Generator Set Technical Specification Compliance (Updated) 5.26.22
Generator Set Technical Specification Compliance (Updated) 5.26.22
Supplier:
I. A. General
1. Scope of Works a. Supply of indoor type generator set
b. Supply of indoor type control panel
c. Supply of fuel system
2. Location Criteria
a. Ambient Temperature 40ºC C
b. Relative Humidity 0 to 99% C
B. Products
e. Transient Frequency Performance: Less than 5 percent variation for 50 percent step-
load increase or decrease. Frequency shall recover
and remain within the steady-state
operating band within five seconds.
f. Output Waveform: At no load, harmonic content measured line to line or line
to neutral
shall not exceed 5 percent total and 3 percent for single
harmonics. Telephone influence
factor, determined according to NEMA MG 1, shall not
exceed 50 percent.
g. Sustained Short-Circuit Current: For a 3-phase, bolted short circuit at system output
terminals, system shall supply a minimum of 250 percent
of rated full-load current for not
less than 10 seconds and then clear the fault
automatically, without damage to generator
system components.
h. Start Time: Comply with NFPA 110, Type 10, system requirements.
C. Engine
1. Engine Brand MTU C 16V4000G83S
2. Fuel Oil #2 Diesel C
3. RPM 1800 C
4. No. of Stroke 4 C
5. Cooling System water cooled C
6. Net brake horsepower of the engine at ≥ 1.45x the rated continuous electric kilowatt rating
rated operating speed ISO3046
7. Governor Electronic adjustable isochronous with speed sensing C
B. Test the engine generator set for eight Record the following test data at 30-minute intervals:
hours of continuous operation as follows: a. Time of day, also reading of running time indicator.
b. KW.
c. Voltage on each phase.
30 minutes at 25% Full Load C
d. Amperes on each phase.
30 minutes at 50% Full Load e. Engine RPM.
1 hour at 75% Full Load f. Frequency.
6 hours at 100% Full Load g. Engine water temperature.
C. Demonstrate that the generator set willh.attain
Fuel pressure
proper voltage, frequency and will accept
70 percent block load within 10 seconds from a cold start after the closing of a single around 10~15s
contact.
II. OTHERS
A. Warranty Three (3) years warranty from date of substantial
completion with three (3) years PMS. C
B. Other features
Legends:
C - Comply
C1 - Comply (as alternative brand or as manufacturer's recommendation)
NC - Non- Complying
TBC - To Be Confirmed and Resubmitted (additional information is required)
Prepared by:
Noted By: