Panduan Dry contact untuk ZXDU68 W301-BBU V9200 Smartfren LTE Project

Dry Contact for Power Monitoring


Solution without EISU at
ZXDU68 W301-BBU V9200
Panduan Dry contact untuk ZXDU68 W301-BBU V9200 Smartfren LTE Project

Daftar isi
1. POWER MONITORING DENGAN DRY CONTACT...................................................................... 3
1.1 Landasan informasi.................................................................................................. 3
1.2 Tabel alarm dan koneksi.......................................................................................... 3
1.3 Material list.............................................................................................................. 4
2. HARDWARE INSTALLATION................................................................................................ 6
2.1 Ethernet cable installation at VEMc1 panel.............................................................6
2.2 Alarm PLN failure..................................................................................................... 6
2.3 Alarm Input SPD PLN Failure.................................................................................... 6
2.4 Fuel tank empty....................................................................................................... 7
2.5 Genset ON................................................................................................................ 7
2.6 Alarm Rectifier Module............................................................................................ 7
2.7 Alarm DC low voltage alarm.................................................................................... 8
2.8 Alarm Door Open..................................................................................................... 8
2.9 Alarm Battery Stolen................................................................................................ 8
3. SETTING ALARM CSU VIA LAPTOP..................................................................................... 9

This material is proprietary to PT SMART TELECOM and is strictly confidential. No information contained herein
may be copied, translated, transcribed or duplicated for any commercial purposes or disclosed to third parties in
any form without the prior written consent of PT SMART TELECOM.

[POC Test] |2 / 16
Panduan Dry contact untuk ZXDU68 W301-BBU V9200 Smartfren LTE Project

1. Power monitoring dengan Dry contact

1.1 Landasan informasi


Untuk memonitor alarm DC power system ZTE ZXDU68 W301 melalui dry contact untuk BBU V9200

Pembagian alarm dry contact sbb :

1. 4 alarm (alarm 1-4) akan menghubungkan koneksi dari VEMC1 port RJ45#1 (VEMc1&EAM1)

2. 4 alarm (alarm 5-8) akan menghubungkan koneksi dari VEMC1 port RJ45#2 (VEMc1&EAM2)

3. Tabel dibawah untuk pembagian koneksi dan alarm dry contactnya pada ZXDU68 W301 melalui VEMc1&EAM1 and
VEM1&EAM2

1.2 Tabel alarm dan koneksi

NO Alarm Source VEMC1koneksi SIB koneksi Jalur Koneksi Alarm Code di Nodeb

VEMc1&EAM1(pin AC power-cut alarm (198092207)


1&2) X2 (Pin 7&8)
1 PLN Failure Dry contact di UIB Dry contact number : 0
putih/orange & NC-1 Koneksi VEMc1&EAM1 (pin 1&2) ke UIB X2 (Pin 7&8/DO1)
orange Alarm Status : Alarm when open (1)

Arrester failure (198092560)


VEMc1&EAM1(pin X1 (pin5&6) Koneksi VEMc1&EAM1(pin 3&6) ke UIB X1 (pin 5&6/DO6)
2 Input SPD PLN Failure Dry contact di UIB 3&6) Dry contact number : 1
putih/hijau & hijau NC-6
Alarm Status : Alarm when open (1)

Fuel Tank Empty (198092550)


VEMc1&EAM1(pin Koneksi VEMc1&EAM1(pin 4&5) ke ATS FGS
3 Fuel Tank Alarm ATS FGS 4&5) / Dry contact number : 2
biru & putih/biru *Jika tidak ada kontaktor di standby kabelnya dan di loop
Alarm Status : Alarm when open (1)

VEMc1&EAM1(pin Genset ON (198092567)


Diesel Generator Set 7&8) Koneksi VEMc1&EAM1(pin 7&8) ke ATS FGS
4 ATS FGS / Dry contact number : 3
On putih/coklat & *Jika tidak ada kontaktor di standby kabelnya dan di loop
coklat Alarm Status : Alarm when open (1)

VEMc1&EAM2(pin Rectifier Module Alarm (198092208)


Rectifier Module & 1&2) X2 (Pin 5&6)
5 Dry contact di UIB Koneksi VEMc1&EAM2(pin 1&2) ke UIB X2 (Pin 5&6/DO2) Dry contact number : 4
Arrester Rectifier putih/orange & NC-2
orang Alarm Status : Alarm when open (1)

Battery Low Voltage Alarm (198092259)


VEMc1&EAM2(pin X2 (Pin 3&4)
6 DC Low Voltage Dry contact diUSIB 3&6) Koneksi VEMc1&EAM2(pin 3&6) ke UIB X2 (Pin 3&4/DO3) Dry contact number : 5
putih/hijau & hijau NC-3
Alarm Status : Alarm when open (1)

Door Control Alarm (198092044)


VEMc1&EAM2(pin X2 (Pin 1&2)
7 Door Open Dry contact di UIB 4&5) Koneksi VEMc1&EAM2(pin 4&5) ke UIB X2 (Pin 1&2/DO4) Dry contact number : 6
biru & putih/biru NC-4
Alarm Status : Alarm when open (1)

VEMc1&EAM2(pin Battery Stolen (198092555)


Battery Stolen/BMS 7&8) X1 (Pin 7&8 ) Koneksi VEMc1&EAM2(pin 7&8) ke UIB X1 (pin 7&8/DO5)
8 Dry contact di UIB Dry contact number : 7
alarm putih/coklat & NC-5
coklat Alarm Status : Alarm when open (1)

This material is proprietary to PT SMART TELECOM and is strictly confidential. No information contained herein
may be copied, translated, transcribed or duplicated for any commercial purposes or disclosed to third parties in
any form without the prior written consent of PT SMART TELECOM.

[POC Test] |3 / 16
Panduan Dry contact untuk ZXDU68 W301-BBU V9200 Smartfren LTE Project

1.3 Material list


No Materials/Cable Name QTY Remark

1 8-core shielded paired cable 20 M For VEMc1&EAM1 and VEMc1&EAM2

2 8P8C Straight shield crimp plug | 5-569552-3 2 PCS Connector

3 VEMc1 Panel 1 KIT V9200

4 SIB/SIU board 1 PCS Interface board power system

8-core shielded paired cable VEMc1 Panel

No Wire Color Signal at VEMc1&EAM1 Signal at VEMc1&EAM2


1 White/Orange Bidirectional dry contact signal1 Bidirectional input contact signal 5
2 Orange Ground of Bidirectional dry contact signal1 Ground of input dry contact signal 5
3 White/Green Bidirectional dry contact signal2 Bidirectional input contact signal 6
4 Blue Ground of Bidirectional dry contact signal3 Ground of input dry contact signal 7
5 White/Blue Bidirectional dry contact signal 3 Bidirectional input contact signal 7
6 Green Ground of Bidirectional dry contact signal 2 Ground of input dry contact signal 6
7 White/Brown Bidirectional dry contact signal 4 Bidirectional input contact signal 8
8 Brown Ground of Bidirectional dry contact signal 4 Ground of input dry contact signal 8

This material is proprietary to PT SMART TELECOM and is strictly confidential. No information contained herein
may be copied, translated, transcribed or duplicated for any commercial purposes or disclosed to third parties in
any form without the prior written consent of PT SMART TELECOM.

[POC Test] |4 / 16
Panduan Dry contact untuk ZXDU68 W301-BBU V9200 Smartfren LTE Project

X1 : Output Relay 5,6,7,8 X2 : Output Relay 1,2,3,4


Pin 7,8--> NO-5 di CSU A5 Pin 7,8--> NO-1 di CSU A1
Pin 5,6--> NO-6 di CSU A6 Pin 5,6--> NO-2 di CSU A2
Pin 3,4--> NO-7 di CSU A7 Pin 3,4--> NO-3 di CSU A3
Pin 1,2--> NO-8 di CSU A8 Pin 1,2--> NO-4 di CSU A4

No Alarm Name Source UIB Pin VEMc1 Panel EAM pin


ACPDB/Rectifier X2 (Pin 7&8)
1 PLN Failure EAM1 Pin 1&2
(UIB) NC-1
ACPDB/Rectifier X1 (Pin 5&6)
2 Input SPD PLN Failure EAM1 Pin 3&6
(UIB) NC-6

3 Fuel Tank Alarm ATS FGS / EAM1 Pin 4&5

4 Diesel Generator Set On ATS FGS / EAM1 Pin 7&8

X2 (Pin 5&6)
5 Rectifier Module & Arrester Rectifier Rectifier (UIB) EAM2 Pin 1&2
NC-2
X2 (Pin 3&4)
6 DC Low Voltage Rectifier (UIB) EAM2 Pin 3&6
NC-3
X2 (Pin 1&2)
7 Door Open Rectifier (UIB) EAM2 Pin 4&5
NC-4
X1 (Pin 7&8 )
8 Battery Stolen/BMS alarm Rectifier (UIB) EAM2 Pin 7&8
NC-5

This material is proprietary to PT SMART TELECOM and is strictly confidential. No information contained herein
may be copied, translated, transcribed or duplicated for any commercial purposes or disclosed to third parties in
any form without the prior written consent of PT SMART TELECOM.

[POC Test] |5 / 16
Panduan Dry contact untuk ZXDU68 W301-BBU V9200 Smartfren LTE Project

2. Hardware installation

2.1 Ethernet cable installation at VEMc1 panel


Install 2 Ethernet cable at VEMc1 card for EAM1 and EAM2

2.2 Alarm PLN failure

 Koneksi dari VEMc1&EAM1(pin 1&2) ke UIB X2 (Pin 7&8 / DO1)

2.3 Alarm Input SPD PLN Failure

 Koneksi VEMc1&EAM1 (pin 3&6) ke UIB X1 (Pin 5&6 / DO6)

This material is proprietary to PT SMART TELECOM and is strictly confidential. No information contained herein
may be copied, translated, transcribed or duplicated for any commercial purposes or disclosed to third parties in
any form without the prior written consent of PT SMART TELECOM.

[POC Test] |6 / 16
Panduan Dry contact untuk ZXDU68 W301-BBU V9200 Smartfren LTE Project

2.4 Fuel tank empty

 Koneksi VEMc1&EAM1(pin 4&5) ke ATS FGS

*Jika tidak ada Genarator di standby kabelnya dan di loop di dalam Tray UIB

2.5 Genset ON

 Koneksi VEMc1&EAM1 (pin 7&8) ke ATS FGS

*Jika tidak ada Genarator di standby kabelnya dan di loop di dalam Tray UIB

2.6 Alarm Rectifier Module

 Koneksi VEMc1&EAM2(pin 1&2) ke UIB X2 (Pin 5&6 / DO2)

This material is proprietary to PT SMART TELECOM and is strictly confidential. No information contained herein
may be copied, translated, transcribed or duplicated for any commercial purposes or disclosed to third parties in
any form without the prior written consent of PT SMART TELECOM.

[POC Test] |7 / 16
Panduan Dry contact untuk ZXDU68 W301-BBU V9200 Smartfren LTE Project

2.7 Alarm DC low voltage

 Koneksi VEMc1&EAM2(pin 3&6) ke UIB X2 (Pin 3&4 / DO3)

2.8 Alarm Door Open

 Koneksi VEMc1&EAM2(pin 4&5) ke UIB X2 (Pin 1&2 / DO4)

2.9 Alarm Battery Stolen

 Koneksi VEMc1&EAM2(pin 7&8) ke UIB X1 (pin 7&8 / DO5)

This material is proprietary to PT SMART TELECOM and is strictly confidential. No information contained herein
may be copied, translated, transcribed or duplicated for any commercial purposes or disclosed to third parties in
any form without the prior written consent of PT SMART TELECOM.

[POC Test] |8 / 16
Panduan Dry contact untuk ZXDU68 W301-BBU V9200 Smartfren LTE Project

3. Conection Relay Input

3.1 PLN_Failure

* Koneksi dari UIB X3 pin 1&3 (IRLY1 & 5V) Ke Terminal PhaseF di ACPDB mengunakan kabel isi
2 (BLue Black)

3.2 InputSPDFailure

* Koneksi dari UIB X3 pin 2&3 (IRLY2 & 5V) Ke Terminal Arrester F di ACPDB
mengunakan kabel isi 2 (BLue Black)

3.3 BatteryStolen

*Koneksi dari UIB X3 Pin 4 (IRLY4) kemudian Konek Ke DO1, lilit Battery Bank1 , kemudian konek
ke DO2 ,lilit Battery Bank2,kemudian konek ke DO3, lilit batre Bank3 kemudian konek ke UIB X3
pin 6 (5v). Menggunakan Kable isi 1

This material is proprietary to PT SMART TELECOM and is strictly confidential. No information contained herein
may be copied, translated, transcribed or duplicated for any commercial purposes or disclosed to third parties in
any form without the prior written consent of PT SMART TELECOM.

[POC Test] |9 / 16
Panduan Dry contact untuk ZXDU68 W301-BBU V9200 Smartfren LTE Project

4. Setting Alarm CSU via laptop


Karena menggunakan relay output, untuk alarm yang tidak dipakai dari penjelasan diatas harus di set NULL alarm alokasi
relaynya dan alokasi yang dipakai juga harus di set sesuai pengaturan koneksi di atas.

Dikarenakan default CSU sudah di set alokasi relaynya, untuk memudahkan perubahan harus menggunakan laptop yang di
hubungkan ke CSU

Step

1. Dari CSU pilih menu local set, akan tampil beberapa sub menu
2. Local menuNet Conn. SetWiredConIP Allocation ModeGanti ke StaticEnter kemudian“ESC” dan pilih“YES”

3. Set IP laptop

IP Address : 192.168.1.3

Subnet Mask : 255.255.255.0

Default Gateway : 192.168.1.1

Konek kabel LAN dari laptop ke CSU

This material is proprietary to PT SMART TELECOM and is strictly confidential. No information contained herein
may be copied, translated, transcribed or duplicated for any commercial purposes or disclosed to third parties in
any form without the prior written consent of PT SMART TELECOM.

[POC Test] |10 / 16


Panduan Dry contact untuk ZXDU68 W301-BBU V9200 Smartfren LTE Project

4. Via browser, masukan IP CSU 192.168.1.2

Kemudian Masukan USER : Superman , Pasword : Supermanfly!

5. Setting Time (UTC+07:00)Bangkok

This material is proprietary to PT SMART TELECOM and is strictly confidential. No information contained herein
may be copied, translated, transcribed or duplicated for any commercial purposes or disclosed to third parties in
any form without the prior written consent of PT SMART TELECOM.

[POC Test] |11 / 16


Panduan Dry contact untuk ZXDU68 W301-BBU V9200 Smartfren LTE Project

6.Masuk ke menu di kotak merah dibawah untuk mengatur input relay

Chanel Name : UIB_X3_DI1


SID :CSU
Signal : Input Relay Alarm (1)
Alarm Name : PLN_Failure

Chanel Name : UIB_X3_DI2


1.SID :CSU
2.Signal : Input Relay Alarm (2)
3.Alarm Name : InputSPDFailure

This material is proprietary to PT SMART TELECOM and is strictly confidential. No information contained herein
may be copied, translated, transcribed or duplicated for any commercial purposes or disclosed to third parties in
any form without the prior written consent of PT SMART TELECOM.

[POC Test] |12 / 16


Panduan Dry contact untuk ZXDU68 W301-BBU V9200 Smartfren LTE Project

Chanel Name : UIB_X3_DI3


1.SID :CSU
2.Signal : Input Relay Alarm (3)
3.Alarm Name : BatteryStolen

Chanel Name : UIB_X14_V3/DI7


1.SID :CSU
2.Signal : Input Relay Alarm (7)
3.Alarm Name : TEC

This material is proprietary to PT SMART TELECOM and is strictly confidential. No information contained herein
may be copied, translated, transcribed or duplicated for any commercial purposes or disclosed to third parties in
any form without the prior written consent of PT SMART TELECOM.

[POC Test] |13 / 16


Panduan Dry contact untuk ZXDU68 W301-BBU V9200 Smartfren LTE Project

7.Masuk ke menu di kotak merah dibawah untuk mengatur output relay

8.Set Alarm level di bawah ini dan untuk alarm lain yang harus di set NULL

Parameter Name Parameter Value Remark

PLN_Failure DO1 di sub menu System

InputSPDFailure DO6 di sub menu System

BatteryStolen DO5 di sub menu System

AC Power OFF DO1 di sub menu AC

AC Voltage Low DO1 di sub menu AC

AC Phase Lack DO1 di sub menu AC

AC SPD Abnormal DO2 di sub menu AC

SMR Fan Fault DO2 di sub menu SMR

SMR Communication Fail DO2 di sub menu SMR

Battery Voltage Low DO3 di sub menu Battery

Battery Loop Broken DO5 di sub menu Battery

DC Voltage Low DO3 di sub menu Load

DC SPD Abnormal DO2 di sub menu Load

Door Alarm DO4 di sub menu Environment

SET SEMUA ALARM Selain dari table di atas untuk output relaynya : NULL

This material is proprietary to PT SMART TELECOM and is strictly confidential. No information contained herein
may be copied, translated, transcribed or duplicated for any commercial purposes or disclosed to third parties in
any form without the prior written consent of PT SMART TELECOM.

[POC Test] |14 / 16


Panduan Dry contact untuk ZXDU68 W301-BBU V9200 Smartfren LTE Project

9.Rubah DO output relay statusnya menjadi close dari DO1~DO8

10. Setting Battery Temperatur Invalid

This material is proprietary to PT SMART TELECOM and is strictly confidential. No information contained herein
may be copied, translated, transcribed or duplicated for any commercial purposes or disclosed to third parties in
any form without the prior written consent of PT SMART TELECOM.

[POC Test] |15 / 16


Panduan Dry contact untuk ZXDU68 W301-BBU V9200 Smartfren LTE Project

Wiring Dry Contact for Rectifier ZXDU68 W301

This material is proprietary to PT SMART TELECOM and is strictly confidential. No information contained herein
may be copied, translated, transcribed or duplicated for any commercial purposes or disclosed to third parties in
any form without the prior written consent of PT SMART TELECOM.

[POC Test] |16 / 16

You might also like