Professional Documents
Culture Documents
Xu2020 PDF
Xu2020 PDF
Contents
1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2 Brief Introduction of the STATCOM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3 STATCOM in East Claydon, UK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.1 Application Background . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.2 System Structure and Operating Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.3 Main Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.4 System Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4 MMC STATCOM in Shanghai, China . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.1 Application Background . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.2 System Structure and Operating Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.3 Main Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.4 System Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5 STATCOM in Cerro Navia, Chile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
5.1 Application Background . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
5.2 System Structure and Operation Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
5.3 Main Operation Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
5.4 System Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
S. Xu
HVDC and Power Electronics Department, Electric Power Research Institute of China Southern
Power Grid (EPRI of CSG), Guangzhou, China
e-mail: xusk@csg.cn
S. Wang
Rongxin Huiko (RXHK) Electric Technology Co., Ltd., Anshang, People’s Republic of China
e-mail: wangshaobo@rxhk.com
G. Zuo
XJ Group Co., Ltd., Xuchang, China
e-mail: 714381833@qq.com
C. Davidson
GE’s Grid Solutions Business – HVDC & FACTS, Stafford, UK
e-mail: Colin.Davidson@ge.com
M. Oliveira
System Lead Engineer, ABB, Västerås, Sweden
e-mail: marcio.oliveira@se.abb.com
R. Memisevic
System Perfomance and Connections, Power Link, Virginia, QLD, Australia
e-mail: rmemisevic@powerlink.com.au
G. Pilz
System Engineering and Network Studies for FACTS Installations Worldwide, Siemens,
Erlangen, Germany
e-mail: georg.pilz@siemens.com
B. Donmez
AMSC, Ayer, USA
e-mail: NetworkPlanning@amsc.com
B. Andersen (*)
Andersen Power Electronic Solutions Ltd, Bexhill-on-Sea, UK
e-mail: bjarne@andersenpes.com
Application Examples of STATCOM 3
Abstract
The chapter starts with a brief introduction of the STATCOM technology and then
provides a number of typical applications of the STATCOM from around the world.
Some application examples are general transmission system applications, where the
purpose of the STATCOM is to regulate and support the ac voltage and to minimize
the over- and undervoltages that may occur during various faults and event in the
network, including the commutation failure of large HVDC schemes. Some exam-
ples demonstrate the ability to improve the power quality, e.g., due to disturbing
loads such as arc furnaces, wind farms, single-phase tractions loads, etc. Some
STATCOM applications demonstrate the capability of the STATCOM to damp
power system oscillations and to increase the power capabilities of ac lines.
1 Introduction
This chapter starts with a brief overview of the design of the STATCOM. It then provides
a number of examples from around the world of the application of STATCOMs.
The following examples are included in this chapter:
1. A relocatable STATCOM in the UK, to help control the transmission network. It
was the first to use the “chain-link” converter, now known as the Modular
Multilevel Converter (MMC). This example was provided by Colin Davidson,
GE’s Grid Solutions Business, Colin.Davidson@ge.com.
2. China’s first chain-link (MMC) STATCOM, which was built in Shanghai to
demonstrate the benefits that a STATCOM can provide in an urban area
with high load density. This example was provided by Shukai Xu, Electric
Power Research Institute of China Southern Power Grid (EPRI of CSG),
xusk@csg.cn, and Guangjie Zuo, XJ Group Co., Ltd., 714381833@qq.com.
3. One STATCOM in Cerro Navia, Chile, provided to increase the dynamic
stability of the system and thereby allow the transmission of additional power
4 S. Xu et al.
through the grid. This example was provided by Marcio Oliveira, ABB,
email: marcio.oliveira@se.abb.com.
4. Four STATCOMs in Guangdong, China, which were built to support the multi-
infeed power system in Guangdong, by providing dynamic reactive power
support and to assist the HVDC recovery after commutation failures. This
example was provided by Shukai Xu, Electric Power Research Institute of
China Southern Power Grid (EPRI of CSG), xusk@csg.cn, and Shaobo Wang,
Rongxin Huiko (RXHK) Electric Technology Co., Ltd., wangshaobo@rxhk.
com.
5. Two STATCOMs in Inner Mongolia, China, to solve the problem of
sub-synchronous resonance and sub-synchronous oscillation, which were
caused by HVDC schemes and long ac lines with series compensation. This
example was provided by Shaobo Wang, Rongxin Huiko (RXHK) Electric
Technology Co., Ltd., wangshaobo@rxhk.com.
6. STATCOMs in the HVDC converter station in Yunnan, China, which were
provided to provide ac voltage support after commutation failures in the
HVDC scheme. These STATCOMs considerably improved the performance of
the HVDC schemes and the ac network. This example was provided by Shukai
Xu, Electric Power Research Institute of China Southern Power Grid (EPRI of
CSG), xusk@csg.cn, and Guangjie Zuo, XJ Group Co., Ltd., 714381833@qq.
com.
7. Two parallel connected STATCOMs in Aurangabad, India, to provide dynamic
reactive power compensation to improve the voltage quality and dynamic
stability of the transmission system. This example was provided by Shaobo
Wang, Rongxin Huiko (RXHK) Electric Technology Co., Ltd.,
wangshaobo@rxhk.com.
8. STATCOM in Alabama, USA, to improve the power quality, which had
decreased due to reduced short-circuit capacity in the regional network, and a
large Electric Arc Furnace (EAF) generating flicker, unbalance, and harmonics.
This contribution was provided by Marcio Oliveira, ABB, email: marcio.
oliveira@se.abb.com.
9. Four STATCOMs in Queensland, Australia, to provide compensation for the
single-phase load of heavy electric trains and to comply with the grid code
requirements. The STATCOM was chosen because of its much lower harmonic
output. This contribution was provided by Rizah Memisevic, Power Link
Australia, email: rmemisevic@powerlink.com.au and Georg Pilz, Siemens,
email: georg.pilz@siemens.com.
10. Hybrid STATCOM in Rourkela, India, to provide dynamic reactive power
compensation to improve the voltage quality and dynamic stability of the
transmission system. Note that this application is almost the same as number
7 above, but from another manufacturer. This contribution was provided by
Georg Pilz, Siemens, georg.pilz@siemens.com.
11. A STATCOM in Australia that is designed to enable an enlarged wind farm to
meet new grid code requirements. This contribution was provided by Bilgehan
Donmez, AMSC, NetworkPlanning@amsc.com.
Application Examples of STATCOM 5
by low-cost combined cycle gas turbine (CCGT) generation. The new CCGT
generation was located mainly in the North and East of England, closer to the
North Sea coast. By the mid-1990s, National Grid in the UK (NG) had become
concerned that the increased generation in the North of England would result in
increased power flows through the already congested Midlands to South transmis-
sion corridors, with a consequent large potential deficit of reactive power in the
South. Following a period of heavy investment in conventional Static Var Compen-
sators, as part of an overall scheme to provide reactive compensation in the South,
National Grid decided to provide a STATCOM-based compensation system at East
Claydon substation, strategically located on the 400 kV grid system, between
Birmingham and London.
Since National Grid were no longer in control of the location of new generation, it
was concerned that new compensation equipment could become redundant
“stranded assets” in the future as a result of future changes to the network. To
mitigate this risk, the new compensation system had to be capable of subsequent
relocation to other 400 kV or 275 kV substations with suitable site areas available.
Up to three relocations were envisaged over an equipment lifetime of 40 years
(Horwill et al. 2001).
400kV BUS
400/15.1
15.1kV BUS
The main technical parameters of STATCOM in the East Claydon substation are
shown in Table 1 (data from Woodhouse et al. 2001).
The available site area was limited, and accordingly a compact arrangement of the
compensation system was devised (Fig. 2). The total footprint of the STATCOM
8 S. Xu et al.
equipment was less than 1400 m2. To facilitate future relocation of the compensator,
should the need arise, each phase of the STATCOM is self-contained in a road-
transportable container, located in the top-right part of Fig. 2. The TSC valve,
associated controls, and other ancillary equipment are mounted in a similar container
shown in the center of the figure. The heat exchangers that reject the valve losses to
air are located on the right-hand side of the figure. All other switchyard-type
equipment is mounted, with associated connections, on metal frames to group
items together for ease of transport and reinstallation.
Further technical information about the East Claydon STATCOM can be found in
the ▶ “Technical Description of Static Compensators (STATCOM)” chapter.
The STATCOM mainly operates in steady-state constant voltage control mode and is
operated from the UK Grid Control Center.
Application Examples of STATCOM 9
The Shanghai Power Grid has a highly concentrated load and is one of the most
important load centers in China. Since 2001 there has been a continuous increase of
the power load in Shanghai, and an increasing proportion of the load is being provided
from remote locations. The supply from remote locations to Shanghai were increasing,
10 S. Xu et al.
resulting in the Shanghai Power Grid facing challenges including controllability and
instability problems. Due to constraints on resources and because of environmental
protection, local power plants, which could provide dynamic reactive power, were not
allowed to be built in urban areas. Consequently, the problem of lack of sufficient
dynamic voltage support in the load center of Shanghai arose. The 220 kV city
network also required dynamic reactive power support for the different district grids,
and the increasing air-conditioning loads further increased the risk of the occurrence of
voltage instability in the Shanghai Power Grid (LIU Wen-hua et al. 2008).
To demonstrate the benefits of STATCOMs, such as the improvement of power
quality and ensuring the safe and stable operation of power grid, Shanghai Electric
Power Grid Corporation decided in 2003 to install a pilot 50 Mvar STATCOM at
the Xijiao substation in the Huangdu district grid. The expected benefits were:
Tsinghua University, Shanghai Electric Power Company, and Xu Ji Electric Co., Ltd.
developed the first 50 Mvar MMC STATCOM in China. It was formally put into
operation at the Xijiao substation in Shanghai Huangdu District on February 28, 2006.
The SLD of the STATCOM is shown in Fig. 4. The main technical parameters and
performance data are shown in Table 2.
The layout of the STATCOM is shown in Fig. 5. The outdoor equipment includes
the 110 kV/10 kV transformer, the valve series reactor, and the water-cooling
radiator. The indoor equipment includes the three-phase converter, control cabinets,
monitoring cabinet and power supply cabinet, 10 kV switchgear, valve cooling
system, and its control and protection system.
Figure 6 shows one of the series reactors with oil cooling. The valve room is on
the right of the reactor, and the control room and other facilities are on the left.
Figure 7 shows one phase of the STATCOM valves, which can be seen to contain
ten MMC modules.
The STATCOM control and protection system is shown in Fig. 8, which includes
the monitoring cubicle (first right) and the control cubicle (second right).
The STATCOMs were designed with voltage control modes for steady state and
transient state. In the steady-state voltage control mode, the output reactive power
Application Examples of STATCOM 11
220kV/110kV 110kV/10kV
220kV Bus
35kV
A B C
LA
1 1 1 DA
R
2 2 2
3 3 RA
3 CD
LINKA
4 4 4
LINKC
LINKB
CCL
5 5 5 S
6 6 6
7 7 7
8 8 8
9 9 9 Link
10 10 10
+30Mvar +30Mvar B
Fixed capacitor Fixed capacitor
Group 1 Group 2
±50 Mvar
STATCOM
9m 4.3m 5m
surge arrester
LINKA
LINKB
LINKC
15m
Series Reactor 1
4m
determined by the rate of decrease of the grid voltage. As soon as the decrease rate of
the grid voltage exceeds the preset threshold, the STATCOM is switched to
the transient voltage control mode even if the grid voltage is still above the amplitude
threshold at this point.
The design estimates the voltage drop and speed up the response time of
the reactive power during faults. Once the STATCOM is switched into transient
state voltage control mode, after a preset duration of output of rated capacitive
reactive power, the output of the STATCOM will gradually decrease to the steady-
state output.
Field test results show that the installed STATCOM can output rated current. Figure 9
shows the 10 kV line current at rated operating conditions. The total harmonic
distortion rate is less than 5%.
A power step response test was also conducted. Figure 10 shows the three-phase
instantaneous reactive power at the substation busbar when changing the reactive
power reference from zero to rated capacitive power. It can be seen that the
0
–2000
–4000
0 4 8 12 16 20
t/ms
65
45
Q(10 Mv ar/div )
25
5
5 10 15 20
t (10 ms/div)
reactive power response time is very fast with an initial response in 3 ms followed by
an overshoot before finally settling to the ordered level at about 25 ms.
In 2006, the Huangdu district grid comprised twelve 220kV buses and twenty
load buses (35 kV and 110 kV), and the power load was 1552 MW. The test results
showed that the voltage increases at the 220 kV and 35 kV buses at the Xijiao
substation were 1.5% and 7.8% higher, respectively, when the installed STATCOM
provided output at the rated reactive power. This resulted in the shedding of loads
being reduced by up to 438 MW.
The Xijiao substation 50 Mvar STATCOM was a milestone for industrial-grade
STATCOM in China. It was the first STATCOM that employed the Modular
Multilevel Converter (MMC) concept in China. Subsequently, the MMC has become
the dominant converter alternative for the large capacity STATCOM in China. For
Huangdu district grid in Shanghai, the STATCOM has provided dynamic reactive
voltage support in case of faults and sudden increase in loads. At the same time, it
has provided valuable operating experience for the application and development of
future FACTS controllers.
The Central Interconnected System (CIS) serves the central part of Chile and
supplies power to approximately 90% of the Chilean population. Transelec S.A. is
the main transmission operator, owning and operating transmission facilities at
voltages from 500 kV down to 66 kV.
Similar to the situation in other parts of the world, a growing opposition to
the construction of new transmission infrastructure exists in Chile. Consequently,
Transelec S.A. investigated optimal means to utilize existing transmission facilities
to a higher degree of capacity. After the completion of feasibility studies, it was
decided to install FACTS controllers at critical points in the grid to increase the
dynamic stability of the system and thereby allow the transmission of additional
power through the grid.
The common tasks of the FACTS controllers installed in 2011 were the following:
• Regulate and control the 220 kV grid voltage under normal steady-state and
contingency conditions.
• Provide dynamic, fast reactive power response following system contingencies,
such as network short circuits and line or generator outages, particularly during
high power flow from Ancoa northward.
• Enable an increase of the power transfer capability of the grid.
16 S. Xu et al.
Polpaico
SVC
Cerro Navia
STATCOM
Polpaico 500 kV
Alto Jahuel
Ancoa 500 kV
220 kV
500 kV
Fig. 11 Location of FACTS devices in the Chilean Central Interconnected System (year 2011)
The normal mode of operation is automatic voltage control. The control system uses
a closed-loop system that controls the positive-phase sequence voltage at the
220 kV bus.
In manual control mode, the STATCOM operates with open-loop control. The
desired reactive power output is manually set by the operator, and the STATCOM
provides a constant output current. In this operation mode, the voltage reference
18 S. Xu et al.
follows the actual line voltage including slope correction, whereas at automatic
control mode, the reactive current power reference follows the reactive current
reference calculated by the voltage regulator. Therefore, transients in the STATCOM
output are avoided at transitions from one control mode to the other, providing a
bumpless transfer.
When the automatic voltage regulator is in operation, a higher level Mvar
regulator can also be activated. The control dynamics of the higher level is very
slow when compared to the voltage regulator, and its output signal is added to the
voltage reference signal in such a way that at steady state the STATCOM will remain
within a window defined by two limits, one at the capacitive range and one at the
inductive range. The main purpose of this function is to leave the controllable part of
the STATCOM, i.e., the voltage-source converter close to zero current at steady state,
leaving the whole converter dynamic range and its fast response to support the
network during system disturbances and recovery. When the STATCOM is controlled
to near-zero current, slower acting reactive power controllers in the ac network will
change their output to achieve the ac voltage required by the system operator.
The STATCOM has also the ability to compensate the voltage unbalance existing
at the Cerro Navia 220 kV bus. The negative-sequence voltage is measured on the
220 kV system and compensated by adding negative-sequence current in the VSC
converter control. The negative-sequence amplitude that can be counteracted by the
Application Examples of STATCOM 19
Fig. 14 Phase reactor connection to valve room and IGBT stack of Cerro Navia STATCOM
North equivalent
Quillota220 (8)
Polpaico500 (3)
Polpaico220 (7)
Lampa220 (9)
SVC
Cerronavia220 (6)
STATCOM
Cerronavia110 (10)
Chena220 (5)
Ajahuel220 (4)
Ajahuel500 (2)
500 kV
220 kV
Ancoa500 (1) 110 kV
66 kV
South equivalent 13.2 kV
Fig. 15 Studied network in the real-time simulator interfaced with the real control systems
As Cerro Navia STATCOM and Polpaico SVC projects were executed almost in
parallel, the factory acceptance tests of the control system in a real-time simulator
environment were performed simultaneously, employing the network setup shown
in Fig. 15. As the FACTS devices were electrically close to each other, this setup
allowed the verification of possible adverse control interactions between the SVC
and STATCOM during steady-state and dynamic conditions as well as providing
suitable settings for the control system of both compensators.
As an example, from the real-time simulator studies, Fig. 16 shows the behavior
at a solid single-phase fault with six-cycle duration at the Alto Jahuel 220 kV bus,
located two buses away from Cerro Navia. At the fault instant, the converter current
is inductive, compensating for the reactive power generated by the filters. The fault
causes a 20% voltage drop at the positive-sequence voltage at Cerro Navia 220 kV
bus. Therefore, the voltage regulator sets the maximum reference for the VSC
capacitive current, as shown in Plot c, providing a very fast 180 phase shift of
converter currents from reactive power absorption to generation. During the fault, it
is still important to keep the balance of the dc voltages of the positive and negative
Application Examples of STATCOM 21
Fig. 16 Single-phase fault at Alto Jahuel 220 kV bus. Plot a: Primary voltages at Cerro Navia
220 kV bus [p.u.]. Plot b: Positive-sequence voltage, Cerro Navia [p.u.]. Plot c: VSC current
reference [p.u.]. Plot d: VSC currents [kA]. Plot e: Converter dc voltages across positive and
negative poles [p.u.]
poles of the three-level converter, keeping the average dc voltage constant, to avoid
further discharge of the dc capacitor for prolonged faults. When the fault is released
at t = 0.22 s, the converter returns rapidly to its original inductive behavior, while the
22 S. Xu et al.
voltage ripple is reduced as the unbalance in the system voltages is eliminated after
fault clearing.
Since the commercial operation of the Cerro Navia STATCOM and Polpaico
SVC in 2011, the power transfer capability on the 500 kV corridor from Ancoa to the
north of Chile, earlier limited to 1400 MW by voltage stability concerns due to a
post-contingency scenario (loss of one transmission line), could be increased to
1600 MW. According to Transelec, this could also optimize the system operation,
allowing transfer from southern generation to the central zone of Chile.
As HVDC transmission capacity takes up a higher share of the West to East Power
Transmission in China, the interaction between HVDC and the existing ac network
has greatly changed the characteristics of the grid, especially the stability of the
system (Rao et al. 2016).
China Southern Power Grid (CSPG) is a typical long-distance bulk power
transmission system with paralleled ac and dc links. Up to 2015, there were seven
HVDC inverter lines feeding into this region. Up to 2020, there will be 11 HVDC
inverter lines feeding into this region, as shown in Fig. 17.
1
HVDC
HVDC Inverter
2 Inverter
3 60
59
9 4 Mumian 65 6 7 8
HVDC HVDC
Inverter Inverter 46
10 5
41
11 61 14 15
12 13 Dongguan
Beijiao Shuixiang 42 43 44 45 47
20 16
19
18
HVDC 21 HVDC 17
Inverter 22 Inverter
62 HVDC 56
30 64 48 54 55
32 Baoan
23 Inverter Shunde 49 53
63 31 50
25 24 29 33 HVDC inverter
52 Series compensator
28
34 37 Major power plant
26 36 35 Pumped storage power station
38 51 500kV transformer station
Nuclear power plant
39 40 The buses for STATCOM installation
27 57 58 according to 2015 power grid
The buses for STATCOM installation
according to 2020 power grid
Fig. 17 Single-line diagram of the 500 kV receiving-end power system with multiple STATCOMs
of the CSG in 2015
Application Examples of STATCOM 23
The four STATCOMs in this project were designed and owned by CSG; the
manufacturer is Rongxin Power Electronic Co.,Ltd. The first STATCOM was
commissioned at Dongguan 500 kV substation in August 2011.The second and
third STATCOMs were commissioned at Beijiao and Shuixiang 500 kV substation in
June 2013. The last STATCOM was commissioned at Mumian 500 kV substation in
October 2013.
The phase reactor of each STATCOMs is 12%, which is divided into two parts
that are located on either side of the valve. Each phase consists of 26 power modules.
Each module is an H-bridge structure and is equipped with a crowbar circuit to
bypass the module if an internal fault occurs.
The SLD of the 35 kV/200 Mvar STATCOM in Dongguan station is shown in
Fig. 18. The SLD of the other STATCOMs are the same as Fig. 18. Note that the
STATCOM consists of two STATCOMs.
35kV BUS
220/35
35kV BUS
#1 STATCOM #2 STATCOM
±100Mvar ±100Mvar
24 S. Xu et al.
The two STATCOMs have a common coordination controller, which balances the
reactive power balance and ensures that the parameters for the STATCOMs are the
same. If one of the STATCOMs fail, the other STATCOM will output the total
reactive power.
The coordination controller also controls eight breaker switched reactors and six
breaker switched capacitors, which are connected to the 35 kV busbar of two other
transformers. The shunt reactors are rated at 15 Mvar each, and the shunt capacitors
are rated at 50 Mvar each.
Each STATCOM can operate in the following control modes:
1. Steady-state constant reactive power control mode, a mode only used during
commissioning test.
2. Steady-state constant voltage control mode, the normal operation mode to control
the voltage of the 220 kV busbar.
Application Examples of STATCOM 25
3. Dynamic reactive power support mode, a mode that will be activated automati-
cally to output reactive current quickly when undervoltage or overvoltage occurs
at the 220 kV busbar.
4. Coordination control mode, a normal operation mode to coordinate with shunt
reactor and shunt capacitor.
5. Remote control mode, a special operation mode to work with Auto-Voltage-
Control system.
6. The two parallel STATCOMs normally receive the same control signals.
However, they can also operate independently.
The response of the STATCOM device was tested by a short-circuit test. The test is
done by short-circuiting one phase and earth with a line which quickly melts (a fuse
wire) (Xiao Leisi et al. 2015). The response of the STATCOM is shown in the
following figures (Li Chunhua et al. 2013).
A single-phase instantaneous earth fault was applied to one of the incoming lines.
The voltage and current responses at the 220 kVand 35 kV buses are shown in Fig. 21.
26 S. Xu et al.
Power Module
Fig. 21 Voltage curves of the 220 kV/35 kV buses and current curves of the STATCOM (the
curves are voltage of 220 kV, voltage of 35 kV, current of STATCOM #1, current of STATCOM #2,
respectively)
Figure 22 shows details of the 220 kV voltage in phase A and the current from
the STATCOM. The response time of STATCOM is 15.8 ms, and the fault detection
Application Examples of STATCOM 27
Fig. 22 The 220 kV bus voltage (blue), STATCOM three-phase current(dot plot), and instanta-
neous reactive current (red)
time including the delay of the controller is 6 ms. (Note:220 kV voltage base is
127 kV; STATCOM phase current base is 2857 A; instantaneous reactive current
base is 4040 A.)
The STATCOM has a specified overload capability as shown in Table 4. The
overload capability is not used, while the power system operates in steady state.
When the power system is in a transient state, the STATCOM overload capability is
automatically enabled.
The annual failure rate of the power module after the commissioning of the
STATCOM in Dongguan substation is 0.64%. According to the operating records,
the STATCOM has responded correctly to occurrences of ac fault and has supported
system recovery.
At start-up the STATCOM is operated with a small reactive power setting (e.g.,
5%) to avoid potential current distortion caused by insufficient control accuracy.
The rapid response of the reactive power compensation means that the
STATCOMs can effectively improve the voltage stability of the system, supporting
the voltage during recovery from commutation failures and speeding up the resump-
tion of power delivery, thereby improving the ability to receive power and withstand
faults in the grid.
The Hulunbuir Region in Inner Mongolia is an area that largely relies on coal-based
generation. The Guohua Baodian and E’wenke power plants are connected to the
Hulunbuir HVDC converter station through an 500 kV substation (substation 6).
Yi-min phase III is connected directly to the converter station. The detailed infor-
mation is shown in Fig. 23.
28 S. Xu et al.
The two STATCOMs in this project are designed and owned by Guohua Electric
Power Co.,. the manufacturer is Rongxin Power Electronic Co., Ltd. The STATCOM
was put into operation in March 2014.
The converter is a MMC structure, and each power module is an H-bridge structure
and is equipped with a crowbar circuit to bypass the module in case of a fault.
The SLD of the two STATCOMs is shown in Fig. 25.
The main technical parameters of the two STATCOMs are shown in Table 5.
One of the Guohua Baodian STATCOM valves is shown in Fig. 26.
The layout of the two STATCOMs is shown in Fig. 27. The valves, control and
protection system, and the valve cooling system are arranged indoor. The reactors
are arranged outdoor.
The annual failure rate of the power module since the commissioning of the
STATCOM is 0.51%. The STATCOM meets the technical requirements (less than
three forced outage per year).
The Yongfu 500 kV DC Transmission Project was China’s first provincial HVDC
transmission project. It serves as the main power transmission channel in the Yunnan
Province and is an important part of CSG’s west-to-east power transmission network.
Application Examples of STATCOM 33
0.05
–0.05
–0.1
0 1 2 3 4 5 6 7 8 9 10
Time(s)
525/35 525/35
system, a 300 Mvar STATCOM was proposed and has been installed at the Funing
converter station, to meet the dynamic reactive power support requirements for the ac
system. This ensured that the dc transmission system could resume smooth operation
after N-1 ac faults, thereby enhancing the operational reliability of the HVDC system.
The three parallel STATCOMs in this project are designed and owned by CSG. The
manufacturers were NREC Co., Ltd. (#1 STATCOM and #2 STATCOM) XJ Group
Co., Ltd. (#3 STATCOM) (YAO Weizheng et al. 2018). The site installation and tests
of the three STATCOMs were finished by May 2016, and the STATCOMs were
formally put into operation in June 2016.
The SLD of the three STATCOMs is shown in Fig. 30.
The main technical parameters of the three STATCOMs are shown in Table 6.
The layout of #3 STATCOM is shown in Fig. 31. The control and protection
system, valve cooling system, and the three-phase power modules are arranged
indoors. Water-cooling radiators, reactors, earthing switches, surge arresters, soft-
start resistors, bypass circuit breakers, and incoming circuit breakers are arranged
outdoors.
Figure 32 shows the outdoor area of #3 STATCOM.
Figure 33 shows the #3 STATCOM valve. Each valve is one phase, and there are a
total of three valves. As can be seen from the picture on the left, the output of the
power modules are cascaded using copper bars, and each power module is
Application Examples of STATCOM 35
48000mm
Reactor B-1
Valve B
15 000 mm
configured with a high-speed bypass switch. The picture on the right shows the
power module dc capacitors and the connection between different layers.
The layout of the outdoor equipment for the #1 STATCOM is shown in Fig. 34.
Figure 35 is the control and protection cubicles for #3 STATCOM. The cubicles
include an ac switchboard (distribution panel), a dc switchboard (distribution panel),
a transient fault recorder cubicle, a monitor cubicle, two control and protection
cubicles, and a power module interface cubicle. Figure 36 shows the valve cooling
system for the #1 STATCOM.
Each STATCOM controller has the above control modes. In order to coordi-
nate the control of the three STATCOMs to achieve the same reactive power
output of each STATCOM and to realize the control interaction with the HVDC
control and protection system, a dedicated coordination controller is also
provided.
The control strategies of the coordination controller implement the above
control modes. The coordination controller communicates both with the HVDC
control and protection system and the three STATCOM control systems. When
the HVDC control and protection system controls the ac bus voltage, the coor-
dinated controller monitors the ac bus voltage. If the bus voltage is within the
preset voltage range, it controls the output of the three STATCOMs to zero
reactive power to achieve reactive power reserve. When the ac bus voltage
exceeds the preset voltage range, the coordinated controller forces the
STATCOM control systems to enter voltage control mode to achieve voltage
stability.
Application Examples of STATCOM 39
RMS
Solid line cursor Dotted cursor
35kV phase A voltage 35kV phase B voltage 35kV phase C voltage
22.6kV 22.6kV
22.6kV 22.6kV
22.6kV 22.6kV
35kV phase A current 35kV phase B current 35kV phase C current
1479A 1477A
1474A 1476A
1480A 1480A
RMS
When the HVDC control and protection system controls the reactive power at the
outgoing ac line, the coordinated controller will always maintain voltage control
mode for the STATCOMs to ensure stable control of the ac outgoing voltage.
The coordinated controller will keep the output of the three STATCOMs equal,
when the STATCOM is in coordination control mode.
The engineering field tests demonstrated that the STATCOM has the ability to output
rated power. The recorded data of the rated 100 Mvar and 100 Mvar output is
shown in Figs. 37 and 38.
In Fig. 37, the current is less than the rated current of 1650 A because the voltage
is greater than the rated voltage of 20.2 kV. In contrast, in Fig. 38, the current is
greater than the rated current of 1650 A because the voltage is less than the rated
voltage of 20.2 kV.
The engineering field test verified that the STATCOM has the specified overload
capability 1.3pu current for 5 s. The recorded data is shown in Fig. 39.
20 Mvar to 40 Mvar step response test was performed by modifying the
reactive power setting, when # 3 STATCOM operates in steady-state constant
reactive power control mode. The test results are shown in Fig. 40. The step response
time satisfies the technical requirements of less than 20 ms.
A test was performed with # 3 STATCOM operating in steady-state constant
voltage control mode, with a disturbance to the power grid voltage by connecting a
40 S. Xu et al.
RMS
Solid line cursor Dotted cursor
Fig. 39 The test record data of overload ability of 1.3p.u current and lasting 5 s
Instantaneous value
Solid line cursor Dotted cursor
-0.2pu -0.4pu
-0.20pu -0.38pu
Solid line cursor :-1.4ms Dotted cursor :2ms Time difference :3.4ms
Instantaneous value
Solid line cursor Dotted cursor
Solid line cursor :-11.4ms Dotted cursor :7.6ms Time difference :19ms
Fig. 41 The recorded data of a step response test when in constant voltage control mode
reactor rated at 60 Mvar. The test results are shown in Fig. 41. The step response time
meets the technical requirements of less than 20 ms. The test was performed on one
STATCOM at a time.
Figure 42 shows the result of a single-phase fault test on the 500 kV ac side of the
receiving terminal of the 500 kV HVDC system with the STATCOMs in operation.
From the top to the bottom, there are the dc voltage, dc current, GAMMA of the
converter, and the dc power of the HVDC, respectively. The traces show that the
HVDC scheme suffered a commutation failure from which it successfully recovered
within about 50 ms, following which pre-fault output was reached about 400 ms after
the ac fault.
Application Examples of STATCOM 41
Fig. 42 The recorded data showing successful recovery of the HVDC converter station supported
by STATCOMs after an ac fault on the inverter side
The STATCOMs at the Funing converter station in China Southern Power Grid
have solved the problem of lack of the dynamic reactive power control in the Funing
converter station. They have achieved stable control of the ac voltage and ensured
the smooth operation of the HVDC transmission system after the N-1 ac fault in the
Funing converter station. This has improved the power grid stability and the
reliability of power supply.
During the recovery of HVDC after an ac system fault, the STATCOM needs to
respond quickly to smooth the voltage fluctuation on the 500 kV busbar. After
clearance of ac faults, a large amount of surplus reactive power stored in the
converter station ac filters may cause high ac overvoltage, and this was considered
in the design of the STATCOM.
400kV BUS
400/38.5
38.5kV BUS
The operation modes are similar to the modes for the Dongguan STATCOM (see
Sect. 6.3) but with different parameters.
44 S. Xu et al.
Theoretical analysis and field tests have shown that the performance of STATCOM
meets the specified requirements. Figure 46 shows the response of the STATCOM
when a fault occurred on the 400 kV line. The fault is a short circuit from phase Y to
phase B. The response of the STATCOM was as expected according to the setting
control logic.
After entering operation, the STATCOM has responded quickly and accurately to
multiple power grid transient disturbances and has provided a powerful dynamic
reactive support for the power network.
The utility Alabama Power Company (APC) has faced challenges with decreased
power quality due to a reduced short-circuit capacity in the regional network (Hasler
et al. 2018). One large power quality polluter in the system was a steel plant
comprising a large Electric Arc Furnace (EAF) generating flicker, unbalance, and
Application Examples of STATCOM 45
38.5kV Bus
Voltages
400kV Bus
Voltages
Line
Currents of
STATCOM 1
Line
Currents of
STATCOM 2
The main parts of the affected utility network are illustrated in Fig. 47. The EAF
Plant within Steel Plant 1 represents an EAF compensated by the STATCOM. Also
relevant for the evaluation of disturbance at the point of evaluation (POE) is the steel
processing plant together with other loads located inside Steel Plant 1 as well as
another steel plant (Steel Plant 2) located only 25 km away. In the nearby area, there
is a power-generating unit that will be partially retired, as well as residential loads
that need to have their power quality kept within standard limits.
Prior to the STATCOM installation, static harmonic filters were used to compen-
sate for the reactive power consumed by Plant 1 EAF as well as to limit
the harmonics created by the same EAF. Static filters are however unable to handle
dynamic load changes, and therefore the disturbance level (mainly flicker) of the
46 S. Xu et al.
230 kV grid was heavily influenced. Flicker short-term perceptibility (Pst) values
(Pst 99%) of 1.7 were recorded at the 230 kV network at a short-circuit level of
8500 MVA.
Due to the future retirement of steam turbines as part of the power-generating
unit, the short-circuit level in the 230 kV network will decrease, certainly leading to
increased disturbance levels. To handle this as well as increased residential and
industrial loads in the area, the utility realized that the power quality on the 230 kV
network needed to be improved.
The large EAF in Plant 1 was considered to be the main contributor to distur-
bances in the network, foremost concerning flicker, but also voltage and current
harmonics as well as low-power factor and voltage unbalance. The most efficient
way to mitigate disturbances is locally at the source of the disturbance. It was thus
decided to install a STATCOM inside Plant 1 to compensate for the EAF. Since the
steel processing plant inside Plant 1 is fed by a separate transformer, it is not
compensated by the STATCOM.
The reason for choosing a STATCOM compensation equipment instead of a
Static Var Compensator (SVC) based on thyristor-controlled reactors (TCR) was
due to the low flicker emission level planned for Plant 1. Typically, a STATCOM can
reduce the flicker by a factor of 3–6, whereas a TCR-based SVC can only reduce by a
factor of 1.5–2. In order not to exceed the recommended planning level at POE,
assuming present and future grid conditions, a STATCOM was deemed necessary.
Additionally, the excellent power quality performance (harmonics, voltage unbal-
ance, step response) of a STATCOM made it a preferred solution over a
TCR-based SVC.
In 2016, ABB commissioned a STATCOM based on the Modular Multilevel
Converter (MMC) topology designed to solve the power quality issues related to the
operation of the arc furnace in Steel Plant 1. The MMC topology allows a low
switching frequency for each H-bridge cell without affecting the overall converter
performance, which reduces the switching losses and offers an excellent output
waveform. In order to obtain high current rating and high performance during
Application Examples of STATCOM 47
The main purpose of the STATCOM is to improve the power quality of the network,
including:
have also the purpose of providing capacitive reactive power needed in order to
compensate for the EAF and a smaller Ladle Furnace used for refining the melted
steel scrap.
The rating and design of the STATCOM (VSC + filters) is mainly determined by
In an EAF application, the control system constantly measures the current drawn
by the furnace, and accuracy is achieved using high resolution electronic current
transducers. The STATCOM provides the current necessary to compensate the
disturbances from the furnace in terms of reactive power, unbalance, and harmonics.
The high power rating of the VSC and fast control enables the STATCOM to
instantaneously generate phase currents that correspond to the full range of
the furnace disturbing currents. The STATCOM control enables compensation of
the complete reactive power absorbed by the furnace loads and also modifies the
individual phase currents in order to minimize the effects of disturbances caused by
load fluctuations. Since the converter responds in less than 100 μs, even the fastest
variations can be counteracted. The high control speed of the converter also allows
compensation of several of the harmonics generated by the furnace.
Application Examples of STATCOM 49
Fig. 50 Pst level records without (left) and with (right) STATCOM in service, measured on 10 min
average using voltage-based method
Fig. 51 Voltage unbalance measured at POE without (left) and with (right) STATCOM in service
(at identical day period) after the connection of the STATCOM, demonstrating the
achieved flicker reduction.
Using the current-based method, which does not consider the background distor-
tion, 1-week measurements showed a reduction on the flicker level Pst99% from 2.1
(STATCOM OFF) to 0.48 (STATCOM ON). Such reduction factor (4.38) can today
only be achieved with STATCOM technology and suitable control algorithms.
150000
125000
100000
kW
75000
50000
25000
TOT P(kW)
Fig. 52 Total EAF power before and after the STATCOM connection at 16:00
STATCOM is in service (right plot). It should be noted that the measurement periods
were the same as those presented in the previous figure, i.e., the flicker reduction
achieved by the STATCOM reduces the voltage unbalance at POE.
Queensland Rail (QR) was expecting a substantial increase in the volume of coal
exported from Central Queensland. To successfully carry more coal from mines
to ports, QR plans to increase the number of trains as well as increasing train
loads.
Today powerful electric locomotives with induction motors (ac motors) will
replace locomotives with dc motors and diesel-electric locomotives. In the future,
most trains in Central Queensland will be electric powered with noticeably larger
electric loads.
The electric trains are a significant single-phase load on Powerlink’s transmission
system in Central Queensland. Additionally new electric locomotives with induction
motors have capability to regenerate up to 65% percent of the active power generated
through electrodynamic braking. In the future all locomotives with this feature will
utilize maximum regeneration, stretching grid capabilities up to limits. The expected
increase in the QR load will affect the quality of the positive-sequence and the
negative-sequence voltage in the region.
New SVCs should ensure load balancing to comply with the grid code require-
ments. Rating of the SVCs have been considered taking into account local QR load
and partial additional loading caused by the adjacent QR. However, SVCs based on
thyristor technology are strong sources of the harmonic currents. At the same time,
the locomotives are also a considerable source of harmonic currents. The connection
points of the QR loads are usually relatively weak. Therefore the decision was made
to install four new STATCOMs based on true multilevel VSC technology to avoid
any kind of negative interaction between the two harmonic sources while still
preserving power quality at the required level.
Four new STATCOMs were installed at the Wycarbah, Duaringa, Bluff, and
Wotonga substations in Queensland, Australia. The STATCOMs are state-of-
the-art voltage-sourced converters (VSC). The VSCs have extremely low har-
monic generation and therefore allow a safe design with respect to possible
harmonic interaction with the ac system also in case of operation during negative
phase sequence control. These advantages will be achieved without filter
components.
The STATCOM solution is owned by Powerlink, and the manufacturer was
Siemens. The STATCOMs were put into operation in 2011.
The SLD of the STATCOM, which uses three-phase transformers and the
connection to the railway catenary using single-phase transformers, is shown in
Fig. 53.
Application Examples of STATCOM 53
132kV
Feeder
100MVA 30/40MVA
132/30.4kV 132/50kV
Filters
40+4
Feeder
Auto
Transformers
Catenary
–100 to + 100MVAr
For safe and reliable operation of the installation to provide maximum support for
the grid, the following additional closed-loop functions were implemented:
Fig. 54 MMC
converter 100 Mvar
Fig. 56 Measurement from site during testing of negative phase sequence control ((a), STATCOM
current; (b), RMS current for each converter phase; (c), negative phase sequence on HV side)
which are mechanically switched. The first installation in Rourkela substation went
into operation in March 2018.
The compensation system was designed to provide a dynamic reactive power output
of 300 Mvar based on using MMC technology. Additionally, an increased induc-
tive power output was required based on mechanically switched branches to achieve
in total 510 Mvar output on the HV side.
Design optimization led to a configuration that employed two STATCOM
branches each with a dynamic range of 150 Mvar. Additionally, two Mechanical
Switched Reactor (MSR) branches each designed to provide 105 Mvar output were
installed in the substation.
The compensation system in this project is owned by Power Grid Corporation of
India, and the manufacturer of the STATCOM is Siemens. The site installation and
tests for the compensation system were completed, and the STATCOM was officially
put into operation in March 2018.
The SLD of the Rourkela hybrid STATCOM is shown in Fig. 57.
The STATCOM uses a Modular Multilevel Converter (MMC). The voltage-
sourced converter consists of three identical phase legs connected in delta. Each
STATCOM phase leg consists of 36 submodules connected in series. The main
components of each submodule are four IGBTs, four diodes, and one dc capacitor.
Fig. 57 SLD of the hybrid 400kV 50Hz Ik=63kA
STATCOM in Rourkela
substation Y Uprim= 400kV
Usec= 35.8kV
Strafo= 511Mvar
STATCOM STATCOM
MSR 105Mvar MSR 105Mvar
150Mvar 150Mvar
58 S. Xu et al.
The main technical parameters of the STATCOM in the Rourkela substation are
shown in Table 10.
A compact arrangement of the compensation system, which occupies less than
81m 88 m, was implemented to fit within the limited available site area. The two
STATCOM branches were placed in a building. Additionally the building contains
the required valve cooling equipment and the control and protection cubicles.
All other equipment, including ac breakers and reactors, were mounted outdoors.
An overview of the installation is shown in Fig. 58. The two breaker switched
reactors can be seen in the foreground; the two sets of STATCOM reactors can be
seen near to the building in the top right-hand corner, and the circuit breakers and
isolators can be seen at the right of the picture.
To ensure safe and reliable operation of the installation and to provide maximum
support for the grid, the following additional closed-loop functions were
implemented:
• Stability controller
• Automatic gain adjustment
• Power oscillation damping
• Sub-synchronous damping function
Application Examples of STATCOM 59
Fig. 59 Recorded data from site during MSR switching on (a) and off (b)
STATCOMs are commonly used to help wind and solar farms meet grid code
requirements around the world. For the Lake Bonney Wind Farm in South
Australia, a centralized FACTS solution was needed to meet the grid code require-
ments of Essential Services Commission of South Australia (ESCOS), National
Electricity Market Management Company of Australia (NEMMCO), and ElectraNet
(Transmission Utility). This section is based on the paper: J. A. Diaz de Leon,
B. Kehrli, and A. Zalay, “How the Lake Bonney wind farm met ESCOSA’s,
Application Examples of STATCOM 61
• Capability to provide +/ 93% power factor (PF) at the high side of the power
transformer at full generation.
• Half of the reactive power capability needs to be dynamic (i.e., WTGs, FACTS
devices), and other half can be static (i.e., static shunt devices).
• The reactive output capability should scale proportional to the generation level.
• Capability to regulate the transmission system voltage.
• Capability to ride through nearby transmission grid faults causing high and low
voltages (low voltage ride through (LVRT) and high voltage ride through (HVRT))
• Capability to restore the transmission system’s post fault voltage to a minimum of
90%.
In order to meet all of these requirements for the Phase 2 installation, a 24 Mvar
STATCOM and a total of 54 Mvar capacitor banks were installed at the Lake Bonney
Wind Farm.
Fig. 60 One-line diagram of the Lake Bonney Wind Farm, first and second phase installations
of WTGs
62 S. Xu et al.
Based on the load flow analysis, the total reactive power losses at the point of
common coupling (PCC) were determined to be 47 Mvar as shown in Fig. 61.
The first requirement from the ESCOSA grid code for the 159 MW wind farm
(Phase 2 portion only) was to have the capability of achieving a +/ 93% PF at the
high side of the power transformers. This equates to +/ 63 Mvar at the 132 kV PCC
bus. Adding the 47 Mvar of reactive power absorption to the 63 Mvar needed for the
0.93 PF requirement, the total capacitive compensation needed came out to
110 Mvar. Similarly, for the inductive compensation, an additional 16 Mvar was
needed to increase the 47 Mvar inductive to a total of 63 Mvar.
The second ESCOSA requirement was that a minimum of 50% of the reactive
power compensation needed to be dynamically variable. Thus, at least 55 Mvar of
the capacitive compensation and 8 Mvar of inductive compensation needed to be
dynamic.
Identifying the breakdown of the dynamic and static reactive power requirements
allowed the selection of the type of resources that can be used in meeting
the grid code. The turbines had +0.98/ 0.96 power factor (PF) capability translating
to +32 and 46 Mvar, respectively. For the remainder of the dynamic
requirement, a pure dynamic capability device such as a synchronous condenser,
STATCOM, or SVC was needed. The requirement was met by using two sets of
3 4 Mvar STATCOM units. The total rating of the STATCOM units came out to be
+/ 24 Mvar on a continuous basis with a short-term overload capability of
+/ 64 Mvar (24 Mvar 2.67 overload). Since the WTGs and STATCOM units
provided only 56 Mvar of continuous capacitive reactive power, an additional
54 Mvar was provided by four 13.5 Mvar switched capacitor banks to meet the
total 110 Mvar requirement. A one-line diagram of the wind farm’s generation and
reactive resources is shown in Fig. 62. A summary of the STATCOM parameters is
provided in (Table 11).
Fig. 62 One-line diagram of the Lake Bonney Wind Farm with the reactive compensation solution
The main controller of the STATCOM system manages the reactive power output of
not only the STATCOM units but also all other reactive power resources at the wind
farm, which are the WTGs and the four capacitor banks. By requesting the appro-
priate amount of vars from each resource according to a voltage droop profile, the
control system is able to regulate the transmission system voltage or the wind farm’s
overall power factor. The integration of the shunt devices and WTGs’ reactive
capability in the overall reactive power control strategy allows the extension of
the STATCOM’s continuous rating. For short duration large voltage excursions, the
STATCOM utilizes its 2.67-times overload for up to 2 s. Capacitor switching is
seamless, i.e., does not cause any significant voltage step changes, due to a soft-
switching algorithm.
For voltage-control mode, independent droop and dead-band characteristics
are selectable for regulation and transient control. In order to provide maximum
reactive power support, the regulation mode is temporarily overridden by transient
voltage control during major disturbances.
The grid code requires the wind farm to stay online for High Voltage Ride Through
(HVRT) and Low Voltage Ride Through (LVRT) events. The STATCOM’s overload
capability is critical in keeping the terminal voltages of WTGs within their rated
operational ranges. The inherent LVRT capability of the WTGs was sufficient to ride
through the low voltage events. However, meeting the ESCOSA HVRT require-
ments was not possible without the STATCOM’s support. Figure 63 shows the Lake
Bonney 132-kV PCC pu voltage requirement (red line) and the 1 kV bus pu voltage
of the Vestas WTGs (orange line). Exceeding the WTG rated voltages causes the
turbines to trip. The region of concern for HVRT compliance is between 0.08 and
0.90 s, during which the WTGs might trip offline on high voltage.
To keep the WTGs online for these high voltage conditions, the simulations were
first run utilizing only the continuous rating of the STATCOM. As shown by the
green line in Fig. 64, the WTG terminal voltages were still too high to prevent
the WTGs from tripping off-line. Next, using the STATCOM’s overload capability,
the WTG terminal voltages (purple line) were brought down to acceptable values
for the WTGs to stay online.
Other contingencies provided by ElectraNet were also tested to ensure compli-
ance with the voltage recovery criteria, which requires the Lake Bonney 132-kV
transmission bus to reach 90% of nominal voltage quickly after the fault clearing.
A hybrid approach utilizing STATCOMs, WTGs, and shunt devices not only
allowed the Lake Bonney Wind Farm to meet the reactive power requirements of
the South Australia grid code but also minimized the overall cost of the project. With
the proper deployment of FACTS devices, the renewable energy resources can have
Application Examples of STATCOM 65
Fig. 64 The impact of STATCOM’s continuous and overload capability on WTG terminal voltages
66 S. Xu et al.
Dominion Energy needed a solution for voltage support in the part of transmission
grid affected by an unplanned event. Such condition could occur due to the unex-
pected outages from natural disasters or closing a power plant with a short notice.
Reliability and power quality have to be guaranteed, while the long-term solution is
under construction. Therefore, a solution that is temporary, but available on short
notice, has been developed.
A short notice modification of the transmission grid can be due to different
reasons such as the switching off of traditional power plants or the integration of
renewable energy sites that are constructed in the span of 18 months or less. The new
generation location creates problems since it is not replacing traditional generation in
the same location or size. To maintain the voltage stability, regulation and tolerance
are difficult since generation is now typically in remote locations compared to the
load centers. Installation and upgrading of new infrastructure are necessary to
make the generation meet the load.
New transmission lines, reconductoring of transmission lines, and installation of
shunt capacitors or reactors are some of the projects that may be required to make the
grid function properly. The challenge is how to carry out the transmission transfor-
mation and still provide reliability and quality of service. Also in this case, the
connection point of reactive power support in the grid is not foreseeable.
The required solution has to be easy to relocate in a very short time. In addition,
the solution should have the capability to be connected anywhere in the entire
network without any negative impacts to the system.
STATCOM
grid code requirements. This makes the design compact and provides the flexibility
to connect at any point in the network. The voltage-sourced converter consists of
three identical phase legs connected in delta. Each phase leg consists of 22 sub-
modules connected in series. The main components of each submodule are four
IGBTs, four diodes, and one dc capacitor.
The main technical parameters of the mobile STATCOM are shown in Table 12.
The design of a mobile STATCOM including step-down transformer requires
separating component equipment into logical practical blocks that can be connected
with temporary power and control cables (see Fig. 66). The mobile STATCOM
system was designed to be fully relocatable in a comparably short duration. The
main trailer contains the STATCOM valves or submodules, protection with control,
and the cooling system. The second trailer contains arm reactors as well as the
necessary instrument transformers. The third trailer contains all required auxiliary
equipment such as auxiliary transformer, batteries, AC and DC distribution panels,
and storage. The heat exchanger is connected using stainless steel hose allowing for
flexible location and orientation. An additional trailer contains the mobile trans-
former inclusive of HV breaker and arrester. All other equipment is designed to be
temporary and relocatable for rapid deployment inclusive the necessary oil
containment.
68 S. Xu et al.
Cables connect the components in each container; therefore no open live parts or
busbars are exposed. This significantly reduces the risk of internal faults at the
substation and improves personnel safety. In general, the fully containerized solution
is beneficial at remote locations. The reduced installation work on-site together with
a compact STATCOM area results in less work and less overall risk for personnel
(Fig. 67).
Application Examples of STATCOM 69
For safe and reliable operation of the installation to provide maximum support for
the grid, additional closed-loop functions were implemented like:
• Stability controller
• Automatic gain adjustment
1.2
With STATCOM
1.1
1
Voltage (pu 115 kV Base)
0.9
0.8
0.7
Without
0.6 STATCOM
0.5
0.4
0.3
0.2
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 6.5 7 7.5 8 8.5 9 9.5 10
Time (seconds)
The mobile STATCOM is a solution that can be connected at any point on the
electrical network that requires voltage support. It has the flexibility to be relocated
within a short period of time and provides grid support until a long-term solution can
be completed.
The STATCOM operates correctly and satisfies Dominion Energy’s specified
requirements. It provides a rapid and stable response throughout its operating range.
15 Cross-References
References
Anderson, P.M., Farmer, R.G.: Subsynchronous resonance; Chapter 6, pages 229 to 286, In: Series
capacitor studies, testing and maintenance, Chapter 8. In: Series Compensation of Power
Systems. PBLSH! Inc., Encinitas (1996)
Cao, Z., Shi, Y., et al.: Simulation analysis on sub synchronous oscillation at sending end of
500 kV power transmission project from Hulun Buir to Liaoning. Power Syst. Technol.
35(6), 107–112 (2011)
Diaz de Leon, J.A., Kehrli, B., Zalay, A.: How the Lake Bonney wind farm met ESCOSA’s,
NEMMCO’s, and ElectraNet’s rigorous interconnecting requirements. In: IEEE/PES
Transmission and Distribution Conference and Exposition (2008)
Farmer, R.G., Schwalb, A.L., Katz, E.: Navajo project report on subsynchronous resonance analysis
and solutions. IEEE Trans. Power Syst. PAS-96(4), 1226–1232 (1977)
Hanson, D.J., Horwill, C., Loughran, J., Monkhouse D.R.: The application of a relocatable
STATCOM on the UK National Grid system. In: CIGRÉ Regional Conference, New Delhi (2001)
Hasler, J-P, Sneed, T., Holmberg, M., Lund, J., Näslund, M.: Power Quality Analysis and IEC
Standard Evaluation Using Measurements and Simulations in a STATCOM Application.
Paper C4-114. CIGRÉ, Paris (2018)
Horwill, C., Totterdell, A.J., Hanson, D.J., et al.: Commission of a 225 MVAr SVC incorporating a
75MVAr STATCOM AT NGC’s 400kV east claydon substation. In: Seventh International
Conference on AC-DC Power Transmission, pp. 232–237. Institution of Electrical Engineers,
London (2001)
IEC/TR 61000-3-7: Electromagnetic Compatibility (EMC) – Part 3–7: Limits – Assessment of
Emission Limits for the Connection of Fluctuating Installations to MV, HV and EHV Power
Systems, Ed.2.0. BSI, London (2008)
Li Chunhua, Zhang Yongkang, et al.: Artificial short circuit test and analysis of 200MVAr static
synchronous compensator artificial short-circuit test and analysing in Southern power grid.
Autom. Elect. Power Syst. 37(4), 125–129 (2013)
Liu Wen-hua, Song Qiang, Teng Le-tian, et al.: 50MVAr STATCOM based on chain circuit
converter employing IGCT’s. Proc. CSEE. 28(15), 55–60 (2008)
Rao, H., Xu, S., Zhao, Y., et al.: Research and application of multiple STATCOMs to improve the
stability of ACDC power systems in China Southern Grid. IET J. 10(13), 3111–3118 (2016)
72 S. Xu et al.
Woodhouse, M.L., Donoghue, M.W., Osborne, M.M.: Type testing of the GTO valves for a novel
STATCOM converter. In: Seventh International Conference on AC-DC Power Transmission.
Institution of Electrical Engineers, London (2001)
Xiao Leisi, Li Ming, et al.: Manual instantaneous earthing test of CSG transmission lines. South.
Power Syst. Technol. 9(3), 63–66 (2015)
Yao Weizheng, Liu Gang, Hu Siquan, et al.: Research on improved control strategies of STATCOM
for LCC-HVDC weak receiving station. Proc. CSEE. 38(12), 3362–3670 (2018)