending character, protection
level computer or display.
Protocol Proprietary protocol
Ending character Yes or No
Protection feature Yes or No  Right Side View
All sequence devices, BASIC common area,
Access range upload/download ladder program, RUN/STOP,
read error log, read user log
F3SP21: 2 max.
F3SP22, F3SP25, F3SP28, F3SP35, F3SP38,
F3SP53, F3SP58, F3SP59, F3SP66, F3SP67,
F3SP71, F3SP76, F3BP20 and F3BP30:
Number of modules 6 max.
* Total number of modules including those
which have similar functions (Ethernet Front Rear
interface modules, and GP-IB communication
modules [slave]) 1
23
4 5
6
7

Current consumption 320 mA 0


F
ED A
8
9 Transmission speed switch
Sets the transmission
External connection D-sub 9-pin connector (female), M2.6 screw
CB
speed of the module.
External dimensions 28.9 (W) x 100 (H) x 83.2 (D) mm* O
F
1
2
O
F
1
2
Data format switch
Weight 120 g F 3
4
F 3
4 Defines the format of
Surrounding air
5 5
Operating :0 to 55°C 6
7
6
7
communication data.
temperature range Storage :-20°C to 75°C 8 8
Module function switch
Surrounding humidity Operating :10 to 90% RH (non-condensing) Enables modem connection.
range Storage :10 to 90% RH (non-condensing) Note: This figure is drawn with the panel cover removed.
Surrounding Must be free of corrosive gases, flammable
atmosphere gases or heavy dust.
*: Excluding protrusions (see external dimensions for details).

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 34M06H21-01E Mar.15,2019-00
<<Contents>> <<Index>> 4

Configuration Example  Cabling Example (for 9-pin device)

F3LC11-1F
Personal computer Personal
link module computer
FA-M3 Display or

RS-232-C cross cable

F3LC11-1F
Personal computer
link module
FA-M3 Modem or
terminal adapter Public
telephone line

RS-232-C straight-through cable Operating Environment


(modem cable)
There is no restriction on the type of CPU modules that
can be used with this module.
External Connection Diagram
The module is connected to a personal computer or
display through an RS-232-C connector. Model and Suffix Codes
Suffix Style Option
Model Description
 Connector Specifications Code Code Code
F3LC11 -1F ..... ..... One RS-232-C port

5
9 External Dimensions
Unit: mm
6
1

D-sub 9-pin connector (female)


83.2 6.7 28.9
Signal 2
Pin Signal Name Direction Description
No. Name
FA- M3 PC
2 RD Receive data
3 SD Send data
Data Terminal Always output ON in
4 ER
ready RDY state
5 SG Signal ground
6 DR Data set ready Always on
Always output ON in 100
7 RS Request to send
RDY state
Always input ON.
8 CS Clear to send Sending not allowed
when input is OFF.

 Cabling Example (for 25-pin device)


D-sub 9-pin D-sub 25-pin
Personal computer or display
Personal computer link module

3 2
SD SD
2 3
RD RD
7 4
RS RS
8 5
CS CS
6 6
DR DR
4 20
ER ER
5 7
SG SG

Connected to the Connected to the


connector frame connector frame

Note: The pin assignments on the personal computer or display shown


in this example assumes a D-sub 25-pin connector.

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 34M06H21-01E Mar.15,2019-00
<<Contents>> <<Index>> 5

General F3LC12-1F
Specifications Personal Computer Link Module

General
The F3LC12-1F is connected to a higher-level computer,
such as a personal computer or FA computer, or a
display for RS-232-C communications.
- It enables reading and writing of all FA-M3 devices.
- It does not require a transmission application
program.
- It allows reading and writing of devices even when a
ladder program is not running.
- It enables direct connection to a display having a
programmable controller interface.
- It enables remote running and stopping of programs
on FA-M3.
- It enables loading and saving of programs.
- It enables reading of program-related information Components and Functions
(program name, size, block name, etc.) and error
logs.  Front View
- It has two personal computer link ports for
simultaneous connections. RDY RDY indicator
Lit when the internal circuit is
functioning normally.
Specifications LC12-1F C LINK

Item Specification
Interface Conforms to the EIA RS-232-C standard
1
Transmission mode Half-duplex
Synchronization Start-stop synchronization
300, 600, 1200, 2400, 4800, 9600, 14400,
Transmission speed 19200, 28800, 38400, 57.6k, 115.2 kbps
Transmission distance 15 m max.
Number of ports 2 (not isolated)
Start bit 1
Data length 7 or 8 bits
Data format Parity bit None, even or odd
Stop bit 1 or 2 bits
Error detection Parity check, checksum 2
Control line RS always on, ER always on
Xon/Xoff control None
Transmission speed, data format, RS-232-C connector
Setup items checksum, ending character, protection D-sub 9-pin connector
(M2.6 screw) for connection to
Protocol Proprietary protocol a higher level computer or display.
Ending character Yes or No
Protection feature Yes or No
All sequence devices, BASIC common
Access range area, upload/download ladder program,
RUN/STOP, read error log, read user log  Right Side View
F3SP21: 2 max.
F3SP22, F3SP25, F3SP28, F3SP35,
F3SP38, F3SP53, F3SP58, F3SP59,
F3SP66, F3SP67, F3SP71, F3SP76,
F3BP20 and F3BP30:
Number of modules 6 max.
* Total number of modules including those
which have similar functions (Ethernet
interface modules, and GP-IB
communication modules) Front Rear
Current consumption 350 mA
External connection D-sub 9-pin connector (female), M2.6 screw 34 5
6
F0 1 2

External dimensions Transmission speed switch


78 9 A

28.9 (W) x 100 (H) x 83.2 (D) mm* Sets the transmission
E

Weight
BC D
120 g speed of the module.
Surrounding air Operating :0 to 55°C O
F
1
2
O
F
1
2 Data format switch
temperature range Storage :-20°C to 75°C F 3
4
F 3
4 Defines the format of
Surrounding humidity Operating :10 to 90% RH
5
6
5
6 communication data.
range
7 7
(non-condensing) 8 8 Module function switch
Storage :10 to 90% RH Enables modem connection.
(non-condensing)
Note: This figure is drawn with the panel cover removed.
Surrounding atmosphere Must be free of corrosive gases, flammable
gases or heavy dust.
*: Excluding protrusions (see external dimensions for details).

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 34M06H21-01E Mar.15,2019-00
<<Contents>> <<Index>> 6

Configuration Example  Cabling Example (for 9-pin device)

F3LC12-1F Personal
Personal computer link module Display computer
FA-M3
RS-232-C
cross cable

RS-232-C cross cable

F3LC12-1F
Personal computer link module
RS-232-C
cross cable Modem or
FA-M3 terminal adapter

Public
telephone line
RS-232-C
straight-through cable
(modem cable)
Operating Environment
There is no restriction on the type of CPU modules that
External Connection Diagram can be used with this module.
The module is connected to a personal computer or
display through an RS-232-C connector.
Model and Suffix Codes
 Connector Specifications Model
Suffix Style Option
Description
Code Code Code
F3LC12 -1F ..... ..... Two RS-232-C ports
5
9
External Dimensions
6 Unit: mm
1

D-sub 9-pin connector (female)


83.2 6.7 28.9
Signal 2
Pin Signal Name Direction Description
No. Name
FA- M3 PC
2 RD Receive data
3 SD Send data
Data Terminal Always output ON in
4 ER
ready RDY state
5 SG Signal ground
6 DR Data set ready Always on 100
Always output ON in
7 RS Request to send
RDY state
Always input ON.
8 CS Clear to send Sending not allowed
when input is OFF.

 Cabling Example (for 25-pin device)


D-sub 9-pin D-sub 25-pin
Personal computer or display
Personal computer link module

3 2
SD SD
2 3
RD RD
7 4
RS RS
8 5
CS CS
6 6
DR DR
4 20
ER ER
5 7
SG SG

Connected to the Connected to the


connector frame connector frame

Note: The pin assignments on the personal computer or display shown


in this example assumes a D-sub 25-pin connector.

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 34M06H21-01E Mar.15,2019-00
<<Contents>> <<Index>> 7

General F3LC11-2F
Specifications Personal Computer Link Module

General
This F3LC11-2F Personal Computer Link Module is
connected to a higher-level computer such as a personal
computer or FA computer through an RS-422-A/RS-485
interface to provide a communication channel.
With the higher-level computer configured as the master
station, the F3LC11-2F allows a maximum of 32 FA-M3
modules to be connected to the higher-level computer.
- It enables reading and writing of all FA-M3 devices.
- It does not require a transmission application
program.
- It allows reading and writing of devices even when a
ladder program is not running.
- It enables direct connection to a display having a
programmable controller interface.
- It enables remote running and stopping of programs Components and Functions
on FA-M3.
- It enables loading and saving of programs.  Front View
- It enables reading of program-related information
(program name, size, block name, etc.) and error logs
- Up to 32 modules can be linked through an RDY indicator
RS-422-A/ RS-485 interface. Lit when the internal circuit is
functioning normally.
Specifications
Item Specification
Conforms to the EIA RS-422-A and EIA RS-485
Interface standards Station No. switch
Transmission mode Half-duplex, 4- or 2-wire system Selects a station number
Synchronization Start-stop synchronization (1 to 32).
300, 600, 1200, 2400, 4800, 9600, 14400,
Transmission speed 19200, 28800, 38400, 57.6k, 76.8k, 115.2 kbps
Transmission media Shielded twisted-pair cable (AWG20 - 16) Termination switch
Transmission distance 1200 m max. Set to the 4- or 2-wire mode
 (built-in resistor to be enabled for a when the module is configured
Terminating resistance 220
terminal station using a switch) at the end of the cable.
Number of ports 1 (isolated)
Start bit 1
Data length 7 or 8 bits
Data format Parity bit None, even or odd RS-422-A/RS-485 terminal block
Stop bit 1 or 2 bits (6 terminals, M3.5 screws)
Error detection Parity check, checksum
Xon/Xoff control None
Transmission speed, data format, checksum,
Setup items ending character, protection
Protocol Proprietary protocol
Ending character Yes or No
Protection feature Yes or No
All sequence devices, BASIC common area,  Right Side View
Access range upload/download ladder program, RUN/STOP,
read error log, read user log
F3SP21: 2 max.
F3SP22, F3SP25, F3SP28, F3SP35, F3SP38,
F3SP53, F3SP58, F3SP59, F3SP66, F3SP67,
F3SP71, F3SP76, F3BP20 and F3BP30:
Number of modules 6 max.
Front Rear
* Total number of modules including those which
have similar functions (Ethernet interface
module, FL-net interface module) SW1 Transmission speed switch
Sets the transmission speed of
Current consumption 350 mA the module.
External connection 6-point terminal block, M3.5 screws SW3 SW2
External dimensions Data format switch
O 1 O 1
28.9 (W) x 100 (H) x 83.2 (D) mm* F
F
2
3
F
F
2
3
Defines the format of
Weight
4 4
120 g 5
6
5
6 communication data.
Surrounding air Operating :0 to 55°C
7
8
7
8

temperature range Storage :-20°C to 75°C This switch is not used.


Surrounding humidity Operating :10 to 90% RH (non-condensing)
range Storage :10 to 90% RH (non-condensing) This figure is drawn with the
panel cover removed.
Surrounding atmosphere Must be free of corrosive gases, flammable
gases or heavy dust.
*: Excluding protrusions (see external dimensions for details).

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 34M06H21-01E Mar.15,2019-00
<<Contents>> <<Index>> 8

Configuration Example (2) 2-wire System


The maximum total number of linked modules is 32. Personal
computer, etc. F3LC11-2F F3LC11-2F
FA computer
A SDA SDA
(A)
B SDB SDB
(B)
F3LC11-2F

Terminator
RDA RDA
Personal computer link
RS-422-A/RS-485 module RDB RDB

Terminator
SG SG SG
(SG)
FA-M3
SHIELD SHIELD SHIELD

RS-485 How to connect the shielding conductor (for 4-wire


or 2-wire system)
(1) Ground (connect to the SHIELD terminal) both ends
Personal computer of the shielding conductor of the twisted-pair cable.
The SHIELD terminal of the F3LC11-2F module is
connected internally to the FG terminal of the FA-M3
power supply module.
RS-232-C
(2) The F3LC11-2F module has a built-in terminator (220
). When configuring the module at the end of a
RS-232-C  RS-422-A/RS-485
converter (commercially available)
cable, set the terminator switch to either a 4- or 2-wire
system.
RS-422-A/RS-485
Cables
FA-M3 Recommended cables for 2-wire systems:
KM80-/KM81- (to be purchased separately).
* For details on KM80- and KM81-, see
“FA-M3 YHLS Master Module, YHLS Slave Units and
RS-485 YHLS Communication Cables” (GS 34M06H46-03E).

Operating Environment
There is no restriction on the type of CPU modules that
 RS422-A/RS-485 Terminal Block & Cabling can be used with this module.
Terminal Block
Model and Suffix Codes
Suffix Style Option
Model Description
Code Code Code
SD A M 3.5
SD A Send data A F3LC11 -2F ..... ..... One RS-422-A/RS-485 port
SD B SD B Send data B
RD A
RD A Receive data A
7.3 mm External Dimensions
8.6 mm Unit: mm
RD B
RD B Receive data B
SG
SG Signal ground
SHIELD
SHIELD Shield

83.2 12.1 28.9


Wiring Diagram 2

(1) 4-wire System


Personal
computer, etc. F3LC11-2F F3LC11-2F

SDA SDA SDA


(SD A)
SDB SDB SDB 100
(SD B)
RDA RDA RDA
(RD A)
RDB RDB RDB
(RD B)
Terminator
Terminator

SG SG SG
(SG)
SHIELD SHIELD SHIELD

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 34M06H21-01E Mar.15,2019-00
<<Contents>> <<Index>> 9

General F3LC31-2F
Specifications Modbus Interface Module

General
This module is an interface module for connecting to
Modbus*1 RTU / Modbus ASCII.
It supports the master function of Modbus
communication which is an open network and can
communicate with various slave devices of other
companies. It also supports slave function and can
communicate with other manufacturer's master devices.
* 1: MODBUS is a registered trademark of Schneider Automation Inc..

Specifications
Item Specification
Conforms to the EIA RS-422 and EIA RS-485
Interface standards.
Transmission mode Half-duplex, 4- or 2-wire system
300, 600, 1200, 2400, 4800, 9600, 14400,
Transmission speed 19200, 28800, 38400, 57600, 115200 bps
Transmission media Shielded twisted-pair cable (AWG20 - 16) Components and Functions
Transmission distance 1200 m max.
220  (built-in resistor to be enabled for a
Terminating resistance terminal station using a switch)
 Front View
Number of ports 1 (isolated)
Start bit 1 bit
RDY RDY indicator :
Data length 7 or 8 bits
Data format Stop bit 1 or 2 bits Lit when the internal circuit is
Parity bit None, even or odd LC31-2F MODBUS functioning normally.
Xon/Xoff control None
Transmission mode Modbus RTU/Modbus ASCII
Error check CRC-16(RTU)/LRC-8(ASCII)
Write protection Yes or No(Slave function only)
10 Function codes supported TERMINATOR
Communicate on
Request data area 250Byte 2- 4-WIRE Terminator switch:
Master function demand
Response data area 250Byte OFF Set to the 4- or 2-wire mode
Broadcast Broadcast address 0 SD A when the module is configured
Auto answer 10 Function codes supported
64K Discrete inputs SD B
at the end of the cable.
64K Coils
Slave function Device size
64K Input registers RD A
64K Holding registers
Station Address 1 to 247 RD B RS-422/RS-485 terminal block
Number of slaves 8 max. (6 terminals, M3.5 screws)
Auto answer 10 Function codes supported SG
64K Discrete inputs
Multi-slave function Device size
64K Coils SHIELD
64K Input registers
64K Holding registers
Station Address 1 to 247
F3SP21: 2 max.
F3SP22, F3SP25, F3SP28, F3SP35, F3SP38,
Number of modules*1 F3SP53, F3SP58, F3SP59, F3SP66, F3SP67,
 Right Side View
F3SP71, F3SP76, F3BP20 and F3BP30: Front Rear
6 max.
External connection 6-point terminal block, M3.5 screws
Current consumption 290 mA
External dimensions*2 28.9 (W) x 100 (H) x 83.2 (D) mm
Weight 130 g
Surrounding air Operating :0 to 55°C
temperature range Storage :-20°C to 75°C
Surrounding humidity Operating :10 to 90% RH (non-condensing)
range Storage :10 to 90% RH (non-condensing)
Surrounding atmosphere Must be free of corrosive gases, flammable
gases or heavy dust.
*1: Total number of modules including those which have similar
functions (Ethernet interface module, FL-net interface module)
*2: Excluding protrusions (see external dimensions for details).

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 34M06H21-01E Mar.15,2019-00
<<Contents>> <<Index>> 10

Configuration Example Slave Function / 4-wire System

Master Function External External


instrument F3LC31-2F instrument
F3LC31-2F

SD A SD A SD A
Response
message
Request SD B SD B SD B
RS-422/RS-485 message
RS-485 RD A RD A RD A

RD B RD B RD B
・・・・
SG SG SG
Slave Slave Slave
Slave Function SHIELD SHIELD SHIELD

Master

Slave Function / 2-wire System


Response
message External External
Request instrument F3LC31-2F instrument
RS-422/RS-485 message RS-485
SD A

SD B

F3LC31-2F F3LC31-2F F3LC31-2F RD A

RD B
 RS422-A/RS-485 Terminal Block & Cabling
Terminal Block
SG SG SG

S HI ELD S HI ELD S HIE LD

Note: In a 2-wire system, SDA and RDA, as well as SDB and RDB, must
SD A M3.5
SD A Send data A be shorted with a wire at the terminal block.
SD B SD B Send data B
RD A
RD A Receive data A
7.3 mm Operating Environment
8.6 mm
RD B
RD B Receive data B
There is no restriction on the type of CPU modules that
can be used with this module.
SG
SG Signal ground
SHIELD
SHIELD Shield
Model and Suffix Codes
Model Suffix Style Option Description
Wiring Diagram Code Code Code
F3LC31 -2F ..... ..... One Modbus RTU/ASCII port
Master Function / 4-wire System

F3LC31-2F
External
instrument
External
instrument
External Dimensions
Unit: mm
SD A SD A SD A

SD B SD B SD B

RD A RD A RD A
83.2 12.1 28.9
2
RD B RD B RD B

SG SG SG

S HI E LD S HI E LD S HI E LD

Master Function / 2-wire System


100
External External
F3LC31-2F instrument instrument

SD A

SD B

RD A

RD B

SG SG SG

S HI ELD S HI ELD S HIE LD

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 34M06H21-01E Mar.15,2019-00
<<Contents>> <<Index>> 11

General F3LC51-2N
Specifications UT Link Module

General
The F3LC51-2N UT Link Module enables the FA-M3 to
be easily connected to external devices such as
temperature controllers that support the FA-M3 personal
computer link protocol and commands.
- Data of external devices are always refreshed. The
module exchanges data with the external devices by
directly accessing the module's registers, without
requiring a communication program.
- It can also exchange data when events occur.
- A single module can support up to 32 external
devices at a maximum cable distance of 1200 m
using RS-485 communications.

Specifications Components and Functions


Item Specification
Interface Conforms to the EIA RS-422-A and EIA  Front View
RS-485 standards.
Transmission mode Half-duplex, 4- or 2-wire system
Synchronization Start-stop synchronization RDY RDY indicator :
300, 600, 1200, 2400, 4800, 9600, 19200, Lit when the internal circuit is
Transmission speed 31250, 38400 bps functioning normally.
LC51-2N UT LINK

Transmission media Shielded twisted-pair cable (AWG20 - 16)


Transmission distance 1200 m max.
Number of connected 32 max. (depending on external instruments)
stations
220  (built-in resistor to be enabled for a
Terminating resistance terminal station using a switch) TERMINATOR
Number of ports 1 (isolated) 2-
OFF
4-WIRE Terminator switch
Start bit 1 SD A
Set to the 4- or 2-wire mode
Data length 7 or 8 bits when the module is configured
Data format Parity bit None, even or odd SD B at the end of the cable.
Stop bit 1 or 2 bits
Error detection Parity check, checksum RD A

Xon/Xoff control None RD B


RS-422-A/RS-485 terminal block
Protocol Proprietary protocol (6 terminals, M3.5 screws)
Ending character Yes or No SG
Access range All control data
SHIELD
Transmission speed, data format, checksum,
Setup items ending character
Number of modules 4 max
Current consumption 290 mA  Right Side View
External connection 6-point terminal block, M3.5 screws
External dimensions 28.9 (W) x 100 (H) x 83.2 (D) mm* Rev.04:07 and earlier Rev.05:08 and later
Weight 130 g Front Rear Front Rear
Surrounding air Operating :0 to 55°C
temperature range Storage :-20°C to 75°C
Surrounding humidity Operating :10 to 90% RH
range (non-condensing)
Storage :10 to 90% RH
(non-condensing)
Surrounding atmosphere Must be free of corrosive gases, flammable SW1
4

gases or heavy dust.


0

SW3 SW2
5

*: Excluding protrusions (see external dimensions for details). O


F
F
1
2
3
O
F
F
1
2
3
O
F
F
1
2
3
4 4 4
5 5 5
6 6 6
5

7 7 7
8 8 8

Transmission spe ed switch


Sets the transmission
speed of the module.

Note: This figure is drawn with Data format swit ch


Defines the format of
the panel cover removed.
communication data.

Mode switch
Sets the communication mode.

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 34M06H21-01E Mar.15,2019-00
<<Contents>> <<Index>> 12

Configuration Example How to connect the shielding conductor (for 4-wire


or 2-wire system)
(1) Ground (connect to the SHIELD terminal) both ends
of the shielding conductor of the twisted-pair cable.
The SHIELD terminal of the F3LC51-2N module is
connected internally to the FG terminal of the FA-M3
power supply module.
(2) The F3LC51-2N module has a built-in terminator (220
). When configuring the module at the end of a
cable, set the terminator switch to either a 4- or 2-wire
system.

Cables
Recommended cables for 2-wire systems:
KM80-/KM81- (to be purchased separately).
* For details on KM80- and KM81-, see
 RS422-A/RS-485 Terminal Block & Cabling “FA-M3 YHLS Master Module, YHLS Slave Units and
Terminal Block YHLS Communication Cables” (GS 34M06H46-03E).

Operating Environment
SD A
SD A Send data A M3.5 There is no restriction on the type of CPU modules that
SD B SD B Send data B
can be used with this module.
RD A 7.3 mm
RD A Receive data A
RD B
RD B Receive data B
8.6 mm
Model and Suffix Codes
Suffix Style Option
SG Model Description
SG Signal ground Code Code Code
SHIELD
SHIELD Shield F3LC51 -2N ..... ..... One RS-422A / RS-485 port

Wiring Diagram
External Dimensions
Unit: mm
4-wire System
F3LC51-2N Externel instrument Externel instrument

83.2 12.1 28.9


2

100

2-wire System
F3LC51-2N Externel instrument Externel instrument

Note: In a 2-wire system, SDA and RDA, as well as SDB and RDB, must
be shorted with a wire at the terminal block.

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 34M06H21-01E Mar.15,2019-00
<<Contents>> <<Index>> 13

General F3RZ81-0F
Specifications Ladder Communication Module
(RS-232-C)

General
The F3RZ81-0F Ladder Communication Module provides
RS-232-C communication capability from a sequence CPU
module under the control of a ladder program. It has one
port using a D-sub 9-pin connector. It can communicate with
devices at a maximum distance of 15 m.

Features
- Maximum transmission rate of 115.2 kbps.
- All input relays are interrupt-capable.

Specifications
Item Specification
Connection method Point to point
Transmission mode Full-duplex/half-duplex
Synchronization Start-stop synchronization
Communication No protocol
Components and Functions
protocol
Character
length 7 or 8 bits  Front View
Data
format Stop
length
bit 1 or 2 bits
Parity bit None, even or odd RDY Indicator RDY:
300, 600, 1200, 2400, 4800, 9600, 14400, Lit when the internal circuit is
Transmission speed 19200, 28800, 38400, 57600, 76800, or 115200 RZ81-0F RS232C
functioning normally.
bps
1: Always on.
RS control 2: Turn on before sending.
1: Ignore DR when sending.
DR check
Control 2: Send only when DR is on.
lines CD check 1: Ignore CD when sending.
2: Send only when CD is off.
1: On (ready)
ER control 2: Off (not ready)
Commu Send buffer Text buffer (3584 bytes max.)*1
nication Receive
buffers buffer 8192-byte rotary buffer (FIFO buffer)
Start - Yes or No
character - Any single character
End - Yes or No Port 1
Format character - Up to 2 characters long, any characters
of (terminator)
received Text length Can be specified as any number between 1 and
text 3584 *1
Character-to
-character 0 to 32760 ms in 1 ms increments,
timeout accurate to 1 ms (0 means not monitored)  Right Side View
interval
Clear-to-send timeout 0 to 32760 ms in 1 ms increments,
interval accurate to 1 ms (0 means not monitored)
Break transmission 1 to 32760 ms in 1 ms increments,
interval accurate to 1 ms
Transmission distance 15 m max.
Number of ports 1 (not isolated)
Current consumption 320 mA Front Rear
External dimensions 28.9 (W) x 100 (H) x 83.2 (D) mm*
SW1
Weight 120 g Transmission speed switch
Sets the transmission
Surrounding air Operating :0 to 55°C speed of the module.
SW3 SW2
temperature range Storage :-20°C to 75°C O 1 O 1
F 2 F 2 Data format switch
F 3 F 3

Surrounding humidity Operating :10 to 90% RH (non-condensing)


4
5
4
5
Defines the format of
communication data.
range
6 6
7 7
Storage :10 to 90% RH (non-condensing) 8 8

This switch is not used.


Surrounding Must be free of corrosive gases, flammable gases
atmosphere or heavy dust.
This figure is drawn with the
*: Excluding protrusions (see external dimensions for details). panel cover removed.
*1: The send/receive data register size can be changed to
accommodate up to 3584 bytes.
All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 34M06H21-01E Mar.15,2019-00
<<Contents>> <<Index>> 14

External Connection Diagram


Signal
Pin Signal Name Direction Signal Description*
 Connecting an RS-232-C Device (DTE: No. Name
FA- M3 PC
Monitored
Data Terminal Equipment) Sends data as follows:
Data 1. Ignore CD when
Null modem cable 1 CD carrier Yes sending (default).
Shield detect 2. Send only when CD is
Connector Connector off.
cover cover
Receive
1(FG) 2 RD ―
data
(SD)3 2(SD) 3 SD Send data ―
Data 1. On when powered
(RD)2 3(RD) 4 ER terminal ― (default).
(RS)7 4(RS) Remote ready 2. On/off by software.
F3RZ81-0F DTE Signal
(CS)8 5(CS) 5 SG ―
(9-pin D-sub (25-pin D-sub
ground
connector) (DR)6 6(DR) connector) Used to check whether
the remote station can
(SG)5 7(SG) receive data.
Data set
6 DR Yes 1. Ignore DR when
(CD)1 8(CD) ready
sending (default).
(ER)4 20(ER) 2. Send data only when
DR is on.
Used when sending data
Note: The remote DTE is assumed to have a D-sub 25-pin connector. An Request to the remote station.
7 RS ―
example of a cable suitable for the above configuration is to send 1. Always on (default).
Yokogawa's YCB215. 2. Turn on before sending
Clear to send signal from
the remote station. The
 Connecting a Modem (DCE: Data 8 CS
Clear to
Yes module can send data
send
Communication Equipment) only when this signal is
on.
(Not
9 ― ― ―
used)
*: Specify 1 or 2 using software.

Operating Environment
There is no restriction on the type of CPU modules that
can be used with this module.

Model and Suffix Codes


Suffix Style Option
Model Description
Code Code Code
F3RZ81 -0F ..... ..... 115200 bps max., 1 ports

Note: The remote DCE is assumed to have a D-sub 25- pin connector. An
example of a cable suitable for the above configuration is
Yokogawa's YCB211.
External Dimensions
Unit: mm
How to connect the shielding conductor (for DTE or
DCE)
(1) Use a cable with connectors protected by metal
covers or metal-plated covers. Connect the shielding 83.2 6.7 28.9
conductor directly to the metal covers. 2
(2) The connector shell of the F3RZ81-0F module is
connected internally to the FG terminal of the FA-M3
power supply module.

 Connector Specifications
100

5
9

6
1

9-pin D-sub connector (female)

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 34M06H21-01E Mar.15,2019-00
<<Contents>> <<Index>> 15

General F3RZ82-0F
Specifications Ladder Communication Module
(RS-232-C)

General
The F3RZ82-0F Ladder Communication Module provides
RS-232-C communication capability from a sequence CPU
module under the control of a ladder program. It has two
ports using two D-sub 9-pin connectors. It can communicate
with devices at a maximum distance of 15 m.

Features
- The two ports operate independently at a maximum
transmission rate of 115.2 kbps.
- All input relays are interrupt-capable.

Specifications
Item Specification
Connection method Point to point
Transmission mode Full-duplex/half-duplex
Synchronization Start-stop synchronization
Communication No protocol
Components and Functions
protocol
Character
length 7 or 8 bits  Front View
Data
format Stop
length
bit 1 or 2 bits
Parity bit None, even or odd RDY Indicator RDY:
300, 600, 1200, 2400, 4800, 9600, 14400, Lit when the internal circuit is
Transmission speed 19200, 28800, 38400, 57600, 76800, or 115200 functioning normally.
RZ82-0F RS232C
bps
1: Always on.
RS control 2: Turn on before sending. 1
1: Ignore DR when sending.
DR check
Control 2: Send only when DR is on.
lines 1: Ignore CD when sending.
CD check 2: Send only when CD is off. Port 1
1: On (ready)
ER control 2: Off (not ready)
Commu Send buffer Text buffer (3584 bytes max.)*1
nication Receive 2
buffers buffer 8192-byte rotary buffer (FIFO buffer)
Start - Yes or No
character - Any single character Port 2
End - Yes or No
Format character - Up to 2 characters long, any characters
of (terminator)
received Text length Can be specified as any number between 1 and
text 3584 *1
Character-to  Right Side View
-character 0 to 32760 ms in 1 ms increments,
timeout accurate to 1 ms (0 means not monitored)
interval
Clear-to-send timeout 0 to 32760 ms in 1 ms increments,
interval accurate to 1 ms (0 means not monitored)
Break transmission 1 to 32760 ms in 1 ms increments,
interval accurate to 1 ms
Transmission distance 15 m max.
Number of ports 2 (not isolated) Front Rear
Current consumption 350 mA
SW1
External dimensions 28.9 (W) x 100 (H) x 83.2 (D) mm* Transmission speed switch
Sets the transmission
Weight 120 g speed of the module.
SW3 SW2
Surrounding air Operating :0 to 55°C O 1 O 1
Data format switch
temperature range F
F
2
3
F
F
2
3
Storage :-20°C to 75°C 4 4 Defines the format of
5 5 communication data.
Surrounding humidity
6 6
Operating :10 to 90% RH (non-condensing) 7
8
7
8
range
Storage :10 to 90% RH (non-condensing) This switch is not used.

Surrounding Must be free of corrosive gases, flammable gases


atmosphere or heavy dust. This figure is drawn with the
*: Excluding protrusions (see external dimensions for details). panel cover removed.

*1: The send/receive data register size can be changed to


accommodate up to 3584 bytes.

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 34M06H21-01E Mar.15,2019-00
<<Contents>> <<Index>> 16

External Connection Diagram


Signal
Pin Signal Name Direction Signal Description*
 Connecting an RS-232-C Device (DTE: No. Name
FA- M3 PC
Monitored
Data Terminal Equipment) Sends data as follows:
Data 1. Ignore CD when
1 CD carrier Yes sending (default).
detect 2. Send only when CD is
off.
Receive
2 RD ―
data
3 SD Send data ―
Data 1. On when powered
4 ER terminal ― (default).
ready 2. On/off by software.
Signal
5 SG ―
ground
Used to check whether
the remote station can
receive data.
Data set
6 DR Yes 1. Ignore DR when
ready
sending (default).
2. Send data only when
DR is on.
Note: The remote DTE is assumed to have a D-sub 25-pin connector. An Used when sending data
example of a cable suitable for the above configuration is Request to the remote station.
7 RS ―
Yokogawa's YCB215. to send 1. Always on (default).
2. Turn on before sending
Clear to send signal from
 Connecting a Modem (DCE: Data the remote station. The
Clear to
Communication Equipment) 8 CS
send
Yes module can send data
only when this signal is
on.
(Not
9 ― ― ―
used)
*: Specify 1 or 2 using software.

Operating Environment
There is no restriction on the type of CPU modules that
can be used with this module.

Model and Suffix Codes


Suffix Style Option
Model Description
Code Code Code
Note: The remote DCE is assumed to have a D-sub 25- pin connector.
F3RZ82 -0F ..... ..... 115200 bps max., 2 ports
An example of a cable suitable for the above configuration is
Yokogawa's YCB211.
External Dimensions
How to connect the shielding conductor (for DTE or
Unit: mm
DCE)
(1) Use a cable with connectors protected by metal
covers or metal-plated covers. Connect the shielding
conductor directly to the metal covers. 83.2 6.7 28.9
(2) The connector shell of the F3RZ82-0F module is 2
connected internally to the FG terminal of the FA-M3
power supply module.

 Connector Specifications

100

9 5

6
1

9-pin D-sub connector (female)

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 34M06H21-01E Mar.15,2019-00
<<Contents>> <<Index>> 17

General F3RZ91-0F
Specifications Ladder Communication Module
(RS-422-A/RS-485)

General
The F3RZ91-0F Ladder Communication Module provides
RS-422-A or RS-485 communication capability from a
sequence CPU module under the control of a ladder
program. It has one port using a terminal block. It can
communicate with devices at a maximum distance of
1200 m.

Features
- The maximum transmission rate is 115.2 kbps.
- All input relays are interrupt-capable.

Specifications
Item Specification
Connection method Point to point Components and Functions
Transmission mode Full-duplex/half-duplex
Synchronization Start-stop synchronization  Front View
Communication No protocol
protocol
Character 7 or 8 bits RDY RDY indicator :
length Lit when the internal circuit is
Data Stop bit
format 1 or 2 bits functioning normally.
length RZ91-0F RS-422

Parity bit None, even or odd


300, 600, 1200, 2400, 4800, 9600, 14400,
Transmission speed 19200, 28800, 38400, 57600, 76800, or 115200 bps
Commu Send buffer Text buffer (1792 bytes max.)*1
nication Receive
buffers buffer 8192-byte rotary buffer (FIFO buffer) TERMINATOR
2- 4-WIRE Terminator switch
Start - Yes or No OFF Set to the 4- or 2-wire mode
character - Any single character SD A
when the module is configured
End - Yes or No SD B at the end of the cable.
Format character - Up to 2 characters long, any characters
of (terminator) RD A
received Text length Can be specified as any number
RS-422-A/RS-485 terminal block
text between 1 and 1792 *1 RD B
(6 terminals, M3.5 screws)
Character-to
-character 0 to 32760 ms in 1 ms increments, SG
timeout accurate to 1 ms (0 means not monitored)
interval SHIELD
Break transmission 1 to 32760 ms in 1 ms increments,
interval accurate to 1 ms
Transmission distance 1200 m max.  Right Side View
Number of ports 1 (isolated)
Current consumption 350 mA
External dimensions 28.9 (W) x 100 (H) x 83.2 (D) mm*
Weight 120 g
Surrounding air Operating :0 to 55°C
temperature range Rear
Storage :-20°C to 75°C Front
Surrounding humidity Operating :10 to 90% RH (non-condensing)
range SW1 Transmission speed switch
Storage :10 to 90% RH (non-condensing) Sets the transmission
Surrounding Must be free of corrosive gases, flammable gases or speed of the module.
atmosphere heavy dust.
SW3
O
F
1
2
SW2
O
F
1
2 Data format switch
F 3 F 3
*: Excluding protrusions (see external dimensions for details). 4
5
4
5
Defines the format of
6 6 communication data.
*1: The send/receive data register size can be changed to 7
8
7
8

accommodate up to 1792 bytes. This switch is not used.

This figure is drawn with the


panel cover removed.

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 34M06H21-01E Mar.15,2019-00
<<Contents>> <<Index>> 18

External Connection Diagram Operating Environment


There is no restriction on the type of CPU modules that
 Point-to-point Configuration can be used with this module.
(1) 4-wire System
Remote device Remote device
Model and Suffix Codes
F3RZ91-0F
Suffix Style Option
Model Description
SD A SD A SD A
Code Code Code
F3RZ91 -0F ..... ..... 115200 bps max., 1 port
SD B SD B SD B

RD A RD A RD A External Dimensions
RD B RD B RD B Unit: mm
SG SG SG

SHIELD SHIELD SHIELD

83.2 12.1 28.9


(2) 2-wire System 2

F3RZ 91-0F Remote device Remote device

SD A

SD B

RD A
100
RD B

SG SG SG

SHIELD SHIELD SHIELD

Note: In a 2-wire system, SDA and RDA, as well as SDB and RDB, must
be shorted with a wire at the terminal block.
How to connect the shielding conductor (for 4-wire
or 2-wire system)
(1) Ground (connect to the SHIELD terminal) both ends
of the shielding conductor of the twisted-pair cable.
The SHIELD terminal of the F3RZ91-0F module is
connected internally to the FG terminal of the FA-M3
power supply module.
(2) The F3RZ91-0F module has a built-in terminator (220
). When configuring the module at the end of a
cable, set the terminator switch to either a 4- or 2-wire
system.

Terminal Block

SD A M3.5
SD A Send data A
SD B
SD B Send data B
RD A 7.3 mm
RD A Receive data A
8.6 mm
RD B
RD B Receive data B
SG
SG Signal ground
SHIELD
SHIELD Shield

Cables
Recommended cables for 2-wire systems:
KM80-/KM81- (to be purchased separately).
* For details on KM80- and KM81-, see
“FA-M3 YHLS Master Module, YHLS Slave Units and
YHLS Communication Cables” (GS 34M06H46-03E).

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 34M06H21-01E Mar.15,2019-00