FIRE PUMP FIELD ACCEPTANCE TEST


Pin No. Date 23/01/2023
Location Misaeed, Qatar Application Number
Project Name NPP0050 QENFB Infrastructure and Utility Buildings – Fresh Water Building
Owner State of Qatar- Qatar Armed Forces

QCDD Approved Drawing Ref. No.


Test Status Passed

PRESSURE SETTING CUT- IN CUT-OUT


Jockey Pump 10.1 bars(147PSI) 110.8 bars(157PSI)
Duty Pump 9.77 bars(141.7PSI) Manual
Standby Pump 9.08 bars (132PSI) Manual

JOCKEY PUMP
Manufacturer Grundfos HP 3.2
Type or Model A96513381P31935 Ampere 9.6
Serial Number 0010 & 0009 Volt 415
Controller Manufacturer TORNATECH Controller Model JP3-415/5.5/3/50
or Type
FIRE PUMP SET DATA
ELECTRIC MOTOR DRIVEN

Manufacturer PATTERSON Type HORIZONTAL SPLIT CASE

Model or Type 12 x 8 MAA2 Serial Number FP-C185764-01


Rated Flow 500 GPM Rated Pressure 154

Rated HP 350 No Flow Pressure 168


Rated Voltage 415 Overload Pressure 132
Phase Cycles 3 Suction Pressure 182

Rated Speed 1470 Rated Amperes 425

Imp. Diameter 22.750 Service Factor 1.15

CONTROLLER
Manufacturer TORNATECH Line Volt 415

_________________________________
Contractor Signature _________________________________
Consultant Signature

Type or Model GPS-415/350/3/50 Control Volt 415


GENERAL HEADQUARTERS (QAF) ‫القيادة العامة للقوات المسلحة القطرية‬
CENTRAL FIREFIGHTING UNIT ‫وحــــــدة اإلطـفـائيــــة المـركزيـــــــــة‬
DOHA – QATAR ‫الدوحة – قطر‬
TELEPHONE: +97440432170 97440432170: ‫تليفــــون‬+
FAX : +97440432179 97440432179 : ‫فاكــــــس‬+

Serial Number WZ1097899 HP capacity 350

NEMA Type 2 Max. Pressure 300 PSI

DIESEL ENGINE DRIVEN


Manufacturer N/A Type N/A

Model or Type N/A Serial Number N/A

Rated Flow N/A Rated Pressure N/A

Rated BHP N/A No Flow Pressure N/A


Rated Speed N/A Overload Pressure N/A
Imp. Diameter N/A Suction Pressure N/A

Fuel Tank Size N/A

CONTROLLER
Manufacturer N/A Line Volt N/A

Type or Model N/A Control Volt N/A

Serial Number N/A HP capacity N/A

NEMA Type N/A Max. Pressure N/A

__________________________ ________________________________
Contractor Signature Consultant Signature
GENERAL HEADQUARTERS (QAF) ‫القيادة العامة للقوات المسلحة القطرية‬
CENTRAL FIREFIGHTING UNIT ‫وحــــــدة اإلطـفـائيــــة المـركزيـــــــــة‬
DOHA – QATAR ‫الدوحة – قطر‬
TELEPHONE: +97440432170 97440432170: ‫تليفــــون‬+
FAX : +97440432179 97440432179 : ‫فاكــــــس‬+

ELECTRIC MOTOR DRIVEN


STANDBY FIRE PUMP
Manufacturer N/A Type N/A

Model or Type N/A Serial Number N/A

Rated Flow N/A Rated Pressure N/A

Rated HP N/A No Flow Pressure N/A


Rated Voltage N/A Overload Pressure N/A
Phase Cycles N/A Suction Pressure N/A

Rated Speed N/A Rated Amperes N/A

Imp. Diameter N/A Service Factor N/A

CONTROLLER
Manufacturer N/A Line Volt N/A

Type or Model N/A Control Volt N/A

Serial Number N/A HP capacity N/A

NEMA Type N/A Max. Pressure N/A

_________________________________ ____________________________________

Contractor Signature Consultant Signature


GENERAL HEADQUARTERS (QAF) ‫القيادة العامة للقوات المسلحة القطرية‬
CENTRAL FIREFIGHTING UNIT ‫وحــــــدة اإلطـفـائيــــة المـركزيـــــــــة‬
DOHA – QATAR ‫الدوحة – قطر‬
TELEPHONE: +97440432170 97440432170: ‫تليفــــون‬+
FAX : +97440432179 97440432179 : ‫فاكــــــس‬+

DIESEL ENGINE DRIVEN


Manufacturer PATTERSON Type HORIZONTAL SPLIT CASE
Model or Type 10X8 M Serial Number FP-C185763-01
Rated Flow 2500 Rated Pressure 154
Rated BHP 360 No Flow Pressure 169
Rated Speed 2100 Overload Pressure 127
Imp. Diameter 16In Suction Pressure 81
Fuel Tank Size 449 gallon
CONTROLLER
Manufacturer TORNATECH Line Volt 208-240
Type or Model GPD-24-220 Control Volt N/A
Serial Number WZ1097903 HP capacity N/A
NEMA Type 2 Max. Pressure 300

CHECK LIST
Activity Yes N/A
Flushing test conducted per NFPA 20 requirements YES

Hydrostatic test conducted per NFPA 20 requirements YES

Were concerned people present during pre-acceptance test per NFPA 20 YES

Fire pump systems are installed as per approved plans and NFPA 20 requirements YES

All test equipment shall be calibrated YES

Sequence of operation simulated and accepted as per approved setting YES

Controllers simulation test were conducted per NFPA 20 requirements YES

All test procedures and requirements simulated and conducted as per NFPA 20 requirements YES

Was the governor set to properly regulate the engine speed at rated pump speed. YES

All required interfacing to fire alarm system was performed and accepted per NFPA 20. YES

Did the fire pumps (duty & standby) performance meet the Manufacturer’s Certified Pump Test YES

Characteristic Curve?
Are fire pumps Manufacturer’s Certified Pump Test Characteristic Curve available on-site YES

_________________________________ ____________________________________

Contractor Signature Consultant Signature


GENERAL HEADQUARTERS (QAF) ‫القيادة العامة للقوات المسلحة القطرية‬
CENTRAL FIREFIGHTING UNIT ‫وحــــــدة اإلطـفـائيــــة المـركزيـــــــــة‬
DOHA – QATAR ‫الدوحة – قطر‬
TELEPHONE: +97440432170 97440432170: ‫تليفــــون‬+
FAX : +97440432179 97440432179 : ‫فاكــــــس‬+

FIRE PUMP PERFORMANCE.


ELECTRIC
DUTY FIRE PUMP
FIRE PUMP
Pump 12 X 8 MAA Serial FP-C185764-01 Design Actual
Model Number Pressure Pressur
PSI (m) e
(PSI(m)
Rated Capacity Speed Capacity Volts Amps Suction Discharge Suction Discharge
(RPM) (GPM)
Shut off 0% 1492 0 412/413/413 246/250 +8 168 +8 184
Rated 100% 1470 2500 410/411 /413 410/419 +8 154 +6 165

150 % of rated 150% 1460 3750 411/411/412 473/482 +8 132 +4 144


flow

DIESEL FIRE PUMP


Pump N/A Serial N/A Design Actual
Model Number Pressure Pressur
PSI (m) e
(PSI(m)
Rated Capacity Speed Capacity - - Suction Discharge Suction Discharge
(RPM) (GPM)
Shut off 0% N/A N/A N/A N/A N/A N/A N/A N/A
Rated 100% N/A N/A N/A N/A N/A N/A N/A N/A

150 % of 150% N/A N/A N/A N/A N/A N/A N/A N/A
rated flow

____________________________________

_________________________________ Consultant Signature


Contractor Signature
GENERAL HEADQUARTERS (QAF) ‫القيادة العامة للقوات المسلحة القطرية‬
CENTRAL FIREFIGHTING UNIT ‫وحــــــدة اإلطـفـائيــــة المـركزيـــــــــة‬
DOHA – QATAR ‫الدوحة – قطر‬
TELEPHONE: +97440432170 97440432170: ‫تليفــــون‬+
FAX : +97440432179 97440432179 : ‫فاكــــــس‬+

FIRE PUMP PERFORMANCE.

STANDBY FIRE PUMP

ELECTRIC FIRE PUMP


Pump N/A Serial N/A Design Actual
Model Number Pressure Pressure
PSI (m) (PSI
(m)
Rated Capacity Speed Capacity Volts Amps Suction Discharge Suction Discharge
(RPM) (GPM)
Shut off 0% N/A N/A N/A N/A N/A N/A N/A N/A
Rated 100% N/A N/A N/A N/A N/A N/A N/A N/A

150 % of rated 150% N/A N/A N/A N/A N/A N/A N/A N/A
flow

Pump 10 X 8 M Serial Design Pressure PSI Actual


Model FP-C185763-01 Number (m) Pressure
(PSI (m)
Rated Capacity Speed Capacity (GPM) Suction Discharge Suction Discharge
(RPM)
Shut 0% 2100 0 +8 169 +6 184
off
Rated 100% 2705 2500 +8 154 +4 156

150 % 150% 2050 3750 +8 127 +2 127


of rated
flow

__________________________ ________________________________
Contractor Signature Consultant Signature
GENERAL HEADQUARTERS (QAF) ‫القيادة العامة للقوات المسلحة القطرية‬
CENTRAL FIREFIGHTING UNIT ‫وحــــــدة اإلطـفـائيــــة المـركزيـــــــــة‬
DOHA – QATAR ‫الدوحة – قطر‬
TELEPHONE: +97440432170 97440432170: ‫تليفــــون‬+
FAX : +97440432179 97440432179 : ‫فاكــــــس‬+

FIREPUMP FIELD ACCEPTANCE TEST

FIRE PUMP ALIGNMENT REPORT

Electrical Fire Pump


Reference Tolerance Pump Side Driver Side Figure/ Illustration
Vertical Parallel –Fig -1 +.30 +.3 +2.3

Vertical Parallel –Fig -2 +.11 +.11 +.28

Horizontal Parallel –Fig -1 -0.7 +0.7 +2.3

Horizontal Parallel –Fig -2 +0.25 +.25 +2.8

Diesel Fire Pump


Horizontal Parallel Pump Side Driver Side Figure/ Illustration
offset
Vertical Parallel offset 60 60 60+1
Vertical Parallel –Fig -1 60 60 60+1

Vertical Parallel –Fig -2 57.5 60 60+1

Horizontal Parallel –Fig -1 57.5 57.5 58+1

Horizontal Parallel -Fig -2 57.5 57.5 58+1

CERTIFICATION
The system as specified above has been installed and tested in accordance with latest edition of NFPA, QCDDFSS and QCDD approved drawings

Contractor (QCDD Certificate No. / ID No. / Mobile No.)


(Signature over Printed Name with Stamp)

CERTIFICATION
The undersigned accepted the testing report for the system as specified herein.

Consultant (UPDA No. / ID No. / Mobile No.)


(Signature over Printed Name with Stamp)

Page6of6