Profibus DP Board B-62924EN - 04
Profibus DP Board B-62924EN - 04
Profibus DP Board B-62924EN - 04
B-62924EN/04
Ȧ No part of this manual may be reproduced in any form.
Ȧ All specifications and designs are subject to change without notice.
SAFETY PRECAUTIONS
This section describes the safety precautions related to the use of
CNC units, to ensure safe operation of machines fitted with FANUC
CNC units. Read this section carefully before attempting to use any
funcction described in this manaul.
Users ahould also read the relevant descriptions in the Operator’s
Manual to become fully familiar with the functions to be used.
CONTENTS
1.1DEFINITION OF WARNING, CAUTION, AND NOTE............s-2
1.2GENERAL WARNINGS AND NOTES ......................................s-3
s-1
SAFETY PRECAUTIONS B-63734EN/01
This manual includes safety precautions for protecting the user and
preventing damage to the machine. Precautions are classified into
Warning and Caution according to their bearing on safety. Also,
supplementary information is described as a Note. Read the Warning,
Caution, and Note thoroughly before attempting to use the machine.
WARNING
Applied when there is a danger of the user being
injured or when there is a damage of both the user
being injured and the equipment being damaged if
the approved procedure is not observed.
CAUTION
Applied when there is a danger of the equipment
being damaged, if the approved procedure is not
observed.
NOTE
The Note is used to indicate supplementary
information other than Warning and Caution.
s-2
B-63734EN/01 SAFETY PRECAUTIONS
WARNING
1 Before operating the machine, thoroughly check the
entered data. Operating the machine with incorrect
data may result in the machine behaving
unexpectedly, possibly causing damage to the
workpiece and/or machine itself, or injury to the user.
2 Never attempt to perform a production run, such as
actually machining a workpiece, without first
checking the operation of the machine. Before
starting the machine for a production run, ensure that
the program command values, offsets, current
position, external signals, and other settings are
suitable for the operation to be performed. Also
check that the machine operates correctly by
performing a trial run using, for example, the single
block, feedrate override, or machine lock function or
by operating the machine with neither a tool nor
workpiece mounted.
3 Ensure that the specified feedrate is appropriate for
the intended operation. Generally, for each machine,
there is a maximum allowable feedrate.
The appropriate feedrate varies with the intended
operation. Refer to the manual provided with the
machine to determine the maximum allowable
feedrate. If a machine is run at other than the correct
speed, it may behave unexpectedly, possibly
causing damage to the workpiece and/or machine
itself, or injury to the user.
4 When using a tool compensation function,
thoroughly check the direction and amount of
compensation. Operating the machine with
incorrectly specified data may result in the machine
behaving unexpectedly, possibly causing damage to
the workpiece and/or machine itself, or injury to the
user.
5 The parameters for the CNC and PMC are factory-
set. Usually, there is not need to change them.
When, however, there is not alternative other than to
change a parameter, ensure that you fully
understand the function of the parameter before
making any change. Failure to set a parameter
correctly may result in the machine behaving
unexpectedly, possibly causing damage to the
workpiece and/or machine itself, or injury to the user.
s-3
SAFETY PRECAUTIONS B-63734EN/01
CAUTION
1 Immediately after switching on the power, do not
touch any of the keys on the MDI panel until the
position display or alarm screen appears on the CNC
unit.
Some of the keys on the MDI panel are dedicated to
maintenance or other special operations. Pressing
any of these keys may place the CNC unit in other
than its normal state. Starting the machine in this
state may cause it to behave unexpectedly.
2 The operator's manual and programming manual
supplied with a CNC unit provide an overall
description of the machine's functions, including any
optional functions. Note that the optional functions
will vary from one machine model to another.
Therefore, some functions described in the manuals
may not actually be available for a particular model.
Check the specification of the machine if in doubt.
3 Some functions may have been implemented at the
request of the machine-tool builder. When using
such functions, refer to the manual supplied by the
machine-tool builder for details of their use and any
related cautions. Refer to the following two
examples.
<1> Some machines have a tool replacement
device that operates when a tool feature is
executed. When the user is working near the
device, he or she may touch it. Execute tool
features in a place sufficiently away from the
tool replacement device.
<2> Many auxiliary features cause machine
operation such as rotation of the spindle.
Understand the operations of auxiliary features
before using them.
NOTE
1 Command programs, parameters, and variables are
stored in nonvolatile memory in the CNC unit.
Usually, they are retained even if the power is turned
off. Such data may be delated inadvertently,
however, or it may prove necessary to delete all data
from nonvolatile memory as part of error recovery.
To guard against the occurrence of the above, and
assure quick restoration of deleted data, backup all
vital data, and keep the backup copy in a safe place.
2 PROFIBUS-DP cannot be used with DeviceNet.
s-4
B-62924EN/04 TABLE OF CONTENTS
TABLE OF CONTENTS
I. GENERAL
1 GENERAL ..............................................................................................3
1.1 ORGANIZATION............................................................................................4
1.2 APPLICABLE MODELS.................................................................................5
2 OVERVIEW OF PROFIBUS-DP FUNCTIONS .......................................6
2.1 SOFTWARE FOR PROFIBUS-DP FUNCTIONS...........................................7
2.2 MASTER FUNCTIONS ..................................................................................8
2.3 SLAVE FUNCTIONS .....................................................................................9
II. OPERATION
1 16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C ..............................13
1.1 OVERVIEW .................................................................................................14
1.2 MASTER FUNCTION SETTING..................................................................15
1.2.1 Bus Parameter Setting ........................................................................................... 18
1.2.2 Slave Parameter Setting......................................................................................... 23
1.2.3 Setting for Address Assignment ............................................................................ 27
1.2.4 Setting for Operation mode ................................................................................... 31
1.2.5 Updating DI/DO Data for the Master Function..................................................... 33
1.3 SLAVE FUNCTION SETTING .....................................................................37
1.3.1 Status Register ....................................................................................................... 44
1.3.2 Updating DI/DO Data for the Slave Function ....................................................... 45
1.4 SETTING THE SLAVE PARAMETERS
FOR USING A SLAVE STATION MANUFACTURED BY FANUC ..............46
1.5 GSD FILE OF THE FANUC CNCS ..............................................................51
2 Series 15i-A.........................................................................................59
2.1 OVERVIEW .................................................................................................60
2.2 MASTER FUNCTION SETTING..................................................................61
2.2.1 Bus Parameter Setting ........................................................................................... 62
2.2.2 Slave Parameter Setting......................................................................................... 66
2.2.3 Setting for Address Assignment ............................................................................ 71
2.3 SLAVE FUNCTION SETTING .....................................................................75
2.3.1 Status Register ....................................................................................................... 79
c-1
TABLE OF CONTENTS B-62924EN/04
III. CONNECTION
1 CONNECTING THE PROFIBUS FUNCTIONS...................................107
1.1 PROFIBUS CONNECTION .......................................................................108
1.2 PROFIBUS CABLE PARAMETERS ..........................................................109
1.3 CABLE LENGTH AND TRANSFER RATE ................................................110
1.4 CONNECTOR............................................................................................111
1.5 CABLE CONNECTION ..............................................................................112
1.6 TERMINATING RESISTOR.......................................................................113
1.7 CABLE SHIELDING...................................................................................114
2 PROFIBUS FOR THE Series 16/18-C ...............................................115
2.1 CONFIGURATION.....................................................................................116
2.2 INSTALLATION .........................................................................................117
2.2.1 Environmental Conditions................................................................................... 117
2.2.2 Cable Installation................................................................................................. 117
2.2.3 PROFIBUS Board Connector Layout ................................................................. 119
2.3 CONNECTION DIAGRAM .........................................................................120
3 PROFIBUS FOR THE LCD-MOUNTED TYPE Series 16i/18i/21i .....121
3.1 CONFIGURATION.....................................................................................122
3.2 INSTALLATION .........................................................................................125
3.2.1 Environmental Conditions................................................................................... 125
c-2
B-62924EN/04 TABLE OF CONTENTS
IV. MAINTENANCE
1 PROFIBUS FOR THE Series 16/18-C ...............................................149
1.1 COMPONENT LAYOUT ............................................................................150
1.2 LED INDICATORS AND THEIR MEANINGS ............................................151
1.2.1 DP-Master Function LED Indicators................................................................... 151
1.2.2 DP-Slave Function LED Indicators ..................................................................... 152
c-3
TABLE OF CONTENTS B-62924EN/04
SUPPLEMENT
A SETTING WHEN EDITION 07 OR EARLIER OF SERIES 6557
IS USED .............................................................................................167
A.1 MASTER FUNCTION SETTING................................................................168
A.1.1 Bus Parameter Setting ......................................................................................... 170
A.1.2 Slave Parameter Setting....................................................................................... 175
A.1.3 Setting for Address Assignment .......................................................................... 179
A.2 SLAVE FUNCTION SETTING ...................................................................183
A.2.1 Status Register ..................................................................................................... 187
A.3 SETTING THE SLAVE PARAMETERS
FOR USING A SLAVE STATION MANUFACTURED BY FANUC ............188
A.4 GSD FILE OF THE FANUC CNCS ............................................................189
B SETTING WHEN SERIES 6556 IS USED ..........................................197
B.1 MASTER FUNCTION SETTING................................................................198
B.1.1 Bus Parameter Setting ......................................................................................... 200
B.1.2 Slave Parameter Setting....................................................................................... 202
B.1.3 Setting for Address Assignment .......................................................................... 204
B.2 SLAVE FUNCTION SETTING ...................................................................207
B.3 SETTING THE SLAVE PARAMETERS
FOR USING A SLAVE STATION MANUFACTURED BY FANUC ............208
B.4 GSD FILE OF THE FANUC CNCS ............................................................209
C SETTING USING A PERSONAL COMPUTER ..................................210
C.1 SETTING USING DP-Configurator MANUFACTURED BY Softing ...........211
c-4
I. GENERAL
B-62924EN/02 GENERAL 1.GENERAL
1 GENERAL
This chapter explains the organization of this manual and applied
models.
-3-
1.GENERAL GENERAL B-62924EN/02
1.1 ORGANIZATION
-4-
B-62924EN/02 GENERAL 1.GENERAL
-5-
2.OVERVIEW OF PROFIBUS-DP FUNCTIONS GENERAL B-62924EN/02
2 OVERVIEW OF PROFIBUS-DP
FUNCTIONS
This chapter explains overview of FANUC PROFIBUS-DP functions.
-6-
B-62924EN/02 GENERAL 2.OVERVIEW OF PROFIBUS-DP FUNCTIONS
Table 2-1 lists each model and the series of each software component
that is applicable to the model.
In this manual, the software component required for using each
PROFIBUS-DP function is expressed as follows:
- Application software for PROFIBUS-DP function
→ CONTROL SOFTWARE
- Control software for PROFIBUS-DP master function
→ MASTER SOFTWARE
- Control software for PROFIBUS-DP slave function
→ SLAVE SOFTWARE
Table 2-1 Each Model and Its Corresponding Series of Each Software Component
Model name Software name Applicable series
LCD-mounted type Series 16i/18i/21i-A/B MASTER SOFTWARE Series 6552
Stand-alone type Series 16i/18i/21i-A SLAVE SOFTWARE Series 6553
Power Mate i-D/H CONTROL SOFTWARE Series 6557
MASTER SOFTWARE Series 6552
Series 15i-A SLAVE SOFTWARE Series 6553
CONTROL SOFTWARE None
MASTER SOFTWARE Series 6554
Series 16/18-C SLAVE SOFTWARE Series 6551
CONTROL SOFTWARE Series 6557
SLAVE SOFTWARE Series 6551
Power Mate-D/H
CONTROL SOFTWARE None
-7-
2.OVERVIEW OF PROFIBUS-DP FUNCTIONS GENERAL B-62924EN/02
SUPPLEMENT- SUPPLEMENT-
Reference item in this manual II-1.2 II-2.2
A.1 B.1
-8-
B-62924EN/02 GENERAL 2.OVERVIEW OF PROFIBUS-DP FUNCTIONS
station numbers
244 bytes
Maximum DI/DO data size 32/32 bytes 32/32 bytes
(Total of DI/DO)
Approval given by the
PROFIBUS certification ¡ ¡ -
organization
Reference item in this manual II-1.3 SUPPLEMENT-A.2 SUPPLEMENT-B.2
0 to 125 1 to 125
numbers
Maximum DI/DO data size 32/32 bytes 32/32 bytes
Approval given by the
PROFIBUS certification ¡ ¡
organization
Reference item in this manual II-2.3 II-3.1
NOTE
When the model is the Power Mate i-D/H and the DPL/MDI and DPL/MDI operation
package are used, the specifications are those of Edition 07 or earlier of series
6557.
For details of operation in this case, see Section 1.3, "Slave Function Setting" in
Part II, "OPERATION."
-9-
II. OPERATION
B-62924EN/04 OPERATION 1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C
NOTE
PROFIBUS-DP cannot be used with DeviceNet.
- 13 -
1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C OPERATION B-62924EN/04
1.1 OVERVIEW
- 14 -
B-62924EN/04 OPERATION 1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C
To use the master function, bus parameters and slave parameters must
be set, and addresses must be assigned.
The bus parameters are referenced by the network, and the slave
parameters are set for each slave. In address assignment, PMC
addresses used by the DP-Master to transfer DI/DO signals to and
from each DP-Slave are set.
The methods of setting the parameters are described below.
NOTE
To set the bus parameters and slave parameters,
you can also use DP-Configurator (tool running on a
PC) manufactured by Softing. For details of this
setting, see Section C.1, "Setting Using DP-
Configurator Manufactured BY Softing," in
"SUPPLEMENT."
Procedure (CRT/MDI)
(1) Press function key <SYSTEM>, then press soft key [PMC] to
switch to the PMC screen.
Screen 1-1
- 15 -
1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C OPERATION B-62924EN/04
Screen 1-2
- 16 -
B-62924EN/04 OPERATION 1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C
NOTE
When Edition 08 of series 6557 of CONTROL
SOFTWARE is used, pay careful attention to the
following points:
- The setting error messages listed in Table 1-1 are
displayed at the lower left of Screen 1-8 (mode
screen).
- The message "SET I/O SIZE[MAS + SLV <=
256],POWER OFF" may be displayed at the lower
left of Screen 1-8 (mode screen).
This message indicates that the total of the DI/DO
sizes set for the master and slave functions
exceeds 256 bytes when these functions are used
together in this node. In this case, set the DI/DO
sizes again so that the total does not exceed 256
bytes, and turn the power off, then on again.
- 17 -
1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C OPERATION B-62924EN/04
Pressing soft key [BUS] on Screen 1-2 displays Screen 1-3 to enable
bus parameter setting. The bus parameters consist of two pages. Use
the page keys to switch between the pages.
Screen 1-3
- 18 -
B-62924EN/04 OPERATION 1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C
Soft key [INIT] on Screen 1-3 initializes the bus parameters to the
standard values used when the transfer rate is 12 Mbps.
CAUTION
To change the transfer rate from 12 Mbps to a
different value, set the bus parameters again
according to Table 1-3, "Bus Parameter Settings
Corresponding to Each Transfer Rate" in this
section.
Screen 1-4
- 19 -
1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C OPERATION B-62924EN/04
Table 1-2 summarizes the bus parameters. Table 1-3 lists the bus
parameter values to be set for each transfer rate. For details, refer to
the following documents issued by PROFIBUS Nutzerorganisation
e.V.:
¡ PROFIBUS STANDARD DIN 19 245 Part 1
This document describes data transfer, access methods, protocols,
and interfacing with the application layer.
¡ Draft Standard PROFIBUS-DP DIN 19 245 Part 3
This document describes an abstract model of the PROFIBUS-
DP communication function, and so forth.
- 20 -
B-62924EN/04 OPERATION 1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C
- 21 -
1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C OPERATION B-62924EN/04
NOTE
For multiple master communication, satisfy the
following conditions:
- The value set for 1:FDL ADD for a master station is
not used as another master station number.
- The same values are set for bus parameters 2 to 11
for all master stations.
- When a larger value is set for T SET, T SL is larger
than T ID1.
(T ID1 = 33 + 2 + 2 × T SET + T QUI)
- 22 -
B-62924EN/04 OPERATION 1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C
CAUTION
When setting slave parameter data, pay careful
attention to the following points:
1 The slave parameters are available for 126 stations.
However, set the slave parameters for no more than
32 DP-Slaves for actual communication.
2 When using DP-Slaves provided by other
manufacturers, set the slave parameters according
to the GSD file attached to each DP-Slave.
3 When setting the slave parameters, carefully check
the slave number of each DP-Slave to be set.
Screen 1-5
- 23 -
1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C OPERATION B-62924EN/04
pressing soft key [DETAIL] when the cursor is placed at the item of
15 CONFIG DATA.) Detailed data as long as the number of bytes
specified in each of these items can be set.
NOTE
Before a DP-Slave manufactured by FANUC can be
connected, data dependent on the FANUC DP-Slave
must be set in the slave parameters. Usually, soft
key [INIT] can be used for initialization to enable a
FANUC DP-Slave to be connected. In 15 CONFIG
DATA, however, variable data dependent on the size
of DI/DO data exchanged with the DP-Slave must be
set. So, when setting 15 CONFIG DATA, see
Section 1.4, "Setting the Slave Parameters for Using
a Slave Station Manufactured by FANUC."
Screen 1-6
- 24 -
B-62924EN/04 OPERATION 1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C
Table 1-4 summarizes the slave parameters. For details, refer to the
following documents issued by PROFIBUS Nutzerorganisation e.V.:
¡ PROFIBUS STANDARD DIN 19 245 Part 1
This document describes data transfer, access methods, protocols,
and interfacing with the application layer.
¡ Draft Standard PROFIBUS-DP DIN 19 245 Part 3
This document describes an abstract model of the PROFIBUS-
DP communication function, and so forth.
- 25 -
1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C OPERATION B-62924EN/04
CAUTION
Set values for parameters USER PRM DATA,
CONFIG DATA, and SLAVE USER DATA so that
the total of the three parameter lengths does not
exceed 207.
- 26 -
B-62924EN/04 OPERATION 1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C
Screen 1-7
CAUTION
When assigning addresses, pay careful attention to the
following points:
1 Assign addresses to all DP-Slaves that are set to
ENABLE in the slave parameters.
2 Be careful not to assign duplicate addresses to a
DP-Slave.
3 Ensure that a specified DI data area, DO data area,
and diagnose data area do not overlap one another.
4 Ensure that the specified addresses do not overlap
an area used for a ladder program.
5 Use the R area only. (When using PMC-SB5, be
careful not to exceed R1499. When using PMC-SB6
or PMC-NB6, be careful not to exceed R2999.)
- 27 -
1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C OPERATION B-62924EN/04
NOTE
Diagnose data is classified as standard diagnose
data and extended diagnose data. The DP-Slaves
manufactured by FANUC use standard diagnose
data (6 bytes) only. On the other hand, DP-Slaves
supplied by other manufacturers may use extended
diagnose data of more than six bytes. When using
DP-Slaves supplied by other manufacturers,
determine the size of the diagnose data by
referencing the GSD file of each DP-Slave.
- 28 -
B-62924EN/04 OPERATION 1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C
- 29 -
1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C OPERATION B-62924EN/04
Soft key [INIT] on Screen 1-7 clears the value of each address
assignment parameter (the address specification fields are set to
R0000). So, specify valid values.
- 30 -
B-62924EN/04 OPERATION 1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C
Pressing soft key [MODE] on Screen 1-2 displays Screen 1-8. On this
screen, you can set the STOP, CLEAR, or OPERATE mode defined
in the PROFIBUS-DP specifications.
Screen 1-8
- 31 -
1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C OPERATION B-62924EN/04
NOTE
For the operation mode, pay careful attention to the
following points:
(1) When the power is turned on in the status in which
at least one slave station is ACTIVE, the master
station automatically starts in the OPERATE mode.
An ACTIVE slave station means a slave station for
which ENABLE and SLAVE TYPE = 192 are set as
slave parameters.
(2) In a case other than (1), that is, when the power is
turned on in the status in which all slave stations
are not ACTIVE, the master station automatically
starts in the STOP mode.
(3) A FANUC master station cannot manually be put in
the OFFLINE mode.
If a FANUC master station is in the OFFLINE mode
immediately after power-on, an error may occur.
See Table 1-1, "Setting Error Message."
- 32 -
B-62924EN/04 OPERATION 1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C
When creating a ladder program, fully consider the data refresh time
and data simultaneity described below.
The data refresh time for the master function means the time required
for updating DI/DO data for all slave stations that is allocated in the R
area of the PMC by address assignment.
NOTE
DI/DO data only for the slave stations for which
ENABLE is set as a slave parameter is to be
updated.
In this section, a slave station for which ENABLE is
set is described as a communication slave station.
CAUTION
Note that DI/DO data may not be updated within the
time displayed for REFRESH TIME in either of the
following cases:
- The status of at least one communication slave
station is changing every moment.
(In this case, diagnose data must be updated.)
- A service is being received from a class-2 master
station every moment.
- 33 -
1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C OPERATION B-62924EN/04
- 34 -
B-62924EN/04 OPERATION 1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C
When both the master and slave functions are used together
In this case, the data refresh time is similar to that described in "When
only the master function is used" above.
However, SIZE: DI/DO data size in expression (A) is as follows:
SIZE = SIZEmas + SIZEslv
SIZEmas : DI/DO data size for the master function
SIZEslv : DI/DO data size for the slave function
- 35 -
1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C OPERATION B-62924EN/04
Data simultaneity
With the FANUC master function and Slave function, when DI/DO
signals are handled with a ladder program, data simultaneity is
guaranteed in each of long data (4-byte data) units and word data (2-
byte data) units under the following constraints.
NOTE
If the following constraints are not satisfied,
simultaneity of each data length cannot be
guaranteed.
- 36 -
B-62924EN/04 OPERATION 1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C
Procedure (CRT/MDI)
(1) Press function key <SYSTEM>. Then, press soft key [PMC] to
switch to the PMC screen.
Screen 1-9
- 37 -
1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C OPERATION B-62924EN/04
CAUTION
On Screen 1-9, check the following items:
(1) CONTROL SOFTWARE is Edition 08 or later of
series 6557.
(2) SLAVE SOFTWARE (series 6553 or 6551) is
Edition 07 or later.
When CONTROL SOFTWARE is Edition 07 or
earlier of series 6557 or 6556, see "SUPPLEMENT."
(3) Pressing soft key [SLAVE] on this screen displays Screen 1-10.
Screen 1-10
- 38 -
B-62924EN/04 OPERATION 1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C
NOTE
If either of the following messages is displayed on
Screen 1-10, take appropriate action corresponding
the message:
- "SET I/O SIZE[MAS+SLV<=256],POWER OFF"
When this node is shared by both master and slave
stations, the total of the DI/DO sizes for all slave
stations for which ENABLE is set and the DI/DO size
for the sharing slave station exceeds 256 bytes.
Set the DI/DO sizes again so that the total does not
exceed 256 bytes, and turn the power off, then on
again. (This message is displayed only when Edition
08 of series 6557 of CONTROL SOFTWARE is
used.)
- "UPGRADE SLAVE SOFTWARE"
Replace SLAVE SOFTWARE (series 6553 or 6551)
with Edition 07 or later of SLAVE SOFTWARE.
CAUTION
When assigning addresses, pay careful attention to the
following points:
1 Ensure that the specified DI and DO areas do not
overlap one another.
2 Ensure that specified addresses do not overlap an
area used for a ladder program.
3 Use the R area only. (When using the PMC-SB5, be
careful not to exceed R1499. When using the PMC-
SB6 or the PMC-NB6, be careful not to exceed
R2999.)
- 39 -
1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C OPERATION B-62924EN/04
CAUTION
DI and DO described in Section 1.3 (this section)
indicate the input and output viewed from the slave
station, respectively.
- 40 -
B-62924EN/04 OPERATION 1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C
- 41 -
1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C OPERATION B-62924EN/04
PROFIBUS
S0001 = 3
S0002 = R300
S0003 = 16
S0004 = R400
S0005 = 32
S0101 = 00
S0102 = 00
S0103 = 00
>
Screen 1-11
- 42 -
B-62924EN/04 OPERATION 1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C
S0001 = 0
> S0002 = 0
Screen 1-12
- 43 -
1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C OPERATION B-62924EN/04
- 44 -
B-62924EN/04 OPERATION 1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C
Data simultaneity
With the FANUC master function and slave function, when DI/DO
signals are handled with a ladder program, data simultaneity is
guaranteed in each of long data (4-byte data) units and word data (2-
byte data) units under the following constraints.
NOTE
If the following constraints are not satisfied,
simultaneity of each data length cannot be
guaranteed.
- 45 -
1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C OPERATION B-62924EN/04
NOTE
All settings indicated in Table 1-11 are represented in hexadecimal.
- 46 -
B-62924EN/04 OPERATION 1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C
CAUTION
Input and output described below indicate the input
and output viewed from the master station,
respectively.
DI and DO indicate the input and output viewed from
the FANUC slave station, respectively.
For CONFIG DATA for using a FANUC slave station, usually set the
value specifying the input/output type with the first data and the
input/output size with the following data.
The value specifying the input/output type is set in hexadecimal as
follows:
(a) For using both input/output (input/output size > 0) : C0
(b) For using only output (input size = 0, output size > 0) : 80
(c) For using only input (input size > 0, output size = 0) : 40
For example, for (a) For using both input/output, the format is as
follows:
Data length: 3
Data: C0 output-size -1 input-size -1
For using only output or input, the same format is used as follows:
(b) For using only output
Data length: Multiple of 2
Data: 80 output-size -1 ... repeated
(c) For using only input
Data length: Multiple of 2
Data: 40 input-size -1 ... repeated
- 47 -
1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C OPERATION B-62924EN/04
<2> When the input size is 65 to 128 and the output size is 65 to
128
(DI SIZE + DO SIZE ≤ 244 must be satisfied, however.)
Data length: 6
Data: C0 XX YY C0 XX YY
<3> When the input size is 1 to 64 and the output size is 65 to
128
Data length: 5
Data: C0 XX YY 80 XX
<4> When the input size is 1 to 64 and the output size is 129 to
192
(DI SIZE + DO SIZE ≤ 244 must be satisfied, however.)
Data length: 7
Data: C0 XX YY 80 XX 80 XX
<5> When the input size is 1 to 64 and the output size is 193 to
244
(DI SIZE + DO SIZE ≤ 244 must be satisfied, however.)
Data length: 9
Data: C0 XX YY 80 XX 80 XX 80 XX
<6> When the input size is 65 to 128 and the output size is 1 to
64
Data length: 5
Data: C0 XX YY 40 YY
<7> When the input size is 129 to 192 and the output size is 1 to
64
(DI SIZE + DO SIZE ≤ 244 must be satisfied, however.)
Data length: 7
Data: C0 XX YY 40 YY 40 YY
<8> When the input size is 193 to 244 and the output size is 1 to
64
(DI SIZE + DO SIZE ≤ 244 must be satisfied, however.)
Data length: 9
Data: C0 XX YY 40 YY 40 YY 40 YY
<9> When the input size is 65 to 128 and the output size is 129
to 192
(DI SIZE + DO SIZE ≤ 244 must be satisfied, however.)
Data length: 8
Data: C0 XX YY C0 XX YY 80 XX
<10>When the input size is 129 to 192 and the output size is 65
to 128
(DI SIZE + DO SIZE ≤ 244 must be satisfied, however.)
Data length: 8
Data: C0 XX YY C0 XX YY 40 YY
- 48 -
B-62924EN/04 OPERATION 1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C
<3> When the input size is 0 and the output size is 129 to 192
Data length: 6
Data: 80 XX 80 XX 80 XX
<4> When the input size is 0 and the output size is 193 to 244
Data length: 8
Data: 80 XX 80 XX 80 XX 80 XX 80 XX
- 49 -
1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C OPERATION B-62924EN/04
Table 1-12 Examples of “(a) Setting CONFIG DATA for Using Both Input/Output”
Input/output sizes for the DI/DO sizes set for a CONFIG DATA set for the master station
master station FANUC slave station (equivalent to Module in the GSD file)
(a)-<1> Data length: 3
DI/DO SIZE = 64 / 64
Input/output sise = 64 / 64 Data: C0 3F 3F
(a)-<2> Data length: 6
DI/DO SIZE = 122 / 122
Input/output sise = 122 / 122 Data: C0 3F 3F C0 39 39
(a)-<3> Data length: 5
DI/DO SIZE = 128 / 64
Input/output sise = 64 / 128 Data: C0 3F 3F 80 3F
(a)-<4> Data length: 7
DI/DO SIZE = 192 / 1
Input/output sise = 1 / 192 Data: C0 3F 00 80 3F 80 3F
(a)-<5> Data length: 9
DI/DO SIZE = 243 / 1
Input/output sise =1 / 243 Data: C0 3F 00 80 3F 80 3F 80 32
(a)-<6> Data length: 5
DI/DO SIZE = 64 / 128
Input/output sise =128 / 64 Data: C0 3F 3F 40 3F
(a)-<7> Data length: 7
DI/DO SIZE = 1 / 192
Input/output sise = 192 / 1 Data: C0 00 3F 40 3F 40 3F
(a)-<8> Data length: 9
DI/DO SIZE = 1 / 243
Input/output sise = 243 / 1 Data: C0 00 3F 40 3F 40 3F 40 32
(a)-<9> Data length: 8
DI/DO SIZE = 129 / 65
Input/output sise = 65 / 129 Data: C0 3F 3F C0 3F 00 80 00
(a)-<10> Data length: 8
DI/DO SIZE = 65 / 129
Input/output sise =129 / 65 Data: C0 3F 3F C0 00 3F 40 00
Table 1-13 Examples of “(b) Setting CONFIG DATA for Using Only Output”
Input/output sizes for the DI/DO sizes set for a CONFIG DATA set for the master station
master station FANUC slave station (equivalent to Module in the GSD file)
(b)-<1> Data length: 2
DI/DO SIZE = 64 / 0
Input/output sise = 0 / 64 Data: 80 3F
(b)-<2> Data length: 4
DI/DO SIZE = 128 / 0
Input/output sise =0 / 128 Data: 80 3F 80 3F
(b)-<3> Data length: 6
DI/DO SIZE = 192 / 0
Input/output sise = 0 / 192 Data: 80 3F 80 3F 80 3F
(b)-<4> Data length: 8
DI/DO SIZE = 244 / 0
Input/output sise = 0 / 244 Data: 80 3F 80 3F 80 3F 80 33
Table 1-14 Examples of “(c) Setting CONFIG DATA for Using Only Input”
Input/output sizes for the DI/DO sizes set for a CONFIG DATA set for the master station
master station FANUC slave station (equivalent to Module in the GSD file)
(c)-<1> Data length: 2
DI/DO SIZE = 0 / 64
Input/output sise =64 / 0 Data: 40 3F
(c)-<2> Data length: 4
DI/DO SIZE = 0 / 128
Input/output sise = 128 / 0 Data: 40 3F 40 3F
(c)-<3> Data length: 6
DI/DO SIZE = 0 / 192
Input/output sise =192 / 0 Data: 40 3F 40 3F 40 3F
(c)-<4> Data length: 8
DI/DO SIZE = 0 / 244
Input/output sise = 244 / 0 Data: 40 3F 40 3F 40 3F 40 33
NOTE
For a FANUC slave station, a total of 244 bytes can
be set for the DI/DO sizes.
- 50 -
B-62924EN/04 OPERATION 1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C
- 51 -
1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C OPERATION B-62924EN/04
#Profibus_DP
Vendor_Name = "FANUC"
Model_Name = "FANUC CNC"
Revision = "1.0"
Ident_Number = 0x00CB
Protocol_Ident =0
Station_Type =1
FMS_supp =0
Hardware_Release = "Release 1.0"
Software_Release = "Release 3.0"
9.6_supp =1
19.2_supp =1
93.75_supp =1
187.5_supp =1
500_supp =1
1.5M_supp =1
3M_supp =1
6M_supp =1
12M_supp =1
MaxTsdr_9.6 = 60
MaxTsdr_19.2 = 60
MaxTsdr_93.75 = 60
MaxTsdr_187.5 = 60
MaxTsdr_500 = 100
MaxTsdr_1.5M = 150
MaxTsdr_3M = 250
MaxTsdr_6M = 450
MaxTsdr_12M = 800
Redundancy =0
Repeater_Ctrl_Sig =2
24V_Pins =0
;
- 52 -
B-62924EN/04 OPERATION 1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C
- 53 -
1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C OPERATION B-62924EN/04
LAS_Len = 32
;
Tsdi_9.6 = 70
Tsdi_19.2 = 70
Tsdi_93.75 = 70
Tsdi_187.5 = 70
Tsdi_500 = 150
Tsdi_1.5M = 200
Tsdi_3M = 250
Tsdi_6M = 450
Tsdi_12M = 800
;
Max_Slaves_supp = 32
;
- 54 -
B-62924EN/04 OPERATION 1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C
#Profibus_DP
Vendor_Name = "FANUC"
Model_Name = "FANUC CNC"
Revision = "1.0"
Ident_Number = 0x00A0
Protocol_Ident =0
Station_Type =0
FMS_supp =0
Hardware_Release = "Release 1.0"
Software_Release = "Release 3.0"
9.6_supp =1
19.2_supp =1
93.75_supp =1
187.5_supp =1
500_supp =1
1.5M_supp =1
3M_supp =1
6M_supp =1
12M_supp =1
MaxTsdr_9.6 = 60
MaxTsdr_19.2 = 60
MaxTsdr_93.75 = 60
MaxTsdr_187.5 = 60
MaxTsdr_500 = 100
MaxTsdr_1.5M = 150
MaxTsdr_3M = 250
MaxTsdr_6M = 450
MaxTsdr_12M = 800
Redundancy =0
Repeater_Ctrl_Sig =2
24V_Pins =0
;
- 55 -
1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C OPERATION B-62924EN/04
NOTE
For a FANUC slave station, the DI/DO sizes can be
changed without restrictions as long as the total of
the DI/DO sizes does not exceed 244 bytes. For
this reason, all of the values to be specified for
Module cannot be listed.
For the values to be specified for Module, see
Tables 1-12 to 1-14 in Section 1.4, "Setting the
Slave Parameters for Using a Slave Station
Manufactured by FANUC."
- 56 -
B-62924EN/04 OPERATION 1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C
#Profibus_DP
Vendor_Name = "FANUC"
Model_Name = "FANUC Power Mate CNC"
Revision = "1.0"
Ident_Number = 0x00A1
Protocol_Ident =0
Station_Type =0
FMS_supp =0
Hardware_Release = "Release 1.0"
Software_Release = "Release 3.0"
9.6_supp =1
19.2_supp =1
93.75_supp =1
187.5_supp =1
500_supp =1
1.5M_supp =1
3M_supp =1
6M_supp =1
12M_supp =1
MaxTsdr_9.6 = 60
MaxTsdr_19.2 = 60
MaxTsdr_93.75 = 60
MaxTsdr_187.5 = 60
MaxTsdr_500 = 100
MaxTsdr_1.5M = 150
MaxTsdr_3M = 250
MaxTsdr_6M = 450
MaxTsdr_12M = 800
Redundancy =0
Repeater_Ctrl_Sig =2
24V_Pins =0
;
; Slave specific parameters
;
Freeze_Mode_supp =0
Sync_Mode_supp =0
Auto_Baud_supp =1
Set_Slave_Add_supp =0
User_Prm_Data_Len =0
Min_Slave_Intervall =1
Modular_Station =1
Max_Module =1
Max_Input_Len = 244
Max_Output_Len = 244
Max_Data_Len = 244
;
Module = "32 Byte Out, 32 Byte In" 0xC0,0x1F,0x1F
EndModule
Module = "28 Byte Out, 28 Byte In" 0xC0,0x1B,0x1B
- 57 -
1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C OPERATION B-62924EN/04
EndModule
Module = "24 Byte Out, 24 Byte In" 0xC0,0x17,0x17
EndModule
Module = "20 Byte Out, 20 Byte In" 0xC0,0x13,0x13
EndModule
Module = "16 Byte Out, 16 Byte In" 0xC0,0x0F,0x0F
EndModule
Module = "12 Byte Out, 12 Byte In" 0xC0,0x0B,0x0B
EndModule
Module = " 8 Byte Out, 8 Byte In" 0xC0,0x07,0x07
EndModule
Module = " 4 Byte Out, 4 Byte In" 0xC0,0x03,0x03
EndModule
Module = " 2 Byte Out, 2 Byte In" 0xC0,0x01,0x01
EndModule
Module = "32 Byte Out, 1 Byte In" 0xC0,0x1F,0x00
EndModule
Module = " 1 Byte Out, 32 Byte In" 0xC0,0x00,0x1F
EndModule
;
NOTE
For a FANUC slave station, the DI/DO sizes can be
changed without restrictions as long as the total of
the DI/DO sizes does not exceed 244 bytes. For
this reason, all of the values to be specified for
Module cannot be listed.
For the values to be specified for Module, see
Tables 1-12 to 1-14 in Section 1.4, "Setting the
Slave Parameters for Using a Slave Station
Manufactured by FANUC."
- 58 -
B-62924EN/04 OPERATION 2.Series 15i-A
2 Series 15i-A
This chapter describes PROFIBUS-DP functions for Series 15i.
NOTE
PROFIBUS-DP cannot be used with DeviceNet.
- 59 -
2.Series 15i-A OPERATION B-62924EN/04
2.1 OVERVIEW
- 60 -
B-62924EN/04 OPERATION 2.Series 15i-A
To use the master function, bus parameters and slave parameters must
be set, and addresses must be assigned.
The bus parameters are referenced by the network, and the slave
parameters are set for each slave. In address assignment, PMC
addresses used by the DP-Master to transfer DI/DO signals to and
from each DP-Slave are set.
The methods of setting the parameters are described below.
- 61 -
2.Series 15i-A OPERATION B-62924EN/04
Screen 2-1
Display procedure
Procedure 1
(1) Press the function key <SYSTEM> several times until the bus
parameter screen, slave parameter screen, or slave function
setting screen appears.
(2) When the slave parameter screen or slave function setting screen
appears, press the soft key [BUS PARAM].
Procedure 2
(1) Press the function key <SYSTEM>.
(2) Press the soft key [PROFIBUS].
(3) When the slave parameter screen or slave function setting screen
appears, press the soft key [BUS PARAM].
Cursor/paging
- 62 -
B-62924EN/04 OPERATION 2.Series 15i-A
Table 2-1 summarizes the bus parameters. Table 2-2 lists the bus
parameter values to be set for each transfer rate. For details, refer to
the following documents issued by PROFIBUS Nutzerorganisation
e.V.:
¡ PROFIBUS STANDARD DIN 19 245 Part 1
This document describes data transfer, access methods, protocols,
and interfacing with the application layer.
¡ Draft Standard PROFIBUS-DP DIN 19 245 Part 3
This document describes an abstract model of the PROFIBUS-
DP communication function, and so forth.
- 63 -
2.Series 15i-A OPERATION B-62924EN/04
- 64 -
B-62924EN/04 OPERATION 2.Series 15i-A
NOTE
For multiple master communication, satisfy the
following conditions:
- The value set for 1:FDL ADD for a master station is
not used as another master station number.
- The same values are set for bus parameters 2 to 11
for all master stations.
- When a larger value is set for T SET, T SL is larger
than T ID1.
(T ID1 = 33 + 2 + 2 × T SET + T QUI)
- 65 -
2.Series 15i-A OPERATION B-62924EN/04
Screen 2-2(a)
Screen 2-2(b)
- 66 -
B-62924EN/04 OPERATION 2.Series 15i-A
Display procedure
Procedure 1
(1) Press the function key <SYSTEM> several times until the bus
parameter screen, slave parameter screen, or slave function
setting screen appears.
(2) When the bus parameter screen or slave function setting screen
appears, enter a slave number, then press the soft key [SLAVE
PARAM].
Procedure 2
(1) Press the function key <SYSTEM>.
(2) Press the soft key [PROFIBUS].
(3) When the bus parameter screen or slave function setting screen
appears, enter a slave number, then press the soft key [SLAVE
PARAM].
Procedure 1
(1) Press the soft key [SLAVE PARAM].
(2) Enter a desired slave number.
(3) Press the soft key [EXEC].
Procedure 2
(1) Enter a desired slave number.
(2) Press the soft key [SLAVE PARAM].
Cursor/paging
1 Use of the cursor keys moves the cursor.
• Pressing the cursor key <↓> in the last line of SLAVE
USER DATA moves the cursor to DISABLE/ENABLE for
the next slave number.
When this cursor key is pressed in the last line of CONFIG
DATA LENGTH for slave No. 125, the cursor moves to
STATION NO. on the slave setting screen.
• Pressing the cursor key <↑> in DISABLE/ENABLE moves
the cursor to CONFIG DATA LENGTH for the preceding
slave number.
When this cursor key is pressed in DISABLE/ENABLE for
slave No. 000, the cursor moves to MASTER USER DATA
LENGTH on the bus parameter screen.
2 Use of the page keys <PAGE ↓> < PAGE ↑> allows paging.
• Pressing the page key <PAGE ↓> on the second page for
slave No. 125 displays the slave setting screen.
• Pressing the page key < PAGE ↑> on the first page for
slave No. 000 displays the bus parameter screen.
- 67 -
2.Series 15i-A OPERATION B-62924EN/04
Initialization
Pressing the soft key [INIT] initializes the slave parameter values for
a specified station number to the basic settings used for connecting
the DP-Slave of FANUC CNC.
NOTE
1 Normally, use of the soft key [INIT] allows
initialization for connecting FANUC's DP-Slave.
However, be sure to set CONFIGURATION DATA
by referencing Section 2.4, "Setting Slave
Parameters When Using FANUC Slave Station."
This is because variable data for the DI/DO size in
data exchange with the SP-Slave must be set.
2 The soft key [INIT] sets each address assignment
parameter to the minimum value (the address
location is set to R0000). So, be sure to set a
correct value.
- 68 -
B-62924EN/04 OPERATION 2.Series 15i-A
- 69 -
2.Series 15i-A OPERATION B-62924EN/04
- 70 -
B-62924EN/04 OPERATION 2.Series 15i-A
Screen 2-2(a)
CAUTION
When assigning addresses, pay careful attention to the
following points:
1 Assign addresses to all DP-Slaves that are set to
ENABLE in the slave parameters.
2 Be careful not to assign duplicate addresses to a
DP-Slave.
3 Ensure that a specified DI data area, DO data area,
and diagnose data area do not overlap one another.
4 Ensure that the specified addresses do not overlap
an area used for a ladder program.
5 Use the R area only. (When using PMC-SB5, be
careful not to exceed R1499. When using PMC-SB6
or PMC-NB6, be careful not to exceed R2999.)
- 71 -
2.Series 15i-A OPERATION B-62924EN/04
NOTE
Diagnose data is classified as standard diagnose
data and extended diagnose data. The DP-Slaves
manufactured by FANUC use standard diagnose
data (6 bytes) only. On the other hand, DP-Slaves
supplied by other manufacturers may use extended
diagnose data of more than six bytes. When using
DP-Slaves supplied by other manufacturers,
determine the size of the diagnose data by
referencing the GSD file of each DP-Slave.
- 72 -
B-62924EN/04 OPERATION 2.Series 15i-A
- 73 -
2.Series 15i-A OPERATION B-62924EN/04
- 74 -
B-62924EN/04 OPERATION 2.Series 15i-A
NOTE
Before a DP-Slave manufactured by FANUC can be
used, data dependent on the FANUC DP-Slave must
be set in the slave parameters of the DP-Master. So,
when setting the slave parameters of the DP-Master,
see Section 2.4, "Setting the Slave Parameters for
Using a slave Station Manufactured by FANUC."
Screen 2-3
NOTE
INPUT DATA SIZE = 0 or OUTPUT DATA SIZE = 0
can be set on the screen, but communication is
disabled in this case.
- 75 -
2.Series 15i-A OPERATION B-62924EN/04
Display procedure
Procedure 1
(1) Press the <SYSTEM> function key several times until the bus
parameter screen, slave parameter screen, or slave function
setting screen appears.
(2) When the bus parameter screen or slave parameter screen
appears, press the soft key [SLAVE SETTING].
Procedure 2
(1) Press the <SYSTEM> function key .
(2) Press the soft key [PROFIBUS-DP].
(3) When the bus parameter screen or slave parameter screen
appears, press the soft key [SLAVE SETTING].
Cursor/paging
1 Use of the cursor keys <↓> <↑> moves the cursor.
• When the cursor key <↓> is pressed in OUTPUT DATA
SIZE, the cursor moves to FDL ADD on the bus parameter
screen.
• When the cursor key <↓> is pressed in STATION NO., the
cursor moves to CONFIG DATA LENGTH on the slave
parameter screen for slave No. 125.
2 Pressing the page key <PAGE ↓> displays the bus parameter
screen.
Pressing the page key <PAGE ↑> displays the slave parameter
screen for slave No. 125.
Initialization
Pressing the soft key [INIT] clears the address assignment parameters.
CAUTION
When assigning addresses, pay careful attention to the
following points:
1 Ensure that the specified DI and DO areas do not
overlap one another.
2 Ensure that specified addresses do not overlap an
area used for a ladder program.
3 Use the R area only. (When using the PMC-SB5, be
careful not to exceed R1499. When using the PMC-
SB6 or the PMC-NB6, be careful not to exceed
R2999.)
- 76 -
B-62924EN/04 OPERATION 2.Series 15i-A
CAUTION
INPUT and OUTPUT on this screen indicate the
input and output viewed from the slave station,
respectively.
- 77 -
2.Series 15i-A OPERATION B-62924EN/04
STATUS on Screen 2-4 indicates the state of the DP-Slave. Each item
under STATUS has the meaning described below.
CFG STATUS
This item indicates whether slave parameter CONFIG
DATA of the DP-Master matches the configuration data
recognized by the DP-Slave. If there is a mismatch, normal
communication cannot be performed.
FF: Initial state
00: State in which normal communication is being
performed (match)
03: State in which received configuration data cannot be
accepted
PARAM STATUS
This item indicates whether slave parameter USER PRM
DATA of the DP-Master matches the parameter data
recognized by the DP-Slave. If there is a mismatch, normal
communication cannot be performed.
FF: Initial state
00: State in which normal communication is being
performed (match)
03: State in which received parameter data cannot be
accepted
WATCHDOG STATUS
This item indicates the connection state of the
communication link with the DP-Master.
00: Connected
01: Disconnected
LIVELIST STATUS
This item indicates whether the software of the slave
function is operating normally. During normal operation,
this item counts up from 00 to FF. When FF is reached,
another count operation starts from 00. This status indicates
whether the software of the slave function is operating
normally, but does not indicate whether communication is
being performed normally.
IDENT NO.
This item displays 00A0 as the identification number of a
DP-Slave using a FANUC CNC.
- 78 -
B-62924EN/04 OPERATION 2.Series 15i-A
- 79 -
2.Series 15i-A OPERATION B-62924EN/04
NOTE
All settings indicated in Table 2-6 are represented in hexadecimal.
- 80 -
B-62924EN/04 OPERATION 2.Series 15i-A
- 81 -
2.Series 15i-A OPERATION B-62924EN/04
#Profibus_DP
Vendor_Name = "FANUC"
Model_Name = "FANUC CNC"
Revision = "1.0"
Ident_Number = 0x00CB
Protocol_Ident =0
Station_Type =1
FMS_supp =0
Hardware_Release = "Release 1.0"
Software_Release = "Release 3.0"
9.6_supp =1
19.2_supp =1
93.75_supp =1
187.5_supp =1
500_supp =1
1.5M_supp =1
3M_supp =1
6M_supp =1
12M_supp =1
MaxTsdr_9.6 = 60
MaxTsdr_19.2 = 60
MaxTsdr_93.75 = 60
MaxTsdr_187.5 = 60
MaxTsdr_500 = 100
MaxTsdr_1.5M = 150
MaxTsdr_3M = 250
MaxTsdr_6M = 450
MaxTsdr_12M = 800
Redundancy =0
Repeater_Ctrl_Sig =2
24V_Pins =0
;
- 82 -
B-62924EN/04 OPERATION 2.Series 15i-A
- 83 -
2.Series 15i-A OPERATION B-62924EN/04
LAS_Len = 32
;
Tsdi_9.6 = 70
Tsdi_19.2 = 70
Tsdi_93.75 = 70
Tsdi_187.5 = 70
Tsdi_500 = 150
Tsdi_1.5M = 200
Tsdi_3M = 250
Tsdi_6M = 450
Tsdi_12M = 800
;
Max_Slaves_supp = 32
;
- 84 -
B-62924EN/04 OPERATION 2.Series 15i-A
#Profibus_DP
Vendor_Name = "FANUC"
Model_Name = "FANUC CNC"
Revision = "1.0"
Ident_Number = 0x00A0
Protocol_Ident =0
Station_Type =0
FMS_supp =0
Hardware_Release = "Release 1.0"
Software_Release = "Release 3.0"
9.6_supp =1
19.2_supp =1
93.75_supp =1
187.5_supp =1
500_supp =1
1.5M_supp =1
3M_supp =1
6M_supp =1
12M_supp =1
MaxTsdr_9.6 = 60
MaxTsdr_19.2 = 60
MaxTsdr_93.75 = 60
MaxTsdr_187.5 = 60
MaxTsdr_500 = 100
MaxTsdr_1.5M = 150
MaxTsdr_3M = 250
MaxTsdr_6M = 450
MaxTsdr_12M = 800
Redundancy =0
Repeater_Ctrl_Sig =2
24V_Pins =0
;
NOTE
For a FANUC slave station, Module in the GSD file
matches slave parameter CONFIG DATA. The
DI/DO sizes for a FANUC slave station can be
changed without restrictions as long as they do not
exceed 32/32 bytes. For this reason, all of the
values to be specified for Module cannot be listed.
For the values to be specified for Module, see the
explanation of CONFIG DATA in Table 2-6 in
Section 2.4, "Setting the Slave Parameters for
Using a Slave Station Manufactured by FANUC."
- 86 -
B-62924EN/04 OPERATION 3.Power Mate-D/H
3 Power Mate-D/H
This chapter describes PROFIBUS-DP functions for Power Mate-
D/H.
NOTE
PROFIBUS-DP cannot be used with DeviceNet.
- 87 -
3.Power Mate-D/H OPERATION B-62924EN/04
Parameters
0171 DI data size
- 88 -
B-62924EN/04 OPERATION 3.Power Mate-D/H
NOTE
All settings indicated in Table 3-1 are represented in hexadecimal.
- 89 -
3.Power Mate-D/H OPERATION B-62924EN/04
- 90 -
B-62924EN/04 OPERATION 3.Power Mate-D/H
#Profibus_DP
Vendor_Name = "FANUC"
Model_Name = "FANUC Power Mate CNC"
Revision = "1.0"
Ident_Number = 0x00A1
Protocol_Ident =0
Station_Type =0
FMS_supp =0
Hardware_Release = "Release 1.0"
Software_Release = "Release 3.0"
9.6_supp =1
19.2_supp =1
93.75_supp =1
187.5_supp =1
500_supp =1
1.5M_supp =1
3M_supp =1
6M_supp =1
12M_supp =1
MaxTsdr_9.6 = 60
MaxTsdr_19.2 = 60
MaxTsdr_93.75 = 60
MaxTsdr_187.5 = 60
MaxTsdr_500 = 100
MaxTsdr_1.5M = 150
MaxTsdr_3M = 250
MaxTsdr_6M = 450
MaxTsdr_12M = 800
Redundancy =0
Repeater_Ctrl_Sig =2
24V_Pins =0
;
; Slave specific parameters
;
Freeze_Mode_supp =0
Sync_Mode_supp =0
Auto_Baud_supp =1
Set_Slave_Add_supp =0
User_Prm_Data_Len =0
Min_Slave_Intervall =1
Modular_Station =1
Max_Module =1
Max_Input_Len = 32
Max_Output_Len = 32
Max_Data_Len = 64
;
Module = "32 Byte Out, 32 Byte In" 0xC0,0x1F,0x1F
EndModule
Module = "28 Byte Out, 28 Byte In" 0xC0,0x1B,0x1B
- 91 -
3.Power Mate-D/H OPERATION B-62924EN/04
EndModule
Module = "24 Byte Out, 24 Byte In" 0xC0,0x17,0x17
EndModule
Module = "20 Byte Out, 20 Byte In" 0xC0,0x13,0x13
EndModule
Module = "16 Byte Out, 16 Byte In" 0xC0,0x0F,0x0F
EndModule
Module = "12 Byte Out, 12 Byte In" 0xC0,0x0B,0x0B
EndModule
Module = " 8 Byte Out, 8 Byte In" 0xC0,0x07,0x07
EndModule
Module = " 4 Byte Out, 4 Byte In" 0xC0,0x03,0x03
EndModule
Module = " 2 Byte Out, 2 Byte In" 0xC0,0x01,0x01
EndModule
Module = "32 Byte Out, 1 Byte In" 0xC0,0x1F,0x00
EndModule
Module = " 1 Byte Out, 32 Byte In" 0xC0,0x00,0x1F
EndModule
;
NOTE
For a FANUC slave station, Module in the GSD file
matches slave parameter CONFIG DATA. The
DI/DO sizes for a FANUC slave station can be
changed without restrictions as long as they do not
exceed 32/32 bytes. For this reason, all of the
values to be specified for Module cannot be listed.
For the values to be specified for Module, see the
explanation of CONFIG DATA in Table 3-1 in
Section 3.2, "Setting the Slave Parameters for
Using a Slave Station Manufactured by FANUC."
- 92 -
B-62924EN/04 OPERATION 4.BUILDING A SAFE SYSTEM
- 93 -
4.BUILDING A SAFE SYSTEM OPERATION B-62924EN/04
For example, the master station can read and check the diagnose data
for each slave station to determine whether communication with the
slave station is being performed normally. A check method with using
no diagnose data is also supported. A signal for indicating normal
communication is provided in DI/DO data to be exchanged, and is
monitored to determine whether communication between the master
station and a slave station is performed normally.
As described above, for the master station, provide safety provisions
to ensure that the system is not started or is stopped safely if the
system is not ready for execution or if an error occurs in the system.
CAUTION
I/O data is not transferred in sync with ladder
execution, so that the concurrency of I/O data is not
guaranteed.
- 94 -
B-62924EN/04 OPERATION 4.BUILDING A SAFE SYSTEM
NOTE
The system execution signal in Table 4-1 means to provide a signal for starting
system operation in the DO data to be sent from the master station to all slave
stations. Ensure that this signal disables system operation when set to 0, and
enables system operation when set to 1, as with the emergency stop signal.
- 95 -
4.BUILDING A SAFE SYSTEM OPERATION B-62924EN/04
- 96 -
B-62924EN/04 OPERATION 5.EXAMPLE OF CONNECTION
5 EXAMPLE OF CONNECTION
This chapter describes an example of connecting the PROFIBUS-DP
function of the FANUC CNCs.
- 97 -
5.EXAMPLE OF CONNECTION OPERATION B-62924EN/04
Series 16i-A
DP-Master (class1) #1
- 98 -
B-62924EN/04 OPERATION 5.EXAMPLE OF CONNECTION
- 99 -
5.EXAMPLE OF CONNECTION OPERATION B-62924EN/04
- 100 -
B-62924EN/04 OPERATION 5.EXAMPLE OF CONNECTION
- 101 -
5.EXAMPLE OF CONNECTION OPERATION B-62924EN/04
R0000
DI data from DP-Slave #3
R0004
DI data from DP-Slave #4
R0008
DI data from DP-Slave #5
R0012
Not used
R0020
DO data to DP-Slave #3
R0036
DO data to DP-Slave #4
R0052
DO data to DP-Slave #5
R0068
Not used
R0070
Diagnose data of DP-Slave #3
R0076
Diagnose data of DP-Slave #4
R0082
Diagnose data of DP-Slave #5
R0088
- 102 -
B-62924EN/04 OPERATION 5.EXAMPLE OF CONNECTION
When the address map shown in Fig.5-3 is assumed for each DP-
Slave, the settings indicated in Table 5-4 to Table 5-6 are required.
- 103 -
5.EXAMPLE OF CONNECTION OPERATION B-62924EN/04
DP-Slave #3, #4
R0000
DI area
R0016
Not used
R0020
DO area
R0024
DP-Slave #5
X1032
DI area
X1048
Y1032
DO area
Y1036
- 104 -
III. CONNECTION
B-62924EN/04 CONNECTION 1.CONNECTING THE PROFIBUS FUNCTIONS
CAUTION
Isolating the PROFIBUS cables from noise sources.
The PROFIBUS cables are of the group C
classification.
Refer to the Section “Action against noise” in the
"Connection Manual (Hardware) " for an explanation
of how to isolate the PROFIBUS cables from cables
of the group A and B classifications.
NOTE
PROFIBUS-DP cannot be used with DeviceNet.
- 107 -
1.CONNECTING THE PROFIBUS FUNCTIONS COONECTION B-62924EN/04
DP-Master
(Class1) #1
#3 #4 #5 #6 #N
DP-Slaves
- 108 -
B-62924EN/04 CONNECTION 1.CONNECTING THE PROFIBUS FUNCTIONS
Item Rating
Characteristic impedance 150 Ω (f < 2 MHz)
Capacitance < 30 nF/Km
Resistance < 110 Ω/Km
Wire gauge > 0.64 mm
Conductor cross-sectional area > 0.34 mm2
Recommended cable:
SINEC L2 bus cable 6XV1 830-0AH10, manufactured by
Siemens
- 109 -
1.CONNECTING THE PROFIBUS FUNCTIONS COONECTION B-62924EN/04
Baud rate (kbps) 9.6 to 93.75 187.5 500 1500 3000 to 12000
Maximum allowable
1200 1000 400 200 100
overall cable length (m)
- 110 -
B-62924EN/04 CONNECTION 1.CONNECTING THE PROFIBUS FUNCTIONS
1.4 CONNECTOR
1 PE PE : Shielding
6 VP RxD/TxD (+) : Transmission/reception
2
data (+)
7
3 RxD/TxD (+) CNTR-P : Not used (repeater control)
8 RxD/TxD (-)
4 DGND : Signal ground
9 VP : Not used (+5V output)
5 CNTR-P
RxD/TxD (-) : Transmission/reception
data (-)
CAUTION
The VP and CNTR-P pins are used for controlling a
repeater. Do not connect these pins to anything
unless a repeater is used. Otherwise, damage to the
device is likely. If you want to use these pins, consult
with FANUC beforehand.
You can use the following cable-end connector to perform wiring and
terminate the cable easily.
Cable-end connector:
S7 SINEC L2 bus connector 6ES7 972-0BA11-0XA0,
manufactured by Siemens, or equivalent
35.6 15.8
35.0
64.0
28.4
There is a 4-pin terminal block (A1, B1, A2, and B2) in this
connector.
NOTE
1 The shape, dimensions, and other characteristics of
the connector are subject to change without notice.
2 This bus connector may not be able to be used
depending on the position of the PROFIBUS board.
- 111 -
1.CONNECTING THE PROFIBUS FUNCTIONS COONECTION B-62924EN/04
A Station at the
next stage
B
Connect two wires to each of the pins Nos. 3 and 8 of the D-Sub
connector.
A: RxD/TxD (+)
B: RxD/TxD (-)
A Station at the
next stage
B
Shielding treatment
Clamp both the cable drawn from the station at the previous stage and
that leading to the station at the next stage on the CNC side.
For an explanation of how to treat the cable at each station, refer to
the respective manuals for the stations.
- 112 -
B-62924EN/04 CONNECTION 1.CONNECTING THE PROFIBUS FUNCTIONS
Each end of the bus cable must be terminated with a resistor as shown
below.
VP (6)
Ru = 390 Ω, 1/4 W
RxD/TxD (+) (3)
Rt = 220 Ω, 1/4 W
RxD/TxD (-) (8)
Rd = 390 Ω, 1/4 W
DGND (5)
- 113 -
1.CONNECTING THE PROFIBUS FUNCTIONS COONECTION B-62924EN/04
Grounding plate
Cable
Cable clamp
Grounding
plate
Shielding
Cable sheath
- 114 -
B-62924EN/04 CONNECTION 2.PROFIBUS FOR THE Series 16/18-C
- 115 -
2.PROFIBUS FOR THE Series 16/18-C CONNECTION B-62924EN/04
2.1 CONFIGURATION
A single PROFIBUS board for the Series 16/18-C has both the master
function and the slave function.
Master function
Slave function
- 116 -
B-62924EN/04 CONNECTION 2.PROFIBUS FOR THE Series 16/18-C
2.2 INSTALLATION
In the same way as for a regular CNC control unit, the PROFIBUS
cable is drawn out only from the front of the unit. The connector
layout of the PROFIBUS board is shown below for reference.
The actual location of the board and the actual connector layout of
other boards may differ from the above figure, however. For an
explanation of the actual connection layout of each individual board,
refer to the Connection Manual (Hardware) (B-62753EN).
- 117 -
2.PROFIBUS FOR THE Series 16/18-C CONNECTION B-62924EN/04
NOTE
6ES7 972-0BA11-0XA0 is a right-angled connector.
When it is used with this board, its cable is drawn
up, as shown in the figure.
When using this connector, always pay careful
attention to its orientation.
- 118 -
B-62924EN/04 CONNECTION 2.PROFIBUS FOR THE Series 16/18-C
PROFIBUS
MASTER
SLAVE
LED1
LED indicator LED2
LED3
- 119 -
2.PROFIBUS FOR THE Series 16/18-C CONNECTION B-62924EN/04
Network 1 (PROFIBUS)
CNC system
CNC main board
DP-Master
PROFIBUS board #1
Option slot JN1
Master function
JN2
Slave function
DP-Slave
#4
DP-Master
#1
Network 2 (PROFIBUS)
DP-Slave DP-Slave
#2 #3
- 120 -
B-62924EN/04 CONNECTION 3.PROFIBUS FOR THE LCD-MOUNTED TYPE Series 16i/18i/21i
- 121 -
3.PROFIBUS FOR THE LCD-MOUNTED TYPE Series 16i/18i/21i CONNECTION B-62924EN/04
3.1 CONFIGURATION
[PROFIBUS board]
The PROFIBUS board consists of two printed circuit boards:
a master function board and a slave function board.
- 122 -
B-62924EN/04 CONNECTION 3.PROFIBUS FOR THE LCD-MOUNTED TYPE Series 16i/18i/21i
[Adapter unit]
The CNC control unit is usually mounted on the machine operator's
panel (pendant). The adapter unit allows the PROFIBUS cable to be
extended and connected in the power magnetics cabinet. This makes it
easy to lay the PROFIBUS bus cable after the machine is installed.
Adapter unit
DIN rail
Ordering information
Name Code Remarks
PROFIBUS board A02B-0236-J311 Master + Slave
Adapter unit A02B-0236-C221
- 123 -
3.PROFIBUS FOR THE LCD-MOUNTED TYPE Series 16i/18i/21i CONNECTION B-62924EN/04
PROFIBUS board
Adapter unit
Internal cable
- 124 -
B-62924EN/04 CONNECTION 3.PROFIBUS FOR THE LCD-MOUNTED TYPE Series 16i/18i/21i
3.2 INSTALLATION
When using the PROFIBUS board, the installation conditions for the
CNC control unit in which the board is installed (environmental
conditions in the cabinet) must be observed. This also applies to the
adapter unit.
Slot-1
Slot-2
Slot-3
Slot-4 PROFIBUS board
- 125 -
3.PROFIBUS FOR THE LCD-MOUNTED TYPE Series 16i/18i/21i CONNECTION B-62924EN/04
The adapter unit is mounted in the power magnetics cabinet, using the
DIN rail. For the procedure for mounting and removing the adapter
unit on and from the DIN rail, refer to "Connection of connector panel
I/O module" in "Connection Manual (Hardware)" of the
corresponding CNC.
JN1 CN1
PROFIBUS board
JN1
(Master)
Adapter unit
JN2
(Slave) JN1 CN1
MAX. 6 m
L<6m
- 126 -
B-62924EN/04 CONNECTION 3.PROFIBUS FOR THE LCD-MOUNTED TYPE Series 16i/18i/21i
[Connector pins]
[Cable wires]
Ordering information
Name Code Remarks
Internal cable A02B-0236-K151 Two 6-m internal cables
- 127 -
3.PROFIBUS FOR THE LCD-MOUNTED TYPE Series 16i/18i/21i CONNECTION B-62924EN/04
[PROFIBUS board]
- 128 -
B-62924EN/04 CONNECTION 3.PROFIBUS FOR THE LCD-MOUNTED TYPE Series 16i/18i/21i
[Adapter unit]
The outside dimensions are the same as those of the connector panel
I/O module. For details, refer to "Connection Manual (Hardware)" of
the corresponding CNC.
PROFIBUS
bus cable
Internal cable
JN2: PCR-EV20MDT
Interface with PROFIBUS board
- 129 -
3.PROFIBUS FOR THE LCD-MOUNTED TYPE Series 16i/18i/21i CONNECTION B-62924EN/04
Network 1 (PROFIBUS)
CNC system
CNC main board
DP-Master
#1 CN1
JN2
Adapter
JN1 unit
PROFIBUS master
Option slot
function board
JN2
JN2 Adapter
unit
PROFIBUS slave
function board
DP-Slave CN1
#4
DP-Master
#1
Network 2 (PROFIBUS)
DP-Slave DP-Slave
#2 #3
- 130 -
B-62924EN/04 CONNECTION 4.PROFIBUS FOR THE STAND-ALONE TYPE Series 16i/18i/21i, Series 15i, and Power Mate i
- 131 -
4.PROFIBUS FOR THE STAND-ALONE TYPE Series 16i/18i/21i, Series 15i, and Power Mate i CONNECTION B-62924EN/04
4.1 CONFIGURATION
Ordering information
Name Code Remarks
PROFIBUS master board A02B-0265-J311 Master function only
PROFIBUS slave board A02B-0265-J310 Slave function only
- 132 -
B-62924EN/04 CONNECTION 4.PROFIBUS FOR THE STAND-ALONE TYPE Series 16i/18i/21i, Series 15i, and Power Mate i
4.2 INSTALLATION
When using the PROFIBUS board, the installation conditions for the
CNC control unit in which the board is installed (environmental
conditions in the cabinet) must be observed.
- 133 -
4.PROFIBUS FOR THE STAND-ALONE TYPE Series 16i/18i/21i, Series 15i, and Power Mate i CONNECTION B-62924EN/04
CN1
CN2
- 134 -
B-62924EN/04 CONNECTION 4.PROFIBUS FOR THE STAND-ALONE TYPE Series 16i/18i/21i, Series 15i, and Power Mate i
Network 1 (PROFIBUS)
CNC system
CNC main board
DP-Master
PROFIBUS master #1
Option slot function board JN1
PROFIBUS slave
function board JN2
DP-Slave
#4
DP-Master
#1
Network 2 (PROFIBUS)
DP-Slave DP-Slave
#2 #3
- 135 -
4.PROFIBUS FOR THE STAND-ALONE TYPE Series 16i/18i/21i, Series 15i, and Power Mate i CONNECTION B-62924EN/04
When axis control card C is specified for the Power Mate i, there are
restrictions on connection of FANUC PROFIBUS-DP boards.
1) When the FANUC PROFIBUS-DP Master or Slave board is
used
Connect the FANUC PROFIBUS-DP board to slot 2 (upper slot)
of the Power Mate i to use the board.
NOTE
1 If a PROFIBUS-DP board is connected to slot 1
(lower slot), a bus connector manufactured by
Siemens interferes with the optical connector of axis
control card C.
2 The specifications of axis control card C for the
Power Mate i are A02B-0259-H021 to A02B-0259-
H024. With an axis control card for the Power Mate i
added following axis control card C, the same
restrictions as with axis control card C are put on
connection of FANUC PROFIBUS-DP boards.
- 136 -
B-62924EN/04 CONNECTION 5.PROFIBUS FOR THE Power Mate-D/H
- 137 -
5.PROFIBUS FOR THE Power Mate-D/H CONNECTION B-62924EN/04
PROFIBUS PROFIBUS
at previous at next
stage stage
Power Mate-D/H
CN2
J139
Machine
CE49
NOTE
The PROFIBUS card is incorporated in the Power
Mate-D/H. CN2 and CE49 are in the lower section of
the unit.
Ordering information
Name Code Remarks
PROFIBUS card A02B-0166-H100 Power Mate-D
PROFIBUS card A02B-0211-J100 Power Mate-H
- 138 -
B-62924EN/04 CONNECTION 5.PROFIBUS FOR THE Power Mate-D/H
When using the PROFIBUS card in the Power Mate-D/H, observe the
installation conditions for the Power Mate-D/H.
- 139 -
5.PROFIBUS FOR THE Power Mate-D/H CONNECTION B-62924EN/04
5.3 SIGNALS
7 6 5 4 3 2 1 0
X1002 *DEC6 *DEC5 *DEC4 *DEC3 *DEC2 *DEC1
CE49- B10 A10 B09 A09 B08 A08 B07 A07
X1000.0, X1000.1, X1000.2, and X1000.7 are common-switchable
DC input signals B.
X1002.0, X1002.1, X1002.2, and X1002.7 are common-switchable
DC input signals B.
X1000.3 to X1000.6 and X1002.3 to X1002.6 are DC input
signals B.
NOTE
To use the above functions (*ESP, *RILK, SKIPn,
*DECn), set bit 3 (BIO) of parameter No. 3001 and
parameter No. 3005.
X1001, X1003 to X1031, X1064, and above cannot
be used.
NOTE
1 Y1000.2 to Y1000.7, Y1001 to Y1031, Y1064, and
above cannot be used.
2 Refer to Item for "Input/Output Signal Specifications"
in the "FANUC Power Mate-Model H Connection
Manual" for an explanation of the rules governing
input/output signals.
3 The maximum load current for the source-type
output signal is 1.4 A.
- 140 -
B-62924EN/04 CONNECTION 5.PROFIBUS FOR THE Power Mate-D/H
5.4.1 Overview
PROFIBUS card
CE49
34-pin ribbon cable connector
A B
Hirose HIF3BA-34D-2.564R
01 +24E +24E
02 X1000.0 X1000.1
03 X1000.2 X1000.3
04 X1000.4 X1000.5
05 DIC1 X1000.7
06 X1000.6 DOC Machine-side power
07 X1002.0 X1002.1 Female J139
Male
1. +24E (output)
24VDC supplied to the Power Mate main unit is sent as a DI signal via a fuse.
Do not connect any 24V output from an external power supply to this pin. Also, do not connect it to
DOC.
- 141 -
5.PROFIBUS FOR THE Power Mate-D/H CONNECTION B-62924EN/04
- 142 -
B-62924EN/04 CONNECTION 5.PROFIBUS FOR THE Power Mate-D/H
Power Mate
Pin number
Example of connection +24E Bit number
+24E CE49(A01, B01)
Address number
CE49(A02)
X1000.0
l l
CE49(B02)
X1000.1
l l
l
CE49(A03)
X1000.2
l l
l
CE49(B03)
X1000.3
l l
CE49(A04)
X1000.4
l l
l
CE49(B04)
X1000.5
l l
l
CE49(A06)
X1000.6
l l
l
CE49(B05)
X1000.7
l
l
DIC1 CE49(A05)
0V CE49(A17, B17)
l
- 143 -
5.PROFIBUS FOR THE Power Mate-D/H CONNECTION B-62924EN/04
Power Mate
Example of connection Pin number
+24E Bit number
+24E CE49(A01, B01)
Address number
CE49(A07)
X1002.0
l l
CE49(B07)
X1002.1
l l
l
CE49(A08)
X1002.2
l l
l
CE49(B08)
X1002.3
l l
CE49(A09)
X1002.4
l l
l
CE49(B09)
X1002.5
l l
l
CE49(A10)
X1002.6
l l
l
CE49(B10)
X1002.7
l
l
DIC2 CE49(A16)
0V CE49(A17, B17)
l
- 144 -
B-62924EN/04 CONNECTION 5.PROFIBUS FOR THE Power Mate-D/H
Power Mate
Pin number Example of
Bit number
connection
Voltage
Address CE49(B06, B15) DOC
number l regulator
Y1000.0
CE49(A11)
l l l
Y1000.1 CE49(B11)
l l l
CE49(A17, B17) 0V
- 145 -
IV. MAINTENANCE
B-62924EN/04 MAINTENANCE 1.PROFIBUS FOR THE Series 16/18-C
- 149 -
1.PROFIBUS FOR THE Series 16/18-C MAINTENANCE B-62924EN/04
Connector name
and other markings
PROFIBUS
DC/DC
MASTER
LSI chip
for JN1
communi-
cation
CPU
FG1
ROM LED1
LED2
DC/DC SLAVE
JN2
LSI chip
CPU for
FG2
communi
-cation
LED1
LED2
ROM LED3
Ordering information
Name Code Remarks
PROFIBUS board A16B-3200-0220 Master + Slave
- 150 -
B-62924EN/04 MAINTENANCE 1.PROFIBUS FOR THE Series 16/18-C
The PROFIBUS interface board for the Series 16/18-C has two
functions (DP-Master and DP-Slave functions). Each function uses
separate LED indicators.
SYSFAIL P-WKR
LED1
ALARM P-DPR
LED2 TOKEN
l: On
¡: Off
- 151 -
1.PROFIBUS FOR THE Series 16/18-C MAINTENANCE B-62924EN/04
SYSFAIL P-C32
LED1
ALARM P-WIN
LED2 RUN
- 152 -
B-62924EN/04 MAINTENANCE 2.LCD-MOUNTED TYPE PROFIBUS FOR THE Series 16i/18i/21i
- 153 -
2.LCD-MOUNTED TYPE PROFIBUS FOR THE Series 16i/18i/21i MAINTENANCE B-62924EN/04
CPU
ADD1
LED
CPU
ADD1
The master board and slave board are connected by the ADD1
connectors.
Ordering information
Name Code Remarks
PROFIBUS master board A20B-8100-0430
PROFIBUS slave board A20B-2100-0430 Daughterboard
- 154 -
B-62924EN/04 MAINTENANCE 2.LCD-MOUNTED TYPE PROFIBUS FOR THE Series 16i/18i/21i
- 155 -
2.LCD-MOUNTED TYPE PROFIBUS FOR THE Series 16i/18i/21i MAINTENANCE B-62924EN/04
- 156 -
B-62924EN/04 MAINTENANCE 3.PROFIBUS FOR THE STAND-ALONE TYPE Series 16i/18i/21i, Series 15i, AND Power Mate i
- 157 -
3.PROFIBUS FOR THE STAND-ALONE TYPE Series 16i/18i/21i, Series 15i, AND Power Mate i MAINTENANCE B-62924EN/04
DC/DC
CPU
CPU
DC/DC
CN1
LSI chip for
communication
Ordering information
Name Code Remarks
PROFIBUS master board A20B-8100-0470
PROFIBUS slave board A20B-8100-0440
- 158 -
B-62924EN/04 MAINTENANCE 3.PROFIBUS FOR THE STAND-ALONE TYPE Series 16i/18i/21i, Series 15i, AND Power Mate i
CN1
LED2 LED1
NOTE
The face plate is indicated by the broken line.
- 159 -
3.PROFIBUS FOR THE STAND-ALONE TYPE Series 16i/18i/21i, Series 15i, AND Power Mate i MAINTENANCE B-62924EN/04
CN2
NOTE
The face plate is indicated by the broken line.
- 160 -
B-62924EN/04 MAINTENANCE 4.PROFIBUS FOR THE Power Mate-D/H
- 161 -
4.PROFIBUS FOR THE Power Mate-D/H MAINTENANCE B-62924EN/04
NOTE
The PROFIBUS card for the Power Mate consists
of two boards, SUB BOARD 1 and SUB BOARD 2.
- 162 -
B-62924EN/04 MAINTENANCE 4.PROFIBUS FOR THE Power Mate-D/H
NOTE
If an alarm is issued when the DPL/MDI is in use,
only the alarm code is displayed on the DPL/MDI.
- 163 -
SUPPLEMENT
B-62924EN/04 SUPPLEMENT A.SETTING WHEN EDITION 07 OR EARLIER OF SERIES 6557 IS USED
- 167 -
A.SETTING WHEN EDITION 07 OR EARLIER OF SERIES 6557 IS USED SUPPLEMENT B-62924EN/04
To use the master function, bus parameters and slave parameters must
be set, and addresses must be assigned.
The bus parameters are referenced by the network, and the slave
parameters are set for each slave. In address assignment, PMC
addresses used by the DP-Master to transfer DI/DO signals to and
from each DP-Slave are set.
The methods of setting the parameters are described below.
Procedure (CRT/MDI)
(1) Press function key <SYSTEM>, then press soft key [PMC] to
switch to the PMC screen.
Screen A-1
- 168 -
B-62924EN/04 SUPPLEMENT A.SETTING WHEN EDITION 07 OR EARLIER OF SERIES 6557 IS USED
Screen A-2
- 169 -
A.SETTING WHEN EDITION 07 OR EARLIER OF SERIES 6557 IS USED SUPPLEMENT B-62924EN/04
Pressing soft key [BUS] on Screen A-2 displays Screen A-3 to enable
bus parameter setting. The bus parameters consist of two pages. Use
the page keys to switch between the pages.
Screen A-3
- 170 -
B-62924EN/04 SUPPLEMENT A.SETTING WHEN EDITION 07 OR EARLIER OF SERIES 6557 IS USED
Soft key [INIT] on Screen A-3 initializes the bus parameters to the
standard values used when the transfer rate is 12 Mbps.
CAUTION
To change the transfer rate from 12 Mbps to a
different value, set the bus parameters again
according to Table A-2, "Bus Parameter Settings
Corresponding to Each Transfer Rate" in this
section.
Screen A-4
- 171 -
A.SETTING WHEN EDITION 07 OR EARLIER OF SERIES 6557 IS USED SUPPLEMENT B-62924EN/04
Table A-1 summarizes the bus parameters. Table A-2 lists the bus
parameter values to be set for each transfer rate. For details, refer to
the following documents issued by PROFIBUS Nutzerorganisation
e.V.:
¡ PROFIBUS STANDARD DIN 19 245 Part 1
This document describes data transfer, access methods, protocols,
and interfacing with the application layer.
¡ Draft Standard PROFIBUS-DP DIN 19 245 Part 3
This document describes an abstract model of the PROFIBUS-
DP communication function, and so forth.
- 172 -
B-62924EN/04 SUPPLEMENT A.SETTING WHEN EDITION 07 OR EARLIER OF SERIES 6557 IS USED
- 173 -
A.SETTING WHEN EDITION 07 OR EARLIER OF SERIES 6557 IS USED SUPPLEMENT B-62924EN/04
NOTE
For multiple master communication, satisfy the
following conditions:
- The value set for 1:FDL ADD for a master station is
not used as another master station number.
- The same values are set for bus parameters 2 to 11
for all master stations.
- When a larger value is set for T SET, T SL is larger
than T ID1.
(T ID1 = 33 + 2 + 2 × T SET + T QUI)
- 174 -
B-62924EN/04 SUPPLEMENT A.SETTING WHEN EDITION 07 OR EARLIER OF SERIES 6557 IS USED
CAUTION
When setting slave parameter data, pay careful
attention to the following points:
1 The slave parameters are available for 125 stations.
However, set the slave parameters for no more than
32 DP-Slaves for actual communication.
2 When using DP-Slaves provided by other
manufacturers, set the slave parameters according
to the GSD file attached to each DP-Slave.
3 When setting the slave parameters, carefully check
the slave number of each DP-Slave to be set.
Screen A-5
- 175 -
A.SETTING WHEN EDITION 07 OR EARLIER OF SERIES 6557 IS USED SUPPLEMENT B-62924EN/04
pressing soft key [DETAIL] when the cursor is placed at the item of
15 CONFIG DATA.) Detailed data as long as the number of bytes
specified in each of these items can be set.
NOTE
Before a DP-Slave manufactured by FANUC can be
connected, data dependent on the FANUC DP-Slave
must be set in the slave parameters. Usually, soft
key [INIT] can be used for initialization to enable a
FANUC DP-Slave to be connected. In 15 CONFIG
DATA, however, variable data dependent on the size
of DI/DO data exchanged with the DP-Slave must be
set. So, when setting 15 CONFIG DATA, see
Section A.3, "Setting the Slave Parameters for Using
a Slave Station Manufactured by FANUC."
Screen A-6
- 176 -
B-62924EN/04 SUPPLEMENT A.SETTING WHEN EDITION 07 OR EARLIER OF SERIES 6557 IS USED
Table A-3 summarizes the slave parameters. For details, refer to the
following documents issued by PROFIBUS Nutzerorganisation e.V.:
¡ PROFIBUS STANDARD DIN 19 245 Part 1
This document describes data transfer, access methods, protocols,
and interfacing with the application layer.
¡ Draft Standard PROFIBUS-DP DIN 19 245 Part 3
This document describes an abstract model of the PROFIBUS-
DP communication function, and so forth.
- 177 -
A.SETTING WHEN EDITION 07 OR EARLIER OF SERIES 6557 IS USED SUPPLEMENT B-62924EN/04
- 178 -
B-62924EN/04 SUPPLEMENT A.SETTING WHEN EDITION 07 OR EARLIER OF SERIES 6557 IS USED
Screen A-7
CAUTION
When assigning addresses, pay careful attention to the
following points:
1 Assign addresses to all DP-Slaves that are set to
ENABLE in the slave parameters.
2 Be careful not to assign duplicate addresses to a
DP-Slave.
3 Ensure that a specified DI data area, DO data area,
and diagnose data area do not overlap one another.
4 Ensure that the specified addresses do not overlap
an area used for a ladder program.
5 Use the R area only. (When using PMC-SB5, be
careful not to exceed R1499. When using PMC-SB6
or PMC-NB6, be careful not to exceed R2999.)
- 179 -
A.SETTING WHEN EDITION 07 OR EARLIER OF SERIES 6557 IS USED SUPPLEMENT B-62924EN/04
NOTE
Diagnose data is classified as standard diagnose
data and extended diagnose data. The DP-Slaves
manufactured by FANUC use standard diagnose
data (6 bytes) only. On the other hand, DP-Slaves
supplied by other manufacturers may use extended
diagnose data of more than six bytes. When using
DP-Slaves supplied by other manufacturers,
determine the size of the diagnose data by
referencing the GSD file of each DP-Slave.
- 180 -
B-62924EN/04 SUPPLEMENT A.SETTING WHEN EDITION 07 OR EARLIER OF SERIES 6557 IS USED
- 181 -
A.SETTING WHEN EDITION 07 OR EARLIER OF SERIES 6557 IS USED SUPPLEMENT B-62924EN/04
Soft key [INIT] on Screen A-7 clears the value of each address
assignment parameter (the address specification fields are set to
R0000). So, specify valid values.
- 182 -
B-62924EN/04 SUPPLEMENT A.SETTING WHEN EDITION 07 OR EARLIER OF SERIES 6557 IS USED
NOTE
Before a DP-Slave manufactured by FANUC can be
used, data dependent on the FANUC DP-Slave must
be set in the slave parameters of the DP-Master. So,
when setting the slave parameters of the DP-Master,
see Section A.3, "Setting the Slave Parameters for
Using a slave Station Manufactured by FANUC."
Procedure (CRT/MDI)
(1) Press function key <SYSTEM>. Then, press soft key [PMC] to
switch to the PMC screen.
Screen A-8
- 183 -
A.SETTING WHEN EDITION 07 OR EARLIER OF SERIES 6557 IS USED SUPPLEMENT B-62924EN/04
(3) Pressing soft key [SLAVE] on this screen displays Screen A-9.
Screen A-9
CAUTION
When assigning addresses, pay careful attention to the
following points:
1 Ensure that the specified DI and DO areas do not
overlap one another.
2 Ensure that specified addresses do not overlap an
area used for a ladder program.
3 Use the R area only. (When using the PMC-SB5, be
careful not to exceed R1499. When using the PMC-
SB6 or the PMC-NB6, be careful not to exceed
R2999.)
- 184 -
B-62924EN/04 SUPPLEMENT A.SETTING WHEN EDITION 07 OR EARLIER OF SERIES 6557 IS USED
CAUTION
Input and output described below indicate the input
and output viewed from the slave station,
respectively.
- 185 -
A.SETTING WHEN EDITION 07 OR EARLIER OF SERIES 6557 IS USED SUPPLEMENT B-62924EN/04
- 186 -
B-62924EN/04 SUPPLEMENT A.SETTING WHEN EDITION 07 OR EARLIER OF SERIES 6557 IS USED
- 187 -
A.SETTING WHEN EDITION 07 OR EARLIER OF SERIES 6557 IS USED SUPPLEMENT B-62924EN/04
NOTE
All settings indicated in Table A-6 are represented in hexadecimal.
- 188 -
B-62924EN/04 SUPPLEMENT A.SETTING WHEN EDITION 07 OR EARLIER OF SERIES 6557 IS USED
- 189 -
A.SETTING WHEN EDITION 07 OR EARLIER OF SERIES 6557 IS USED SUPPLEMENT B-62924EN/04
#Profibus_DP
Vendor_Name = "FANUC"
Model_Name = "FANUC CNC"
Revision = "1.0"
Ident_Number = 0x00CB
Protocol_Ident =0
Station_Type =1
FMS_supp =0
Hardware_Release = "Release 1.0"
Software_Release = "Release 3.0"
9.6_supp =1
19.2_supp =1
93.75_supp =1
187.5_supp =1
500_supp =1
1.5M_supp =1
3M_supp =1
6M_supp =1
12M_supp =1
MaxTsdr_9.6 = 60
MaxTsdr_19.2 = 60
MaxTsdr_93.75 = 60
MaxTsdr_187.5 = 60
MaxTsdr_500 = 100
MaxTsdr_1.5M = 150
MaxTsdr_3M = 250
MaxTsdr_6M = 450
MaxTsdr_12M = 800
Redundancy =0
Repeater_Ctrl_Sig =2
24V_Pins =0
;
- 190 -
B-62924EN/04 SUPPLEMENT A.SETTING WHEN EDITION 07 OR EARLIER OF SERIES 6557 IS USED
- 191 -
A.SETTING WHEN EDITION 07 OR EARLIER OF SERIES 6557 IS USED SUPPLEMENT B-62924EN/04
LAS_Len = 32
;
Tsdi_9.6 = 70
Tsdi_19.2 = 70
Tsdi_93.75 = 70
Tsdi_187.5 = 70
Tsdi_500 = 150
Tsdi_1.5M = 200
Tsdi_3M = 250
Tsdi_6M = 450
Tsdi_12M = 800
;
Max_Slaves_supp = 32
;
- 192 -
B-62924EN/04 SUPPLEMENT A.SETTING WHEN EDITION 07 OR EARLIER OF SERIES 6557 IS USED
#Profibus_DP
Vendor_Name = "FANUC"
Model_Name = "FANUC CNC"
Revision = "1.0"
Ident_Number = 0x00A1
Protocol_Ident =0
Station_Type =0
FMS_supp =0
Hardware_Release = "Release 1.0"
Software_Release = "Release 3.0"
9.6_supp =1
19.2_supp =1
93.75_supp =1
187.5_supp =1
500_supp =1
1.5M_supp =1
3M_supp =1
6M_supp =1
12M_supp =1
MaxTsdr_9.6 = 60
MaxTsdr_19.2 = 60
MaxTsdr_93.75 = 60
MaxTsdr_187.5 = 60
MaxTsdr_500 = 100
MaxTsdr_1.5M = 150
MaxTsdr_3M = 250
MaxTsdr_6M = 450
MaxTsdr_12M = 800
Redundancy =0
Repeater_Ctrl_Sig =2
24V_Pins =0
;
- 193 -
A.SETTING WHEN EDITION 07 OR EARLIER OF SERIES 6557 IS USED SUPPLEMENT B-62924EN/04
NOTE
For a FANUC slave station, Module in the GSD file
matches slave parameter CONFIG DATA. The
DI/DO sizes for a FANUC slave station can be
changed without restrictions as long as they do not
exceed 32/32 bytes. For this reason, all of the
values to be specified for Module cannot be listed.
For the values to be specified for Module, see the
explanation of CONFIG DATA in Table A-6 in
Supplement A.3, "Setting the Slave Parameters for
Using a Slave Station Manufactured by FANUC."
- 194 -
B-62924EN/04 SUPPLEMENT A.SETTING WHEN EDITION 07 OR EARLIER OF SERIES 6557 IS USED
#Profibus_DP
Vendor_Name = "FANUC"
Model_Name = "FANUC Power Mate CNC"
Revision = "1.0"
Ident_Number = 0x00A1
Protocol_Ident =0
Station_Type =0
FMS_supp =0
Hardware_Release = "Release 1.0"
Software_Release = "Release 3.0"
9.6_supp =1
19.2_supp =1
93.75_supp =1
187.5_supp =1
500_supp =1
1.5M_supp =1
3M_supp =1
6M_supp =1
12M_supp =1
MaxTsdr_9.6 = 60
MaxTsdr_19.2 = 60
MaxTsdr_93.75 = 60
MaxTsdr_187.5 = 60
MaxTsdr_500 = 100
MaxTsdr_1.5M = 150
MaxTsdr_3M = 250
MaxTsdr_6M = 450
MaxTsdr_12M = 800
Redundancy =0
Repeater_Ctrl_Sig =2
24V_Pins =0
;
; Slave specific parameters
;
Freeze_Mode_supp =0
Sync_Mode_supp =0
Auto_Baud_supp =1
Set_Slave_Add_supp =0
User_Prm_Data_Len =0
Min_Slave_Intervall =1
Modular_Station =1
Max_Module =1
Max_Input_Len = 32
Max_Output_Len = 32
Max_Data_Len = 64
;
Module = "32 Byte Out, 32 Byte In" 0xC0,0x1F,0x1F
EndModule
Module = "28 Byte Out, 28 Byte In" 0xC0,0x1B,0x1B
- 195 -
A.SETTING WHEN EDITION 07 OR EARLIER OF SERIES 6557 IS USED SUPPLEMENT B-62924EN/04
EndModule
Module = "24 Byte Out, 24 Byte In" 0xC0,0x17,0x17
EndModule
Module = "20 Byte Out, 20 Byte In" 0xC0,0x13,0x13
EndModule
Module = "16 Byte Out, 16 Byte In" 0xC0,0x0F,0x0F
EndModule
Module = "12 Byte Out, 12 Byte In" 0xC0,0x0B,0x0B
EndModule
Module = " 8 Byte Out, 8 Byte In" 0xC0,0x07,0x07
EndModule
Module = " 4 Byte Out, 4 Byte In" 0xC0,0x03,0x03
EndModule
Module = " 2 Byte Out, 2 Byte In" 0xC0,0x01,0x01
EndModule
Module = "32 Byte Out, 1 Byte In" 0xC0,0x1F,0x00
EndModule
Module = " 1 Byte Out, 32 Byte In" 0xC0,0x00,0x1F
EndModule
;
NOTE
For a FANUC slave station, Module in the GSD file
matches slave parameter CONFIG DATA. The
DI/DO sizes for a FANUC slave station can be
changed without restrictions as long as they do not
exceed 32/32 bytes. For this reason, all of the
values to be specified for Module cannot be listed.
For the values to be specified for Module, see the
explanation of CONFIG DATA in Table A-6 in
Supplement A.3, "Setting the Slave Parameters for
Using a Slave Station Manufactured by FANUC."
- 196 -
B-62924EN/04 SUPPLEMENT B.SETTING WHEN SERIES 6556 IS USED
- 197 -
B.SETTING WHEN SERIES 6556 IS USED SUPPLEMENT B-62924EN/04
To use the master function, bus parameters and slave parameters must
be set, and addresses must be assigned.
The bus parameters are referenced by the network, and the slave
parameters are set for each slave. In address assignment, PMC
addresses used by the DP-Master to transfer DI/DO signals to and
from each DP-Slave are set.
The methods of setting the parameters are described below.
Procedure (CRT/MDI)
(1) Press function key <SYSTEM>, then press soft key [PMC] to
switch to the PMC screen.
Screen B-1
- 198 -
B-62924EN/04 SUPPLEMENT B.SETTING WHEN SERIES 6556 IS USED
Screen B-2
- 199 -
B.SETTING WHEN SERIES 6556 IS USED SUPPLEMENT B-62924EN/04
Pressing soft key [BUS] on Screen B-2 displays Screen B-3 to enable
bus parameter setting. The bus parameters consist of two pages. Use
the page keys to switch between the pages.
Screen B-3
- 200 -
B-62924EN/04 SUPPLEMENT B.SETTING WHEN SERIES 6556 IS USED
CAUTION
To change the transfer rate from 12 Mbps to a
different value, set the bus parameters again
according to Table B-2, "Bus Parameter Settings
Corresponding to Each Transfer Rate" in this
section.
Screen B-4
For details of the bus parameters, see Table A-1, "Bus Parameters," in
the previous chapter.
- 201 -
B.SETTING WHEN SERIES 6556 IS USED SUPPLEMENT B-62924EN/04
CAUTION
When setting slave parameter data, pay careful
attention to the following points:
1 The slave parameters are available for 125 stations.
However, set the slave parameters for no more than
32 DP-Slaves for actual communication.
2 When using DP-Slaves provided by other
manufacturers, set the slave parameters according
to the GSD file attached to each DP-Slave.
3 When setting the slave parameters, carefully check
the slave number of each DP-Slave to be set.
Screen B-5
- 202 -
B-62924EN/04 SUPPLEMENT B.SETTING WHEN SERIES 6556 IS USED
pressing soft key [DETAIL] when the cursor is placed at the item of
15 CONFIG DATA.) Detailed data as long as the number of bytes
specified in each of these items can be set.
NOTE
Before a DP-Slave manufactured by FANUC can be
connected, data dependent on the FANUC DP-Slave
must be set in the slave parameters. Usually, soft
key [INIT] can be used for initialization to enable a
FANUC DP-Slave to be connected. In 15 CONFIG
DATA, however, variable data dependent on the size
of DI/DO data exchanged with the DP-Slave must be
set. So, when setting 15 CONFIG DATA, see
Section A.3, "Setting the Slave Parameters for Using
a Slave Station Manufactured by FANUC."
Screen B-6
- 203 -
B.SETTING WHEN SERIES 6556 IS USED SUPPLEMENT B-62924EN/04
Screen B-7
CAUTION
When assigning addresses, pay careful attention to the
following points:
1 Ensure that a specified DI data area, DO data area,
and diagnose data area do not overlap one another.
2 Ensure that the specified addresses do not overlap
an area used for a ladder program.
3 Use the R area only. (When using PMC-SB5, be
careful not to exceed R1499. When using PMC-SB6,
be careful not to exceed R2999.)
- 204 -
B-62924EN/04 SUPPLEMENT B.SETTING WHEN SERIES 6556 IS USED
CAUTION
Always set even-numbered bytes for DI SIZE and
DO SIZE.
NOTE
Diagnose data is classified as standard diagnose
data and extended diagnose data. When series
6556 of CONTROL SOFTWARE is used, only
standard diagnose data (6 bytes) can be detected.
- 205 -
B.SETTING WHEN SERIES 6556 IS USED SUPPLEMENT B-62924EN/04
Soft key [INIT] on Screen B-7 clears the value of each address
assignment parameter (the address specification fields are set to
R0000). So, specify valid values.
- 206 -
B-62924EN/04 SUPPLEMENT B.SETTING WHEN SERIES 6556 IS USED
The contents of this section are the same as those of Section A.2,
"SLAVE FUNCTION SETTING." See Section A.2.
CAUTION
When 6556 series of CONTROL SOFTWARE is
used, INPUT DATA SIZE = 0 or OUTPUT DATA
SIZE = 0 can be set on the slave function setting
screen, but communication is disabled in this case.
- 207 -
B.SETTING WHEN SERIES 6556 IS USED SUPPLEMENT B-62924EN/04
The contents of this section are the same as those of Section A.3, "
SETTING THE SLAVE PARAMETERS FOR USING A SLAVE
STATION MANUFACTURED BY FANUC." See Section A.3.
- 208 -
B-62924EN/04 SUPPLEMENT B.SETTING WHEN SERIES 6556 IS USED
The contents of this section are the same as those of Section A.4, "
GSD FILE OF THE FANUC CNCS." See Section A.4.
- 209 -
C.SETTING USING A PERSONAL COMPUTER SUPPLEMENT B-62924EN/04
- 210 -
B-62924EN/04 SUPPLEMENT C.SETTING USING A PERSONAL COMPUTER
CAUTION
On Windows NT 4.0, the remote communication
parameter download function cannot be used, which
is also described in the Softing PROFIBUS-DP
Configurator manual. Use Softing PROFIBUS-DP
Configurator on Windows 3.1, Windows 95, or
Windows 98.
- 211 -
C.SETTING USING A PERSONAL COMPUTER SUPPLEMENT B-62924EN/04
Screen C-1
NOTE
Check that a green check mark is displayed for the
set I/F board as shown in Screen C-1. If a red cross
is displayed for the set I/F board, proper remote
downloading cannot be performed. In this case,
check the installed software again.
- 212 -
B-62924EN/04 SUPPLEMENT C.SETTING USING A PERSONAL COMPUTER
Screen C-2
NOTE
When the I/F board type is PROFIcard, set a file for
Loadcard INI under Hardware Setup Files. The file is
stored on cardinst (dos/loadcard.ini) which is a
floppy disk provided by Softing. Specify the file.
- 213 -
C.SETTING USING A PERSONAL COMPUTER SUPPLEMENT B-62924EN/04
(1) Press function key <SYSTEM>, then press soft key [PMC] to
switch to the PMC screen.
(2) Pressing soft keys [PMCDGN], [IOCHK], and [PROFI] in the
stated order displays Screen C-3.
Screen C-3
CAUTION
Check that CONTROL SOFTWARE is Edition 08 or
later of series 6557 on Screen C-3.
For remote downloading, MASTER SOFTWARE is
required.
(3) Pressing soft key [MASTER] on this screen displays Screen C-4.
Screen C-4
- 214 -
B-62924EN/04 SUPPLEMENT C.SETTING USING A PERSONAL COMPUTER
(5) Turn the power to the FANUC master station, then on again.
Screen C-4 is displayed again. Press soft key [MODE].
Screen C-5 is displayed. On this screen, check that CURRENT
MODE is STOP.
Screen C-5
- 215 -
C.SETTING USING A PERSONAL COMPUTER SUPPLEMENT B-62924EN/04
Screen C-6
Screen C-7
On this screen, click Add to select the GSD file for each device
(master or slave station) to be used for PROFIBUS-DP
Configurator.
When the GSD file for each device is read correctly, it is added
to Import DDB list on Screen C-7.
- 216 -
B-62924EN/04 SUPPLEMENT C.SETTING USING A PERSONAL COMPUTER
Screen C-8
Screen C-9
CAUTION
For Softing PROFIBUS-DP Configurator, the default
TTR value is 50000. Click Edit and change the TTR
value to 65000.
- 217 -
C.SETTING USING A PERSONAL COMPUTER SUPPLEMENT B-62924EN/04
Screen C-10
Screen C-11
- 218 -
B-62924EN/04 SUPPLEMENT C.SETTING USING A PERSONAL COMPUTER
The format for the FANUC slave stations is used for the module
names in Available Modules on Screen C-11.
CAUTION
For a FANUC slave station, set only one item for
Current Slots.
(7) Select the Settings tab on Screen C-11. Screen C-12 is displayed.
Screen C-12
CAUTION
For setting for a FANUC slave station, change the
values for the following two parameters:
- Set 55 for Min. Station Delay Responder on Screen
C-12.
- With PROFIBUS-DP Configurator, the value set for
Watchdog Time cannot be changed. After remote
downloading, set WD FACT1 = WD FACT2 = 10
directly on the slave parameter setting screen of the
FANUC master station.
- 219 -
C.SETTING USING A PERSONAL COMPUTER SUPPLEMENT B-62924EN/04
Screen C-13
CAUTION
Pay careful attention to the following points:
- The station number specified for Station Address on
Screen C-13 is used when PROFIBUS-DP
Configurator is attached to the network. For this
reason, do not specify the station numbers of the
FANUC master station and other master and slave
stations on the network.
- Set the same baud rate as for the FANUC master
station or another master station on the network.
- When the baud rate is 19.2 or 9.6 kbps, set 10000
[msec] for Poll Timeout of PROFIBUS-DP
Configurator. At this time, the values set for Poll
Timeout for the FANUC master station or another
master station on the network need not be changed.
Screen C-14
- 220 -
B-62924EN/04 SUPPLEMENT C.SETTING USING A PERSONAL COMPUTER
CAUTION
Pay careful attention to the following two points:
<1> For Softing PROFIBUS-DP Configurator, the
default TTR value is 50000. Change the TTR
value to 65000.
<2> Change the values of the following three
parameters on Screen C-14 only when the baud
rate is 12 Mbps:
- Min. St. Delay Resp. : 11 → 13
- Max. St. Delay : 800 → 802
- Quiet Time : 9 → 12
At this time, the values set for these three
parameters for the FANUC master station or
another master station on the network need not
be changed.
CAUTION
Remote downloading overwrites the bus parameters
and slave parameters set on the FANUC master
station.
Setting for address assignment cannot be
performed with PROFIBUS-DP Configurator. After
completion of remote downloading, perform setting
for address assignment and turn the power off, then
on again.
- 221 -
B-62924EN/04 INDEX
INDEX
<Number> <L>
16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C....... 13 LCD-MOUNTED TYPE PROFIBUS FOR THE Series
16i/18i/21i .............................................................. 153
<A>
LED INDICATORS AND THEIR MEANINGS
ALARM MESSAGES AND MEANINGS ................... 163
................................................................ 151, 155, 159
APPLICABLE MODELS................................................. 5
LED Indicators of the DP-Master Function.......... 155, 159
<B> LED Indicators of the DP-Slave Function ............ 156, 160
BUILDING A SAFE SYSTEM...................................... 93
<M>
Built-in I/O Machine Interface ..................................... 140
MASTER FUNCTION SETTING............ 15, 61, 168, 198
BUILT-IN I/O MACHINE INTERFACE..................... 141
MASTER FUNCTIONS................................................... 8
Bus Parameter Setting............................... 18, 62, 170, 200
Master Station Setting..................................................... 99
<C> Mounting the Adapter Unit........................................... 126
CABLE CONNECTION .............................................. 112 Mounting the Board.............................................. 125, 133
Cable Installation.......................................................... 117
<N>
CABLE LENGTH AND TRANSFER RATE............... 110
NOTES ON CONNECTING PROFIBUS BOARDS FOR
CABLE SHIELDING ................................................... 114
THE Power Mate i.................................................. 136
COMPLETE CONNECTION DIAGRAM........... 130, 135
COMPONENT LAYOUT ............................ 150, 154, 158 <O>
CONFIGURATION...................................... 116, 122, 132 ORGANIZATION ............................................................ 4
CONNECTING THE PROFIBUS FUNCTIONS......... 107 OVERVIEW OF PROFIBUS-DP FUNCTIONS ............. 6
Connection between the PROFIBUS Board and Adapter
<P>
Units ....................................................................... 126
Power Mate-D/H............................................................. 87
CONNECTION DIAGRAM................................. 120, 138
PROFIBUS Board Connector Layout........................... 119
CONNECTOR.............................................................. 111
PROFIBUS CABLE PARAMETERS .......................... 109
Connector Layout ................................................. 128, 134
PROFIBUS CONNECTION ........................................ 108
<D> PROFIBUS DRAWING NUMBER ............................. 162
Details of DI Connection .............................................. 143 PROFIBUS FOR THE LCD-MOUNTED TYPE Series
Details of DO Connection ............................................ 145 16i/18i/21i .............................................................. 121
DP-Master Function LED Indicators............................ 151 PROFIBUS FOR THE Power Mate-D/H ............. 137, 161
DP-Slave Function LED Indicators .............................. 152 PROFIBUS FOR THE Series 16/18-C ................. 115, 149
Environmental Conditions............................ 117, 125, 133 PROFIBUS FOR THE STAND-ALONE TYPE Series
ENVIRONMENTAL CONDITIONS........................... 139 16i/18i/21i, Series 15i, and Power Mate i ...... 131, 157
EXAMPLE OF CONFIGURATION.............................. 98 PROFIBUS Interface .................................................... 140
EXAMPLE OF CONNECTION..................................... 97
<S>
<G> SAFETY PRECAUTIONS .............................................s-1
GSD FILE OF THE FANUC CNCS .. 51, 81, 90, 189, 209 Series 15i-A .................................................................... 59
Setting for Address Assignment................ 27, 71, 179, 204
<I>
Setting for Operation mode............................................. 31
INSTALLATION ......................................... 117, 125, 133
i-1
INDEX B-62924EN/04
<T>
TERMINATING RESISTOR ....................................... 113
<U>
Updating DI/DO Data for the Master Function .............. 33
Updating DI/DO Data for the Slave Function ................ 45
i-2
Revision Record
01 Aug., 1996