PROJECT NAME: SHEET CONTENT: PROPOSE BY: REMARKS:

EMILIO AGUINALDO PROPOSED TITLE PAGE AVILA, MARVIN C.


COLLEGE - CAVITE 2-STOREY RESIDENTIAL BUILDING DATE : PROPOSE TO:
FEBRUARY 2023 PROF. AMELIA NATIVIDAD
P-1 3-POINT PERSPECTIVE
A NOT TO SCALE

PROJECT NAME: SHEET CONTENT: PROPOSE BY: REMARKS:


EMILIO AGUINALDO PROPOSED BUILDING PERSPECTIVE AVILA, MARVIN C.
COLLEGE - CAVITE 2-STOREY RESIDENTIAL BUILDING DATE : PROPOSE TO:
FEBRUARY 2023 PROF. AMELIA NATIVIDAD
1.0 GENERAL 3.0 LOADING CRITERIA
1.1 GOVERNING CODES
ASSOCIATION OF STRUCTURAL ENGINEERS OF THE PHILIPPINES (ASEP) PUBLICATIONS: 3.1 LATERAL LOADS
NATIONAL STRUCTURAL CODE OF THE PHILIPPINES (NSCP), VOL. 1, 7TH ED., 2015
3.1.1 DEAD LOADS (DL)
ASEP GUIDE - EARTHQUAKE RESISTANT DESIGN OF STRUCTURES, 1991
CONCRETE ------------------------------------------------------------------------------------------------------------ 24.00 kN/m³
UNIFORM BUILDING CODE, 1997
STEEL -------------------------------------------------------------------------------------------------------------------- 77.30 kN/m³
AMERICAN CONCRETE INSTITUTE (ACI) PUBLICATIONS: SOIL ---------------------------------------------------------------------------------------------------------------------- 18.00 kN/m³
BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE (ACI 318-99) SUPERIMPOSED ----------------------------------------------------------------------------------------------------- 3.30 kPa
DETAILS AND DETAILING OF REINFORCEMENT FOR CONCRETE (ACI 315-80, REVISED 1986) FLOOR FINISH
AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC) PUBLICATIONS: CERAMIC OR QUARRY TILE (20mm) ON 13mm MORTAR BED ------------------------------ 0.77 kPa
MANUAL OF STEEL CONSTRUCTION - ALLOWABLE STRESS DESIGN, 9TH ED.,1989 SUBFLOORING, 19mm ------------------------------------------------------------------------------------- 0.14 kPa
AMERICAN IRON AND STEEL INSTITUTE (AISI) PUBLICATIONS: CEMENT FINISH (25mm) ON STONE CONCRETE FILL ----------------------------------------- 1.53 kPa
COLD-FORMED STEEL DESIGN MANUAL, 1996 EDITION ROOFING SHEET
CEMENT TILE ------------------------------------------------------------------------------------------------- 0.77 kPa
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
RIGID INSULATION, 13mm -------------------------------------------------------------------------------- 0.04 kPa
AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM) WALL
AMERICAN WELDING SOCIETY (AWS) CERAMIC TILE ------------------------------------------------------------------------------------------------ 0.77 kPa
1.2 GOVERNING STANDARDS CONCRETE HOLLOW BLOCK (CHB)
ASTM C496 STANDARD TEST METHOD FOR SPLITTING TENSILE STRENGTH OF CYLINDRICAL 4'' THK. CHB ------------------------------------------------------------------------------------------- 2.11 kPa
CONCRETE SPECIMENS 6'' THK. CHB ------------------------------------------------------------------------------------------- 2.73 kPa
ASTM A36 SPECIFICATION FOR STRUCTURAL STEEL CEILINGS
ASTM A53 STANDARD SPECIFICATION FOR PIPE, STEEL, BLACK, AND HOT DIPPED, ZINC- GYPSUM BOARD (PER mm THICKNESS) ----------------------------------------------------------- 0.008 kPa
PLASTER ON WOOD LATH ------------------------------------------------------------------------------- 0.38 kPa
COATED WELDED AND SEAMLESS.
PLASTER ON TILE OR CONCRETE -------------------------------------------------------------------- 0.24 kPa
ASTM A611 SPECIFICATION FOR STEEL, SHEET, CARBON, COLD-ROLLED, STRUCTURAL QUALITY WOOD FURRING SUSPENSION SYSTEM ----------------------------------------------------------- 0.12 kPa
ASTM A615 SPECIFICATION FOR DEFORMED AND PLAIN BILLET-STEEL BARS FOR CONCRETE FLOOR FILL
REINFORCEMENT LIGHTWEIGHT CONCRETE, PER mm ----------------------------------------------------------------- 0.015 kPa
PNS 49 STEEL BARS FOR CONCRETE REINFORCEMENT SPECIFICATION. WATERPROOFING MEMBRANES
ASTM C33/ STANDARD SPECIFICATION FOR CONCRETE AGGREGATES BITUMINOUS, GRAVEL-COVERED --------------------------------------------------------------------- 0.26 kPa
PNS 18 ELECTRICAL/MECHANICAL/PLUMBING ---------------------------------------------------------------------- 0.35 kPa
ASTM C39 STANDARD TEST METHOD FOR COMPRESSIVE STRENGTH OF CYLINDRICAL
3.1.2 LIVE LOADS (LL)
CONCRETE SPECIMENS
OFFICE --------------------------------------------------------------------------------------- 2.4 kPa
ASTM C94/PNS 46 STANDARD SPECIFICATION FOR READY-MIXED CONCRETE
DINING ROOMS ---------------------------------------------------------------------------- 4.8 kPa
PNS 46 BASIC FLOOR AREA --------------------------------------------------------------------- 1.9 kPa
ASTM C150/ STANDARD SPECIFICATION FOR PORTLAND CEMENT EXTERIOR BALCONIES------------------------------------------------------------------ 2.9 kPa
PNS 07 BALCONY RAILINGS ---------------------------------------------------------------------- 0.75 kPa
PNS 16 PHILIPPINE NATIONAL STANDARD FOR CONCRETE HOLLOW BLOCKS PARKING ------------------------------------------------------------------------------------- 2.40 kPa
SG 671 SPECIFICATIONS FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL RESIDENTIAL ------------------------------------------------------------------------------- 1.90 kPa
MEMBERS BY THE AMERICAN IRON AND STEEL INSTITUTE (AISI) DRIVEWAY ----------------------------------------------------------------------------------- 4.80 kPa

3.2 LATERAL LOADS


2.0 MATERIAL SPECIFICATION 3.2.1 WIND LOAD (WL), SEE NSCP 2015
DESIGN WIND PRESSURE, P ---------------------------------------------------------- qGCp - qi (GCpi) (N/m²)
VELOCITY PRESSURE, qz ------------------------------------------------------------- 0.613 Kz Kzt Kd V² (N/m²)
2.1 REINFORCED CONCRETE (ASTM C150)
VELOCITY PRESSURE EXPOSURE ------------------------------------------------- EXPOSURE B
BASIC WIND SPEED, V ------------------------------------------------------------------- ZONE II, 250km PER HOUR
2.1.1 28TH-DAY COMPRESSIVE STRENGTH, f'c
IMPORTANCE FACTOR, Iw -------------------------------------------------------------- STANDARD OCCUPANCY, 1.0
2.1.1.1 FOOTING -------------------------------------------------------------------------------------------- f'c = 20.70 MPa (3000psi)
3.3 SEISMIC LOADS (vL), SEE NSCP
2.1.1.2 COLUMN
3.3.1 DESIGN BASE SHEAR, V ----------------------------------------------------------------- (Cv I W) / R T <= (2.5 Ca I W) / R
FOUNDATION TO 2ND FLOOR --------------------------------------------------------------- f'c = 48.30 MPa (7000psi)
2.1.1.3 BEAM
1ST TO ROOF ------------------------------------------------------------------------------------- f'c =27.60 MPa (4000psi)
ZONE FACTOR, Z (ZONE 4) -------------------------------------------------------------- 0.40
2.1.1.4 SUSPENDED SLAB
IMPORTANCE FACTOR, I ----------------------------------------------------------------- STANDARD OCCUPANCY 1.0
FOUNDATION TO 2ND FLOOR --------------------------------------------------------------- f'c = 20.70 MPa (3000psi)
SOIL TYPE ------------------------------------------------------------------------------------- SD, STIFF SOIL
2.1.1.5 SLAB ON FILL -------------------------------------------------------------------------------------- f'c = 20.70 MPa (3000psi)
FUNDAMENTAL PERIOD OF VIBRATION, T ---------------------------------------- Ct(hn)^(3/4)
NUMERICAL COEFFICIENT, Ct --------------------------------------------------------- 0.0488
2.2 REINFORCING STEEL (ASTM A615) NUMERICAL COEFFICIENT, R ---------------------------------------------------------- 8.50
2.2.1 YIELD STRENGTH, fy ---------------------------------------------------------------------------------------------- fy = 415 N/mm² SEISMIC COEFFICIENT, Ca -------------------------------------------------------------- 0.44 Na
NUMERICAL COEFFICIENT, Cv -------------------------------------------------------- 0.64 Nv
2.3 STRUCTURAL STEEL NEAR-SOURCE FACTOR, Na ----------------------------------------------------------- 1.0
2.3.1 YIELD STRENGTH, Fy NEAR-SOURCE FACTOR, Nv ----------------------------------------------------------- 1.1
2.3.1.1 ROLLED SECTIONS (ASTM A36) -------------------------------------------------------------- Fy = 248 N/mm² SEISMIC LOAD,
ρEh E+ =Ev, WHERE: --------------------------------------------- Eh = V
2.3.1.2 COLD-FRAMED SECTIONS (ASTM A446) -------------------------------------------------- Fy = 276 N/mm² Cv = 0.5 Ca D
2.3.2 ULTIMATE TENSILE STRENGTH, Fu -------------------------------------------------------------------------- Fy = 400 N/mm² D = DEAD LOAD
2.3.3 WELDING ELECTRODE E60XX --------------------------------------------------------------------------------- Fy = 414 N/mm² ρ
2.4 MATERIAL TEST PRIOR TO IMPLEMENTATION OF GRADE 75 REBARS USING ASTM 706 OR GRADE 60 REBARS USING ASTM 615 >= 0.11 Ca I W
2.4.1 REVERSE BEND TEST >= (0.8 Z Nv I W) /R
2.4.2 VICKERS
2.4.3 CHEMICAL TEST 2.0 CONCRETE AND REINFORCEMENT STEEL
2.4.4 LOW CYCLE FATIGUE TEST 2.1 MINIMUM CONCRETE COVER TO ALL REINFORCING BARS SHALL
2.4.5 TENSILE TEST BE AS FOLLOWS:
2.4.6 DEFORMATION GEOMETRY

2.5 LOCATION OR THICKNESS


2.5.1.2 NOMINAL SHEAR STRENGTH (Fnv) ---------------------------------------------------------- 165 N/mm² MEMBER FIGURE
CONDITION OF COVER
2.5.2 HIGH STRENGTH BOLTS (ASTM A325)
2.5.2.1 NOMINAL TENSILE STRENGTH (Fnt) -------------------------------------------------------- 520 N/mm²
2.5.2.2 NOMINAL SHEAR STRENGTH (Fnv) ---------------------------------------------------------- 330 N/mm² SIDE
2.6 SOIL DATA FOOTING/FOUNDATION 75
75
2.6.1 ALLOWABLE PILE CAPACITY, qu -------------------------------------------------------------------------------- 1,300 kN SLAB
BOTTOM

75
UPPER PART OF
GROUND FLOOR 40
LEVEL
COLUMN LOWER PART OF 40

40
GROUND FLOOR
LEVEL
INDOORS FACE ; TOP, 40
SIDE & BOTTOM
40

S-1 STRUCTURAL GENERAL NOTES


BEAM OUTDOORS FACE ;

40
TOP, SIDE & BOTTOM

BOTTOM

20
A NOT TO SCALE

20
SLAB AND STAIR TOP & BOTTOM 20

PROJECT NAME: SHEET CONTENT: PROPOSE BY: REMARKS:


EMILIO AGUINALDO PROPOSED STRUCTURAL GEN NOTES AVILA, MARVIN C.
COLLEGE - CAVITE 2-STOREY RESIDENTIAL BUILDING DATE : PROPOSE TO:
FEBRUARY 2023 PROF. AMELIA NATIVIDAD
SPLICE LENGTH OF BARS
TABLE 304-1. ALLOWABLE FOUNDATION AND LATERAL PRESSURE
PARAMETERS

LATERAL BEARING MATERIAL psi MPa


ALLOWABLE ACI 318-05 DEV'T &
BELOW NATURAL LATERAL SLIDING
CLASS OF MATERIALS FOUNDATION f'c 3000 20.7 SPLICE LENGTH
GRADE (kPa/m OF
PRESSURE (kPA)
DEPTH) RESISTANCE (kPA) fy 60000 414 16mm & HIGHER
COEFFICIENT
fyh 60000 414 12mm & HIGHER
1. "INTACT" TUFFACEOUS - -
1000 300
SANDSTONE TENSION LAP SPLICE (mm)
2. "LIGHTLY WEATHERED" BAR SIZE BEAM COMP. SPLICE
- - BEAM COLUMN UNIT WT. (kg/m)
TUFFACEOUS 500 150 (mmØ) (mm)
LAP CLASS
SANDSTONE TOP BAR BOTTOM BAR TIED SPIRAL
3. SANDY GRAVEL AND/OR - 10 300 495 380 380 380 0.6160
100 30 0.35
GRAVEL (GW & GP)
12 350 A 685 525 525 525 0.8880
4. WELL-GRADED SAND,
POORLY-GRADED SAND, 16 460 910 700 700 700 1.5790
SILTY SAND,CLAYEY -
75 25 0.25 NOTE: f'c IS USED FOR FOOTING, SLAB ON FILL
SAND, SILTY GRAVEL AND
CLAYEY GRAVEL (SW, SP,
SM, SC, GM, AND GC)

5. CLAY, SANDY CLAY,


SILTY CLAY AND CLAYEY 50 15 - 7 SPLICE LENGTH OF BARS
SILT (CL,ML, MH, AND CH)
PARAMETERS

MATERIAL psi MPa ACI 318-05 DEV'T &


f'c 4000 27.6 SPLICE LENGTH
TABLE 305-1. MINIMUM REQUIREMENTS FOR FOUNDATIONS
fy 60000 414 16mm & HIGHER
fyh 60000 414 12mm & HIGHER
THICKNESS OF FOUNDATION WALL (mm) DEPTH BELOW TENSION LAP SPLICE (mm)
NUMBER OF FLOORS WIDTH OF FOOTING THICKNESS OF UNDISTRIBUTED
SUPPORTED BY THE BAR SIZE BEAM COMP. SPLICE
(mm) FOOTING (mm) GROUND SURFACE BEAM COLUMN UNIT WT. (kg/m)
FOUNDATIONS (mmØ) (mm)
(mm) LAP CLASS
CONCRETE UNIT MASONRY TOP BAR BOTTOM BAR TIED SPIRAL
10 300 495 380 380 380 0.6160
2 150 150 375 175 450 12 350 A 595 455 455 455 0.8880
16 460 790 610 610 610 1.5790

NOTE: f'c IS USED FOR COLUMNS BEAMS, GIRDERS


HOOKS DIMENSIONS (PRIMARY REINFORCEMENTS)

L (mm)
BAR DIAMETER (mm) D (mm) NOTE: FOR SPLICE LENGTH OF BARS
180° HOOK 90° HOOK
1. DEVELOPMENT LENGTH OF INDIVIDUAL BARS WITHIN A BUNDLE,
10 60 65 120
IN TENSION OR COMPRESSION, SHALL BE THAT FOR INDIVIDUAL
12 72 65 145 BARS, INCREASED 20% FOR THREE-BUNDLED AND 33% FOR
FOUR-BUNDLE BARS.
16 96 65 192
2. FOR COLUMNS AT ANY LEVEL,NO MORE THAN ALTERNATE BARS
SHOULD BE SPLICED, NOT MORE THAN 33% OF THE BARS SHALL BE
HOOKS DIMENSIONS (STIRRUPS AND TIES) SPLICED WITH THE REQUIRED LAP LENGTH, MINIMUM DISTANCE
BETWEEN TWO ADJACENT SPLICED SHALL BE 600mm.
L (mm) 3. TOP BARS ARE HORIZONTAL WITH MORE THAN 300mm DEPTH OF
BAR DIAMETER (mm) D (mm) CONCRETE CAST BELOW REINFORCEMENT.
TYPE I TYPE II
90° HOOK 180° HOOK 135° HOOK 4. LAP SPLICE SHALL BE "CLASS B" TENSION LAP SPLICE IF MORE
THAN ONE HALF OF THE BARS WERE SPLICED AT ANY SECTION,
10 40 60 60 75 WHILE "CLASS A" TENSION LAP SPLICE IF HALF OR FEWER THAN
12 48 72 72 75 HALF OF BARS WERE SPLICED.

16 64 96 96 96

NOTE: TYPE I - FOR GENERAL USE


TYPE II - FOR SEISMIC USE (FOR ALL COLUMNS AND ALL BEAMS CONNECTED TO COLUMNS)
S-2 STRUCTURAL GENERAL NOTES
SCALE
A 1:100mm

PROJECT NAME: SHEET CONTENT: PROPOSE BY: REMARKS:


EMILIO AGUINALDO PROPOSED STRUCTURAL GEN NOTES AVILA, MARVIN C.
COLLEGE - CAVITE 2-STOREY RESIDENTIAL BUILDING DATE : PROPOSE TO:
FEBRUARY 2023 PROF. AMELIA NATIVIDAD
3 1 2 3 4 5
1 2 4 5

C1 F1 C1 F1 C1 F1 C1 F1 C1 F1 C1 F1
D
WF-1
WF-1
C1 F1
D B1 B1 B1
C1 F1
WF-1
B1 S1 B1 S1 B1 S1 B1
WF-1 WF-1

C1 F1 C1 F1 C1 F1 C1 F1 B1

C B1 C1 F1 C1 F1
B1
C1 F1
C
WF-1 C1 F1

WF-1
B1
B1
S1 B1
B1
WF-1
S1

C1 F1 C1 F1 B1
C1 F1 B1 C1 F1 B1
C1 F1 C1 F1
B
WF-1 WF-1

WF-1
WF-1 C1 F1
B C1 F1

B1
S1 S1 B1 S1 B1
B1
WF-1
WF-1 WF-1 WF-1

B1
C1 F1 WF-1 WF-1
C1 F1 B1 B1

A A
C1 F1 C1 F1 C1 F1 C1 F1

S-3 FOUNDATION PLAN S-3 SECOND FLOOR FRAMING PLAN


A SCALE 1:1MTS B SCALE 1:1MTS

PROJECT NAME: SHEET CONTENT: PROPOSE BY: REMARKS:


EMILIO AGUINALDO PROPOSED
FOUNDATION PLAN
SECOND FLOOR FRAMING PLAN
AVILA, MARVIN C.
COLLEGE - CAVITE 2-STOREY RESIDENTIAL BUILDING DATE : PROPOSE TO:
FEBRUARY 2023 PROF. AMELIA NATIVIDAD
1 2 3 4 5

5.85 m

C1 F1 C1 F1
B1 B1
C1 F1
D
B1
C1 F1
B1 S1 B1 S1 B1 B1

C1 F1 B1

B1 C1 F1 C1 F1 B1 C1 F1
C 3.15 m

B1
B1
S1 B1
B1
S1

C1 F1 B1 C1 F1 B1 C1 F1 B1

C1 F1
B 0.15 m

C1 F1

B1
S1 B1
S1 B1

C1 F1 B1

C1 F1
B1

C1 F1
A S-4 SECTION DETAIL
B SCALE 1:1MTS

S-4 ROOF FRAMING PLAN


A SCALE 1:1MTS

PROJECT NAME: SHEET CONTENT: PROPOSE BY: REMARKS:


ROOF FRAMING PLAN
EMILIO AGUINALDO PROPOSED SECTION DETAIL
AVILA, MARVIN C.
COLLEGE - CAVITE 2-STOREY RESIDENTIAL BUILDING DATE : PROPOSE TO:
FEBRUARY 2023 PROF. AMELIA NATIVIDAD
NGL

75mm Concrete Cover

10 - 12mmØ Horizontal Rebar O.C Both Side


SPACED @150mm 1.500
1.400

0.150
0.300

0.600
1.500

TYPICAL COLUMN FOOTING SCHEDULE

FOOTING DIMENSIONS (mm) SHORT BARS LONG BARS


SYMBOL BAR Ø (mm)
BOTTOM BOTTOM
B H T D TOP BAR TOP BAR
BAR BAR
10 - - - -
C1F1 1500 1500 600 2000
12 - 10 - 10

S-5 COLUMN FOOTING DETAILS


A SCALE 1:1MTS

PROJECT NAME: SHEET CONTENT: PROPOSE BY: REMARKS:


EMILIO AGUINALDO PROPOSED COLUMN FOOTING DETAILS AVILA, MARVIN C.
COLLEGE - CAVITE 2-STOREY RESIDENTIAL BUILDING DATE : PROPOSE TO:
FEBRUARY 2023 PROF. AMELIA NATIVIDAD
10mmØ Stirrups Rest@250
10mmØ Stirrups 5@150
0.300 50mm THK. CONCRETE
CLEAR COVER

10mmØ Stirrups 3@100

10mmØ Stirrups 1@50


0.400
10mmØ Stirrups 5@150 10mmØ Stirrups 3@100 10mmØ Stirrups 3@100 10mmØ Stirrups 5@150

6-12mmØ HORIZONTAL BARS


BEAM
10mmØ STIRRUP

10mmØ Stirrups 1@50 10mmØ Stirrups 1@50


10mmØ Stirrups Rest@250 10mmØ Stirrups Rest@250
0.400

10mmØ Stirrups 1@50

10mmØ Stirrups 3@100


0.400

ROOF BEAM

10mmØ Stirrups 5@150


10mmØ Stirrups Rest@250
S-6 BEAM DETAILS
A SCALE 1:1MTS

PROJECT NAME: SHEET CONTENT: PROPOSE BY: REMARKS:


EMILIO AGUINALDO PROPOSED BEAM DETAILS AVILA, MARVIN C.
COLLEGE - CAVITE 2-STOREY RESIDENTIAL BUILDING DATE : PROPOSE TO:
FEBRUARY 2023 PROF. AMELIA NATIVIDAD
300mm X 300mm RC COLUMN

NGL

6-12mm Ø VERTICAL BARS


0.30 SPACED @150mm
6-12mm Ø VERTICAL BARS
SPACED @150mm 10mm Ø TIES

1.40
10mm Ø TIES SPACED @150mm
0.30

SPACED @150mm
40mm THK. CONCRETE
40mm THK. CONCRETE
CLEAR COVER
CLEAR COVER

S-7 COLUMN DETAILS


A SCALE 1:1mm

PROJECT NAME: SHEET CONTENT: PROPOSE BY: REMARKS:


EMILIO AGUINALDO PROPOSED COLUMN DETAILS AVILA, MARVIN C.
COLLEGE - CAVITE 2-STOREY RESIDENTIAL BUILDING DATE : PROPOSE TO:
FEBRUARY 2023 PROF. AMELIA NATIVIDAD
0.300
10mmØ @200MM O.C
STIRRUPS
2-16mmØ TOP BARS

2-16mmØ WEB BARS


0.400

2-16mmØ BOTTOM BARS

1 SB-1 DETAILS
S-7 SCALE: 1:1 m

S-8 STAIR DETAILS


A SCALE 1:1MTS

PROJECT NAME: SHEET CONTENT: PROPOSE BY: REMARKS:


EMILIO AGUINALDO PROPOSED STAIR DETAILS AVILA, MARVIN C.
COLLEGE - CAVITE 2-STOREY RESIDENTIAL BUILDING DATE : PROPOSE TO:
FEBRUARY 2023 PROF. AMELIA NATIVIDAD
25

125

S-9 SLAB REINFORCEMENT DETAIL


A SCALE 1:1 mm

PROJECT NAME: SHEET CONTENT: PROPOSE BY: REMARKS:


EMILIO AGUINALDO PROPOSED SLAB REINFORCEMENT DETAIL AVILA, MARVIN C.
COLLEGE - CAVITE 2-STOREY RESIDENTIAL BUILDING DATE : PROPOSE TO:
FEBRUARY 2023 PROF. AMELIA NATIVIDAD
1.00 6.20 1.30 1.50 1.00 6.30 1.30 1.50

0.75
W1 0.75
W1
0.60
W2 T&B 1 0.60
W2 T&B 2 BEDROOM 3
D5 0.80
D5
KITCHEN 5.00

D2

4.65 4.65

1.50
W3 HALL 1 1.50 W3 GAME ROOM
HALL 2
D2 0.80 D2
0.80 0.80 W1
0.20
10.10
D2 1.30 D2 D2 1.30

W1
MASTER'S D3 1.90

BEDROOM BEDROOM
CAR 0.95

4.00 BEDROOM 1 LIVING ROOM PORT 4.00 4.00 2 D4 BALCONY


T&B 3
D1 1.00

W1 W1 W1 W1
1.25 1.30 2.35 1.30 1.30 2.50 0.93 1.30 3.20 1.30 3.27

A-1 FIRST FLOOR PLAN A-1 SECOND FLOOR PLAN


A SCALE 1:1MTS B SCALE 1:1MTS

PROJECT NAME: SHEET CONTENT: PROPOSE BY: REMARKS:


FIRST FLOOR PLAN
EMILIO AGUINALDO PROPOSED SECOND FLOOR PLAN
AVILA, MARVIN C.
COLLEGE - CAVITE 2-STOREY RESIDENTIAL BUILDING DATE : PROPOSE TO:
FEBRUARY 2023 PROF. AMELIA NATIVIDAD
A-2 FRONT ELEVATION A-2 REAR ELEVATION
A SCALE 1:1MTS B SCALE 1:1MTS

A-2 LEFT-SIDE ELEVATION A-2 RIGHT-SIDE ELEVATION


C SCALE 1:1MTS D SCALE 1:1MTS

PROJECT NAME: SHEET CONTENT: PROPOSE BY: REMARKS:


EMILIO AGUINALDO PROPOSED BUILDING ELEVATIONS AVILA, MARVIN C.
COLLEGE - CAVITE 2-STOREY RESIDENTIAL BUILDING DATE : PROPOSE TO:
FEBRUARY 2023 PROF. AMELIA NATIVIDAD
A-3 CROSS-SECTION A-3 LONGITUDINAL SECTION
A NOT TO SCALE B NOT TO SCALE

PROJECT NAME: SHEET CONTENT: PROPOSE BY: REMARKS:


EMILIO AGUINALDO PROPOSED BUILDING SECTIONS AVILA, MARVIN C.
COLLEGE - CAVITE 2-STOREY RESIDENTIAL BUILDING DATE : PROPOSE TO:
FEBRUARY 2023 PROF. AMELIA NATIVIDAD
2.86

0.60

1.30
0.60 1.50
2.10 2.10 2.17 2.18 2.10

1.50 1.60

1.30
0.79

0.80
1.00 0.80 1.90 1.00

D1 D2 D3 D5
D4 W1 W2 W3
SPECS : PANEL DOOR SPECS : PANEL DOOR SPECS : BI-FOLD DOOR SPECS : FLASH TYPE
SPECS : PANEL DOOR SPECS : CASEMENT SPECS : AWNING SPECS : GLASS BLOCKS
MATERIAL: HARDWOOD MATERIAL: HARDWOOD MATERIAL: HARDWOOD DOOR W/ LOUVER
MATERIAL: GLASS MATERIAL: GLASS MATERIAL: GLASS MATERIAL: GLASS
TIMBER TIMBER TIMBER MATERIAL: PVC
LOC : T&B 3 LOC : W1 LOC : W2 LOC : W3
LOC : LIVING ROOM LOC : KITCHEN, LOC : MASTER's LOC : T&B 1 and 2
QTY : ONE (1) SET QTY : EIGHT (8) SETS QTY : TWO (2) SETS QTY : ONE (1) SET
QTY : ONE (1) SET BEDROOMS 1, 2, 3. BEDROOM QTY : TWO (2) SETS
GAMEROOM, and QTY : ONE (1) SET
MASTER's BEDROOM
QTY : SIX (6) SETS

A-4 SCHEDULE OF DOORS AND WINDOWS


A SCALE 1:1MTS

PROJECT NAME: SHEET CONTENT: PROPOSE BY: REMARKS:


EMILIO AGUINALDO PROPOSED SCHEDULE OF DOORS AND WINDOWS AVILA, MARVIN C.
COLLEGE - CAVITE 2-STOREY RESIDENTIAL BUILDING DATE : PROPOSE TO:
FEBRUARY 2023 PROF. AMELIA NATIVIDAD
2,74

2,28 2,74

2,24

1,45

1,90
1,90
2,35

2,34

1,44

0,86
0,90 1,19

0,35
2,24

2,74

2,80 2,80 2,80

5,80 0,20 5,80 0,20 5,80 0,20

2,60 2,60 2,60

0,20 0,20 0,20

A-5 STAIR PLAN


A SCALE 1:1MTS

PROJECT NAME: SHEET CONTENT: PROPOSE BY: REMARKS:


EMILIO AGUINALDO PROPOSED STAIR PLAN AVILA, MARVIN C.
COLLEGE - CAVITE 2-STOREY RESIDENTIAL BUILDING DATE : PROPOSE TO:
FEBRUARY 2023 PROF. AMELIA NATIVIDAD
BALCONY

A-6 ROOF PLAN


A SCALE 1:1MTS

PROJECT NAME: SHEET CONTENT: PROPOSE BY: REMARKS:


EMILIO AGUINALDO PROPOSED ROOF PLAN AVILA, MARVIN C.
COLLEGE - CAVITE 2-STOREY RESIDENTIAL BUILDING DATE : PROPOSE TO:
FEBRUARY 2023 PROF. AMELIA NATIVIDAD
ROOM FINISH SCHEDULE
ROOM NAME FLOOR FINISH WALL FINISH CEILING FINISH CEILING HEIGHT REMARKS
LIVING ROOM PFT PSG FCB 3

KITCHEN PFT PSG FCB 3

CAR PORT PC PSG SSP 3

T&B 1 CFT PSG FCB 3

T&B 2 CFT PSG FCB 2.4

T&B 3 CFT PSG FCB 2.4

BEDROOM 1 PFT CWT FCB 3

BEDROOM 2 PFT CWT FCB 2.4

BEDROOM 3 PFT CWT FCB 2.4

MASTER'S BEDROOM LWF CWT FCB 2.4

GAME ROOM LWF PSG SW 2.4

BALCONY CFT PSG N/A N/A

HALL 1 PFT PSG FCB 3

HALL 2 PFT PSG FCB 2.4

STAIRCASE PFT PSG FCB VARIES

A-7 SCHEDULE OF ROOM FINISHES


A SCALE 1:1MTS

PROJECT NAME: SHEET CONTENT: PROPOSE BY: REMARKS:


EMILIO AGUINALDO PROPOSED SCHEDULES OF ROOM FINISHES AVILA, MARVIN C.
COLLEGE - CAVITE 2-STOREY RESIDENTIAL BUILDING DATE : PROPOSE TO:
FEBRUARY 2023 PROF. AMELIA NATIVIDAD
ROOM FINISH LEGEND
FLOOR FINISH GROUP WALL FINISH GROUP CEILING FINISH GROUP

PFT Porcelain floor PSG Painted FCB Fiber Cement


Tiles (60x60 CM) (Semi-Gloss Board (Hardflex)
Finish)
CFT1 Ceramic Floor CWT Ceramic Wall SSP Slab Soffit -
Tiles (30x30 CM) Tiles (Glazed) Painted
CFT2 Ceramic Floor PWT Porcelain Wall SW SOLID WOOD
Tiles (20x20 CM) Tiles (Glazed)
LWF Laminated Wood
Flooring
PWO Peeble Wash Out
PC Plain Cement

A-8 ROOM FINISH LEGEND


SCALE 1:1MTS
A

PROJECT NAME: SHEET CONTENT: PROPOSE BY: REMARKS:


EMILIO AGUINALDO PROPOSED ROOM FINISH LEGEND AVILA, MARVIN C.
COLLEGE - CAVITE 2-STOREY RESIDENTIAL BUILDING DATE : PROPOSE TO:
FEBRUARY 2023 PROF. AMELIA NATIVIDAD
P-1 PLUMPING GENERAL NOTES
SCALE 1:100mm
A
PROJECT NAME: SHEET CONTENT: PROPOSE BY: REMARKS:
EMILIO AGUINALDO PROPOSED PLUMBING GENERAL NOTES AVILA, MARVIN C.
COLLEGE - CAVITE 2-STOREY RESIDENTIAL BUILDING DATE : PROPOSE TO:
FEBRUARY 2023 PROF. AMELIA NATIVIDAD
CB 2 3 4
ST CB CB 2 3 4
1.000 6.300 1.300 1.500 1.000 6.200 1.300 1.500

A A
0.750
FCO W1 0.750
FD
W1
0.600
W2 T&B 1 0.600
W2 T&B 2 BEDROOM 3
DC D5

FCO
D5 0.800
FD
KITCHEN 5.000
LC D2
B LC B
4.650 4.650

1.500 W3 HALL 1 1.500 W3 GAME ROOM


HALL 2

1 0.800
D2 0.800
1 0.800
D2
W1
CB 0.200
C 10.000 C
D2 1.300 D2 D2 1.300 FD

W1
MASTER'S D3 1.900

LIVING ROOM CAR BEDROOM BEDROOM


PORT
0.953

4.000 BEDROOM 1 4.000 4.000 2 D4 BALCONY

FCO
T&B 3

D1 1.003

W1 W1 W1 FD
W1
D D
1.250 1.300 2.350 1.300 1.300 2.500 0.925 1.300 3.200 1.300 3.275

CB CB

FIRST FLOOR SECOND FLOOR

P-2 SEWER VENT AND LINE LAYOUT P-2 SEWER VENT AND LINE LAYOUT
A SCALE 1:1MTS B SCALE 1:1MTS

9.000

0.25m Stainless Gutter

ROOF VENT
6.000 6.000

FIREWALL

2.500

4.000
BALCONY 4.000

7.500 2.500

ROOF PLAN

P-2 SEWER VENT AND LINE LAYOUT


C SCALE 1:1MTS

PROJECT NAME: SHEET CONTENT: PROPOSE BY: REMARKS:


1ST FLOOR, 2ND FLOOR, AND ROOF
EMILIO AGUINALDO PROPOSED SEWER VENT AND LINE LAYOUT
AVILA, MARVIN C.
COLLEGE - CAVITE 2-STOREY RESIDENTIAL BUILDING DATE : PROPOSE TO:
FEBRUARY 2023 PROF. AMELIA NATIVIDAD
2 3 4 2 3 4
1.000 6.200 1.300 1.500 1.000 6.200 1.300 1.500

A A
0.750
W1 0.750
W1
0.600
W2 T&B 1 0.600
W2 T&B 2 BEDROOM 3
D5 0.800
D5
KITCHEN 5.000

D2
B B
4.650
4.650

1.500
W3 HALL 1 1.500 W3 GAME ROOM
HALL 2
1 D2 0.800
1 D2
0.800
0.800 W1
0.200
C C
D2 10.000

1.300
D2 D2 1.300

W1
MASTER'S D3 1.900

BEDROOM BEDROOM
CAR 0.953

4.000 BEDROOM 1 LIVING ROOM 4.000


2
PORT BALCONY
4.000
D4

T&B 3

D1 1.003

W1 W1 W1
D W1
1.250 1.300 2.350 1.300 1.300 2.500
D
0.925 1.300 3.200 1.300 3.275

FIRST FLOOR SECOND FLOOR

P-3 COLD WATER LINE LAYOUT COLD WATER LINE LAYOUT


P-3
A SCALE 1:1MTS
B SCALE 1:1MTS

9.000

0.25m Stainless Gutter

ROOF VENT
6.000 6.000

FIREWALL

P-3 Gutter details


2.500
D SCALE NTS

4.000
BALCONY 4.000

7.500 2.500

P-3 STORM DRAINAGE LAYOUT


C SCALE 1:1MTS

PROJECT NAME: SHEET CONTENT: PROPOSE BY: REMARKS:


EMILIO AGUINALDO PROPOSED AVILA, MARVIN C.
COLLEGE - CAVITE 2-STOREY RESIDENTIAL BUILDING DATE : PROPOSE TO:
FEBRUARY 2023 PROF. AMELIA NATIVIDAD
ELECTRICAL GENERAL NOTES:
NEAREST METAL WATER PIPE.
1. ALL ELECTRICAL INSTALLATIONS HEREIN AND OTHER RELATED WORKS TO BE DONE IN
6. MOUNTING HEIGHT FOR ALL WIRING DEVICES AND PANEL BOARDS SHALL BE.
THIS BUILDING SHALL BE IN ACCORDANCE WITH THE PROVISIONS AND STANDARDS OF
THE FOLLOWING: 6.1 LIGHTING OUTLETS 1.40M ABOVE FLOOR FINISH.
1.1 THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE. 6.2 CONVENIENCE OUTLETS 0.30M ABOVE FLOOR FINISH.
1.2 REPUBLIC ACT 7926 OTHERWISE KNOWN AS THE NEW ELECTRICAL 6.3 TELEPHONE OUTLETS 0.30M ABOVE FLOOR FINISH.
ENGINEERING LAW 6.4 PANEL BOARDS & CABINETS 1.40M ABOVE FLOOR FINISH.
1.3 THE NATIONAL BUILDING CODE OF THE PHILIPPINES. 7. WIRING METHODS SHALL BE AS FOLLOWS:
1.4 FIRE CODE OF THE PHILIPPINES. 7.1 SERVICE ENTRANCE RESISTS INTERMEDIATE METALLIC
1.5 EXISTING RULES AND REGULATION OF THE LOCAL POWER UTILITY COMPANY.
CONDUIT (IMC).
1.6 THE EXISTING CITY/MUNICIPAL ORDINANCES AND,
1.7 THE BUREAU OF LABOR STANDARDS. 7.2 LIGHTING AND POWER SYSTEM POLYVINYL CHLORIDE (PVC).
2. ALL ELECTRICAL INSTALLATIONS HEREIN SHALL BE DONE UNDER THE DIRECT 7.3 TELEPHONE OUTLETS POLYVINYL CHLORIDE (PVC).
SUPERVISION OF A DULY REGISTERED ELECTRICAL ENGINEER. HE SHALL BE RESPONSIBLE 7.4 ALL VIBRATING EQUIPMENTS LIQUID TIGHT FLEXIBLE METAL
IN THE INTERPRETATION OF THE PLANS AND SPECIFICATION AND THE REQUIRED CONDUIT.
STANDARDS OF THE ELECTRICAL CODE. 8. NO CHANGES OR MODIFICATION SHALL BE MADE WITHOUT THE DESIGNERS WRITTEN
3. MATERIALS AND EQUIPMENT TO BE USED SHALL HAVE INSPECTED COMMODITY CONSENT.
CLEARANCE (ICC) LABEL FOR FOREIGN MADE PRODUCTS AND P.S. MARK FOR LOCAL IN
9. ALL WORKS SHALL BE EXECUTED IN A WORKMANSHIP MANNER AND SHALL PREVENT A
NATURE OF THE BUREAU OF PRODUCT STANDARD (BPS).
4. PROVIDE GROUNDING WIRE TO ALL OUTLETS AND LIGHTING CIRCUITS, ALL NON CURRENT NEAT AND ORDERLY ACCEPTANCE. ALL WIRING SHALL BE CONCEALED IN THE LEAST
CARRYING METAL PARTS SHALL BE GROUNDED AND BOBDED INCLUDING FENCE AND POSSIBLE WAY.
GATE.
5. ALL PANEL BOARDS, MAIN DISTRIBUTION PANELS, ETC., SHALL HAVE GROUNDING BUS FOR
BRANCH CIRCUITS AND SUB FEEDER GROUNDING SYSTEM SHALL BE BONDED TO THE
NEAREST METAL WATER PIPE.

ELECTRICAL NOTES
E-1
A SCALE 1:1MTS

PROJECT NAME: SHEET CONTENT: PROPOSE BY: REMARKS:


EMILIO AGUINALDO PROPOSED ELECTRICAL NOTES AVILA, MARVIN C.
COLLEGE - CAVITE 2-STOREY RESIDENTIAL BUILDING DATE : PROPOSE TO:
FEBRUARY 2023 PROF. AMELIA NATIVIDAD
1.000 6.200 1.300 1.500
1.000 6.200 1.300 1.500

0.750
W1 0.750 T&B 2 W1
0.600
W2 KITCHEN 0.600 W2 BEDROOM 3 Wirings
D5 D5
T&B 1 Types Diameter
0.800 5.000
D2 Lightings 2mm THHN
Appliances/Laundry 3.5mm THHN
4.650
HALL 1 4.650
GAME ROOM Airconditions 5.5mm THHN
1.500 W3 1.500 W3
Feeder/Large Appliances 8mm THHN
D2 0.800 HALL 2 D2 Service Entrance 25mm THHN
0.800 0.800 W1
0.200
BREAKER
10.000
D2 1.300
MB

D2 D2 1.300
SCHEDULE ELECTRICAL LAY OUT
W1 WIRE
BEDROOM MASTER'S D3 1.900
SWITCH BOARD
2 BEDROOM
LIVING ROOM CAR 0.953 CEILING LIGHT
4.000 4.000 BREAKER BREAKER
PORT 5.000 D4
METER BOX
BALCONY
MB

BEDROOM 1 DUPLEX RECEPTACLE OUTLET


WIRE FOR SWITCHES
D1 1.003
W1 W1 W1 T&B 3 W1
1.250 1.300 2.350 1.300 1.300 2.500 0.925 1.300 3.200 1.300 3.275

E-2 FIRST FLOOR POWER LAYOUT E-2 SECOND FLOOR POWER LAYOUT
A SCALE 1:1MTS B SCALE 1:1MTS

SERVICE ENTRANCE

PROJECT NAME: SHEET CONTENT: PROPOSE BY: REMARKS:


EMILIO AGUINALDO PROPOSED POWER LAYOUT AVILA, MARVIN C.
COLLEGE - CAVITE 2-STOREY RESIDENTIAL BUILDING DATE : PROPOSE TO:
FEBRUARY 2023 PROF. AMELIA NATIVIDAD
1.000 6.200 1.300 1.500
1.000 6.300 1.300 1.500

0.750
W1 0.750 T&B 2 BREAKER
W1 CL4

CL3 BEDROOM 3
0.600
W2 KITCHEN 0.600 W2 CL3
D5 D5
T&B 1 CL1 5.000
CL2 CL4

SCHEDULE ELECTRICAL LAY OUT


0.800
CL1
D2 WIRE
CL4
CL4

4.650
HALL 1 SWITCH BOARD
4.650 CL1 GAME ROOM
1.500 W3 1.500 W3 CEILING LIGHT

CL4
BREAKER BREAKER
CL4 CL3
D2 0.800 HALL 2 D2 MB
METER BOX
0.800 0.800 W1
0.200 DUPLEX RECEPTACLE OUTLET
BREAKER

CL1 10.000
D2 1.300
MB

D2 D2 CL4 1.300 CL4


WIRE FOR SWITCHES
W1
CL1
BEDROOM MASTER'S CL1
D3 1.900
LIGHTING SCHEDULE
2 BEDROOM Location Specs Quantity TOTAL:
CL2 LIVING ROOM CAR 0.953
CL1 12 watts, LED 8 pcs. 96 watts
4.000 4.000
PORT 5.000
CL2 D4 CL2 CL2 10 watts, LED 4 pcs. 40 watts
BEDROOM 1 CL3
BALCONY CL3 7 watts, LED 4 pcs. 28 watts
CL1
CL4 5 watts, LED 16 pcs. 80 watts
CL1

CL4 CL4 D1 1.003 CL4 CL4 CL4 CL4

W1 W1 W1 T&B 3 W1
CL4 CL4
1.250 1.300 2.350 1.300 1.300 2.500 0.925 1.300 3.200 1.300 3.275

E-3 FIRST FLOOR LIGHTING LAYOUT E-3 SECOND FLOOR LIGHTING LAYOUT
A SCALE 1:1MTS B SCALE 1:1MTS

SERVICE ENTRANCE

PROJECT NAME: SHEET CONTENT: PROPOSE BY: REMARKS:


EMILIO AGUINALDO PROPOSED LIGHTING LAYOUT AVILA, MARVIN C.
COLLEGE - CAVITE 2-STOREY RESIDENTIAL BUILDING DATE : PROPOSE TO:
FEBRUARY 2023 PROF. AMELIA NATIVIDAD
1.00 6.20 1.30 1.50
1.00 6.20 1.30 1.50

0.75
W1 0.75
W1 Aircondition Schedule
0.60
W2 T&B 1 0.60
W2 T&B 2 BEDROOM 3 Location Floor Area(sqm)
AC Unit Size
D5 0.80
D5 (Horsepower)
KITCHEN 5.00

D2
Bedroom 1 17.04 sqm 1.0 hp
Bedroom 2 13.68 sqm 0.75 hp
4.65 5.65

1.50
W3 HALL 1 1.50 W3 GAME ROOM Bedroom 3 9.9225 sqm 0.5 hp
HALL 2
Master's Bedroom 20.88 sqm 1.0 hp
D2 0.80 D2
0.80 0.80 W1
0.20
10.00
D2 1.30 D2 D2 1.30

W1 SPLIT-TYPE INVERTER AIR CONDITIONER


MASTER'S D3 1.90

CAR BEDROOM BEDROOM


LIVING ROOM
BEDROOM 1 PORT 2
0.95

AUX
BALCONY
4.00 4.00
5.00
D4 Inverter

T&B 3
AUX
Inverter

D1 1.00

W1 W1 W1 W1 INDOOR UNIT
1.25 1.30 2.35 1.30 1.30 2.50 0.925 1.30 3.20 1.30 3.275

M-1 FIRST FLOOR MECHANICAL PLAN M-1 SECOND FLOOR MECHANICAL PLAN OUTDOOR UNIT
A SCALE 1:1MTS B SCALE 1:1MTS

PROJECT NAME: SHEET CONTENT: PROPOSE BY: REMARKS:


EMILIO AGUINALDO PROPOSED MECHANICAL PLAN AVILA, MARVIN C.
COLLEGE - CAVITE 2-STOREY RESIDENTIAL BUILDING DATE : PROPOSE TO:
FEBRUARY 2023 PROF. AMELIA NATIVIDAD