Back Deck
March 31st, 2011
509 ITM
Intelligent Transformer Monitor
Front Panel
RS-485 Output
Digital output for
MODBUS, DNP, and
IEC 60870
communications RS-485 Aux Input
Digital input for direct
Analog Outputs winding monitoring
4 programmable, and other advanced
magnetically isolated, sensors
current loops for
integration with
SCADA systems
Side Panel
Ethernet Port
For IEC61850 and other protocols
over Ethernet and for remote
USB 2.0 Port monitoring via web browser
For logged data download and
upload of new configuration files
via USB flash drive
(No PC required)
Output (AC/DC)
Input (pot) Input (RTD)
Oil Temperature : e.g. AKM345 GEN2
Oil Level Indicator Direct Winding Simulation:
e.g. AKM345 DW
Direct Winding temperature via Ambient Temperature
Fibre
Rapid Pressure Detection e.g. RPRR
509ITM System Overview
Hardware Features
• The complete transformer monitoring system can monitor
parameters such as:
– Liquid Temperatures (Main Tank Top or Bottom, Load Tap Changer)
– Winding Temperatures
– Ambient Temperatures
– Winding Current
– Cooling Bank Currents
– A variety of parameters from transducers such as Tank Pressure, or
Dissolved Gas in Oil analysis
9
509 ITM System Overview
Hardware Features
• Sixteen (16) inputs to monitor RTD, CT, voltage, or digital inputs
• Eight (8) form C adjustable relays (DOs) to operate:
– Cooling equipment
– Signal alarms
– Provide trip functions, depending on transformer conditions
• Four (4) DC output Loops (AOs) for SCADA system use
– 0-1ma or 4-20 ma
• Digital communication ports
– RS-232
– RS-485
• Mounting
– Can be mounted outdoors (heater available inside enclosure)
– In the transformer control cabinet
– In a 19 inch control rack
• Powered by a universal power supply
– 90-264 VAC 47-63 Hz single phase power
– 40-290 VDC
10
509 ITM System Overview
Software Applications
• 509 ITM Manager Software – Used for configuration
and calibration
11
Inputs
Up to 16 Configurable Inputs – 32 with QUALITROL Advantage
Fiber •Completely configurable to your specification
Ability to customize each input to take any of the •Field upgradable for future monitoring needs
following:
•Clip on CT is isolated from CT circuit surges
•RTDs (10 or 100 OHM)
•Easy installation of all external sensors (non
•CTs (for calculated winding temperature) intrusive sensors, universal power supply and
•Fiber optic direct winding temperature sensors mounting kits)
(16)
Customer Benefit
•CTs (for AC current measurement)
One device that meets all application needs
•Potentiometer (for level gauges) while still being quick and easy to install.
•0-1mA or 4-20mA input
•Switch contact detection (powered or dry)
•AC voltage (0-140V or 0-320V)
•DC Voltage (0-100mA or 0-10V)
•Tap position
Input Modules
Input
Selection
CT Input
Module Setup
Type
Selection
and Name Calculated
Winding
Custom Setup
Scaling of
Input
Communication
Communication Ports
•RS-232 (for setup/local communication)
•USB 2.0 (1 for setup, 1 for data download)
•RS-485 4 wire (for protocols)
•Fiber optic with echo and repeat (protocols)
•Ethernet (web interface, protocols)
Protocols
•DNP 3.0
•IEC 61850, IEC 60870
•MODBUS
QUALITROL Advantage
•Up-to-date communication features and
protocols for integration into any data network
Customer Benefit
Wide array of communication options to ensure
the remote accessibility of information
Mounting Options
Weather Proof Enclosure
NEMA 3R (vented), UV stabilized, Corrosion proof
Panel Mount
For mounting in control cabinet
QUALITROL Advantage
•Flexible mounting options for any application
Customer Benefit
Easily mount device where most convenient
during installation
Display
Local Easy to Read Display
Easy to read, two line, 16 alphanumeric
character LCD display with back light
Character size: 0.38” (9.66mm) high x 0.19”
(4.84mm) wide
QUALITROL Advantage
•Easy to read key information at a glance
•Many settings can be changed via key pad
Customer Benefit
Most common features and information are
available locally without a PC
Fan Bank Control
Fan Bank Switching
Alternates first-on cooling fan bank
every 24 hrs.
QUALITROL Advantage
Equalize use and wear on fan banks
Customer benefit
Extended fan motor life, reduced repair
costs
A B
Fan Bank Control
Fan Bank Exercising
Activates fans on regular schedule
independent of temperature or alarm set
points – setup available on each relay
QUALITROL Advantage
For off-season or intermittently used fan
banks to reduce seizure due to non-use,
debris, nesting animals, icing, etc.
Customer Benefit
Reliable cooling when needed and
reduced maintenance costs
TransLife™
TransLife™
Provides a dashboard of key
transformer life information including
consumed life, historical temperatures,
and predictive loading temperature
estimations for each individual winding
QUALITROL Advantage
•Know the critical information about
your transformer’s life at a glance
•Critical forecast allows for predictive
loading based on the current operating
conditions
Customer Benefit
Provides the key transformer operating
characteristics that determine the health
of the transformer in a simple
dashboard style giving you the
information you need, not just data
Event Recorder
Event Recorder QUALITROL Advantage
•Data download possible without PC (flash drive)
•Up to 8 separate event triggers (logic matrix
controlled) •Reduce time to troubleshoot alarms with total
system snap shot records
•Selectable record type: time and date or total
system snapshot
Customer Benefits
•USB flash drive download via side port
Simplify root cause analysis after alarms
•Data download in MS Excel® format
Record Type
Matrix logic
event triggers
Seasonal Set Point
Seasonal Set Point
•Adjusts the set point to compensate for
changing seasonal weather conditions.
•Example: for the warmer summer months
when the cooling system is not as efficient due
to higher ambient temperatures, one might
enter a Seasonal Set point value of 70°C for a
cooling bank that is normally set to actuate at
80° C
QUALITROL Advantage
Save time by automatically enabling different
set points based on the date/time of year
Customer Benefit
Efficiently optimize set points for varying
cyclical weather conditions based on the
date/time of year
Ambient Temperature Forecast
Ambient Temperature Forecast
•Measures ambient temperature for a specified
amount of time and allows you to adjust the set
point for relay operation during forecasted
periods of high temperatures
•Similar to Seasonal Set Point feature except
that the Seasonal Set Point is used for a
specific period of time, such as summer, while
the Ambient Temperature Forecast is used for a
specific condition, for example, a heat wave
QUALITROL Advantage
Save time by automatically enabling different
set points based on prolonged ambient
conditions
Customer Benefit
Efficiently optimize set points for varying
cyclical weather conditions based on ambient
conditions
509 ITM Translife Improvement
509 ITM Expansion
Overview
RS-485 Output
Digital output for
MODBUS, DNP, and
IEC 60870
communications RS-485 Aux Input
Digital input for direct
Analog Outputs winding monitoring
4 programmable, and other advanced
magnetically isolated, sensors
current loops for
integration with
SCADA systems
Back Panels 509 + Exp
Module Input Ports
8 Modular inputs on each for maximum flexibility in monitoring inputs on each panel
• For those applications requiring more than eight input modules Qualitrol offers an Expansion
Module that will accept an additional eight input modules doubling the input capability of the 509
ITM unit.
• The Expansion Module uses the same input modules described in the hardware section of the
manual IST 099-1 and all the software features of the standard input modules apply to these
additional inputs (e.g. controlling relays, data logging, driving output current loops, etc.).
• The Expansion Module communicates to the 509 ITM unit through a digital cable/wiring and has
the same input power supply range as the 509 ITM unit.
• NOTE: When first applying power to the 509ITM and Expansion Module it may take up to 45
seconds for the microprocessors to establish communications before the input modules installed
on the Expansion Module to take affect (e.g. on the LCD display, control relays, etc.) in the
509ITM unit.
• NOTE: After establishing communications any changes in the Expansion Module inputs will be
reflected in the 509 ITM within 15 seconds. Therefore if the measurement of any parameter is
time critical, Qualitrol recommends installing that input module directly in the 509 ITM.
Inputs
Up to 16 Configurable Inputs – 32 with QUALITROL Advantage
Fiber •Completely configurable to your specification
Ability to customize each input to take any of the •Field upgradable for future monitoring needs
following:
•Clip on CT is isolated from CT circuit surges
•RTDs (10 or 100 OHM)
•Easy installation of all external sensors (non
•CTs (for calculated winding temperature) intrusive sensors, universal power supply and
•Fiber optic direct winding temperature sensors mounting kits)
(16)
Customer Benefit
•CTs (for AC current measurement)
One device that meets all application needs
•Potentiometer (for level gauges) while still being quick and easy to install.
•0-1mA or 4-20mA input Customer able to utilize a further 8 flexible
inputs to a total of 16 on the 509 ITM.
•Switch contact detection (powered or dry)
•AC voltage (0-140V or 0-320V)
•DC Voltage (0-100mA or 0-10V)
•Tap position
Input Modules
Input
Selection
CT Input
Module Setup
Type
Selection
and Name Calculated
Winding
Custom Setup
Scaling of
Input
Expansion Communication
EARTH GROUN D
TB21
1
TB14 TB13
IN PUT MODULE 10 3 INPUT MODULE 9 3
2 5 4 3 2 1 TB
22
2
EARTH GROUN D
VACC N EUT IN PUT (- )
1 1
I
NU
PN94A<<N
UI00T
TV--TXXF
PE
OS
WAVV:AA:
ELAD T
R ,
:
TB14
R6
TB15 ︵ ︶
22AXXU
40E
CC TT.
4
7
-
6
3
H
Z
.
IN PUT MODULE 11 3 INPUT MODULE 10 3
9G
W
2 2
WWE
SS0
ADA
CCM
IIP
N
T2
NS
1 1
L
I
E
I
NU
PN94A<<N
UI
TV0
PR
OS6
WAVVE
ELA
R C
:
E-
TB15 ︵ ︶
2-
49
,C SS0
4
7
-
6
3
H
Z
.
TB16 3
INPUT MODULE 11
0T
2T
0GWWS
D T
IN PUT MODULE 12 3
11.14
AX
:AAE
2
XXF
TT2
A
CCP
I
NI
2 TB21
T
D
N
1
[283.0]
L
I
E
U
:
.
A
M
S
1 3 2 1
TB16
T/ RXD- (A)
T/ RXD+ (B)
SIGN AL GROUN D
TB17 INPUT MODULE 12 3
IN PUT M ODULE 13 3
11.64 2
2
1
TB21
3 2 1
1
[295.6]
T/ RXD- (A)
T/ RXD+ (B)
SIGN AL GROUN D
TB17
TB18 INPUT MODULE 13 3
IN PUT MODULE 14 3
2
2
1
1
TB18
TB19 INPUT MODULE 14 3
IN PUT MODULE 15 3
2
2
1
1
MODEL N O. TB19
TB20 SERIAL N O. INPUT MODULE 15 3
IN PUT MODULE 16 3 MFG. DATE
2
2
1
1 MODEL NO.
TB20 SERIAL NO.
INPUT MODULE 16 3 MFG. DATE
2
1
4.23
[107.3]
(4) ? 22
[? .5] 6.51
[165.4]
QUALITROL Advantage
Detect damaged fan or pump motors, cooling system efficiency losses and blocked cooling lines
Customer Benefit
Prior to experiencing dangerous temperature levels, replace or repair key cooling system parts
based on predictive maintenance alarms
509 ITM
Load Tap Changer
Monitor
509 ITM LTC Monitor
LTC Monitor
Tracks all of the parameters of a load tap system to alert you of potential system problems:
•Monitors tap position, tap counts, make and break currents, motor actuations, and motor currents
•Monitors the differential temperature of the tap changer with respect to the main tank
•Two alarm priorities to signal if any or all parameters exceed selected set points
•Provides alarms for excessive actuations or total run time
QUALITROL Advantage
•Alerts you of incorrect loading and multiple tap counts signifying incorrect operation
•Detect coking of the tap contacts based on differential temperature (main tank vs. LTC tank)
•Alerts for prompting maintenance based on run time and excessive actuations
Customer Benefit
Prior to experiencing dangerous failures, replace or repair LTCs based on predictive maintenance
alarms
509 DW
Intelligent Transformer Monitor
with Direct Winding
509DW ITM with Direct Winding
Intelligent Transformer Monitor with Direct Winding
•Real time comparison of calculated (what it should be) and direct
winding (what it really is) temperatures to automatically alarm on
potential problems
•Maximize cooling efficiency with more accurate hot spot
temperature measurement
•Safely optimize loading without compromising transformer life
(more accurate winding temp)
•Avoid emergency shutdowns by monitoring long-term, gradual
transformer deterioration
QUALITROL Advantage
•Alerts you of discrepancies in calculated and direct winding
temperatures indicating incorrect operation
Customer Benefit
Know that the direct winding temperature is valid based on other
operating conditions such as load and cooling system status –
immediately be alerted if it is not
System Overview
What 505 / 509 ITM can do for you!
Deliver Reward
• Shorten problem resolution
• Increase
Review with Range of
productivity/efficiency of customer communication
transformer tools & features
More efficient
Meet Need
Need to
Unique to simplify Single product
customer multiple tools
Missed Trafo
Improved Trafo
warnings
Health
Unique to
Manage Risks customer
Guarantees engineers Address Reason
get health information Instant update on how
and take actions quickly Transformer is performing
Questions?
QUALITROL509 Record
43
Back-Up
Relay Outputs
8 Relay Outputs QUALITROL Advantage
Relay
Selection Cooling
Equipment
Exerciser
Matrix Logic
Control
Matrix relay logic
Up to 4 individual inputs with separate set point, hysteresis
and actuation direction can be used with AND, OR, and
MINUS logic in order to control a relay
Analog Outputs
4 Current loop (Analog) Outputs QUALITROL Advantage
•0-1mA or 4-20mA customer selectable •Flexible analog outputs for integration into
SCADA systems
•Magnetically isolated for maximum
resistance to stray current surges Customer Benefit
•Customer configurable output control Real time device with continuous monitoring
(direct signal, max, differential)
Current loop
Selection
Custom range
Matrix Logic
Control
Weatherproof Enclosure
Panel Mount
19” Rack Mount
Indicators and Interface
Local Control Interface
8 large buttons for easy use, even with gloves
QUALITROL Advantage
•Clear indication of alarm/relay status
•Easy to use local interface for information and
settings
Customer Benefit
Quick display and interpretation of the most
critical information on site
ITM Manager
ITM Manager
Next generation software:
•Simplifies setup with tab based setup
•Improved interface
•Offline setup
•New interactive and searchable help
features entire user manual
QUALITROL Advantage
Added flexibility for setup and use as an
evolution of the user friendly software of
the previous generation Remotes
interface
Customer Benefits
Retraining not required to integrate new
monitor, documentation easily accessed
within the software for reference when
questions arise
Integrated Data Logging
Data Logging
•Logs up to 20 separate parameters
•Selectable sample and store rate from 1min to
24 hrs (with sample types: MIN, MAX, AVG)
•Memory capable of storing 8 parameters at 1 hr
rate for 19 months
•32MB of non-volatile flash memory,
automatically rewriting oldest data when
memory runs out
•USB flash drive download via side port
•Data download in MS Excel® format
QUALITROL Advantage
•Data download possible without PC (flash drive)
•Keep data for long term trending in your most
remote areas without communications
Customer Benefits
Simplify root cause analysis after alarms and Time left before
long term trending for predictive maintenance memory overwritten
509 ITM Cooling Monitor
509 ITM LTC Monitor Alarms
LTC Monitor Tap Position Values
509 Test Specifications
Agency Approvals
•CE
•Hydro Quebec Accepted
Electrical Immunity
•Dielectric Isolation (Hi-Pot): 2500VAC 60 seconds
to ground
•Surge Withstand Capability (SWC): IEEE C37.90.1
•Conducted/Radiated Emissions: IEC 61000-6-1
•Conducted/Radiated Radio Frequency Immunity:
IEC 61000-6-2
•Special 5kV impulse model available
Safety:
•IEC 61010-1
Environment Specifications
Temperature
•Operating: -40C to +72C
•Storage: -50C to +80C
Humidity
•5%-90% (non-condensing)
• Protocols
• DNP 3.0
• IEC 61850, IEC 60870
• MODBUS
Benefits
• Easy to Install and Use
– Universal RTD probes fit all existing wells.
– Surface mount RTD´s for equipment without wells.
– Clamp on CT´s.
– Weather proof enclosure available.
– Universal power supply
– Easy to use windows based software.
Benefits
• High Reliability
– IEEE Surge with stand
• IEEE C37.90.1
– RF immunity
• IEC 61000-6-1 and 61000-6-2